Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2018-10-19 09:20:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1579.69 | 503.95 | 559.38 |
Net Site Energy | 1579.69 | 503.95 | 559.38 |
Total Source Energy | 4778.96 | 1524.58 | 1692.28 |
Net Source Energy | 4778.96 | 1524.58 | 1692.28 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 107.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 205.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 362.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1472.19 | 107.49 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 107.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 188.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 205.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 362.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 267.82 | 38.06 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 521.32 | 38.06 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 241.27 | 34.29 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.66 | 34.29 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1472.19 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1472.19 | 100.00 |
Total On-Site and Utility Electric Sources | 1472.19 | 100.00 |
Total Electricity End Uses | 1472.19 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 34.75 |
Time Setpoint Not Met During Occupied Cooling | 0.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2280.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 01-AUG-17:15 | 12-FEB-07:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 84110.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25323.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6521.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85397.89 | 84110.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 84110.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25323.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6521.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 116.52 | 0.00 | 0.00 | 0.00 |
Cooling | 596.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 651.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1147.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4662.43 | 116.52 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.26 | 0.00 | 0.00 | 0.00 |
Cooling | 211.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 406.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1651.02 | 41.26 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.26 | 0.00 | 0.00 | 0.00 |
Cooling | 211.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 406.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1651.02 | 41.26 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.62_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 112.97 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 193.95 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.82 | 83.82 | 39.47 | |
Exterior Lighting Total | 2508.33 | 39.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3390.62 | 2489.86 | 900.75 | 0.73 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3326.98 | 2450.15 | 876.83 | 0.74 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7312.29 | 5782.82 | 1529.47 | 0.79 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2728.93 | 1966.90 | 762.03 | 0.72 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2321.54 | 1656.95 | 664.59 | 0.71 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2310.28 | 1647.81 | 662.48 | 0.71 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2296.78 | 1633.53 | 663.25 | 0.71 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2319.89 | 1656.90 | 662.99 | 0.71 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8316.59 | 6219.58 | 2097.01 | 0.75 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8213.23 | 6132.88 | 2080.35 | 0.75 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7319.87 | 5377.81 | 1942.06 | 0.73 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6906.20 | 5085.71 | 1820.48 | 0.74 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5770.56 | 4218.05 | 1552.51 | 0.73 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5752.48 | 4203.27 | 1549.21 | 0.73 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5809.54 | 4221.02 | 1588.52 | 0.73 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5792.26 | 4206.96 | 1585.30 | 0.73 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5227.83 | 3952.51 | 1275.32 | 0.76 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5095.31 | 3854.48 | 1240.83 | 0.76 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4832.27 | 3590.26 | 1242.01 | 0.74 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4320.77 | 3210.15 | 1110.62 | 0.74 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3662.48 | 2715.04 | 947.44 | 0.74 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3642.29 | 2698.56 | 943.73 | 0.74 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3990.48 | 2936.74 | 1053.73 | 0.74 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3999.39 | 2944.03 | 1055.37 | 0.74 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3257.8 | 3.24 | 11.06 | 11.51 | 10.94 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3195.8 | 3.24 | 11.05 | 11.50 | 10.93 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6973.4 | 3.14 | 10.72 | 11.14 | 10.44 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2626.7 | 3.27 | 11.14 | 11.60 | 11.07 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2236.7 | 3.28 | 11.19 | 11.65 | 11.14 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2226.0 | 3.28 | 11.19 | 11.65 | 11.14 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2213.6 | 3.28 | 11.20 | 11.67 | 11.16 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2234.9 | 3.28 | 11.19 | 11.65 | 11.13 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7976.6 | 3.22 | 10.98 | 11.42 | 10.82 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7878.6 | 3.22 | 10.98 | 11.43 | 10.83 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7032.8 | 3.24 | 11.06 | 11.51 | 10.94 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6633.9 | 3.24 | 11.05 | 11.50 | 10.93 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5547.0 | 3.25 | 11.08 | 11.53 | 10.98 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5529.8 | 3.25 | 11.08 | 11.54 | 10.98 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5587.7 | 3.26 | 11.11 | 11.56 | 11.02 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5571.3 | 3.26 | 11.11 | 11.56 | 11.02 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5008.6 | 3.20 | 10.93 | 11.37 | 10.75 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4881.4 | 3.20 | 10.92 | 11.36 | 10.74 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4637.7 | 3.23 | 11.01 | 11.45 | 10.87 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4146.8 | 3.23 | 11.01 | 11.45 | 10.87 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3515.8 | 3.23 | 11.02 | 11.46 | 10.88 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3496.6 | 3.23 | 11.02 | 11.47 | 10.88 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3833.4 | 3.24 | 11.05 | 11.50 | 10.93 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3841.8 | 3.24 | 11.05 | 11.50 | 10.93 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2269.31 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2249.76 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 4326.87 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2242.48 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1704.60 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1704.60 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1704.60 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1758.92 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 4497.02 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 4529.19 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 4477.68 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 4509.86 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3409.21 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3409.21 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3409.21 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3409.21 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 3405.25 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 3423.37 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 3395.20 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 3413.33 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2614.39 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2614.11 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2594.26 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2593.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 189.29 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.03 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 484.27 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 145.53 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 120.80 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 120.01 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.46 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 120.92 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 484.99 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 477.23 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 409.13 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 388.18 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 318.57 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 317.29 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 316.03 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 314.81 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 312.75 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.22 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 277.46 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 248.08 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 209.17 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 207.74 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 223.96 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 224.59 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1733.83 | 2080.59 | 0.141 | 0.169 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
G NW APARTMENT | 1713.12 | 2055.74 | 0.139 | 0.167 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.76 | 0.01445 |
OFFICE | 4222.28 | 5066.73 | 0.360 | 0.432 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 29.98 | 0.01445 |
G NE APARTMENT | 1332.99 | 1599.58 | 0.108 | 0.130 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.41 | 0.01445 |
G N1 APARTMENT | 1106.50 | 1327.80 | 0.090 | 0.108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.70 | 0.01445 |
G N2 APARTMENT | 1099.26 | 1319.11 | 0.089 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.70 | 0.01445 |
