Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 11:18

Tabular Output Report in Format: HTML

Building: SchoolPrimary

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 11:18:23


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3129.51 455.47 455.47
Net Site Energy 3129.51 455.47 455.47
Total Source Energy 8763.39 1275.42 1275.42
Net Source Energy 8763.39 1275.42 1275.42


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 6871.00
Net Conditioned Building Area 6871.00
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 52.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 371.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 627.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 52.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1144.07 361.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 24.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 268.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.84 137.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 718.47
Refrigeration 63.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2578.49 551.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 718.47
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 9.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 42.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 371.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 627.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 52.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 947.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 149.71 361.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 28.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 17.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 24.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 268.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 25.84 137.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 268.99
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 449.48
Refrigeration General 7.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 19.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 36.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 52.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 371.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 627.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 52.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1144.07 361.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 24.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 268.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 25.84 137.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 718.47
Refrigeration Unassigned 63.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 98.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 97.02 27.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
Other 179.27 52.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 375.27 80.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 98.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 97.02 27.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
Other 179.27 52.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 375.27 80.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 2578.493 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 2578.493 100.00
     
Total On-Site and Utility Electric Sources 2578.493 100.00
Total Electricity End Uses 2578.493 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 718.47 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 718.47 100.00
Total Water End Uses 718.47 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 115.83
Time Setpoint Not Met During Occupied Cooling 37.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 538.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

ZoneHeatingSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

ZoneElectricSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

SpaceGainsMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

PeakSpaceGainsMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

SpaceGainComponentsAtCoolingPeakMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

ComfortReportSimple55Monthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

OccupantComfortDataSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV_POD_1 COOLING COIL | VAV_POD_2 COOLING COIL | VAV_POD_3 COOLING COIL | VAV_OTHER COOLING COIL | PSZ-AC_2:5 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |

WindowReportMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |

WindowEnergyReportMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |

WindowZoneSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

WindowEnergyZoneSummaryMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| GYM_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL | MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL | COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL | LOBBY_ZN_1_FLR_1_DAYLCTRL | OFFICES_ZN_1_FLR_1_DAYLCTRL | CAFETERIA_ZN_1_FLR_1_DAYLCTRL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL |

CoilReportMonthly

| VAV_POD_1 HEATING COIL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_2 HEATING COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_3 HEATING COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_OTHER HEATING COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | PSZ-AC_2:5 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | VAV_POD_2 COOLING COIL | VAV_POD_3 COOLING COIL | VAV_OTHER COOLING COIL | PSZ-AC_2:5 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| VAV_POD_1 FAN | VAV_POD_2 FAN | VAV_POD_3 FAN | VAV_OTHER FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_POD_1 | VAV_POD_2 | VAV_POD_3 | VAV_OTHER | PSZ-AC_2:5 | PSZ-AC_1:6 | PSZ-AC_2:7 |

AirLoopSystemComponentLoadsMonthly

| VAV_POD_1 | VAV_POD_2 | VAV_POD_3 | VAV_OTHER | PSZ-AC_2:5 | PSZ-AC_1:6 | PSZ-AC_2:7 |

AirLoopSystemComponentEnergyUseMonthly

| VAV_POD_1 | VAV_POD_2 | VAV_POD_3 | VAV_OTHER | PSZ-AC_2:5 | PSZ-AC_1:6 | PSZ-AC_2:7 |

MechanicalVentilationLoadsMonthly

| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 11:18
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2512.00 928.00 328.00 928.00 328.00
Above Ground Wall Area [m2] 2512.00 928.00 328.00 928.00 328.00
Window Opening Area [m2] 879.14 324.75 114.79 324.80 114.80
Gross Window-Wall Ratio [%] 35.00 34.99 35.00 35.00 35.00
Above Ground Window-Wall Ratio [%] 35.00 34.99 35.00 35.00 35.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2512.00 928.00 328.00 928.00 328.00
Above Ground Wall Area [m2] 2512.00 928.00 328.00 928.00 328.00
Window Opening Area [m2] 879.14 324.75 114.79 324.80 114.80
Gross Window-Wall Ratio [%] 35.00 34.99 35.00 35.00 35.00
Above Ground Window-Wall Ratio [%] 35.00 34.99 35.00 35.00 35.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 6871.00
Skylight Area [m2] 13.38
Skylight-Roof Ratio [%] 0.19


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 28.00 28.00 13.6336 3.72 15.0000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 Yes Yes 1908.00 1.00 212.00 0.00 74.20 74.20 13.6336 3.72 15.0000
CORRIDOR_POD_1_ZN_1_FLR_1 192.00 Yes Yes 768.00 1.00 12.00 0.00 4.20 4.20 7.1339 18.58 4.0000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 28.00 28.00 13.6336 3.72 15.0000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 Yes Yes 1908.00 1.00 212.00 0.00 74.20 74.20 13.6336 3.72 15.0000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 28.00 28.00 13.6336 3.72 15.0000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 Yes Yes 1908.00 1.00 212.00 0.00 74.20 74.20 13.6336 3.72 15.0000
CORRIDOR_POD_2_ZN_1_FLR_1 192.00 Yes Yes 768.00 1.00 12.00 0.00 4.20 4.20 7.1339 18.58 4.0000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 28.00 28.00 13.6336 3.72 15.0000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 Yes Yes 1908.00 1.00 212.00 0.00 74.20 74.20 13.6336 3.72 15.0000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 28.00 28.00 13.6336 3.72 15.0000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 Yes Yes 1908.00 1.00 212.00 0.00 74.20 74.20 13.6336 3.72 15.0000
CORRIDOR_POD_3_ZN_1_FLR_1 192.00 Yes Yes 768.00 1.00 12.00 0.00 4.20 4.20 7.1339 18.58 4.0000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 Yes Yes 396.00 1.00 80.00 0.00 27.95 27.95 13.6336 3.72 15.0000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 Yes Yes 1260.00 1.00 140.00 0.00 49.00 49.00 13.6336 3.72 15.0000
COMPUTER_CLASS_ZN_1_FLR_1 162.00 Yes Yes 648.00 1.00 72.00 0.00 25.20 25.20 13.6336 3.72 20.0000
MAIN_CORRIDOR_ZN_1_FLR_1 546.00 Yes Yes 2184.00 1.00 36.00 0.00 12.60 12.60 7.1339 18.58 4.0000
LOBBY_ZN_1_FLR_1 171.00 Yes Yes 684.00 1.00 76.00 0.00 26.60 26.60 9.6875 9.29 4.0000
MECH_ZN_1_FLR_1 252.00 Yes Yes 1008.00 1.00 0.00 0.00 0.00 0.00 4.5208 61.93 10.0000
BATH_ZN_1_FLR_1 190.00 Yes Yes 760.00 1.00 40.00 0.00 14.00 14.00 10.5486 18.58 4.0000
OFFICES_ZN_1_FLR_1 441.00 Yes Yes 1764.00 1.00 168.00 0.00 58.80 58.80 11.3407 18.58 10.8000
GYM_ZN_1_FLR_1 357.00 Yes Yes 1428.00 1.00 68.00 0.00 23.80 23.80 11.9479 3.10 5.0000
KITCHEN_ZN_1_FLR_1 168.00 Yes Yes 672.00 1.00 32.00 0.00 11.20 11.20 13.0243 6.22 1630.3893
CAFETERIA_ZN_1_FLR_1 315.00 Yes Yes 1260.00 1.00 144.00 0.00 50.40 50.40 6.9965 0.93 25.3900
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 Yes Yes 1596.00 1.00 160.00 0.00 56.00 56.00 16.3073 9.29 15.0000
Total 6871.00     27484.00   2512.00 0.00 879.14 879.14 11.6558 4.37 51.7447
Conditioned Total 6871.00     27484.00   2512.00 0.00 879.14 879.14 11.6558 4.37 51.7447
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 GENERAL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 Yes Yes 1.00 MULT_CLASS_1_POD_1_ZN_1_FLR_1 GENERAL MULT_CLASS_1_POD_1_ZN_1_FLR_1 13.6336 3.72 15.0000  
CORRIDOR_POD_1_ZN_1_FLR_1 192.00 Yes Yes 1.00 CORRIDOR_POD_1_ZN_1_FLR_1 GENERAL CORRIDOR_POD_1_ZN_1_FLR_1 7.1339 18.58 4.0000  
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 GENERAL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 Yes Yes 1.00 MULT_CLASS_2_POD_1_ZN_1_FLR_1 GENERAL MULT_CLASS_2_POD_1_ZN_1_FLR_1 13.6336 3.72 15.0000  
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 GENERAL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 Yes Yes 1.00 MULT_CLASS_1_POD_2_ZN_1_FLR_1 GENERAL MULT_CLASS_1_POD_2_ZN_1_FLR_1 13.6336 3.72 15.0000  
CORRIDOR_POD_2_ZN_1_FLR_1 192.00 Yes Yes 1.00 CORRIDOR_POD_2_ZN_1_FLR_1 GENERAL CORRIDOR_POD_2_ZN_1_FLR_1 7.1339 18.58 4.0000  
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 GENERAL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 Yes Yes 1.00 MULT_CLASS_2_POD_2_ZN_1_FLR_1 GENERAL MULT_CLASS_2_POD_2_ZN_1_FLR_1 13.6336 3.72 15.0000  
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 GENERAL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 Yes Yes 1.00 MULT_CLASS_1_POD_3_ZN_1_FLR_1 GENERAL MULT_CLASS_1_POD_3_ZN_1_FLR_1 13.6336 3.72 15.0000  
CORRIDOR_POD_3_ZN_1_FLR_1 192.00 Yes Yes 1.00 CORRIDOR_POD_3_ZN_1_FLR_1 GENERAL CORRIDOR_POD_3_ZN_1_FLR_1 7.1339 18.58 4.0000  
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 Yes Yes 1.00 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 GENERAL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 13.6336 3.72 15.0000  
MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 Yes Yes 1.00 MULT_CLASS_2_POD_3_ZN_1_FLR_1 GENERAL MULT_CLASS_2_POD_3_ZN_1_FLR_1 13.6336 3.72 15.0000  
COMPUTER_CLASS_ZN_1_FLR_1 162.00 Yes Yes 1.00 COMPUTER_CLASS_ZN_1_FLR_1 GENERAL COMPUTER_CLASS_ZN_1_FLR_1 13.6336 3.72 20.0000  
MAIN_CORRIDOR_ZN_1_FLR_1 546.00 Yes Yes 1.00 MAIN_CORRIDOR_ZN_1_FLR_1 GENERAL MAIN_CORRIDOR_ZN_1_FLR_1 7.1339 18.58 4.0000  
LOBBY_ZN_1_FLR_1 171.00 Yes Yes 1.00 LOBBY_ZN_1_FLR_1 GENERAL LOBBY_ZN_1_FLR_1 9.6875 9.29 4.0000  
MECH_ZN_1_FLR_1 252.00 Yes Yes 1.00 MECH_ZN_1_FLR_1 GENERAL MECH_ZN_1_FLR_1 4.5208 61.93 10.0000  
BATH_ZN_1_FLR_1 190.00 Yes Yes 1.00 BATH_ZN_1_FLR_1 GENERAL BATH_ZN_1_FLR_1 10.5486 18.58 4.0000  
OFFICES_ZN_1_FLR_1 441.00 Yes Yes 1.00 OFFICES_ZN_1_FLR_1 GENERAL OFFICES_ZN_1_FLR_1 11.3407 18.58 10.8000  
GYM_ZN_1_FLR_1 357.00 Yes Yes 1.00 GYM_ZN_1_FLR_1 GENERAL GYM_ZN_1_FLR_1 11.9479 3.10 5.0000  
KITCHEN_ZN_1_FLR_1 168.00 Yes Yes 1.00 KITCHEN_ZN_1_FLR_1 GENERAL KITCHEN_ZN_1_FLR_1 13.0243 6.22 1630.3893  
CAFETERIA_ZN_1_FLR_1 315.00 Yes Yes 1.00 CAFETERIA_ZN_1_FLR_1 GENERAL CAFETERIA_ZN_1_FLR_1 6.9965 0.93 25.3900  
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 Yes Yes 1.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 GENERAL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 16.3073 9.29 15.0000  
Total 6871.00             11.6558 2.19 51.7447  
Conditioned Total 6871.00             11.6558 2.19 51.7447  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 6871.00 6871.00 0.00 0.00 11.6558 4.37 51.7447
Total 6871.00 6871.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-OCT-10:00 30-MAR-07:10 - - - - - - - - - - 02-JAN-13:09
Heating 0.00 140552.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 159362.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 33662.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 76582.98 36063.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1825.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 36086.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 13.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3951.27 15557.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2339.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 313823.37 192173.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 22888.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 117663.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 159362.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 33662.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 65099.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 9998.36 36063.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 915.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 570.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1825.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 36086.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 13.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3951.27 15557.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 893.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1203.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 56.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1177.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1988.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 165.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3623.28 391.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 76.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 851.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 81.83 149.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 201.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 8166.09 597.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 8.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 171.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 289.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 527.33 56.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 11.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 123.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 11.91 21.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 29.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1188.49 86.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 8.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 171.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 289.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 527.33 56.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 11.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 123.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 11.91 21.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 29.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1188.49 86.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT 0.547872 0.137693 0.677000 0.370909 0.677000 0.500000 0.002767 0.000054 0.370909 12.80 0.008000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT 2.16 0.168541 0.677000 1.46 0.677000 0.500000 0.002261 0.000187 1.46 12.80 0.008000
CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT 0.426118 0.343342 0.677000 0.288482 0.915578 0.500000 0.001110 0.000042 0.288482 12.80 0.008000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT 0.503005 0.149975 0.677000 0.340534 0.677000 0.500000 0.002540 0.000051 0.340534 12.80 0.008000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT 1.84 0.197685 0.677000 1.24 0.677000 0.500000 0.001927 0.000166 1.24 12.80 0.008000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT 0.544439 0.138561 0.680000 0.370219 0.680000 0.500000 0.002750 0.000053 0.370219 12.80 0.008000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT 2.14 0.170096 0.680000 1.45 0.680000 0.500000 0.002240 0.000184 1.45 12.80 0.008000
CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT 0.425728 0.343656 0.680000 0.289495 0.916416 0.500000 0.001109 0.000042 0.289495 12.80 0.008000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT 0.503187 0.149920 0.680000 0.342167 0.680000 0.500000 0.002541 0.000051 0.342167 12.80 0.008000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT 1.84 0.197605 0.680000 1.25 0.680000 0.500000 0.001928 0.000167 1.25 12.80 0.008000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT 0.544827 0.138462 0.658000 0.358496 0.658000 0.500000 0.002752 0.000052 0.358496 12.80 0.008000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT 2.15 0.169354 0.658000 1.41 0.658000 0.500000 0.002250 0.000181 1.41 12.80 0.008000
CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT 0.429655 0.340515 0.658000 0.282713 0.908040 0.500000 0.001119 0.000041 0.282713 12.80 0.008000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT 0.506247 0.149014 0.658000 0.333111 0.658000 0.500000 0.002557 0.000050 0.333111 12.80 0.008000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT 1.23 0.194509 0.658000 0.811993 0.658000 0.500000 0.001959 0.000110 0.811993 12.80 0.008000
COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT 0.685988 0.179951 0.744000 0.510375 0.744000 0.500000 0.002117 0.000062 0.510375 12.80 0.008000
MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT 0.894187 0.465285 0.312000 0.278986 1.00 0.500000 0.000819 0.000057 0.278986 12.80 0.008000
LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT 0.489875 0.265990 0.327000 0.160189 0.709307 0.500000 0.001432 0.000042 0.160189 12.80 0.008000
MECH_ZN_1_FLR_1 VAV BOX COMPONENT 0.433328 0.443138 0.200000 0.086666 1.00 0.500000 0.000860 0.000008 0.086666 12.80 0.008000
BATH_ZN_1_FLR_1 VAV BOX COMPONENT 0.455406 0.621794 0.200000 0.091081 0.847771 0.500000 0.001198 0.000024 0.091081 12.80 0.008000
OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT 1.30 0.258625 0.246000 0.319637 0.689668 0.500000 0.001473 0.000083 0.319637 12.80 0.008000
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT 1.44 0.211142 0.401000 0.577429 0.563044 0.500000 0.001804 0.000096 0.577429 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 6143.50 0.000054 132.71
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 21406.96 0.000187 453.14
CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 4806.02 0.000042 103.93
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 5799.88 0.000051 125.93
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 18960.18 0.000166 403.78
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 6104.86 0.000053 131.77
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 21079.22 0.000184 445.52
CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 4799.91 0.000042 103.71
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 5818.67 0.000051 126.30
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 19033.61 0.000167 405.28
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 5992.72 0.000052 129.67
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 20731.53 0.000181 438.93
CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 4738.62 0.000041 102.58
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 5759.16 0.000050 125.40
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 12626.07 0.000110 269.80
COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL 7045.91 0.000062 147.83
MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL 6570.02 0.000057 153.64
LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL 4780.93 0.000042 120.98
MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL 923.37 0.000008 18.76
BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL 2700.30 0.000024 68.15
OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL 9464.08 0.000083 238.75
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL 10949.72 0.000096 242.86
VAV_POD_1 HEATING COIL 17345.57 0.000152 298.18
VAV_POD_2 HEATING COIL 17262.19 0.000151 296.75
VAV_POD_3 HEATING COIL 15379.05 0.000135 264.38
VAV_OTHER HEATING COIL 17949.62 0.000157 308.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
GYM_ZN_1_FLR_1 DIRECT AIR 1.41
KITCHEN_ZN_1_FLR_1 DIRECT AIR 1.36
CAFETERIA_ZN_1_FLR_1 DIRECT AIR 2.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_POD_1 3.70 3.70 5.47 3.70 5.41 5.41 0.300000 0.684809 5.41
VAV_POD_2 3.71 3.71 5.45 3.71 5.38 5.38 0.300000 0.688311 5.38
VAV_POD_3 3.20 3.20 4.86 3.20 4.80 4.80 0.300000 0.666847 4.80
VAV_OTHER 3.02 2.02 5.70 2.02 5.60 5.60 0.300000 0.361608 5.60
PSZ-AC_2:5 1.41 1.41 1.41 1.41 1.41 1.41 1.00 1.00 1.41
PSZ-AC_1:6 1.36 1.36 1.36 1.36 1.36 1.36 1.00 1.00 1.36
PSZ-AC_2:7 2.20 2.20 2.20 2.20 2.20 2.20 1.00 1.00 2.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_POD_1_OA_CONTROLLER 5.41  
VAV_POD_2_OA_CONTROLLER 5.38  
VAV_POD_3_OA_CONTROLLER 4.80  
VAV_OTHER_OA_CONTROLLER 5.60  
PSZ-AC_2:5_OA_CONTROLLER 1.41 0.544068
PSZ-AC_1:6_OA_CONTROLLER 1.36 0.254814
PSZ-AC_2:7_OA_CONTROLLER 2.20 1.49
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
VAV_POD_1 COOLING COIL 5.41 116206.71 0.749325 1.80 38731.70 0.749325
VAV_POD_2 COOLING COIL 5.38 115735.82 0.749110 1.79 38574.75 0.749110
VAV_POD_3 COOLING COIL 4.80 102597.88 0.750524 1.60 34195.87 0.750524
VAV_OTHER COOLING COIL 5.60 107343.16 0.793401 1.87 35777.47 0.793401
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_POD_1 FAN 5.41
VAV_POD_2 FAN 5.38
VAV_POD_3 FAN 4.80
VAV_OTHER FAN 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
VAV_POD_1_HEATC_CONTROLLER 0.000152
VAV_POD_2_HEATC_CONTROLLER 0.000151
VAV_POD_3_HEATC_CONTROLLER 0.000135
VAV_OTHER_HEATC_CONTROLLER 0.000157
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN 1.41 1557.76
PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN 1.36 1505.58
PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN 2.20 2352.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC_2:5_UNITARY_PACKAGE_DX 1.41 1.41 1.41 0.928612 27920.64 42858.59 40.00 1.00
PSZ-AC_1:6_UNITARY_PACKAGE_DX 1.36 1.36 1.36 0.897510 27792.32 63444.76 40.00 1.00
PSZ-AC_2:7_UNITARY_PACKAGE_DX 2.20 2.20 2.20 1.45 47552.11 80011.94 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC_2:5 COOLING COIL 1.41 0.703494 0.937993 27920.64 13960.32 0.779690 0.779690
PSZ-AC_1:6 COOLING COIL 1.36 0.679932 0.906573 27792.32 13896.16 0.767780 0.767780
PSZ-AC_2:7 COOLING COIL 2.20 1.10 1.47 47552.11 23776.06 0.746430 0.746430
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC_2:5 HEATING COIL 42858.59
PSZ-AC_1:6 HEATING COIL 63444.76
PSZ-AC_2:7 HEATING COIL 80011.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002399 0.287829
SWHSYS1 0.000105 0.012650
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.002399 722.34 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 274171.66 274171.66 0.002399
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000105 13.47
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000105
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 |
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 |
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 |
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 |
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 |
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 |
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
BATH_ZN_1_FLR_1_WALL_5 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
CAFETERIA_ZN_1_FLR_1_WALL_3 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 CAFETERIA_ZN_1_FLR_1_WALL_3 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 |
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 |
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 |
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 |
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 |
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 |
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 |
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 |
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 |
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 |
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 |
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 |
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 |
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 |
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 |
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 |
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 |
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 |
LOBBY_ZN_1_FLR_1_WALL_1 LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 |
BATH_ZN_1_FLR_1_WALL_5 BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 |
OFFICES_ZN_1_FLR_1_WALL_1 OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 |
OFFICES_ZN_1_FLR_1_WALL_2 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 |
GYM_ZN_1_FLR_1_WALL_2 GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 |
GYM_ZN_1_FLR_1_CEILING GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 |
KITCHEN_ZN_1_FLR_1_WALL_2 KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 |
CAFETERIA_ZN_1_FLR_1_WALL_2 CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 |
CAFETERIA_ZN_1_FLR_1_WALL_3 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 |
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 SchoolPrimary 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 25 288 92


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.0 -64.00 0.00 0.00 -58.50 4.50 2.00 1 1 1 -64.00 -53.00 0.00 9.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.05 28.00 6 4 0 Yes
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.0 -53.00 0.00 0.00 -26.50 4.50 2.00 1 1 1 -53.00 0.00 0.00 9.00 0.00 4.00 4.00 1908.00 TARP TARP 477.00 212.00 133.90 74.20 6 5 0 Yes
3 CORRIDOR_POD_1_ZN_1_FLR_1 0.0 -64.00 9.00 0.00 -32.00 10.50 2.00 1 1 1 -64.00 0.00 9.00 12.00 0.00 4.00 4.00 768.00 TARP TARP 192.00 12.00 7.80 4.20 8 1 0 Yes
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.0 -64.00 12.00 0.00 -58.50 16.50 2.00 1 1 1 -64.00 -53.00 12.00 21.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.05 28.00 6 4 0 Yes
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.0 -53.00 12.00 0.00 -26.50 16.50 2.00 1 1 1 -53.00 0.00 12.00 21.00 0.00 4.00 4.00 1908.00 TARP TARP 477.00 212.00 133.90 74.20 6 5 0 Yes
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.0 -64.00 30.00 0.00 -58.50 34.50 2.00 1 1 1 -64.00 -53.00 30.00 39.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.05 28.00 6 4 0 Yes
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.0 -53.00 30.00 0.00 -26.50 34.50 2.00 1 1 1 -53.00 0.00 30.00 39.00 0.00 4.00 4.00 1908.00 TARP TARP 477.00 212.00 133.90 74.20 6 5 0 Yes
8 CORRIDOR_POD_2_ZN_1_FLR_1 0.0 -64.00 39.00 0.00 -32.00 40.50 2.00 1 1 1 -64.00 0.00 39.00 42.00 0.00 4.00 4.00 768.00 TARP TARP 192.00 12.00 7.80 4.20 8 1 0 Yes
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.0 -64.00 42.00 0.00 -58.50 46.50 2.00 1 1 1 -64.00 -53.00 42.00 51.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.05 28.00 6 4 0 Yes
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.0 -53.00 42.00 0.00 -26.50 46.50 2.00 1 1 1 -53.00 0.00 42.00 51.00 0.00 4.00 4.00 1908.00 TARP TARP 477.00 212.00 133.90 74.20 6 5 0 Yes
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.0 -64.00 61.00 0.00 -58.50 65.50 2.00 1 1 1 -64.00 -53.00 61.00 70.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.05 28.00 6 4 0 Yes
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.0 -53.00 61.00 0.00 -26.50 65.50 2.00 1 1 1 -53.00 0.00 61.00 70.00 0.00 4.00 4.00 1908.00 TARP TARP 477.00 212.00 133.90 74.20 6 5 0 Yes
13 CORRIDOR_POD_3_ZN_1_FLR_1 0.0 -64.00 70.00 0.00 -32.00 71.50 2.00 1 1 1 -64.00 0.00 70.00 73.00 0.00 4.00 4.00 768.00 TARP TARP 192.00 12.00 7.80 4.20 9 1 0 Yes
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.0 -64.00 73.00 0.00 -58.50 77.50 2.00 1 1 1 -64.00 -53.00 73.00 82.00 0.00 4.00 4.00 396.00 TARP TARP 99.00 80.00 50.10 27.95 6 4 0 Yes
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.0 -53.00 73.00 0.00 -35.50 77.50 2.00 1 1 1 -53.00 -18.00 73.00 82.00 0.00 4.00 4.00 1260.00 TARP TARP 315.00 140.00 87.10 49.00 6 5 0 Yes
16 COMPUTER_CLASS_ZN_1_FLR_1 0.0 -18.00 73.00 0.00 -9.00 77.50 2.00 1 1 1 -18.00 0.00 73.00 82.00 0.00 4.00 4.00 648.00 TARP TARP 162.00 72.00 44.85 25.20 6 3 0 Yes
17 MAIN_CORRIDOR_ZN_1_FLR_1 0.0 0.00 9.00 0.00 6.50 30.00 2.00 1 1 1 0.00 13.00 9.00 51.00 0.00 4.00 4.00 2184.00 TARP TARP 546.00 36.00 21.45 12.60 11 3 0 Yes
18 LOBBY_ZN_1_FLR_1 0.0 0.00 0.00 0.00 9.50 4.50 2.00 1 1 1 0.00 19.00 0.00 9.00 0.00 4.00 4.00 684.00 TARP TARP 171.00 76.00 47.45 26.60 7 3 0 Yes
19 MECH_ZN_1_FLR_1 0.0 13.00 9.00 0.00 16.00 30.00 2.00 1 1 1 13.00 19.00 9.00 51.00 0.00 4.00 4.00 1008.00 TARP TARP 252.00 0.00 0.00 0.00 9 0 0 Yes
20 BATH_ZN_1_FLR_1 0.0 0.00 51.00 0.00 9.50 56.00 2.00 1 1 1 0.00 19.00 51.00 61.00 0.00 4.00 4.00 760.00 TARP TARP 190.00 40.00 26.00 14.00 7 1 0 Yes
21 OFFICES_ZN_1_FLR_1 0.0 19.00 0.00 0.00 29.50 10.50 2.00 1 1 1 19.00 40.00 0.00 21.00 0.00 4.00 4.00 1764.00 TARP TARP 441.00 168.00 107.25 58.80 7 4 0 Yes
22 GYM_ZN_1_FLR_1 0.0 19.00 21.00 0.00 29.50 29.50 2.00 1 1 1 19.00 40.00 21.00 38.00 0.00 4.00 4.00 1428.00 TARP TARP 357.00 68.00 42.25 37.18 6 12 0 Yes
23 KITCHEN_ZN_1_FLR_1 0.0 19.00 38.00 0.00 29.50 42.00 2.00 1 1 1 19.00 40.00 38.00 46.00 0.00 4.00 4.00 672.00 TARP TARP 168.00 32.00 20.80 11.20 6 1 0 Yes
24 CAFETERIA_ZN_1_FLR_1 0.0 19.00 46.00 0.00 29.50 53.50 2.00 1 1 1 19.00 40.00 46.00 61.00 0.00 4.00 4.00 1260.00 TARP TARP 315.00 144.00 91.65 50.40 7 4 0 Yes
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.0 0.00 61.00 0.00 9.50 71.50 2.00 1 1 1 0.00 19.00 61.00 82.00 0.00 4.00 4.00 1596.00 TARP TARP 399.00 160.00 102.05 56.00 8 4 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 128.4 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
3 CORRIDOR_POD_1_ZN_1_FLR_1 192.00 10.3 18.579 5.382E-002 7.134 4.000 0.000 0.000 0.000 0.000 11.134 No
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 128.4 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 128.4 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
8 CORRIDOR_POD_2_ZN_1_FLR_1 192.00 10.3 18.579 5.382E-002 7.134 4.000 0.000 0.000 0.000 0.000 11.134 No
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 128.4 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 128.4 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
13 CORRIDOR_POD_3_ZN_1_FLR_1 192.00 10.3 18.579 5.382E-002 7.134 4.000 0.000 0.000 0.000 0.000 11.134 No
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 26.6 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 84.8 3.716 0.269 13.634 15.000 0.000 0.000 0.000 0.000 28.634 No
16 COMPUTER_CLASS_ZN_1_FLR_1 162.00 43.6 3.716 0.269 13.634 20.000 0.000 0.000 0.000 0.000 33.634 No
17 MAIN_CORRIDOR_ZN_1_FLR_1 546.00 29.4 18.579 5.382E-002 7.134 4.000 0.000 0.000 0.000 0.000 11.134 No
18 LOBBY_ZN_1_FLR_1 171.00 18.4 9.289 0.108 9.688 4.000 0.000 0.000 0.000 0.000 13.688 No
19 MECH_ZN_1_FLR_1 252.00 4.1 61.932 1.615E-002 4.521 10.000 0.000 0.000 0.000 0.000 14.521 No
20 BATH_ZN_1_FLR_1 190.00 10.2 18.578 5.383E-002 10.549 4.000 0.000 0.000 0.000 0.000 14.549 No
21 OFFICES_ZN_1_FLR_1 441.00 23.7 18.579 5.382E-002 11.341 10.800 0.000 0.000 0.000 0.000 22.141 No
22 GYM_ZN_1_FLR_1 357.00 115.3 3.096 0.323 11.948 5.000 0.000 0.000 0.000 0.000 16.948 No
23 KITCHEN_ZN_1_FLR_1 168.00 27.0 6.224 0.161 13.024 199.289 1431.100 0.000 0.000 0.000 1643.414 No
24 CAFETERIA_ZN_1_FLR_1 315.00 339.1 0.929 1.076 6.997 25.390 0.000 0.000 0.000 0.000 32.387 No
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 43.0 9.289 0.108 16.307 15.000 0.000 0.000 0.000 0.000 31.307 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 128.4 128.4 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 122 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORRIDOR_POD_1_ZN_1_FLR_1 BLDG_OCC_SCH CORRIDOR_POD_1_ZN_1_FLR_1 192.00 10.3 10.3 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 128.4 128.4 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 122 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 128.4 128.4 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 122 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORRIDOR_POD_2_ZN_1_FLR_1 BLDG_OCC_SCH CORRIDOR_POD_2_ZN_1_FLR_1 192.00 10.3 10.3 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 128.4 128.4 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 122 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 128.4 128.4 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 122 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 CORRIDOR_POD_3_ZN_1_FLR_1 BLDG_OCC_SCH CORRIDOR_POD_3_ZN_1_FLR_1 192.00 10.3 10.3 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 BLDG_OCC_SCH CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 26.6 26.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 25 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 BLDG_OCC_SCH MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 84.8 84.8 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 81 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 COMPUTER_CLASS_ZN_1_FLR_1 BLDG_OCC_SCH_EXTEND COMPUTER_CLASS_ZN_1_FLR_1 162.00 43.6 43.6 0.269 3.716 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 41 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 MECH_ZN_1_FLR_1 BLDG_OCC_SCH MECH_ZN_1_FLR_1 252.00 4.1 4.1 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 BATH_ZN_1_FLR_1 BLDG_OCC_SCH BATH_ZN_1_FLR_1 190.00 10.2 10.2 5.383E-002 18.578 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 OFFICES_ZN_1_FLR_1 BLDG_OCC_SCH_OFFICES_W_SB OFFICES_ZN_1_FLR_1 441.00 23.7 23.7 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 23 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 GYM_ZN_1_FLR_1 BLDG_OCC_SCH_GYM GYM_ZN_1_FLR_1 357.00 115.3 115.3 0.323 3.096 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 110 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 KITCHEN_ZN_1_FLR_1 BLDG_OCC_SCH KITCHEN_ZN_1_FLR_1 168.00 27.0 27.0 0.161 6.224 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 26 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 CAFETERIA_ZN_1_FLR_1 BLDG_OCC_SCH_CAFETERIA CAFETERIA_ZN_1_FLR_1 315.00 339.1 339.1 1.076 0.929 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 322 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
23 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 BLDG_OCC_SCH LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 43.0 43.0 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 41 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
24 MAIN_CORRIDOR_ZN_1_FLR_1 BLDG_OCC_SCH MAIN_CORRIDOR_ZN_1_FLR_1 546.00 29.4 29.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 28 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
25 LOBBY_ZN_1_FLR_1 BLDG_OCC_SCH LOBBY_ZN_1_FLR_1 171.00 18.4 18.4 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 128.4 6503.208 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6503.208
3 CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_POD_1_ZN_1_FLR_1 192.00 10.3 1369.707 7.134 132.544 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1369.707
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 128.4 6503.208 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6503.208
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 128.4 6503.208 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6503.208
8 CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_POD_2_ZN_1_FLR_1 192.00 10.3 1369.707 7.134 132.544 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1369.707
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 128.4 6503.208 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6503.208
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 128.4 6503.208 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6503.208
13 CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_POD_3_ZN_1_FLR_1 192.00 10.3 1369.707 7.134 132.544 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1369.707
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 26.6 1349.722 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1349.722
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS LTG_SCH_CLASSROOM MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 84.8 4294.571 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 4294.571
16 COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS LTG_SCH_COMPUTER_ROOM COMPUTER_CLASS_ZN_1_FLR_1 162.00 43.6 2208.637 13.634 50.662 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 2208.637
17 MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS LTG_SCH_CORRIDOR MAIN_CORRIDOR_ZN_1_FLR_1 546.00 29.4 3895.104 7.134 132.541 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 3895.104
18 LOBBY_ZN_1_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_ZN_1_FLR_1 171.00 18.4 1656.564 9.688 89.992 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1656.564
19 MECH_ZN_1_FLR_1_LIGHTS LTG_SCH_MECHANICAL MECH_ZN_1_FLR_1 252.00 4.1 1139.252 4.521 279.983 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 1139.252
20 BATH_ZN_1_FLR_1_LIGHTS LTG_SCH_BATH BATH_ZN_1_FLR_1 190.00 10.2 2004.238 10.549 195.975 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 2004.238
21 OFFICES_ZN_1_FLR_1_LIGHTS LTG_SCH_OFFICE OFFICES_ZN_1_FLR_1 441.00 23.7 5001.240 11.341 210.698 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 5001.240
22 GYM_ZN_1_FLR_1_LIGHTS LTG_SCH_GYM GYM_ZN_1_FLR_1 357.00 115.3 4265.411 11.948 36.991 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 4265.411
23 KITCHEN_ZN_1_FLR_1_LIGHTS LTG_SCH_KITCHEN KITCHEN_ZN_1_FLR_1 168.00 27.0 2188.086 13.024 81.061 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 2188.086
24 CAFETERIA_ZN_1_FLR_1_LIGHTS LTG_SCH_CAFETERIA CAFETERIA_ZN_1_FLR_1 315.00 339.1 2203.907 6.997 6.500 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 2203.907
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS LTG_SCH_LIBRARY LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 43.0 6506.617 16.307 151.479 0.000 0.370 0.200 0.430 1.000 LightsWired 0.000 6506.617


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 128.4 7155.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 1394.662 6797.250
3 CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORRIDOR_POD_1_ZN_1_FLR_1 192.00 10.3 768.000 4.000 74.318 0.000 0.500 0.000 0.500 MiscPlug 149.700 729.600
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 128.4 7155.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 1394.662 6797.250
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 128.4 7155.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 1394.662 6797.250
8 CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORRIDOR_POD_2_ZN_1_FLR_1 192.00 10.3 768.000 4.000 74.318 0.000 0.500 0.000 0.500 MiscPlug 149.700 729.600
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 128.4 7155.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 1394.662 6797.250
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 128.4 7155.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 1394.662 6797.250
13 CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORRIDOR_POD_3_ZN_1_FLR_1 192.00 10.3 768.000 4.000 74.318 0.000 0.500 0.000 0.500 MiscPlug 149.700 729.600
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 26.6 1485.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 289.458 1410.750
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 84.8 4725.000 15.000 55.740 0.000 0.500 0.000 0.500 MiscPlug 921.003 4488.750
16 COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH COMPUTER_CLASS_ZN_1_FLR_1 162.00 43.6 3240.000 20.000 74.320 0.000 0.500 0.000 0.500 MiscPlug 631.545 3078.000
17 MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MAIN_CORRIDOR_ZN_1_FLR_1 546.00 29.4 2184.000 4.000 74.316 0.000 0.500 0.000 0.500 MiscPlug 425.708 2074.800
18 LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH LOBBY_ZN_1_FLR_1 171.00 18.4 684.000 4.000 37.158 0.000 0.500 0.000 0.500 MiscPlug 133.326 649.800
19 MECH_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH MECH_ZN_1_FLR_1 252.00 4.1 2520.000 10.000 619.317 0.000 0.500 0.000 0.500 MiscPlug 491.202 2394.000
20 BATH_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH BATH_ZN_1_FLR_1 190.00 10.2 760.000 4.000 74.313 0.000 0.500 0.000 0.500 MiscPlug 148.140 722.000
21 OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH OFFICES_ZN_1_FLR_1 441.00 23.7 4762.800 10.800 200.653 0.000 0.500 0.000 0.500 MiscPlug 928.371 4524.660
22 GYM_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH GYM_ZN_1_FLR_1 357.00 115.3 1785.000 5.000 15.480 0.000 0.500 0.000 0.500 MiscPlug 347.935 1695.750
23 KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_ZN_1_FLR_1 168.00 27.0 31995.600 190.450 1185.330 0.250 0.300 0.200 0.250 Cooking 3199.560 7998.900
24 KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER ALWAYS_ON KITCHEN_ZN_1_FLR_1 168.00 27.0 915.000 5.446 33.898 0.000 0.000 1.000 0.000 ReachInFreezer 915.000 915.000
25 KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_ZN_1_FLR_1 168.00 27.0 570.000 3.393 21.117 0.000 0.000 1.000 0.000 ReachInRefrigerator 570.000 570.000
26 CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP KITCHEN_ELEC_EQUIP_SCH CAFETERIA_ZN_1_FLR_1 315.00 339.1 7997.850 25.390 23.587 0.000 0.500 0.000 0.500 Cooking 799.785 1999.463
27 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP BLDG_EQUIP_SCH LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 43.0 5985.000 15.000 139.335 0.000 0.500 0.000 0.500 MiscPlug 1166.604 5685.750


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_ZN_1_FLR_1 168.00 27.0 240424.800 1431.100 8906.931 0.100 0.200 0.700 0.000 Cooking 4808.496 48084.960


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.975 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
4 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
5 NONRES_EXT_WALL_GRD 20 4 7 0.167 1.199 0.900 0.900 0.700 0.700 Smooth
6 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 37 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
7 MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 38 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
8 CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 39 2 7 0.167 0.1980E-01 0.000 0.900 0.000 0.700 MediumRough
9 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 40 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
10 MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 41 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
11 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 42 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
12 MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 43 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
13 CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 44 2 7 0.167 0.1980E-01 0.000 0.900 0.000 0.700 MediumRough
14 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 45 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
15 MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 46 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
16 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 47 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
17 MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 48 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
18 CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 49 2 7 0.167 0.1980E-01 0.000 0.900 0.000 0.700 MediumRough
19 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 50 2 7 0.167 0.2658 0.000 0.900 0.000 0.700 MediumRough
20 MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 51 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
21 COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR 52 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
22 MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR 53 2 7 0.167 0.2090E-01 0.000 0.900 0.000 0.700 MediumRough
23 LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR 54 2 7 0.167 0.1435 0.000 0.900 0.000 0.700 MediumRough
24 MECH_ZN_1_FLR_1_FLOOR_FFACTOR 55 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
25 BATH_ZN_1_FLR_1_FLOOR_FFACTOR 56 2 7 0.167 0.6720E-01 0.000 0.900 0.000 0.700 MediumRough
26 OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR 57 2 7 0.167 0.1226 0.000 0.900 0.000 0.700 MediumRough
27 GYM_ZN_1_FLR_1_FLOOR_FFACTOR 58 2 7 0.167 0.6074E-01 0.000 0.900 0.000 0.700 MediumRough
28 KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR 59 2 7 0.167 0.6074E-01 0.000 0.900 0.000 0.700 MediumRough
29 CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR 60 2 7 0.167 0.1477 0.000 0.900 0.000 0.700 MediumRough
30 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR 61 2 7 0.167 0.1292 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2516
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
6 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
7 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
8 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
9 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
10 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6002
11 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
12 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.685
13 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
14 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 6.890
15 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
16 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 50.42
17 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
18 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.685
19 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
20 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 6.890
21 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
22 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 3.685
23 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
24 ~FC_Insulation_7 0.0000 0.000 0.000 0.000 6.890
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_8 0.0000 0.000 0.000 0.000 50.42
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_9 0.0000 0.000 0.000 0.000 3.685
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_10 0.0000 0.000 0.000 0.000 6.890
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_11 0.0000 0.000 0.000 0.000 3.685
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_12 0.0000 0.000 0.000 0.000 6.890
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
36 ~FC_Insulation_13 0.0000 0.000 0.000 0.000 50.42
37 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
38 ~FC_Insulation_14 0.0000 0.000 0.000 0.000 3.685
39 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
40 ~FC_Insulation_15 0.0000 0.000 0.000 0.000 6.890
41 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
42 ~FC_Insulation_16 0.0000 0.000 0.000 0.000 6.890
43 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
44 ~FC_Insulation_17 0.0000 0.000 0.000 0.000 47.78
45 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
46 ~FC_Insulation_18 0.0000 0.000 0.000 0.000 6.890
47 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
48 ~FC_Insulation_19 0.0000 0.000 0.000 0.000 176.9
49 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
50 ~FC_Insulation_20 0.0000 0.000 0.000 0.000 14.80
51 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
52 ~FC_Insulation_21 0.0000 0.000 0.000 0.000 8.077
53 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
54 ~FC_Insulation_22 0.0000 0.000 0.000 0.000 16.39
55 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
56 ~FC_Insulation_23 0.0000 0.000 0.000 0.000 16.39
57 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
58 ~FC_Insulation_24 0.0000 0.000 0.000 0.000 6.693
59 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
60 ~FC_Insulation_25 0.0000 0.000 0.000 0.000 7.662
61 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.9747841 3.9747841 3.9747841  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
14 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
15 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
16 1 -12.650482 3.3590720 -12.650482 0.19281313
17 0 16.907513 1.4507143 16.907513  
18 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
19 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
20 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
21 0 21.361010 0.87247630E-01 5.4456762  
22 7 -0.27991554E-12 0.13844840E-14 -0.87333690E-13 0.18783897E-15
23 6 0.23602301E-07 0.31643105E-09 0.54490824E-08 -0.10821103E-12
24 5 -0.16400413E-03 0.28071651E-05 -0.84647433E-04 0.53993493E-08
25 4 0.26106082 0.14101882E-02 0.88530219E-01 -0.29241196E-04
26 3 -6.6493978 0.44924573E-01 -2.1559396 0.25989366E-01
27 2 38.835009 0.16365057 14.511379 -0.31067105
28 1 -78.983906 0.75414638E-01 -28.465032 1.0453378
29 0 46.824349 0.15487056E-02 16.308099  
30 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
31 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
32 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
33 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
34 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
35 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
36 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
37 0 0.27084135 0.13419224E-04 60.838472  
38 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
39 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
40 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
41 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
42 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
43 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
44 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
45 0 0.14507897 0.72057125E-05 60.838472  
46 7 -0.21707302E-07 -0.21810081E-14 -0.84952625E-14 0.13770899E-15
47 6 0.21407607E-05 0.45739277E-09 0.32038929E-02 -0.26876939E-04
48 5 -0.77205346E-04 0.24803070E-06 -0.22452059 0.19631768E-02
49 4 0.12599243E-02 0.10780209E-04 4.8427850 -0.45392265E-01
50 3 -0.93942915E-02 0.82583168E-04 -38.096111 0.39947953
51 2 0.30967349E-01 0.13253122E-03 116.62920 -1.4198824
52 1 -0.43132160E-01 0.38654114E-04 -143.99276 2.0504445
53 0 0.20639933E-01 0.87079362E-06 60.838472  
54 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
55 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
56 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
57 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
58 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
59 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
60 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
61 0 0.27084135 0.13419224E-04 60.838472  
62 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
63 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
64 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
65 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
66 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
67 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
68 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
69 0 0.14507897 0.72057125E-05 60.838472  
70 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
71 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
72 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
73 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
74 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
75 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
76 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
77 0 0.27084135 0.13419224E-04 60.838472  
78 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
79 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
80 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
81 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
82 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
83 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
84 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
85 0 0.14507897 0.72057125E-05 60.838472  
86 7 -0.21707302E-07 -0.21810081E-14 -0.84952625E-14 0.13770899E-15
87 6 0.21407607E-05 0.45739277E-09 0.32038929E-02 -0.26876939E-04
88 5 -0.77205346E-04 0.24803070E-06 -0.22452059 0.19631768E-02
89 4 0.12599243E-02 0.10780209E-04 4.8427850 -0.45392265E-01
90 3 -0.93942915E-02 0.82583168E-04 -38.096111 0.39947953
91 2 0.30967349E-01 0.13253122E-03 116.62920 -1.4198824
92 1 -0.43132160E-01 0.38654114E-04 -143.99276 2.0504445
93 0 0.20639933E-01 0.87079362E-06 60.838472  
94 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
95 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
96 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
97 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
98 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
99 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
100 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
101 0 0.27084135 0.13419224E-04 60.838472  
102 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
103 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
104 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
105 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
106 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
107 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
108 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
109 0 0.14507897 0.72057125E-05 60.838472  
110 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
111 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
112 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
113 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
114 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
115 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
116 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
117 0 0.27084135 0.13419224E-04 60.838472  
118 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
119 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
120 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
121 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
122 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
123 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
124 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
125 0 0.14507897 0.72057125E-05 60.838472  
126 7 -0.21707302E-07 -0.21810081E-14 -0.84952625E-14 0.13770899E-15
127 6 0.21407607E-05 0.45739277E-09 0.32038929E-02 -0.26876939E-04
128 5 -0.77205346E-04 0.24803070E-06 -0.22452059 0.19631768E-02
129 4 0.12599243E-02 0.10780209E-04 4.8427850 -0.45392265E-01
130 3 -0.93942915E-02 0.82583168E-04 -38.096111 0.39947953
131 2 0.30967349E-01 0.13253122E-03 116.62920 -1.4198824
132 1 -0.43132160E-01 0.38654114E-04 -143.99276 2.0504445
133 0 0.20639933E-01 0.87079362E-06 60.838472  
134 7 -0.15772792E-08 -0.28680592E-15 0.12691911E-13 -0.18935729E-15
135 6 0.74265588E-05 0.51025248E-08 0.31846465E-02 -0.26715484E-04
136 5 -0.53586969E-03 0.30237275E-05 -0.22342768 0.19535297E-02
137 4 0.12337436E-01 0.13766923E-03 4.8246004 -0.45217444E-01
138 3 -0.10837303 0.10950400E-02 -37.993479 0.39834495
139 2 0.38485319 0.18220149E-02 116.42957 -1.4172120
140 1 -0.55550401 0.55531650E-03 -143.87530 2.0485138
141 0 0.27084135 0.13419224E-04 60.838472  
142 7 -0.29578731E-08 -0.18610472E-14 0.16360026E-14 -0.48190060E-16
143 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
144 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
145 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
146 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
147 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
148 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
149 0 0.14507897 0.72057125E-05 60.838472  
150 7 -0.29578731E-08 -0.18610472E-14 0.16360026E-14 -0.48190060E-16
151 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
152 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
153 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
154 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
155 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
156 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
157 0 0.14507897 0.72057125E-05 60.838472  
158 7 -0.20570949E-07 -0.14658537E-14 -0.76832012E-14 0.12671469E-15
159 6 0.20860838E-05 0.47270270E-09 0.32038024E-02 -0.26876180E-04
160 5 -0.77354338E-04 0.25871613E-06 -0.22451551 0.19631320E-02
161 4 0.12908389E-02 0.11299182E-04 4.8427016 -0.45391462E-01
162 3 -0.97548753E-02 0.86890235E-04 -38.095646 0.39947438
163 2 0.32375441E-01 0.13995703E-03 116.62830 -1.4198704
164 1 -0.45248243E-01 0.40996175E-04 -143.99224 2.0504359
165 0 0.21692461E-01 0.93166815E-06 60.838472  
166 7 -0.29578731E-08 -0.18610471E-14 0.16360024E-14 -0.48190056E-16
167 6 0.41253938E-05 0.27444675E-08 0.31942391E-02 -0.26795954E-04
168 5 -0.29029299E-03 0.16230583E-05 -0.22397289 0.19583421E-02
169 4 0.66360716E-02 0.73828161E-04 4.8336813 -0.45304736E-01
170 3 -0.58145393E-01 0.58669454E-03 -38.044778 0.39891197
171 2 0.20628369 0.97546675E-03 116.52942 -1.4185475
172 1 -0.29762541 0.29693282E-03 -143.93407 2.0494798
173 0 0.14507897 0.72057125E-05 60.838472  
174 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
175 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
176 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
177 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
178 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
179 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
180 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
181 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
182 0 0.84795330E-02 0.69040512E-07 60.838472  
183 7 -0.63667935E-08 -0.10874325E-13 0.11269204E-14 -0.19557179E-16
184 6 0.22887183E-05 0.12967685E-08 0.32001644E-02 -0.26845660E-04
185 5 -0.14389595E-03 0.76205050E-06 -0.22430950 0.19613133E-02
186 4 0.31719958E-02 0.34552480E-04 4.8392847 -0.45358602E-01
187 3 -0.27412176E-01 0.27382890E-03 -38.076416 0.39926170
188 2 0.96706121E-01 0.45412367E-03 116.59097 -1.4193709
189 1 -0.13917125 0.13776341E-03 -143.97030 2.0500753
190 0 0.67751290E-01 0.33403087E-05 60.838472  
191 7 -0.34692083E-08 -0.29835039E-14 0.22457095E-14 -0.46878358E-16
192 6 0.35887165E-05 0.23456121E-08 0.31958645E-02 -0.26809589E-04
193 5 -0.24929292E-03 0.13860889E-05 -0.22406525 0.19591573E-02
194 4 0.56768486E-02 0.63026314E-04 4.8352193 -0.45319520E-01
195 3 -0.49670058E-01 0.50068761E-03 -38.053464 0.39900799
196 2 0.17611533 0.83223021E-03 116.54632 -1.4187736
197 1 -0.25403345 0.25321776E-03 -143.94402 2.0496434
198 0 0.12381374 0.61501487E-05 60.838472  
199 7 -0.70485818E-08 -0.82048821E-14 -0.11525862E-14 0.12346975E-16
200 6 0.21636134E-05 0.11761400E-08 0.32006654E-02 -0.26849864E-04
201 5 -0.13228193E-03 0.68999669E-06 -0.22433795 0.19615643E-02
202 4 0.28871477E-02 0.31257738E-04 4.8397578 -0.45363150E-01
203 3 -0.24853202E-01 0.24753724E-03 -38.079085 0.39929121
204 2 0.87536903E-01 0.41023195E-03 116.59616 -1.4194403
205 1 -0.12588244 0.12433901E-03 -143.97335 2.0501255
206 0 0.61258788E-01 0.30111189E-05 60.838472  
207 7 -0.70485818E-08 -0.82048821E-14 -0.11525862E-14 0.12346975E-16
208 6 0.21636134E-05 0.11761400E-08 0.32006654E-02 -0.26849864E-04
209 5 -0.13228193E-03 0.68999669E-06 -0.22433795 0.19615643E-02
210 4 0.28871477E-02 0.31257738E-04 4.8397578 -0.45363150E-01
211 3 -0.24853202E-01 0.24753724E-03 -38.079085 0.39929121
212 2 0.87536903E-01 0.41023195E-03 116.59616 -1.4194403
213 1 -0.12588244 0.12433901E-03 -143.97335 2.0501255
214 0 0.61258788E-01 0.30111189E-05 60.838472  
215 7 -0.28726507E-08 -0.17143581E-14 0.24267693E-14 -0.55541839E-16
216 6 0.42346750E-05 0.28245518E-08 0.31939123E-02 -0.26793213E-04
217 5 -0.29857172E-03 0.16707368E-05 -0.22395432 0.19581782E-02
218 4 0.68293023E-02 0.76000496E-04 4.8333721 -0.45301763E-01
219 3 -0.59851213E-01 0.60399479E-03 -38.043031 0.39889267
220 2 0.21235346 0.10042645E-02 116.52602 -1.4185020
221 1 -0.30639453 0.30573542E-03 -143.93207 2.0494469
222 0 0.14935640 0.74123768E-05 60.838472  
223 7 -0.32902409E-08 -0.25529066E-14 0.11988885E-14 -0.45014903E-16
224 6 0.37562854E-05 0.24712502E-08 0.31953527E-02 -0.26805296E-04
225 5 -0.26216584E-03 0.14606656E-05 -0.22403617 0.19589006E-02
226 4 0.59784819E-02 0.66426580E-04 4.8347351 -0.45314865E-01
227 3 -0.52336689E-01 0.52775921E-03 -38.050729 0.39897776
228 2 0.18560952 0.87732663E-03 116.54100 -1.4187024
229 1 -0.26775360 0.26697134E-03 -143.94089 2.0495919
230 0 0.13050713 0.64865099E-05 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.495_SHGC_0.25 35 1 VerySmooth 2.814 2.814 1.000 0.251    
2 NONRESSKYLIGHT_U_0.55_SHGC_0.35 36 1 VerySmooth 3.127 3.127 1.000 0.351    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   2.05411E-002 0.16139 0.61177 0.61177 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.11105 1.00000 No
2 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   1.15759E-002 0.26293 0.50711 0.50711 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 7.71143E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 3 0
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 3 0
3 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 3 0
4 MULT_CLASS_2_POD_1_ZN_1_FLR_1 3 0
5 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 3 0
6 MULT_CLASS_1_POD_2_ZN_1_FLR_1 3 0
7 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 3 0
8 MULT_CLASS_2_POD_2_ZN_1_FLR_1 3 0
9 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 3 0
10 MULT_CLASS_1_POD_3_ZN_1_FLR_1 3 0
11 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 3 0
12 MULT_CLASS_2_POD_3_ZN_1_FLR_1 3 0
13 COMPUTER_CLASS_ZN_1_FLR_1 2 0
14 LOBBY_ZN_1_FLR_1 2 0
15 OFFICES_ZN_1_FLR_1 3 0
16 GYM_ZN_1_FLR_1 11 0
17 CAFETERIA_ZN_1_FLR_1 3 0
18 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 3 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0  
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 0  
3 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0  
4 MULT_CLASS_2_POD_1_ZN_1_FLR_1 0  
5 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0  
6 MULT_CLASS_1_POD_2_ZN_1_FLR_1 0  
7 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0  
8 MULT_CLASS_2_POD_2_ZN_1_FLR_1 0  
9 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0  
10 MULT_CLASS_1_POD_3_ZN_1_FLR_1 0  
11 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0  
12 MULT_CLASS_2_POD_3_ZN_1_FLR_1 0  
13 COMPUTER_CLASS_ZN_1_FLR_1 0  
14 LOBBY_ZN_1_FLR_1 0  
15 OFFICES_ZN_1_FLR_1 0  
16 GYM_ZN_1_FLR_1 0  
17 CAFETERIA_ZN_1_FLR_1 0  
18 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 6000.0 1.384 1.2733
2 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.7570 58614.2 0.746 0.2471


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 4 No No
2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
3 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
4 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 0 No No
5 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
6 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
7 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
8 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
9 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
10 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
11 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
12 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 4 No No
13 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
14 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
15 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
16 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
17 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
18 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
19 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
20 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
22 MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 53.00 15.39 0.35 0 No No
23 MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
24 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
25 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
26 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
27 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
28 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
29 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 4 No No
30 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 1 No No
31 CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
32 CORRIDOR_POD_1_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 3.00 5.73 0.35 0 No No
33 CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
34 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
35 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
36 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 4 No No
37 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
38 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
39 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 0 No No
40 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
41 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
42 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
43 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
44 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
45 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
46 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
47 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 4 No No
48 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
49 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
50 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
51 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 0 No No
52 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 0 No No
53 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
54 MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
55 MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 53.00 15.39 0.35 0 No No
56 MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
57 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 4 No No
58 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
59 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
60 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 0 No No
61 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
62 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
63 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
64 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
65 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
66 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
67 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
68 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 4 No No
69 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
70 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
71 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
72 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
73 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
74 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
75 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
76 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
77 MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
78 MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 53.00 15.39 0.35 0 No No
79 MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
80 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
81 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
82 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
83 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
84 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
85 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 4 No No
86 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 1 No No
87 CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
88 CORRIDOR_POD_2_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 3.00 5.73 0.35 0 No No
89 CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
90 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
91 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
92 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 4 No No
93 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
94 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
95 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 0 No No
96 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
97 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
98 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
99 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
100 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
101 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
102 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
103 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 4 No No
104 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
105 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
106 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 1 No No
107 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 0 No No
108 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 0 928.00 272.88 4.00 0 4.00 53.00 15.39 0.35 0 No No
109 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
110 MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
111 MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 53.00 15.39 0.35 0 No No
112 MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
113 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 4 No No
114 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
115 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 1 No No
116 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR 0 928.00 249.14 4.00 0 4.00 20.00 9.90 0.35 0 No No
117 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
118 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
119 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
120 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
121 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
122 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
123 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
124 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 4 No No
125 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
126 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
127 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 1 No No
128 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
129 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 0 928.00 249.14 4.00 0 4.00 53.00 15.39 0.35 0 No No
130 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
131 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
132 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
133 MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
134 MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 53.00 15.39 0.35 0 No No
135 MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 53.00 15.39 0.35 0 No No
136 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
137 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
138 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
139 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
140 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
141 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
142 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 4 No No
143 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 0 328.00 216.04 4.00 0 4.00 3.00 5.73 0.35 1 No No
144 CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
145 CORRIDOR_POD_3_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 3.00 5.73 0.35 0 No No
146 CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 3.00 5.73 0.35 0 No No
147 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
148 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
149 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 4 No No
150 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
151 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 1 No No
152 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR 0 928.00 272.88 4.00 0 4.00 20.00 9.90 0.35 0 No No
153 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 4 No No
154 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 0 328.00 216.04 4.00 0 4.00 20.00 9.90 0.35 1 No No
155 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
156 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 20.00 9.90 0.35 0 No No
157 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 20.00 9.90 0.35 0 No No
158 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 35.00 14.32 0.35 0 No No
159 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 35.00 14.32 0.35 0 No No
160 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 4 No No
161 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 1 No No
162 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 1 No No
163 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 1 No No
164 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 0 No No
165 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 0 928.00 272.88 4.00 0 4.00 35.00 14.32 0.35 0 No No
166 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 35.00 14.32 0.35 0 No No
167 MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 35.00 14.32 0.35 0 No No
168 MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 35.00 14.32 0.35 0 No No
169 MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 35.00 14.32 0.35 0 No No
170 COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 18.00 12.00 0.35 0 No No
171 COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 18.00 12.00 0.35 0 No No
172 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 18.00 12.00 0.35 4 No No
173 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 0 928.00 272.88 4.00 0 4.00 18.00 12.00 0.35 1 No No
174 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 0 928.00 272.88 4.00 0 4.00 18.00 12.00 0.35 1 No No
175 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR 0 928.00 272.88 4.00 0 4.00 18.00 12.00 0.35 0 No No
176 COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 18.00 12.00 0.35 0 No No
177 COMPUTER_CLASS_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 18.00 12.00 0.35 0 No No
178 COMPUTER_CLASS_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 18.00 12.00 0.35 0 No No
179 COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 18.00 12.00 0.35 0 No No
180 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
181 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
182 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
183 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
184 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
185 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
186 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 0 328.00 216.04 4.00 0 4.00 9.00 19.85 0.35 4 No No
187 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 0 328.00 216.04 4.00 0 4.00 9.00 19.85 0.35 1 No No
188 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 0 328.00 216.04 4.00 0 4.00 9.00 19.85 0.35 1 No No
189 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR 0 328.00 216.04 4.00 0 4.00 9.00 19.85 0.35 0 No No
190 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
191 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
192 MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
193 MAIN_CORRIDOR_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 9.00 19.85 0.35 0 No No
194 MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 9.00 19.85 0.35 0 No No
195 LOBBY_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 19.00 12.21 0.35 4 No No
196 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 19.00 12.21 0.35 1 No No
197 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 19.00 12.21 0.35 1 No No
198 LOBBY_ZN_1_FLR_1_WALL_1_DOOR 0 928.00 249.14 4.00 0 4.00 19.00 12.21 0.35 0 No No
199 LOBBY_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
200 LOBBY_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
201 LOBBY_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
202 LOBBY_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
203 LOBBY_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
204 LOBBY_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 19.00 12.21 0.35 0 No No
205 LOBBY_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 19.00 12.21 0.35 0 No No
206 MECH_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
207 MECH_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
208 MECH_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
209 MECH_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
210 MECH_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
211 MECH_ZN_1_FLR_1_WALL_6 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
212 MECH_ZN_1_FLR_1_WALL_7 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
213 MECH_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
214 MECH_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 0.00 10.50 -999.00 0 No No
215 MECH_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 0.00 10.50 -999.00 0 No No
216 BATH_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
217 BATH_ZN_1_FLR_1_WALL_2 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
218 BATH_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
219 BATH_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
220 BATH_ZN_1_FLR_1_WALL_5 0 328.00 216.04 4.00 0 4.00 10.00 13.10 0.35 4 No No
221 BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 0 328.00 216.04 4.00 0 4.00 10.00 13.10 0.35 1 No No
222 BATH_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
223 BATH_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 10.00 13.10 0.35 0 No No
224 BATH_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 10.00 13.10 0.35 0 No No
225 OFFICES_ZN_1_FLR_1_WALL_1 0 928.00 249.14 4.00 0 4.00 42.00 21.00 0.35 4 No No
226 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 0 928.00 249.14 4.00 0 4.00 42.00 21.00 0.35 1 No No
227 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 0 928.00 249.14 4.00 0 4.00 42.00 21.00 0.35 1 No No
228 OFFICES_ZN_1_FLR_1_WALL_1_DOOR 0 928.00 249.14 4.00 0 4.00 42.00 21.00 0.35 0 No No
229 OFFICES_ZN_1_FLR_1_WALL_2 0 328.00 190.47 4.00 0 4.00 42.00 21.00 0.35 4 No No
230 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 0 328.00 190.47 4.00 0 4.00 42.00 21.00 0.35 1 No No
231 OFFICES_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 42.00 21.00 0.35 0 No No
232 OFFICES_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 42.00 21.00 0.35 0 No No
233 OFFICES_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 42.00 21.00 0.35 0 No No
234 OFFICES_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 42.00 21.00 0.35 0 No No
235 OFFICES_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 42.00 21.00 0.35 0 No No
236 OFFICES_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 42.00 21.00 0.35 0 No No
237 GYM_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 17.00 18.79 0.55 0 No No
238 GYM_ZN_1_FLR_1_WALL_2 0 328.00 190.47 4.00 0 4.00 17.00 18.79 0.55 4 No No
239 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 0 328.00 190.47 4.00 0 4.00 17.00 18.79 0.55 5 No No
240 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 0 328.00 190.47 4.00 0 4.00 17.00 18.79 0.55 5 No No
241 GYM_ZN_1_FLR_1_WALL_2_DOOR 0 328.00 190.47 4.00 0 4.00 17.00 18.79 0.55 0 No No
242 GYM_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 17.00 18.79 0.55 0 No No
243 GYM_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 17.00 18.79 0.55 0 No No
244 GYM_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 17.00 18.79 0.55 0 No No
245 GYM_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 0 No No
246 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
247 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
248 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
249 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
250 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
251 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
252 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
253 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
254 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 0 6871.00 354.65 0.00 0 4.00 17.00 18.79 0.55 5 No No
255 GYM_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 17.00 18.79 0.55 0 No No
256 KITCHEN_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 8.00 11.59 0.35 0 No No
257 KITCHEN_ZN_1_FLR_1_WALL_2 0 328.00 190.47 4.00 0 4.00 8.00 11.59 0.35 4 No No
258 KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 0 328.00 190.47 4.00 0 4.00 8.00 11.59 0.35 1 No No
259 KITCHEN_ZN_1_FLR_1_WALL_3 0 0.00 0.00 0.00 0 4.00 8.00 11.59 0.35 0 No No
260 KITCHEN_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 8.00 11.59 0.35 0 No No
261 KITCHEN_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 8.00 11.59 0.35 0 No No
262 KITCHEN_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 8.00 11.59 0.35 0 No No
263 KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 8.00 11.59 0.35 0 No No
264 CAFETERIA_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 36.00 17.50 0.35 0 No No
265 CAFETERIA_ZN_1_FLR_1_WALL_2 0 328.00 190.47 4.00 0 4.00 36.00 17.50 0.35 4 No No
266 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 0 328.00 190.47 4.00 0 4.00 36.00 17.50 0.35 1 No No
267 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 0 328.00 190.47 4.00 0 4.00 36.00 17.50 0.35 1 No No
268 CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR 0 328.00 190.47 4.00 0 4.00 36.00 17.50 0.35 0 No No
269 CAFETERIA_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 36.00 17.50 0.35 4 No No
270 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 0 928.00 272.88 4.00 0 4.00 36.00 17.50 0.35 1 No No
271 CAFETERIA_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 36.00 17.50 0.35 0 No No
272 CAFETERIA_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 36.00 17.50 0.35 0 No No
273 CAFETERIA_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 36.00 17.50 0.35 0 No No
274 CAFETERIA_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 36.00 17.50 0.35 0 No No
275 CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 36.00 17.50 0.35 0 No No
276 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No
277 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 0 328.00 190.47 4.00 0 4.00 40.00 19.95 0.35 4 No No
278 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 0 328.00 190.47 4.00 0 4.00 40.00 19.95 0.35 1 No No
279 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 0 328.00 190.47 4.00 0 4.00 40.00 19.95 0.35 1 No No
280 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR 0 328.00 190.47 4.00 0 4.00 40.00 19.95 0.35 0 No No
281 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 0 928.00 272.88 4.00 0 4.00 40.00 19.95 0.35 4 No No
282 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 0 928.00 272.88 4.00 0 4.00 40.00 19.95 0.35 1 No No
283 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No
284 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No
285 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No
286 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No
287 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING 0 6871.00 354.65 0.00 0 4.00 40.00 19.95 0.35 0 No No
288 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.00 40.00 19.95 0.35 0 No No


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES CurtainWall 3.043 0.356 0.402


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 128.4 0.121 2.531E-004 1.743E-004 0.228 0.000 0.000 0.224 0.000
3 CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORRIDOR_POD_1_ZN_1_FLR_1 192.00 10.3 6.835E-003 3.560E-005 3.350E-005 3.204E-002 0.000 0.000 0.224 0.000
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 128.4 0.121 2.531E-004 1.743E-004 0.228 0.000 0.000 0.224 0.000
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 128.4 0.121 2.531E-004 1.743E-004 0.228 0.000 0.000 0.224 0.000
8 CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORRIDOR_POD_2_ZN_1_FLR_1 192.00 10.3 6.835E-003 3.560E-005 3.350E-005 3.204E-002 0.000 0.000 0.224 0.000
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 128.4 0.121 2.531E-004 1.743E-004 0.228 0.000 0.000 0.224 0.000
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 128.4 0.121 2.531E-004 1.743E-004 0.228 0.000 0.000 0.224 0.000
13 CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORRIDOR_POD_3_ZN_1_FLR_1 192.00 10.3 6.835E-003 3.560E-005 3.350E-005 3.204E-002 0.000 0.000 0.224 0.000
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 26.6 4.557E-002 4.603E-004 2.518E-004 0.414 0.000 0.000 0.224 0.000
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 84.8 7.974E-002 2.531E-004 1.738E-004 0.228 0.000 0.000 0.224 0.000
16 COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL COMPUTER_CLASS_ZN_1_FLR_1 162.00 43.6 4.101E-002 2.531E-004 1.738E-004 0.228 0.000 0.000 0.224 0.000
17 MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MAIN_CORRIDOR_ZN_1_FLR_1 546.00 29.4 2.050E-002 3.755E-005 3.511E-005 3.380E-002 0.000 0.000 0.224 0.000
18 LOBBY_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL LOBBY_ZN_1_FLR_1 171.00 18.4 4.329E-002 2.531E-004 1.739E-004 0.228 0.000 0.000 0.224 0.000
19 LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH LOBBY_ZN_1_FLR_1 171.00 18.4 3.031 1.773E-002 1.218E-002 15.954 1.000 0.000 0.000 0.000
20 MECH_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL MECH_ZN_1_FLR_1 252.00 4.1 0.000 0.000 0.000 0.000 0.000 0.000 0.224 0.000
21 BATH_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL BATH_ZN_1_FLR_1 190.00 10.2 2.278E-002 1.199E-004 9.906E-005 0.108 0.000 0.000 0.224 0.000
22 OFFICES_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL OFFICES_ZN_1_FLR_1 441.00 23.7 9.569E-002 2.170E-004 1.566E-004 0.195 0.000 0.000 0.224 0.000
23 GYM_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL GYM_ZN_1_FLR_1 357.00 115.3 3.873E-002 1.085E-004 9.072E-005 9.764E-002 0.000 0.000 0.224 0.000
24 KITCHEN_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL KITCHEN_ZN_1_FLR_1 168.00 27.0 1.823E-002 1.085E-004 9.113E-005 9.764E-002 0.000 0.000 0.224 0.000
25 CAFETERIA_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL CAFETERIA_ZN_1_FLR_1 315.00 339.1 8.202E-002 2.604E-004 1.779E-004 0.234 0.000 0.000 0.224 0.000
26 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION INFIL_SCH_PNNL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 43.0 9.113E-002 2.284E-004 1.625E-004 0.206 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 Mixing/Well-Stirred
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 Mixing/Well-Stirred
3 CORRIDOR_POD_1_ZN_1_FLR_1 Mixing/Well-Stirred
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 Mixing/Well-Stirred
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 Mixing/Well-Stirred
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 Mixing/Well-Stirred
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 Mixing/Well-Stirred
8 CORRIDOR_POD_2_ZN_1_FLR_1 Mixing/Well-Stirred
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 Mixing/Well-Stirred
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 Mixing/Well-Stirred
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 Mixing/Well-Stirred
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 Mixing/Well-Stirred
13 CORRIDOR_POD_3_ZN_1_FLR_1 Mixing/Well-Stirred
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 Mixing/Well-Stirred
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 Mixing/Well-Stirred
16 COMPUTER_CLASS_ZN_1_FLR_1 Mixing/Well-Stirred
17 MAIN_CORRIDOR_ZN_1_FLR_1 Mixing/Well-Stirred
18 LOBBY_ZN_1_FLR_1 Mixing/Well-Stirred
19 MECH_ZN_1_FLR_1 Mixing/Well-Stirred
20 BATH_ZN_1_FLR_1 Mixing/Well-Stirred
21 OFFICES_ZN_1_FLR_1 Mixing/Well-Stirred
22 GYM_ZN_1_FLR_1 Mixing/Well-Stirred
23 KITCHEN_ZN_1_FLR_1 Mixing/Well-Stirred
24 CAFETERIA_ZN_1_FLR_1 Mixing/Well-Stirred
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5575E-004
2 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT2 3.0937E-003
3 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5579E-004
4 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1964E-003
5 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT1 2.7349E-004
6 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT2 3.7786E-003
7 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT1 2.8684E-004
8 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 GYM_ZN_1_FLR_1_DAYLREFPT2 2.4302E-003
9 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.6316E-004
10 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.8651E-003
11 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.5266E-004
12 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.8210E-003
13 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.9330E-004
14 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT2 2.4510E-003
15 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.6274E-004
16 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.7953E-003
17 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT1 7.1371E-003
18 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT2 2.9270E-004
19 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT1 7.8581E-003
20 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT2 2.8756E-004
21 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT1 7.7277E-003
22 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1197E-004
23 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT1 4.5991E-003
24 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1434E-004
25 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5428E-004
26 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT2 1.1815E-003
27 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5419E-004
28 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT2 9.9939E-004
29 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT1 2.7165E-004
30 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT2 1.3587E-003
31 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT1 2.8674E-004
32 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 GYM_ZN_1_FLR_1_DAYLREFPT2 2.0782E-003
33 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT1 3.2650E-004
34 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT2 9.7281E-004
35 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT1 3.1286E-004
36 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT2 8.2570E-004
37 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT1 3.4253E-004
38 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT2 1.0541E-003
39 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT1 3.5823E-004
40 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 GYM_ZN_1_FLR_1_DAYLREFPT2 1.5730E-003
41 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT1 1.7486E-003
42 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT2 2.8399E-004
43 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT1 1.4501E-003
44 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT2 2.7784E-004
45 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT1 1.9949E-003
46 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT2 2.9656E-004
47 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT1 3.7206E-003
48 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1303E-004
49 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5106E-004
50 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT2 3.3478E-004
51 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT1 2.5141E-004
52 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1392E-004
53 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT1 2.6843E-004
54 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT2 3.1485E-004
55 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT1 2.8462E-004
56 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 GYM_ZN_1_FLR_1_DAYLREFPT2 3.6234E-004
57 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT1 2.7141E-004
58 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT2 3.2786E-004
59 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT1 2.6695E-004
60 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT2 3.0844E-004
61 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT1 2.8068E-004
62 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT2 3.0863E-004
63 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT1 3.0055E-004
64 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 GYM_ZN_1_FLR_1_DAYLREFPT2 3.5364E-004
65 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT1 3.5167E-004
66 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT2 2.6204E-004
67 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT1 3.2621E-004
68 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT2 2.5968E-004
69 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT1 3.2279E-004
70 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT2 2.7417E-004
71 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT1 3.8025E-004
72 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 GYM_ZN_1_FLR_1_DAYLREFPT2 2.9249E-004
73 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT1 6.9940E-004
74 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT2 1.8902E-004
75 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT1 7.3251E-004
76 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT2 1.6840E-004
77 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT1 4.6127E-004
78 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT2 1.5697E-004
79 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT1 2.2096E-004
80 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 GYM_ZN_1_FLR_1_DAYLREFPT2 1.2726E-004
81 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.2920E-002
82 Clear Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT2 2.1416E-003
83 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT1 2.9132E-002
84 Clear Turbid Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.8768E-003
85 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.4059E-002
86 Intermediate Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.7146E-003
87 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT1 3.1013E-002
88 Overcast Sky 12/21 GYM_ZN_1_FLR_1_DAYLCTRL GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 GYM_ZN_1_FLR_1_DAYLREFPT2 1.4985E-003
89 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.0666E-003
90 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.6431E-002
91 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.4823E-003
92 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.4895E-002
93 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.0162E-003
94 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.4489E-002
95 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 3.1090E-003
96 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
97 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.0340E-003
98 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.4275E-003
99 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.0958E-003
100 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.6212E-003
101 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.5448E-004
102 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.4762E-003
103 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 3.6854E-004
104 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 5.7829E-004
105 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.6771E-002
106 Clear Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.5103E-002
107 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.1637E-002
108 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.6307E-002
109 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.9435E-002
110 Intermediate Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 9.3219E-003
111 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.0626E-002
112 Overcast Sky 12/21 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 3.7641E-003
113 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.7619E-003
114 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.8174E-003
115 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.9979E-003
116 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 3.0464E-003
117 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.0071E-003
118 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.0456E-003
119 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 9.8316E-004
120 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.0027E-003
121 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 9.9398E-002
122 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.4656E-002
123 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 0.1117
124 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.9039E-002
125 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.4545E-002
126 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.8329E-002
127 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 3.0175E-002
128 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.0159E-002
129 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.7607E-003
130 Clear Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.8113E-003
131 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.9966E-003
132 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 3.0397E-003
133 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.0059E-003
134 Intermediate Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.0409E-003
135 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 9.8314E-004
136 Overcast Sky 12/21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.0026E-003
137 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.4895E-003
138 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.4807E-002
139 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.9138E-003
140 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.2922E-002
141 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.3891E-003
142 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.3135E-002
143 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 3.2122E-003
144 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
145 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.8940E-004
146 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.6176E-004
147 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 6.1160E-004
148 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.1273E-004
149 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.0475E-004
150 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 1.9250E-004
151 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.3988E-004
152 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.7813E-004
153 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.4308E-003
154 Clear Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.2050E-003
155 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.7093E-003
156 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 3.2214E-003
157 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.5250E-003
158 Intermediate Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 2.2008E-003
159 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 6.9121E-003
160 Overcast Sky 12/21 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 3.3065E-003
161 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.0331E-004
162 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 5.1677E-004
163 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.2514E-004
164 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.3564E-004
165 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.6005E-004
166 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.6717E-004
167 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.0631E-004
168 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 7.1286E-004
169 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.7852E-002
170 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 7.4582E-003
171 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.3862E-002
172 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 5.6766E-003
173 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 1.4853E-002
174 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 4.5389E-003
175 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 2.5690E-002
176 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 7.0662E-003
177 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.7667E-004
178 Clear Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 6.1511E-004
179 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 4.8425E-004
180 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 5.1483E-004
181 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 5.0303E-004
182 Intermediate Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 5.2503E-004
183 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 7.4864E-004
184 Overcast Sky 12/21 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 7.6600E-004
185 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.0666E-003
186 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.6431E-002
187 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.4823E-003
188 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.4895E-002
189 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.0162E-003
190 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.4489E-002
191 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 3.1090E-003
192 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
193 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 8.5307E-004
194 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.2466E-003
195 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 9.0641E-004
196 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.4318E-003
197 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 6.4865E-004
198 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.3703E-003
199 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 3.2636E-004
200 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 5.3611E-004
201 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 3.1961E-002
202 Clear Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 9.9488E-003
203 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 3.5691E-002
204 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.0860E-002
205 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 2.1688E-002
206 Intermediate Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 6.6340E-003
207 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 8.0873E-003
208 Overcast Sky 12/21 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.8218E-003
209 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.6547E-003
210 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.7036E-003
211 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.8159E-003
212 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.8586E-003
213 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.3931E-003
214 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.4272E-003
215 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.4868E-004
216 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.6602E-004
217 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.7668E-002
218 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.7983E-002
219 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 8.8116E-002
220 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 3.1248E-002
221 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 6.1540E-002
222 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.9154E-002
223 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 2.5704E-002
224 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.0662E-003
225 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.5582E-003
226 Clear Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.5743E-003
227 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.7282E-003
228 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.7420E-003
229 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.3189E-003
230 Intermediate Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.3306E-003
231 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.0630E-004
232 Overcast Sky 12/21 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.1284E-004
233 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.4895E-003
234 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.4807E-002
235 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.9138E-003
236 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.2922E-002
237 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.3891E-003
238 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.3135E-002
239 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 3.2122E-003
240 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
241 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 8.0345E-004
242 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.7582E-004
243 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 6.2348E-004
244 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.2461E-004
245 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.1389E-004
246 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.0164E-004
247 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.4968E-004
248 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.8793E-004
249 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.5104E-003
250 Clear Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 4.2846E-003
251 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.7738E-003
252 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 3.2859E-003
253 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.5705E-003
254 Intermediate Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 2.2463E-003
255 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 6.9622E-003
256 Overcast Sky 12/21 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 3.3566E-003
257 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.1945E-004
258 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 5.3293E-004
259 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.4128E-004
260 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 4.5180E-004
261 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 4.7619E-004
262 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 4.8333E-004
263 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.2245E-004
264 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.2901E-004
265 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.7873E-002
266 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.4696E-003
267 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.3882E-002
268 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 5.6891E-003
269 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 1.4872E-002
270 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 4.5502E-003
271 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 2.5708E-002
272 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.0741E-003
273 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.9282E-004
274 Clear Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 6.3654E-004
275 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.0040E-004
276 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 5.3517E-004
277 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 5.1918E-004
278 Intermediate Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 5.4404E-004
279 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 7.6479E-004
280 Overcast Sky 12/21 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 7.8432E-004
281 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 5.0666E-003
282 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.6431E-002
283 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 4.4823E-003
284 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.4895E-002
285 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 4.0162E-003
286 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.4489E-002
287 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.1090E-003
288 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
289 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.6934E-004
290 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.2628E-003
291 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 9.2171E-004
292 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.4471E-003
293 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 6.6135E-004
294 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.3830E-003
295 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.3358E-004
296 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 5.4333E-004
297 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.2092E-002
298 Clear Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0080E-002
299 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.5815E-002
300 Clear Turbid Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0984E-002
301 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 2.1795E-002
302 Intermediate Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 6.7400E-003
303 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.1554E-003
304 Overcast Sky 12/21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.8899E-003
305 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.6709E-003
306 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.7264E-003
307 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.8322E-003
308 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.8806E-003
309 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.4093E-003
310 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.4479E-003
311 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.6486E-004
312 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 7.8436E-004
313 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.7757E-002
314 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.7999E-002
315 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.8214E-002
316 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 3.1264E-002
317 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 6.1568E-002
318 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.9170E-002
319 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 2.5708E-002
320 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 7.0823E-003
321 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.5743E-003
322 Clear Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.5903E-003
323 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.7442E-003
324 Clear Turbid Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.7580E-003
325 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.3349E-003
326 Intermediate Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.3466E-003
327 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.2239E-004
328 Overcast Sky 12/21 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 7.2893E-004
329 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.3678E-003
330 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 4.5301E-004
331 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0436E-003
332 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 3.5812E-004
333 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.2187E-004
334 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.7034E-004
335 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0124E-003
336 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 3.7472E-004
337 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 5.4897E-003
338 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.4808E-002
339 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 4.9139E-003
340 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.2922E-002
341 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 4.3893E-003
342 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.3136E-002
343 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.2123E-003
344 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0177E-002
345 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.1194E-002
346 Clear Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 6.2781E-003
347 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.4759E-003
348 Clear Turbid Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 4.7520E-003
349 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 5.7948E-003
350 Intermediate Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 2.8715E-003
351 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.7334E-003
352 Overcast Sky 12/21 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 4.2075E-003
353 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0476E-003
354 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.1921E-003
355 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.4559E-004
356 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 9.5698E-004
357 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.0880E-004
358 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 7.7947E-004
359 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0019E-003
360 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0711E-003
361 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 2.5298E-002
362 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.3187E-002
363 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.9396E-002
364 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 9.8884E-003
365 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.8041E-002
366 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 6.5335E-003
367 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 3.0309E-002
368 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 9.8951E-003
369 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0485E-003
370 Clear Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.1904E-003
371 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 8.4723E-004
372 Clear Turbid Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 9.5844E-004
373 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 7.1272E-004
374 Intermediate Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 7.9015E-004
375 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 1.0019E-003
376 Overcast Sky 12/21 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 1.0710E-003
377 Clear Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 2.2716E-004
378 Clear Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 2.6326E-004
379 Clear Turbid Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 1.8336E-004
380 Clear Turbid Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 2.1115E-004
381 Intermediate Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 1.5361E-004
382 Intermediate Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 1.7126E-004
383 Overcast Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 2.1634E-004
384 Overcast Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 2.3384E-004
385 Clear Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 2.7178E-002
386 Clear Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 1.5374E-002
387 Clear Turbid Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 2.0917E-002
388 Clear Turbid Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 1.1642E-002
389 Intermediate Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 1.9352E-002
390 Intermediate Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 7.9711E-003
391 Overcast Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 3.2157E-002
392 Overcast Sky 12/21 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 1.1856E-002
393 Clear Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT1 5.6741E-004
394 Clear Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT2 6.0735E-004
395 Clear Turbid Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT1 6.1351E-004
396 Clear Turbid Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT2 6.4928E-004
397 Intermediate Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT1 4.1271E-004
398 Intermediate Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT2 4.4141E-004
399 Overcast Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT1 2.0295E-004
400 Overcast Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 LOBBY_ZN_1_FLR_1_DAYLREFPT2 2.1668E-004
401 Clear Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT1 0.1054
402 Clear Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT2 4.9806E-002
403 Clear Turbid Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT1 0.1182
404 Clear Turbid Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT2 5.4639E-002
405 Intermediate Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT1 7.8731E-002
406 Intermediate Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT2 3.1980E-002
407 Overcast Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT1 3.2143E-002
408 Overcast Sky 12/21 LOBBY_ZN_1_FLR_1_DAYLCTRL LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 LOBBY_ZN_1_FLR_1_DAYLREFPT2 1.1907E-002
409 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.9578E-003
410 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.6215E-002
411 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.5256E-003
412 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.4111E-002
413 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.1643E-003
414 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.3370E-002
415 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 1.8702E-003
416 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.0449E-002
417 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.5777E-004
418 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 2.3936E-004
419 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.7330E-004
420 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 2.5763E-004
421 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 1.8691E-004
422 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.7264E-004
423 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT1 9.1918E-005
424 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 OFFICES_ZN_1_FLR_1_DAYLREFPT2 8.3722E-005
425 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT1 4.5720E-002
426 Clear Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT2 7.3878E-003
427 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT1 5.0181E-002
428 Clear Turbid Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT2 7.9265E-003
429 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT1 2.9039E-002
430 Intermediate Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT2 4.3738E-003
431 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT1 1.0478E-002
432 Overcast Sky 12/21 OFFICES_ZN_1_FLR_1_DAYLCTRL OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 OFFICES_ZN_1_FLR_1_DAYLREFPT2 1.7872E-003
433 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.2772E-002
434 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 4.2411E-003
435 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 9.6313E-003
436 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 3.2196E-003
437 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 6.6433E-003
438 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.9239E-003
439 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.0180E-002
440 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 2.8000E-003
441 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.9299E-004
442 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 4.2711E-004
443 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.7707E-004
444 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 4.2361E-004
445 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.5795E-004
446 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 2.9409E-004
447 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.2411E-004
448 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.6954E-004
449 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 2.7430E-003
450 Clear Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.5478E-002
451 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 2.4020E-003
452 Clear Turbid Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.3281E-002
453 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 2.1228E-003
454 Intermediate Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.2849E-002
455 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 1.6545E-003
456 Overcast Sky 12/21 CAFETERIA_ZN_1_FLR_1_DAYLCTRL CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 1.0223E-002
457 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 2.8013E-003
458 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 1.3597E-002
459 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 2.1420E-003
460 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 1.0244E-002
461 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 1.3173E-003
462 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 6.9652E-003
463 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 1.8503E-003
464 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 1.0393E-002
465 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 5.0775E-005
466 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 5.0775E-005
467 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 4.2949E-005
468 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 4.2949E-005
469 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 4.5493E-005
470 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 4.5493E-005
471 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 5.4255E-005
472 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 5.4255E-005
473 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 1.4138E-002
474 Clear Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 2.9675E-003
475 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 1.1990E-002
476 Clear Turbid Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 2.5734E-003
477 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 1.1951E-002
478 Intermediate Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 2.3431E-003
479 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 9.9387E-003
480 Overcast Sky 12/21 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 1.9035E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 Cooling 7398.60056 7398.60056 0.54787 0.54787 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 30.85500 8.23278E-003 99.00000 26.64155 0.18608 0.00000
2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 Heating 2480.56155 2480.56155 0.10389 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
3 MULT_CLASS_1_POD_1_ZN_1_FLR_1 Cooling 29122.29824 29122.29824 2.15659 2.15659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 477.00000 128.36383 0.89659 0.00000
4 MULT_CLASS_1_POD_1_ZN_1_FLR_1 Heating 6987.46151 6987.46151 0.29500 0.89659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 477.00000 128.36383 0.89659 0.00000
5 CORRIDOR_POD_1_ZN_1_FLR_1 Cooling 5999.33798 5999.33798 0.42612 0.42612 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.99583 8.22354E-003 192.00000 10.33400 5.85216E-002 0.00000
6 CORRIDOR_POD_1_ZN_1_FLR_1 Heating 1955.68353 1955.68353 8.38296E-002 8.38296E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 192.00000 10.33400 5.85216E-002 0.00000
7 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 Cooling 6792.66592 6792.66592 0.50300 0.50300 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 99.00000 26.64155 0.18608 0.00000
8 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 Heating 2436.93764 2436.93764 0.10211 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
9 MULT_CLASS_2_POD_1_ZN_1_FLR_1 Cooling 24828.69880 24828.69880 1.83865 1.83865 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30000 8.23349E-003 477.00000 128.36383 0.89659 0.00000
10 MULT_CLASS_2_POD_1_ZN_1_FLR_1 Heating 6666.73527 6666.73527 0.28175 0.89659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 477.00000 128.36383 0.89659 0.00000
11 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 Cooling 7352.23876 7352.23876 0.54444 0.54444 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 30.85500 8.23278E-003 99.00000 26.64155 0.18608 0.00000
12 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 Heating 2448.76222 2448.76222 0.10260 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
13 MULT_CLASS_1_POD_2_ZN_1_FLR_1 Cooling 28856.13263 28856.13263 2.13688 2.13688 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 477.00000 128.36383 0.89659 0.00000
14 MULT_CLASS_1_POD_2_ZN_1_FLR_1 Heating 6728.40582 6728.40582 0.28430 0.89659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 477.00000 128.36383 0.89659 0.00000
15 CORRIDOR_POD_2_ZN_1_FLR_1 Cooling 5994.08917 5994.08917 0.42573 0.42573 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.99583 8.22354E-003 192.00000 10.33400 5.85216E-002 0.00000
16 CORRIDOR_POD_2_ZN_1_FLR_1 Heating 1939.56474 1939.56474 8.31446E-002 8.31446E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 192.00000 10.33400 5.85216E-002 0.00000
17 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 Cooling 6795.12996 6795.12996 0.50319 0.50319 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 99.00000 26.64155 0.18608 0.00000
18 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 Heating 2439.60193 2439.60193 0.10222 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
19 MULT_CLASS_2_POD_2_ZN_1_FLR_1 Cooling 24838.73823 24838.73823 1.83939 1.83939 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30000 8.23349E-003 477.00000 128.36383 0.89659 0.00000
20 MULT_CLASS_2_POD_2_ZN_1_FLR_1 Heating 6680.68970 6680.68970 0.28233 0.89659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 477.00000 128.36383 0.89659 0.00000
21 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 Cooling 7357.47568 7357.47568 0.54483 0.54483 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 30.85500 8.23278E-003 99.00000 26.64155 0.18608 0.00000
22 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 Heating 2452.38604 2452.38604 0.10274 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
23 MULT_CLASS_1_POD_3_ZN_1_FLR_1 Cooling 28982.44717 28982.44717 2.14623 2.14623 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 477.00000 128.36383 0.89659 0.00000
24 MULT_CLASS_1_POD_3_ZN_1_FLR_1 Heating 6784.17758 6784.17758 0.28661 0.89659 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 477.00000 128.36383 0.89659 0.00000
25 CORRIDOR_POD_3_ZN_1_FLR_1 Cooling 6046.78430 6046.78430 0.42965 0.42965 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.99583 8.22354E-003 192.00000 10.33400 5.85216E-002 0.00000
26 CORRIDOR_POD_3_ZN_1_FLR_1 Heating 1945.27816 1945.27816 8.33845E-002 8.33845E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 192.00000 10.33400 5.85216E-002 0.00000
27 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 Cooling 6836.45686 6836.45686 0.50625 0.50625 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 99.00000 26.64155 0.18608 0.00000
28 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 Heating 2469.51205 2469.51205 0.10344 0.18608 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 99.00000 26.64155 0.18608 0.00000
29 MULT_CLASS_2_POD_3_ZN_1_FLR_1 Cooling 16664.11958 16664.11958 1.23403 1.23403 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 31.30000 8.23349E-003 315.00000 84.76857 0.59209 0.00000
30 MULT_CLASS_2_POD_3_ZN_1_FLR_1 Heating 4606.59705 4606.59705 0.19459 0.59209 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 315.00000 84.76857 0.59209 0.00000
31 COMPUTER_CLASS_ZN_1_FLR_1 Cooling 9263.51286 9263.51286 0.68599 0.68599 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30000 8.23349E-003 162.00000 43.59526 0.30450 0.00000
32 COMPUTER_CLASS_ZN_1_FLR_1 Heating 2005.62848 2005.62848 8.51378E-002 0.30450 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 162.00000 43.59526 0.30450 0.00000
33 MAIN_CORRIDOR_ZN_1_FLR_1 Cooling 12761.59833 12761.59833 0.89419 0.89419 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.99583 8.22354E-003 546.00000 29.38800 0.16642 0.00000
34 MAIN_CORRIDOR_ZN_1_FLR_1 Heating 3813.63344 3813.63344 0.16280 0.16642 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 546.00000 29.38800 0.16642 0.00000
35 LOBBY_ZN_1_FLR_1 Cooling 6616.74347 6616.74347 0.48988 0.48988 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 171.00000 18.40800 9.55546E-002 0.00000
36 LOBBY_ZN_1_FLR_1 Heating 3198.71228 3198.71228 0.13436 0.13436 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 171.00000 18.40800 9.55546E-002 0.00000
37 MECH_ZN_1_FLR_1 Cooling 5853.72977 5853.72977 0.43333 0.43333 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 252.00000 4.06900 0.00000 0.00000
38 MECH_ZN_1_FLR_1 Heating 71.50388 71.50388 3.12293E-003 3.12293E-003 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 252.00000 4.06900 0.00000 0.00000
39 BATH_ZN_1_FLR_1 Cooling 6151.63472 6151.63472 0.45541 0.45541 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 30.29133 8.23188E-003 190.00000 10.22700 0.00000 0.00000
40 BATH_ZN_1_FLR_1 Heating 1800.53700 1800.53700 7.86382E-002 7.86382E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 190.00000 10.22700 0.00000 0.00000
41 OFFICES_ZN_1_FLR_1 Cooling 17551.51989 17551.51989 1.29934 1.29934 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 441.00000 23.73648 0.19042 0.00000
42 OFFICES_ZN_1_FLR_1 Heating 6307.05419 6307.05419 0.26569 0.26569 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 441.00000 23.73648 0.19042 0.00000
43 GYM_ZN_1_FLR_1 Cooling 18997.97497 18997.97497 1.40699 1.40699 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 29.54967 8.23070E-003 357.00000 115.31008 0.54407 0.00000
44 GYM_ZN_1_FLR_1 Heating 2879.78296 2879.78296 0.12577 0.54407 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 357.00000 115.31008 0.54407 0.00000
45 KITCHEN_ZN_1_FLR_1 Cooling 18345.45236 18345.45236 1.35986 1.35986 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 30.49900 8.23222E-003 168.00000 26.99300 0.25481 0.00000
46 KITCHEN_ZN_1_FLR_1 Heating 0.00000 0.00000 0.00000 0.25481   00:10:00 3.80000 5.05843E-003 168.00000 26.99300 0.25481 0.00000
47 CAFETERIA_ZN_1_FLR_1 Cooling 29659.48121 29659.48121 2.19893 2.19893 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.85500 8.23278E-003 315.00000 339.07427 1.48823 0.00000
48 CAFETERIA_ZN_1_FLR_1 Heating 3694.82826 3694.82826 0.16137 1.48823 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:30:00 3.80000 5.05843E-003 315.00000 339.07427 1.48823 0.00000
49 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 Cooling 19975.83743 19975.83743 1.43997 1.43997 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.99583 8.22354E-003 399.00000 42.95403 0.34458 0.00000
50 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 Heating 5246.81121 5246.81121 0.22155 0.34458 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 3.80000 5.05843E-003 399.00000 42.95403 0.34458 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_POD_1 Cooling Sensible 104073.84 5.40983 5.40983 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_POD_1 Heating Sensible 24041.81 2.24949 2.24949 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00
3 VAV_POD_2 Cooling Sensible 103728.07 5.38382 5.38382 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_POD_2 Heating Sensible 24034.84 2.24884 2.24884 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00
5 VAV_POD_3 Cooling Sensible 91517.68 4.79650 4.79650 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_POD_3 Heating Sensible 20785.22 1.94478 1.94478 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00
7 VAV_OTHER Cooling Sensible 90364.79 5.59822 5.59822 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
8 VAV_OTHER Heating Sensible 13864.02 1.29720 1.29720 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00
9 PSZ-AC_2:5 Cooling Sensible 23313.13 1.40699 1.40699 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 PSZ-AC_2:5 Heating Sensible 23388.51 0.54407 0.54407 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 PSZ-AC_1:6 Cooling Sensible 19984.65 1.35986 1.35986 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 PSZ-AC_1:6 Heating Sensible 10954.00 0.25481 0.25481 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 PSZ-AC_2:7 Cooling Sensible 41608.84 2.19893 2.19893 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 PSZ-AC_2:7 Heating Sensible 63976.17 1.48823 1.48823 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.54787
2 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13769
3 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67700
4 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37091
5 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67700
6 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76703E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.37460E-005
9 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37091
10 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6143.49798
13 Coil:Heating:Water CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.37460E-005
14 Coil:Heating:Water CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 132.71292
15 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.15659
16 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16854
17 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67700
18 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.46001
19 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67700
20 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26058E-003
22 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.87277E-004
23 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.46001
24 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21406.96346
27 Coil:Heating:Water MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.87277E-004
28 Coil:Heating:Water MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 453.14310
29 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.42612
30 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34334
31 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67700
32 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28848
33 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91558
34 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10968E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.20452E-005
37 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28848
38 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4806.02345
41 Coil:Heating:Water CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.20452E-005
42 Coil:Heating:Water CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.92891
43 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50300
44 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14997
45 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67700
46 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34053
47 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67700
48 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.54043E-003
50 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.07398E-005
51 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34053
52 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5799.87539
55 Coil:Heating:Water CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.07398E-005
56 Coil:Heating:Water CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 125.92829
57 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.83865
58 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19769
59 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.67700
60 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.24477
61 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67700
62 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.92731E-003
64 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.65872E-004
65 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.24477
66 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18960.17924
69 Coil:Heating:Water MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.65872E-004
70 Coil:Heating:Water MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 403.77692
71 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.54444
72 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13856
73 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68000
74 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37022
75 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68000
76 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.74969E-003
78 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.34079E-005
79 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37022
80 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6104.85506
83 Coil:Heating:Water CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.34079E-005
84 Coil:Heating:Water CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 131.77343
85 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13688
86 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17010
87 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68000
88 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.45308
89 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68000
90 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.23992E-003
92 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.84410E-004
93 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.45308
94 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21079.21878
97 Coil:Heating:Water MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.84410E-004
98 Coil:Heating:Water MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 445.52002
99 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.42573
100 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34366
101 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68000
102 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28949
103 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91642
104 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10867E-003
106 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.19917E-005
107 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28949
108 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4799.91370
111 Coil:Heating:Water CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.19917E-005
112 Coil:Heating:Water CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.70760
113 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50319
114 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14992
115 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68000
116 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34217
117 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68000
118 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.54135E-003
120 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.09043E-005
121 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34217
122 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5818.66888
125 Coil:Heating:Water CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.09043E-005
126 Coil:Heating:Water CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 126.30009
127 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.83939
128 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19761
129 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68000
130 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25079
131 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68000
132 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.92809E-003
134 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66514E-004
135 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25079
136 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19033.61289
139 Coil:Heating:Water MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66514E-004
140 Coil:Heating:Water MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 405.27782
141 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.54483
142 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13846
143 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65800
144 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.35850
145 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65800
146 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.75165E-003
148 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.24269E-005
149 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35850
150 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5992.71570
153 Coil:Heating:Water CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.24269E-005
154 Coil:Heating:Water CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 129.67023
155 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14623
156 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16935
157 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65800
158 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.41222
159 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65800
160 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.24972E-003
162 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.81368E-004
163 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.41222
164 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20731.52770
167 Coil:Heating:Water MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.81368E-004
168 Coil:Heating:Water MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 438.92825
169 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.42965
170 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34052
171 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65800
172 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28271
173 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90804
174 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
175 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11889E-003
176 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.14555E-005
177 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28271
178 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
179 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
180 Coil:Heating:Water CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4738.61892
181 Coil:Heating:Water CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.14555E-005
182 Coil:Heating:Water CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 102.58412
183 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50625
184 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14901
185 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65800
186 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33311
187 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65800
188 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
189 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55680E-003
190 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.03836E-005
191 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33311
192 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
193 AirTerminal:SingleDuct:VAV:Reheat CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
194 Coil:Heating:Water CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5759.15924
195 Coil:Heating:Water CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.03836E-005
196 Coil:Heating:Water CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 125.39565
197 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23403
198 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19451
199 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65800
200 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.81199
201 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65800
202 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
203 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.95878E-003
204 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.10458E-004
205 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.81199
206 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
207 AirTerminal:SingleDuct:VAV:Reheat MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
208 Coil:Heating:Water MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12626.07276
209 Coil:Heating:Water MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.10458E-004
210 Coil:Heating:Water MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 269.79612
211 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.68599
212 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17995
213 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.74400
214 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.51038
215 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74400
216 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
217 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11725E-003
218 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.16407E-005
219 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.51038
220 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
221 AirTerminal:SingleDuct:VAV:Reheat COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
222 Coil:Heating:Water COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7045.91290
223 Coil:Heating:Water COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.16407E-005
224 Coil:Heating:Water COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 147.82772
225 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.89419
226 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.46529
227 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
228 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27899
229 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
230 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
231 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.18853E-004
232 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.74774E-005
233 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27899
234 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
235 AirTerminal:SingleDuct:VAV:Reheat MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
236 Coil:Heating:Water MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6570.01723
237 Coil:Heating:Water MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.74774E-005
238 Coil:Heating:Water MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 153.63979
239 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.48988
240 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26599
241 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32700
242 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16019
243 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.70931
244 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
245 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.43238E-003
246 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.18257E-005
247 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.16019
248 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
249 AirTerminal:SingleDuct:VAV:Reheat LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
250 Coil:Heating:Water LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4780.93312
251 Coil:Heating:Water LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.18257E-005
252 Coil:Heating:Water LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 120.98335
253 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.43333
254 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.44314
255 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
256 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66655E-002
257 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
258 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
259 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.59777E-004
260 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.07801E-006
261 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66655E-002
262 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
263 AirTerminal:SingleDuct:VAV:Reheat MECH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
264 Coil:Heating:Water MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 923.36652
265 Coil:Heating:Water MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.07801E-006
266 Coil:Heating:Water MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.75839
267 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.45541
268 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.62179
269 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
270 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.10812E-002
271 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84777
272 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
273 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19844E-003
274 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.36234E-005
275 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.10812E-002
276 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
277 AirTerminal:SingleDuct:VAV:Reheat BATH_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
278 Coil:Heating:Water BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2700.30052
279 Coil:Heating:Water BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.36234E-005
280 Coil:Heating:Water BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 68.15381
281 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29934
282 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25863
283 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24600
284 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31964
285 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68967
286 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
287 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.47317E-003
288 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.27959E-005
289 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31964
290 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
291 AirTerminal:SingleDuct:VAV:Reheat OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
292 Coil:Heating:Water OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9464.07964
293 Coil:Heating:Water OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.27959E-005
294 Coil:Heating:Water OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 238.74669
295 AirTerminal:SingleDuct:ConstantVolume:NoReheat GYM_ZN_1_FLR_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.40699
296 AirTerminal:SingleDuct:ConstantVolume:NoReheat KITCHEN_ZN_1_FLR_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.35986
297 AirTerminal:SingleDuct:ConstantVolume:NoReheat CAFETERIA_ZN_1_FLR_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 2.19893
298 Fan:ZoneExhaust LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
299 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.43997
300 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21114
301 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.40100
302 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.57743
303 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56304
304 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
305 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.80448E-003
306 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.57930E-005
307 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57743
308 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
309 AirTerminal:SingleDuct:VAV:Reheat LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
310 Coil:Heating:Water LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10949.72382
311 Coil:Heating:Water LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.57930E-005
312 Coil:Heating:Water LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 242.86315
313 AirLoopHVAC VAV_POD_1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.70470
314 AirLoopHVAC VAV_POD_1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.70470
315 AirLoopHVAC VAV_POD_1 Sum of Air Terminal Maximum Flow Rates [m3/s] 5.47224
316 AirLoopHVAC VAV_POD_1 Adjusted Heating Design Air Flow Rate [m3/s] 3.70470
317 AirLoopHVAC VAV_POD_1 Adjusted Cooling Design Air Flow Rate [m3/s] 5.40983
318 AirLoopHVAC VAV_POD_1 Adjusted Main Design Air Flow Rate [m3/s] 5.40983
319 AirLoopHVAC VAV_POD_1 User Heating Air Flow Ratio [] 0.30000
320 AirLoopHVAC VAV_POD_1 Calculated Heating Air Flow Ratio [] 0.68481
321 AirLoopHVAC VAV_POD_2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.70575
322 AirLoopHVAC VAV_POD_2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.70575
323 AirLoopHVAC VAV_POD_2 Sum of Air Terminal Maximum Flow Rates [m3/s] 5.44963
324 AirLoopHVAC VAV_POD_2 Adjusted Heating Design Air Flow Rate [m3/s] 3.70575
325 AirLoopHVAC VAV_POD_2 Adjusted Cooling Design Air Flow Rate [m3/s] 5.38382
326 AirLoopHVAC VAV_POD_2 Adjusted Main Design Air Flow Rate [m3/s] 5.38382
327 AirLoopHVAC VAV_POD_2 User Heating Air Flow Ratio [] 0.30000
328 AirLoopHVAC VAV_POD_2 Calculated Heating Air Flow Ratio [] 0.68831
329 AirLoopHVAC VAV_POD_3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.19853
330 AirLoopHVAC VAV_POD_3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.19853
331 AirLoopHVAC VAV_POD_3 Sum of Air Terminal Maximum Flow Rates [m3/s] 4.86100
332 AirLoopHVAC VAV_POD_3 Adjusted Heating Design Air Flow Rate [m3/s] 3.19853
333 AirLoopHVAC VAV_POD_3 Adjusted Cooling Design Air Flow Rate [m3/s] 4.79650
334 AirLoopHVAC VAV_POD_3 Adjusted Main Design Air Flow Rate [m3/s] 4.79650
335 AirLoopHVAC VAV_POD_3 User Heating Air Flow Ratio [] 0.30000
336 AirLoopHVAC VAV_POD_3 Calculated Heating Air Flow Ratio [] 0.66685
337 AirLoopHVAC VAV_OTHER Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.01643
338 AirLoopHVAC VAV_OTHER Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.02436
339 AirLoopHVAC VAV_OTHER Sum of Air Terminal Maximum Flow Rates [m3/s] 5.69809
340 AirLoopHVAC VAV_OTHER Adjusted Heating Design Air Flow Rate [m3/s] 2.02436
341 AirLoopHVAC VAV_OTHER Adjusted Cooling Design Air Flow Rate [m3/s] 5.59822
342 AirLoopHVAC VAV_OTHER Adjusted Main Design Air Flow Rate [m3/s] 5.59822
343 AirLoopHVAC VAV_OTHER User Heating Air Flow Ratio [] 0.30000
344 AirLoopHVAC VAV_OTHER Calculated Heating Air Flow Ratio [] 0.36161
345 AirLoopHVAC PSZ-AC_2:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.40699
346 AirLoopHVAC PSZ-AC_2:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.40699
347 AirLoopHVAC PSZ-AC_2:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.40699
348 AirLoopHVAC PSZ-AC_2:5 Adjusted Heating Design Air Flow Rate [m3/s] 1.40699
349 AirLoopHVAC PSZ-AC_2:5 Adjusted Cooling Design Air Flow Rate [m3/s] 1.40699
350 AirLoopHVAC PSZ-AC_2:5 Adjusted Main Design Air Flow Rate [m3/s] 1.40699
351 AirLoopHVAC PSZ-AC_2:5 User Heating Air Flow Ratio [] 1.00000
352 AirLoopHVAC PSZ-AC_2:5 Calculated Heating Air Flow Ratio [] 1.00000
353 AirLoopHVAC PSZ-AC_1:6 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.35986
354 AirLoopHVAC PSZ-AC_1:6 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.35986
355 AirLoopHVAC PSZ-AC_1:6 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.35986
356 AirLoopHVAC PSZ-AC_1:6 Adjusted Heating Design Air Flow Rate [m3/s] 1.35986
357 AirLoopHVAC PSZ-AC_1:6 Adjusted Cooling Design Air Flow Rate [m3/s] 1.35986
358 AirLoopHVAC PSZ-AC_1:6 Adjusted Main Design Air Flow Rate [m3/s] 1.35986
359 AirLoopHVAC PSZ-AC_1:6 User Heating Air Flow Ratio [] 1.00000
360 AirLoopHVAC PSZ-AC_1:6 Calculated Heating Air Flow Ratio [] 1.00000
361 AirLoopHVAC PSZ-AC_2:7 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.19893
362 AirLoopHVAC PSZ-AC_2:7 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.19893
363 AirLoopHVAC PSZ-AC_2:7 Sum of Air Terminal Maximum Flow Rates [m3/s] 2.19893
364 AirLoopHVAC PSZ-AC_2:7 Adjusted Heating Design Air Flow Rate [m3/s] 2.19893
365 AirLoopHVAC PSZ-AC_2:7 Adjusted Cooling Design Air Flow Rate [m3/s] 2.19893
366 AirLoopHVAC PSZ-AC_2:7 Adjusted Main Design Air Flow Rate [m3/s] 2.19893
367 AirLoopHVAC PSZ-AC_2:7 User Heating Air Flow Ratio [] 1.00000
368 AirLoopHVAC PSZ-AC_2:7 Calculated Heating Air Flow Ratio [] 1.00000
369 AirLoopHVAC VAV_POD_1 Design Supply Air Flow Rate [m3/s] 5.40983
370 AirLoopHVAC VAV_POD_2 Design Supply Air Flow Rate [m3/s] 5.38382
371 AirLoopHVAC VAV_POD_3 Design Supply Air Flow Rate [m3/s] 4.79650
372 AirLoopHVAC VAV_OTHER Design Supply Air Flow Rate [m3/s] 5.59822
373 AirLoopHVAC PSZ-AC_2:5 Design Supply Air Flow Rate [m3/s] 1.40699
374 AirLoopHVAC PSZ-AC_1:6 Design Supply Air Flow Rate [m3/s] 1.35986
375 AirLoopHVAC PSZ-AC_2:7 Design Supply Air Flow Rate [m3/s] 2.19893
376 Controller:OutdoorAir VAV_POD_1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.40983
377 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.40983
378 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 116206.71178
379 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74932
380 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.80310
381 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 38731.69704
382 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74932
383 Coil:Heating:Water VAV_POD_1 HEATING COIL Design Size Rated Capacity [W] 17345.56958
384 Coil:Heating:Water VAV_POD_1 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51747E-004
385 Coil:Heating:Water VAV_POD_1 HEATING COIL Design Size U-Factor Times Area Value [W/K] 298.18255
386 Fan:VariableVolume VAV_POD_1 FAN Design Size Maximum Flow Rate [m3/s] 5.40983
387 Controller:WaterCoil VAV_POD_1_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51747E-004
388 Controller:OutdoorAir VAV_POD_2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.38382
389 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.38382
390 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 115735.82267
391 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74911
392 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.79443
393 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 38574.74970
394 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74911
395 Coil:Heating:Water VAV_POD_2 HEATING COIL Design Size Rated Capacity [W] 17262.18602
396 Coil:Heating:Water VAV_POD_2 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51017E-004
397 Coil:Heating:Water VAV_POD_2 HEATING COIL Design Size U-Factor Times Area Value [W/K] 296.74913
398 Fan:VariableVolume VAV_POD_2 FAN Design Size Maximum Flow Rate [m3/s] 5.38382
399 Controller:WaterCoil VAV_POD_2_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51017E-004
400 Controller:OutdoorAir VAV_POD_3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.79650
401 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.79650
402 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 102597.88277
403 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.75052
404 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.59867
405 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 34195.87433
406 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.75052
407 Coil:Heating:Water VAV_POD_3 HEATING COIL Design Size Rated Capacity [W] 15379.05303
408 Coil:Heating:Water VAV_POD_3 HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.34543E-004
409 Coil:Heating:Water VAV_POD_3 HEATING COIL Design Size U-Factor Times Area Value [W/K] 264.37675
410 Fan:VariableVolume VAV_POD_3 FAN Design Size Maximum Flow Rate [m3/s] 4.79650
411 Controller:WaterCoil VAV_POD_3_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.34543E-004
412 Controller:OutdoorAir VAV_OTHER_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.59822
413 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.59822
414 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 107343.15694
415 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.79340
416 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.86589
417 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 35777.47421
418 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.79340
419 Coil:Heating:Water VAV_OTHER HEATING COIL Design Size Rated Capacity [W] 17949.61535
420 Coil:Heating:Water VAV_OTHER HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.57031E-004
421 Coil:Heating:Water VAV_OTHER HEATING COIL Design Size U-Factor Times Area Value [W/K] 308.56652
422 Fan:VariableVolume VAV_OTHER FAN Design Size Maximum Flow Rate [m3/s] 5.59822
423 Controller:WaterCoil VAV_OTHER_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.57031E-004
424 Controller:OutdoorAir PSZ-AC_2:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.40699
425 Controller:OutdoorAir PSZ-AC_2:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.54407
426 Fan:SystemModel PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.40699
427 Fan:SystemModel PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1557.75903
428 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.40699
429 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.40699
430 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.40699
431 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.92861
432 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.40699
433 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.70349
434 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.93799
435 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 27920.64000
436 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 13960.32000
437 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.77969
438 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.77969
439 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 27920.64000
440 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 42858.58882
441 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
442 AirLoopHVAC:UnitarySystem PSZ-AC_2:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
443 Coil:Heating:Fuel PSZ-AC_2:5 HEATING COIL Design Size Nominal Capacity [W] 42858.58882
444 Controller:OutdoorAir PSZ-AC_1:6_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.35986
445 Controller:OutdoorAir PSZ-AC_1:6_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.25481
446 Fan:SystemModel PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.35986
447 Fan:SystemModel PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1505.58485
448 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.35986
449 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.35986
450 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.35986
451 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.89751
452 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.35986
453 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.67993
454 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.90657
455 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 27792.32000
456 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 13896.16000
457 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.76778
458 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.76778
459 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 27792.32000
460 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 63444.76469
461 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
462 AirLoopHVAC:UnitarySystem PSZ-AC_1:6_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
463 Coil:Heating:Fuel PSZ-AC_1:6 HEATING COIL Design Size Nominal Capacity [W] 63444.76469
464 Controller:OutdoorAir PSZ-AC_2:7_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.19893
465 Controller:OutdoorAir PSZ-AC_2:7_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.48823
466 Fan:SystemModel PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 2.19893
467 Fan:SystemModel PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2352.95968
468 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 2.19893
469 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 2.19893
470 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 2.19893
471 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.45129
472 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 2.19893
473 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.09947
474 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.46595
475 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 47552.11000
476 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 23776.05500
477 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.74643
478 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.74643
479 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 47552.11000
480 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 80011.93633
481 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
482 AirLoopHVAC:UnitarySystem PSZ-AC_2:7_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
483 Coil:Heating:Fuel PSZ-AC_2:7 HEATING COIL Design Size Nominal Capacity [W] 80011.93633
484 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.39857E-003
485 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.28783
486 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.39857E-003
487 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 722.34494
488 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
489 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 274171.66087
490 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 274171.66000
491 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.39857E-003
492 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 1.05414E-004
493 PlantLoop SWHSYS1 Plant Loop Volume [m3] 1.26497E-002
494 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 1.05414E-004
495 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 13.46550
496 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 1.05414E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 5823.06
2 Coil:Heating:Water MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 20292.40
3 Coil:Heating:Water CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 4555.33
4 Coil:Heating:Water CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 5497.23
5 Coil:Heating:Water MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL 17972.48
6 Coil:Heating:Water CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 5786.46
7 Coil:Heating:Water MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 19983.28
8 Coil:Heating:Water CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 4549.55
9 Coil:Heating:Water CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 5515.05
10 Coil:Heating:Water MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL 18042.10
11 Coil:Heating:Water CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 5680.10
12 Coil:Heating:Water MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 19652.12
13 Coil:Heating:Water CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 4491.41
14 Coil:Heating:Water CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 5458.57
15 Coil:Heating:Water MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL 11968.14
16 Coil:Heating:Water COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL 6679.79
17 Coil:Heating:Water MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL 6224.76
18 Coil:Heating:Water LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL 4527.92
19 Coil:Heating:Water MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL 875.51
20 Coil:Heating:Water BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL 2557.42
21 Coil:Heating:Water OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL 8963.34
22 Coil:Heating:Water LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL 10377.35
23 Coil:Heating:Water VAV_POD_1 HEATING COIL 14557.73
24 Coil:Heating:Water VAV_POD_2 HEATING COIL 14487.75
25 Coil:Heating:Water VAV_POD_3 HEATING COIL 12907.28
26 Coil:Heating:Water VAV_OTHER HEATING COIL 15064.70


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed VAV_POD_1 COOLING COIL N/A N/A 112220.08 382910.82 10.65 2.95 3.12 3.10 3.23 10.05 10.63 10.57 11.03 6.1407 4.8858 3.2791 1.3409
2 Coil:Cooling:DX:TwoSpeed VAV_POD_2 COOLING COIL N/A N/A 111768.51 381369.98 10.66 2.95 3.12 3.10 3.23 10.05 10.63 10.57 11.03 6.1112 4.8627 3.2630 1.3348
3 Coil:Cooling:DX:TwoSpeed VAV_POD_3 COOLING COIL N/A N/A 99062.50 338015.26 10.65 2.94 3.11 3.10 3.23 10.05 10.62 10.56 11.03 5.4445 4.3309 2.9063 1.1881
4 Coil:Cooling:DX:TwoSpeed VAV_OTHER COOLING COIL N/A N/A 103195.83 352118.80 10.43 2.89 3.05 3.03 3.19 9.88 10.39 10.33 10.90 6.3546 5.0776 3.4094 1.3397


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:5 COOLING COIL 26815.1     11.51 11.51  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:6 COOLING COIL 26723.3     11.57 11.57  
3 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:7 COOLING COIL 45821.8     11.52 11.52  


Zone Surfaces

Zone Name # Surfaces
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 11
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 12
3 CORRIDOR_POD_1_ZN_1_FLR_1 10
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 11
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 12
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 11
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 12
8 CORRIDOR_POD_2_ZN_1_FLR_1 10
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 11
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 12
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 11
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 12
13 CORRIDOR_POD_3_ZN_1_FLR_1 11
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 11
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 12
16 COMPUTER_CLASS_ZN_1_FLR_1 10
17 MAIN_CORRIDOR_ZN_1_FLR_1 15
18 LOBBY_ZN_1_FLR_1 11
19 MECH_ZN_1_FLR_1 10
20 BATH_ZN_1_FLR_1 9
21 OFFICES_ZN_1_FLR_1 12
22 GYM_ZN_1_FLR_1 19
23 KITCHEN_ZN_1_FLR_1 8
24 CAFETERIA_ZN_1_FLR_1 12
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 13


