Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2018-10-19 09:20:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1587.90 | 506.57 | 562.29 |
Net Site Energy | 1587.90 | 506.57 | 562.29 |
Total Source Energy | 5000.96 | 1595.40 | 1770.89 |
Net Source Energy | 5000.96 | 1595.40 | 1770.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 323.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 320.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1574.49 | 13.41 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 323.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 214.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 320.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 304.06 | 4.75 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 557.55 | 4.75 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 273.93 | 4.28 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 502.29 | 4.28 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1574.49 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1574.49 | 100.00 |
Total On-Site and Utility Electric Sources | 1574.49 | 100.00 |
Total Electricity End Uses | 1574.49 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 18.50 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3455.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-17:15 | 05-FEB-07:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 38133.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29077.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6799.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18649.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89555.69 | 38133.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 38133.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29077.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6799.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18649.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 14.54 | 0.00 | 0.00 | 0.00 |
Cooling | 1025.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 679.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1014.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4986.42 | 14.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5.15 | 0.00 | 0.00 | 0.00 |
Cooling | 363.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 359.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1765.75 | 5.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5.15 | 0.00 | 0.00 | 0.00 |
Cooling | 363.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 359.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1765.75 | 5.15 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.72_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 4.600 | 0.293 | 0.130 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 4.600 | 0.293 | 0.130 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 112.97 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 193.95 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.69 | 83.69 | 39.40 | |
Exterior Lighting Total | 2508.33 | 39.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4054.30 | 2923.03 | 1131.27 | 0.72 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3846.04 | 2771.27 | 1074.77 | 0.72 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8132.61 | 6291.51 | 1841.10 | 0.77 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3282.18 | 2341.40 | 940.78 | 0.71 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2460.78 | 1687.47 | 773.31 | 0.69 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2449.65 | 1678.60 | 771.05 | 0.69 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2802.34 | 1928.13 | 874.21 | 0.69 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2843.95 | 1962.85 | 881.11 | 0.69 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9396.21 | 6876.79 | 2519.42 | 0.73 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8965.32 | 6542.51 | 2422.81 | 0.73 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8534.78 | 6204.23 | 2330.55 | 0.73 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7805.83 | 5646.03 | 2159.80 | 0.72 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5858.42 | 4108.09 | 1750.33 | 0.70 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5840.76 | 4093.95 | 1746.81 | 0.70 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6651.35 | 4672.74 | 1978.60 | 0.70 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6666.40 | 4684.83 | 1981.57 | 0.70 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5811.65 | 4306.40 | 1505.25 | 0.74 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5509.95 | 4074.86 | 1435.09 | 0.74 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5255.92 | 3843.91 | 1412.01 | 0.73 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4669.01 | 3407.56 | 1261.44 | 0.73 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3750.35 | 2668.73 | 1081.61 | 0.71 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3756.55 | 2671.17 | 1085.38 | 0.71 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4377.40 | 3166.85 | 1210.56 | 0.72 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4388.37 | 3175.47 | 1212.90 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3902.4 | 3.27 | 11.14 | 11.60 | 11.07 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3702.1 | 3.27 | 11.15 | 11.60 | 11.07 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7773.5 | 3.17 | 10.82 | 11.25 | 10.59 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3162.4 | 3.28 | 11.19 | 11.65 | 11.14 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2379.6 | 3.33 | 11.37 | 11.85 | 11.41 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2369.0 | 3.33 | 11.37 | 11.85 | 11.42 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2709.1 | 3.33 | 11.35 | 11.83 | 11.39 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2748.5 | 3.32 | 11.34 | 11.82 | 11.37 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9031.1 | 3.25 | 11.07 | 11.53 | 10.97 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8619.4 | 3.25 | 11.09 | 11.54 | 10.99 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8208.5 | 3.25 | 11.11 | 11.56 | 11.01 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7511.0 | 3.26 | 11.13 | 11.59 | 11.05 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5653.6 | 3.30 | 11.27 | 11.74 | 11.26 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5636.8 | 3.30 | 11.27 | 11.74 | 11.26 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6417.7 | 3.30 | 11.26 | 11.73 | 11.25 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6432.0 | 3.30 | 11.26 | 11.73 | 11.24 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5579.1 | 3.23 | 11.02 | 11.47 | 10.88 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5290.5 | 3.23 | 11.03 | 11.48 | 10.90 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5052.0 | 3.25 | 11.08 | 11.53 | 10.97 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4488.8 | 3.25 | 11.09 | 11.54 | 10.99 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3614.3 | 3.28 | 11.20 | 11.67 | 11.16 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3620.5 | 3.28 | 11.21 | 11.67 | 11.16 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4212.0 | 3.26 | 11.13 | 11.58 | 11.05 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4222.5 | 3.26 | 11.13 | 11.58 | 11.04 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1476.43 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 2771.00 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 2849.07 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 1902.87 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 1917.66 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 1902.87 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 1917.66 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 1433.51 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 1433.51 