G S1 APARTMENT | 1085.01 | 1302.01 | 0.088 | 0.106 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
G S2 APARTMENT | 1107.61 | 1329.14 | 0.090 | 0.108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.70 | 0.01445 |
M SW APARTMENT | 4442.17 | 5330.60 | 0.361 | 0.433 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
M NW APARTMENT | 4371.11 | 5245.33 | 0.355 | 0.426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
M SE APARTMENT | 3747.17 | 4496.60 | 0.304 | 0.365 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
M NE APARTMENT | 3555.47 | 4266.57 | 0.289 | 0.347 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.41 | 0.01445 |
M N1 APARTMENT | 2917.97 | 3501.57 | 0.237 | 0.284 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.70 | 0.01445 |
M N2 APARTMENT | 2906.20 | 3487.44 | 0.236 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.70 | 0.01445 |
M S1 APARTMENT | 2894.66 | 3473.59 | 0.235 | 0.282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.76 | 0.01445 |
M S2 APARTMENT | 2883.52 | 3460.23 | 0.234 | 0.281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.76 | 0.01445 |
T SW APARTMENT | 2864.48 | 3437.37 | 0.233 | 0.279 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.83 | 0.01445 |
T NW APARTMENT | 2795.60 | 3354.72 | 0.227 | 0.272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.36 | 0.01445 |
T SE APARTMENT | 2541.16 | 3049.40 | 0.206 | 0.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
T NE APARTMENT | 2272.03 | 2726.44 | 0.185 | 0.221 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
T N1 APARTMENT | 1915.89 | 2299.06 | 0.156 | 0.187 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
T N2 APARTMENT | 1902.77 | 2283.32 | 0.155 | 0.185 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
T S1 APARTMENT | 2051.24 | 2461.49 | 0.167 | 0.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 34.40 | 0.01445 |
T S2 APARTMENT | 2057.04 | 2468.45 | 0.167 | 0.201 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 34.40 | 0.01445 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1176.06 | 1411.28 | 0.035 | 0.042 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
G NW APARTMENT | 1185.65 | 1422.77 | 0.035 | 0.042 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
OFFICE | 2656.76 | 3188.11 | 0.076 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G NE APARTMENT | 1179.49 | 1415.39 | 0.035 | 0.042 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
G N1 APARTMENT | 687.16 | 824.59 | 0.021 | 0.026 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
G N2 APARTMENT | 687.01 | 824.42 | 0.021 | 0.026 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
G S1 APARTMENT | 679.10 | 814.92 | 0.020 | 0.026 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
G S2 APARTMENT | 770.54 | 924.65 | 0.023 | 0.028 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M SW APARTMENT | 2369.22 | 2843.06 | 0.071 | 0.085 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M NW APARTMENT | 2396.42 | 2875.71 | 0.072 | 0.086 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M SE APARTMENT | 2352.86 | 2823.44 | 0.070 | 0.084 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M NE APARTMENT | 2380.07 | 2856.09 | 0.071 | 0.085 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M N1 APARTMENT | 1127.37 | 1352.85 | 0.034 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M N2 APARTMENT | 1126.94 | 1352.32 | 0.034 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M S1 APARTMENT | 1101.56 | 1321.87 | 0.033 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
M S2 APARTMENT | 1101.13 | 1321.35 | 0.033 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T SW APARTMENT | 2162.83 | 2595.40 | 0.065 | 0.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T NW APARTMENT | 2178.16 | 2613.79 | 0.065 | 0.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T SE APARTMENT | 2154.34 | 2585.20 | 0.064 | 0.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T NE APARTMENT | 2169.66 | 2603.60 | 0.065 | 0.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T N1 APARTMENT | 1494.01 | 1792.81 | 0.045 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T N2 APARTMENT | 1493.77 | 1792.52 | 0.045 | 0.053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T S1 APARTMENT | 1476.98 | 1772.37 | 0.044 | 0.053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
T S2 APARTMENT | 1476.74 | 1772.09 | 0.044 | 0.053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -6.30 | 0.00230 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.17 | 0.17 | 0.04 | 0.04 |
SPLIT GNW | 0.17 | 0.17 | 0.04 | 0.04 |
SPLIT OFFICE | 0.43 | 0.43 | 0.09 | 0.09 |
SPLIT GNE | 0.13 | 0.13 | 0.04 | 0.04 |
SPLIT GN1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GN2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT MSW | 0.43 | 0.43 | 0.08 | 0.08 |
SPLIT MNW | 0.43 | 0.43 | 0.09 | 0.09 |
SPLIT MSE | 0.37 | 0.37 | 0.08 | 0.08 |
SPLIT MNE | 0.35 | 0.35 | 0.09 | 0.09 |
SPLIT MN1 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MN2 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MS1 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MS2 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TSW | 0.28 | 0.28 | 0.08 | 0.08 |
SPLIT TNW | 0.27 | 0.27 | 0.08 | 0.08 |
SPLIT TSE | 0.25 | 0.25 | 0.08 | 0.08 |
SPLIT TNE | 0.22 | 0.22 | 0.08 | 0.08 |
SPLIT TN1 | 0.19 | 0.19 | 0.05 | 0.05 |
SPLIT TN2 | 0.19 | 0.19 | 0.05 | 0.05 |
SPLIT TS1 | 0.20 | 0.20 | 0.05 | 0.05 |