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.65 44.00 26.65 180.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 Window CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 180.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 Window CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.46 13.46 13.46 180.00 90.00 8.46 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR Door CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
6 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
7 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
10 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
11 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
12 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   133.90 212.00 133.90 180.00 90.00 53.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
13 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 Window MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
14 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 Window MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
15 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 Window MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 Door MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 Door MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 LOBBY_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 0.00 90.00 53.00 4.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
21 MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   477.00 477.00 477.00 270.00 180.00 9.00 53.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
22 MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   477.00 477.00 477.00 90.00 0.00 9.00 53.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
23 MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   954.00 954.00 954.00 0.00 90.00 954.00 1.00 0.00 MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
24 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
25 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 180.00 90.00 53.00 4.00 0.00 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 90.00 90.00 3.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 0.00 90.00 53.00 4.00 0.00 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   7.80 12.00 7.80 270.00 90.00 3.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
30 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 Window CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 4.20 4.20 4.20 270.00 90.00 2.90 1.45 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
31 CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.980E-002 1.971E-002   192.00 192.00 192.00 270.00 180.00 3.00 64.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
32 CORRIDOR_POD_1_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   192.00 192.00 192.00 90.00 0.00 3.00 64.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
33 CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   384.00 384.00 384.00 0.00 90.00 384.00 1.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
34 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
36 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.65 44.00 26.65 0.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
37 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 Window CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 0.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
38 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 Window CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.46 13.46 13.46 0.00 90.00 8.46 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.60 0.40 4
39 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 Door CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
40 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
43 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
44 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
45 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 180.00 90.00 53.00 4.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   133.90 212.00 133.90 0.00 90.00 53.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
48 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 Window MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
49 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 Window MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
50 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 Window MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
51 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 Door MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
52 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 Door MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
53 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   477.00 477.00 477.00 270.00 180.00 9.00 53.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
55 MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   477.00 477.00 477.00 90.00 0.00 9.00 53.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
56 MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   954.00 954.00 954.00 0.00 90.00 954.00 1.00 0.00 MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
57 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.65 44.00 26.65 180.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
58 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 Window CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 180.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
59 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 Window CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.46 13.46 13.46 180.00 90.00 8.46 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.62 0.38 4
60 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR Door CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
61 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
62 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
67 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   133.90 212.00 133.90 180.00 90.00 53.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
69 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 Window MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
70 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 Window MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
71 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 Window MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
72 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 Door MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
73 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 Door MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
74 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 0.00 90.00 53.00 4.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   477.00 477.00 477.00 270.00 180.00 9.00 53.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
78 MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   477.00 477.00 477.00 90.00 0.00 9.00 53.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
79 MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   954.00 954.00 954.00 0.00 90.00 954.00 1.00 0.00 MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
80 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 180.00 90.00 53.00 4.00 0.00 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
82 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 90.00 90.00 3.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
83 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 0.00 90.00 53.00 4.00 0.00 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
84 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
85 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   7.80 12.00 7.80 270.00 90.00 3.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 Window CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 4.20 4.20 4.20 270.00 90.00 2.90 1.45 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.980E-002 1.971E-002   192.00 192.00 192.00 270.00 180.00 3.00 64.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
88 CORRIDOR_POD_2_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   192.00 192.00 192.00 90.00 0.00 3.00 64.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
89 CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   384.00 384.00 384.00 0.00 90.00 384.00 1.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
90 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.65 44.00 26.65 0.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
93 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 Window CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 0.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.62 0.38 4
94 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 Window CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.46 13.46 13.46 0.00 90.00 8.46 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.60 0.40 4
95 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR Door CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.62 0.38 4
96 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
99 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
100 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
101 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 180.00 90.00 53.00 4.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
102 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
103 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   133.90 212.00 133.90 0.00 90.00 53.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
104 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 Window MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
105 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 Window MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
106 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 Window MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 0.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
107 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 Door MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
108 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 Door MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
109 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   477.00 477.00 477.00 270.00 180.00 9.00 53.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
111 MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   477.00 477.00 477.00 90.00 0.00 9.00 53.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
112 MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   954.00 954.00 954.00 0.00 90.00 954.00 1.00 0.00 MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
113 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.65 44.00 26.65 180.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
114 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 Window CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 180.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
115 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 Window CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.46 13.46 13.46 180.00 90.00 8.46 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
116 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR Door CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
117 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
118 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
119 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
122 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
123 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
124 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   133.90 212.00 133.90 180.00 90.00 53.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
125 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 Window MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.74 24.74 24.74 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
126 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 Window MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
127 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 Window MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.73 24.73 24.73 180.00 90.00 16.82 1.47 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
128 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 Door MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
129 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 Door MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
130 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 0.00 90.00 53.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   477.00 477.00 477.00 270.00 180.00 9.00 53.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   477.00 477.00 477.00 90.00 0.00 9.00 53.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
135 MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   954.00 954.00 954.00 0.00 90.00 954.00 1.00 0.00 MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
137 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   212.00 212.00 212.00 180.00 90.00 53.00 4.00 0.00 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
138 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 90.00 90.00 3.00 4.00 0.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   72.00 72.00 72.00 0.00 90.00 18.00 4.00 0.00 COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   140.00 140.00 140.00 0.00 90.00 35.00 4.00 0.00 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 0.00 90.00 11.00 4.00 0.00 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
142 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   7.80 12.00 7.80 270.00 90.00 3.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 Window CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 4.20 4.20 4.20 270.00 90.00 2.90 1.45 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.980E-002 1.971E-002   192.00 192.00 192.00 270.00 180.00 3.00 64.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
145 CORRIDOR_POD_3_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   192.00 192.00 192.00 90.00 0.00 3.00 64.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
146 CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   384.00 384.00 384.00 0.00 90.00 384.00 1.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
147 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   44.00 44.00 44.00 180.00 90.00 11.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.70 44.00 26.70 0.00 90.00 11.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
150 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 Window CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.94 1.94 1.94 0.00 90.00 1.22 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
151 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 Window CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 13.41 13.41 13.41 0.00 90.00 8.43 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
152 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR Door CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   23.40 36.00 23.40 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 Window CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 12.60 12.60 12.60 270.00 90.00 8.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 0.266 0.250   99.00 99.00 99.00 270.00 180.00 9.00 11.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
156 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   99.00 99.00 99.00 90.00 0.00 9.00 11.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
157 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   198.00 198.00 198.00 0.00 90.00 198.00 1.00 0.00 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
158 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   140.00 140.00 140.00 180.00 90.00 35.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
159 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
160 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   87.10 140.00 87.10 0.00 90.00 35.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 Window MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 16.33 16.33 16.33 0.00 90.00 10.82 1.51 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 Window MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 16.33 16.33 16.33 0.00 90.00 10.82 1.51 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 Window MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 16.33 16.33 16.33 0.00 90.00 10.82 1.51 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 Door MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 Door MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
167 MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   315.00 315.00 315.00 270.00 180.00 9.00 35.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   315.00 315.00 315.00 90.00 0.00 9.00 35.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
169 MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   630.00 630.00 630.00 0.00 90.00 630.00 1.00 0.00 MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
170 COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   72.00 72.00 72.00 180.00 90.00 18.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
171 COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
172 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   44.85 72.00 44.85 0.00 90.00 18.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 Window COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.84 1.84 1.84 0.00 90.00 1.22 1.51 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 Window COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 23.36 23.36 23.36 0.00 90.00 15.46 1.51 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR Door COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 COMPUTER_CLASS_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   162.00 162.00 162.00 270.00 180.00 9.00 18.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 COMPUTER_CLASS_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   162.00 162.00 162.00 90.00 0.00 9.00 18.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
179 COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   324.00 324.00 324.00 0.00 90.00 324.00 1.00 0.00 COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
180 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   52.00 52.00 52.00 180.00 90.00 13.00 4.00 0.00 LOBBY_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
181 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   168.00 168.00 168.00 90.00 90.00 42.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
182 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   52.00 52.00 52.00 0.00 90.00 13.00 4.00 0.00 BATH_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
183 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 270.00 90.00 3.00 4.00 0.00 CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   21.45 36.00 21.45 270.00 90.00 9.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
187 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 Window MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 2.00 2.00 2.00 270.00 90.00 1.22 1.64 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.74 0.26 4
188 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 Window MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 10.60 10.60 10.60 270.00 90.00 6.46 1.64 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
189 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR Door MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
190 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
191 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 270.00 90.00 3.00 4.00 0.00 CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR 2.090E-002 2.079E-002   546.00 546.00 546.00 270.00 180.00 42.00 13.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 MAIN_CORRIDOR_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   546.00 546.00 546.00 90.00 0.00 42.00 13.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1092.00 1092.00 1092.00 0.00 90.00 1092.00 1.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
195 LOBBY_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   47.45 76.00 47.45 180.00 90.00 19.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
196 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 Window LOBBY_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.83 1.83 1.83 180.00 90.00 1.22 1.50 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
197 LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 Window LOBBY_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 24.77 24.77 24.77 180.00 90.00 16.46 1.50 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 LOBBY_ZN_1_FLR_1_WALL_1_DOOR Door LOBBY_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 LOBBY_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 90.00 90.00 9.00 4.00 0.00 OFFICES_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 LOBBY_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.00 24.00 24.00 0.00 90.00 6.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 LOBBY_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   52.00 52.00 52.00 0.00 90.00 13.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 LOBBY_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
203 LOBBY_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR 0.144 0.139   171.00 171.00 171.00 270.00 180.00 9.00 19.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
204 LOBBY_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   171.00 171.00 171.00 90.00 0.00 9.00 19.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
205 LOBBY_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   342.00 342.00 342.00 0.00 90.00 342.00 1.00 0.00 LOBBY_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
206 MECH_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.00 24.00 24.00 180.00 90.00 6.00 4.00 0.00 LOBBY_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
207 MECH_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.00 48.00 48.00 90.00 90.00 12.00 4.00 0.00 OFFICES_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
208 MECH_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   68.00 68.00 68.00 90.00 90.00 17.00 4.00 0.00 GYM_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
209 MECH_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   32.00 32.00 32.00 90.00 90.00 8.00 4.00 0.00 KITCHEN_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
210 MECH_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.00 20.00 20.00 90.00 90.00 5.00 4.00 0.00 CAFETERIA_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
211 MECH_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.00 24.00 24.00 0.00 90.00 6.00 4.00 0.00 BATH_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 MECH_ZN_1_FLR_1_WALL_7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   168.00 168.00 168.00 270.00 90.00 42.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 MECH_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction MECH_ZN_1_FLR_1_FLOOR_FFACTOR 5.650E-003 5.642E-003   252.00 252.00 252.00 270.00 180.00 42.00 6.00 0.00 MECH_ZN_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
214 MECH_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   252.00 252.00 252.00 90.00 0.00 42.00 6.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
215 MECH_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   504.00 504.00 504.00 0.00 90.00 504.00 1.00 0.00 MECH_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
216 BATH_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   52.00 52.00 52.00 180.00 90.00 13.00 4.00 0.00 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
217 BATH_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.00 24.00 24.00 180.00 90.00 6.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
218 BATH_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.00 40.00 40.00 90.00 90.00 10.00 4.00 0.00 CAFETERIA_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
219 BATH_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   76.00 76.00 76.00 0.00 90.00 19.00 4.00 0.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
220 BATH_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   26.00 40.00 26.00 270.00 90.00 10.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
221 BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 Window BATH_ZN_1_FLR_1_WALL_5 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 14.00 14.00 14.00 270.00 90.00 9.90 1.41 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
222 BATH_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction BATH_ZN_1_FLR_1_FLOOR_FFACTOR 6.720E-002 6.612E-002   190.00 190.00 190.00 270.00 180.00 10.00 19.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
223 BATH_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   190.00 190.00 190.00 90.00 0.00 10.00 19.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
224 BATH_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   380.00 380.00 380.00 0.00 90.00 380.00 1.00 0.00 BATH_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
225 OFFICES_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   52.65 84.00 52.65 180.00 90.00 21.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
226 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 Window OFFICES_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.82 1.82 1.82 180.00 90.00 1.22 1.49 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
227 OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 Window OFFICES_ZN_1_FLR_1_WALL_1 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 27.58 27.58 27.58 180.00 90.00 18.46 1.49 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
228 OFFICES_ZN_1_FLR_1_WALL_1_DOOR Door OFFICES_ZN_1_FLR_1_WALL_1 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
229 OFFICES_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   54.60 84.00 54.60 90.00 90.00 21.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
230 OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 Window OFFICES_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 29.40 29.40 29.40 90.00 90.00 20.90 1.41 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
231 OFFICES_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 0.00 90.00 21.00 4.00 0.00 GYM_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 OFFICES_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.00 48.00 48.00 270.00 90.00 12.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
233 OFFICES_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 LOBBY_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
234 OFFICES_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR 0.123 0.119   441.00 441.00 441.00 270.00 180.00 21.00 21.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
235 OFFICES_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   441.00 441.00 441.00 90.00 0.00 21.00 21.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
236 OFFICES_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   882.00 882.00 882.00 0.00 90.00 882.00 1.00 0.00 OFFICES_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
237 GYM_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 180.00 90.00 21.00 4.00 0.00 OFFICES_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
238 GYM_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   42.25 68.00 42.25 90.00 90.00 17.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
239 GYM_ZN_1_FLR_1_WALL_2_WINDOW1 Window GYM_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.85 1.85 1.85 90.00 90.00 1.22 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
240 GYM_ZN_1_FLR_1_WALL_2_WINDOW2 Window GYM_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 21.95 21.95 21.95 90.00 90.00 14.46 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
241 GYM_ZN_1_FLR_1_WALL_2_DOOR Door GYM_ZN_1_FLR_1_WALL_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
242 GYM_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 0.00 90.00 21.00 4.00 0.00 KITCHEN_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
243 GYM_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   68.00 68.00 68.00 270.00 90.00 17.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
244 GYM_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction GYM_ZN_1_FLR_1_FLOOR_FFACTOR 6.074E-002 5.986E-002   357.00 357.00 357.00 270.00 180.00 17.00 21.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
245 GYM_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   343.62 357.00 343.62 90.00 0.00 17.00 21.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
246 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
247 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
248 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
249 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
250 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
251 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
252 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
253 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
254 GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 Window GYM_ZN_1_FLR_1_CEILING Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.55_SHGC_0.35 N/A 3.127 No 1.49 1.49 1.49 90.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
255 GYM_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   714.00 714.00 714.00 0.00 90.00 714.00 1.00 0.00 GYM_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
256 KITCHEN_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 180.00 90.00 21.00 4.00 0.00 GYM_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
257 KITCHEN_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   20.80 32.00 20.80 90.00 90.00 8.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
258 KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 Window KITCHEN_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 11.20 11.20 11.20 90.00 90.00 7.90 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
259 KITCHEN_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 0.00 90.00 21.00 4.00 0.00 CAFETERIA_ZN_1_FLR_1_WALL_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
260 KITCHEN_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   32.00 32.00 32.00 270.00 90.00 8.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
261 KITCHEN_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR 6.074E-002 5.986E-002   168.00 168.00 168.00 270.00 180.00 8.00 21.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
262 KITCHEN_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   168.00 168.00 168.00 90.00 0.00 8.00 21.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
263 KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   336.00 336.00 336.00 0.00 90.00 336.00 1.00 0.00 KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
264 CAFETERIA_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   84.00 84.00 84.00 180.00 90.00 21.00 4.00 0.00 KITCHEN_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
265 CAFETERIA_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   37.05 60.00 37.05 90.00 90.00 15.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
266 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 Window CAFETERIA_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.87 1.87 1.87 90.00 90.00 1.22 1.53 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
267 CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 Window CAFETERIA_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 19.13 19.13 19.13 90.00 90.00 12.46 1.53 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
268 CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR Door CAFETERIA_ZN_1_FLR_1_WALL_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
269 CAFETERIA_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   54.60 84.00 54.60 0.00 90.00 21.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
270 CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 Window CAFETERIA_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 29.40 29.40 29.40 0.00 90.00 20.90 1.41 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
271 CAFETERIA_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.00 40.00 40.00 270.00 90.00 10.00 4.00 0.00 BATH_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
272 CAFETERIA_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.00 20.00 20.00 270.00 90.00 5.00 4.00 0.00 MECH_ZN_1_FLR_1_WALL_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
273 CAFETERIA_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR 0.148 0.143   315.00 315.00 315.00 270.00 180.00 15.00 21.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
274 CAFETERIA_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   315.00 315.00 315.00 90.00 0.00 15.00 21.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
275 CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   630.00 630.00 630.00 0.00 90.00 630.00 1.00 0.00 CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
276 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   76.00 76.00 76.00 180.00 90.00 19.00 4.00 0.00 BATH_ZN_1_FLR_1_WALL_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
277 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   52.65 84.00 52.65 90.00 90.00 21.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
278 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 Window LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 1.82 1.82 1.82 90.00 90.00 1.22 1.49 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
279 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 Window LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 27.57 27.57 27.57 90.00 90.00 18.46 1.49 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
280 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR Door LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.975 3.975   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
281 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.199 1.016   49.40 76.00 49.40 0.00 90.00 19.00 4.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
282 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 Window LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 Window5 Detailed Fenestration NONRESWINDOW_U_0.495_SHGC_0.25 N/A 2.814 No 26.60 26.60 26.60 0.00 90.00 18.90 1.41 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
283 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
284 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.00 12.00 12.00 270.00 90.00 3.00 4.00 0.00 CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
285 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.00 36.00 36.00 270.00 90.00 9.00 4.00 0.00 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
286 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR 0.129 0.125   399.00 399.00 399.00 270.00 180.00 21.00 19.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
287 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   399.00 399.00 399.00 90.00 0.00 21.00 19.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
288 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   798.00 798.00 798.00 0.00 90.00 798.00 1.00 0.00 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 4.1869248113E-002 4.0592265068E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 3.3272104276E-002 3.4841651824E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORRIDOR_POD_1_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3479356960E-002 9.4510365865E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.6022044538E-002 1.8972720872E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 MULT_CLASS_2_POD_1_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.6550630658E-002 1.2928139181E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 3.9868456605E-002 4.0995912400E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 MULT_CLASS_1_POD_2_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 3.0073542717E-002 3.3318544513E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 CORRIDOR_POD_2_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3045229741E-002 9.2225103157E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.6099447994E-002 1.9058571813E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 MULT_CLASS_2_POD_2_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.6603424489E-002 1.2974952090E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 4.0157162288E-002 4.1014800870E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 MULT_CLASS_1_POD_3_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 3.1398350780E-002 3.4232384147E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 CORRIDOR_POD_3_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3494408104E-002 9.5812668357E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.6732279931E-002 1.9827653967E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 MULT_CLASS_2_POD_3_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.7488235117E-002 1.4015699510E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 COMPUTER_CLASS_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.7174071549E-002 1.3806946748E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 MAIN_CORRIDOR_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 9.5838457766E-003 8.4214548241E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 LOBBY_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 3.2700563277E-002 3.5779003741E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 MECH_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 7.9778421402E-003 7.4200982445E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 BATH_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3736259354E-002 1.0181234614E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
21 OFFICES_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.8751414463E-002 3.4247310643E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
22 GYM_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.0220538468E-002 2.3388023835E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
23 KITCHEN_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 0.4476698566 0.4438021949 Pass Pass 2.6376440073 12.6945466162 Pass Pass
24 CAFETERIA_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.1668594255E-002 2.4766168743E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
25 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 RunPeriod: RUNPERIOD 1 2.0426121957E-002 2.0615387195E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 9794.07 79.03 968.44 4495.15 2095.85 17432.60



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.65 180.00 90.00 S
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 212.00 133.90 180.00 90.00 S
MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 477.00 477.00 270.00 180.00  
MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 477.00 477.00 90.00 0.00  
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 12.00 7.80 270.00 90.00 W
CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.020 0.020 192.00 192.00 270.00 180.00  
CORRIDOR_POD_1_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 192.00 192.00 90.00 0.00  
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.65 0.00 90.00 N
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 212.00 133.90 0.00 90.00 N
MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 477.00 477.00 270.00 180.00  
MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 477.00 477.00 90.00 0.00  
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.65 180.00 90.00 S
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 212.00 133.90 180.00 90.00 S
MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 477.00 477.00 270.00 180.00  
MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 477.00 477.00 90.00 0.00  
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 12.00 7.80 270.00 90.00 W
CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.020 0.020 192.00 192.00 270.00 180.00  
CORRIDOR_POD_2_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 192.00 192.00 90.00 0.00  
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.65 0.00 90.00 N
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 212.00 133.90 0.00 90.00 N
MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 477.00 477.00 270.00 180.00  
MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 477.00 477.00 90.00 0.00  
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.65 180.00 90.00 S
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 212.00 133.90 180.00 90.00 S
MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 477.00 477.00 270.00 180.00  
MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 477.00 477.00 90.00 0.00  
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 12.00 7.80 270.00 90.00 W
CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.020 0.020 192.00 192.00 270.00 180.00  
CORRIDOR_POD_3_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 192.00 192.00 90.00 0.00  
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 44.00 26.70 0.00 90.00 N
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 23.40 270.00 90.00 W
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.255 0.266 99.00 99.00 270.00 180.00  
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 99.00 99.00 90.00 0.00  
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 140.00 87.10 0.00 90.00 N
MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 315.00 315.00 270.00 180.00  
MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 315.00 315.00 90.00 0.00  
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 72.00 44.85 0.00 90.00 N
COMPUTER_CLASS_ZN_1_FLR_1_FLOOR COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 162.00 162.00 270.00 180.00  
COMPUTER_CLASS_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 162.00 162.00 90.00 0.00  
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 36.00 21.45 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.021 0.021 546.00 546.00 270.00 180.00  
MAIN_CORRIDOR_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 546.00 546.00 90.00 0.00  
LOBBY_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 76.00 47.45 180.00 90.00 S
LOBBY_ZN_1_FLR_1_FLOOR LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.140 0.144 171.00 171.00 270.00 180.00  
LOBBY_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 171.00 171.00 90.00 0.00  
MECH_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 252.00 252.00 90.00 0.00  
BATH_ZN_1_FLR_1_WALL_5 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 40.00 26.00 270.00 90.00 W
BATH_ZN_1_FLR_1_FLOOR BATH_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.066 0.067 190.00 190.00 270.00 180.00  
BATH_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 190.00 190.00 90.00 0.00  
OFFICES_ZN_1_FLR_1_WALL_1 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 84.00 52.65 180.00 90.00 S
OFFICES_ZN_1_FLR_1_WALL_2 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 84.00 54.60 90.00 90.00 E
OFFICES_ZN_1_FLR_1_FLOOR OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.120 0.123 441.00 441.00 270.00 180.00  
OFFICES_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 441.00 441.00 90.00 0.00  
GYM_ZN_1_FLR_1_WALL_2 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 68.00 42.25 90.00 90.00 E
GYM_ZN_1_FLR_1_FLOOR GYM_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.060 0.061 357.00 357.00 270.00 180.00  
GYM_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 357.00 343.62 90.00 0.00  
KITCHEN_ZN_1_FLR_1_WALL_2 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 32.00 20.80 90.00 90.00 E
KITCHEN_ZN_1_FLR_1_FLOOR KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.060 0.061 168.00 168.00 270.00 180.00  
KITCHEN_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 168.00 168.00 90.00 0.00  
CAFETERIA_ZN_1_FLR_1_WALL_2 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 60.00 37.05 90.00 90.00 E
CAFETERIA_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 84.00 54.60 0.00 90.00 N
CAFETERIA_ZN_1_FLR_1_FLOOR CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.144 0.148 315.00 315.00 270.00 180.00  
CAFETERIA_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 315.00 315.00 90.00 0.00  
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 84.00 52.65 90.00 90.00 E
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 NONRES_EXT_WALL_GRD 0.30 1.016 1.199 76.00 49.40 0.00 90.00 N
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.127 0.129 399.00 399.00 270.00 180.00  
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 399.00 399.00 90.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 212.00 212.00 0.00 90.00 N
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 212.00 212.00 180.00 90.00 S
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 12.00 12.00 90.00 90.00 E
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 212.00 212.00 0.00 90.00 N
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 212.00 212.00 180.00 90.00 S
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 212.00 212.00 0.00 90.00 N
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 212.00 212.00 180.00 90.00 S
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 12.00 12.00 90.00 90.00 E
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 212.00 212.00 0.00 90.00 N
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 212.00 212.00 180.00 90.00 S
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 212.00 212.00 0.00 90.00 N
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 212.00 212.00 180.00 90.00 S
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 12.00 12.00 90.00 90.00 E
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 72.00 72.00 0.00 90.00 N
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 140.00 140.00 0.00 90.00 N
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 INT_WALL 0.30 2.511 6.299 44.00 44.00 0.00 90.00 N
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 44.00 44.00 180.00 90.00 S
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 140.00 140.00 180.00 90.00 S
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 72.00 72.00 180.00 90.00 S
COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 52.00 52.00 180.00 90.00 S
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 168.00 168.00 90.00 90.00 E
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 52.00 52.00 0.00 90.00 N
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 12.00 12.00 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 INT_WALL 0.30 2.511 6.299 12.00 12.00 270.00 90.00 W
LOBBY_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 36.00 36.00 90.00 90.00 E
LOBBY_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 24.00 24.00 0.00 90.00 N
LOBBY_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 52.00 52.00 0.00 90.00 N
LOBBY_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
MECH_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 24.00 24.00 180.00 90.00 S
MECH_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 48.00 48.00 90.00 90.00 E
MECH_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 68.00 68.00 90.00 90.00 E
MECH_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 32.00 32.00 90.00 90.00 E
MECH_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 20.00 20.00 90.00 90.00 E
MECH_ZN_1_FLR_1_WALL_6 INT_WALL 0.30 2.511 6.299 24.00 24.00 0.00 90.00 N
MECH_ZN_1_FLR_1_WALL_7 INT_WALL 0.30 2.511 6.299 168.00 168.00 270.00 90.00 W
MECH_ZN_1_FLR_1_FLOOR MECH_ZN_1_FLR_1_FLOOR_FFACTOR 1.00 0.006 0.006 252.00 252.00 270.00 180.00  
BATH_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 52.00 52.00 180.00 90.00 S
BATH_ZN_1_FLR_1_WALL_2 INT_WALL 0.30 2.511 6.299 24.00 24.00 180.00 90.00 S
BATH_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 40.00 40.00 90.00 90.00 E
BATH_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 76.00 76.00 0.00 90.00 N
OFFICES_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 84.00 84.00 0.00 90.00 N
OFFICES_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 48.00 48.00 270.00 90.00 W
OFFICES_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
GYM_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 84.00 84.00 180.00 90.00 S
GYM_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 84.00 84.00 0.00 90.00 N
GYM_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 68.00 68.00 270.00 90.00 W
KITCHEN_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 84.00 84.00 180.00 90.00 S
KITCHEN_ZN_1_FLR_1_WALL_3 INT_WALL 0.30 2.511 6.299 84.00 84.00 0.00 90.00 N
KITCHEN_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 32.00 32.00 270.00 90.00 W
CAFETERIA_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 84.00 84.00 180.00 90.00 S
CAFETERIA_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 40.00 40.00 270.00 90.00 W
CAFETERIA_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 20.00 20.00 270.00 90.00 W
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 INT_WALL 0.30 2.511 6.299 76.00 76.00 180.00 90.00 S
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 INT_WALL 0.30 2.511 6.299 12.00 12.00 270.00 90.00 W
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 INT_WALL 0.30 2.511 6.299 36.00 36.00 270.00 90.00 W
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 954.00   0.00 90.00 N
CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 384.00   0.00 90.00 N
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 954.00   0.00 90.00 N
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 954.00   0.00 90.00 N
CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 384.00   0.00 90.00 N
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 954.00   0.00 90.00 N
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 954.00   0.00 90.00 N
CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 384.00   0.00 90.00 N
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 198.00   0.00 90.00 N
MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 630.00   0.00 90.00 N
COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 324.00   0.00 90.00 N
MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1092.00   0.00 90.00 N
LOBBY_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 342.00   0.00 90.00 N
MECH_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 504.00   0.00 90.00 N
BATH_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 380.00   0.00 90.00 N
OFFICES_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 882.00   0.00 90.00 N
GYM_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 714.00   0.00 90.00 N
KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 336.00   0.00 90.00 N
CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 630.00   0.00 90.00 N
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 798.00   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.46 0.00 0.00 13.46 13.46 2.814 0.251 0.276             No CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   4.20 0.00 0.00 4.20 4.20 2.814 0.251 0.276             No CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 270.00 90.00 W
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.46 0.00 0.00 13.46 13.46 2.814 0.251 0.276             No CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.46 0.00 0.00 13.46 13.46 2.814 0.251 0.276             No CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   4.20 0.00 0.00 4.20 4.20 2.814 0.251 0.276             No CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 270.00 90.00 W
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.46 0.00 0.00 13.46 13.46 2.814 0.251 0.276             No CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.46 0.00 0.00 13.46 13.46 2.814 0.251 0.276             No CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   24.74 0.00 0.00 24.74 24.74 2.814 0.251 0.276             No MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 180.00 90.00 S
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   24.73 0.00 0.00 24.73 24.73 2.814 0.251 0.276             No MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 180.00 90.00 S
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   4.20 0.00 0.00 4.20 4.20 2.814 0.251 0.276             No CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 270.00 90.00 W
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.94 0.00 0.00 1.94 1.94 2.814 0.251 0.276             No CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   13.41 0.00 0.00 13.41 13.41 2.814 0.251 0.276             No CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0.00 90.00 N
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   12.60 0.00 0.00 12.60 12.60 2.814 0.251 0.276             No CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 270.00 90.00 W
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   16.33 0.00 0.00 16.33 16.33 2.814 0.251 0.276             No MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   16.33 0.00 0.00 16.33 16.33 2.814 0.251 0.276             No MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 NONRESWINDOW_U_0.495_SHGC_0.25   16.33 0.00 0.00 16.33 16.33 2.814 0.251 0.276             No MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 0.00 90.00 N
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.84 0.00 0.00 1.84 1.84 2.814 0.251 0.276             No COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 0.00 90.00 N
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   23.36 0.00 0.00 23.36 23.36 2.814 0.251 0.276             No COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 0.00 90.00 N
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   2.00 0.00 0.00 2.00 2.00 2.814 0.251 0.276             No MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 270.00 90.00 W
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   10.60 0.00 0.00 10.60 10.60 2.814 0.251 0.276             No MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 270.00 90.00 W
LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.83 0.00 0.00 1.83 1.83 2.814 0.251 0.276             No LOBBY_ZN_1_FLR_1_WALL_1 180.00 90.00 S
LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   24.77 0.00 0.00 24.77 24.77 2.814 0.251 0.276             No LOBBY_ZN_1_FLR_1_WALL_1 180.00 90.00 S
BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   14.00 0.00 0.00 14.00 14.00 2.814 0.251 0.276             No BATH_ZN_1_FLR_1_WALL_5 270.00 90.00 W
OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.82 0.00 0.00 1.82 1.82 2.814 0.251 0.276             No OFFICES_ZN_1_FLR_1_WALL_1 180.00 90.00 S
OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   27.58 0.00 0.00 27.58 27.58 2.814 0.251 0.276             No OFFICES_ZN_1_FLR_1_WALL_1 180.00 90.00 S
OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   29.40 0.00 0.00 29.40 29.40 2.814 0.251 0.276             No OFFICES_ZN_1_FLR_1_WALL_2 90.00 90.00 E
GYM_ZN_1_FLR_1_WALL_2_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.85 0.00 0.00 1.85 1.85 2.814 0.251 0.276             No GYM_ZN_1_FLR_1_WALL_2 90.00 90.00 E
GYM_ZN_1_FLR_1_WALL_2_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   21.95 0.00 0.00 21.95 21.95 2.814 0.251 0.276             No GYM_ZN_1_FLR_1_WALL_2 90.00 90.00 E
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 NONRESSKYLIGHT_U_0.55_SHGC_0.35 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.127 0.351 0.402 0.000 0.000 CurtainWall 3.043 0.356 0.402 No GYM_ZN_1_FLR_1_CEILING 90.00 0.00  
KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   11.20 0.00 0.00 11.20 11.20 2.814 0.251 0.276             No KITCHEN_ZN_1_FLR_1_WALL_2 90.00 90.00 E
CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.87 0.00 0.00 1.87 1.87 2.814 0.251 0.276             No CAFETERIA_ZN_1_FLR_1_WALL_2 90.00 90.00 E
CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   19.13 0.00 0.00 19.13 19.13 2.814 0.251 0.276             No CAFETERIA_ZN_1_FLR_1_WALL_2 90.00 90.00 E
CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   29.40 0.00 0.00 29.40 29.40 2.814 0.251 0.276             No CAFETERIA_ZN_1_FLR_1_WALL_3 0.00 90.00 N
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 NONRESWINDOW_U_0.495_SHGC_0.25   1.82 0.00 0.00 1.82 1.82 2.814 0.251 0.276             No LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 90.00 90.00 E
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 NONRESWINDOW_U_0.495_SHGC_0.25   27.57 0.00 0.00 27.57 27.57 2.814 0.251 0.276             No LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 90.00 90.00 E
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 NONRESWINDOW_U_0.495_SHGC_0.25   26.60 0.00 0.00 26.60 26.60 2.814 0.251 0.276             No LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 0.00 90.00 N
Total or Average             892.52 2.819 0.252 0.278                      
North Total or Average             324.75 2.814 0.251 0.276                      
Non-North Total or Average             567.77 2.822 0.253 0.279                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 SWINGING DOOR_CON 2.492 3.975 1.95 MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 COMPUTER_CLASS_ZN_1_FLR_1_WALL_3
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7
LOBBY_ZN_1_FLR_1_WALL_1_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 LOBBY_ZN_1_FLR_1_WALL_1
OFFICES_ZN_1_FLR_1_WALL_1_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 OFFICES_ZN_1_FLR_1_WALL_1
GYM_ZN_1_FLR_1_WALL_2_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 GYM_ZN_1_FLR_1_WALL_2
CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 CAFETERIA_ZN_1_FLR_1_WALL_2
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR SWINGING DOOR_CON 2.492 3.975 1.95 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 0.82 0.99 1.00 0.88 1.00 1.00 0.75 1.00 1.00
CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 0.82 0.99 1.00 0.88 1.00 1.00 0.75 1.00 1.00
CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 0.00 0.00 0.76 0.00 0.00 0.99 0.00 0.00 0.31
LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 0.00 0.00 0.85 0.00 0.00 1.00 0.00 0.00 0.57
OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GYM_ZN_1_FLR_1_WALL_2_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GYM_ZN_1_FLR_1_WALL_2_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 0.02 0.02 0.00 1.00 0.73 0.00 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 0.89 0.96 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 27.49 0.0000 Y 6.97
MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1 GENERAL 13.6336 477.00 6503.21 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 33.17 0.0000 Y 40.49
CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS CORRIDOR_POD_1_ZN_1_FLR_1 CORRIDOR_POD_1_ZN_1_FLR_1 GENERAL 7.1339 192.00 1369.71 LightsWired LTG_SCH_CORRIDOR 52.69 168.00 51.68 0.0000 Y 13.29
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 32.01 0.0000 Y 8.11
MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1 GENERAL 13.6336 477.00 6503.21 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 39.58 0.0000 Y 48.32
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 28.57 0.0000 Y 7.24
MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1 GENERAL 13.6336 477.00 6503.21 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 34.75 0.0000 Y 42.43
CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS CORRIDOR_POD_2_ZN_1_FLR_1 CORRIDOR_POD_2_ZN_1_FLR_1 GENERAL 7.1339 192.00 1369.71 LightsWired LTG_SCH_CORRIDOR 52.69 168.00 51.68 0.0000 Y 13.29
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 32.42 0.0000 Y 8.21
MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1 GENERAL 13.6336 477.00 6503.21 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 39.49 0.0000 Y 48.21
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 28.50 0.0000 Y 7.22
MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1 GENERAL 13.6336 477.00 6503.21 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 42.22 0.0000 Y 51.54
CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS CORRIDOR_POD_3_ZN_1_FLR_1 CORRIDOR_POD_3_ZN_1_FLR_1 GENERAL 7.1339 192.00 1369.71 LightsWired LTG_SCH_CORRIDOR 52.69 168.00 51.68 0.0000 Y 13.29
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 GENERAL 13.6336 99.00 1349.72 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 30.40 0.0000 Y 7.70
MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1 GENERAL 13.6336 315.00 4294.57 LightsWired LTG_SCH_CLASSROOM 50.71 168.00 36.25 0.0000 Y 29.23
COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1 GENERAL 13.6336 162.00 2208.64 LightsWired LTG_SCH_COMPUTER_ROOM 50.71 168.00 36.26 0.0000 Y 15.03
MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS MAIN_CORRIDOR_ZN_1_FLR_1 MAIN_CORRIDOR_ZN_1_FLR_1 GENERAL 7.1339 546.00 3895.10 LightsWired LTG_SCH_CORRIDOR 52.69 168.00 51.68 0.0000 Y 37.79
LOBBY_ZN_1_FLR_1_LIGHTS LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1 GENERAL 9.6875 171.00 1656.56 LightsWired LTG_SCH_LOBBY 56.14 168.00 35.92 0.0000 Y 11.17
MECH_ZN_1_FLR_1_LIGHTS MECH_ZN_1_FLR_1 MECH_ZN_1_FLR_1 GENERAL 4.5208 252.00 1139.25 LightsWired LTG_SCH_MECHANICAL 74.85 168.00 73.41 0.0000 Y 15.70
BATH_ZN_1_FLR_1_LIGHTS BATH_ZN_1_FLR_1 BATH_ZN_1_FLR_1 GENERAL 10.5486 190.00 2004.24 LightsWired LTG_SCH_BATH 41.17 168.00 40.38 0.0000 Y 15.19
OFFICES_ZN_1_FLR_1_LIGHTS OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1 GENERAL 11.3407 441.00 5001.24 LightsWired LTG_SCH_OFFICE 58.96 168.00 43.66 0.0000 Y 40.98
GYM_ZN_1_FLR_1_LIGHTS GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1 GENERAL 11.9479 357.00 4265.41 LightsWired LTG_SCH_GYM 70.17 153.29 36.01 0.0000 Y 28.83
KITCHEN_ZN_1_FLR_1_LIGHTS KITCHEN_ZN_1_FLR_1 KITCHEN_ZN_1_FLR_1 GENERAL 13.0243 168.00 2188.09 LightsWired LTG_SCH_KITCHEN 74.85 168.00 73.41 0.0000 Y 30.15
CAFETERIA_ZN_1_FLR_1_LIGHTS CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1 GENERAL 6.9965 315.00 2203.91 LightsWired LTG_SCH_CAFETERIA 74.85 168.00 51.36 0.0000 Y 21.25
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 GENERAL 16.3073 399.00 6506.62 LightsWired LTG_SCH_LIBRARY 65.02 168.00 54.18 0.0000 Y 66.17
Interior Lighting Total       11.6558 6871.00 80087.12               627.80


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
GYM_ZN_1_FLR_1_DAYLREFPT1 GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.50 4265.41 2132.71
GYM_ZN_1_FLR_1_DAYLREFPT2 GYM_ZN_1_FLR_1 GYM_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.50 4265.41 2132.71
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_1_POD_1_ZN_1_FLR_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.20 1349.72 269.94
MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_1_POD_1_ZN_1_FLR_1 MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_2_POD_1_ZN_1_FLR_1 CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.22 1349.72 296.94
MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_2_POD_1_ZN_1_FLR_1 MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1 CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.20 1349.72 269.94
MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_1_POD_2_ZN_1_FLR_1 MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_2_POD_2_ZN_1_FLR_1 CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.20 1349.72 269.94
MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_2_POD_2_ZN_1_FLR_1 MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 6503.21 1820.90
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_1_POD_3_ZN_1_FLR_1 CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.20 1349.72 269.94
MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.14 6503.21 910.45
MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_1_POD_3_ZN_1_FLR_1 MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.14 6503.21 910.45
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.56 1349.72 755.84
CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 CORNER_CLASS_2_POD_3_ZN_1_FLR_1 CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.20 1349.72 269.94
MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT1 MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 4294.57 1202.48
MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLREFPT2 MULT_CLASS_2_POD_3_ZN_1_FLR_1 MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 4294.57 1202.48
COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT1 COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 2208.64 618.42
COMPUTER_CLASS_ZN_1_FLR_1_DAYLREFPT2 COMPUTER_CLASS_ZN_1_FLR_1 COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 2208.64 618.42
LOBBY_ZN_1_FLR_1_DAYLREFPT1 LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 1656.56 463.84
LOBBY_ZN_1_FLR_1_DAYLREFPT2 LOBBY_ZN_1_FLR_1 LOBBY_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.28 1656.56 463.84
OFFICES_ZN_1_FLR_1_DAYLREFPT1 OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.24 5001.24 1200.30
OFFICES_ZN_1_FLR_1_DAYLREFPT2 OFFICES_ZN_1_FLR_1 OFFICES_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.18 5001.24 900.22
CAFETERIA_ZN_1_FLR_1_DAYLREFPT1 CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.34 2203.91 749.33
CAFETERIA_ZN_1_FLR_1_DAYLREFPT2 CAFETERIA_ZN_1_FLR_1 CAFETERIA_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.16 2203.91 352.63
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.26 6506.62 1691.72
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLREFPT2 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL SplitFlux Stepped 0.18 6506.62 1171.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 177.17 AstronomicalClock -   42.14 42.14 1.40
EXTERIOR_LIGHTS_B 3804.83 AstronomicalClock -   83.75 71.27 50.90
Exterior Lighting Total 3982.00           52.30



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 274171.66 0.80        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_POD_1 COOLING COIL Coil:Cooling:DX:TwoSpeed   116206.71 87076.56 29130.15 0.75 3.40    
VAV_POD_2 COOLING COIL Coil:Cooling:DX:TwoSpeed   115735.82 86698.85 29036.97 0.75 3.40    
VAV_POD_3 COOLING COIL Coil:Cooling:DX:TwoSpeed   102597.88 77002.13 25595.75 0.75 3.40    
VAV_OTHER COOLING COIL Coil:Cooling:DX:TwoSpeed   107343.16 85166.14 22177.02 0.79 3.40    
PSZ-AC_2:5 COOLING COIL Coil:Cooling:DX:MultiSpeed   27920.64 21769.44 6151.20 0.78 3.80    
PSZ-AC_1:6 COOLING COIL Coil:Cooling:DX:MultiSpeed   27792.32 21338.39 6453.93 0.77 3.80    
PSZ-AC_2:7 COOLING COIL Coil:Cooling:DX:MultiSpeed   47552.11 35494.32 12057.79 0.75 3.73    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
VAV_POD_1 COOLING COIL   112220.1 2.95 10.05 N/A N/A 10.65
VAV_POD_2 COOLING COIL   111768.5 2.95 10.05 N/A N/A 10.66
VAV_POD_3 COOLING COIL   99062.5 2.94 10.05 N/A N/A 10.65
VAV_OTHER COOLING COIL   103195.8 2.89 9.88 N/A N/A 10.43
PSZ-AC_2:5 COOLING COIL   26815.1     11.51 11.51  
PSZ-AC_1:6 COOLING COIL   26723.3     11.57 11.57  
PSZ-AC_2:7 COOLING COIL   45821.8     11.52 11.52  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
VAV_POD_1 COOLING COIL Coil:Cooling:DX:TwoSpeed                
VAV_POD_2 COOLING COIL Coil:Cooling:DX:TwoSpeed                
VAV_POD_3 COOLING COIL Coil:Cooling:DX:TwoSpeed                
VAV_OTHER COOLING COIL Coil:Cooling:DX:TwoSpeed                
PSZ-AC_2:5 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC_1:6 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC_2:7 COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 6143.50 5823.06 -
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 21406.96 20292.40 -
CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4806.02 4555.33 -
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 5799.88 5497.23 -
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 18960.18 17972.48 -
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 6104.86 5786.46 -
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 21079.22 19983.28 -
CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4799.91 4549.55 -
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 5818.67 5515.05 -
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 19033.61 18042.10 -
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 5992.72 5680.10 -
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 20731.53 19652.12 -
CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4738.62 4491.41 -
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 5759.16 5458.57 -
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 12626.07 11968.14 -
COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 7045.91 6679.79 -
MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 6570.02 6224.76 -
LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4780.93 4527.92 -
MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 923.37 875.51 -
BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2700.30 2557.42 -
OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 9464.08 8963.34 -
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10949.72 10377.35 -
VAV_POD_1 HEATING COIL Coil:Heating:Water 17345.57 14557.73 -
VAV_POD_2 HEATING COIL Coil:Heating:Water 17262.19 14487.75 -
VAV_POD_3 HEATING COIL Coil:Heating:Water 15379.05 12907.28 -
VAV_OTHER HEATING COIL Coil:Heating:Water 17949.62 15064.70 -
PSZ-AC_2:5 HEATING COIL Coil:Heating:Fuel   42858.59 0.80
PSZ-AC_1:6 HEATING COIL Coil:Heating:Fuel   63444.76 0.80
PSZ-AC_2:7 HEATING COIL Coil:Heating:Fuel   80011.94 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
BATH_ZN_1_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.28 91.94 324.68 1.00 2.55 General    
GYM_ZN_1_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.54 0.00 0.00 1.00 0.00 General    
KITCHEN_ZN_1_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 2.12 689.53 324.68 1.00 1.45 General    
CAFETERIA_ZN_1_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 1.38 0.00 0.00 1.00 0.00 General    
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
VAV_POD_1 FAN Fan:VariableVolume 0.60 1389.42 5.41 12434.29 2298.46 1.00 1.13 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
VAV_POD_2 FAN Fan:VariableVolume 0.60 1389.42 5.38 12374.51 2298.46 1.00 1.13 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00
VAV_POD_3 FAN Fan:VariableVolume 0.60 1389.42 4.80 11024.58 2298.46 1.00 1.14 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
VAV_OTHER FAN Fan:VariableVolume 0.60 1314.72 5.60 12175.51 2174.89 1.00 1.13 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00
PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.41 1557.76 1107.16 1.00 1.33 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.36 1505.58 1107.16 1.00 1.33 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 622.50 2.20 2352.96 1070.05 1.00 1.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002399 722.34 301156.09 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000105 13.47 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 6000.00 1.00 1.38 1.27
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.75 0.25


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
VAV_POD_1 COOLING COIL Coil:Cooling:DX:TwoSpeed None 112220.08 2.95 10.05 10.65 6.1407 3.12 10.63 4.8858 3.10 10.57 3.2791 3.23 11.03 1.3409
VAV_POD_2 COOLING COIL Coil:Cooling:DX:TwoSpeed None 111768.51 2.95 10.05 10.66 6.1112 3.12 10.63 4.8627 3.10 10.57 3.2630 3.23 11.03 1.3348
VAV_POD_3 COOLING COIL Coil:Cooling:DX:TwoSpeed None 99062.50 2.94 10.05 10.65 5.4445 3.11 10.62 4.3309 3.10 10.56 2.9063 3.23 11.03 1.1881
VAV_OTHER COOLING COIL Coil:Cooling:DX:TwoSpeed None 103195.83 2.89 9.88 10.43 6.3546 3.05 10.39 5.0776 3.03 10.33 3.4094 3.19 10.90 1.3397
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 7398.60 7398.60 74.73 0.548 0.548 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 24.00 24.00 0.00925 30.86 0.00823 0.186 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 29122.30 29122.30 61.05 2.157 2.157 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00943 31.23 0.00823 0.897 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 5999.34 5999.34 31.25 0.426 0.426 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.00 24.00 0.00915 25.00 0.00822 0.059 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 6792.67 6792.67 68.61 0.503 0.503 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00932 30.41 0.00823 0.186 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 24828.70 24828.70 52.05 1.839 1.839 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00959 31.30 0.00823 0.897 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 7352.24 7352.24 74.27 0.544 0.544 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 24.00 24.00 0.00926 30.86 0.00823 0.186 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 28856.13 28856.13 60.50 2.137 2.137 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00944 31.23 0.00823 0.897 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 5994.09 5994.09 31.22 0.426 0.426 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.00 24.00 0.00915 25.00 0.00822 0.059 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 6795.13 6795.13 68.64 0.503 0.503 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00932 30.41 0.00823 0.186 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 24838.74 24838.74 52.07 1.839 1.839 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00959 31.30 0.00823 0.897 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 7357.48 7357.48 74.32 0.545 0.545 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 24.00 24.00 0.00926 30.86 0.00823 0.186 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 28982.45 28982.45 60.76 2.146 2.146 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00944 31.23 0.00823 0.897 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 6046.78 6046.78 31.49 0.430 0.430 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.00 24.00 0.00914 25.00 0.00822 0.059 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 6836.46 6836.46 69.06 0.506 0.506 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00932 30.41 0.00823 0.186 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 16664.12 16664.12 52.90 1.234 1.234 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00957 31.30 0.00823 0.592 0.00
COMPUTER_CLASS_ZN_1_FLR_1 9263.51 9263.51 57.18 0.686 0.686 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00949 31.30 0.00823 0.305 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 12761.60 12761.60 23.37 0.894 0.894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.00 24.00 0.00942 25.00 0.00822 0.166 0.00
LOBBY_ZN_1_FLR_1 6616.74 6616.74 38.69 0.490 0.490 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00908 31.23 0.00823 0.096 0.00
MECH_ZN_1_FLR_1 5853.73 5853.73 23.23 0.433 0.433 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00865 31.23 0.00823 0.000 0.00
BATH_ZN_1_FLR_1 6151.63 6151.63 32.38 0.455 0.455 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 24.00 24.00 0.00885 30.29 0.00823 0.000 0.00
OFFICES_ZN_1_FLR_1 17551.52 17551.52 39.80 1.299 1.299 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00878 30.93 0.00823 0.190 0.00
GYM_ZN_1_FLR_1 18997.97 18997.97 53.22 1.407 1.407 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 24.00 23.99 0.00980 29.55 0.00823 0.544 0.00
KITCHEN_ZN_1_FLR_1 18345.45 18345.45 109.20 1.360 1.360 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.99 0.01053 30.50 0.00823 0.255 0.00
CAFETERIA_ZN_1_FLR_1 29659.48 29659.48 94.16 2.199 2.199 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 24.00 23.98 0.01093 30.86 0.00823 1.488 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 19975.84 19975.84 50.06 1.440 1.440 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:10:00 24.00 24.00 0.00908 25.00 0.00822 0.345 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 2480.56 2480.56 25.06 0.104 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 6987.46 6987.46 14.65 0.295 0.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00772 3.80 0.00506 0.897 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 1955.68 1955.68 10.19 0.084 0.084 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00794 3.80 0.00506 0.059 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 2436.94 2436.94 24.62 0.102 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 6666.74 6666.74 13.98 0.282 0.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00771 3.80 0.00506 0.897 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 2448.76 2448.76 24.73 0.103 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 6728.41 6728.41 14.11 0.284 0.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00772 3.80 0.00506 0.897 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 1939.56 1939.56 10.10 0.083 0.083 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00794 3.80 0.00506 0.059 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 2439.60 2439.60 24.64 0.102 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 6680.69 6680.69 14.01 0.282 0.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00771 3.80 0.00506 0.897 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 2452.39 2452.39 24.77 0.103 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 6784.18 6784.18 14.22 0.287 0.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00772 3.80 0.00506 0.897 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 1945.28 1945.28 10.13 0.083 0.083 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00794 3.80 0.00506 0.059 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 2469.51 2469.51 24.94 0.103 0.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00770 3.80 0.00506 0.186 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 4606.60 4606.60 14.62 0.195 0.592 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00772 3.80 0.00506 0.592 0.00
COMPUTER_CLASS_ZN_1_FLR_1 2005.63 2005.63 12.38 0.085 0.305 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00769 3.80 0.00506 0.305 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 3813.63 3813.63 6.98 0.163 0.166 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00791 3.80 0.00506 0.166 0.00
LOBBY_ZN_1_FLR_1 3198.71 3198.71 18.71 0.134 0.134 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00778 3.80 0.00506 0.096 0.00
MECH_ZN_1_FLR_1 71.50 71.50 0.28 0.003 0.003 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00510 3.80 0.00506 0.000 0.00
BATH_ZN_1_FLR_1 1800.54 1800.54 9.48 0.079 0.079 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00785 3.80 0.00506 0.000 0.00
OFFICES_ZN_1_FLR_1 6307.05 6307.05 14.30 0.266 0.266 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00776 3.80 0.00506 0.190 0.00
GYM_ZN_1_FLR_1 2879.78 2879.78 8.07 0.126 0.544 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00784 3.80 0.00506 0.544 0.00
KITCHEN_ZN_1_FLR_1 0.00 0.00 0.00 0.000 0.255   00:10:00 21.00 26.70 0.02000 3.80 0.00506 0.255 0.00
CAFETERIA_ZN_1_FLR_1 3694.83 3694.83 11.73 0.161 1.488 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:30:00 21.00 21.00 0.00775 3.80 0.00506 1.488 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 5246.81 5246.81 13.15 0.222 0.345 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 21.00 0.00773 3.80 0.00506 0.345 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_POD_1 5.41 5.41 2.25 2.25 5.4098 3.7047 5.4098 0.6848 0.3000
VAV_POD_2 5.38 5.38 2.25 2.25 5.3838 3.7057 5.3838 0.6883 0.3000
VAV_POD_3 4.80 4.80 1.94 1.94 4.7965 3.1985 4.7965 0.6668 0.3000
VAV_OTHER 5.60 5.60 1.30 1.30 5.5982 2.0244 5.5982 0.3616 0.3000
PSZ-AC_2:5 1.41 1.41 0.54 0.54 1.4070 1.4070 1.4070 1.0000 1.0000
PSZ-AC_1:6 1.36 1.36 0.25 0.25 1.3599 1.3599 1.3599 1.0000 1.0000
PSZ-AC_2:7 2.20 2.20 1.49 1.49 2.1989 2.1989 2.1989 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX 6143.498 6143.498 0.370909 0.00005375 132.713 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 6143.50 6143.50 0.370909 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00770025 48.8790 2480.56 0.00 6164.94 6164.94
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX 21406.963 21406.963 1.460012 0.00018728 453.143 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21406.96 21406.96 1.460012 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00772464 49.0311 6987.46 0.00 21482.60 21482.60
CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX 4806.023 4806.023 0.288482 0.00004205 103.929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 4806.02 4806.02 0.288482 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00794098 50.3862 1955.68 0.00 4822.79 4822.79
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX 5799.875 5799.875 0.340534 0.00005074 125.928 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 5799.88 5799.88 0.340534 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00769566 48.8501 2436.94 0.00 5820.06 5820.06
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX 18960.179 18960.179 1.244767 0.00016587 403.777 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 18960.18 18960.18 1.244767 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00771404 48.9646 6666.74 0.00 19026.92 19026.92
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX 6104.855 6104.855 0.370219 0.00005341 131.773 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 6104.86 6104.86 0.370219 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00769694 48.8582 2448.76 0.00 6126.17 6126.17
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX 21079.219 21079.219 1.453079 0.00018441 445.520 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21079.22 21079.22 1.453079 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00771609 48.9775 6728.41 0.00 21155.26 21155.26
CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX 4799.914 4799.914 0.289495 0.00004199 103.708 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 4799.91 4799.91 0.289495 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00794062 50.3840 1939.56 0.00 4816.66 4816.66
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX 5818.669 5818.669 0.342167 0.00005090 126.300 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 5818.67 5818.67 0.342167 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00769594 48.8519 2439.60 0.00 5838.92 5838.92
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX 19033.613 19033.613 1.250788 0.00016651 405.278 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 19033.61 19033.61 1.250788 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00771450 48.9675 6680.69 0.00 19100.62 19100.62
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX 5992.716 5992.716 0.358496 0.00005243 129.670 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 5992.72 5992.72 0.358496 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00769732 48.8606 2452.39 0.00 6013.61 6013.61
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX 20731.528 20731.528 1.412222 0.00018137 438.928 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 20731.53 20731.53 1.412222 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00771793 48.9891 6784.18 0.00 20804.77 20804.77
CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX 4738.619 4738.619 0.282713 0.00004146 102.584 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 4738.62 4738.62 0.282713 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00794085 50.3854 1945.28 0.00 4755.14 4755.14
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX 5759.159 5759.159 0.333111 0.00005038 125.396 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 5759.16 5759.16 0.333111 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00769908 48.8716 2469.51 0.00 5779.17 5779.17
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX 12626.073 12626.073 0.811993 0.00011046 269.796 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 12626.07 12626.07 0.811993 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00772430 49.0290 4606.60 0.00 12670.43 12670.43
COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX 7045.913 7045.913 0.510375 0.00006164 147.828 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 7045.91 7045.91 0.510375 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00768848 48.8044 2005.63 0.00 7071.40 7071.40
MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX 6570.017 6570.017 0.278986 0.00005748 153.640 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 6570.02 6570.02 0.278986 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00791375 50.2156 3813.63 0.00 6591.61 6591.61
LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT LOBBY_ZN_1_FLR_1 VAV BOX 4780.933 4780.933 0.160189 0.00004183 120.983 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 4780.93 4780.93 0.160189 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00777541 49.3494 3198.71 0.00 4795.74 4795.74
MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_ZN_1_FLR_1 VAV BOX 923.367 923.367 0.086666 0.00000808 18.758 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 923.37 923.37 0.086666 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00510208 32.5198 71.50 0.00 926.76 926.76
BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 2700.301 2700.301 0.091081 0.00002362 68.154 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 2700.30 2700.30 0.091081 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00784695 49.7973 1800.54 0.00 2708.68 2708.68
OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT OFFICES_ZN_1_FLR_1 VAV BOX 9464.080 9464.080 0.319637 0.00008280 238.747 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 9464.08 9464.08 0.319637 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00775589 49.2269 6307.05 0.00 9493.44 9493.44
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10949.724 10949.724 0.577429 0.00009579 242.863 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 10949.72 10949.72 0.577429 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00772829 49.0539 5246.81 0.00 10987.40 10987.40
VAV_POD_1 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC VAV_POD_1 116206.712 87076.560 5.409831 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 115297.25 113547.51 5.409831 29.00 17.99 0.00860887 10.89 10.89 0.00850000 31.30 0.00823349 18.45 68.5116 24.00 0.00942561 49.7346 73055.60 0.00 116542.81 86389.30
VAV_POD_1 HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_POD_1 17345.570 17345.570 1.622949 0.00015175 298.183 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 17345.57 17345.57 1.622949 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 228.3719 21.00 0.00774703 49.1716 19053.77 0.00 17622.57 17622.57
VAV_POD_2 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC VAV_POD_2 115735.823 86698.852 5.383825 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 114845.53 113145.37 5.383825 29.02 18.00 0.00860630 10.89 10.89 0.00850000 31.30 0.00823349 18.45 68.8425 24.00 0.00943003 49.7576 72704.35 0.00 116070.56 86012.32
VAV_POD_2 HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_POD_2 17262.186 17262.186 1.615147 0.00015102 296.749 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 17262.19 17262.19 1.615147 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 229.4750 21.00 0.00774395 49.1523 18783.53 0.00 17537.86 17537.86
VAV_POD_3 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC VAV_POD_3 102597.883 77002.132 4.796503 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 101718.78 99970.09 4.796503 28.87 17.96 0.00862267 10.89 10.89 0.00850000 31.30 0.00823349 18.45 66.6917 24.00 0.00940189 49.6111 64773.42 0.00 102894.62 76380.73
VAV_POD_3 HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_POD_3 15379.053 15379.053 1.438951 0.00013454 264.377 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 15379.05 15379.05 1.438951 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 222.3057 21.00 0.00775003 49.1904 16991.36 0.00 15624.65 15624.65
VAV_OTHER COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC VAV_OTHER 107343.157 85166.135 5.598224 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 104611.01 100663.65 5.598224 26.39 17.22 0.00873665 11.00 11.00 0.00850000 31.30 0.00823349 18.45 32.7922 24.00 0.00898215 47.4209 75616.43 0.00 107653.62 84408.27
VAV_OTHER HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_OTHER 17949.615 17949.615 1.679467 0.00015703 308.567 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 17949.62 17949.62 1.679467 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 109.3073 21.00 0.00777220 49.3290 22441.21 0.00 18236.26 18236.26
PSZ-AC_2:5 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_2:5 27920.640 21769.444 1.406990 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 13960.32 12629.66 0.937993 27.75 18.05 0.00919251 12.80 11.93 0.00850000 31.30 0.00823349 18.45 58.0034 23.99 0.00980309 51.6995 18885.22 0.00 -999.00 -999.00
PSZ-AC_2:5 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_2:5 42858.589 42858.589 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 42858.59 42858.59 1.406988 14.35 10.81 0.00676350 40.00 20.96 0.00800000 3.80 0.00505843 3.80 38.6690 21.00 0.00783853 49.7445 2850.64 0.00 -999.00 -999.00
PSZ-AC_1:6 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_1:6 27792.320 21338.387 1.359860 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 13896.16 10936.98 0.906573 26.09 18.23 0.01010047 12.80 11.93 0.00850000 30.50 0.00823222 18.19 28.1074 23.99 0.01053127 55.5035 18345.45 0.00 -999.00 -999.00
PSZ-AC_1:6 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_1:6 63444.765 63444.765 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 63444.76 63444.76 1.359864 0.71 0.71 0.01719987 40.00 20.96 0.00800000 3.80 0.00505843 3.80 18.7382 26.70 0.01999958 88.3760 0.00 0.00 -999.00 -999.00
PSZ-AC_2:7 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_2:7 47552.110 35494.321 2.198930 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 23776.06 22036.10 1.465953 29.91 18.67 0.00908622 12.80 11.93 0.00850000 31.30 0.00823349 18.45 101.5193 23.98 0.01097682 57.8239 29336.42 0.00 -999.00 -999.00
PSZ-AC_2:7 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_2:7 80011.936 80011.936 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 80011.94 80011.94 2.198931 9.36 7.65 0.00592689 40.00 20.96 0.00800000 3.80 0.00505843 3.80 67.6795 21.00 0.00774544 49.1614 3693.79 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX CORNER_CLASS_1_POD_1_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 6143.498 6143.498 0.370909 0.00005375 132.713 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.1965 2.240749 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 6143.50 6143.50 1.0000 0.43833270 0.370909 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05374052 60.00 32.22 27.78 0.000 6143.50 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00770025 21.00 0.00770025 48.8790 2480.56 0.00 6164.94 6164.94 0.43833270 12.80 11.60 0.00800000 33059.8 26.59 16.87 0.00800000 47124.3
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX MULT_CLASS_1_POD_1_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 21406.963 21406.963 1.460012 0.00018728 453.143 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 7.6538 7.807869 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 21406.96 21406.96 1.0000 1.72541058 1.460012 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.18725835 60.00 32.22 27.78 0.000 21406.96 3.80 0.00505843 3.80 0.00000000 0.0000 20.78 0.00772464 21.00 0.00772464 49.0311 6987.46 0.00 21482.60 21482.60 1.72541058 12.80 11.60 0.00800000 33059.8 25.01 16.32 0.00800000 45510.5
CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX CORRIDOR_POD_1_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4806.023 4806.023 0.288482 0.00004205 103.929 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 1.7183 1.752925 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 4806.02 4806.02 1.0000 0.34092158 0.288482 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04204090 60.00 32.22 27.78 0.000 4806.02 3.80 0.00505843 3.80 0.00000000 0.0000 20.84 0.00794098 21.00 0.00794098 50.3862 1955.68 0.00 4822.79 4822.79 0.34092158 12.80 11.60 0.00800000 33059.8 26.67 16.90 0.00800000 47206.2
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX CORNER_CLASS_2_POD_1_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 5799.875 5799.875 0.340534 0.00005074 125.928 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.0737 2.115418 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 5799.88 5799.88 1.0000 0.40243605 0.340534 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05073466 60.00 32.22 27.78 0.000 5799.88 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00769566 21.00 0.00769566 48.8501 2436.94 0.00 5820.06 5820.06 0.40243605 12.80 11.60 0.00800000 33059.8 26.98 17.01 0.00800000 47521.9
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX MULT_CLASS_2_POD_1_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 18960.179 18960.179 1.244767 0.00016587 403.777 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 6.7790 6.915441 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 18960.18 18960.18 1.0000 1.47103860 1.244767 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.16585500 60.00 32.22 27.78 0.000 18960.18 3.80 0.00505843 3.80 0.00000000 0.0000 20.75 0.00771404 21.00 0.00771404 48.9646 6666.74 0.00 19026.92 19026.92 1.47103860 12.80 11.60 0.00800000 33059.8 25.48 16.49 0.00800000 45994.2
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX CORNER_CLASS_1_POD_2_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 6104.855 6104.855 0.370219 0.00005341 131.773 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.1827 2.226654 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 6104.86 6104.86 1.0000 0.43751633 0.370219 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05340249 60.00 32.22 27.78 0.000 6104.86 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00769694 21.00 0.00769694 48.8582 2448.76 0.00 6126.17 6126.17 0.43751633 12.80 11.60 0.00800000 33059.8 26.53 16.85 0.00800000 47062.0
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX MULT_CLASS_1_POD_2_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 21079.219 21079.219 1.453079 0.00018441 445.520 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 7.5367 7.688329 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 21079.22 21079.22 1.0000 1.71721785 1.453079 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.18439139 60.00 32.22 27.78 0.000 21079.22 3.80 0.00505843 3.80 0.00000000 0.0000 20.75 0.00771609 21.00 0.00771609 48.9775 6728.41 0.00 21155.26 21155.26 1.71721785 12.80 11.60 0.00800000 33059.8 24.88 16.27 0.00800000 45379.3
CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX CORRIDOR_POD_2_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4799.914 4799.914 0.289495 0.00004199 103.708 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 1.7162 1.750697 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 4799.91 4799.91 1.0000 0.34211896 0.289495 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04198746 60.00 32.22 27.78 0.000 4799.91 3.80 0.00505843 3.80 0.00000000 0.0000 20.84 0.00794062 21.00 0.00794062 50.3840 1939.56 0.00 4816.66 4816.66 0.34211896 12.80 11.60 0.00800000 33059.8 26.61 16.88 0.00800000 47138.7
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX CORNER_CLASS_2_POD_2_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 5818.669 5818.669 0.342167 0.00005090 126.300 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.0804 2.122272 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 5818.67 5818.67 1.0000 0.40436599 0.342167 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05089906 60.00 32.22 27.78 0.000 5818.67 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00769594 21.00 0.00769594 48.8519 2439.60 0.00 5838.92 5838.92 0.40436599 12.80 11.60 0.00800000 33059.8 26.96 17.00 0.00800000 47499.5
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX MULT_CLASS_2_POD_2_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 19033.613 19033.613 1.250788 0.00016651 405.278 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 6.8053 6.942225 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 19033.61 19033.61 1.0000 1.47815467 1.250788 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.16649736 60.00 32.22 27.78 0.000 19033.61 3.80 0.00505843 3.80 0.00000000 0.0000 20.75 0.00771450 21.00 0.00771450 48.9675 6680.69 0.00 19100.62 19100.62 1.47815467 12.80 11.60 0.00800000 33059.8 25.47 16.48 0.00800000 45981.8
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX CORNER_CLASS_1_POD_3_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 5992.716 5992.716 0.358496 0.00005243 129.670 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.1426 2.185753 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 5992.72 5992.72 1.0000 0.42366293 0.358496 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05242154 60.00 32.22 27.78 0.000 5992.72 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00769732 21.00 0.00769732 48.8606 2452.39 0.00 6013.61 6013.61 0.42366293 12.80 11.60 0.00800000 33059.8 26.72 16.92 0.00800000 47254.2
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX MULT_CLASS_1_POD_3_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 20731.528 20731.528 1.412222 0.00018137 438.928 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 7.4123 7.561514 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 20731.53 20731.53 1.0000 1.66893399 1.412222 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.18134995 60.00 32.22 27.78 0.000 20731.53 3.80 0.00505843 3.80 0.00000000 0.0000 20.75 0.00771793 21.00 0.00771793 48.9891 6784.18 0.00 20804.77 20804.77 1.66893399 12.80 11.60 0.00800000 33059.8 25.02 16.32 0.00800000 45525.7
CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX CORRIDOR_POD_3_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4738.619 4738.619 0.282713 0.00004146 102.584 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 1.6942 1.728340 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 4738.62 4738.62 1.0000 0.33410414 0.282713 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04145128 60.00 32.22 27.78 0.000 4738.62 3.80 0.00505843 3.80 0.00000000 0.0000 20.84 0.00794085 21.00 0.00794085 50.3854 1945.28 0.00 4755.14 4755.14 0.33410414 12.80 11.60 0.00800000 33059.8 26.76 16.93 0.00800000 47292.3
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX CORNER_CLASS_2_POD_3_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 5759.159 5759.159 0.333111 0.00005038 125.396 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.0591 2.100567 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 5759.16 5759.16 1.0000 0.39366312 0.333111 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05037850 60.00 32.22 27.78 0.000 5759.16 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00769908 21.00 0.00769908 48.8716 2469.51 0.00 5779.17 5779.17 0.39366312 12.80 11.60 0.00800000 33059.8 27.20 17.08 0.00800000 47740.3
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX MULT_CLASS_2_POD_3_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 12626.073 12626.073 0.811993 0.00011046 269.796 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 4.5143 4.605171 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 12626.07 12626.07 1.0000 0.95959597 0.811993 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.11044712 60.00 32.22 27.78 0.000 12626.07 3.80 0.00505843 3.80 0.00000000 0.0000 20.78 0.00772430 21.00 0.00772430 49.0290 4606.60 0.00 12670.43 12670.43 0.95959597 12.80 11.60 0.00800000 33059.8 25.75 16.58 0.00800000 46263.7
COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPUTER_CLASS_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 7045.913 7045.913 0.510375 0.00006164 147.828 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.5192 2.569891 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 7045.91 7045.91 1.0000 0.60315035 0.510375 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.06163443 60.00 32.22 27.78 0.000 7045.91 3.80 0.00505843 3.80 0.00000000 0.0000 20.80 0.00768848 21.00 0.00768848 48.8044 2005.63 0.00 7071.40 7071.40 0.60315035 12.80 11.60 0.00800000 33059.8 24.30 16.06 0.00800000 44783.9
MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX MAIN_CORRIDOR_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 6570.017 6570.017 0.278986 0.00005748 153.640 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 2.3490 2.396315 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 6570.02 6570.02 1.0000 0.32970021 0.278986 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05747151 60.00 32.22 27.78 0.000 6570.02 3.80 0.00505843 3.80 0.00000000 0.0000 20.69 0.00791375 21.00 0.00791375 50.2156 3813.63 0.00 6591.61 6591.61 0.32970021 12.80 11.60 0.00800000 33059.8 32.41 18.83 0.00800000 53052.6
LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT LOBBY_ZN_1_FLR_1 VAV BOX LOBBY_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4780.933 4780.933 0.160189 0.00004183 120.983 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 1.7094 1.743774 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 4780.93 4780.93 1.0000 0.18930815 0.160189 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04182142 60.00 32.22 27.78 0.000 4780.93 3.80 0.00505843 3.80 0.00000000 0.0000 20.76 0.00777541 21.00 0.00777541 49.3494 3198.71 0.00 4795.74 4795.74 0.18930815 12.80 11.60 0.00800000 33059.8 37.64 20.47 0.00800000 58392.8
MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_ZN_1_FLR_1 VAV BOX MECH_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 923.367 923.367 0.086666 0.00000808 18.758 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 0.3301 0.336784 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 923.37 923.37 1.0000 0.10241948 0.086666 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.00807719 60.00 32.22 27.78 0.000 923.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00510208 21.00 0.00510208 32.5198 71.50 0.00 926.76 926.76 0.10241948 12.80 11.60 0.00800000 33059.8 21.67 15.10 0.00800000 42108.5
BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BATH_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2700.301 2700.301 0.091081 0.00002362 68.154 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 0.9655 0.984894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 2700.30 2700.30 1.0000 0.10763779 0.091081 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.02362100 60.00 32.22 27.78 0.000 2700.30 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00784695 21.00 0.00784695 49.7973 1800.54 0.00 2708.68 2708.68 0.10763779 12.80 11.60 0.00800000 33059.8 37.48 20.42 0.00800000 58224.6
OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT OFFICES_ZN_1_FLR_1 VAV BOX OFFICES_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 9464.080 9464.080 0.319637 0.00008280 238.747 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 3.3838 3.451881 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 9464.08 9464.08 1.0000 0.37774044 0.319637 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.08278745 60.00 32.22 27.78 0.000 9464.08 3.80 0.00505843 3.80 0.00000000 0.0000 20.75 0.00775589 21.00 0.00775589 49.2269 6307.05 0.00 9493.44 9493.44 0.37774044 12.80 11.60 0.00800000 33059.8 37.45 20.41 0.00800000 58192.0
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 N/A N/A N/A Yes Yes Yes No 10949.724 10949.724 0.577429 0.00009579 242.863 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 3.9150 3.993747 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 10949.72 10949.72 1.0000 0.68239295 0.577429 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.09578319 60.00 32.22 27.78 0.000 10949.72 3.80 0.00505843 3.80 0.00000000 0.0000 20.78 0.00772829 21.00 0.00772829 49.0539 5246.81 0.00 10987.40 10987.40 0.68239295 12.80 11.60 0.00800000 33059.8 28.59 17.56 0.00800000 49161.1
VAV_POD_1 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC VAV_POD_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 116206.712 87076.560 5.409831 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.8435 1004.8586 1.1818 VAV_POD_1 FAN Fan:VariableVolume 5.409831 6.39322298   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 Sensible 115297.25 113547.51 0.9922 6.39322298 5.409831 29.00 17.99 0.00860887 51134.8 10.89 10.89 0.00850000 32377.7 -999.0 -999.00 -999.00 -999.00 12434.289 102862.96 31.30 0.00823349 18.45 3.70636000 68.5116 24.00 0.00942561 24.00 0.00942561 49.7346 73055.60 0.00 116542.81 86389.30 6.14073901 26.67 19.44 0.01118466 55322.4 12.90 12.89 0.00925940 36343.8
VAV_POD_1 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_POD_1 CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 17345.570 17345.570 1.622949 0.00015175 298.183 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_POD_1 FAN Fan:VariableVolume 5.409831 6.39322298   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 6.2017 6.326536 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 Sensible 17345.57 17345.57 1.0000 1.91796690 1.622949 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 0.15173113 60.00 32.22 27.78 0.000 17345.57 3.80 0.00505843 3.80 3.70636000 228.3719 21.04 0.00773409 21.00 0.00774703 49.1716 19053.77 0.00 17622.57 17622.57 1.91796690 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
VAV_POD_2 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC VAV_POD_2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 115735.823 86698.852 5.383825 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.8387 1004.8586 1.1818 VAV_POD_2 FAN Fan:VariableVolume 5.383825 6.36248950   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 114845.53 113145.37 0.9923 6.36248950 5.383825 29.02 18.00 0.00860630 51152.9 10.89 10.89 0.00850000 32377.7 -999.0 -999.00 -999.00 -999.00 12374.515 102471.02 31.30 0.00823349 18.45 3.70636000 68.8425 24.00 0.00943003 24.00 0.00943003 49.7576 72704.35 0.00 116070.56 86012.32 6.11121927 26.67 19.44 0.01118466 55322.4 12.90 12.88 0.00925621 36329.4
VAV_POD_2 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_POD_2 CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 17262.186 17262.186 1.615147 0.00015102 296.749 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_POD_2 FAN Fan:VariableVolume 5.383825 6.36248950   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 6.1719 6.296123 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 Sensible 17262.19 17262.19 1.0000 1.90874685 1.615147 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 0.15100173 60.00 32.22 27.78 0.000 17262.19 3.80 0.00505843 3.80 3.70636000 229.4750 21.04 0.00773046 21.00 0.00774395 49.1523 18783.53 0.00 17537.86 17537.86 1.90874685 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
VAV_POD_3 COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC VAV_POD_3 CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 102597.883 77002.132 4.796503 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.8691 1004.8586 1.1818 VAV_POD_3 FAN Fan:VariableVolume 4.796503 5.66840511   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 Sensible 101718.78 99970.09 0.9914 5.66840511 4.796503 28.87 17.96 0.00862267 51034.4 10.89 10.89 0.00850000 32377.7 -999.0 -999.00 -999.00 -999.00 11024.578 90694.20 31.30 0.00823349 18.45 3.19887000 66.6917 24.00 0.00940189 24.00 0.00940189 49.6111 64773.42 0.00 102894.62 76380.73 5.44454596 26.67 19.44 0.01118466 55322.4 12.94 12.92 0.00927532 36423.7
VAV_POD_3 HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_POD_3 CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15379.053 15379.053 1.438951 0.00013454 264.377 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_POD_3 FAN Fan:VariableVolume 4.796503 5.66840511   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 5.4986 5.609279 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:30:00 Sensible 15379.05 15379.05 1.0000 1.70052153 1.438951 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 0.13452894 60.00 32.22 27.78 0.000 15379.05 3.80 0.00505843 3.80 3.19887000 222.3057 21.04 0.00773602 21.00 0.00775003 49.1904 16991.36 0.00 15624.65 15624.65 1.70052153 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
VAV_OTHER COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC VAV_OTHER COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 107343.157 85166.135 5.598224 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.0810 1004.8586 1.1818 VAV_OTHER FAN Fan:VariableVolume 5.598224 6.61586193   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 104611.01 100663.65 0.9745 6.61586193 5.598224 26.39 17.22 0.00873665 48799.0 11.00 11.00 0.00850000 32482.6 -999.0 -999.00 -999.00 -999.00 12175.513 92435.50 31.30 0.00823349 18.45 1.83578000 32.7922 24.00 0.00898215 24.00 0.00898215 47.4209 75616.43 0.00 107653.62 84408.27 6.35458539 26.67 19.44 0.01118466 55322.4 13.68 13.67 0.00975042 38381.3
VAV_OTHER HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_OTHER COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 17949.615 17949.615 1.679467 0.00015703 308.567 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_OTHER FAN Fan:VariableVolume 5.598224 6.61586193   4197.9300 999.8980 2.39832861 54.44 82.22 27.78 279689.47 6.4177 6.546853 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 Sensible 17949.62 17949.62 1.0000 1.98475858 1.679467 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 0.15701505 60.00 32.22 27.78 0.000 17949.62 3.80 0.00505843 3.80 1.83578000 109.3073 20.78 0.00775427 21.00 0.00777220 49.3290 22441.21 0.00 18236.26 18236.26 1.98475858 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
PSZ-AC_2:5 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_2:5 GYM_ZN_1_FLR_1 Coincident CoolingDesignCapacity N/A No No unknown No 27920.640 21769.444 1.406990 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.9284 1004.8586 1.1818 PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.406988 1.66274837   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 Sensible 13960.32 12629.66 1.0000 1.10850051 0.937993 27.75 18.05 0.00919251 51351.7 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 13960.32 31.30 0.00823349 18.45 0.54406764 58.0034 23.99 0.00980309 23.99 0.00980309 51.6995 18885.22 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:5 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_2:5 GYM_ZN_1_FLR_1 Coincident HeatingDesignCapacity N/A Yes No unknown No 42858.589 42858.589 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.406988 1.66274837   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 42858.59 42858.59 1.0000 1.66274837 1.406988 14.35 10.81 0.00676350 31513.8 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 42858.59 3.80 0.00505843 3.80 0.54406764 38.6690 21.00 0.00783853 21.00 0.00783853 49.7445 2850.64 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_1:6 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_1:6 KITCHEN_ZN_1_FLR_1 Coincident CoolingDesignCapacity N/A No No unknown No 27792.320 21338.387 1.359860 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.6163 1004.8586 1.1818 PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.359864 1.60705777   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 Sensible 13896.16 10936.98 1.0000 1.07136902 0.906573 26.09 18.23 0.01010047 51967.5 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 13896.16 30.50 0.00823222 18.19 0.25481392 28.1074 23.95 0.01053127 23.99 0.01053127 55.5035 18345.45 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_1:6 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_1:6 KITCHEN_ZN_1_FLR_1 Coincident HeatingDesignCapacity N/A Yes No unknown No 63444.765 63444.765 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.359864 1.60705777   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 63444.76 63444.76 1.0000 1.60705777 1.359864 0.71 0.71 0.01719987 43754.1 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 63444.76 3.80 0.00505843 3.80 0.25481392 18.7382 0.00 0.01999958 26.70 0.01999958 88.3760 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:7 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_2:7 CAFETERIA_ZN_1_FLR_1 Coincident CoolingDesignCapacity N/A No No unknown No 47552.110 35494.321 2.198930 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.7308 1004.8586 1.1818 PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.198931 2.59864926   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 Sensible 23776.06 22036.10 1.0000 1.73243237 1.465953 29.91 18.67 0.00908622 53285.8 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 23776.06 31.30 0.00823349 18.45 1.48822502 101.5193 23.98 0.01097682 23.98 0.01097682 57.8239 29336.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:7 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_2:7 CAFETERIA_ZN_1_FLR_1 Coincident HeatingDesignCapacity N/A Yes No unknown No 80011.936 80011.936 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.198931 2.59864926   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 80011.94 80011.94 1.0000 2.59864926 2.198931 9.36 7.65 0.00592689 24330.3 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 80011.94 3.80 0.00505843 3.80 1.48822502 67.6795 21.00 0.00774544 21.00 0.00774544 49.1614 3693.79 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_POD_1_OA_CONTROLLER DifferentialDryBulb 0.00 5.41 -      
VAV_POD_2_OA_CONTROLLER DifferentialDryBulb 0.00 5.38 -      
VAV_POD_3_OA_CONTROLLER DifferentialDryBulb 0.00 4.80 -      
VAV_OTHER_OA_CONTROLLER DifferentialDryBulb 0.00 5.60 -      
PSZ-AC_2:5_OA_CONTROLLER DifferentialDryBulb 0.54 1.41 -      
PSZ-AC_1:6_OA_CONTROLLER DifferentialDryBulb 0.25 1.36 -      
PSZ-AC_2:7_OA_CONTROLLER DifferentialDryBulb 1.49 2.20 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_POD_1_ZN_1_FLR_1 VAV_POD_1_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_POD_2_ZN_1_FLR_1 VAV_POD_2_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_POD_3_ZN_1_FLR_1 VAV_POD_3_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
COMPUTER_CLASS_ZN_1_FLR_1 VAV_OTHER_DCV 0.004719 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MAIN_CORRIDOR_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000559 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
BATH_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
OFFICES_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV_OTHER_DCV 0.000000 0.000864 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 561.00 2299.00 2.83
MULT_CLASS_1_POD_1_ZN_1_FLR_1 815.17 1982.17 0.17
CORRIDOR_POD_1_ZN_1_FLR_1 149.67 2821.50 1.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 208.33 2920.33 55.17
MULT_CLASS_2_POD_1_ZN_1_FLR_1 344.00 2682.67 16.83
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 536.83 2329.17 3.50
MULT_CLASS_1_POD_2_ZN_1_FLR_1 789.33 2001.17 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 153.17 2816.00 1.50
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 215.33 2911.50 55.17
MULT_CLASS_2_POD_2_ZN_1_FLR_1 346.67 2681.33 17.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 621.33 2218.00 2.50
MULT_CLASS_1_POD_3_ZN_1_FLR_1 978.50 1764.50 1.83
CORRIDOR_POD_3_ZN_1_FLR_1 245.00 2607.83 0.50
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 258.33 2837.33 53.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 386.33 2618.50 15.50
COMPUTER_CLASS_ZN_1_FLR_1 801.00 2020.50 19.83
MAIN_CORRIDOR_ZN_1_FLR_1 1412.67 810.83 0.00
LOBBY_ZN_1_FLR_1 682.50 2405.50 194.33
MECH_ZN_1_FLR_1 3123.17 47.67 15.00
BATH_ZN_1_FLR_1 2321.83 750.50 152.67
OFFICES_ZN_1_FLR_1 1461.83 395.67 0.00
GYM_ZN_1_FLR_1 2453.83 338.50 77.67
KITCHEN_ZN_1_FLR_1 3220.00 61.50 61.50
CAFETERIA_ZN_1_FLR_1 1899.00 745.50 205.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 1794.00 703.00 0.00
Facility 3253.67 3179.83 538.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.33 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.17 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 0.00 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 272.00 35.33 115.83 31.83
MECH_ZN_1_FLR_1 0.00 0.17 0.00 0.00
BATH_ZN_1_FLR_1 0.00 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 0.00 3.67 0.00 0.00
GYM_ZN_1_FLR_1 0.00 7.50 0.00 0.00
KITCHEN_ZN_1_FLR_1 0.00 1247.00 0.00 9.17
CAFETERIA_ZN_1_FLR_1 0.00 3.50 0.00 2.33
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.00 0.00 0.00 0.00
Facility 272.00 1287.33 115.83 37.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 14.35 26.64 396.00 3.021 0.021 0.000 0.000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 69.12 128.36 1908.00 2.573 0.011 0.000 0.000
CORRIDOR_POD_1_ZN_1_FLR_1 5.56 10.33 768.00 1.197 0.002 0.000 0.000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 14.35 26.64 396.00 2.728 0.021 0.000 0.000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 69.12 128.36 1908.00 2.093 0.011 0.000 0.000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 14.35 26.64 396.00 3.012 0.021 0.000 0.000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 69.12 128.36 1908.00 2.550 0.011 0.000 0.000
CORRIDOR_POD_2_ZN_1_FLR_1 5.56 10.33 768.00 1.201 0.002 0.000 0.000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 14.35 26.64 396.00 2.740 0.021 0.000 0.000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 69.12 128.36 1908.00 2.102 0.011 0.000 0.000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 14.35 26.64 396.00 2.952 0.021 0.000 0.000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 69.12 128.36 1908.00 2.570 0.011 0.000 0.000
CORRIDOR_POD_3_ZN_1_FLR_1 5.56 10.33 768.00 1.186 0.002 0.000 0.000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 14.35 26.64 396.00 2.691 0.021 0.000 0.000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 45.65 84.77 1260.00 2.088 0.011 0.000 0.000
COMPUTER_CLASS_ZN_1_FLR_1 38.16 43.60 648.00 2.692 0.011 0.000 0.000
MAIN_CORRIDOR_ZN_1_FLR_1 15.83 29.39 2184.00 0.776 0.002 0.000 0.000
LOBBY_ZN_1_FLR_1 9.91 18.41 684.00 0.884 2.709 0.000 0.000
MECH_ZN_1_FLR_1 2.19 4.07 1008.00 0.366 0.000 0.000 0.000
BATH_ZN_1_FLR_1 5.51 10.23 760.00 0.414 0.005 0.000 0.000
OFFICES_ZN_1_FLR_1 14.92 23.74 1764.00 1.340 0.009 0.000 0.000
GYM_ZN_1_FLR_1 64.64 115.31 1428.00 2.150 0.005 0.000 0.000
KITCHEN_ZN_1_FLR_1 14.54 26.99 672.00 4.703 0.005 0.000 0.000
CAFETERIA_ZN_1_FLR_1 209.95 339.07 1260.00 4.325 0.013 0.000 0.000
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 23.13 42.95 1596.00 1.748 0.010 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 14.35 26.64 396.00 0.939 0.000 0.000 0.000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 69.12 128.36 1908.00 0.767 0.000 0.000 0.000
CORRIDOR_POD_1_ZN_1_FLR_1 5.56 10.33 768.00 0.336 0.000 0.000 0.000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 14.35 26.64 396.00 0.741 0.000 0.000 0.000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 69.12 128.36 1908.00 0.562 0.000 0.000 0.000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 14.35 26.64 396.00 0.935 0.000 0.000 0.000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 69.12 128.36 1908.00 0.762 0.000 0.000 0.000
CORRIDOR_POD_2_ZN_1_FLR_1 5.56 10.33 768.00 0.339 0.000 0.000 0.000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 14.35 26.64 396.00 0.746 0.000 0.000 0.000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 69.12 128.36 1908.00 0.566 0.000 0.000 0.000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 14.35 26.64 396.00 0.917 0.000 0.000 0.000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 69.12 128.36 1908.00 0.749 0.000 0.000 0.000
CORRIDOR_POD_3_ZN_1_FLR_1 5.56 10.33 768.00 0.319 0.000 0.000 0.000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 14.35 26.64 396.00 0.704 0.000 0.000 0.000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 45.65 84.77 1260.00 0.532 0.000 0.000 0.000
COMPUTER_CLASS_ZN_1_FLR_1 38.16 43.60 648.00 0.846 0.000 0.000 0.000
MAIN_CORRIDOR_ZN_1_FLR_1 15.83 29.39 2184.00 0.213 0.000 0.000 0.000
LOBBY_ZN_1_FLR_1 9.91 18.41 684.00 0.348 0.000 0.000 0.000
MECH_ZN_1_FLR_1 2.19 4.07 1008.00 0.102 0.000 0.000 0.000
BATH_ZN_1_FLR_1 5.51 10.23 760.00 0.130 0.000 0.000 0.000
OFFICES_ZN_1_FLR_1 14.92 23.74 1764.00 0.352 0.000 0.000 0.000
GYM_ZN_1_FLR_1 64.64 115.31 1428.00 1.363 0.000 0.000 0.000
KITCHEN_ZN_1_FLR_1 14.54 26.99 672.00 1.381 0.000 0.000 0.000
CAFETERIA_ZN_1_FLR_1 209.95 339.07 1260.00 4.113 0.000 0.000 0.000
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 23.13 42.95 1596.00 0.574 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 69.12 128.36 1908.00 477.00 0.0000 0.291
CORRIDOR_POD_1_ZN_1_FLR_1 VAV_POD_1 5.56 10.33 768.00 192.00 0.0000 0.059
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 69.12 128.36 1908.00 477.00 0.0000 0.291
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 69.12 128.36 1908.00 477.00 0.0000 0.291
CORRIDOR_POD_2_ZN_1_FLR_1 VAV_POD_2 5.56 10.33 768.00 192.00 0.0000 0.059
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 69.12 128.36 1908.00 477.00 0.0000 0.291
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 69.12 128.36 1908.00 477.00 0.0000 0.291
CORRIDOR_POD_3_ZN_1_FLR_1 VAV_POD_3 5.56 10.33 768.00 192.00 0.0000 0.059
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 14.35 26.64 396.00 99.00 0.0000 0.060
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 45.65 84.77 1260.00 315.00 0.0000 0.192
COMPUTER_CLASS_ZN_1_FLR_1 VAV_OTHER 38.16 43.60 648.00 162.00 0.0000 0.099
MAIN_CORRIDOR_ZN_1_FLR_1 VAV_OTHER 15.83 29.39 2184.00 546.00 0.0000 0.166
LOBBY_ZN_1_FLR_1 VAV_OTHER 9.91 18.41 684.00 171.00 0.0000 0.096
MECH_ZN_1_FLR_1 VAV_OTHER 2.19 4.07 1008.00 252.00 0.0000 0.000
BATH_ZN_1_FLR_1 VAV_OTHER 5.51 10.23 760.00 190.00 0.0000 0.000
OFFICES_ZN_1_FLR_1 VAV_OTHER 14.92 23.74 1764.00 441.00 0.0000 0.190
GYM_ZN_1_FLR_1 PSZ-AC_2:5 64.64 115.31 1428.00 357.00 0.5441 0.544
KITCHEN_ZN_1_FLR_1 PSZ-AC_1:6 14.54 26.99 672.00 168.00 0.4528 0.198
CAFETERIA_ZN_1_FLR_1 PSZ-AC_2:7 209.95 339.07 1260.00 315.00 1.4882 0.288
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV_OTHER 23.13 42.95 1596.00 399.00 0.0000 0.345
Total Facility   892.82 1571.19 27484.00 6871.00 2.4851 4.109


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 4226879.27 0.00 4226879.27 137800.90 4364680.17 2670255.53 5157.43 0.00 3602.57 326.58
MULT_CLASS_1_POD_1_ZN_1_FLR_1 17261405.33 0.00 17261405.33 365172.40 17626577.72 12865776.65 5157.43 0.00 3602.57 326.58
CORRIDOR_POD_1_ZN_1_FLR_1 3251436.49 0.00 3251436.49 20670.14 3272106.63 1845537.18 5157.43 0.00 3602.57 326.58
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 3828322.14 0.00 3828322.14 137800.90 3966123.04 2670255.53 5161.31 2.11 3596.57 326.58
MULT_CLASS_2_POD_1_ZN_1_FLR_1 14103326.51 0.00 14103326.51 365172.40 14468498.91 12865776.65 5665.67 4.05 3090.29 326.58
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 4197243.69 0.00 4197243.69 137800.90 4335044.60 2670255.53 5171.40 0.00 3588.60 312.60
MULT_CLASS_1_POD_2_ZN_1_FLR_1 17040515.26 0.00 17040515.26 365172.40 17405687.66 12865776.65 5171.40 0.50 3588.10 312.60
CORRIDOR_POD_2_ZN_1_FLR_1 3247383.56 0.00 3247383.56 20670.14 3268053.70 1845537.18 5171.40 0.00 3588.60 312.60
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 3828671.30 0.00 3828671.30 137800.90 3966472.21 2670255.53 5174.73 2.50 3582.77 312.60
MULT_CLASS_2_POD_2_ZN_1_FLR_1 14104048.27 0.00 14104048.27 365172.40 14469220.67 12865776.65 5680.67 2.99 3076.34 312.60
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 4130064.06 0.00 4130064.06 137800.90 4267864.96 2670255.53 5153.49 0.00 3606.51 330.51
MULT_CLASS_1_POD_3_ZN_1_FLR_1 17200965.45 0.00 17200965.45 365172.40 17566137.85 12865776.65 5153.49 0.00 3606.51 330.51
CORRIDOR_POD_3_ZN_1_FLR_1 3218837.41 0.00 3218837.41 20670.14 3239507.54 1845537.18 5153.49 0.00 3606.51 330.51
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 3776482.12 0.00 3776482.12 137800.90 3914283.02 2670255.53 5160.16 4.00 3595.84 330.51
MULT_CLASS_2_POD_3_ZN_1_FLR_1 9295631.09 0.00 9295631.09 241151.58 9536782.67 8496267.60 5633.63 4.29 3122.07 330.51
COMPUTER_CLASS_ZN_1_FLR_1 6322211.28 0.00 6322211.28 124020.81 6446232.09 5228855.46 5225.55 29.63 3504.83 474.05
MAIN_CORRIDOR_ZN_1_FLR_1 5815638.03 0.00 5815638.03 62010.41 5877648.43 5248246.35 5135.55 14.12 3610.33 474.05
LOBBY_ZN_1_FLR_1 2221479.28 0.00 2221479.28 8852648.47 11074127.75 3013410.78 5158.95 9.88 3591.17 474.05
MECH_ZN_1_FLR_1 1316869.26 0.00 1316869.26 0.00 1316869.26 0.00 0.00 0.00 3750.05 474.05
BATH_ZN_1_FLR_1 1136154.43 0.00 1136154.43 68900.45 1205054.89 0.00 0.00 0.00 3750.05 474.05
OFFICES_ZN_1_FLR_1 8234501.46 0.00 8234501.46 289381.90 8523883.36 6005204.96 5128.44 11.01 3620.55 978.05
GYM_ZN_1_FLR_1 10470799.79 0.00 10470799.79 117130.77 10587930.56 17157717.19 5361.33 506.98 2891.69 446.54
KITCHEN_ZN_1_FLR_1 14665675.18 0.00 14665675.18 55120.36 14720795.55 6482703.52 3316.17 22.90 5420.93 3568.62
CAFETERIA_ZN_1_FLR_1 17694984.57 0.00 17694984.57 248041.63 17943026.20 16140030.55 5373.29 1.80 3384.91 781.16
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 9753516.56 0.00 9753516.56 275601.81 10029118.37 10866548.77 5217.53 16.93 3525.54 474.05
Total Facility 0.20E+09 0.00 0.20E+09 13048686.02 0.21E+09 0.16E+09 5978.59 539.33 5591.76 4815.07


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.3261 0.0000 0.3261 0.0022 0.3284 0.1254 0.00 0.00 3276.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 1.3365 0.0000 1.3365 0.0059 1.3423 0.6042 0.00 0.00 3276.00
CORRIDOR_POD_1_ZN_1_FLR_1 0.2506 0.0000 0.2506 0.0003 0.2510 0.0585 0.00 0.00 3276.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.2950 0.0000 0.2950 0.0022 0.2972 0.1254 3.89 2.11 3270.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 1.0876 0.0000 1.0876 0.0059 1.0935 0.6042 508.24 4.05 2763.71
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.3252 0.0000 0.3252 0.0022 0.3275 0.1254 0.00 0.00 3276.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 1.3245 0.0000 1.3245 0.0059 1.3304 0.6042 0.00 0.50 3275.50
CORRIDOR_POD_2_ZN_1_FLR_1 0.2514 0.0000 0.2514 0.0003 0.2517 0.0585 0.00 0.00 3276.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.2963 0.0000 0.2963 0.0022 0.2986 0.1254 3.33 2.50 3270.17
MULT_CLASS_2_POD_2_ZN_1_FLR_1 1.0925 0.0000 1.0925 0.0059 1.0983 0.6042 509.28 2.99 2763.74
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.3186 0.0000 0.3186 0.0022 0.3208 0.1254 0.00 0.00 3276.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 1.3337 0.0000 1.3337 0.0059 1.3396 0.6042 0.00 0.00 3276.00
CORRIDOR_POD_3_ZN_1_FLR_1 0.2480 0.0000 0.2480 0.0003 0.2484 0.0585 0.00 0.00 3276.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.2909 0.0000 0.2909 0.0022 0.2931 0.1254 6.67 4.00 3265.33
MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.7166 0.0000 0.7166 0.0039 0.7205 0.3990 480.14 4.29 2791.56
COMPUTER_CLASS_ZN_1_FLR_1 0.4739 0.0000 0.4739 0.0020 0.4759 0.2780 181.88 29.63 3064.50
MAIN_CORRIDOR_ZN_1_FLR_1 0.4590 0.0000 0.4590 0.0010 0.4600 0.1664 50.58 11.88 3213.53
LOBBY_ZN_1_FLR_1 0.1649 0.0000 0.1649 0.5058 0.6707 0.0956 109.11 9.25 3157.64
MECH_ZN_1_FLR_1 0.0991 0.0000 0.0991 0.0000 0.0991 0.0000 0.00 0.00 3276.00
BATH_ZN_1_FLR_1 0.0849 0.0000 0.0849 0.0011 0.0860 0.0000 0.00 0.00 3276.00
OFFICES_ZN_1_FLR_1 0.6410 0.0000 0.6410 0.0044 0.6454 0.1904 42.99 8.83 2720.18
GYM_ZN_1_FLR_1 0.8319 0.0000 0.8319 0.0019 0.8338 0.5441 0.00 494.87 2781.13
KITCHEN_ZN_1_FLR_1 0.8557 0.0000 0.8557 0.0009 0.8566 0.2182 0.00 0.00 3276.00
CAFETERIA_ZN_1_FLR_1 1.4762 0.0000 1.4762 0.0043 1.4805 1.0066 0.00 0.00 2728.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.7564 0.0000 0.7564 0.0044 0.7609 0.3446 132.55 14.72 3128.74
Total Facility 15.3368 0.0000 15.3368 0.5733 15.9101 7.1915 543.09 499.70 3276.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_POD_1 59594869.55 0.00 59594869.55 32917601.53 5157.43 0.00 3602.57 326.58
VAV_POD_2 59240820.57 0.00 59240820.57 32917601.53 5171.40 0.00 3588.60 312.60
VAV_POD_3 52542887.93 0.00 52542887.93 28548092.48 5153.49 0.00 3606.51 330.51
VAV_OTHER 48602225.36 0.00 48602225.36 30362266.32 5044.03 0.03 3715.93 474.05
PSZ-AC_2:5 14623533.09 0.00 14623533.09 17157717.19 5284.59 4.80 3470.61 446.53
PSZ-AC_1:6 20482094.31 0.00 20482094.31 6482703.52 2956.90 20.32 5782.78 3568.62
PSZ-AC_2:7 24712812.26 0.00 24712812.26 16140030.55 5336.00 2.13 3421.86 781.15


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_POD_1 4.6030 0.0000 4.6030 1.5176 0.00 0.00 3276.00
VAV_POD_2 4.5948 0.0000 4.5948 1.5176 0.00 0.00 3276.00
VAV_POD_3 4.0611 0.0000 4.0611 1.3124 0.00 0.00 3276.00
VAV_OTHER 3.7647 0.0000 3.7647 1.0750 0.00 0.00 3276.00
PSZ-AC_2:5 1.1618 0.0000 1.1618 0.5441 0.00 0.00 3276.00
PSZ-AC_1:6 1.1951 0.0000 1.1951 0.2182 0.00 0.00 3276.00
PSZ-AC_2:7 2.0617 0.0000 2.0617 1.0066 0.00 0.00 2728.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_POD_1 0.00 0.00 3101.23 0.00 0.00 0.00 501.35 0.00 0.00 0.00
VAV_POD_2 0.00 0.00 3086.55 0.00 0.00 0.00 502.05 0.00 0.00 0.00
VAV_POD_3 0.00 0.00 3133.40 0.00 0.00 0.00 473.11 0.00 0.00 0.00
VAV_OTHER 0.00 0.00 3499.50 33.72 0.00 0.00 216.83 0.00 0.00 0.00
PSZ-AC_2:5 0.00 53.67 3131.27 537.59 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC_1:6 0.00 221.03 5015.23 1608.37 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC_2:7 0.00 270.94 485.21 44.16 2708.84 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_POD_1 0.0000 0.0000 5.0751 0.0000 0.0000 0.0000 1.9984 0.0000 0.0000 0.0000
VAV_POD_2 0.0000 0.0000 5.0684 0.0000 0.0000 0.0000 1.9876 0.0000 0.0000 0.0000
VAV_POD_3 0.0000 0.0000 4.4456 0.0000 0.0000 0.0000 1.7921 0.0000 0.0000 0.0000
VAV_OTHER 0.0000 0.0000 3.8958 0.0000 0.0000 0.0000 1.9251 0.0000 0.0000 0.0000
PSZ-AC_2:5 0.0000 0.7694 1.2324 0.7616 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC_1:6 0.0000 0.3559 1.2563 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC_2:7 0.0000 2.0969 2.3221 0.0000 2.0288 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Surfaces by Class

Total Outdoors
Wall 121 33
Floor 25 24
Roof 25 25
Internal Mass 25 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 67 67
Door 25 25
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 7
Conditioned Zones 25
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1320
Defaulted Fields 1018
Fields with Defaults 4324
Autosized Fields 325
Autosizable Fields 484
Autocalculated Fields 317
Autocalculatable Fields 632



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
Electricity:Building 1779.73 25637.89 29-JUL-10:30 123947.64 02-JAN-16:50
Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 26.08 328.37 01-JUL-08:10 2135.86 02-JAN-16:50
Electricity:SpaceType:GENERAL 1771.88 25537.55 29-JUL-08:50 123705.66 02-JAN-16:50
InteriorLights:Electricity 627.81 5641.25 10-JUN-14:40 53121.69 02-JAN-16:50
InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 6.97 38.91 01-JAN-08:10 822.99 02-JAN-07:10
InteriorLights:Electricity:SpaceType:GENERAL 627.81 5641.25 10-JUN-14:40 53121.69 02-JAN-16:50
LightsWired:InteriorLights:Electricity 627.81 5641.25 10-JUN-14:40 53121.69 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 6.97 38.91 01-JAN-08:10 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 627.81 5641.25 10-JUN-14:40 53121.69 02-JAN-16:50
Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 132.56 1738.37 01-JUL-08:20 10290.98 02-JAN-16:50
InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 40.49 343.71 01-JAN-07:30 3965.33 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 40.49 343.71 01-JAN-07:30 3965.33 02-JAN-16:50
Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 23.17 320.67 30-JUN-23:10 1546.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 27.22 325.13 01-JUL-11:20 2135.86 02-JAN-08:10
InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 8.11 35.67 01-JAN-15:10 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 8.11 35.67 01-JAN-15:10 822.99 02-JAN-07:10
Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 140.39 1738.37 30-JUL-17:10 10290.98 02-JAN-16:20
InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 48.32 343.71 06-MAY-17:20 3965.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 48.32 343.71 06-MAY-17:20 3965.33 02-JAN-07:10
Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 26.35 328.37 01-JUL-09:10 2135.86 02-JAN-16:50
InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 7.24 38.91 01-JAN-08:20 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 7.24 38.91 01-JAN-08:20 822.99 02-JAN-07:10
Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 134.50 1738.37 15-JUL-11:00 10290.98 02-JAN-16:40
InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 42.43 343.71 01-JAN-07:30 3965.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 42.43 343.71 01-JAN-07:30 3965.33 02-JAN-07:10
Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 23.17 320.67 30-JUN-23:10 1546.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 27.32 328.37 01-JUL-11:10 2135.86 02-JAN-08:10
InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 8.21 38.91 01-JAN-15:10 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 8.21 38.91 01-JAN-15:10 822.99 02-JAN-07:10
Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 140.28 1738.37 30-JUL-17:10 10290.98 02-JAN-16:20
InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 48.21 343.71 06-MAY-17:20 3965.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 48.21 343.71 06-MAY-17:20 3965.33 02-JAN-07:10
Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 26.33 328.37 01-JUL-09:10 2135.86 02-JAN-16:50
InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 7.22 38.91 01-JAN-08:20 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 7.22 38.91 01-JAN-08:20 822.99 02-JAN-07:10
Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 143.62 1957.10 01-JUL-11:30 10290.98 02-JAN-16:40
InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 51.55 562.44 01-JAN-07:30 3965.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 51.55 562.44 01-JAN-07:30 3965.33 02-JAN-07:10
Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 23.17 320.67 30-JUN-23:10 1546.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 13.29 170.97 01-JAN-00:10 867.83 02-JAN-07:10
Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 26.81 328.37 01-JUL-08:20 2135.86 02-JAN-16:50
InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 7.70 38.91 01-JAN-12:30 822.99 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 7.70 38.91 01-JAN-12:30 822.99 02-JAN-07:10
Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 90.03 1147.98 01-JUL-06:20 6795.93 02-JAN-16:30
InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 29.23 226.98 26-FEB-13:20 2618.61 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 29.23 226.98 26-FEB-13:20 2618.61 02-JAN-07:10
Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 56.72 748.28 01-JUL-06:20 4211.16 02-JAN-16:30
InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 15.03 116.73 26-FEB-13:20 1346.72 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 15.03 116.73 26-FEB-13:20 1346.72 02-JAN-07:10
Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 65.89 911.90 30-JUN-23:10 4398.75 02-JAN-08:10
InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 37.79 486.19 01-JAN-00:10 2467.90 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 37.79 486.19 01-JAN-00:10 2467.90 02-JAN-07:10
Electricity:Zone:LOBBY_ZN_1_FLR_1 19.97 230.25 01-JUL-07:10 1722.90 02-JAN-16:50
InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 11.17 96.93 01-JAN-07:30 1118.18 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 11.17 96.93 01-JAN-07:30 1118.18 02-JAN-16:50
Electricity:Zone:MECH_ZN_1_FLR_1 48.13 693.19 30-JUN-23:10 3253.23 02-JAN-08:10
InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 15.70 201.99 01-JAN-00:10 1025.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 15.70 201.99 01-JAN-00:10 1025.33 02-JAN-07:10
Electricity:Zone:BATH_ZN_1_FLR_1 24.97 343.59 30-JUN-23:10 1664.00 02-JAN-08:10
InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 15.19 195.45 01-JAN-00:10 992.10 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 15.19 195.45 01-JAN-00:10 992.10 02-JAN-07:10
Electricity:Zone:OFFICES_ZN_1_FLR_1 102.27 1333.51 01-JUL-06:00 7756.41 02-JAN-16:40
InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 40.98 405.14 01-JAN-07:30 3545.68 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 40.98 405.14 01-JAN-07:30 3545.68 02-JAN-07:10
Electricity:Zone:GYM_ZN_1_FLR_1 51.80 347.93 01-JUL-07:30 5177.04 02-JAN-16:20
InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 28.83 0.00 02-FEB-07:30 3598.94 02-JAN-16:20
LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 28.83 0.00 02-FEB-07:30 3598.94 02-JAN-16:20
Electricity:Zone:KITCHEN_ZN_1_FLR_1 204.60 5172.85 01-JAN-11:30 13625.76 02-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 30.15 387.95 01-JAN-00:10 1969.28 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 30.15 387.95 01-JAN-00:10 1969.28 02-JAN-07:10
Electricity:Zone:CAFETERIA_ZN_1_FLR_1 51.19 995.16 01-JAN-07:50 3652.39 06-DEC-12:40
InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 21.25 195.38 01-JAN-07:50 1983.52 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 21.25 195.38 01-JAN-07:50 1983.52 02-JAN-16:30
Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 143.19 1727.84 01-JUL-06:10 10378.59 02-JAN-15:50
InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 66.17 561.24 05-FEB-07:20 5087.33 02-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 66.17 561.24 05-FEB-07:20 5087.33 02-JAN-07:10
InteriorEquipment:Electricity 1144.07 19837.34 30-JUN-23:10 76582.98 02-JAN-10:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1144.07 19837.34 30-JUN-23:10 76582.98 02-JAN-10:10
MiscPlug:InteriorEquipment:Electricity 947.54 14352.99 30-JUN-23:10 65099.62 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 947.54 14352.99 30-JUN-23:10 65099.62 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 92.07 1394.66 30-JUN-23:10 6325.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 9.88 149.70 30-JUN-23:10 678.98 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 19.11 289.46 30-JUN-23:10 1312.87 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 60.80 921.00 30-JUN-23:10 4177.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 60.80 921.00 30-JUN-23:10 4177.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 41.69 631.55 30-JUN-23:10 2864.44 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 41.69 631.55 30-JUN-23:10 2864.44 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 28.10 425.71 30-JUN-23:10 1930.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 28.10 425.71 30-JUN-23:10 1930.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 8.80 133.33 30-JUN-23:10 604.72 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 8.80 133.33 30-JUN-23:10 604.72 02-JAN-08:10
InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 32.43 491.20 30-JUN-23:10 2227.90 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 32.43 491.20 30-JUN-23:10 2227.90 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 9.78 148.14 30-JUN-23:10 671.91 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 9.78 148.14 30-JUN-23:10 671.91 02-JAN-08:10
InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 61.29 928.37 30-JUN-23:10 4210.73 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 61.29 928.37 30-JUN-23:10 4210.73 02-JAN-08:10
InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 22.97 347.93 30-JUN-23:10 1578.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 22.97 347.93 30-JUN-23:10 1578.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 166.60 4684.56 01-JAN-00:10 9483.90 02-JAN-10:10
Cooking:InteriorEquipment:Electricity 149.71 3999.34 01-JAN-00:10 9998.36 02-JAN-10:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 119.77 3199.56 01-JAN-00:10 7998.90 02-JAN-10:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 149.71 3999.34 01-JAN-00:10 9998.36 02-JAN-10:10
ReachInFreezer:InteriorEquipment:Electricity 28.86 915.00 01-JAN-00:10 915.00 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 28.86 915.00 01-JAN-00:10 915.00 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 28.86 915.00 01-JAN-00:10 915.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 29.94 799.79 01-JAN-00:10 1999.46 02-JAN-10:10
Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 29.94 799.79 01-JAN-00:10 1999.46 02-JAN-10:10
InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 77.02 1166.60 30-JUN-23:10 5291.26 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 77.02 1166.60 30-JUN-23:10 5291.26 02-JAN-08:10
Refrigeration:Electricity 63.51 1149.08 14-OCT-22:30 3556.23 12-MAR-10:50
Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 7.85 100.34 01-JAN-11:30 2172.58 02-JAN-11:10
General:Refrigeration:Electricity 7.85 100.34 01-JAN-11:30 2172.58 02-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 7.85 100.34 01-JAN-11:30 2172.58 02-JAN-11:10
Electricity:Plant 81.77 1048.74 14-OCT-22:30 7405.14 29-MAR-10:40
LowTempRefrigeration:Refrigeration:Electricity 19.21 0.00 01-JAN-11:10 2138.98 12-MAR-10:50
MedTempRefrigeration:Refrigeration:Electricity 36.45 1020.60 22-NOV-21:10 1245.48 01-JAN-07:30
Electricity:HVAC 664.68 444.01 29-JUL-09:30 197274.49 16-OCT-11:00
ExteriorEquipment:Electricity 24.18 444.01 29-JUL-09:00 1831.05 06-DEC-13:00
Transformer:ExteriorEquipment:Electricity 24.18 444.01 29-JUL-09:00 1831.05 06-DEC-13:00
ElectricityPurchased:Facility 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
ElectricityPurchased:Plant 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
Cogeneration:ElectricityPurchased 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
General:Cogeneration:ElectricityPurchased 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
ElectricityNet:Plant 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
Cogeneration:ElectricityNet 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
General:Cogeneration:ElectricityNet 2578.49 27964.10 29-JUL-08:50 313823.37 16-OCT-11:00
Fans:Electricity 268.85 0.00 01-JAN-00:40 38044.32 03-OCT-14:00
General:Fans:Electricity 268.85 0.00 01-JAN-00:40 38044.32 03-OCT-14:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 371.65 0.00 01-JAN-00:20 159362.69 16-OCT-11:00
General:Cooling:Electricity 371.65 0.00 01-JAN-00:20 159362.69 16-OCT-11:00
ExteriorLights:Electricity 52.30 0.00 01-JAN-07:00 3982.00 01-JAN-06:10
General:ExteriorLights:Electricity 52.30 0.00 01-JAN-07:00 3982.00 01-JAN-06:10
WaterSystems:Electricity 25.84 0.00 01-JAN-00:10 4823.74 04-APR-12:50
Water Heater:WaterSystems:Electricity 25.84 0.00 01-JAN-00:10 4823.74 04-APR-12:50
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.28 0.00 01-JAN-00:10 323.15 03-JAN-08:10
General:Pumps:Electricity 0.28 0.00 01-JAN-00:10 323.15 03-JAN-08:10
WIRED_LTG_ELECTRICITY 7.47 0.00 01-JAN-00:10 632.15 02-JAN-17:00


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 551.02 5814.99 01-JAN-00:10 192173.84 30-MAR-07:10
NaturalGas:Building 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
NaturalGas:SpaceType:GENERAL 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
InteriorEquipment:NaturalGas 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
Cooking:InteriorEquipment:NaturalGas 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 361.03 4808.50 01-JAN-00:10 48084.96 02-JAN-10:10
NaturalGas:HVAC 9.41 0.00 01-JAN-00:10 28808.73 02-JAN-21:00
Heating:NaturalGas 52.30 0.00 01-JAN-00:10 143507.26 03-JAN-08:10
General:Heating:NaturalGas 9.41 0.00 01-JAN-00:10 28808.73 02-JAN-21:00
NaturalGas:Plant 180.57 1006.49 01-JAN-00:10 133221.38 30-MAR-07:10
Boiler:Heating:NaturalGas 42.89 0.00 01-JAN-00:10 119240.31 03-JAN-08:10
WaterSystems:NaturalGas 137.68 1006.49 01-JAN-00:10 25214.27 31-JAN-13:50
Water Heater:WaterSystems:NaturalGas 137.68 1006.49 01-JAN-00:10 25214.27 31-JAN-13:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water:Plant 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterSystems:Water 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water Heater:WaterSystems:Water 268.99 0.00 01-JAN-00:10 0.00 02-JAN-13:10
MainsWater:Facility 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
MainsWater:Plant 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterSystems:MainsWater 718.47 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water Heater:WaterSystems:MainsWater 268.99 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterUse:WaterSystems:Water 449.48 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterUse:WaterSystems:MainsWater 449.48 0.00 01-JAN-00:10 0.00 02-JAN-13:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 3776.83 4208.48 29-SEP-22:30 832306.88 16-OCT-12:00
EnergyTransfer:Building 2158.24 2104.24 29-SEP-22:30 311519.33 16-OCT-13:10
EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 308.18 2104.24 29-SEP-22:30 27957.15 05-JUN-10:50
Refrigeration:EnergyTransfer 188.53 4192.43 14-OCT-22:30 10745.76 12-MAR-10:50
Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 94.26 2096.22 14-OCT-22:30 5372.88 12-MAR-10:50
General:Refrigeration:EnergyTransfer 94.26 2096.22 14-OCT-22:30 5372.88 12-MAR-10:50
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 94.26 2096.22 14-OCT-22:30 5372.88 12-MAR-10:50
EnergyTransfer:Plant 196.83 2096.22 14-OCT-22:30 102364.43 03-JAN-08:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 18.04 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 76.22 2011.79 22-NOV-21:10 2686.44 01-JAN-07:30
EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 39.35 0.00 01-JAN-00:10 7219.86 16-OCT-14:20
Heating:EnergyTransfer 9.07 0.00 01-JAN-00:10 30508.00 03-JAN-07:20
Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.06 0.00 01-JAN-00:10 1772.73 30-MAR-06:20
General:Heating:EnergyTransfer 9.07 0.00 01-JAN-00:10 30508.00 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.06 0.00 01-JAN-00:10 1772.73 30-MAR-06:20
Cooling:EnergyTransfer 2054.90 0.00 01-JAN-00:40 308490.87 16-OCT-13:00
Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 39.29 0.00 01-JAN-00:10 7219.86 16-OCT-14:20
General:Cooling:EnergyTransfer 2054.90 0.00 01-JAN-00:40 308490.87 16-OCT-13:00
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 39.29 0.00 01-JAN-00:10 7219.86 16-OCT-14:20
EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 173.19 0.00 01-JAN-00:10 29442.66 16-OCT-13:00
Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.09 0.00 01-JAN-00:10 2865.39 28-JUL-07:10
General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.09 0.00 01-JAN-00:10 2865.39 28-JUL-07:10
Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 173.10 0.00 01-JAN-00:10 29442.66 16-OCT-13:00
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 173.10 0.00 01-JAN-00:10 29442.66 16-OCT-13:00
EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 32.01 0.00 01-JAN-00:10 4681.26 16-OCT-14:30
Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1266.45 02-JAN-08:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1266.45 02-JAN-08:10
Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 32.00 0.00 01-JAN-00:10 4681.26 16-OCT-14:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 32.00 0.00 01-JAN-00:10 4681.26 16-OCT-14:30
EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 31.82 0.00 01-JAN-00:10 4789.94 29-SEP-15:00
Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2559.39 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2559.39 03-JAN-07:20
Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 31.70 0.00 01-JAN-00:10 4789.94 29-SEP-15:00
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 31.70 0.00 01-JAN-00:10 4789.94 29-SEP-15:00
EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 133.17 0.00 01-JAN-00:10 18149.94 16-OCT-13:20
Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.14 0.00 01-JAN-00:10 3682.18 09-JAN-07:20
General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.14 0.00 01-JAN-00:10 3682.18 09-JAN-07:20
Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 133.03 0.00 01-JAN-00:10 18149.94 16-OCT-13:20
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 133.03 0.00 01-JAN-00:10 18149.94 16-OCT-13:20
EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 38.93 0.00 01-JAN-00:10 7179.86 16-OCT-14:20
Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.06 0.00 01-JAN-00:10 1750.12 30-MAR-06:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.06 0.00 01-JAN-00:10 1750.12 30-MAR-06:20
Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 38.88 0.00 01-JAN-00:10 7179.86 16-OCT-14:20
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 38.88 0.00 01-JAN-00:10 7179.86 16-OCT-14:20
EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 170.84 0.00 01-JAN-00:10 29059.56 16-OCT-13:00
Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.08 0.00 01-JAN-00:10 2796.05 28-JUL-07:10
General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.08 0.00 01-JAN-00:10 2796.05 28-JUL-07:10
Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 170.76 0.00 01-JAN-00:10 29059.56 16-OCT-13:00
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 170.76 0.00 01-JAN-00:10 29059.56 16-OCT-13:00
EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 31.92 0.00 01-JAN-00:10 4634.65 16-OCT-14:30
Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1337.20 02-JAN-08:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1337.20 02-JAN-08:10
Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 31.91 0.00 01-JAN-00:10 4634.65 16-OCT-14:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 31.91 0.00 01-JAN-00:10 4634.65 16-OCT-14:30
EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 31.81 0.00 01-JAN-00:10 4809.25 29-SEP-15:00
Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2618.44 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2618.44 03-JAN-07:20
Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 31.70 0.00 01-JAN-00:10 4809.25 29-SEP-15:00
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 31.70 0.00 01-JAN-00:10 4809.25 29-SEP-15:00
EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 133.06 0.00 01-JAN-00:10 18130.18 16-OCT-13:20
Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.14 0.00 01-JAN-00:10 3699.75 09-JAN-07:20
General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.14 0.00 01-JAN-00:10 3699.75 09-JAN-07:20
Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 132.91 0.00 01-JAN-00:10 18130.18 16-OCT-13:20
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 132.91 0.00 01-JAN-00:10 18130.18 16-OCT-13:20
EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 39.01 0.00 01-JAN-00:10 7218.32 16-OCT-14:20
Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 1633.06 30-MAR-06:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 1633.06 30-MAR-06:20
Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 38.95 0.00 01-JAN-00:10 7218.32 16-OCT-14:20
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 38.95 0.00 01-JAN-00:10 7218.32 16-OCT-14:20
EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 176.77 0.00 01-JAN-00:10 29586.67 16-OCT-13:00
Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 2512.97 28-JUL-07:10
General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 2512.97 28-JUL-07:10
Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 176.72 0.00 01-JAN-00:10 29586.67 16-OCT-13:00
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 176.72 0.00 01-JAN-00:10 29586.67 16-OCT-13:00
EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 32.34 0.00 01-JAN-00:10 4781.37 16-OCT-14:30
Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1275.08 02-JAN-08:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 0.01 0.00 01-JAN-00:10 1275.08 02-JAN-08:10
Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 32.34 0.00 01-JAN-00:10 4781.37 16-OCT-14:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 32.34 0.00 01-JAN-00:10 4781.37 16-OCT-14:30
EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 31.83 0.00 01-JAN-00:10 4877.91 29-SEP-15:00
Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2607.83 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.11 0.00 01-JAN-00:10 2607.83 03-JAN-07:20
Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 31.72 0.00 01-JAN-00:10 4877.91 29-SEP-15:00
General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 31.72 0.00 01-JAN-00:10 4877.91 29-SEP-15:00
EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 88.03 0.00 01-JAN-00:10 12088.83 29-SEP-13:50
Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.09 0.00 01-JAN-00:10 2479.48 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.09 0.00 01-JAN-00:10 2479.48 03-JAN-07:20
Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 87.93 0.00 01-JAN-00:10 12088.83 29-SEP-13:50
General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 87.93 0.00 01-JAN-00:10 12088.83 29-SEP-13:50
EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 62.21 0.00 01-JAN-00:10 7162.78 29-SEP-13:40
Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 0.02 0.00 01-JAN-00:10 819.50 02-JAN-08:10
General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 0.02 0.00 01-JAN-00:10 819.50 02-JAN-08:10
Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 62.19 0.00 01-JAN-00:10 7162.78 29-SEP-13:40
General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 62.19 0.00 01-JAN-00:10 7162.78 29-SEP-13:40
EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 64.62 0.00 01-JAN-00:10 11401.15 16-OCT-14:00
Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 9.41 03-JAN-08:10
General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 9.41 03-JAN-08:10
Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 64.62 0.00 01-JAN-00:10 11401.15 16-OCT-14:00
General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 64.62 0.00 01-JAN-00:10 11401.15 16-OCT-14:00
EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 26.47 0.00 01-JAN-00:10 10201.33 29-SEP-14:40
Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 7.57 0.00 01-JAN-00:10 6967.69 03-JAN-07:20
General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 7.57 0.00 01-JAN-00:10 6967.69 03-JAN-07:20
Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 18.90 0.00 01-JAN-00:10 10201.33 29-SEP-14:40
General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 18.90 0.00 01-JAN-00:10 10201.33 29-SEP-14:40
EnergyTransfer:Zone:MECH_ZN_1_FLR_1 18.92 0.00 01-JAN-00:10 3167.89 16-OCT-12:50
Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 18.92 0.00 01-JAN-00:10 3167.89 16-OCT-12:50
General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 18.92 0.00 01-JAN-00:10 3167.89 16-OCT-12:50
EnergyTransfer:Zone:BATH_ZN_1_FLR_1 14.61 0.00 01-JAN-00:10 2677.20 20-AUG-15:50
Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 14.61 0.00 01-JAN-00:10 2677.20 20-AUG-15:50
General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 14.61 0.00 01-JAN-00:10 2677.20 20-AUG-15:50
EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 92.50 0.00 01-JAN-00:10 18038.48 16-OCT-12:50
Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 92.50 0.00 01-JAN-00:10 18038.48 16-OCT-12:50
General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 92.50 0.00 01-JAN-00:10 18038.48 16-OCT-12:50
EnergyTransfer:Zone:GYM_ZN_1_FLR_1 109.51 0.00 01-JAN-00:10 15453.10 16-OCT-16:00
Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 614.95 31-MAR-06:50
General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 0.05 0.00 01-JAN-00:10 614.95 31-MAR-06:50
Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 109.46 0.00 01-JAN-00:10 15453.10 16-OCT-16:00
General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 109.46 0.00 01-JAN-00:10 15453.10 16-OCT-16:00
Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 147.91 29-MAR-06:10
General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 147.91 29-MAR-06:10
Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 213.92 0.00 01-JAN-00:40 22863.47 05-JUN-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 213.92 0.00 01-JAN-00:40 22863.47 05-JUN-10:50
EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 169.31 0.00 01-JAN-00:10 27813.42 16-OCT-13:20
Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 0.28 0.00 01-JAN-00:10 2433.89 09-JAN-06:40
General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 0.28 0.00 01-JAN-00:10 2433.89 09-JAN-06:40
Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 169.03 0.00 01-JAN-00:10 27813.42 16-OCT-13:20
General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 169.03 0.00 01-JAN-00:10 27813.42 16-OCT-13:20
EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 107.81 0.00 01-JAN-00:10 16930.95 16-OCT-12:00
Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 1452.95 03-JAN-08:10
General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.00 0.00 01-JAN-00:10 1452.95 03-JAN-08:10
Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 107.81 0.00 01-JAN-00:10 16930.95 16-OCT-12:00
General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 107.81 0.00 01-JAN-00:10 16930.95 16-OCT-12:00
PlantLoopHeatingDemand:Facility 102.86 0.00 01-JAN-00:10 92362.29 03-JAN-08:10
PlantLoopHeatingDemand:Plant 75.29 0.00 01-JAN-00:10 15270.76 01-FEB-13:40
WaterSystems:PlantLoopHeatingDemand 75.29 0.00 01-JAN-00:10 15270.76 01-FEB-13:40
General:WaterSystems:PlantLoopHeatingDemand 75.29 0.00 01-JAN-00:10 15270.76 01-FEB-13:40
EnergyTransfer:HVAC 1421.77 0.00 01-JAN-00:20 513772.84 16-OCT-11:20
HeatingCoils:EnergyTransfer 35.10 0.00 01-JAN-00:10 105635.12 03-JAN-08:10
PlantLoopHeatingDemand:HVAC 27.57 0.00 01-JAN-00:10 86221.56 03-JAN-08:10
HeatingCoils:PlantLoopHeatingDemand 27.57 0.00 01-JAN-00:10 86221.56 03-JAN-08:10
CoolingCoils:EnergyTransfer 1386.66 0.00 01-JAN-00:20 513772.84 16-OCT-11:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 75.29 0.00 01-JAN-00:10 15270.76 01-FEB-13:40
WaterUse:WaterSystems:EnergyTransfer 75.29 0.00 01-JAN-00:10 15270.76 01-FEB-13:40
Boilers:EnergyTransfer 27.28 0.00 01-JAN-00:10 93392.26 03-JAN-08:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.000 0.000 0.059 -39.287 0.000 0.000 12.233 6.966 19.109 23.546 0.000 0.018 0.001 0.000 -11.225 0.000 -1.253 -10.168
MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.000 0.000 0.089 -173.106 0.000 0.000 57.041 40.488 92.071 66.751 0.000 0.048 0.000 0.000 -32.073 0.000 -3.582 -47.728
CORRIDOR_POD_1_ZN_1_FLR_1 0.000 0.000 0.010 -32.004 0.000 0.000 4.749 13.288 9.883 3.302 0.000 0.003 2.757 0.000 -1.801 0.000 -0.187 -0.000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.000 0.000 0.113 -31.704 0.000 0.000 12.643 8.111 19.109 12.764 0.000 0.027 0.000 0.000 -10.325 0.000 -1.101 -9.638
MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.000 0.000 0.142 -133.027 0.000 0.000 58.124 48.319 92.071 11.306 0.000 0.066 0.000 0.000 -29.369 0.000 -3.163 -44.469
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.000 0.000 0.059 -38.875 0.000 0.000 12.244 7.238 19.109 22.713 0.000 0.018 0.000 0.000 -11.083 0.000 -1.252 -10.170
MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.000 0.000 0.084 -170.759 0.000 0.000 57.039 42.427 92.071 60.375 0.000 0.048 0.000 0.000 -31.332 0.000 -3.584 -46.369
CORRIDOR_POD_2_ZN_1_FLR_1 0.000 0.000 0.011 -31.905 0.000 0.000 4.752 13.288 9.883 3.302 0.000 0.003 2.655 0.000 -1.801 0.000 -0.187 -0.001
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.000 0.000 0.114 -31.701 0.000 0.000 12.642 8.215 19.109 12.796 0.000 0.026 0.000 0.000 -10.346 0.000 -1.105 -9.749
MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.000 0.000 0.144 -132.915 0.000 0.000 58.151 48.209 92.071 11.531 0.000 0.065 0.000 0.000 -29.413 0.000 -3.171 -44.673
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.000 0.000 0.053 -38.954 0.000 0.000 12.165 7.221 19.109 22.696 0.000 0.018 0.000 0.000 -11.188 0.000 -1.263 -9.856
MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.000 0.000 0.055 -176.720 0.000 0.000 56.467 51.545 92.071 60.365 0.000 0.045 0.000 0.000 -31.909 0.000 -3.651 -48.267
CORRIDOR_POD_3_ZN_1_FLR_1 0.000 0.000 0.008 -32.336 0.000 0.000 4.704 13.288 9.883 3.279 0.000 0.003 3.198 0.000 -1.835 0.000 -0.192 -0.000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.000 0.000 0.110 -31.725 0.000 0.000 12.590 7.702 19.109 13.430 0.000 0.026 0.000 0.000 -10.556 0.000 -1.113 -9.574
MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.000 0.000 0.094 -87.934 0.000 0.000 38.332 29.226 60.801 10.544 0.000 0.042 0.000 0.000 -20.035 0.000 -2.101 -28.971
COMPUTER_CLASS_ZN_1_FLR_1 0.000 0.000 0.024 -62.190 0.000 0.000 32.929 15.032 41.692 5.188 0.000 0.023 0.000 0.000 -11.055 0.000 -1.158 -20.486
MAIN_CORRIDOR_ZN_1_FLR_1 0.000 0.000 0.000 -64.624 0.000 0.000 12.539 37.789 28.104 7.013 0.000 0.006 0.000 0.000 -5.852 0.000 -0.640 -14.335
LOBBY_ZN_1_FLR_1 0.000 0.000 7.571 -18.901 0.000 0.000 8.653 11.169 8.802 24.167 0.000 0.950 3.150 0.000 -11.151 0.000 -34.410 -0.000
MECH_ZN_1_FLR_1 0.000 0.000 0.000 -18.917 0.000 0.000 1.434 15.700 32.427 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -30.644
BATH_ZN_1_FLR_1 0.000 0.000 0.000 -14.607 0.000 0.000 4.005 15.191 9.780 7.944 0.000 0.005 0.000 0.000 -6.729 0.000 -0.743 -14.846
OFFICES_ZN_1_FLR_1 0.000 0.000 0.000 -92.499 0.000 0.000 10.055 40.985 61.288 44.369 0.000 0.022 0.001 0.000 -27.127 0.000 -3.109 -33.984
GYM_ZN_1_FLR_1 0.000 0.000 0.049 -109.466 0.000 0.000 51.273 28.833 22.969 40.119 0.000 0.009 0.000 0.000 -20.731 0.000 -1.310 -11.744
KITCHEN_ZN_1_FLR_1 0.000 0.000 0.000 -213.914 0.000 0.000 11.445 30.154 138.079 7.260 0.000 0.004 33.752 0.000 -6.086 0.000 -0.694 -0.002
CAFETERIA_ZN_1_FLR_1 0.000 0.000 0.280 -169.035 0.000 0.000 141.141 21.247 29.938 18.166 0.000 0.019 0.001 0.000 -22.258 0.000 -2.504 -16.994
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.000 0.000 0.002 -107.814 0.000 0.000 18.345 66.175 77.015 22.196 0.000 0.025 0.000 0.000 -25.493 0.000 -2.888 -47.563
Total Facility 0.000 0.000 9.071 -2054.919 0.000 0.000 705.695 627.807 1115.552 515.122 0.000 1.519 45.516 0.000 -380.772 0.000 -74.359 -510.231