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 1424.54 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 216.37 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.96 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 512.82 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.57 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 115.37 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 114.62 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 132.57 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 135.66 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 520.30 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 492.96 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 464.85 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 419.94 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 291.37 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.17 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.39 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 333.42 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.57 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 312.89 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.54 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.79 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.68 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.63 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 235.61 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 236.33 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2053.77 | 2464.53 | 0.161 | 0.193 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 32.95 | 0.01651 |
G NW APARTMENT | 1945.49 | 2334.59 | 0.152 | 0.183 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
OFFICE | 4633.70 | 5560.44 | 0.382 | 0.458 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 30.23 | 0.01651 |
G NE APARTMENT | 1619.01 | 1942.81 | 0.127 | 0.152 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
G N1 APARTMENT | 1095.18 | 1314.21 | 0.086 | 0.103 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
G N2 APARTMENT | 1088.07 | 1305.68 | 0.085 | 0.102 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
G S1 APARTMENT | 1258.41 | 1510.09 | 0.099 | 0.118 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
G S2 APARTMENT | 1287.72 | 1545.27 | 0.101 | 0.121 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70 | 0.01651 |
M SW APARTMENT | 4938.61 | 5926.34 | 0.387 | 0.465 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
M NW APARTMENT | 4679.24 | 5615.09 | 0.367 | 0.440 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 32.40 | 0.01651 |
M SE APARTMENT | 4412.27 | 5294.72 | 0.346 | 0.415 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
M NE APARTMENT | 3985.95 | 4783.14 | 0.312 | 0.375 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 31.49 | 0.01651 |
M N1 APARTMENT | 2765.75 | 3318.91 | 0.217 | 0.260 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
M N2 APARTMENT | 2754.35 | 3305.22 | 0.216 | 0.259 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
M S1 APARTMENT | 3155.09 | 3786.10 | 0.247 | 0.297 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
M S2 APARTMENT | 3164.87 | 3797.84 | 0.248 | 0.298 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
T SW APARTMENT | 3147.12 | 3776.54 | 0.247 | 0.296 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 33.27 | 0.01651 |
T NW APARTMENT | 2969.79 | 3563.75 | 0.233 | 0.279 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
T SE APARTMENT | 2757.62 | 3309.14 | 0.216 | 0.259 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
T NE APARTMENT | 2437.25 | 2924.70 | 0.191 | 0.229 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
T N1 APARTMENT | 1838.38 | 2206.05 | 0.144 | 0.173 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
T N2 APARTMENT | 1837.96 | 2205.56 | 0.144 | 0.173 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.78 | 0.01651 |
T S1 APARTMENT | 2236.42 | 2683.71 | 0.175 | 0.210 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 33.90 | 0.01651 |
T S2 APARTMENT | 2243.23 | 2691.87 | 0.176 | 0.211 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90 | 0.01651 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 641.90 | 770.28 | 0.018 | 0.027 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
G NW APARTMENT | 650.05 | 780.07 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
OFFICE | 1735.66 | 2082.79 | 0.048 | 0.057 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60 | 0.00526 |
G NE APARTMENT | 650.05 | 780.07 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
G N1 APARTMENT | 320.53 | 384.64 | 0.009 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
G N2 APARTMENT | 320.53 | 384.64 | 0.009 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
G S1 APARTMENT | 313.87 | 376.65 | 0.009 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
G S2 APARTMENT | 374.20 | 449.05 | 0.011 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M SW APARTMENT | 1037.26 | 1244.72 | 0.030 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M NW APARTMENT | 1061.59 | 1273.91 | 0.031 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M SE APARTMENT | 1037.26 | 1244.72 | 0.030 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M NE APARTMENT | 1061.59 | 1273.91 | 0.031 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M N1 APARTMENT | 208.71 | 250.45 | 0.006 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M N2 APARTMENT | 208.71 | 250.45 | 0.006 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M S1 APARTMENT | 170.67 | 204.81 | 0.005 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
M S2 APARTMENT | 170.67 | 204.81 | 0.005 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T SW APARTMENT | 1155.44 | 1386.52 | 0.033 | 0.040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T NW APARTMENT | 1167.95 | 1401.54 | 0.034 | 0.040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T SE APARTMENT | 1155.44 | 1386.52 | 0.033 | 0.040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T NE APARTMENT | 1167.95 | 1401.54 | 0.034 | 0.040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T N1 APARTMENT | 758.51 | 910.22 | 0.022 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T N2 APARTMENT | 758.51 | 910.22 | 0.022 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T S1 APARTMENT | 745.51 | 894.61 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
T S2 APARTMENT | 745.51 | 894.61 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 4.60 | 0.00526 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.19 | 0.19 | 0.03 | 0.03 |
SPLIT GNW | 0.18 | 0.18 | 0.03 | 0.03 |
SPLIT OFFICE | 0.46 | 0.46 | 0.06 | 0.06 |
SPLIT GNE | 0.15 | 0.15 | 0.03 | 0.03 |
SPLIT GN1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GN2 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT MSW | 0.46 | 0.46 | 0.05 | 0.05 |
SPLIT MNW | 0.44 | 0.44 | 0.05 | 0.05 |
SPLIT MSE | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT MNE | 0.37 | 0.37 | 0.05 | 0.05 |
SPLIT MN1 | 0.26 | 0.26 | 0.05 | 0.05 |
SPLIT MN2 | 0.26 | 0.26 | 0.05 | 0.05 |
SPLIT MS1 | 0.30 | 0.30 | 0.05 | 0.05 |
SPLIT MS2 | 0.30 | 0.30 | 0.05 | 0.05 |
SPLIT TSW | 0.30 | 0.30 | 0.04 | 0.04 |
SPLIT TNW | 0.28 | 0.28 | 0.04 | 0.04 |
SPLIT TSE | 0.26 | 0.26 | 0.04 | 0.04 |
SPLIT TNE | 0.23 | 0.23 | 0.04 | 0.04 |
SPLIT TN1 | 0.17 | 0.17 | 0.03 | 0.03 |
SPLIT TN2 | 0.17 | 0.17 | 0.03 | 0.03 |
SPLIT TS1 | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT TS2 | 0.21 | 0.21 | 0.03 | 0.03 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 5750.25 | 5125.25 | 2729.75 |
G NW APARTMENT | 5593.75 | 5750.00 | 2969.25 |
OFFICE | 817.00 | 824.75 | 5.75 |
G NE APARTMENT | 5592.75 | 5676.75 | 2896.75 |
G N1 APARTMENT | 5548.00 | 6135.75 | 3244.75 |
G N2 APARTMENT | 5548.00 | 6132.50 | 3240.50 |
G S1 APARTMENT | 5603.75 | 5311.75 | 2805.50 |
G S2 APARTMENT | 5587.25 | 5417.00 | 2896.50 |
