COMcheck 101 Training: Lighting Requirements
Page 4 of 7
Guestrooms
- A master switch is required at the entry to control all permanently wired lighting fixtures and switched receptacles
Exception: bathroom
- Suites are required to have a master switch at the entry to each room or at the primary entry to the suite
Exterior Lighting Controls
All exterior lighting not intended for 24-hour operation must have automatic switching or photocell controls. Automatic time switches require a combination 7-day and seasonal daylight program schedule adjustment and a minimum 4-hour power backup.
Timeclock used to control the exterior lighting system for the building.