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 16-OCT-14:03 0.00 0.00 0.00 -7229.14 0.00 0.00 1760.14 197.52 1312.87 4271.43 0.00 26.15 0.00 0.00 -0.00 0.00 0.00 -338.97
MULT_CLASS_1_POD_1_ZN_1_FLR_1 15-OCT-11:02 0.00 0.00 0.00 -34967.23 0.00 0.00 0.00 343.71 1952.53 14221.98 0.00 90.57 18358.44 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 16-OCT-14:30 0.00 0.00 0.00 -4681.50 0.00 0.00 682.64 867.83 678.98 753.81 0.00 3.32 1694.91 0.00 -0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 29-SEP-15:00 0.00 0.00 0.00 -4789.96 0.00 0.00 1760.10 181.06 1312.87 2933.55 0.00 31.64 0.00 0.00 -0.00 0.00 0.00 -1429.26
MULT_CLASS_2_POD_1_ZN_1_FLR_1 16-OCT-13:20 0.00 0.00 0.00 -18149.31 0.00 0.00 8480.77 2855.04 6325.65 2609.70 0.00 94.12 0.00 0.00 -0.00 0.00 0.00 -2215.97
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 14-JAN-14:58 0.00 0.00 0.00 -7603.88 0.00 0.00 0.00 38.91 405.24 3701.63 0.00 0.00 3465.69 0.00 -0.00 0.00 -7.60 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 19-NOV-13:09 0.00 0.00 0.00 -32529.43 0.00 0.00 0.00 343.71 1952.53 13500.33 0.00 0.00 16740.34 0.00 -0.00 0.00 -7.48 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 16-OCT-14:30 0.00 0.00 0.00 -4634.89 0.00 0.00 682.64 867.83 678.98 753.92 0.00 3.32 1648.19 0.00 -0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 29-SEP-15:00 0.00 0.00 0.00 -4809.26 0.00 0.00 1760.10 197.52 1312.87 2937.35 0.00 31.64 0.00 0.00 -0.00 0.00 0.00 -1430.22
MULT_CLASS_2_POD_2_ZN_1_FLR_1 16-OCT-13:20 0.00 0.00 0.00 -18129.54 0.00 0.00 8480.77 2855.04 6325.65 2629.05 0.00 94.12 0.00 0.00 -0.00 0.00 0.00 -2255.09
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 30-SEP-15:32 0.00 0.00 0.00 -9363.03 0.00 0.00 0.00 38.91 405.24 3022.29 0.00 15.94 5880.64 0.00 -0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 15-OCT-13:32 0.00 0.00 0.00 -34830.68 0.00 0.00 0.00 562.44 1952.53 11492.32 0.00 183.14 20640.25 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 16-OCT-14:30 0.00 0.00 0.00 -4781.62 0.00 0.00 682.64 867.83 678.98 753.59 0.00 3.32 1795.26 0.00 -0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 04-JUN-15:41 0.00 0.00 0.00 -5526.62 0.00 0.00 0.00 38.91 405.24 2065.29 0.00 0.00 3131.15 0.00 -0.00 0.00 -113.97 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 29-SEP-14:02 0.00 0.00 0.00 -12121.91 0.00 0.00 5600.34 1396.59 4177.31 2198.71 0.00 65.79 0.00 0.00 -0.00 0.00 0.00 -1316.84
COMPUTER_CLASS_ZN_1_FLR_1 10-JUN-13:32 0.00 0.00 0.00 -8011.94 0.00 0.00 0.00 116.73 884.16 845.37 0.00 0.00 6234.31 0.00 -0.00 0.00 -68.64 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 02-OCT-06:12 0.00 0.00 0.00 -13060.33 0.00 0.00 0.00 2467.90 595.99 0.00 0.00 0.00 10141.63 0.00 -141.20 0.00 -3.98 0.00
LOBBY_ZN_1_FLR_1 29-SEP-14:10 0.00 0.00 0.00 -10385.47 0.00 0.00 1033.86 492.00 604.72 3687.88 0.00 11668.38 0.00 0.00 -0.00 0.00 0.00 -7101.37
MECH_ZN_1_FLR_1 05-OCT-06:01 0.00 0.00 0.00 -7416.48 0.00 0.00 0.00 1025.33 687.68 0.00 0.00 0.00 5703.47 0.00 -0.00 0.00 0.00 0.00
BATH_ZN_1_FLR_1 01-JUL-15:52 0.00 0.00 0.00 -7676.20 0.00 0.00 0.00 195.45 148.14 2308.35 0.00 0.00 5055.83 0.00 -0.00 0.00 -31.58 0.00
OFFICES_ZN_1_FLR_1 30-SEP-11:42 0.00 0.00 0.00 -22387.56 0.00 0.00 0.00 405.14 1299.72 6463.16 0.00 117.56 14101.98 0.00 -0.00 0.00 0.00 0.00
GYM_ZN_1_FLR_1 20-NOV-06:01 0.00 0.00 0.00 -40845.51 0.00 0.00 0.00 709.00 487.11 0.00 0.00 0.00 41472.36 0.00 -1701.15 0.00 -121.80 0.00
KITCHEN_ZN_1_FLR_1 09-JAN-06:01 0.00 0.00 0.00 -57340.24 0.00 0.00 0.00 387.95 2721.46 0.00 0.00 0.00 54988.48 0.00 -662.67 0.00 -94.97 0.00
CAFETERIA_ZN_1_FLR_1 16-OCT-05:01 0.00 0.00 0.00 -58518.76 0.00 0.00 0.00 390.75 799.79 0.00 0.00 0.00 58559.04 0.00 -1138.97 0.00 -91.86 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 05-OCT-06:12 0.00 0.00 0.00 -20363.64 0.00 0.00 0.00 5087.33 1633.25 0.00 0.00 0.00 14166.84 0.00 -523.78 0.00 0.00 0.00
Total Facility 16-OCT-13:00 0.00 0.00 0.00 -308481.48 0.00 0.00 97750.84 33184.71 73747.43 91903.46 0.00 4545.20 7349.84 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 30-MAR-06:12 0.00 0.00 4514.90 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -683.58 0.00 -44.65 -5014.90
MULT_CLASS_1_POD_1_ZN_1_FLR_1 30-MAR-07:01 0.00 0.00 12358.36 0.00 0.00 0.00 10560.85 2114.84 6325.65 76.50 0.00 0.00 0.00 0.00 -0.00 0.00 -121.06 -31315.14
CORRIDOR_POD_1_ZN_1_FLR_1 03-JAN-08:61 0.00 0.00 3060.92 0.00 0.00 0.00 850.18 867.83 678.98 0.00 0.00 0.00 0.00 0.00 -89.55 0.00 -3.33 -5365.02
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 09-JAN-07:11 0.00 0.00 4534.68 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -835.30 0.00 -32.67 -4894.94
MULT_CLASS_2_POD_1_ZN_1_FLR_1 03-JAN-07:11 0.00 0.00 12584.55 0.00 0.00 0.00 0.00 3965.33 1952.53 0.00 0.00 0.00 0.00 0.00 -2407.97 0.00 -23.95 -16070.49
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 30-MAR-06:12 0.00 0.00 4474.86 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -694.42 0.00 -44.70 -4963.98
MULT_CLASS_1_POD_2_ZN_1_FLR_1 30-MAR-07:01 0.00 0.00 12076.69 0.00 0.00 0.00 10561.68 2855.04 6325.65 0.00 0.00 0.00 0.00 0.00 -362.86 0.00 -121.10 -31335.10
CORRIDOR_POD_2_ZN_1_FLR_1 03-JAN-08:61 0.00 0.00 3051.40 0.00 0.00 0.00 850.18 867.83 678.98 0.00 0.00 0.00 0.00 0.00 -88.99 0.00 -3.33 -5356.08
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 03-JAN-07:11 0.00 0.00 4557.85 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -823.46 0.00 -8.29 -4954.34
MULT_CLASS_2_POD_2_ZN_1_FLR_1 03-JAN-07:11 0.00 0.00 12688.15 0.00 0.00 0.00 0.00 3965.33 1952.53 0.00 0.00 0.00 0.00 0.00 -2401.32 0.00 -23.89 -16180.80
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 30-MAR-06:12 0.00 0.00 4382.55 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -698.67 0.00 -44.93 -4867.19
MULT_CLASS_1_POD_3_ZN_1_FLR_1 30-MAR-07:01 0.00 0.00 11953.31 0.00 0.00 0.00 10560.32 3410.18 6325.65 0.00 0.00 0.00 0.00 0.00 -367.10 0.00 -121.20 -31761.16
CORRIDOR_POD_3_ZN_1_FLR_1 03-JAN-08:61 0.00 0.00 3027.58 0.00 0.00 0.00 850.19 867.83 678.98 0.00 0.00 0.00 0.00 0.00 -89.66 0.00 -3.33 -5331.59
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 09-JAN-07:11 0.00 0.00 4527.22 0.00 0.00 0.00 0.00 822.99 405.24 0.00 0.00 0.00 0.00 0.00 -835.19 0.00 -32.62 -4887.65
MULT_CLASS_2_POD_3_ZN_1_FLR_1 03-JAN-07:11 0.00 0.00 8531.77 0.00 0.00 0.00 0.00 2618.61 1289.40 0.00 0.00 0.00 0.00 0.00 -1592.45 0.00 -15.74 -10831.61
COMPUTER_CLASS_ZN_1_FLR_1 03-JAN-07:11 0.00 0.00 4173.17 0.00 0.00 0.00 0.00 1346.72 884.16 0.00 0.00 0.00 0.00 0.00 -851.38 0.00 -8.39 -5544.28
MAIN_CORRIDOR_ZN_1_FLR_1 03-JAN-08:61 0.00 0.00 94.14 0.00 0.00 0.00 2314.03 2467.90 1930.85 0.00 0.00 0.00 0.00 0.00 -301.96 0.00 -10.66 -6494.31
LOBBY_ZN_1_FLR_1 03-JAN-07:10 0.00 0.00 7579.46 0.00 0.00 0.00 0.00 805.09 186.66 0.00 0.00 0.00 12320.91 0.00 -27.22 0.00 -20864.89 0.00
MECH_ZN_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BATH_ZN_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GYM_ZN_1_FLR_1 26-MAY-06:02 0.00 0.00 969.77 0.00 0.00 0.00 0.00 2399.29 487.11 0.00 0.00 0.00 0.00 0.00 -597.64 0.00 -37.19 -3221.35
KITCHEN_ZN_1_FLR_1 29-MAR-06:02 0.00 0.00 1120.40 0.00 0.00 0.00 0.00 1969.28 2721.46 220.70 0.00 0.00 0.00 0.00 -0.00 0.00 -17.82 -6014.02
CAFETERIA_ZN_1_FLR_1 03-JAN-07:01 0.00 0.00 15317.91 0.00 0.00 0.00 0.00 1547.14 799.79 0.00 0.00 0.00 0.00 0.00 -280.05 0.00 -9.35 -17375.44
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 03-JAN-08:61 0.00 0.00 7442.02 0.00 0.00 0.00 3484.47 3459.38 5291.26 1907.53 0.00 0.00 0.00 0.00 -0.00 0.00 -45.81 -21538.85
Total Facility 03-JAN-08:61 -43873.84 43873.84 115947.45 -43873.84 0.00 0.00 94513.56 37172.32 76151.68 30955.47 0.00 0.00 0.00 0.00 -6780.29 0.00 -3130.83 -300955.52



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_POD_1 5.4722 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.4098 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_POD_2 5.4496 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.3838 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_POD_3 4.8610 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.7965 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_OTHER 5.6981 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.5982 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ-AC_2:5 1.4070 0.0000 115.3101 1.0000 Calculated from schedules 0.5441 1.4070 0.3867 1.0000 Not calculated 0.5441 0.3867    
PSZ-AC_1:6 1.3599 0.0000 26.9930 1.0000 Calculated from schedules 0.4528 1.3599 0.3330 1.0000 Not calculated 0.4528 0.3330    
PSZ-AC_2:7 2.1989 0.0000 339.0743 1.0000 Calculated from schedules 1.4882 2.1989 0.6768 1.0000 Not calculated 1.4882 0.6768    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_POD_1 3.7047 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.7047 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_POD_2 3.7057 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.7057 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_POD_3 3.1985 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1985 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_OTHER 3.0164 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0244 0.0000 1.0000 Not calculated 0.0000 0.0000    
PSZ-AC_2:5 1.4070 0.0000 115.3101 1.0000 Calculated from schedules 0.5441 1.4070 1.0000 1.0000 Not calculated 0.5441 0.3867    
PSZ-AC_1:6 1.3599 0.0000 26.9930 1.0000 Calculated from schedules 0.4528 1.3599 1.0000 1.0000 Not calculated 0.4528 0.3330    
PSZ-AC_2:7 2.1989 0.0000 339.0743 1.0000 Calculated from schedules 1.4882 2.1989 1.0000 1.0000 Not calculated 1.4882 0.6768    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 0.004719 128.3638 0.000610 477.00 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_POD_1_ZN_1_FLR_1 VAV_POD_1 0.000000 10.3340 0.000305 192.00 0.0000 1.0000 0.0000 1.000 0.0000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 0.004719 128.3638 0.000610 477.00 0.0000 1.0000 0.0000 1.000 0.0000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 0.004719 128.3638 0.000610 477.00 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_POD_2_ZN_1_FLR_1 VAV_POD_2 0.000000 10.3340 0.000305 192.00 0.0000 1.0000 0.0000 1.000 0.0000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 0.004719 128.3638 0.000610 477.00 0.0000 1.0000 0.0000 1.000 0.0000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 0.004719 128.3638 0.000610 477.00 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_POD_3_ZN_1_FLR_1 VAV_POD_3 0.000000 10.3340 0.000305 192.00 0.0000 1.0000 0.0000 1.000 0.0000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 0.004719 26.6416 0.000610 99.00 0.0000 1.0000 0.0000 1.000 0.0000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 0.004719 84.7686 0.000610 315.00 0.0000 1.0000 0.0000 1.000 0.0000
COMPUTER_CLASS_ZN_1_FLR_1 VAV_OTHER 0.004719 43.5953 0.000610 162.00 0.0000 1.0000 0.0000 1.000 0.0000
MAIN_CORRIDOR_ZN_1_FLR_1 VAV_OTHER 0.000000 29.3880 0.000305 546.00 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_ZN_1_FLR_1 VAV_OTHER 0.000000 18.4080 0.000559 171.00 0.0000 1.0000 0.0000 1.000 0.0000
MECH_ZN_1_FLR_1 VAV_OTHER 0.000000 4.0690 0.000000 252.00 0.0000 1.0000 0.0000 1.000 0.0000
BATH_ZN_1_FLR_1 VAV_OTHER 0.000000 10.2270 0.000000 190.00 0.0000 1.0000 0.0000 1.000 0.0000
OFFICES_ZN_1_FLR_1 VAV_OTHER 0.000000 23.7365 0.000432 441.00 0.0000 1.0000 0.0000 1.000 0.0000
GYM_ZN_1_FLR_1 PSZ-AC_2:5 0.000000 115.3101 0.001524 357.00 0.5441 1.0000 0.5441 1.000 0.5441
KITCHEN_ZN_1_FLR_1 PSZ-AC_1:6 0.009440 26.9930 0.001179 168.00 0.4528 1.0000 0.4528 1.000 0.4528
CAFETERIA_ZN_1_FLR_1 PSZ-AC_2:7 0.003540 339.0743 0.000914 315.00 1.4882 1.0000 1.4882 1.000 1.4882
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV_OTHER 0.000000 42.9540 0.000864 399.00 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_POD_1   0.00 0.000566 1344.0000 0.0000 0.0000 0.0000
VAV_POD_2   0.00 0.000566 1344.0000 0.0000 0.0000 0.0000
VAV_POD_3   0.00 0.000560 1182.0000 0.0000 0.0000 0.0000
VAV_OTHER   0.00 0.000414 2161.0000 0.0000 0.0000 0.0000
PSZ-AC_2:5 0.000000 115.31 0.001524 357.0000 0.5441 0.5441 0.5441
PSZ-AC_1:6 0.009440 26.99 0.001179 168.0000 0.4528 0.4528 0.4528
PSZ-AC_2:7 0.003540 339.07 0.000914 315.0000 1.4882 1.4882 1.4882


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5479 0.5479 0.3709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1566 2.1566 1.4600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4261 0.4261 0.2885 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5030 0.5030 0.3405 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8387 1.8387 1.2448 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5444 0.5444 0.3702 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1369 2.1369 1.4531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4257 0.4257 0.2895 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5032 0.5032 0.3422 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8394 1.8394 1.2508 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5448 0.5448 0.3585 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1462 2.1462 1.4122 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4297 0.4297 0.2827 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5062 0.5062 0.3331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2340 1.2340 0.8120 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
COMPUTER_CLASS_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6860 0.6860 0.5104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MAIN_CORRIDOR_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8942 0.8942 0.2790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4899 0.4899 0.1602 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4333 0.4333 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BATH_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4554 0.4554 0.0911 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
OFFICES_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2993 1.2993 0.3196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
GYM_ZN_1_FLR_1 PSZ-AC_2:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.4070 1.4070 1.4070 No 0.5441 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_ZN_1_FLR_1 PSZ-AC_1:6 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3599 1.3599 1.3599 No 0.4528 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFETERIA_ZN_1_FLR_1 PSZ-AC_2:7 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.1989 2.1989 2.1989 No 1.4882 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4400 1.4400 0.5774 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_POD_1 5.4722 5.4098 5.4722 3.7047 0.0000 1.0000
VAV_POD_2 5.4496 5.3838 5.4496 3.7057 0.0000 1.0000
VAV_POD_3 4.8610 4.7965 4.8610 3.1985 0.0000 1.0000
VAV_OTHER 5.6981 5.5982 5.6981 2.0244 0.0000 1.0000
PSZ-AC_2:5 1.4070 1.4070 1.4070 1.4070 0.5441 1.0000
PSZ-AC_1:6 1.3599 1.3599 1.3599 1.3599 0.4528 1.0000
PSZ-AC_2:7 2.1989 2.1989 2.1989 2.1989 1.4882 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3709 0.3709 0.3709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4600 1.4600 1.4600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2885 0.2885 0.2885 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3405 0.3405 0.3405 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV_POD_1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2448 1.2448 1.2448 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3702 0.3702 0.3702 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4531 1.4531 1.4531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2895 0.2895 0.2895 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3422 0.3422 0.3422 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV_POD_2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2508 1.2508 1.2508 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3585 0.3585 0.3585 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4122 1.4122 1.4122 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2827 0.2827 0.2827 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3331 0.3331 0.3331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV_POD_3 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8120 0.8120 0.8120 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
COMPUTER_CLASS_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5104 0.5104 0.5104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MAIN_CORRIDOR_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4471 0.4471 0.2790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2449 0.2449 0.1602 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2167 0.2167 0.0867 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BATH_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2277 0.2277 0.0911 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
OFFICES_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6497 0.6497 0.3196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
GYM_ZN_1_FLR_1 PSZ-AC_2:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.4070 1.4070 1.4070 No 0.5441 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_ZN_1_FLR_1 PSZ-AC_1:6 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3599 1.3599 1.3599 No 0.4528 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFETERIA_ZN_1_FLR_1 PSZ-AC_2:7 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.1989 2.1989 2.1989 No 1.4882 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV_OTHER AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7200 0.7200 0.5774 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_POD_1 3.7047 3.7047 3.7047 3.7047 0.0000 1.0000
VAV_POD_2 3.7057 3.7057 3.7057 3.7057 0.0000 1.0000
VAV_POD_3 3.1985 3.1985 3.1985 3.1985 0.0000 1.0000
VAV_OTHER 3.0164 2.0244 2.0244 2.0244 0.0000 1.0000
PSZ-AC_2:5 1.4070 1.4070 1.4070 1.4070 0.5441 1.0000
PSZ-AC_1:6 1.3599 1.3599 1.3599 1.3599 0.4528 1.0000
PSZ-AC_2:7 2.1989 2.1989 2.1989 2.1989 1.4882 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 6871.00
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_1_POD_1_ZN_1_FLR_1 477.00 477.00 0.00 62.83
CORRIDOR_POD_1_ZN_1_FLR_1 192.00 192.00 0.00 62.83
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_2_POD_1_ZN_1_FLR_1 477.00 477.00 0.00 62.83
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_1_POD_2_ZN_1_FLR_1 477.00 477.00 0.00 62.83
CORRIDOR_POD_2_ZN_1_FLR_1 192.00 192.00 0.00 62.83
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_2_POD_2_ZN_1_FLR_1 477.00 477.00 0.00 62.83
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_1_POD_3_ZN_1_FLR_1 477.00 477.00 0.00 62.83
CORRIDOR_POD_3_ZN_1_FLR_1 192.00 192.00 0.00 62.83
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 99.00 99.00 0.00 62.83
MULT_CLASS_2_POD_3_ZN_1_FLR_1 315.00 315.00 0.00 62.83
COMPUTER_CLASS_ZN_1_FLR_1 162.00 162.00 0.00 62.83
MAIN_CORRIDOR_ZN_1_FLR_1 546.00 546.00 0.00 62.83
LOBBY_ZN_1_FLR_1 171.00 171.00 0.00 62.83
MECH_ZN_1_FLR_1 252.00 252.00 0.00 62.83
BATH_ZN_1_FLR_1 190.00 190.00 0.00 62.83
OFFICES_ZN_1_FLR_1 441.00 441.00 0.00 53.16
GYM_ZN_1_FLR_1 357.00 357.00 0.00 62.83
KITCHEN_ZN_1_FLR_1 168.00 168.00 0.00 62.83
CAFETERIA_ZN_1_FLR_1 315.00 315.00 0.00 52.32
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 399.00 399.00 0.00 62.83
Totals 6871.00 6871.00 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 115.83
Number of hours cooling loads not met 37.33
Number of hours not met 153.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 9.41 28808.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 42.89 119240.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 371.65 159362.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 627.81 53121.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 52.30 3982.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 947.54 65099.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 149.71 9998.36 361.03 48084.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 28.86 915.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 17.98 570.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 24.18 1831.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 268.85 38044.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.28 323.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 25.84 4823.74 137.68 25214.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.85 2172.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 19.21 2138.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 36.45 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1207.58 2578.49
Natural Gas 361.03 551.02
Additional 0.00 0.00
Total 1568.61 3129.51


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 91.37
Space Heating 0.00
Space Cooling 54.09
Fans (All) 39.13
Service Water Heating 3.76
Receptacle Equipment 166.51
Miscellaneous (All) 375.27
Subtotal 375.27


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 7.61
Service Water Heating 20.04
Miscellaneous (All) 80.19
Subtotal 80.19


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 20.06
Space Heating 1.67
Space Cooling 11.88
Fans (All) 8.59
Service Water Heating 5.23
Receptacle Equipment 48.09
Miscellaneous 4.48


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_GYM 3659. 8760.
LTG_SCH_CLASSROOM 2644. 8760.
LTG_SCH_LIBRARY 3390. 8760.
LTG_SCH_BATH 2147. 8760.
LTG_SCH_KITCHEN 3903. 8760.
LTG_SCH_OFFICE 3074. 8760.
LTG_SCH_LOBBY 2927. 8760.
LTG_SCH_MECHANICAL 3903. 8760.
LTG_SCH_COMPUTER_ROOM 2644. 8760.
LTG_SCH_CAFETERIA 3903. 8760.
LTG_SCH_CORRIDOR 2747. 8760.
BLDG_EQUIP_SCH 3617. 8760.
WALKIN_OCC_LGHT_SCH_2 2473. 8760.
KITCHEN_ELEC_EQUIP_SCH 1045. 8760.
KITCHEN_GAS_EQUIP_SCH 425. 8760.
BLDG_OCC_SCH 1755. 3380.
BLDG_OCC_SCH_EXTEND 2948. 3380.
BLDG_OCC_SCH_OFFICES 2197. 3380.
BLDG_OCC_SCH_OFFICES_W_SB 1743. 2860.
OFFICES BINARY OCCUPANCY 3380. 3380.
BLDG_OCC_SCH_GYM 1828. 3380.
BLDG_OCC_SCH_CAFETERIA 1687. 2815.
INFIL_SCH 6205. 8760.
INFIL_SCH_PNNL 6030. 8760.
INFIL_DOOR_OPENING_SCH 827. 2860.
BLDG_SWH_SCH 1227. 3120.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 5940. 8760.
WORK_EFF_SCH 0. 0.
KITCHEN_EXHAUST_SCH 2860. 2860.
MINOA_SCHED 8760. 8760.
BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED 438. 8760.
BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED 438. 8760.
KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3380. 3380.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6570. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 2594. 2860.
OFFICES_ZN_1_FLR_1_MDP_SCH 2027. 8240.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_SETBACK MECH_ZN_1_FLR_1 DUAL SP CONTROL January 15.60 365 15.60 365
CLGSETP_SCH_SETUP MECH_ZN_1_FLR_1 DUAL SP CONTROL July 26.70 365 26.70 365
HTGSETP_SCH_NO_OPTIMUM GYM_ZN_1_FLR_1 DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_NO_OPTIMUM GYM_ZN_1_FLR_1 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 8675.83 84.17 0.00 0.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 8726.00 34.00 0.00 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 8746.33 13.67 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 8671.50 88.50 0.00 0.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 8728.50 31.50 0.00 0.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 8733.67 26.33 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 8684.50 75.50 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 8723.83 36.17 0.00 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 8732.83 27.17 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 8749.67 10.33 0.00 0.00 0.00
MECH_ZN_1_FLR_1 6772.17 1987.83 0.00 0.00 0.00
BATH_ZN_1_FLR_1 8443.50 316.50 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 8656.67 103.33 0.00 0.00 0.00
GYM_ZN_1_FLR_1 8242.50 517.50 0.00 0.00 0.00
KITCHEN_ZN_1_FLR_1 5821.17 2938.83 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 8507.00 253.00 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 8713.83 46.17 0.00 0.00 0.00
Min 5821.17 0.00 0.00 0.00 0.00
Max 8760.00 2938.83 0.00 0.00 0.00
Average 8496.38 263.62 0.00 0.00 0.00
Sum 212409.50 6590.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 141584.00 0.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 122876.00 0.00 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 47696.00 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 29077.67 34.33 0.00 0.00 0.00
MECH_ZN_1_FLR_1 3466.50 1045.50 0.00 0.00 0.00
BATH_ZN_1_FLR_1 14178.67 1129.33 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 38444.00 0.00 0.00 0.00 0.00
GYM_ZN_1_FLR_1 202800.00 0.00 0.00 0.00 0.00
KITCHEN_ZN_1_FLR_1 44688.00 0.00 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 552560.00 0.00 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 70792.00 0.00 0.00 0.00 0.00
Min 3466.50 0.00 0.00 0.00 0.00
Max 552560.00 1129.33 0.00 0.00 0.00
Average 105993.71 88.37 0.00 0.00 0.00
Sum 2649842.83 2209.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 8454.17 305.83 0.00 0.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 8499.00 261.00 0.00 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 8740.17 19.83 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 8583.83 176.17 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 8672.50 87.50 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 8446.17 313.83 0.00 0.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 8496.50 263.50 0.00 0.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 8739.67 20.33 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 8569.33 190.67 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 8659.67 100.33 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 8455.17 304.83 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 8471.17 288.83 0.00 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 8737.67 22.33 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 8571.50 188.50 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 8652.83 107.17 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 8500.00 260.00 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 8553.50 206.50 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 8540.17 219.83 0.00 0.00 0.00
MECH_ZN_1_FLR_1 5376.83 3383.17 0.00 0.00 0.00
BATH_ZN_1_FLR_1 6420.50 2339.50 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 8149.83 610.17 0.00 0.00 0.00
GYM_ZN_1_FLR_1 6497.00 2263.00 0.00 0.00 0.00
KITCHEN_ZN_1_FLR_1 5092.17 3667.83 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 7576.67 1183.33 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 8162.67 597.33 0.00 0.00 0.00
Min 5092.17 19.83 0.00 0.00 0.00
Max 8740.17 3667.83 0.00 0.00 0.00
Average 8064.75 695.25 0.00 0.00 0.00
Sum 201618.67 17381.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 215026.83 625.17 0.00 0.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 215067.17 584.83 0.00 0.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 215652.00 0.00 0.00 0.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 15308.00 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 42916.00 0.00 0.00 0.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 141184.00 400.00 0.00 0.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 122821.33 54.67 0.00 0.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 47696.00 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 28482.00 630.00 0.00 0.00 0.00
MECH_ZN_1_FLR_1 3153.00 1359.00 0.00 0.00 0.00
BATH_ZN_1_FLR_1 10887.67 4420.33 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 38444.00 0.00 0.00 0.00 0.00
GYM_ZN_1_FLR_1 199400.83 3399.17 0.00 0.00 0.00
KITCHEN_ZN_1_FLR_1 44047.67 640.33 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 518286.67 34273.33 0.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 70792.00 0.00 0.00 0.00 0.00
Min 3153.00 0.00 0.00 0.00 0.00
Max 518286.67 34273.33 0.00 0.00 0.00
Average 104226.61 1855.47 0.00 0.00 0.00
Sum 2605665.17 46386.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 11:18:23

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 0.00 8760.00 0.00 0.00
MECH_ZN_1_FLR_1 0.00 0.00 0.00 0.00
BATH_ZN_1_FLR_1 0.00 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 0.00 0.00 8760.00 0.00
GYM_ZN_1_FLR_1 0.00 0.00 0.00 8760.00
KITCHEN_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 0.00 8760.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.00 0.00 0.00 8760.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 8760.00 8760.00
Average 0.00 700.80 4905.60 700.80
Sum 0.00 17520.00 122640.00 17520.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORNER_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_1_POD_1_ZN_1_FLR_1 0.00 0.00 215652.00 0.00
CORRIDOR_POD_1_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_2_POD_1_ZN_1_FLR_1 0.00 0.00 215652.00 0.00
CORNER_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_1_POD_2_ZN_1_FLR_1 0.00 0.00 215652.00 0.00
CORRIDOR_POD_2_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_2_POD_2_ZN_1_FLR_1 0.00 0.00 215652.00 0.00
CORNER_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_1_POD_3_ZN_1_FLR_1 0.00 0.00 215652.00 0.00
CORRIDOR_POD_3_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CORNER_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 42916.00 0.00
MULT_CLASS_2_POD_3_ZN_1_FLR_1 0.00 0.00 141584.00 0.00
COMPUTER_CLASS_ZN_1_FLR_1 0.00 0.00 122876.00 0.00
MAIN_CORRIDOR_ZN_1_FLR_1 0.00 0.00 0.00 0.00
LOBBY_ZN_1_FLR_1 0.00 29112.00 0.00 0.00
MECH_ZN_1_FLR_1 0.00 0.00 0.00 0.00
BATH_ZN_1_FLR_1 0.00 0.00 0.00 0.00
OFFICES_ZN_1_FLR_1 0.00 0.00 38444.00 0.00
GYM_ZN_1_FLR_1 0.00 0.00 0.00 202800.00
KITCHEN_ZN_1_FLR_1 0.00 0.00 0.00 0.00
CAFETERIA_ZN_1_FLR_1 0.00 552560.00 0.00 0.00
LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 0.00 0.00 0.00 70792.00
Min 0.00 0.00 0.00 0.00
Max 0.00 552560.00 215652.00 202800.00
Average 0.00 23266.88 65546.40 10943.68
Sum 0.00 581672.00 1638660.00 273592.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324560E+10 5766.92 15-JAN-15:06 23.70 11.44 0.759381E+09 1277.24 06-JAN-15:00 23.70 11.44
February 0.271530E+10 4882.63 21-FEB-15:03 18.67 14.13 0.664107E+09 1277.38 01-FEB-13:50 18.67 14.13
March 0.301944E+10 4924.31 19-MAR-14:51 18.00 14.37 0.777163E+09 1277.23 21-MAR-14:20 17.67 14.23
April 0.317754E+10 5817.83 30-APR-13:26 24.00 16.79 0.720937E+09 1277.23 10-APR-14:20 24.00 16.79
May 0.328981E+10 4973.55 29-MAY-16:41 18.00 13.36 0.778300E+09 1277.23 03-MAY-14:09 18.00 13.36
June 0.327497E+10 5200.59 18-JUN-15:17 22.67 17.71 0.474606E+09 1277.19 05-JUN-14:20 22.67 17.71
July 0.267984E+10 6285.10 23-JUL-15:48 24.00 19.32 0.149269E+09 187.50 31-JUL-15:30 25.00 20.20
August 0.314842E+10 6747.52 06-AUG-14:06 25.00 20.20 0.173973E+09 187.35 14-AUG-15:39 25.33 18.77
September 0.357110E+10 7068.02 30-SEP-11:43 31.83 17.26 0.458983E+09 1277.23 29-SEP-14:20 31.83 17.26
October 0.433078E+10 7229.09 16-OCT-14:03 31.67 15.90 0.803876E+09 1277.31 18-OCT-11:39 25.00 17.41
November 0.355247E+10 5698.97 18-NOV-14:38 24.67 14.62 0.777655E+09 1277.35 30-NOV-14:00 21.00 13.08
December 0.328084E+10 5404.82 19-DEC-14:40 22.33 9.68 0.731758E+09 1277.37 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.392861E+11         0.727001E+10        
Minimum of Months 0.267984E+10 4882.63   18.00 9.68 0.149269E+09 187.35   17.67 11.44
Maximum of Months 0.433078E+10 7229.09   31.83 20.20 0.803876E+09 1277.38   31.83 20.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.155239E+11 29118.23 15-JAN-15:06 23.70 11.44 0.389979E+10 6153.97 06-JAN-15:20 23.70 11.44
February 0.128551E+11 29516.46 20-FEB-11:41 16.83 9.71 0.343307E+10 6154.71 01-FEB-13:50 16.83 9.71
March 0.141256E+11 27938.35 11-MAR-13:41 24.00 12.91 0.403168E+10 6153.91 21-MAR-14:20 17.67 14.23
April 0.137006E+11 32142.39 30-APR-12:10 24.83 16.89 0.366505E+10 6153.92 10-APR-14:20 24.83 16.89
May 0.140612E+11 17635.59 29-MAY-16:41 18.00 13.36 0.396561E+10 6153.89 01-MAY-14:20 18.00 13.36
June 0.135122E+11 18285.55 25-JUN-14:31 21.33 16.63 0.240824E+10 6153.74 05-JUN-14:20 21.33 16.63
July 0.103022E+11 18701.62 30-JUL-13:01 24.00 19.79 0.707424E+09 869.78 31-JUL-13:30 27.50 21.02
August 0.123862E+11 18423.20 06-AUG-14:07 25.00 20.20 0.830881E+09 870.32 14-AUG-13:30 25.50 20.34
September 0.151055E+11 32012.19 30-SEP-11:02 31.17 17.79 0.229034E+10 6156.41 29-SEP-09:00 31.17 17.79
October 0.193269E+11 34967.31 15-OCT-11:02 32.00 16.46 0.400672E+10 6244.27 16-OCT-12:00 34.10 16.81
November 0.165020E+11 27918.17 23-NOV-11:41 17.83 6.57 0.395293E+10 6154.48 30-NOV-14:00 21.00 13.08
December 0.157031E+11 32392.43 16-DEC-11:48 22.83 13.49 0.373791E+10 6154.62 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.173104E+12         0.369297E+11        
Minimum of Months 0.103022E+11 17635.59   16.83 6.57 0.707424E+09 869.78   16.83 9.71
Maximum of Months 0.193269E+11 34967.31   32.00 20.20 0.403168E+10 6244.27   34.10 21.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.245300E+10 3041.71 15-JAN-15:07 23.70 11.44 0.278571E+09 477.82 18-JAN-15:39 22.33 15.21
February 0.219781E+10 2877.55 04-FEB-14:17 19.33 8.80 0.251208E+09 469.53 03-FEB-15:00 19.33 8.80
March 0.257892E+10 3020.71 19-MAR-14:51 18.00 14.37 0.299015E+09 476.31 24-MAR-14:00 18.00 15.44
April 0.259398E+10 3698.28 30-APR-12:10 24.83 16.89 0.283024E+09 495.41 27-APR-14:00 24.83 16.89
May 0.285241E+10 3399.15 29-MAY-16:41 18.00 13.36 0.315678E+09 495.46 03-MAY-14:09 18.00 13.36
June 0.291458E+10 3482.41 04-JUN-15:41 19.17 14.74 0.196890E+09 495.43 05-JUN-14:20 20.67 15.69
July 0.236398E+10 3424.32 02-JUL-15:32 22.00 16.84 61231944.32 72.68 03-JUL-15:09 21.83 16.79
August 0.266477E+10 3211.50 20-AUG-14:22 23.00 18.14 69681752.61 71.53 14-AUG-15:39 23.00 18.14
September 0.287239E+10 4197.99 29-SEP-15:00 33.00 17.49 0.181939E+09 495.44 29-SEP-14:20 33.00 17.49
October 0.335526E+10 4681.26 16-OCT-14:30 31.00 15.99 0.315793E+09 495.49 18-OCT-11:50 24.50 17.54
November 0.269143E+10 2926.31 20-NOV-13:00 19.00 15.88 0.292680E+09 476.17 01-NOV-14:00 19.00 15.88
December 0.246499E+10 3046.42 16-DEC-11:48 22.83 13.49 0.270319E+09 473.68 05-DEC-15:00 22.83 13.49
                     
Annual Sum or Average 0.320035E+11         0.281603E+10        
Minimum of Months 0.219781E+10 2877.55   18.00 8.80 61231944.32 71.53   18.00 8.80
Maximum of Months 0.335526E+10 4681.26   33.00 18.14 0.315793E+09 495.49   33.00 18.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.216775E+10 3431.75 15-JAN-15:06 23.70 11.44 0.676004E+09 1206.08 18-JAN-15:39 22.33 15.21
February 0.198979E+10 3100.43 01-FEB-16:00 19.00 15.88 0.611277E+09 1179.86 03-FEB-15:00 21.00 10.02
March 0.241404E+10 3501.37 11-MAR-16:22 20.00 12.30 0.738035E+09 1210.33 23-MAR-14:00 22.00 17.40
April 0.271493E+10 4289.94 30-APR-12:10 24.83 16.89 0.694698E+09 1277.07 26-APR-14:50 24.83 16.89
May 0.306059E+10 4353.47 29-MAY-16:41 18.00 13.36 0.782699E+09 1277.17 03-MAY-14:20 18.00 13.36
June 0.312657E+10 4579.72 18-JUN-16:51 21.00 17.19 0.485858E+09 1277.19 05-JUN-14:20 21.00 17.19
July 0.250961E+10 4485.54 02-JUL-15:32 22.00 16.84 0.149751E+09 182.01 31-JUL-16:10 24.00 19.89
August 0.269932E+10 4124.43 19-AUG-15:48 25.17 18.95 0.168472E+09 179.85 14-AUG-16:10 25.17 18.95
September 0.291959E+10 4789.94 29-SEP-15:00 33.00 17.49 0.441827E+09 1277.23 29-SEP-14:20 33.00 17.49
October 0.340774E+10 4787.41 16-OCT-15:00 30.00 16.08 0.763792E+09 1277.21 16-OCT-14:20 30.00 16.08
November 0.252373E+10 3169.76 10-NOV-15:30 18.50 15.67 0.699612E+09 1192.25 10-NOV-15:20 18.50 15.67
December 0.216981E+10 3304.54 19-DEC-13:30 24.50 10.72 0.648080E+09 1185.70 05-DEC-15:00 24.50 10.72
                     
Annual Sum or Average 0.317035E+11         0.686011E+10        
Minimum of Months 0.198979E+10 3100.43   18.00 10.72 0.149751E+09 179.85   18.00 10.02
Maximum of Months 0.340774E+10 4789.94   33.00 18.95 0.782699E+09 1277.23   33.00 19.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100647E+11 12929.79 18-JAN-14:10 24.33 14.82 0.357500E+10 6102.51 18-JAN-15:00 22.00 15.39
February 0.923777E+10 12046.05 01-FEB-15:04 19.00 14.95 0.324536E+10 5975.60 03-FEB-15:30 22.00 9.51
March 0.110857E+11 12605.43 23-MAR-15:00 22.00 17.40 0.392124E+10 6118.48 23-MAR-14:00 22.00 17.40
April 0.111327E+11 16019.62 30-APR-12:10 24.83 16.89 0.363387E+10 6153.92 13-APR-14:20 24.83 16.89
May 0.125905E+11 15346.73 04-MAY-14:10 22.83 16.63 0.407852E+10 6154.31 24-MAY-11:09 21.00 15.42
June 0.125080E+11 15506.34 05-JUN-15:00 20.00 15.11 0.250818E+10 6153.88 07-JUN-14:20 19.00 14.25
July 0.929297E+10 14660.21 02-JUL-14:16 22.67 17.13 0.721041E+09 849.29 03-JUL-12:39 22.67 17.13
August 0.100976E+11 13752.08 06-AUG-14:07 25.00 20.20 0.809907E+09 824.80 14-AUG-13:20 25.67 20.38
September 0.116422E+11 18116.33 29-SEP-14:02 33.83 17.79 0.225977E+10 6153.94 29-SEP-14:20 33.67 17.73
October 0.141095E+11 18149.94 16-OCT-13:20 33.40 16.49 0.395208E+10 6154.10 18-OCT-11:39 25.00 17.41
November 0.111803E+11 12694.35 28-NOV-13:30 24.50 10.63 0.370135E+10 6034.65 10-NOV-15:50 24.50 10.63
December 0.100836E+11 13225.54 19-DEC-13:30 24.50 10.72 0.344015E+10 6005.83 05-DEC-15:00 24.50 10.72
                     
Annual Sum or Average 0.133026E+12         0.358465E+11        
Minimum of Months 0.923777E+10 12046.05   19.00 10.63 0.721041E+09 824.80   19.00 9.51
Maximum of Months 0.141095E+11 18149.94   33.83 20.20 0.407852E+10 6154.31   33.67 20.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.319535E+10 7603.80 14-JAN-14:58 26.00 13.89 0.756814E+09 1277.24 06-JAN-15:00 26.00 13.89
February 0.269568E+10 4817.85 21-FEB-15:03 18.67 14.13 0.662774E+09 1277.38 01-FEB-13:50 18.67 14.13
March 0.299374E+10 4937.57 19-MAR-15:11 18.00 14.57 0.775837E+09 1277.23 21-MAR-14:20 17.67 14.23
April 0.314994E+10 5589.26 30-APR-13:30 24.00 16.79 0.720069E+09 1277.23 10-APR-14:20 24.00 16.79
May 0.327173E+10 4216.39 01-MAY-15:00 19.00 13.72 0.777624E+09 1277.23 03-MAY-14:09 22.83 16.45
June 0.325180E+10 5213.11 18-JUN-15:24 22.50 17.63 0.474572E+09 1277.19 05-JUN-14:20 22.50 17.63
July 0.264090E+10 5839.36 23-JUL-14:29 24.50 19.46 0.148815E+09 186.74 31-JUL-15:39 24.67 20.10
August 0.311531E+10 6616.76 19-AUG-15:50 25.17 18.95 0.173287E+09 186.42 14-AUG-15:39 25.17 18.95
September 0.352883E+10 6629.15 29-SEP-15:00 33.00 17.49 0.458880E+09 1277.23 29-SEP-14:20 33.00 17.49
October 0.430165E+10 7561.00 15-OCT-11:50 32.00 16.80 0.804670E+09 1277.31 18-OCT-11:39 25.00 17.41
November 0.350923E+10 7588.46 19-NOV-13:09 26.67 15.00 0.776491E+09 1277.35 30-NOV-14:00 21.00 13.08
December 0.322087E+10 5351.05 19-DEC-14:40 22.33 9.68 0.729671E+09 1277.37 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.388750E+11         0.725950E+10        
Minimum of Months 0.264090E+10 4216.39   18.00 9.68 0.148815E+09 186.42   17.67 12.37
Maximum of Months 0.430165E+10 7603.80   33.00 19.46 0.804670E+09 1277.38   33.00 20.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150972E+11 24684.36 22-JAN-14:12 17.67 12.39 0.388461E+10 6154.59 18-JAN-13:09 17.67 12.39
February 0.127096E+11 24467.44 05-FEB-13:00 17.00 10.63 0.343134E+10 6154.68 01-FEB-13:50 17.00 10.63
March 0.140393E+11 20301.04 11-MAR-14:12 23.33 12.87 0.403473E+10 6153.91 21-MAR-14:20 17.67 14.23
April 0.136158E+11 25212.15 30-APR-12:19 24.67 16.92 0.367075E+10 6153.92 13-APR-14:20 24.67 16.92
May 0.140719E+11 17816.96 01-MAY-13:10 20.83 14.02 0.397989E+10 6153.89 01-MAY-14:20 19.67 14.02
June 0.135085E+11 17773.71 25-JUN-14:51 21.00 16.52 0.242070E+10 6153.74 05-JUN-14:20 21.00 16.52
July 0.101955E+11 17966.52 02-JUL-14:31 22.33 16.99 0.706975E+09 866.84 31-JUL-13:39 27.33 20.96
August 0.122556E+11 18849.18 20-AUG-13:11 23.67 18.43 0.828378E+09 868.28 14-AUG-13:20 23.67 18.43
September 0.148818E+11 26841.90 29-SEP-13:30 35.00 18.05 0.229248E+10 6154.85 28-SEP-14:39 35.00 18.05
October 0.190618E+11 32319.49 15-OCT-11:50 32.00 16.80 0.400940E+10 6218.78 16-OCT-12:00 34.10 16.81
November 0.161294E+11 32529.42 19-NOV-13:09 26.67 15.00 0.394686E+10 6154.47 30-NOV-14:00 21.00 13.08
December 0.151907E+11 28024.40 25-DEC-11:31 22.33 9.61 0.372572E+10 6154.60 20-DEC-14:00 22.33 9.61
                     
Annual Sum or Average 0.170757E+12         0.369318E+11        
Minimum of Months 0.101955E+11 17773.71   17.00 9.61 0.706975E+09 866.84   17.00 9.61
Maximum of Months 0.190618E+11 32529.42   35.00 18.43 0.403473E+10 6218.78   35.00 20.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242574E+10 2959.10 21-JAN-12:12 16.00 13.58 0.277404E+09 476.77 18-JAN-15:39 16.00 13.58
February 0.219643E+10 2869.38 05-FEB-14:52 17.00 11.02 0.250904E+09 468.72 03-FEB-15:00 17.00 11.02
March 0.257959E+10 3068.71 19-MAR-15:11 18.00 14.57 0.299017E+09 475.51 24-MAR-14:00 18.00 15.44
April 0.259329E+10 3330.97 30-APR-12:20 24.67 16.92 0.283027E+09 495.39 27-APR-14:00 24.67 16.92
May 0.286145E+10 3251.27 01-MAY-15:00 19.00 13.72 0.315957E+09 495.46 03-MAY-14:09 22.83 16.45
June 0.291981E+10 3501.22 05-JUN-15:00 20.00 15.11 0.197223E+09 495.43 05-JUN-14:20 20.00 15.11
July 0.235811E+10 3472.97 02-JUL-14:31 22.33 16.99 61208775.54 72.77 03-JUL-15:09 21.83 16.79
August 0.266208E+10 3267.80 20-AUG-13:11 23.67 18.43 69545247.09 71.40 14-AUG-15:39 23.67 18.43
September 0.285915E+10 4172.65 29-SEP-15:00 33.00 17.49 0.181868E+09 495.44 29-SEP-14:20 33.00 17.49
October 0.334265E+10 4634.65 16-OCT-14:30 31.00 15.99 0.315843E+09 495.49 18-OCT-11:50 24.50 17.54
November 0.267411E+10 3359.87 19-NOV-13:09 26.67 15.00 0.292182E+09 474.71 01-NOV-14:00 26.67 15.00
December 0.243268E+10 2994.91 19-DEC-13:30 24.50 10.72 0.269207E+09 472.03 05-DEC-15:00 24.50 10.72
                     
Annual Sum or Average 0.319051E+11         0.281339E+10        
Minimum of Months 0.219643E+10 2869.38   16.00 10.72 61208775.54 71.40   16.00 10.72
Maximum of Months 0.334265E+10 4634.65   33.00 18.43 0.315957E+09 495.49   33.00 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.216082E+10 3349.64 15-JAN-15:21 23.10 11.12 0.675552E+09 1205.75 18-JAN-15:39 22.33 15.21
February 0.199275E+10 3114.73 01-FEB-16:00 19.00 15.88 0.611201E+09 1179.41 03-FEB-15:00 21.00 10.02
March 0.241874E+10 3503.65 19-MAR-15:11 18.00 14.57 0.738150E+09 1210.03 23-MAR-14:00 22.00 17.40
April 0.271746E+10 4066.20 30-APR-16:41 22.00 15.83 0.694648E+09 1277.07 26-APR-14:50 22.00 15.83
May 0.307203E+10 3810.29 03-MAY-15:00 22.00 15.39 0.783047E+09 1277.18 03-MAY-14:20 22.00 15.39
June 0.313147E+10 4572.02 25-JUN-16:21 21.00 16.52 0.486362E+09 1277.19 05-JUN-14:20 21.00 16.52
July 0.250851E+10 4592.24 01-JUL-16:21 21.50 17.30 0.149856E+09 182.66 24-JUL-16:10 23.83 19.26
August 0.270525E+10 4257.86 06-AUG-15:52 24.00 19.90 0.168447E+09 179.89 14-AUG-16:10 24.67 18.50
September 0.291401E+10 4809.25 29-SEP-15:00 33.00 17.49 0.441933E+09 1277.23 29-SEP-14:20 33.00 17.49
October 0.340663E+10 4794.63 16-OCT-15:00 30.00 16.08 0.764265E+09 1277.21 16-OCT-14:20 30.00 16.08
November 0.251832E+10 3579.28 19-NOV-13:09 26.67 15.00 0.699854E+09 1192.03 10-NOV-15:20 26.67 15.00
December 0.215483E+10 3278.19 19-DEC-13:30 24.50 10.72 0.648289E+09 1188.29 05-DEC-15:50 24.50 10.72
                     
Annual Sum or Average 0.317008E+11         0.686161E+10        
Minimum of Months 0.199275E+10 3114.73   18.00 10.72 0.149856E+09 179.89   21.00 10.02
Maximum of Months 0.340663E+10 4809.25   33.00 19.90 0.783047E+09 1277.23   33.00 19.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100278E+11 12889.79 18-JAN-14:30 23.80 14.82 0.356779E+10 6092.69 18-JAN-15:00 22.00 15.39
February 0.924148E+10 12086.78 01-FEB-15:04 19.00 14.95 0.324154E+10 5966.38 03-FEB-15:30 22.00 9.51
March 0.110924E+11 12644.94 23-MAR-15:00 22.00 17.40 0.391817E+10 6110.44 23-MAR-14:00 22.00 17.40
April 0.111332E+11 14627.16 26-APR-14:10 25.50 16.68 0.363065E+10 6153.92 13-APR-14:20 25.50 16.68
May 0.126257E+11 15392.50 04-MAY-14:10 22.83 16.63 0.407708E+10 6154.22 24-MAY-11:09 21.00 15.42
June 0.125230E+11 15685.73 05-JUN-13:40 21.00 15.98 0.250867E+10 6153.88 07-JUN-14:20 19.00 14.25
July 0.928813E+10 15170.52 02-JUL-14:31 22.33 16.99 0.721216E+09 850.24 03-JUL-12:39 22.67 17.13
August 0.101117E+11 14223.43 20-AUG-13:11 23.67 18.43 0.809412E+09 824.66 14-AUG-13:20 23.67 18.43
September 0.116122E+11 18123.89 29-SEP-14:02 33.83 17.79 0.225869E+10 6153.94 29-SEP-14:20 33.67 17.73
October 0.140927E+11 18130.18 16-OCT-13:20 33.40 16.49 0.395193E+10 6154.10 18-OCT-11:39 25.00 17.41
November 0.111528E+11 12995.55 19-NOV-13:09 26.67 15.00 0.369864E+10 6020.30 10-NOV-15:20 26.67 15.00
December 0.100127E+11 13101.81 19-DEC-13:30 24.50 10.72 0.343639E+10 5997.35 05-DEC-15:00 24.50 10.72
                     
Annual Sum or Average 0.132914E+12         0.358202E+11        
Minimum of Months 0.924148E+10 12086.78   19.00 10.72 0.721216E+09 824.66   19.00 9.51
Maximum of Months 0.140927E+11 18130.18   33.83 18.43 0.407708E+10 6154.22   33.67 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.320496E+10 5180.72 15-JAN-15:06 23.70 11.44 0.764458E+09 1277.24 06-JAN-15:00 23.70 11.44
February 0.270214E+10 4879.70 21-FEB-15:03 18.67 14.13 0.669958E+09 1277.38 01-FEB-13:50 18.67 14.13
March 0.300799E+10 4903.66 11-MAR-15:47 22.00 13.04 0.784377E+09 1277.23 21-MAR-14:20 17.67 14.23
April 0.314846E+10 5251.91 30-APR-11:46 25.17 16.93 0.729508E+09 1277.23 10-APR-14:20 25.17 16.93
May 0.325783E+10 4270.92 03-MAY-15:00 22.00 15.39 0.789112E+09 1277.23 03-MAY-14:09 22.00 15.39
June 0.325472E+10 5498.39 04-JUN-15:41 19.17 14.74 0.481943E+09 1277.19 05-JUN-14:20 20.67 15.69
July 0.264888E+10 5356.72 30-JUL-13:10 24.00 19.79 0.150447E+09 189.51 31-JUL-15:39 24.67 20.10
August 0.311878E+10 6672.43 06-AUG-14:07 25.00 20.20 0.175397E+09 189.25 14-AUG-15:39 25.33 18.77
September 0.354806E+10 9363.05 30-SEP-15:32 30.00 18.24 0.463672E+09 1277.23 29-SEP-14:20 30.00 18.24
October 0.430482E+10 9326.72 15-OCT-15:32 30.33 15.09 0.809632E+09 1277.31 18-OCT-11:39 25.00 17.41
November 0.351956E+10 5601.32 18-NOV-14:38 24.67 14.62 0.783294E+09 1277.35 30-NOV-14:00 21.00 13.08
December 0.323761E+10 5415.09 19-DEC-14:40 22.33 9.68 0.736718E+09 1277.37 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.389538E+11         0.733852E+10        
Minimum of Months 0.264888E+10 4270.92   18.67 9.68 0.150447E+09 189.25   17.67 11.44
Maximum of Months 0.430482E+10 9363.05   30.33 20.20 0.809632E+09 1277.38   30.00 20.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157044E+11 29042.70 15-JAN-15:06 23.70 11.44 0.392946E+10 6153.98 06-JAN-15:00 23.70 11.44
February 0.131574E+11 28360.19 20-FEB-11:41 16.83 9.71 0.348880E+10 6154.75 01-FEB-13:50 16.83 9.71
March 0.145249E+11 24743.22 11-MAR-13:10 24.00 13.64 0.412489E+10 6153.93 07-MAR-15:20 24.00 13.64
April 0.141499E+11 32216.88 30-APR-11:46 25.17 16.93 0.373248E+10 6153.92 10-APR-14:20 25.17 16.93
May 0.144850E+11 18918.06 01-MAY-13:10 20.83 14.02 0.407245E+10 6154.38 24-MAY-11:09 21.00 15.42
June 0.139338E+11 18104.79 25-JUN-14:31 21.33 16.63 0.248139E+10 6153.88 07-JUN-14:20 21.33 16.63
July 0.104717E+11 17479.65 01-JUL-15:31 22.33 17.56 0.721086E+09 888.74 31-JUL-13:39 27.33 20.96
August 0.125160E+11 18026.66 06-AUG-14:08 25.00 20.20 0.847332E+09 890.25 14-AUG-13:20 25.67 20.38
September 0.154551E+11 32537.19 30-SEP-08:17 25.77 15.07 0.232474E+10 6155.55 28-SEP-11:09 25.77 15.07
October 0.197430E+11 34830.64 15-OCT-13:32 31.33 15.44 0.403099E+10 6308.51 16-OCT-13:09 33.75 16.65
November 0.167882E+11 26732.89 19-NOV-12:50 26.83 15.05 0.398286E+10 6155.54 28-NOV-11:20 23.33 9.66
December 0.157890E+11 32560.63 16-DEC-11:49 22.83 13.49 0.376786E+10 6154.71 07-DEC-12:09 22.83 13.49
                     
Annual Sum or Average 0.176718E+12         0.375043E+11        
Minimum of Months 0.104717E+11 17479.65   16.83 9.71 0.721086E+09 888.74   16.83 9.66
Maximum of Months 0.197430E+11 34830.64   31.33 20.20 0.412489E+10 6308.51   33.75 20.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.245678E+10 3025.96 15-JAN-15:07 23.70 11.44 0.281706E+09 482.17 18-JAN-15:00 22.00 15.39
February 0.221873E+10 2860.15 20-FEB-15:52 17.00 10.63 0.255479E+09 476.15 03-FEB-15:00 17.00 10.63
March 0.261717E+10 3035.09 19-MAR-15:42 18.00 14.87 0.304858E+09 484.40 24-MAR-14:00 18.00 15.44
April 0.262384E+10 3675.78 30-APR-11:46 25.17 16.93 0.289046E+09 495.44 28-APR-14:20 25.17 16.93
May 0.289527E+10 3443.76 03-MAY-15:00 22.00 15.39 0.322574E+09 495.46 03-MAY-14:09 22.00 15.39
June 0.297416E+10 3669.71 05-JUN-15:00 20.00 15.11 0.201464E+09 495.44 06-JUN-14:20 18.00 13.88
July 0.238431E+10 3398.09 02-JUL-14:10 22.83 17.20 62409328.37 73.81 03-JUL-15:20 21.67 16.74
August 0.268968E+10 3178.18 06-AUG-14:08 25.00 20.20 70957758.48 72.68 14-AUG-15:30 25.50 18.91
September 0.292852E+10 4375.42 29-SEP-15:00 33.00 17.49 0.184841E+09 495.44 29-SEP-11:30 33.00 17.49
October 0.338281E+10 4781.37 16-OCT-14:30 31.00 15.99 0.318238E+09 495.49 18-OCT-11:39 25.00 17.41
November 0.270213E+10 2981.11 20-NOV-13:00 19.00 15.88 0.296546E+09 482.22 13-NOV-15:20 19.00 15.88
December 0.246229E+10 3134.65 17-DEC-11:56 23.00 9.83 0.273309E+09 476.76 07-DEC-15:50 23.00 9.83
                     
Annual Sum or Average 0.323357E+11         0.286143E+10        
Minimum of Months 0.221873E+10 2860.15   17.00 9.83 62409328.37 72.68   17.00 9.83
Maximum of Months 0.338281E+10 4781.37   33.00 20.20 0.322574E+09 495.49   33.00 18.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215218E+10 3375.50 15-JAN-15:06 23.70 11.44 0.678625E+09 1210.61 18-JAN-15:50 22.17 15.30
February 0.199052E+10 3083.41 01-FEB-16:00 19.00 15.88 0.615234E+09 1192.85 03-FEB-15:00 21.00 10.02
March 0.242597E+10 3475.42 19-MAR-15:42 18.00 14.87 0.743800E+09 1225.78 23-MAR-14:00 22.00 17.40
April 0.271288E+10 4236.43 30-APR-11:46 25.17 16.93 0.702256E+09 1277.08 26-APR-14:50 25.17 16.93
May 0.305933E+10 3917.10 03-MAY-15:00 22.00 15.39 0.792943E+09 1277.22 30-MAY-14:20 19.33 14.36
June 0.313595E+10 5526.64 04-JUN-15:41 19.17 14.74 0.492521E+09 1277.19 05-JUN-14:20 20.67 15.69
July 0.252634E+10 4745.84 02-JUL-16:52 21.00 16.52 0.151784E+09 185.84 31-JUL-16:10 24.00 19.89
August 0.272750E+10 4230.11 19-AUG-16:52 24.00 17.65 0.170265E+09 182.93 14-AUG-16:10 24.00 17.65
September 0.292865E+10 5079.28 30-SEP-15:32 30.00 18.24 0.445979E+09 1277.23 29-SEP-14:20 30.00 18.24
October 0.339675E+10 4887.23 15-OCT-15:32 30.33 15.09 0.766684E+09 1277.21 16-OCT-14:20 31.33 15.95
November 0.251711E+10 3198.23 28-NOV-14:00 25.00 11.02 0.703165E+09 1207.59 10-NOV-15:20 25.00 11.02
December 0.215120E+10 3335.37 19-DEC-14:00 23.00 9.83 0.649667E+09 1189.31 05-DEC-15:00 23.00 9.83
                     
Annual Sum or Average 0.317244E+11         0.691292E+10        
Minimum of Months 0.199052E+10 3083.41   18.00 9.83 0.151784E+09 182.93   19.33 9.83
Maximum of Months 0.339675E+10 5526.64   30.33 18.24 0.792943E+09 1277.23   31.33 19.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.656266E+10 8708.89 18-JAN-14:30 23.80 14.82 0.235661E+10 4023.51 18-JAN-15:00 22.00 15.39
February 0.606211E+10 7882.11 01-FEB-15:40 19.00 15.51 0.214576E+10 3950.64 03-FEB-15:39 21.67 9.69
March 0.729771E+10 8223.76 23-MAR-15:00 22.00 17.40 0.259721E+10 4040.86 23-MAR-14:00 22.00 17.40
April 0.735994E+10 10543.63 30-APR-11:46 25.17 16.93 0.241381E+10 4063.91 13-APR-14:20 25.17 16.93
May 0.839683E+10 10489.47 04-MAY-13:40 23.00 16.67 0.271175E+10 4064.20 24-MAY-11:09 21.00 15.42
June 0.839131E+10 10666.13 05-JUN-13:40 21.00 15.98 0.166827E+10 4063.88 07-JUN-14:20 19.00 14.25
July 0.621669E+10 9856.55 01-JUL-15:31 22.33 17.56 0.482585E+09 566.28 03-JUL-12:39 22.67 17.13
August 0.673803E+10 9148.48 06-AUG-14:08 25.00 20.20 0.539677E+09 551.08 14-AUG-13:30 25.50 20.34
September 0.774348E+10 12121.78 29-SEP-14:02 33.83 17.79 0.149799E+10 4063.92 29-SEP-14:20 33.67 17.73
October 0.927735E+10 11907.47 16-OCT-13:30 33.05 16.33 0.260689E+10 4064.02 18-OCT-11:39 25.00 17.41
November 0.732595E+10 8426.45 28-NOV-13:50 24.83 10.89 0.244194E+10 4001.47 10-NOV-15:20 24.83 10.89
December 0.656101E+10 8820.82 19-DEC-13:30 24.50 10.72 0.226185E+10 3940.22 07-DEC-15:50 24.50 10.72
                     
Annual Sum or Average 0.879331E+11         0.237243E+11        
Minimum of Months 0.606211E+10 7882.11   19.00 10.72 0.482585E+09 551.08   19.00 9.69
Maximum of Months 0.927735E+10 12121.78   33.83 20.20 0.271175E+10 4064.20   33.67 20.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.456051E+10 6309.89 24-JAN-15:05 24.83 15.39 0.181367E+10 2080.61 18-JAN-16:30 24.83 15.39
February 0.416269E+10 4987.17 01-FEB-14:10 19.00 15.70 0.165602E+10 2040.02 03-FEB-15:39 21.67 9.69
March 0.506522E+10 6782.32 19-MAR-11:59 21.00 15.98 0.200746E+10 2082.69 23-MAR-15:20 21.67 17.34
April 0.506005E+10 7476.17 08-APR-12:31 22.33 16.70 0.185632E+10 2090.02 13-APR-14:20 20.00 15.65
May 0.578299E+10 7704.29 06-MAY-13:22 19.35 15.26 0.207395E+10 2090.20 24-MAY-11:09 21.00 15.42
June 0.639961E+10 8013.07 10-JUN-13:32 21.00 15.97 0.211196E+10 2090.00 07-JUN-14:20 21.00 15.97
July 0.480894E+10 7557.02 01-JUL-08:22 21.00 17.12 0.869727E+09 995.88 31-JUL-14:09 26.83 20.78
August 0.502982E+10 7011.75 12-AUG-11:42 23.83 18.68 0.981146E+09 981.76 07-AUG-14:09 23.83 18.68
September 0.574697E+10 7967.50 23-SEP-10:41 21.83 18.03 0.184718E+10 2090.01 29-SEP-14:20 33.67 17.73
October 0.624156E+10 7976.28 05-OCT-06:01 20.00 18.62 0.198273E+10 2090.01 23-OCT-14:20 18.33 14.83
November 0.488116E+10 6672.53 18-NOV-12:30 25.50 14.73 0.188682E+10 2066.67 10-NOV-14:09 25.50 14.73
December 0.444906E+10 6418.28 05-DEC-15:10 24.67 13.10 0.174854E+10 2048.90 05-DEC-16:30 22.00 12.40
                     
Annual Sum or Average 0.621886E+11         0.208355E+11        
Minimum of Months 0.416269E+10 4987.17   19.00 13.10 0.869727E+09 981.76   18.33 9.69
Maximum of Months 0.639961E+10 8013.07   25.50 18.68 0.211196E+10 2090.20   33.67 20.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.341873E+10 6110.25 18-JAN-14:40 23.53 14.82 0.900963E+09 1408.96 17-JAN-09:50 23.53 14.82
February 0.336451E+10 6346.88 03-FEB-15:10 22.67 9.08 0.837143E+09 1409.04 01-FEB-13:50 22.67 9.08
March 0.428528E+10 7790.21 23-MAR-15:00 22.00 17.40 0.101398E+10 1408.98 13-MAR-08:00 22.00 17.40
April 0.592299E+10 12179.69 27-APR-07:01 16.17 14.82 0.891120E+09 1432.64 27-APR-07:10 16.17 14.82
May 0.702010E+10 12422.18 01-MAY-07:01 15.15 12.62 0.980794E+09 1468.65 01-MAY-07:10 15.15 12.62
June 0.770708E+10 12810.04 26-JUN-06:12 18.00 15.44 0.605105E+09 1481.93 05-JUN-07:10 18.00 15.44
July 0.544762E+10 12344.81 03-JUL-06:12 18.00 15.44 0.208091E+09 232.87 03-JUL-07:10 18.17 15.52
August 0.563427E+10 11983.18 07-AUG-07:03 19.50 18.53 0.239196E+09 228.37 21-AUG-07:10 17.00 15.07
September 0.672082E+10 12749.15 25-SEP-06:12 17.33 16.49 0.550076E+09 1498.55 25-SEP-07:10 18.00 16.69
October 0.733126E+10 13061.20 02-OCT-06:12 19.33 17.79 0.936504E+09 1523.72 02-OCT-07:10 20.00 18.03
November 0.431965E+10 6656.83 01-NOV-14:15 17.00 13.28 0.932537E+09 1409.02 30-NOV-15:09 20.50 12.92
December 0.345180E+10 6112.92 07-DEC-14:30 20.00 15.38 0.879873E+09 1409.06 20-DEC-15:09 18.67 12.31
                     
Annual Sum or Average 0.646241E+11         0.897538E+10        
Minimum of Months 0.336451E+10 6110.25   15.15 9.08 0.208091E+09 228.37   15.15 9.08
Maximum of Months 0.770708E+10 13061.20   23.53 18.53 0.101398E+10 1523.72   23.53 18.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119977E+10 7894.94 22-JAN-15:29 16.00 12.29 0.486060E+09 883.14 24-JAN-15:39 24.33 15.19
February 0.835982E+09 6708.83 20-FEB-14:32 17.00 11.61 0.420536E+09 882.60 01-FEB-13:39 17.00 11.61
March 0.796080E+09 3376.41 23-MAR-14:00 23.00 17.27 0.487466E+09 882.52 10-MAR-15:09 23.00 17.27
April 0.125499E+10 7020.97 26-APR-14:10 25.50 16.68 0.471895E+09 906.67 26-APR-14:20 25.00 16.61
May 0.130455E+10 3121.74 03-MAY-13:00 24.00 15.05 0.511188E+09 882.55 03-MAY-13:00 23.00 16.67
June 0.155030E+10 2280.99 25-JUN-14:51 21.00 16.52 0.324325E+09 882.51 14-JUN-12:00 21.00 16.52
July 0.178668E+10 7342.39 31-JUL-14:10 26.83 20.78 0.118120E+09 154.51 31-JUL-14:20 26.67 20.72
August 0.207629E+10 7687.35 17-AUG-14:10 27.78 21.12 0.138960E+09 162.45 17-AUG-14:20 27.57 21.05
September 0.209884E+10 10385.64 29-SEP-14:10 33.83 17.79 0.321377E+09 1488.90 29-SEP-14:20 33.67 17.73
October 0.313976E+10 9582.67 16-OCT-14:10 31.67 15.90 0.564964E+09 1351.64 16-OCT-14:20 31.33 15.95
November 0.141142E+10 7763.09 19-NOV-11:38 26.00 15.32 0.502693E+09 882.87 28-NOV-14:39 23.67 10.89
December 0.144619E+10 7530.29 31-DEC-12:35 19.00 10.66 0.475258E+09 889.92 05-DEC-15:20 19.00 10.66
                     
Annual Sum or Average 0.189009E+11         0.482284E+10        
Minimum of Months 0.796080E+09 2280.99   16.00 10.66 0.118120E+09 154.51   17.00 10.66
Maximum of Months 0.313976E+10 10385.64   33.83 21.12 0.564964E+09 1488.90   33.67 21.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.115647E+10 1684.83 20-JAN-13:20 18.33 15.04 0.152139E+09 247.12 25-JAN-15:00 15.00 13.80
February 0.107350E+10 1663.15 03-FEB-15:00 23.00 8.84 0.142210E+09 247.13 01-FEB-14:09 23.00 8.84
March 0.135211E+10 2397.99 19-MAR-13:28 19.50 14.94 0.172200E+09 247.12 22-MAR-12:39 22.00 17.22
April 0.167592E+10 7375.06 29-APR-14:31 19.73 14.53 0.155103E+09 247.13 13-APR-14:09 19.73 14.53
May 0.194818E+10 7361.28 06-MAY-13:22 19.35 15.26 0.171166E+09 247.14 24-MAY-11:09 21.00 15.42
June 0.225701E+10 7402.61 18-JUN-12:41 23.00 17.76 0.105824E+09 247.12 13-JUN-12:09 23.00 17.76
July 0.145964E+10 7365.73 01-JUL-10:41 23.83 17.98 35708036.54 39.02 17-JUL-10:00 23.00 18.43
August 0.151044E+10 7317.35 12-AUG-15:52 21.00 17.71 40907621.39 39.02 22-AUG-13:09 22.67 17.06
September 0.197458E+10 7391.71 23-SEP-10:41 21.83 18.03 96112066.43 247.12 20-SEP-12:09 21.83 18.03
October 0.208729E+10 7416.84 05-OCT-06:01 20.00 18.62 0.163527E+09 247.14 18-OCT-12:09 23.83 17.80
November 0.130234E+10 1868.68 01-NOV-14:03 17.00 13.37 0.160628E+09 247.13 29-NOV-15:50 17.17 10.97
December 0.111985E+10 1654.85 07-DEC-14:30 20.00 15.38 0.149300E+09 247.13 20-DEC-15:09 18.67 12.31
                     
Annual Sum or Average 0.189173E+11         0.154482E+10        
Minimum of Months 0.107350E+10 1654.85   17.00 8.84 35708036.54 39.02   15.00 8.84
Maximum of Months 0.225701E+10 7416.84   23.83 18.62 0.172200E+09 247.14   23.83 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.943439E+09 1326.92 24-JAN-15:05 24.83 15.39 0.320451E+09 566.97 18-JAN-15:30 24.83 15.39
February 0.895539E+09 1117.28 03-FEB-16:00 21.00 10.02 0.302676E+09 578.16 03-FEB-15:00 21.00 10.02
March 0.111822E+10 1328.05 12-MAR-14:31 18.67 15.58 0.371871E+09 610.61 23-MAR-14:00 22.00 17.40
April 0.120457E+10 6528.62 29-APR-16:20 18.33 14.18 0.362758E+09 621.11 13-APR-14:20 18.33 14.18
May 0.137646E+10 5578.80 28-MAY-17:12 18.33 14.18 0.406678E+09 621.10 01-MAY-14:20 18.33 14.18
June 0.154865E+10 7425.18 25-JUN-16:10 21.00 16.52 0.254642E+09 621.10 01-JUN-14:20 21.00 16.52
July 0.133160E+10 7676.43 01-JUL-15:52 22.00 17.40 84705340.80 98.07 24-JUL-16:30 23.50 19.16
August 0.140058E+10 7670.45 19-AUG-16:52 24.00 17.65 96173442.68 98.07 14-AUG-16:10 24.00 17.65
September 0.135982E+10 7432.18 30-SEP-16:22 27.50 18.25 0.230473E+09 621.10 29-SEP-14:20 27.50 18.25
October 0.143667E+10 2390.32 16-OCT-15:00 30.00 16.08 0.387484E+09 621.10 18-OCT-12:00 23.00 18.43
November 0.105622E+10 1225.59 18-NOV-12:30 25.50 14.73 0.349003E+09 581.61 10-NOV-15:20 25.50 14.73
December 0.934986E+09 1380.21 05-DEC-15:10 24.67 13.10 0.315005E+09 567.21 07-DEC-15:20 18.67 15.17
                     
Annual Sum or Average 0.146068E+11         0.348192E+10        
Minimum of Months 0.895539E+09 1117.28   18.33 10.02 84705340.80 98.07   18.33 10.02
Maximum of Months 0.154865E+10 7676.43   30.00 18.25 0.406678E+09 621.11   27.50 19.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.634637E+10 16183.27 22-JAN-11:24 16.50 11.73 0.650891E+09 1138.07 06-JAN-16:10 16.50 11.73
February 0.539479E+10 14612.01 20-FEB-13:08 17.00 10.37 0.588443E+09 1138.19 01-FEB-13:50 17.00 10.37
March 0.607689E+10 21463.44 12-MAR-14:31 18.67 15.58 0.710091E+09 1138.05 13-MAR-07:00 14.00 12.84
April 0.760221E+10 21418.94 30-APR-12:01 24.83 16.89 0.624676E+09 1141.49 26-APR-07:10 24.83 16.89
May 0.793801E+10 17989.20 01-MAY-07:01 15.15 12.62 0.687339E+09 1191.93 01-MAY-07:10 15.15 12.62
June 0.911422E+10 17913.21 19-JUN-07:03 18.33 15.57 0.688000E+09 1228.80 19-JUN-07:10 18.33 15.57
July 0.746873E+10 20784.76 30-JUL-13:26 24.00 19.60 0.353416E+09 651.57 24-JUL-07:10 24.00 19.60
August 0.856305E+10 21474.28 06-AUG-12:51 26.00 20.47 0.406512E+09 651.86 07-AUG-07:10 19.50 18.53
September 0.955268E+10 22387.91 30-SEP-11:42 31.83 17.26 0.612000E+09 1246.12 11-SEP-07:10 31.83 17.26
October 0.105769E+11 22060.97 15-OCT-09:52 31.00 16.50 0.657294E+09 1246.31 16-OCT-07:10 25.50 12.31
November 0.737410E+10 20888.34 18-NOV-12:30 25.50 14.73 0.655968E+09 1186.65 20-NOV-08:09 11.33 11.16
December 0.648965E+10 12440.39 19-DEC-13:20 25.00 11.01 0.623233E+09 1148.21 05-DEC-08:09 25.00 11.01
                     
Annual Sum or Average 0.924976E+11         0.725786E+10        
Minimum of Months 0.539479E+10 12440.39   15.15 10.37 0.353416E+09 651.57   11.33 10.37
Maximum of Months 0.105769E+11 22387.91   31.83 20.47 0.710091E+09 1246.31   31.83 19.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.718027E+10 27649.82 17-JAN-06:01 15.83 13.52 0.327410E+10 5528.77 20-JAN-16:49 16.17 14.73
February 0.664834E+10 26016.63 16-FEB-07:01 12.25 11.69 0.298024E+10 5528.78 01-FEB-16:49 12.25 11.69
March 0.846587E+10 34758.50 20-MAR-05:01 10.83 10.73 0.357665E+10 5528.79 22-MAR-17:49 16.33 14.89
April 0.959588E+10 37275.61 17-APR-05:01 11.00 9.40 0.316175E+10 5528.99 11-APR-15:50 11.00 9.40
May 0.107051E+11 40200.55 24-MAY-05:02 15.17 7.58 0.347894E+10 5528.80 05-MAY-17:10 15.17 7.58
June 0.117416E+11 35753.50 05-JUN-05:01 12.17 11.07 0.347982E+10 5529.08 14-JUN-15:00 22.00 16.85
July 0.963623E+10 31280.86 10-JUL-05:01 17.00 13.94 0.190644E+10 2037.01 03-JUL-11:50 17.00 13.94
August 0.102500E+11 30872.77 28-AUG-05:01 14.00 14.00 0.219240E+10 2036.97 14-AUG-15:50 14.00 14.00
September 0.101402E+11 33933.24 29-SEP-05:01 18.30 11.33 0.310050E+10 5529.07 05-SEP-15:39 18.30 11.33
October 0.102393E+11 39503.97 18-OCT-05:02 15.00 8.51 0.332152E+10 5529.01 30-OCT-15:39 24.00 16.44
November 0.787425E+10 40859.01 20-NOV-06:01 9.33 7.59 0.331680E+10 5528.82 10-NOV-17:10 9.33 7.59
December 0.698602E+10 29014.48 06-DEC-06:01 12.33 6.18 0.313835E+10 5528.76 07-DEC-16:49 16.33 14.28
                     
Annual Sum or Average 0.109463E+12         0.369275E+11        
Minimum of Months 0.664834E+10 26016.63   9.33 6.18 0.190644E+10 2036.97   9.33 7.58
Maximum of Months 0.117416E+11 40859.01   18.30 14.00 0.357665E+10 5529.08   24.00 16.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.168000E+11 57384.82 09-JAN-06:01 2.17 -0.2 0.642822E+10 8102.79 24-JAN-11:00 23.00 14.79
February 0.153482E+11 51793.88 06-FEB-06:11 9.00 1.66 0.581077E+10 8103.19 01-FEB-11:00 9.00 1.66
March 0.181981E+11 49959.93 07-MAR-05:12 5.00 4.22 0.671372E+10 8102.85 20-MAR-10:00 17.00 13.94
April 0.182030E+11 39696.89 20-APR-05:01 9.17 8.59 0.617519E+10 8233.34 26-APR-10:00 26.00 18.33
May 0.196827E+11 43062.11 15-MAY-05:01 8.50 7.86 0.657108E+10 8102.86 30-MAY-11:00 20.00 14.58
June 0.190884E+11 36666.08 13-JUN-05:01 11.33 10.19 0.611521E+10 8137.76 14-JUN-10:00 23.00 17.27
July 0.173353E+11 31502.32 11-JUL-03:32 17.00 14.51 0.565783E+10 7022.27 31-JUL-10:00 27.00 20.84
August 0.181168E+11 33113.64 22-AUG-04:12 15.67 13.45 0.599195E+10 7024.97 14-AUG-10:00 15.67 13.45
September 0.179875E+11 34481.40 20-SEP-05:01 12.00 10.91 0.586281E+10 8270.87 22-SEP-10:50 22.00 20.03
October 0.194897E+11 45003.86 26-OCT-05:01 11.00 5.61 0.643134E+10 8283.15 16-OCT-10:00 11.00 5.61
November 0.172867E+11 51179.66 30-NOV-06:01 8.00 2.20 0.631761E+10 8102.85 09-NOV-11:00 8.00 2.20
December 0.163835E+11 55574.60 26-DEC-06:01 7.00 1.09 0.628546E+10 8102.83 08-DEC-11:00 7.00 1.09
                     
Annual Sum or Average 0.213920E+12         0.743612E+11        
Minimum of Months 0.153482E+11 31502.32   2.17 -0.2 0.565783E+10 7022.27   7.00 1.09
Maximum of Months 0.196827E+11 57384.82   17.00 14.51 0.671372E+10 8283.15   27.00 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138684E+11 27577.37 19-JAN-09:06 18.50 13.10 0.921386E+10 16259.89 17-JAN-14:09 18.50 13.10
February 0.129024E+11 24001.10 01-FEB-09:07 22.33 11.86 0.829675E+10 16259.96 13-FEB-11:09 17.00 15.07
March 0.159934E+11 24558.19 23-MAR-08:06 17.33 14.09 0.997086E+10 16260.88 23-MAR-11:09 22.00 16.77
April 0.150349E+11 29329.12 27-APR-05:01 15.00 14.41 0.901812E+10 16261.11 27-APR-10:09 21.00 16.52
May 0.168670E+11 37071.47 01-MAY-05:01 13.17 11.94 0.997688E+10 16261.19 04-MAY-11:30 23.00 15.97
June 0.176660E+11 46829.30 06-JUN-05:01 16.00 13.67 0.100564E+11 16261.47 26-JUN-11:30 23.50 18.58
July 0.827630E+10 47062.30 10-JUL-05:01 17.00 13.94 0.233376E+10 5990.03 24-JUL-17:19 22.67 19.10
August 0.895333E+10 45755.94 28-AUG-05:01 14.00 14.00 0.268228E+10 5989.96 14-AUG-16:49 14.00 14.00
September 0.152510E+11 43938.84 26-SEP-05:01 15.83 14.71 0.880109E+10 17067.40 29-SEP-12:09 36.00 18.21
October 0.162738E+11 58524.32 16-OCT-05:01 18.67 9.56 0.961000E+10 17991.38 16-OCT-11:20 36.67 17.78
November 0.145833E+11 25669.43 10-NOV-09:06 18.33 14.79 0.932593E+10 16259.37 20-NOV-10:20 16.67 14.43
December 0.133606E+11 29480.02 19-DEC-09:06 19.67 7.57 0.880441E+10 16259.26 08-DEC-10:50 19.67 7.57
                     
Annual Sum or Average 0.169030E+12         0.980904E+11        
Minimum of Months 0.827630E+10 24001.10   13.17 7.57 0.233376E+10 5989.96   14.00 7.57
Maximum of Months 0.176660E+11 58524.32   22.33 14.79 0.100564E+11 17991.38   36.67 19.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.694090E+10 10756.08 18-JAN-14:10 24.33 14.82 0.133279E+10 2059.38 06-JAN-15:00 24.33 14.82
February 0.644702E+10 10319.96 01-FEB-13:00 24.00 13.82 0.121755E+10 2059.62 01-FEB-13:50 19.83 15.75
March 0.806195E+10 11995.37 23-MAR-14:00 23.00 17.27 0.147623E+10 2059.33 13-MAR-08:20 23.00 17.27
April 0.961379E+10 14217.88 26-APR-13:30 26.50 16.94 0.130046E+10 2059.44 13-APR-10:09 26.50 16.94
May 0.110506E+11 14666.85 29-MAY-10:00 21.00 15.98 0.143191E+10 2060.66 04-MAY-07:10 21.00 15.98
June 0.119061E+11 18686.46 05-JUN-07:02 17.17 14.01 0.883740E+09 2104.40 05-JUN-07:10 17.17 14.01
July 0.828704E+10 19580.69 23-JUL-09:21 25.00 19.90 0.301851E+09 328.29 24-JUL-07:10 17.67 17.28
August 0.859702E+10 17735.57 19-AUG-09:37 24.00 19.90 0.345869E+09 325.18 07-AUG-15:30 24.00 19.90
September 0.104896E+11 18323.73 10-SEP-08:37 21.00 17.14 0.802791E+09 2059.34 25-SEP-07:19 18.00 16.69
October 0.116296E+11 20367.56 05-OCT-06:12 20.00 18.62 0.136704E+10 2134.11 05-OCT-07:10 20.00 18.62
November 0.795289E+10 10693.16 10-NOV-13:10 20.83 16.38 0.135734E+10 2059.53 30-NOV-15:09 20.50 12.92
December 0.683659E+10 10442.98 05-DEC-15:50 23.33 12.56 0.128288E+10 2059.59 20-DEC-15:09 18.67 12.31
                     
Annual Sum or Average 0.107813E+12         0.131005E+11        
Minimum of Months 0.644702E+10 10319.96   17.17 12.56 0.301851E+09 325.18   17.17 12.31
Maximum of Months 0.119061E+11 20367.56   26.50 19.90 0.147623E+10 2134.11   26.50 19.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7804199.32 4306.66 03-JAN-07:11 4.33
February 5536912.53 3783.01 27-FEB-08:61 9.50
March 13219042.86 4514.92 30-MAR-06:12 5.87
April 4040867.43 3755.50 19-APR-07:01 12.33
May 3639394.13 3734.82 15-MAY-07:01 13.50
June 3433782.18 3713.61 01-JUN-07:01 14.33
July 5329379.14 3705.03 27-JUL-07:01 16.50
August 6405026.41 3687.60 24-AUG-07:02 17.17
September 781722.25 3720.35 01-SEP-07:01 16.17
October 1058785.05 3746.19 25-OCT-07:01 13.83
November 3749074.11 3750.93 30-NOV-08:61 12.83
December 4418658.87 4035.14 13-DEC-07:12 7.33
         
Annual Sum or Average 59416844.28      
Minimum of Months 781722.25 3687.60   4.33
Maximum of Months 13219042.86 4514.92   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8717495.42 12297.91 03-JAN-08:61 7.67
February 7491977.33 12247.30 27-FEB-08:61 9.50
March 20661803.45 12357.86 30-MAR-07:01 7.33
April 4925705.45 11715.25 19-APR-07:01 12.33
May 6753785.49 11984.76 15-MAY-07:01 13.50
June 469796.04 3901.88 01-JUN-07:01 14.33
July 17653238.26 12083.56 14-JUL-07:02 17.33
August 18763693.77 12038.99 24-AUG-07:02 17.17
September 1129833.25 11989.87 01-SEP-07:01 16.17
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 2447663.31 12187.07 13-DEC-08:61 8.50
         
Annual Sum or Average 89014991.75      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 20661803.45 12357.86   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4349283.55 3060.92 03-JAN-08:61 7.67
February 1391391.57 2885.53 28-FEB-08:61 12.97
March 3950734.91 3053.70 30-MAR-07:01 7.33
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 65213.29 652.13 14-JUL-07:02 17.33
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 570123.28 2839.60 15-DEC-08:61 9.50
         
Annual Sum or Average 10326746.61      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 4349283.55 3060.92   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 32882609.23 4534.76 09-JAN-07:11 4.33
February 12325492.16 4028.34 06-FEB-07:12 10.00
March 20498952.72 4345.21 30-MAR-06:12 5.87
April 4265176.41 3609.60 19-APR-07:01 12.33
May 3152655.06 3583.01 15-MAY-07:01 13.50
June 1474726.84 3565.72 01-JUN-07:01 14.33
July 3919538.71 3549.26 14-JUL-07:02 17.33
August 7098952.07 3553.04 24-AUG-07:02 17.17
September 2149582.83 3589.38 01-SEP-07:01 16.17
October 1974940.31 3619.18 30-OCT-07:01 13.67
November 7674435.68 3879.58 24-NOV-07:12 9.00
December 15829798.12 4193.06 26-DEC-07:12 8.33
         
Annual Sum or Average 0.113247E+09      
Minimum of Months 1474726.84 3549.26   4.33
Maximum of Months 32882609.23 4534.76   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 28260584.34 12584.67 03-JAN-07:11 4.33
February 18970197.27 11241.38 06-FEB-08:61 12.33
March 24853554.91 11240.14 30-MAR-07:01 7.33
April 6497879.76 10912.88 03-APR-07:01 11.83
May 1384702.66 10431.33 15-MAY-07:01 13.50
June 0.00 0.00 01-JUN-00:03 13.07
July 8354284.09 10947.34 14-JUL-07:02 17.33
August 18778139.62 11006.09 24-AUG-07:02 17.17
September 1835589.57 11133.10 01-SEP-07:01 16.17
October 824075.89 10651.96 30-OCT-07:01 13.67
November 12451170.78 11195.58 24-NOV-08:61 10.67
December 19874459.84 11263.23 26-DEC-08:61 11.83
         
Annual Sum or Average 0.142085E+09      
Minimum of Months 0.00 0.00   4.33
Maximum of Months 28260584.34 12584.67   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8849367.40 4339.08 03-JAN-07:11 4.33
February 5404731.66 3750.80 27-FEB-08:61 9.50
March 12842580.94 4474.88 30-MAR-06:12 5.87
April 3918034.75 3721.65 19-APR-07:01 12.33
May 3442211.42 3701.43 15-MAY-07:01 13.50
June 3231475.67 3682.21 01-JUN-07:01 14.33
July 5288475.13 3673.63 27-JUL-07:01 16.50
August 6529960.92 3653.86 24-AUG-07:02 17.17
September 690392.71 3687.23 01-SEP-07:01 16.17
October 983078.84 3708.85 25-OCT-07:01 13.83
November 3615771.54 3721.57 30-NOV-08:61 12.83
December 4604710.92 4042.16 13-DEC-07:12 7.33
         
Annual Sum or Average 59400791.91      
Minimum of Months 690392.71 3653.86   4.33
Maximum of Months 12842580.94 4474.88   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9551427.91 12050.42 03-JAN-08:61 7.67
February 6449694.93 11981.02 27-FEB-08:61 9.50
March 19159989.91 12076.20 30-MAR-07:01 7.33
April 3219347.12 11261.42 19-APR-07:01 12.33
May 6086140.89 11563.15 15-MAY-07:01 13.50
June 0.00 0.00 01-JUN-00:03 13.07
July 16748350.74 11806.97 14-JUL-07:02 17.33
August 18402712.52 11763.50 24-AUG-07:02 17.17
September 1070158.09 11700.68 01-SEP-07:01 16.17
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 2856467.89 11960.19 13-DEC-08:61 8.50
         
Annual Sum or Average 83544290.00      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 19159989.91 12076.20   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4554612.33 3051.40 03-JAN-08:61 7.67
February 1385711.83 2872.12 28-FEB-08:61 12.97
March 3882293.20 3041.99 30-MAR-07:01 7.33
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 57958.78 579.59 14-JUL-07:02 17.33
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 772688.79 2842.07 15-DEC-08:61 9.50
         
Annual Sum or Average 10653264.92      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 4554612.33 3051.40   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 33358456.51 4557.88 03-JAN-07:11 4.33
February 12294547.59 4035.37 06-FEB-07:12 10.00
March 20401531.54 4356.13 30-MAR-06:12 5.87
April 4272466.78 3617.60 19-APR-07:01 12.33
May 3148810.03 3590.53 15-MAY-07:01 13.50
June 1419838.59 3565.03 01-JUN-07:01 14.33
July 3858637.24 3557.55 14-JUL-07:02 17.33
August 7122283.77 3560.14 24-AUG-07:02 17.17
September 2137724.05 3598.07 01-SEP-07:01 16.17
October 1968501.59 3627.50 30-OCT-07:01 13.67
November 7578622.13 3887.24 24-NOV-07:12 9.00
December 15961254.27 4202.04 26-DEC-07:12 8.33
         
Annual Sum or Average 0.113523E+09      
Minimum of Months 1419838.59 3557.55   4.33
Maximum of Months 33358456.51 4557.88   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 29311203.56 12688.26 03-JAN-07:11 4.33
February 19093651.80 11275.58 06-FEB-08:61 12.33
March 24604437.77 11272.51 30-MAR-07:01 7.33
April 6468058.33 10954.44 03-APR-07:01 11.83
May 1445049.50 10463.84 15-MAY-07:01 13.50
June 0.00 0.00 01-JUN-00:03 13.07
July 8502917.72 10991.73 14-JUL-07:02 17.33
August 19074308.73 11039.18 24-AUG-07:02 17.17
September 1841265.78 11168.49 01-SEP-07:01 16.17
October 860493.32 10688.81 30-OCT-07:01 13.67
November 12555391.05 11231.25 24-NOV-08:61 10.67
December 20509127.71 11302.10 26-DEC-08:61 11.83
         
Annual Sum or Average 0.144266E+09      
Minimum of Months 0.00 0.00   4.33
Maximum of Months 29311203.56 12688.26   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7677591.46 4249.97 03-JAN-07:11 4.33
February 5005658.41 3709.70 27-FEB-08:61 9.50
March 11999098.04 4382.56 30-MAR-06:12 5.87
April 3561382.97 3680.36 19-APR-07:01 12.33
May 2919250.07 3659.76 15-MAY-07:01 13.50
June 2399522.17 3613.13 01-JUN-07:01 14.33
July 4688124.87 3621.61 14-JUL-07:02 17.33
August 5508113.66 3615.60 24-AUG-07:02 17.17
September 496080.05 3647.14 01-SEP-07:01 16.17
October 767335.81 3633.43 25-OCT-07:01 13.83
November 3275462.77 3674.67 03-NOV-07:01 11.50
December 4254628.35 3950.59 13-DEC-07:12 7.33
         
Annual Sum or Average 52552248.64      
Minimum of Months 496080.05 3613.13   4.33
Maximum of Months 11999098.04 4382.56   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7726844.54 11923.21 03-JAN-08:61 7.67
February 4994268.36 11806.54 27-FEB-08:61 9.50
March 13485427.30 11952.82 30-MAR-07:01 7.33
April 577753.39 5554.89 19-APR-07:01 12.33
May 1330352.70 11011.24 15-MAY-07:01 13.50
June 0.00 0.00 01-JUN-00:03 13.07
July 12626827.06 11682.83 14-JUL-07:02 17.33
August 10885818.75 11518.72 24-AUG-07:02 17.17
September 969962.55 11316.23 01-SEP-07:01 16.17
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 2017974.07 11494.04 13-DEC-08:61 8.50
         
Annual Sum or Average 54615228.74      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 13485427.30 11952.82   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4072100.35 3027.58 03-JAN-08:61 7.67
February 554681.57 2796.66 28-FEB-08:61 12.97
March 2478861.38 2980.97 30-MAR-07:01 7.33
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 496990.83 2766.62 15-DEC-08:61 9.50
         
Annual Sum or Average 7602634.13      
Minimum of Months 0.00 0.00   7.33
Maximum of Months 4072100.35 3027.58   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 33688925.64 4527.30 09-JAN-07:11 4.33
February 12022959.59 4018.25 06-FEB-07:12 10.00
March 19565266.52 4316.05 30-MAR-06:12 5.87
April 4119763.45 3612.37 19-APR-07:01 12.33
May 2886277.95 3585.33 15-MAY-07:01 13.50
June 764917.46 3533.13 01-JUN-07:01 14.33
July 3168604.61 3550.87 14-JUL-07:02 17.33
August 6293291.21 3557.73 24-AUG-07:02 17.17
September 1757379.90 3594.39 01-SEP-07:01 16.17
October 1963986.09 3622.87 30-OCT-07:01 13.67
November 7684156.91 3884.83 24-NOV-07:12 9.00
December 16099636.52 4184.58 26-DEC-07:12 8.33
         
Annual Sum or Average 0.110015E+09      
Minimum of Months 764917.46 3533.13   4.33
Maximum of Months 33688925.64 4527.30   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20918841.31 8531.85 03-JAN-07:11 4.33
February 12980282.26 7585.77 06-FEB-08:61 12.33
March 16598004.27 7579.57 30-MAR-07:01 7.33
April 3715599.49 7336.40 03-APR-07:01 11.83
May 343044.87 5145.67 15-MAY-07:01 13.50
June 0.00 0.00 01-JUN-00:03 13.07
July 3974237.44 7316.27 14-JUL-07:02 17.33
August 10412123.11 7422.21 24-AUG-07:02 17.17
September 1238565.83 7505.38 01-SEP-07:01 16.17
October 728183.55 7249.90 30-OCT-07:01 13.67
November 8899611.62 7557.66 24-NOV-08:61 10.67
December 14388391.15 7935.53 26-DEC-07:12 8.33
         
Annual Sum or Average 94196884.90      
Minimum of Months 0.00 0.00   4.33
Maximum of Months 20918841.31 8531.85   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6214731.76 4173.26 03-JAN-07:11 4.33
February 3962515.27 3873.34 06-FEB-08:61 12.33
March 5322200.92 3878.11 30-MAR-07:01 7.33
April 211981.93 3533.03 03-APR-07:01 11.83
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 721199.41 3522.35 14-JUL-07:02 17.33
August 1953537.80 3610.38 24-AUG-07:02 17.17
September 318240.15 3712.80 01-SEP-07:01 16.17
October 131572.70 2192.88 30-OCT-07:01 13.67
November 1437482.31 3759.20 24-NOV-08:61 10.67
December 4099209.94 3890.05 26-DEC-08:61 11.83
         
Annual Sum or Average 24372672.18      
Minimum of Months 0.00 0.00   4.33
Maximum of Months 6214731.76 4173.26   17.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5648.60 94.14 03-JAN-08:61 7.67
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 5648.60      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 5648.60 94.14   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.958884E+09 7579.82 03-JAN-07:10 3.67
February 0.972769E+09 6771.85 09-FEB-07:10 7.08
March 0.157971E+10 7198.07 30-MAR-06:10 5.58
April 0.628300E+09 6118.68 03-APR-06:10 10.17
May 0.600489E+09 5889.12 15-MAY-06:10 11.33
June 0.387321E+09 5223.49 01-JUN-06:40 13.67
July 0.232522E+09 4779.19 17-JUL-06:40 15.47
August 0.223692E+09 5039.95 28-AUG-07:00 14.00
September 0.257022E+09 5709.56 20-SEP-06:07 12.17
October 0.262363E+09 6123.22 12-OCT-06:10 9.67
November 0.686596E+09 6326.62 30-NOV-07:10 8.67
December 0.781753E+09 7047.40 22-DEC-07:10 5.50
         
Annual Sum or Average 0.757143E+10      
Minimum of Months 0.223692E+09 4779.19   3.67
Maximum of Months 0.157971E+10 7579.82   15.47



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17442091.40 833.78 25-JAN-07:02 16.17
February 7030398.07 916.05 16-FEB-07:02 12.25
March 10582276.80 922.79 24-MAR-06:02 12.17
April 1006931.03 969.78 04-APR-06:02 11.17
May 740094.09 969.93 26-MAY-06:02 12.17
June 183600.53 932.63 01-JUN-06:02 13.17
July 151930.74 520.44 14-JUL-06:02 17.00
August 105399.13 526.55 31-AUG-06:02 16.33
September 249012.22 962.33 20-SEP-06:02 12.17
October 787176.41 927.20 30-OCT-06:02 10.50
November 2234863.70 952.67 01-NOV-06:02 11.83
December 8416033.08 896.13 19-DEC-07:02 16.17
         
Annual Sum or Average 48929807.20      
Minimum of Months 105399.13 520.44   10.50
Maximum of Months 17442091.40 969.93   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 88745.50 1120.62 29-MAR-06:02 7.17
April 0.00 0.00 01-APR-00:10 9.63
May 13832.92 230.55 24-MAY-06:01 16.17
June 29493.81 168.28 20-JUN-06:01 17.00
July 54513.65 221.98 12-JUL-06:01 17.00
August 69391.62 221.51 02-AUG-06:01 17.00
September 55514.36 208.93 29-SEP-06:01 19.08
October 29653.31 199.57 17-OCT-06:01 17.67
November 0.00 0.00 01-NOV-00:03 14.77
December 6328.16 105.47 20-DEC-07:01 7.83
         
Annual Sum or Average 347473.34      
Minimum of Months 0.00 0.00   7.17
Maximum of Months 88745.50 1120.62   19.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 53440783.65 15317.91 03-JAN-07:01 3.67
February 51705202.27 6125.75 10-FEB-08:04 9.58
March 57673819.56 11349.76 30-MAR-07:03 7.33
April 12370578.15 2276.93 19-APR-07:07 12.33
May 4837859.46 1576.17 12-MAY-07:08 13.33
June 1895880.05 1330.57 29-JUN-06:02 15.17
July 1609562.72 1350.26 11-JUL-06:02 17.00
August 2333408.14 1316.30 03-AUG-06:02 18.00
September 2053515.73 1346.84 14-SEP-06:02 16.00
October 5126874.25 1365.28 23-OCT-06:02 16.17
November 38909969.16 2729.91 24-NOV-08:05 10.67
December 47990329.81 10763.53 22-DEC-08:04 8.67
         
Annual Sum or Average 0.279948E+09      
Minimum of Months 1609562.72 1316.30   3.67
Maximum of Months 57673819.56 15317.91   18.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1789828.18 7441.96 03-JAN-08:61 7.67
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:05 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:03 15.20
June 0.00 0.00 01-JUN-00:03 13.07
July 0.00 0.00 01-JUL-00:03 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:03 18.42
November 0.00 0.00 01-NOV-00:03 14.77
December 0.00 0.00 01-DEC-00:05 10.63
         
Annual Sum or Average 1789828.18      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 1789828.18 7441.96   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.693329E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.588341E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.663663E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.567227E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.574700E+09 822.99 01-MAY-18:19 0.175721E+10 1312.87 01-MAY-07:10
June 0.554419E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.354435E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.379957E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.586338E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.662566E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.664552E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.676639E+09 822.99 01-DEC-16:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.696617E+10     0.191090E+11    
Minimum of Months 0.354435E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.693329E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381275E+10 3965.33 02-JAN-16:49 0.831942E+10 6325.65 02-JAN-08:09
February 0.332934E+10 3965.33 01-FEB-17:19 0.751906E+10 6325.65 01-FEB-08:09
March 0.385864E+10 3965.33 01-MAR-17:30 0.861368E+10 6325.65 01-MAR-08:09
April 0.336807E+10 3965.33 03-APR-17:30 0.800359E+10 6325.65 03-APR-07:10
May 0.354988E+10 3965.33 01-MAY-18:19 0.846655E+10 6325.65 01-MAY-07:10
June 0.350449E+10 3965.33 01-JUN-18:19 0.829584E+10 6325.65 01-JUN-07:10
July 0.219394E+10 2202.96 03-JUL-18:19 0.506686E+10 3329.29 03-JUL-07:10
August 0.230092E+10 2202.96 01-AUG-18:19 0.526656E+10 3329.29 01-AUG-07:10
September 0.341433E+10 3965.33 05-SEP-06:10 0.787684E+10 6325.65 05-SEP-07:10
October 0.372627E+10 3965.33 02-OCT-06:10 0.831942E+10 6325.65 02-OCT-07:10
November 0.371960E+10 3965.33 01-NOV-06:10 0.815072E+10 6325.65 01-NOV-07:10
December 0.371024E+10 3965.33 01-DEC-16:19 0.817229E+10 6325.65 01-DEC-08:09
             
Annual Sum or Average 0.404885E+11     0.920708E+11    
Minimum of Months 0.219394E+10 2202.96   0.506686E+10 3329.29  
Maximum of Months 0.385864E+10 3965.33   0.861368E+10 6325.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119548E+10 867.83 02-JAN-07:10 0.892986E+09 678.98 02-JAN-08:09
February 0.108092E+10 867.83 01-FEB-07:10 0.807077E+09 678.98 01-FEB-08:09
March 0.126572E+10 867.83 01-MAR-07:10 0.924571E+09 678.98 01-MAR-08:09
April 0.114559E+10 867.83 03-APR-06:10 0.859085E+09 678.98 03-APR-07:10
May 0.123060E+10 867.83 01-MAY-06:10 0.908779E+09 678.98 01-MAY-07:10
June 0.121583E+10 867.83 01-JUN-06:10 0.890455E+09 678.98 01-JUN-07:10
July 0.726757E+09 482.12 03-JUL-07:10 0.543864E+09 357.36 03-JUL-07:10
August 0.767082E+09 482.12 01-AUG-07:10 0.565300E+09 357.36 01-AUG-07:10
September 0.112391E+10 867.83 05-SEP-06:10 0.845480E+09 678.98 05-SEP-07:10
October 0.119548E+10 867.83 02-OCT-06:10 0.892986E+09 678.98 02-OCT-07:10
November 0.118071E+10 867.83 01-NOV-06:10 0.874878E+09 678.98 01-NOV-07:10
December 0.116036E+10 867.83 01-DEC-07:10 0.877193E+09 678.98 01-DEC-08:09
             
Annual Sum or Average 0.132884E+11     0.988265E+10    
Minimum of Months 0.726757E+09 482.12   0.543864E+09 357.36  
Maximum of Months 0.126572E+10 867.83   0.924571E+09 678.98  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.844791E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.703403E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.768237E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.643240E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.628976E+09 822.99 01-MAY-18:19 0.175721E+10 1312.87 01-MAY-07:10
June 0.601380E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.381654E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.423229E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.672757E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.807697E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.799300E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.836167E+09 822.99 01-DEC-07:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.811083E+10     0.191090E+11    
Minimum of Months 0.381654E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.844791E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.478008E+10 3965.33 02-JAN-07:10 0.831942E+10 6325.65 02-JAN-08:09
February 0.409210E+10 3965.33 01-FEB-07:10 0.751906E+10 6325.65 01-FEB-08:09
March 0.459742E+10 3965.33 01-MAR-17:10 0.861368E+10 6325.65 01-MAR-08:09
April 0.392767E+10 3965.33 03-APR-17:19 0.800359E+10 6325.65 03-APR-07:10
May 0.392888E+10 3965.33 01-MAY-18:19 0.846655E+10 6325.65 01-MAY-07:10
June 0.383983E+10 3965.33 01-JUN-18:30 0.829584E+10 6325.65 01-JUN-07:10
July 0.241257E+10 2202.96 03-JUL-18:40 0.506686E+10 3329.29 03-JUL-07:10
August 0.262971E+10 2202.96 01-AUG-18:30 0.526656E+10 3329.29 01-AUG-07:10
September 0.405088E+10 3965.33 05-SEP-06:10 0.787684E+10 6325.65 05-SEP-07:10
October 0.470512E+10 3965.33 02-OCT-06:10 0.831942E+10 6325.65 02-OCT-07:10
November 0.463095E+10 3965.33 01-NOV-06:10 0.815072E+10 6325.65 01-NOV-07:10
December 0.472373E+10 3965.33 01-DEC-16:10 0.817229E+10 6325.65 01-DEC-08:09
             
Annual Sum or Average 0.483189E+11     0.920708E+11    
Minimum of Months 0.241257E+10 2202.96   0.506686E+10 3329.29  
Maximum of Months 0.478008E+10 3965.33   0.861368E+10 6325.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.707012E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.603904E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.684792E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.593311E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.612437E+09 822.99 01-MAY-06:10 0.175721E+10 1312.87 01-MAY-07:10
June 0.598915E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.375579E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.397549E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.605934E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.683209E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.679166E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.696214E+09 822.99 01-DEC-07:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.723802E+10     0.191090E+11    
Minimum of Months 0.375579E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.707012E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.384406E+10 3965.33 02-JAN-07:10 0.831942E+10 6325.65 02-JAN-08:09
February 0.343557E+10 3965.33 01-FEB-17:19 0.751906E+10 6325.65 01-FEB-08:09
March 0.398507E+10 3965.33 01-MAR-17:19 0.861368E+10 6325.65 01-MAR-08:09
April 0.356597E+10 3965.33 03-APR-17:19 0.800359E+10 6325.65 03-APR-07:10
May 0.388039E+10 3965.33 01-MAY-18:10 0.846655E+10 6325.65 01-MAY-07:10
June 0.389957E+10 3965.33 01-JUN-18:19 0.829584E+10 6325.65 01-JUN-07:10
July 0.240597E+10 2202.96 03-JUL-18:19 0.506686E+10 3329.29 03-JUL-07:10
August 0.247382E+10 2202.96 01-AUG-18:19 0.526656E+10 3329.29 01-AUG-07:10
September 0.355412E+10 3965.33 05-SEP-06:10 0.787684E+10 6325.65 05-SEP-07:10
October 0.383944E+10 3965.33 02-OCT-06:10 0.831942E+10 6325.65 02-OCT-07:10
November 0.375364E+10 3965.33 01-NOV-06:10 0.815072E+10 6325.65 01-NOV-07:10
December 0.378908E+10 3965.33 01-DEC-16:10 0.817229E+10 6325.65 01-DEC-08:09
             
Annual Sum or Average 0.424267E+11     0.920708E+11    
Minimum of Months 0.240597E+10 2202.96   0.506686E+10 3329.29  
Maximum of Months 0.398507E+10 3965.33   0.861368E+10 6325.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119548E+10 867.83 02-JAN-07:10 0.892986E+09 678.98 02-JAN-08:09
February 0.108092E+10 867.83 01-FEB-07:10 0.807077E+09 678.98 01-FEB-08:09
March 0.126572E+10 867.83 01-MAR-07:10 0.924571E+09 678.98 01-MAR-08:09
April 0.114559E+10 867.83 03-APR-06:10 0.859085E+09 678.98 03-APR-07:10
May 0.123060E+10 867.83 01-MAY-06:10 0.908779E+09 678.98 01-MAY-07:10
June 0.121583E+10 867.83 01-JUN-06:10 0.890455E+09 678.98 01-JUN-07:10
July 0.726757E+09 482.12 03-JUL-07:10 0.543864E+09 357.36 03-JUL-07:10
August 0.767082E+09 482.12 01-AUG-07:10 0.565300E+09 357.36 01-AUG-07:10
September 0.112391E+10 867.83 05-SEP-06:10 0.845480E+09 678.98 05-SEP-07:10
October 0.119548E+10 867.83 02-OCT-06:10 0.892986E+09 678.98 02-OCT-07:10
November 0.118071E+10 867.83 01-NOV-06:10 0.874878E+09 678.98 01-NOV-07:10
December 0.116036E+10 867.83 01-DEC-07:10 0.877193E+09 678.98 01-DEC-08:09
             
Annual Sum or Average 0.132884E+11     0.988265E+10    
Minimum of Months 0.726757E+09 482.12   0.543864E+09 357.36  
Maximum of Months 0.126572E+10 867.83   0.924571E+09 678.98  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.851782E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.711167E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.778516E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.653155E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.640136E+09 822.99 01-MAY-18:19 0.175721E+10 1312.87 01-MAY-07:10
June 0.613634E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.388697E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.430115E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.681605E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.815977E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.806853E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.842986E+09 822.99 01-DEC-07:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.821462E+10     0.191090E+11    
Minimum of Months 0.388697E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.851782E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.477005E+10 3965.33 02-JAN-07:10 0.831942E+10 6325.65 02-JAN-08:09
February 0.408562E+10 3965.33 01-FEB-07:10 0.751906E+10 6325.65 01-FEB-08:09
March 0.458989E+10 3965.33 01-MAR-17:10 0.861368E+10 6325.65 01-MAR-08:09
April 0.391698E+10 3965.33 03-APR-17:19 0.800359E+10 6325.65 03-APR-07:10
May 0.392147E+10 3965.33 01-MAY-18:19 0.846655E+10 6325.65 01-MAY-07:10
June 0.383202E+10 3965.33 01-JUN-18:30 0.829584E+10 6325.65 01-JUN-07:10
July 0.240244E+10 2202.96 03-JUL-18:40 0.506686E+10 3329.29 03-JUL-07:10
August 0.262299E+10 2202.96 01-AUG-18:30 0.526656E+10 3329.29 01-AUG-07:10
September 0.404310E+10 3965.33 05-SEP-06:10 0.787684E+10 6325.65 05-SEP-07:10
October 0.469408E+10 3965.33 02-OCT-06:10 0.831942E+10 6325.65 02-OCT-07:10
November 0.462106E+10 3965.33 01-NOV-06:10 0.815072E+10 6325.65 01-NOV-07:10
December 0.470926E+10 3965.33 01-DEC-16:10 0.817229E+10 6325.65 01-DEC-08:09
             
Annual Sum or Average 0.482090E+11     0.920708E+11    
Minimum of Months 0.240244E+10 2202.96   0.506686E+10 3329.29  
Maximum of Months 0.477005E+10 3965.33   0.861368E+10 6325.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.706042E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.602627E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.683450E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.591700E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.610496E+09 822.99 01-MAY-06:10 0.175721E+10 1312.87 01-MAY-07:10
June 0.596341E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.374136E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.395938E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.604587E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.682038E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.678014E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.695521E+09 822.99 01-DEC-07:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.722089E+10     0.191090E+11    
Minimum of Months 0.374136E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.706042E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.465312E+10 3965.33 02-JAN-07:10 0.831942E+10 6325.65 02-JAN-08:09
February 0.418460E+10 3965.33 01-FEB-17:19 0.751906E+10 6325.65 01-FEB-08:09
March 0.488337E+10 3965.33 01-MAR-17:30 0.861368E+10 6325.65 01-MAR-08:09
April 0.439658E+10 3965.33 03-APR-17:19 0.800359E+10 6325.65 03-APR-07:10
May 0.474835E+10 3965.33 01-MAY-18:10 0.846655E+10 6325.65 01-MAY-07:10
June 0.472271E+10 3965.33 01-JUN-18:19 0.829584E+10 6325.65 01-JUN-07:10
July 0.286052E+10 2202.96 03-JUL-18:19 0.506686E+10 3329.29 03-JUL-07:10
August 0.298673E+10 2202.96 01-AUG-18:19 0.526656E+10 3329.29 01-AUG-07:10
September 0.434263E+10 3965.33 05-SEP-06:10 0.787684E+10 6325.65 05-SEP-07:10
October 0.464981E+10 3965.33 02-OCT-06:10 0.831942E+10 6325.65 02-OCT-07:10
November 0.457414E+10 3965.33 01-NOV-06:10 0.815072E+10 6325.65 01-NOV-07:10
December 0.454266E+10 3965.33 01-DEC-16:10 0.817229E+10 6325.65 01-DEC-08:09
             
Annual Sum or Average 0.515452E+11     0.920708E+11    
Minimum of Months 0.286052E+10 2202.96   0.506686E+10 3329.29  
Maximum of Months 0.488337E+10 3965.33   0.861368E+10 6325.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119548E+10 867.83 02-JAN-07:10 0.892986E+09 678.98 02-JAN-08:09
February 0.108092E+10 867.83 01-FEB-07:10 0.807077E+09 678.98 01-FEB-08:09
March 0.126572E+10 867.83 01-MAR-07:10 0.924571E+09 678.98 01-MAR-08:09
April 0.114559E+10 867.83 03-APR-06:10 0.859085E+09 678.98 03-APR-07:10
May 0.123060E+10 867.83 01-MAY-06:10 0.908779E+09 678.98 01-MAY-07:10
June 0.121583E+10 867.83 01-JUN-06:10 0.890455E+09 678.98 01-JUN-07:10
July 0.726757E+09 482.12 03-JUL-07:10 0.543864E+09 357.36 03-JUL-07:10
August 0.767082E+09 482.12 01-AUG-07:10 0.565300E+09 357.36 01-AUG-07:10
September 0.112391E+10 867.83 05-SEP-06:10 0.845480E+09 678.98 05-SEP-07:10
October 0.119548E+10 867.83 02-OCT-06:10 0.892986E+09 678.98 02-OCT-07:10
November 0.118071E+10 867.83 01-NOV-06:10 0.874878E+09 678.98 01-NOV-07:10
December 0.116036E+10 867.83 01-DEC-07:10 0.877193E+09 678.98 01-DEC-08:09
             
Annual Sum or Average 0.132884E+11     0.988265E+10    
Minimum of Months 0.726757E+09 482.12   0.543864E+09 357.36  
Maximum of Months 0.126572E+10 867.83   0.924571E+09 678.98  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.808428E+09 822.99 02-JAN-07:10 0.172667E+10 1312.87 02-JAN-08:09
February 0.671927E+09 822.99 01-FEB-07:10 0.156056E+10 1312.87 01-FEB-08:09
March 0.732044E+09 822.99 01-MAR-17:30 0.178775E+10 1312.87 01-MAR-08:09
April 0.604331E+09 822.99 03-APR-06:10 0.166112E+10 1312.87 03-APR-07:10
May 0.585545E+09 822.99 01-MAY-18:19 0.175721E+10 1312.87 01-MAY-07:10
June 0.553307E+09 822.99 01-JUN-18:30 0.172178E+10 1312.87 01-JUN-07:10
July 0.356653E+09 457.22 03-JUL-18:40 0.105161E+10 690.98 03-JUL-07:10
August 0.400784E+09 457.22 01-AUG-18:30 0.109306E+10 690.98 01-AUG-07:10
September 0.641516E+09 822.99 05-SEP-06:10 0.163481E+10 1312.87 05-SEP-07:10
October 0.776523E+09 822.99 02-OCT-06:10 0.172667E+10 1312.87 02-OCT-07:10
November 0.766636E+09 822.99 01-NOV-06:10 0.169166E+10 1312.87 01-NOV-07:10
December 0.804581E+09 822.99 01-DEC-07:10 0.169614E+10 1312.87 01-DEC-08:09
             
Annual Sum or Average 0.770228E+10     0.191090E+11    
Minimum of Months 0.356653E+09 457.22   0.105161E+10 690.98  
Maximum of Months 0.808428E+09 822.99   0.178775E+10 1312.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.294578E+10 2618.61 02-JAN-07:10 0.549396E+10 4177.31 02-JAN-08:09
February 0.249878E+10 2618.61 01-FEB-07:10 0.496542E+10 4177.31 01-FEB-08:09
March 0.277102E+10 2618.61 01-MAR-17:19 0.568828E+10 4177.31 01-MAR-08:09
April 0.234723E+10 2618.61 03-APR-17:30 0.528539E+10 4177.31 03-APR-07:10
May 0.233887E+10 2618.61 01-MAY-18:19 0.559112E+10 4177.31 01-MAY-07:10
June 0.226294E+10 2618.61 01-JUN-18:30 0.547839E+10 4177.31 01-JUN-07:10
July 0.143293E+10 1454.79 03-JUL-18:40 0.334604E+10 2198.59 03-JUL-07:10
August 0.157000E+10 1454.79 01-AUG-18:30 0.347792E+10 2198.59 01-AUG-07:10
September 0.243995E+10 2618.61 05-SEP-06:10 0.520168E+10 4177.31 05-SEP-07:10
October 0.286409E+10 2618.61 02-OCT-06:10 0.549396E+10 4177.31 02-OCT-07:10
November 0.284357E+10 2618.61 01-NOV-06:10 0.538255E+10 4177.31 01-NOV-07:10
December 0.291106E+10 2618.61 01-DEC-16:10 0.539679E+10 4177.31 01-DEC-08:09
             
Annual Sum or Average 0.292262E+11     0.608015E+11    
Minimum of Months 0.143293E+10 1454.79   0.334604E+10 2198.59  
Maximum of Months 0.294578E+10 2618.61   0.568828E+10 4177.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151413E+10 1346.72 02-JAN-07:10 0.376728E+10 2864.44 02-JAN-08:09
February 0.128439E+10 1346.72 01-FEB-07:10 0.340486E+10 2864.44 01-FEB-08:09
March 0.142369E+10 1346.72 01-MAR-17:19 0.390054E+10 2864.44 01-MAR-08:09
April 0.120671E+10 1346.72 03-APR-17:30 0.362427E+10 2864.44 03-APR-07:10
May 0.120712E+10 1346.72 01-MAY-18:19 0.383391E+10 2864.44 01-MAY-07:10
June 0.116300E+10 1346.72 01-JUN-18:30 0.375661E+10 2864.44 01-JUN-07:10
July 0.736661E+09 748.18 03-JUL-18:40 0.229443E+10 1507.60 03-JUL-07:10
August 0.811144E+09 748.18 01-AUG-18:30 0.238486E+10 1507.60 01-AUG-07:10
September 0.125450E+10 1346.72 05-SEP-06:10 0.356687E+10 2864.44 05-SEP-07:10
October 0.147231E+10 1346.72 02-OCT-06:10 0.376728E+10 2864.44 02-OCT-07:10
November 0.146179E+10 1346.72 01-NOV-06:10 0.369089E+10 2864.44 01-NOV-07:10
December 0.149656E+10 1346.72 01-DEC-16:10 0.370066E+10 2864.44 01-DEC-08:09
             
Annual Sum or Average 0.150320E+11     0.416925E+11    
Minimum of Months 0.736661E+09 748.18   0.229443E+10 1507.60  
Maximum of Months 0.151413E+10 1346.72   0.390054E+10 2864.44  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.339965E+10 2467.90 02-JAN-07:10 0.253943E+10 1930.85 02-JAN-08:09
February 0.307387E+10 2467.90 01-FEB-07:10 0.229513E+10 1930.85 01-FEB-08:09
March 0.359940E+10 2467.90 01-MAR-07:10 0.262925E+10 1930.85 01-MAR-08:09
April 0.325776E+10 2467.90 03-APR-06:10 0.244302E+10 1930.85 03-APR-07:10
May 0.349953E+10 2467.90 01-MAY-06:10 0.258434E+10 1930.85 01-MAY-07:10
June 0.345752E+10 2467.90 01-JUN-06:10 0.253223E+10 1930.85 01-JUN-07:10
July 0.206671E+10 1371.04 03-JUL-07:10 0.154661E+10 1016.24 03-JUL-07:10
August 0.218139E+10 1371.04 01-AUG-07:10 0.160757E+10 1016.24 01-AUG-07:10
September 0.319611E+10 2467.90 05-SEP-06:10 0.240433E+10 1930.85 05-SEP-07:10
October 0.339965E+10 2467.90 02-OCT-06:10 0.253943E+10 1930.85 02-OCT-07:10
November 0.335764E+10 2467.90 01-NOV-06:10 0.248793E+10 1930.85 01-NOV-07:10
December 0.329977E+10 2467.90 01-DEC-07:10 0.249452E+10 1930.85 01-DEC-08:09
             
Annual Sum or Average 0.377890E+11     0.281038E+11    
Minimum of Months 0.206671E+10 1371.04   0.154661E+10 1016.24  
Maximum of Months 0.359940E+10 2467.90   0.262925E+10 1930.85  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106371E+10 1118.18 02-JAN-16:49 0.795316E+09 604.72 02-JAN-08:09
February 0.930973E+09 1118.18 01-FEB-17:19 0.718803E+09 604.72 01-FEB-08:09
March 0.106640E+10 1118.18 01-MAR-17:30 0.823446E+09 604.72 01-MAR-08:09
April 0.924693E+09 1118.18 03-APR-17:30 0.765123E+09 604.72 03-APR-07:10
May 0.963537E+09 1118.18 01-MAY-18:19 0.809381E+09 604.72 01-MAY-07:10
June 0.943492E+09 1118.18 01-JUN-18:30 0.793062E+09 604.72 01-JUN-07:10
July 0.595757E+09 621.21 03-JUL-18:30 0.484379E+09 318.27 03-JUL-07:10
August 0.631795E+09 621.21 01-AUG-18:30 0.503470E+09 318.27 01-AUG-07:10
September 0.940676E+09 1118.18 05-SEP-17:30 0.753006E+09 604.72 05-SEP-07:10
October 0.102897E+10 1118.18 02-OCT-06:10 0.795316E+09 604.72 02-OCT-07:10
November 0.104186E+10 1118.18 01-NOV-06:10 0.779188E+09 604.72 01-NOV-07:10
December 0.103743E+10 1118.18 01-DEC-16:19 0.781250E+09 604.72 01-DEC-08:09
             
Annual Sum or Average 0.111693E+11     0.880174E+10    
Minimum of Months 0.595757E+09 621.21   0.484379E+09 318.27  
Maximum of Months 0.106640E+10 1118.18   0.823446E+09 604.72  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141243E+10 1025.33 02-JAN-07:10 0.293011E+10 2227.90 02-JAN-08:09
February 0.127708E+10 1025.33 01-FEB-07:10 0.264822E+10 2227.90 01-FEB-08:09
March 0.149542E+10 1025.33 01-MAR-07:10 0.303375E+10 2227.90 01-MAR-08:09
April 0.135348E+10 1025.33 03-APR-06:10 0.281887E+10 2227.90 03-APR-07:10
May 0.145392E+10 1025.33 01-MAY-06:10 0.298193E+10 2227.90 01-MAY-07:10
June 0.143647E+10 1025.33 01-JUN-06:10 0.292181E+10 2227.90 01-JUN-07:10
July 0.858646E+09 569.63 03-JUL-07:10 0.178455E+10 1172.58 03-JUL-07:10
August 0.906292E+09 569.63 01-AUG-07:10 0.185489E+10 1172.58 01-AUG-07:10
September 0.132787E+10 1025.33 05-SEP-06:10 0.277423E+10 2227.90 05-SEP-07:10
October 0.141243E+10 1025.33 02-OCT-06:10 0.293011E+10 2227.90 02-OCT-07:10
November 0.139498E+10 1025.33 01-NOV-06:10 0.287069E+10 2227.90 01-NOV-07:10
December 0.137093E+10 1025.33 01-DEC-07:10 0.287829E+10 2227.90 01-DEC-08:09
             
Annual Sum or Average 0.156999E+11     0.324275E+11    
Minimum of Months 0.858646E+09 569.63   0.178455E+10 1172.58  
Maximum of Months 0.149542E+10 1025.33   0.303375E+10 2227.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136667E+10 992.10 02-JAN-07:10 0.883684E+09 671.91 02-JAN-08:09
February 0.123571E+10 992.10 01-FEB-07:10 0.798670E+09 671.91 01-FEB-08:09
March 0.144697E+10 992.10 01-MAR-07:10 0.914940E+09 671.91 01-MAR-08:09
April 0.130963E+10 992.10 03-APR-06:10 0.850137E+09 671.91 03-APR-07:10
May 0.140682E+10 992.10 01-MAY-06:10 0.899312E+09 671.91 01-MAY-07:10
June 0.138993E+10 992.10 01-JUN-06:10 0.881180E+09 671.91 01-JUN-07:10
July 0.830837E+09 551.17 03-JUL-07:10 0.538198E+09 353.64 03-JUL-07:10
August 0.876938E+09 551.17 01-AUG-07:10 0.559411E+09 353.64 01-AUG-07:10
September 0.128485E+10 992.10 05-SEP-06:10 0.836673E+09 671.91 05-SEP-07:10
October 0.136667E+10 992.10 02-OCT-06:10 0.883684E+09 671.91 02-OCT-07:10
November 0.134978E+10 992.10 01-NOV-06:10 0.865765E+09 671.91 01-NOV-07:10
December 0.132652E+10 992.10 01-DEC-07:10 0.868056E+09 671.91 01-DEC-08:09
             
Annual Sum or Average 0.151913E+11     0.977971E+10    
Minimum of Months 0.830837E+09 551.17   0.538198E+09 353.64  
Maximum of Months 0.144697E+10 992.10   0.914940E+09 671.91  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381299E+10 3545.68 02-JAN-07:10 0.553791E+10 4210.73 02-JAN-08:09
February 0.336344E+10 3545.68 01-FEB-17:10 0.500514E+10 4210.73 01-FEB-08:09
March 0.389896E+10 3545.68 01-MAR-17:30 0.573379E+10 4210.73 01-MAR-08:09
April 0.343237E+10 3545.68 03-APR-17:19 0.532767E+10 4210.73 03-APR-07:10
May 0.365727E+10 3545.68 01-MAY-18:10 0.563585E+10 4210.73 01-MAY-07:10
June 0.359268E+10 3545.68 01-JUN-18:10 0.552221E+10 4210.73 01-JUN-07:10
July 0.221131E+10 1969.84 03-JUL-18:19 0.337280E+10 2216.18 03-JUL-07:10
August 0.233250E+10 1969.84 01-AUG-18:10 0.350574E+10 2216.18 01-AUG-07:10
September 0.345605E+10 3545.68 05-SEP-06:10 0.524330E+10 4210.73 05-SEP-07:10
October 0.378519E+10 3545.68 02-OCT-06:10 0.553791E+10 4210.73 02-OCT-07:10
November 0.373207E+10 3545.68 01-NOV-06:10 0.542561E+10 4210.73 01-NOV-07:10
December 0.370982E+10 3545.68 01-DEC-16:10 0.543997E+10 4210.73 01-DEC-08:09
             