SPLIT TS2 | 0.20 | 0.20 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3744.00 | 5819.00 | 1492.25 |
G NW APARTMENT | 3945.75 | 6108.50 | 1845.00 |
OFFICE | 653.50 | 1313.25 | 31.25 |
G NE APARTMENT | 3931.50 | 6061.00 | 1766.50 |
G N1 APARTMENT | 3679.25 | 6357.25 | 1804.00 |
G N2 APARTMENT | 3677.75 | 6357.25 | 1802.00 |
G S1 APARTMENT | 3463.00 | 6045.25 | 1385.00 |
G S2 APARTMENT | 3477.00 | 6115.00 | 1473.75 |
M SW APARTMENT | 4720.00 | 2891.50 | 391.25 |
M NW APARTMENT | 4554.75 | 3609.50 | 516.75 |
M SE APARTMENT | 4727.50 | 2869.50 | 343.50 |
M NE APARTMENT | 4523.50 | 3644.75 | 480.00 |
M N1 APARTMENT | 4361.50 | 3356.00 | 361.25 |
M N2 APARTMENT | 4360.75 | 3361.00 | 360.25 |
M S1 APARTMENT | 4694.25 | 2448.00 | 312.00 |
M S2 APARTMENT | 4696.25 | 2452.00 | 311.50 |
T SW APARTMENT | 4872.00 | 4096.75 | 1112.75 |
T NW APARTMENT | 4965.00 | 4580.75 | 1464.00 |
T SE APARTMENT | 4860.50 | 4071.25 | 1072.25 |
T NE APARTMENT | 4954.75 | 4624.50 | 1473.75 |
T N1 APARTMENT | 4822.25 | 4549.25 | 1301.25 |
T N2 APARTMENT | 4821.75 | 4553.50 | 1301.75 |
T S1 APARTMENT | 4743.25 | 3919.50 | 918.00 |
T S2 APARTMENT | 4742.00 | 3916.50 | 917.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5773.25 | 6477.25 | 2280.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G NW APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
OFFICE | 4.50 | 1.00 | 0.00 | 0.00 |
G NE APARTMENT | 5.50 | 0.00 | 5.50 | 0.00 |
G N1 APARTMENT | 2.75 | 0.50 | 2.75 | 0.50 |
G N2 APARTMENT | 2.25 | 0.50 | 2.25 | 0.50 |
G S1 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
G S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M NW APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M NE APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T NE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T N2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 39.25 | 1.75 | 34.75 | 0.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.367 | 0.100 | 0.000 | 0.093 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.100 | 0.000 | 0.090 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.520 | 0.109 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.100 | 0.000 | 0.089 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.060 | 0.000 | 0.089 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.060 | 0.000 | 0.089 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.060 | 0.000 | 0.093 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.060 | 0.000 | 0.093 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.144 | 0.000 | 0.116 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.144 | 0.000 | 0.113 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.144 | 0.000 | 0.116 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.144 | 0.000 | 0.112 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.087 | 0.000 | 0.113 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.087 | 0.000 | 0.113 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.087 | 0.000 | 0.116 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.087 | 0.000 | 0.116 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.190 | 0.000 | 0.140 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.190 | 0.000 | 0.135 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.190 | 0.000 | 0.140 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.190 | 0.000 | 0.135 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.115 | 0.000 | 0.135 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.115 | 0.000 | 0.135 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.115 | 0.000 | 0.140 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.115 | 0.000 | 0.140 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.498 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 362.28 | 0.00 | 01-JAN-00:15 | 32310.28 | 01-JAN-07:30 |
WaterSystems:Electricity | 362.28 | 0.00 | 01-JAN-00:15 | 32310.28 | 01-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 362.28 | 0.00 | 01-JAN-00:15 | 32310.28 | 01-JAN-07:30 |
Fans:Electricity | 205.66 | 6521.51 | 02-JAN-08:15 | 6521.51 | 06-JAN-18:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
ElectricityPurchased:Plant | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
Cogeneration:ElectricityPurchased | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
ElectricityNet:Plant | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
Cogeneration:ElectricityNet | 1472.19 | 19891.81 | 01-JAN-03:15 | 85397.89 | 01-AUG-17:15 |
ExteriorLights:Electricity | 39.47 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.47 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 394.02 | 6521.51 | 02-JAN-08:15 | 31899.37 | 08-JUL-16:15 |
General:Fans:Electricity | 205.66 | 6521.51 | 02-JAN-08:15 | 6521.51 | 06-JAN-18:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 188.36 | 0.00 | 01-JAN-00:15 | 25377.86 | 08-JUL-16:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 107.49 | 0.00 | 01-JAN-11:45 | 84110.63 | 12-FEB-07:15 |
Gas:HVAC | 107.49 | 0.00 | 01-JAN-11:45 | 84110.63 | 12-FEB-07:15 |
Heating:Gas | 107.49 | 0.00 | 01-JAN-11:45 | 84110.63 | 12-FEB-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1438.06 | 1199.03 | 20-JAN-14:45 | 157898.05 | 01-AUG-17:15 |
EnergyTransfer:Building | 583.96 | 1083.76 | 20-JAN-15:00 | 61580.33 | 01-AUG-17:15 |
EnergyTransfer:Zone:G SW APARTMENT | 12.06 | 0.02 | 24-MAY-10:00 | 1967.09 | 18-AUG-17:15 |
Heating:EnergyTransfer | 40.00 | 0.00 | 12-JAN-16:15 | 40692.82 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.36 | 0.00 | 01-JAN-09:30 | 1360.75 | 12-FEB-06:00 |