M SW APARTMENT | 6968.00 | 1374.75 | 699.00 |
M NW APARTMENT | 6598.75 | 2148.75 | 848.75 |
M SE APARTMENT | 6947.00 | 1359.50 | 672.25 |
M NE APARTMENT | 6570.50 | 2126.00 | 810.50 |
M N1 APARTMENT | 6580.50 | 1759.75 | 592.00 |
M N2 APARTMENT | 6578.75 | 1763.50 | 590.00 |
M S1 APARTMENT | 6928.25 | 901.50 | 474.50 |
M S2 APARTMENT | 6927.75 | 905.25 | 476.25 |
T SW APARTMENT | 6673.50 | 2719.00 | 1375.75 |
T NW APARTMENT | 6404.75 | 3329.00 | 1546.00 |
T SE APARTMENT | 6669.25 | 2665.00 | 1320.25 |
T NE APARTMENT | 6378.50 | 3367.50 | 1544.25 |
T N1 APARTMENT | 6357.00 | 3188.25 | 1350.25 |
T N2 APARTMENT | 6354.00 | 3182.50 | 1346.00 |
T S1 APARTMENT | 6694.25 | 2437.25 | 1209.50 |
T S2 APARTMENT | 6692.25 | 2441.00 | 1213.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 7144.25 | 6320.50 | 3455.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G NW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
OFFICE | 0.25 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G N1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G N2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
G S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
M S2 APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
T SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NE APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T N1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
T N2 APARTMENT | 4.50 | 0.00 | 4.50 | 0.00 |
T S1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 18.50 | 1.00 | 18.50 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.369 | 0.075 | 0.000 | 0.093 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.075 | 0.000 | 0.092 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.521 | 0.087 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.075 | 0.000 | 0.092 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.090 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.090 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.093 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.093 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.108 | 0.000 | 0.113 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.108 | 0.000 | 0.113 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.108 | 0.000 | 0.113 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.108 | 0.000 | 0.113 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.113 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.113 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.113 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.113 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.142 | 0.000 | 0.136 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.142 | 0.000 | 0.136 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.142 | 0.000 | 0.136 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.142 | 0.000 | 0.136 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.086 | 0.000 | 0.136 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.086 | 0.000 | 0.136 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.086 | 0.000 | 0.136 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.086 | 0.000 | 0.136 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.500 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.366 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.366 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 320.37 | 0.00 | 01-JAN-00:15 | 31202.91 | 01-JAN-06:15 |
WaterSystems:Electricity | 320.37 | 0.00 | 01-JAN-00:15 | 31202.91 | 01-JAN-06:15 |
Water Heater:WaterSystems:Electricity | 320.37 | 0.00 | 01-JAN-00:15 | 31202.91 | 01-JAN-06:15 |
Fans:Electricity | 214.43 | 6799.41 | 03-JAN-08:30 | 6799.41 | 03-JAN-17:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
ElectricityPurchased:Plant | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
Cogeneration:ElectricityPurchased | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
ElectricityNet:Plant | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
Cogeneration:ElectricityNet | 1574.49 | 20169.70 | 03-JAN-03:45 | 89555.69 | 09-SEP-17:15 |
ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 538.30 | 6799.41 | 04-JAN-08:30 | 37106.08 | 10-SEP-15:15 |
General:Fans:Electricity | 214.43 | 6799.41 | 03-JAN-08:30 | 6799.41 | 03-JAN-17:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 323.87 | 0.00 | 03-JAN-01:30 | 30306.67 | 10-SEP-15:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 13.41 | 0.00 | 01-JAN-00:15 | 38133.26 | 05-FEB-07:15 |
Gas:HVAC | 13.41 | 0.00 | 01-JAN-00:15 | 38133.26 | 05-FEB-07:15 |
Heating:Gas | 13.41 | 0.00 | 01-JAN-00:15 | 38133.26 | 05-FEB-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2127.35 | 1700.15 | 15-FEB-07:45 | 183107.17 | 10-SEP-15:15 |
EnergyTransfer:Building | 780.53 | 1657.28 | 10-MAR-13:45 | 67000.40 | 10-SEP-15:15 |
EnergyTransfer:Zone:G SW APARTMENT | 16.64 | 0.01 | 30-JAN-05:15 | 2384.65 | 30-AUG-16:15 |
Heating:EnergyTransfer | 6.32 | 0.00 | 01-JAN-16:15 | 15838.15 | 05-FEB-07:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.29 | 0.00 | 01-JAN-00:45 | 717.36 | 05-FEB-07:00 |
Cooling:EnergyTransfer | 774.21 | 727.89 | 10-MAR-12:30 | 67000.40 | 10-SEP-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 16.34 | 0.00 | 01-JAN-00:15 | 2384.65 | 30-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.65 | 0.02 | 25-DEC-16:15 | 2170.39 | 07-JUL-16:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.71 | 0.00 | 01-JAN-04:15 | 868.83 | 05-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 12.93 | 0.00 | 01-JAN-00:15 | 2170.39 | 07-JUL-16:30 |
EnergyTransfer:Zone:OFFICE | 31.90 | 0.15 | 05-DEC-19:45 | 3820.20 | 10-SEP-10:45 |
Heating:EnergyTransfer:Zone:OFFICE | 0.25 | 0.00 | 01-JAN-00:15 | 1608.20 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 31.65 | 0.00 | 01-JAN-02:15 | 3820.20 | 10-SEP-10:45 |
EnergyTransfer:Zone:G NE APARTMENT | 13.64 | 0.00 | 27-OCT-13:15 | 1729.64 | 10-SEP-09:45 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.57 | 0.00 | 01-JAN-00:15 | 808.72 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 13.07 | 0.00 | 01-JAN-09:30 | 1729.64 | 10-SEP-09:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 10.39 | 0.00 | 13-DEC-06:30 | 1285.62 | 18-JUL-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 431.35 | 05-FEB-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 10.17 | 0.00 | 01-JAN-10:15 | 1285.62 | 18-JUL-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 10.39 | 0.00 | 07-FEB-12:30 | 1280.68 | 18-JUL-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 429.70 | 05-FEB-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 10.17 | 0.00 | 01-JAN-10:15 | 1280.68 | 18-JUL-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 13.38 | 0.03 | 07-NOV-07:00 | 1482.76 | 10-SEP-14:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 300.35 | 10-JAN-05:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 13.33 | 0.00 | 05-JAN-03:00 | 1482.76 | 10-SEP-14:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 13.06 | 0.02 | 14-DEC-07:45 | 1495.73 | 10-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 297.85 | 05-FEB-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 13.01 | 0.00 | 05-JAN-02:45 | 1495.73 | 10-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 64.03 | 0.11 | 24-DEC-08:00 | 5931.37 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 117.22 | 08-JAN-12:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 64.02 | 0.00 | 08-JAN-09:15 | 5931.37 | 11-OCT-15:30 |
EnergyTransfer:Zone:M NW APARTMENT | 51.83 | 0.06 | 05-NOV-06:45 | 5217.69 | 07-JUL-16:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 658.65 | 05-FEB-07:45 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 51.76 | 0.00 | 06-JAN-10:45 | 5217.69 | 07-JUL-16:30 |
EnergyTransfer:Zone:M SE APARTMENT | 64.33 | 1.19 | 24-DEC-06:30 | 5355.73 | 09-OCT-11:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 135.29 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 64.33 | 0.00 | 08-JAN-09:30 | 5355.73 | 09-OCT-11:30 |