Annual Sum or Average 0.409847E+11     0.612879E+11    
Minimum of Months 0.221131E+10 1969.84   0.337280E+10 2216.18  
Maximum of Months 0.389896E+10 3545.68   0.573379E+10 4210.73  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.321333E+10 3598.94 02-JAN-16:19 0.207549E+10 1578.10 02-JAN-08:09
February 0.249603E+10 3598.94 01-FEB-17:10 0.187582E+10 1578.10 01-FEB-08:09
March 0.261352E+10 3598.94 01-MAR-17:19 0.214891E+10 1578.10 01-MAR-08:09
April 0.211448E+10 3598.94 03-APR-17:19 0.199670E+10 1578.10 03-APR-07:10
May 0.213914E+10 3598.94 01-MAY-18:10 0.211220E+10 1578.10 01-MAY-07:10
June 0.207560E+10 3598.94 01-JUN-18:19 0.206961E+10 1578.10 01-JUN-07:10
July 0.135219E+10 1999.41 03-JUL-18:19 0.126406E+10 830.58 03-JUL-07:10
August 0.147816E+10 1999.41 01-AUG-18:19 0.131388E+10 830.58 01-AUG-07:10
September 0.231963E+10 3598.94 05-SEP-06:10 0.196508E+10 1578.10 05-SEP-07:10
October 0.277335E+10 3598.94 02-OCT-06:10 0.207549E+10 1578.10 02-OCT-07:10
November 0.303849E+10 3598.94 01-NOV-06:10 0.203341E+10 1578.10 01-NOV-07:10
December 0.321859E+10 3598.94 01-DEC-16:10 0.203879E+10 1578.10 01-DEC-08:09
             
Annual Sum or Average 0.288325E+11     0.229695E+11    
Minimum of Months 0.135219E+10 1999.41   0.126406E+10 830.58  
Maximum of Months 0.321859E+10 3598.94   0.214891E+10 1578.10  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.271276E+10 1969.28 02-JAN-07:10 0.141194E+11 9483.90 02-JAN-10:09
February 0.245280E+10 1969.28 01-FEB-07:10 0.127554E+11 9483.90 01-FEB-10:09
March 0.287216E+10 1969.28 01-MAR-07:10 0.142691E+11 9483.90 01-MAR-10:09
April 0.259954E+10 1969.28 03-APR-06:10 0.136398E+11 9483.90 03-APR-09:09
May 0.279246E+10 1969.28 01-MAY-06:10 0.141943E+11 9483.90 01-MAY-09:09
June 0.275894E+10 1969.28 01-JUN-06:10 0.137895E+11 9483.90 01-JUN-09:09
July 0.164915E+10 1094.04 03-JUL-07:10 0.140445E+11 9483.90 03-JUL-09:09
August 0.174066E+10 1094.04 01-AUG-07:10 0.142691E+11 9483.90 01-AUG-09:09
September 0.255034E+10 1969.28 05-SEP-06:10 0.136398E+11 9483.90 01-SEP-09:09
October 0.271276E+10 1969.28 02-OCT-06:10 0.141194E+11 9483.90 02-OCT-09:09
November 0.267924E+10 1969.28 01-NOV-06:10 0.137146E+11 9483.90 01-NOV-09:09
December 0.263306E+10 1969.28 01-DEC-07:10 0.140445E+11 9483.90 01-DEC-10:09
             
Annual Sum or Average 0.301539E+11     0.166599E+12    
Minimum of Months 0.164915E+10 1094.04   0.127554E+11 9483.90  
Maximum of Months 0.287216E+10 1969.28   0.142691E+11 9483.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.205758E+10 1983.52 02-JAN-16:30 0.253516E+10 1999.46 02-JAN-10:09
February 0.176971E+10 1983.52 01-FEB-17:10 0.229042E+10 1999.46 01-FEB-10:09
March 0.201759E+10 1983.52 01-MAR-17:19 0.257259E+10 1999.46 01-MAR-10:09
April 0.173950E+10 1983.52 03-APR-17:19 0.244734E+10 1999.46 03-APR-09:09
May 0.180850E+10 1983.52 01-MAY-18:19 0.255387E+10 1999.46 01-MAY-09:09
June 0.176683E+10 1983.52 01-JUN-18:19 0.248477E+10 1999.46 01-JUN-09:09
July 0.111025E+10 1101.95 03-JUL-18:30 0.251644E+10 1999.46 03-JUL-09:09
August 0.118146E+10 1101.95 01-AUG-18:19 0.257259E+10 1999.46 01-AUG-09:09
September 0.177213E+10 1983.52 05-SEP-06:10 0.244734E+10 1999.46 01-SEP-09:09
October 0.201796E+10 1983.52 02-OCT-06:10 0.253516E+10 1999.46 02-OCT-09:09
November 0.199928E+10 1983.52 01-NOV-06:10 0.246606E+10 1999.46 01-NOV-09:09
December 0.200628E+10 1983.52 01-DEC-16:10 0.251644E+10 1999.46 01-DEC-10:09
             
Annual Sum or Average 0.212471E+11     0.299382E+11    
Minimum of Months 0.111025E+10 1101.95   0.229042E+10 1999.46  
Maximum of Months 0.205758E+10 1983.52   0.257259E+10 1999.46  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.627048E+10 5087.33 02-JAN-07:10 0.695901E+10 5291.26 02-JAN-08:09
February 0.546624E+10 5087.33 01-FEB-16:49 0.628953E+10 5291.26 01-FEB-08:09
March 0.627406E+10 5087.33 01-MAR-16:00 0.720516E+10 5291.26 01-MAR-08:09
April 0.551407E+10 5087.33 03-APR-17:10 0.669483E+10 5291.26 03-APR-07:10
May 0.581156E+10 5087.33 01-MAY-17:00 0.708208E+10 5291.26 01-MAY-07:10
June 0.565558E+10 5087.33 01-JUN-18:19 0.693929E+10 5291.26 01-JUN-07:10
July 0.345708E+10 2826.28 03-JUL-18:19 0.423831E+10 2784.88 03-JUL-07:10
August 0.371318E+10 2826.28 01-AUG-18:10 0.440537E+10 2784.88 01-AUG-07:10
September 0.559467E+10 5087.33 05-SEP-06:10 0.658880E+10 5291.26 05-SEP-07:10
October 0.621685E+10 5087.33 02-OCT-06:10 0.695901E+10 5291.26 02-OCT-07:10
November 0.607342E+10 5087.33 01-NOV-06:10 0.681790E+10 5291.26 01-NOV-07:10
December 0.612763E+10 5087.33 01-DEC-14:50 0.683594E+10 5291.26 01-DEC-08:09
             
Annual Sum or Average 0.661748E+11     0.770152E+11    
Minimum of Months 0.345708E+10 2826.28   0.423831E+10 2784.88  
Maximum of Months 0.627406E+10 5087.33   0.720516E+10 5291.26  



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.693329E+09 0.172667E+10 0.00 0.00 0.00 0.00 149301.49 0.135636E+09
February 0.182593E+10 0.588341E+09 0.156056E+10 0.00 0.00 0.00 0.00 30160.83 0.152078E+09
March 0.221033E+10 0.663663E+09 0.178775E+10 0.00 0.00 0.00 0.00 2345.02 0.161073E+09
April 0.192203E+10 0.567227E+09 0.166112E+10 0.00 0.00 0.00 0.00 122899.71 0.102287E+09
May 0.211423E+10 0.574700E+09 0.175721E+10 0.00 0.00 0.00 0.00 3352.40 0.117239E+09
June 0.130399E+10 0.554419E+09 0.172178E+10 0.00 0.00 0.00 0.00 549397.09 63663089.63
July 0.448857E+09 0.354435E+09 0.105161E+10 0.00 0.00 0.00 0.00 3367409.56 42612622.35
August 0.516185E+09 0.379957E+09 0.109306E+10 0.00 0.00 0.00 0.00 3126852.65 50595651.66
September 0.118544E+10 0.586338E+09 0.163481E+10 0.00 0.00 0.00 0.00 2544731.44 60116754.59
October 0.201813E+10 0.662566E+09 0.172667E+10 0.00 0.00 0.00 0.00 7729497.57 94941112.98
November 0.201813E+10 0.664552E+09 0.169166E+10 0.00 0.00 0.00 0.00 278516.91 0.129972E+09
December 0.192203E+10 0.676639E+09 0.169614E+10 0.00 0.00 0.00 0.00 132012.47 0.142394E+09
                   
Annual Sum or Average 0.195034E+11 0.696617E+10 0.191090E+11 0.00 0.00 0.00 0.00 18036477.14 0.125261E+10
Minimum of Months 0.448857E+09 0.354435E+09 0.105161E+10 0.00 0.00 0.00 0.00 2345.02 42612622.35
Maximum of Months 0.221033E+10 0.693329E+09 0.178775E+10 0.00 0.00 0.00 0.00 7729497.57 0.161073E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.972371E+10 0.381275E+10 0.831942E+10 0.00 0.00 0.00 0.00 219733.75 0.400762E+09
February 0.879765E+10 0.332934E+10 0.751906E+10 0.00 0.00 0.00 0.00 54511.08 0.452130E+09
March 0.106498E+11 0.385864E+10 0.861368E+10 0.00 0.00 0.00 0.00 1257.36 0.468531E+09
April 0.926068E+10 0.336807E+10 0.800359E+10 0.00 0.00 0.00 0.00 261620.15 0.287166E+09
May 0.101867E+11 0.354988E+10 0.846655E+10 0.00 0.00 0.00 0.00 0.00 0.326586E+09
June 0.628284E+10 0.350449E+10 0.829584E+10 0.00 0.00 0.00 0.00 1040264.42 0.172662E+09
July 0.216267E+10 0.219394E+10 0.506686E+10 0.00 0.00 0.00 0.00 9856349.85 0.102470E+09
August 0.248707E+10 0.230092E+10 0.526656E+10 0.00 0.00 0.00 0.00 8880430.60 0.128294E+09
September 0.571168E+10 0.341433E+10 0.787684E+10 0.00 0.00 0.00 0.00 6556544.66 0.164953E+09
October 0.972371E+10 0.372627E+10 0.831942E+10 0.00 0.00 0.00 0.00 20330912.51 0.275437E+09
November 0.972371E+10 0.371960E+10 0.815072E+10 0.00 0.00 0.00 0.00 466112.94 0.380410E+09
December 0.926068E+10 0.371024E+10 0.817229E+10 0.00 0.00 0.00 0.00 230123.86 0.422195E+09
                   
Annual Sum or Average 0.939710E+11 0.404885E+11 0.920708E+11 0.00 0.00 0.00 0.00 47897861.19 0.358160E+10
Minimum of Months 0.216267E+10 0.219394E+10 0.506686E+10 0.00 0.00 0.00 0.00 0.00 0.102470E+09
Maximum of Months 0.106498E+11 0.385864E+10 0.861368E+10 0.00 0.00 0.00 0.00 20330912.51 0.468531E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 96752.89 20079564.74
February 0.708259E+09 0.108092E+10 0.807077E+09 0.00 0.00 0.00 0.00 9027.24 23558482.93
March 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 13486.24 25177162.64
April 0.745536E+09 0.114559E+10 0.859085E+09 0.00 0.00 0.00 0.00 54998.34 15268645.73
May 0.820090E+09 0.123060E+10 0.908779E+09 0.00 0.00 0.00 0.00 297.83 18357408.13
June 0.505804E+09 0.121583E+10 0.890455E+09 0.00 0.00 0.00 0.00 23840.24 9883750.66
July 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 473755.05 5690382.06
August 0.200223E+09 0.767082E+09 0.565300E+09 0.00 0.00 0.00 0.00 555551.91 6738956.65
September 0.459822E+09 0.112391E+10 0.845480E+09 0.00 0.00 0.00 0.00 419492.07 8157522.76
October 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 1340958.13 14112366.05
November 0.782813E+09 0.118071E+10 0.874878E+09 0.00 0.00 0.00 0.00 120801.84 19319472.79
December 0.745536E+09 0.116036E+10 0.877193E+09 0.00 0.00 0.00 0.00 89785.20 20955913.82
                   
Annual Sum or Average 0.756518E+10 0.132884E+11 0.988265E+10 0.00 0.00 0.00 0.00 3198746.98 0.187300E+09
Minimum of Months 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 297.83 5690382.06
Maximum of Months 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 1340958.13 25177162.64



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.844791E+09 0.172667E+10 0.00 0.00 0.00 0.00 1085454.70 0.111428E+09
February 0.182593E+10 0.703403E+09 0.156056E+10 0.00 0.00 0.00 0.00 93630.78 0.132003E+09
March 0.221033E+10 0.768237E+09 0.178775E+10 0.00 0.00 0.00 0.00 206967.29 0.147049E+09
April 0.192203E+10 0.643240E+09 0.166112E+10 0.00 0.00 0.00 0.00 554985.91 92203224.99
May 0.211423E+10 0.628976E+09 0.175721E+10 0.00 0.00 0.00 0.00 7513.71 0.115248E+09
June 0.130399E+10 0.601380E+09 0.172178E+10 0.00 0.00 0.00 0.00 456683.38 64804024.62
July 0.448857E+09 0.381654E+09 0.105161E+10 0.00 0.00 0.00 0.00 3518092.07 41473866.89
August 0.516185E+09 0.423229E+09 0.109306E+10 0.00 0.00 0.00 0.00 4346758.26 44820047.54
September 0.118544E+10 0.672757E+09 0.163481E+10 0.00 0.00 0.00 0.00 3340833.75 49083787.50
October 0.201813E+10 0.807697E+09 0.172667E+10 0.00 0.00 0.00 0.00 10288996.08 79863668.35
November 0.201813E+10 0.799300E+09 0.169166E+10 0.00 0.00 0.00 0.00 1449810.24 0.108165E+09
December 0.192203E+10 0.836167E+09 0.169614E+10 0.00 0.00 0.00 0.00 1490472.99 0.114636E+09
                   
Annual Sum or Average 0.195034E+11 0.811083E+10 0.191090E+11 0.00 0.00 0.00 0.00 26840199.17 0.110078E+10
Minimum of Months 0.448857E+09 0.381654E+09 0.105161E+10 0.00 0.00 0.00 0.00 7513.71 41473866.89
Maximum of Months 0.221033E+10 0.844791E+09 0.178775E+10 0.00 0.00 0.00 0.00 10288996.08 0.147049E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.972371E+10 0.478008E+10 0.831942E+10 0.00 0.00 0.00 0.00 2287272.27 0.329481E+09
February 0.879765E+10 0.409210E+10 0.751906E+10 0.00 0.00 0.00 0.00 100447.51 0.393868E+09
March 0.106498E+11 0.459742E+10 0.861368E+10 0.00 0.00 0.00 0.00 335556.06 0.430386E+09
April 0.926068E+10 0.392767E+10 0.800359E+10 0.00 0.00 0.00 0.00 820349.89 0.262049E+09
May 0.101867E+11 0.392888E+10 0.846655E+10 0.00 0.00 0.00 0.00 0.00 0.326632E+09
June 0.628284E+10 0.383983E+10 0.829584E+10 0.00 0.00 0.00 0.00 559430.31 0.179922E+09
July 0.216267E+10 0.241257E+10 0.506686E+10 0.00 0.00 0.00 0.00 9566995.22 0.101043E+09
August 0.248707E+10 0.262971E+10 0.526656E+10 0.00 0.00 0.00 0.00 12501798.29 0.113242E+09
September 0.571168E+10 0.405088E+10 0.787684E+10 0.00 0.00 0.00 0.00 8255213.69 0.134261E+09
October 0.972371E+10 0.470512E+10 0.831942E+10 0.00 0.00 0.00 0.00 26093743.13 0.235055E+09
November 0.972371E+10 0.463095E+10 0.815072E+10 0.00 0.00 0.00 0.00 3227979.53 0.317951E+09
December 0.926068E+10 0.472373E+10 0.817229E+10 0.00 0.00 0.00 0.00 2534107.30 0.339490E+09
                   
Annual Sum or Average 0.939710E+11 0.483189E+11 0.920708E+11 0.00 0.00 0.00 0.00 66282893.19 0.316338E+10
Minimum of Months 0.216267E+10 0.241257E+10 0.506686E+10 0.00 0.00 0.00 0.00 0.00 0.101043E+09
Maximum of Months 0.106498E+11 0.478008E+10 0.861368E+10 0.00 0.00 0.00 0.00 26093743.13 0.430386E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.707012E+09 0.172667E+10 0.00 0.00 0.00 0.00 147265.30 0.135354E+09
February 0.182593E+10 0.603904E+09 0.156056E+10 0.00 0.00 0.00 0.00 30877.54 0.152138E+09
March 0.221033E+10 0.684792E+09 0.178775E+10 0.00 0.00 0.00 0.00 279.14 0.161060E+09
April 0.192203E+10 0.593311E+09 0.166112E+10 0.00 0.00 0.00 0.00 123238.22 0.102210E+09
May 0.211423E+10 0.612437E+09 0.175721E+10 0.00 0.00 0.00 0.00 4144.80 0.116838E+09
June 0.130399E+10 0.598915E+09 0.172178E+10 0.00 0.00 0.00 0.00 545634.45 63737572.30
July 0.448857E+09 0.375579E+09 0.105161E+10 0.00 0.00 0.00 0.00 3440964.90 42488661.35
August 0.516185E+09 0.397549E+09 0.109306E+10 0.00 0.00 0.00 0.00 3171549.30 50204338.36
September 0.118544E+10 0.605934E+09 0.163481E+10 0.00 0.00 0.00 0.00 2535175.94 60295546.07
October 0.201813E+10 0.683209E+09 0.172667E+10 0.00 0.00 0.00 0.00 7709539.48 95359416.50
November 0.201813E+10 0.679166E+09 0.169166E+10 0.00 0.00 0.00 0.00 243497.63 0.130374E+09
December 0.192203E+10 0.696214E+09 0.169614E+10 0.00 0.00 0.00 0.00 139514.34 0.142321E+09
                   
Annual Sum or Average 0.195034E+11 0.723802E+10 0.191090E+11 0.00 0.00 0.00 0.00 18091681.03 0.125238E+10
Minimum of Months 0.448857E+09 0.375579E+09 0.105161E+10 0.00 0.00 0.00 0.00 279.14 42488661.35
Maximum of Months 0.221033E+10 0.707012E+09 0.178775E+10 0.00 0.00 0.00 0.00 7709539.48 0.161060E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.972371E+10 0.384406E+10 0.831942E+10 0.00 0.00 0.00 0.00 207478.82 0.398296E+09
February 0.879765E+10 0.343557E+10 0.751906E+10 0.00 0.00 0.00 0.00 54642.99 0.453094E+09
March 0.106498E+11 0.398507E+10 0.861368E+10 0.00 0.00 0.00 0.00 0.00 0.469902E+09
April 0.926068E+10 0.356597E+10 0.800359E+10 0.00 0.00 0.00 0.00 257031.26 0.288397E+09
May 0.101867E+11 0.388039E+10 0.846655E+10 0.00 0.00 0.00 0.00 0.00 0.328016E+09
June 0.628284E+10 0.389957E+10 0.829584E+10 0.00 0.00 0.00 0.00 963426.43 0.174578E+09
July 0.216267E+10 0.240597E+10 0.506686E+10 0.00 0.00 0.00 0.00 9981109.65 0.102721E+09
August 0.248707E+10 0.247382E+10 0.526656E+10 0.00 0.00 0.00 0.00 8980501.23 0.127613E+09
September 0.571168E+10 0.355412E+10 0.787684E+10 0.00 0.00 0.00 0.00 6574721.66 0.165132E+09
October 0.972371E+10 0.383944E+10 0.831942E+10 0.00 0.00 0.00 0.00 20445354.57 0.275879E+09
November 0.972371E+10 0.375364E+10 0.815072E+10 0.00 0.00 0.00 0.00 438840.51 0.380554E+09
December 0.926068E+10 0.378908E+10 0.817229E+10 0.00 0.00 0.00 0.00 223769.98 0.419592E+09
                   
Annual Sum or Average 0.939710E+11 0.424267E+11 0.920708E+11 0.00 0.00 0.00 0.00 48126877.09 0.358377E+10
Minimum of Months 0.216267E+10 0.240597E+10 0.506686E+10 0.00 0.00 0.00 0.00 0.00 0.102721E+09
Maximum of Months 0.106498E+11 0.398507E+10 0.861368E+10 0.00 0.00 0.00 0.00 20445354.57 0.469902E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 97973.32 19999202.96
February 0.708259E+09 0.108092E+10 0.807077E+09 0.00 0.00 0.00 0.00 9146.92 23571294.59
March 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 10977.06 25203388.17
April 0.745536E+09 0.114559E+10 0.859085E+09 0.00 0.00 0.00 0.00 54204.63 15298659.59
May 0.820090E+09 0.123060E+10 0.908779E+09 0.00 0.00 0.00 0.00 289.32 18390130.83
June 0.505804E+09 0.121583E+10 0.890455E+09 0.00 0.00 0.00 0.00 22792.44 9948306.18
July 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 475082.89 5710476.13
August 0.200223E+09 0.767082E+09 0.565300E+09 0.00 0.00 0.00 0.00 558702.33 6717997.03
September 0.459822E+09 0.112391E+10 0.845480E+09 0.00 0.00 0.00 0.00 418595.46 8181279.77
October 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 1340713.32 14137001.24
November 0.782813E+09 0.118071E+10 0.874878E+09 0.00 0.00 0.00 0.00 119029.09 19326090.64
December 0.745536E+09 0.116036E+10 0.877193E+09 0.00 0.00 0.00 0.00 91199.01 20884864.27
                   
Annual Sum or Average 0.756518E+10 0.132884E+11 0.988265E+10 0.00 0.00 0.00 0.00 3198705.80 0.187369E+09
Minimum of Months 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 289.32 5710476.13
Maximum of Months 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 1340713.32 25203388.17



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.851782E+09 0.172667E+10 0.00 0.00 0.00 0.00 1062127.62 0.111508E+09
February 0.182593E+10 0.711167E+09 0.156056E+10 0.00 0.00 0.00 0.00 94116.45 0.132230E+09
March 0.221033E+10 0.778516E+09 0.178775E+10 0.00 0.00 0.00 0.00 181292.56 0.147414E+09
April 0.192203E+10 0.653155E+09 0.166112E+10 0.00 0.00 0.00 0.00 541152.49 92588724.47
May 0.211423E+10 0.640136E+09 0.175721E+10 0.00 0.00 0.00 0.00 7322.82 0.115620E+09
June 0.130399E+10 0.613634E+09 0.172178E+10 0.00 0.00 0.00 0.00 446677.37 65405976.44
July 0.448857E+09 0.388697E+09 0.105161E+10 0.00 0.00 0.00 0.00 3485924.64 41982584.30
August 0.516185E+09 0.430115E+09 0.109306E+10 0.00 0.00 0.00 0.00 4275325.70 44925048.33
September 0.118544E+10 0.681605E+09 0.163481E+10 0.00 0.00 0.00 0.00 3316025.73 49598563.48
October 0.201813E+10 0.815977E+09 0.172667E+10 0.00 0.00 0.00 0.00 10222022.63 80229325.90
November 0.201813E+10 0.806853E+09 0.169166E+10 0.00 0.00 0.00 0.00 1409506.07 0.108524E+09
December 0.192203E+10 0.842986E+09 0.169614E+10 0.00 0.00 0.00 0.00 1381439.75 0.114759E+09
                   
Annual Sum or Average 0.195034E+11 0.821462E+10 0.191090E+11 0.00 0.00 0.00 0.00 26422933.82 0.110478E+10
Minimum of Months 0.448857E+09 0.388697E+09 0.105161E+10 0.00 0.00 0.00 0.00 7322.82 41982584.30
Maximum of Months 0.221033E+10 0.851782E+09 0.178775E+10 0.00 0.00 0.00 0.00 10222022.63 0.147414E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.972371E+10 0.477005E+10 0.831942E+10 0.00 0.00 0.00 0.00 2228585.92 0.329401E+09
February 0.879765E+10 0.408562E+10 0.751906E+10 0.00 0.00 0.00 0.00 101493.70 0.394233E+09
March 0.106498E+11 0.458989E+10 0.861368E+10 0.00 0.00 0.00 0.00 285122.35 0.431040E+09
April 0.926068E+10 0.391698E+10 0.800359E+10 0.00 0.00 0.00 0.00 792012.95 0.262742E+09
May 0.101867E+11 0.392147E+10 0.846655E+10 0.00 0.00 0.00 0.00 0.00 0.327325E+09
June 0.628284E+10 0.383202E+10 0.829584E+10 0.00 0.00 0.00 0.00 548091.71 0.181198E+09
July 0.216267E+10 0.240244E+10 0.506686E+10 0.00 0.00 0.00 0.00 9486435.17 0.102093E+09
August 0.248707E+10 0.262299E+10 0.526656E+10 0.00 0.00 0.00 0.00 12306897.17 0.113332E+09
September 0.571168E+10 0.404310E+10 0.787684E+10 0.00 0.00 0.00 0.00 8221243.99 0.135289E+09
October 0.972371E+10 0.469408E+10 0.831942E+10 0.00 0.00 0.00 0.00 25977951.61 0.235778E+09
November 0.972371E+10 0.462106E+10 0.815072E+10 0.00 0.00 0.00 0.00 3139041.51 0.318641E+09
December 0.926068E+10 0.470926E+10 0.817229E+10 0.00 0.00 0.00 0.00 2319700.38 0.339633E+09
                   
Annual Sum or Average 0.939710E+11 0.482090E+11 0.920708E+11 0.00 0.00 0.00 0.00 65406576.47 0.317070E+10
Minimum of Months 0.216267E+10 0.240244E+10 0.506686E+10 0.00 0.00 0.00 0.00 0.00 0.102093E+09
Maximum of Months 0.106498E+11 0.477005E+10 0.861368E+10 0.00 0.00 0.00 0.00 25977951.61 0.431040E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.706042E+09 0.172667E+10 0.00 0.00 0.00 0.00 147812.90 0.135972E+09
February 0.182593E+10 0.602627E+09 0.156056E+10 0.00 0.00 0.00 0.00 27128.47 0.153324E+09
March 0.221033E+10 0.683450E+09 0.178775E+10 0.00 0.00 0.00 0.00 4269.78 0.162152E+09
April 0.192203E+10 0.591700E+09 0.166112E+10 0.00 0.00 0.00 0.00 125845.96 0.103456E+09
May 0.211423E+10 0.610496E+09 0.175721E+10 0.00 0.00 0.00 0.00 1435.11 0.118945E+09
June 0.130399E+10 0.596341E+09 0.172178E+10 0.00 0.00 0.00 0.00 453609.55 64723517.02
July 0.448857E+09 0.374136E+09 0.105161E+10 0.00 0.00 0.00 0.00 3221376.21 42911147.98
August 0.516185E+09 0.395938E+09 0.109306E+10 0.00 0.00 0.00 0.00 2950353.11 50998292.14
September 0.118544E+10 0.604587E+09 0.163481E+10 0.00 0.00 0.00 0.00 2522794.42 60443994.32
October 0.201813E+10 0.682038E+09 0.172667E+10 0.00 0.00 0.00 0.00 7673420.07 95761222.35
November 0.201813E+10 0.678014E+09 0.169166E+10 0.00 0.00 0.00 0.00 270181.55 0.130752E+09
December 0.192203E+10 0.695521E+09 0.169614E+10 0.00 0.00 0.00 0.00 122186.13 0.143244E+09
                   
Annual Sum or Average 0.195034E+11 0.722089E+10 0.191090E+11 0.00 0.00 0.00 0.00 17520413.26 0.126268E+10
Minimum of Months 0.448857E+09 0.374136E+09 0.105161E+10 0.00 0.00 0.00 0.00 1435.11 42911147.98
Maximum of Months 0.221033E+10 0.706042E+09 0.178775E+10 0.00 0.00 0.00 0.00 7673420.07 0.162152E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.972371E+10 0.465312E+10 0.831942E+10 0.00 0.00 0.00 0.00 219890.02 0.402461E+09
February 0.879765E+10 0.418460E+10 0.751906E+10 0.00 0.00 0.00 0.00 54066.35 0.460044E+09
March 0.106498E+11 0.488337E+10 0.861368E+10 0.00 0.00 0.00 0.00 728.28 0.477564E+09
April 0.926068E+10 0.439658E+10 0.800359E+10 0.00 0.00 0.00 0.00 270355.76 0.295289E+09
May 0.101867E+11 0.474835E+10 0.846655E+10 0.00 0.00 0.00 0.00 0.00 0.338782E+09
June 0.628284E+10 0.472271E+10 0.829584E+10 0.00 0.00 0.00 0.00 561896.44 0.181451E+09
July 0.216267E+10 0.286052E+10 0.506686E+10 0.00 0.00 0.00 0.00 8685580.52 0.106415E+09
August 0.248707E+10 0.298673E+10 0.526656E+10 0.00 0.00 0.00 0.00 7670939.22 0.132394E+09
September 0.571168E+10 0.434263E+10 0.787684E+10 0.00 0.00 0.00 0.00 6483922.11 0.168774E+09
October 0.972371E+10 0.464981E+10 0.831942E+10 0.00 0.00 0.00 0.00 20104411.65 0.279113E+09
November 0.972371E+10 0.457414E+10 0.815072E+10 0.00 0.00 0.00 0.00 448099.09 0.383806E+09
December 0.926068E+10 0.454266E+10 0.817229E+10 0.00 0.00 0.00 0.00 225138.18 0.424752E+09
                   
Annual Sum or Average 0.939710E+11 0.515452E+11 0.920708E+11 0.00 0.00 0.00 0.00 44725027.60 0.365084E+10
Minimum of Months 0.216267E+10 0.286052E+10 0.506686E+10 0.00 0.00 0.00 0.00 0.00 0.106415E+09
Maximum of Months 0.106498E+11 0.488337E+10 0.861368E+10 0.00 0.00 0.00 0.00 20104411.65 0.477564E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 90164.09 20291397.88
February 0.708259E+09 0.108092E+10 0.807077E+09 0.00 0.00 0.00 0.00 7985.33 24023401.99
March 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 10352.77 25692457.23
April 0.745536E+09 0.114559E+10 0.859085E+09 0.00 0.00 0.00 0.00 42812.74 15720998.44
May 0.820090E+09 0.123060E+10 0.908779E+09 0.00 0.00 0.00 0.00 2.85 18967603.96
June 0.505804E+09 0.121583E+10 0.890455E+09 0.00 0.00 0.00 0.00 13408.68 10330530.36
July 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 410964.73 5949042.11
August 0.200223E+09 0.767082E+09 0.565300E+09 0.00 0.00 0.00 0.00 482246.94 6979075.02
September 0.459822E+09 0.112391E+10 0.845480E+09 0.00 0.00 0.00 0.00 410694.71 8436640.96
October 0.782813E+09 0.119548E+10 0.892986E+09 0.00 0.00 0.00 0.00 1321395.74 14339783.48
November 0.782813E+09 0.118071E+10 0.874878E+09 0.00 0.00 0.00 0.00 112780.47 19607772.10
December 0.745536E+09 0.116036E+10 0.877193E+09 0.00 0.00 0.00 0.00 82209.94 21217382.71
                   
Annual Sum or Average 0.756518E+10 0.132884E+11 0.988265E+10 0.00 0.00 0.00 0.00 2985018.99 0.191556E+09
Minimum of Months 0.174107E+09 0.726757E+09 0.543864E+09 0.00 0.00 0.00 0.00 2.85 5949042.11
Maximum of Months 0.857367E+09 0.126572E+10 0.924571E+09 0.00 0.00 0.00 0.00 1321395.74 25692457.23



Table of Contents

Report: SpaceGainsMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.201813E+10 0.808428E+09 0.172667E+10 0.00 0.00 0.00 0.00 1103029.39 0.111603E+09
February 0.182593E+10 0.671927E+09 0.156056E+10 0.00 0.00 0.00 0.00 87553.70 0.132857E+09
March 0.221033E+10 0.732044E+09 0.178775E+10 0.00 0.00 0.00 0.00 211580.22 0.148323E+09
April 0.192203E+10 0.604331E+09 0.166112E+10 0.00 0.00 0.00 0.00 514045.05 93788081.41
May 0.211423E+10 0.585545E+09 0.175721E+10 0.00 0.00 0.00 0.00 4665.70 0.117985E+09
June 0.130399E+10 0.553307E+09 0.172178E+10 0.00 0.00 0.00 0.00 391153.25 66542859.06
July 0.448857E+09 0.356653E+09 0.105161E+10 0.00 0.00 0.00 0.00 3220180.32 42800421.01
August 0.516185E+09 0.400784E+09 0.109306E+10 0.00 0.00 0.00 0.00 4006619.30 45703850.41
September 0.118544E+10 0.641516E+09 0.163481E+10 0.00 0.00 0.00 0.00 3304702.19 49776982.29
October 0.201813E+10 0.776523E+09 0.172667E+10 0.00 0.00 0.00 0.00 10186033.33 80300952.37
November 0.201813E+10 0.766636E+09 0.169166E+10 0.00 0.00 0.00 0.00 1432960.24 0.108435E+09
December 0.192203E+10 0.804581E+09 0.169614E+10 0.00 0.00 0.00 0.00 1434765.55 0.114780E+09
                   
Annual Sum or Average 0.195034E+11 0.770228E+10 0.191090E+11 0.00 0.00 0.00 0.00 25897288.23 0.111290E+10
Minimum of Months 0.448857E+09 0.356653E+09 0.105161E+10 0.00 0.00 0.00 0.00 4665.70 42800421.01
Maximum of Months 0.221033E+10 0.808428E+09 0.178775E+10 0.00 0.00 0.00 0.00 10186033.33 0.148323E+09



Table of Contents

Report: SpaceGainsMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.642132E+10 0.294578E+10 0.549396E+10 0.00 0.00 0.00 0.00 1577978.43 0.216688E+09
February 0.580977E+10 0.249878E+10 0.496542E+10 0.00 0.00 0.00 0.00 66965.97 0.260176E+09
March 0.703288E+10 0.277102E+10 0.568828E+10 0.00 0.00 0.00 0.00 249095.95 0.285349E+09
April 0.611554E+10 0.234723E+10 0.528539E+10 0.00 0.00 0.00 0.00 516011.47 0.175132E+09
May 0.672710E+10 0.233887E+10 0.559112E+10 0.00 0.00 0.00 0.00 0.00 0.220062E+09
June 0.414905E+10 0.226294E+10 0.547839E+10 0.00 0.00 0.00 0.00 282864.55 0.122020E+09
July 0.142818E+10 0.143293E+10 0.334604E+10 0.00 0.00 0.00 0.00 5717110.69 69058336.76
August 0.164241E+10 0.157000E+10 0.347792E+10 0.00 0.00 0.00 0.00 7642484.29 75706824.99
September 0.377186E+10 0.243995E+10 0.520168E+10 0.00 0.00 0.00 0.00 5445181.02 89398686.09
October 0.642132E+10 0.286409E+10 0.549396E+10 0.00 0.00 0.00 0.00 17171941.01 0.154846E+09
November 0.642132E+10 0.284357E+10 0.538255E+10 0.00 0.00 0.00 0.00 2137376.58 0.209217E+09
December 0.611554E+10 0.291106E+10 0.539679E+10 0.00 0.00 0.00 0.00 1649742.31 0.222864E+09
                   
Annual Sum or Average 0.620563E+11 0.292262E+11 0.608015E+11 0.00 0.00 0.00 0.00 42456752.27 0.210052E+10
Minimum of Months 0.142818E+10 0.143293E+10 0.334604E+10 0.00 0.00 0.00 0.00 0.00 69058336.76
Maximum of Months 0.703288E+10 0.294578E+10 0.568828E+10 0.00 0.00 0.00 0.00 17171941.01 0.285349E+09



Table of Contents

Report: SpaceGainsMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.488438E+10 0.151413E+10 0.376728E+10 0.00 0.00 0.00 0.00 413513.55 0.121518E+09
February 0.441920E+10 0.128439E+10 0.340486E+10 0.00 0.00 0.00 0.00 31456.86 0.146998E+09
March 0.534956E+10 0.142369E+10 0.390054E+10 0.00 0.00 0.00 0.00 32072.92 0.158920E+09
April 0.465179E+10 0.120671E+10 0.362427E+10 0.00 0.00 0.00 0.00 456053.08 96840425.26
May 0.511697E+10 0.120712E+10 0.383391E+10 0.00 0.00 0.00 0.00 0.00 0.116653E+09
June 0.511697E+10 0.116300E+10 0.375661E+10 0.00 0.00 0.00 0.00 90984.54 62257319.76
July 0.244831E+10 0.736661E+09 0.229443E+10 0.00 0.00 0.00 0.00 3267709.11 33269903.01
August 0.281556E+10 0.811144E+09 0.238486E+10 0.00 0.00 0.00 0.00 4605078.13 41381833.95
September 0.454162E+10 0.125450E+10 0.356687E+10 0.00 0.00 0.00 0.00 2880486.71 49861283.80
October 0.488438E+10 0.147231E+10 0.376728E+10 0.00 0.00 0.00 0.00 9451778.98 85281484.79
November 0.488438E+10 0.146179E+10 0.369089E+10 0.00 0.00 0.00 0.00 875446.98 0.118655E+09
December 0.465179E+10 0.149656E+10 0.370066E+10 0.00 0.00 0.00 0.00 398272.72 0.126301E+09
                   
Annual Sum or Average 0.537649E+11 0.150320E+11 0.416925E+11 0.00 0.00 0.00 0.00 22502853.58 0.115794E+10
Minimum of Months 0.244831E+10 0.736661E+09 0.229443E+10 0.00 0.00 0.00 0.00 0.00 33269903.01
Maximum of Months 0.534956E+10 0.151413E+10 0.390054E+10 0.00 0.00 0.00 0.00 9451778.98 0.158920E+09



Table of Contents

Report: SpaceGainsMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.222618E+10 0.339965E+10 0.253943E+10 0.00 0.00 0.00 0.00 145971.30 64898083.68
February 0.201416E+10 0.307387E+10 0.229513E+10 0.00 0.00 0.00 0.00 9168.92 80284493.19
March 0.243819E+10 0.359940E+10 0.262925E+10 0.00 0.00 0.00 0.00 0.00 86081813.08
April 0.212017E+10 0.325776E+10 0.244302E+10 0.00 0.00 0.00 0.00 57554.05 52668291.20
May 0.233218E+10 0.349953E+10 0.258434E+10 0.00 0.00 0.00 0.00 0.00 62266185.19
June 0.143841E+10 0.345752E+10 0.253223E+10 0.00 0.00 0.00 0.00 5641.30 33882013.37
July 0.495129E+09 0.206671E+10 0.154661E+10 0.00 0.00 0.00 0.00 386000.14 23335531.49
August 0.569398E+09 0.218139E+10 0.160757E+10 0.00 0.00 0.00 0.00 455878.53 28218808.27
September 0.130765E+10 0.319611E+10 0.240433E+10 0.00 0.00 0.00 0.00 1111111.29 29049422.73
October 0.222618E+10 0.339965E+10 0.253943E+10 0.00 0.00 0.00 0.00 3603716.36 46241122.49
November 0.222618E+10 0.335764E+10 0.248793E+10 0.00 0.00 0.00 0.00 199039.03 63817271.10
December 0.212017E+10 0.329977E+10 0.249452E+10 0.00 0.00 0.00 0.00 55579.90 68833258.46
                   
Annual Sum or Average 0.215140E+11 0.377890E+11 0.281038E+11 0.00 0.00 0.00 0.00 6029660.81 0.639576E+09
Minimum of Months 0.495129E+09 0.206671E+10 0.154661E+10 0.00 0.00 0.00 0.00 0.00 23335531.49
Maximum of Months 0.243819E+10 0.359940E+10 0.262925E+10 0.00 0.00 0.00 0.00 3603716.36 86081813.08



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.139443E+10 0.106371E+10 0.795316E+09 0.00 0.00 0.00 0.00 13705643.02 0.413099E+10
February 0.126163E+10 0.930973E+09 0.718803E+09 0.00 0.00 0.00 0.00 2800158.24 0.382696E+10
March 0.152723E+10 0.106640E+10 0.823446E+09 0.00 0.00 0.00 0.00 0.00 0.482968E+10
April 0.132803E+10 0.924693E+09 0.765123E+09 0.00 0.00 0.00 0.00 18929809.81 0.295255E+10
May 0.146083E+10 0.963537E+09 0.809381E+09 0.00 0.00 0.00 0.00 0.00 0.285357E+10
June 0.900991E+09 0.943492E+09 0.793062E+09 0.00 0.00 0.00 0.00 3846948.20 0.198137E+10
July 0.310138E+09 0.595757E+09 0.484379E+09 0.00 0.00 0.00 0.00 0.193009E+09 0.105596E+10
August 0.356659E+09 0.631795E+09 0.503470E+09 0.00 0.00 0.00 0.00 0.187517E+09 0.124983E+10
September 0.819082E+09 0.940676E+09 0.753006E+09 0.00 0.00 0.00 0.00 0.198057E+09 0.201155E+10
October 0.139443E+10 0.102897E+10 0.795316E+09 0.00 0.00 0.00 0.00 0.317203E+09 0.197992E+10
November 0.139443E+10 0.104186E+10 0.779188E+09 0.00 0.00 0.00 0.00 1274802.35 0.385094E+10
December 0.132803E+10 0.103743E+10 0.781250E+09 0.00 0.00 0.00 0.00 13825532.30 0.368680E+10
                   
Annual Sum or Average 0.134759E+11 0.111693E+11 0.880174E+10 0.00 0.00 0.00 0.00 0.950168E+09 0.344101E+11
Minimum of Months 0.310138E+09 0.595757E+09 0.484379E+09 0.00 0.00 0.00 0.00 0.00 0.105596E+10
Maximum of Months 0.152723E+10 0.106640E+10 0.823446E+09 0.00 0.00 0.00 0.00 0.317203E+09 0.482968E+10



Table of Contents

Report: SpaceGainsMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.308232E+09 0.141243E+10 0.293011E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.278876E+09 0.127708E+10 0.264822E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.337587E+09 0.149542E+10 0.303375E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.293554E+09 0.135348E+10 0.281887E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.322909E+09 0.145392E+10 0.298193E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.199160E+09 0.143647E+10 0.292181E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 68554512.00 0.858646E+09 0.178455E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 78837688.80 0.906292E+09 0.185489E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.181054E+09 0.132787E+10 0.277423E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.308232E+09 0.141243E+10 0.293011E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308232E+09 0.139498E+10 0.287069E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.293554E+09 0.137093E+10 0.287829E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.297878E+10 0.156999E+11 0.324275E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 68554512.00 0.858646E+09 0.178455E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337587E+09 0.149542E+10 0.303375E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.774708E+09 0.136667E+10 0.883684E+09 0.00 0.00 0.00 0.00 168623.09 69696421.28
February 0.700926E+09 0.123571E+10 0.798670E+09 0.00 0.00 0.00 0.00 2818.87 86847837.76
March 0.848489E+09 0.144697E+10 0.914940E+09 0.00 0.00 0.00 0.00 0.00 95396904.65
April 0.737817E+09 0.130963E+10 0.850137E+09 0.00 0.00 0.00 0.00 2456.34 63269143.23
May 0.811598E+09 0.140682E+10 0.899312E+09 0.00 0.00 0.00 0.00 0.00 76096458.61
June 0.500567E+09 0.138993E+10 0.881180E+09 0.00 0.00 0.00 0.00 0.00 44725344.97
July 0.172304E+09 0.830837E+09 0.538198E+09 0.00 0.00 0.00 0.00 96188.92 32191669.89
August 0.198150E+09 0.876938E+09 0.559411E+09 0.00 0.00 0.00 0.00 95397.91 37626656.08
September 0.455061E+09 0.128485E+10 0.836673E+09 0.00 0.00 0.00 0.00 899318.70 37442060.50
October 0.774708E+09 0.136667E+10 0.883684E+09 0.00 0.00 0.00 0.00 3169387.68 56045886.11
November 0.774708E+09 0.134978E+10 0.865765E+09 0.00 0.00 0.00 0.00 209599.68 70413078.34
December 0.737817E+09 0.132652E+10 0.868056E+09 0.00 0.00 0.00 0.00 55134.61 73653352.93
                   
Annual Sum or Average 0.748685E+10 0.151913E+11 0.977971E+10 0.00 0.00 0.00 0.00 4698925.81 0.743405E+09
Minimum of Months 0.172304E+09 0.830837E+09 0.538198E+09 0.00 0.00 0.00 0.00 0.00 32191669.89
Maximum of Months 0.848489E+09 0.144697E+10 0.914940E+09 0.00 0.00 0.00 0.00 3169387.68 95396904.65



Table of Contents

Report: SpaceGainsMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.156120E+10 0.381299E+10 0.553791E+10 0.00 0.00 0.00 0.00 95441.44 0.324789E+09
February 0.141251E+10 0.336344E+10 0.500514E+10 0.00 0.00 0.00 0.00 42780.35 0.379659E+09
March 0.170988E+10 0.389896E+10 0.573379E+10 0.00 0.00 0.00 0.00 0.00 0.402614E+09
April 0.148685E+10 0.343237E+10 0.532767E+10 0.00 0.00 0.00 0.00 197159.39 0.252254E+09
May 0.163554E+10 0.365727E+10 0.563585E+10 0.00 0.00 0.00 0.00 0.00 0.291207E+09
June 0.163554E+10 0.359268E+10 0.552221E+10 0.00 0.00 0.00 0.00 26337.37 0.162179E+09
July 0.840841E+09 0.221131E+10 0.337280E+10 0.00 0.00 0.00 0.00 1626534.12 0.120038E+09
August 0.966967E+09 0.233250E+10 0.350574E+10 0.00 0.00 0.00 0.00 1583573.05 0.144608E+09
September 0.145455E+10 0.345605E+10 0.524330E+10 0.00 0.00 0.00 0.00 4259679.63 0.148137E+09
October 0.156120E+10 0.378519E+10 0.553791E+10 0.00 0.00 0.00 0.00 13712940.20 0.229615E+09
November 0.156120E+10 0.373207E+10 0.542561E+10 0.00 0.00 0.00 0.00 30005.37 0.311467E+09
December 0.148685E+10 0.370982E+10 0.543997E+10 0.00 0.00 0.00 0.00 136430.96 0.342349E+09
                   
Annual Sum or Average 0.173131E+11 0.409847E+11 0.612879E+11 0.00 0.00 0.00 0.00 21710881.86 0.310892E+10
Minimum of Months 0.840841E+09 0.221131E+10 0.337280E+10 0.00 0.00 0.00 0.00 0.00 0.120038E+09
Maximum of Months 0.170988E+10 0.389896E+10 0.573379E+10 0.00 0.00 0.00 0.00 13712940.20 0.402614E+09



Table of Contents

Report: SpaceGainsMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.789800E+10 0.321333E+10 0.207549E+10 0.00 0.00 0.00 0.00 45330.67 0.133175E+09
February 0.714581E+10 0.249603E+10 0.187582E+10 0.00 0.00 0.00 0.00 17315.93 0.160628E+09
March 0.865019E+10 0.261352E+10 0.214891E+10 0.00 0.00 0.00 0.00 0.00 0.171196E+09
April 0.752191E+10 0.211448E+10 0.199670E+10 0.00 0.00 0.00 0.00 79779.92 0.108196E+09
May 0.827410E+10 0.213914E+10 0.211220E+10 0.00 0.00 0.00 0.00 0.00 0.126995E+09
June 0.827410E+10 0.207560E+10 0.206961E+10 0.00 0.00 0.00 0.00 10649.64 70870072.40
July 0.453307E+10 0.135219E+10 0.126406E+10 0.00 0.00 0.00 0.00 658244.51 52289544.85
August 0.521303E+10 0.147816E+10 0.131388E+10 0.00 0.00 0.00 0.00 627726.15 61822679.93
September 0.737247E+10 0.231963E+10 0.196508E+10 0.00 0.00 0.00 0.00 1727032.58 62890783.09
October 0.789800E+10 0.277335E+10 0.207549E+10 0.00 0.00 0.00 0.00 5514278.86 95188275.23
November 0.789800E+10 0.303849E+10 0.203341E+10 0.00 0.00 0.00 0.00 5507.77 0.127601E+09
December 0.752191E+10 0.321859E+10 0.203879E+10 0.00 0.00 0.00 0.00 55972.85 0.138933E+09
                   
Annual Sum or Average 0.882006E+11 0.288325E+11 0.229695E+11 0.00 0.00 0.00 0.00 8741838.89 0.130978E+10
Minimum of Months 0.453307E+10 0.135219E+10 0.126406E+10 0.00 0.00 0.00 0.00 0.00 52289544.85
Maximum of Months 0.865019E+10 0.321859E+10 0.214891E+10 0.00 0.00 0.00 0.00 5514278.86 0.171196E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.204475E+10 0.271276E+10 0.811357E+10 0.909844E+10 0.00 0.00 0.00 21611.05 73964264.66
February 0.185001E+10 0.245280E+10 0.733032E+10 0.822599E+10 0.00 0.00 0.00 8124.20 88531915.27
March 0.223949E+10 0.287216E+10 0.823336E+10 0.959699E+10 0.00 0.00 0.00 0.00 91455380.59
April 0.194738E+10 0.259954E+10 0.783252E+10 0.872454E+10 0.00 0.00 0.00 34688.86 55426957.89
May 0.214212E+10 0.279246E+10 0.817347E+10 0.934772E+10 0.00 0.00 0.00 0.00 64593994.57
June 0.132119E+10 0.275894E+10 0.795231E+10 0.922308E+10 0.00 0.00 0.00 4504.51 35444884.25
July 0.454778E+09 0.164915E+10 0.805368E+10 0.884917E+10 0.00 0.00 0.00 308388.30 26228130.09
August 0.522995E+09 0.174066E+10 0.823336E+10 0.959699E+10 0.00 0.00 0.00 295497.39 31908521.68
September 0.120108E+10 0.255034E+10 0.783252E+10 0.872454E+10 0.00 0.00 0.00 767784.89 31562079.35
October 0.204475E+10 0.271276E+10 0.811357E+10 0.909844E+10 0.00 0.00 0.00 2468252.04 49412709.17
November 0.204475E+10 0.267924E+10 0.789242E+10 0.897381E+10 0.00 0.00 0.00 10105.74 68626554.45
December 0.194738E+10 0.263306E+10 0.805368E+10 0.884917E+10 0.00 0.00 0.00 26795.48 76631882.14
                   
Annual Sum or Average 0.197607E+11 0.301539E+11 0.958148E+11 0.108309E+12 0.00 0.00 0.00 3945752.47 0.693787E+09
Minimum of Months 0.454778E+09 0.164915E+10 0.733032E+10 0.822599E+10 0.00 0.00 0.00 0.00 26228130.09
Maximum of Months 0.223949E+10 0.287216E+10 0.823336E+10 0.959699E+10 0.00 0.00 0.00 2468252.04 91455380.59



Table of Contents

Report: SpaceGainsMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.229168E+11 0.205758E+10 0.253516E+10 0.00 0.00 0.00 0.00 293138.55 0.251019E+09
February 0.207343E+11 0.176971E+10 0.229042E+10 0.00 0.00 0.00 0.00 36664.90 0.297728E+09
March 0.250994E+11 0.201759E+10 0.257259E+10 0.00 0.00 0.00 0.00 0.00 0.322870E+09
April 0.218255E+11 0.173950E+10 0.244734E+10 0.00 0.00 0.00 0.00 168969.23 0.205454E+09
May 0.240081E+11 0.180850E+10 0.255387E+10 0.00 0.00 0.00 0.00 0.00 0.247903E+09
June 0.240081E+11 0.176683E+10 0.248477E+10 0.00 0.00 0.00 0.00 22474.90 0.142707E+09
July 0.556624E+10 0.111025E+10 0.251644E+10 0.00 0.00 0.00 0.00 1396423.05 0.104991E+09
August 0.640118E+10 0.118146E+10 0.257259E+10 0.00 0.00 0.00 0.00 1340033.12 0.121261E+09
September 0.210126E+11 0.177213E+10 0.244734E+10 0.00 0.00 0.00 0.00 3633579.46 0.123306E+09
October 0.229168E+11 0.201796E+10 0.253516E+10 0.00 0.00 0.00 0.00 11633699.38 0.187920E+09
November 0.229168E+11 0.199928E+10 0.246606E+10 0.00 0.00 0.00 0.00 265477.54 0.240176E+09
December 0.218255E+11 0.200628E+10 0.251644E+10 0.00 0.00 0.00 0.00 196355.64 0.258723E+09
                   
Annual Sum or Average 0.239231E+12 0.212471E+11 0.299382E+11 0.00 0.00 0.00 0.00 18986815.76 0.250406E+10
Minimum of Months 0.556624E+10 0.111025E+10 0.229042E+10 0.00 0.00 0.00 0.00 0.00 0.104991E+09
Maximum of Months 0.250994E+11 0.205758E+10 0.257259E+10 0.00 0.00 0.00 0.00 11633699.38 0.322870E+09



Table of Contents

Report: SpaceGainsMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.325382E+10 0.627048E+10 0.695901E+10 0.00 0.00 0.00 0.00 323134.42 0.290297E+09
February 0.294393E+10 0.546624E+10 0.628953E+10 0.00 0.00 0.00 0.00 40761.37 0.353314E+09
March 0.356371E+10 0.627406E+10 0.720516E+10 0.00 0.00 0.00 0.00 0.00 0.382698E+09
April 0.309888E+10 0.551407E+10 0.669483E+10 0.00 0.00 0.00 0.00 199212.02 0.241243E+09
May 0.340876E+10 0.581156E+10 0.708208E+10 0.00 0.00 0.00 0.00 0.00 0.286051E+09
June 0.210241E+10 0.565558E+10 0.693929E+10 0.00 0.00 0.00 0.00 25075.11 0.158331E+09
July 0.723690E+09 0.345708E+10 0.423831E+10 0.00 0.00 0.00 0.00 1570655.27 0.110575E+09
August 0.832243E+09 0.371318E+10 0.440537E+10 0.00 0.00 0.00 0.00 1784665.51 0.131919E+09
September 0.191128E+10 0.559467E+10 0.658880E+10 0.00 0.00 0.00 0.00 4688873.69 0.134291E+09
October 0.325382E+10 0.621685E+10 0.695901E+10 0.00 0.00 0.00 0.00 15457517.26 0.211644E+09
November 0.325382E+10 0.607342E+10 0.681790E+10 0.00 0.00 0.00 0.00 776337.30 0.284281E+09
December 0.309888E+10 0.612763E+10 0.683594E+10 0.00 0.00 0.00 0.00 163924.75 0.303641E+09
                   
Annual Sum or Average 0.314452E+11 0.661748E+11 0.770152E+11 0.00 0.00 0.00 0.00 25030156.69 0.288829E+10
Minimum of Months 0.723690E+09 0.345708E+10 0.423831E+10 0.00 0.00 0.00 0.00 0.00 0.110575E+09
Maximum of Months 0.356371E+10 0.627406E+10 0.720516E+10 0.00 0.00 0.00 0.00 15457517.26 0.382698E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 27.76 14-JAN-12:10 238.65 07-JAN-01:55
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 6.97 01-FEB-12:00 274.79 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 7.76 11-MAR-14:00 253.32 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 18.09 30-APR-12:20 204.89 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-18:19 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 1.07 03-MAY-12:00 199.32 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 11.33 29-JUN-11:00 143.68 03-JUN-16:53
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.69 19-JUL-12:00 118.29 31-JUL-05:53
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 46.48 19-AUG-14:40 102.69 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 92.04 30-SEP-11:50 148.63 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 207.89 14-OCT-12:10 196.80 30-OCT-02:53
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 38.36 19-NOV-13:00 240.16 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-16:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 19.98 16-DEC-13:20 226.38 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 1.07   102.69  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 207.89   274.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14633.48 02-JAN-08:09 3965.33 02-JAN-16:49 6325.65 02-JAN-08:09 0.00 0.00 0.00 0.00 52.53 14-JAN-12:10 690.11 07-JAN-01:55
February 14633.48 01-FEB-08:09 3965.33 01-FEB-17:19 6325.65 01-FEB-08:09 0.00 0.00 0.00 0.00 17.05 01-FEB-12:00 817.00 25-FEB-13:00
March 14633.48 01-MAR-08:09 3965.33 01-MAR-17:30 6325.65 01-MAR-08:09 0.00 0.00 0.00 0.00 9.41 11-MAR-14:00 739.64 28-MAR-21:00
April 14633.48 03-APR-07:10 3965.33 03-APR-17:30 6325.65 03-APR-07:10 0.00 0.00 0.00 0.00 28.29 30-APR-12:30 506.96 01-APR-05:53
May 14633.48 01-MAY-07:10 3965.33 01-MAY-18:19 6325.65 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 495.17 26-MAY-06:00
June 14633.48 01-JUN-07:10 3965.33 01-JUN-18:19 6325.65 01-JUN-07:10 0.00 0.00 0.00 0.00 25.92 29-JUN-11:00 331.10 03-JUN-16:53
July 2310.55 03-JUL-07:10 2202.96 03-JUL-18:19 3329.29 03-JUL-07:10 0.00 0.00 0.00 0.00 59.24 19-JUL-12:00 317.20 31-JUL-05:53
August 2310.55 01-AUG-07:10 2202.96 01-AUG-18:19 3329.29 01-AUG-07:10 0.00 0.00 0.00 0.00 147.48 19-AUG-14:40 227.88 27-AUG-17:55
September 14633.48 18-SEP-07:10 3965.33 05-SEP-06:10 6325.65 05-SEP-07:10 0.00 0.00 0.00 0.00 230.72 30-SEP-12:00 353.38 02-SEP-14:52
October 14633.48 02-OCT-07:10 3965.33 02-OCT-06:10 6325.65 02-OCT-07:10 0.00 0.00 0.00 0.00 532.53 14-OCT-12:10 569.57 30-OCT-02:53
November 14633.48 01-NOV-07:10 3965.33 01-NOV-06:10 6325.65 01-NOV-07:10 0.00 0.00 0.00 0.00 78.38 19-NOV-13:00 721.42 23-NOV-03:55
December 14633.48 01-DEC-08:09 3965.33 01-DEC-16:19 6325.65 01-DEC-08:09 0.00 0.00 0.00 0.00 39.19 16-DEC-13:20 659.20 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2310.55   2202.96   3329.29   0.00 0.00 0.00 0.00 0.00   227.88  
Maximum of Months 14633.48   3965.33   6325.65   0.00 0.00 0.00 0.00 532.53   817.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1178.08 02-JAN-08:09 867.83 02-JAN-07:10 678.98 02-JAN-08:09 0.00 0.00 0.00 0.00 5.12 14-JAN-12:10 38.54 27-JAN-05:00
February 1178.08 01-FEB-08:09 867.83 01-FEB-07:10 678.98 01-FEB-08:09 0.00 0.00 0.00 0.00 1.51 01-FEB-12:00 44.90 25-FEB-13:00
March 1178.08 01-MAR-08:09 867.83 01-MAR-07:10 678.98 01-MAR-08:09 0.00 0.00 0.00 0.00 2.95 11-MAR-14:00 42.82 28-MAR-21:10
April 1178.08 03-APR-07:10 867.83 03-APR-06:10 678.98 03-APR-07:10 0.00 0.00 0.00 0.00 4.02 01-APR-11:53 29.07 01-APR-05:53
May 1178.08 01-MAY-07:10 867.83 01-MAY-06:10 678.98 01-MAY-07:10 0.00 0.00 0.00 0.00 0.10 03-MAY-12:00 28.73 26-MAY-06:00
June 1178.08 01-JUN-07:10 867.83 01-JUN-06:10 678.98 01-JUN-07:10 0.00 0.00 0.00 0.00 1.17 29-JUN-11:00 18.20 03-JUN-17:00
July 186.01 03-JUL-07:10 482.12 03-JUL-07:10 357.36 03-JUL-07:10 0.00 0.00 0.00 0.00 4.77 22-JUL-12:53 17.81 31-JUL-05:53
August 186.01 01-AUG-07:10 482.12 01-AUG-07:10 357.36 01-AUG-07:10 0.00 0.00 0.00 0.00 7.45 19-AUG-14:40 11.82 27-AUG-18:02
September 1178.08 18-SEP-07:10 867.83 05-SEP-06:10 678.98 05-SEP-07:10 0.00 0.00 0.00 0.00 14.62 30-SEP-12:00 14.56 03-SEP-18:00
October 1178.08 02-OCT-07:10 867.83 02-OCT-06:10 678.98 02-OCT-07:10 0.00 0.00 0.00 0.00 32.87 14-OCT-12:10 29.85 30-OCT-02:53
November 1178.08 01-NOV-07:10 867.83 01-NOV-06:10 678.98 01-NOV-07:10 0.00 0.00 0.00 0.00 7.83 19-NOV-13:00 39.20 23-NOV-03:55
December 1178.08 01-DEC-08:09 867.83 01-DEC-07:10 678.98 01-DEC-08:09 0.00 0.00 0.00 0.00 4.45 16-DEC-13:20 36.08 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 186.01   482.12   357.36   0.00 0.00 0.00 0.00 0.10   11.82  
Maximum of Months 1178.08   867.83   678.98   0.00 0.00 0.00 0.00 32.87   44.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 58.00 14-JAN-13:10 223.64 27-JAN-05:00
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 11.56 01-FEB-12:00 260.88 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 41.94 11-MAR-14:00 249.16 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 37.69 30-APR-12:20 187.14 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-18:19 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 1.58 03-MAY-12:00 199.51 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 10.61 29-JUN-11:00 143.37 03-JUN-17:00
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.66 19-JUL-12:00 113.49 09-JUL-17:00
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 56.41 19-AUG-14:40 92.31 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 112.08 30-SEP-12:00 111.74 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 240.42 14-OCT-12:10 166.18 30-OCT-02:53
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 75.12 19-NOV-13:00 213.36 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-07:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 64.16 25-DEC-11:52 207.36 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 1.58   92.31  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 240.42   260.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14633.48 02-JAN-08:09 3965.33 02-JAN-07:10 6325.65 02-JAN-08:09 0.00 0.00 0.00 0.00 135.84 14-JAN-13:10 651.19 27-JAN-05:00
February 14633.48 01-FEB-08:09 3965.33 01-FEB-07:10 6325.65 01-FEB-08:09 0.00 0.00 0.00 0.00 21.81 01-FEB-12:00 771.09 25-FEB-13:00
March 14633.48 01-MAR-08:09 3965.33 01-MAR-17:10 6325.65 01-MAR-08:09 0.00 0.00 0.00 0.00 103.60 11-MAR-14:00 732.25 28-MAR-21:00
April 14633.48 03-APR-07:10 3965.33 03-APR-17:19 6325.65 03-APR-07:10 0.00 0.00 0.00 0.00 76.89 30-APR-12:30 497.62 01-APR-05:53
May 14633.48 01-MAY-07:10 3965.33 01-MAY-18:19 6325.65 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 505.74 26-MAY-06:00
June 14633.48 01-JUN-07:10 3965.33 01-JUN-18:30 6325.65 01-JUN-07:10 0.00 0.00 0.00 0.00 21.47 29-JUN-11:00 332.49 03-JUN-17:00
July 2310.55 03-JUL-07:10 2202.96 03-JUL-18:40 3329.29 03-JUL-07:10 0.00 0.00 0.00 0.00 60.95 22-JUL-12:53 304.78 31-JUL-05:53
August 2310.55 01-AUG-07:10 2202.96 01-AUG-18:30 3329.29 01-AUG-07:10 0.00 0.00 0.00 0.00 172.09 19-AUG-14:40 197.23 27-AUG-18:02
September 14633.48 18-SEP-07:10 3965.33 05-SEP-06:10 6325.65 05-SEP-07:10 0.00 0.00 0.00 0.00 288.32 30-SEP-12:00 244.53 23-SEP-20:53
October 14633.48 02-OCT-07:10 3965.33 02-OCT-06:10 6325.65 02-OCT-07:10 0.00 0.00 0.00 0.00 620.55 14-OCT-12:10 492.11 11-OCT-02:00
November 14633.48 01-NOV-07:10 3965.33 01-NOV-06:10 6325.65 01-NOV-07:10 0.00 0.00 0.00 0.00 188.76 19-NOV-13:00 642.84 23-NOV-03:55
December 14633.48 01-DEC-08:09 3965.33 01-DEC-16:10 6325.65 01-DEC-08:09 0.00 0.00 0.00 0.00 130.17 25-DEC-11:52 600.77 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2310.55   2202.96   3329.29   0.00 0.00 0.00 0.00 0.00   197.23  
Maximum of Months 14633.48   3965.33   6325.65   0.00 0.00 0.00 0.00 620.55   771.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 27.50 14-JAN-12:10 238.62 07-JAN-01:55
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 7.07 01-FEB-12:00 273.77 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 0.24 10-MAR-11:00 252.99 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 15.11 30-APR-12:30 203.55 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-06:10 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 1.18 03-MAY-12:00 197.71 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 11.37 29-JUN-11:00 142.05 03-JUN-16:53
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.80 19-JUL-12:00 118.56 31-JUL-05:53
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 42.04 19-AUG-14:50 101.06 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 91.80 30-SEP-11:50 146.82 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 216.34 14-OCT-12:00 197.05 30-OCT-02:53
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 37.51 19-NOV-12:40 240.98 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-07:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 18.15 16-DEC-13:30 226.19 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 0.24   101.06  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 216.34   273.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14633.48 02-JAN-08:09 3965.33 02-JAN-07:10 6325.65 02-JAN-08:09 0.00 0.00 0.00 0.00 49.53 14-JAN-12:10 689.37 27-JAN-05:00
February 14633.48 01-FEB-08:09 3965.33 01-FEB-17:19 6325.65 01-FEB-08:09 0.00 0.00 0.00 0.00 17.05 01-FEB-12:00 816.57 25-FEB-13:00
March 14633.48 01-MAR-08:09 3965.33 01-MAR-17:19 6325.65 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 741.75 28-MAR-21:00
April 14633.48 03-APR-07:10 3965.33 03-APR-17:19 6325.65 03-APR-07:10 0.00 0.00 0.00 0.00 25.49 26-APR-13:00 511.13 01-APR-05:53
May 14633.48 01-MAY-07:10 3965.33 01-MAY-18:10 6325.65 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 498.92 26-MAY-06:00
June 14633.48 01-JUN-07:10 3965.33 01-JUN-18:19 6325.65 01-JUN-07:10 0.00 0.00 0.00 0.00 25.45 29-JUN-11:00 329.35 03-JUN-16:53
July 2310.55 03-JUL-07:10 2202.96 03-JUL-18:19 3329.29 03-JUL-07:10 0.00 0.00 0.00 0.00 59.24 19-JUL-12:00 318.32 31-JUL-05:53
August 2310.55 01-AUG-07:10 2202.96 01-AUG-18:19 3329.29 01-AUG-07:10 0.00 0.00 0.00 0.00 138.45 19-AUG-14:50 223.66 27-AUG-17:55
September 14633.48 18-SEP-07:10 3965.33 05-SEP-06:10 6325.65 05-SEP-07:10 0.00 0.00 0.00 0.00 232.90 30-SEP-12:00 346.99 02-SEP-14:52
October 14633.48 02-OCT-07:10 3965.33 02-OCT-06:10 6325.65 02-OCT-07:10 0.00 0.00 0.00 0.00 560.43 14-OCT-12:00 567.56 30-OCT-02:53
November 14633.48 01-NOV-07:10 3965.33 01-NOV-06:10 6325.65 01-NOV-07:10 0.00 0.00 0.00 0.00 81.26 19-NOV-12:40 725.08 23-NOV-03:55
December 14633.48 01-DEC-08:09 3965.33 01-DEC-16:10 6325.65 01-DEC-08:09 0.00 0.00 0.00 0.00 36.06 16-DEC-13:30 658.20 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2310.55   2202.96   3329.29   0.00 0.00 0.00 0.00 0.00   223.66  
Maximum of Months 14633.48   3965.33   6325.65   0.00 0.00 0.00 0.00 560.43   816.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1178.08 02-JAN-08:09 867.83 02-JAN-07:10 678.98 02-JAN-08:09 0.00 0.00 0.00 0.00 5.28 14-JAN-12:20 38.51 27-JAN-05:00
February 1178.08 01-FEB-08:09 867.83 01-FEB-07:10 678.98 01-FEB-08:09 0.00 0.00 0.00 0.00 1.52 01-FEB-12:00 44.88 25-FEB-13:00
March 1178.08 01-MAR-08:09 867.83 01-MAR-07:10 678.98 01-MAR-08:09 0.00 0.00 0.00 0.00 1.25 11-MAR-10:53 42.82 28-MAR-21:10
April 1178.08 03-APR-07:10 867.83 03-APR-06:10 678.98 03-APR-07:10 0.00 0.00 0.00 0.00 4.01 01-APR-11:53 29.10 01-APR-05:53
May 1178.08 01-MAY-07:10 867.83 01-MAY-06:10 678.98 01-MAY-07:10 0.00 0.00 0.00 0.00 0.09 03-MAY-12:00 28.77 26-MAY-06:00
June 1178.08 01-JUN-07:10 867.83 01-JUN-06:10 678.98 01-JUN-07:10 0.00 0.00 0.00 0.00 1.16 29-JUN-11:00 18.23 03-JUN-17:00
July 186.01 03-JUL-07:10 482.12 03-JUL-07:10 357.36 03-JUL-07:10 0.00 0.00 0.00 0.00 4.82 22-JUL-12:53 17.91 31-JUL-05:53
August 186.01 01-AUG-07:10 482.12 01-AUG-07:10 357.36 01-AUG-07:10 0.00 0.00 0.00 0.00 6.93 19-AUG-14:50 11.73 27-AUG-18:02
September 1178.08 18-SEP-07:10 867.83 05-SEP-06:10 678.98 05-SEP-07:10 0.00 0.00 0.00 0.00 14.61 30-SEP-12:00 15.23 04-SEP-17:55
October 1178.08 02-OCT-07:10 867.83 02-OCT-06:10 678.98 02-OCT-07:10 0.00 0.00 0.00 0.00 34.66 14-OCT-12:00 29.80 30-OCT-02:53
November 1178.08 01-NOV-07:10 867.83 01-NOV-06:10 678.98 01-NOV-07:10 0.00 0.00 0.00 0.00 7.48 19-NOV-12:40 39.20 23-NOV-03:55
December 1178.08 01-DEC-08:09 867.83 01-DEC-07:10 678.98 01-DEC-08:09 0.00 0.00 0.00 0.00 4.19 16-DEC-13:30 36.01 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 186.01   482.12   357.36   0.00 0.00 0.00 0.00 0.09   11.73  
Maximum of Months 1178.08   867.83   678.98   0.00 0.00 0.00 0.00 34.66   44.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 57.94 14-JAN-13:10 223.50 27-JAN-05:00
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 11.57 01-FEB-12:00 261.06 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 22.79 11-MAR-14:20 249.21 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 33.53 30-APR-12:30 187.33 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-18:19 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 1.54 03-MAY-12:00 199.87 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 10.57 29-JUN-11:00 143.85 03-JUN-17:00
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.65 19-JUL-12:00 115.71 16-JUL-18:00
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 51.27 19-AUG-14:50 91.93 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 111.78 30-SEP-12:00 111.81 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 252.12 14-OCT-12:00 166.62 11-OCT-02:00
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 73.93 19-NOV-12:40 213.26 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-07:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 73.40 25-DEC-12:00 207.21 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 1.54   91.93  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 252.12   261.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14633.48 02-JAN-08:09 3965.33 02-JAN-07:10 6325.65 02-JAN-08:09 0.00 0.00 0.00 0.00 134.60 14-JAN-13:10 650.45 27-JAN-05:00
February 14633.48 01-FEB-08:09 3965.33 01-FEB-07:10 6325.65 01-FEB-08:09 0.00 0.00 0.00 0.00 21.90 01-FEB-12:00 771.09 25-FEB-13:00
March 14633.48 01-MAR-08:09 3965.33 01-MAR-17:10 6325.65 01-MAR-08:09 0.00 0.00 0.00 0.00 56.27 11-MAR-14:20 732.10 28-MAR-21:00
April 14633.48 03-APR-07:10 3965.33 03-APR-17:19 6325.65 03-APR-07:10 0.00 0.00 0.00 0.00 68.54 30-APR-12:30 497.51 01-APR-05:53
May 14633.48 01-MAY-07:10 3965.33 01-MAY-18:19 6325.65 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 505.77 26-MAY-06:00
June 14633.48 01-JUN-07:10 3965.33 01-JUN-18:30 6325.65 01-JUN-07:10 0.00 0.00 0.00 0.00 21.44 29-JUN-11:00 333.49 03-JUN-17:00
July 2310.55 03-JUL-07:10 2202.96 03-JUL-18:40 3329.29 03-JUL-07:10 0.00 0.00 0.00 0.00 60.75 22-JUL-12:53 307.72 31-JUL-05:53
August 2310.55 01-AUG-07:10 2202.96 01-AUG-18:30 3329.29 01-AUG-07:10 0.00 0.00 0.00 0.00 161.49 19-AUG-14:50 196.13 27-AUG-18:02
September 14633.48 18-SEP-07:10 3965.33 05-SEP-06:10 6325.65 05-SEP-07:10 0.00 0.00 0.00 0.00 287.53 30-SEP-12:00 249.59 24-SEP-15:10
October 14633.48 02-OCT-07:10 3965.33 02-OCT-06:10 6325.65 02-OCT-07:10 0.00 0.00 0.00 0.00 653.86 14-OCT-12:00 493.37 11-OCT-02:00
November 14633.48 01-NOV-07:10 3965.33 01-NOV-06:10 6325.65 01-NOV-07:10 0.00 0.00 0.00 0.00 183.72 19-NOV-12:40 641.99 23-NOV-03:55
December 14633.48 01-DEC-08:09 3965.33 01-DEC-16:10 6325.65 01-DEC-08:09 0.00 0.00 0.00 0.00 153.40 25-DEC-12:00 600.16 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2310.55   2202.96   3329.29   0.00 0.00 0.00 0.00 0.00   196.13  
Maximum of Months 14633.48   3965.33   6325.65   0.00 0.00 0.00 0.00 653.86   771.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 27.85 14-JAN-12:10 239.75 07-JAN-01:55
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 6.57 01-FEB-12:00 276.23 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 9.90 11-MAR-13:30 254.48 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 24.13 30-APR-12:10 205.41 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-06:10 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 0.67 03-MAY-12:00 200.70 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 10.73 29-JUN-11:00 144.36 03-JUN-16:53
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.32 19-JUL-12:00 119.60 31-JUL-05:53
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 42.71 19-AUG-14:20 102.65 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 93.85 30-SEP-12:00 148.66 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 206.22 14-OCT-12:10 197.68 30-OCT-02:53
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 36.89 19-NOV-13:00 242.71 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-07:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 19.28 16-DEC-13:20 227.32 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 0.67   102.65  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 206.22   276.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 14633.48 02-JAN-08:09 3965.33 02-JAN-07:10 6325.65 02-JAN-08:09 0.00 0.00 0.00 0.00 52.38 14-JAN-12:10 695.46 07-JAN-01:55
February 14633.48 01-FEB-08:09 3965.33 01-FEB-17:19 6325.65 01-FEB-08:09 0.00 0.00 0.00 0.00 17.05 01-FEB-12:00 832.35 25-FEB-13:00
March 14633.48 01-MAR-08:09 3965.33 01-MAR-17:30 6325.65 01-MAR-08:09 0.00 0.00 0.00 0.00 6.07 11-MAR-13:30 751.73 28-MAR-21:00
April 14633.48 03-APR-07:10 3965.33 03-APR-17:19 6325.65 03-APR-07:10 0.00 0.00 0.00 0.00 41.98 30-APR-12:10 517.47 01-APR-05:53
May 14633.48 01-MAY-07:10 3965.33 01-MAY-18:10 6325.65 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 509.97 26-MAY-06:00
June 14633.48 01-JUN-07:10 3965.33 01-JUN-18:19 6325.65 01-JUN-07:10 0.00 0.00 0.00 0.00 21.75 29-JUN-11:00 341.90 03-JUN-16:53
July 2310.55 03-JUL-07:10 2202.96 03-JUL-18:19 3329.29 03-JUL-07:10 0.00 0.00 0.00 0.00 56.91 19-JUL-12:00 324.35 31-JUL-05:53
August 2310.55 01-AUG-07:10 2202.96 01-AUG-18:19 3329.29 01-AUG-07:10 0.00 0.00 0.00 0.00 131.61 19-AUG-14:30 231.09 27-AUG-17:55
September 14633.48 18-SEP-07:10 3965.33 05-SEP-06:10 6325.65 05-SEP-07:10 0.00 0.00 0.00 0.00 239.16 30-SEP-12:00 358.28 02-SEP-14:52
October 14633.48 02-OCT-07:10 3965.33 02-OCT-06:10 6325.65 02-OCT-07:10 0.00 0.00 0.00 0.00 528.38 14-OCT-12:10 570.83 30-OCT-02:53
November 14633.48 01-NOV-07:10 3965.33 01-NOV-06:10 6325.65 01-NOV-07:10 0.00 0.00 0.00 0.00 75.21 19-NOV-13:00 732.58 23-NOV-03:55
December 14633.48 01-DEC-08:09 3965.33 01-DEC-16:10 6325.65 01-DEC-08:09 0.00 0.00 0.00 0.00 36.93 16-DEC-13:20 663.47 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2310.55   2202.96   3329.29   0.00 0.00 0.00 0.00 0.00   231.09  
Maximum of Months 14633.48   3965.33   6325.65   0.00 0.00 0.00 0.00 528.38   832.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1178.08 02-JAN-08:09 867.83 02-JAN-07:10 678.98 02-JAN-08:09 0.00 0.00 0.00 0.00 4.99 14-JAN-12:10 38.90 27-JAN-05:00
February 1178.08 01-FEB-08:09 867.83 01-FEB-07:10 678.98 01-FEB-08:09 0.00 0.00 0.00 0.00 1.43 01-FEB-12:00 45.69 25-FEB-13:00
March 1178.08 01-MAR-08:09 867.83 01-MAR-07:10 678.98 01-MAR-08:09 0.00 0.00 0.00 0.00 2.67 11-MAR-13:30 43.51 28-MAR-21:10
April 1178.08 03-APR-07:10 867.83 03-APR-06:10 678.98 03-APR-07:10 0.00 0.00 0.00 0.00 3.40 01-APR-11:53 29.48 01-APR-05:53
May 1178.08 01-MAY-07:10 867.83 01-MAY-06:10 678.98 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 03-MAY-12:00 29.41 26-MAY-06:00
June 1178.08 01-JUN-07:10 867.83 01-JUN-06:10 678.98 01-JUN-07:10 0.00 0.00 0.00 0.00 0.98 29-JUN-11:00 18.74 03-JUN-17:00
July 186.01 03-JUL-07:10 482.12 03-JUL-07:10 357.36 03-JUL-07:10 0.00 0.00 0.00 0.00 4.26 22-JUL-12:53 18.23 31-JUL-05:53
August 186.01 01-AUG-07:10 482.12 01-AUG-07:10 357.36 01-AUG-07:10 0.00 0.00 0.00 0.00 7.07 19-AUG-14:20 11.98 27-AUG-17:55
September 1178.08 18-SEP-07:10 867.83 05-SEP-06:10 678.98 05-SEP-07:10 0.00 0.00 0.00 0.00 14.78 30-SEP-12:00 14.83 02-SEP-15:00
October 1178.08 02-OCT-07:10 867.83 02-OCT-06:10 678.98 02-OCT-07:10 0.00 0.00 0.00 0.00 32.58 14-OCT-12:10 29.98 30-OCT-02:53
November 1178.08 01-NOV-07:10 867.83 01-NOV-06:10 678.98 01-NOV-07:10 0.00 0.00 0.00 0.00 7.57 19-NOV-13:00 39.71 23-NOV-03:55
December 1178.08 01-DEC-08:09 867.83 01-DEC-07:10 678.98 01-DEC-08:09 0.00 0.00 0.00 0.00 4.25 16-DEC-13:20 36.35 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 186.01   482.12   357.36   0.00 0.00 0.00 0.00 0.00   11.98  
Maximum of Months 1178.08   867.83   678.98   0.00 0.00 0.00 0.00 32.58   45.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3037.14 02-JAN-08:09 822.99 02-JAN-07:10 1312.87 02-JAN-08:09 0.00 0.00 0.00 0.00 57.31 14-JAN-13:10 223.77 27-JAN-05:00
February 3037.14 01-FEB-08:09 822.99 01-FEB-07:10 1312.87 01-FEB-08:09 0.00 0.00 0.00 0.00 11.22 01-FEB-12:00 262.89 25-FEB-13:00
March 3037.14 01-MAR-08:09 822.99 01-MAR-17:30 1312.87 01-MAR-08:09 0.00 0.00 0.00 0.00 42.29 11-MAR-13:30 250.51 28-MAR-21:00
April 3037.14 03-APR-07:10 822.99 03-APR-06:10 1312.87 03-APR-07:10 0.00 0.00 0.00 0.00 41.91 30-APR-12:10 190.06 16-APR-18:00
May 3037.14 01-MAY-07:10 822.99 01-MAY-18:19 1312.87 01-MAY-07:10 0.00 0.00 0.00 0.00 1.30 03-MAY-12:00 203.75 20-MAY-18:00
June 3037.14 01-JUN-07:10 822.99 01-JUN-18:30 1312.87 01-JUN-07:10 0.00 0.00 0.00 0.00 10.23 29-JUN-11:00 147.29 03-JUN-17:00
July 479.55 03-JUL-07:10 457.22 03-JUL-18:40 690.98 03-JUL-07:10 0.00 0.00 0.00 0.00 22.24 19-JUL-12:00 116.35 31-JUL-05:53
August 479.55 01-AUG-07:10 457.22 01-AUG-18:30 690.98 01-AUG-07:10 0.00 0.00 0.00 0.00 52.13 19-AUG-14:20 93.81 27-AUG-17:55
September 3037.14 18-SEP-07:10 822.99 05-SEP-06:10 1312.87 05-SEP-07:10 0.00 0.00 0.00 0.00 114.52 30-SEP-12:00 114.01 02-SEP-15:00
October 3037.14 02-OCT-07:10 822.99 02-OCT-06:10 1312.87 02-OCT-07:10 0.00 0.00 0.00 0.00 238.80 14-OCT-11:40 167.10 11-OCT-02:00
November 3037.14 01-NOV-07:10 822.99 01-NOV-06:10 1312.87 01-NOV-07:10 0.00 0.00 0.00 0.00 73.92 19-NOV-13:00 213.07 23-NOV-03:55
December 3037.14 01-DEC-08:09 822.99 01-DEC-07:10 1312.87 01-DEC-08:09 0.00 0.00 0.00 0.00 66.32 25-DEC-11:52 207.42 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 479.55   457.22   690.98   0.00 0.00 0.00 0.00 1.30   93.81  
Maximum of Months 3037.14   822.99   1312.87   0.00 0.00 0.00 0.00 238.80   262.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 9663.62 02-JAN-08:09 2618.61 02-JAN-07:10 4177.31 02-JAN-08:09 0.00 0.00 0.00 0.00 89.35 14-JAN-13:10 428.67 27-JAN-05:00
February 9663.62 01-FEB-08:09 2618.61 01-FEB-07:10 4177.31 01-FEB-08:09 0.00 0.00 0.00 0.00 14.48 01-FEB-12:00 512.80 25-FEB-13:00
March 9663.62 01-MAR-08:09 2618.61 01-MAR-17:19 4177.31 01-MAR-08:09 0.00 0.00 0.00 0.00 65.93 11-MAR-13:30 484.93 28-MAR-21:00
April 9663.62 03-APR-07:10 2618.61 03-APR-17:30 4177.31 03-APR-07:10 0.00 0.00 0.00 0.00 60.58 30-APR-12:10 328.01 01-APR-05:53
May 9663.62 01-MAY-07:10 2618.61 01-MAY-18:19 4177.31 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 336.43 26-MAY-06:00
June 9663.62 01-JUN-07:10 2618.61 01-JUN-18:30 4177.31 01-JUN-07:10 0.00 0.00 0.00 0.00 13.12 29-JUN-11:00 226.48 03-JUN-16:53
July 1525.83 03-JUL-07:10 1454.79 03-JUL-18:40 2198.59 03-JUL-07:10 0.00 0.00 0.00 0.00 37.24 31-JUL-13:00 205.72 31-JUL-05:53
August 1525.83 01-AUG-07:10 1454.79 01-AUG-18:30 2198.59 01-AUG-07:10 0.00 0.00 0.00 0.00 105.40 19-AUG-14:30 132.06 27-AUG-18:02
September 9663.62 18-SEP-07:10 2618.61 05-SEP-06:10 4177.31 05-SEP-07:10 0.00 0.00 0.00 0.00 194.85 30-SEP-12:00 162.38 02-SEP-14:52
October 9663.62 02-OCT-07:10 2618.61 02-OCT-06:10 4177.31 02-OCT-07:10 0.00 0.00 0.00 0.00 407.81 14-OCT-12:10 325.03 11-OCT-02:00
November 9663.62 01-NOV-07:10 2618.61 01-NOV-06:10 4177.31 01-NOV-07:10 0.00 0.00 0.00 0.00 123.34 19-NOV-13:00 421.26 23-NOV-03:55
December 9663.62 01-DEC-08:09 2618.61 01-DEC-16:10 4177.31 01-DEC-08:09 0.00 0.00 0.00 0.00 88.48 25-DEC-11:52 395.05 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1525.83   1454.79   2198.59   0.00 0.00 0.00 0.00 0.00   132.06  
Maximum of Months 9663.62   2618.61   4177.31   0.00 0.00 0.00 0.00 407.81   512.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 4969.86 02-JAN-08:09 1346.72 02-JAN-07:10 2864.44 02-JAN-08:09 0.00 0.00 0.00 0.00 38.77 14-JAN-15:00 232.15 27-JAN-05:00
February 4969.86 01-FEB-08:09 1346.72 01-FEB-07:10 2864.44 01-FEB-08:09 0.00 0.00 0.00 0.00 7.16 01-FEB-12:00 283.00 25-FEB-13:00
March 4969.86 01-MAR-08:09 1346.72 01-MAR-17:19 2864.44 01-MAR-08:09 0.00 0.00 0.00 0.00 29.46 11-MAR-13:50 267.80 28-MAR-21:00
April 4969.86 03-APR-07:10 1346.72 03-APR-17:30 2864.44 03-APR-07:10 0.00 0.00 0.00 0.00 40.16 30-APR-12:10 180.33 01-APR-05:53
May 4969.86 01-MAY-07:10 1346.72 01-MAY-18:19 2864.44 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 184.79 26-MAY-06:00
June 4969.86 01-JUN-07:10 1346.72 01-JUN-18:30 2864.44 01-JUN-07:10 0.00 0.00 0.00 0.00 18.39 25-JUN-13:00 118.46 06-JUN-21:00
July 2615.72 03-JUL-07:10 748.18 03-JUL-18:40 1507.60 03-JUL-07:10 0.00 0.00 0.00 0.00 57.07 23-JUL-10:50 106.93 31-JUL-05:53
August 2615.72 01-AUG-07:10 748.18 01-AUG-18:30 1507.60 01-AUG-07:10 0.00 0.00 0.00 0.00 65.03 19-AUG-13:50 68.10 21-AUG-24:00
September 4969.86 05-SEP-07:10 1346.72 05-SEP-06:10 2864.44 05-SEP-07:10 0.00 0.00 0.00 0.00 101.90 30-SEP-11:50 86.82 02-SEP-15:00
October 4969.86 02-OCT-07:10 1346.72 02-OCT-06:10 2864.44 02-OCT-07:10 0.00 0.00 0.00 0.00 221.10 14-OCT-11:50 182.12 11-OCT-02:00
November 4969.86 01-NOV-07:10 1346.72 01-NOV-06:10 2864.44 01-NOV-07:10 0.00 0.00 0.00 0.00 65.54 19-NOV-13:00 235.26 23-NOV-03:55
December 4969.86 01-DEC-08:09 1346.72 01-DEC-16:10 2864.44 01-DEC-08:09 0.00 0.00 0.00 0.00 18.29 17-DEC-13:20 215.16 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2615.72   748.18   1507.60   0.00 0.00 0.00 0.00 0.00   68.10  
Maximum of Months 4969.86   1346.72   2864.44   0.00 0.00 0.00 0.00 221.10   283.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3350.23 02-JAN-08:09 2467.90 02-JAN-07:10 1930.85 02-JAN-08:09 0.00 0.00 0.00 0.00 10.28 14-JAN-15:00 123.12 27-JAN-05:00
February 3350.23 01-FEB-08:09 2467.90 01-FEB-07:10 1930.85 01-FEB-08:09 0.00 0.00 0.00 0.00 2.89 01-FEB-12:00 149.60 25-FEB-13:00
March 3350.23 01-MAR-08:09 2467.90 01-MAR-07:10 1930.85 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 144.85 28-MAR-21:00
April 3350.23 03-APR-07:10 2467.90 03-APR-06:10 1930.85 03-APR-07:10 0.00 0.00 0.00 0.00 5.21 30-APR-10:52 98.26 01-APR-05:53
May 3350.23 01-MAY-07:10 2467.90 01-MAY-06:10 1930.85 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 95.38 26-MAY-06:00
June 3350.23 01-JUN-07:10 2467.90 01-JUN-06:10 1930.85 01-JUN-07:10 0.00 0.00 0.00 0.00 1.63 29-JUN-11:00 59.46 06-JUN-21:00
July 528.98 03-JUL-07:10 1371.04 03-JUL-07:10 1016.24 03-JUL-07:10 0.00 0.00 0.00 0.00 8.35 23-JUL-10:52 62.48 31-JUL-05:53
August 528.98 01-AUG-07:10 1371.04 01-AUG-07:10 1016.24 01-AUG-07:10 0.00 0.00 0.00 0.00 13.25 19-AUG-13:00 40.63 21-AUG-24:00
September 3350.23 18-SEP-07:10 2467.90 05-SEP-06:10 1930.85 05-SEP-07:10 0.00 0.00 0.00 0.00 38.10 30-SEP-12:00 53.67 02-SEP-15:00
October 3350.23 02-OCT-07:10 2467.90 02-OCT-06:10 1930.85 02-OCT-07:10 0.00 0.00 0.00 0.00 93.67 14-OCT-11:52 95.21 11-OCT-02:00
November 3350.23 01-NOV-07:10 2467.90 01-NOV-06:10 1930.85 01-NOV-07:10 0.00 0.00 0.00 0.00 17.12 19-NOV-13:00 127.69 23-NOV-03:55
December 3350.23 01-DEC-08:09 2467.90 01-DEC-07:10 1930.85 01-DEC-08:09 0.00 0.00 0.00 0.00 7.11 16-DEC-12:53 114.77 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 528.98   1371.04   1016.24   0.00 0.00 0.00 0.00 0.00   40.63  
Maximum of Months 3350.23   2467.90   1930.85   0.00 0.00 0.00 0.00 93.67   149.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2098.51 02-JAN-08:09 1118.18 02-JAN-16:49 604.72 02-JAN-08:09 0.00 0.00 0.00 0.00 2956.66 24-JAN-15:10 59523.58 09-JAN-07:01
February 2098.51 01-FEB-08:09 1118.18 01-FEB-17:19 604.72 01-FEB-08:09 0.00 0.00 0.00 0.00 931.76 01-FEB-12:00 47306.95 21-FEB-07:01
March 2098.51 01-MAR-08:09 1118.18 01-MAR-17:30 604.72 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 45204.43 07-MAR-07:01
April 2098.51 03-APR-07:10 1118.18 03-APR-17:30 604.72 03-APR-07:10 0.00 0.00 0.00 0.00 4272.14 26-APR-14:10 39031.57 03-APR-06:01
May 2098.51 01-MAY-07:10 1118.18 01-MAY-18:19 604.72 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 35314.75 30-MAY-06:01
June 2098.51 01-JUN-07:10 1118.18 01-JUN-18:30 604.72 01-JUN-07:10 0.00 0.00 0.00 0.00 468.73 29-JUN-11:00 29910.91 05-JUN-06:01
July 331.34 03-JUL-07:10 621.21 03-JUL-18:30 318.27 03-JUL-07:10 0.00 0.00 0.00 0.00 8943.12 19-JUL-14:03 27240.09 17-JUL-06:01
August 331.34 01-AUG-07:10 621.21 01-AUG-18:30 318.27 01-AUG-07:10 0.00 0.00 0.00 0.00 11194.34 17-AUG-14:02 31974.79 28-AUG-06:01
September 2098.51 18-SEP-07:10 1118.18 05-SEP-17:30 604.72 05-SEP-07:10 0.00 0.00 0.00 0.00 23853.07 29-SEP-14:01 34330.57 20-SEP-06:01
October 2098.51 02-OCT-07:10 1118.18 02-OCT-06:10 604.72 02-OCT-07:10 0.00 0.00 0.00 0.00 16170.09 16-OCT-14:01 44015.14 30-OCT-06:01
November 2098.51 01-NOV-07:10 1118.18 01-NOV-06:10 604.72 01-NOV-07:10 0.00 0.00 0.00 0.00 467.50 28-NOV-14:00 45376.62 24-NOV-07:01
December 2098.51 01-DEC-08:09 1118.18 01-DEC-16:19 604.72 01-DEC-08:09 0.00 0.00 0.00 0.00 2045.97 05-DEC-15:10 53592.16 22-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 331.34   621.21   318.27   0.00 0.00 0.00 0.00 0.00   27240.09  
Maximum of Months 2098.51   1118.18   604.72   0.00 0.00 0.00 0.00 23853.07   59523.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 463.87 02-JAN-08:09 1025.33 02-JAN-07:10 2227.90 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03
February 463.87 01-FEB-08:09 1025.33 01-FEB-07:10 2227.90 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03
March 463.87 01-MAR-08:09 1025.33 01-MAR-07:10 2227.90 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 463.87 03-APR-07:10 1025.33 03-APR-06:10 2227.90 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10
May 463.87 01-MAY-07:10 1025.33 01-MAY-06:10 2227.90 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 01-MAY-00:03
June 463.87 01-JUN-07:10 1025.33 01-JUN-06:10 2227.90 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:03 0.00 01-JUN-00:03
July 73.24 03-JUL-07:10 569.63 03-JUL-07:10 1172.58 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 01-JUL-00:03
August 73.24 01-AUG-07:10 569.63 01-AUG-07:10 1172.58 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 01-AUG-00:03
September 463.87 18-SEP-07:10 1025.33 05-SEP-06:10 2227.90 05-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 01-SEP-00:03
October 463.87 02-OCT-07:10 1025.33 02-OCT-06:10 2227.90 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 01-OCT-00:03
November 463.87 01-NOV-07:10 1025.33 01-NOV-06:10 2227.90 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 0.00 01-NOV-00:03
December 463.87 01-DEC-08:09 1025.33 01-DEC-07:10 2227.90 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 73.24   569.63   1172.58   0.00 0.00 0.00 0.00 0.00   0.00  
Maximum of Months 463.87   1025.33   2227.90   0.00 0.00 0.00 0.00 0.00   0.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1165.88 02-JAN-08:09 992.10 02-JAN-07:10 671.91 02-JAN-08:09 0.00 0.00 0.00 0.00 12.86 14-JAN-10:51 133.98 27-JAN-05:00
February 1165.88 01-FEB-08:09 992.10 01-FEB-07:10 671.91 01-FEB-08:09 0.00 0.00 0.00 0.00 1.72 01-FEB-12:00 160.73 25-FEB-13:00
March 1165.88 01-MAR-08:09 992.10 01-MAR-07:10 671.91 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 156.38 28-MAR-21:00
April 1165.88 03-APR-07:10 992.10 03-APR-06:10 671.91 03-APR-07:10 0.00 0.00 0.00 0.00 2.22 30-APR-10:52 105.66 01-APR-05:53
May 1165.88 01-MAY-07:10 992.10 01-MAY-06:10 671.91 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 110.09 26-MAY-06:00
June 1165.88 01-JUN-07:10 992.10 01-JUN-06:10 671.91 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:03 73.22 03-JUN-17:00
July 184.09 03-JUL-07:10 551.17 03-JUL-07:10 353.64 03-JUL-07:10 0.00 0.00 0.00 0.00 3.87 19-JUL-12:00 73.15 31-JUL-05:53
August 184.09 01-AUG-07:10 551.17 01-AUG-07:10 353.64 01-AUG-07:10 0.00 0.00 0.00 0.00 6.92 19-AUG-13:00 51.27 27-AUG-18:00
September 1165.88 18-SEP-07:10 992.10 05-SEP-06:10 671.91 05-SEP-07:10 0.00 0.00 0.00 0.00 35.26 30-SEP-12:00 67.75 02-SEP-15:00
October 1165.88 02-OCT-07:10 992.10 02-OCT-06:10 671.91 02-OCT-07:10 0.00 0.00 0.00 0.00 95.36 14-OCT-11:52 108.70 11-OCT-02:00
November 1165.88 01-NOV-07:10 992.10 01-NOV-06:10 671.91 01-NOV-07:10 0.00 0.00 0.00 0.00 18.11 19-NOV-13:00 138.39 23-NOV-03:55
December 1165.88 01-DEC-08:09 992.10 01-DEC-07:10 671.91 01-DEC-08:09 0.00 0.00 0.00 0.00 9.05 16-DEC-12:53 123.50 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 184.09   551.17   353.64   0.00 0.00 0.00 0.00 0.00   51.27  
Maximum of Months 1165.88   992.10   671.91   0.00 0.00 0.00 0.00 95.36   160.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2705.96 02-JAN-08:09 3545.68 02-JAN-07:10 4210.73 02-JAN-08:09 0.00 0.00 0.00 0.00 10.25 13-JAN-14:00 561.38 27-JAN-05:00
February 2705.96 01-FEB-08:09 3545.68 01-FEB-17:10 4210.73 01-FEB-08:09 0.00 0.00 0.00 0.00 13.50 01-FEB-12:00 688.19 25-FEB-13:00
March 2705.96 01-MAR-08:09 3545.68 01-MAR-17:30 4210.73 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 640.39 28-MAR-21:00
April 2705.96 03-APR-07:10 3545.68 03-APR-17:19 4210.73 03-APR-07:10 0.00 0.00 0.00 0.00 20.19 26-APR-13:00 435.61 01-APR-06:00
May 2705.96 01-MAY-07:10 3545.68 01-MAY-18:10 4210.73 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 426.48 26-MAY-06:00
June 2705.96 01-JUN-07:10 3545.68 01-JUN-18:10 4210.73 01-JUN-07:10 0.00 0.00 0.00 0.00 7.59 29-JUN-11:00 276.05 06-JUN-21:00
July 1424.19 03-JUL-07:10 1969.84 03-JUL-18:19 2216.18 03-JUL-07:10 0.00 0.00 0.00 0.00 33.35 31-JUL-13:00 301.87 31-JUL-05:53
August 1424.19 01-AUG-07:10 1969.84 01-AUG-18:10 2216.18 01-AUG-07:10 0.00 0.00 0.00 0.00 28.49 19-AUG-13:50 206.65 27-AUG-18:00
September 2705.96 05-SEP-07:10 3545.68 05-SEP-06:10 4210.73 05-SEP-07:10 0.00 0.00 0.00 0.00 145.57 30-SEP-11:47 301.12 02-SEP-15:00
October 2705.96 02-OCT-07:10 3545.68 02-OCT-06:10 4210.73 02-OCT-07:10 0.00 0.00 0.00 0.00 351.53 14-OCT-11:52 456.53 30-OCT-02:53
November 2705.96 01-NOV-07:10 3545.68 01-NOV-06:10 4210.73 01-NOV-07:10 0.00 0.00 0.00 0.00 16.04 19-NOV-13:00 585.93 23-NOV-03:55
December 2705.96 01-DEC-08:09 3545.68 01-DEC-16:10 4210.73 01-DEC-08:09 0.00 0.00 0.00 0.00 11.91 05-DEC-10:00 531.68 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1424.19   1969.84   2216.18   0.00 0.00 0.00 0.00 0.00   206.65  
Maximum of Months 2705.96   3545.68   4210.73   0.00 0.00 0.00 0.00 351.53   688.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 13145.35 02-JAN-16:10 3598.94 02-JAN-16:19 1578.10 02-JAN-08:09 0.00 0.00 0.00 0.00 4.15 13-JAN-14:00 250.82 02-JAN-03:00
February 13145.35 01-FEB-16:10 3598.94 01-FEB-17:10 1578.10 01-FEB-08:09 0.00 0.00 0.00 0.00 5.46 01-FEB-12:00 294.10 25-FEB-13:00
March 13145.35 01-MAR-16:10 3598.94 01-MAR-17:19 1578.10 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 275.39 28-MAR-21:00
April 13145.35 03-APR-15:09 3598.94 03-APR-17:19 1578.10 03-APR-07:10 0.00 0.00 0.00 0.00 8.17 26-APR-13:00 189.88 01-APR-06:00
May 13145.35 01-MAY-15:09 3598.94 01-MAY-18:10 1578.10 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 190.67 13-MAY-11:00
June 13145.35 01-JUN-15:09 3598.94 01-JUN-18:19 1578.10 01-JUN-07:10 0.00 0.00 0.00 0.00 3.07 29-JUN-11:00 121.97 03-JUN-17:00
July 4843.02 03-JUL-07:10 1999.41 03-JUL-18:19 830.58 03-JUL-07:10 0.00 0.00 0.00 0.00 13.50 31-JUL-13:00 102.47 16-JUL-18:00
August 4843.02 01-AUG-07:10 1999.41 01-AUG-18:19 830.58 01-AUG-07:10 0.00 0.00 0.00 0.00 10.87 17-AUG-14:00 86.40 26-AUG-17:50
September 13145.35 05-SEP-15:09 3598.94 05-SEP-06:10 1578.10 05-SEP-07:10 0.00 0.00 0.00 0.00 57.65 30-SEP-11:45 126.63 02-SEP-14:52
October 13145.35 02-OCT-15:09 3598.94 02-OCT-06:10 1578.10 02-OCT-07:10 0.00 0.00 0.00 0.00 146.04 14-OCT-11:53 190.92 11-OCT-02:00
November 13145.35 01-NOV-15:09 3598.94 01-NOV-06:10 1578.10 01-NOV-07:10 0.00 0.00 0.00 0.00 1.74 28-NOV-14:00 246.87 23-NOV-03:55
December 13145.35 01-DEC-16:10 3598.94 01-DEC-16:10 1578.10 01-DEC-08:09 0.00 0.00 0.00 0.00 4.82 05-DEC-10:00 221.46 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 4843.02   1999.41   830.58   0.00 0.00 0.00 0.00 0.00   86.40  
Maximum of Months 13145.35   3598.94   1578.10   0.00 0.00 0.00 0.00 146.04   294.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3077.20 02-JAN-08:09 1969.28 02-JAN-07:10 6399.12 02-JAN-10:09 14425.49 02-JAN-10:09 0.00 0.00 0.00 5.81 14-JAN-11:30 160.60 02-JAN-03:00
February 3077.20 01-FEB-08:09 1969.28 01-FEB-07:10 6399.12 01-FEB-10:09 14425.49 01-FEB-10:09 0.00 0.00 0.00 2.57 01-FEB-12:00 164.60 12-FEB-18:50
March 3077.20 01-MAR-08:09 1969.28 01-MAR-07:10 6399.12 01-MAR-10:09 14425.49 01-MAR-10:09 0.00 0.00 0.00 0.00 01-MAR-00:05 161.92 28-MAR-22:00
April 3077.20 03-APR-07:10 1969.28 03-APR-06:10 6399.12 03-APR-09:09 14425.49 03-APR-09:09 0.00 0.00 0.00 3.84 26-APR-13:00 108.58 01-APR-05:53
May 3077.20 01-MAY-07:10 1969.28 01-MAY-06:10 6399.12 01-MAY-09:09 14425.49 01-MAY-09:09 0.00 0.00 0.00 0.00 01-MAY-00:03 120.73 13-MAY-11:00
June 3077.20 01-JUN-07:10 1969.28 01-JUN-06:10 6399.12 01-JUN-09:09 14425.49 01-JUN-09:09 0.00 0.00 0.00 1.32 29-JUN-11:00 70.78 03-JUN-16:50
July 485.87 03-JUL-07:10 1094.04 03-JUL-07:10 6399.12 03-JUL-09:09 14425.49 03-JUL-09:09 0.00 0.00 0.00 6.35 31-JUL-13:00 59.12 20-JUL-20:50
August 485.87 01-AUG-07:10 1094.04 01-AUG-07:10 6399.12 01-AUG-09:09 14425.49 01-AUG-09:09 0.00 0.00 0.00 5.12 17-AUG-14:00 51.15 27-AUG-18:10
September 3077.20 18-SEP-07:10 1969.28 05-SEP-06:10 6399.12 01-SEP-09:09 14425.49 01-SEP-09:09 0.00 0.00 0.00 26.65 30-SEP-12:00 73.25 02-SEP-15:00
October 3077.20 02-OCT-07:10 1969.28 02-OCT-06:10 6399.12 02-OCT-09:09 14425.49 02-OCT-09:09 0.00 0.00 0.00 67.72 14-OCT-11:53 111.23 11-OCT-02:10
November 3077.20 01-NOV-07:10 1969.28 01-NOV-06:10 6399.12 01-NOV-09:09 14425.49 01-NOV-09:09 0.00 0.00 0.00 3.87 19-NOV-09:45 146.20 23-NOV-04:30
December 3077.20 01-DEC-08:09 1969.28 01-DEC-07:10 6399.12 01-DEC-10:09 14425.49 01-DEC-10:09 0.00 0.00 0.00 2.27 05-DEC-10:00 129.43 24-DEC-06:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 485.87   1094.04   6399.12   14425.49   0.00 0.00 0.00 0.00   51.15  
Maximum of Months 3077.20   1969.28   6399.12   14425.49   0.00 0.00 0.00 67.72   164.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 38654.47 02-JAN-09:09 1983.52 02-JAN-16:30 1999.46 02-JAN-10:09 0.00 0.00 0.00 0.00 28.51 14-JAN-10:51 461.96 27-JAN-05:00
February 38654.47 01-FEB-09:09 1983.52 01-FEB-17:10 1999.46 01-FEB-10:09 0.00 0.00 0.00 0.00 11.57 01-FEB-12:00 563.13 25-FEB-13:00
March 38654.47 01-MAR-09:09 1983.52 01-MAR-17:19 1999.46 01-MAR-10:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 523.33 28-MAR-22:00
April 38654.47 03-APR-08:09 1983.52 03-APR-17:19 1999.46 03-APR-09:09 0.00 0.00 0.00 0.00 17.30 26-APR-13:00 364.31 01-APR-06:00
May 38654.47 01-MAY-08:09 1983.52 01-MAY-18:19 1999.46 01-MAY-09:09 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 364.77 26-MAY-06:00
June 38654.47 01-JUN-08:09 1983.52 01-JUN-18:19 1999.46 01-JUN-09:09 0.00 0.00 0.00 0.00 6.49 29-JUN-11:00 261.77 03-JUN-16:53
July 14241.12 03-JUL-16:10 1101.95 03-JUL-18:30 1999.46 03-JUL-09:09 0.00 0.00 0.00 0.00 28.58 31-JUL-13:00 211.78 16-JUL-18:00
August 14241.12 01-AUG-16:10 1101.95 01-AUG-18:19 1999.46 01-AUG-09:09 0.00 0.00 0.00 0.00 27.46 19-AUG-13:25 183.97 27-AUG-17:55
September 38654.47 05-SEP-08:09 1983.52 05-SEP-06:10 1999.46 01-SEP-09:09 0.00 0.00 0.00 0.00 120.10 30-SEP-11:35 228.76 02-SEP-14:52
October 38654.47 02-OCT-08:09 1983.52 02-OCT-06:10 1999.46 02-OCT-09:09 0.00 0.00 0.00 0.00 304.76 14-OCT-11:52 371.73 11-OCT-02:00
November 38654.47 01-NOV-08:09 1983.52 01-NOV-06:10 1999.46 01-NOV-09:09 0.00 0.00 0.00 0.00 29.49 19-NOV-12:52 462.80 23-NOV-03:55
December 38654.47 01-DEC-09:09 1983.52 01-DEC-16:10 1999.46 01-DEC-10:09 0.00 0.00 0.00 0.00 24.36 16-DEC-12:53 427.30 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 14241.12   1101.95   1999.46   0.00 0.00 0.00 0.00 0.00   183.97  
Maximum of Months 38654.47   1983.52   1999.46   0.00 0.00 0.00 0.00 304.76   563.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 4896.76 02-JAN-08:09 5087.33 02-JAN-07:10 5291.26 02-JAN-08:09 0.00 0.00 0.00 0.00 50.27 14-JAN-15:00 534.00 27-JAN-05:00
February 4896.76 01-FEB-08:09 5087.33 01-FEB-16:49 5291.26 01-FEB-08:09 0.00 0.00 0.00 0.00 12.86 01-FEB-12:00 661.57 25-FEB-13:00
March 4896.76 01-MAR-08:09 5087.33 01-MAR-16:00 5291.26 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 623.90 28-MAR-21:00
April 4896.76 03-APR-07:10 5087.33 03-APR-17:10 5291.26 03-APR-07:10 0.00 0.00 0.00 0.00 19.23 26-APR-13:00 424.57 01-APR-06:00
May 4896.76 01-MAY-07:10 5087.33 01-MAY-17:00 5291.26 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:03 434.59 13-MAY-11:00
June 4896.76 01-JUN-07:10 5087.33 01-JUN-18:19 5291.26 01-JUN-07:10 0.00 0.00 0.00 0.00 7.23 29-JUN-11:00 276.00 06-JUN-21:00
July 773.17 03-JUL-07:10 2826.28 03-JUL-18:19 2784.88 03-JUL-07:10 0.00 0.00 0.00 0.00 31.76 31-JUL-13:00 285.13 31-JUL-05:53
August 773.17 01-AUG-07:10 2826.28 01-AUG-18:10 2784.88 01-AUG-07:10 0.00 0.00 0.00 0.00 56.75 19-AUG-13:00 186.20 26-AUG-18:00
September 4896.76 18-SEP-07:10 5087.33 05-SEP-06:10 5291.26 05-SEP-07:10 0.00 0.00 0.00 0.00 161.58 30-SEP-12:00 253.74 02-SEP-15:00
October 4896.76 02-OCT-07:10 5087.33 02-OCT-06:10 5291.26 02-OCT-07:10 0.00 0.00 0.00 0.00 400.73 14-OCT-11:52 435.40 11-OCT-02:00
November 4896.76 01-NOV-07:10 5087.33 01-NOV-06:10 5291.26 01-NOV-07:10 0.00 0.00 0.00 0.00 86.25 19-NOV-13:00 551.65 23-NOV-03:55
December 4896.76 01-DEC-08:09 5087.33 01-DEC-14:50 5291.26 01-DEC-08:09 0.00 0.00 0.00 0.00 17.16 16-DEC-12:53 497.22 23-DEC-03:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 773.17   2826.28   2784.88   0.00 0.00 0.00 0.00 0.00   186.20  
Maximum of Months 4896.76   5087.33   5291.26   0.00 0.00 0.00 0.00 400.73   661.57  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5766.92 15-JAN-15:06 0.00 350.20 3647.17 0.00 0.00 0.00 0.00 0.00 42.91
February 4882.63 21-FEB-15:03 24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 0.00 17.30
March 4924.31 19-MAR-14:51 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 129.36
April 5817.83 30-APR-13:26 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 44.14
May 4973.55 29-MAY-16:41 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 149.10
June 5200.59 18-JUN-15:17 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 53.00
July 6285.10 23-JUL-15:48 0.00 311.29 2315.67 0.00 0.00 0.00 0.00 0.00 31.87
August 6747.52 06-AUG-14:06 0.00 389.11 2894.58 0.00 0.00 0.00 0.00 0.00 25.75
September 7068.02 30-SEP-11:43 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 64.09 0.00
October 7229.09 16-OCT-14:03 21259.96 1382.63 9190.09 0.00 0.00 0.00 0.00 26.15 0.00
November 5698.97 18-NOV-14:38 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 0.00 30.57
December 5404.82 19-DEC-14:40 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4882.63   0.00 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7229.09   24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 64.09 149.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29118.23 15-JAN-15:06 0.00 3093.41 17572.74 0.00 0.00 0.00 0.00 0.00 115.89
February 29516.46 20-FEB-11:41 0.00 2749.70 15620.22 0.00 0.00 0.00 0.00 0.00 347.97
March 27938.35 11-MAR-13:41 0.00 3437.13 19525.27 0.00 0.00 0.00 0.00 0.00 114.52
April 32142.39 30-APR-12:10 0.00 3437.13 19525.27 0.00 0.00 0.00 0.00 0.00 82.71
May 17635.59 29-MAY-16:41 0.00 2916.35 13667.69 0.00 0.00 0.00 0.00 0.00 345.53
June 18285.55 25-JUN-14:31 0.00 2405.99 13667.69 0.00 0.00 0.00 0.00 0.00 186.69
July 18701.62 30-JUL-13:01 0.00 2405.99 9762.63 0.00 0.00 0.00 0.00 0.00 17.18
August 18423.20 06-AUG-14:07 0.00 3437.13 13946.62 0.00 0.00 0.00 0.00 0.00 36.26
September 32012.19 30-SEP-11:02 0.00 2062.28 11715.16 0.00 0.00 0.00 0.00 148.78 0.00
October 34967.31 15-OCT-11:02 0.00 2062.28 11715.16 0.00 0.00 0.00 0.00 90.57 0.00
November 27918.17 23-NOV-11:41 0.00 3093.41 17572.74 0.00 0.00 0.00 0.00 0.00 199.04
December 32392.43 16-DEC-11:48 0.00 3437.13 19525.27 0.00 0.00 0.00 0.00 0.00 103.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17635.59   0.00 2062.28 9762.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34967.31   0.00 3437.13 19525.27 0.00 0.00 0.00 0.00 148.78 347.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3041.71 15-JAN-15:07 0.00 1538.70 1886.21 0.00 0.00 0.00 0.00 0.00 0.75
February 2877.55 04-FEB-14:17 0.00 1025.80 1257.48 0.00 0.00 0.00 0.00 0.00 9.18
March 3020.71 19-MAR-14:51 0.00 1196.77 1467.06 0.00 0.00 0.00 0.00 0.00 14.22
April 3698.28 30-APR-12:10 0.00 1709.67 2095.79 0.00 0.00 0.00 0.00 0.00 0.51
May 3399.15 29-MAY-16:41 0.00 1196.77 1467.06 0.00 0.00 0.00 0.00 0.00 18.99
June 3482.41 04-JUN-15:41 0.00 1367.73 1676.64 0.00 0.00 0.00 0.00 0.00 14.57
July 3424.32 02-JUL-15:32 0.00 1025.80 898.20 0.00 0.00 0.00 0.00 0.00 5.60
August 3211.50 20-AUG-14:22 0.00 1025.80 898.20 0.00 0.00 0.00 0.00 0.00 3.73
September 4197.99 29-SEP-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 4.75 0.00
October 4681.26 16-OCT-14:30 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 3.32 0.00
November 2926.31 20-NOV-13:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 1.84
December 3046.42 16-DEC-11:48 0.00 1709.67 2095.79 0.00 0.00 0.00 0.00 0.00 0.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2877.55   0.00 867.83 678.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4681.26   1178.08 1709.67 2095.79 0.00 0.00 0.00 0.00 4.75 18.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3431.75 15-JAN-15:06 0.00 321.01 3647.17 0.00 0.00 0.00 0.00 0.00 3.18
February 3100.43 01-FEB-16:00 3037.14 181.06 1312.87 0.00 0.00 0.00 0.00 0.00 8.59
March 3501.37 11-MAR-16:22 0.00 214.01 2431.45 0.00 0.00 0.00 0.00 0.00 48.14
April 4289.94 30-APR-12:10 0.00 659.32 4052.41 0.00 0.00 0.00 0.00 0.00 0.35
May 4353.47 29-MAY-16:41 0.00 249.68 2836.69 0.00 0.00 0.00 0.00 0.00 140.24
June 4579.72 18-JUN-16:51 0.00 249.68 2836.69 0.00 0.00 0.00 0.00 0.00 65.85
July 4485.54 02-JUL-15:32 0.00 214.01 1736.75 0.00 0.00 0.00 0.00 0.00 49.09
August 4124.43 19-AUG-15:48 0.00 321.01 2605.12 0.00 0.00 0.00 0.00 0.00 4.37
September 4789.94 29-SEP-15:00 3037.14 181.06 1312.87 0.00 0.00 0.00 0.00 31.64 0.00
October 4787.41 16-OCT-15:00 3037.14 181.06 1312.87 0.00 0.00 0.00 0.00 16.72 0.00
November 3169.76 10-NOV-15:30 3037.14 181.06 1312.87 0.00 0.00 0.00 0.00 0.00 19.63
December 3304.54 19-DEC-13:30 3037.14 334.68 1312.87 0.00 0.00 0.00 0.00 6.20 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3100.43   0.00 181.06 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4789.94   3037.14 659.32 4052.41 0.00 0.00 0.00 0.00 31.64 140.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12929.79 18-JAN-14:10 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 4.40 0.00
February 12046.05 01-FEB-15:04 102434.34 19985.27 44279.53 0.00 0.00 0.00 0.00 0.00 16.46
March 12605.43 23-MAR-15:00 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 0.00 16.81
April 16019.62 30-APR-12:10 0.00 4895.30 19525.27 0.00 0.00 0.00 0.00 0.00 10.62
May 15346.73 04-MAY-14:10 29266.95 4229.69 12651.29 0.00 0.00 0.00 0.00 0.00 16.09
June 15506.34 05-JUN-15:00 14633.48 2484.94 6325.65 0.00 0.00 0.00 0.00 0.00 43.41
July 14660.21 02-JUL-14:16 0.00 3426.71 9762.63 0.00 0.00 0.00 0.00 0.00 98.73
August 13752.08 06-AUG-14:07 0.00 4895.30 13946.62 0.00 0.00 0.00 0.00 13.61 0.00
September 18116.33 29-SEP-14:02 146334.77 24849.41 63256.47 0.00 0.00 0.00 0.00 99.62 0.00
October 18149.94 16-OCT-13:20 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 94.12 0.00
November 12694.35 28-NOV-13:30 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 8.32 0.00
December 13225.54 19-DEC-13:30 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 10.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12046.05   0.00 2484.94 6325.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18149.94   146334.77 24849.41 63256.47 0.00 0.00 0.00 0.00 99.62 98.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7603.80 14-JAN-14:58 0.00 389.11 4052.41 0.00 0.00 0.00 0.00 0.00 7.60
February 4817.85 21-FEB-15:03 24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 0.00 17.30
March 4937.57 19-MAR-15:11 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 114.58
April 5589.26 30-APR-13:30 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 44.10
May 4216.39 01-MAY-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 12.47
June 5213.11 18-JUN-15:24 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 51.85
July 5839.36 23-JUL-14:29 0.00 311.29 2315.67 0.00 0.00 0.00 0.00 0.00 27.14
August 6616.76 19-AUG-15:50 0.00 350.20 2605.12 0.00 0.00 0.00 0.00 0.00 19.01
September 6629.15 29-SEP-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 31.64 0.00
October 7561.00 15-OCT-11:50 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 72.90 0.00
November 7588.46 19-NOV-13:09 0.00 350.20 3647.17 0.00 0.00 0.00 0.00 0.00 0.73
December 5351.05 19-DEC-14:40 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4216.39   0.00 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7603.80   24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 72.90 114.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24684.36 22-JAN-14:12 0.00 1718.56 9762.63 0.00 0.00 0.00 0.00 0.00 253.74
February 24467.44 05-FEB-13:00 0.00 2405.99 13667.69 0.00 0.00 0.00 0.00 0.00 383.64
March 20301.04 11-MAR-14:12 0.00 2062.28 11715.16 0.00 0.00 0.00 0.00 0.00 130.90
April 25212.15 30-APR-12:19 0.00 2405.99 13667.69 0.00 0.00 0.00 0.00 0.00 88.37
May 17816.96 01-MAY-13:10 14633.48 2114.84 6325.65 0.00 0.00 0.00 0.00 0.00 28.11
June 17773.71 25-JUN-14:51 0.00 2916.35 13667.69 0.00 0.00 0.00 0.00 0.00 183.92
July 17966.52 02-JUL-14:31 0.00 3916.24 11157.30 0.00 0.00 0.00 0.00 0.00 125.36
August 18849.18 20-AUG-13:11 0.00 2916.35 9762.63 0.00 0.00 0.00 0.00 0.00 98.31
September 26841.90 29-SEP-13:30 14633.48 1744.75 6325.65 0.00 0.00 0.00 0.00 101.86 0.00
October 32319.49 15-OCT-11:50 0.00 2062.28 11715.16 0.00 0.00 0.00 0.00 189.42 0.00
November 32529.42 19-NOV-13:09 0.00 3093.41 17572.74 0.00 0.00 0.00 0.00 0.00 7.48
December 28024.40 25-DEC-11:31 0.00 3093.41 17572.74 0.00 0.00 0.00 0.00 0.00 179.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17773.71   0.00 1718.56 6325.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32529.42   14633.48 3916.24 17572.74 0.00 0.00 0.00 0.00 189.42 383.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2959.10 21-JAN-12:12 0.00 1025.80 1257.48 0.00 0.00 0.00 0.00 0.00 16.17
February 2869.38 05-FEB-14:52 0.00 1025.80 1257.48 0.00 0.00 0.00 0.00 0.00 13.72
March 3068.71 19-MAR-15:11 0.00 1196.77 1467.06 0.00 0.00 0.00 0.00 0.00 12.68
April 3330.97 30-APR-12:20 0.00 1196.77 1467.06 0.00 0.00 0.00 0.00 0.00 0.43
May 3251.27 01-MAY-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 1.87
June 3501.22 05-JUN-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 2.46
July 3472.97 02-JUL-14:31 0.00 1367.73 1197.60 0.00 0.00 0.00 0.00 0.00 6.48
August 3267.80 20-AUG-13:11 0.00 1196.77 1047.90 0.00 0.00 0.00 0.00 0.00 2.65
September 4172.65 29-SEP-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 4.75 0.00
October 4634.65 16-OCT-14:30 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 3.32 0.00
November 3359.87 19-NOV-13:09 0.00 1538.70 1886.21 0.00 0.00 0.00 0.00 5.27 0.00
December 2994.91 19-DEC-13:30 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.61 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2869.38   0.00 867.83 678.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4634.65   1178.08 1538.70 1886.21 0.00 0.00 0.00 0.00 5.27 16.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3349.64 15-JAN-15:21 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 9.31
February 3114.73 01-FEB-16:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 8.59
March 3503.65 19-MAR-15:11 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 80.60
April 4066.20 30-APR-16:41 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 30.42
May 3810.29 03-MAY-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.75
June 4572.02 25-JUN-16:21 0.00 272.38 2836.69 0.00 0.00 0.00 0.00 0.00 65.02
July 4592.24 01-JUL-16:21 0.00 272.38 2026.21 0.00 0.00 0.00 0.00 0.00 63.74
August 4257.86 06-AUG-15:52 0.00 233.47 1736.75 0.00 0.00 0.00 0.00 0.00 27.24
September 4809.25 29-SEP-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 31.64 0.00
October 4794.63 16-OCT-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 16.72 0.00
November 3579.28 19-NOV-13:09 0.00 350.20 3647.17 0.00 0.00 0.00 0.00 47.07 0.00
December 3278.19 19-DEC-13:30 3037.14 351.14 1312.87 0.00 0.00 0.00 0.00 6.03 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3114.73   0.00 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4809.25   3037.14 351.14 3647.17 0.00 0.00 0.00 0.00 47.07 80.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12889.79 18-JAN-14:30 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 0.17 0.00
February 12086.78 01-FEB-15:04 102434.34 19985.27 44279.53 0.00 0.00 0.00 0.00 0.00 16.42
March 12644.94 23-MAR-15:00 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 0.00 16.69
April 14627.16 26-APR-14:10 14633.48 2484.94 6325.65 0.00 0.00 0.00 0.00 11.50 0.00
May 15392.50 04-MAY-14:10 29266.95 4229.69 12651.29 0.00 0.00 0.00 0.00 0.00 16.09
June 15685.73 05-JUN-13:40 14633.48 2114.84 6325.65 0.00 0.00 0.00 0.00 0.00 35.00
July 15170.52 02-JUL-14:31 0.00 3916.24 11157.30 0.00 0.00 0.00 0.00 0.00 118.34
August 14223.43 20-AUG-13:11 0.00 3937.07 9762.63 0.00 0.00 0.00 0.00 0.00 49.12
September 18123.89 29-SEP-14:02 146334.77 24849.41 63256.47 0.00 0.00 0.00 0.00 99.62 0.00
October 18130.18 16-OCT-13:20 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 94.12 0.00
November 12995.55 19-NOV-13:09 0.00 5061.95 17572.74 0.00 0.00 0.00 0.00 126.72 0.00
December 13101.81 19-DEC-13:30 14633.48 2855.04 6325.65 0.00 0.00 0.00 0.00 10.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12086.78   0.00 2114.84 6325.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18130.18   146334.77 24849.41 63256.47 0.00 0.00 0.00 0.00 126.72 118.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5180.72 15-JAN-15:06 0.00 350.20 3647.17 0.00 0.00 0.00 0.00 0.00 42.86
February 4879.70 21-FEB-15:03 24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 0.00 17.30
March 4903.66 11-MAR-15:47 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 0.00 47.89
April 5251.91 30-APR-11:46 0.00 389.11 4052.41 0.00 0.00 0.00 0.00 0.00 19.94
May 4270.92 03-MAY-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.75
June 5498.39 04-JUN-15:41 0.00 311.29 3241.93 0.00 0.00 0.00 0.00 0.00 113.97
July 5356.72 30-JUL-13:10 0.00 272.38 2026.21 0.00 0.00 0.00 0.00 0.00 8.18
August 6672.43 06-AUG-14:07 0.00 389.11 2894.58 0.00 0.00 0.00 0.00 0.00 25.70
September 9363.05 30-SEP-15:32 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 15.94 0.00
October 9326.72 15-OCT-15:32 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 33.57 0.00
November 5601.32 18-NOV-14:38 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 0.00 30.55
December 5415.09 19-DEC-14:40 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4270.92   0.00 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9363.05   24297.09 1580.15 10502.96 0.00 0.00 0.00 0.00 33.57 113.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29042.70 15-JAN-15:06 0.00 5061.95 17572.74 0.00 0.00 0.00 0.00 0.00 115.87
February 28360.19 20-FEB-11:41 0.00 4499.51 15620.22 0.00 0.00 0.00 0.00 0.00 348.02
March 24743.22 11-MAR-13:10 0.00 3937.07 13667.69 0.00 0.00 0.00 0.00 0.00 107.05
April 32216.88 30-APR-11:46 0.00 5624.39 19525.27 0.00 0.00 0.00 0.00 0.00 65.05
May 18918.06 01-MAY-13:10 14633.48 3040.09 6325.65 0.00 0.00 0.00 0.00 0.00 28.11
June 18104.79 25-JUN-14:31 0.00 4192.25 13667.69 0.00 0.00 0.00 0.00 0.00 196.96
July 17479.65 01-JUL-15:31 0.00 4447.43 9762.63 0.00 0.00 0.00 0.00 0.00 123.78
August 18026.66 06-AUG-14:08 0.00 5624.39 13946.62 0.00 0.00 0.00 0.00 0.00 40.46
September 32537.19 30-SEP-08:17 0.00 5624.39 19525.27 0.00 0.00 0.00 0.00 0.00 12.30
October 34830.64 15-OCT-13:32 0.00 3374.63 11715.16 0.00 0.00 0.00 0.00 183.14 0.00
November 26732.89 19-NOV-12:50 0.00 2812.20 9762.63 0.00 0.00 0.00 0.00 0.00 0.23
December 32560.63 16-DEC-11:49 0.00 5624.39 19525.27 0.00 0.00 0.00 0.00 0.00 103.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17479.65   0.00 2812.20 6325.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34830.64   14633.48 5624.39 19525.27 0.00 0.00 0.00 0.00 183.14 348.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3025.96 15-JAN-15:07 0.00 1538.70 1886.21 0.00 0.00 0.00 0.00 0.00 0.95
February 2860.15 20-FEB-15:52 0.00 1025.80 1257.48 0.00 0.00 0.00 0.00 0.00 15.65
March 3035.09 19-MAR-15:42 0.00 1025.80 1257.48 0.00 0.00 0.00 0.00 0.00 10.55
April 3675.78 30-APR-11:46 0.00 1709.67 2095.79 0.00 0.00 0.00 0.00 0.13 0.00
May 3443.76 03-MAY-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 0.86
June 3669.71 05-JUN-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 2.46
July 3398.09 02-JUL-14:10 0.00 1196.77 1047.90 0.00 0.00 0.00 0.00 0.00 5.75
August 3178.18 06-AUG-14:08 0.00 1709.67 1497.00 0.00 0.00 0.00 0.00 0.42 0.00
September 4375.42 29-SEP-15:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 4.75 0.00
October 4781.37 16-OCT-14:30 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 3.32 0.00
November 2981.11 20-NOV-13:00 1178.08 867.83 678.98 0.00 0.00 0.00 0.00 0.00 1.87
December 3134.65 17-DEC-11:56 0.00 1709.67 2095.79 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2860.15   0.00 867.83 678.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4781.37   1178.08 1709.67 2095.79 0.00 0.00 0.00 0.00 4.75 15.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3375.50 15-JAN-15:06 0.00 350.20 3647.17 0.00 0.00 0.00 0.00 0.00 3.46
February 3083.41 01-FEB-16:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 8.85
March 3475.42 19-MAR-15:42 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 0.00 67.62
April 4236.43 30-APR-11:46 0.00 691.75 4052.41 0.00 0.00 0.00 0.00 4.61 0.00
May 3917.10 03-MAY-15:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 5.75
June 5526.64 04-JUN-15:41 0.00 311.29 3241.93 0.00 0.00 0.00 0.00 0.00 113.97
July 4745.84 02-JUL-16:52 0.00 233.47 1736.75 0.00 0.00 0.00 0.00 0.00 56.67
August 4230.11 19-AUG-16:52 0.00 233.47 1736.75 0.00 0.00 0.00 0.00 0.00 13.86
September 5079.28 30-SEP-15:32 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 25.06 0.00
October 4887.23 15-OCT-15:32 0.00 233.47 2431.45 0.00 0.00 0.00 0.00 55.28 0.00
November 3198.23 28-NOV-14:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 4.85 0.00
December 3335.37 19-DEC-14:00 3037.14 197.52 1312.87 0.00 0.00 0.00 0.00 1.63 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3083.41   0.00 197.52 1312.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5526.64   3037.14 691.75 4052.41 0.00 0.00 0.00 0.00 55.28 113.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8708.89 18-JAN-14:30 9663.62 1641.00 4177.31 0.00 0.00 0.00 0.00 0.71 0.00
February 7882.11 01-FEB-15:40 9663.62 1641.00 4177.31 0.00 0.00 0.00 0.00 0.00 14.47
March 8223.76 23-MAR-15:00 9663.62 1396.59 4177.31 0.00 0.00 0.00 0.00 0.00 11.11
April 10543.63 30-APR-11:46 0.00 2751.27 12894.05 0.00 0.00 0.00 0.00 2.09 0.00
May 10489.47 04-MAY-13:40 9663.62 1152.19 4177.31 0.00 0.00 0.00 0.00 0.00 9.33
June 10666.13 05-JUN-13:40 9663.62 1152.19 4177.31 0.00 0.00 0.00 0.00 0.00 23.12
July 9856.55 01-JUL-15:31 0.00 1925.89 6447.02 0.00 0.00 0.00 0.00 0.00 77.12
August 9148.48 06-AUG-14:08 0.00 2269.80 9210.03 0.00 0.00 0.00 0.00 4.69 0.00
September 12121.78 29-SEP-14:02 96636.17 13965.95 41773.14 0.00 0.00 0.00 0.00 65.79 0.00
October 11907.47 16-OCT-13:30 9663.62 1641.00 4177.31 0.00 0.00 0.00 0.00 58.89 0.00
November 8426.45 28-NOV-13:50 9663.62 1641.00 4177.31 0.00 0.00 0.00 0.00 6.27 0.00
December 8820.82 19-DEC-13:30 9663.62 1641.00 4177.31 0.00 0.00 0.00 0.00 7.34 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7882.11   0.00 1152.19 4177.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12121.78   96636.17 13965.95 41773.14 0.00 0.00 0.00 0.00 65.79 77.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6309.89 24-JAN-15:05 9939.72 1436.50 5728.89 0.00 0.00 0.00 0.00 2.10 0.00
February 4987.17 01-FEB-14:10 4969.86 718.25 2864.44 0.00 0.00 0.00 0.00 0.00 12.31
March 6782.32 19-MAR-11:59 0.00 990.46 6189.14 0.00 0.00 0.00 0.00 0.00 36.44
April 7476.17 08-APR-12:31 0.00 990.46 6189.14 0.00 0.00 0.00 0.00 0.00 36.12
May 7704.29 06-MAY-13:22 0.00 700.40 5304.98 0.00 0.00 0.00 0.00 0.00 75.04
June 8013.07 10-JUN-13:32 0.00 700.40 5304.98 0.00 0.00 0.00 0.00 0.00 68.64
July 7557.02 01-JUL-08:22 0.00 700.40 3789.27 0.00 0.00 0.00 0.00 0.00 27.69
August 7011.75 12-AUG-11:42 0.00 707.47 3157.73 0.00 0.00 0.00 0.00 0.00 6.18
September 7967.50 23-SEP-10:41 0.00 1131.95 7073.31 0.00 0.00 0.00 0.00 0.00 42.03
October 7976.28 05-OCT-06:01 0.00 13467.16 8841.63 0.00 0.00 0.00 0.00 0.00 0.00
November 6672.53 18-NOV-12:30 0.00 1496.30 7957.47 0.00 0.00 0.00 0.00 6.67 0.00
December 6418.28 05-DEC-15:10 4969.86 843.94 2864.44 0.00 0.00 0.00 0.00 4.03 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4987.17   0.00 700.40 2864.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8013.07   9939.72 13467.16 8841.63 0.00 0.00 0.00 0.00 6.67 75.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6110.25 18-JAN-14:40 3350.23 2467.90 1930.85 0.00 0.00 0.00 0.00 0.00 0.66
February 6346.88 03-FEB-15:10 6700.46 4935.80 3861.70 0.00 0.00 0.00 0.00 0.00 2.12
March 7790.21 23-MAR-15:00 3350.23 2467.90 1930.85 0.00 0.00 0.00 0.00 0.00 2.94
April 12179.69 27-APR-07:01 23451.62 17275.29 13515.93 0.00 0.00 0.00 0.00 0.00 0.72
May 12422.18 01-MAY-07:01 30152.09 22211.09 17377.63 0.00 0.00 0.00 0.00 0.00 0.62
June 12810.04 26-JUN-06:12 0.00 9871.60 2383.97 0.00 0.00 0.00 0.00 0.00 3.86
July 12344.81 03-JUL-06:12 0.00 2430.93 2128.54 0.00 0.00 0.00 0.00 0.00 0.00
August 11983.18 07-AUG-07:03 2115.94 5484.15 4064.94 0.00 0.00 0.00 0.00 0.00 0.98
September 12749.15 25-SEP-06:12 0.00 12339.49 2979.96 0.00 0.00 0.00 0.00 0.00 4.21
October 13061.20 02-OCT-06:12 0.00 12339.49 2979.96 0.00 0.00 0.00 0.00 0.00 3.98
November 6656.83 01-NOV-14:15 6700.46 4935.80 3861.70 0.00 0.00 0.00 0.00 0.00 8.34
December 6112.92 07-DEC-14:30 3350.23 2467.90 1930.85 0.00 0.00 0.00 0.00 0.00 7.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6110.25   0.00 2430.93 1930.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13061.20   30152.09 22211.09 17377.63 0.00 0.00 0.00 0.00 0.00 8.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7894.94 22-JAN-15:29 0.00 678.49 1306.60 0.00 0.00 0.00 0.00 0.00 111.78
February 6708.83 20-FEB-14:32 0.00 581.57 1119.94 0.00 0.00 0.00 0.00 0.00 200.05
March 3376.41 23-MAR-14:00 2098.51 492.00 604.72 0.00 0.00 0.00 0.00 0.00 473.22
April 7020.97 26-APR-14:10 2098.51 492.00 604.72 0.00 0.00 0.00 0.00 4272.14 0.00
May 3121.74 03-MAY-13:00 2098.51 492.00 604.72 0.00 0.00 0.00 0.00 0.00 1.38
June 2280.99 25-JUN-14:51 0.00 678.49 1306.60 0.00 0.00 0.00 0.00 0.00 50.94
July 7342.39 31-JUL-14:10 994.03 820.00 954.81 0.00 0.00 0.00 0.00 5963.04 0.00
August 7687.35 17-AUG-14:10 1325.38 1093.33 1273.09 0.00 0.00 0.00 0.00 7277.13 0.00
September 10385.64 29-SEP-14:10 20985.12 4920.00 6047.16 0.00 0.00 0.00 0.00 11668.38 0.00
October 9582.67 16-OCT-14:10 14689.58 3444.00 4233.01 0.00 0.00 0.00 0.00 8850.10 0.00
November 7763.09 19-NOV-11:38 0.00 581.57 1119.94 0.00 0.00 0.00 0.00 0.00 8.86
December 7530.29 31-DEC-12:35 0.00 581.57 1119.94 0.00 0.00 0.00 0.00 0.00 104.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2280.99   0.00 492.00 604.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10385.64   20985.12 4920.00 6047.16 0.00 0.00 0.00 0.00 11668.38 473.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1684.83 20-JAN-13:20 463.87 1025.33 2227.90 0.00 0.00 0.00 0.00 0.00 0.00
February 1663.15 03-FEB-15:00 463.87 1025.33 2227.90 0.00 0.00 0.00 0.00 0.00 0.00
March 2397.99 19-MAR-13:28 0.00 1211.94 4126.09 0.00 0.00 0.00 0.00 0.00 0.00
April 7375.06 29-APR-14:31 0.00 1413.93 4813.78 0.00 0.00 0.00 0.00 0.00 0.00
May 7361.28 06-MAY-13:22 0.00 1211.94 4126.09 0.00 0.00 0.00 0.00 0.00 0.00
June 7402.61 18-JUN-12:41 0.00 1413.93 4813.78 0.00 0.00 0.00 0.00 0.00 0.00
July 7365.73 01-JUL-10:41 0.00 1817.90 4420.82 0.00 0.00 0.00 0.00 0.00 0.00
August 7317.35 12-AUG-15:52 0.00 1211.94 2947.21 0.00 0.00 0.00 0.00 0.00 0.00
September 7391.71 23-SEP-10:41 0.00 1615.91 5501.46 0.00 0.00 0.00 0.00 0.00 0.00
October 7416.84 05-OCT-06:01 0.00 10253.27 6876.82 0.00 0.00 0.00 0.00 0.00 0.00
November 1868.68 01-NOV-14:03 3247.06 7177.29 15595.31 0.00 0.00 0.00 0.00 0.00 0.00
December 1654.85 07-DEC-14:30 463.87 1025.33 2227.90 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1654.85   0.00 1025.33 2227.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7416.84   3247.06 10253.27 15595.31 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1326.92 24-JAN-15:05 2331.76 1984.20 1343.81 0.00 0.00 0.00 0.00 0.00 0.41
February 1117.28 03-FEB-16:00 1165.88 992.10 671.91 0.00 0.00 0.00 0.00 0.00 6.98
March 1328.05 12-MAR-14:31 0.00 1368.17 1451.77 0.00 0.00 0.00 0.00 0.00 34.01
April 6528.62 29-APR-16:20 0.00 1172.72 1244.38 0.00 0.00 0.00 0.00 0.00 62.24
May 5578.80 28-MAY-17:12 0.00 977.27 1036.98 0.00 0.00 0.00 0.00 0.00 55.59
June 7425.18 25-JUN-16:10 0.00 1563.63 1659.17 0.00 0.00 0.00 0.00 0.00 34.24
July 7676.43 01-JUL-15:52 0.00 1172.72 888.84 0.00 0.00 0.00 0.00 0.00 31.58
August 7670.45 19-AUG-16:52 0.00 1172.72 888.84 0.00 0.00 0.00 0.00 0.00 9.38
September 7432.18 30-SEP-16:22 0.00 1172.72 1244.38 0.00 0.00 0.00 0.00 1.26 0.00
October 2390.32 16-OCT-15:00 1165.88 992.10 671.91 0.00 0.00 0.00 0.00 4.60 0.00
November 1225.59 18-NOV-12:30 0.00 1759.08 1866.57 0.00 0.00 0.00 0.00 2.66 0.00
December 1380.21 05-DEC-15:10 1165.88 992.10 671.91 0.00 0.00 0.00 0.00 0.00 0.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1117.28   0.00 977.27 671.91 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7676.43   2331.76 1984.20 1866.57 0.00 0.00 0.00 0.00 4.60 62.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16183.27 22-JAN-11:24 0.00 2025.72 6498.60 0.00 0.00 0.00 0.00 0.00 108.52
February 14612.01 20-FEB-13:08 0.00 2025.72 6498.60 0.00 0.00 0.00 0.00 0.00 376.03
March 21463.44 12-MAR-14:31 0.00 2836.00 9098.04 0.00 0.00 0.00 0.00 0.00 178.39
April 21418.94 30-APR-12:01 0.00 4051.43 12997.20 0.00 0.00 0.00 0.00 0.00 64.44
May 17989.20 01-MAY-07:01 24353.63 18508.44 37896.60 0.00 0.00 0.00 0.00 0.00 2.88
June 17913.21 19-JUN-07:03 10823.83 8225.98 16842.93 0.00 0.00 0.00 0.00 0.00 22.42
July 20784.76 30-JUL-13:26 0.00 2836.00 6498.60 0.00 0.00 0.00 0.00 0.00 53.49
August 21474.28 06-AUG-12:51 0.00 4051.43 9283.71 0.00 0.00 0.00 0.00 0.00 24.14
September 22387.91 30-SEP-11:42 0.00 2430.86 7798.32 0.00 0.00 0.00 0.00 117.56 0.00
October 22060.97 15-OCT-09:52 0.00 2025.72 6498.60 0.00 0.00 0.00 0.00 76.03 0.00
November 20888.34 18-NOV-12:30 0.00 3646.29 11697.48 0.00 0.00 0.00 0.00 0.00 18.54
December 12440.39 19-DEC-13:20 2705.96 2056.49 4210.73 0.00 0.00 0.00 0.00 6.23 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12440.39   0.00 2025.72 4210.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22387.91   24353.63 18508.44 37896.60 0.00 0.00 0.00 0.00 117.56 376.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27649.82 17-JAN-06:01 0.00 7089.97 4871.08 0.00 0.00 0.00 0.00 0.00 78.05
February 26016.63 16-FEB-07:01 0.00 11996.47 4871.08 0.00 0.00 0.00 0.00 0.00 7.59
March 34758.50 20-MAR-05:01 0.00 4962.98 3409.76 0.00 0.00 0.00 0.00 0.00 75.35
April 37275.61 17-APR-05:01 0.00 4962.98 3409.76 0.00 0.00 0.00 0.00 0.00 144.46
May 40200.55 24-MAY-05:02 0.00 2835.99 2922.65 0.00 0.00 0.00 0.00 0.00 64.28
June 35753.50 05-JUN-05:01 0.00 3781.32 3896.87 0.00 0.00 0.00 0.00 0.00 58.85
July 31280.86 10-JUL-05:01 0.00 7089.97 3479.35 0.00 0.00 0.00 0.00 0.00 12.77
August 30872.77 28-AUG-05:01 0.00 5671.97 2783.48 0.00 0.00 0.00 0.00 0.00 34.28
September 33933.24 29-SEP-05:01 0.00 4962.98 3409.76 0.00 0.00 0.00 0.00 0.00 40.51
October 39503.97 18-OCT-05:02 0.00 4253.98 2922.65 0.00 0.00 0.00 0.00 0.00 42.53
November 40859.01 20-NOV-06:01 0.00 7089.97 4871.08 0.00 0.00 0.00 0.00 0.00 121.80
December 29014.48 06-DEC-06:01 0.00 5671.97 3896.87 0.00 0.00 0.00 0.00 0.00 133.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 26016.63   0.00 2835.99 2783.48 0.00 0.00 0.00 0.00 0.00 7.59
Maximum of Months 40859.01   0.00 11996.47 4871.08 0.00 0.00 0.00 0.00 0.00 144.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 57384.82 09-JAN-06:01 0.00 3879.48 25596.48 14425.49 0.00 0.00 0.00 0.00 94.97
February 51793.88 06-FEB-06:11 0.00 3879.48 25596.48 14425.49 0.00 0.00 0.00 0.00 61.03
March 49959.93 07-MAR-05:12 0.00 2327.69 15357.89 8655.29 0.00 0.00 0.00 0.00 20.68
April 39696.89 20-APR-05:01 0.00 3103.58 20477.18 11540.39 0.00 0.00 0.00 0.00 26.35
May 43062.11 15-MAY-05:01 0.00 3879.48 25596.48 14425.49 0.00 0.00 0.00 0.00 63.34
June 36666.08 13-JUN-05:01 0.00 3103.58 20477.18 11540.39 0.00 0.00 0.00 0.00 29.51
July 31502.32 11-JUL-03:32 0.00 2327.69 15357.89 8655.29 0.00 0.00 0.00 0.00 6.55
August 33113.64 22-AUG-04:12 0.00 2327.69 15357.89 8655.29 0.00 0.00 0.00 0.00 27.48
September 34481.40 20-SEP-05:01 0.00 2715.63 17917.54 10097.84 0.00 0.00 0.00 0.00 29.41
October 45003.86 26-OCT-05:01 0.00 3103.58 20477.18 11540.39 0.00 0.00 0.00 0.00 39.62
November 51179.66 30-NOV-06:01 0.00 3103.58 20477.18 11540.39 0.00 0.00 0.00 0.00 92.80
December 55574.60 26-DEC-06:01 0.00 3879.48 25596.48 14425.49 0.00 0.00 0.00 0.00 13.20
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31502.32   0.00 2327.69 15357.89 8655.29 0.00 0.00 0.00 0.00 6.55
Maximum of Months 57384.82   0.00 3879.48 25596.48 14425.49 0.00 0.00 0.00 0.00 94.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27577.37 19-JAN-09:06 270581.27 6942.31 8397.74 0.00 0.00 0.00 0.00 0.00 2.01
February 24001.10 01-FEB-09:07 115963.40 2975.27 3599.03 0.00 0.00 0.00 0.00 0.00 5.99
March 24558.19 23-MAR-08:06 309235.74 7934.07 9597.42 0.00 0.00 0.00 0.00 0.00 0.00
April 29329.12 27-APR-05:01 0.00 2735.27 5598.50 0.00 0.00 0.00 0.00 0.00 13.16
May 37071.47 01-MAY-05:01 0.00 3126.02 6398.28 0.00 0.00 0.00 0.00 0.00 0.00
June 46829.30 06-JUN-05:01 0.00 3907.53 7997.85 0.00 0.00 0.00 0.00 0.00 0.00
July 47062.30 10-JUL-05:01 0.00 3907.53 7997.85 0.00 0.00 0.00 0.00 0.00 22.86
August 45755.94 28-AUG-05:01 0.00 3126.02 6398.28 0.00 0.00 0.00 0.00 0.00 62.57
September 43938.84 26-SEP-05:01 0.00 3907.53 7997.85 0.00 0.00 0.00 0.00 0.00 61.35
October 58524.32 16-OCT-05:01 0.00 3907.53 7997.85 0.00 0.00 0.00 0.00 0.00 91.86
November 25669.43 10-NOV-09:06 270581.27 6942.31 8397.74 0.00 0.00 0.00 0.00 0.00 12.37
December 29480.02 19-DEC-09:06 193272.34 4958.79 5998.39 0.00 0.00 0.00 0.00 0.00 11.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24001.10   0.00 2735.27 3599.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 58524.32   309235.74 7934.07 9597.42 0.00 0.00 0.00 0.00 0.00 91.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10756.08 18-JAN-14:10 4896.76 4341.19 5291.26 0.00 0.00 0.00 0.00 1.93 0.00
February 10319.96 01-FEB-13:00 4896.76 4341.19 5291.26 0.00 0.00 0.00 0.00 0.00 0.02
March 11995.37 23-MAR-14:00 4896.76 4341.19 5291.26 0.00 0.00 0.00 0.00 0.00 6.53
April 14217.88 26-APR-13:30 4896.76 4341.19 5291.26 0.00 0.00 0.00 0.00 15.07 0.00
May 14666.85 29-MAY-10:00 0.00 3367.44 9799.48 0.00 0.00 0.00 0.00 0.00 227.52
June 18686.46 05-JUN-07:02 29380.56 17093.42 31747.59 0.00 0.00 0.00 0.00 0.00 3.89
July 19580.69 23-JUL-09:21 0.00 4349.61 8166.23 0.00 0.00 0.00 0.00 0.00 39.14
August 17735.57 19-AUG-09:37 0.00 3728.24 6999.63 0.00 0.00 0.00 0.00 0.00 56.42
September 18323.73 10-SEP-08:37 0.00 3728.24 9799.48 0.00 0.00 0.00 0.00 0.00 63.25
October 20367.56 05-OCT-06:12 0.00 25436.64 8166.23 0.00 0.00 0.00 0.00 0.00 0.00
November 10693.16 10-NOV-13:10 4896.76 4341.19 5291.26 0.00 0.00 0.00 0.00 0.00 25.88
December 10442.98 05-DEC-15:50 4896.76 5087.33 5291.26 0.00 0.00 0.00 0.00 0.00 2.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10319.96   0.00 3367.44 5291.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20367.56   29380.56 25436.64 31747.59 0.00 0.00 0.00 0.00 15.07 227.52