Cooling:EnergyTransfer | 543.96 | 0.00 | 08-JAN-07:15 | 61580.33 | 01-AUG-17:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 10.70 | 0.00 | 01-JAN-00:15 | 1967.09 | 18-AUG-17:15 |
EnergyTransfer:Zone:G NW APARTMENT | 11.07 | 0.01 | 21-FEB-21:00 | 1843.02 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.36 | 0.00 | 01-JAN-10:00 | 1410.31 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 8.71 | 0.00 | 01-JAN-00:15 | 1843.02 | 01-AUG-17:15 |
EnergyTransfer:Zone:OFFICE | 24.56 | 0.01 | 18-APR-07:00 | 3316.75 | 25-SEP-11:00 |
Heating:EnergyTransfer:Zone:OFFICE | 0.35 | 0.00 | 01-JAN-00:15 | 3128.67 | 12-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 24.21 | 0.00 | 01-JAN-01:15 | 3316.75 | 25-SEP-11:00 |
EnergyTransfer:Zone:G NE APARTMENT | 11.15 | 0.02 | 06-OCT-13:15 | 1478.08 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.20 | 0.00 | 01-JAN-09:30 | 1404.15 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 8.95 | 0.00 | 01-JAN-00:15 | 1478.08 | 01-AUG-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.60 | 0.00 | 14-APR-20:45 | 1157.95 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.97 | 0.00 | 01-JAN-05:15 | 784.27 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 7.62 | 0.00 | 01-JAN-00:15 | 1157.95 | 01-AUG-17:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.60 | 0.00 | 19-JAN-11:45 | 1152.77 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.97 | 0.00 | 01-JAN-05:15 | 785.53 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 7.63 | 0.00 | 01-JAN-00:15 | 1152.77 | 01-AUG-17:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 10.19 | 0.07 | 04-APR-08:30 | 1313.10 | 23-SEP-15:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.40 | 0.00 | 01-JAN-04:15 | 714.70 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.79 | 0.00 | 01-JAN-00:15 | 1313.10 | 23-SEP-15:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 10.03 | 0.01 | 08-MAR-19:45 | 1290.15 | 23-SEP-15:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.48 | 0.00 | 01-JAN-05:15 | 817.65 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 9.55 | 0.00 | 01-JAN-00:15 | 1290.15 | 23-SEP-15:15 |
EnergyTransfer:Zone:M SW APARTMENT | 45.42 | 0.38 | 30-JAN-12:15 | 4972.99 | 11-OCT-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.77 | 0.00 | 01-JAN-00:15 | 2604.98 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 44.65 | 0.00 | 03-JAN-01:15 | 4972.99 | 11-OCT-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 38.05 | 0.04 | 18-FEB-13:45 | 4645.74 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.10 | 0.00 | 01-JAN-00:15 | 2843.82 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 35.94 | 0.00 | 02-JAN-02:30 | 4645.74 | 01-AUG-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 46.07 | 0.02 | 28-JAN-01:30 | 4256.71 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.79 | 0.00 | 01-JAN-00:15 | 2635.50 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 45.27 | 0.00 | 03-JAN-00:15 | 4256.71 | 10-OCT-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 38.48 | 0.04 | 31-JAN-19:15 | 3896.77 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.99 | 0.00 | 01-JAN-00:15 | 2848.10 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 36.48 | 0.00 | 02-JAN-02:00 | 3896.77 | 01-AUG-17:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 34.23 | 0.04 | 26-JAN-15:15 | 3062.30 | 06-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1268.59 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 33.88 | 0.00 | 04-JAN-05:00 | 3062.30 | 06-JUN-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 34.24 | 0.07 | 15-NOV-12:30 | 3054.33 | 06-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 1271.88 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 33.88 | 0.00 | 04-JAN-05:00 | 3054.33 | 06-JUN-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 43.70 | 1.25 | 19-JAN-21:30 | 3838.42 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1043.92 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 43.62 | 0.00 | 05-JAN-04:45 | 3838.42 | 11-OCT-15:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 43.71 | 0.67 | 19-JAN-21:30 | 3833.89 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1046.91 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 43.62 | 0.00 | 05-JAN-04:45 | 3833.89 | 11-OCT-15:30 |
EnergyTransfer:Zone:T SW APARTMENT | 23.19 | 0.00 | 06-DEC-19:30 | 3243.90 | 18-AUG-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.36 | 0.00 | 01-JAN-15:15 | 2715.36 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 19.82 | 0.00 | 01-JAN-00:15 | 3243.90 | 18-AUG-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 21.55 | 0.00 | 04-OCT-11:15 | 3092.84 | 01-AUG-17:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 4.92 | 0.00 | 01-JAN-15:15 | 2737.06 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 16.63 | 0.00 | 01-JAN-00:15 | 3092.84 | 01-AUG-17:00 |