EnergyTransfer:Zone:M NE APARTMENT | 52.18 | 0.04 | 15-FEB-12:45 | 4259.06 | 10-SEP-10:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 691.82 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 52.14 | 0.00 | 06-JAN-11:00 | 4259.06 | 10-SEP-10:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 44.92 | 3.00 | 11-JAN-12:15 | 3305.14 | 28-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 142.22 | 23-DEC-16:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 44.92 | 0.00 | 11-JAN-12:15 | 3305.14 | 28-JUN-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 44.93 | 1.82 | 11-JAN-12:15 | 3297.31 | 28-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 142.84 | 23-DEC-16:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 44.92 | 0.00 | 11-JAN-12:15 | 3297.31 | 28-JUN-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 57.55 | 140.47 | 08-JAN-09:30 | 4698.49 | 01-JAN-13:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 57.55 | 140.47 | 08-JAN-09:30 | 4698.49 | 01-JAN-13:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 57.56 | 139.87 | 08-JAN-09:30 | 4703.82 | 01-JAN-13:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 57.56 | 139.87 | 08-JAN-09:30 | 4703.82 | 01-JAN-13:45 |
EnergyTransfer:Zone:T SW APARTMENT | 31.99 | 0.00 | 09-NOV-03:30 | 3604.88 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.56 | 0.00 | 01-JAN-00:15 | 1466.39 | 05-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 31.43 | 0.00 | 01-JAN-05:00 | 3604.88 | 11-OCT-15:30 |
EnergyTransfer:Zone:T NW APARTMENT | 27.19 | 0.02 | 25-NOV-09:30 | 3349.26 | 07-JUL-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 1.03 | 0.00 | 01-JAN-00:15 | 1511.10 | 05-FEB-09:15 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 26.17 | 0.00 | 01-JAN-03:15 | 3349.26 | 07-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 32.00 | 0.07 | 01-MAR-05:15 | 3272.17 | 09-OCT-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.50 | 0.00 | 01-JAN-00:15 | 1440.75 | 05-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 31.50 | 0.00 | 01-JAN-05:00 | 3272.17 | 09-OCT-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 27.09 | 0.04 | 08-APR-02:00 | 2682.31 | 22-JUL-16:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.87 | 0.00 | 01-JAN-00:15 | 1468.13 | 05-FEB-02:45 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 26.21 | 0.00 | 01-JAN-02:30 | 2682.31 | 22-JUL-16:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 22.87 | 0.01 | 15-FEB-15:00 | 2215.08 | 22-JUL-16:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 925.30 | 05-FEB-09:15 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 22.54 | 0.00 | 01-JAN-09:00 | 2215.08 | 22-JUL-16:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 22.87 | 0.01 | 31-DEC-12:30 | 2208.33 | 22-JUL-16:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 923.94 | 05-FEB-09:15 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 22.54 | 0.00 | 01-JAN-09:00 | 2208.33 | 22-JUL-16:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 28.07 | 0.13 | 18-JAN-07:15 | 2817.52 | 09-OCT-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 874.27 | 05-FEB-06:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 27.96 | 0.00 | 04-JAN-03:45 | 2817.52 | 09-OCT-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 28.08 | 0.00 | 17-APR-09:00 | 2821.69 | 09-OCT-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 875.85 | 05-FEB-06:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 27.97 | 0.00 | 01-JAN-06:45 | 2821.69 | 09-OCT-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1346.82 | 0.00 | 03-JAN-01:30 | 116106.77 | 10-SEP-15:15 |
HeatingCoils:EnergyTransfer | 10.73 | 0.00 | 01-JAN-00:15 | 30506.60 | 05-FEB-07:15 |
CoolingCoils:EnergyTransfer | 1336.09 | 0.00 | 03-JAN-01:30 | 116106.77 | 10-SEP-15:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.291 | -16.344 | 0.000 | 0.000 | 3.624 | 2.413 | 12.213 | 15.250 | 0.000 | 0.410 | 0.000 | 0.000 | -3.551 | 0.000 | -1.600 | -12.705 |
G NW APARTMENT | 0.711 | -12.934 | 0.000 | 0.000 | 3.653 | 2.413 | 12.213 | 9.611 | 0.000 | 0.408 | 0.000 | 0.000 | -3.604 | 0.000 | -1.473 | -10.998 |
OFFICE | 0.254 | -31.647 | 0.000 | 0.000 | 0.517 | 21.914 | 7.534 | 15.546 | 0.000 | 0.367 | 0.000 | 0.000 | -3.376 | 0.000 | -0.777 | -10.333 |
G NE APARTMENT | 0.570 | -13.074 | 0.000 | 0.000 | 3.662 | 2.413 | 12.213 | 9.594 | 0.000 | 0.408 | 0.000 | 0.000 | -3.460 | 0.000 | -1.464 | -10.862 |
G N1 APARTMENT | 0.221 | -10.168 | 0.000 | 0.000 | 3.665 | 2.413 | 12.213 | 4.190 | 0.000 | 0.283 | 0.000 | 0.000 | -2.192 | 0.000 | -1.112 | -9.513 |
G N2 APARTMENT | 0.219 | -10.174 | 0.000 | 0.000 | 3.666 | 2.413 | 12.213 | 4.189 | 0.000 | 0.283 | 0.000 | 0.000 | -2.191 | 0.000 | -1.111 | -9.507 |
G S1 APARTMENT | 0.042 | -13.333 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 9.861 | 0.000 | 0.283 | 0.000 | 0.000 | -2.132 | 0.000 | -1.276 | -11.693 |
G S2 APARTMENT | 0.054 | -13.011 | 0.000 | 0.000 | 3.623 | 2.413 | 12.213 | 9.866 | 0.000 | 0.283 | 0.000 | 0.000 | -2.125 | 0.000 | -1.275 | -12.041 |
M SW APARTMENT | 0.003 | -64.023 | 0.000 | 0.000 | 3.538 | 2.413 | 12.213 | 14.668 | 0.000 | 0.569 | 37.021 | 0.000 | -4.178 | 0.000 | -2.224 | 0.000 |
M NW APARTMENT | 0.062 | -51.764 | 0.000 | 0.000 | 3.560 | 2.413 | 12.213 | 9.104 | 0.000 | 0.566 | 30.345 | 0.000 | -4.307 | 0.000 | -2.191 | 0.000 |
M SE APARTMENT | 0.001 | -64.327 | 0.000 | 0.000 | 3.540 | 2.413 | 12.213 | 14.703 | 0.000 | 0.569 | 37.221 | 0.000 | -4.110 | 0.000 | -2.223 | 0.000 |
M NE APARTMENT | 0.043 | -52.138 | 0.000 | 0.000 | 3.564 | 2.413 | 12.213 | 9.057 | 0.000 | 0.566 | 30.616 | 0.000 | -4.148 | 0.000 | -2.186 | 0.000 |
M N1 APARTMENT | 0.003 | -44.917 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 3.886 | 0.000 | 0.386 | 26.900 | 0.000 | -2.716 | 0.000 | -1.717 | 0.000 |
M N2 APARTMENT | 0.003 | -44.923 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 3.886 | 0.000 | 0.386 | 26.905 | 0.000 | -2.715 | 0.000 | -1.717 | 0.000 |
M S1 APARTMENT | 0.000 | -57.550 | 0.000 | 0.000 | 3.528 | 2.413 | 12.213 | 9.487 | 0.000 | 0.388 | 33.783 | 0.000 | -2.523 | 0.000 | -1.739 | 0.000 |
M S2 APARTMENT | 0.000 | -57.558 | 0.000 | 0.000 | 3.528 | 2.413 | 12.213 | 9.487 | 0.000 | 0.388 | 33.790 | 0.000 | -2.522 | 0.000 | -1.739 | 0.000 |
T SW APARTMENT | 0.558 | -31.427 | 0.000 | 0.000 | 3.581 | 2.413 | 12.213 | 14.377 | 0.000 | 0.741 | 4.177 | 0.000 | -3.952 | 0.000 | -2.680 | -0.000 |
T NW APARTMENT | 1.026 | -26.166 | 0.000 | 0.000 | 3.602 | 2.413 | 12.213 | 8.892 | 0.000 | 0.737 | 3.941 | 0.000 | -4.051 | 0.000 | -2.606 | -0.000 |
T SE APARTMENT | 0.498 | -31.503 | 0.000 | 0.000 | 3.585 | 2.413 | 12.213 | 14.411 | 0.000 | 0.741 | 4.208 | 0.000 | -3.885 | 0.000 | -2.680 | -0.000 |
T NE APARTMENT | 0.873 | -26.214 | 0.000 | 0.000 | 3.609 | 2.413 | 12.213 | 8.867 | 0.000 | 0.737 | 4.016 | 0.000 | -3.909 | 0.000 | -2.605 | -0.000 |
T N1 APARTMENT | 0.328 | -22.541 | 0.000 | 0.000 | 3.600 | 2.413 | 12.213 | 3.810 | 0.000 | 0.501 | 4.178 | 0.000 | -2.515 | 0.000 | -1.987 | -0.000 |
T N2 APARTMENT | 0.330 | -22.544 | 0.000 | 0.000 | 3.600 | 2.413 | 12.213 | 3.809 | 0.000 | 0.501 | 4.178 | 0.000 | -2.513 | 0.000 | -1.987 | -0.000 |
T S1 APARTMENT | 0.114 | -27.955 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 9.319 | 0.000 | 0.505 | 4.288 | 0.000 | -2.400 | 0.000 | -2.068 | -0.000 |
T S2 APARTMENT | 0.116 | -27.965 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 9.318 | 0.000 | 0.505 | 4.296 | 0.000 | -2.399 | 0.000 | -2.068 | -0.000 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.219 | 0.000 | 0.035 | 0.000 | 0.000 | -0.467 | 0.000 | -0.356 | -16.501 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.806 | 0.000 | 2.445 | 0.000 | 0.000 | -0.971 | 0.000 | -9.190 | -16.424 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.231 | 0.000 | 0.032 | 0.000 | 0.000 | -0.517 | 0.000 | -0.296 | -16.519 |