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.215324E+12 221483.01 18-JAN-12:00 0.540835E+11 188825.37 03-JAN-08:09
February 0.187375E+12 212719.62 01-FEB-11:00 0.469221E+11 141734.02 27-FEB-08:09
March 0.213671E+12 201780.50 23-MAR-13:00 0.585891E+11 192173.84 30-MAR-07:10
April 0.209131E+12 225012.38 26-APR-12:00 0.441840E+11 96576.58 03-APR-07:10
May 0.222068E+12 212338.64 03-MAY-11:00 0.467043E+11 96129.34 15-MAY-07:10
June 0.232295E+12 209885.52 26-JUN-10:50 0.413008E+11 66600.15 14-JUN-11:00
July 0.180077E+12 162458.57 31-JUL-11:00 0.383545E+11 115599.94 13-JUL-07:10
August 0.194490E+12 163654.80 14-AUG-10:50 0.416023E+11 109399.19 24-AUG-07:10
September 0.233194E+12 298218.90 29-SEP-12:00 0.392445E+11 107905.46 01-SEP-07:10
October 0.261323E+12 313823.37 16-OCT-10:00 0.440305E+11 68678.72 12-OCT-07:10
November 0.214650E+12 214120.09 28-NOV-13:00 0.466556E+11 104102.81 24-NOV-08:09
December 0.214895E+12 224935.49 19-DEC-12:00 0.493449E+11 142235.45 13-DEC-08:09
             
Annual Sum or Average 0.257849E+13     0.551016E+12    
Minimum of Months 0.180077E+12 162458.57   0.383545E+11 66600.15  
Maximum of Months 0.261323E+12 313823.37   0.585891E+11 192173.84  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.598274E+11 0.528597E+10 0.102273E+12 0.217218E+10 0.216448E+11 35760280.57 0.00 0.160745E+11 0.00 0.00 0.00 0.262842E+10 0.00
February 0.521004E+11 0.447546E+10 0.924273E+11 0.196245E+10 0.189184E+11 28443346.58 0.00 0.102161E+11 0.00 0.00 0.00 0.237789E+10 0.00
March 0.595015E+11 0.452142E+10 0.105488E+12 0.224997E+10 0.219830E+11 43425806.97 0.00 0.116197E+11 0.00 0.00 0.00 0.286412E+10 0.00
April 0.520644E+11 0.395022E+10 0.984551E+11 0.208768E+10 0.212105E+11 18119409.63 0.00 0.236048E+11 0.00 0.00 0.00 0.250563E+10 0.00
May 0.544518E+11 0.373122E+10 0.103881E+12 0.220971E+10 0.227687E+11 19013987.11 0.00 0.268524E+11 0.00 0.00 0.00 0.274620E+10 0.00
June 0.534671E+11 0.344578E+10 0.101650E+12 0.216623E+10 0.233737E+11 16507890.11 0.00 0.411563E+11 0.00 0.00 0.00 0.176699E+10 0.00
July 0.329884E+11 0.361657E+10 0.687059E+11 0.140752E+10 0.202895E+11 19815039.31 0.00 0.469493E+11 0.00 0.00 0.00 0.739230E+09 0.00
August 0.351665E+11 0.391218E+10 0.710419E+11 0.144024E+10 0.228175E+11 22553119.72 0.00 0.538980E+11 0.00 0.00 0.00 0.827085E+09 0.00
September 0.527063E+11 0.419391E+10 0.971506E+11 0.205487E+10 0.235664E+11 15131159.38 0.00 0.466270E+11 0.00 0.00 0.00 0.161998E+10 0.00
October 0.586794E+11 0.477468E+10 0.102273E+12 0.217181E+10 0.277218E+11 14603364.29 0.00 0.576535E+11 0.00 0.00 0.00 0.262829E+10 0.00
November 0.582081E+11 0.500624E+10 0.100063E+12 0.212862E+10 0.228493E+11 21316293.95 0.00 0.185456E+11 0.00 0.00 0.00 0.262360E+10 0.00
December 0.586458E+11 0.539109E+10 0.100665E+12 0.213291E+10 0.217090E+11 26894604.25 0.00 0.184486E+11 0.00 0.00 0.00 0.251063E+10 0.00
                           
Annual Sum or Average 0.627807E+12 0.523047E+11 0.114407E+13 0.241842E+11 0.268853E+12 0.281584E+09 0.00 0.371646E+12 0.00 0.00 0.00 0.258381E+11 0.00
Minimum of Months 0.329884E+11 0.344578E+10 0.687059E+11 0.140752E+10 0.189184E+11 14603364.29 0.00 0.102161E+11 0.00 0.00 0.00 0.739230E+09 0.00
Maximum of Months 0.598274E+11 0.539109E+10 0.105488E+12 0.224997E+10 0.277218E+11 43425806.97 0.00 0.576535E+11 0.00 0.00 0.00 0.286412E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.303281E+11 0.00 0.998865E+10 0.00 0.137667E+11 0.00 0.00
February 0.274200E+11 0.00 0.704215E+10 0.00 0.124599E+11 0.00 0.00
March 0.319900E+11 0.00 0.120018E+11 0.00 0.145973E+11 0.00 0.00
April 0.290818E+11 0.00 0.224861E+10 0.00 0.128536E+11 0.00 0.00
May 0.311591E+11 0.00 0.190901E+10 0.00 0.136363E+11 0.00 0.00
June 0.307436E+11 0.00 0.905671E+09 0.00 0.965150E+10 0.00 0.00
July 0.294972E+11 0.00 0.297966E+10 0.00 0.587761E+10 0.00 0.00
August 0.319900E+11 0.00 0.341660E+10 0.00 0.619570E+10 0.00 0.00
September 0.290818E+11 0.00 0.107312E+10 0.00 0.908959E+10 0.00 0.00
October 0.303281E+11 0.00 0.579566E+09 0.00 0.131228E+11 0.00 0.00
November 0.299127E+11 0.00 0.346790E+10 0.00 0.132750E+11 0.00 0.00
December 0.294972E+11 0.00 0.669069E+10 0.00 0.131569E+11 0.00 0.00
               
Annual Sum or Average 0.361030E+12 0.00 0.523034E+11 0.00 0.137683E+12 0.00 0.00
Minimum of Months 0.274200E+11 0.00 0.579566E+09 0.00 0.587761E+10 0.00 0.00
Maximum of Months 0.319900E+11 0.00 0.120018E+11 0.00 0.145973E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 53121.69 02-JAN-16:49 3982.00 01-JAN-06:10 76582.98 02-JAN-10:09 1830.66 25-JAN-10:09 29895.35 18-JAN-14:30 323.15 03-JAN-08:09 0.00 01-JAN-00:10
February 53121.69 01-FEB-17:19 3982.00 01-FEB-06:10 76582.98 01-FEB-10:09 1828.62 28-FEB-10:39 28351.63 21-FEB-14:50 213.43 27-FEB-08:09 0.00 01-FEB-00:10
March 53121.69 01-MAR-17:30 3982.00 01-MAR-06:10 76582.98 01-MAR-10:09 1828.70 28-MAR-09:09 28730.52 23-MAR-13:00 320.91 30-MAR-07:10 0.00 01-MAR-00:10
April 53121.69 03-APR-17:30 3982.00 01-APR-05:10 76582.98 03-APR-09:09 1825.72 14-APR-09:39 33377.59 26-APR-13:39 121.92 03-APR-07:10 0.00 01-APR-00:10
May 53121.69 01-MAY-18:19 3982.00 01-MAY-18:30 76582.98 01-MAY-09:09 1827.42 09-MAY-09:09 29547.26 04-MAY-12:30 116.99 15-MAY-07:10 0.00 01-MAY-00:10
June 53121.69 01-JUN-18:30 3982.00 01-JUN-18:49 76582.98 01-JUN-09:09 1827.36 16-JUN-09:09 27546.97 05-JUN-12:00 80.54 01-JUN-07:10 0.00 01-JUN-00:10
July 29512.02 03-JUL-18:40 3982.00 01-JUL-18:00 45746.32 03-JUL-09:09 831.78 03-JUL-11:30 22217.74 31-JUL-11:00 210.73 14-JUL-07:10 0.00 01-JUL-00:10
August 29512.02 01-AUG-18:30 3982.00 01-AUG-18:49 45746.32 01-AUG-09:09 831.79 23-AUG-11:39 22307.41 14-AUG-11:09 202.66 24-AUG-07:10 0.00 01-AUG-00:10
September 53121.69 05-SEP-17:30 3982.00 01-SEP-05:10 76582.98 05-SEP-09:09 1828.84 18-SEP-09:09 38031.28 29-SEP-14:30 200.88 01-SEP-07:10 0.00 01-SEP-00:10
October 53121.69 02-OCT-06:10 3982.00 01-OCT-05:10 76582.98 02-OCT-09:09 1827.96 23-OCT-11:39 38044.32 03-OCT-13:00 83.32 30-OCT-07:10 0.00 01-OCT-00:10
November 53121.69 01-NOV-06:10 3982.00 01-NOV-05:10 76582.98 01-NOV-09:09 1826.92 27-NOV-10:30 29416.81 28-NOV-14:39 144.63 24-NOV-08:09 0.00 01-NOV-00:10
December 53121.69 01-DEC-16:19 3982.00 01-DEC-06:10 76582.98 01-DEC-10:09 1831.05 06-DEC-12:00 29985.16 05-DEC-15:30 242.77 13-DEC-08:09 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 29512.02   3982.00   45746.32   831.78   22217.74   80.54   0.00  
Maximum of Months 53121.69   3982.00   76582.98   1831.05   38044.32   323.15   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 73370.97 18-JAN-12:00 0.00 0.00 0.00 4823.73 19-JAN-13:50 0.00
February 68428.94 01-FEB-11:00 0.00 0.00 0.00 4823.73 03-FEB-13:30 0.00
March 60560.71 23-MAR-13:00 0.00 0.00 0.00 4823.74 07-MAR-13:09 0.00
April 80044.44 26-APR-12:00 0.00 0.00 0.00 4823.74 04-APR-12:50 0.00
May 67714.69 04-MAY-11:00 0.00 0.00 0.00 4823.69 08-MAY-12:30 0.00
June 72265.25 26-JUN-11:00 0.00 0.00 0.00 4823.73 15-JUN-12:39 0.00
July 73845.81 31-JUL-14:09 0.00 0.00 0.00 1635.57 05-JUL-18:00 0.00
August 73292.86 14-AUG-10:00 0.00 0.00 0.00 1635.53 23-AUG-18:49 0.00
September 148006.56 29-SEP-12:00 0.00 0.00 0.00 4823.72 18-SEP-12:50 0.00
October 159362.69 16-OCT-10:00 0.00 0.00 0.00 4823.74 24-OCT-12:09 0.00
November 70530.46 28-NOV-13:00 0.00 0.00 0.00 4823.72 15-NOV-13:50 0.00
December 77297.64 19-DEC-12:00 0.00 0.00 0.00 4823.66 20-DEC-13:09 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 60560.71   0.00 0.00 0.00 1635.53   0.00
Maximum of Months 159362.69   0.00 0.00 0.00 4823.74   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 221483.01 18-JAN-12:00 34308.26 76582.98 0.00 1825.36 28733.38 13.47 0.00 73370.97 0.00
February 212719.62 01-FEB-11:00 33338.34 76582.98 0.00 1824.82 26265.84 13.47 0.00 68428.94 0.00
March 201780.50 23-MAR-13:00 32877.46 72583.64 0.00 1657.31 28730.52 13.48 0.00 60560.71 0.00
April 225012.38 26-APR-12:00 32137.27 72583.64 0.00 1656.95 32106.94 13.47 0.00 80044.44 0.00
May 212338.64 03-MAY-11:00 32999.66 76582.98 0.00 1824.49 28453.22 13.47 0.00 65795.99 0.00
June 209885.52 26-JUN-10:50 32253.52 76582.98 0.00 1824.49 24840.43 13.52 0.00 70542.45 0.00
July 162458.57 31-JUL-11:00 17610.17 45746.32 0.00 831.51 22217.74 13.52 0.00 73475.90 0.00
August 163654.80 14-AUG-10:50 18067.94 45746.32 0.00 831.63 22196.04 13.53 0.00 72975.67 0.00
September 298218.90 29-SEP-12:00 32137.27 72583.64 0.00 1656.95 37025.31 13.47 0.00 148006.56 0.00
October 313823.37 16-OCT-10:00 33662.05 76582.98 0.00 1825.22 36086.58 13.47 0.00 159362.69 0.00
November 214120.09 28-NOV-13:00 33847.38 72583.64 0.00 1657.77 28905.28 13.47 0.00 70530.46 0.00
December 224935.49 19-DEC-12:00 34308.26 76582.98 0.00 1825.55 28209.50 13.47 0.00 77297.64 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 162458.57   17610.17 45746.32 0.00 831.51 22196.04 13.47 0.00 60560.71 0.00
Maximum of Months 313823.37   34308.26 76582.98 0.00 1825.55 37025.31 13.53 0.00 159362.69 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 48084.96 02-JAN-10:09 0.00 143507.26 03-JAN-08:09 0.00 25214.27 31-JAN-13:50 0.00
February 48084.96 01-FEB-10:09 0.00 101074.45 27-FEB-08:09 0.00 25214.17 01-FEB-13:30 0.00
March 48084.96 01-MAR-10:09 0.00 140552.69 30-MAR-07:10 0.00 24961.25 02-MAR-13:50 0.00
April 48084.96 03-APR-09:09 0.00 44973.00 03-APR-07:10 0.00 24071.98 03-APR-12:30 0.00
May 48084.96 01-MAY-09:09 0.00 44589.43 15-MAY-07:10 0.00 22904.28 02-MAY-12:39 0.00
June 48084.96 01-JUN-09:09 0.00 16818.89 01-JUN-07:10 0.00 21578.09 02-JUN-12:50 0.00
July 48084.96 03-JUL-09:09 0.00 75541.85 14-JUL-07:10 0.00 15022.70 12-JUL-18:19 0.00
August 48084.96 01-AUG-09:09 0.00 72328.98 24-AUG-07:10 0.00 15020.47 08-AUG-18:19 0.00
September 48084.96 01-SEP-09:09 0.00 70835.25 01-SEP-07:10 0.00 21309.84 29-SEP-12:00 0.00
October 48084.96 02-OCT-09:09 0.00 21960.40 30-OCT-07:10 0.00 22620.27 30-OCT-12:39 0.00
November 48084.96 01-NOV-09:09 0.00 52502.03 24-NOV-08:09 0.00 23900.04 30-NOV-13:00 0.00
December 48084.96 01-DEC-10:09 0.00 105165.24 13-DEC-08:09 0.00 24624.14 22-DEC-13:00 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 48084.96   0.00 16818.89   0.00 15020.47   0.00
Maximum of Months 48084.96   0.00 143507.26   0.00 25214.27   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.33 27.27 0.00 27.27
                 
Annual Sum or Average 0.00   0.00   0.33 27.27 0.00 27.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 27.27 0.00 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 27.27 0.00 27.27
                 
Annual Sum or Average 0.00   0.00   0.17 27.27 0.00 27.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 27.27 0.00 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 37.00 17.11 19.17 17.83 0.00 17.83 0.00 17.83
February 37.00 17.76 20.67 18.27 0.00 18.27 0.00 18.27
March 53.83 17.33 33.17 17.92 0.00 17.92 0.00 17.92
April 23.17 17.71 6.67 18.15 0.00 18.15 0.00 18.15
May 22.67 18.09 6.17 18.45 0.00 18.45 0.00 18.45
June 15.00 18.79 2.17 18.96 0.00 18.96 0.00 18.96
July 3.83 19.03 0.00 19.03 2.83 21.52 2.83 22.53
August 4.00 19.01 0.17 19.06 2.00 21.01 2.00 22.01
September 8.67 18.59 0.17 18.62 10.00 22.80 8.67 23.91
October 8.67 17.48 0.33 17.58 20.50 23.42 18.33 24.34
November 28.17 18.01 11.83 18.53 0.00 18.53 0.00 18.53
December 30.00 16.99 15.33 17.64 0.00 17.64 0.00 17.64
                 
Annual Sum or Average 272.00 17.66 115.83 18.12 35.33 18.78 31.83 19.27
Minimum of Months 3.83 16.99 0.00 17.58 0.00 17.64 0.00 17.64
Maximum of Months 53.83 19.03 33.17 19.06 20.50 23.42 18.33 24.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 27.26 0.00 27.26
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 27.26 0.00 27.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 27.26 0.00 27.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.67 27.34 0.00 27.34
October 0.00 0.00 0.00 0.00 2.00 27.36 0.00 27.36
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.67 27.35 0.00 27.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 27.36 0.00 27.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 24.58 0.00 24.58
April 0.00 0.00 0.00 0.00 1.00 25.52 0.00 25.52
May 0.00 0.00 0.00 0.00 1.00 24.64 0.00 24.64
June 0.00 0.00 0.00 0.00 1.17 24.69 0.00 24.69
July 0.00 0.00 0.00 0.00 1.33 25.08 0.00 25.08
August 0.00 0.00 0.00 0.00 0.83 24.75 0.00 24.75
September 0.00 0.00 0.00 0.00 0.83 25.20 0.00 25.20
October 0.00 0.00 0.00 0.00 0.67 24.68 0.00 24.68
November 0.00 0.00 0.00 0.00 0.33 24.59 0.00 24.59
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.50 24.92 0.00 24.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 25.52 0.00 25.52



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 97.33 27.59 0.00 27.59
February 0.00 0.00 0.00 0.00 96.00 27.62 0.00 27.62
March 0.00 0.00 0.00 0.00 97.00 27.66 0.00 27.66
April 0.00 0.00 0.00 0.00 107.17 27.78 0.50 27.77
May 0.00 0.00 0.00 0.00 105.33 27.83 0.00 27.83
June 0.00 0.00 0.00 0.00 99.33 27.88 0.00 27.88
July 0.00 0.00 0.00 0.00 112.67 27.93 0.00 27.93
August 0.00 0.00 0.00 0.00 101.67 27.90 0.17 27.89
September 0.00 0.00 0.00 0.00 109.33 27.79 3.50 27.70
October 0.00 0.00 0.00 0.00 113.33 27.72 5.00 27.60
November 0.00 0.00 0.00 0.00 100.50 27.67 0.00 27.67
December 0.00 0.00 0.00 0.00 107.33 27.59 0.00 27.59
                 
Annual Sum or Average 0.00   0.00   1247.00 27.75 9.17 27.73
Minimum of Months 0.00 0.00 0.00 0.00 96.00 27.59 0.00 27.59
Maximum of Months 0.00 0.00 0.00 0.00 113.33 27.93 5.00 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.57 0.00 24.57
July 0.00 0.00 0.00 0.00 0.50 25.53 0.00 25.53
August 0.00 0.00 0.00 0.00 0.17 24.59 0.00 24.59
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 2.67 24.86 2.33 24.87
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.50 24.93 2.33 24.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 25.53 2.33 25.53



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 190.33 21.92 44.00 22.29 0.83 22.29
February 194.67 21.81 26.50 22.06 0.00 22.06
March 250.67 21.66 30.83 21.87 2.00 21.87
April 158.83 22.04 67.33 22.54 0.00 22.54
May 207.83 22.02 37.17 22.28 0.00 22.28
June 219.00 21.96 25.50 22.11 0.00 22.11
July 243.17 21.55 6.17 21.58 0.00 21.58
August 257.17 21.60 8.83 21.64 0.00 21.64
September 125.00 22.06 103.00 22.78 0.00 22.78
October 102.17 22.33 127.00 23.17 0.00 23.17
November 171.33 22.08 56.67 22.53 0.00 22.53
December 178.83 22.00 28.00 22.26 0.00 22.26
             
Annual Sum or Average 2299.00 21.87 561.00 22.24 2.83 22.24
Minimum of Months 102.17 21.55 6.17 21.58 0.00 21.58
Maximum of Months 257.17 22.33 127.00 23.17 2.00 23.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 136.83 22.36 82.33 22.97 0.00 22.97
February 155.33 22.24 55.83 22.69 0.00 22.69
March 219.50 22.11 48.17 22.43 0.17 22.43
April 134.00 22.31 90.17 22.96 0.00 22.96
May 179.67 22.29 62.33 22.71 0.00 22.71
June 212.33 22.15 35.00 22.39 0.00 22.39
July 255.83 21.45 0.00 21.45 0.00 21.45
August 290.50 21.63 0.00 21.63 0.00 21.63
September 97.33 22.25 125.00 23.10 0.00 23.10
October 59.50 22.69 161.00 23.58 0.00 23.58
November 116.17 22.49 94.00 23.15 0.00 23.15
December 125.17 22.44 61.33 22.95 0.00 22.95
             
Annual Sum or Average 1982.17 22.08 815.17 22.61 0.17 22.61
Minimum of Months 59.50 21.45 0.00 21.45 0.00 21.45
Maximum of Months 290.50 22.69 161.00 23.58 0.17 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 270.67 22.19 0.83 22.19 0.83 22.19
February 247.00 22.18 0.00 22.18 0.00 22.18
March 291.00 22.01 0.17 22.01 0.17 22.01
April 212.00 22.73 7.17 22.77 0.00 22.77
May 223.83 22.82 8.33 22.86 0.00 22.86
June 211.17 22.90 18.33 22.98 0.00 22.98
July 258.67 22.15 0.00 22.15 0.00 22.15
August 299.00 22.06 0.00 22.06 0.00 22.06
September 157.50 22.76 39.17 22.98 0.00 22.98
October 125.33 23.14 75.67 23.43 0.00 23.43
November 266.67 22.66 0.00 22.66 0.00 22.66
December 258.67 22.37 0.00 22.37 0.00 22.37
             
Annual Sum or Average 2821.50 22.43 149.67 22.50 1.00 22.50
Minimum of Months 125.33 22.01 0.00 22.01 0.00 22.01
Maximum of Months 299.00 23.14 75.67 23.43 0.83 23.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 272.17 21.52 24.00 21.48 24.00 21.44
February 247.00 21.53 5.50 21.52 5.50 21.51
March 295.33 21.51 4.67 21.51 4.17 21.50
April 220.83 22.07 16.00 22.17 0.00 22.17
May 223.17 22.20 21.83 22.34 0.00 22.34
June 205.17 22.19 28.50 22.35 0.00 22.35
July 247.33 21.60 1.00 21.60 0.00 21.60
August 295.00 21.43 0.00 21.43 0.00 21.43
September 200.00 21.92 34.67 22.16 0.00 22.16
October 183.33 22.26 50.67 22.55 0.00 22.55
November 271.00 21.77 6.67 21.76 6.67 21.74
December 260.00 21.57 14.83 21.54 14.83 21.52
             
Annual Sum or Average 2920.33 21.76 208.33 21.84 55.17 21.82
Minimum of Months 183.33 21.43 0.00 21.43 0.00 21.43
Maximum of Months 295.33 22.26 50.67 22.55 24.00 22.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 255.50 22.13 2.50 22.12 2.50 22.11
February 244.67 22.23 0.17 22.23 0.17 22.23
March 282.83 22.16 8.83 22.21 0.17 22.21
April 175.33 22.47 40.33 22.74 0.00 22.74
May 159.00 22.55 69.00 22.98 0.00 22.98
June 169.00 22.52 65.67 22.90 0.00 22.90
July 260.00 21.65 0.00 21.65 0.00 21.65
August 299.00 21.43 0.00 21.43 0.00 21.43
September 190.83 22.30 60.83 22.69 9.67 22.74
October 128.33 22.75 91.83 23.25 2.83 23.26
November 261.83 22.49 3.50 22.51 0.17 22.51
December 256.33 22.28 1.33 22.28 1.33 22.27
             
Annual Sum or Average 2682.67 22.18 344.00 22.37 16.83 22.38
Minimum of Months 128.33 21.43 0.00 21.43 0.00 21.43
Maximum of Months 299.00 22.75 91.83 23.25 9.67 23.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 193.17 21.92 42.00 22.26 1.50 22.25
February 196.00 21.81 24.67 22.04 0.00 22.04
March 252.50 21.66 29.00 21.86 2.00 21.85
April 161.67 22.05 64.50 22.53 0.00 22.53
May 212.50 22.03 35.33 22.27 0.00 22.27
June 222.00 21.97 23.83 22.11 0.00 22.11
July 245.17 21.52 5.67 21.56 0.00 21.56
August 263.00 21.58 6.50 21.61 0.00 21.61
September 126.00 22.07 100.67 22.76 0.00 22.76
October 100.83 22.34 125.83 23.18 0.00 23.18
November 174.33 22.09 54.33 22.52 0.00 22.52
December 182.00 22.00 24.50 22.23 0.00 22.23
             
Annual Sum or Average 2329.17 21.87 536.83 22.22 3.50 22.22
Minimum of Months 100.83 21.52 5.67 21.56 0.00 21.56
Maximum of Months 263.00 22.34 125.83 23.18 2.00 23.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 144.50 22.37 78.00 22.93 0.00 22.93
February 157.00 22.26 52.83 22.68 0.00 22.68
March 220.17 22.13 44.17 22.43 0.00 22.43
April 133.17 22.35 89.17 22.98 0.00 22.98
May 178.00 22.34 63.50 22.75 0.00 22.75
June 208.50 22.20 36.67 22.44 0.00 22.44
July 256.33 21.44 0.00 21.44 0.00 21.44
August 292.50 21.61 0.00 21.61 0.00 21.61
September 97.50 22.27 123.00 23.09 0.00 23.09
October 59.17 22.72 160.00 23.59 0.00 23.59
November 121.33 22.51 90.00 23.13 0.00 23.13
December 133.00 22.45 52.00 22.88 0.00 22.88
             
Annual Sum or Average 2001.17 22.10 789.33 22.61 0.00 22.61
Minimum of Months 59.17 21.44 0.00 21.44 0.00 21.44
Maximum of Months 292.50 22.72 160.00 23.59 0.00 23.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 271.50 22.16 1.33 22.15 1.33 22.15
February 247.00 22.17 0.00 22.17 0.00 22.17
March 291.50 22.01 0.17 22.01 0.17 22.01
April 212.00 22.73 6.67 22.77 0.00 22.77
May 223.33 22.83 9.50 22.88 0.00 22.88
June 204.00 22.91 21.17 22.99 0.00 22.99
July 256.50 22.14 0.00 22.14 0.00 22.14
August 299.00 22.04 0.00 22.04 0.00 22.04
September 158.17 22.75 38.50 22.98 0.00 22.98
October 125.33 23.14 75.83 23.44 0.00 23.44
November 268.33 22.65 0.00 22.65 0.00 22.65
December 259.33 22.33 0.00 22.33 0.00 22.33
             
Annual Sum or Average 2816.00 22.42 153.17 22.49 1.50 22.49
Minimum of Months 125.33 22.01 0.00 22.01 0.00 22.01
Maximum of Months 299.00 23.14 75.83 23.44 1.33 23.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 272.17 21.51 24.50 21.47 24.50 21.44
February 247.00 21.53 5.50 21.52 5.50 21.51
March 295.33 21.51 4.67 21.51 4.17 21.50
April 220.17 22.06 16.00 22.17 0.00 22.17
May 221.67 22.20 22.50 22.34 0.00 22.34
June 202.17 22.19 32.67 22.37 0.00 22.37
July 246.00 21.60 2.33 21.61 0.00 21.61
August 295.00 21.43 0.00 21.43 0.00 21.43
September 198.67 21.91 35.33 22.17 0.00 22.17
October 182.33 22.25 50.83 22.55 0.00 22.55
November 271.00 21.77 6.17 21.76 6.17 21.74
December 260.00 21.57 14.83 21.55 14.83 21.52
             
Annual Sum or Average 2911.50 21.76 215.33 21.84 55.17 21.83
Minimum of Months 182.33 21.43 0.00 21.43 0.00 21.43
Maximum of Months 295.33 22.25 50.83 22.55 24.50 22.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 256.33 22.12 2.83 22.11 2.83 22.10
February 244.83 22.22 0.33 22.22 0.33 22.22
March 282.83 22.16 8.83 22.21 0.17 22.21
April 175.50 22.46 40.33 22.74 0.00 22.74
May 159.50 22.55 69.50 22.98 0.00 22.98
June 166.17 22.52 67.50 22.91 0.00 22.91
July 260.00 21.65 0.00 21.65 0.00 21.65
August 299.00 21.42 0.00 21.42 0.00 21.42
September 191.00 22.30 60.50 22.69 9.67 22.73
October 127.17 22.74 92.17 23.24 2.50 23.25
November 262.50 22.49 3.33 22.50 0.17 22.50
December 256.50 22.27 1.33 22.27 1.33 22.26
             
Annual Sum or Average 2681.33 22.17 346.67 22.37 17.00 22.37
Minimum of Months 127.17 21.42 0.00 21.42 0.00 21.42
Maximum of Months 299.00 22.74 92.17 23.24 9.67 23.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 186.50 21.98 46.67 22.36 0.83 22.35
February 188.83 21.86 28.17 22.12 0.00 22.12
March 247.00 21.72 33.00 21.95 1.67 21.94
April 151.17 22.12 74.67 22.67 0.00 22.67
May 197.83 22.11 47.83 22.43 0.00 22.43
June 205.00 22.07 32.83 22.26 0.00 22.26
July 238.50 21.60 7.33 21.64 0.00 21.64
August 250.67 21.65 12.83 21.71 0.00 21.71
September 115.67 22.15 111.17 22.90 0.00 22.90
October 94.33 22.41 134.00 23.26 0.00 23.26
November 166.50 22.15 61.83 22.63 0.00 22.63
December 176.00 22.07 31.00 22.35 0.00 22.35
             
Annual Sum or Average 2218.00 21.94 621.33 22.34 2.50 22.34
Minimum of Months 94.33 21.60 7.33 21.64 0.00 21.64
Maximum of Months 250.67 22.41 134.00 23.26 1.67 23.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 128.17 22.45 87.67 23.07 0.00 23.07
February 137.50 22.34 65.33 22.87 0.00 22.87
March 197.83 22.26 61.83 22.66 0.00 22.66
April 110.17 22.45 109.67 23.20 0.00 23.20
May 148.17 22.47 90.00 23.03 0.00 23.03
June 163.33 22.35 67.00 22.77 0.00 22.77
July 253.00 21.61 2.33 21.63 0.00 21.63
August 276.33 21.77 2.67 21.78 0.00 21.78
September 78.17 22.42 148.83 23.36 1.83 23.36
October 47.83 22.81 173.17 23.69 0.00 23.69
November 105.17 22.58 104.67 23.27 0.00 23.27
December 118.83 22.54 65.33 23.06 0.00 23.06
             
Annual Sum or Average 1764.50 22.21 978.50 22.82 1.83 22.82
Minimum of Months 47.83 21.61 2.33 21.63 0.00 21.63
Maximum of Months 276.33 22.81 173.17 23.69 1.83 23.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 265.67 22.29 0.50 22.29 0.50 22.28
February 246.33 22.35 0.00 22.35 0.00 22.35
March 285.50 22.18 0.83 22.19 0.00 22.19
April 187.00 22.89 23.50 23.00 0.00 23.00
May 189.33 22.98 27.17 23.11 0.00 23.11
June 145.17 23.06 45.83 23.25 0.00 23.25
July 247.50 22.30 0.00 22.30 0.00 22.30
August 296.33 22.22 0.00 22.22 0.00 22.22
September 118.33 22.86 63.00 23.22 0.00 23.22
October 110.83 23.23 84.17 23.53 0.00 23.53
November 258.00 22.78 0.00 22.78 0.00 22.78
December 257.83 22.49 0.00 22.49 0.00 22.49
             
Annual Sum or Average 2607.83 22.55 245.00 22.66 0.50 22.66
Minimum of Months 110.83 22.18 0.00 22.19 0.00 22.19
Maximum of Months 296.33 23.23 84.17 23.53 0.50 23.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 272.17 21.55 23.83 21.51 23.83 21.47
February 246.50 21.58 5.17 21.57 5.17 21.56
March 293.67 21.57 5.33 21.57 3.83 21.56
April 210.17 22.12 22.33 22.27 0.00 22.27
May 204.17 22.26 32.83 22.47 0.00 22.47
June 184.50 22.26 49.17 22.52 0.00 22.52
July 235.50 21.68 5.50 21.71 0.00 21.71
August 292.00 21.52 0.67 21.52 0.00 21.52
September 188.00 21.96 39.67 22.26 0.00 22.26
October 180.17 22.29 53.67 22.61 0.00 22.61
November 270.50 21.81 5.83 21.80 5.83 21.78
December 260.00 21.59 14.33 21.57 14.33 21.54
             
Annual Sum or Average 2837.33 21.81 258.33 21.91 53.00 21.90
Minimum of Months 180.17 21.52 0.67 21.51 0.00 21.47
Maximum of Months 293.67 22.29 53.67 22.61 23.83 22.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 255.33 22.13 3.33 22.11 3.33 22.10
February 244.67 22.25 0.50 22.24 0.50 22.24
March 281.67 22.20 9.17 22.25 0.17 22.24
April 160.50 22.46 48.83 22.80 0.00 22.80
May 145.33 22.59 81.83 23.08 0.00 23.08
June 143.00 22.59 80.17 23.04 0.00 23.04
July 260.00 21.77 0.00 21.77 0.00 21.77
August 299.00 21.51 0.00 21.51 0.00 21.51
September 183.83 22.34 63.83 22.75 8.00 22.78
October 128.50 22.75 93.17 23.25 1.83 23.26
November 260.17 22.49 4.00 22.51 0.17 22.51
December 256.50 22.26 1.50 22.25 1.50 22.25
             
Annual Sum or Average 2618.50 22.21 386.33 22.42 15.50 22.42
Minimum of Months 128.50 21.51 0.00 21.51 0.00 21.51
Maximum of Months 299.00 22.75 93.17 23.25 8.00 23.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 235.83 22.56 12.00 22.61 0.50 22.61
February 228.17 22.74 0.00 22.74 0.00 22.74
March 255.50 22.68 19.50 22.76 0.00 22.76
April 94.33 22.95 89.17 23.41 0.00 23.41
May 67.33 23.08 125.67 23.62 0.00 23.62
June 13.83 23.00 231.50 23.86 1.67 23.86
July 248.67 22.24 0.00 22.24 0.00 22.24
August 295.67 22.07 0.00 22.07 0.00 22.07
September 40.33 22.68 181.17 23.64 7.33 23.65
October 81.00 23.23 132.33 23.63 10.17 23.64
November 209.50 22.97 6.00 22.99 0.00 22.99
December 250.33 22.80 3.67 22.82 0.17 22.82
             
Annual Sum or Average 2020.50 22.62 801.00 22.98 19.83 22.99
Minimum of Months 13.83 22.07 0.00 22.07 0.00 22.07
Maximum of Months 295.67 23.23 231.50 23.86 10.17 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 174.67 23.25 8.50 23.28 0.00 23.28
February 141.83 23.69 1.00 23.69 0.00 23.69
March 133.33 23.67 33.67 23.73 0.00 23.73
April 4.50 23.85 119.50 23.99 0.00 23.99
May 2.17 23.92 142.67 24.00 0.00 24.00
June 0.00 0.00 233.00 24.00 0.00 24.00
July 0.00 0.00 237.67 24.00 0.00 24.00
August 0.17 23.52 270.00 24.00 0.00 24.00
September 1.33 23.57 219.17 24.00 0.00 24.00
October 30.00 23.99 131.67 24.00 0.00 24.00
November 114.00 23.87 13.00 23.89 0.00 23.89
December 208.83 23.74 2.83 23.74 0.00 23.74
             
Annual Sum or Average 810.83 23.64 1412.67 23.87 0.00 23.87
Minimum of Months 0.00 0.00 1.00 23.28 0.00 23.28
Maximum of Months 208.83 23.99 270.00 24.00 0.00 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 233.00 21.74 23.50 21.76 9.67 21.67
February 228.00 21.46 16.50 21.44 8.67 21.34
March 280.67 21.16 34.00 21.06 23.33 20.90
April 208.50 21.96 26.17 22.14 2.33 22.11
May 250.33 21.93 9.00 21.98 1.17 21.97
June 214.00 22.29 35.17 22.50 0.00 22.50
July 171.67 22.63 84.50 22.99 29.67 23.03
August 158.00 22.83 153.17 23.25 54.67 23.29
September 102.83 22.51 127.83 23.31 13.83 23.35
October 124.33 23.16 138.00 23.68 41.50 23.73
November 223.00 22.03 23.67 22.17 2.17 22.15
December 211.17 21.90 11.00 21.83 7.33 21.73
             
Annual Sum or Average 2405.50 22.02 682.50 22.34 194.33 22.34
Minimum of Months 102.83 21.16 9.00 21.06 0.00 20.90
Maximum of Months 280.67 23.16 153.17 23.68 54.67 23.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.83 24.23 183.33 25.83 0.00 25.83
February 0.00 0.00 240.67 26.09 0.00 26.09
March 0.17 24.44 286.50 26.14 0.00 26.14
April 0.00 0.00 260.00 26.56 0.00 26.56
May 0.00 0.00 286.00 26.61 0.00 26.61
June 15.00 26.70 286.00 26.67 15.00 26.67
July 0.00 0.00 260.00 26.43 0.00 26.43
August 0.00 0.00 299.00 26.38 0.00 26.38
September 0.00 0.00 260.00 26.63 0.00 26.63
October 0.00 0.00 273.00 26.62 0.00 26.62
November 0.00 0.00 264.83 26.33 0.00 26.33
December 0.67 24.66 223.83 26.12 0.00 26.12
             
Annual Sum or Average 47.67 25.01 3123.17 26.38 15.00 26.39
Minimum of Months 0.00 0.00 183.33 25.83 0.00 25.83
Maximum of Months 31.83 26.70 299.00 26.67 15.00 26.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 161.83 23.03 64.33 23.58 0.17 23.58
February 109.67 23.58 69.67 24.12 0.00 24.12
March 99.67 23.58 134.00 24.46 0.67 24.47
April 11.17 26.35 251.83 25.85 9.83 25.88
May 7.33 26.64 282.50 26.01 7.17 26.03
June 50.50 26.70 286.00 26.31 50.50 26.36
July 8.50 26.68 260.00 25.77 8.50 25.80
August 1.00 26.69 299.00 25.60 1.00 25.60
September 35.17 26.55 260.00 26.10 35.17 26.15
October 41.67 26.43 260.00 26.03 39.67 26.09
November 63.50 23.91 126.00 24.70 0.00 24.70
December 160.50 23.62 28.50 23.82 0.00 23.82
             
Annual Sum or Average 750.50 24.12 2321.83 25.36 152.67 25.42
Minimum of Months 1.00 23.03 28.50 23.58 0.00 23.58
Maximum of Months 161.83 26.70 299.00 26.31 50.50 26.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 84.83 23.68 41.33 23.78 0.00 23.78
February 72.00 23.64 31.67 23.75 0.00 23.75
March 94.50 23.55 53.00 23.71 0.00 23.71
April 3.50 23.79 128.67 23.99 0.00 23.99
May 8.50 23.81 126.67 23.99 0.00 23.99
June 0.17 23.84 196.33 24.00 0.00 24.00
July 0.17 23.50 208.17 24.00 0.00 24.00
August 0.00 0.00 245.33 24.00 0.00 24.00
September 0.33 23.54 203.83 24.00 0.00 24.00
October 3.83 23.97 151.67 24.01 0.00 24.01
November 43.83 23.97 64.17 23.99 0.00 23.99
December 84.00 23.87 11.00 23.88 0.00 23.88
             
Annual Sum or Average 395.67 23.72 1461.83 23.94 0.00 23.94
Minimum of Months 0.00 0.00 11.00 23.71 0.00 23.71
Maximum of Months 94.50 23.97 245.33 24.01 0.00 24.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 78.50 23.40 113.00 23.75 1.83 23.75
February 35.67 23.27 124.00 23.83 3.83 23.83
March 55.50 22.84 168.33 23.71 0.00 23.71
April 0.00 0.00 253.33 24.00 0.00 24.00
May 0.00 0.00 272.33 24.00 0.00 24.00
June 0.83 24.00 286.00 24.00 0.83 24.00
July 19.33 24.00 260.00 24.00 19.33 24.00
August 30.83 24.00 299.00 24.00 30.83 24.00
September 11.17 24.00 259.00 24.00 11.17 24.00
October 9.50 24.00 214.83 24.00 9.50 24.00
November 25.83 23.93 152.33 23.99 0.33 23.99
December 71.33 23.67 51.67 23.81 0.00 23.81
             
Annual Sum or Average 338.50 23.52 2453.83 23.94 77.67 23.94
Minimum of Months 0.00 0.00 51.67 23.71 0.00 23.71
Maximum of Months 78.50 24.00 299.00 24.00 30.83 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 263.00 24.00 0.00 24.00
February 0.67 24.00 244.67 24.00 0.67 24.00
March 0.00 0.00 296.33 24.00 0.00 24.00
April 1.33 24.47 260.00 24.01 1.33 24.01
May 0.00 0.00 286.00 24.00 0.00 24.00
June 1.50 24.06 286.00 24.00 1.50 24.00
July 11.67 24.03 260.00 24.01 11.67 24.01
August 24.50 24.02 299.00 24.01 24.50 24.01
September 10.00 24.35 260.00 24.03 10.00 24.04
October 11.83 24.50 272.33 24.04 11.83 24.06
November 0.00 0.00 259.00 24.00 0.00 24.00
December 0.00 0.00 233.67 24.00 0.00 24.00
             
Annual Sum or Average 61.50 24.18 3220.00 24.01 61.50 24.01
Minimum of Months 0.00 0.00 233.67 24.00 0.00 24.00
Maximum of Months 24.50 24.50 299.00 24.04 24.50 24.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 106.50 22.26 88.83 23.04 0.00 23.04
February 101.17 22.19 80.50 22.99 6.67 23.02
March 108.67 21.91 118.67 22.98 2.50 23.00
April 28.50 22.26 176.33 23.73 0.83 23.73
May 19.17 22.62 206.17 23.85 3.00 23.85
June 20.17 23.94 237.50 23.98 19.00 23.98
July 29.50 23.90 196.50 23.98 28.00 23.98
August 49.33 23.93 226.00 23.97 47.83 23.97
September 48.00 23.91 211.83 23.97 46.00 23.97
October 50.50 23.96 200.17 23.99 47.67 23.99
November 82.33 22.39 100.00 23.25 1.17 23.25
December 101.67 22.33 56.50 22.92 2.33 22.94
             
Annual Sum or Average 745.50 22.68 1899.00 23.61 205.00 23.64
Minimum of Months 19.17 21.91 56.50 22.92 0.00 22.94
Maximum of Months 108.67 23.96 237.50 23.99 47.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 151.50 23.24 30.33 23.37 0.00 23.37
February 125.67 23.41 25.00 23.51 0.00 23.51
March 114.50 23.35 75.83 23.61 0.00 23.61
April 5.83 23.58 193.33 23.99 0.00 23.99
May 2.50 23.54 215.67 23.99 0.00 23.99
June 0.00 0.00 274.00 24.00 0.00 24.00
July 6.33 23.08 234.67 23.95 0.00 23.95
August 12.00 23.05 255.50 23.92 0.00 23.92
September 4.00 23.00 244.83 23.98 0.00 23.98
October 6.17 23.81 180.50 23.99 0.00 23.99
November 104.83 23.62 52.00 23.74 0.00 23.74
December 169.67 23.53 12.33 23.56 0.00 23.56
             
Annual Sum or Average 703.00 23.42 1794.00 23.83 0.00 23.83
Minimum of Months 0.00 0.00 12.33 23.37 0.00 23.37
Maximum of Months 169.67 23.81 274.00 24.00 0.00 24.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.47661 42.61029 0.21043 7.58149
February 247.00000 22.21625 45.48067 0.15381 6.96849
March 299.00000 21.97191 49.12454 0.10229 6.81415
April 260.00000 22.62440 52.36989 0.32585 8.45485
May 286.00000 22.41087 51.20673 -0.6286 15.15620
June 286.00000 22.22787 56.88364 -0.6177 14.19197
July 260.00000 21.62358 62.48166 -0.7479 17.66747
August 299.00000 21.75066 62.59870 -0.7001 16.38373
September 260.00000 22.79261 56.54950 -0.4002 10.30484
October 273.00000 23.20154 47.12597 0.47439 10.92045
November 273.00000 22.71156 41.87280 0.28425 8.14714
December 260.00000 22.57921 35.90853 0.20194 7.35257
           
Annual Sum or Average 3276.00000 22.37444 50.48309 -0.1202 10.90015
Minimum of Months 247.00000 21.62358 35.90853 -0.7479 6.81415
Maximum of Months 299.00000 23.20154 62.59870 0.47439 17.66747



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.12598 41.65796 0.36794 9.02249
February 247.00000 22.84467 44.65285 0.30252 8.10466
March 299.00000 22.55273 48.41030 0.23653 7.62259
April 260.00000 23.02253 52.00045 0.40237 9.35444
May 286.00000 22.82523 50.92239 -0.5257 12.42591
June 286.00000 22.50183 56.58456 -0.5655 12.80730
July 260.00000 21.46717 63.22383 -0.8336 20.21708
August 299.00000 21.66574 63.08351 -0.7585 17.84048
September 260.00000 23.09886 55.89493 -0.3290 8.79714
October 273.00000 23.56565 46.56228 0.55474 12.18320
November 273.00000 23.29254 41.02913 0.42046 9.61926
December 260.00000 23.20109 35.12216 0.35501 8.62465
           
Annual Sum or Average 3276.00000 22.75289 50.06738 -0.0403 11.43635
Minimum of Months 247.00000 21.46717 35.12216 -0.8336 7.62259
Maximum of Months 299.00000 23.56565 63.22383 0.55474 20.21708



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.20441 40.95922 0.06050 5.89916
February 247.00000 22.17832 43.52252 0.07090 5.51500
March 299.00000 22.04639 46.98890 0.06085 5.73137
April 260.00000 22.90147 49.64110 0.29374 7.19055
May 286.00000 23.02133 47.57733 -0.5532 12.11723
June 286.00000 23.08499 52.96181 -0.4881 10.38347
July 260.00000 22.15580 60.06348 -0.7355 16.90339
August 299.00000 22.05514 61.00381 -0.7641 17.69445
September 260.00000 23.11544 54.37184 -0.4659 10.35607
October 273.00000 23.49854 44.42060 0.41461 9.11733
November 273.00000 22.67788 39.91523 0.17339 6.06208
December 260.00000 22.37591 34.07039 0.06069 5.50182
           
Annual Sum or Average 3276.00000 22.60727 48.08235 -0.1629 9.44556
Minimum of Months 247.00000 22.04639 34.07039 -0.7641 5.50182
Maximum of Months 299.00000 23.49854 61.00381 0.41461 17.69445



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 21.52483 44.94403 -0.0987 6.11281
February 247.00000 21.52930 47.30775 -0.0717 5.69395
March 299.00000 21.53178 50.60994 -0.0473 5.81413
April 260.00000 22.26024 53.75852 0.20587 6.70533
May 286.00000 22.47400 51.35666 -0.6340 14.83938
June 286.00000 22.47056 56.30169 -0.5587 12.50082
July 260.00000 21.65378 62.44819 -0.7559 17.79409
August 299.00000 21.44902 63.80050 -0.8318 20.23615
September 260.00000 22.25452 58.64357 -0.6291 14.84411
October 273.00000 22.65647 48.97508 0.29192 7.89302
November 273.00000 21.78281 44.23960 -0.0044 5.78411
December 260.00000 21.57323 37.94203 -0.1195 5.94068
           
Annual Sum or Average 3276.00000 21.93046 51.80933 -0.2771 10.43690
Minimum of Months 247.00000 21.44902 37.94203 -0.8318 5.69395
Maximum of Months 299.00000 22.65647 63.80050 0.29192 20.23615



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.23297 44.70399 0.05628 6.18902
February 247.00000 22.23990 47.00151 0.08177 5.86442
March 299.00000 22.24774 50.06276 0.10622 6.17068
April 260.00000 22.89729 53.29905 0.32222 7.94516
May 286.00000 23.12215 50.87341 -0.4723 10.86783
June 286.00000 22.96949 55.48962 -0.4485 9.98065
July 260.00000 21.64533 62.73837 -0.8047 19.09119
August 299.00000 21.42617 64.15250 -0.8807 21.71220
September 260.00000 22.70403 57.85587 -0.5329 12.53416
October 273.00000 23.32404 48.41660 0.42000 9.50423
November 273.00000 22.54070 43.95160 0.15275 6.35207
December 260.00000 22.30246 37.94757 0.04006 5.86413
           
Annual Sum or Average 3276.00000 22.46868 51.48928 -0.1699 10.25016
Minimum of Months 247.00000 21.42617 37.94757 -0.8807 5.86413
Maximum of Months 299.00000 23.32404 64.15250 0.42000 21.71220



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.44917 42.67862 0.20169 7.49826
February 247.00000 22.20008 45.53088 0.14879 6.90577
March 299.00000 21.95693 49.16848 0.09741 6.76072
April 260.00000 22.60934 52.42869 0.32072 8.35612
May 286.00000 22.39855 51.25723 -0.6351 15.27897
June 286.00000 22.22537 56.91338 -0.6206 14.21817
July 260.00000 21.59481 62.62494 -0.7594 18.00867
August 299.00000 21.71344 62.76531 -0.7142 16.75127
September 260.00000 22.78382 56.60820 -0.4051 10.33757
October 273.00000 23.21120 47.12864 0.47558 10.91613
November 273.00000 22.69981 41.90741 0.28010 8.07764
December 260.00000 22.55589 35.96141 0.19416 7.27351
           
Annual Sum or Average 3276.00000 22.35868 50.54679 -0.1265 10.93957
Minimum of Months 247.00000 21.59481 35.96141 -0.7594 6.76072
Maximum of Months 299.00000 23.21120 62.76531 0.47558 18.00867



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.08393 41.81556 0.35264 8.81897
February 247.00000 22.84434 44.69366 0.29998 8.02422
March 299.00000 22.56405 48.40560 0.23789 7.58149
April 260.00000 23.04331 51.97602 0.40521 9.35733
May 286.00000 22.86465 50.84151 -0.5158 12.13552
June 286.00000 22.55978 56.42968 -0.5502 12.40697
July 260.00000 21.46093 63.28866 -0.8383 20.37128
August 299.00000 21.63726 63.22192 -0.7706 18.18143
September 260.00000 23.09916 55.94074 -0.3326 8.79460
October 273.00000 23.57331 46.59677 0.55342 12.12062
November 273.00000 23.27527 41.12184 0.41227 9.46295
December 260.00000 23.16030 35.26729 0.33912 8.39794
           
Annual Sum or Average 3276.00000 22.75344 50.10417 -0.0431 11.35642
Minimum of Months 247.00000 21.46093 35.26729 -0.8383 7.58149
Maximum of Months 299.00000 23.57331 63.28866 0.55342 20.37128



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.16431 41.04213 0.05109 5.89260
February 247.00000 22.16681 43.55007 0.06861 5.49955
March 299.00000 22.04559 46.97390 0.06100 5.72919
April 260.00000 22.90029 49.64587 0.29390 7.19039
May 286.00000 23.02899 47.55505 -0.5501 12.04569
June 286.00000 23.10621 52.90971 -0.4807 10.23423
July 260.00000 22.15180 60.11182 -0.7362 16.93622
August 299.00000 22.03598 61.10044 -0.7696 17.86691
September 260.00000 23.11050 54.40586 -0.4669 10.37910
October 273.00000 23.49878 44.43529 0.41484 9.11928
November 273.00000 22.66024 39.94767 0.16953 6.02999
December 260.00000 22.33442 34.16080 0.05122 5.48331
           
Annual Sum or Average 3276.00000 22.59821 48.11032 -0.1646 9.44055
Minimum of Months 247.00000 22.03598 34.16080 -0.7696 5.48331
Maximum of Months 299.00000 23.49878 61.10044 0.41484 17.86691



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 21.51973 44.93959 -0.0999 6.12013
February 247.00000 21.52839 47.29338 -0.0715 5.69508
March 299.00000 21.53324 50.58564 -0.0461 5.81553
April 260.00000 22.25995 53.74904 0.20663 6.71456
May 286.00000 22.47864 51.33411 -0.6312 14.77701
June 286.00000 22.48422 56.26603 -0.5528 12.37511
July 260.00000 21.66024 62.45515 -0.7525 17.70479
August 299.00000 21.44764 63.82940 -0.8314 20.22145
September 260.00000 22.25811 58.64178 -0.6269 14.79402
October 273.00000 22.66089 48.96499 0.29360 7.91774
November 273.00000 21.78476 44.22016 -0.0035 5.78495
December 260.00000 21.57467 37.93588 -0.1195 5.94574
           
Annual Sum or Average 3276.00000 21.93299 51.79992 -0.2756 10.41216
Minimum of Months 247.00000 21.44764 37.93588 -0.8314 5.69508
Maximum of Months 299.00000 22.66089 63.82940 0.29360 20.22145



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.21555 44.71562 0.05241 6.18066
February 247.00000 22.22952 47.00169 0.08008 5.85648
March 299.00000 22.24173 50.04766 0.10579 6.16765
April 260.00000 22.88842 53.30882 0.32115 7.93295
May 286.00000 23.11882 50.86616 -0.4717 10.86099
June 286.00000 22.97541 55.47460 -0.4448 9.91120
July 260.00000 21.64747 62.76066 -0.8026 19.03554
August 299.00000 21.42047 64.19674 -0.8816 21.74416
September 260.00000 22.70032 57.87526 -0.5328 12.53270
October 273.00000 23.32172 48.42122 0.42018 9.51116
November 273.00000 22.53255 43.94567 0.15160 6.34068
December 260.00000 22.29121 37.95717 0.03734 5.85573
           
Annual Sum or Average 3276.00000 22.46301 51.49572 -0.1703 10.23831
Minimum of Months 247.00000 21.42047 37.95717 -0.8816 5.85573
Maximum of Months 299.00000 23.32172 64.19674 0.42018 21.74416



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.54744 42.52869 0.22324 7.69446
February 247.00000 22.29975 45.38782 0.17116 7.08058
March 299.00000 22.05361 49.00307 0.11929 6.91674
April 260.00000 22.74290 52.08977 0.34972 8.75521
May 286.00000 22.54404 50.89755 -0.5917 14.16957
June 286.00000 22.38185 56.30417 -0.5757 13.08797
July 260.00000 21.69757 61.97789 -0.7308 17.17132
August 299.00000 21.82768 62.11419 -0.6818 15.88158
September 260.00000 22.91230 56.05181 -0.3686 9.66585
October 273.00000 23.28579 46.84838 0.49005 11.14006
November 273.00000 22.79542 41.75810 0.30065 8.29293
December 260.00000 22.65333 35.86313 0.21624 7.44732
           
Annual Sum or Average 3276.00000 22.47087 50.19839 -0.0982 10.67075
Minimum of Months 247.00000 21.69757 35.86313 -0.7308 6.91674
Maximum of Months 299.00000 23.28579 62.11419 0.49005 17.17132



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.22279 41.40116 0.38725 9.26428
February 247.00000 23.02287 44.22317 0.34226 8.53507
March 299.00000 22.78742 47.85976 0.28911 8.12560
April 260.00000 23.24210 51.29745 0.45256 10.11194
May 286.00000 23.11751 50.10833 -0.4357 10.39704
June 286.00000 22.85508 55.33493 -0.4611 10.42902
July 260.00000 21.64576 62.33490 -0.7826 18.55195
August 299.00000 21.85106 62.20303 -0.7071 16.29025
September 260.00000 23.31928 55.01299 -0.2644 7.82184
October 273.00000 23.65636 46.13184 0.57491 12.55574
November 273.00000 23.39450 40.73546 0.44272 9.93346
December 260.00000 23.29694 34.92553 0.37406 8.84116
           
Annual Sum or Average 3276.00000 22.94185 49.43052 0.00894 10.93359
Minimum of Months 247.00000 21.64576 34.92553 -0.7826 7.82184
Maximum of Months 299.00000 23.65636 62.33490 0.57491 18.55195



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.32224 40.68926 0.08639 6.01945
February 247.00000 22.35172 43.11480 0.10977 5.65667
March 299.00000 22.24366 46.47682 0.10541 5.89368
April 260.00000 23.12234 49.00437 0.34316 7.82982
May 286.00000 23.25145 46.92353 -0.4816 10.46921
June 286.00000 23.35717 51.98596 -0.4045 8.76294
July 260.00000 22.34396 59.13967 -0.6798 15.21685
August 299.00000 22.23331 60.13266 -0.7113 16.04135
September 260.00000 23.32034 53.55672 -0.4030 9.10698
October 273.00000 23.59025 44.06731 0.43462 9.41770
November 273.00000 22.81919 39.60215 0.20470 6.30881
December 260.00000 22.49457 33.85301 0.08699 5.58408
           
Annual Sum or Average 3276.00000 22.78584 47.49927 -0.1157 8.91472
Minimum of Months 247.00000 22.23331 33.85301 -0.7113 5.58408
Maximum of Months 299.00000 23.59025 60.13266 0.43462 16.04135



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 21.55598 44.93365 -0.0917 6.12688
February 247.00000 21.58044 47.25798 -0.0586 5.70616
March 299.00000 21.59593 50.50128 -0.0303 5.84530
April 260.00000 22.37190 53.47718 0.23219 6.99499
May 286.00000 22.61160 51.00278 -0.5892 13.73847
June 286.00000 22.61724 55.73541 -0.5126 11.50522
July 260.00000 21.78120 61.74098 -0.7161 16.64672
August 299.00000 21.54741 63.21641 -0.8005 19.25639
September 260.00000 22.35849 58.17392 -0.5972 14.04184
October 273.00000 22.70556 48.75839 0.30177 8.01610
November 273.00000 21.82567 44.19767 0.00587 5.83589
December 260.00000 21.59405 37.96656 -0.1145 5.93609
           
Annual Sum or Average 3276.00000 22.01311 51.52582 -0.2533 10.05185
Minimum of Months 247.00000 21.54741 37.96656 -0.8005 5.70616
Maximum of Months 299.00000 22.70556 63.21641 0.30177 19.25639



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.22555 44.74947 0.05443 6.21327
February 247.00000 22.25793 47.00097 0.08721 5.91211
March 299.00000 22.28355 50.00805 0.11679 6.24924
April 260.00000 22.97035 53.08997 0.34129 8.20655
May 286.00000 23.21211 50.56076 -0.4383 10.15269
June 286.00000 23.09161 54.92839 -0.4064 9.15076
July 260.00000 21.77226 62.02560 -0.7653 17.81852
August 299.00000 21.50974 63.61623 -0.8552 20.82118
September 260.00000 22.76653 57.49298 -0.5123 12.04269
October 273.00000 23.32488 48.32397 0.41926 9.50000
November 273.00000 22.54395 43.96542 0.15377 6.38207
December 260.00000 22.27400 38.02568 0.03354 5.86102
           
Annual Sum or Average 3276.00000 22.51775 51.26047 -0.1539 9.92938
Minimum of Months 247.00000 21.50974 38.02568 -0.8552 5.86102
Maximum of Months 299.00000 23.32488 63.61623 0.41926 20.82118



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.70816 44.55482 0.18689 6.67009
February 247.00000 22.80433 46.75165 0.23296 6.54600
March 299.00000 22.81755 49.87407 0.26027 7.01637
April 260.00000 23.44986 52.96653 0.46898 9.96436
May 286.00000 23.61330 50.70928 -0.2960 7.30203
June 286.00000 23.80683 55.99323 -0.1683 5.89083
July 260.00000 22.26393 62.69812 -0.6041 12.99441
August 299.00000 22.07579 64.10379 -0.6675 14.74990
September 260.00000 23.59940 58.04837 -0.2381 7.04233
October 273.00000 23.62875 48.67703 0.50499 10.85659
November 273.00000 23.11356 43.71784 0.30050 7.36252
December 260.00000 22.83500 38.07083 0.18200 6.20298
           
Annual Sum or Average 3276.00000 23.05752 51.46368 0.00738 8.57935
Minimum of Months 247.00000 22.07579 38.07083 -0.6675 5.89083
Maximum of Months 299.00000 23.80683 64.10379 0.50499 14.74990



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 25.67888 34.17908 0.70630 16.48288
February 247.00000 26.06091 35.72387 0.80809 19.03901
March 299.00000 26.09404 38.24131 0.84023 20.30762
April 260.00000 26.55822 40.24364 0.99449 25.99497
May 286.00000 26.60709 38.68346 0.40067 8.48601
June 286.00000 26.66850 42.90783 0.47597 9.82810
July 260.00000 26.42696 46.64388 0.42271 8.91454
August 299.00000 26.38110 47.49083 0.41093 8.71940
September 260.00000 26.62609 44.42623 0.46718 9.69379
October 273.00000 26.62355 37.21485 0.99736 26.19886
November 273.00000 26.30994 33.31536 0.85316 20.66298
December 260.00000 26.01438 28.64636 0.74089 16.90596
           
Annual Sum or Average 3276.00000 26.33937 39.06230 0.67308 15.84404
Minimum of Months 247.00000 25.67888 28.64636 0.40067 8.48601
Maximum of Months 299.00000 26.66850 47.49083 0.99736 26.19886



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.70448 41.58823 0.33330 8.89233
February 247.00000 24.19359 43.05985 0.46083 10.00026
March 299.00000 24.42496 45.44998 0.53686 11.99618
April 260.00000 25.78202 46.36272 0.88155 22.02093
May 286.00000 25.97682 44.41197 0.27273 7.44879
June 286.00000 26.24635 46.58320 0.39876 8.91653
July 260.00000 25.74519 49.57666 0.28808 7.29153
August 299.00000 25.59654 50.75092 0.24653 6.84836
September 260.00000 26.04038 48.64764 0.34215 8.12621
October 273.00000 25.90262 43.06922 0.89141 22.44664
November 273.00000 24.61678 40.19107 0.54477 11.86873
December 260.00000 24.02609 35.18251 0.36543 8.44591
           
Annual Sum or Average 3276.00000 25.19705 44.64231 0.46131 11.14492
Minimum of Months 247.00000 23.70448 35.18251 0.24653 6.84836
Maximum of Months 299.00000 26.24635 50.75092 0.89141 22.44664



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 231.00000 23.87967 37.76967 0.43396 9.31087
February 209.00000 23.87305 39.93520 0.44152 9.29486
March 253.00000 23.82825 42.85498 0.44234 9.48605
April 220.00000 23.99443 46.26841 0.56504 11.78734
May 242.00000 23.99203 44.69176 -0.2271 6.21644
June 242.00000 23.99950 50.37923 -0.1532 5.64057
July 220.00000 23.98930 54.36918 -0.1170 5.40255
August 253.00000 23.99312 55.03664 -0.1067 5.35339
September 220.00000 23.99773 51.69059 -0.1155 5.42852
October 231.00000 24.00368 42.91411 0.58483 12.36571
November 231.00000 23.99416 37.15011 0.48362 10.07776
December 220.00000 23.94754 31.39183 0.41767 8.80696
           
Annual Sum or Average 2772.00000 23.95754 44.64583 0.21545 8.23060
Minimum of Months 209.00000 23.82825 31.39183 -0.2271 5.35339
Maximum of Months 253.00000 24.00368 55.03664 0.58483 12.36571



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.80560 43.40686 0.47415 10.09944
February 247.00000 23.86390 45.70741 0.51521 10.75811
March 299.00000 23.74871 48.46228 0.52011 11.08853
April 260.00000 23.99207 49.01191 0.64141 13.67873
May 286.00000 23.99666 47.33428 -0.1128 5.33902
June 286.00000 24.00039 51.49751 -0.0562 5.15495
July 260.00000 24.00033 56.02396 -0.0154 5.07020
August 299.00000 24.00030 57.25605 -0.0221 5.07214
September 260.00000 23.99956 53.69119 -0.0606 5.13293
October 273.00000 23.99993 46.12561 0.61683 13.14152
November 273.00000 23.97753 42.20002 0.52826 11.03483
December 260.00000 23.88390 37.38128 0.45545 9.51661
           
Annual Sum or Average 3276.00000 23.93864 48.26512 0.28550 8.70924
Minimum of Months 247.00000 23.74871 37.38128 -0.1128 5.07020
Maximum of Months 299.00000 24.00039 57.25605 0.64141 13.67873



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.99923 45.72528 0.74298 16.88585
February 247.00000 23.99932 46.74590 0.75586 17.26926
March 299.00000 23.99903 48.83198 0.77423 17.88840
April 260.00000 24.00302 51.01897 0.83008 19.75225
May 286.00000 24.00075 49.61244 0.14292 5.80370
June 286.00000 24.00266 53.07054 0.17956 6.04668
July 260.00000 24.00395 57.60775 0.19953 6.19509
August 299.00000 24.00406 58.55172 0.19791 6.18475
September 260.00000 24.01625 55.17555 0.18621 6.13263
October 273.00000 24.02485 50.68835 0.83349 20.00571
November 273.00000 23.99964 44.79485 0.75075 17.16810
December 260.00000 23.99920 41.11260 0.71302 16.03318
           
Annual Sum or Average 3276.00000 24.00429 50.32023 0.52089 12.85723
Minimum of Months 247.00000 23.99903 41.11260 0.14292 5.80370
Maximum of Months 299.00000 24.02485 58.55172 0.83349 20.00571



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 231.00000 23.16969 49.36796 0.38624 9.50540
February 209.00000 23.08143 51.81430 0.39588 9.41251
March 253.00000 23.04604 54.14152 0.41635 10.12793
April 220.00000 23.69099 55.52689 0.62110 13.60125
May 242.00000 23.80835 53.81158 -0.1115 5.85110
June 242.00000 23.96850 57.38230 -0.0047 5.21659
July 200.00000 23.97043 58.69149 -0.0432 5.15344
August 230.00000 23.96614 60.04014 -0.0528 5.16825
September 219.00000 23.95500 59.17382 -0.0183 5.26855
October 231.00000 23.96612 52.34982 0.67598 14.88723
November 231.00000 23.36544 48.86213 0.45450 10.18641
December 220.00000 23.21196 43.97872 0.36539 8.88773
           
Annual Sum or Average 2728.00000 23.59734 53.74549 0.25754 8.62042
Minimum of Months 200.00000 23.04604 43.97872 -0.1115 5.15344
Maximum of Months 253.00000 23.97043 60.04014 0.67598 14.88723



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.55738 39.45800 0.34392 8.23667
February 247.00000 23.69063 41.27311 0.40152 8.68211
March 299.00000 23.73434 44.13696 0.44034 9.48798
April 260.00000 23.97166 47.15844 0.58758 12.34920
May 286.00000 23.98843 45.33781 -0.1680 5.72488
June 286.00000 23.99889 50.40736 -0.0964 5.31247
July 260.00000 23.90850 54.51333 -0.1240 5.52749
August 299.00000 23.86932 55.37437 -0.1445 5.68721
September 260.00000 23.97818 52.00116 -0.1127 5.43097
October 273.00000 23.99196 43.65019 0.58333 12.35036
November 273.00000 23.82663 38.42866 0.43598 9.27624
December 260.00000 23.68466 33.05648 0.34006 7.81030
           
Annual Sum or Average 3276.00000 23.85112 45.50081 0.20263 7.96150
Minimum of Months 247.00000 23.55738 33.05648 -0.1680 5.31247
Maximum of Months 299.00000 23.99889 55.37437 0.58758 12.35036



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 23.51113 40.70037 0.30768 7.73156
February 247.00000 23.81808 42.09524 0.40020 8.49650
March 299.00000 23.84588 44.91297 0.43171 9.12795
April 260.00000 23.99643 47.31656 0.53883 11.13686
May 286.00000 23.99852 45.50798 -0.2428 6.29867
June 286.00000 24.00039 50.43208 -0.1840 5.76976
July 260.00000 23.99242 54.18377 -0.1781 5.70573
August 299.00000 23.98827 54.97162 -0.1840 5.75253
September 260.00000 23.99559 52.05881 -0.1852 5.77849
October 273.00000 23.99959 43.93495 0.53122 11.08759
November 273.00000 23.93189 39.08603 0.42308 8.93827
December 260.00000 23.78387 34.12705 0.33342 7.57057
           
Annual Sum or Average 3276.00000 23.90622 45.87186 0.16108 7.76162
Minimum of Months 247.00000 23.51113 34.12705 -0.2428 5.70573
Maximum of Months 299.00000 24.00039 54.97162 0.53883 11.13686



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 273.00000 22.04048 41.20678 0.08996 6.88407
February 247.00000 21.64571 45.13234 0.01495 6.24520
March 299.00000 21.31837 49.12632 -0.0585 6.80642
April 260.00000 22.31152 51.47238 0.20340 7.02277
May 286.00000 22.15157 50.12688 -0.7814 19.57478
June 286.00000 22.61757 55.65308 -0.6038 14.14809
July 260.00000 22.97441 61.36155 -0.4528 10.59254
August 299.00000 23.20957 61.63687 -0.3601 9.00700
September 260.00000 23.29818 55.99032 -0.3386 9.25660
October 273.00000 23.63810 45.31894 0.50595 11.67037
November 273.00000 22.36147 40.96608 0.18066 6.79248
December 260.00000 22.29004 34.58872 0.11349 6.71070
           
Annual Sum or Average 3276.00000 22.48673 49.51514 -0.1310 9.63575
Minimum of Months 247.00000 21.31837 34.58872 -0.7814 6.24520
Maximum of Months 299.00000 23.63810 61.63687 0.50595 19.57478



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.504341E+10 0.00 155.91 323153.82 03-JAN-08:61 0.00 35.79 45.06 0.01 0.00 0.01 1.18 03-JAN-08:61
February 0.354463E+10 0.00 162.69 286659.73 27-FEB-08:61 0.00 34.14 44.39 0.01 0.00 0.01 1.05 27-FEB-08:61
March 0.624119E+10 0.00 224.57 312068.49 30-MAR-07:01 0.00 35.55 48.24 0.01 0.00 0.01 1.14 30-MAR-07:01
April 0.107736E+10 0.00 83.56 197250.13 18-APR-07:01 0.00 42.24 46.49 0.00 0.00 0.00 0.72 18-APR-07:01
May 0.100806E+10 0.00 76.98 215152.72 15-MAY-07:01 0.00 45.39 49.16 0.00 0.00 0.00 0.78 15-MAY-07:01
June 0.545160E+09 0.00 70.94 63121.59 01-JUN-07:01 0.00 47.32 50.68 0.00 0.00 0.00 0.23 01-JUN-07:01
July 0.188362E+10 0.00 137.07 234381.06 14-JUL-07:02 0.00 31.89 40.98 0.00 0.00 0.00 0.85 14-JUL-07:02
August 0.217848E+10 0.00 161.33 229055.72 24-AUG-07:02 0.00 27.84 39.14 0.00 0.00 0.00 0.84 24-AUG-07:02
September 0.650296E+09 0.00 65.70 233527.78 01-SEP-07:01 0.00 44.53 48.01 0.00 0.00 0.00 0.85 01-SEP-07:01
October 0.344585E+09 0.00 40.61 102504.59 30-OCT-07:01 0.00 49.33 51.12 0.00 0.00 0.00 0.37 30-OCT-07:01
November 0.161541E+10 0.00 128.32 144326.78 24-NOV-08:61 0.00 38.95 45.92 0.00 0.00 0.00 0.53 24-NOV-08:61
December 0.314809E+10 0.00 142.46 287619.73 13-DEC-08:61 0.00 32.43 40.88 0.01 0.00 0.00 1.05 13-DEC-08:61
                           
Annual Sum or Average 0.272803E+11 0.00 1450.13     0.00 38.77 45.83 0.00 0.00 0.00    
Minimum of Months 0.344585E+09 0.00 40.61 63121.59   0.00 27.84 39.14 0.00 0.00 0.00 0.23  
Maximum of Months 0.624119E+10 0.00 224.57 323153.82   0.00 49.33 51.12 0.01 0.00 0.01 1.18  



Table of Contents

Report: DXReportMonthly

For: VAV_POD_1 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.122356E+11 0.357359E+10 177.90 0.118269E+11 0.408678E+09 0.00 1.00 13-JAN-11:30 0.00 01-JAN-00:03 59030.70 18-JAN-13:00 59030.70 18-JAN-13:00 5717.46 20-JAN-16:40 15864.08 18-JAN-13:00 0.00
February 0.725582E+10 0.218092E+10 137.73 0.649411E+10 0.761712E+09 0.00 1.00 01-FEB-09:40 0.00 01-FEB-00:03 53847.63 01-FEB-12:00 53847.63 01-FEB-12:00 7458.80 13-FEB-14:10 14475.25 01-FEB-12:00 0.00
March 0.786014E+10 0.233256E+10 134.19 0.673217E+10 0.112797E+10 0.00 1.00 10-MAR-11:40 0.00 01-MAR-00:05 49764.41 11-MAR-13:41 49764.41 11-MAR-13:41 7711.63 24-MAR-15:00 13380.59 11-MAR-13:41 0.00
April 0.161433E+11 0.468608E+10 208.79 0.147224E+11 0.142091E+10 0.00 1.00 04-APR-12:00 0.00 01-APR-00:10 62528.36 30-APR-12:10 62528.36 30-APR-12:10 9991.49 26-APR-19:00 16800.85 30-APR-12:10 0.00
May 0.181190E+11 0.533621E+10 254.17 0.166402E+11 0.147879E+10 0.00 1.00 02-MAY-12:30 0.00 01-MAY-00:03 48699.22 03-MAY-13:00 48699.22 03-MAY-13:00 14678.39 05-MAY-15:00 13094.94 03-MAY-13:00 0.00
June 0.286364E+11 0.810531E+10 300.20 0.242752E+11 0.436117E+10 0.00 1.00 13-JUN-11:00 0.00 01-JUN-00:03 53252.10 28-JUN-09:40 40277.94 14-JUN-14:00 21496.99 28-JUN-09:30 13934.25 28-JUN-09:40 0.00
July 0.369310E+11 0.100400E+11 285.55 0.283703E+11 0.856071E+10 0.00 1.00 12-JUL-15:30 0.00 01-JUL-00:03 69989.20 30-JUL-13:07 45259.83 23-JUL-14:14 29482.63 31-JUL-18:50 17977.50 30-JUL-13:07 0.00
August 0.435362E+11 0.117740E+11 326.06 0.324837E+11 0.110525E+11 0.00 1.00 02-AUG-09:00 0.00 01-AUG-00:03 76669.72 06-AUG-14:07 50007.80 19-AUG-14:11 30039.22 07-AUG-07:30 19572.05 06-AUG-14:07 0.00
September 0.351125E+11 0.976974E+10 290.43 0.270603E+11 0.805222E+10 0.00 1.00 05-SEP-12:40 0.00 01-SEP-00:03 105206.62 29-SEP-13:00 105206.62 29-SEP-13:00 48452.27 22-SEP-10:00 32513.81 29-SEP-13:00 0.00
October 0.458257E+11 0.125566E+11 311.75 0.378514E+11 0.797424E+10 0.00 1.00 01-OCT-10:31 0.00 01-OCT-00:03 110628.18 16-OCT-11:20 110628.18 16-OCT-11:20 43392.31 03-OCT-15:00 34947.31 16-OCT-11:00 0.00
November 0.141593E+11 0.414486E+10 208.13 0.132121E+11 0.947131E+09 0.00 1.00 08-NOV-10:20 0.00 01-NOV-00:03 59012.91 28-NOV-14:00 59012.91 28-NOV-14:00 9975.47 10-NOV-17:00 15859.32 28-NOV-14:00 0.00
December 0.150300E+11 0.426912E+10 172.18 0.148363E+11 0.193646E+09 0.00 1.00 04-DEC-09:20 0.00 01-DEC-00:05 64519.25 19-DEC-13:00 64519.25 19-DEC-13:00 5559.34 07-DEC-16:03 17333.90 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.280845E+12 0.787690E+11 2807.08 0.234505E+12 0.463397E+11 0.00                         0.00
Minimum of Months 0.725582E+10 0.218092E+10 134.19 0.649411E+10 0.193646E+09 0.00 1.00   0.00   48699.22   40277.94   5559.34   13094.94   0.00
Maximum of Months 0.458257E+11 0.125566E+11 326.06 0.378514E+11 0.110525E+11 0.00 1.00   0.00   110628.18   110628.18   48452.27   34947.31   0.00



Table of Contents

Report: DXReportMonthly

For: VAV_POD_2 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.120767E+11 0.352856E+10 179.37 0.116738E+11 0.402846E+09 0.00 1.00 13-JAN-11:30 0.00 01-JAN-00:03 58308.44 18-JAN-13:00 58308.44 18-JAN-13:00 5718.74 20-JAN-16:40 15670.39 18-JAN-13:00 0.00
February 0.719056E+10 0.216266E+10 139.83 0.643195E+10 0.758605E+09 0.00 1.00 01-FEB-09:40 0.00 01-FEB-00:03 53343.63 01-FEB-12:00 53343.63 01-FEB-12:00 7422.39 13-FEB-14:10 14339.99 01-FEB-12:00 0.00
March 0.777838E+10 0.230863E+10 137.36 0.667114E+10 0.110723E+10 0.00 1.00 10-MAR-11:40 0.00 01-MAR-00:05 46111.27 23-MAR-15:00 44924.63 23-MAR-14:00 7638.36 24-MAR-15:00 12315.04 23-MAR-15:00 0.00
April 0.160373E+11 0.465503E+10 212.13 0.146409E+11 0.139639E+10 0.00 1.00 04-APR-11:50 0.00 01-APR-00:10 59523.56 26-APR-13:00 59523.56 26-APR-13:00 9993.37 26-APR-19:00 15832.04 26-APR-13:00 0.00
May 0.181240E+11 0.533376E+10 257.00 0.166644E+11 0.145962E+10 0.00 1.00 02-MAY-12:20 0.00 01-MAY-00:03 48912.14 03-MAY-13:00 48912.14 03-MAY-13:00 14659.97 05-MAY-15:00 13151.90 03-MAY-13:00 0.00
June 0.285215E+11 0.806851E+10 300.37 0.242254E+11 0.429613E+10 0.00 1.00 13-JUN-11:00 0.00 01-JUN-00:03 53325.64 28-JUN-09:40 40515.79 14-JUN-14:00 21527.02 28-JUN-09:30 13953.28 28-JUN-09:40 0.00
July 0.367358E+11 0.998468E+10 284.28 0.282337E+11 0.850208E+10 0.00 1.00 12-JUL-15:30 0.00 01-JUL-00:03 68909.23 30-JUL-13:19 44749.95 23-JUL-14:30 29534.38 31-JUL-18:50 17725.65 30-JUL-13:19 0.00
August 0.434180E+11 0.117402E+11 325.76 0.324174E+11 0.110005E+11 0.00 1.00 02-AUG-09:00 0.00 01-AUG-00:03 75913.82 06-AUG-14:21 48528.63 19-AUG-14:28 30093.11 07-AUG-07:30 19379.52 06-AUG-14:21 0.00
September 0.347963E+11 0.968136E+10 289.33 0.268601E+11 0.793624E+10 0.00 1.00 05-SEP-12:40 0.00 01-SEP-00:03 104344.30 29-SEP-13:00 104344.30 29-SEP-13:00 48523.12 22-SEP-10:00 32251.16 29-SEP-13:00 0.00
October 0.455011E+11 0.124657E+11 310.54 0.375995E+11 0.790158E+10 0.00 1.00 01-OCT-10:37 0.00 01-OCT-00:03 109628.53 16-OCT-11:30 109628.53 16-OCT-11:30 43136.15 03-OCT-15:00 34603.13 16-OCT-11:00 0.00
November 0.139524E+11 0.408725E+10 208.83 0.130156E+11 0.936822E+09 0.00 1.00 08-NOV-10:20 0.00 01-NOV-00:03 69411.46 19-NOV-13:09 69411.46 19-NOV-13:09 9977.39 10-NOV-17:00 18643.00 19-NOV-13:09 0.00
December 0.146781E+11 0.417396E+10 171.38 0.144848E+11 0.193282E+09 0.00 1.00 04-DEC-09:30 0.00 01-DEC-00:05 63540.87 19-DEC-13:00 63540.87 19-DEC-13:00 5521.69 07-DEC-16:03 17071.72 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.278810E+12 0.781903E+11 2816.19 0.232919E+12 0.458914E+11 0.00                         0.00
Minimum of Months 0.719056E+10 0.216266E+10 137.36 0.643195E+10 0.193282E+09 0.00 1.00   0.00   46111.27   40515.79   5521.69   12315.04   0.00
Maximum of Months 0.455011E+11 0.124657E+11 325.76 0.375995E+11 0.110005E+11 0.00 1.00   0.00   109628.53   109628.53   48523.12   34603.13   0.00



Table of Contents

Report: DXReportMonthly

For: VAV_POD_3 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.110589E+11 0.322277E+10 177.41 0.106637E+11 0.395253E+09 0.00 1.00 13-JAN-11:20 0.00 01-JAN-00:03 54645.86 18-JAN-13:00 54645.86 18-JAN-13:00 5669.29 20-JAN-13:50 14683.40 18-JAN-13:00 0.00
February 0.653818E+10 0.195812E+10 136.70 0.585350E+10 0.684685E+09 0.00 1.00 01-FEB-09:50 0.00 01-FEB-00:03 49378.95 01-FEB-12:00 49378.95 01-FEB-12:00 6667.98 13-FEB-14:00 13272.49 01-FEB-12:00 0.00
March 0.705683E+10 0.208633E+10 134.15 0.600822E+10 0.104860E+10 0.00 1.00 10-MAR-11:10 0.00 01-MAR-00:05 44697.76 23-MAR-14:50 42115.08 23-MAR-14:00 7549.60 23-MAR-15:00 11938.09 23-MAR-14:50 0.00
April 0.144504E+11 0.418370E+10 208.75 0.131345E+11 0.131590E+10 0.00 1.00 04-APR-11:40 0.00 01-APR-00:10 57949.12 30-APR-11:46 57949.12 30-APR-11:46 8659.79 26-APR-19:00 15567.81 30-APR-11:46 0.00
May 0.160172E+11 0.470791E+10 253.50 0.146263E+11 0.139081E+10 0.00 1.00 02-MAY-12:10 0.00 01-MAY-00:03 45180.29 03-MAY-13:00 45180.29 03-MAY-13:00 12913.54 05-MAY-15:00 12147.08 03-MAY-13:00 0.00
June 0.252712E+11 0.715097E+10 300.85 0.211265E+11 0.414471E+10 0.00 1.00 14-JUN-11:10 0.00 01-JUN-00:03 50191.43 28-JUN-13:00 36843.83 14-JUN-14:00 18577.79 28-JUN-09:30 13056.98 28-JUN-13:00 0.00
July 0.323000E+11 0.878758E+10 285.73 0.245894E+11 0.771057E+10 0.00 1.00 01-JUL-15:31 0.00 01-JUL-00:03 58947.69 30-JUL-13:11 39054.86 23-JUL-14:19 25330.54 31-JUL-18:50 15165.11 30-JUL-13:11 0.00
August 0.382874E+11 0.103569E+11 326.78 0.282448E+11 0.100426E+11 0.00 1.00 02-AUG-09:00 0.00 01-AUG-00:03 66020.05 06-AUG-14:08 43727.80 19-AUG-14:11 25790.34 07-AUG-07:30 16855.05 06-AUG-14:08 0.00
September 0.314141E+11 0.873339E+10 291.76 0.239338E+11 0.748026E+10 0.00 1.00 05-SEP-12:40 0.00 01-SEP-00:03 95279.44 29-SEP-13:00 95279.44 29-SEP-13:00 41592.76 22-SEP-10:00 29451.32 29-SEP-13:00 0.00
October 0.412825E+11 0.113041E+11 311.93 0.340028E+11 0.727975E+10 0.00 1.00 01-OCT-10:21 0.00 01-OCT-00:03 99139.47 16-OCT-11:30 99139.47 16-OCT-11:30 40122.40 03-OCT-15:00 31358.36 16-OCT-11:00 0.00
November 0.128507E+11 0.374622E+10 206.09 0.119781E+11 0.872614E+09 0.00 1.00 08-NOV-10:20 0.00 01-NOV-00:03 54294.24 28-NOV-14:00 54294.24 28-NOV-14:00 9263.08 20-NOV-13:00 14589.23 28-NOV-14:00 0.00
December 0.134632E+11 0.381572E+10 170.14 0.132868E+11 0.176431E+09 0.00 1.00 04-DEC-09:20 0.00 01-DEC-00:05 59314.29 19-DEC-13:00 59314.29 19-DEC-13:00 5110.99 07-DEC-16:00 15933.21 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.249991E+12 0.700537E+11 2803.77 0.207448E+12 0.425422E+11 0.00                         0.00
Minimum of Months 0.653818E+10 0.195812E+10 134.15 0.585350E+10 0.176431E+09 0.00 1.00   0.00   44697.76   36843.83   5110.99   11938.09   0.00
Maximum of Months 0.412825E+11 0.113041E+11 326.78 0.340028E+11 0.100426E+11 0.00 1.00   0.00   99139.47   99139.47   41592.76   31358.36   0.00



Table of Contents

Report: DXReportMonthly

For: VAV_OTHER COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.800451E+10 0.238185E+10 163.02 0.750387E+10 0.500634E+09 0.00 1.00 13-JAN-13:10 0.00 01-JAN-00:03 48551.03 18-JAN-13:10 48551.03 18-JAN-13:10 4547.66 20-JAN-13:40 13052.34 18-JAN-13:10 0.00
February 0.472713E+10 0.144329E+10 123.07 0.418219E+10 0.544933E+09 0.00 1.00 01-FEB-11:10 0.00 01-FEB-00:03 45511.16 01-FEB-12:00 45511.16 01-FEB-12:00 6364.86 01-FEB-16:00 12237.31 01-FEB-12:00 0.00
March 0.583197E+10 0.174368E+10 120.64 0.491606E+10 0.915907E+09 0.00 1.00 22-MAR-12:40 0.00 01-MAR-00:05 41084.51 23-MAR-14:00 41084.51 23-MAR-14:00 10035.15 12-MAR-14:31 10999.42 23-MAR-14:00 0.00
April 0.149481E+11 0.432251E+10 209.36 0.137912E+11 0.115693E+10 0.00 1.00 04-APR-11:40 0.00 01-APR-00:10 69431.97 26-APR-14:10 63071.93 26-APR-13:00 12966.42 27-APR-07:01 18590.97 26-APR-14:10 0.00
May 0.173806E+11 0.506278E+10 262.39 0.160547E+11 0.132592E+10 0.00 1.00 01-MAY-12:10 0.00 01-MAY-00:03 55071.86 03-MAY-13:00 55071.86 03-MAY-13:00 13325.84 03-MAY-07:02 14799.70 03-MAY-13:00 0.00
June 0.299045E+11 0.838043E+10 324.65 0.250826E+11 0.482190E+10 0.00 1.00 02-JUN-10:20 0.00 01-JUN-00:03 71491.42 29-JUN-13:00 52009.92 26-JUN-11:00 33257.72 30-JUN-07:03 18486.95 29-JUN-13:00 0.00
July 0.344824E+11 0.944501E+10 320.99 0.249603E+11 0.952207E+10 0.00 1.00 01-JUL-08:20 0.00 01-JUL-00:03 104121.33 23-JUL-09:21 60533.14 23-JUL-09:21 43588.19 23-JUL-09:21 26644.05 23-JUL-09:21 0.00
August 0.387145E+11 0.105244E+11 346.48 0.272514E+11 0.114632E+11 0.00 1.00 03-AUG-12:50 0.00 01-AUG-00:03 96393.98 06-AUG-12:51 60741.61 19-AUG-14:39 48381.56 07-AUG-07:03 24482.33 06-AUG-12:51 0.00
September 0.326594E+11 0.911680E+10 301.20 0.252017E+11 0.745771E+10 0.00 1.00 03-SEP-14:15 0.00 01-SEP-00:03 90950.09 29-SEP-13:00 90950.09 29-SEP-13:00 44783.84 22-SEP-07:03 28145.99 29-SEP-13:00 0.00
October 0.404619E+11 0.111449E+11 321.80 0.332405E+11 0.722142E+10 0.00 1.00 01-OCT-00:32 0.00 01-OCT-00:03 103010.75 05-OCT-07:03 96806.76 16-OCT-11:00 58680.21 05-OCT-07:03 30660.15 16-OCT-11:00 0.00
November 0.954285E+10 0.285550E+10 192.32 0.876301E+10 0.779845E+09 0.00 1.00 08-NOV-10:50 0.00 01-NOV-00:03 52864.63 19-NOV-11:38 52864.63 19-NOV-11:38 7097.30 10-NOV-16:50 14208.39 19-NOV-11:38 0.00
December 0.959344E+10 0.279257E+10 155.14 0.943756E+10 0.155880E+09 0.00 1.00 04-DEC-10:00 0.00 01-DEC-00:05 49041.04 19-DEC-13:10 49041.04 19-DEC-13:10 4757.32 07-DEC-16:00 13183.70 19-DEC-13:10 0.00
                                       
Annual Sum or Average 0.246251E+12 0.692137E+11 2841.06 0.200385E+12 0.458663E+11 0.00                         0.00
Minimum of Months 0.472713E+10 0.144329E+10 120.64 0.418219E+10 0.155880E+09 0.00 1.00   0.00   41084.51   41084.51   4547.66   10999.42   0.00
Maximum of Months 0.404619E+11 0.111449E+11 346.48 0.332405E+11 0.114632E+11 0.00 1.00   0.00   104121.33   96806.76   58680.21   30660.15   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_2:5 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.150681E+10 0.373417E+09 89.83 0.125574E+10 0.251069E+09 0.00 1.00 17-JAN-06:01 0.00 01-JAN-00:03 26275.07 18-JAN-06:02 18918.49 18-JAN-06:02 13824.76 31-JAN-06:01 5562.89 18-JAN-06:02 0.00 01-JAN-00:03
February 0.670978E+09 0.171948E+09 61.63 0.576602E+09 94375259.15 0.00 1.00 02-FEB-06:01 0.00 01-FEB-00:03 26275.07 02-FEB-06:01 15931.14 02-FEB-06:01 10343.93 02-FEB-06:01 5562.89 02-FEB-06:01 0.00 01-FEB-00:03
March 0.127784E+10 0.308362E+09 73.06 0.900633E+09 0.377206E+09 0.00 1.00 12-MAR-12:32 0.00 01-MAR-00:05 28186.11 12-MAR-12:32 18768.45 12-MAR-12:32 13664.17 24-MAR-06:01 5996.75 12-MAR-12:32 0.00 01-MAR-00:05
April 0.497337E+10 0.116926E+10 203.41 0.356958E+10 0.140379E+10 0.00 1.00 02-APR-12:17 0.00 01-APR-00:10 28661.46 08-APR-11:45 27972.03 30-APR-10:27 14128.17 27-APR-05:01 6439.27 30-APR-11:02 0.00 01-APR-00:10
May 0.571194E+10 0.134420E+10 239.90 0.420048E+10 0.151146E+10 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:03 28068.02 28-MAY-14:02 26275.07 24-MAY-05:02 14730.74 03-MAY-05:01 6010.32 28-MAY-12:02 0.00 01-MAY-00:03
June 0.102040E+11 0.229498E+10 286.09 0.684404E+10 0.335992E+10 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:03 29010.36 18-JUN-13:12 22235.32 17-JUN-13:32 15957.20 28-JUN-05:01 6333.45 25-JUN-12:02 0.00 01-JUN-00:03
July 0.110901E+11 0.248412E+10 273.41 0.714491E+10 0.394515E+10 0.00 1.00 01-JUL-08:05 0.00 01-JUL-00:03 30280.34 23-JUL-10:56 23330.86 22-JUL-15:00 17027.84 20-JUL-05:01 6626.01 23-JUL-10:56 0.00 01-JUL-00:03
August 0.119696E+11 0.268547E+10 304.29 0.755411E+10 0.441551E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:03 30279.26 06-AUG-12:53 23023.35 19-AUG-14:45 17974.62 07-AUG-05:17 6692.17 19-AUG-13:43 0.00 01-AUG-00:03
September 0.949028E+10 0.217153E+10 260.82 0.618615E+10 0.330412E+10 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:03 29671.44 09-SEP-10:47 27915.35 30-SEP-11:02 16487.86 22-SEP-05:03 7072.08 30-SEP-11:42 0.00 01-SEP-00:03
October 0.980511E+10 0.229436E+10 281.19 0.731740E+10 0.248771E+10 0.00 1.00 01-OCT-10:10 0.00 01-OCT-00:03 30566.96 01-OCT-12:02 27162.24 15-OCT-17:01 16165.85 05-OCT-05:08 7077.29 14-OCT-12:22 0.00 01-OCT-00:03
November 0.160483E+10 0.410684E+09 133.39 0.132036E+10 0.284475E+09 0.00 1.00 01-NOV-05:02 0.00 01-NOV-00:03 26275.07 21-NOV-06:01 26275.07 28-NOV-06:01 12342.56 10-NOV-06:01 5575.64 10-NOV-06:01 0.00 01-NOV-00:03
December 0.179426E+10 0.453643E+09 115.85 0.174669E+10 47566457.84 0.00 1.00 05-DEC-07:00 0.00 01-DEC-00:05 26275.07 06-DEC-06:01 25270.94 06-DEC-06:01 10212.98 08-DEC-06:01 5562.89 06-DEC-06:01 0.00 01-DEC-00:05
                                         
Annual Sum or Average 0.700990E+11 0.161620E+11 2322.87 0.486167E+11 0.214824E+11 0.00                            
Minimum of Months 0.670978E+09 0.171948E+09 61.63 0.576602E+09 47566457.84 0.00 1.00   0.00   26275.07   15931.14   10212.98   5562.89   0.00  
Maximum of Months 0.119696E+11 0.268547E+10 304.29 0.755411E+10 0.441551E+10 0.00 1.00   0.00   30566.96   27972.03   17974.62   7077.29   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_1:6 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.750376E+10 0.168679E+10 239.31 0.610846E+10 0.139529E+10 0.00 1.00 01-JAN-08:43 0.00 01-JAN-00:03 27451.47 16-JAN-19:23 26910.90 14-JAN-14:53 14310.02 21-JAN-07:12 6246.94 14-JAN-14:53 0.00 01-JAN-00:03
February 0.597050E+10 0.133498E+10 203.89 0.446347E+10 0.150703E+10 0.00 1.00 01-FEB-02:53 0.00 01-FEB-00:03 28389.96 01-FEB-11:50 26154.34 03-FEB-05:12 14358.95 13-FEB-06:11 6396.58 01-FEB-11:50 0.00 01-FEB-00:03
March 0.747902E+10 0.166565E+10 236.35 0.512260E+10 0.235643E+10 0.00 1.00 01-MAR-06:11 0.00 01-MAR-00:05 28166.10 12-MAR-12:43 26738.57 11-MAR-11:00 13605.01 19-MAR-06:53 6029.85 23-MAR-10:50 0.00 01-MAR-00:05
April 0.110729E+11 0.243891E+10 265.76 0.796818E+10 0.310477E+10 0.00 1.00 01-APR-07:53 0.00 01-APR-00:20 29345.12 26-APR-11:05 27000.51 02-APR-12:47 14084.81 30-APR-22:52 6542.53 26-APR-11:05 0.00 01-APR-00:10
May 0.120131E+11 0.264889E+10 306.13 0.876704E+10 0.324609E+10 0.00 1.00 01-MAY-00:12 0.00 01-MAY-00:03 27988.92 29-MAY-09:58 26154.34 24-MAY-03:32 14655.18 03-MAY-05:01 5982.70 28-MAY-11:44 0.00 01-MAY-00:03
June 0.157369E+11 0.346802E+10 346.86 0.105617E+11 0.517521E+10 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:03 29666.31 28-JUN-10:50 22008.44 04-JUN-10:52 15933.42 28-JUN-05:32 6454.01 29-JUN-10:50 0.00 01-JUN-00:03
July 0.183120E+11 0.403435E+10 355.50 0.114163E+11 0.689573E+10 0.00 1.00 01-JUL-03:32 0.00 01-JUL-00:03 30204.27 23-JUL-10:52 22105.20 04-JUL-08:52 17975.00 29-JUL-18:53 6701.46 19-JUL-10:50 0.00 01-JUL-00:03
August 0.201154E+11 0.443253E+10 389.34 0.121955E+11 0.791993E+10 0.00 1.00 01-AUG-03:32 0.00 01-AUG-00:03 30203.15 06-AUG-12:51 22705.92 19-AUG-14:58 17962.59 07-AUG-03:32 6723.32 14-AUG-10:55 0.00 01-AUG-00:03
September 0.160396E+11 0.356925E+10 332.88 0.102685E+11 0.577106E+10 0.00 1.00 01-SEP-03:32 0.00 01-SEP-00:03 30738.41 22-SEP-11:40 28594.32 30-SEP-15:32 17915.91 30-SEP-20:53 7442.10 29-SEP-11:10 0.00 01-SEP-00:03
October 0.177655E+11 0.399157E+10 355.48 0.129740E+11 0.479159E+10 0.00 1.00 01-OCT-00:12 0.00 01-OCT-00:03 30500.99 01-OCT-11:52 28254.43 14-OCT-12:52 18714.68 01-OCT-06:12 7687.99 14-OCT-12:12 0.00 01-OCT-00:03
November 0.821740E+10 0.182674E+10 248.96 0.652430E+10 0.169310E+10 0.00 1.00 01-NOV-03:32 0.00 01-NOV-00:03 27925.74 19-NOV-14:42 27368.88 18-NOV-13:22 14209.75 19-NOV-22:03 6404.02 19-NOV-12:42 0.00 01-NOV-00:03
December 0.734381E+10 0.164959E+10 241.23 0.642044E+10 0.923368E+09 0.00 1.00 01-DEC-04:32 0.00 01-DEC-00:10 26747.87 16-DEC-12:53 26747.87 16-DEC-12:53 12819.14 09-DEC-08:32 6219.17 16-DEC-12:53 0.00 01-DEC-00:05
                                         
Annual Sum or Average 0.147570E+12 0.327473E+11 3521.69 0.102790E+12 0.447796E+11 0.00                            
Minimum of Months 0.597050E+10 0.133498E+10 203.89 0.446347E+10 0.923368E+09 0.00 1.00   0.00   26747.87   22008.44   12819.14   5982.70   0.00  
Maximum of Months 0.201154E+11 0.443253E+10 389.34 0.129740E+11 0.791993E+10 0.00 1.00   0.00   30738.41   28594.32   18714.68   7687.99   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_2:7 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.545113E+10 0.130755E+10 131.91 0.454044E+10 0.910688E+09 0.00 1.00 13-JAN-13:50 0.00 01-JAN-00:03 27425.83 17-JAN-14:00 26891.12 18-JAN-13:00 8335.35 17-JAN-13:00 6335.70 18-JAN-13:00 0.00 01-JAN-00:03
February 0.396796E+10 0.964178E+09 100.34 0.306547E+10 0.902498E+09 0.00 1.00 01-FEB-11:40 0.00 01-FEB-00:03 25567.17 01-FEB-12:00 25567.17 01-FEB-12:00 9029.08 01-FEB-14:00 6026.66 01-FEB-12:00 0.00 01-FEB-00:03
March 0.493179E+10 0.117452E+10 120.36 0.339382E+10 0.153798E+10 0.00 1.00 22-MAR-10:30 0.00 01-MAR-00:05 30410.18 23-MAR-14:00 21514.94 23-MAR-14:00 10638.34 22-MAR-13:00 6728.94 23-MAR-14:00 0.00 01-MAR-00:05
April 0.938964E+10 0.214934E+10 164.91 0.675657E+10 0.263307E+10 0.00 1.00 03-APR-10:00 0.00 01-APR-00:10 48194.46 30-APR-12:01 40506.79 30-APR-12:01 24590.76 27-APR-05:01 10980.21 30-APR-12:01 0.00 01-APR-00:10
May 0.105861E+11 0.241861E+10 197.57 0.783172E+10 0.275440E+10 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:03 46135.84 03-MAY-05:01 26549.85 04-MAY-12:00 25487.49 03-MAY-05:01 9990.73 03-MAY-05:01 0.00 01-MAY-00:03
June 0.163429E+11 0.368804E+10 237.42 0.110257E+11 0.531720E+10 0.00 1.00 01-JUN-09:30 0.00 01-JUN-00:03 49402.23 18-JUN-13:51 36017.31 25-JUN-11:51 27200.90 28-JUN-05:01 10978.24 25-JUN-11:51 0.00 01-JUN-00:03
July 0.884876E+10 0.217355E+10 218.79 0.553496E+10 0.331380E+10 0.00 1.00 01-JUL-10:13 0.00 01-JUL-00:03 51546.83 23-JUL-11:01 34636.97 01-JUL-12:02 28989.21 20-JUL-05:01 11463.02 23-JUL-11:01 0.00 01-JUL-00:03
August 0.966380E+10 0.238460E+10 240.41 0.591779E+10 0.374601E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:03 51563.56 06-AUG-12:51 37486.08 19-AUG-14:47 30135.38 07-AUG-05:01 11600.60 19-AUG-13:22 0.00 01-AUG-00:03
September 0.156277E+11 0.358493E+10 217.51 0.102539E+11 0.537376E+10 0.00 1.00 05-SEP-05:01 0.00 01-SEP-00:03 52459.79 22-SEP-12:00 47410.37 29-SEP-13:40 27688.28 22-SEP-05:01 13227.58 29-SEP-11:00 0.00 01-SEP-00:03
October 0.166549E+11 0.389623E+10 232.52 0.128226E+11 0.383224E+10 0.00 1.00 01-OCT-11:02 0.00 01-OCT-00:03 51926.55 01-OCT-12:18 47106.68 16-OCT-12:00 27794.33 05-OCT-05:42 13502.93 16-OCT-11:00 0.00 01-OCT-00:03
November 0.623288E+10 0.147432E+10 131.79 0.502196E+10 0.121092E+10 0.00 1.00 10-NOV-09:06 0.00 01-NOV-00:03 26682.51 10-NOV-13:00 23797.24 28-NOV-14:00 9468.53 10-NOV-15:00 5778.92 10-NOV-13:00 0.00 01-NOV-00:03
December 0.540068E+10 0.129397E+10 130.15 0.497842E+10 0.422267E+09 0.00 1.00 04-DEC-09:07 0.00 01-DEC-00:05 26301.85 19-DEC-13:00 26301.85 19-DEC-13:00 8114.86 07-DEC-13:00 6238.18 19-DEC-13:00 0.00 01-DEC-00:05
                                         