EnergyTransfer:Zone:T SE APARTMENT | 23.20 | 0.00 | 18-SEP-03:00 | 2752.50 | 18-AUG-13:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.26 | 0.00 | 01-JAN-09:45 | 2674.64 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 19.95 | 0.00 | 01-JAN-00:15 | 2752.50 | 18-AUG-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 21.48 | 0.02 | 09-MAR-05:00 | 2709.77 | 12-FEB-01:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 4.71 | 0.00 | 01-JAN-10:15 | 2709.77 | 12-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 16.76 | 0.00 | 01-JAN-00:15 | 2590.25 | 08-JUL-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.37 | 0.01 | 05-MAR-15:30 | 2148.55 | 01-AUG-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 2.58 | 0.00 | 01-JAN-06:15 | 1811.11 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 14.79 | 0.00 | 01-JAN-00:15 | 2148.55 | 01-AUG-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.38 | 0.04 | 22-FEB-12:15 | 2139.99 | 08-JUL-16:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 2.58 | 0.00 | 01-JAN-06:15 | 1809.61 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 14.79 | 0.00 | 01-JAN-00:15 | 2139.99 | 08-JUL-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.83 | 0.08 | 22-APR-06:45 | 2338.36 | 10-OCT-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.48 | 0.00 | 01-JAN-05:15 | 1797.54 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 18.35 | 0.00 | 01-JAN-00:15 | 2338.36 | 10-OCT-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.84 | 0.00 | 20-JAN-01:00 | 2340.82 | 10-OCT-14:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.48 | 0.00 | 01-JAN-05:15 | 1798.05 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 18.36 | 0.00 | 01-JAN-00:15 | 2340.82 | 10-OCT-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 854.10 | 0.00 | 01-JAN-11:45 | 96644.70 | 20-AUG-15:30 |
HeatingCoils:EnergyTransfer | 85.99 | 0.00 | 01-JAN-11:45 | 67288.51 | 12-FEB-07:15 |
CoolingCoils:EnergyTransfer | 768.10 | 0.00 | 01-JAN-00:15 | 96644.70 | 20-AUG-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.360 | -10.704 | 0.000 | 0.000 | 3.744 | 2.413 | 12.213 | 11.988 | 0.000 | 0.237 | 0.000 | 0.000 | -5.099 | 0.000 | -3.248 | -12.904 |
G NW APARTMENT | 2.361 | -8.707 | 0.000 | 0.000 | 3.770 | 2.413 | 12.213 | 7.171 | 0.000 | 0.236 | 0.000 | 0.000 | -5.311 | 0.000 | -3.099 | -11.046 |
OFFICE | 0.346 | -24.214 | 0.000 | 0.000 | 0.520 | 21.914 | 7.534 | 12.072 | 0.000 | 0.223 | 0.000 | 0.000 | -4.903 | 0.000 | -2.276 | -11.216 |
G NE APARTMENT | 2.197 | -8.954 | 0.000 | 0.000 | 3.781 | 2.413 | 12.213 | 7.074 | 0.000 | 0.236 | 0.000 | 0.000 | -5.063 | 0.000 | -3.075 | -10.822 |
G N1 APARTMENT | 0.973 | -7.622 | 0.000 | 0.000 | 3.779 | 2.413 | 12.213 | 2.922 | 0.000 | 0.160 | 0.000 | 0.000 | -3.282 | 0.000 | -2.154 | -9.401 |
G N2 APARTMENT | 0.971 | -7.626 | 0.000 | 0.000 | 3.779 | 2.413 | 12.213 | 2.921 | 0.000 | 0.160 | 0.000 | 0.000 | -3.281 | 0.000 | -2.153 | -9.398 |
G S1 APARTMENT | 0.402 | -9.789 | 0.000 | 0.000 | 3.745 | 2.413 | 12.213 | 7.788 | 0.000 | 0.159 | 0.000 | 0.000 | -3.076 | 0.000 | -2.311 | -11.543 |
G S2 APARTMENT | 0.476 | -9.552 | 0.000 | 0.000 | 3.745 | 2.413 | 12.213 | 7.790 | 0.000 | 0.159 | 0.000 | 0.000 | -3.070 | 0.000 | -2.312 | -11.862 |
M SW APARTMENT | 0.765 | -44.651 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 11.434 | 0.000 | 0.332 | 24.449 | 0.000 | -5.796 | 0.000 | -4.781 | -0.000 |
M NW APARTMENT | 2.102 | -35.943 | 0.000 | 0.000 | 3.657 | 2.413 | 12.213 | 6.719 | 0.000 | 0.330 | 19.169 | 0.000 | -6.013 | 0.000 | -4.647 | -0.000 |
M SE APARTMENT | 0.794 | -45.271 | 0.000 | 0.000 | 3.628 | 2.413 | 12.213 | 11.450 | 0.000 | 0.332 | 24.867 | 0.000 | -5.654 | 0.000 | -4.771 | -0.001 |
M NE APARTMENT | 1.992 | -36.484 | 0.000 | 0.000 | 3.664 | 2.413 | 12.213 | 6.600 | 0.000 | 0.330 | 19.636 | 0.000 | -5.733 | 0.000 | -4.631 | -0.000 |
M N1 APARTMENT | 0.355 | -33.875 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 2.652 | 0.000 | 0.218 | 19.480 | 0.000 | -3.801 | 0.000 | -3.295 | 0.000 |
M N2 APARTMENT | 0.359 | -33.877 | 0.000 | 0.000 | 3.642 | 2.413 | 12.213 | 2.651 | 0.000 | 0.218 | 19.475 | 0.000 | -3.800 | 0.000 | -3.295 | 0.000 |
M S1 APARTMENT | 0.084 | -43.617 | 0.000 | 0.000 | 3.598 | 2.413 | 12.213 | 7.429 | 0.000 | 0.220 | 24.603 | 0.000 | -3.534 | 0.000 | -3.409 | 0.000 |
M S2 APARTMENT | 0.085 | -43.623 | 0.000 | 0.000 | 3.598 | 2.413 | 12.213 | 7.428 | 0.000 | 0.220 | 24.606 | 0.000 | -3.532 | 0.000 | -3.408 | 0.000 |
T SW APARTMENT | 3.364 | -19.821 | 0.000 | 0.000 | 3.687 | 2.413 | 12.213 | 11.289 | 0.000 | 0.443 | 0.000 | 0.000 | -5.429 | 0.000 | -5.923 | -2.236 |
T NW APARTMENT | 4.924 | -16.625 | 0.000 | 0.000 | 3.713 | 2.413 | 12.213 | 6.615 | 0.000 | 0.440 | 0.000 | 0.000 | -5.643 | 0.000 | -5.747 | -2.302 |
T SE APARTMENT | 3.257 | -19.946 | 0.000 | 0.000 | 3.693 | 2.413 | 12.213 | 11.317 | 0.000 | 0.443 | 0.001 | 0.000 | -5.303 | 0.000 | -5.918 | -2.170 |
T NE APARTMENT | 4.712 | -16.762 | 0.000 | 0.000 | 3.723 | 2.413 | 12.213 | 6.530 | 0.000 | 0.440 | 0.000 | 0.000 | -5.390 | 0.000 | -5.727 | -2.152 |
T N1 APARTMENT | 2.580 | -14.785 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 2.630 | 0.000 | 0.294 | 0.000 | 0.000 | -3.524 | 0.000 | -3.974 | -1.554 |
T N2 APARTMENT | 2.583 | -14.793 | 0.000 | 0.000 | 3.709 | 2.413 | 12.213 | 2.629 | 0.000 | 0.294 | 0.000 | 0.000 | -3.521 | 0.000 | -3.974 | -1.552 |
T S1 APARTMENT | 1.478 | -18.349 | 0.000 | 0.000 | 3.674 | 2.413 | 12.213 | 7.358 | 0.000 | 0.297 | 0.000 | 0.000 | -3.310 | 0.000 | -4.146 | -1.627 |
T S2 APARTMENT | 1.482 | -18.359 | 0.000 | 0.000 | 3.674 | 2.413 | 12.213 | 7.357 | 0.000 | 0.297 | 0.000 | 0.000 | -3.309 | 0.000 | -4.146 | -1.621 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.139 | 0.000 | 0.024 | 0.000 | 0.000 | -0.655 | 0.000 | -0.877 | -15.701 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.516 | 0.000 | 0.961 | 0.000 | 0.000 | -1.644 | 0.000 | -12.633 | -10.535 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.142 | 0.000 | 0.022 | 0.000 | 0.000 | -0.727 | 0.000 | -0.734 | -15.773 |