Total Facility | 6.319 | -774.199 | 0.000 | 0.000 | 83.107 | 128.627 | 294.692 | 226.441 | 0.000 | 14.020 | 289.864 | 0.000 | -77.428 | 0.000 | -54.348 | -137.096 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-16:15 | 0.00 | -2386.18 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2132.08 | 0.00 | 50.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -614.26 |
G NW APARTMENT | 07-JUL-16:30 | 0.00 | -2170.37 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1964.71 | 0.00 | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -671.53 |
OFFICE | 10-SEP-10:45 | 0.00 | -3820.07 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2223.82 | 0.00 | 62.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -700.37 |
G NE APARTMENT | 10-SEP-09:45 | 0.00 | -1729.44 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1750.64 | 0.00 | 73.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -570.33 |
G N1 APARTMENT | 18-JUL-17:30 | 0.00 | -1285.73 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 542.09 | 0.00 | 30.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211.89 |
G N2 APARTMENT | 18-JUL-17:30 | 0.00 | -1280.79 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 542.17 | 0.00 | 30.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -216.90 |
G S1 APARTMENT | 10-SEP-14:15 | 0.00 | -1482.63 | 0.00 | 0.00 | 40.66 | 50.41 | 400.26 | 1161.48 | 0.00 | 32.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -202.55 |
G S2 APARTMENT | 10-SEP-13:30 | 0.00 | -1495.63 | 0.00 | 0.00 | 40.71 | 28.81 | 382.60 | 1301.20 | 0.00 | 36.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -294.34 |
M SW APARTMENT | 11-OCT-15:30 | 0.00 | -5931.51 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2435.71 | 0.00 | 99.78 | 2775.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 07-JUL-16:30 | 0.00 | -5217.70 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1937.27 | 0.00 | 85.72 | 2377.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 09-OCT-11:30 | 0.00 | -5355.54 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2248.31 | 0.00 | 182.18 | 2449.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 10-SEP-10:00 | 0.00 | -4259.12 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1680.31 | 0.00 | 111.72 | 1991.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 28-JUN-17:23 | 0.00 | -3305.28 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 593.12 | 0.00 | 64.00 | 1723.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 28-JUN-17:23 | 0.00 | -3297.47 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 593.16 | 0.00 | 64.00 | 1715.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 01-JAN-13:45 | 0.00 | -4697.86 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2133.02 | 0.00 | 27.11 | 2079.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 01-JAN-13:45 | 0.00 | -4703.19 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2132.98 | 0.00 | 27.11 | 2085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 11-OCT-15:30 | 0.00 | -3605.02 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2380.11 | 0.00 | 131.12 | 473.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 07-JUL-16:30 | 0.00 | -3349.30 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1889.95 | 0.00 | 112.89 | 529.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 09-OCT-13:30 | 0.00 | -3272.39 | 0.00 | 0.00 | 40.76 | 28.81 | 382.60 | 1957.55 | 0.00 | 263.71 | 598.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 22-JUL-16:23 | 0.00 | -2682.41 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1002.39 | 0.00 | 54.96 | 807.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 22-JUL-16:23 | 0.00 | -2215.47 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 629.43 | 0.00 | 33.15 | 735.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 22-JUL-16:23 | 0.00 | -2208.72 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 629.52 | 0.00 | 33.15 | 728.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 09-OCT-13:30 | 0.00 | -2817.58 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1701.64 | 0.00 | 159.05 | 504.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 09-OCT-13:30 | 0.00 | -2821.75 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1701.56 | 0.00 | 159.05 | 508.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-SEP-15:15 | 0.00 | -66996.10 | 0.00 | 0.00 | 1192.00 | 5565.24 | 11658.39 | 27035.11 | 0.00 | 1881.04 | 19664.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 26-JAN-07:01 | 1188.28 | 0.00 | 0.00 | 0.00 | 162.90 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.40 | 0.00 | -96.16 | -1158.85 |
G NW APARTMENT | 05-FEB-08:17 | 883.19 | 0.00 | 0.00 | 0.00 | 74.14 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -744.69 | 0.00 | -290.64 | -353.70 |
OFFICE | 22-JAN-07:01 | 2520.77 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -541.83 | 0.00 | -112.03 | -2441.48 |
G NE APARTMENT | 05-FEB-07:00 | 809.28 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.38 | 0.00 | -279.10 | -115.16 |
G N1 APARTMENT | 24-JAN-08:01 | 1031.11 | 0.00 | 0.00 | 0.00 | 74.04 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -275.72 | 0.00 | -47.56 | -1213.56 |
G N2 APARTMENT | 24-JAN-08:01 | 957.99 | 0.00 | 0.00 | 0.00 | 74.86 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.73 | 0.00 | -47.57 | -1144.25 |
G S1 APARTMENT | 10-JAN-05:15 | 600.70 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -484.13 | 0.00 | -74.41 | -578.56 |
G S2 APARTMENT | 10-JAN-06:00 | 541.89 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -450.88 | 0.00 | -68.61 | -558.80 |
M SW APARTMENT | 10-MAR-12:23 | 135.04 | 0.00 | 0.00 | 0.00 | 41.78 | 28.81 | 406.15 | 199.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -515.98 | -295.77 |
M NW APARTMENT | 05-FEB-07:45 | 658.65 | 0.00 | 0.00 | 0.00 | 161.22 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 134.22 | 0.00 | -995.59 | 0.00 | -434.73 | 0.00 |
M SE APARTMENT | 05-FEB-07:05 | 137.15 | 0.00 | 0.00 | 0.00 | 161.22 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 682.69 | 0.00 | -1044.41 | 0.00 | -412.88 | 0.00 |
M NE APARTMENT | 05-FEB-07:00 | 692.07 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 167.56 | 0.00 | -1066.03 | 0.00 | -401.96 | 0.00 |
M N1 APARTMENT | 23-DEC-16:00 | 142.23 | 0.00 | 0.00 | 0.00 | 40.77 | 50.41 | 400.26 | 42.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -156.66 | -519.69 |
M N2 APARTMENT | 23-DEC-16:00 | 142.85 | 0.00 | 0.00 | 0.00 | 40.84 | 50.41 | 400.26 | 43.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -154.86 | -522.70 |
M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 05-FEB-06:53 | 1470.05 | 0.00 | 0.00 | 0.00 | 190.63 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1005.94 | 0.00 | -529.32 | -544.10 |
T NW APARTMENT | 05-FEB-09:15 | 1521.97 | 0.00 | 0.00 | 0.00 | 47.84 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -594.35 | 0.00 | -520.40 | -878.26 |
T SE APARTMENT | 05-FEB-05:00 | 1440.72 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -956.22 | 0.00 | -414.75 | -526.31 |
T NE APARTMENT | 05-FEB-02:45 | 1468.09 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -929.36 | 0.00 | -436.87 | -535.50 |
T N1 APARTMENT | 05-FEB-09:15 | 930.20 | 0.00 | 0.00 | 0.00 | 47.84 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -376.84 | 0.00 | -313.55 | -710.84 |
T N2 APARTMENT | 05-FEB-09:15 | 929.08 | 0.00 | 0.00 | 0.00 | 47.81 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.28 | 0.00 | -313.83 | -708.97 |
T S1 APARTMENT | 05-FEB-06:45 | 874.30 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.62 | 0.00 | -301.69 | -553.34 |