Annual Sum or Average 0.113098E+12 0.265098E+11 2123.67 0.811434E+11 0.319548E+11 0.00                            
Minimum of Months 0.396796E+10 0.964178E+09 100.34 0.306547E+10 0.422267E+09 0.00 1.00   0.00   25567.17   21514.94   8114.86   5778.92   0.00  
Maximum of Months 0.166549E+11 0.389623E+10 240.41 0.128226E+11 0.537376E+10 0.00 1.00   0.00   52459.79   47410.37   30135.38   13502.93   0.00  



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 175.53 230.61 0.00 0.00 0.00
February 173.53 80.11 93.42 206.43 199.60 0.00 0.00 0.00
March 198.91 88.00 110.91 245.56 198.53 0.00 0.00 0.00
April 274.20 142.78 131.43 381.32 164.94 0.00 0.00 0.00
May 269.35 124.41 144.94 369.09 146.49 0.00 0.00 0.00
June 285.35 142.67 142.68 417.92 111.78 0.00 0.00 0.00
July 302.07 161.63 140.43 471.24 93.92 0.00 0.00 0.00
August 283.40 153.59 129.81 447.17 98.13 0.00 0.00 0.00
September 242.64 129.83 112.81 356.22 130.27 0.00 0.00 0.00
October 185.49 101.27 84.22 273.69 154.11 0.00 0.00 0.00
November 167.55 87.64 79.91 209.49 211.27 0.00 0.00 0.00
December 147.98 79.37 68.61 181.29 234.83 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 311.78 164.36 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 175.53 93.92 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 471.24 234.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 57.55 42.21 15.33 85.57 33.26 0.00 0.00 0.00
February 45.23 27.86 17.37 63.72 29.56 0.00 0.00 0.00
March 36.06 17.42 18.64 50.39 30.61 0.00 0.00 0.00
April 30.13 11.49 18.64 44.34 26.41 0.00 0.00 0.00
May 21.45 2.64 18.81 25.75 23.73 0.00 0.00 0.00
June 18.82 1.14 17.68 23.18 18.12 0.00 0.00 0.00
July 19.94 2.24 17.69 29.24 15.25 0.00 0.00 0.00
August 25.61 8.08 17.53 42.89 15.67 0.00 0.00 0.00
September 35.64 18.06 17.58 57.42 20.63 0.00 0.00 0.00
October 45.32 30.30 15.02 73.03 23.10 0.00 0.00 0.00
November 55.09 38.89 16.20 81.49 30.87 0.00 0.00 0.00
December 61.48 46.79 14.69 91.79 33.65 0.00 0.00 0.00
                 
Annual Sum or Average 37.66 20.57 17.09 55.71 25.05 0.00 0.00 0.00
Minimum of Months 18.82 1.14 14.69 23.18 15.25 0.00 0.00 0.00
Maximum of Months 61.48 46.79 18.81 91.79 33.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 399.39 292.97 106.42 593.87 230.84 0.00 0.00 0.00
February 313.90 193.34 120.55 442.25 205.15 0.00 0.00 0.00
March 250.25 120.88 129.37 349.70 212.46 0.00 0.00 0.00
April 209.09 79.73 129.36 307.73 183.29 0.00 0.00 0.00
May 148.89 18.32 130.57 178.57 164.94 0.00 0.00 0.00
June 130.62 7.89 122.73 160.22 126.16 0.00 0.00 0.00
July 138.36 15.57 122.78 202.35 106.14 0.00 0.00 0.00
August 177.75 56.07 121.68 297.62 108.83 0.00 0.00 0.00
September 247.34 125.33 122.00 398.50 143.16 0.00 0.00 0.00
October 314.55 210.29 104.27 506.86 160.30 0.00 0.00 0.00
November 382.31 269.90 112.40 565.55 214.23 0.00 0.00 0.00
December 426.68 324.75 101.92 637.02 233.56 0.00 0.00 0.00
                 
Annual Sum or Average 261.37 142.75 118.62 386.54 173.91 0.00 0.00 0.00
Minimum of Months 130.62 7.89 101.92 160.22 106.14 0.00 0.00 0.00
Maximum of Months 426.68 324.75 130.57 637.02 233.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 733.91 538.36 195.55 1076.94 463.02 0.00 0.00 0.00
February 576.81 355.29 221.53 799.57 413.68 0.00 0.00 0.00
March 459.86 222.13 237.72 631.55 421.91 0.00 0.00 0.00
April 384.22 146.51 237.71 561.20 353.26 0.00 0.00 0.00
May 273.59 33.67 239.92 324.44 316.11 0.00 0.00 0.00
June 240.02 14.49 225.52 293.86 238.74 0.00 0.00 0.00
July 254.24 28.62 225.62 382.85 187.64 0.00 0.00 0.00
August 326.62 103.03 223.60 555.36 196.09 0.00 0.00 0.00
September 454.50 230.31 224.19 731.71 273.32 0.00 0.00 0.00
October 578.02 386.42 191.60 927.32 314.37 0.00 0.00 0.00
November 702.52 495.97 206.55 1027.86 427.15 0.00 0.00 0.00
December 784.05 596.77 187.29 1156.42 468.00 0.00 0.00 0.00
                 
Annual Sum or Average 480.29 262.32 217.98 705.56 339.01 0.00 0.00 0.00
Minimum of Months 240.02 14.49 187.29 293.86 187.64 0.00 0.00 0.00
Maximum of Months 784.05 596.77 239.92 1156.42 468.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 733.91 538.36 195.55 1076.94 463.02 0.00 0.00 0.00
February 576.81 355.29 221.53 799.57 413.68 0.00 0.00 0.00
March 459.86 222.13 237.72 631.55 421.91 0.00 0.00 0.00
April 384.22 146.51 237.71 561.20 353.26 0.00 0.00 0.00
May 273.59 33.67 239.92 324.44 316.11 0.00 0.00 0.00
June 240.02 14.49 225.52 293.86 238.74 0.00 0.00 0.00
July 254.24 28.62 225.62 382.85 187.64 0.00 0.00 0.00
August 326.62 103.03 223.60 555.36 196.09 0.00 0.00 0.00
September 454.50 230.31 224.19 731.71 273.32 0.00 0.00 0.00
October 578.02 386.42 191.60 927.32 314.37 0.00 0.00 0.00
November 702.52 495.97 206.55 1027.86 427.15 0.00 0.00 0.00
December 784.05 596.77 187.29 1156.42 468.00 0.00 0.00 0.00
                 
Annual Sum or Average 480.29 262.32 217.98 705.56 339.01 0.00 0.00 0.00
Minimum of Months 240.02 14.49 187.29 293.86 187.64 0.00 0.00 0.00
Maximum of Months 784.05 596.77 239.92 1156.42 468.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 733.90 538.35 195.55 1076.92 463.01 0.00 0.00 0.00
February 576.80 355.28 221.52 799.55 413.67 0.00 0.00 0.00
March 459.85 222.13 237.72 631.54 421.90 0.00 0.00 0.00
April 384.21 146.50 237.71 561.19 353.25 0.00 0.00 0.00
May 273.59 33.67 239.92 324.44 316.10 0.00 0.00 0.00
June 240.01 14.49 225.52 293.86 238.73 0.00 0.00 0.00
July 254.24 28.62 225.62 382.84 187.63 0.00 0.00 0.00
August 326.62 103.03 223.59 555.35 196.09 0.00 0.00 0.00
September 454.49 230.31 224.18 731.70 273.31 0.00 0.00 0.00
October 578.00 386.41 191.59 927.30 314.36 0.00 0.00 0.00
November 702.51 495.96 206.55 1027.84 427.15 0.00 0.00 0.00
December 784.04 596.75 187.28 1156.39 467.99 0.00 0.00 0.00
                 
Annual Sum or Average 480.29 262.31 217.98 705.54 339.00 0.00 0.00 0.00
Minimum of Months 240.01 14.49 187.28 293.86 187.63 0.00 0.00 0.00
Maximum of Months 784.04 596.75 239.92 1156.39 467.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 48.48 24.45 24.03 61.11 78.95 0.00 0.00 0.00
February 57.84 26.70 31.14 69.72 70.77 0.00 0.00 0.00
March 66.30 29.33 36.97 81.84 71.33 0.00 0.00 0.00
April 91.40 47.59 43.81 127.15 58.22 0.00 0.00 0.00
May 89.79 41.47 48.31 120.83 53.31 0.00 0.00 0.00
June 95.12 47.56 47.56 136.56 40.71 0.00 0.00 0.00
July 100.69 53.88 46.81 157.71 31.68 0.00 0.00 0.00
August 94.47 51.20 43.27 150.72 32.36 0.00 0.00 0.00
September 80.88 43.28 37.60 120.24 43.75 0.00 0.00 0.00
October 61.83 33.76 28.07 92.86 52.48 0.00 0.00 0.00
November 55.85 29.21 26.64 72.03 72.57 0.00 0.00 0.00
December 49.33 26.46 22.87 63.34 80.16 0.00 0.00 0.00
                 
Annual Sum or Average 74.40 37.96 36.44 104.69 57.12 0.00 0.00 0.00
Minimum of Months 48.48 24.45 22.87 61.11 31.68 0.00 0.00 0.00
Maximum of Months 100.69 53.88 48.31 157.71 80.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 196.96 200.70 0.00 0.00 0.00
February 173.53 80.11 93.42 223.22 179.56 0.00 0.00 0.00
March 198.91 88.00 110.91 258.55 185.60 0.00 0.00 0.00
April 274.20 142.78 131.43 392.61 155.50 0.00 0.00 0.00
May 269.35 124.41 144.94 371.39 145.56 0.00 0.00 0.00
June 285.35 142.67 142.68 416.34 113.95 0.00 0.00 0.00
July 302.07 161.63 140.43 473.05 93.82 0.00 0.00 0.00
August 283.40 153.59 129.81 455.85 92.28 0.00 0.00 0.00
September 242.64 129.83 112.81 370.42 117.27 0.00 0.00 0.00
October 185.49 101.27 84.22 289.31 136.85 0.00 0.00 0.00
November 167.55 87.64 79.91 229.88 185.10 0.00 0.00 0.00
December 147.98 79.37 68.61 204.07 202.75 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 323.98 150.59 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 196.96 92.28 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 473.05 202.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 6.62 0.00 6.62 4.32 30.70 0.00 0.00 0.00
February 8.52 0.00 8.52 4.89 27.83 0.00 0.00 0.00
March 10.55 0.00 10.55 7.19 29.04 0.00 0.00 0.00
April 12.07 0.05 12.01 9.60 23.75 0.00 0.00 0.00
May 14.78 0.78 14.00 12.10 21.14 0.00 0.00 0.00
June 16.03 1.84 14.20 17.07 16.55 0.00 0.00 0.00
July 14.86 1.51 13.35 19.03 13.49 0.00 0.00 0.00
August 12.04 0.29 11.75 15.75 13.24 0.00 0.00 0.00
September 10.14 0.00 10.14 10.91 17.88 0.00 0.00 0.00
October 8.13 0.00 8.13 10.00 20.49 0.00 0.00 0.00
November 7.19 0.00 7.19 4.74 28.52 0.00 0.00 0.00
December 6.10 0.00 6.10 3.92 30.98 0.00 0.00 0.00
                 
Annual Sum or Average 10.59 0.38 10.22 9.99 22.77 0.00 0.00 0.00
Minimum of Months 6.10 0.00 6.10 3.92 13.24 0.00 0.00 0.00
Maximum of Months 16.03 1.84 14.20 19.03 30.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.30 0.00 49.30 34.00 213.85 0.00 0.00 0.00
February 63.01 0.00 63.01 38.86 193.50 0.00 0.00 0.00
March 77.84 0.00 77.84 55.97 201.92 0.00 0.00 0.00
April 89.16 0.37 88.79 73.64 165.53 0.00 0.00 0.00
May 108.47 5.44 103.03 92.46 147.91 0.00 0.00 0.00
June 117.07 12.76 104.32 126.74 115.81 0.00 0.00 0.00
July 109.20 10.48 98.72 140.68 94.88 0.00 0.00 0.00
August 89.17 2.03 87.14 117.28 93.25 0.00 0.00 0.00
September 75.24 0.01 75.23 82.72 125.33 0.00 0.00 0.00
October 60.13 0.00 60.13 74.69 143.62 0.00 0.00 0.00
November 53.54 0.00 53.54 37.48 198.60 0.00 0.00 0.00
December 45.57 0.00 45.57 31.10 215.97 0.00 0.00 0.00
                 
Annual Sum or Average 78.20 2.60 75.60 75.72 158.98 0.00 0.00 0.00
Minimum of Months 45.57 0.00 45.57 31.10 93.25 0.00 0.00 0.00
Maximum of Months 117.07 12.76 104.32 140.68 215.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 79.74 0.00 79.74 43.08 422.85 0.00 0.00 0.00
February 102.62 0.00 102.62 46.91 387.49 0.00 0.00 0.00
March 127.34 0.00 127.34 74.12 401.73 0.00 0.00 0.00
April 145.28 0.30 144.98 109.06 322.42 0.00 0.00 0.00
May 174.04 6.54 167.50 134.46 294.86 0.00 0.00 0.00
June 186.68 16.91 169.77 194.27 230.17 0.00 0.00 0.00
July 173.75 13.79 159.96 234.05 171.94 0.00 0.00 0.00
August 144.08 2.38 141.70 200.21 166.88 0.00 0.00 0.00
September 122.76 0.02 122.75 130.22 234.54 0.00 0.00 0.00
October 98.34 0.00 98.34 116.26 277.88 0.00 0.00 0.00
November 86.60 0.00 86.60 47.72 391.77 0.00 0.00 0.00
December 73.49 0.00 73.49 39.77 427.36 0.00 0.00 0.00
                 
Annual Sum or Average 126.32 3.34 122.98 114.66 310.37 0.00 0.00 0.00
Minimum of Months 73.49 0.00 73.49 39.77 166.88 0.00 0.00 0.00
Maximum of Months 186.68 16.91 169.77 234.05 427.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.55 0.00 83.55 46.05 426.08 0.00 0.00 0.00
February 107.66 0.00 107.66 51.63 389.04 0.00 0.00 0.00
March 133.47 0.00 133.47 80.78 402.53 0.00 0.00 0.00
April 152.28 0.57 151.71 114.98 321.44 0.00 0.00 0.00
May 185.13 8.88 176.24 145.57 289.71 0.00 0.00 0.00
June 198.40 20.06 178.33 210.03 228.22 0.00 0.00 0.00
July 184.22 16.57 167.64 249.05 172.20 0.00 0.00 0.00
August 151.31 3.27 148.04 207.79 166.69 0.00 0.00 0.00
September 128.10 0.02 128.08 136.13 236.68 0.00 0.00 0.00
October 102.72 0.00 102.72 120.61 281.06 0.00 0.00 0.00
November 90.78 0.00 90.78 51.28 394.73 0.00 0.00 0.00
December 76.99 0.00 76.99 41.82 430.92 0.00 0.00 0.00
                 
Annual Sum or Average 132.98 4.14 128.85 121.81 311.15 0.00 0.00 0.00
Minimum of Months 76.99 0.00 76.99 41.82 166.69 0.00 0.00 0.00
Maximum of Months 198.40 20.06 178.33 249.05 430.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.83 0.00 83.83 46.30 426.18 0.00 0.00 0.00
February 107.98 0.00 107.98 51.98 389.09 0.00 0.00 0.00
March 133.85 0.00 133.85 81.23 402.54 0.00 0.00 0.00
April 152.94 0.66 152.28 115.53 320.98 0.00 0.00 0.00
May 187.21 9.79 177.42 146.48 286.81 0.00 0.00 0.00
June 201.12 21.67 179.45 211.49 224.75 0.00 0.00 0.00
July 186.92 18.13 168.79 250.83 169.01 0.00 0.00 0.00
August 152.63 3.74 148.89 208.79 165.31 0.00 0.00 0.00
September 128.52 0.02 128.50 136.67 236.74 0.00 0.00 0.00
October 103.02 0.00 103.02 120.97 281.19 0.00 0.00 0.00
November 91.08 0.00 91.08 51.58 394.83 0.00 0.00 0.00
December 77.26 0.00 77.26 42.03 431.03 0.00 0.00 0.00
                 
Annual Sum or Average 133.97 4.53 129.45 122.49 310.24 0.00 0.00 0.00
Minimum of Months 77.26 0.00 77.26 42.03 165.31 0.00 0.00 0.00
Maximum of Months 201.12 21.67 179.45 250.83 431.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 176.01 230.17 0.00 0.00 0.00
February 173.53 80.11 93.42 206.72 199.62 0.00 0.00 0.00
March 198.91 88.00 110.91 245.92 198.54 0.00 0.00 0.00
April 274.20 142.78 131.43 381.77 164.94 0.00 0.00 0.00
May 269.35 124.41 144.94 369.73 146.40 0.00 0.00 0.00
June 285.35 142.67 142.68 418.21 111.89 0.00 0.00 0.00
July 302.07 161.63 140.43 471.98 93.71 0.00 0.00 0.00
August 283.40 153.59 129.81 448.01 97.76 0.00 0.00 0.00
September 242.64 129.83 112.81 356.51 130.39 0.00 0.00 0.00
October 185.49 101.27 84.22 273.73 154.54 0.00 0.00 0.00
November 167.55 87.64 79.91 209.64 211.50 0.00 0.00 0.00
December 147.98 79.37 68.61 181.56 234.51 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 312.18 164.32 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 176.01 93.71 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 471.98 234.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 55.53 41.60 13.93 83.40 33.08 0.00 0.00 0.00
February 43.68 27.80 15.88 61.76 29.10 0.00 0.00 0.00
March 34.33 17.41 16.92 48.01 30.17 0.00 0.00 0.00
April 28.10 11.49 16.61 41.73 26.01 0.00 0.00 0.00
May 19.26 2.64 16.62 22.85 23.43 0.00 0.00 0.00
June 16.66 1.14 15.52 20.24 17.87 0.00 0.00 0.00
July 17.66 2.24 15.42 26.21 14.81 0.00 0.00 0.00
August 23.52 8.08 15.44 40.14 15.12 0.00 0.00 0.00
September 33.82 18.06 15.76 54.92 20.08 0.00 0.00 0.00
October 43.82 30.21 13.61 71.14 22.53 0.00 0.00 0.00
November 53.32 38.58 14.74 79.43 30.56 0.00 0.00 0.00
December 59.19 45.90 13.28 89.30 33.52 0.00 0.00 0.00
                 
Annual Sum or Average 35.71 20.40 15.30 53.24 24.67 0.00 0.00 0.00
Minimum of Months 16.66 1.14 13.28 20.24 14.81 0.00 0.00 0.00
Maximum of Months 59.19 45.90 16.92 89.30 33.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 381.34 288.73 92.61 573.58 226.70 0.00 0.00 0.00
February 298.49 192.94 105.55 422.19 199.94 0.00 0.00 0.00
March 232.78 120.83 111.95 325.49 208.01 0.00 0.00 0.00
April 188.55 79.73 108.82 281.13 179.40 0.00 0.00 0.00
May 126.61 18.32 108.28 149.16 162.30 0.00 0.00 0.00
June 108.68 7.89 100.80 130.54 123.86 0.00 0.00 0.00
July 115.28 15.57 99.70 171.46 101.94 0.00 0.00 0.00
August 156.50 56.07 100.44 269.35 103.51 0.00 0.00 0.00
September 228.89 125.32 103.57 373.07 137.63 0.00 0.00 0.00
October 299.67 209.67 90.00 487.88 153.93 0.00 0.00 0.00
November 365.68 267.73 97.95 545.43 209.43 0.00 0.00 0.00
December 406.90 318.59 88.31 615.01 229.57 0.00 0.00 0.00
                 
Annual Sum or Average 242.20 141.60 100.60 361.85 169.51 0.00 0.00 0.00
Minimum of Months 108.68 7.89 88.31 130.54 101.94 0.00 0.00 0.00
Maximum of Months 406.90 318.59 111.95 615.01 229.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 694.39 528.60 165.79 1034.07 454.15 0.00 0.00 0.00
February 544.03 354.54 189.49 756.89 403.32 0.00 0.00 0.00
March 422.49 222.03 200.46 579.79 414.49 0.00 0.00 0.00
April 340.28 146.51 193.77 503.72 346.94 0.00 0.00 0.00
May 225.93 33.67 192.26 260.46 313.00 0.00 0.00 0.00
June 193.09 14.49 178.60 229.07 235.86 0.00 0.00 0.00
July 204.87 28.62 176.25 315.79 179.31 0.00 0.00 0.00
August 281.18 103.03 178.15 494.54 185.19 0.00 0.00 0.00
September 415.05 230.29 184.76 677.60 261.86 0.00 0.00 0.00
October 546.02 384.97 161.05 887.16 300.14 0.00 0.00 0.00
November 665.42 490.15 175.27 983.97 417.40 0.00 0.00 0.00
December 733.96 577.46 156.50 1100.40 461.57 0.00 0.00 0.00
                 
Annual Sum or Average 438.42 259.18 179.24 651.68 330.68 0.00 0.00 0.00
Minimum of Months 193.09 14.49 156.50 229.07 179.31 0.00 0.00 0.00
Maximum of Months 733.96 577.46 200.46 1100.40 461.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 692.74 527.52 165.22 1033.12 455.97 0.00 0.00 0.00
February 541.93 353.55 188.38 755.97 406.36 0.00 0.00 0.00
March 421.89 221.91 199.98 579.19 414.84 0.00 0.00 0.00
April 339.83 146.51 193.32 503.14 346.87 0.00 0.00 0.00
May 225.44 33.67 191.77 259.82 312.96 0.00 0.00 0.00
June 192.61 14.49 178.12 228.42 235.82 0.00 0.00 0.00
July 204.36 28.62 175.74 315.10 179.23 0.00 0.00 0.00
August 280.71 103.03 177.68 493.91 185.09 0.00 0.00 0.00
September 414.59 230.25 184.34 676.98 261.81 0.00 0.00 0.00
October 544.75 384.26 160.49 886.05 301.30 0.00 0.00 0.00
November 662.59 488.16 174.43 982.65 421.32 0.00 0.00 0.00
December 730.80 575.13 155.67 1098.67 465.33 0.00 0.00 0.00
                 
Annual Sum or Average 437.22 258.58 178.64 650.81 331.81 0.00 0.00 0.00
Minimum of Months 192.61 14.49 155.67 228.42 179.23 0.00 0.00 0.00
Maximum of Months 730.80 575.13 199.98 1098.67 465.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 643.28 488.11 155.17 953.25 456.91 0.00 0.00 0.00
February 508.11 330.34 177.78 703.87 410.74 0.00 0.00 0.00
March 401.12 211.15 189.97 546.55 417.65 0.00 0.00 0.00
April 328.18 142.44 185.75 484.34 345.51 0.00 0.00 0.00
May 217.14 33.09 184.06 248.79 312.00 0.00 0.00 0.00
June 185.48 14.28 171.20 219.55 234.86 0.00 0.00 0.00
July 197.48 28.11 169.37 306.36 177.39 0.00 0.00 0.00
August 271.51 100.33 171.18 479.35 182.91 0.00 0.00 0.00
September 398.82 222.05 176.77 649.79 260.16 0.00 0.00 0.00
October 515.26 363.09 152.17 837.83 302.32 0.00 0.00 0.00
November 619.05 454.82 164.24 913.57 423.68 0.00 0.00 0.00
December 678.81 532.31 146.50 1014.68 465.04 0.00 0.00 0.00
                 
Annual Sum or Average 413.25 243.01 170.24 612.92 331.97 0.00 0.00 0.00
Minimum of Months 185.48 14.28 146.50 219.55 177.39 0.00 0.00 0.00
Maximum of Months 678.81 532.31 189.97 1014.68 465.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 48.48 24.45 24.03 61.24 78.67 0.00 0.00 0.00
February 57.84 26.70 31.14 69.73 70.79 0.00 0.00 0.00
March 66.30 29.33 36.97 81.83 71.41 0.00 0.00 0.00
April 91.40 47.59 43.81 127.12 58.31 0.00 0.00 0.00
May 89.79 41.47 48.31 120.79 53.41 0.00 0.00 0.00
June 95.12 47.56 47.56 136.41 40.88 0.00 0.00 0.00
July 100.69 53.88 46.81 157.71 31.71 0.00 0.00 0.00
August 94.47 51.20 43.27 150.80 32.30 0.00 0.00 0.00
September 80.88 43.28 37.60 120.23 43.79 0.00 0.00 0.00
October 61.83 33.76 28.07 92.86 52.52 0.00 0.00 0.00
November 55.85 29.21 26.64 72.05 72.52 0.00 0.00 0.00
December 49.33 26.46 22.87 63.43 79.87 0.00 0.00 0.00
                 
Annual Sum or Average 74.40 37.96 36.44 104.70 57.11 0.00 0.00 0.00
Minimum of Months 48.48 24.45 22.87 61.24 31.71 0.00 0.00 0.00
Maximum of Months 100.69 53.88 48.31 157.71 79.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 196.91 200.59 0.00 0.00 0.00
February 173.53 80.11 93.42 223.10 179.66 0.00 0.00 0.00
March 198.91 88.00 110.91 258.34 185.82 0.00 0.00 0.00
April 274.20 142.78 131.43 392.39 155.72 0.00 0.00 0.00
May 269.35 124.41 144.94 371.16 145.79 0.00 0.00 0.00
June 285.35 142.67 142.68 415.86 114.36 0.00 0.00 0.00
July 302.07 161.63 140.43 472.69 94.06 0.00 0.00 0.00
August 283.40 153.59 129.81 455.75 92.32 0.00 0.00 0.00
September 242.64 129.83 112.81 370.14 117.55 0.00 0.00 0.00
October 185.49 101.27 84.22 289.09 137.07 0.00 0.00 0.00
November 167.55 87.64 79.91 229.67 185.26 0.00 0.00 0.00
December 147.98 79.37 68.61 203.86 202.70 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 323.75 150.76 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 196.91 92.32 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 472.69 202.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 6.75 0.00 6.75 4.45 30.75 0.00 0.00 0.00
February 8.68 0.00 8.68 5.05 27.89 0.00 0.00 0.00
March 10.74 0.00 10.74 7.40 29.11 0.00 0.00 0.00
April 12.29 0.05 12.23 9.86 23.82 0.00 0.00 0.00
May 15.03 0.79 14.24 12.41 21.20 0.00 0.00 0.00
June 16.29 1.85 14.44 17.35 16.63 0.00 0.00 0.00
July 15.11 1.52 13.60 19.34 13.57 0.00 0.00 0.00
August 12.27 0.29 11.98 16.06 13.29 0.00 0.00 0.00
September 10.34 0.00 10.34 11.14 17.98 0.00 0.00 0.00
October 8.28 0.00 8.28 10.16 20.60 0.00 0.00 0.00
November 7.34 0.00 7.34 4.87 28.61 0.00 0.00 0.00
December 6.23 0.00 6.23 4.02 31.06 0.00 0.00 0.00
                 
Annual Sum or Average 10.79 0.38 10.41 10.21 22.85 0.00 0.00 0.00
Minimum of Months 6.23 0.00 6.23 4.02 13.29 0.00 0.00 0.00
Maximum of Months 16.29 1.85 14.44 19.34 31.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.96 0.00 49.96 34.65 214.07 0.00 0.00 0.00
February 63.78 0.00 63.78 39.65 193.83 0.00 0.00 0.00
March 78.74 0.00 78.74 56.95 202.33 0.00 0.00 0.00
April 90.22 0.37 89.86 74.84 165.98 0.00 0.00 0.00
May 109.71 5.49 104.22 93.90 148.24 0.00 0.00 0.00
June 118.35 12.85 105.50 128.02 116.31 0.00 0.00 0.00
July 110.45 10.52 99.93 142.08 95.32 0.00 0.00 0.00
August 90.29 2.04 88.24 118.72 93.53 0.00 0.00 0.00
September 76.20 0.01 76.18 83.76 125.92 0.00 0.00 0.00
October 60.86 0.00 60.86 75.41 144.27 0.00 0.00 0.00
November 54.25 0.00 54.25 38.10 199.14 0.00 0.00 0.00
December 46.21 0.00 46.21 31.57 216.35 0.00 0.00 0.00
                 
Annual Sum or Average 79.15 2.62 76.53 76.72 159.41 0.00 0.00 0.00
Minimum of Months 46.21 0.00 46.21 31.57 93.53 0.00 0.00 0.00
Maximum of Months 118.35 12.85 105.50 142.08 216.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.80 0.00 80.80 44.06 422.66 0.00 0.00 0.00
February 103.85 0.00 103.85 48.12 387.71 0.00 0.00 0.00
March 128.79 0.00 128.79 75.64 402.14 0.00 0.00 0.00
April 147.18 0.32 146.86 111.01 322.54 0.00 0.00 0.00
May 176.09 6.63 169.46 136.77 295.10 0.00 0.00 0.00
June 189.00 17.24 171.76 196.67 230.69 0.00 0.00 0.00
July 176.18 14.13 162.05 236.94 172.38 0.00 0.00 0.00
August 145.98 2.43 143.55 202.79 167.22 0.00 0.00 0.00
September 124.30 0.02 124.28 131.94 235.31 0.00 0.00 0.00
October 99.52 0.00 99.52 117.44 278.75 0.00 0.00 0.00
November 87.75 0.00 87.75 48.66 392.29 0.00 0.00 0.00
December 74.51 0.00 74.51 40.47 427.55 0.00 0.00 0.00
                 
Annual Sum or Average 127.92 3.42 124.51 116.36 310.74 0.00 0.00 0.00
Minimum of Months 74.51 0.00 74.51 40.47 167.22 0.00 0.00 0.00
Maximum of Months 189.00 17.24 171.76 236.94 427.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.23 0.00 85.23 47.62 426.16 0.00 0.00 0.00
February 109.60 0.00 109.60 53.64 389.43 0.00 0.00 0.00
March 135.76 0.00 135.76 83.33 403.03 0.00 0.00 0.00
April 154.98 0.57 154.42 118.16 322.05 0.00 0.00 0.00
May 188.34 9.02 179.31 149.46 290.06 0.00 0.00 0.00
June 201.98 20.53 181.46 214.12 228.70 0.00 0.00 0.00
July 187.84 16.96 170.88 253.54 172.75 0.00 0.00 0.00
August 154.33 3.38 150.95 211.77 167.07 0.00 0.00 0.00
September 130.52 0.02 130.50 139.05 237.69 0.00 0.00 0.00
October 104.57 0.00 104.57 122.60 282.24 0.00 0.00 0.00
November 92.59 0.00 92.59 52.91 395.51 0.00 0.00 0.00
December 78.60 0.00 78.60 43.02 431.41 0.00 0.00 0.00
                 
Annual Sum or Average 135.47 4.23 131.24 124.60 311.72 0.00 0.00 0.00
Minimum of Months 78.60 0.00 78.60 43.02 167.07 0.00 0.00 0.00
Maximum of Months 201.98 20.53 181.46 253.54 431.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.46 0.00 85.46 47.83 426.24 0.00 0.00 0.00
February 109.86 0.00 109.86 53.92 389.47 0.00 0.00 0.00
March 136.06 0.00 136.06 83.70 403.04 0.00 0.00 0.00
April 155.56 0.66 154.90 118.61 321.59 0.00 0.00 0.00
May 190.46 10.04 180.43 150.31 286.91 0.00 0.00 0.00
June 204.92 22.37 182.55 215.56 224.74 0.00 0.00 0.00
July 190.53 18.60 171.92 255.18 169.37 0.00 0.00 0.00
August 155.37 3.76 151.61 212.48 165.91 0.00 0.00 0.00
September 130.87 0.02 130.84 139.48 237.73 0.00 0.00 0.00
October 104.82 0.00 104.82 122.89 282.35 0.00 0.00 0.00
November 92.84 0.00 92.84 53.16 395.59 0.00 0.00 0.00
December 78.82 0.00 78.82 43.19 431.50 0.00 0.00 0.00
                 
Annual Sum or Average 136.41 4.65 131.76 125.20 310.74 0.00 0.00 0.00
Minimum of Months 78.82 0.00 78.82 43.19 165.91 0.00 0.00 0.00
Maximum of Months 204.92 22.37 182.55 255.18 431.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 175.41 231.61 0.00 0.00 0.00
February 173.53 80.11 93.42 205.87 201.26 0.00 0.00 0.00
March 198.91 88.00 110.91 244.92 200.05 0.00 0.00 0.00
April 274.20 142.78 131.43 380.31 166.76 0.00 0.00 0.00
May 269.35 124.41 144.94 367.73 148.37 0.00 0.00 0.00
June 285.35 142.67 142.68 416.28 113.60 0.00 0.00 0.00
July 302.07 161.63 140.43 470.62 94.84 0.00 0.00 0.00
August 283.40 153.59 129.81 446.57 99.05 0.00 0.00 0.00
September 242.64 129.83 112.81 355.47 131.82 0.00 0.00 0.00
October 185.49 101.27 84.22 273.21 155.48 0.00 0.00 0.00
November 167.55 87.64 79.91 209.13 212.87 0.00 0.00 0.00
December 147.98 79.37 68.61 181.02 236.19 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 311.08 165.81 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 175.41 94.84 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 470.62 236.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 55.73 41.72 14.01 83.54 33.23 0.00 0.00 0.00
February 43.77 27.81 15.96 61.71 29.34 0.00 0.00 0.00
March 34.42 17.41 17.01 47.98 30.43 0.00 0.00 0.00
April 28.20 11.49 16.72 41.66 26.34 0.00 0.00 0.00
May 19.37 2.64 16.73 22.74 23.79 0.00 0.00 0.00
June 16.77 1.14 15.63 20.12 18.17 0.00 0.00 0.00
July 17.77 2.24 15.53 26.17 15.01 0.00 0.00 0.00
August 23.62 8.08 15.54 40.08 15.35 0.00 0.00 0.00
September 33.91 18.06 15.85 54.90 20.34 0.00 0.00 0.00
October 43.91 30.23 13.68 71.16 22.69 0.00 0.00 0.00
November 53.47 38.65 14.83 79.51 30.72 0.00 0.00 0.00
December 59.48 46.10 13.38 89.56 33.69 0.00 0.00 0.00
                 
Annual Sum or Average 35.83 20.44 15.40 53.24 24.90 0.00 0.00 0.00
Minimum of Months 16.77 1.14 13.38 20.12 15.01 0.00 0.00 0.00
Maximum of Months 59.48 46.10 17.01 89.56 33.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 383.18 289.55 93.64 575.03 228.08 0.00 0.00 0.00
February 299.59 193.01 106.58 422.52 201.81 0.00 0.00 0.00
March 233.95 120.84 113.11 326.07 209.95 0.00 0.00 0.00
April 189.92 79.73 110.19 281.56 181.79 0.00 0.00 0.00
May 128.09 18.32 109.77 149.39 164.89 0.00 0.00 0.00
June 110.14 7.89 102.26 130.69 125.99 0.00 0.00 0.00
July 116.82 15.57 101.24 172.25 103.49 0.00 0.00 0.00
August 157.92 56.07 101.85 269.90 105.28 0.00 0.00 0.00
September 230.12 125.32 104.80 373.75 139.60 0.00 0.00 0.00
October 300.74 209.78 90.96 488.62 155.26 0.00 0.00 0.00
November 367.22 268.21 99.00 546.58 210.81 0.00 0.00 0.00
December 409.33 319.95 89.38 617.27 231.03 0.00 0.00 0.00
                 
Annual Sum or Average 243.68 141.84 101.84 362.64 171.33 0.00 0.00 0.00
Minimum of Months 110.14 7.89 89.38 130.69 103.49 0.00 0.00 0.00
Maximum of Months 409.33 319.95 113.11 617.27 231.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 699.02 531.01 168.00 1037.13 458.53 0.00 0.00 0.00
February 546.23 354.74 191.49 756.28 409.88 0.00 0.00 0.00
March 424.76 222.06 202.69 578.87 422.14 0.00 0.00 0.00
April 342.92 146.52 196.40 503.10 354.78 0.00 0.00 0.00
May 228.78 33.67 195.11 258.75 321.78 0.00 0.00 0.00
June 195.90 14.49 181.41 226.52 243.78 0.00 0.00 0.00
July 207.82 28.62 179.20 315.12 184.50 0.00 0.00 0.00
August 283.90 103.03 180.87 493.38 190.89 0.00 0.00 0.00
September 417.42 230.30 187.12 676.96 268.78 0.00 0.00 0.00
October 548.25 385.34 162.91 888.32 304.63 0.00 0.00 0.00
November 669.40 491.86 177.54 986.40 421.35 0.00 0.00 0.00
December 741.82 582.59 159.23 1107.87 465.15 0.00 0.00 0.00
                 
Annual Sum or Average 441.72 260.01 181.71 652.13 336.75 0.00 0.00 0.00
Minimum of Months 195.90 14.49 159.23 226.52 184.50 0.00 0.00 0.00
Maximum of Months 741.82 582.59 202.69 1107.87 465.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 697.28 529.82 167.47 1036.22 460.57 0.00 0.00 0.00
February 544.62 353.96 190.66 755.82 412.41 0.00 0.00 0.00
March 424.23 221.94 202.28 578.37 422.46 0.00 0.00 0.00
April 342.53 146.51 196.02 502.60 354.70 0.00 0.00 0.00
May 228.37 33.67 194.70 258.22 321.73 0.00 0.00 0.00
June 195.50 14.49 181.01 225.98 243.73 0.00 0.00 0.00
July 207.40 28.62 178.78 314.54 184.42 0.00 0.00 0.00
August 283.51 103.03 180.48 492.83 190.79 0.00 0.00 0.00
September 417.01 230.25 186.76 676.41 268.74 0.00 0.00 0.00
October 546.94 384.55 162.38 887.12 305.85 0.00 0.00 0.00
November 666.41 489.67 176.74 985.17 425.73 0.00 0.00 0.00
December 737.98 579.67 158.31 1105.62 469.66 0.00 0.00 0.00
                 
Annual Sum or Average 440.52 259.34 181.18 651.31 337.96 0.00 0.00 0.00
Minimum of Months 195.50 14.49 158.31 225.98 184.42 0.00 0.00 0.00
Maximum of Months 737.98 579.67 202.28 1105.62 469.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 645.51 489.02 156.49 953.72 462.33 0.00 0.00 0.00
February 509.79 330.57 179.22 702.81 417.11 0.00 0.00 0.00
March 402.57 211.16 191.42 544.62 425.17 0.00 0.00 0.00
April 329.87 142.43 187.44 482.53 353.20 0.00 0.00 0.00
May 218.98 33.08 185.90 245.84 320.75 0.00 0.00 0.00
June 187.29 14.28 173.01 215.73 242.74 0.00 0.00 0.00
July 199.39 28.11 171.28 304.28 182.41 0.00 0.00 0.00
August 273.27 100.33 172.94 476.87 188.39 0.00 0.00 0.00
September 400.34 222.05 178.30 648.01 266.83 0.00 0.00 0.00
October 516.65 363.26 153.39 837.86 306.51 0.00 0.00 0.00
November 621.32 455.65 165.67 914.53 428.64 0.00 0.00 0.00
December 683.03 534.87 148.16 1017.89 470.13 0.00 0.00 0.00
                 
Annual Sum or Average 415.23 243.40 171.83 611.83 338.21 0.00 0.00 0.00
Minimum of Months 187.29 14.28 148.16 215.73 182.41 0.00 0.00 0.00
Maximum of Months 683.03 534.87 191.42 1017.89 470.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 48.48 24.45 24.03 60.81 79.75 0.00 0.00 0.00
February 57.84 26.70 31.14 69.16 72.04 0.00 0.00 0.00
March 66.30 29.33 36.97 81.12 72.72 0.00 0.00 0.00
April 91.40 47.59 43.81 126.20 59.56 0.00 0.00 0.00
May 89.79 41.47 48.31 119.70 54.68 0.00 0.00 0.00
June 95.12 47.56 47.56 135.22 42.05 0.00 0.00 0.00
July 100.69 53.88 46.81 156.76 32.51 0.00 0.00 0.00
August 94.47 51.20 43.27 149.90 33.15 0.00 0.00 0.00
September 80.88 43.28 37.60 119.43 44.89 0.00 0.00 0.00
October 61.83 33.76 28.07 92.53 53.14 0.00 0.00 0.00
November 55.85 29.21 26.64 71.60 73.58 0.00 0.00 0.00
December 49.33 26.46 22.87 63.03 81.01 0.00 0.00 0.00
                 
Annual Sum or Average 74.40 37.96 36.44 103.97 58.18 0.00 0.00 0.00
Minimum of Months 48.48 24.45 22.87 60.81 32.51 0.00 0.00 0.00
Maximum of Months 100.69 53.88 48.31 156.76 81.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 8.72 0.00 8.72 6.44 31.82 0.00 0.00 0.00
February 10.95 0.00 10.95 7.61 28.67 0.00 0.00 0.00
March 13.41 0.00 13.41 10.68 29.70 0.00 0.00 0.00
April 15.45 0.06 15.39 13.69 24.57 0.00 0.00 0.00
May 18.57 0.86 17.71 17.01 21.98 0.00 0.00 0.00
June 19.79 1.93 17.85 21.90 17.23 0.00 0.00 0.00
July 18.74 1.57 17.17 24.09 14.41 0.00 0.00 0.00
August 15.56 0.31 15.25 20.36 14.23 0.00 0.00 0.00
September 13.17 0.00 13.17 14.82 18.94 0.00 0.00 0.00
October 10.45 0.00 10.45 12.71 21.71 0.00 0.00 0.00
November 9.46 0.00 9.46 7.15 29.62 0.00 0.00 0.00
December 8.12 0.00 8.12 5.81 32.26 0.00 0.00 0.00
                 
Annual Sum or Average 13.54 0.40 13.15 13.56 23.73 0.00 0.00 0.00
Minimum of Months 8.12 0.00 8.12 5.81 14.23 0.00 0.00 0.00
Maximum of Months 19.79 1.93 17.85 24.09 32.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 145.45 73.36 72.09 196.54 200.86 0.00 0.00 0.00
February 173.53 80.11 93.42 222.38 180.40 0.00 0.00 0.00
March 198.91 88.00 110.91 257.34 186.81 0.00 0.00 0.00
April 274.20 142.78 131.43 390.78 157.15 0.00 0.00 0.00
May 269.35 124.41 144.94 368.84 147.70 0.00 0.00 0.00
June 285.35 142.67 142.68 413.80 115.95 0.00 0.00 0.00
July 302.07 161.63 140.43 470.65 95.38 0.00 0.00 0.00
August 283.40 153.59 129.81 454.11 93.42 0.00 0.00 0.00
September 242.64 129.83 112.81 369.06 118.55 0.00 0.00 0.00
October 185.49 101.27 84.22 288.67 137.37 0.00 0.00 0.00
November 167.55 87.64 79.91 229.30 185.54 0.00 0.00 0.00
December 147.98 79.37 68.61 203.66 202.87 0.00 0.00 0.00
                 
Annual Sum or Average 223.19 113.87 109.32 322.60 151.68 0.00 0.00 0.00
Minimum of Months 145.45 73.36 68.61 196.54 93.42 0.00 0.00 0.00
Maximum of Months 302.07 161.63 144.94 470.65 202.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 60.28 0.00 60.28 45.33 219.28 0.00 0.00 0.00
February 75.67 0.00 75.67 53.24 197.67 0.00 0.00 0.00
March 92.72 0.00 92.72 74.25 205.18 0.00 0.00 0.00
April 106.83 0.41 106.42 94.91 169.87 0.00 0.00 0.00
May 128.37 5.98 122.40 117.60 151.97 0.00 0.00 0.00
June 136.79 13.37 123.42 151.40 119.14 0.00 0.00 0.00
July 129.52 10.86 118.66 166.57 99.59 0.00 0.00 0.00
August 107.56 2.15 105.41 140.88 98.39 0.00 0.00 0.00
September 91.04 0.01 91.03 102.95 130.89 0.00 0.00 0.00
October 72.22 0.00 72.22 88.73 149.78 0.00 0.00 0.00
November 65.39 0.00 65.39 50.32 204.10 0.00 0.00 0.00
December 56.12 0.00 56.12 41.26 222.26 0.00 0.00 0.00
                 
Annual Sum or Average 93.62 2.75 90.87 94.22 163.82 0.00 0.00 0.00
Minimum of Months 56.12 0.00 56.12 41.26 98.39 0.00 0.00 0.00
Maximum of Months 136.79 13.37 123.42 166.57 222.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.44 0.00 73.44 48.28 289.03 0.00 0.00 0.00
February 92.19 0.00 92.19 57.30 262.37 0.00 0.00 0.00
March 112.97 0.00 112.97 83.01 269.92 0.00 0.00 0.00
April 130.15 0.50 129.65 111.44 218.28 0.00 0.00 0.00
May 156.40 7.28 149.12 138.60 195.70 0.00 0.00 0.00
June 166.66 16.29 150.36 181.83 152.46 0.00 0.00 0.00
July 157.80 13.23 144.57 210.08 118.56 0.00 0.00 0.00
August 131.05 2.62 128.42 177.55 117.18 0.00 0.00 0.00
September 110.92 0.02 110.90 123.98 164.83 0.00 0.00 0.00
October 87.98 0.00 87.98 103.24 194.89 0.00 0.00 0.00
November 79.66 0.00 79.66 54.44 268.45 0.00 0.00 0.00
December 68.37 0.00 68.37 43.29 293.08 0.00 0.00 0.00
                 
Annual Sum or Average 114.06 3.35 110.71 111.46 211.77 0.00 0.00 0.00
Minimum of Months 68.37 0.00 68.37 43.29 117.18 0.00 0.00 0.00
Maximum of Months 166.66 16.29 150.36 210.08 293.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.44 0.00 73.44 48.28 289.03 0.00 0.00 0.00
February 92.19 0.00 92.19 57.30 262.37 0.00 0.00 0.00
March 112.97 0.00 112.97 83.01 269.92 0.00 0.00 0.00
April 130.15 0.50 129.65 111.44 218.28 0.00 0.00 0.00
May 156.40 7.28 149.12 138.60 195.70 0.00 0.00 0.00
June 166.66 16.29 150.36 181.83 152.46 0.00 0.00 0.00
July 157.80 13.23 144.57 210.08 118.56 0.00 0.00 0.00
August 131.05 2.62 128.42 177.55 117.18 0.00 0.00 0.00
September 110.92 0.02 110.90 123.98 164.83 0.00 0.00 0.00
October 87.98 0.00 87.98 103.24 194.89 0.00 0.00 0.00
November 79.66 0.00 79.66 54.44 268.45 0.00 0.00 0.00
December 68.37 0.00 68.37 43.29 293.08 0.00 0.00 0.00
                 
Annual Sum or Average 114.06 3.35 110.71 111.46 211.77 0.00 0.00 0.00
Minimum of Months 68.37 0.00 68.37 43.29 117.18 0.00 0.00 0.00
Maximum of Months 166.66 16.29 150.36 210.08 293.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.44 0.00 73.44 48.28 289.02 0.00 0.00 0.00
February 92.19 0.00 92.19 57.30 262.36 0.00 0.00 0.00
March 112.97 0.00 112.97 83.01 269.91 0.00 0.00 0.00
April 130.15 0.50 129.65 111.44 218.27 0.00 0.00 0.00
May 156.40 7.28 149.12 138.60 195.69 0.00 0.00 0.00
June 166.65 16.29 150.36 181.83 152.45 0.00 0.00 0.00
July 157.79 13.23 144.57 210.07 118.56 0.00 0.00 0.00
August 131.04 2.62 128.42 177.55 117.18 0.00 0.00 0.00
September 110.91 0.02 110.90 123.98 164.83 0.00 0.00 0.00
October 87.98 0.00 87.98 103.24 194.88 0.00 0.00 0.00
November 79.66 0.00 79.66 54.44 268.44 0.00 0.00 0.00
December 68.37 0.00 68.37 43.29 293.07 0.00 0.00 0.00
                 
Annual Sum or Average 114.05 3.35 110.71 111.45 211.76 0.00 0.00 0.00
Minimum of Months 68.37 0.00 68.37 43.29 117.18 0.00 0.00 0.00
Maximum of Months 166.65 16.29 150.36 210.07 293.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 8.28 0.00 8.28 4.90 34.91 0.00 0.00 0.00
February 10.40 0.00 10.40 5.84 32.10 0.00 0.00 0.00
March 12.74 0.00 12.74 8.69 32.80 0.00 0.00 0.00
April 14.68 0.06 14.62 11.95 26.48 0.00 0.00 0.00
May 17.64 0.82 16.82 15.12 23.32 0.00 0.00 0.00
June 18.79 1.84 16.96 19.88 18.33 0.00 0.00 0.00
July 17.79 1.49 16.30 23.38 13.99 0.00 0.00 0.00
August 14.78 0.30 14.48 19.43 14.17 0.00 0.00 0.00
September 12.51 0.00 12.51 13.25 20.31 0.00 0.00 0.00
October 9.92 0.00 9.92 11.48 23.21 0.00 0.00 0.00
November 8.98 0.00 8.98 5.54 32.73 0.00 0.00 0.00
December 7.71 0.00 7.71 4.30 35.61 0.00 0.00 0.00
                 
Annual Sum or Average 12.86 0.38 12.48 12.02 25.62 0.00 0.00 0.00
Minimum of Months 7.71 0.00 7.71 4.30 13.99 0.00 0.00 0.00
Maximum of Months 18.79 1.84 16.96 23.38 35.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.02 0.00 105.02 62.16 442.73 0.00 0.00 0.00
February 131.83 0.00 131.83 74.07 407.11 0.00 0.00 0.00
March 161.55 0.00 161.55 110.18 415.92 0.00 0.00 0.00
April 186.13 0.72 185.41 151.52 335.76 0.00 0.00 0.00
May 223.66 10.42 213.25 191.75 295.71 0.00 0.00 0.00
June 238.33 23.30 215.03 252.16 232.42 0.00 0.00 0.00
July 225.66 18.91 206.74 296.50 177.42 0.00 0.00 0.00
August 187.40 3.75 183.65 246.37 179.70 0.00 0.00 0.00
September 158.62 0.02 158.59 168.06 257.57 0.00 0.00 0.00
October 125.82 0.00 125.82 145.55 294.31 0.00 0.00 0.00
November 113.92 0.00 113.92 70.31 415.06 0.00 0.00 0.00
December 97.77 0.00 97.77 54.55 451.61 0.00 0.00 0.00
                 
Annual Sum or Average 163.11 4.79 158.32 152.48 324.94 0.00 0.00 0.00
Minimum of Months 97.77 0.00 97.77 54.55 177.42 0.00 0.00 0.00
Maximum of Months 238.33 23.30 215.03 296.50 451.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.21 10.77 8.44 24.43 37.78 0.00 0.00 0.00
February 23.10 12.14 10.96 27.17 36.54 0.00 0.00 0.00
March 27.13 13.92 13.21 32.07 37.32 0.00 0.00 0.00
April 36.82 21.36 15.45 51.00 30.47 0.00 0.00 0.00
May 29.92 14.17 15.75 38.28 28.86 0.00 0.00 0.00
June 28.59 13.21 15.38 38.96 22.69 0.00 0.00 0.00
July 32.29 16.72 15.57 48.69 18.58 0.00 0.00 0.00
August 35.61 20.54 15.07 55.46 18.66 0.00 0.00 0.00
September 34.05 20.19 13.86 50.64 22.08 0.00 0.00 0.00
October 25.65 15.58 10.07 39.47 24.49 0.00 0.00 0.00
November 21.99 12.64 9.35 28.44 35.71 0.00 0.00 0.00
December 18.26 10.43 7.83 23.69 38.99 0.00 0.00 0.00
                 
Annual Sum or Average 27.73 15.15 12.58 38.24 29.31 0.00 0.00 0.00
Minimum of Months 18.26 10.43 7.83 23.69 18.58 0.00 0.00 0.00
Maximum of Months 36.82 21.36 15.75 55.46 38.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 59.19 19.90 39.30 53.12 206.44 0.00 0.00 0.00
February 83.97 31.43 52.54 75.81 197.48 0.00 0.00 0.00
March 122.95 53.57 69.38 130.67 199.18 0.00 0.00 0.00
April 195.99 109.07 86.92 264.17 160.43 0.00 0.00 0.00
May 194.72 98.31 96.41 254.49 148.71 0.00 0.00 0.00
June 206.26 110.87 95.40 291.00 116.56 0.00 0.00 0.00
July 220.50 126.52 93.98 334.86 96.95 0.00 0.00 0.00
August 206.44 119.67 86.77 317.12 98.53 0.00 0.00 0.00
September 163.37 90.44 72.93 233.50 117.85 0.00 0.00 0.00
October 99.32 48.53 50.80 142.47 133.62 0.00 0.00 0.00
November 70.17 26.55 43.62 68.00 194.97 0.00 0.00 0.00
December 51.72 15.99 35.73 44.08 213.38 0.00 0.00 0.00
                 
Annual Sum or Average 139.79 71.08 68.71 184.67 156.78 0.00 0.00 0.00
Minimum of Months 51.72 15.99 35.73 44.08 96.95 0.00 0.00 0.00
Maximum of Months 220.50 126.52 96.41 334.86 213.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.43 39.92 14.50 81.36 32.52 0.00 0.00 0.00
February 42.78 26.35 16.43 60.83 28.88 0.00 0.00 0.00
March 34.10 16.47 17.63 48.45 29.41 0.00 0.00 0.00
April 28.49 10.86 17.63 42.70 24.85 0.00 0.00 0.00
May 20.29 2.50 17.79 25.23 22.30 0.00 0.00 0.00
June 17.80 1.07 16.72 22.21 17.22 0.00 0.00 0.00
July 18.85 2.12 16.73 26.90 15.23 0.00 0.00 0.00
August 24.22 7.64 16.58 39.40 16.28 0.00 0.00 0.00
September 33.71 17.08 16.63 54.19 20.16 0.00 0.00 0.00
October 42.87 28.66 14.21 68.78 22.85 0.00 0.00 0.00
November 52.10 36.78 15.32 77.43 30.10 0.00 0.00 0.00
December 58.15 44.26 13.89 86.95 33.07 0.00 0.00 0.00
                 
Annual Sum or Average 35.62 19.45 16.17 52.84 24.38 0.00 0.00 0.00
Minimum of Months 17.80 1.07 13.89 22.21 15.23 0.00 0.00 0.00
Maximum of Months 58.15 44.26 17.79 86.95 33.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 734.87 539.06 195.81 1098.51 439.05 0.00 0.00 0.00
February 577.57 355.75 221.82 821.29 389.90 0.00 0.00 0.00
March 460.46 222.42 238.03 654.11 397.05 0.00 0.00 0.00
April 384.72 146.70 238.02 576.54 335.48 0.00 0.00 0.00
May 273.95 33.71 240.24 340.68 301.12 0.00 0.00 0.00
June 240.33 14.51 225.82 299.82 232.57 0.00 0.00 0.00
July 254.57 28.66 225.92 363.19 205.60 0.00 0.00 0.00
August 327.05 103.16 223.89 531.91 219.78 0.00 0.00 0.00
September 455.09 230.61 224.48 731.60 272.18 0.00 0.00 0.00
October 578.77 386.93 191.85 928.61 308.49 0.00 0.00 0.00
November 703.44 496.62 206.82 1045.42 406.41 0.00 0.00 0.00
December 785.08 597.55 187.53 1173.98 446.51 0.00 0.00 0.00
                 
Annual Sum or Average 480.92 262.66 218.26 713.47 329.21 0.00 0.00 0.00
Minimum of Months 240.33 14.51 187.53 299.82 205.60 0.00 0.00 0.00
Maximum of Months 785.08 597.55 240.24 1173.98 446.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.32 44.76 56.56 108.76 263.96 0.00 0.00 0.00
February 132.87 57.94 74.93 134.71 253.53 0.00 0.00 0.00
March 176.26 80.88 95.38 192.46 262.10 0.00 0.00 0.00
April 264.43 148.03 116.40 345.83 223.45 0.00 0.00 0.00
May 253.42 126.09 127.33 313.67 210.37 0.00 0.00 0.00
June 264.49 138.91 125.58 350.52 171.14 0.00 0.00 0.00
July 284.50 160.47 124.04 412.65 144.24 0.00 0.00 0.00
August 273.64 158.16 115.48 404.10 145.99 0.00 0.00 0.00
September 227.66 128.29 99.37 313.59 171.80 0.00 0.00 0.00
October 151.82 81.14 70.68 211.39 189.54 0.00 0.00 0.00
November 117.92 55.20 62.72 129.21 254.60 0.00 0.00 0.00
December 92.43 40.62 51.81 98.96 272.60 0.00 0.00 0.00
                 
Annual Sum or Average 195.32 101.89 93.42 251.91 213.37 0.00 0.00 0.00
Minimum of Months 92.43 40.62 51.81 98.96 144.24 0.00 0.00 0.00
Maximum of Months 284.50 160.47 127.33 412.65 272.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 356.57 190.70 165.87 402.64 583.21 0.00 0.00 0.00
February 376.14 172.31 203.83 399.83 532.63 0.00 0.00 0.00
March 456.91 203.57 253.33 517.40 533.49 0.00 0.00 0.00
April 584.15 292.96 291.19 766.56 435.84 0.00 0.00 0.00
May 551.27 230.06 321.21 693.78 394.00 0.00 0.00 0.00
June 547.84 237.70 310.14 743.51 314.21 0.00 0.00 0.00
July 620.74 308.46 312.28 913.50 279.46 0.00 0.00 0.00
August 613.03 325.62 287.41 914.73 286.42 0.00 0.00 0.00
September 446.34 204.53 241.81 614.86 349.84 0.00 0.00 0.00
October 395.09 203.07 192.02 554.60 390.66 0.00 0.00 0.00
November 360.17 182.98 177.19 405.39 542.60 0.00 0.00 0.00
December 343.59 190.90 152.69 384.44 593.62 0.00 0.00 0.00
                 
Annual Sum or Average 471.62 229.02 242.59 610.74 435.82 0.00 0.00 0.00
Minimum of Months 343.59 172.31 152.69 384.44 279.46 0.00 0.00 0.00
Maximum of Months 620.74 325.62 321.21 914.73 593.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.04 39.64 14.40 78.84 34.99 0.00 0.00 0.00
February 42.47 26.16 16.31 57.89 32.35 0.00 0.00 0.00
March 33.86 16.36 17.50 44.99 33.91 0.00 0.00 0.00
April 28.29 10.79 17.50 39.78 28.64 0.00 0.00 0.00
May 20.15 2.48 17.67 21.91 26.25 0.00 0.00 0.00
June 17.67 1.07 16.61 19.09 20.51 0.00 0.00 0.00
July 18.72 2.11 16.61 24.01 17.99 0.00 0.00 0.00
August 24.05 7.59 16.46 37.07 18.64 0.00 0.00 0.00
September 33.47 16.96 16.51 52.50 22.15 0.00 0.00 0.00
October 42.56 28.45 14.11 67.60 24.00 0.00 0.00 0.00
November 51.73 36.52 15.21 75.07 32.51 0.00 0.00 0.00
December 57.73 43.94 13.79 84.73 35.25 0.00 0.00 0.00
                 
Annual Sum or Average 35.37 19.32 16.05 50.27 27.24 0.00 0.00 0.00
Minimum of Months 17.67 1.07 13.79 19.09 17.99 0.00 0.00 0.00
Maximum of Months 57.73 43.94 17.67 84.73 35.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 818.31 600.27 218.04 1193.89 529.77 0.00 0.00 0.00
February 643.15 396.14 247.00 876.57 489.85 0.00 0.00 0.00
March 512.74 247.68 265.06 681.21 513.50 0.00 0.00 0.00
April 428.41 163.35 265.05 602.30 433.60 0.00 0.00 0.00
May 305.06 37.54 267.52 331.82 397.16 0.00 0.00 0.00
June 267.62 16.16 251.46 289.05 310.35 0.00 0.00 0.00
July 283.48 31.91 251.57 363.60 272.17 0.00 0.00 0.00
August 364.19 114.88 249.31 561.38 282.15 0.00 0.00 0.00
September 506.76 256.79 249.97 795.01 335.43 0.00 0.00 0.00
October 644.49 430.86 213.63 1023.68 363.45 0.00 0.00 0.00
November 783.31 553.00 230.30 1136.67 492.22 0.00 0.00 0.00
December 874.21 665.39 208.82 1283.00 533.83 0.00 0.00 0.00
                 
Annual Sum or Average 535.53 292.48 243.05 761.18 412.38 0.00 0.00 0.00
Minimum of Months 267.62 16.16 208.82 289.05 272.17 0.00 0.00 0.00
Maximum of Months 874.21 665.39 267.52 1283.00 533.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 41.01 26.53 14.48 45.78 44.79 0.00 0.00 0.00
February 49.23 28.06 21.17 53.75 39.32 0.00 0.00 0.00
March 62.71 35.51 27.20 71.71 38.61 0.00 0.00 0.00
April 96.20 70.18 26.02 117.32 32.88 0.00 0.00 0.00
May 94.92 61.02 33.90 114.59 29.86 0.00 0.00 0.00
June 101.26 69.85 31.42 125.64 23.76 0.00 0.00 0.00
July 111.17 83.44 27.73 141.13 22.48 0.00 0.00 0.00
August 102.60 78.70 23.90 131.08 23.38 0.00 0.00 0.00
September 78.30 55.63 22.67 97.84 27.29 0.00 0.00 0.00
October 56.29 39.03 17.26 69.94 31.58 0.00 0.00 0.00
November 45.01 28.75 16.26 50.74 41.49 0.00 0.00 0.00
December 38.16 25.51 12.65 41.97 46.19 0.00 0.00 0.00
                 
Annual Sum or Average 73.19 50.30 22.89 88.64 33.44 0.00 0.00 0.00
Minimum of Months 38.16 25.51 12.65 41.97 22.48 0.00 0.00 0.00
Maximum of Months 111.17 83.44 33.90 141.13 46.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.48 12.03 10.46 25.29 37.44 0.00 0.00 0.00
February 23.72 10.87 12.85 24.72 35.21 0.00 0.00 0.00
March 28.81 12.84 15.97 31.81 35.49 0.00 0.00 0.00
April 36.83 18.47 18.36 47.24 29.29 0.00 0.00 0.00
May 34.76 14.51 20.25 42.30 26.79 0.00 0.00 0.00
June 34.55 14.99 19.56 45.60 21.50 0.00 0.00 0.00
July 39.14 19.45 19.69 56.41 19.22 0.00 0.00 0.00
August 38.66 20.53 18.12 56.86 19.32 0.00 0.00 0.00
September 28.14 12.90 15.25 38.27 23.09 0.00 0.00 0.00
October 24.91 12.80 12.11 34.75 25.13 0.00 0.00 0.00
November 22.71 11.54 11.17 25.37 34.78 0.00 0.00 0.00
December 21.67 12.04 9.63 24.21 37.82 0.00 0.00 0.00
                 
Annual Sum or Average 29.74 14.44 15.30 37.83 28.72 0.00 0.00 0.00
Minimum of Months 21.67 10.87 9.63 24.21 19.22 0.00 0.00 0.00
Maximum of Months 39.14 20.53 20.25 56.86 37.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 266.14 142.33 123.80 299.59 442.84 0.00 0.00 0.00
February 280.75 128.61 152.14 293.03 416.55 0.00 0.00 0.00
March 341.03 151.94 189.09 377.29 419.85 0.00 0.00 0.00
April 436.00 218.66 217.34 560.77 346.65 0.00 0.00 0.00
May 411.46 171.71 239.75 501.95 317.15 0.00 0.00 0.00
June 408.90 177.41 231.49 541.03 254.55 0.00 0.00 0.00
July 463.31 230.23 233.09 669.33 227.54 0.00 0.00 0.00
August 457.56 243.03 214.53 674.79 228.77 0.00 0.00 0.00
September 333.14 152.65 180.49 454.46 273.23 0.00 0.00 0.00
October 294.89 151.56 143.33 412.26 297.41 0.00 0.00 0.00
November 268.83 136.57 132.25 300.73 411.53 0.00 0.00 0.00
December 256.45 142.49 113.97 286.86 447.50 0.00 0.00 0.00
                 
Annual Sum or Average 352.01 170.94 181.07 448.76 339.88 0.00 0.00 0.00
Minimum of Months 256.45 128.61 113.97 286.86 227.54 0.00 0.00 0.00
Maximum of Months 463.31 243.03 239.75 674.79 447.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.84 72.65 63.19 150.89 257.41 0.00 0.00 0.00
February 143.29 65.64 77.65 148.39 243.85 0.00 0.00 0.00
March 174.06 77.55 96.51 190.63 240.60 0.00 0.00 0.00
April 222.53 111.60 110.93 287.76 194.02 0.00 0.00 0.00
May 210.01 87.64 122.37 257.46 176.42 0.00 0.00 0.00
June 208.70 90.55 118.15 279.51 141.53 0.00 0.00 0.00
July 236.47 117.51 118.96 345.87 125.43 0.00 0.00 0.00
August 233.53 124.05 109.49 349.25 127.31 0.00 0.00 0.00
September 170.03 77.91 92.12 234.77 152.08 0.00 0.00 0.00
October 150.51 77.36 73.15 212.69 167.04 0.00 0.00 0.00
November 137.21 69.71 67.50 154.18 235.44 0.00 0.00 0.00
December 130.89 72.73 58.17 144.52 258.16 0.00 0.00 0.00
                 
Annual Sum or Average 179.66 87.25 92.42 230.22 193.00 0.00 0.00 0.00
Minimum of Months 130.89 65.64 58.17 144.52 125.43 0.00 0.00 0.00
Maximum of Months 236.47 124.05 122.37 349.25 258.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 122.92 0.00 122.92 59.05 571.80 0.00 0.00 0.00
February 154.63 0.00 154.63 71.53 520.97 0.00 0.00 0.00
March 189.85 0.00 189.85 109.58 534.74 0.00 0.00 0.00
April 216.98 0.58 216.39 156.41 440.02 0.00 0.00 0.00
May 256.47 9.02 247.45 191.67 389.13 0.00 0.00 0.00
June 268.37 19.05 249.32 253.36 314.92 0.00 0.00 0.00
July 254.90 15.23 239.67 267.31 275.08 0.00 0.00 0.00
August 216.87 2.84 214.03 222.81 281.12 0.00 0.00 0.00
September 186.39 0.01 186.38 172.98 349.18 0.00 0.00 0.00
October 147.98 0.00 147.98 153.65 393.07 0.00 0.00 0.00
November 133.33 0.00 133.33 70.12 529.30 0.00 0.00 0.00
December 114.31 0.00 114.31 52.71 576.80 0.00 0.00 0.00
                 
Annual Sum or Average 188.72 3.92 184.81 148.90 430.86 0.00 0.00 0.00
Minimum of Months 114.31 0.00 114.31 52.71 275.08 0.00 0.00 0.00
Maximum of Months 268.37 19.05 249.32 267.31 576.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.70 12.14 10.56 27.30 33.86 0.00 0.00 0.00
February 23.94 10.97 12.97 26.85 31.14 0.00 0.00 0.00
March 29.08 12.96 16.13 34.13 31.81 0.00 0.00 0.00
April 37.18 18.65 18.54 49.74 26.58 0.00 0.00 0.00
May 35.09 14.64 20.45 44.55 24.75 0.00 0.00 0.00
June 34.87 15.13 19.74 47.43 20.28 0.00 0.00 0.00
July 39.51 19.64 19.88 58.11 17.83 0.00 0.00 0.00
August 39.02 20.73 18.30 58.59 17.74 0.00 0.00 0.00
September 28.41 13.02 15.39 39.92 21.58 0.00 0.00 0.00
October 25.15 12.93 12.22 36.24 23.97 0.00 0.00 0.00
November 22.93 11.65 11.28 27.43 31.58 0.00 0.00 0.00
December 21.87 12.15 9.72 26.26 34.08 0.00 0.00 0.00
                 
Annual Sum or Average 30.02 14.58 15.44 39.80 26.24 0.00 0.00 0.00
Minimum of Months 21.87 10.97 9.72 26.26 17.74 0.00 0.00 0.00
Maximum of Months 39.51 20.73 20.45 58.59 34.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 232.00 124.08 107.92 279.04 346.09 0.00 0.00 0.00
February 244.73 112.11 132.62 274.42 318.29 0.00 0.00 0.00
March 297.28 132.45 164.83 348.88 325.18 0.00 0.00 0.00
April 380.06 190.61 189.45 508.43 271.70 0.00 0.00 0.00
May 358.67 149.68 208.99 455.32 252.94 0.00 0.00 0.00
June 356.44 154.65 201.79 484.85 207.10 0.00 0.00 0.00
July 403.87 200.69 203.18 594.04 182.13 0.00 0.00 0.00
August 398.86 211.86 187.00 598.85 181.35 0.00 0.00 0.00
September 290.40 133.07 157.33 408.05 220.54 0.00 0.00 0.00
October 257.06 132.12 124.94 370.40 244.97 0.00 0.00 0.00
November 234.34 119.05 115.28 280.36 322.81 0.00 0.00 0.00
December 223.55 124.21 99.34 268.45 348.36 0.00 0.00 0.00
                 
Annual Sum or Average 306.85 149.01 157.84 406.85 268.19 0.00 0.00 0.00
Minimum of Months 223.55 112.11 99.34 268.45 181.35 0.00 0.00 0.00
Maximum of Months 403.87 211.86 208.99 598.85 348.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 119.60 0.00 119.60 57.42 536.86 0.00 0.00 0.00
February 150.13 0.00 150.13 68.78 499.00 0.00 0.00 0.00
March 183.98 0.00 183.98 105.53 512.19 0.00 0.00 0.00
April 211.96 0.82 211.15 148.94 416.16 0.00 0.00 0.00
May 254.71 11.86 242.85 193.06 360.70 0.00 0.00 0.00
June 271.41 26.53 244.87 262.23 283.14 0.00 0.00 0.00
July 256.98 21.54 235.44 280.94 241.72 0.00 0.00 0.00
August 213.41 4.27 209.14 224.97 253.28 0.00 0.00 0.00
September 180.63 0.03 180.60 169.09 324.71 0.00 0.00 0.00
October 143.28 0.00 143.28 148.07 364.56 0.00 0.00 0.00
November 129.73 0.00 129.73 65.85 506.06 0.00 0.00 0.00
December 111.34 0.00 111.34 49.47 548.91 0.00 0.00 0.00
                 
Annual Sum or Average 185.75 5.45 180.30 148.36 403.39 0.00 0.00 0.00
Minimum of Months 111.34 0.00 111.34 49.47 241.72 0.00 0.00 0.00
Maximum of Months 271.41 26.53 244.87 280.94 548.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 6.25 0.00 6.25 2.57 35.32 0.00 0.00 0.00
February 7.70 0.00 7.70 2.54 33.75 0.00 0.00 0.00
March 9.66 0.16 9.50 4.35 34.81 0.00 0.00 0.00
April 23.69 10.29 13.40 27.03 26.18 0.00 0.00 0.00
May 28.46 12.75 15.71 34.35 24.30 0.00 0.00 0.00
June 29.65 14.05 15.59 39.96 19.55 0.00 0.00 0.00
July 33.59 17.66 15.93 49.85 16.20 0.00 0.00 0.00
August 28.53 14.57 13.96 41.79 16.07 0.00 0.00 0.00
September 12.70 2.49 10.21 13.43 20.31 0.00 0.00 0.00
October 7.58 0.00 7.58 8.04 23.42 0.00 0.00 0.00
November 6.75 0.00 6.75 2.84 33.38 0.00 0.00 0.00
December 5.84 0.00 5.84 2.46 35.99 0.00 0.00 0.00
                 
Annual Sum or Average 16.76 6.04 10.72 19.22 26.57 0.00 0.00 0.00
Minimum of Months 5.84 0.00 5.84 2.46 16.07 0.00 0.00 0.00
Maximum of Months 33.59 17.66 15.93 49.85 35.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 297.99 153.36 144.63 340.03 511.59 0.00 0.00 0.00
February 334.96 153.35 181.62 361.48 482.28 0.00 0.00 0.00
March 418.66 190.28 228.38 479.24 493.29 0.00 0.00 0.00
April 537.38 274.77 262.61 708.68 408.77 0.00 0.00 0.00
May 505.50 215.77 289.73 631.45 376.96 0.00 0.00 0.00
June 502.53 222.94 279.59 678.13 302.92 0.00 0.00 0.00
July 570.55 289.31 281.24 844.42 258.00 0.00 0.00 0.00
August 564.25 305.40 258.85 851.72 258.43 0.00 0.00 0.00
September 408.68 191.38 217.30 571.70 320.53 0.00 0.00 0.00
October 356.02 184.06 171.96 510.49 352.94 0.00 0.00 0.00
November 309.48 153.75 155.72 351.58 484.91 0.00 0.00 0.00
December 280.93 148.79 132.14 315.44 521.35 0.00 0.00 0.00
                 
Annual Sum or Average 424.47 207.33 217.14 555.01 397.17 0.00 0.00 0.00
Minimum of Months 280.93 148.79 132.14 315.44 258.00 0.00 0.00 0.00
Maximum of Months 570.55 305.40 289.73 851.72 521.35 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.470143E+09 0.617668E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.499384E+09 0.482864E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.657706E+09 0.531742E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.988387E+09 0.427524E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.988581E+09 0.392369E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.108325E+10 0.289730E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126216E+10 0.251564E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.119771E+10 0.262838E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.923314E+09 0.337653E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.733062E+09 0.412765E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.543008E+09 0.547603E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.485574E+09 0.628968E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.983227E+10 0.518329E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.470143E+09 0.251564E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126216E+10 0.628968E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.154132E+09 0.113063E+09 41069569.02 0.229185E+09 89084187.86
February 0.109417E+09 67394689.24 42022097.76 0.154157E+09 71508539.67
March 96577052.92 46650957.16 49926095.76 0.134958E+09 81993051.33
April 78089924.64 29776093.52 48313831.12 0.114929E+09 68452515.66
May 57459831.90 7071103.33 50388728.57 68958649.14 63556340.81
June 48781649.07 2945201.88 45836447.19 60078540.20 46967146.21
July 53395639.77 6010701.79 47384937.98 78308100.61 40848450.42
August 68596990.08 21637321.73 46959668.35 0.114886E+09 41976486.56
September 92373003.20 46808216.68 45564786.53 0.148829E+09 53467654.42
October 0.121392E+09 81153802.42 40238577.34 0.195606E+09 61863165.59
November 0.142781E+09 0.100801E+09 41980011.42 0.211216E+09 80010495.68
December 0.164663E+09 0.125329E+09 39333271.75 0.245837E+09 90136519.11
           
Annual Sum or Average 0.118766E+10 0.648641E+09 0.539018E+09 0.175695E+10 0.789865E+09
Minimum of Months 48781649.07 2945201.88 39333271.75 60078540.20 40848450.42
Maximum of Months 0.164663E+09 0.125329E+09 50388728.57 0.245837E+09 90136519.11



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106972E+10 0.784689E+09 0.285035E+09 0.159061E+10 0.618270E+09
February 0.759384E+09 0.467739E+09 0.291645E+09 0.106989E+10 0.496290E+09
March 0.670273E+09 0.323771E+09 0.346502E+09 0.936647E+09 0.569055E+09
April 0.541967E+09 0.206655E+09 0.335312E+09 0.797641E+09 0.475088E+09
May 0.398788E+09 49075498.60 0.349712E+09 0.478269E+09 0.441777E+09
June 0.338559E+09 20440551.34 0.318118E+09 0.415290E+09 0.327017E+09
July 0.370581E+09 41716005.77 0.328865E+09 0.541969E+09 0.284297E+09
August 0.476083E+09 0.150169E+09 0.325914E+09 0.797139E+09 0.291485E+09
September 0.641095E+09 0.324863E+09 0.316233E+09 0.103292E+10 0.371075E+09
October 0.842498E+09 0.563231E+09 0.279267E+09 0.135756E+10 0.429348E+09
November 0.990938E+09 0.699585E+09 0.291353E+09 0.146590E+10 0.555296E+09
December 0.114281E+10 0.869823E+09 0.272984E+09 0.170618E+10 0.625573E+09
           
Annual Sum or Average 0.824270E+10 0.450176E+10 0.374094E+10 0.121900E+11 0.548457E+10
Minimum of Months 0.338559E+09 20440551.34 0.272984E+09 0.415290E+09 0.284297E+09
Maximum of Months 0.114281E+10 0.869823E+09 0.349712E+09 0.170618E+10 0.625573E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196571E+10 0.144194E+10 0.523770E+09 0.288448E+10 0.124015E+10
February 0.139543E+10 0.859511E+09 0.535918E+09 0.193431E+10 0.100078E+10
March 0.123168E+10 0.594958E+09 0.636719E+09 0.169155E+10 0.113004E+10
April 0.995899E+09 0.379746E+09 0.616153E+09 0.145463E+10 0.915653E+09
May 0.732796E+09 90180533.33 0.642615E+09 0.868988E+09 0.846665E+09
June 0.622119E+09 37561306.03 0.584558E+09 0.761689E+09 0.618807E+09
July 0.680961E+09 76656819.71 0.604305E+09 0.102542E+10 0.502570E+09
August 0.874831E+09 0.275949E+09 0.598882E+09 0.148747E+10 0.525217E+09
September 0.117806E+10 0.596963E+09 0.581096E+09 0.189659E+10 0.708438E+09
October 0.154816E+10 0.103499E+10 0.513171E+09 0.248372E+10 0.842008E+09
November 0.182093E+10 0.128555E+10 0.535381E+09 0.266421E+10 0.110718E+10
December 0.210000E+10 0.159838E+10 0.501627E+09 0.309735E+10 0.125349E+10
           
Annual Sum or Average 0.151466E+11 0.827237E+10 0.687419E+10 0.222504E+11 0.106910E+11
Minimum of Months 0.622119E+09 37561306.03 0.501627E+09 0.761689E+09 0.502570E+09
Maximum of Months 0.210000E+10 0.159838E+10 0.642615E+09 0.309735E+10 0.125349E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196571E+10 0.144194E+10 0.523770E+09 0.288448E+10 0.124015E+10
February 0.139543E+10 0.859511E+09 0.535918E+09 0.193431E+10 0.100078E+10
March 0.123168E+10 0.594958E+09 0.636719E+09 0.169155E+10 0.113004E+10
April 0.995899E+09 0.379746E+09 0.616153E+09 0.145463E+10 0.915653E+09
May 0.732796E+09 90180533.33 0.642615E+09 0.868988E+09 0.846665E+09
June 0.622119E+09 37561306.03 0.584558E+09 0.761689E+09 0.618807E+09
July 0.680961E+09 76656819.71 0.604305E+09 0.102542E+10 0.502570E+09
August 0.874831E+09 0.275949E+09 0.598882E+09 0.148747E+10 0.525217E+09
September 0.117806E+10 0.596963E+09 0.581096E+09 0.189659E+10 0.708438E+09
October 0.154816E+10 0.103499E+10 0.513171E+09 0.248372E+10 0.842008E+09
November 0.182093E+10 0.128555E+10 0.535381E+09 0.266421E+10 0.110718E+10
December 0.210000E+10 0.159838E+10 0.501627E+09 0.309735E+10 0.125349E+10
           
Annual Sum or Average 0.151466E+11 0.827237E+10 0.687419E+10 0.222504E+11 0.106910E+11
Minimum of Months 0.622119E+09 37561306.03 0.501627E+09 0.761689E+09 0.502570E+09
Maximum of Months 0.210000E+10 0.159838E+10 0.642615E+09 0.309735E+10 0.125349E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196567E+10 0.144191E+10 0.523760E+09 0.288442E+10 0.124013E+10
February 0.139540E+10 0.859494E+09 0.535908E+09 0.193427E+10 0.100076E+10
March 0.123165E+10 0.594946E+09 0.636706E+09 0.169151E+10 0.113001E+10
April 0.995880E+09 0.379739E+09 0.616141E+09 0.145461E+10 0.915635E+09
May 0.732781E+09 90178785.55 0.642603E+09 0.868971E+09 0.846649E+09
June 0.622107E+09 37560578.06 0.584546E+09 0.761674E+09 0.618795E+09
July 0.680948E+09 76655334.03 0.604293E+09 0.102540E+10 0.502560E+09
August 0.874814E+09 0.275944E+09 0.598870E+09 0.148744E+10 0.525206E+09
September 0.117804E+10 0.596952E+09 0.581084E+09 0.189656E+10 0.708424E+09
October 0.154813E+10 0.103497E+10 0.513161E+09 0.248368E+10 0.841992E+09
November 0.182089E+10 0.128552E+10 0.535371E+09 0.266416E+10 0.110716E+10
December 0.209996E+10 0.159834E+10 0.501617E+09 0.309729E+10 0.125347E+10
           
Annual Sum or Average 0.151463E+11 0.827221E+10 0.687406E+10 0.222500E+11 0.106908E+11
Minimum of Months 0.622107E+09 37560578.06 0.501617E+09 0.761674E+09 0.502560E+09
Maximum of Months 0.209996E+10 0.159834E+10 0.642603E+09 0.309729E+10 0.125347E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129861E+09 65496202.37 64365119.12 0.163678E+09 0.211470E+09
February 0.139932E+09 64599315.81 75333044.03 0.168656E+09 0.171216E+09
March 0.177586E+09 78566695.06 99018941.22 0.219205E+09 0.191057E+09
April 0.236914E+09 0.123361E+09 0.113553E+09 0.329566E+09 0.150914E+09
May 0.240482E+09 0.111078E+09 0.129404E+09 0.323641E+09 0.142788E+09
June 0.246546E+09 0.123268E+09 0.123278E+09 0.353957E+09 0.105515E+09
July 0.269688E+09 0.144308E+09 0.125380E+09 0.422420E+09 84848998.34
August 0.253020E+09 0.137126E+09 0.115894E+09 0.403682E+09 86680723.16
September 0.209644E+09 0.112177E+09 97466490.85 0.311660E+09 0.113409E+09
October 0.165605E+09 90413387.60 75191820.23 0.248725E+09 0.140556E+09
November 0.144766E+09 75722540.26 69042985.65 0.186699E+09 0.188094E+09
December 0.132115E+09 70860135.06 61254550.57 0.169662E+09 0.214688E+09
           
Annual Sum or Average 0.234616E+10 0.119698E+10 0.114918E+10 0.330155E+10 0.180124E+10
Minimum of Months 0.129861E+09 64599315.81 61254550.57 0.163678E+09 84848998.34
Maximum of Months 0.269688E+09 0.144308E+09 0.129404E+09 0.422420E+09 0.214688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.527530E+09 0.537565E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.540023E+09 0.434403E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.692498E+09 0.497119E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.101765E+10 0.403069E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.994742E+09 0.389871E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.107915E+10 0.295361E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126703E+10 0.251279E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.122095E+10 0.247159E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.960134E+09 0.303953E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.774886E+09 0.366537E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.595844E+09 0.479771E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.546570E+09 0.543035E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.102170E+11 0.474912E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.527530E+09 0.247159E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126703E+10 0.543035E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 17721130.25 0.00 17721130.25 11569730.20 82233617.94
February 20604150.95 0.00 20604150.95 11827030.60 67330532.58
March 28267420.40 0.00 28267420.40 19256780.40 77792011.34
April 31272555.87 137152.87 31135403.00 24885094.18 61559805.93
May 39590281.94 2099552.07 37490729.87 32406594.52 56622722.31
June 41560950.07 4764969.01 36795981.06 44232736.17 42886943.79
July 39788742.93 4044444.17 35744298.76 50957974.49 36134692.77
August 32247959.38 785143.79 31462815.59 42196483.17 35451012.13
September 26282409.07 4547.06 26277862.01 28284870.33 46354598.61
October 21764693.85 0.00 21764693.85 26794074.03 54872375.13
November 18632003.03 0.00 18632003.03 12273671.71 73922287.28
December 16336065.68 0.00 16336065.68 10498826.01 82987777.80
           
Annual Sum or Average 0.334068E+09 11835808.96 0.322233E+09 0.315184E+09 0.718148E+09
Minimum of Months 16336065.68 0.00 16336065.68 10498826.01 35451012.13
Maximum of Months 41560950.07 4764969.01 37490729.87 50957974.49 82987777.80



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132042E+09 0.00 0.132042E+09 91058611.11 0.572768E+09
February 0.152440E+09 0.00 0.152440E+09 94006408.19 0.468117E+09
March 0.208489E+09 0.00 0.208489E+09 0.149905E+09 0.540814E+09
April 0.231100E+09 951880.49 0.230148E+09 0.190871E+09 0.429049E+09
May 0.290527E+09 14571497.52 0.275956E+09 0.247631E+09 0.396154E+09
June 0.303458E+09 33070260.64 0.270388E+09 0.328507E+09 0.300168E+09
July 0.292469E+09 28069610.20 0.264399E+09 0.376804E+09 0.254124E+09
August 0.238836E+09 5449130.87 0.233387E+09 0.314123E+09 0.249755E+09
September 0.195020E+09 31581.53 0.194988E+09 0.214413E+09 0.324855E+09
October 0.161039E+09 0.00 0.161039E+09 0.200042E+09 0.384664E+09
November 0.138766E+09 0.00 0.138766E+09 97146531.62 0.514775E+09
December 0.122062E+09 0.00 0.122062E+09 83301983.50 0.578459E+09
           
Annual Sum or Average 0.246625E+10 82143961.26 0.238410E+10 0.238781E+10 0.501370E+10
Minimum of Months 0.122062E+09 0.00 0.122062E+09 83301983.50 0.249755E+09
Maximum of Months 0.303458E+09 33070260.64 0.275956E+09 0.376804E+09 0.578459E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.213574E+09 0.00 0.213574E+09 0.115387E+09 0.113257E+10
February 0.248262E+09 0.00 0.248262E+09 0.113494E+09 0.937409E+09
March 0.341068E+09 0.00 0.341068E+09 0.198523E+09 0.107599E+10
April 0.376559E+09 775753.22 0.375783E+09 0.282688E+09 0.835708E+09
May 0.466136E+09 17510422.78 0.448625E+09 0.360134E+09 0.789742E+09
June 0.483871E+09 43831700.77 0.440039E+09 0.503555E+09 0.596608E+09
July 0.465384E+09 36947173.43 0.428437E+09 0.626892E+09 0.460516E+09
August 0.385893E+09 6367722.48 0.379526E+09 0.536254E+09 0.446959E+09
September 0.318202E+09 46869.22 0.318156E+09 0.337523E+09 0.607916E+09
October 0.263400E+09 0.00 0.263400E+09 0.311392E+09 0.744269E+09
November 0.224475E+09 0.00 0.224475E+09 0.123696E+09 0.101546E+10
December 0.196829E+09 0.00 0.196829E+09 0.106520E+09 0.114463E+10
           
Annual Sum or Average 0.398365E+10 0.105480E+09 0.387817E+10 0.361606E+10 0.978778E+10
Minimum of Months 0.196829E+09 0.00 0.196829E+09 0.106520E+09 0.446959E+09
Maximum of Months 0.483871E+09 43831700.77 0.448625E+09 0.626892E+09 0.114463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223775E+09 0.00 0.223775E+09 0.123333E+09 0.114121E+10
February 0.260448E+09 0.00 0.260448E+09 0.124912E+09 0.941166E+09
March 0.357475E+09 0.00 0.357475E+09 0.216355E+09 0.107813E+10
April 0.394706E+09 1469095.36 0.393237E+09 0.298032E+09 0.833184E+09
May 0.495849E+09 23796075.00 0.472053E+09 0.389885E+09 0.775949E+09
June 0.514242E+09 51999397.95 0.462243E+09 0.544388E+09 0.591542E+09
July 0.493409E+09 44391470.39 0.449017E+09 0.667048E+09 0.461223E+09
August 0.405274E+09 8760764.82 0.396513E+09 0.556556E+09 0.446454E+09
September 0.332023E+09 50040.20 0.331973E+09 0.352857E+09 0.613472E+09
October 0.275113E+09 0.00 0.275113E+09 0.323045E+09 0.752787E+09
November 0.235293E+09 0.00 0.235293E+09 0.132926E+09 0.102315E+10
December 0.206201E+09 0.00 0.206201E+09 0.112006E+09 0.115417E+10
           
Annual Sum or Average 0.419381E+10 0.130467E+09 0.406334E+10 0.384134E+10 0.981243E+10
Minimum of Months 0.206201E+09 0.00 0.206201E+09 0.112006E+09 0.446454E+09
Maximum of Months 0.514242E+09 51999397.95 0.472053E+09 0.667048E+09 0.115417E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.224527E+09 0.00 0.224527E+09 0.124018E+09 0.114147E+10
February 0.261231E+09 0.00 0.261231E+09 0.125746E+09 0.941283E+09
March 0.358496E+09 0.00 0.358496E+09 0.217572E+09 0.107817E+10
April 0.396422E+09 1700835.68 0.394721E+09 0.299466E+09 0.831992E+09
May 0.501420E+09 26220947.32 0.475199E+09 0.392345E+09 0.768201E+09
June 0.521301E+09 56166869.09 0.465134E+09 0.548187E+09 0.582542E+09
July 0.500641E+09 48553441.40 0.452087E+09 0.671823E+09 0.452670E+09
August 0.408817E+09 10018307.09 0.398798E+09 0.559218E+09 0.442765E+09
September 0.333119E+09 56393.97 0.333062E+09 0.354249E+09 0.613622E+09
October 0.275942E+09 0.00 0.275942E+09 0.324014E+09 0.753148E+09
November 0.236078E+09 0.00 0.236078E+09 0.133708E+09 0.102339E+10
December 0.206923E+09 0.00 0.206923E+09 0.112580E+09 0.115447E+10
           
Annual Sum or Average 0.422492E+10 0.142717E+09 0.408220E+10 0.386293E+10 0.978374E+10
Minimum of Months 0.206923E+09 0.00 0.206923E+09 0.112580E+09 0.442765E+09
Maximum of Months 0.521301E+09 56166869.09 0.475199E+09 0.671823E+09 0.115447E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.471434E+09 0.616486E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.500100E+09 0.482931E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.658675E+09 0.531759E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.989552E+09 0.427536E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.990288E+09 0.392108E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.108399E+10 0.290014E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126415E+10 0.250991E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.119994E+10 0.261851E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.924079E+09 0.337964E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.733147E+09 0.413924E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.543376E+09 0.548207E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.486296E+09 0.628100E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.984502E+10 0.518187E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.471434E+09 0.250991E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126415E+10 0.628100E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148727E+09 0.111427E+09 37299118.58 0.223390E+09 88595292.19
February 0.105672E+09 67252160.39 38419587.41 0.149404E+09 70405227.99
March 91956412.15 46631570.80 45324841.34 0.128602E+09 80819214.01
April 72841652.27 29776093.52 43065558.75 0.108158E+09 67419281.59
May 51576977.36 7071103.33 44505874.03 61199756.02 62762054.62
June 43177372.41 2945201.88 40232170.53 52468355.65 46323614.38
July 47302254.63 6010701.79 41291552.84 70195541.85 39653824.72
August 62988015.56 21637321.73 41350693.83 0.107502E+09 40491312.30
September 87658638.90 46803985.92 40854652.98 0.142351E+09 52049409.44
October 0.117370E+09 80917184.94 36452716.25 0.190532E+09 60345419.54
November 0.138201E+09 99991094.62 38210065.28 0.205876E+09 79207044.23
December 0.158528E+09 0.122950E+09 35577815.04 0.239190E+09 89791203.43
           
Annual Sum or Average 0.112600E+10 0.643414E+09 0.482585E+09 0.167887E+10 0.777863E+09
Minimum of Months 43177372.41 2945201.88 35577815.04 52468355.65 39653824.72
Maximum of Months 0.158528E+09 0.122950E+09 45324841.34 0.239190E+09 89791203.43



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102137E+10 0.773339E+09 0.248036E+09 0.153628E+10 0.607192E+09
February 0.722097E+09 0.466749E+09 0.255348E+09 0.102136E+10 0.483706E+09
March 0.623477E+09 0.323635E+09 0.299842E+09 0.871794E+09 0.557131E+09
April 0.488721E+09 0.206655E+09 0.282066E+09 0.728696E+09 0.465005E+09
May 0.339104E+09 49075498.60 0.290029E+09 0.399522E+09 0.434694E+09
June 0.281701E+09 20440551.34 0.261261E+09 0.338372E+09 0.321046E+09
July 0.308762E+09 41716005.77 0.267046E+09 0.459233E+09 0.273042E+09
August 0.419178E+09 0.150169E+09 0.269009E+09 0.721437E+09 0.277243E+09
September 0.593286E+09 0.324833E+09 0.268453E+09 0.966992E+09 0.356749E+09
October 0.802634E+09 0.561589E+09 0.241045E+09 0.130674E+10 0.412290E+09
November 0.947844E+09 0.693967E+09 0.253877E+09 0.141376E+10 0.542831E+09
December 0.108984E+10 0.853308E+09 0.236529E+09 0.164724E+10 0.614868E+09
           
Annual Sum or Average 0.763802E+10 0.446548E+10 0.317254E+10 0.114114E+11 0.534580E+10
Minimum of Months 0.281701E+09 20440551.34 0.236529E+09 0.338372E+09 0.273042E+09
Maximum of Months 0.108984E+10 0.853308E+09 0.299842E+09 0.164724E+10 0.614868E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185986E+10 0.141580E+10 0.444056E+09 0.276965E+10 0.121640E+10
February 0.131612E+10 0.857697E+09 0.458423E+09 0.183107E+10 0.975723E+09
March 0.113161E+10 0.594697E+09 0.536909E+09 0.155291E+10 0.111018E+10
April 0.882004E+09 0.379746E+09 0.502258E+09 0.130565E+10 0.899279E+09
May 0.605128E+09 90180533.33 0.514948E+09 0.697606E+09 0.838330E+09
June 0.500498E+09 37561306.03 0.462936E+09 0.593739E+09 0.611349E+09
July 0.548726E+09 76656819.71 0.472069E+09 0.845820E+09 0.480267E+09
August 0.753108E+09 0.275949E+09 0.477159E+09 0.132458E+10 0.496023E+09
September 0.107580E+10 0.596903E+09 0.478894E+09 0.175633E+10 0.678729E+09
October 0.146245E+10 0.103110E+10 0.431351E+09 0.237618E+10 0.803898E+09
November 0.172476E+10 0.127046E+10 0.454296E+09 0.255045E+10 0.108190E+10
December 0.196585E+10 0.154667E+10 0.419181E+09 0.294732E+10 0.123627E+10
           
Annual Sum or Average 0.138259E+11 0.817342E+10 0.565248E+10 0.205513E+11 0.104283E+11
Minimum of Months 0.500498E+09 37561306.03 0.419181E+09 0.593739E+09 0.480267E+09
Maximum of Months 0.196585E+10 0.154667E+10 0.536909E+09 0.294732E+10 0.123627E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185543E+10 0.141291E+10 0.442523E+09 0.276712E+10 0.122127E+10
February 0.131105E+10 0.855310E+09 0.455737E+09 0.182885E+10 0.983072E+09
March 0.113000E+10 0.594369E+09 0.535634E+09 0.155130E+10 0.111110E+10
April 0.880829E+09 0.379746E+09 0.501083E+09 0.130413E+10 0.899090E+09
May 0.603812E+09 90180533.33 0.513631E+09 0.695889E+09 0.838238E+09
June 0.499243E+09 37561306.03 0.461682E+09 0.592057E+09 0.611244E+09
July 0.547362E+09 76656819.71 0.470705E+09 0.843964E+09 0.480047E+09
August 0.751852E+09 0.275949E+09 0.475903E+09 0.132288E+10 0.495749E+09
September 0.107461E+10 0.596810E+09 0.477803E+09 0.175473E+10 0.678614E+09
October 0.145905E+10 0.102920E+10 0.429844E+09 0.237318E+10 0.807014E+09
November 0.171744E+10 0.126531E+10 0.452130E+09 0.254704E+10 0.109205E+10
December 0.195736E+10 0.154042E+10 0.416945E+09 0.294268E+10 0.124633E+10
           
Annual Sum or Average 0.137880E+11 0.815443E+10 0.563362E+10 0.205238E+11 0.104638E+11
Minimum of Months 0.499243E+09 37561306.03 0.416945E+09 0.592057E+09 0.480047E+09
Maximum of Months 0.195736E+10 0.154042E+10 0.535634E+09 0.294268E+10 0.124633E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172295E+10 0.130735E+10 0.415601E+09 0.255318E+10 0.122379E+10
February 0.122923E+10 0.799152E+09 0.430074E+09 0.170281E+10 0.993665E+09
March 0.107437E+10 0.565542E+09 0.508827E+09 0.146389E+10 0.111862E+10
April 0.850646E+09 0.369194E+09 0.481452E+09 0.125542E+10 0.895562E+09
May 0.581597E+09 88618566.13 0.492979E+09 0.666364E+09 0.835652E+09
June 0.480753E+09 37010526.50 0.443743E+09 0.569067E+09 0.608764E+09
July 0.528930E+09 75292865.80 0.453637E+09 0.820560E+09 0.475115E+09
August 0.727226E+09 0.268729E+09 0.458497E+09 0.128389E+10 0.489904E+09
September 0.103373E+10 0.575550E+09 0.458179E+09 0.168426E+10 0.674337E+09
October 0.138007E+10 0.972495E+09 0.407579E+09 0.224405E+10 0.809740E+09
November 0.160458E+10 0.117888E+10 0.425697E+09 0.236797E+10 0.109817E+10
December 0.181813E+10 0.142573E+10 0.392394E+09 0.271772E+10 0.124556E+10
           
Annual Sum or Average 0.130322E+11 0.766355E+10 0.536866E+10 0.193292E+11 0.104689E+11
Minimum of Months 0.480753E+09 37010526.50 0.392394E+09 0.569067E+09 0.475115E+09
Maximum of Months 0.181813E+10 0.142573E+10 0.508827E+09 0.271772E+10 0.124556E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129861E+09 65496202.37 64365119.12 0.164015E+09 0.210716E+09
February 0.139932E+09 64599315.81 75333044.03 0.168695E+09 0.171246E+09
March 0.177586E+09 78566695.06 99018941.22 0.219160E+09 0.191261E+09
April 0.236914E+09 0.123361E+09 0.113553E+09 0.329501E+09 0.151128E+09
May 0.240482E+09 0.111078E+09 0.129404E+09 0.323511E+09 0.143048E+09
June 0.246546E+09 0.123268E+09 0.123278E+09 0.353582E+09 0.105963E+09
July 0.269688E+09 0.144308E+09 0.125380E+09 0.422411E+09 84932904.36
August 0.253020E+09 0.137126E+09 0.115894E+09 0.403902E+09 86520393.17
September 0.209644E+09 0.112177E+09 97466490.85 0.311648E+09 0.113509E+09
October 0.165605E+09 90413387.60 75191820.23 0.248704E+09 0.140662E+09
November 0.144766E+09 75722540.26 69042985.65 0.186766E+09 0.187977E+09
December 0.132115E+09 70860135.06 61254550.57 0.169898E+09 0.213936E+09
           
Annual Sum or Average 0.234616E+10 0.119698E+10 0.114918E+10 0.330179E+10 0.180090E+10
Minimum of Months 0.129861E+09 64599315.81 61254550.57 0.164015E+09 84932904.36
Maximum of Months 0.269688E+09 0.144308E+09 0.129404E+09 0.422411E+09 0.213936E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.527413E+09 0.537272E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.539727E+09 0.434639E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.691939E+09 0.497704E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.101708E+10 0.403616E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.994120E+09 0.390479E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.107791E+10 0.296430E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126604E+10 0.251942E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.122069E+10 0.247257E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.959408E+09 0.304678E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.774292E+09 0.367119E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.595293E+09 0.480183E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.546023E+09 0.542905E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.102099E+11 0.475422E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.527413E+09 0.247257E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126604E+10 0.542905E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 18091933.85 0.00 18091933.85 11922566.53 82357234.47
February 20990862.73 0.00 20990862.73 12228409.11 67465734.18
March 28771455.45 0.00 28771455.45 19820252.09 77960638.04
April 31848453.21 137152.87 31711300.34 25545588.48 61740530.83
May 40267500.50 2119121.78 38148378.72 33249124.83 56787849.03
June 42226536.74 4798086.84 37428449.90 44983151.88 43105818.09
July 40481317.10 4060920.97 36420396.13 51789046.75 36346505.79
August 32869625.67 789157.48 32080468.18 43012974.00 35604073.67
September 26799032.34 4547.06 26794485.29 28884090.79 46614272.60
October 22173728.30 0.00 22173728.30 27219249.04 55176183.45
November 19019271.62 0.00 19019271.62 12623064.35 74161772.71
December 16691833.66 0.00 16691833.66 10773389.72 83187571.23
           
Annual Sum or Average 0.340232E+09 11908986.99 0.328323E+09 0.322051E+09 0.720508E+09
Minimum of Months 16691833.66 0.00 16691833.66 10773389.72 35604073.67
Maximum of Months 42226536.74 4798086.84 38148378.72 51789046.75 83187571.23



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133821E+09 0.00 0.133821E+09 92806724.06 0.573355E+09
February 0.154295E+09 0.00 0.154295E+09 95923890.01 0.468925E+09
March 0.210907E+09 0.00 0.210907E+09 0.152546E+09 0.541925E+09
April 0.233863E+09 951880.49 0.232911E+09 0.193989E+09 0.430214E+09
May 0.293844E+09 14707316.97 0.279137E+09 0.251508E+09 0.397036E+09
June 0.306760E+09 33300107.91 0.273460E+09 0.331836E+09 0.301472E+09
July 0.295843E+09 28183963.96 0.267659E+09 0.380552E+09 0.255309E+09
August 0.241832E+09 5476987.04 0.236355E+09 0.317980E+09 0.250514E+09
September 0.197498E+09 31581.54 0.197467E+09 0.217107E+09 0.326391E+09
October 0.163001E+09 0.00 0.163001E+09 0.201989E+09 0.386411E+09
November 0.140624E+09 0.00 0.140624E+09 98763155.41 0.516176E+09
December 0.123769E+09 0.00 0.123769E+09 84563979.02 0.579480E+09
           
Annual Sum or Average 0.249606E+10 82651837.92 0.241341E+10 0.241956E+10 0.502721E+10
Minimum of Months 0.123769E+09 0.00 0.123769E+09 84563979.02 0.250514E+09
Maximum of Months 0.306760E+09 33300107.91 0.279137E+09 0.380552E+09 0.579480E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.216424E+09 0.00 0.216424E+09 0.118003E+09 0.113206E+10
February 0.251234E+09 0.00 0.251234E+09 0.116408E+09 0.937951E+09
March 0.344942E+09 0.00 0.344942E+09 0.202600E+09 0.107710E+10
April 0.381484E+09 836213.97 0.380648E+09 0.287738E+09 0.836028E+09
May 0.471642E+09 17762544.52 0.453880E+09 0.366329E+09 0.790392E+09
June 0.489887E+09 44696303.15 0.445191E+09 0.509761E+09 0.597958E+09
July 0.471889E+09 37854730.90 0.434034E+09 0.634627E+09 0.461701E+09
August 0.390989E+09 6514359.72 0.384475E+09 0.543157E+09 0.447882E+09
September 0.322174E+09 46869.22 0.322127E+09 0.341980E+09 0.609923E+09
October 0.266544E+09 0.00 0.266544E+09 0.314560E+09 0.746593E+09
November 0.227452E+09 0.00 0.227452E+09 0.126115E+09 0.101681E+10
December 0.199564E+09 0.00 0.199564E+09 0.108394E+09 0.114515E+10
           
Annual Sum or Average 0.403423E+10 0.107711E+09 0.392651E+10 0.366967E+10 0.979955E+10
Minimum of Months 0.199564E+09 0.00 0.199564E+09 0.108394E+09 0.447882E+09
Maximum of Months 0.489887E+09 44696303.15 0.453880E+09 0.634627E+09 0.114515E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228287E+09 0.00 0.228287E+09 0.127545E+09 0.114142E+10
February 0.265154E+09 0.00 0.265154E+09 0.129754E+09 0.942103E+09
March 0.363608E+09 0.00 0.363608E+09 0.223201E+09 0.107948E+10
April 0.401714E+09 1469095.36 0.400245E+09 0.306272E+09 0.834765E+09
May 0.504444E+09 24167101.66 0.480277E+09 0.400324E+09 0.776885E+09
June 0.523543E+09 53208628.08 0.470335E+09 0.555007E+09 0.592782E+09
July 0.503117E+09 45431402.51 0.457686E+09 0.679095E+09 0.462691E+09
August 0.413365E+09 9056174.53 0.404308E+09 0.567197E+09 0.447485E+09
September 0.338310E+09 50040.20 0.338260E+09 0.360406E+09 0.616093E+09
October 0.280091E+09 0.00 0.280091E+09 0.328363E+09 0.755944E+09
November 0.240006E+09 0.00 0.240006E+09 0.137149E+09 0.102517E+10
December 0.210531E+09 0.00 0.210531E+09 0.115217E+09 0.115548E+10
           
Annual Sum or Average 0.427217E+10 0.133382E+09 0.413879E+10 0.392953E+10 0.983029E+10
Minimum of Months 0.210531E+09 0.00 0.210531E+09 0.115217E+09 0.447485E+09
Maximum of Months 0.523543E+09 53208628.08 0.480277E+09 0.679095E+09 0.115548E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228893E+09 0.00 0.228893E+09 0.128104E+09 0.114163E+10
February 0.265785E+09 0.00 0.265785E+09 0.130435E+09 0.942201E+09
March 0.364431E+09 0.00 0.364431E+09 0.224186E+09 0.107951E+10
April 0.403204E+09 1700835.68 0.401503E+09 0.307436E+09 0.833556E+09
May 0.510138E+09 26884567.09 0.483254E+09 0.402593E+09 0.768472E+09
June 0.531154E+09 57984847.96 0.473169E+09 0.558738E+09 0.582514E+09
July 0.510311E+09 49829157.49 0.460482E+09 0.683463E+09 0.453642E+09
August 0.416150E+09 10073580.95 0.406076E+09 0.569100E+09 0.444381E+09
September 0.339203E+09 56393.97 0.339146E+09 0.361531E+09 0.616193E+09
October 0.280759E+09 0.00 0.280759E+09 0.329143E+09 0.756233E+09
November 0.240639E+09 0.00 0.240639E+09 0.137785E+09 0.102537E+10
December 0.211112E+09 0.00 0.211112E+09 0.115684E+09 0.115572E+10
           
Annual Sum or Average 0.430178E+10 0.146529E+09 0.415525E+10 0.394820E+10 0.979943E+10
Minimum of Months 0.211112E+09 0.00 0.211112E+09 0.115684E+09 0.444381E+09
Maximum of Months 0.531154E+09 57984847.96 0.483254E+09 0.683463E+09 0.115572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.469816E+09 0.620341E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.498033E+09 0.486885E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.656005E+09 0.535825E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.985760E+09 0.432254E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.984923E+09 0.397402E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.107899E+10 0.294453E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126050E+10 0.254012E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.119610E+10 0.265282E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.921381E+09 0.341687E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.731774E+09 0.416439E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.542066E+09 0.551750E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.484834E+09 0.632606E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.981018E+10 0.522894E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.469816E+09 0.254012E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126050E+10 0.632606E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.149277E+09 0.111742E+09 37535676.68 0.223742E+09 89013639.33
February 0.105890E+09 67279411.71 38610231.65 0.149290E+09 70981086.64
March 92189163.48 46634368.60 45554794.88 0.128516E+09 81511889.01
April 73103493.08 29776093.52 43327399.57 0.107991E+09 68265521.87
May 51870478.02 7071103.33 44799374.70 60906913.41 63730869.48
June 43456974.58 2945201.88 40511772.71 52154440.22 47086827.49
July 47606258.84 6010701.79 41595557.06 70106140.18 40204390.18
August 63267852.11 21637321.73 41630530.38 0.107347E+09 41111673.07
September 87894693.28 46804778.61 41089914.67 0.142298E+09 52719898.43
October 0.117607E+09 80959110.82 36647561.40 0.190585E+09 60761289.97
November 0.138607E+09 0.100170E+09 38437149.32 0.206083E+09 79621899.79
December 0.159313E+09 0.123475E+09 35838110.84 0.239873E+09 90233635.92
           
Annual Sum or Average 0.113008E+10 0.644505E+09 0.485578E+09 0.167889E+10 0.785243E+09
Minimum of Months 43456974.58 2945201.88 35838110.84 52154440.22 40204390.18
Maximum of Months 0.159313E+09 0.123475E+09 45554794.88 0.239873E+09 90233635.92



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102631E+10 0.775520E+09 0.250793E+09 0.154017E+10 0.610882E+09
February 0.724772E+09 0.466939E+09 0.257834E+09 0.102217E+10 0.488214E+09
March 0.626608E+09 0.323654E+09 0.302954E+09 0.873348E+09 0.562343E+09
April 0.492270E+09 0.206655E+09 0.285615E+09 0.729811E+09 0.471196E+09
May 0.343082E+09 49075498.60 0.294007E+09 0.400123E+09 0.441651E+09
June 0.285491E+09 20440551.34 0.265050E+09 0.338755E+09 0.326575E+09
July 0.312882E+09 41716005.77 0.271166E+09 0.461368E+09 0.277199E+09
August 0.422971E+09 0.150169E+09 0.272801E+09 0.722900E+09 0.281976E+09
September 0.596478E+09 0.324839E+09 0.271640E+09 0.968769E+09 0.361855E+09
October 0.805507E+09 0.561880E+09 0.243627E+09 0.130872E+10 0.415845E+09
November 0.951824E+09 0.695206E+09 0.256618E+09 0.141674E+10 0.546413E+09
December 0.109636E+10 0.856953E+09 0.239405E+09 0.165329E+10 0.618787E+09
           
Annual Sum or Average 0.768456E+10 0.447305E+10 0.321151E+10 0.114362E+11 0.540294E+10
Minimum of Months 0.285491E+09 20440551.34 0.239405E+09 0.338755E+09 0.277199E+09
Maximum of Months 0.109636E+10 0.856953E+09 0.302954E+09 0.165329E+10 0.618787E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.187225E+10 0.142227E+10 0.449976E+09 0.277786E+10 0.122814E+10
February 0.132144E+10 0.858182E+09 0.463259E+09 0.182959E+10 0.991571E+09
March 0.113767E+10 0.594778E+09 0.542894E+09 0.155045E+10 0.113067E+10
April 0.888846E+09 0.379771E+09 0.509075E+09 0.130404E+10 0.919598E+09
May 0.612773E+09 90186444.90 0.522586E+09 0.693045E+09 0.861850E+09
June 0.507775E+09 37563768.28 0.470211E+09 0.587131E+09 0.631865E+09
July 0.556638E+09 76661844.76 0.479976E+09 0.844005E+09 0.494152E+09
August 0.760407E+09 0.275967E+09 0.484440E+09 0.132146E+10 0.511268E+09
September 0.108196E+10 0.596944E+09 0.485012E+09 0.175468E+10 0.696674E+09
October 0.146844E+10 0.103209E+10 0.436346E+09 0.237927E+10 0.815919E+09
November 0.173509E+10 0.127490E+10 0.460190E+09 0.255675E+10 0.109214E+10
December 0.198689E+10 0.156041E+10 0.426483E+09 0.296732E+10 0.124586E+10
           
Annual Sum or Average 0.139302E+11 0.819972E+10 0.573045E+10 0.205656E+11 0.106197E+11
Minimum of Months 0.507775E+09 37563768.28 0.426483E+09 0.587131E+09 0.494152E+09
Maximum of Months 0.198689E+10 0.156041E+10 0.542894E+09 0.296732E+10 0.124586E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.186760E+10 0.141906E+10 0.448543E+09 0.277541E+10 0.123359E+10
February 0.131755E+10 0.856297E+09 0.461249E+09 0.182848E+10 0.997710E+09
March 0.113625E+10 0.594452E+09 0.541795E+09 0.154910E+10 0.113152E+10
April 0.887838E+09 0.379746E+09 0.508092E+09 0.130273E+10 0.919387E+09
May 0.611668E+09 90180533.33 0.521487E+09 0.691615E+09 0.861728E+09
June 0.506727E+09 37561306.03 0.469166E+09 0.585740E+09 0.631749E+09
July 0.555499E+09 76656819.71 0.478842E+09 0.842452E+09 0.493947E+09
August 0.759343E+09 0.275949E+09 0.483393E+09 0.132000E+10 0.511016E+09
September 0.108090E+10 0.596810E+09 0.484090E+09 0.175324E+10 0.696584E+09
October 0.146491E+10 0.102999E+10 0.434929E+09 0.237606E+10 0.819191E+09
November 0.172734E+10 0.126923E+10 0.458103E+09 0.255356E+10 0.110348E+10
December 0.197661E+10 0.155259E+10 0.424022E+09 0.296129E+10 0.125795E+10
           
Annual Sum or Average 0.138922E+11 0.817852E+10 0.571371E+10 0.205397E+11 0.106579E+11
Minimum of Months 0.506727E+09 37561306.03 0.424022E+09 0.585740E+09 0.493947E+09
Maximum of Months 0.197661E+10 0.155259E+10 0.541795E+09 0.296129E+10 0.125795E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172892E+10 0.130979E+10 0.419131E+09 0.255445E+10 0.123830E+10
February 0.123329E+10 0.799723E+09 0.433565E+09 0.170024E+10 0.100908E+10
March 0.107825E+10 0.565561E+09 0.512686E+09 0.145871E+10 0.113877E+10
April 0.855026E+09 0.369176E+09 0.485850E+09 0.125073E+10 0.915501E+09
May 0.586525E+09 88614020.23 0.497911E+09 0.658470E+09 0.859086E+09
June 0.485451E+09 37008788.61 0.448442E+09 0.559174E+09 0.629169E+09
July 0.534037E+09 75289214.27 0.458748E+09 0.814978E+09 0.488572E+09
August 0.731915E+09 0.268716E+09 0.463200E+09 0.127725E+10 0.504588E+09
September 0.103769E+10 0.575542E+09 0.462146E+09 0.167963E+10 0.691629E+09
October 0.138381E+10 0.972961E+09 0.410846E+09 0.224413E+10 0.820944E+09
November 0.161047E+10 0.118105E+10 0.429416E+09 0.237046E+10 0.111103E+10
December 0.182943E+10 0.143258E+10 0.396842E+09 0.272632E+10 0.125918E+10
           
Annual Sum or Average 0.130948E+11 0.767602E+10 0.541878E+10 0.192945E+11 0.106659E+11
Minimum of Months 0.485451E+09 37008788.61 0.396842E+09 0.559174E+09 0.488572E+09
Maximum of Months 0.182943E+10 0.143258E+10 0.512686E+09 0.272632E+10 0.125918E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129861E+09 65496202.37 64365119.12 0.162863E+09 0.213592E+09
February 0.139932E+09 64599315.81 75333044.03 0.167300E+09 0.174287E+09
March 0.177586E+09 78566695.06 99018941.22 0.217261E+09 0.194786E+09
April 0.236914E+09 0.123361E+09 0.113553E+09 0.327111E+09 0.154391E+09
May 0.240482E+09 0.111078E+09 0.129404E+09 0.320594E+09 0.146446E+09
June 0.246546E+09 0.123268E+09 0.123278E+09 0.350491E+09 0.108994E+09
July 0.269688E+09 0.144308E+09 0.125380E+09 0.419861E+09 87085776.56
August 0.253020E+09 0.137126E+09 0.115894E+09 0.401494E+09 88796821.48
September 0.209644E+09 0.112177E+09 97466490.85 0.309571E+09 0.116351E+09
October 0.165605E+09 90413387.60 75191820.23 0.247834E+09 0.142341E+09
November 0.144766E+09 75722540.26 69042985.65 0.185595E+09 0.190719E+09
December 0.132115E+09 70860135.06 61254550.57 0.168811E+09 0.216972E+09
           
Annual Sum or Average 0.234616E+10 0.119698E+10 0.114918E+10 0.327879E+10 0.183476E+10
Minimum of Months 0.129861E+09 64599315.81 61254550.57 0.162863E+09 87085776.56
Maximum of Months 0.269688E+09 0.144308E+09 0.129404E+09 0.419861E+09 0.216972E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 23356239.37 0.00 23356239.37 17252869.86 85219433.88
February 26481017.09 0.00 26481017.09 18406159.44 69347351.13
March 35927250.35 0.00 35927250.35 28595298.02 79555753.48
April 40057377.51 154171.13 39903206.37 35492849.76 63695696.69
May 49740502.58 2316145.16 47424357.42 45552137.58 58880879.82
June 51291331.66 5014490.96 46276840.70 56766341.39 44672830.29
July 50183758.70 4206136.99 45977621.70 64528083.85 38586585.39
August 41676036.15 834501.41 40841534.74 54521193.14 38121789.95
September 34136537.95 5350.41 34131187.54 38409023.48 49084515.73
October 27980797.83 0.00 27980797.83 34045458.01 58136650.53
November 24517330.91 0.00 24517330.91 18533726.92 76781884.08
December 21742678.15 0.00 21742678.15 15569343.61 86401093.74
           
Annual Sum or Average 0.427091E+09 12530796.07 0.414560E+09 0.427672E+09 0.748484E+09
Minimum of Months 21742678.15 0.00 21742678.15 15569343.61 38121789.95
Maximum of Months 51291331.66 5014490.96 47424357.42 64528083.85 86401093.74



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.389579E+09 0.196486E+09 0.193093E+09 0.526417E+09 0.537984E+09
February 0.419792E+09 0.193795E+09 0.225997E+09 0.537970E+09 0.436419E+09
March 0.532750E+09 0.235697E+09 0.297054E+09 0.689266E+09 0.500365E+09
April 0.710735E+09 0.370078E+09 0.340657E+09 0.101289E+10 0.407342E+09
May 0.721437E+09 0.333230E+09 0.388207E+09 0.987910E+09 0.395588E+09
June 0.739629E+09 0.369800E+09 0.369829E+09 0.107256E+10 0.300533E+09
July 0.809055E+09 0.432917E+09 0.376137E+09 0.126058E+10 0.255476E+09
August 0.759051E+09 0.411374E+09 0.347678E+09 0.121629E+10 0.250214E+09
September 0.628924E+09 0.336527E+09 0.292396E+09 0.956612E+09 0.307282E+09
October 0.496810E+09 0.271236E+09 0.225573E+09 0.773160E+09 0.367925E+09
November 0.434291E+09 0.227164E+09 0.207127E+09 0.594343E+09 0.480929E+09
December 0.396339E+09 0.212577E+09 0.183762E+09 0.545481E+09 0.543357E+09
           
Annual Sum or Average 0.703839E+10 0.359088E+10 0.344751E+10 0.101735E+11 0.478342E+10
Minimum of Months 0.389579E+09 0.193795E+09 0.183762E+09 0.526417E+09 0.250214E+09
Maximum of Months 0.809055E+09 0.432917E+09 0.388207E+09 0.126058E+10 0.543357E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161454E+09 0.00 0.161454E+09 0.121413E+09 0.587308E+09
February 0.183054E+09 0.00 0.183054E+09 0.128808E+09 0.478213E+09
March 0.248353E+09 0.00 0.248353E+09 0.198864E+09 0.549567E+09
April 0.276903E+09 1065730.73 0.275837E+09 0.245995E+09 0.440306E+09
May 0.343839E+09 16010695.39 0.327828E+09 0.314982E+09 0.407024E+09
June 0.354560E+09 34663409.09 0.319896E+09 0.392430E+09 0.308809E+09
July 0.346903E+09 29075542.96 0.317828E+09 0.446131E+09 0.266736E+09
August 0.288092E+09 5768614.17 0.282324E+09 0.377324E+09 0.263523E+09
September 0.235974E+09 36985.49 0.235937E+09 0.266845E+09 0.339260E+09
October 0.193422E+09 0.00 0.193422E+09 0.237654E+09 0.401170E+09
November 0.169480E+09 0.00 0.169480E+09 0.130433E+09 0.529029E+09
December 0.150300E+09 0.00 0.150300E+09 0.110520E+09 0.595311E+09
           
Annual Sum or Average 0.295233E+10 86620977.84 0.286571E+10 0.297140E+10 0.516626E+10
Minimum of Months 0.150300E+09 0.00 0.150300E+09 0.110520E+09 0.263523E+09
Maximum of Months 0.354560E+09 34663409.09 0.327828E+09 0.446131E+09 0.595311E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196705E+09 0.00 0.196705E+09 0.129307E+09 0.774145E+09
February 0.223023E+09 0.00 0.223023E+09 0.138617E+09 0.634730E+09
March 0.302579E+09 0.00 0.302579E+09 0.222336E+09 0.722953E+09
April 0.337361E+09 1298449.69 0.336062E+09 0.288860E+09 0.565783E+09
May 0.418913E+09 19506880.98 0.399406E+09 0.371233E+09 0.524166E+09
June 0.431974E+09 42232706.26 0.389742E+09 0.471312E+09 0.395170E+09
July 0.422645E+09 35424642.22 0.387220E+09 0.562684E+09 0.317563E+09
August 0.350993E+09 7028281.24 0.343964E+09 0.475561E+09 0.313858E+09
September 0.287496E+09 45061.85 0.287451E+09 0.321368E+09 0.427241E+09
October 0.235653E+09 0.00 0.235653E+09 0.276529E+09 0.521981E+09
November 0.206484E+09 0.00 0.206484E+09 0.141114E+09 0.695816E+09
December 0.183116E+09 0.00 0.183116E+09 0.115939E+09 0.784990E+09
           
Annual Sum or Average 0.359694E+10 0.105536E+09 0.349141E+10 0.351486E+10 0.667840E+10
Minimum of Months 0.183116E+09 0.00 0.183116E+09 0.115939E+09 0.313858E+09
Maximum of Months 0.431974E+09 42232706.26 0.399406E+09 0.562684E+09 0.784990E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196705E+09 0.00 0.196705E+09 0.129306E+09 0.774144E+09
February 0.223022E+09 0.00 0.223022E+09 0.138617E+09 0.634730E+09
March 0.302578E+09 0.00 0.302578E+09 0.222336E+09 0.722953E+09
April 0.337360E+09 1298447.20 0.336062E+09 0.288860E+09 0.565783E+09
May 0.418913E+09 19506843.53 0.399406E+09 0.371232E+09 0.524166E+09
June 0.431974E+09 42232625.18 0.389741E+09 0.471311E+09 0.395170E+09
July 0.422645E+09 35424574.21 0.387220E+09 0.562683E+09 0.317563E+09
August 0.350992E+09 7028267.75 0.343964E+09 0.475560E+09 0.313858E+09
September 0.287496E+09 45061.77 0.287451E+09 0.321368E+09 0.427241E+09
October 0.235653E+09 0.00 0.235653E+09 0.276529E+09 0.521981E+09
November 0.206484E+09 0.00 0.206484E+09 0.141114E+09 0.695816E+09
December 0.183116E+09 0.00 0.183116E+09 0.115939E+09 0.784990E+09
           
Annual Sum or Average 0.359694E+10 0.105536E+09 0.349140E+10 0.351486E+10 0.667840E+10
Minimum of Months 0.183116E+09 0.00 0.183116E+09 0.115939E+09 0.313858E+09
Maximum of Months 0.431974E+09 42232625.18 0.399406E+09 0.562683E+09 0.784990E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196699E+09 0.00 0.196699E+09 0.129302E+09 0.774119E+09
February 0.223015E+09 0.00 0.223015E+09 0.138613E+09 0.634709E+09
March 0.302568E+09 0.00 0.302568E+09 0.222329E+09 0.722929E+09
April 0.337349E+09 1298406.25 0.336051E+09 0.288851E+09 0.565764E+09
May 0.418899E+09 19506228.39 0.399393E+09 0.371220E+09 0.524148E+09
June 0.431960E+09 42231293.39 0.389728E+09 0.471296E+09 0.395157E+09
July 0.422631E+09 35423457.10 0.387207E+09 0.562665E+09 0.317553E+09
August 0.350981E+09 7028046.12 0.343953E+09 0.475545E+09 0.313848E+09
September 0.287486E+09 45060.35 0.287441E+09 0.321358E+09 0.427227E+09
October 0.235645E+09 0.00 0.235645E+09 0.276520E+09 0.521963E+09
November 0.206477E+09 0.00 0.206477E+09 0.141110E+09 0.695793E+09
December 0.183110E+09 0.00 0.183110E+09 0.115935E+09 0.784964E+09
           
Annual Sum or Average 0.359682E+10 0.105532E+09 0.349129E+10 0.351474E+10 0.667817E+10
Minimum of Months 0.183110E+09 0.00 0.183110E+09 0.115935E+09 0.313848E+09
Maximum of Months 0.431960E+09 42231293.39 0.399393E+09 0.562665E+09 0.784964E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 22181161.28 0.00 22181161.28 13128789.81 93505779.23
February 25148779.90 0.00 25148779.90 14129139.93 77661411.86
March 34119777.20 0.00 34119777.20 23270363.02 87842332.30
April 38041937.38 146417.51 37895519.87 30969572.15 68624458.52
May 47238056.74 2199660.84 45038395.90 40497442.33 62453303.73
June 48710871.86 4762300.56 43948571.31 51538523.80 47503863.66
July 47658886.91 3994600.59 43664286.32 62620110.91 37471196.14
August 39579108.93 792532.39 38786576.54 52032775.35 37952132.07
September 32419017.21 5081.32 32413935.89 34348995.06 52643568.90
October 26573025.34 0.00 26573025.34 30741331.16 62157549.91
November 23283845.26 0.00 23283845.26 14371387.72 84834287.51
December 20648768.79 0.00 20648768.79 11521259.77 95380112.62
           
Annual Sum or Average 0.405603E+09 11900593.21 0.393703E+09 0.379170E+09 0.808030E+09
Minimum of Months 20648768.79 0.00 20648768.79 11521259.77 37471196.14
Maximum of Months 48710871.86 4762300.56 45038395.90 62620110.91 95380112.62