Total Facility | 40.002 | -543.952 | 0.000 | 0.000 | 85.495 | 128.627 | 294.692 | 172.611 | 0.000 | 7.726 | 176.286 | 0.000 | -109.403 | 0.000 | -106.665 | -145.418 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 18-AUG-17:08 | 0.00 | -1968.30 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1461.06 | 0.00 | 83.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.36 |
G NW APARTMENT | 01-AUG-17:08 | 0.00 | -1844.17 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1455.87 | 0.00 | 113.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -650.18 |
OFFICE | 25-SEP-11:00 | 0.00 | -3316.47 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2225.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1144.03 |
G NE APARTMENT | 01-AUG-17:08 | 0.00 | -1479.07 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 672.29 | 0.00 | 113.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -231.69 |
G N1 APARTMENT | 01-AUG-17:11 | 0.00 | -1158.33 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 427.98 | 0.00 | 68.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -263.05 |
G N2 APARTMENT | 01-AUG-17:08 | 0.00 | -1153.13 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 428.06 | 0.00 | 68.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -268.32 |
G S1 APARTMENT | 23-SEP-15:15 | 0.00 | -1313.10 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 1108.76 | 0.00 | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -447.98 |
G S2 APARTMENT | 23-SEP-15:15 | 0.00 | -1290.15 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 1109.13 | 0.00 | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.31 |
M SW APARTMENT | 11-OCT-16:15 | 0.00 | -4970.88 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 1883.80 | 0.00 | 60.86 | 2208.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 01-AUG-17:08 | 0.00 | -4648.64 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1440.22 | 0.00 | 162.91 | 2120.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 10-OCT-13:30 | 0.00 | -4256.43 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1978.61 | 0.00 | 43.63 | 1782.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 01-AUG-17:08 | 0.00 | -3899.48 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 661.61 | 0.00 | 162.91 | 2150.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 06-JUN-17:23 | 0.00 | -3062.90 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 464.80 | 0.00 | 122.42 | 1550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 06-JUN-17:23 | 0.00 | -3054.95 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 464.85 | 0.00 | 122.42 | 1542.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 11-OCT-15:30 | 0.00 | -3838.12 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 1125.31 | 0.00 | 104.84 | 1987.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 11-OCT-15:30 | 0.00 | -3833.59 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 1125.33 | 0.00 | 104.84 | 1982.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 18-AUG-16:05 | 0.00 | -3245.39 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1691.87 | 0.00 | 147.35 | 588.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 01-AUG-17:00 | 0.00 | -3093.05 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1474.17 | 0.00 | 249.51 | 551.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 18-AUG-13:00 | 0.00 | -2752.29 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1370.72 | 0.00 | 79.75 | 843.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 08-JUL-16:05 | 0.00 | -2591.55 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 813.66 | 0.00 | 92.97 | 867.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 01-AUG-17:08 | 0.00 | -2149.29 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 407.34 | 0.00 | 129.46 | 687.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 08-JUL-16:05 | 0.00 | -2141.15 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 497.13 | 0.00 | 56.08 | 770.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 10-OCT-14:15 | 0.00 | -2338.23 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1467.57 | 0.00 | 39.16 | 340.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 10-OCT-14:15 | 0.00 | -2340.70 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1467.52 | 0.00 | 39.16 | 342.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-AUG-17:08 | 0.00 | -61607.42 | 0.00 | 0.00 | 3261.64 | 6475.86 | 14071.03 | 17224.20 | 0.00 | 3495.24 | 17079.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 21-DEC-17:01 | 1939.88 | 0.00 | 0.00 | 0.00 | 99.77 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -305.94 | 0.00 | -208.96 | -2257.41 |
G NW APARTMENT | 26-MAR-06:01 | 1923.82 | 0.00 | 0.00 | 0.00 | 163.28 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -477.08 | 0.00 | -99.91 | -1986.35 |
OFFICE | 31-DEC-07:01 | 3936.87 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -412.61 | 0.00 | -177.44 | -3921.39 |
G NE APARTMENT | 12-FEB-01:00 | 1404.08 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -905.41 | 0.00 | -703.17 | -264.46 |
G N1 APARTMENT | 24-FEB-07:01 | 1249.49 | 0.00 | 0.00 | 0.00 | 161.37 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -336.97 | 0.00 | -104.76 | -1445.37 |
G N2 APARTMENT | 24-FEB-07:01 | 1248.84 | 0.00 | 0.00 | 0.00 | 161.37 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -336.95 | 0.00 | -104.76 | -1444.73 |