T S2 APARTMENT | 23-DEC-07:01 | 1174.31 | 0.00 | 0.00 | 0.00 | 162.51 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -357.04 | 0.00 | -194.78 | -1261.24 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-FEB-07:01 | 12170.80 | 0.00 | 0.00 | 0.00 | 3722.06 | 4156.84 | 9398.91 | 0.00 | 0.00 | 0.00 | 13365.55 | 0.00 | -20095.58 | 0.00 | -22718.58 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Sec1.1A-General InformationData | |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 18.50 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 19.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 13.41 | 38133.26 | 0.00 | 0.00 |
Space Cooling | 323.87 | 29077.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 214.43 | 6799.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 320.37 | 18649.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1574.49 | 13.41 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1574.49 |
Natural Gas | 0.00 | 13.41 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1587.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 103.32 |
Fans-Interior | 68.41 |
Service Water Heating | 102.20 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.57 |
Subtotal | 502.29 |
Natural Gas [MJ/m2] | |
Space Heating | 4.28 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 4.28 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.39 |
Space Heating | 0.84 |
Space Cooling | 20.40 |
Fans-Interior | 13.50 |
Service Water Heating | 20.18 |
Receptacle Equipment | 32.21 |
Miscellaneous | 2.48 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.193169 |
G NW APARTMENT DIRECT AIR | 0.182981 |
OFFICE DIRECT AIR | 0.457831 |
G NE APARTMENT DIRECT AIR | 0.152281 |
G N1 APARTMENT DIRECT AIR | 0.103002 |
G N2 APARTMENT DIRECT AIR | 0.102334 |
G S1 APARTMENT DIRECT AIR | 0.118357 |
G S2 APARTMENT DIRECT AIR | 0.121114 |
M SW APARTMENT DIRECT AIR | 0.464513 |
M NW APARTMENT DIRECT AIR | 0.440102 |
M SE APARTMENT DIRECT AIR | 0.415008 |
M NE APARTMENT DIRECT AIR | 0.374912 |
M N1 APARTMENT DIRECT AIR | 0.260124 |
M N2 APARTMENT DIRECT AIR | 0.259051 |
M S1 APARTMENT DIRECT AIR | 0.296749 |
M S2 APARTMENT DIRECT AIR | 0.297669 |
T SW APARTMENT DIRECT AIR | 0.296020 |
T NW APARTMENT DIRECT AIR | 0.279341 |
T SE APARTMENT DIRECT AIR | 0.259383 |
T NE APARTMENT DIRECT AIR | 0.229251 |
T N1 APARTMENT DIRECT AIR | 0.172911 |
T N2 APARTMENT DIRECT AIR | 0.172872 |
T S1 APARTMENT DIRECT AIR | 0.210349 |
T S2 APARTMENT DIRECT AIR | 0.210989 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.193169 |
SPLIT GNW MAIN BRANCH | 0.182981 |
SPLIT OFFICE MAIN BRANCH | 0.457831 |
SPLIT GNE MAIN BRANCH | 0.152281 |
SPLIT GN1 MAIN BRANCH | 0.103002 |
SPLIT GN2 MAIN BRANCH | 0.102334 |
SPLIT GS1 MAIN BRANCH | 0.118357 |
SPLIT GS2 MAIN BRANCH | 0.121114 |
SPLIT MSW MAIN BRANCH | 0.464513 |
SPLIT MNW MAIN BRANCH | 0.440102 |
SPLIT MSE MAIN BRANCH | 0.415008 |
SPLIT MNE MAIN BRANCH | 0.374912 |
SPLIT MN1 MAIN BRANCH | 0.260124 |
SPLIT MN2 MAIN BRANCH | 0.259051 |
SPLIT MS1 MAIN BRANCH | 0.296749 |
SPLIT MS2 MAIN BRANCH | 0.297669 |
SPLIT TSW MAIN BRANCH | 0.296020 |
SPLIT TNW MAIN BRANCH | 0.279341 |
SPLIT TSE MAIN BRANCH | 0.259383 |
SPLIT TNE MAIN BRANCH | 0.229251 |
SPLIT TN1 MAIN BRANCH | 0.172911 |
SPLIT TN2 MAIN BRANCH | 0.172872 |
SPLIT TS1 MAIN BRANCH | 0.210349 |
SPLIT TS2 MAIN BRANCH | 0.210989 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.193169 |
SPLIT GNW | 0.182981 |
SPLIT OFFICE | 0.457831 |
SPLIT GNE | 0.152281 |
SPLIT GN1 | 0.103002 |
SPLIT GN2 | 0.102334 |
SPLIT GS1 | 0.118357 |
SPLIT GS2 | 0.121114 |
SPLIT MSW | 0.464513 |
SPLIT MNW | 0.440102 |
SPLIT MSE | 0.415008 |
SPLIT MNE | 0.374912 |
SPLIT MN1 | 0.260124 |
SPLIT MN2 | 0.259051 |
SPLIT MS1 | 0.296749 |
SPLIT MS2 | 0.297669 |
SPLIT TSW | 0.296020 |
SPLIT TNW | 0.279341 |
SPLIT TSE | 0.259383 |
SPLIT TNE | 0.229251 |
SPLIT TN1 | 0.172911 |
SPLIT TN2 | 0.172872 |
SPLIT TS1 | 0.210349 |
SPLIT TS2 | 0.210989 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.193169 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.182981 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.457831 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.152281 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.103002 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.102334 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.118357 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.121114 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.464513 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.440102 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.415008 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.374912 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.260124 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.259051 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.296749 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.297669 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.296020 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.279341 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.259383 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.229251 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.172911 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.172872 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.210349 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.210989 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.193169 | 4054.30 | 0.720970 |
SPLIT GNW COOLING COIL | 0.182981 | 3846.04 | 0.720551 |
SPLIT OFFICE COOLING COIL | 0.457831 | 8132.61 | 0.773616 |
SPLIT GNE COOLING COIL | 0.152281 | 3282.18 | 0.713367 |
SPLIT GN1 COOLING COIL | 0.103002 | 2460.78 | 0.685745 |
SPLIT GN2 COOLING COIL | 0.102334 | 2449.65 | 0.685242 |
SPLIT GS1 COOLING COIL | 0.118357 | 2802.34 | 0.688043 |
SPLIT GS2 COOLING COIL | 0.121114 | 2843.95 | 0.690182 |
SPLIT MSW COOLING COIL | 0.464513 | 9396.21 | 0.731869 |
SPLIT MNW COOLING COIL | 0.440102 | 8965.32 | 0.729758 |
SPLIT MSE COOLING COIL | 0.415008 | 8534.78 | 0.726935 |
SPLIT MNE COOLING COIL | 0.374912 | 7805.83 | 0.723309 |
SPLIT MN1 COOLING COIL | 0.260124 | 5858.42 | 0.701229 |
SPLIT MN2 COOLING COIL | 0.259051 | 5840.76 | 0.700928 |
SPLIT MS1 COOLING COIL | 0.296749 | 6651.35 | 0.702526 |
SPLIT MS2 COOLING COIL | 0.297669 | 6666.40 | 0.702753 |
SPLIT TSW COOLING COIL | 0.296020 | 5811.65 | 0.740994 |
SPLIT TNW COOLING COIL | 0.279341 | 5509.95 | 0.739546 |
SPLIT TSE COOLING COIL | 0.259383 | 5255.92 | 0.731349 |
SPLIT TNE COOLING COIL | 0.229251 | 4669.01 | 0.729826 |
SPLIT TN1 COOLING COIL | 0.172911 | 3750.35 | 0.711596 |
SPLIT TN2 COOLING COIL | 0.172872 | 3756.55 | 0.711070 |
SPLIT TS1 COOLING COIL | 0.210349 | 4377.40 | 0.723453 |
SPLIT TS2 COOLING COIL | 0.210989 | 4388.37 | 0.723610 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.193169 | 0.193169 | 0.193169 | 0.193169 | 1476.43 | 4054.30 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.182981 | 0.182981 | 0.182981 | 0.182981 | 1424.54 | 3846.04 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.457831 | 0.457831 | 0.457831 | 0.457831 | 2771.00 | 8132.61 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.152281 | 0.152281 | 0.152281 | 0.152281 | 1424.54 | 3282.18 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.103002 | 0.103002 | 0.103002 | 0.103002 | 1424.54 | 2460.78 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.102334 | 0.102334 | 0.102334 | 0.102334 | 1424.54 | 2449.65 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.118357 | 0.118357 | 0.118357 | 0.118357 | 1424.54 | 2802.34 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.121114 | 0.121114 | 0.121114 | 0.121114 | 1424.54 | 2843.95 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.464513 | 0.464513 | 0.464513 | 0.464513 | 2849.07 | 9396.21 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.440102 | 0.440102 | 0.440102 | 0.440102 | 2849.07 | 8965.32 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.415008 | 0.415008 | 0.415008 | 0.415008 | 2849.07 | 8534.78 