Table of Contents

Report: WindowEnergyReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.281296E+09 0.00 0.281296E+09 0.166496E+09 0.118582E+10
February 0.318931E+09 0.00 0.318931E+09 0.179182E+09 0.984883E+09
March 0.432699E+09 0.00 0.432699E+09 0.295109E+09 0.111400E+10
April 0.482439E+09 1856831.50 0.480582E+09 0.392749E+09 0.870279E+09
May 0.599062E+09 27895567.62 0.571166E+09 0.513579E+09 0.792018E+09
June 0.617740E+09 60394345.69 0.557345E+09 0.653599E+09 0.602433E+09
July 0.604398E+09 50658560.09 0.553740E+09 0.794133E+09 0.475201E+09
August 0.501933E+09 10050704.41 0.491882E+09 0.659867E+09 0.481300E+09
September 0.411130E+09 64440.13 0.411066E+09 0.435606E+09 0.667613E+09
October 0.336993E+09 0.00 0.336993E+09 0.389854E+09 0.788267E+09
November 0.295280E+09 0.00 0.295280E+09 0.182254E+09 0.107585E+10
December 0.261863E+09 0.00 0.261863E+09 0.146110E+09 0.120959E+10
           
Annual Sum or Average 0.514376E+10 0.150920E+09 0.499284E+10 0.480854E+10 0.102472E+11
Minimum of Months 0.261863E+09 0.00 0.261863E+09 0.146110E+09 0.475201E+09
Maximum of Months 0.617740E+09 60394345.69 0.571166E+09 0.794133E+09 0.120959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 51461854.79 28845621.92 22616232.87 65424347.17 0.101190E+09
February 55879368.38 29367947.06 26511421.32 65736176.59 88404967.25
March 72667928.25 37290988.46 35376939.79 85906803.51 99947482.33
April 95436343.43 55377467.77 40058875.65 0.132191E+09 78969760.18
May 80146159.21 37950150.62 42196008.59 0.102538E+09 77294412.23
June 74107764.19 34245781.81 39861982.38 0.100993E+09 58807169.50
July 86480845.47 44777218.47 41703627.00 0.130418E+09 49758152.32
August 95389711.57 55015045.38 40374666.19 0.148548E+09 49976728.40
September 88266489.18 52340211.94 35926277.24 0.131254E+09 57223238.60
October 68702375.46 41731409.12 26970966.34 0.105715E+09 65593518.88
November 56993734.64 32757400.58 24236334.06 73707620.53 92569052.16
December 48914854.64 27930544.25 20984310.39 63442759.32 0.104442E+09
           
Annual Sum or Average 0.874447E+09 0.477630E+09 0.396818E+09 0.120587E+10 0.924176E+09
Minimum of Months 48914854.64 27930544.25 20984310.39 63442759.32 49758152.32
Maximum of Months 95436343.43 55377467.77 42196008.59 0.148548E+09 0.104442E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.158546E+09 53287432.01 0.105259E+09 0.142283E+09 0.552916E+09
February 0.203138E+09 76038693.99 0.127099E+09 0.183402E+09 0.477755E+09
March 0.329303E+09 0.143478E+09 0.185825E+09 0.349988E+09 0.533486E+09
April 0.508002E+09 0.282718E+09 0.225284E+09 0.684720E+09 0.415832E+09
May 0.521527E+09 0.263310E+09 0.258217E+09 0.681637E+09 0.398305E+09
June 0.534637E+09 0.287370E+09 0.247268E+09 0.754263E+09 0.302123E+09
July 0.590580E+09 0.338876E+09 0.251704E+09 0.896880E+09 0.259668E+09
August 0.552926E+09 0.320527E+09 0.232399E+09 0.849378E+09 0.263894E+09
September 0.423442E+09 0.234414E+09 0.189028E+09 0.605224E+09 0.305475E+09
October 0.266023E+09 0.129971E+09 0.136052E+09 0.381585E+09 0.357877E+09
November 0.181877E+09 68808672.30 0.113068E+09 0.176266E+09 0.505351E+09
December 0.138526E+09 42836818.23 95689366.98 0.118051E+09 0.571522E+09
           
Annual Sum or Average 0.440853E+10 0.224164E+10 0.216689E+10 0.582368E+10 0.494420E+10
Minimum of Months 0.138526E+09 42836818.23 95689366.98 0.118051E+09 0.259668E+09
Maximum of Months 0.590580E+09 0.338876E+09 0.258217E+09 0.896880E+09 0.571522E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.145777E+09 0.106934E+09 38842936.86 0.217913E+09 87095668.06
February 0.103485E+09 63741542.89 39743826.67 0.147153E+09 69860126.12
March 91341450.96 44122230.11 47219220.86 0.129756E+09 78762546.94
April 73856164.78 28162072.76 45694092.02 0.110680E+09 64403036.53
May 54344312.33 6687812.36 47656499.97 67580714.57 59734329.21
June 46136513.15 2785556.46 43350956.70 57556889.38 44645988.93
July 50500285.04 5684890.16 44815394.88 72046850.13 40784521.20
August 64877714.87 20464465.18 44413249.69 0.105516E+09 43597191.96
September 87365174.42 44270965.33 43094209.09 0.140448E+09 52250588.93
October 0.114812E+09 76754839.83 38056872.83 0.184210E+09 61195261.06
November 0.135041E+09 95336619.04 39704014.72 0.200691E+09 78019154.51
December 0.155737E+09 0.118536E+09 37200775.33 0.232883E+09 88575383.12
           
Annual Sum or Average 0.112327E+10 0.613481E+09 0.509792E+09 0.166643E+10 0.768924E+09
Minimum of Months 46136513.15 2785556.46 37200775.33 57556889.38 40784521.20
Maximum of Months 0.155737E+09 0.118536E+09 47656499.97 0.232883E+09 88575383.12



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196828E+10 0.144382E+10 0.524456E+09 0.294226E+10 0.117596E+10
February 0.139726E+10 0.860636E+09 0.536620E+09 0.198686E+10 0.943249E+09
March 0.123329E+10 0.595737E+09 0.637552E+09 0.175196E+10 0.106345E+10
April 0.997204E+09 0.380243E+09 0.616960E+09 0.149440E+10 0.869568E+09
May 0.733755E+09 90298631.88 0.643457E+09 0.912473E+09 0.806531E+09
June 0.622934E+09 37610495.54 0.585323E+09 0.777131E+09 0.602809E+09
July 0.681853E+09 76757207.88 0.605096E+09 0.972774E+09 0.550671E+09
August 0.875977E+09 0.276311E+09 0.599666E+09 0.142467E+10 0.588648E+09
September 0.117960E+10 0.597745E+09 0.581857E+09 0.189632E+10 0.705486E+09
October 0.155018E+10 0.103634E+10 0.513843E+09 0.248720E+10 0.826256E+09
November 0.182331E+10 0.128723E+10 0.536082E+09 0.270972E+10 0.105341E+10
December 0.210275E+10 0.160047E+10 0.502284E+09 0.314437E+10 0.119594E+10
           
Annual Sum or Average 0.151664E+11 0.828320E+10 0.688320E+10 0.225001E+11 0.103820E+11
Minimum of Months 0.622934E+09 37610495.54 0.502284E+09 0.777131E+09 0.550671E+09
Maximum of Months 0.210275E+10 0.160047E+10 0.643457E+09 0.314437E+10 0.119594E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.271385E+09 0.119884E+09 0.151501E+09 0.291315E+09 0.706982E+09
February 0.321430E+09 0.140169E+09 0.181262E+09 0.325885E+09 0.613338E+09
March 0.472105E+09 0.216633E+09 0.255472E+09 0.515496E+09 0.702007E+09
April 0.685403E+09 0.383689E+09 0.301714E+09 0.896396E+09 0.579191E+09
May 0.678754E+09 0.337723E+09 0.341031E+09 0.840126E+09 0.563465E+09
June 0.685571E+09 0.360056E+09 0.325515E+09 0.908552E+09 0.443599E+09
July 0.762013E+09 0.429795E+09 0.332218E+09 0.110524E+10 0.386325E+09
August 0.732910E+09 0.423605E+09 0.309306E+09 0.108235E+10 0.391024E+09
September 0.590098E+09 0.332538E+09 0.257559E+09 0.812832E+09 0.445301E+09
October 0.406634E+09 0.217326E+09 0.189308E+09 0.566196E+09 0.507671E+09
November 0.305648E+09 0.143066E+09 0.162583E+09 0.334904E+09 0.659925E+09
December 0.247566E+09 0.108795E+09 0.138771E+09 0.265066E+09 0.730133E+09
           
Annual Sum or Average 0.615952E+10 0.321328E+10 0.294624E+10 0.794435E+10 0.672896E+10
Minimum of Months 0.247566E+09 0.108795E+09 0.138771E+09 0.265066E+09 0.386325E+09
Maximum of Months 0.762013E+09 0.429795E+09 0.341031E+09 0.110524E+10 0.730133E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.955036E+09 0.510776E+09 0.444260E+09 0.107843E+10 0.156206E+10
February 0.909968E+09 0.416864E+09 0.493105E+09 0.967276E+09 0.128855E+10
March 0.122377E+10 0.545248E+09 0.678527E+09 0.138580E+10 0.142889E+10
April 0.151411E+10 0.759357E+09 0.754754E+09 0.198693E+10 0.112970E+10
May 0.147652E+10 0.616186E+09 0.860333E+09 0.185821E+10 0.105530E+10
June 0.141999E+10 0.616109E+09 0.803882E+09 0.192717E+10 0.814422E+09
July 0.166259E+10 0.826185E+09 0.836405E+09 0.244673E+10 0.748503E+09
August 0.164194E+10 0.872145E+09 0.769798E+09 0.245001E+10 0.767140E+09
September 0.115690E+10 0.530136E+09 0.626765E+09 0.159372E+10 0.906795E+09
October 0.105820E+10 0.543890E+09 0.514315E+09 0.148545E+10 0.104633E+10
November 0.933559E+09 0.474287E+09 0.459273E+09 0.105078E+10 0.140643E+10
December 0.920285E+09 0.511320E+09 0.408965E+09 0.102969E+10 0.158996E+10
           
Annual Sum or Average 0.148729E+11 0.722250E+10 0.765038E+10 0.192602E+11 0.137441E+11
Minimum of Months 0.909968E+09 0.416864E+09 0.408965E+09 0.967276E+09 0.748503E+09
Maximum of Months 0.166259E+10 0.872145E+09 0.860333E+09 0.245001E+10 0.158996E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.144743E+09 0.106175E+09 38567482.86 0.211177E+09 93705353.32
February 0.102751E+09 63289235.43 39461982.67 0.140043E+09 78260728.31
March 90693536.89 43809140.51 46884396.38 0.120493E+09 90827784.57
April 73332426.07 27962235.81 45370190.26 0.103098E+09 74230878.80
May 53959036.43 6640355.91 47318680.51 58692008.71 70297913.26
June 45809487.06 2765790.26 43043696.81 49472591.67 53169985.40
July 50142339.18 5644550.40 44497788.77 64307143.62 48181417.36
August 64417719.00 20319250.14 44098468.86 99297886.69 49927071.55
September 86745518.16 43956820.31 42788697.84 0.136086E+09 57417559.79
October 0.113997E+09 76210190.52 37787042.16 0.181069E+09 64287615.08
November 0.134083E+09 94660114.17 39422455.92 0.194569E+09 84256665.60
December 0.154632E+09 0.117695E+09 36936966.51 0.226938E+09 94423967.59
           
Annual Sum or Average 0.111531E+10 0.609128E+09 0.506178E+09 0.158524E+10 0.858987E+09
Minimum of Months 45809487.06 2765790.26 36936966.51 49472591.67 48181417.36
Maximum of Months 0.154632E+09 0.117695E+09 47318680.51 0.226938E+09 94423967.59



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.219175E+10 0.160775E+10 0.584004E+09 0.319772E+10 0.141892E+10
February 0.155590E+10 0.958350E+09 0.597549E+09 0.212059E+10 0.118505E+10
March 0.137332E+10 0.663375E+09 0.709942E+09 0.182456E+10 0.137535E+10
April 0.111043E+10 0.423415E+09 0.687013E+09 0.156115E+10 0.112390E+10
May 0.817069E+09 0.100551E+09 0.716518E+09 0.888747E+09 0.106376E+10
June 0.693665E+09 41880670.46 0.651784E+09 0.749224E+09 0.804434E+09
July 0.759275E+09 85471974.85 0.673803E+09 0.973870E+09 0.728979E+09
August 0.975438E+09 0.307682E+09 0.667756E+09 0.150361E+10 0.755707E+09
September 0.131353E+10 0.665611E+09 0.647923E+09 0.206067E+10 0.869436E+09
October 0.172619E+10 0.115400E+10 0.572186E+09 0.274182E+10 0.973468E+09
November 0.203033E+10 0.143338E+10 0.596950E+09 0.294624E+10 0.127585E+10
December 0.234149E+10 0.178218E+10 0.559314E+09 0.343639E+10 0.142980E+10
           
Annual Sum or Average 0.168884E+11 0.922365E+10 0.766474E+10 0.240046E+11 0.130047E+11
Minimum of Months 0.693665E+09 41880670.46 0.559314E+09 0.749224E+09 0.728979E+09
Maximum of Months 0.234149E+10 0.178218E+10 0.716518E+09 0.343639E+10 0.142980E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109843E+09 71056934.23 38786345.08 0.122628E+09 0.119976E+09
February 0.119095E+09 67880147.58 51215239.50 0.130020E+09 95133620.58
March 0.167971E+09 95115141.97 72855674.49 0.192073E+09 0.103403E+09
April 0.249338E+09 0.181898E+09 67439880.63 0.304103E+09 85212743.35
May 0.254243E+09 0.163439E+09 90803915.12 0.306929E+09 79974810.73
June 0.262478E+09 0.181041E+09 81437262.36 0.325651E+09 61574202.58
July 0.297766E+09 0.223495E+09 74271232.62 0.378007E+09 60199870.09
August 0.274798E+09 0.210788E+09 64009310.68 0.351082E+09 62620923.65
September 0.202966E+09 0.144204E+09 58762165.27 0.253604E+09 70735936.49
October 0.150765E+09 0.104530E+09 46234662.83 0.187330E+09 84576545.28
November 0.116671E+09 74521616.16 42149486.29 0.131513E+09 0.107543E+09
December 0.102217E+09 68330546.32 33886912.74 0.112407E+09 0.123704E+09
           
Annual Sum or Average 0.230815E+10 0.158630E+10 0.721852E+09 0.279535E+10 0.105466E+10
Minimum of Months 0.102217E+09 67880147.58 33886912.74 0.112407E+09 60199870.09
Maximum of Months 0.297766E+09 0.223495E+09 90803915.12 0.378007E+09 0.123704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60222174.36 32208239.76 28013934.60 67738407.75 0.100267E+09
February 57380296.45 26286370.20 31093926.25 59795292.00 85171137.65
March 77168142.24 34381930.22 42786212.02 85209908.53 95048672.79
April 95475994.97 47883132.98 47592861.99 0.122435E+09 75927873.24
May 93105526.16 38855112.80 54250413.36 0.113299E+09 71748176.04
June 89541018.28 38850266.73 50690751.54 0.118188E+09 55739886.93
July 0.104839E+09 52097145.66 52741550.52 0.151092E+09 51487576.33
August 0.103537E+09 54995239.73 48541490.57 0.152285E+09 51751245.95
September 72951250.49 33429028.81 39522221.68 99192377.49 59844330.13
October 66727697.32 34296319.60 32431377.73 93066669.76 67312548.29
November 58867884.43 29907321.41 28960563.02 65766750.77 90160788.63
December 58030819.31 32242527.82 25788291.49 64849295.56 0.101301E+09
           
Annual Sum or Average 0.937846E+09 0.455433E+09 0.482414E+09 0.119292E+10 0.905760E+09
Minimum of Months 57380296.45 26286370.20 25788291.49 59795292.00 51487576.33
Maximum of Months 0.104839E+09 54995239.73 54250413.36 0.152285E+09 0.101301E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.712824E+09 0.381227E+09 0.331598E+09 0.802434E+09 0.118611E+10
February 0.679187E+09 0.311133E+09 0.368054E+09 0.708903E+09 0.100772E+10
March 0.913408E+09 0.406955E+09 0.506453E+09 0.101054E+10 0.112453E+10
April 0.113011E+10 0.566759E+09 0.563355E+09 0.145353E+10 0.898525E+09
May 0.110206E+10 0.459901E+09 0.642157E+09 0.134441E+10 0.849447E+09
June 0.105987E+10 0.459844E+09 0.600024E+09 0.140235E+10 0.659783E+09
July 0.124094E+10 0.616638E+09 0.624303E+09 0.179272E+10 0.609445E+09
August 0.122553E+10 0.650940E+09 0.574587E+09 0.180734E+10 0.612726E+09
September 0.863500E+09 0.395676E+09 0.467823E+09 0.117796E+10 0.708216E+09
October 0.789830E+09 0.405942E+09 0.383888E+09 0.110420E+10 0.796575E+09
November 0.696795E+09 0.353992E+09 0.342803E+09 0.779483E+09 0.106669E+10
December 0.686886E+09 0.381632E+09 0.305254E+09 0.768331E+09 0.119859E+10
           
Annual Sum or Average 0.111009E+11 0.539064E+10 0.571030E+10 0.141522E+11 0.107184E+11
Minimum of Months 0.679187E+09 0.311133E+09 0.305254E+09 0.708903E+09 0.609445E+09
Maximum of Months 0.124094E+10 0.650940E+09 0.642157E+09 0.180734E+10 0.119859E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.363822E+09 0.194580E+09 0.169242E+09 0.404135E+09 0.689446E+09
February 0.346653E+09 0.158804E+09 0.187849E+09 0.358996E+09 0.589925E+09
March 0.466198E+09 0.207712E+09 0.258486E+09 0.510583E+09 0.644420E+09
April 0.576802E+09 0.289277E+09 0.287524E+09 0.745873E+09 0.502895E+09
May 0.562481E+09 0.234736E+09 0.327745E+09 0.689575E+09 0.472526E+09
June 0.540947E+09 0.234707E+09 0.306240E+09 0.724483E+09 0.366849E+09
July 0.633365E+09 0.314735E+09 0.318629E+09 0.926367E+09 0.335957E+09
August 0.625499E+09 0.332244E+09 0.293255E+09 0.935435E+09 0.340981E+09
September 0.440722E+09 0.201955E+09 0.238767E+09 0.608520E+09 0.394186E+09
October 0.403124E+09 0.207195E+09 0.195929E+09 0.569670E+09 0.447397E+09
November 0.355640E+09 0.180680E+09 0.174960E+09 0.399626E+09 0.610260E+09
December 0.350583E+09 0.194787E+09 0.155796E+09 0.387087E+09 0.691453E+09
           
Annual Sum or Average 0.566584E+10 0.275141E+10 0.291442E+10 0.726035E+10 0.608630E+10
Minimum of Months 0.346653E+09 0.158804E+09 0.155796E+09 0.358996E+09 0.335957E+09
Maximum of Months 0.633365E+09 0.332244E+09 0.327745E+09 0.935435E+09 0.691453E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.329236E+09 0.00 0.329236E+09 0.158159E+09 0.153151E+10
February 0.374084E+09 0.00 0.374084E+09 0.173052E+09 0.126034E+10
March 0.508491E+09 0.00 0.508491E+09 0.293489E+09 0.143225E+10
April 0.562409E+09 1516069.03 0.560893E+09 0.405416E+09 0.114053E+10
May 0.686940E+09 24165604.27 0.662774E+09 0.513360E+09 0.104224E+10
June 0.695614E+09 49365136.70 0.646249E+09 0.656698E+09 0.816270E+09
July 0.682722E+09 40782279.27 0.641940E+09 0.715962E+09 0.736770E+09
August 0.580865E+09 7618989.67 0.573246E+09 0.596774E+09 0.752965E+09
September 0.483116E+09 25801.14 0.483090E+09 0.448376E+09 0.905064E+09
October 0.396347E+09 0.00 0.396347E+09 0.411531E+09 0.105281E+10
November 0.345581E+09 0.00 0.345581E+09 0.181739E+09 0.137196E+10
December 0.306173E+09 0.00 0.306173E+09 0.141187E+09 0.154491E+10
           
Annual Sum or Average 0.595158E+10 0.123474E+09 0.582810E+10 0.469574E+10 0.135876E+11
Minimum of Months 0.306173E+09 0.00 0.306173E+09 0.141187E+09 0.736770E+09
Maximum of Months 0.695614E+09 49365136.70 0.662774E+09 0.715962E+09 0.154491E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60793275.14 32513677.93 28279597.21 73120920.68 90691896.78
February 57924447.05 26535649.92 31388797.13 64951232.74 75335385.95
March 77899945.54 34707982.00 43191963.54 91421724.22 85211575.55
April 96381415.87 48337219.78 48044196.08 0.128933E+09 68902062.78
May 93988467.35 39223584.80 54764882.55 0.119311E+09 66301970.65
June 90390156.42 39218692.78 51171463.64 0.122941E+09 52566245.05
July 0.105833E+09 52591194.92 53241710.82 0.155649E+09 47762210.38
August 0.104519E+09 55516772.28 49001820.73 0.156924E+09 47527268.00
September 73643064.04 33746044.01 39897020.03 0.103478E+09 55926929.33
October 67360491.48 34621559.51 32738931.97 97062022.90 64192968.31
November 59426142.17 30190939.44 29235202.73 71097262.71 81863404.53
December 58581138.96 32548291.16 26032847.81 70345359.48 91287311.38
           
Annual Sum or Average 0.946740E+09 0.459752E+09 0.486988E+09 0.125523E+10 0.827569E+09
Minimum of Months 57924447.05 26535649.92 26032847.81 64951232.74 47527268.00
Maximum of Months 0.105833E+09 55516772.28 54764882.55 0.156924E+09 91287311.38



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.621376E+09 0.332326E+09 0.289049E+09 0.747378E+09 0.926974E+09
February 0.592053E+09 0.271224E+09 0.320829E+09 0.663875E+09 0.770013E+09
March 0.796225E+09 0.354755E+09 0.441471E+09 0.934433E+09 0.870958E+09
April 0.985127E+09 0.494061E+09 0.491066E+09 0.131784E+10 0.704249E+09
May 0.960668E+09 0.400909E+09 0.559759E+09 0.121952E+10 0.677471E+09
June 0.923889E+09 0.400859E+09 0.523030E+09 0.125674E+10 0.536812E+09
July 0.108173E+10 0.537541E+09 0.544190E+09 0.159108E+10 0.487827E+09
August 0.106830E+10 0.567444E+09 0.500854E+09 0.160397E+10 0.485716E+09
September 0.752715E+09 0.344923E+09 0.407793E+09 0.105766E+10 0.571636E+09
October 0.688500E+09 0.353871E+09 0.334629E+09 0.992083E+09 0.656125E+09
November 0.607402E+09 0.308585E+09 0.298817E+09 0.726694E+09 0.836736E+09
December 0.598765E+09 0.332680E+09 0.266085E+09 0.719009E+09 0.933059E+09
           
Annual Sum or Average 0.967675E+10 0.469918E+10 0.497757E+10 0.128303E+11 0.845758E+10
Minimum of Months 0.592053E+09 0.271224E+09 0.266085E+09 0.663875E+09 0.485716E+09
Maximum of Months 0.108173E+10 0.567444E+09 0.559759E+09 0.160397E+10 0.933059E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.320341E+09 0.00 0.320341E+09 0.153788E+09 0.143794E+10
February 0.363199E+09 0.00 0.363199E+09 0.166398E+09 0.120717E+10
March 0.492759E+09 0.00 0.492759E+09 0.282656E+09 0.137184E+10
April 0.549404E+09 2114555.97 0.547289E+09 0.386050E+09 0.107869E+10
May 0.682214E+09 31767416.05 0.650446E+09 0.517103E+09 0.966086E+09
June 0.703484E+09 68776958.86 0.634707E+09 0.679709E+09 0.733911E+09
July 0.688292E+09 57689865.89 0.630602E+09 0.752463E+09 0.647426E+09
August 0.571604E+09 11445721.88 0.560158E+09 0.602553E+09 0.678373E+09
September 0.468197E+09 73384.29 0.468124E+09 0.438294E+09 0.841651E+09
October 0.383769E+09 0.00 0.383769E+09 0.396600E+09 0.976450E+09
November 0.336266E+09 0.00 0.336266E+09 0.170677E+09 0.131170E+10
December 0.298210E+09 0.00 0.298210E+09 0.132494E+09 0.147019E+10
           
Annual Sum or Average 0.585774E+10 0.171868E+09 0.568587E+10 0.467879E+10 0.127214E+11
Minimum of Months 0.298210E+09 0.00 0.298210E+09 0.132494E+09 0.647426E+09
Maximum of Months 0.703484E+09 68776958.86 0.650446E+09 0.752463E+09 0.147019E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 16731294.85 0.00 16731294.85 6885718.54 94597552.59
February 18623259.36 0.00 18623259.36 6149696.26 81650061.31
March 25865764.72 425769.45 25439995.27 11639593.93 93231524.84
April 61404270.06 26677431.28 34726838.78 70073186.43 67845741.97
May 76238169.64 34152054.39 42086115.25 92013759.28 65089861.13
June 76841371.12 36420419.81 40420951.31 0.103575E+09 50676796.25
July 89966207.94 47293880.93 42672327.02 0.133527E+09 43379097.40
August 76417954.87 39015569.97 37402384.90 0.111926E+09 43030791.77
September 32920580.13 6454853.57 26465726.55 34800553.32 52653104.98
October 20293901.53 73.47 20293828.06 21543488.94 62717974.91
November 17503974.20 0.00 17503974.20 7357383.20 86525406.23
December 15646977.37 0.00 15646977.37 6595104.38 96388734.70
           
Annual Sum or Average 0.528454E+09 0.190440E+09 0.338014E+09 0.606086E+09 0.837787E+09
Minimum of Months 15646977.37 0.00 15646977.37 6149696.26 43030791.77
Maximum of Months 89966207.94 47293880.93 42672327.02 0.133527E+09 96388734.70



Table of Contents

Report: WindowEnergyReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.798146E+09 0.410759E+09 0.387387E+09 0.910724E+09 0.137023E+10
February 0.810346E+09 0.370978E+09 0.439368E+09 0.874502E+09 0.116673E+10
March 0.112133E+10 0.509644E+09 0.611683E+09 0.128360E+10 0.132123E+10
April 0.139290E+10 0.712208E+09 0.680692E+09 0.183691E+10 0.105952E+10
May 0.135394E+10 0.577926E+09 0.776017E+09 0.169127E+10 0.100965E+10
June 0.130256E+10 0.577854E+09 0.724704E+09 0.175770E+10 0.785159E+09
July 0.152815E+10 0.774886E+09 0.753268E+09 0.226169E+10 0.691033E+09
August 0.151129E+10 0.817992E+09 0.693303E+09 0.228124E+10 0.692188E+09
September 0.105929E+10 0.496052E+09 0.563241E+09 0.148185E+10 0.830802E+09
October 0.953554E+09 0.492986E+09 0.460568E+09 0.136730E+10 0.945323E+09
November 0.802162E+09 0.398526E+09 0.403636E+09 0.911285E+09 0.125689E+10
December 0.752438E+09 0.398511E+09 0.353926E+09 0.844866E+09 0.139637E+10
           
Annual Sum or Average 0.133861E+11 0.653832E+10 0.684779E+10 0.175029E+11 0.125251E+11
Minimum of Months 0.752438E+09 0.370978E+09 0.353926E+09 0.844866E+09 0.691033E+09
Maximum of Months 0.152815E+10 0.817992E+09 0.776017E+09 0.228124E+10 0.139637E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 843.45 483.19 602.39 408.54 193.85 0.00 0.00
February 705.87 427.78 532.65 301.31 231.34 0.00 0.00
March 639.34 435.29 485.22 226.30 258.92 0.00 0.00
April 725.83 367.08 513.42 233.99 279.43 0.00 0.00
May 566.55 328.30 439.70 145.38 294.32 0.00 0.00
June 593.88 248.63 434.79 151.69 283.10 0.00 0.00
July 696.54 209.04 460.36 179.45 280.91 0.00 0.00
August 783.69 218.64 486.76 217.73 269.02 0.00 0.00
September 806.64 288.56 525.61 273.22 252.39 0.00 0.00
October 849.36 333.28 545.36 341.85 203.51 0.00 0.00
November 847.47 447.30 604.94 396.43 208.51 0.00 0.00
December 896.82 488.77 636.13 450.91 185.21 0.00 0.00
               
Annual Sum or Average 746.65 355.94 522.22 277.18 245.04 0.00 0.00
Minimum of Months 566.55 209.04 434.79 145.38 185.21 0.00 0.00
Maximum of Months 896.82 488.77 636.13 450.91 294.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3230.80 1389.05 2201.72 1615.06 586.66 0.00 0.00
February 2398.69 1241.03 1730.43 1065.85 664.58 0.00 0.00
March 1894.64 1265.71 1379.56 666.39 713.17 0.00 0.00
April 1683.59 1059.78 1152.65 439.52 713.14 0.00 0.00
May 973.32 948.32 820.78 101.01 719.77 0.00 0.00
June 881.58 716.21 720.04 43.47 676.57 0.00 0.00
July 1148.54 562.91 762.72 85.86 676.86 0.00 0.00
August 1666.06 588.28 979.87 309.08 670.79 0.00 0.00
September 2195.12 819.95 1363.49 690.93 672.56 0.00 0.00
October 2781.93 943.10 1734.04 1159.25 574.78 0.00 0.00
November 3083.56 1281.46 2107.54 1487.89 619.65 0.00 0.00
December 3469.23 1403.99 2352.14 1790.28 561.85 0.00 0.00
               
Annual Sum or Average 2116.65 1017.02 1440.87 786.94 653.93 0.00 0.00
Minimum of Months 881.58 562.91 720.04 43.47 561.85 0.00 0.00
Maximum of Months 3469.23 1403.99 2352.14 1790.28 719.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 61.11 78.95 48.48 24.45 24.03 0.00 0.00
February 69.72 70.77 57.84 26.70 31.14 0.00 0.00
March 81.84 71.33 66.30 29.33 36.97 0.00 0.00
April 127.15 58.22 91.40 47.59 43.81 0.00 0.00
May 120.83 53.31 89.79 41.47 48.31 0.00 0.00
June 136.56 40.71 95.12 47.56 47.56 0.00 0.00
July 157.71 31.68 100.69 53.88 46.81 0.00 0.00
August 150.72 32.36 94.47 51.20 43.27 0.00 0.00
September 120.24 43.75 80.88 43.28 37.60 0.00 0.00
October 92.86 52.48 61.83 33.76 28.07 0.00 0.00
November 72.03 72.57 55.85 29.21 26.64 0.00 0.00
December 63.34 80.16 49.33 26.46 22.87 0.00 0.00
               
Annual Sum or Average 104.69 57.12 74.40 37.96 36.44 0.00 0.00
Minimum of Months 61.11 31.68 48.48 24.45 22.87 0.00 0.00
Maximum of Months 157.71 80.16 100.69 53.88 48.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 228.47 438.45 201.37 73.36 128.01 0.00 0.00
February 259.80 393.73 245.05 80.11 164.95 0.00 0.00
March 313.76 408.61 287.30 88.00 199.30 0.00 0.00
April 470.52 339.45 375.43 143.20 232.23 0.00 0.00
May 473.57 312.24 392.61 130.64 261.97 0.00 0.00
June 558.03 244.19 418.46 157.27 261.19 0.00 0.00
July 631.45 200.88 426.12 173.62 252.49 0.00 0.00
August 587.51 197.39 384.61 155.92 228.69 0.00 0.00
September 458.46 254.89 328.02 129.85 198.17 0.00 0.00
October 369.55 296.50 253.74 101.27 152.47 0.00 0.00
November 264.00 404.12 228.28 87.64 140.63 0.00 0.00
December 232.08 442.69 199.65 79.37 120.28 0.00 0.00
               
Annual Sum or Average 404.75 327.41 311.98 116.85 195.14 0.00 0.00
Minimum of Months 228.47 197.39 199.65 73.36 120.28 0.00 0.00
Maximum of Months 631.45 442.69 426.12 173.62 261.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 135.40 1275.09 247.12 0.00 247.12 0.00 0.00
February 150.48 1165.57 318.26 0.00 318.26 0.00 0.00
March 236.07 1206.74 394.65 0.00 394.65 0.00 0.00
April 339.53 964.80 450.50 1.52 448.97 0.00 0.00
May 425.01 869.87 546.37 25.21 521.16 0.00 0.00
June 614.09 681.44 586.19 58.64 527.55 0.00 0.00
July 732.67 511.89 544.89 48.50 496.39 0.00 0.00
August 615.93 498.01 448.02 9.39 438.63 0.00 0.00
September 403.00 707.93 379.38 0.06 379.32 0.00 0.00
October 357.84 840.12 304.08 0.00 304.08 0.00 0.00
November 150.56 1181.30 268.46 0.00 268.46 0.00 0.00
December 123.59 1289.28 227.73 0.00 227.73 0.00 0.00
               
Annual Sum or Average 358.50 931.29 393.28 12.01 381.27 0.00 0.00
Minimum of Months 123.59 498.01 227.73 0.00 227.73 0.00 0.00
Maximum of Months 732.67 1289.28 586.19 58.64 527.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 824.45 481.40 582.32 403.69 178.62 0.00 0.00
February 684.28 422.29 515.69 300.84 214.85 0.00 0.00
March 612.98 430.27 466.02 226.24 239.78 0.00 0.00
April 696.04 361.76 490.86 233.99 256.86 0.00 0.00
May 533.39 323.77 415.22 145.38 269.84 0.00 0.00
June 560.61 245.24 410.69 151.69 259.00 0.00 0.00
July 662.86 203.67 435.01 179.45 255.55 0.00 0.00
August 753.21 212.11 463.42 217.73 245.68 0.00 0.00
September 778.75 282.35 505.35 273.21 232.14 0.00 0.00
October 829.00 327.26 528.98 341.15 187.83 0.00 0.00
November 826.69 443.67 586.55 393.95 192.60 0.00 0.00
December 876.41 488.13 614.06 443.86 170.20 0.00 0.00
               
Annual Sum or Average 720.23 351.45 501.09 275.87 225.22 0.00 0.00
Minimum of Months 533.39 203.67 410.69 145.38 170.20 0.00 0.00
Maximum of Months 876.41 488.13 614.06 443.86 269.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3018.68 1365.27 2030.41 1544.23 486.18 0.00 0.00
February 2214.40 1218.09 1594.08 1038.43 555.65 0.00 0.00
March 1704.91 1246.36 1245.51 655.10 590.42 0.00 0.00
April 1491.15 1039.27 1008.29 435.45 572.84 0.00 0.00
May 769.03 937.92 668.51 100.43 568.08 0.00 0.00
June 677.01 706.52 571.18 43.26 527.92 0.00 0.00
July 937.24 535.92 606.71 85.35 521.36 0.00 0.00
August 1467.78 553.18 833.40 306.39 527.02 0.00 0.00
September 2004.20 783.66 1228.45 682.59 545.86 0.00 0.00
October 2609.41 902.13 1606.02 1132.32 473.71 0.00 0.00
November 2877.38 1259.58 1947.06 1433.12 513.94 0.00 0.00
December 3211.99 1390.17 2143.57 1684.89 458.68 0.00 0.00
               
Annual Sum or Average 1914.48 993.53 1288.88 760.76 528.12 0.00 0.00
Minimum of Months 677.01 535.92 571.18 43.26 458.68 0.00 0.00
Maximum of Months 3211.99 1390.17 2143.57 1684.89 590.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 61.24 78.67 48.48 24.45 24.03 0.00 0.00
February 69.73 70.79 57.84 26.70 31.14 0.00 0.00
March 81.83 71.41 66.30 29.33 36.97 0.00 0.00
April 127.12 58.31 91.40 47.59 43.81 0.00 0.00
May 120.79 53.41 89.79 41.47 48.31 0.00 0.00
June 136.41 40.88 95.12 47.56 47.56 0.00 0.00
July 157.71 31.71 100.69 53.88 46.81 0.00 0.00
August 150.80 32.30 94.47 51.20 43.27 0.00 0.00
September 120.23 43.79 80.88 43.28 37.60 0.00 0.00
October 92.86 52.52 61.83 33.76 28.07 0.00 0.00
November 72.05 72.52 55.85 29.21 26.64 0.00 0.00
December 63.43 79.87 49.33 26.46 22.87 0.00 0.00
               
Annual Sum or Average 104.70 57.11 74.40 37.96 36.44 0.00 0.00
Minimum of Months 61.24 31.71 48.48 24.45 22.87 0.00 0.00
Maximum of Months 157.71 79.87 100.69 53.88 48.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 229.30 438.70 202.17 73.36 128.81 0.00 0.00
February 260.72 394.30 245.98 80.11 165.87 0.00 0.00
March 314.80 409.36 288.39 88.00 200.39 0.00 0.00
April 471.79 340.22 376.72 143.20 233.52 0.00 0.00
May 475.07 312.82 394.10 130.70 263.40 0.00 0.00
June 558.95 245.01 419.99 157.37 262.62 0.00 0.00
July 632.75 201.60 427.64 173.67 253.96 0.00 0.00
August 589.16 197.76 385.96 155.93 230.03 0.00 0.00
September 459.48 255.89 329.17 129.85 199.33 0.00 0.00
October 370.18 297.45 254.62 101.27 153.36 0.00 0.00
November 264.57 404.94 229.14 87.64 141.50 0.00 0.00
December 232.47 443.12 200.42 79.37 121.05 0.00 0.00
               
Annual Sum or Average 405.75 328.08 313.12 116.86 196.26 0.00 0.00
Minimum of Months 229.30 197.76 200.42 73.36 121.05 0.00 0.00
Maximum of Months 632.75 443.12 427.64 173.67 263.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 139.48 1275.03 251.50 0.00 251.50 0.00 0.00
February 155.60 1166.54 323.32 0.00 323.32 0.00 0.00
March 242.61 1208.15 400.61 0.00 400.61 0.00 0.00
April 347.73 966.13 457.72 1.55 456.17 0.00 0.00
May 435.05 870.58 554.89 25.69 529.20 0.00 0.00
June 624.29 682.06 595.90 60.14 535.76 0.00 0.00
July 744.11 512.94 554.55 49.70 504.85 0.00 0.00
August 626.17 499.34 455.68 9.57 446.11 0.00 0.00
September 410.44 710.71 385.68 0.06 385.62 0.00 0.00
October 362.92 843.32 308.91 0.00 308.91 0.00 0.00
November 154.69 1183.36 273.19 0.00 273.19 0.00 0.00
December 126.65 1290.42 231.93 0.00 231.93 0.00 0.00
               
Annual Sum or Average 365.64 932.67 399.80 12.29 387.51 0.00 0.00
Minimum of Months 126.65 499.34 231.93 0.00 231.93 0.00 0.00
Maximum of Months 744.11 1290.42 595.90 60.14 535.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 824.74 483.68 584.37 404.63 179.74 0.00 0.00
February 683.61 425.91 516.89 300.93 215.96 0.00 0.00
March 612.48 433.94 467.27 226.25 241.03 0.00 0.00
April 694.85 366.20 492.33 233.99 258.33 0.00 0.00
May 531.36 328.57 416.81 145.38 271.44 0.00 0.00
June 558.67 249.34 412.26 151.69 260.57 0.00 0.00
July 662.20 206.49 436.66 179.45 257.21 0.00 0.00
August 752.21 215.33 464.94 217.73 247.20 0.00 0.00
September 778.28 285.93 506.67 273.21 233.46 0.00 0.00
October 829.15 329.59 530.14 341.28 188.86 0.00 0.00
November 827.00 446.17 588.24 394.50 193.74 0.00 0.00
December 877.59 490.65 616.79 445.42 171.37 0.00 0.00
               
Annual Sum or Average 719.69 354.77 502.70 276.14 226.55 0.00 0.00
Minimum of Months 531.36 206.49 412.26 145.38 171.37 0.00 0.00
Maximum of Months 877.59 490.65 616.79 445.42 271.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3024.42 1378.78 2041.81 1549.85 491.95 0.00 0.00
February 2212.66 1237.15 1600.64 1039.27 561.37 0.00 0.00
March 1701.23 1269.14 1251.56 655.16 596.39 0.00 0.00
April 1488.18 1062.63 1015.32 435.45 579.87 0.00 0.00
May 762.77 964.21 676.14 100.43 575.71 0.00 0.00
June 668.19 730.21 578.69 43.26 535.42 0.00 0.00
July 933.91 551.31 614.61 85.35 529.26 0.00 0.00
August 1463.06 570.05 840.68 306.39 534.29 0.00 0.00
September 2001.18 804.17 1234.78 682.60 552.18 0.00 0.00
October 2611.37 915.06 1611.84 1133.15 478.69 0.00 0.00
November 2882.80 1272.41 1957.14 1437.19 519.95 0.00 0.00
December 3229.19 1402.75 2162.83 1697.13 465.71 0.00 0.00
               
Annual Sum or Average 1914.16 1011.82 1297.48 762.76 534.72 0.00 0.00
Minimum of Months 668.19 551.31 578.69 43.26 465.71 0.00 0.00
Maximum of Months 3229.19 1402.75 2162.83 1697.13 596.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 60.81 79.75 48.48 24.45 24.03 0.00 0.00
February 69.16 72.04 57.84 26.70 31.14 0.00 0.00
March 81.12 72.72 66.30 29.33 36.97 0.00 0.00
April 126.20 59.56 91.40 47.59 43.81 0.00 0.00
May 119.70 54.68 89.79 41.47 48.31 0.00 0.00
June 135.22 42.05 95.12 47.56 47.56 0.00 0.00
July 156.76 32.51 100.69 53.88 46.81 0.00 0.00
August 149.90 33.15 94.47 51.20 43.27 0.00 0.00
September 119.43 44.89 80.88 43.28 37.60 0.00 0.00
October 92.53 53.14 61.83 33.76 28.07 0.00 0.00
November 71.60 73.58 55.85 29.21 26.64 0.00 0.00
December 63.03 81.01 49.33 26.46 22.87 0.00 0.00
               
Annual Sum or Average 103.97 58.18 74.40 37.96 36.44 0.00 0.00
Minimum of Months 60.81 32.51 48.48 24.45 22.87 0.00 0.00
Maximum of Months 156.76 81.01 100.69 53.88 48.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 242.49 446.13 214.45 73.36 141.09 0.00 0.00
February 277.22 400.73 260.14 80.11 180.03 0.00 0.00
March 335.51 414.94 305.04 88.00 217.05 0.00 0.00
April 495.01 347.23 396.49 143.25 253.24 0.00 0.00
May 500.75 318.95 416.30 131.26 285.04 0.00 0.00
June 584.37 249.59 441.93 157.98 283.95 0.00 0.00
July 659.47 207.55 450.32 174.06 276.26 0.00 0.00
August 613.84 204.54 406.52 156.05 250.46 0.00 0.00
September 481.76 263.30 346.85 129.85 217.00 0.00 0.00
October 386.02 304.77 268.15 101.27 166.88 0.00 0.00
November 279.55 412.05 242.40 87.64 154.75 0.00 0.00
December 244.51 451.16 212.21 79.37 132.84 0.00 0.00
               
Annual Sum or Average 425.87 334.72 330.35 117.01 213.34 0.00 0.00
Minimum of Months 242.49 204.54 212.21 73.36 132.84 0.00 0.00
Maximum of Months 659.47 451.16 450.32 174.06 285.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 144.83 867.09 220.32 0.00 220.32 0.00 0.00
February 171.89 787.11 276.56 0.00 276.56 0.00 0.00
March 249.03 809.75 338.91 0.00 338.91 0.00 0.00
April 334.33 654.83 390.46 1.50 388.96 0.00 0.00
May 415.80 587.10 469.21 21.85 447.36 0.00 0.00
June 545.49 457.37 499.96 48.88 451.08 0.00 0.00
July 630.24 355.69 473.39 39.68 433.71 0.00 0.00
August 532.66 351.54 393.13 7.87 385.26 0.00 0.00
September 371.95 494.49 332.75 0.05 332.69 0.00 0.00
October 309.73 584.65 263.95 0.00 263.95 0.00 0.00
November 163.32 805.33 238.98 0.00 238.98 0.00 0.00
December 129.86 879.24 205.10 0.00 205.10 0.00 0.00
               
Annual Sum or Average 334.36 635.30 342.17 10.04 332.13 0.00 0.00
Minimum of Months 129.86 351.54 205.10 0.00 205.10 0.00 0.00
Maximum of Months 630.24 879.24 499.96 48.88 451.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 67.06 477.64 113.31 0.00 113.31 0.00 0.00
February 79.91 439.21 142.23 0.00 142.23 0.00 0.00
March 118.87 448.71 174.29 0.00 174.29 0.00 0.00
April 163.47 362.23 200.80 0.77 200.03 0.00 0.00
May 206.87 319.02 241.30 11.24 230.06 0.00 0.00
June 272.04 250.75 257.12 25.14 231.98 0.00 0.00
July 319.88 191.41 243.45 20.41 223.05 0.00 0.00
August 265.79 193.87 202.18 4.05 198.13 0.00 0.00
September 181.31 277.88 171.12 0.03 171.10 0.00 0.00
October 157.03 317.51 135.74 0.00 135.74 0.00 0.00
November 75.86 447.79 122.90 0.00 122.90 0.00 0.00
December 58.85 487.22 105.48 0.00 105.48 0.00 0.00
               
Annual Sum or Average 164.50 350.56 175.97 5.16 170.81 0.00 0.00
Minimum of Months 58.85 191.41 105.48 0.00 105.48 0.00 0.00
Maximum of Months 319.88 487.22 257.12 25.14 231.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 76.74 243.41 78.41 30.66 47.74 0.00 0.00
February 102.34 233.38 107.07 43.57 63.50 0.00 0.00
March 162.63 236.39 150.08 67.49 82.59 0.00 0.00
April 314.77 190.50 232.81 130.44 102.37 0.00 0.00
May 291.96 176.75 224.64 112.48 112.16 0.00 0.00
June 329.26 138.55 234.86 124.08 110.78 0.00 0.00
July 383.09 115.07 252.79 143.24 109.55 0.00 0.00
August 372.23 116.84 242.05 140.21 101.84 0.00 0.00
September 283.95 139.74 197.42 110.63 86.79 0.00 0.00
October 181.66 157.83 124.97 64.11 60.87 0.00 0.00
November 95.65 229.89 92.16 39.18 52.97 0.00 0.00
December 66.90 251.51 69.98 26.42 43.56 0.00 0.00
               
Annual Sum or Average 222.37 185.55 167.52 86.23 81.29 0.00 0.00
Minimum of Months 66.90 115.07 69.98 26.42 43.56 0.00 0.00
Maximum of Months 383.09 251.51 252.79 143.24 112.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1179.87 471.57 789.30 578.99 210.31 0.00 0.00
February 882.11 418.78 620.35 382.10 238.25 0.00 0.00
March 702.55 426.45 494.56 238.90 255.66 0.00 0.00
April 619.24 360.33 413.22 157.56 255.65 0.00 0.00
May 365.91 323.43 294.24 36.21 258.03 0.00 0.00
June 322.02 249.79 258.13 15.58 242.54 0.00 0.00
July 390.09 220.82 273.43 30.78 242.65 0.00 0.00
August 571.31 236.05 351.27 110.80 240.47 0.00 0.00
September 785.79 292.34 488.80 247.69 241.11 0.00 0.00
October 997.39 331.34 621.64 415.58 206.06 0.00 0.00
November 1122.84 436.51 755.54 533.40 222.14 0.00 0.00
December 1260.92 479.58 843.22 641.80 201.42 0.00 0.00
               
Annual Sum or Average 766.32 353.59 516.54 282.11 234.43 0.00 0.00
Minimum of Months 322.02 220.82 258.13 15.58 201.42 0.00 0.00
Maximum of Months 1260.92 479.58 843.22 641.80 258.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 108.76 263.96 101.32 44.76 56.56 0.00 0.00
February 134.71 253.53 132.87 57.94 74.93 0.00 0.00
March 192.46 262.10 176.26 80.88 95.38 0.00 0.00
April 345.83 223.45 264.43 148.03 116.40 0.00 0.00
May 313.67 210.37 253.42 126.09 127.33 0.00 0.00
June 350.52 171.14 264.49 138.91 125.58 0.00 0.00
July 412.65 144.24 284.50 160.47 124.04 0.00 0.00
August 404.10 145.99 273.64 158.16 115.48 0.00 0.00
September 313.59 171.80 227.66 128.29 99.37 0.00 0.00
October 211.39 189.54 151.82 81.14 70.68 0.00 0.00
November 129.21 254.60 117.92 55.20 62.72 0.00 0.00
December 98.96 272.60 92.43 40.62 51.81 0.00 0.00
               
Annual Sum or Average 251.91 213.37 195.32 101.89 93.42 0.00 0.00
Minimum of Months 98.96 144.24 92.43 40.62 51.81 0.00 0.00
Maximum of Months 412.65 272.60 284.50 160.47 127.33 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1657.56 1130.14 1228.92 830.61 398.31 0.00 0.00
February 1318.45 1039.00 1061.76 594.62 467.14 0.00 0.00
March 1223.24 1060.54 1003.50 467.60 535.90 0.00 0.00
April 1389.22 878.67 1040.85 467.10 573.74 0.00 0.00
May 1025.52 795.43 876.47 270.08 606.40 0.00 0.00
June 1039.24 632.66 833.13 254.92 578.21 0.00 0.00
July 1292.63 561.14 922.94 342.48 580.46 0.00 0.00
August 1502.44 576.46 1001.27 448.08 553.19 0.00 0.00
September 1455.35 700.40 986.57 478.28 508.29 0.00 0.00
October 1635.11 767.33 1082.14 662.37 419.76 0.00 0.00
November 1599.32 1049.53 1195.21 772.50 422.70 0.00 0.00
December 1731.93 1142.46 1275.54 900.24 375.30 0.00 0.00
               
Annual Sum or Average 1406.94 860.19 1042.51 540.82 501.69 0.00 0.00
Minimum of Months 1025.52 561.14 833.13 254.92 375.30 0.00 0.00
Maximum of Months 1731.93 1142.46 1275.54 900.24 606.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 716.81 863.29 657.72 393.13 264.59 0.00 0.00
February 785.08 789.30 747.53 392.01 355.52 0.00 0.00
March 1037.73 786.01 934.26 484.38 449.87 0.00 0.00
April 1653.62 661.52 1338.59 868.72 469.87 0.00 0.00
May 1564.52 601.60 1300.53 735.40 565.13 0.00 0.00
June 1710.24 482.73 1354.83 821.01 533.82 0.00 0.00
July 1991.85 444.97 1503.01 1000.67 502.35 0.00 0.00
August 1906.11 453.26 1419.60 971.86 447.73 0.00 0.00
September 1367.64 536.27 1066.03 666.26 399.77 0.00 0.00
October 1065.01 595.27 826.40 515.61 310.79 0.00 0.00
November 766.38 803.37 696.64 406.86 289.78 0.00 0.00
December 666.89 879.10 621.59 384.13 237.46 0.00 0.00
               
Annual Sum or Average 1272.15 657.39 1040.47 638.09 402.38 0.00 0.00
Minimum of Months 666.89 444.97 621.59 384.13 237.46 0.00 0.00
Maximum of Months 1991.85 879.10 1503.01 1000.67 565.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 150.89 257.41 135.84 72.65 63.19 0.00 0.00
February 148.39 243.85 143.29 65.64 77.65 0.00 0.00
March 190.63 240.60 174.06 77.55 96.51 0.00 0.00
April 287.76 194.02 222.53 111.60 110.93 0.00 0.00
May 257.46 176.42 210.01 87.64 122.37 0.00 0.00
June 279.51 141.53 208.70 90.55 118.15 0.00 0.00
July 345.87 125.43 236.47 117.51 118.96 0.00 0.00
August 349.25 127.31 233.53 124.05 109.49 0.00 0.00
September 234.77 152.08 170.03 77.91 92.12 0.00 0.00
October 212.69 167.04 150.51 77.36 73.15 0.00 0.00
November 154.18 235.44 137.21 69.71 67.50 0.00 0.00
December 144.52 258.16 130.89 72.73 58.17 0.00 0.00
               
Annual Sum or Average 230.22 193.00 179.66 87.25 92.42 0.00 0.00
Minimum of Months 144.52 125.43 130.89 65.64 58.17 0.00 0.00
Maximum of Months 349.25 258.16 236.47 124.05 122.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 326.39 912.75 377.62 136.22 241.40 0.00 0.00
February 345.46 843.06 423.31 123.08 300.22 0.00 0.00
March 461.96 861.10 516.21 145.41 370.80 0.00 0.00
April 696.08 719.81 634.23 209.84 424.38 0.00 0.00
May 684.96 660.25 650.24 173.35 476.89 0.00 0.00
June 782.17 538.83 659.68 188.83 470.85 0.00 0.00
July 917.28 472.86 698.28 235.56 462.73 0.00 0.00
August 875.63 475.60 654.75 235.43 419.32 0.00 0.00
September 612.21 582.54 505.20 146.10 359.10 0.00 0.00
October 540.85 642.57 430.18 145.05 285.14 0.00 0.00
November 344.98 850.78 390.59 130.70 259.89 0.00 0.00
December 306.54 918.36 359.74 136.36 223.38 0.00 0.00
               
Annual Sum or Average 576.05 705.79 525.59 167.50 358.09 0.00 0.00
Minimum of Months 306.54 472.86 359.74 123.08 223.38 0.00 0.00
Maximum of Months 917.28 918.36 698.28 235.56 476.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 368.85 1052.61 423.84 153.36 270.48 0.00 0.00
February 407.78 990.00 492.79 153.35 339.45 0.00 0.00
March 558.25 1009.42 612.29 190.44 421.85 0.00 0.00
April 867.35 833.80 773.04 285.88 487.16 0.00 0.00
May 848.26 751.35 788.68 240.38 548.29 0.00 0.00
June 970.20 595.49 803.58 263.52 540.06 0.00 0.00
July 1168.00 508.71 861.12 328.51 532.61 0.00 0.00
August 1112.96 522.26 806.20 324.24 481.95 0.00 0.00
September 746.19 657.52 602.01 193.90 408.11 0.00 0.00
October 647.65 721.97 506.88 184.06 322.82 0.00 0.00
November 392.17 996.26 445.96 153.75 292.21 0.00 0.00
December 334.96 1073.83 398.11 148.79 249.32 0.00 0.00
               
Annual Sum or Average 703.84 808.37 626.98 218.82 408.16 0.00 0.00
Minimum of Months 334.96 508.71 398.11 148.79 249.32 0.00 0.00
Maximum of Months 1168.00 1073.83 861.12 328.51 548.29 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.225909E+10 0.129418E+10 0.161344E+10 0.109424E+10 0.519198E+09 0.00 0.00
February 0.170765E+10 0.103488E+10 0.128859E+10 0.728929E+09 0.559664E+09 0.00 0.00
March 0.171241E+10 0.116589E+10 0.129960E+10 0.606119E+09 0.693481E+09 0.00 0.00
April 0.188136E+10 0.951462E+09 0.133079E+10 0.606509E+09 0.724283E+09 0.00 0.00
May 0.151744E+10 0.879331E+09 0.117768E+10 0.389376E+09 0.788308E+09 0.00 0.00
June 0.153934E+10 0.644441E+09 0.112697E+10 0.393185E+09 0.733784E+09 0.00 0.00
July 0.186562E+10 0.559895E+09 0.123303E+10 0.480644E+09 0.752387E+09 0.00 0.00
August 0.209903E+10 0.585595E+09 0.130373E+10 0.583180E+09 0.720551E+09 0.00 0.00
September 0.209081E+10 0.747949E+09 0.136239E+10 0.708198E+09 0.654194E+09 0.00 0.00
October 0.227492E+10 0.892664E+09 0.146070E+10 0.915621E+09 0.545079E+09 0.00 0.00
November 0.219663E+10 0.115941E+10 0.156801E+10 0.102755E+10 0.540460E+09 0.00 0.00
December 0.240203E+10 0.130911E+10 0.170381E+10 0.120773E+10 0.496079E+09 0.00 0.00
               
Annual Sum or Average 0.235463E+11 0.112248E+11 0.164687E+11 0.874128E+10 0.772747E+10 0.00 0.00
Minimum of Months 0.151744E+10 0.559895E+09 0.112697E+10 0.389376E+09 0.496079E+09 0.00 0.00
Maximum of Months 0.240203E+10 0.130911E+10 0.170381E+10 0.120773E+10 0.788308E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.865337E+10 0.372043E+10 0.589708E+10 0.432578E+10 0.157130E+10 0.00 0.00
February 0.580290E+10 0.300231E+10 0.418626E+10 0.257852E+10 0.160774E+10 0.00 0.00
March 0.507460E+10 0.339009E+10 0.369501E+10 0.178486E+10 0.191014E+10 0.00 0.00
April 0.436387E+10 0.274694E+10 0.298768E+10 0.113923E+10 0.184845E+10 0.00 0.00
May 0.260695E+10 0.253998E+10 0.219837E+10 0.270540E+09 0.192783E+10 0.00 0.00
June 0.228505E+10 0.185641E+10 0.186635E+10 0.112683E+09 0.175366E+10 0.00 0.00
July 0.307625E+10 0.150770E+10 0.204287E+10 0.229969E+09 0.181290E+10 0.00 0.00
August 0.446237E+10 0.157564E+10 0.262448E+10 0.827842E+09 0.179663E+10 0.00 0.00
September 0.568975E+10 0.212530E+10 0.353415E+10 0.179088E+10 0.174328E+10 0.00 0.00
October 0.745112E+10 0.252601E+10 0.464444E+10 0.310494E+10 0.153950E+10 0.00 0.00
November 0.799258E+10 0.332153E+10 0.546275E+10 0.385662E+10 0.160613E+10 0.00 0.00
December 0.929198E+10 0.376046E+10 0.629997E+10 0.479510E+10 0.150487E+10 0.00 0.00
               
Annual Sum or Average 0.667508E+11 0.320728E+11 0.454394E+11 0.248170E+11 0.206224E+11 0.00 0.00
Minimum of Months 0.228505E+10 0.150770E+10 0.186635E+10 0.112683E+09 0.150487E+10 0.00 0.00
Maximum of Months 0.929198E+10 0.376046E+10 0.629997E+10 0.479510E+10 0.192783E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.163678E+09 0.211470E+09 0.129861E+09 65496202.37 64365119.12 0.00 0.00
February 0.168656E+09 0.171216E+09 0.139932E+09 64599315.81 75333044.03 0.00 0.00
March 0.219205E+09 0.191057E+09 0.177586E+09 78566695.06 99018941.22 0.00 0.00
April 0.329566E+09 0.150914E+09 0.236914E+09 0.123361E+09 0.113553E+09 0.00 0.00
May 0.323641E+09 0.142788E+09 0.240482E+09 0.111078E+09 0.129404E+09 0.00 0.00
June 0.353957E+09 0.105515E+09 0.246546E+09 0.123268E+09 0.123278E+09 0.00 0.00
July 0.422420E+09 84848998.34 0.269688E+09 0.144308E+09 0.125380E+09 0.00 0.00
August 0.403682E+09 86680723.16 0.253020E+09 0.137126E+09 0.115894E+09 0.00 0.00
September 0.311660E+09 0.113409E+09 0.209644E+09 0.112177E+09 97466490.85 0.00 0.00
October 0.248725E+09 0.140556E+09 0.165605E+09 90413387.60 75191820.23 0.00 0.00
November 0.186699E+09 0.188094E+09 0.144766E+09 75722540.26 69042985.65 0.00 0.00
December 0.169662E+09 0.214688E+09 0.132115E+09 70860135.06 61254550.57 0.00 0.00
               
Annual Sum or Average 0.330155E+10 0.180124E+10 0.234616E+10 0.119698E+10 0.114918E+10 0.00 0.00
Minimum of Months 0.163678E+09 84848998.34 0.129861E+09 64599315.81 61254550.57 0.00 0.00
Maximum of Months 0.422420E+09 0.214688E+09 0.269688E+09 0.144308E+09 0.129404E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.611943E+09 0.117435E+10 0.539342E+09 0.196486E+09 0.342857E+09 0.00 0.00
February 0.628519E+09 0.952514E+09 0.592836E+09 0.193795E+09 0.399040E+09 0.00 0.00
March 0.840364E+09 0.109443E+10 0.769507E+09 0.235697E+09 0.533810E+09 0.00 0.00
April 0.121959E+10 0.879860E+09 0.973107E+09 0.371167E+09 0.601940E+09 0.00 0.00
May 0.126842E+10 0.836291E+09 0.105155E+10 0.349901E+09 0.701654E+09 0.00 0.00
June 0.144641E+10 0.632933E+09 0.108465E+10 0.407635E+09 0.677013E+09 0.00 0.00
July 0.169129E+10 0.538035E+09 0.114131E+10 0.465031E+09 0.676281E+09 0.00 0.00
August 0.157359E+10 0.528685E+09 0.103014E+10 0.417608E+09 0.612527E+09 0.00 0.00
September 0.118834E+10 0.660671E+09 0.850226E+09 0.336564E+09 0.513663E+09 0.00 0.00
October 0.989801E+09 0.794153E+09 0.679613E+09 0.271236E+09 0.408377E+09 0.00 0.00
November 0.684279E+09 0.104748E+10 0.591689E+09 0.227164E+09 0.364525E+09 0.00 0.00
December 0.621600E+09 0.118571E+10 0.534738E+09 0.212577E+09 0.322160E+09 0.00 0.00
               
Annual Sum or Average 0.127641E+11 0.103251E+11 0.983871E+10 0.368486E+10 0.615385E+10 0.00 0.00
Minimum of Months 0.611943E+09 0.528685E+09 0.534738E+09 0.193795E+09 0.322160E+09 0.00 0.00
Maximum of Months 0.169129E+10 0.118571E+10 0.114131E+10 0.465031E+09 0.701654E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.362668E+09 0.341519E+10 0.661876E+09 0.00 0.661876E+09 0.00 0.00
February 0.364035E+09 0.281974E+10 0.769941E+09 0.00 0.769941E+09 0.00 0.00
March 0.632296E+09 0.323213E+10 0.105704E+10 0.00 0.105704E+10 0.00 0.00
April 0.880055E+09 0.250075E+10 0.116769E+10 3945684.26 0.116374E+10 0.00 0.00
May 0.113834E+10 0.232987E+10 0.146340E+10 67527445.10 0.139588E+10 0.00 0.00
June 0.159172E+10 0.176629E+10 0.151941E+10 0.151998E+09 0.136742E+10 0.00 0.00
July 0.196239E+10 0.137104E+10 0.145943E+10 0.129892E+09 0.132954E+10 0.00 0.00
August 0.164972E+10 0.133387E+10 0.119998E+10 25146794.40 0.117484E+10 0.00 0.00
September 0.104458E+10 0.183496E+10 0.983344E+09 153303.40 0.983191E+09 0.00 0.00
October 0.958438E+09 0.225019E+10 0.814455E+09 0.00 0.814455E+09 0.00 0.00
November 0.390251E+09 0.306193E+10 0.695846E+09 0.00 0.695846E+09 0.00 0.00
December 0.331034E+09 0.345321E+10 0.609953E+09 0.00 0.609953E+09 0.00 0.00
               
Annual Sum or Average 0.113055E+11 0.293692E+11 0.124024E+11 0.378663E+09 0.120237E+11 0.00 0.00
Minimum of Months 0.331034E+09 0.133387E+10 0.609953E+09 0.00 0.609953E+09 0.00 0.00
Maximum of Months 0.196239E+10 0.345321E+10 0.151941E+10 0.151998E+09 0.139588E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.220822E+10 0.128939E+10 0.155968E+10 0.108125E+10 0.478428E+09 0.00 0.00
February 0.165541E+10 0.102159E+10 0.124756E+10 0.727797E+09 0.519764E+09 0.00 0.00
March 0.164180E+10 0.115244E+10 0.124818E+10 0.605963E+09 0.642221E+09 0.00 0.00
April 0.180413E+10 0.937688E+09 0.127230E+10 0.606509E+09 0.665789E+09 0.00 0.00
May 0.142864E+10 0.867199E+09 0.111212E+10 0.389376E+09 0.722742E+09 0.00 0.00
June 0.145310E+10 0.635653E+09 0.106451E+10 0.393185E+09 0.671322E+09 0.00 0.00
July 0.177541E+10 0.545520E+09 0.116512E+10 0.480644E+09 0.684475E+09 0.00 0.00
August 0.201740E+10 0.568103E+09 0.124122E+10 0.583180E+09 0.658037E+09 0.00 0.00
September 0.201852E+10 0.731860E+09 0.130987E+10 0.708165E+09 0.601704E+09 0.00 0.00
October 0.222040E+10 0.876541E+09 0.141681E+10 0.913742E+09 0.503071E+09 0.00 0.00
November 0.214277E+10 0.115000E+10 0.152034E+10 0.102112E+10 0.499214E+09 0.00 0.00
December 0.234737E+10 0.130740E+10 0.164470E+10 0.118883E+10 0.455868E+09 0.00 0.00
               
Annual Sum or Average 0.227132E+11 0.110834E+11 0.158024E+11 0.869977E+10 0.710263E+10 0.00 0.00
Minimum of Months 0.142864E+10 0.545520E+09 0.106451E+10 0.389376E+09 0.455868E+09 0.00 0.00
Maximum of Months 0.234737E+10 0.130740E+10 0.164470E+10 0.118883E+10 0.722742E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.808524E+10 0.365675E+10 0.543824E+10 0.413606E+10 0.130218E+10 0.00 0.00
February 0.535707E+10 0.294681E+10 0.385639E+10 0.251216E+10 0.134423E+10 0.00 0.00
March 0.456643E+10 0.333824E+10 0.333598E+10 0.175461E+10 0.158137E+10 0.00 0.00
April 0.386506E+10 0.269379E+10 0.261348E+10 0.112869E+10 0.148479E+10 0.00 0.00
May 0.205977E+10 0.251213E+10 0.179054E+10 0.268980E+09 0.152156E+10 0.00 0.00
June 0.175480E+10 0.183130E+10 0.148049E+10 0.112133E+09 0.136836E+10 0.00 0.00
July 0.251031E+10 0.143540E+10 0.162502E+10 0.228607E+09 0.139641E+10 0.00 0.00
August 0.393131E+10 0.148164E+10 0.223219E+10 0.820627E+09 0.141156E+10 0.00 0.00
September 0.519488E+10 0.203125E+10 0.318414E+10 0.176926E+10 0.141488E+10 0.00 0.00
October 0.698903E+10 0.241627E+10 0.430157E+10 0.303280E+10 0.126877E+10 0.00 0.00
November 0.745817E+10 0.326483E+10 0.504678E+10 0.371466E+10 0.133212E+10 0.00 0.00
December 0.860299E+10 0.372344E+10 0.574134E+10 0.451282E+10 0.122852E+10 0.00 0.00
               
Annual Sum or Average 0.603751E+11 0.313318E+11 0.406462E+11 0.239914E+11 0.166548E+11 0.00 0.00
Minimum of Months 0.175480E+10 0.143540E+10 0.148049E+10 0.112133E+09 0.122852E+10 0.00 0.00
Maximum of Months 0.860299E+10 0.372344E+10 0.574134E+10 0.451282E+10 0.158137E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.164015E+09 0.210716E+09 0.129861E+09 65496202.37 64365119.12 0.00 0.00
February 0.168695E+09 0.171246E+09 0.139932E+09 64599315.81 75333044.03 0.00 0.00
March 0.219160E+09 0.191261E+09 0.177586E+09 78566695.06 99018941.22 0.00 0.00
April 0.329501E+09 0.151128E+09 0.236914E+09 0.123361E+09 0.113553E+09 0.00 0.00
May 0.323511E+09 0.143048E+09 0.240482E+09 0.111078E+09 0.129404E+09 0.00 0.00
June 0.353582E+09 0.105963E+09 0.246546E+09 0.123268E+09 0.123278E+09 0.00 0.00
July 0.422411E+09 84932904.36 0.269688E+09 0.144308E+09 0.125380E+09 0.00 0.00
August 0.403902E+09 86520393.17 0.253020E+09 0.137126E+09 0.115894E+09 0.00 0.00
September 0.311648E+09 0.113509E+09 0.209644E+09 0.112177E+09 97466490.85 0.00 0.00
October 0.248704E+09 0.140662E+09 0.165605E+09 90413387.60 75191820.23 0.00 0.00
November 0.186766E+09 0.187977E+09 0.144766E+09 75722540.26 69042985.65 0.00 0.00
December 0.169898E+09 0.213936E+09 0.132115E+09 70860135.06 61254550.57 0.00 0.00
               
Annual Sum or Average 0.330179E+10 0.180090E+10 0.234616E+10 0.119698E+10 0.114918E+10 0.00 0.00
Minimum of Months 0.164015E+09 84932904.36 0.129861E+09 64599315.81 61254550.57 0.00 0.00
Maximum of Months 0.422411E+09 0.213936E+09 0.269688E+09 0.144308E+09 0.129404E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.614160E+09 0.117500E+10 0.541492E+09 0.196486E+09 0.345006E+09 0.00 0.00
February 0.630733E+09 0.953883E+09 0.595078E+09 0.193795E+09 0.401282E+09 0.00 0.00
March 0.843155E+09 0.109644E+10 0.772429E+09 0.235697E+09 0.536732E+09 0.00 0.00
April 0.122289E+10 0.881850E+09 0.976446E+09 0.371167E+09 0.605279E+09 0.00 0.00
May 0.127243E+10 0.837856E+09 0.105555E+10 0.350056E+09 0.705492E+09 0.00 0.00
June 0.144880E+10 0.635078E+09 0.108861E+10 0.407898E+09 0.680717E+09 0.00 0.00
July 0.169475E+10 0.539966E+09 0.114538E+10 0.465162E+09 0.680216E+09 0.00 0.00
August 0.157800E+10 0.529692E+09 0.103375E+10 0.417640E+09 0.616113E+09 0.00 0.00
September 0.119098E+10 0.663266E+09 0.853221E+09 0.336564E+09 0.516658E+09 0.00 0.00
October 0.991493E+09 0.796698E+09 0.681985E+09 0.271236E+09 0.410748E+09 0.00 0.00
November 0.685768E+09 0.104961E+10 0.593934E+09 0.227164E+09 0.366770E+09 0.00 0.00
December 0.622637E+09 0.118685E+10 0.536800E+09 0.212577E+09 0.324223E+09 0.00 0.00
               
Annual Sum or Average 0.127958E+11 0.103462E+11 0.987468E+10 0.368544E+10 0.618924E+10 0.00 0.00
Minimum of Months 0.614160E+09 0.529692E+09 0.536800E+09 0.193795E+09 0.324223E+09 0.00 0.00
Maximum of Months 0.169475E+10 0.118685E+10 0.114538E+10 0.465162E+09 0.705492E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.373572E+09 0.341503E+10 0.673605E+09 0.00 0.673605E+09 0.00 0.00
February 0.376423E+09 0.282208E+10 0.782173E+09 0.00 0.782173E+09 0.00 0.00
March 0.649807E+09 0.323591E+10 0.107298E+10 0.00 0.107298E+10 0.00 0.00
April 0.901315E+09 0.250422E+10 0.118640E+10 4006145.00 0.118240E+10 0.00 0.00
May 0.116525E+10 0.233175E+10 0.148622E+10 68814213.27 0.141741E+10 0.00 0.00
June 0.161815E+10 0.176790E+10 0.154458E+10 0.155890E+09 0.138869E+10 0.00 0.00
July 0.199302E+10 0.137387E+10 0.148532E+10 0.133115E+09 0.135220E+10 0.00 0.00
August 0.167713E+10 0.133742E+10 0.122050E+10 25644115.19 0.119486E+10 0.00 0.00
September 0.106387E+10 0.184216E+10 0.999686E+09 153303.40 0.999533E+09 0.00 0.00
October 0.972049E+09 0.225875E+10 0.827394E+09 0.00 0.827394E+09 0.00 0.00
November 0.400969E+09 0.306728E+10 0.708096E+09 0.00 0.708096E+09 0.00 0.00
December 0.339217E+09 0.345627E+10 0.621207E+09 0.00 0.621207E+09 0.00 0.00
               
Annual Sum or Average 0.115308E+11 0.294126E+11 0.126082E+11 0.387623E+09 0.122206E+11 0.00 0.00
Minimum of Months 0.339217E+09 0.133742E+10 0.621207E+09 0.00 0.621207E+09 0.00 0.00
Maximum of Months 0.199302E+10 0.345627E+10 0.154458E+10 0.155890E+09 0.141741E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.220897E+10 0.129548E+10 0.156517E+10 0.108375E+10 0.481422E+09 0.00 0.00
February 0.165378E+10 0.103037E+10 0.125045E+10 0.728013E+09 0.522441E+09 0.00 0.00
March 0.164046E+10 0.116227E+10 0.125155E+10 0.605985E+09 0.645562E+09 0.00 0.00
April 0.180104E+10 0.949192E+09 0.127611E+10 0.606509E+09 0.669600E+09 0.00 0.00
May 0.142321E+10 0.880038E+09 0.111639E+10 0.389376E+09 0.727013E+09 0.00 0.00
June 0.144807E+10 0.646285E+09 0.106858E+10 0.393185E+09 0.675391E+09 0.00 0.00
July 0.177363E+10 0.553071E+09 0.116954E+10 0.480644E+09 0.688899E+09 0.00 0.00
August 0.201471E+10 0.576730E+09 0.124529E+10 0.583180E+09 0.662110E+09 0.00 0.00
September 0.201731E+10 0.741126E+09 0.131330E+10 0.708171E+09 0.605126E+09 0.00 0.00
October 0.222080E+10 0.882769E+09 0.141992E+10 0.914075E+09 0.505848E+09 0.00 0.00
November 0.214358E+10 0.115647E+10 0.152472E+10 0.102254E+10 0.502182E+09 0.00 0.00
December 0.235054E+10 0.131417E+10 0.165201E+10 0.119301E+10 0.459005E+09 0.00 0.00
               
Annual Sum or Average 0.226961E+11 0.111880E+11 0.158530E+11 0.870843E+10 0.714460E+10 0.00 0.00
Minimum of Months 0.142321E+10 0.553071E+09 0.106858E+10 0.389376E+09 0.459005E+09 0.00 0.00
Maximum of Months 0.235054E+10 0.131417E+10 0.165201E+10 0.119301E+10 0.727013E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.810059E+10 0.369291E+10 0.546877E+10 0.415112E+10 0.131765E+10 0.00 0.00
February 0.535287E+10 0.299291E+10 0.387228E+10 0.251420E+10 0.135807E+10 0.00 0.00
March 0.455657E+10 0.339926E+10 0.335217E+10 0.175479E+10 0.159737E+10 0.00 0.00
April 0.385735E+10 0.275433E+10 0.263171E+10 0.112869E+10 0.150302E+10 0.00 0.00
May 0.204301E+10 0.258255E+10 0.181096E+10 0.268981E+09 0.154198E+10 0.00 0.00
June 0.173195E+10 0.189269E+10 0.149995E+10 0.112134E+09 0.138782E+10 0.00 0.00
July 0.250139E+10 0.147662E+10 0.164617E+10 0.228608E+09 0.141757E+10 0.00 0.00
August 0.391867E+10 0.152683E+10 0.225167E+10 0.820632E+09 0.143103E+10 0.00 0.00
September 0.518707E+10 0.208440E+10 0.320054E+10 0.176930E+10 0.143125E+10 0.00 0.00
October 0.699429E+10 0.245089E+10 0.431716E+10 0.303504E+10 0.128212E+10 0.00 0.00
November 0.747221E+10 0.329810E+10 0.507290E+10 0.372519E+10 0.134771E+10 0.00 0.00
December 0.864908E+10 0.375713E+10 0.579293E+10 0.454558E+10 0.124735E+10 0.00 0.00
               
Annual Sum or Average 0.603650E+11 0.319086E+11 0.409172E+11 0.240543E+11 0.168629E+11 0.00 0.00
Minimum of Months 0.173195E+10 0.147662E+10 0.149995E+10 0.112134E+09 0.124735E+10 0.00 0.00
Maximum of Months 0.864908E+10 0.375713E+10 0.579293E+10 0.454558E+10 0.159737E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.162863E+09 0.213592E+09 0.129861E+09 65496202.37 64365119.12 0.00 0.00
February 0.167300E+09 0.174287E+09 0.139932E+09 64599315.81 75333044.03 0.00 0.00
March 0.217261E+09 0.194786E+09 0.177586E+09 78566695.06 99018941.22 0.00 0.00
April 0.327111E+09 0.154391E+09 0.236914E+09 0.123361E+09 0.113553E+09 0.00 0.00
May 0.320594E+09 0.146446E+09 0.240482E+09 0.111078E+09 0.129404E+09 0.00 0.00
June 0.350491E+09 0.108994E+09 0.246546E+09 0.123268E+09 0.123278E+09 0.00 0.00
July 0.419861E+09 87085776.56 0.269688E+09 0.144308E+09 0.125380E+09 0.00 0.00
August 0.401494E+09 88796821.48 0.253020E+09 0.137126E+09 0.115894E+09 0.00 0.00
September 0.309571E+09 0.116351E+09 0.209644E+09 0.112177E+09 97466490.85 0.00 0.00
October 0.247834E+09 0.142341E+09 0.165605E+09 90413387.60 75191820.23 0.00 0.00
November 0.185595E+09 0.190719E+09 0.144766E+09 75722540.26 69042985.65 0.00 0.00
December 0.168811E+09 0.216972E+09 0.132115E+09 70860135.06 61254550.57 0.00 0.00
               
Annual Sum or Average 0.327879E+10 0.183476E+10 0.234616E+10 0.119698E+10 0.114918E+10 0.00 0.00
Minimum of Months 0.162863E+09 87085776.56 0.129861E+09 64599315.81 61254550.57 0.00 0.00
Maximum of Months 0.419861E+09 0.216972E+09 0.269688E+09 0.144308E+09 0.129404E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.649487E+09 0.119492E+10 0.574389E+09 0.196486E+09 0.377903E+09 0.00 0.00
February 0.670650E+09 0.969446E+09 0.629327E+09 0.193795E+09 0.435532E+09 0.00 0.00
March 0.898623E+09 0.111139E+10 0.817030E+09 0.235697E+09 0.581334E+09 0.00 0.00
April 0.128306E+10 0.900019E+09 0.102770E+10 0.371298E+09 0.656397E+09 0.00 0.00
May 0.134122E+10 0.854269E+09 0.111502E+10 0.351557E+09 0.763460E+09 0.00 0.00
June 0.151468E+10 0.646943E+09 0.114548E+10 0.409477E+09 0.736002E+09 0.00 0.00
July 0.176633E+10 0.555894E+09 0.120614E+10 0.466199E+09 0.739943E+09 0.00 0.00
August 0.164411E+10 0.547833E+09 0.108882E+10 0.417977E+09 0.670843E+09 0.00 0.00
September 0.124872E+10 0.682480E+09 0.899035E+09 0.336570E+09 0.562465E+09 0.00 0.00
October 0.103391E+10 0.816284E+09 0.718212E+09 0.271236E+09 0.446976E+09 0.00 0.00
November 0.724602E+09 0.106803E+10 0.628289E+09 0.227164E+09 0.401124E+09 0.00 0.00
December 0.654884E+09 0.120838E+10 0.568382E+09 0.212577E+09 0.355804E+09 0.00 0.00
               
Annual Sum or Average 0.134303E+11 0.105559E+11 0.104178E+11 0.369003E+10 0.672778E+10 0.00 0.00
Minimum of Months 0.649487E+09 0.547833E+09 0.568382E+09 0.193795E+09 0.355804E+09 0.00 0.00
Maximum of Months 0.176633E+10 0.120838E+10 0.120614E+10 0.466199E+09 0.763460E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.387915E+09 0.232241E+10 0.590109E+09 0.00 0.590109E+09 0.00 0.00
February 0.415847E+09 0.190417E+10 0.669060E+09 0.00 0.669060E+09 0.00 0.00
March 0.667000E+09 0.216884E+10 0.907725E+09 0.00 0.907725E+09 0.00 0.00
April 0.866571E+09 0.169733E+10 0.101207E+10 3895303.14 0.100818E+10 0.00 0.00
May 0.111368E+10 0.157248E+10 0.125672E+10 58519952.90 0.119820E+10 0.00 0.00
June 0.141392E+10 0.118550E+10 0.129591E+10 0.126697E+09 0.116921E+10 0.00 0.00
July 0.168803E+10 0.952679E+09 0.126792E+10 0.106273E+09 0.116165E+10 0.00 0.00
August 0.142667E+10 0.941564E+09 0.105297E+10 21084595.11 0.103188E+10 0.00 0.00
September 0.964094E+09 0.128171E+10 0.862478E+09 135183.97 0.862343E+09 0.00 0.00
October 0.829578E+09 0.156592E+10 0.706951E+09 0.00 0.706951E+09 0.00 0.00
November 0.423338E+09 0.208742E+10 0.619445E+09 0.00 0.619445E+09 0.00 0.00
December 0.347812E+09 0.235494E+10 0.549341E+09 0.00 0.549341E+09 0.00 0.00
               
Annual Sum or Average 0.105445E+11 0.200350E+11 0.107907E+11 0.316604E+09 0.104741E+11 0.00 0.00
Minimum of Months 0.347812E+09 0.941564E+09 0.549341E+09 0.00 0.549341E+09 0.00 0.00
Maximum of Months 0.168803E+10 0.235494E+10 0.129591E+10 0.126697E+09 0.119820E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.179625E+09 0.127932E+10 0.303477E+09 0.00 0.303477E+09 0.00 0.00
February 0.193311E+09 0.106254E+10 0.344080E+09 0.00 0.344080E+09 0.00 0.00
March 0.318379E+09 0.120184E+10 0.466819E+09 0.00 0.466819E+09 0.00 0.00
April 0.423718E+09 0.938903E+09 0.520481E+09 2003249.01 0.518477E+09 0.00 0.00
May 0.554076E+09 0.854471E+09 0.646300E+09 30095228.46 0.616204E+09 0.00 0.00
June 0.705138E+09 0.649936E+09 0.666450E+09 65156646.25 0.601294E+09 0.00 0.00
July 0.856753E+09 0.512672E+09 0.652057E+09 54653160.68 0.597404E+09 0.00 0.00
August 0.711900E+09 0.519252E+09 0.541512E+09 10843236.80 0.530669E+09 0.00 0.00
September 0.469955E+09 0.720257E+09 0.443549E+09 69521.46 0.443480E+09 0.00 0.00
October 0.420595E+09 0.850425E+09 0.363566E+09 0.00 0.363566E+09 0.00 0.00
November 0.196626E+09 0.116068E+10 0.318564E+09 0.00 0.318564E+09 0.00 0.00
December 0.157631E+09 0.130497E+10 0.282511E+09 0.00 0.282511E+09 0.00 0.00
               
Annual Sum or Average 0.518771E+10 0.110553E+11 0.554937E+10 0.162821E+09 0.538654E+10 0.00 0.00
Minimum of Months 0.157631E+09 0.512672E+09 0.282511E+09 0.00 0.282511E+09 0.00 0.00
Maximum of Months 0.856753E+09 0.130497E+10 0.666450E+09 65156646.25 0.616204E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.205540E+09 0.651939E+09 0.210008E+09 82133053.93 0.127875E+09 0.00 0.00
February 0.247569E+09 0.564591E+09 0.259017E+09 0.105407E+09 0.153611E+09 0.00 0.00
March 0.435598E+09 0.633137E+09 0.401971E+09 0.180769E+09 0.221202E+09 0.00 0.00
April 0.815880E+09 0.493771E+09 0.603439E+09 0.338096E+09 0.265343E+09 0.00 0.00
May 0.781972E+09 0.473396E+09 0.601673E+09 0.301260E+09 0.300413E+09 0.00 0.00
June 0.853452E+09 0.359126E+09 0.608745E+09 0.321615E+09 0.287130E+09 0.00 0.00
July 0.102606E+10 0.308191E+09 0.677061E+09 0.383653E+09 0.293408E+09 0.00 0.00
August 0.996989E+09 0.312933E+09 0.648316E+09 0.375542E+09 0.272773E+09 0.00 0.00
September 0.735988E+09 0.362208E+09 0.511709E+09 0.286755E+09 0.224954E+09 0.00 0.00
October 0.486551E+09 0.422722E+09 0.334725E+09 0.171702E+09 0.163023E+09 0.00 0.00
November 0.247935E+09 0.595881E+09 0.238871E+09 0.101566E+09 0.137305E+09 0.00 0.00
December 0.179174E+09 0.673644E+09 0.187441E+09 70767362.49 0.116674E+09 0.00 0.00
               
Annual Sum or Average 0.701271E+10 0.585154E+10 0.528298E+10 0.271927E+10 0.256371E+10 0.00 0.00
Minimum of Months 0.179174E+09 0.308191E+09 0.187441E+09 70767362.49 0.116674E+09 0.00 0.00
Maximum of Months 0.102606E+10 0.673644E+09 0.677061E+09 0.383653E+09 0.300413E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.316017E+10 0.126306E+10 0.211406E+10 0.155076E+10 0.563299E+09 0.00 0.00
February 0.213401E+10 0.101311E+10 0.150074E+10 0.924378E+09 0.576364E+09 0.00 0.00
March 0.188171E+10 0.114221E+10 0.132463E+10 0.639859E+09 0.684772E+09 0.00 0.00
April 0.160508E+10 0.933971E+09 0.107106E+10 0.408405E+09 0.662654E+09 0.00 0.00
May 0.980053E+09 0.866265E+09 0.788100E+09 96986444.24 0.691113E+09 0.00 0.00
June 0.834688E+09 0.647455E+09 0.669070E+09 40396051.99 0.628674E+09 0.00 0.00
July 0.104482E+10 0.591456E+09 0.732354E+09 82442098.04 0.649911E+09 0.00 0.00
August 0.153019E+10 0.632245E+09 0.940855E+09 0.296775E+09 0.644080E+09 0.00 0.00
September 0.203677E+10 0.757736E+09 0.126697E+10 0.642016E+09 0.624951E+09 0.00 0.00
October 0.267141E+10 0.887452E+09 0.166500E+10 0.111310E+10 0.551900E+09 0.00 0.00
November 0.291041E+10 0.113143E+10 0.195836E+10 0.138257E+10 0.575786E+09 0.00 0.00
December 0.337726E+10 0.128452E+10 0.225849E+10 0.171900E+10 0.539484E+09 0.00 0.00
               
Annual Sum or Average 0.241666E+11 0.111509E+11 0.162897E+11 0.889669E+10 0.739299E+10 0.00 0.00
Minimum of Months 0.834688E+09 0.591456E+09 0.669070E+09 40396051.99 0.539484E+09 0.00 0.00
Maximum of Months 0.337726E+10 0.128452E+10 0.225849E+10 0.171900E+10 0.691113E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.291315E+09 0.706982E+09 0.271385E+09 0.119884E+09 0.151501E+09 0.00 0.00
February 0.325885E+09 0.613338E+09 0.321430E+09 0.140169E+09 0.181262E+09 0.00 0.00
March 0.515496E+09 0.702007E+09 0.472105E+09 0.216633E+09 0.255472E+09 0.00 0.00
April 0.896396E+09 0.579191E+09 0.685403E+09 0.383689E+09 0.301714E+09 0.00 0.00
May 0.840126E+09 0.563465E+09 0.678754E+09 0.337723E+09 0.341031E+09 0.00 0.00
June 0.908552E+09 0.443599E+09 0.685571E+09 0.360056E+09 0.325515E+09 0.00 0.00
July 0.110524E+10 0.386325E+09 0.762013E+09 0.429795E+09 0.332218E+09 0.00 0.00
August 0.108235E+10 0.391024E+09 0.732910E+09 0.423605E+09 0.309306E+09 0.00 0.00
September 0.812832E+09 0.445301E+09 0.590098E+09 0.332538E+09 0.257559E+09 0.00 0.00
October 0.566196E+09 0.507671E+09 0.406634E+09 0.217326E+09 0.189308E+09 0.00 0.00
November 0.334904E+09 0.659925E+09 0.305648E+09 0.143066E+09 0.162583E+09 0.00 0.00
December 0.265066E+09 0.730133E+09 0.247566E+09 0.108795E+09 0.138771E+09 0.00 0.00
               
Annual Sum or Average 0.794435E+10 0.672896E+10 0.615952E+10 0.321328E+10 0.294624E+10 0.00 0.00
Minimum of Months 0.265066E+09 0.386325E+09 0.247566E+09 0.108795E+09 0.138771E+09 0.00 0.00
Maximum of Months 0.110524E+10 0.730133E+09 0.762013E+09 0.429795E+09 0.341031E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.443961E+10 0.302697E+10 0.329153E+10 0.222470E+10 0.106683E+10 0.00 0.00
February 0.318960E+10 0.251355E+10 0.256862E+10 0.143850E+10 0.113012E+10 0.00 0.00
March 0.327632E+10 0.284054E+10 0.268779E+10 0.125243E+10 0.143535E+10 0.00 0.00
April 0.360087E+10 0.227752E+10 0.269787E+10 0.121073E+10 0.148714E+10 0.00 0.00
May 0.274676E+10 0.213047E+10 0.234755E+10 0.723377E+09 0.162417E+10 0.00 0.00
June 0.269370E+10 0.163986E+10 0.215947E+10 0.660755E+09 0.149871E+10 0.00 0.00
July 0.346219E+10 0.150295E+10 0.247201E+10 0.917302E+09 0.155471E+10 0.00 0.00
August 0.402412E+10 0.154398E+10 0.268180E+10 0.120015E+10 0.148165E+10 0.00 0.00
September 0.377228E+10 0.181545E+10 0.255718E+10 0.123970E+10 0.131748E+10 0.00 0.00
October 0.437947E+10 0.205523E+10 0.289839E+10 0.177410E+10 0.112429E+10 0.00 0.00
November 0.414544E+10 0.272037E+10 0.309797E+10 0.200233E+10 0.109565E+10 0.00 0.00
December 0.463879E+10 0.305997E+10 0.341641E+10 0.241120E+10 0.100522E+10 0.00 0.00
               
Annual Sum or Average 0.443691E+11 0.271268E+11 0.328766E+11 0.170553E+11 0.158213E+11 0.00 0.00
Minimum of Months 0.269370E+10 0.150295E+10 0.215947E+10 0.660755E+09 0.100522E+10 0.00 0.00
Maximum of Months 0.463879E+10 0.305997E+10 0.341641E+10 0.241120E+10 0.162417E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.191989E+10 0.231223E+10 0.176164E+10 0.105295E+10 0.708689E+09 0.00 0.00
February 0.189926E+10 0.190947E+10 0.180843E+10 0.948341E+09 0.860085E+09 0.00 0.00
March 0.277945E+10 0.210526E+10 0.250231E+10 0.129737E+10 0.120494E+10 0.00 0.00
April 0.428619E+10 0.171467E+10 0.346963E+10 0.225172E+10 0.121791E+10 0.00 0.00
May 0.419042E+10 0.161132E+10 0.348335E+10 0.196970E+10 0.151364E+10 0.00 0.00
June 0.443294E+10 0.125123E+10 0.351171E+10 0.212806E+10 0.138365E+10 0.00 0.00
July 0.533497E+10 0.119182E+10 0.402567E+10 0.268019E+10 0.134549E+10 0.00 0.00
August 0.510532E+10 0.121402E+10 0.380224E+10 0.260303E+10 0.119921E+10 0.00 0.00
September 0.354493E+10 0.139002E+10 0.276314E+10 0.172694E+10 0.103621E+10 0.00 0.00
October 0.285253E+10 0.159437E+10 0.221344E+10 0.138101E+10 0.832431E+09 0.00 0.00
November 0.198645E+10 0.208232E+10 0.180570E+10 0.105459E+10 0.751109E+09 0.00 0.00
December 0.178619E+10 0.235458E+10 0.166487E+10 0.102885E+10 0.636024E+09 0.00 0.00
               
Annual Sum or Average 0.401185E+11 0.207313E+11 0.328121E+11 0.201228E+11 0.126894E+11 0.00 0.00
Minimum of Months 0.178619E+10 0.119182E+10 0.166487E+10 0.948341E+09 0.636024E+09 0.00 0.00
Maximum of Months 0.533497E+10 0.235458E+10 0.402567E+10 0.268019E+10 0.151364E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.404135E+09 0.689446E+09 0.363822E+09 0.194580E+09 0.169242E+09 0.00 0.00
February 0.358996E+09 0.589925E+09 0.346653E+09 0.158804E+09 0.187849E+09 0.00 0.00
March 0.510583E+09 0.644420E+09 0.466198E+09 0.207712E+09 0.258486E+09 0.00 0.00
April 0.745873E+09 0.502895E+09 0.576802E+09 0.289277E+09 0.287524E+09 0.00 0.00
May 0.689575E+09 0.472526E+09 0.562481E+09 0.234736E+09 0.327745E+09 0.00 0.00
June 0.724483E+09 0.366849E+09 0.540947E+09 0.234707E+09 0.306240E+09 0.00 0.00
July 0.926367E+09 0.335957E+09 0.633365E+09 0.314735E+09 0.318629E+09 0.00 0.00
August 0.935435E+09 0.340981E+09 0.625499E+09 0.332244E+09 0.293255E+09 0.00 0.00
September 0.608520E+09 0.394186E+09 0.440722E+09 0.201955E+09 0.238767E+09 0.00 0.00
October 0.569670E+09 0.447397E+09 0.403124E+09 0.207195E+09 0.195929E+09 0.00 0.00
November 0.399626E+09 0.610260E+09 0.355640E+09 0.180680E+09 0.174960E+09 0.00 0.00
December 0.387087E+09 0.691453E+09 0.350583E+09 0.194787E+09 0.155796E+09 0.00 0.00
               
Annual Sum or Average 0.726035E+10 0.608630E+10 0.566584E+10 0.275141E+10 0.291442E+10 0.00 0.00
Minimum of Months 0.358996E+09 0.335957E+09 0.346653E+09 0.158804E+09 0.155796E+09 0.00 0.00
Maximum of Months 0.935435E+09 0.691453E+09 0.633365E+09 0.332244E+09 0.327745E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.874207E+09 0.244472E+10 0.101140E+10 0.364840E+09 0.646565E+09 0.00 0.00
February 0.835729E+09 0.203954E+10 0.102406E+10 0.297760E+09 0.726302E+09 0.00 0.00
March 0.123731E+10 0.230638E+10 0.138262E+10 0.389463E+09 0.993154E+09 0.00 0.00
April 0.180424E+10 0.186574E+10 0.164392E+10 0.543914E+09 0.110000E+10 0.00 0.00
May 0.183459E+10 0.176841E+10 0.174160E+10 0.464298E+09 0.127730E+10 0.00 0.00
June 0.202738E+10 0.139665E+10 0.170989E+10 0.489443E+09 0.122045E+10 0.00 0.00
July 0.245684E+10 0.126651E+10 0.187029E+10 0.630915E+09 0.123937E+10 0.00 0.00
August 0.234529E+10 0.127384E+10 0.175368E+10 0.630580E+09 0.112310E+10 0.00 0.00
September 0.158684E+10 0.150996E+10 0.130947E+10 0.378695E+09 0.930779E+09 0.00 0.00
October 0.144862E+10 0.172107E+10 0.115221E+10 0.388493E+09 0.763715E+09 0.00 0.00
November 0.894198E+09 0.220522E+10 0.101241E+10 0.338776E+09 0.673633E+09 0.00 0.00
December 0.821030E+09 0.245975E+10 0.963520E+09 0.365229E+09 0.598291E+09 0.00 0.00
               
Annual Sum or Average 0.181663E+11 0.222578E+11 0.165751E+11 0.528241E+10 0.112927E+11 0.00 0.00
Minimum of Months 0.821030E+09 0.126651E+10 0.963520E+09 0.297760E+09 0.598291E+09 0.00 0.00
Maximum of Months 0.245684E+10 0.245975E+10 0.187029E+10 0.630915E+09 0.127730E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.987934E+09 0.281930E+10 0.113522E+10 0.410759E+09 0.724460E+09 0.00 0.00
February 0.986501E+09 0.239500E+10 0.119217E+10 0.370978E+09 0.821191E+09 0.00 0.00
March 0.149522E+10 0.270363E+10 0.163995E+10 0.510070E+09 0.112988E+10 0.00 0.00
April 0.224818E+10 0.216121E+10 0.200371E+10 0.741000E+09 0.126271E+10 0.00 0.00
May 0.227198E+10 0.201242E+10 0.211239E+10 0.643845E+09 0.146855E+10 0.00 0.00
June 0.251475E+10 0.154351E+10 0.208288E+10 0.683051E+09 0.139983E+10 0.00 0.00
July 0.312836E+10 0.136252E+10 0.230641E+10 0.879870E+09 0.142654E+10 0.00 0.00
August 0.298096E+10 0.139882E+10 0.215932E+10 0.868453E+09 0.129086E+10 0.00 0.00
September 0.193412E+10 0.170429E+10 0.156041E+10 0.502580E+09 0.105783E+10 0.00 0.00
October 0.173467E+10 0.193371E+10 0.135762E+10 0.492986E+09 0.864630E+09 0.00 0.00
November 0.101650E+10 0.258229E+10 0.115593E+10 0.398526E+09 0.757406E+09 0.00 0.00
December 0.897156E+09 0.287615E+10 0.106630E+10 0.398511E+09 0.667784E+09 0.00 0.00
               
Annual Sum or Average 0.221963E+11 0.254929E+11 0.197723E+11 0.690063E+10 0.128717E+11 0.00 0.00
Minimum of Months 0.897156E+09 0.136252E+10 0.106630E+10 0.370978E+09 0.667784E+09 0.00 0.00
Maximum of Months 0.312836E+10 0.287615E+10 0.230641E+10 0.879870E+09 0.146855E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.262841E+10 -0.247156E+10 0.00 0.00 744.00 0.00 -156857034.7 81.22 0.00 0.00
February 0.237781E+10 -0.223618E+10 0.00 0.00 672.00 0.00 -141630821.4 81.22 0.00 0.00
March 0.286404E+10 -0.270695E+10 0.00 0.00 744.00 0.00 -157097424.6 81.22 0.00 0.00
April 0.250548E+10 -0.235386E+10 0.00 0.00 720.00 0.00 -151614848.6 81.22 0.00 0.00
May 0.274612E+10 -0.258925E+10 0.00 0.00 744.00 0.00 -156874315.8 81.22 0.00 0.00
June 0.176697E+10 -0.161507E+10 0.00 0.00 720.00 0.00 -151899048.1 81.22 0.00 0.00
July 0.739159E+09 -582666394.6 0.00 0.00 744.00 0.00 -156492149.2 81.21 0.00 0.00
August 0.827014E+09 -670018579.1 0.00 0.00 744.00 0.00 -156995289.9 81.22 0.00 0.00
September 0.161981E+10 -0.146825E+10 0.00 0.00 720.00 0.00 -151566196.3 81.22 0.00 0.00
October 0.262830E+10 -0.247157E+10 0.00 0.00 744.00 0.00 -156729073.2 81.22 0.00 0.00
November 0.262341E+10 -0.247156E+10 0.00 0.00 720.00 0.00 -151855562.5 81.22 0.00 0.00
December 0.251058E+10 -0.235388E+10 0.00 0.00 744.00 0.00 -156705901.6 81.22 0.00 0.00
                     
Annual Sum or Average 0.258371E+11 -0.239908E+11 0.00 0.00 8760.00 0.00 -0.184632E+10 81.22 0.00 0.00
Minimum of Months 0.739159E+09 -0.270695E+10 0.00 0.00 672.00 0.00 -157097424.6 81.21 0.00 0.00
Maximum of Months 0.286404E+10 -582666394.6 0.00 0.00 744.00 0.00 -141630821.4 81.22 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.891809E+10 -0.804842E+10 0.00 0.00 744.00 0.00 -869672876.5 58.99 0.00 0.00
February 0.806737E+10 -0.729105E+10 0.00 0.00 672.00 0.00 -776311935.1 58.99 0.00 0.00
March 0.958331E+10 -0.872705E+10 0.00 0.00 744.00 0.00 -856262532.0 59.00 0.00 0.00
April 0.824651E+10 -0.743230E+10 0.00 0.00 720.00 0.00 -814204254.6 58.99 0.00 0.00
May 0.881003E+10 -0.797220E+10 0.00 0.00 744.00 0.00 -837828041.3 58.99 0.00 0.00
June 0.567005E+10 -0.486395E+10 0.00 0.00 720.00 0.00 -806101666.9 58.99 0.00 0.00
July 0.255983E+10 -0.172222E+10 0.00 0.00 744.00 0.00 -837607613.8 58.99 0.00 0.00
August 0.281797E+10 -0.197826E+10 0.00 0.00 744.00 0.00 -839712720.9 58.98 0.00 0.00
September 0.521217E+10 -0.440503E+10 0.00 0.00 720.00 0.00 -807136437.0 58.99 0.00 0.00
October 0.839856E+10 -0.756340E+10 0.00 0.00 744.00 0.00 -835158099.3 58.99 0.00 0.00
November 0.858474E+10 -0.776083E+10 0.00 0.00 720.00 0.00 -823905409.6 58.99 0.00 0.00
December 0.842059E+10 -0.755889E+10 0.00 0.00 744.00 0.00 -861693377.4 58.99 0.00 0.00
                     
Annual Sum or Average 0.852892E+11 -0.753236E+11 0.00 0.00 8760.00 0.00 -0.996559E+10 58.99 0.00 0.00
Minimum of Months 0.255983E+10 -0.872705E+10 0.00 0.00 672.00 0.00 -869672876.5 58.98 0.00 0.00
Maximum of Months 0.958331E+10 -0.172222E+10 0.00 0.00 744.00 0.00 -776311935.1 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: GYM_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.38 0.17 01-JAN-08:50 1577.20 13.30 0.00 241.17 277.39 9.23 0.00 0.00
February 279.67 0.30 0.00 02-FEB-07:30 1746.60 13.83 0.00 240.67 367.39 10.23 0.00 21.50
March 338.17 0.26 0.00 01-MAR-06:00 3179.17 13.95 0.00 301.17 1042.79 10.89 0.00 87.83
April 358.33 0.23 0.00 01-APR-08:20 2092.21 14.44 0.00 319.83 420.23 11.75 0.00 96.67
May 393.83 0.24 0.00 01-MAY-07:00 2116.90 15.03 0.00 361.50 408.59 12.54 0.00 106.17
June 381.00 0.25 0.00 01-JUN-07:30 2099.68 14.91 0.00 351.00 404.39 12.51 0.00 90.00
July 408.67 0.23 0.00 01-JUL-07:30 2270.42 14.67 0.00 361.17 414.01 12.34 0.00 121.33
August 390.67 0.24 0.00 01-AUG-08:09 2262.54 14.23 0.00 341.83 410.05 11.71 0.00 93.67
September 328.83 0.25 0.00 01-SEP-07:00 2633.17 13.92 0.00 294.17 696.39 10.94 0.00 65.17
October 296.17 0.29 0.00 01-OCT-13:09 3550.01 12.80 0.00 253.67 2082.83 9.35 0.00 88.33
November 300.00 0.38 0.00 01-NOV-09:09 1826.94 12.89 0.00 241.67 288.75 9.15 0.00 0.67
December 297.00 0.42 0.17 01-DEC-08:50 1535.28 12.68 0.00 236.83 250.20 8.60 0.00 0.00
                         
Annual Sum or Average 4065.67 0.28     2248.75 13.97 0.00 3544.67 575.18 10.93 0.00 771.33
Minimum of Months 279.67 0.23 0.00   1535.28 12.68 0.00 236.83 250.20 8.60 0.00 0.00
Maximum of Months 408.67 0.42 0.17   3550.01 15.03 0.00 361.50 2082.83 12.54 0.00 121.33



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.32 0.24 01-JAN-08:09 1038.93 25.08 245.67 249.33 923.53 26.16 266.00 245.17
February 279.67 0.32 0.24 01-FEB-08:20 894.49 22.74 216.83 235.50 1064.76 26.43 253.17 228.00
March 338.17 0.34 0.24 01-MAR-07:40 816.34 21.74 243.67 275.67 1104.31 22.93 275.00 269.33
April 358.33 0.34 0.24 01-APR-08:30 643.02 21.52 242.67 284.17 889.47 22.71 290.33 283.17
May 393.83 0.34 0.24 01-MAY-07:49 593.94 21.15 215.83 311.67 881.64 22.37 303.50 306.17
June 381.00 0.34 0.24 01-JUN-07:30 598.26 20.75 153.00 300.50 1000.08 23.85 326.83 296.50
July 408.67 0.34 0.24 01-JUL-08:09 615.53 20.76 194.83 321.17 1031.10 23.94 358.00 314.33
August 390.67 0.34 0.24 01-AUG-08:09 630.81 20.99 221.33 308.33 992.34 22.26 312.17 301.50
September 328.83 0.33 0.24 01-SEP-07:40 810.58 21.77 232.33 274.33 1263.63 23.02 268.33 265.17
October 296.17 0.32 0.24 01-OCT-09:39 789.97 22.30 184.83 265.50 1005.49 25.09 266.50 255.83
November 300.00 0.33 0.24 01-NOV-07:40 991.71 24.87 247.50 249.83 1227.59 26.95 273.50 244.00
December 297.00 0.33 0.24 01-DEC-08:09 1365.96 25.97 237.00 246.50 1197.43 27.32 271.83 244.00
                         
Annual Sum or Average 4065.67 0.33     793.21 22.29 2635.50 3322.50 1041.74 24.24 3465.17 3253.17
Minimum of Months 279.67 0.32 0.24   593.94 20.75 153.00 235.50 881.64 22.26 253.17 228.00
Maximum of Months 408.67 0.34 0.24   1365.96 25.97 247.50 321.17 1263.63 27.32 358.00 314.33



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.48 0.44 01-JAN-07:30 7276.38 37.18 285.00 275.33 1163.57 27.12 240.83 259.83
February 279.67 0.48 0.44 01-FEB-07:30 6496.83 35.44 275.50 271.50 791.57 23.50 215.50 235.67
March 338.17 0.51 0.44 01-MAR-06:00 1668.18 19.54 11.17 308.83 633.94 21.37 213.17 256.83
April 358.33 0.51 0.44 01-APR-08:20 991.55 18.70 0.00 322.67 487.15 21.14 175.17 254.50
May 393.83 0.52 0.44 01-MAY-07:19 878.45 18.23 0.00 353.33 407.89 20.65 132.83 243.33
June 381.00 0.53 0.44 01-JUN-07:30 761.05 17.83 0.00 345.00 363.41 20.28 70.83 214.67
July 408.67 0.53 0.44 01-JUL-08:20 753.03 17.90 0.00 353.83 373.29 20.37 101.67 227.33
August 390.67 0.52 0.44 01-AUG-07:49 839.53 18.22 0.00 344.50 422.00 20.66 147.00 250.17
September 328.83 0.50 0.44 01-SEP-07:19 1290.66 19.48 14.00 302.50 568.49 21.31 186.00 250.50
October 296.17 0.49 0.44 01-OCT-09:39 3370.14 26.81 142.33 297.17 710.63 22.25 145.00 250.00
November 300.00 0.49 0.44 01-NOV-06:49 7060.78 36.82 292.67 276.33 1029.03 26.72 246.83 263.83
December 297.00 0.48 0.44 01-DEC-07:30 7118.43 37.31 286.17 277.17 1616.90 29.89 243.67 264.67
                         
Annual Sum or Average 4065.67 0.51     2901.70 24.35 1306.83 3728.17 677.49 22.65 2118.50 2971.33
Minimum of Months 279.67 0.48 0.44   753.03 17.83 0.00 271.50 363.41 20.28 70.83 214.67
Maximum of Months 408.67 0.53 0.44   7276.38 37.31 292.67 353.83 1616.90 29.89 246.83 264.67



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.55 0.22 01-JAN-15:09 396.81 23.62 134.50 79.50 528.79 22.24 87.00 124.67
February 279.67 0.50 0.22 01-FEB-13:20 354.00 23.64 154.17 89.17 763.03 23.81 111.50 151.67
March 338.17 0.47 0.22 01-MAR-13:20 423.35 23.59 191.00 123.33 896.15 23.53 137.17 193.33
April 358.33 0.44 0.22 01-APR-12:09 398.61 22.17 192.83 141.83 761.72 20.64 125.17 209.50
May 393.83 0.40 0.22 01-MAY-12:30 449.91 22.26 229.17 191.50 826.19 20.91 148.00 266.00
June 381.00 0.39 0.22 01-JUN-12:30 502.70 22.40 212.00 182.83 971.66 21.05 146.83 257.50
July 408.67 0.39 0.22 01-JUL-11:20 500.42 22.52 256.00 199.67 990.48 20.98 157.33 273.83
August 390.67 0.43 0.22 01-AUG-12:00 444.76 22.35 222.17 168.50 900.05 20.88 140.83 230.33
September 328.83 0.44 0.22 01-SEP-12:00 477.58 24.45 195.50 139.83 1077.01 24.34 135.67 193.17
October 296.17 0.52 0.22 01-OCT-13:09 347.94 23.26 144.83 93.50 727.08 22.75 90.17 150.50
November 300.00 0.54 0.22 01-NOV-12:50 369.89 23.67 152.67 90.67 823.69 23.68 106.83 140.67
December 297.00 0.58 0.22 02-DEC-13:30 338.26 23.41 131.17 75.00 450.94 21.96 86.50 120.83
                         
Annual Sum or Average 4065.67 0.46     423.03 23.04 2216.00 1575.33 823.24 22.11 1473.00 2312.00
Minimum of Months 279.67 0.39 0.22   338.26 22.17 131.17 75.00 450.94 20.64 86.50 120.83
Maximum of Months 408.67 0.58 0.22   502.70 24.45 256.00 199.67 1077.01 24.34 157.33 273.83



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.78 0.63 01-JAN-09:20 287.18 13.85 0.00 57.50 123.92 14.42 0.00 0.00
February 279.67 0.73 0.63 04-FEB-09:09 365.53 14.83 0.00 121.00 147.57 15.25 0.00 0.00
March 338.17 0.70 0.53 05-MAR-14:09 439.89 15.32 0.00 202.17 171.57 15.67 0.00 0.00
April 358.33 0.66 0.53 05-APR-09:09 456.42 16.49 0.00 292.33 189.31 16.89 0.00 0.00
May 393.83 0.60 0.44 01-MAY-17:10 635.95 17.28 0.00 369.50 244.81 17.77 0.00 15.83
June 381.00 0.61 0.44 09-JUN-15:09 675.30 19.25 42.50 363.17 238.76 17.96 0.00 2.00
July 408.67 0.62 0.44 30-JUL-17:10 607.66 19.09 45.17 375.33 225.42 17.77 0.00 1.33
August 390.67 0.65 0.44 01-AUG-17:10 472.03 16.58 0.00 334.17 199.89 16.96 0.00 9.17
September 328.83 0.69 0.53 02-SEP-08:20 404.62 15.74 0.00 209.17 169.24 16.13 0.00 0.00
October 296.17 0.79 0.53 05-OCT-11:30 300.77 14.14 0.00 92.17 128.66 14.53 0.00 0.00
November 300.00 0.78 0.63 01-NOV-08:50 294.73 13.57 0.00 78.00 125.51 14.07 0.00 0.00
December 297.00 0.81 0.63 01-DEC-10:39 255.62 13.11 0.00 37.17 113.04 13.72 0.00 0.00
                         
Annual Sum or Average 4065.67 0.69     449.06 16.00 87.67 2531.67 178.58 16.11 0.00 28.33
Minimum of Months 279.67 0.60 0.44   255.62 13.11 0.00 37.17 113.04 13.72 0.00 0.00
Maximum of Months 408.67 0.81 0.63   675.30 19.25 45.17 375.33 244.81 17.96 0.00 15.83



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.34 0.24 01-JAN-08:20 864.68 23.50 172.50 238.17 856.62 24.60 247.67 239.50
February 279.67 0.35 0.24 01-FEB-08:39 736.17 21.19 152.00 221.83 1003.40 24.98 217.67 220.67
March 338.17 0.37 0.24 01-MAR-07:00 682.89 20.21 156.17 256.33 1051.60 21.22 212.17 257.33
April 358.33 0.37 0.24 01-APR-09:20 532.30 19.91 80.17 252.17 842.84 20.88 165.67 265.17
May 393.83 0.38 0.24 01-MAY-09:50 493.49 19.53 44.50 264.67 839.32 20.54 131.50 283.17
June 381.00 0.39 0.24 01-JUN-10:30 505.46 19.09 14.83 237.33 960.17 22.17 117.00 264.33
July 408.67 0.39 0.24 01-JUL-09:09 518.97 19.08 20.33 268.33 989.15 22.24 151.17 285.83
August 390.67 0.38 0.24 01-AUG-08:20 529.85 19.35 43.83 270.50 949.01 20.40 128.33 281.00
September 328.83 0.35 0.24 01-SEP-07:00 690.71 20.24 117.33 255.33 1214.74 21.31 180.17 255.33
October 296.17 0.34 0.24 01-OCT-09:50 667.02 20.70 104.33 246.67 956.30 23.53 173.67 244.33
November 300.00 0.36 0.24 01-NOV-07:49 827.20 23.38 177.00 235.17 1163.72 25.52 243.50 235.50
December 297.00 0.36 0.24 01-DEC-08:20 1191.28 24.47 160.17 234.17 1128.51 25.85 248.00 235.33
                         
Annual Sum or Average 4065.67 0.37     667.51 20.70 1243.17 2980.67 990.70 22.57 2216.50 3067.50
Minimum of Months 279.67 0.34 0.24   493.49 19.08 14.83 221.83 839.32 20.40 117.00 220.67
Maximum of Months 408.67 0.39 0.24   1191.28 24.47 177.00 270.50 1214.74 25.85 248.00 285.83



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.48 0.44 01-JAN-07:30 6962.70 37.08 284.50 271.33 915.42 25.26 113.83 253.83
February 279.67 0.52 0.44 01-FEB-08:30 6166.46 33.59 254.50 260.33 547.62 19.44 29.17 192.17
March 338.17 0.54 0.44 01-MAR-07:00 1420.42 18.39 9.83 297.33 441.34 18.50 1.17 205.83
April 358.33 0.56 0.44 01-APR-09:00 795.90 17.51 0.00 307.83 328.23 18.09 0.00 157.83
May 393.83 0.60 0.44 02-MAY-09:50 701.69 17.03 0.00 337.33 265.09 17.55 0.00 71.00
June 381.00 0.62 0.44 04-JUN-09:50 600.01 16.58 0.00 324.67 231.41 17.06 0.00 18.83
July 408.67 0.62 0.44 05-JUL-11:39 587.40 16.63 0.00 332.67 235.79 17.13 0.00 30.00
August 390.67 0.60 0.44 01-AUG-09:50 663.91 16.99 0.00 323.83 277.15 17.51 0.00 87.50
September 328.83 0.54 0.44 01-SEP-08:09 1075.92 18.39 14.00 290.00 395.92 18.36 0.50 183.17
October 296.17 0.52 0.44 01-OCT-09:00 3147.53 26.21 141.83 291.83 533.52 19.45 18.00 201.50
November 300.00 0.50 0.44 01-NOV-06:00 6755.20 36.58 290.17 272.17 780.74 24.54 101.83 250.67
December 297.00 0.50 0.44 01-DEC-07:40 6728.92 35.46 265.83 265.00 1268.94 25.89 121.67 246.33
                         
Annual Sum or Average 4065.67 0.56     2668.17 23.25 1260.67 3574.33 488.24 19.60 386.17 1898.67
Minimum of Months 279.67 0.48 0.44   587.40 16.58 0.00 260.33 231.41 17.06 0.00 18.83
Maximum of Months 408.67 0.62 0.44   6962.70 37.08 290.17 337.33 1268.94 25.89 121.67 253.83



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.57 0.24 01-JAN-15:09 398.54 23.62 134.50 80.17 530.52 22.24 87.00 126.00
February 279.67 0.51 0.24 01-FEB-13:20 355.90 23.64 154.17 90.17 764.93 23.81 111.33 152.17
March 338.17 0.48 0.24 01-MAR-13:20 425.52 23.58 191.00 124.50 898.31 23.53 137.17 194.83
April 358.33 0.45 0.24 01-APR-12:09 401.37 22.17 192.83 143.33 764.48 20.64 125.17 214.67
May 393.83 0.41 0.24 01-MAY-12:30 452.77 22.26 229.17 196.67 829.05 20.91 148.00 271.00
June 381.00 0.40 0.24 01-JUN-12:30 505.66 22.40 212.00 185.33 974.62 21.05 146.83 262.67
July 408.67 0.41 0.24 01-JUL-11:09 503.49 22.52 256.00 202.50 993.55 20.98 157.33 277.33
August 390.67 0.44 0.24 01-AUG-12:00 447.57 22.34 222.17 170.50 902.86 20.88 140.83 233.33
September 328.83 0.45 0.24 01-SEP-12:00 480.01 24.45 195.50 140.67 1079.43 24.34 135.67 195.00
October 296.17 0.53 0.24 01-OCT-13:09 349.87 23.26 144.83 94.17 729.02 22.75 90.17 151.50
November 300.00 0.55 0.24 01-NOV-12:50 371.64 23.67 152.67 91.50 825.44 23.68 106.83 141.17
December 297.00 0.59 0.24 01-DEC-12:30 339.87 23.41 131.17 75.17 452.55 21.96 86.50 121.83
                         
Annual Sum or Average 4065.67 0.48     425.43 23.04 2216.00 1594.67 825.63 22.11 1472.83 2341.50
Minimum of Months 279.67 0.40 0.24   339.87 22.17 131.17 75.17 452.55 20.64 86.50 121.83
Maximum of Months 408.67 0.59 0.24   505.66 24.45 256.00 202.50 1079.43 24.34 157.33 277.33



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.78 0.63 01-JAN-09:20 289.05 13.90 0.00 58.00 125.72 14.42 0.00 0.00
February 279.67 0.73 0.63 04-FEB-09:09 367.52 14.87 0.00 122.83 149.48 15.25 0.00 0.00
March 338.17 0.70 0.53 04-MAR-13:00 442.15 15.36 0.00 205.17 173.71 15.67 0.00 0.00
April 358.33 0.65 0.53 05-APR-09:09 459.45 16.53 0.00 299.67 192.23 16.90 0.00 0.00
May 393.83 0.60 0.44 01-MAY-17:10 638.78 17.31 0.00 369.50 247.50 17.77 0.00 16.00
June 381.00 0.60 0.44 09-JUN-15:09 678.29 19.27 42.50 363.17 241.61 17.97 0.00 2.17
July 408.67 0.62 0.44 30-JUL-17:10 610.82 19.12 45.17 375.33 228.46 17.78 0.00 1.33
August 390.67 0.65 0.44 01-AUG-17:10 475.10 16.62 0.00 337.67 202.87 16.97 0.00 9.17
September 328.83 0.69 0.53 02-SEP-08:20 407.36 15.78 0.00 214.17 171.89 16.13 0.00 0.00
October 296.17 0.78 0.53 05-OCT-11:20 303.02 14.19 0.00 93.83 130.84 14.54 0.00 0.00
November 300.00 0.77 0.63 01-NOV-08:50 296.62 13.62 0.00 78.67 127.33 14.08 0.00 0.00
December 297.00 0.80 0.63 01-DEC-10:30 257.37 13.16 0.00 38.50 114.74 13.72 0.00 0.00
                         
Annual Sum or Average 4065.67 0.69     451.60 16.04 87.67 2556.50 181.03 16.11 0.00 28.67
Minimum of Months 279.67 0.60 0.44   257.37 13.16 0.00 38.50 114.74 13.72 0.00 0.00
Maximum of Months 408.67 0.80 0.63   678.29 19.27 45.17 375.33 247.50 17.97 0.00 16.00



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.34 0.24 01-JAN-08:20 868.64 23.50 172.33 239.00 860.59 24.60 247.67 239.67
February 279.67 0.35 0.24 01-FEB-08:30 740.26 21.19 151.50 222.33 1007.50 24.98 217.50 221.67
March 338.17 0.36 0.24 01-MAR-07:00 686.70 20.20 156.17 256.83 1055.40 21.22 211.17 258.83
April 358.33 0.37 0.24 01-APR-09:09 536.41 19.91 79.67 253.83 846.94 20.87 164.33 266.67
May 393.83 0.38 0.24 01-MAY-09:09 497.22 19.53 44.50 267.17 843.05 20.54 131.00 285.17
June 381.00 0.39 0.24 01-JUN-10:30 509.16 19.09 14.67 240.33 963.88 22.17 116.00 267.67
July 408.67 0.38 0.24 01-JUL-09:09 522.91 19.08 20.33 271.17 993.09 22.24 150.00 288.83
August 390.67 0.38 0.24 01-AUG-08:20 533.83 19.35 43.17 272.83 952.99 20.40 126.50 284.33
September 328.83 0.35 0.24 01-SEP-07:00 694.62 20.24 116.17 256.50 1218.64 21.30 179.33 257.17
October 296.17 0.34 0.24 01-OCT-09:39 670.82 20.69 104.00 247.83 960.09 23.52 173.33 245.17
November 300.00 0.35 0.24 01-NOV-07:49 831.37 23.37 177.00 236.50 1167.89 25.51 243.00 236.17
December 297.00 0.36 0.24 01-DEC-08:20 1194.93 24.46 159.83 234.33 1132.16 25.84 247.83 236.00
                         
Annual Sum or Average 4065.67 0.36     671.40 20.70 1239.33 2998.67 994.59 22.57 2207.67 3087.33
Minimum of Months 279.67 0.34 0.24   497.22 19.08 14.67 222.33 843.05 20.40 116.00 221.67
Maximum of Months 408.67 0.39 0.24   1194.93 24.46 177.00 272.83 1218.64 25.84 247.83 288.83



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.74 0.72 01-JAN-07:30 6965.76 37.11 284.67 271.33 917.36 25.25 113.67 254.00
February 279.67 0.76 0.72 01-FEB-08:30 6192.42 34.51 265.50 262.50 550.13 19.44 29.17 192.83
March 338.17 0.77 0.72 01-MAR-07:00 1424.43 18.49 10.50 297.67 443.70 18.50 1.17 206.50
April 358.33 0.78 0.72 01-APR-09:00 798.88 17.56 0.00 308.00 331.30 18.10 0.00 161.33
May 393.83 0.80 0.72 02-MAY-09:50 704.41 17.08 0.00 337.50 267.92 17.55 0.00 73.50
June 381.00 0.81 0.72 04-JUN-09:39 602.93 16.63 0.00 325.00 234.38 17.06 0.00 20.17
July 408.67 0.81 0.72 01-JUL-11:30 590.55 16.69 0.00 333.17 238.94 17.13 0.00 32.83
August 390.67 0.80 0.72 01-AUG-09:50 666.98 17.04 0.00 324.33 280.23 17.51 0.00 93.33
September 328.83 0.77 0.72 01-SEP-08:09 1078.59 18.44 14.00 290.33 398.73 18.36 0.50 185.33
October 296.17 0.76 0.72 01-OCT-09:00 3149.88 26.23 141.83 291.83 535.92 19.45 18.00 202.33
November 300.00 0.75 0.72 01-NOV-06:00 6757.86 36.58 290.17 272.17 782.98 24.54 101.83 250.83
December 297.00 0.75 0.72 01-DEC-07:40 6732.88 35.47 265.83 265.33 1290.60 26.24 125.67 248.00
                         
Annual Sum or Average 4065.67 0.78     2672.80 23.36 1272.50 3579.17 492.34 19.63 390.00 1921.00
Minimum of Months 279.67 0.74 0.72   590.55 16.63 0.00 262.50 234.38 17.06 0.00 20.17
Maximum of Months 408.67 0.81 0.72   6965.76 37.11 290.17 337.50 1290.60 26.24 125.67 254.00



Table of Contents

Report: DaylightingReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.50 0.24 01-JAN-12:30 446.66 23.77 140.00 100.50 555.72 22.30 87.83 139.83
February 279.67 0.45 0.24 01-FEB-12:30 407.56 23.78 158.67 125.00 791.61 23.86 112.67 166.00
March 338.17 0.42 0.24 01-MAR-12:20 481.72 23.72 196.17 180.00 927.22 23.59 138.67 218.83
April 358.33 0.39 0.24 01-APR-10:00 466.87 22.32 209.50 205.67 799.02 20.70 128.50 254.00
May 393.83 0.35 0.24 01-MAY-07:40 524.87 22.42 239.00 278.50 865.96 20.98 150.50 303.50
June 381.00 0.34 0.24 01-JUN-07:19 579.69 22.56 232.00 285.17 1012.48 21.12 148.00 308.83
July 408.67 0.34 0.24 01-JUL-08:20 577.20 22.67 273.50 302.17 1031.91 21.04 161.50 319.50
August 390.67 0.38 0.24 01-AUG-08:09 513.88 22.49 235.83 234.83 937.87 20.94 143.50 276.33
September 328.83 0.40 0.24 01-SEP-11:30 540.16 24.58 202.33 186.67 1111.13 24.39 137.67 217.83
October 296.17 0.47 0.24 01-OCT-12:39 396.99 23.40 151.00 121.33 754.08 22.80 91.17 167.67
November 300.00 0.49 0.24 01-NOV-09:39 419.18 23.81 157.00 118.83 850.35 23.73 109.00 153.33
December 297.00 0.53 0.24 01-DEC-10:00 385.42 23.56 135.83 98.83 476.49 22.02 88.33 132.33
                         
Annual Sum or Average 4065.67 0.42     485.73 23.19 2330.83 2237.50 857.06 22.17 1497.33 2658.00
Minimum of Months 279.67 0.34 0.24   385.42 22.32 135.83 98.83 476.49 20.70 87.83 132.33
Maximum of Months 408.67 0.53 0.24   579.69 24.58 273.50 302.17 1111.13 24.39 161.50 319.50