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.374912 | 0.374912 | 0.374912 | 0.374912 | 2849.07 | 7805.83 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.260124 | 0.260124 | 0.260124 | 0.260124 | 2849.07 | 5858.42 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.259051 | 0.259051 | 0.259051 | 0.259051 | 2849.07 | 5840.76 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.296749 | 0.296749 | 0.296749 | 0.296749 | 2849.07 | 6651.35 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.297669 | 0.297669 | 0.297669 | 0.297669 | 2849.07 | 6666.40 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.296020 | 0.296020 | 0.296020 | 0.296020 | 1902.87 | 5811.65 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.279341 | 0.279341 | 0.279341 | 0.279341 | 1917.66 | 5509.95 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.259383 | 0.259383 | 0.259383 | 0.259383 | 1902.87 | 5255.92 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.229251 | 0.229251 | 0.229251 | 0.229251 | 1917.66 | 4669.01 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.172911 | 0.172911 | 0.172911 | 0.172911 | 1433.51 | 3750.35 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.172872 | 0.172872 | 0.172872 | 0.172872 | 1433.51 | 3756.55 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.210349 | 0.210349 | 0.210349 | 0.210349 | 1424.54 | 4377.40 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.210989 | 0.210989 | 0.210989 | 0.210989 | 1424.54 | 4388.37 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.193169 |
SPLIT GNW SUPPLY FAN | 0.182981 |
SPLIT OFFICE SUPPLY FAN | 0.457831 |
SPLIT GNE SUPPLY FAN | 0.152281 |
SPLIT GN1 SUPPLY FAN | 0.103002 |
SPLIT GN2 SUPPLY FAN | 0.102334 |
SPLIT GS1 SUPPLY FAN | 0.118357 |
SPLIT GS2 SUPPLY FAN | 0.121114 |
SPLIT MSW SUPPLY FAN | 0.464513 |
SPLIT MNW SUPPLY FAN | 0.440102 |
SPLIT MSE SUPPLY FAN | 0.415008 |
SPLIT MNE SUPPLY FAN | 0.374912 |
SPLIT MN1 SUPPLY FAN | 0.260124 |
SPLIT MN2 SUPPLY FAN | 0.259051 |
SPLIT MS1 SUPPLY FAN | 0.296749 |
SPLIT MS2 SUPPLY FAN | 0.297669 |
SPLIT TSW SUPPLY FAN | 0.296020 |
SPLIT TNW SUPPLY FAN | 0.279341 |
SPLIT TSE SUPPLY FAN | 0.259383 |
SPLIT TNE SUPPLY FAN | 0.229251 |
SPLIT TN1 SUPPLY FAN | 0.172911 |
SPLIT TN2 SUPPLY FAN | 0.172872 |
SPLIT TS1 SUPPLY FAN | 0.210349 |
SPLIT TS2 SUPPLY FAN | 0.210989 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1476.43 |
SPLIT GNW HEATING COIL | 1424.54 |
SPLIT OFFICE HEATING COIL | 2771.00 |
SPLIT GNE HEATING COIL | 1424.54 |
SPLIT GN1 HEATING COIL | 1424.54 |
SPLIT GN2 HEATING COIL | 1424.54 |
SPLIT GS1 HEATING COIL | 1424.54 |
SPLIT GS2 HEATING COIL | 1424.54 |
SPLIT MSW HEATING COIL | 2849.07 |
SPLIT MNW HEATING COIL | 2849.07 |
SPLIT MSE HEATING COIL | 2849.07 |
SPLIT MNE HEATING COIL | 2849.07 |
SPLIT MN1 HEATING COIL | 2849.07 |
SPLIT MN2 HEATING COIL | 2849.07 |
SPLIT MS1 HEATING COIL | 2849.07 |
SPLIT MS2 HEATING COIL | 2849.07 |
SPLIT TSW HEATING COIL | 1902.87 |
SPLIT TNW HEATING COIL | 1917.66 |
SPLIT TSE HEATING COIL | 1902.87 |
SPLIT TNE HEATING COIL | 1917.66 |
SPLIT TN1 HEATING COIL | 1433.51 |
SPLIT TN2 HEATING COIL | 1433.51 |
SPLIT TS1 HEATING COIL | 1424.54 |
SPLIT TS2 HEATING COIL | 1424.54 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 13.57 |
February | 23.43 | 15.49 |
March | 23.47 | 17.07 |
April | 24.12 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 23.95 | 18.91 |
December | 23.43 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 23.19 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.62 | 13.57 |
February | 23.01 | 15.49 |
March | 23.26 | 17.07 |
April | 24.06 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.25 | 24.23 |
November | 23.63 | 18.91 |
December | 22.98 | 15.68 |
Annual Sum or Average | 23.82 | 21.89 |
Minimum of Months | 22.62 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 13.57 |
February | 23.36 | 15.49 |
March | 23.46 | 17.07 |
April | 23.87 | 21.23 |
May | 23.90 | 26.90 |
June | 23.90 | 27.61 |
July | 23.90 | 27.94 |
August | 23.90 | 27.43 |
September | 23.90 | 26.23 |
October | 23.89 | 24.23 |
November | 23.77 | 18.91 |
December | 23.34 | 15.68 |
Annual Sum or Average | 23.69 | 21.89 |
Minimum of Months | 23.09 | 13.57 |
Maximum of Months | 23.90 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 13.57 |
February | 22.95 | 15.49 |
March | 23.24 | 17.07 |
April | 24.04 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.24 | 24.23 |
November | 23.60 | 18.91 |
December | 22.90 | 15.68 |
Annual Sum or Average | 23.80 | 21.89 |
Minimum of Months | 22.55 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.47 | 13.57 |
February | 22.84 | 15.49 |
March | 23.12 | 17.07 |
April | 23.95 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.23 | 24.23 |
November | 23.51 | 18.91 |
December | 22.85 | 15.68 |
Annual Sum or Average | 23.75 | 21.89 |
Minimum of Months | 22.47 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.47 | 13.57 |
February | 22.84 | 15.49 |
March | 23.12 | 17.07 |
April | 23.95 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.23 | 24.23 |
November | 23.51 | 18.91 |
December | 22.84 | 15.68 |
Annual Sum or Average | 23.75 | 21.89 |
Minimum of Months | 22.47 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 13.57 |
February | 23.43 | 15.49 |
March | 23.45 | 17.07 |
April | 24.08 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 23.99 | 18.91 |
December | 23.48 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 23.23 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 13.57 |
February | 23.42 | 15.49 |
March | 23.44 | 17.07 |
April | 24.07 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 23.98 | 18.91 |
December | 23.47 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 23.22 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.12 | 13.57 |
February | 24.19 | 15.49 |
March | 24.20 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.40 | 24.23 |
November | 24.38 | 18.91 |
December | 24.20 | 15.68 |
Annual Sum or Average | 24.32 | 21.89 |
Minimum of Months | 24.12 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 13.57 |
February | 23.94 | 15.49 |
March | 24.09 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.39 | 24.23 |
November | 24.33 | 18.91 |
December | 23.92 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.62 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.11 | 13.57 |
February | 24.19 | 15.49 |
March | 24.20 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.40 | 24.23 |
November | 24.38 | 18.91 |
December | 24.18 | 15.68 |
Annual Sum or Average | 24.32 | 21.89 |
Minimum of Months | 24.11 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 13.57 |
February | 23.91 | 15.49 |
March | 24.08 | 17.07 |
April | 24.39 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.39 | 24.23 |
November | 24.33 | 18.91 |
December | 23.87 | 15.68 |
Annual Sum or Average | 24.21 | 21.89 |
Minimum of Months | 23.57 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 13.57 |
February | 24.01 | 15.49 |
March | 24.19 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.39 | 24.23 |
November | 24.37 | 18.91 |
December | 24.05 | 15.68 |
Annual Sum or Average | 24.27 | 21.89 |
Minimum of Months | 23.77 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 13.57 |
February | 24.01 | 15.49 |
March | 24.19 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.39 | 24.23 |
November | 24.37 | 18.91 |
December | 24.05 | 15.68 |
Annual Sum or Average | 24.26 | 21.89 |
Minimum of Months | 23.77 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.26 | 13.57 |
February | 24.29 | 15.49 |
March | 24.29 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.40 | 24.23 |
November | 24.40 | 18.91 |
December | 24.30 | 15.68 |
Annual Sum or Average | 24.36 | 21.89 |
Minimum of Months | 24.26 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.26 | 13.57 |
February | 24.29 | 15.49 |
March | 24.29 | 17.07 |
April | 24.40 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.40 | 24.23 |
November | 24.40 | 18.91 |
December | 24.30 | 15.68 |
Annual Sum or Average | 24.36 | 21.89 |
Minimum of Months | 24.26 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.55 | 13.57 |
February | 23.84 | 15.49 |
March | 23.86 | 17.07 |
April | 24.33 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.36 | 24.23 |
November | 24.18 | 18.91 |
December | 23.73 | 15.68 |
Annual Sum or Average | 24.15 | 21.89 |
Minimum of Months | 23.55 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 13.57 |
February | 23.58 | 15.49 |
March | 23.73 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.32 | 24.23 |
November | 24.01 | 18.91 |
December | 23.40 | 15.68 |
Annual Sum or Average | 24.04 | 21.89 |
Minimum of Months | 23.11 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.54 | 13.57 |
February | 23.83 | 15.49 |
March | 23.86 | 17.07 |
April | 24.33 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.35 | 24.23 |
November | 24.17 | 18.91 |
December | 23.70 | 15.68 |
Annual Sum or Average | 24.15 | 21.89 |
Minimum of Months | 23.54 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.04 | 13.57 |
February | 23.54 | 15.49 |
March | 23.72 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 24.02 | 18.91 |
December | 23.34 | 15.68 |
Annual Sum or Average | 24.02 | 21.89 |
Minimum of Months | 23.04 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 13.57 |
February | 23.56 | 15.49 |
March | 23.74 | 17.07 |
April | 24.33 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.33 | 24.23 |
November | 24.05 | 18.91 |
December | 23.41 | 15.68 |
Annual Sum or Average | 24.04 | 21.89 |
Minimum of Months | 23.06 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 13.57 |
February | 23.56 | 15.49 |
March | 23.74 | 17.07 |
April | 24.33 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.33 | 24.23 |
November | 24.05 | 18.91 |
December | 23.40 | 15.68 |
Annual Sum or Average | 24.04 | 21.89 |
Minimum of Months | 23.05 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 13.57 |
February | 23.92 | 15.49 |
March | 23.94 | 17.07 |
April | 24.35 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.37 | 24.23 |
November | 24.25 | 18.91 |
December | 23.84 | 15.68 |
Annual Sum or Average | 24.20 | 21.89 |
Minimum of Months | 23.67 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 13.57 |
February | 23.92 | 15.49 |
March | 23.93 | 17.07 |
April | 24.35 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.37 | 24.23 |
November | 24.25 | 18.91 |
December | 23.84 | 15.68 |
Annual Sum or Average | 24.20 | 21.89 |
Minimum of Months | 23.67 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.57 | 13.57 |
February | 25.14 | 15.49 |
March | 25.41 | 17.07 |
April | 26.45 | 21.23 |
May | 27.18 | 26.90 |
June | 27.29 | 27.61 |
July | 27.32 | 27.94 |
August | 27.26 | 27.43 |
September | 27.10 | 26.23 |
October | 26.85 | 24.23 |
November | 25.91 | 18.91 |
December | 25.03 | 15.68 |
Annual Sum or Average | 26.30 | 21.89 |
Minimum of Months | 24.57 | 13.57 |
Maximum of Months | 27.32 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 13.57 |
February | 22.88 | 15.49 |
March | 23.28 | 17.07 |
April | 24.55 | 21.23 |
May | 25.89 | 26.90 |
June | 26.88 | 27.61 |
July | 27.03 | 27.94 |
August | 26.97 | 27.43 |
September | 26.71 | 26.23 |
October | 25.52 | 24.23 |
November | 23.99 | 18.91 |
December | 22.95 | 15.68 |
Annual Sum or Average | 24.92 | 21.89 |
Minimum of Months | 22.31 | 13.57 |
Maximum of Months | 27.03 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.99 | 13.57 |
February | 26.25 | 15.49 |
March | 26.37 | 17.07 |
April | 26.80 | 21.23 |
May | 27.04 | 26.90 |
June | 27.09 | 27.61 |
July | 27.10 | 27.94 |
August | 27.08 | 27.43 |
September | 27.02 | 26.23 |
October | 26.97 | 24.23 |
November | 26.68 | 18.91 |
December | 26.26 | 15.68 |
Annual Sum or Average | 26.72 | 21.89 |
Minimum of Months | 25.99 | 13.57 |
Maximum of Months | 27.10 | 27.94 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:30
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.117778E+12 | 76315.099 | 01-JAN-18:30 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 8641.725 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23336.451 | 0.000 | 0.000 | 0.000 |
February | 0.108767E+12 | 75466.387 | 02-FEB-18:00 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 10313.801 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20815.663 | 0.000 | 0.000 | 0.000 |
March | 0.120829E+12 | 77687.966 | 07-MAR-18:30 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 12278.207 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21072.836 | 0.000 | 0.000 | 0.000 |
April | 0.123831E+12 | 80263.273 | 28-APR-16:30 | 7009.952 | 26456.413 | 6799.406 | 0.000 | 22911.974 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17085.529 | 0.000 | 0.000 | 0.000 |
May | 0.143439E+12 | 82316.519 | 28-MAY-16:15 | 7009.952 | 26456.413 | 6799.406 | 0.000 | 24019.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18030.890 | 0.000 | 0.000 | 0.000 |
June | 0.141563E+12 | 83951.166 | 15-JUN-17:30 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 23144.086 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18978.487 | 0.000 | 0.000 | 0.000 |
July | 0.148751E+12 | 85375.577 | 23-JUL-17:15 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 24993.223 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18553.761 | 0.000 | 0.000 | 0.000 |
August | 0.147781E+12 | 87205.749 | 24-AUG-17:00 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 25280.730 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20096.426 | 0.000 | 0.000 | 0.000 |
September | 0.140792E+12 | 89555.694 | 09-SEP-17:15 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 29077.819 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18649.282 | 0.000 | 0.000 | 0.000 |
October | 0.139282E+12 | 86818.526 | 07-OCT-16:30 | 7009.952 | 26456.413 | 6799.406 | 0.000 | 24998.230 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21554.527 | 0.000 | 0.000 | 0.000 |
November | 0.121012E+12 | 77537.922 | 03-NOV-17:15 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 17474.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18235.309 | 0.000 | 0.000 | 0.000 |
December | 0.120669E+12 | 76367.114 | 15-DEC-18:15 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 13621.454 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18408.737 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.157449E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.108767E+12 | 75466.387 | 7009.952 | 26456.413 | 6799.406 | 0.000 | 8641.725 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17085.529 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.148751E+12 | 89555.694 | 8572.775 | 26456.413 | 6799.406 | 0.000 | 29077.819 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23336.451 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:30
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.486896E+10 | 21472.173 | 05-JAN-04:00 | 21472.173 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21472.173 |
February | 0.336922E+10 | 38133.256 | 05-FEB-07:15 | 38133.256 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38133.256 |
March | 0.195892E+10 | 15189.862 | 09-MAR-06:45 | 15189.862 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15189.862 |
April | 0.000 | 0.000 | 01-APR-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 01-OCT-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.108988E+09 | 3409.584 | 16-NOV-04:00 | 3409.584 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3409.584 |
December | 0.310392E+10 | 27281.061 | 20-DEC-07:30 | 27281.061 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27281.061 |
Annual Sum or Average | 0.134100E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.486896E+10 | 38133.256 | 38133.256 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38133.256 |