Table of Contents

Report: DaylightingReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.68 0.53 01-JAN-09:20 390.04 16.29 0.00 173.50 205.97 18.73 0.00 0.00
February 279.67 0.63 0.44 14-FEB-11:30 480.61 17.06 0.00 217.83 236.86 19.21 0.00 2.17
March 338.17 0.60 0.44 05-MAR-14:09 568.38 17.39 0.00 289.17 269.62 19.36 6.50 31.00
April 358.33 0.56 0.44 01-APR-12:20 604.06 18.50 0.00 328.50 304.91 20.55 54.33 51.17
May 393.83 0.52 0.44 01-MAY-07:10 805.04 19.27 0.00 377.83 373.18 21.20 162.00 197.67
June 381.00 0.51 0.44 01-JUN-06:00 850.11 21.07 42.67 369.67 407.92 22.88 197.17 206.67
July 408.67 0.52 0.44 01-JUL-06:19 778.39 20.88 45.33 380.83 357.73 21.19 184.17 202.67
August 390.67 0.55 0.44 01-AUG-07:49 621.79 18.53 0.00 359.50 317.80 20.55 67.00 87.00
September 328.83 0.58 0.44 02-SEP-08:20 538.01 17.80 0.00 291.00 274.22 19.92 4.83 20.00
October 296.17 0.68 0.44 05-OCT-11:20 403.35 16.44 0.00 180.83 210.05 18.69 0.50 2.17
November 300.00 0.68 0.44 02-NOV-11:30 397.33 15.88 0.00 178.17 206.92 18.19 0.00 0.50
December 297.00 0.71 0.53 01-DEC-09:09 351.62 15.57 0.00 146.50 190.34 18.07 0.00 0.00
                         
Annual Sum or Average 4065.67 0.59     585.25 18.09 88.00 3293.33 287.98 20.03 676.50 801.00
Minimum of Months 279.67 0.51 0.44   351.62 15.57 0.00 146.50 190.34 18.07 0.00 0.00
Maximum of Months 408.67 0.71 0.53   850.11 21.07 45.33 380.83 407.92 22.88 197.17 206.67



Table of Contents

Report: DaylightingReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.68 0.53 01-JAN-09:20 390.30 15.80 0.00 173.50 206.57 18.42 0.00 0.00
February 279.67 0.63 0.44 14-FEB-11:30 481.19 16.58 0.00 217.83 237.63 18.92 0.00 2.17
March 338.17 0.60 0.44 03-MAR-13:30 569.21 16.94 0.00 289.50 270.50 19.10 0.00 33.33
April 358.33 0.56 0.44 01-APR-12:20 605.00 18.12 0.00 328.50 305.76 20.35 46.17 52.67
May 393.83 0.52 0.44 01-MAY-07:10 777.09 18.82 0.00 374.50 359.46 21.01 122.00 190.50
June 381.00 0.51 0.44 01-JUN-06:00 851.78 20.60 42.67 369.67 409.86 22.68 159.17 207.83
July 408.67 0.52 0.44 01-JUL-06:19 779.94 20.48 45.33 380.83 358.31 21.12 133.67 203.50
August 390.67 0.55 0.44 01-AUG-07:49 622.89 18.20 0.00 359.50 309.06 20.42 62.17 75.83
September 328.83 0.58 0.44 02-SEP-08:20 538.71 17.44 0.00 291.00 275.04 19.73 4.17 20.83
October 296.17 0.68 0.44 05-OCT-11:20 403.65 16.02 0.00 181.33 210.54 18.47 0.00 2.50
November 300.00 0.68 0.44 02-NOV-11:30 397.65 15.42 0.00 178.17 207.52 17.91 0.00 0.50
December 297.00 0.71 0.53 01-DEC-09:09 351.79 15.08 0.00 146.50 190.89 17.77 0.00 0.00
                         
Annual Sum or Average 4065.67 0.59     583.29 17.67 88.00 3290.83 286.48 19.82 527.33 789.67
Minimum of Months 279.67 0.51 0.44   351.79 15.08 0.00 146.50 190.89 17.77 0.00 0.00
Maximum of Months 408.67 0.71 0.53   851.78 20.60 45.33 380.83 409.86 22.68 159.17 207.83



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.46 0.44 01-JAN-07:30 7283.50 37.26 285.17 283.50 1157.45 27.21 249.33 267.33
February 279.67 0.48 0.44 01-FEB-07:40 6505.44 35.50 275.50 278.33 769.56 22.48 203.17 243.17
March 338.17 0.50 0.44 01-MAR-07:10 1676.16 19.99 16.50 319.50 627.56 21.67 231.17 284.50
April 358.33 0.49 0.44 01-APR-07:19 997.86 19.24 0.00 339.00 483.14 21.58 237.83 294.67
May 393.83 0.49 0.44 01-MAY-06:49 885.08 18.80 0.00 372.33 405.31 21.12 182.50 315.50
June 381.00 0.50 0.44 01-JUN-06:00 767.07 18.40 0.00 362.83 361.02 20.75 124.17 299.50
July 408.67 0.50 0.44 01-JUL-07:10 759.09 18.47 0.00 373.00 370.66 20.84 162.83 317.33
August 390.67 0.50 0.44 01-AUG-07:19 845.36 18.77 0.00 360.17 418.52 21.12 204.17 309.00
September 328.83 0.49 0.44 01-SEP-06:00 1298.38 19.91 14.00 314.33 562.20 21.65 221.67 276.33
October 296.17 0.48 0.44 01-OCT-09:39 3380.49 27.04 144.00 311.50 698.90 22.50 164.83 269.50
November 300.00 0.48 0.44 01-NOV-06:49 7067.76 36.89 293.00 282.67 1023.11 26.86 253.83 271.67
December 297.00 0.47 0.44 01-DEC-07:19 7124.40 37.41 286.17 283.33 1610.55 29.98 254.17 274.00
                         
Annual Sum or Average 4065.67 0.49     2908.74 24.73 1314.33 3880.50 671.32 22.89 2489.67 3422.50
Minimum of Months 279.67 0.46 0.44   759.09 18.40 0.00 278.33 361.02 20.75 124.17 243.17
Maximum of Months 408.67 0.50 0.44   7283.50 37.41 293.00 373.00 1610.55 29.98 254.17 317.33



Table of Contents

Report: DaylightingReportMonthly

For: OFFICES_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.62 0.58 01-JAN-07:30 1052.23 27.32 273.67 264.33 728.34 25.94 268.00 241.17
February 279.67 0.62 0.58 01-FEB-07:19 753.80 25.41 244.00 250.83 744.93 24.88 242.17 220.67
March 338.17 0.64 0.58 01-MAR-06:00 619.55 21.61 225.83 279.67 973.05 23.71 272.33 263.17
April 358.33 0.63 0.58 01-APR-05:00 561.81 21.31 201.83 304.17 822.76 22.02 265.17 273.67
May 393.83 0.64 0.58 01-MAY-06:49 455.59 20.82 139.00 308.83 848.32 21.64 260.67 281.83
June 381.00 0.64 0.58 01-JUN-06:49 417.16 20.46 84.50 290.33 799.11 21.34 250.50 272.83
July 408.67 0.64 0.58 01-JUL-05:00 435.35 20.57 128.17 317.50 866.15 21.47 292.83 280.83
August 390.67 0.64 0.58 01-AUG-07:30 472.05 20.85 157.17 315.33 833.47 21.63 279.33 281.17
September 328.83 0.63 0.58 01-SEP-06:49 569.78 21.44 199.33 278.50 651.44 22.14 239.50 245.17
October 296.17 0.64 0.58 01-OCT-09:39 639.42 22.44 154.17 261.17 729.38 22.86 210.67 234.83
November 300.00 0.62 0.58 01-NOV-06:49 934.09 26.84 267.00 268.17 892.15 26.11 270.00 244.67
December 297.00 0.62 0.58 01-DEC-07:19 1493.97 30.04 278.67 269.17 740.20 25.77 264.33 242.67
                         
Annual Sum or Average 4065.67 0.63     671.88 22.94 2353.33 3408.00 807.17 23.09 3115.50 3082.67
Minimum of Months 279.67 0.62 0.58   417.16 20.46 84.50 250.83 651.44 21.34 210.67 220.67
Maximum of Months 408.67 0.64 0.58   1493.97 30.04 278.67 317.50 973.05 26.11 292.83 281.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFETERIA_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.57 0.50 01-JAN-07:49 250.70 22.74 191.33 210.17 581.64 24.36 151.17 250.00
February 279.67 0.55 0.50 01-FEB-07:10 314.30 24.53 198.67 230.67 676.34 24.75 156.67 246.33
March 338.17 0.56 0.50 01-MAR-06:40 320.39 22.44 242.67 283.00 921.91 24.89 191.67 302.33
April 358.33 0.53 0.50 01-APR-05:00 403.06 24.86 312.33 325.50 807.38 24.73 186.67 326.50
May 393.83 0.53 0.50 01-MAY-06:19 390.08 22.77 300.17 361.17 868.02 24.28 200.67 365.33
June 381.00 0.53 0.50 01-JUN-06:19 395.16 22.58 296.17 354.67 830.68 23.64 177.33 358.00
July 408.67 0.54 0.50 01-JUL-05:40 393.80 22.77 334.67 366.50 892.54 23.96 213.00 371.17
August 390.67 0.54 0.50 01-AUG-06:00 362.92 23.01 323.00 349.00 837.76 24.48 200.67 352.17
September 328.83 0.54 0.50 01-SEP-06:40 332.52 23.48 257.67 287.83 620.56 23.40 164.83 300.33
October 296.17 0.58 0.50 01-OCT-09:39 289.02 22.52 172.67 207.00 631.95 23.24 125.67 250.50
November 300.00 0.57 0.50 01-NOV-06:40 323.70 24.38 194.00 227.50 760.74 24.57 153.00 250.83
December 297.00 0.57 0.50 01-DEC-07:19 259.77 23.79 182.67 213.17 582.47 23.83 139.83 246.67
                         
Annual Sum or Average 4065.67 0.55     341.96 23.28 3006.00 3416.17 763.38 24.18 2061.17 3620.17
Minimum of Months 279.67 0.53 0.50   250.70 22.44 172.67 207.00 581.64 23.24 125.67 246.33
Maximum of Months 408.67 0.58 0.50   403.06 24.86 334.67 366.50 921.91 24.89 213.00 371.17



Table of Contents

Report: DaylightingReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.81 0.62 01-JAN-08:39 528.57 21.22 55.17 67.83 259.70 17.96 9.50 0.00
February 279.67 0.78 0.56 01-FEB-07:40 626.11 21.84 58.50 78.00 327.67 20.58 55.50 11.33
March 338.17 0.76 0.56 01-MAR-06:49 874.99 22.23 85.50 113.83 338.17 18.39 51.83 20.67
April 358.33 0.75 0.56 01-APR-06:10 764.63 22.08 82.67 122.50 428.81 21.49 96.33 70.17
May 393.83 0.74 0.56 01-MAY-07:19 824.38 21.69 96.00 133.67 419.09 19.27 72.50 78.17
June 381.00 0.73 0.56 01-JUN-06:00 788.96 20.99 77.33 113.83 463.92 19.19 60.33 99.33
July 408.67 0.73 0.56 01-JUL-06:10 850.85 21.35 87.83 143.67 427.43 19.46 82.00 91.33
August 390.67 0.75 0.56 01-AUG-07:49 797.22 21.85 84.17 129.50 432.55 21.37 101.83 80.83
September 328.83 0.77 0.56 01-SEP-07:40 576.90 20.49 54.83 88.83 353.04 19.71 54.33 24.17
October 296.17 0.81 0.56 10-OCT-08:30 590.75 20.02 45.17 75.67 301.85 18.17 32.17 5.50
November 300.00 0.80 0.56 01-NOV-06:00 710.89 21.64 66.50 70.67 333.05 20.36 47.67 22.67
December 297.00 0.82 0.56 02-DEC-07:19 531.04 20.61 56.17 52.17 265.36 19.38 29.50 10.33
                         
Annual Sum or Average 4065.67 0.77     718.24 21.36 849.83 1190.17 370.30 19.65 693.50 514.50
Minimum of Months 279.67 0.73 0.56   528.57 20.02 45.17 52.17 259.70 17.96 9.50 0.00
Maximum of Months 408.67 0.82 0.62   874.99 22.23 96.00 143.67 463.92 21.49 101.83 99.33



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_1 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.124627E+09 12123.89 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 23343839.44 5762.33 09-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.264783E+09 11916.40 30-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 11296.98 4.48 26-APR-10:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 64070.23 4.40 30-JUN-12:10 0.00 0.00 0.00 0.00 0.00
July 943.32 2.53 23-JUL-17:30 0.00 0.00 0.00 0.00 0.00
August 33428.95 4.11 19-AUG-14:13 0.00 0.00 0.00 0.00 0.00
September 75251.35 5.79 28-SEP-14:30 0.00 0.00 0.00 0.00 0.00
October 142519.56 5.70 03-OCT-12:50 0.00 0.00 0.00 0.00 0.00
November 642890.20 1658.22 24-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 48837657.11 8566.72 13-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.462562E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.264783E+09 12123.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108656E+09 5931.11 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.144146E+09 5932.58 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.271054E+09 5931.99 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 29160034.49 5932.07 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 43771801.55 5931.21 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 13412801.91 5931.74 08-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 0.102784E+09 5933.39 20-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 98500415.71 5933.42 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 11780743.05 5930.81 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 2160810.52 5926.22 12-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 18617897.69 5931.98 10-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 76029460.69 5931.28 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.920075E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2160810.52 5926.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271054E+09 5933.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44127835.47 20659.96 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 87465596.33 20673.81 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.219530E+09 20668.09 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 10711249.12 20667.18 20-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 20593650.56 20669.63 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 4616978.21 13400.09 01-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 0.384966E+09 20676.29 20-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 0.247424E+09 20676.37 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 21498989.14 20668.40 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 460195.47 7669.92 03-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 9666986.39 20658.91 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105106E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384966E+09 20676.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 35728882.43 4637.44 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 5503445.08 4641.00 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 18210333.40 4638.27 02-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 414494.00 2536.08 14-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 66915.87 669.16 24-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 54965.93 641.27 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 1217707.82 4637.17 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 61196744.54     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 35728882.43 4641.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.454488E+09 5599.20 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.334766E+09 5600.64 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.395710E+09 5600.07 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 48925176.49 5600.14 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 23840422.70 5599.31 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 3937479.37 5599.29 01-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 58185533.19 5601.28 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.138834E+09 5601.45 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 28762624.43 5601.44 08-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 9106506.16 5599.34 10-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 0.213118E+09 5600.05 10-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.363809E+09 5599.38 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.207348E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3937479.37 5599.20   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454488E+09 5601.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.565384E+09 18306.19 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.241369E+09 18310.35 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.354628E+09 18305.07 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 13341808.05 18306.58 04-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 4193921.75 18300.36 15-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 91890926.29 18312.21 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.259181E+09 18312.71 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 56551807.99 18305.36 01-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 1818819.32 18292.53 30-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 38854487.84 18304.28 16-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.253273E+09 18298.81 12-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188049E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.565384E+09 18312.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_2 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122234E+09 12010.35 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 21809156.69 5580.46 09-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.254011E+09 11753.04 30-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 13539.57 4.60 26-APR-10:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 11397.42 3.76 19-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 12775.30 4.28 13-AUG-15:03 0.00 0.00 0.00 0.00 0.00
September 50251.78 4.83 21-SEP-14:20 0.00 0.00 0.00 0.00 0.00
October 131459.49 5.64 03-OCT-14:00 0.00 0.00 0.00 0.00 0.00
November 543492.96 1520.12 24-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 47046717.29 8431.64 13-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.445864E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.254011E+09 12010.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116169E+09 5893.83 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.141569E+09 5895.28 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.268684E+09 5894.70 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 29000619.89 5894.78 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 42745348.58 5893.93 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 12228622.37 5894.45 08-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 0.106419E+09 5896.08 20-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 0.101254E+09 5896.10 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 11959996.24 5893.54 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 2007604.30 5888.99 12-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 18475687.40 5894.68 10-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 79828787.35 5894.00 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.930342E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2007604.30 5888.99   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.268684E+09 5896.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56244038.40 20345.38 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 73974978.00 20358.85 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.188738E+09 20353.28 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 8246008.03 20352.40 20-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 16569641.01 20354.79 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 1760422.51 5853.20 22-JUN-07:02 0.00 0.00 0.00 0.00 0.00
July 0.370996E+09 20361.25 20-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 0.242754E+09 20361.33 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 21699072.19 20353.60 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 467062.16 7784.37 03-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 12165263.95 20344.35 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.993614E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.370996E+09 20361.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44628024.71 4631.58 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 5575281.99 4635.12 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 17758095.84 4632.40 02-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 407662.10 2470.02 14-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 57458.53 574.59 24-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 77963.60 909.58 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 1447600.87 4631.31 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 69952087.64     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 44628024.71 4635.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.462399E+09 5617.36 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.337686E+09 5618.79 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.396268E+09 5618.22 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 49450781.49 5618.29 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 23848470.90 5617.46 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 3888167.13 5617.44 01-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 58834522.67 5619.43 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.141225E+09 5619.60 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 29173050.78 5619.59 08-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 9131859.34 5617.49 10-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 0.214834E+09 5618.20 10-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.369554E+09 5617.53 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.209629E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3888167.13 5617.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.462399E+09 5619.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.585773E+09 18377.11 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.248803E+09 18381.27 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.362120E+09 18375.98 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 13358109.73 18377.50 04-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 4318576.68 18371.26 15-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 95010877.98 18383.13 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.269456E+09 18383.63 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 58427394.60 18376.27 01-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 1859868.67 18363.41 30-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 38215617.79 18375.19 16-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.267735E+09 18369.71 12-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.194508E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.585773E+09 18383.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_3 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116666E+09 10854.41 12-JAN-08:03 0.00 0.00 0.00 0.00 0.00
February 22934956.25 5181.83 27-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.245939E+09 10685.62 30-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 35569.61 4.37 26-APR-10:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 71838.30 3.71 14-JUN-14:10 0.00 0.00 0.00 0.00 0.00
July 181411.72 3.86 18-JUL-11:40 0.00 0.00 0.00 0.00 0.00
August 275312.67 3.87 15-AUG-16:00 0.00 0.00 0.00 0.00 0.00
September 126332.37 5.07 28-SEP-14:05 0.00 0.00 0.00 0.00 0.00
October 154893.86 4.91 03-OCT-10:33 0.00 0.00 0.00 0.00 0.00
November 712787.09 1663.57 24-NOV-08:03 0.00 0.00 0.00 0.00 0.00
December 47321233.37 7643.23 13-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.434419E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.245939E+09 10854.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 91822989.28 5785.48 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.112019E+09 5786.95 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.221460E+09 5786.36 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 18533292.68 5786.43 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 27983916.22 5785.59 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 6889798.29 5785.57 01-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 74941852.77 5787.61 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 68506834.91 5787.80 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 8583187.62 5785.18 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 1518262.06 5780.67 12-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 11181910.66 5784.82 16-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 58791546.09 5785.66 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.702232E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1518262.06 5780.67   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221460E+09 5787.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 37812782.88 20006.88 02-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 33649125.27 20021.55 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 94898185.36 20015.94 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 2426458.55 14719.23 19-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 4940146.02 20011.00 15-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.181539E+09 20023.54 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.102465E+09 20024.08 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 10026814.60 20016.22 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 3657074.08 20007.04 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.471414E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181539E+09 20024.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 29780988.22 4572.35 12-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 1126115.60 4573.01 28-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 7629706.90 4573.18 02-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 822933.65 4572.09 14-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 39359744.37     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 29780988.22 4573.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.432590E+09 5559.81 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.306303E+09 5561.28 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.352497E+09 5560.68 24-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 35926814.90 5560.75 12-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 16972312.84 5559.91 19-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 2349594.56 5559.90 01-JUN-07:01 0.00 0.00 0.00 0.00 0.00
July 39498035.91 5561.93 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.103714E+09 5562.11 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 23159603.58 5562.10 08-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 7805651.51 5559.95 10-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 0.191710E+09 5560.66 10-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.345204E+09 5559.99 08-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.185773E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2349594.56 5559.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.432590E+09 5562.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.378413E+09 12190.33 31-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.148117E+09 12193.19 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.211612E+09 12189.56 17-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 7768723.82 12190.59 04-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 1375599.05 10413.85 15-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 36181136.46 12194.48 27-JUL-07:01 0.00 0.00 0.00 0.00 0.00
August 0.130392E+09 12194.83 25-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 33933948.01 12189.74 01-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 1373716.60 12181.04 30-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 27955183.23 12189.03 16-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.173355E+09 12185.31 12-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.115048E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.378413E+09 12194.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_OTHER HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 83370169.55 6014.13 02-JAN-21:00 0.00 0.00 0.00 0.00 0.00
February 2405610.28 1960.39 27-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 82501196.29 5470.14 30-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 15096.44 5.13 26-APR-11:10 0.00 0.00 0.00 0.00 0.00
May 2613.57 4.36 02-MAY-10:30 0.00 0.00 0.00 0.00 0.00
June 159756.44 5.00 26-JUN-10:00 0.00 0.00 0.00 0.00 0.00
July 86814.09 4.56 24-JUL-15:05 0.00 0.00 0.00 0.00 0.00
August 64583.50 4.73 14-AUG-12:20 0.00 0.00 0.00 0.00 0.00
September 163458.96 5.32 28-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 103210.18 5.39 10-OCT-12:50 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 34992121.92 3399.06 13-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.203865E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 83370169.55 6014.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 40400418.44 6802.29 02-JAN-08:02 0.00 0.00 0.00 0.00 0.00
February 10174803.33 6805.52 13-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 18495603.75 6803.38 13-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 990322.61 6802.59 03-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 2472794.87 6805.06 14-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 6723077.77 6805.18 24-AUG-07:02 0.00 0.00 0.00 0.00 0.00
September 852377.32 6803.62 01-SEP-07:01 0.00 0.00 0.00 0.00 0.00
October 421999.71 7033.33 30-OCT-07:01 0.00 0.00 0.00 0.00 0.00
November 3982065.89 7041.48 20-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 12465989.31 6801.61 12-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 96979453.02     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 40400418.44 7041.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 113558.81 1892.65 03-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 113558.81     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 113558.81 1892.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.118839E+10 5680.19 26-JAN-08:12 0.00 0.00 0.00 0.00 0.00
February 0.127753E+10 5681.15 13-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 0.205393E+10 5685.23 24-MAR-07:12 0.00 0.00 0.00 0.00 0.00
April 0.806105E+09 5892.25 27-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 0.787953E+09 5910.68 01-MAY-07:03 0.00 0.00 0.00 0.00 0.00
June 0.501473E+09 5922.93 05-JUN-07:03 0.00 0.00 0.00 0.00 0.00
July 0.306391E+09 5887.34 24-JUL-07:02 0.00 0.00 0.00 0.00 0.00
August 0.291668E+09 5887.81 07-AUG-07:03 0.00 0.00 0.00 0.00 0.00
September 0.324045E+09 5909.27 27-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.311678E+09 5890.82 10-OCT-07:02 0.00 0.00 0.00 0.00 0.00
November 0.859566E+09 5890.93 20-NOV-08:02 0.00 0.00 0.00 0.00 0.00
December 0.974860E+09 5679.87 08-DEC-15:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.968359E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.291668E+09 5679.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205393E+10 5922.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 3127373.49 11705.21 02-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3127373.49     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3127373.49 11705.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:5 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:6 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:7 HEATING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.181296E+10 32486.68 11-JAN-08:03 0.00 0.00 0.00 0.00 0.00
February 0.112708E+10 25138.06 10-FEB-08:04 0.00 0.00 0.00 0.00 0.00
March 0.191947E+10 34161.00 30-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.403144E+09 16562.19 19-APR-07:07 0.00 0.00 0.00 0.00 0.00
May 0.212900E+09 14119.15 12-MAY-07:08 0.00 0.00 0.00 0.00 0.00
June 7547422.03 8323.16 12-JUN-07:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 772281.86 1001.95 21-AUG-20:00 0.00 0.00 0.00 0.00 0.00
September 21405830.47 7896.84 20-SEP-07:09 0.00 0.00 0.00 0.00 0.00
October 11788636.33 10095.22 25-OCT-07:09 0.00 0.00 0.00 0.00 0.00
November 0.678705E+09 19770.57 24-NOV-08:05 0.00 0.00 0.00 0.00 0.00
December 0.133485E+10 31179.34 22-DEC-08:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.753064E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.191947E+10 34161.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_1 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.122356E+11 0.118269E+11 59030.70 18-JAN-13:00 59030.70 0.00
February 0.00 0.00 0.725582E+10 0.649411E+10 53847.63 01-FEB-12:00 53847.63 0.00
March 0.00 0.00 0.786014E+10 0.673217E+10 49764.41 11-MAR-13:41 49764.41 0.00
April 0.00 0.00 0.161433E+11 0.147224E+11 62528.36 30-APR-12:10 62528.36 0.00
May 0.00 0.00 0.181190E+11 0.166402E+11 48699.22 03-MAY-13:00 48699.22 0.00
June 0.00 0.00 0.286364E+11 0.242752E+11 53252.10 28-JUN-09:40 31806.96 0.00
July 0.00 0.00 0.369310E+11 0.283703E+11 69989.20 30-JUL-13:07 42273.89 0.00
August 0.00 0.00 0.435362E+11 0.324837E+11 76669.72 06-AUG-14:07 47071.54 0.00
September 0.00 0.00 0.351125E+11 0.270603E+11 105206.62 29-SEP-13:00 105206.62 0.00
October 0.00 0.00 0.458257E+11 0.378514E+11 110628.18 16-OCT-11:20 110628.18 0.00
November 0.00 0.00 0.141593E+11 0.132121E+11 59012.91 28-NOV-14:00 59012.91 0.00
December 0.00 0.00 0.150300E+11 0.148363E+11 64519.25 19-DEC-13:00 64519.25 0.00
                 
Annual Sum or Average 0.00 0.00 0.280845E+12 0.234505E+12       0.00
Minimum of Months 0.00 0.00 0.725582E+10 0.649411E+10 48699.22   31806.96 0.00
Maximum of Months 0.00 0.00 0.458257E+11 0.378514E+11 110628.18   110628.18 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_2 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.120767E+11 0.116738E+11 58308.44 18-JAN-13:00 58308.44 0.00
February 0.00 0.00 0.719056E+10 0.643195E+10 53343.63 01-FEB-12:00 53343.63 0.00
March 0.00 0.00 0.777838E+10 0.667114E+10 46111.27 23-MAR-15:00 39613.39 0.00
April 0.00 0.00 0.160373E+11 0.146409E+11 59523.56 26-APR-13:00 59523.56 0.00
May 0.00 0.00 0.181240E+11 0.166644E+11 48912.14 03-MAY-13:00 48912.14 0.00
June 0.00 0.00 0.285215E+11 0.242254E+11 53325.64 28-JUN-09:40 31849.57 0.00
July 0.00 0.00 0.367358E+11 0.282337E+11 68909.23 30-JUL-13:19 42414.42 0.00
August 0.00 0.00 0.434180E+11 0.324174E+11 75913.82 06-AUG-14:21 46803.21 0.00
September 0.00 0.00 0.347963E+11 0.268601E+11 104344.30 29-SEP-13:00 104344.30 0.00
October 0.00 0.00 0.455011E+11 0.375995E+11 109628.53 16-OCT-11:30 109628.53 0.00
November 0.00 0.00 0.139524E+11 0.130156E+11 69411.46 19-NOV-13:09 69411.46 0.00
December 0.00 0.00 0.146781E+11 0.144848E+11 63540.87 19-DEC-13:00 63540.87 0.00
                 
Annual Sum or Average 0.00 0.00 0.278810E+12 0.232919E+12       0.00
Minimum of Months 0.00 0.00 0.719056E+10 0.643195E+10 46111.27   31849.57 0.00
Maximum of Months 0.00 0.00 0.455011E+11 0.375995E+11 109628.53   109628.53 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_POD_3 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.110589E+11 0.106637E+11 54645.86 18-JAN-13:00 54645.86 0.00
February 0.00 0.00 0.653818E+10 0.585350E+10 49378.95 01-FEB-12:00 49378.95 0.00
March 0.00 0.00 0.705683E+10 0.600822E+10 44697.76 23-MAR-14:50 38053.10 0.00
April 0.00 0.00 0.144504E+11 0.131345E+11 57949.12 30-APR-11:46 57949.12 0.00
May 0.00 0.00 0.160172E+11 0.146263E+11 45180.29 03-MAY-13:00 45180.29 0.00
June 0.00 0.00 0.252712E+11 0.211265E+11 50191.43 28-JUN-13:00 32479.12 0.00
July 0.00 0.00 0.323000E+11 0.245894E+11 58947.69 30-JUL-13:11 36352.72 0.00
August 0.00 0.00 0.382874E+11 0.282448E+11 66020.05 06-AUG-14:08 40537.90 0.00
September 0.00 0.00 0.314141E+11 0.239338E+11 95279.44 29-SEP-13:00 95279.44 0.00
October 0.00 0.00 0.412825E+11 0.340028E+11 99139.47 16-OCT-11:30 99139.47 0.00
November 0.00 0.00 0.128507E+11 0.119781E+11 54294.24 28-NOV-14:00 54294.24 0.00
December 0.00 0.00 0.134632E+11 0.132868E+11 59314.29 19-DEC-13:00 59314.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.249991E+12 0.207448E+12       0.00
Minimum of Months 0.00 0.00 0.653818E+10 0.585350E+10 44697.76   32479.12 0.00
Maximum of Months 0.00 0.00 0.412825E+11 0.340028E+11 99139.47   99139.47 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_OTHER COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.800451E+10 0.750387E+10 48551.03 18-JAN-13:10 48551.03 0.00
February 0.00 0.00 0.472713E+10 0.418219E+10 45511.16 01-FEB-12:00 45511.16 0.00
March 0.00 0.00 0.583197E+10 0.491606E+10 41084.51 23-MAR-14:00 41084.51 0.00
April 0.00 0.00 0.149481E+11 0.137912E+11 69431.97 26-APR-14:10 60460.28 0.00
May 0.00 0.00 0.173806E+11 0.160547E+11 55071.86 03-MAY-13:00 55071.86 0.00
June 0.00 0.00 0.299045E+11 0.250826E+11 71491.42 29-JUN-13:00 47919.49 0.00
July 0.00 0.00 0.344824E+11 0.249603E+11 104121.33 23-JUL-09:21 60533.14 0.00
August 0.00 0.00 0.387145E+11 0.272514E+11 96393.98 06-AUG-12:51 55607.18 0.00
September 0.00 0.00 0.326594E+11 0.252017E+11 90950.09 29-SEP-13:00 90950.09 0.00
October 0.00 0.00 0.404619E+11 0.332405E+11 103010.75 05-OCT-07:03 44330.54 0.00
November 0.00 0.00 0.954285E+10 0.876301E+10 52864.63 19-NOV-11:38 52864.63 0.00
December 0.00 0.00 0.959344E+10 0.943756E+10 49041.04 19-DEC-13:10 49041.04 0.00
                 
Annual Sum or Average 0.00 0.00 0.246251E+12 0.200385E+12       0.00
Minimum of Months 0.00 0.00 0.472713E+10 0.418219E+10 41084.51   41084.51 0.00
Maximum of Months 0.00 0.00 0.404619E+11 0.332405E+11 104121.33   90950.09 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:5 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.150681E+10 0.125574E+10 26275.07 18-JAN-06:02 18918.49 0.00
February 0.00 0.00 0.670978E+09 0.576602E+09 26275.07 02-FEB-06:01 15931.14 0.00
March 0.00 0.00 0.127784E+10 0.900633E+09 28186.11 12-MAR-12:32 18768.45 0.00
April 0.00 0.00 0.497337E+10 0.356958E+10 28661.46 08-APR-11:45 20955.17 0.00
May 0.00 0.00 0.571194E+10 0.420048E+10 28068.02 28-MAY-14:02 20353.70 0.00
June 0.00 0.00 0.102040E+11 0.684404E+10 29010.36 18-JUN-13:12 19979.40 0.00
July 0.00 0.00 0.110901E+11 0.714491E+10 30280.34 23-JUL-10:56 20078.39 0.00
August 0.00 0.00 0.119696E+11 0.755411E+10 30279.26 06-AUG-12:53 20074.39 0.00
September 0.00 0.00 0.949028E+10 0.618615E+10 29671.44 09-SEP-10:47 23094.10 0.00
October 0.00 0.00 0.980511E+10 0.731740E+10 30566.96 01-OCT-12:02 18865.07 0.00
November 0.00 0.00 0.160483E+10 0.132036E+10 26275.07 21-NOV-06:01 14682.48 0.00
December 0.00 0.00 0.179426E+10 0.174669E+10 26275.07 06-DEC-06:01 25270.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.700990E+11 0.486167E+11       0.00
Minimum of Months 0.00 0.00 0.670978E+09 0.576602E+09 26275.07   14682.48 0.00
Maximum of Months 0.00 0.00 0.119696E+11 0.755411E+10 30566.96   25270.94 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:6 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.750376E+10 0.610846E+10 27451.47 16-JAN-19:23 16754.87 0.00
February 0.00 0.00 0.597050E+10 0.446347E+10 28389.96 01-FEB-11:50 23068.90 0.00
March 0.00 0.00 0.747902E+10 0.512260E+10 28166.10 12-MAR-12:43 18658.48 0.00
April 0.00 0.00 0.110729E+11 0.796818E+10 29345.12 26-APR-11:05 21030.99 0.00
May 0.00 0.00 0.120131E+11 0.876704E+10 27988.92 29-MAY-09:58 19856.34 0.00
June 0.00 0.00 0.157369E+11 0.105617E+11 29666.31 28-JUN-10:50 18764.00 0.00
July 0.00 0.00 0.183120E+11 0.114163E+11 30204.27 23-JUL-10:52 20114.04 0.00
August 0.00 0.00 0.201154E+11 0.121955E+11 30203.15 06-AUG-12:51 20110.05 0.00
September 0.00 0.00 0.160396E+11 0.102685E+11 30738.41 22-SEP-11:40 16420.86 0.00
October 0.00 0.00 0.177655E+11 0.129740E+11 30500.99 01-OCT-11:52 18539.95 0.00
November 0.00 0.00 0.821740E+10 0.652430E+10 27925.74 19-NOV-14:42 21001.17 0.00
December 0.00 0.00 0.734381E+10 0.642044E+10 26747.87 16-DEC-12:53 26747.87 0.00
                 
Annual Sum or Average 0.00 0.00 0.147570E+12 0.102790E+12       0.00
Minimum of Months 0.00 0.00 0.597050E+10 0.446347E+10 26747.87   16420.86 0.00
Maximum of Months 0.00 0.00 0.201154E+11 0.129740E+11 30738.41   26747.87 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:7 COOLING COIL

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.545113E+10 0.454044E+10 27425.83 17-JAN-14:00 21345.40 0.00
February 0.00 0.00 0.396796E+10 0.306547E+10 25567.17 01-FEB-12:00 25567.17 0.00
March 0.00 0.00 0.493179E+10 0.339382E+10 30410.18 23-MAR-14:00 21514.94 0.00
April 0.00 0.00 0.938964E+10 0.675657E+10 48194.46 30-APR-12:01 40506.79 0.00
May 0.00 0.00 0.105861E+11 0.783172E+10 46135.84 03-MAY-05:01 20648.35 0.00
June 0.00 0.00 0.163429E+11 0.110257E+11 49402.23 18-JUN-13:51 32813.33 0.00
July 0.00 0.00 0.884876E+10 0.553496E+10 51546.83 23-JUL-11:01 32537.48 0.00
August 0.00 0.00 0.966380E+10 0.591779E+10 51563.56 06-AUG-12:51 32847.01 0.00
September 0.00 0.00 0.156277E+11 0.102539E+11 52459.79 22-SEP-12:00 29284.85 0.00
October 0.00 0.00 0.166549E+11 0.128226E+11 51926.55 01-OCT-12:18 30947.64 0.00
November 0.00 0.00 0.623288E+10 0.502196E+10 26682.51 10-NOV-13:00 17346.13 0.00
December 0.00 0.00 0.540068E+10 0.497842E+10 26301.85 19-DEC-13:00 26301.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.113098E+12 0.811434E+11       0.00
Minimum of Months 0.00 0.00 0.396796E+10 0.306547E+10 25567.17   17346.13 0.00
Maximum of Months 0.00 0.00 0.166549E+11 0.128226E+11 52459.79   40506.79 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 1883.00 323153.82 03-JAN-08:61
February 0.00 0.00 01-FEB-00:03 1465.21 286659.73 27-FEB-08:61
March 0.00 0.00 01-MAR-00:05 2330.19 312068.49 30-MAR-07:01
April 0.00 0.00 01-APR-00:10 415.65 197250.13 18-APR-07:01
May 0.00 0.00 01-MAY-00:03 376.37 215152.72 15-MAY-07:01
June 0.00 0.00 01-JUN-00:03 210.32 63121.59 01-JUN-07:01
July 0.00 0.00 01-JUL-00:03 703.26 234381.06 14-JUL-07:02
August 0.00 0.00 01-AUG-00:03 813.35 229055.72 24-AUG-07:02
September 0.00 0.00 01-SEP-00:03 250.89 233527.78 01-SEP-07:01
October 0.00 0.00 01-OCT-00:03 128.65 102504.59 30-OCT-07:01
November 0.00 0.00 01-NOV-00:03 623.23 144326.78 24-NOV-08:61
December 0.00 0.00 01-DEC-00:05 1175.36 287619.73 13-DEC-08:61
             
Annual Sum or Average 0.00     865.05    
Minimum of Months 0.00 0.00   128.65 63121.59  
Maximum of Months 0.00 0.00   2330.19 323153.82  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 3153.14 15683.88 31-JAN-13:30
February 0.00 0.00 01-FEB-00:03 3162.33 15684.23 03-FEB-13:30
March 0.00 0.00 01-MAR-00:05 3420.44 15605.23 01-MAR-14:00
April 0.00 0.00 01-APR-00:10 3013.05 15323.60 03-APR-12:20
May 0.00 0.00 01-MAY-00:03 3132.20 14987.29 01-MAY-13:00
June 0.00 0.00 01-JUN-00:03 2040.16 14605.95 01-JUN-13:00
July 0.00 0.00 01-JUL-00:03 789.49 4823.98 20-JUL-18:13
August 0.00 0.00 01-AUG-00:03 906.96 4837.66 28-AUG-18:20
September 0.00 0.00 01-SEP-00:03 1848.18 14526.82 29-SEP-12:40
October 0.00 0.00 01-OCT-00:03 2972.66 14903.58 31-OCT-13:00
November 0.00 0.00 01-NOV-00:03 3146.98 15275.51 30-NOV-13:50
December 0.00 0.00 01-DEC-00:05 2963.34 15547.30 29-DEC-14:00
             
Annual Sum or Average 0.00     2541.05    
Minimum of Months 0.00 0.00   789.49 4823.98  
Maximum of Months 0.00 0.00   3420.44 15684.23  



Table of Contents

Report: FanReportMonthly

For: VAV_POD_1 FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.547350E+10 0.44 7634.62 18-JAN-15:10 1.40
February 0.473242E+10 0.43 7581.64 21-FEB-15:03 1.39
March 0.546963E+10 0.45 7116.46 11-MAR-13:41 1.35
April 0.490705E+10 0.42 7218.62 26-APR-14:00 1.35
May 0.523297E+10 0.43 6493.94 03-MAY-14:10 1.27
June 0.521617E+10 0.45 6277.55 05-JUN-14:05 1.24
July 0.472876E+10 0.39 5056.99 23-JUL-15:48 1.08
August 0.542174E+10 0.45 5160.46 06-AUG-14:06 1.10
September 0.536032E+10 0.45 9763.35 25-SEP-14:40 1.63
October 0.652004E+10 0.50 9728.10 03-OCT-14:30 1.63
November 0.568264E+10 0.47 7587.39 27-NOV-15:20 1.41
December 0.547322E+10 0.44 7701.11 18-DEC-15:30 1.42
           
Annual Sum or Average 0.642185E+11 0.44      
Minimum of Months 0.472876E+10 0.39 5056.99   1.08
Maximum of Months 0.652004E+10 0.50 9763.35   1.63



Table of Contents

Report: FanReportMonthly

For: VAV_POD_2 FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.542700E+10 0.44 7634.80 18-JAN-15:00 1.41
February 0.473423E+10 0.43 7558.56 21-FEB-14:50 1.40
March 0.548548E+10 0.46 6683.77 23-MAR-14:20 1.29
April 0.491855E+10 0.42 7219.01 26-APR-14:30 1.35
May 0.526860E+10 0.44 6558.77 03-MAY-14:10 1.28
June 0.523618E+10 0.45 6429.99 05-JUN-15:00 1.26
July 0.474377E+10 0.40 4977.17 23-JUL-14:29 1.08
August 0.545548E+10 0.45 5192.07 19-AUG-15:50 1.10
September 0.535193E+10 0.45 9764.96 25-SEP-14:30 1.63
October 0.651358E+10 0.50 9757.61 03-OCT-14:30 1.63
November 0.564273E+10 0.47 7713.94 19-NOV-13:09 1.42
December 0.540935E+10 0.43 7732.37 19-DEC-15:40 1.43
           
Annual Sum or Average 0.641869E+11 0.44      
Minimum of Months 0.473423E+10 0.40 4977.17   1.08
Maximum of Months 0.651358E+10 0.50 9764.96   1.63



Table of Contents

Report: FanReportMonthly

For: VAV_POD_3 FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.477687E+10 0.44 6943.44 18-JAN-15:30 1.42
February 0.409220E+10 0.42 6943.50 21-FEB-15:40 1.42
March 0.465430E+10 0.44 6627.00 23-MAR-14:20 1.38
April 0.427648E+10 0.41 7292.78 26-APR-14:10 1.46
May 0.448710E+10 0.42 6412.39 03-MAY-14:20 1.35
June 0.441135E+10 0.44 6158.24 05-JUN-14:05 1.32
July 0.393402E+10 0.38 4054.21 30-JUL-13:10 1.02
August 0.451756E+10 0.44 4390.53 06-AUG-14:07 1.07
September 0.463030E+10 0.44 8708.25 25-SEP-15:00 1.64
October 0.573758E+10 0.50 8429.03 03-OCT-14:50 1.60
November 0.500027E+10 0.47 6947.56 06-NOV-15:13 1.43
December 0.475206E+10 0.43 7026.03 18-DEC-15:50 1.45
           
Annual Sum or Average 0.552701E+11 0.44      
Minimum of Months 0.393402E+10 0.38 4054.21   1.02
Maximum of Months 0.573758E+10 0.50 8708.25   1.64



Table of Contents

Report: FanReportMonthly

For: VAV_OTHER FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.203725E+10 0.25 4679.45 18-JAN-14:30 1.00
February 0.182715E+10 0.25 4307.68 03-FEB-14:00 0.96
March 0.222041E+10 0.27 5079.98 23-MAR-14:00 1.04
April 0.318163E+10 0.31 8091.09 26-APR-12:40 1.39
May 0.358432E+10 0.34 7409.91 04-MAY-12:10 1.32
June 0.409924E+10 0.38 6922.33 05-JUN-07:02 1.26
July 0.247162E+10 0.28 5125.37 31-JUL-13:00 1.05
August 0.267172E+10 0.30 5558.75 19-AUG-09:37 1.10
September 0.377441E+10 0.35 7687.21 28-SEP-13:00 1.34
October 0.426275E+10 0.38 7876.30 18-OCT-14:00 1.36
November 0.243472E+10 0.28 4701.29 29-NOV-13:10 1.01
December 0.206205E+10 0.24 4803.10 05-DEC-13:40 1.02
           
Annual Sum or Average 0.346273E+11 0.30      
Minimum of Months 0.182715E+10 0.24 4307.68   0.96
Maximum of Months 0.426275E+10 0.38 8091.09   1.39



Table of Contents

Report: FanReportMonthly

For: BATH_ZN_1_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 98748698.34 0.11 91.94 02-JAN-07:01 0.27
February 88337528.97 0.11 91.94 01-FEB-07:01 0.27
March 0.107281E+09 0.12 91.94 01-MAR-07:01 0.27
April 96860952.34 0.11 91.94 03-APR-06:01 0.27
May 0.107117E+09 0.12 91.94 01-MAY-06:01 0.27
June 0.112073E+09 0.13 91.94 01-JUN-06:01 0.27
July 0.106294E+09 0.12 91.94 01-JUL-08:20 0.27
August 0.115222E+09 0.13 91.94 01-AUG-06:01 0.27
September 0.104538E+09 0.12 91.94 01-SEP-06:01 0.27
October 0.111374E+09 0.12 91.94 01-OCT-00:32 0.27
November 99179448.88 0.11 91.94 01-NOV-06:01 0.27
December 94152595.69 0.10 91.94 01-DEC-07:01 0.27
           
Annual Sum or Average 0.124118E+10 0.12      
Minimum of Months 88337528.97 0.10 91.94   0.27
Maximum of Months 0.115222E+09 0.13 91.94   0.27



Table of Contents

Report: FanReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:03 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: GYM_ZN_1_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:03 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:03 0.00
July 0.00 -0.0 0.00 01-JUL-00:03 0.00
August 0.00 -0.0 0.00 01-AUG-00:03 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 -0.0 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.129588E+10 0.19 689.53 01-JAN-00:10 0.27
February 0.117153E+10 0.19 689.53 01-FEB-00:13 0.27
March 0.128890E+10 0.19 689.53 01-MAR-00:15 0.27
April 0.126041E+10 0.19 689.53 01-APR-00:10 0.27
May 0.129708E+10 0.19 689.53 01-MAY-00:12 0.27
June 0.125331E+10 0.19 689.53 01-JUN-00:13 0.27
July 0.150445E+10 0.22 689.53 01-JUL-00:13 0.27
August 0.152217E+10 0.22 689.53 01-AUG-00:13 0.27
September 0.145951E+10 0.22 689.53 01-SEP-00:13 0.27
October 0.151056E+10 0.22 689.53 01-OCT-00:12 0.27
November 0.146236E+10 0.22 689.53 01-NOV-00:13 0.27
December 0.149978E+10 0.22 689.53 01-DEC-00:05 0.27
           
Annual Sum or Average 0.165260E+11 0.20      
Minimum of Months 0.117153E+10 0.19 689.53   0.27
Maximum of Months 0.152217E+10 0.22 689.53   0.27



Table of Contents

Report: FanReportMonthly

For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:03 0.00
July 0.00 -0.0 0.00 01-JUL-00:03 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00
September 0.00 -0.0 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_2:5_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.660101E+09 0.22 1482.06 17-JAN-06:01 0.90
February 0.596789E+09 0.22 1097.67 16-FEB-07:01 0.78
March 0.724512E+09 0.24 1557.76 13-MAR-05:01 0.92
April 0.644979E+09 0.23 1557.76 04-APR-06:01 0.92
May 0.710581E+09 0.25 1557.76 01-MAY-05:01 0.92
June 0.762426E+09 0.27 1557.76 01-JUN-05:01 0.92
July 0.735568E+09 0.26 1557.76 03-JUL-05:01 0.92
August 0.816184E+09 0.28 1557.76 01-AUG-05:01 0.92
September 0.686714E+09 0.24 1557.76 01-SEP-05:01 0.92
October 0.723462E+09 0.24 1557.76 02-OCT-05:01 0.91
November 0.660612E+09 0.23 1557.76 21-NOV-06:01 0.92
December 0.628339E+09 0.21 1188.15 08-DEC-06:01 0.81
           
Annual Sum or Average 0.835026E+10 0.24      
Minimum of Months 0.596789E+09 0.21 1097.67   0.78
Maximum of Months 0.816184E+09 0.28 1557.76   0.92



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.843198E+09 0.45 1505.58 02-JAN-06:01 0.92
February 0.754210E+09 0.45 1505.58 01-FEB-06:11 0.92
March 0.900824E+09 0.46 1505.58 01-MAR-06:11 0.92
April 0.933549E+09 0.46 1505.58 03-APR-05:11 0.92
May 0.999955E+09 0.47 1505.58 01-MAY-05:01 0.92
June 0.107348E+10 0.47 1505.58 01-JUN-05:01 0.92
July 0.109023E+10 0.46 1505.58 01-JUL-10:52 0.91
August 0.118932E+10 0.48 1505.58 01-AUG-03:32 0.92
September 0.106718E+10 0.47 1505.58 01-SEP-03:32 0.92
October 0.115865E+10 0.48 1505.58 01-OCT-04:52 0.91
November 0.857782E+09 0.46 1505.58 01-NOV-05:02 0.92
December 0.816020E+09 0.45 1505.58 01-DEC-06:01 0.92
           
Annual Sum or Average 0.116844E+11 0.46      
Minimum of Months 0.754210E+09 0.45 1505.58   0.91
Maximum of Months 0.118932E+10 0.48 1505.58   0.92



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103227E+10 0.22 1514.40 11-JAN-08:03 0.72
February 0.921516E+09 0.22 1384.73 10-FEB-08:04 0.68
March 0.113166E+10 0.24 1543.94 30-MAR-07:03 0.73
April 0.991024E+09 0.21 1737.79 26-APR-11:00 0.77
May 0.108096E+10 0.23 1477.30 03-MAY-08:07 0.70
June 0.120946E+10 0.26 2352.96 06-JUN-05:01 0.89
July 0.974818E+09 0.22 2352.96 03-JUL-05:01 0.88
August 0.110808E+10 0.24 2352.96 01-AUG-05:01 0.88
September 0.113151E+10 0.24 2352.96 05-SEP-05:01 0.88
October 0.118380E+10 0.24 2352.96 02-OCT-05:01 0.88
November 0.100905E+10 0.22 1290.03 24-NOV-08:05 0.66
December 0.974011E+09 0.21 1491.33 22-DEC-08:04 0.71
           
Annual Sum or Average 0.127482E+11 0.23      
Minimum of Months 0.921516E+09 0.21 1290.03   0.66
Maximum of Months 0.120946E+10 0.26 2352.96   0.89



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 23544380.71 21189942.64 608.87 03-JAN-08:61 547.99 547.99 39.77 1.83
February 17390865.75 15651779.17 585.41 27-FEB-08:61 526.87 526.87 39.60 1.62
March 30046488.07 27041839.27 597.77 30-MAR-07:01 537.99 537.99 39.10 1.74
April 6485219.28 5836697.35 554.41 19-APR-07:01 498.97 498.97 45.63 1.27
May 6216377.72 5594739.95 558.80 15-MAY-07:01 502.92 502.92 42.90 1.32
June 3710280.72 3339252.65 339.34 01-JUN-07:01 305.41 305.41 49.14 0.46
July 8180848.96 7362764.06 569.88 14-JUL-07:02 512.90 512.90 43.00 1.44
August 9173800.82 8256420.74 567.97 24-AUG-07:02 511.18 511.18 43.30 1.42
September 3496969.03 3147272.13 568.06 01-SEP-07:01 511.25 511.25 42.58 1.42
October 2387464.43 2148717.98 445.81 30-OCT-07:01 401.23 401.23 47.68 0.71
November 9100394.09 8190354.68 490.93 24-NOV-08:61 441.84 441.84 42.62 0.88
December 15260413.90 13734372.51 590.45 13-DEC-08:61 531.40 531.40 40.78 1.67
                 
Annual Sum or Average 0.134994E+09 0.121494E+09            
Minimum of Months 2387464.43 2148717.98 339.34   305.41 305.41 39.10 0.46
Maximum of Months 30046488.07 27041839.27 608.87   547.99 547.99 49.14 1.83



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12215899.87 3664769.96 13.47 02-JAN-08:61 4.04 4.04 54.22 0.11
February 11052480.83 3315744.25 13.47 01-FEB-08:62 4.04 4.04 46.16 0.11
March 13379318.90 4013795.67 13.47 01-MAR-08:61 4.04 4.04 47.36 0.11
April 11634190.35 3490257.10 13.47 03-APR-07:01 4.04 4.04 47.43 0.11
May 12797609.38 3839282.82 13.47 01-MAY-07:01 4.04 4.04 47.25 0.11
June 12797609.38 3839282.82 13.47 01-JUN-07:01 4.04 4.04 47.76 0.11
July 11634190.35 3490257.10 13.47 03-JUL-07:03 4.04 4.04 52.75 0.11
August 13379318.90 4013795.67 13.47 01-AUG-07:03 4.04 4.04 53.36 0.11
September 11634190.35 3490257.10 13.47 01-SEP-07:01 4.04 4.04 51.96 0.11
October 12215899.87 3664769.96 13.47 02-OCT-07:03 4.04 4.04 46.83 0.11
November 12215899.87 3664769.96 13.47 01-NOV-07:01 4.04 4.04 47.67 0.11
December 11634190.35 3490257.10 13.47 01-DEC-08:61 4.04 4.04 47.42 0.11
                 
Annual Sum or Average 0.146591E+09 43977239.52            
Minimum of Months 11052480.83 3315744.25 13.47   4.04 4.04 46.16 0.11
Maximum of Months 13379318.90 4013795.67 13.47   4.04 4.04 54.22 0.11



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 82.00 82.00 1883.00 323153.82 03-JAN-08:61
February 0.00 0.00 01-FEB-00:03 28.19 28.19 1465.21 286659.73 27-FEB-08:61
March 0.00 0.00 01-MAR-00:05 25.17 25.17 2330.19 312068.49 30-MAR-07:01
April 0.00 0.00 01-APR-00:10 24.73 24.73 415.65 197250.13 18-APR-07:01
May 0.00 0.00 01-MAY-00:03 48.85 48.85 376.37 215152.72 15-MAY-07:01
June 0.00 0.00 01-JUN-00:03 48.17 48.17 210.32 63121.59 01-JUN-07:01
July 0.00 0.00 01-JUL-00:03 48.72 48.72 703.26 234381.06 14-JUL-07:02
August 0.00 0.00 01-AUG-00:03 31.25 31.25 813.35 229055.72 24-AUG-07:02
September 0.00 0.00 01-SEP-00:03 23.45 23.45 250.89 233527.78 01-SEP-07:01
October 0.00 0.00 01-OCT-00:03 49.45 49.45 128.65 102504.59 30-OCT-07:01
November 0.00 0.00 01-NOV-00:03 47.81 47.81 623.23 144326.78 24-NOV-08:61
December 0.00 0.00 01-DEC-00:05 35.30 35.30 1175.36 287619.73 13-DEC-08:61
                 
Annual Sum or Average 0.00         865.05    
Minimum of Months 0.00 0.00   23.45 23.45 128.65 63121.59  
Maximum of Months 0.00 0.00   82.00 82.00 2330.19 323153.82  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 60.00 60.00 3153.14 15683.88 31-JAN-13:30
February 0.00 0.00 01-FEB-00:03 48.44 48.44 3162.33 15684.23 03-FEB-13:30
March 0.00 0.00 01-MAR-00:05 48.82 48.82 3420.44 15605.23 01-MAR-14:00
April 0.00 0.00 01-APR-00:10 48.84 48.84 3013.05 15323.60 03-APR-12:20
May 0.00 0.00 01-MAY-00:03 48.65 48.65 3132.20 14987.29 01-MAY-13:00
June 0.00 0.00 01-JUN-00:03 49.02 49.02 2040.16 14605.95 01-JUN-13:00
July 0.00 0.00 01-JUL-00:03 49.25 49.25 789.49 4823.98 20-JUL-18:13
August 0.00 0.00 01-AUG-00:03 49.42 49.42 906.96 4837.66 28-AUG-18:20
September 0.00 0.00 01-SEP-00:03 49.14 49.14 1848.18 14526.82 29-SEP-12:40
October 0.00 0.00 01-OCT-00:03 49.03 49.03 2972.66 14903.58 31-OCT-13:00
November 0.00 0.00 01-NOV-00:03 48.89 48.89 3146.98 15275.51 30-NOV-13:50
December 0.00 0.00 01-DEC-00:05 48.85 48.85 2963.34 15547.30 29-DEC-14:00
                 
Annual Sum or Average 0.00         2541.05    
Minimum of Months 0.00 0.00   48.44 48.44 789.49 4823.98  
Maximum of Months 0.00 0.00   60.00 60.00 3420.44 15684.23  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_POD_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.133301E+10 0.00 0.00 0.904709E+10 0.00 0.00
February 0.836594E+09 0.00 0.00 0.691334E+10 0.00 0.00
March 0.152392E+10 0.00 0.00 0.780219E+10 0.00 0.00
April 0.102150E+09 0.00 0.00 0.959313E+10 0.00 0.00
May 92399796.55 0.00 0.00 0.105692E+11 0.00 0.00
June 22031329.71 0.00 0.00 0.133215E+11 0.00 0.00
July 0.638242E+09 0.00 0.00 0.147688E+11 0.00 0.00
August 0.744041E+09 0.00 0.00 0.171957E+11 0.00 0.00
September 0.118724E+09 0.00 0.00 0.151301E+11 0.00 0.00
October 13228655.55 0.00 0.00 0.190767E+11 0.00 0.00
November 0.271693E+09 0.00 0.00 0.982750E+10 0.00 0.00
December 0.752833E+09 0.00 0.00 0.974234E+10 0.00 0.00
             
Annual Sum or Average 0.644887E+10 0.00 0.00 0.142987E+12 0.00 0.00
Minimum of Months 13228655.55 0.00 0.00 0.691334E+10 0.00 0.00
Maximum of Months 0.152392E+10 0.00 0.00 0.190767E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_POD_2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.138745E+10 0.00 0.00 0.895556E+10 0.00 0.00
February 0.829417E+09 0.00 0.00 0.689689E+10 0.00 0.00
March 0.148758E+10 0.00 0.00 0.779411E+10 0.00 0.00
April 0.100069E+09 0.00 0.00 0.957358E+10 0.00 0.00
May 87482037.18 0.00 0.00 0.106024E+11 0.00 0.00
June 17888609.44 0.00 0.00 0.133047E+11 0.00 0.00
July 0.631667E+09 0.00 0.00 0.147284E+11 0.00 0.00
August 0.754759E+09 0.00 0.00 0.171956E+11 0.00 0.00
September 0.121388E+09 0.00 0.00 0.150333E+11 0.00 0.00
October 13130791.79 0.00 0.00 0.189793E+11 0.00 0.00
November 0.272536E+09 0.00 0.00 0.972999E+10 0.00 0.00
December 0.777777E+09 0.00 0.00 0.958331E+10 0.00 0.00
             
Annual Sum or Average 0.648114E+10 0.00 0.00 0.142377E+12 0.00 0.00
Minimum of Months 13130791.79 0.00 0.00 0.689689E+10 0.00 0.00
Maximum of Months 0.148758E+10 0.00 0.00 0.189793E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_POD_3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.108709E+10 0.00 0.00 0.799964E+10 0.00 0.00
February 0.624150E+09 0.00 0.00 0.605032E+10 0.00 0.00
March 0.113403E+10 0.00 0.00 0.674063E+10 0.00 0.00
April 64690859.57 0.00 0.00 0.846018E+10 0.00 0.00
May 51271974.12 0.00 0.00 0.919502E+10 0.00 0.00
June 9311231.14 0.00 0.00 0.115623E+11 0.00 0.00
July 0.332341E+09 0.00 0.00 0.127216E+11 0.00 0.00
August 0.405354E+09 0.00 0.00 0.148744E+11 0.00 0.00
September 75829886.19 0.00 0.00 0.133637E+11 0.00 0.00
October 10852524.03 0.00 0.00 0.170417E+11 0.00 0.00
November 0.231560E+09 0.00 0.00 0.874648E+10 0.00 0.00
December 0.629152E+09 0.00 0.00 0.856777E+10 0.00 0.00
             
Annual Sum or Average 0.465563E+10 0.00 0.00 0.125324E+12 0.00 0.00
Minimum of Months 9311231.14 0.00 0.00 0.605032E+10 0.00 0.00
Maximum of Months 0.113403E+10 0.00 0.00 0.170417E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_OTHER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.131540E+10 0.00 0.00 0.441910E+10 0.00 0.00
February 0.129011E+10 0.00 0.00 0.327044E+10 0.00 0.00
March 0.215493E+10 0.00 0.00 0.396409E+10 0.00 0.00
April 0.807110E+09 0.00 0.00 0.750414E+10 0.00 0.00
May 0.787956E+09 0.00 0.00 0.864710E+10 0.00 0.00
June 0.501633E+09 0.00 0.00 0.124797E+11 0.00 0.00
July 0.308950E+09 0.00 0.00 0.119166E+11 0.00 0.00
August 0.298455E+09 0.00 0.00 0.131961E+11 0.00 0.00
September 0.325061E+09 0.00 0.00 0.128912E+11 0.00 0.00
October 0.312203E+09 0.00 0.00 0.154076E+11 0.00 0.00
November 0.863548E+09 0.00 0.00 0.529021E+10 0.00 0.00
December 0.102232E+10 0.00 0.00 0.485462E+10 0.00 0.00
             
Annual Sum or Average 0.998767E+10 0.00 0.00 0.103841E+12 0.00 0.00
Minimum of Months 0.298455E+09 0.00 0.00 0.327044E+10 0.00 0.00
Maximum of Months 0.215493E+10 0.00 0.00 0.154076E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_2:5

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.103352E+10 0.00 0.00
February 0.00 0.00 0.00 0.768737E+09 0.00 0.00
March 0.00 0.00 0.00 0.103287E+10 0.00 0.00
April 0.00 0.00 0.00 0.181424E+10 0.00 0.00
May 0.00 0.00 0.00 0.205478E+10 0.00 0.00
June 0.00 0.00 0.00 0.305741E+10 0.00 0.00
July 0.00 0.00 0.00 0.321969E+10 0.00 0.00
August 0.00 0.00 0.00 0.350166E+10 0.00 0.00
September 0.00 0.00 0.00 0.285825E+10 0.00 0.00
October 0.00 0.00 0.00 0.301783E+10 0.00 0.00
November 0.00 0.00 0.00 0.107130E+10 0.00 0.00
December 0.00 0.00 0.00 0.108198E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.245123E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.768737E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.350166E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_1:6

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.252999E+10 0.00 0.00
February 0.00 0.00 0.00 0.208919E+10 0.00 0.00
March 0.00 0.00 0.00 0.256648E+10 0.00 0.00
April 0.00 0.00 0.00 0.337246E+10 0.00 0.00
May 0.00 0.00 0.00 0.364885E+10 0.00 0.00
June 0.00 0.00 0.00 0.454150E+10 0.00 0.00
July 0.00 0.00 0.00 0.512458E+10 0.00 0.00
August 0.00 0.00 0.00 0.562184E+10 0.00 0.00
September 0.00 0.00 0.00 0.463642E+10 0.00 0.00
October 0.00 0.00 0.00 0.515022E+10 0.00 0.00
November 0.00 0.00 0.00 0.268452E+10 0.00 0.00
December 0.00 0.00 0.00 0.246561E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.444317E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.208919E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.562184E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_2:7

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.233982E+10 0.00 0.00
February 0.00 0.00 0.00 0.188569E+10 0.00 0.00
March 0.00 0.00 0.00 0.230618E+10 0.00 0.00
April 0.00 0.00 0.00 0.314036E+10 0.00 0.00
May 0.00 0.00 0.00 0.349957E+10 0.00 0.00
June 0.00 0.00 0.00 0.489750E+10 0.00 0.00
July 0.00 0.00 0.00 0.314837E+10 0.00 0.00
August 0.00 0.00 0.00 0.349268E+10 0.00 0.00
September 0.00 0.00 0.00 0.471644E+10 0.00 0.00
October 0.00 0.00 0.00 0.508004E+10 0.00 0.00
November 0.00 0.00 0.00 0.248337E+10 0.00 0.00
December 0.00 0.00 0.00 0.226798E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.392580E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.188569E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.508004E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_POD_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.547350E+10 0.122356E+11 0.133301E+10 0.00 0.00 0.00 0.00 0.00
February 0.473242E+10 0.725582E+10 0.836594E+09 0.00 0.00 0.00 0.00 0.00
March 0.546963E+10 0.786014E+10 0.152392E+10 0.00 0.00 0.00 0.00 0.00
April 0.490705E+10 0.161433E+11 0.102150E+09 0.00 0.00 0.00 0.00 0.00
May 0.523297E+10 0.181190E+11 92399796.55 0.00 0.00 0.00 0.00 0.00
June 0.521617E+10 0.286364E+11 22031329.71 0.00 0.00 0.00 0.00 0.00
July 0.472876E+10 0.369310E+11 0.638242E+09 0.00 0.00 0.00 0.00 0.00
August 0.542174E+10 0.435362E+11 0.744041E+09 0.00 0.00 0.00 0.00 0.00
September 0.536032E+10 0.351125E+11 0.118724E+09 0.00 0.00 0.00 0.00 0.00
October 0.652004E+10 0.458257E+11 13228655.55 0.00 0.00 0.00 0.00 0.00
November 0.568264E+10 0.141593E+11 0.271693E+09 0.00 0.00 0.00 0.00 0.00
December 0.547322E+10 0.150300E+11 0.752833E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.642185E+11 0.280845E+12 0.644887E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.472876E+10 0.725582E+10 13228655.55 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.652004E+10 0.458257E+11 0.152392E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_POD_2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.542700E+10 0.120767E+11 0.138745E+10 0.00 0.00 0.00 0.00 0.00
February 0.473423E+10 0.719056E+10 0.829417E+09 0.00 0.00 0.00 0.00 0.00
March 0.548548E+10 0.777838E+10 0.148758E+10 0.00 0.00 0.00 0.00 0.00
April 0.491855E+10 0.160373E+11 0.100069E+09 0.00 0.00 0.00 0.00 0.00
May 0.526860E+10 0.181240E+11 87482037.18 0.00 0.00 0.00 0.00 0.00
June 0.523618E+10 0.285215E+11 17888609.44 0.00 0.00 0.00 0.00 0.00
July 0.474377E+10 0.367358E+11 0.631667E+09 0.00 0.00 0.00 0.00 0.00
August 0.545548E+10 0.434180E+11 0.754759E+09 0.00 0.00 0.00 0.00 0.00
September 0.535193E+10 0.347963E+11 0.121388E+09 0.00 0.00 0.00 0.00 0.00
October 0.651358E+10 0.455011E+11 13130791.79 0.00 0.00 0.00 0.00 0.00
November 0.564273E+10 0.139524E+11 0.272536E+09 0.00 0.00 0.00 0.00 0.00
December 0.540935E+10 0.146781E+11 0.777777E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.641869E+11 0.278810E+12 0.648114E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.473423E+10 0.719056E+10 13130791.79 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.651358E+10 0.455011E+11 0.148758E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_POD_3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.477687E+10 0.110589E+11 0.108709E+10 0.00 0.00 0.00 0.00 0.00
February 0.409220E+10 0.653818E+10 0.624150E+09 0.00 0.00 0.00 0.00 0.00
March 0.465430E+10 0.705683E+10 0.113403E+10 0.00 0.00 0.00 0.00 0.00
April 0.427648E+10 0.144504E+11 64690859.57 0.00 0.00 0.00 0.00 0.00
May 0.448710E+10 0.160172E+11 51271974.12 0.00 0.00 0.00 0.00 0.00
June 0.441135E+10 0.252712E+11 9311231.14 0.00 0.00 0.00 0.00 0.00
July 0.393402E+10 0.323000E+11 0.332341E+09 0.00 0.00 0.00 0.00 0.00
August 0.451756E+10 0.382874E+11 0.405354E+09 0.00 0.00 0.00 0.00 0.00
September 0.463030E+10 0.314141E+11 75829886.19 0.00 0.00 0.00 0.00 0.00
October 0.573758E+10 0.412825E+11 10852524.03 0.00 0.00 0.00 0.00 0.00
November 0.500027E+10 0.128507E+11 0.231560E+09 0.00 0.00 0.00 0.00 0.00
December 0.475206E+10 0.134632E+11 0.629152E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.552701E+11 0.249991E+12 0.465563E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.393402E+10 0.653818E+10 9311231.14 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.573758E+10 0.412825E+11 0.113403E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_OTHER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.203725E+10 0.800451E+10 0.131540E+10 0.00 0.00 0.00 0.00 0.00
February 0.182715E+10 0.472713E+10 0.129011E+10 0.00 0.00 0.00 0.00 0.00
March 0.222041E+10 0.583197E+10 0.215493E+10 0.00 0.00 0.00 0.00 0.00
April 0.318163E+10 0.149481E+11 0.807110E+09 0.00 0.00 0.00 0.00 0.00
May 0.358432E+10 0.173806E+11 0.787956E+09 0.00 0.00 0.00 0.00 0.00
June 0.409924E+10 0.299045E+11 0.501633E+09 0.00 0.00 0.00 0.00 0.00
July 0.247162E+10 0.344824E+11 0.308950E+09 0.00 0.00 0.00 0.00 0.00
August 0.267172E+10 0.387145E+11 0.298455E+09 0.00 0.00 0.00 0.00 0.00
September 0.377441E+10 0.326594E+11 0.325061E+09 0.00 0.00 0.00 0.00 0.00
October 0.426275E+10 0.404619E+11 0.312203E+09 0.00 0.00 0.00 0.00 0.00
November 0.243472E+10 0.954285E+10 0.863548E+09 0.00 0.00 0.00 0.00 0.00
December 0.206205E+10 0.959344E+10 0.102232E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.346273E+11 0.246251E+12 0.998767E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.182715E+10 0.472713E+10 0.298455E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.426275E+10 0.404619E+11 0.215493E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_2:5

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.660101E+09 0.150391E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.596789E+09 0.670212E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.724512E+09 0.127592E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.644979E+09 0.493275E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.710581E+09 0.569662E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.762426E+09 0.101282E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.735568E+09 0.108879E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.816184E+09 0.118023E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.686714E+09 0.944643E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.723462E+09 0.976430E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.660612E+09 0.160407E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.628339E+09 0.179359E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.835026E+10 0.695062E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.596789E+09 0.670212E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.816184E+09 0.118023E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_1:6

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.843198E+09 0.735324E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.754210E+09 0.589778E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.900824E+09 0.734912E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.933549E+09 0.107968E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.999955E+09 0.118175E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.107348E+10 0.153184E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109023E+10 0.173906E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.118932E+10 0.193015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.106718E+10 0.155476E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.115865E+10 0.172588E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.857782E+09 0.804714E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.816020E+09 0.718564E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116844E+11 0.143264E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.754210E+09 0.589778E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118932E+10 0.193015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_2:7

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.103227E+10 0.545113E+10 0.181296E+10 0.00 0.00 0.00 0.00 0.00
February 0.921516E+09 0.396796E+10 0.112708E+10 0.00 0.00 0.00 0.00 0.00
March 0.113166E+10 0.493179E+10 0.191947E+10 0.00 0.00 0.00 0.00 0.00
April 0.991024E+09 0.938731E+10 0.403144E+09 0.00 0.00 0.00 0.00 0.00
May 0.108096E+10 0.105836E+11 0.212900E+09 0.00 0.00 0.00 0.00 0.00
June 0.120946E+10 0.163225E+11 7547422.03 0.00 0.00 0.00 0.00 0.00
July 0.974818E+09 0.877779E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.110808E+10 0.960011E+10 772281.86 0.00 0.00 0.00 0.00 0.00
September 0.113151E+10 0.156064E+11 21405830.47 0.00 0.00 0.00 0.00 0.00
October 0.118380E+10 0.166372E+11 11788636.33 0.00 0.00 0.00 0.00 0.00
November 0.100905E+10 0.623288E+10 0.678705E+09 0.00 0.00 0.00 0.00 0.00
December 0.974011E+09 0.540068E+10 0.133485E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127482E+11 0.112899E+12 0.753064E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.921516E+09 0.396796E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120946E+10 0.166372E+11 0.191947E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_POD_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.547350E+10 0.133301E+10 0.00 0.00 0.357359E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.473242E+10 0.836594E+09 0.00 0.00 0.218092E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.546963E+10 0.152392E+10 0.00 0.00 0.233256E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.490705E+10 0.102150E+09 0.00 0.00 0.468608E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.523297E+10 92399796.55 0.00 0.00 0.533621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.521617E+10 22031329.71 0.00 0.00 0.810531E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.472876E+10 0.638242E+09 0.00 0.00 0.100400E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.542174E+10 0.744041E+09 0.00 0.00 0.117740E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.536032E+10 0.118724E+09 0.00 0.00 0.976974E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.652004E+10 13228655.55 0.00 0.00 0.125566E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568264E+10 0.271693E+09 0.00 0.00 0.414486E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.547322E+10 0.752833E+09 0.00 0.00 0.426912E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.642185E+11 0.644887E+10 0.00 0.00 0.787690E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.472876E+10 13228655.55 0.00 0.00 0.218092E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.652004E+10 0.152392E+10 0.00 0.00 0.125566E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_POD_2

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.542700E+10 0.138745E+10 0.00 0.00 0.352856E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.473423E+10 0.829417E+09 0.00 0.00 0.216266E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.548548E+10 0.148758E+10 0.00 0.00 0.230863E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.491855E+10 0.100069E+09 0.00 0.00 0.465503E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.526860E+10 87482037.18 0.00 0.00 0.533376E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.523618E+10 17888609.44 0.00 0.00 0.806851E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.474377E+10 0.631667E+09 0.00 0.00 0.998468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.545548E+10 0.754759E+09 0.00 0.00 0.117402E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.535193E+10 0.121388E+09 0.00 0.00 0.968136E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.651358E+10 13130791.79 0.00 0.00 0.124657E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.564273E+10 0.272536E+09 0.00 0.00 0.408725E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.540935E+10 0.777777E+09 0.00 0.00 0.417396E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.641869E+11 0.648114E+10 0.00 0.00 0.781903E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.473423E+10 13130791.79 0.00 0.00 0.216266E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.651358E+10 0.148758E+10 0.00 0.00 0.124657E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_POD_3

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.477687E+10 0.108709E+10 0.00 0.00 0.322277E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.409220E+10 0.624150E+09 0.00 0.00 0.195812E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.465430E+10 0.113403E+10 0.00 0.00 0.208633E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.427648E+10 64690859.57 0.00 0.00 0.418370E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.448710E+10 51271974.12 0.00 0.00 0.470791E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.441135E+10 9311231.14 0.00 0.00 0.715097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.393402E+10 0.332341E+09 0.00 0.00 0.878758E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.451756E+10 0.405354E+09 0.00 0.00 0.103569E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.463030E+10 75829886.19 0.00 0.00 0.873339E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.573758E+10 10852524.03 0.00 0.00 0.113041E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.500027E+10 0.231560E+09 0.00 0.00 0.374622E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.475206E+10 0.629152E+09 0.00 0.00 0.381572E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.552701E+11 0.465563E+10 0.00 0.00 0.700537E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.393402E+10 9311231.14 0.00 0.00 0.195812E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.573758E+10 0.113403E+10 0.00 0.00 0.113041E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_OTHER

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.203725E+10 0.131540E+10 0.00 0.00 0.238185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.182715E+10 0.129011E+10 0.00 0.00 0.144329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.222041E+10 0.215493E+10 0.00 0.00 0.174368E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.318163E+10 0.807110E+09 0.00 0.00 0.432251E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.358432E+10 0.787956E+09 0.00 0.00 0.506278E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.409924E+10 0.501633E+09 0.00 0.00 0.838043E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.247162E+10 0.308950E+09 0.00 0.00 0.944501E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.267172E+10 0.298455E+09 0.00 0.00 0.105244E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.377441E+10 0.325061E+09 0.00 0.00 0.911680E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.426275E+10 0.312203E+09 0.00 0.00 0.111449E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.243472E+10 0.863548E+09 0.00 0.00 0.285550E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.206205E+10 0.102232E+10 0.00 0.00 0.279257E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.346273E+11 0.998767E+10 0.00 0.00 0.692137E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.182715E+10 0.298455E+09 0.00 0.00 0.144329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.426275E+10 0.215493E+10 0.00 0.00 0.111449E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_2:5

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.660101E+09 0.00 0.00 0.00 0.373417E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.596789E+09 0.00 0.00 0.00 0.171948E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.724512E+09 0.00 0.00 0.00 0.308362E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.644979E+09 0.00 0.00 0.00 0.116926E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.710581E+09 0.00 0.00 0.00 0.134420E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.762426E+09 0.00 0.00 0.00 0.229498E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.735568E+09 0.00 0.00 0.00 0.248412E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.816184E+09 0.00 0.00 0.00 0.268547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.686714E+09 0.00 0.00 0.00 0.217153E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.723462E+09 0.00 0.00 0.00 0.229436E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.660612E+09 0.00 0.00 0.00 0.410684E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.628339E+09 0.00 0.00 0.00 0.453643E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.835026E+10 0.00 0.00 0.00 0.161620E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.596789E+09 0.00 0.00 0.00 0.171948E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.816184E+09 0.00 0.00 0.00 0.268547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_1:6

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.843198E+09 0.00 0.00 0.00 0.168679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.754210E+09 0.00 0.00 0.00 0.133498E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.900824E+09 0.00 0.00 0.00 0.166565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.933549E+09 0.00 0.00 0.00 0.243891E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.999955E+09 0.00 0.00 0.00 0.264889E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.107348E+10 0.00 0.00 0.00 0.346802E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109023E+10 0.00 0.00 0.00 0.403435E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.118932E+10 0.00 0.00 0.00 0.443253E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.106718E+10 0.00 0.00 0.00 0.356925E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.115865E+10 0.00 0.00 0.00 0.399157E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.857782E+09 0.00 0.00 0.00 0.182674E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.816020E+09 0.00 0.00 0.00 0.164959E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.116844E+11 0.00 0.00 0.00 0.327473E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.754210E+09 0.00 0.00 0.00 0.133498E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118932E+10 0.00 0.00 0.00 0.443253E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_2:7

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.103227E+10 0.00 0.00 0.00 0.130755E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.921516E+09 0.00 0.00 0.00 0.964178E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.113166E+10 0.00 0.00 0.00 0.117452E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.991024E+09 0.00 0.00 0.00 0.214934E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.108096E+10 0.00 0.00 0.00 0.241861E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.120946E+10 0.00 0.00 0.00 0.368804E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.974818E+09 0.00 0.00 0.00 0.217355E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.110808E+10 0.00 0.00 0.00 0.238460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.113151E+10 0.00 0.00 0.00 0.358493E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.118380E+10 0.00 0.00 0.00 0.389623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.100905E+10 0.00 0.00 0.00 0.147432E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.974011E+09 0.00 0.00 0.00 0.129397E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.127482E+11 0.00 0.00 0.00 0.265098E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.921516E+09 0.00 0.00 0.00 0.964178E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120946E+10 0.00 0.00 0.00 0.389623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209418E+10 0.00 0.00 2426608.47 0.00 14576312.71 0.151922E+10 0.00 1.23
February 0.233749E+10 0.00 0.00 1531029.62 0.00 5781786.32 0.115868E+10 0.00 1.25
March 0.326690E+10 111068.10 0.00 1085435.43 2576980.71 24692090.58 0.882424E+09 0.00 1.29
April 0.174616E+10 25510.75 0.00 2086265.31 527396.29 3394747.28 0.132609E+10 0.00 1.30
May 0.212220E+10 0.00 0.00 1367223.02 0.00 3338992.08 0.113228E+10 0.00 1.39
June 0.131653E+10 19042875.13 0.00 625970.30 61021335.99 2160073.48 0.539641E+09 0.00 1.35
July 0.263255E+09 29611669.73 601128.58 49851.07 0.480457E+09 685086.09 3552645.87 24838.95 0.85
August 0.246018E+09 41413340.28 1646094.87 26819.92 0.611663E+09 785319.36 4504631.84 33415.45 0.94
September 0.755315E+09 0.146342E+09 0.00 1900563.34 43990531.73 990174.50 0.648741E+09 0.00 1.33
October 0.920072E+09 0.208222E+09 0.00 2689623.99 0.102075E+09 1134213.91 0.870488E+09 0.00 1.37
November 0.193106E+10 120416.59 0.00 3102467.25 2017804.50 3244187.01 0.178243E+10 0.00 1.38
December 0.199487E+10 0.00 0.00 2580629.84 0.00 4755232.18 0.129741E+10 0.00 1.21
                   
Annual Sum or Average 0.189940E+11 0.444890E+09 2247223.45 19472487.57 0.130433E+10 65538215.51 0.111655E+11 58254.40 1.24
Minimum of Months 0.246018E+09 0.00 0.00 26819.92 0.00 685086.09 3552645.87 0.00 0.85
Maximum of Months 0.326690E+10 0.208222E+09 1646094.87 3102467.25 0.611663E+09 24692090.58 0.178243E+10 33415.45 1.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_1_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.629774E+10 0.00 0.00 17873492.23 0.00 11370368.18 0.887747E+10 0.00 1.08
February 0.705891E+10 0.00 0.00 11696956.56 0.00 8313727.44 0.720029E+10 0.00 1.07
March 0.989316E+10 549488.69 0.00 8680725.12 10143778.35 20434396.25 0.666705E+10 0.00 1.07
April 0.560423E+10 116291.37 0.00 12419072.44 2075991.88 5889710.47 0.674129E+10 0.00 1.09
May 0.625533E+10 0.00 0.00 9534455.79 0.00 6478880.44 0.663018E+10 0.00 1.15
June 0.406747E+10 40758433.18 0.00 4771983.74 0.274399E+09 1918357.42 0.325386E+10 0.00 1.10
July 0.104970E+10 26302270.36 2361787.73 0.00 0.198138E+10 3319258.13 0.00 102210.50 0.70
August 0.986935E+09 26974334.79 4797961.10 1445.70 0.254515E+10 1954648.04 420166.13 114850.62 0.77
September 0.282949E+10 0.664274E+09 0.00 9543994.92 0.111440E+09 1250176.62 0.288585E+10 0.00 1.12
October 0.271590E+10 0.104031E+10 0.00 16641783.03 0.304168E+09 0.00 0.472431E+10 0.00 1.21
November 0.565872E+10 546314.69 0.00 20791721.92 7942691.02 0.00 0.993028E+10 0.00 1.22
December 0.570802E+10 0.00 0.00 18622698.93 0.00 3801995.29 0.803908E+10 0.00 1.07
                   
Annual Sum or Average 0.581256E+11 0.179983E+10 7159748.82 0.130578E+09 0.523669E+10 64731518.28 0.649501E+11 217061.11 1.05
Minimum of Months 0.986935E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.70
Maximum of Months 0.989316E+10 0.104031E+10 4797961.10 20791721.92 0.254515E+10 20434396.25 0.993028E+10 114850.62 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273978E+10 0.00 0.00 21478.29 0.00 4651076.66 50714956.83 0.00 0.49
February 0.268973E+10 0.00 0.00 1851.99 0.00 1141831.65 10989606.83 0.00 0.50
March 0.320636E+10 0.00 0.00 13762.59 2090680.99 3877983.70 30398823.77 0.00 0.51
April 0.202926E+10 0.00 0.00 396697.21 430033.94 0.00 0.349738E+09 0.00 0.52
May 0.201118E+10 0.00 0.00 725303.86 0.00 0.00 0.521456E+09 0.00 0.56
June 0.108424E+10 11233734.99 0.00 466756.71 51037724.96 0.00 0.363870E+09 0.00 0.54
July 0.208064E+09 0.00 9309.60 0.00 0.397171E+09 0.00 0.00 699.23 0.34
August 0.195477E+09 0.00 0.00 0.00 0.509192E+09 0.00 0.00 0.00 0.38
September 0.752075E+09 52980959.01 0.00 872696.09 88062450.10 0.00 0.331846E+09 0.00 0.53
October 0.860192E+09 0.173193E+09 0.00 1225116.47 63451997.03 0.00 0.505150E+09 0.00 0.54
November 0.268631E+10 0.00 0.00 28044.23 1656866.26 0.00 0.140589E+09 0.00 0.54
December 0.249554E+10 0.00 0.00 8859.95 0.00 742861.07 24323828.08 0.00 0.47
                   
Annual Sum or Average 0.209582E+11 0.237407E+09 9309.60 3760567.38 0.111309E+10 10413753.07 0.232908E+10 699.23 0.49
Minimum of Months 0.195477E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.320636E+10 0.173193E+09 9309.60 1225116.47 0.509192E+09 4651076.66 0.521456E+09 699.23 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.310273E+10 0.00 0.00 57227.59 0.00 82003332.62 0.114720E+09 0.00 1.11
February 0.304992E+10 0.00 0.00 35985.04 0.00 31416508.17 0.107996E+09 0.00 1.13
March 0.366027E+10 0.00 0.00 57918.92 2467914.76 45584443.04 0.119464E+09 0.00 1.18
April 0.208837E+10 0.00 0.00 571222.46 507627.48 3737821.57 0.716234E+09 0.00 1.18
May 0.190637E+10 0.00 0.00 1011547.54 0.00 2547674.12 0.107920E+10 0.00 1.28
June 0.104867E+10 20108393.90 0.00 731519.82 53399069.01 1363363.59 0.656410E+09 0.00 1.24
July 0.242811E+09 12335802.26 557969.55 10173.92 0.455936E+09 628981.91 2156082.88 16735.23 0.78
August 0.229976E+09 1223385.87 1505283.32 0.00 0.598304E+09 771858.58 0.00 36685.82 0.86
September 0.894809E+09 90676595.65 0.00 561717.37 74414501.31 1880743.43 0.371835E+09 0.00 1.20
October 0.109340E+10 0.154755E+09 0.00 711285.98 0.108092E+09 2425181.00 0.512044E+09 0.00 1.20
November 0.298742E+10 0.00 0.00 103846.55 1955824.31 8942582.39 0.340536E+09 0.00 1.23
December 0.284697E+10 0.00 0.00 43962.80 0.00 37724320.46 90679407.69 0.00 1.07
                   
Annual Sum or Average 0.231517E+11 0.279099E+09 2063252.87 3896407.98 0.129508E+10 0.219027E+09 0.411127E+10 53421.05 1.12
Minimum of Months 0.229976E+09 0.00 0.00 0.00 0.00 628981.91 0.00 0.00 0.78
Maximum of Months 0.366027E+10 0.154755E+09 1505283.32 1011547.54 0.598304E+09 82003332.62 0.107920E+10 36685.82 1.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_2_POD_1_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.902338E+10 0.00 0.00 2393280.24 0.00 46357605.86 0.298869E+10 0.00 0.85
February 0.790112E+10 0.00 0.00 1847282.81 0.00 18886895.22 0.373637E+10 0.00 0.86
March 0.961529E+10 0.00 0.00 2318177.66 9021055.37 22977338.14 0.434246E+10 0.00 0.90
April 0.513024E+10 0.00 0.00 7731076.39 1855548.52 7207063.14 0.516521E+10 0.00 0.90
May 0.472326E+10 0.00 0.00 11020844.25 0.00 2508447.55 0.633159E+10 0.00 0.99
June 0.313169E+10 94690649.89 0.00 6758137.00 0.174004E+09 0.00 0.324494E+10 0.00 0.96
July 0.895991E+09 0.00 779028.40 0.00 0.171297E+10 1783200.39 0.00 48067.14 0.59
August 0.841146E+09 0.00 4078445.36 0.00 0.219292E+10 2314472.14 0.00 110085.64 0.66
September 0.291745E+10 0.371657E+09 0.00 4738077.82 0.255276E+09 2101066.85 0.178549E+10 0.00 0.93
October 0.306552E+10 0.736172E+09 0.00 8542792.72 0.306090E+09 1422668.09 0.290192E+10 0.00 0.94
November 0.691564E+10 0.00 0.00 4212672.68 7149193.17 12337852.76 0.526569E+10 0.00 0.94
December 0.748348E+10 0.00 0.00 2306358.31 0.00 20633024.79 0.336974E+10 0.00 0.82
                   
Annual Sum or Average 0.616442E+11 0.120252E+10 4857473.76 51868699.88 0.465928E+10 0.138530E+09 0.391321E+11 158152.77 0.86
Minimum of Months 0.841146E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.961529E+10 0.736172E+09 4078445.36 11020844.25 0.219292E+10 46357605.86 0.633159E+10 110085.64 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209867E+10 0.00 0.00 2311493.80 0.00 17709589.38 0.147233E+10 0.00 1.22
February 0.235455E+10 0.00 0.00 1472306.73 0.00 5793385.27 0.112706E+10 0.00 1.25
March 0.330015E+10 0.00 0.00 1024045.28 367325.63 21610124.45 0.840071E+09 0.00 1.28
April 0.176733E+10 36118.21 0.00 2000349.07 653396.91 3123922.70 0.129945E+10 0.00 1.29
May 0.215083E+10 0.00 0.00 1292682.86 0.00 3229255.20 0.110346E+10 0.00 1.39
June 0.132506E+10 18212742.88 0.00 582399.22 59762075.92 2078424.11 0.538415E+09 0.00 1.34
July 0.265457E+09 27263636.65 596864.90 38533.44 0.479028E+09 690287.46 2551919.00 24864.12 0.85
August 0.246955E+09 30678198.72 1646499.75 31802.65 0.620430E+09 787219.61 3841625.03 34325.10 0.94
September 0.750936E+09 0.147824E+09 0.00 1824575.24 40355915.95 899475.69 0.646682E+09 0.00 1.32
October 0.884169E+09 0.205822E+09 0.00 2688471.55 0.102424E+09 1137699.10 0.899025E+09 0.00 1.36
November 0.192363E+10 307787.90 0.00 3013616.98 1334948.19 3230304.85 0.175968E+10 0.00 1.37
December 0.198170E+10 0.00 0.00 2497202.37 0.00 4728064.08 0.127438E+10 0.00 1.19
                   
Annual Sum or Average 0.190494E+11 0.430144E+09 2243364.65 18777479.19 0.130436E+10 65017751.90 0.109670E+11 59189.22 1.23
Minimum of Months 0.246955E+09 0.00 0.00 31802.65 0.00 690287.46 2551919.00 0.00 0.85
Maximum of Months 0.330015E+10 0.205822E+09 1646499.75 3013616.98 0.620430E+09 21610124.45 0.175968E+10 34325.10 1.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_1_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.638152E+10 0.00 0.00 16682505.36 0.00 12007155.76 0.846699E+10 0.00 1.06
February 0.702077E+10 0.00 0.00 11184542.53 0.00 8279302.59 0.708912E+10 0.00 1.06
March 0.982840E+10 0.00 0.00 8400238.62 1441724.76 19630498.75 0.662285E+10 0.00 1.06
April 0.547671E+10 170540.88 0.00 12334131.57 2564532.46 4441912.26 0.680432E+10 0.00 1.08
May 0.607205E+10 0.00 0.00 9824369.02 0.00 5726918.74 0.678856E+10 0.00 1.14
June 0.399909E+10 47570335.51 0.00 5044527.23 0.258475E+09 0.00 0.333353E+10 0.00 1.10
July 0.105198E+10 0.00 2342790.77 0.00 0.198709E+10 2678131.82 0.00 97447.66 0.69
August 0.985499E+09 10680528.68 4789834.37 0.00 0.254634E+10 1950559.85 0.00 114272.71 0.76
September 0.277452E+10 0.654383E+09 0.00 9171252.16 0.108448E+09 1245408.14 0.289097E+10 0.00 1.10
October 0.267181E+10 0.102201E+10 0.00 16341821.22 0.304306E+09 0.00 0.470316E+10 0.00 1.19
November 0.563928E+10 1180000.01 0.00 19820781.88 5239568.66 0.00 0.969115E+10 0.00 1.20
December 0.576253E+10 0.00 0.00 17293381.47 0.00 4774272.67 0.768971E+10 0.00 1.04
                   
Annual Sum or Average 0.576642E+11 0.173600E+10 7132625.14 0.126098E+09 0.521391E+10 60734160.58 0.640804E+11 211720.38 1.04
Minimum of Months 0.985499E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69
Maximum of Months 0.982840E+10 0.102201E+10 4789834.37 19820781.88 0.254634E+10 19630498.75 0.969115E+10 114272.71 1.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273078E+10 0.00 0.00 17119.23 0.00 5200207.56 47336660.03 0.00 0.49
February 0.269511E+10 0.00 0.00 1051.63 0.00 1144274.34 10283135.67 0.00 0.50
March 0.321964E+10 0.00 0.00 12053.53 287232.85 3883570.11 25928944.67 0.00 0.52
April 0.204008E+10 0.00 0.00 392696.58 539171.18 0.00 0.348924E+09 0.00 0.52
May 0.201116E+10 0.00 0.00 751199.29 0.00 0.00 0.536060E+09 0.00 0.56
June 0.108185E+10 11704219.56 0.00 506477.73 49268735.85 0.00 0.380310E+09 0.00 0.54
July 0.210118E+09 0.00 9591.29 0.00 0.396362E+09 0.00 0.00 634.64 0.34
August 0.196728E+09 0.00 0.00 0.00 0.510408E+09 0.00 0.00 0.00 0.38
September 0.755528E+09 51370422.71 0.00 855931.47 88756451.22 0.00 0.330398E+09 0.00 0.53
October 0.855730E+09 0.171363E+09 0.00 1242204.98 64225894.22 0.00 0.510727E+09 0.00 0.53
November 0.270005E+10 0.00 0.00 21258.86 1278961.87 0.00 0.121008E+09 0.00 0.54
December 0.248373E+10 0.00 0.00 6642.13 0.00 907252.52 22073603.00 0.00 0.47
                   
Annual Sum or Average 0.209805E+11 0.234438E+09 9591.29 3806635.42 0.111113E+10 11135304.53 0.233305E+10 634.64 0.49
Minimum of Months 0.196728E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.321964E+10 0.171363E+09 9591.29 1242204.98 0.510408E+09 5200207.56 0.536060E+09 634.64 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.308835E+10 0.00 0.00 57115.62 0.00 82549212.97 0.118787E+09 0.00 1.11
February 0.305866E+10 0.00 0.00 36796.22 0.00 31626818.58 0.108653E+09 0.00 1.14
March 0.366658E+10 0.00 0.00 58818.78 339493.60 47433537.36 0.126617E+09 0.00 1.18
April 0.209271E+10 0.00 0.00 578922.25 637270.99 3781589.04 0.727293E+09 0.00 1.19
May 0.190526E+10 0.00 0.00 1041977.91 0.00 2580894.67 0.110067E+10 0.00 1.28
June 0.105636E+10 21423065.53 0.00 752918.13 50643649.47 1494382.50 0.666980E+09 0.00 1.24
July 0.245446E+09 14874723.09 558168.02 18105.37 0.453041E+09 637984.80 2246198.45 16452.98 0.78
August 0.231744E+09 1230990.03 1516292.12 0.00 0.600490E+09 778304.45 0.00 37177.68 0.87
September 0.893266E+09 90726626.16 0.00 574839.50 73599497.01 1734488.16 0.377815E+09 0.00 1.19
October 0.108385E+10 0.154161E+09 0.00 733083.12 0.108917E+09 2440945.21 0.525194E+09 0.00 1.20
November 0.297081E+10 0.00 0.00 109446.71 1511663.32 8936397.24 0.354514E+09 0.00 1.23
December 0.282791E+10 0.00 0.00 49558.22 0.00 38498541.01 96344222.80 0.00 1.07
                   
Annual Sum or Average 0.231209E+11 0.282417E+09 2074460.13 4011581.82 0.128918E+10 0.222493E+09 0.420511E+10 53630.66 1.12
Minimum of Months 0.231744E+09 0.00 0.00 0.00 0.00 637984.80 0.00 0.00 0.78
Maximum of Months 0.366658E+10 0.154161E+09 1516292.12 1041977.91 0.600490E+09 82549212.97 0.110067E+10 37177.68 1.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_2_POD_2_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.910488E+10 0.00 0.00 2305495.85 0.00 46646701.28 0.287179E+10 0.00 0.85
February 0.797088E+10 0.00 0.00 1801356.09 0.00 19037148.25 0.370211E+10 0.00 0.87
March 0.970079E+10 0.00 0.00 2286093.64 1241014.47 23016617.00 0.431351E+10 0.00 0.90
April 0.517410E+10 0.00 0.00 7665709.41 2329535.89 7296134.35 0.517527E+10 0.00 0.91
May 0.475293E+10 0.00 0.00 11024602.04 0.00 2542867.32 0.637589E+10 0.00 0.99
June 0.315689E+10 95503556.05 0.00 6827269.99 0.167935E+09 0.00 0.328860E+10 0.00 0.96
July 0.906033E+09 0.00 785146.01 0.00 0.171173E+10 1800464.80 0.00 48434.11 0.59
August 0.847651E+09 0.00 4108650.64 0.00 0.220104E+10 2330626.79 0.00 112729.18 0.66
September 0.291984E+10 0.371198E+09 0.00 4727383.12 0.252465E+09 2112325.69 0.179881E+10 0.00 0.92
October 0.304931E+10 0.731737E+09 0.00 8592336.53 0.310035E+09 1415771.23 0.293133E+10 0.00 0.94
November 0.690183E+10 0.00 0.00 4166928.82 5525865.81 13522929.87 0.526921E+10 0.00 0.94
December 0.747320E+10 0.00 0.00 2249405.65 0.00 20724595.58 0.333431E+10 0.00 0.81
                   
Annual Sum or Average 0.619583E+11 0.119844E+10 4893796.66 51646581.16 0.465230E+10 0.140446E+09 0.390608E+11 161163.30 0.86
Minimum of Months 0.847651E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.970079E+10 0.731737E+09 4108650.64 11024602.04 0.220104E+10 46646701.28 0.637589E+10 112729.18 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.201640E+10 0.00 0.00 2549630.62 0.00 15393798.05 0.151383E+10 0.00 1.20
February 0.225362E+10 0.00 0.00 1649552.06 0.00 4891997.36 0.118183E+10 0.00 1.22
March 0.313385E+10 0.00 0.00 1189673.32 2440289.03 18166029.14 0.949635E+09 0.00 1.25
April 0.164754E+10 9111.23 0.00 2305819.63 624043.57 3088709.17 0.137899E+10 0.00 1.26
May 0.196915E+10 0.00 0.00 1575037.07 0.00 2417252.35 0.124120E+10 0.00 1.35
June 0.121956E+10 28541450.01 0.00 761318.46 57284709.54 1792504.62 0.637514E+09 0.00 1.34
July 0.262065E+09 31362196.09 532083.94 44137.11 0.464437E+09 702879.08 5587018.15 21113.87 0.85
August 0.248465E+09 62247430.72 1102836.55 41947.16 0.582032E+09 507706.28 4877650.02 24100.97 0.94
September 0.727370E+09 0.153665E+09 0.00 2045350.49 33180179.19 307701.27 0.664672E+09 0.00 1.31
October 0.842770E+09 0.224966E+09 0.00 2779930.06 90597363.99 968949.79 0.892471E+09 0.00 1.34
November 0.184219E+10 97097.66 0.00 3239693.05 1910006.11 3019691.35 0.179603E+10 0.00 1.35
December 0.190609E+10 0.00 0.00 2714080.38 0.00 4504457.37 0.131337E+10 0.00 1.17
                   
Annual Sum or Average 0.180691E+11 0.500889E+09 1634920.50 20896169.41 0.123251E+10 55761675.83 0.115800E+11 45214.84 1.21
Minimum of Months 0.248465E+09 0.00 0.00 41947.16 0.00 307701.27 4877650.02 0.00 0.85
Maximum of Months 0.313385E+10 0.224966E+09 1102836.55 3239693.05 0.582032E+09 18166029.14 0.179603E+10 24100.97 1.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_1_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.583897E+10 0.00 0.00 19822437.51 0.00 10309124.63 0.934570E+10 0.00 1.08
February 0.612811E+10 0.00 0.00 13768180.52 0.00 5554203.57 0.816979E+10 0.00 1.07
March 0.832423E+10 837783.37 0.00 11304257.05 8817189.32 14011526.61 0.816045E+10 0.00 1.06
April 0.491024E+10 54546.84 0.00 15292091.35 2458292.77 1884416.61 0.757947E+10 0.00 1.09
May 0.529078E+10 0.00 0.00 13379401.67 0.00 2930665.60 0.763714E+10 0.00 1.13
June 0.370925E+10 0.191397E+09 0.00 7141709.30 0.146698E+09 0.00 0.372322E+10 0.00 1.11
July 0.105487E+10 59312720.81 2111927.31 0.00 0.189373E+10 2174940.01 0.00 67283.01 0.69
August 0.997890E+09 86006799.74 3283484.98 4812.69 0.245286E+10 1798353.91 381742.86 53538.60 0.77
September 0.253316E+10 0.712185E+09 0.00 11842272.12 69599571.74 592246.97 0.322270E+10 0.00 1.12
October 0.236858E+10 0.115694E+10 0.00 18334203.02 0.247181E+09 0.00 0.502415E+10 0.00 1.21
November 0.514508E+10 417955.82 0.00 23184806.23 7524080.77 0.00 0.105309E+11 0.00 1.22
December 0.523984E+10 0.00 0.00 20481023.09 0.00 2228204.78 0.848091E+10 0.00 1.06
                   
Annual Sum or Average 0.515410E+11 0.220715E+10 5395412.29 0.154555E+09 0.482887E+10 41483682.69 0.718748E+11 120821.61 1.05
Minimum of Months 0.997890E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69
Maximum of Months 0.832423E+10 0.115694E+10 3283484.98 23184806.23 0.245286E+10 14011526.61 0.105309E+11 67283.01 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.267660E+10 0.00 0.00 47145.23 0.00 4405592.47 78014847.03 0.00 0.48
February 0.263011E+10 0.00 0.00 17851.83 0.00 379188.02 55243578.23 0.00 0.49
March 0.315187E+10 0.00 0.00 53324.46 1924432.39 2380452.93 71503209.88 0.00 0.51
April 0.180035E+10 0.00 0.00 842055.59 499311.18 0.00 0.571467E+09 0.00 0.51
May 0.170019E+10 0.00 0.00 1294155.62 0.00 0.00 0.839404E+09 0.00 0.55
June 0.886787E+09 37722714.29 0.00 1064522.52 29960514.87 0.00 0.586070E+09 0.00 0.55
July 0.211611E+09 0.00 0.00 0.00 0.391417E+09 0.00 0.00 0.00 0.34
August 0.200205E+09 0.00 0.00 0.00 0.508924E+09 0.00 0.00 0.00 0.38
September 0.667547E+09 89704509.16 0.00 1245302.01 51211996.30 0.00 0.425078E+09 0.00 0.53
October 0.771611E+09 0.196296E+09 0.00 1551696.70 49534410.87 0.00 0.572504E+09 0.00 0.53
November 0.253420E+10 0.00 0.00 94710.01 1577781.87 0.00 0.260870E+09 0.00 0.53
December 0.245962E+10 0.00 0.00 18189.41 0.00 446064.64 33813419.48 0.00 0.46
                   
Annual Sum or Average 0.196907E+11 0.323723E+09 0.00 6228953.37 0.103505E+10 7611298.06 0.349397E+10 0.00 0.49
Minimum of Months 0.200205E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.315187E+10 0.196296E+09 0.00 1551696.70 0.508924E+09 4405592.47 0.839404E+09 0.00 0.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.302836E+10 0.00 0.00 69087.90 0.00 86169379.29 0.136315E+09 0.00 1.09
February 0.301484E+10 0.00 0.00 51721.61 0.00 27601933.71 0.122035E+09 0.00 1.11
March 0.358846E+10 0.00 0.00 81953.13 2267490.76 42232734.80 0.170080E+09 0.00 1.15
April 0.196562E+10 0.00 0.00 766193.27 588320.74 3761892.94 0.821990E+09 0.00 1.16
May 0.174363E+10 0.00 0.00 1338207.41 0.00 2188924.58 0.123558E+10 0.00 1.25
June 0.977528E+09 32879101.65 0.00 978419.79 46869658.15 1300930.97 0.750146E+09 0.00 1.25
July 0.240899E+09 19548769.59 394505.74 35429.46 0.441237E+09 503427.56 7917254.80 12621.36 0.79
August 0.235194E+09 4803656.75 1383524.24 0.00 0.593433E+09 700813.41 0.00 27352.57 0.88
September 0.870121E+09 91672631.77 0.00 695942.09 71870561.25 1756905.07 0.398492E+09 0.00 1.19
October 0.106887E+10 0.167227E+09 0.00 732622.10 98803399.97 2422547.43 0.505472E+09 0.00 1.18
November 0.290100E+10 0.00 0.00 140963.87 1859044.69 8907780.06 0.383399E+09 0.00 1.21
December 0.281499E+10 0.00 0.00 44519.36 0.00 40507739.70 82928129.71 0.00 1.05
                   
Annual Sum or Average 0.224495E+11 0.316131E+09 1778029.98 4935060.00 0.125693E+10 0.218055E+09 0.461435E+10 39973.94 1.11
Minimum of Months 0.235194E+09 0.00 0.00 0.00 0.00 503427.56 0.00 0.00 0.79
Maximum of Months 0.358846E+10 0.167227E+09 1383524.24 1338207.41 0.593433E+09 86169379.29 0.123558E+10 27352.57 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MULT_CLASS_2_POD_3_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.603473E+10 0.00 0.00 1533409.56 0.00 38403101.62 0.184979E+10 0.00 0.84
February 0.519260E+10 0.00 0.00 1230113.99 0.00 12587530.69 0.250747E+10 0.00 0.85
March 0.632799E+10 0.00 0.00 1650305.72 5527251.37 15279654.82 0.292007E+10 0.00 0.89
April 0.337441E+10 0.00 0.00 5626087.41 1434094.76 4046805.36 0.346466E+10 0.00 0.90
May 0.306034E+10 0.00 0.00 7963002.62 0.00 390000.37 0.435495E+10 0.00 0.98
June 0.207295E+10 0.115212E+09 0.00 4936889.32 79183794.74 0.00 0.228345E+10 0.00 0.98
July 0.607107E+09 0.00 459717.86 0.00 0.112372E+10 670048.13 0.00 23764.18 0.60
August 0.573399E+09 0.00 2164714.82 0.00 0.145949E+10 1619869.48 0.00 50262.08 0.67
September 0.197213E+10 0.240871E+09 0.00 3253903.65 0.174419E+09 716716.27 0.117737E+10 0.00 0.93
October 0.205902E+10 0.520622E+09 0.00 5446232.58 0.184602E+09 943233.52 0.184280E+10 0.00 0.94
November 0.464091E+10 0.00 0.00 2702285.05 4531620.36 9538628.78 0.337498E+10 0.00 0.93
December 0.505748E+10 0.00 0.00 1310099.16 0.00 14470481.58 0.208958E+10 0.00 0.80
                   
Annual Sum or Average 0.409731E+11 0.876705E+09 2624432.69 35652329.07 0.303291E+10 98666070.61 0.258651E+11 74026.26 0.86
Minimum of Months 0.573399E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
Maximum of Months 0.632799E+10 0.520622E+09 2164714.82 7963002.62 0.145949E+10 38403101.62 0.435495E+10 50262.08 0.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: COMPUTER_CLASS_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.311610E+10 247186.29 0.00 1744489.68 25612.66 8246037.47 0.194586E+10 0.00 1.00
February 0.276758E+10 410273.61 0.00 1486351.25 0.00 5920561.79 0.230293E+10 0.00 1.02
March 0.318876E+10 0.00 0.00 2033135.87 9273424.70 6845999.28 0.298464E+10 0.00 1.07
April 0.106353E+10 332427.13 0.00 5306712.20 4740152.82 175191.20 0.341789E+10 0.00 1.12
May 0.980726E+09 1136685.87 0.00 7061716.13 447119.74 0.00 0.392650E+10 0.00 1.25
June 0.697193E+09 95054495.15 0.00 7758917.66 13977792.51 0.00 0.276993E+10 0.00 1.43
July 0.952236E+09 29925097.95 0.00 8292.62 0.597266E+09 616098.04 18862457.11 0.00 1.11
August 0.874083E+09 12424451.24 0.00 0.00 0.758590E+09 2172113.48 0.00 0.00 1.19
September 0.701286E+09 0.180060E+09 0.00 5418289.84 50231312.97 356947.94 0.187511E+10 0.00 1.24
October 0.778211E+09 0.368816E+09 0.00 4632542.27 0.122088E+09 468870.13 0.185999E+10 0.00 1.17
November 0.203254E+10 0.00 0.00 3001277.96 2224153.89 3370162.19 0.314754E+10 0.00 1.11
December 0.258710E+10 0.00 0.00 1727702.44 0.00 5653578.78 0.206914E+10 0.00 0.95
                   
Annual Sum or Average 0.197394E+11 0.688407E+09 0.00 40179427.92 0.155886E+10 33825560.30 0.263184E+11 0.00 1.14
Minimum of Months 0.697193E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.95
Maximum of Months 0.318876E+10 0.368816E+09 0.00 7758917.66 0.758590E+09 8246037.47 0.392650E+10 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MAIN_CORRIDOR_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.160395E+10 194603.81 0.00 3995012.76 14000.65 155969.89 0.157527E+10 0.00 0.20
February 0.105245E+10 449219.93 0.00 5035760.26 0.00 0.00 0.235029E+10 0.00 0.21
March 0.987785E+09 0.00 0.00 7133332.75 5069134.19 0.00 0.330729E+10 0.00 0.24
April 0.279067E+09 478170.12 0.00 12349130.41 2591110.78 0.00 0.426178E+10 0.00 0.36
May 0.316038E+09 1726234.52 0.00 14641926.42 244409.16 0.00 0.495963E+10 0.00 0.43
June 0.277423E+09 0.125709E+09 0.00 13778112.66 7640683.80 0.00 0.351573E+10 0.00 0.49
July 0.171661E+09 0.549275E+09 0.00 4154513.74 56063982.28 0.00 0.589934E+09 0.00 0.29
August 0.122286E+09 0.636575E+09 0.00 3634079.79 66882272.41 0.00 0.509320E+09 0.00 0.30
September 0.236025E+09 0.231293E+09 0.00 10996260.05 25804392.22 0.00 0.244456E+10 0.00 0.40
October 0.265709E+09 0.510261E+09 0.00 9264868.40 63733577.70 0.00 0.228734E+10 0.00 0.38
November 0.613415E+09 0.00 0.00 7954930.05 1215789.73 0.00 0.328253E+10 0.00 0.26
December 0.118453E+10 0.00 0.00 4815525.64 0.00 0.00 0.179187E+10 0.00 0.19
                   
Annual Sum or Average 0.711033E+10 0.205596E+10 0.00 97753452.94 0.229259E+09 155969.89 0.308755E+11 0.00 0.31
Minimum of Months 0.122286E+09 0.00 0.00 3634079.79 0.00 0.00 0.509320E+09 0.00 0.19
Maximum of Months 0.160395E+10 0.636575E+09 0.00 14641926.42 66882272.41 155969.89 0.495963E+10 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.110639E+10 216751.20 0.00 566414.92 8038.93 0.558810E+09 92446754.60 0.00 0.34
February 0.100264E+10 216520.90 0.00 255030.53 0.00 0.664152E+09 79938559.83 0.00 0.33
March 0.103780E+10 0.00 0.00 149415.46 2910609.06 0.107170E+10 42921821.73 0.00 0.35
April 0.103738E+10 234394.51 0.00 389448.56 1487770.94 0.386717E+09 85469254.29 0.00 0.36
May 0.120459E+10 334928.12 0.00 163657.94 247838.32 0.365323E+09 50019059.84 0.00 0.39
June 0.906420E+09 20304423.36 0.00 113964.79 10948262.76 0.175443E+09 30217556.32 0.00 0.42
July 0.254380E+09 0.141852E+09 11589.09 9549.78 0.105187E+09 67380372.37 1452780.36 7489.51 0.35
August 0.217874E+09 0.196976E+09 190935.14 87453.30 0.116725E+09 64224813.54 10871891.22 28169.13 0.38
September 0.511730E+09 91153474.95 78985.06 860728.16 28590629.47 0.121209E+09 0.226041E+09 4714.52 0.41
October 0.450139E+09 0.232348E+09 0.00 1868769.79 43314587.50 0.166749E+09 0.350259E+09 0.00 0.47
November 0.121222E+10 8916.99 0.00 789417.01 689258.76 0.397608E+09 0.197518E+09 0.00 0.38
December 0.924270E+09 0.00 0.00 1235758.67 0.00 0.502050E+09 0.244325E+09 0.00 0.35
                   
Annual Sum or Average 0.986583E+10 0.683645E+09 281509.29 6489608.90 0.310109E+09 0.454137E+10 0.141148E+10 40373.15 0.38
Minimum of Months 0.217874E+09 0.00 0.00 9549.78 0.00 64224813.54 1452780.36 0.00 0.33
Maximum of Months 0.121222E+10 0.232348E+09 190935.14 1868769.79 0.116725E+09 0.107170E+10 0.350259E+09 28169.13 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.713900E+09 9028.71 0.00 526790.22 38079.59 0.00 0.164046E+09 0.00 0.11
February 0.639677E+09 88893.35 0.00 631634.20 0.00 0.00 0.237278E+09 0.00 0.12
March 0.802761E+09 0.00 0.00 780303.50 1574697.54 0.00 0.284678E+09 0.00 0.13
April 0.303978E+09 709015.56 0.00 2759244.28 455062.86 0.00 0.680330E+09 0.00 0.17
May 0.268065E+09 378022.10 0.00 3325052.29 75924.31 0.00 0.845738E+09 0.00 0.20
June 0.128540E+09 32922610.56 0.00 4155321.36 1035538.96 0.00 0.679630E+09 0.00 0.24
July 0.122183E+09 84394934.41 0.00 1151901.68 33936002.93 0.00 58276958.45 0.00 0.13
August 0.127706E+09 89672334.92 0.00 510983.93 52945265.37 0.00 23961804.21 0.00 0.14
September 0.132966E+09 55361969.09 0.00 3038800.34 5725548.12 0.00 0.442636E+09 0.00 0.20
October 0.206848E+09 0.120416E+09 0.00 2207242.09 13691009.78 0.00 0.348483E+09 0.00 0.18
November 0.520260E+09 0.00 0.00 1386796.99 377678.13 0.00 0.421504E+09 0.00 0.13
December 0.654959E+09 0.00 0.00 407028.63 0.00 0.00 0.142413E+09 0.00 0.11
                   
Annual Sum or Average 0.462184E+10 0.383953E+09 0.00 20881099.50 0.109855E+09 0.00 0.432898E+10 0.00 0.15
Minimum of Months 0.122183E+09 0.00 0.00 407028.63 0.00 0.00 23961804.21 0.00 0.11
Maximum of Months 0.802761E+09 0.120416E+09 0.00 4155321.36 52945265.37 0.00 0.845738E+09 0.00 0.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BATH_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.905138E+09 0.00 0.00 0.00 48683.51 0.00 0.00 0.00 0.15
February 0.906202E+09 0.00 0.00 0.00 73217.14 0.00 0.00 0.00 0.16
March 0.110033E+10 0.00 0.00 3109.72 1654928.93 0.00 2950649.01 0.00 0.16
April 0.674334E+09 25057.34 0.00 502946.32 877595.76 0.00 0.133530E+09 0.00 0.17
May 0.681913E+09 242063.98 0.00 783731.65 79792.68 0.00 0.204213E+09 0.00 0.20
June 0.427617E+09 14565207.69 0.00 1116836.86 4217197.41 0.00 0.201745E+09 0.00 0.23
July 0.159100E+09 22627194.14 0.00 286262.88 90973136.29 0.00 17816743.24 0.00 0.17
August 0.151901E+09 18198123.58 0.00 118996.77 0.120541E+09 0.00 5464955.71 0.00 0.19
September 0.357466E+09 17474500.66 0.00 553123.31 24552070.60 0.00 0.103266E+09 0.00 0.19
October 0.426099E+09 50706442.55 0.00 167446.55 35526957.55 0.00 39938517.33 0.00 0.18
November 0.925571E+09 0.00 0.00 0.00 396920.96 0.00 0.00 0.00 0.17
December 0.832267E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
                   
Annual Sum or Average 0.754794E+10 0.123839E+09 0.00 3532454.06 0.278942E+09 0.00 0.708924E+09 0.00 0.18
Minimum of Months 0.151901E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
Maximum of Months 0.110033E+10 50706442.55 0.00 1116836.86 0.120541E+09 0.00 0.204213E+09 0.00 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: OFFICES_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.633918E+09 476421.84 0.00 13217659.10 16040.67 0.00 0.489757E+10 0.00 0.44
February 0.612439E+09 861295.05 0.00 11058772.75 0.00 0.00 0.471122E+10 0.00 0.43
March 0.913552E+09 1154941.59 0.00 11840675.78 5519547.88 0.00 0.503632E+10 0.00 0.43
April 0.315232E+09 1429610.34 0.00 15992744.55 2726418.10 0.00 0.539652E+10 0.00 0.58
May 0.387855E+09 1962676.95 0.00 16086124.46 280021.74 0.00 0.549470E+10 0.00 0.60
June 0.320854E+09 0.171503E+09 0.00 15672696.93 8450432.86 0.00 0.389641E+10 0.00 0.71
July 0.182028E+09 0.820948E+09 0.00 5763622.68 58867519.90 0.00 0.756725E+09 0.00 0.48
August 0.124097E+09 0.108513E+10 0.00 5790068.17 66765032.81 0.00 0.712948E+09 0.00 0.55
September 0.231638E+09 0.327752E+09 0.00 16034670.28 23336815.96 0.00 0.333767E+10 0.00 0.70
October 0.269956E+09 0.732707E+09 0.00 14081038.99 55372081.64 0.00 0.325494E+10 0.00 0.65
November 0.302770E+09 23322.19 0.00 17181604.10 1375328.57 0.00 0.616217E+10 0.00 0.55
December 0.455911E+09 0.00 0.00 13917302.87 0.00 0.00 0.465987E+10 0.00 0.44
                   
Annual Sum or Average 0.475025E+10 0.314395E+10 0.00 0.156637E+09 0.222709E+09 0.00 0.483171E+11 0.00 0.55
Minimum of Months 0.124097E+09 0.00 0.00 5763622.68 0.00 0.00 0.712948E+09 0.00 0.43
Maximum of Months 0.913552E+09 0.108513E+10 0.00 17181604.10 66765032.81 0.00 0.616217E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GYM_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120433E+10 854877.97 0.00 13796628.25 0.00 0.00 0.826543E+10 0.00 0.70
February 0.930564E+09 385915.95 0.00 12771562.85 0.00 0.00 0.853492E+10 0.00 0.71
March 0.166833E+10 996942.39 0.00 15016836.72 0.00 0.00 0.970953E+10 0.00 0.75
April 87173145.48 23065321.10 0.00 22675783.47 0.00 0.00 0.830865E+10 0.00 0.86
May 23438656.69 5528342.27 0.00 26578435.11 0.00 0.00 0.905666E+10 0.00 0.94
June 0.00 0.354408E+09 0.00 26747814.07 0.00 0.00 0.611545E+10 0.00 1.05
July 79383.51 0.134367E+10 0.00 18282272.05 0.00 0.00 0.269381E+10 0.00 0.93
August 0.00 0.152593E+10 0.00 16232290.02 235.92 0.00 0.293288E+10 0.00 1.03
September 2406135.70 0.449047E+09 0.00 22510043.34 0.00 0.00 0.487051E+10 0.00 0.92
October 7955726.71 0.648575E+09 0.00 20074581.62 0.00 0.00 0.507465E+10 0.00 0.89
November 0.238970E+09 0.00 0.00 17983599.41 0.00 0.00 0.995370E+10 0.00 0.82
December 0.740052E+09 0.00 0.00 13867284.38 0.00 0.00 0.811470E+10 0.00 0.68
                   
Annual Sum or Average 0.490330E+10 0.435246E+10 0.00 0.226537E+09 235.92 0.00 0.836309E+11 0.00 0.86
Minimum of Months 0.00 0.00 0.00 12771562.85 0.00 0.00 0.269381E+10 0.00 0.68
Maximum of Months 0.166833E+10 0.152593E+10 0.00 26747814.07 235.92 0.00 0.995370E+10 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 52612137.55 0.00 0.00 0.177992E+11 0.00 2.16
February 0.00 0.00 0.00 47555186.19 0.00 0.00 0.169199E+11 0.00 2.25
March 0.00 376909.02 0.00 56821760.82 0.00 0.00 0.194873E+11 0.00 2.37
April 0.00 158608.22 0.00 56348410.15 0.00 0.00 0.152129E+11 0.00 2.57
May 0.00 0.00 0.00 59017900.80 0.00 0.00 0.162820E+11 0.00 2.75
June 10214.64 0.119997E+09 0.00 54761880.46 0.00 0.00 0.115499E+11 0.00 2.99
July 11686.09 0.623037E+09 0.00 43648041.43 0.00 0.00 0.727340E+10 0.00 2.66
August 5781.62 0.752030E+09 0.00 41053161.77 0.00 0.00 0.682533E+10 0.00 2.88
September 0.00 0.210551E+09 0.00 53138568.34 0.00 0.00 0.983552E+10 0.00 2.86
October 0.00 0.495238E+09 0.00 54315191.25 0.00 0.00 0.110779E+11 0.00 2.68
November 0.00 0.00 0.00 54120778.90 0.00 0.00 0.175243E+11 0.00 2.41
December 36099.64 0.00 0.00 51677328.93 0.00 0.00 0.174285E+11 0.00 2.09
                   
Annual Sum or Average 63781.99 0.220139E+10 0.00 0.625070E+09 0.00 0.00 0.167216E+12 0.00 2.56
Minimum of Months 0.00 0.00 0.00 41053161.77 0.00 0.00 0.682533E+10 0.00 2.09
Maximum of Months 36099.64 0.752030E+09 0.00 59017900.80 0.00 0.00 0.194873E+11 0.00 2.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFETERIA_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.756056E+10 0.00 0.00 16892235.43 0.00 28070645.96 0.127314E+11 0.00 1.56
February 0.700216E+10 0.00 0.00 14497904.39 0.00 12532682.76 0.120837E+11 0.00 1.56
March 0.863976E+10 0.00 0.00 17804771.98 0.00 19434301.21 0.152536E+11 0.00 1.72
April 0.299628E+10 126749.26 0.00 23388630.56 0.00 4033298.21 0.129409E+11 0.00 1.56
May 0.237959E+10 0.00 0.00 27886291.91 0.00 2073161.37 0.150610E+11 0.00 1.67
June 0.163465E+10 5669693.18 0.00 31567720.82 0.00 0.00 0.108799E+11 0.00 1.84
July 0.140358E+10 0.134362E+10 0.00 10360133.54 0.00 0.00 0.272227E+10 0.00 1.57
August 0.178867E+10 0.143588E+10 0.00 9961771.24 0.00 0.00 0.279246E+10 0.00 1.78
September 0.149098E+10 0.340640E+09 0.00 25486821.44 0.00 0.00 0.841048E+10 0.00 1.67
October 0.138281E+10 0.318194E+09 0.00 26215701.89 0.00 0.00 0.924069E+10 0.00 1.68
November 0.558891E+10 0.00 0.00 19322520.79 0.00 4881077.19 0.136340E+11 0.00 1.61
December 0.685197E+10 94360.07 0.00 16845056.56 0.00 17338770.17 0.120074E+11 0.00 1.48
                   
Annual Sum or Average 0.487199E+11 0.344423E+10 0.00 0.240230E+09 0.00 88363936.88 0.127758E+12 0.00 1.64
Minimum of Months 0.138281E+10 0.00 0.00 9961771.24 0.00 0.00 0.272227E+10 0.00 1.48
Maximum of Months 0.863976E+10 0.143588E+10 0.00 31567720.82 0.00 28070645.96 0.152536E+11 0.00 1.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.227587E+10 415052.30 0.00 9932673.80 28977.68 1510273.17 0.420152E+10 0.00 0.55
February 0.181072E+10 812756.07 0.00 10006783.45 0.00 0.00 0.489467E+10 0.00 0.57
March 0.182994E+10 0.00 0.00 13210862.92 10491778.15 0.00 0.645877E+10 0.00 0.62
April 0.595483E+09 869371.00 0.00 18906032.29 5343569.44 0.00 0.681038E+10 0.00 0.80
May 0.662958E+09 2607000.83 0.00 21955548.34 505862.86 0.00 0.770358E+10 0.00 0.92
June 0.560728E+09 0.188531E+09 0.00 20383557.47 15703960.66 0.00 0.529480E+10 0.00 1.03
July 0.456902E+09 0.809041E+09 0.00 4835689.01 0.111510E+09 0.00 0.748546E+09 0.00 0.60
August 0.437783E+09 0.971146E+09 0.00 3427373.06 0.134590E+09 0.00 0.593495E+09 0.00 0.63
September 0.522416E+09 0.377209E+09 0.00 15599295.13 53311235.57 0.00 0.356914E+10 0.00 0.85
October 0.565862E+09 0.775170E+09 0.00 13852164.10 0.130259E+09 0.00 0.358045E+10 0.00 0.82
November 0.125739E+10 0.00 0.00 13953705.53 2516365.85 0.00 0.607972E+10 0.00 0.67
December 0.203478E+10 0.00 0.00 10443329.60 0.00 0.00 0.398918E+10 0.00 0.53
                   
Annual Sum or Average 0.130108E+11 0.312580E+10 0.00 0.156507E+09 0.464261E+09 1510273.17 0.539243E+11 0.00 0.71
Minimum of Months 0.437783E+09 0.00 0.00 3427373.06 0.00 0.00 0.593495E+09 0.00 0.53
Maximum of Months 0.227587E+10 0.971146E+09 0.00 21955548.34 0.134590E+09 1510273.17 0.770358E+10 0.00 1.03



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 11:18:23

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.398752E+12 0.944344E+10 0.109056E+12 0.444502E+12 0.102209E+12
February 0.528766E+12 0.100705E+11 0.975035E+11 0.428801E+12 0.713355E+11
March 0.787148E+12 0.111232E+11 0.110897E+12 0.446817E+12 0.829898E+11
April 0.110320E+13 0.708613E+10 0.811767E+11 0.447809E+12 0.138050E+12
May 0.116442E+13 0.753560E+10 0.829377E+11 0.460244E+12 0.152219E+12
June 0.117572E+13 0.419890E+10 0.561588E+11 0.354898E+12 0.223047E+12
July 0.126696E+13 0.107268E+10 0.355629E+11 0.175834E+12 0.256145E+12
August 0.114934E+13 0.106959E+10 0.318975E+11 0.119705E+12 0.288889E+12
September 0.879358E+12 0.331696E+10 0.565373E+11 0.305841E+12 0.250968E+12
October 0.561156E+12 0.513366E+10 0.662485E+11 0.351985E+12 0.304898E+12
November 0.448356E+12 0.922032E+10 0.114077E+12 0.479179E+12 0.111480E+12
December 0.330890E+12 0.976013E+10 0.126388E+12 0.479513E+12 0.113620E+12
           
Annual Sum or Average 0.979407E+13 0.790311E+11 0.968441E+12 0.449513E+13 0.209585E+13
Minimum of Months 0.330890E+12 0.106959E+10 0.318975E+11 0.119705E+12 0.713355E+11
Maximum of Months 0.126696E+13 0.111232E+11 0.126388E+12 0.479513E+12 0.304898E+12