G S1 APARTMENT | 06-JAN-17:01 | 1133.43 | 0.00 | 0.00 | 0.00 | 98.73 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -306.74 | 0.00 | -91.49 | -1566.58 |
G S2 APARTMENT | 18-MAR-07:02 | 964.99 | 0.00 | 0.00 | 0.00 | 74.05 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -244.91 | 0.00 | -191.74 | -1034.09 |
M SW APARTMENT | 12-FEB-06:00 | 2604.95 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -978.86 | 0.00 | -962.36 | -1200.12 |
M NW APARTMENT | 12-FEB-06:00 | 2843.78 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -997.08 | 0.00 | -962.36 | -1420.74 |
M SE APARTMENT | 12-FEB-06:00 | 2635.46 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -962.53 | 0.00 | -962.36 | -1246.97 |
M NE APARTMENT | 12-FEB-06:00 | 2848.07 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -980.86 | 0.00 | -961.98 | -1441.63 |
M N1 APARTMENT | 10-JAN-10:30 | 1276.37 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -199.46 | 0.00 | -114.80 | -1444.48 |
M N2 APARTMENT | 09-FEB-07:02 | 2052.39 | 0.00 | 0.00 | 0.00 | 161.22 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -484.45 | 0.00 | -156.15 | -2049.24 |
M S1 APARTMENT | 11-FEB-22:23 | 1863.51 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -523.38 | 0.00 | -378.26 | -1655.89 |
M S2 APARTMENT | 10-JAN-06:23 | 1694.62 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -433.27 | 0.00 | -175.36 | -1694.34 |
T SW APARTMENT | 12-FEB-06:00 | 2715.33 | 0.00 | 0.00 | 0.00 | 189.96 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -950.96 | 0.00 | -1270.43 | -1030.63 |
T NW APARTMENT | 12-FEB-01:00 | 2736.93 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -922.20 | 0.00 | -1339.11 | -944.58 |
T SE APARTMENT | 12-FEB-06:00 | 2674.60 | 0.00 | 0.00 | 0.00 | 190.36 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.83 | 0.00 | -1267.99 | -1009.88 |
T NE APARTMENT | 12-FEB-01:00 | 2709.64 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -906.07 | 0.00 | -1337.58 | -934.95 |
T N1 APARTMENT | 12-FEB-06:00 | 1811.08 | 0.00 | 0.00 | 0.00 | 190.07 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.86 | 0.00 | -766.29 | -991.73 |
T N2 APARTMENT | 06-MAR-07:01 | 2203.22 | 0.00 | 0.00 | 0.00 | 163.43 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -315.30 | 0.00 | -145.61 | -2381.97 |
T S1 APARTMENT | 12-FEB-06:00 | 1797.51 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -569.72 | 0.00 | -768.04 | -996.16 |
T S2 APARTMENT | 12-FEB-06:00 | 1798.02 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -569.70 | 0.00 | -768.03 | -996.70 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-06:00 | 39960.63 | 0.00 | 0.00 | 0.00 | 4366.67 | 4156.84 | 6111.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18922.97 | 0.00 | -18982.29 | -16690.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sec1.1A-General InformationData | |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 34.75 |
Number of hours cooling loads not met | 0.75 |
Number of hours not met | 35.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 107.49 | 84110.63 | 0.00 | 0.00 |
Space Cooling | 188.36 | 25323.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 205.66 | 6521.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 362.28 | 18523.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1472.19 | 107.49 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1472.19 |
Natural Gas | 0.00 | 107.49 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1579.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 60.09 |
Fans-Interior | 65.61 |
Service Water Heating | 115.57 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.59 |
Subtotal | 469.66 |
Natural Gas [MJ/m2] | |
Space Heating | 34.29 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 34.29 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.45 |
Space Heating | 6.80 |
Space Cooling | 11.92 |
Fans-Interior | 13.02 |
Service Water Heating | 22.93 |
Receptacle Equipment | 32.37 |
Miscellaneous | 2.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.168996 |
G NW APARTMENT DIRECT AIR | 0.166977 |
OFFICE DIRECT AIR | 0.432340 |
G NE APARTMENT DIRECT AIR | 0.129926 |
G N1 APARTMENT DIRECT AIR | 0.107849 |
G N2 APARTMENT DIRECT AIR | 0.107143 |
G S1 APARTMENT DIRECT AIR | 0.105754 |
G S2 APARTMENT DIRECT AIR | 0.107958 |
M SW APARTMENT DIRECT AIR | 0.432982 |
M NW APARTMENT DIRECT AIR | 0.426056 |
M SE APARTMENT DIRECT AIR | 0.365256 |
M NE APARTMENT DIRECT AIR | 0.346556 |
M N1 APARTMENT DIRECT AIR | 0.284413 |
M N2 APARTMENT DIRECT AIR | 0.283265 |
M S1 APARTMENT DIRECT AIR | 0.282140 |
M S2 APARTMENT DIRECT AIR | 0.281055 |
T SW APARTMENT DIRECT AIR | 0.279217 |
T NW APARTMENT DIRECT AIR | 0.272495 |
T SE APARTMENT DIRECT AIR | 0.247708 |
T NE APARTMENT DIRECT AIR | 0.221475 |
T N1 APARTMENT DIRECT AIR | 0.186742 |
T N2 APARTMENT DIRECT AIR | 0.185463 |
T S1 APARTMENT DIRECT AIR | 0.199942 |
T S2 APARTMENT DIRECT AIR | 0.200507 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.168996 |
SPLIT GNW MAIN BRANCH | 0.166977 |
SPLIT OFFICE MAIN BRANCH | 0.432340 |
SPLIT GNE MAIN BRANCH | 0.129926 |
SPLIT GN1 MAIN BRANCH | 0.107849 |
SPLIT GN2 MAIN BRANCH | 0.107143 |
SPLIT GS1 MAIN BRANCH | 0.105754 |
SPLIT GS2 MAIN BRANCH | 0.107958 |
SPLIT MSW MAIN BRANCH | 0.432982 |
SPLIT MNW MAIN BRANCH | 0.426056 |
SPLIT MSE MAIN BRANCH | 0.365256 |
SPLIT MNE MAIN BRANCH | 0.346556 |
SPLIT MN1 MAIN BRANCH | 0.284413 |
SPLIT MN2 MAIN BRANCH | 0.283265 |
SPLIT MS1 MAIN BRANCH | 0.282140 |
SPLIT MS2 MAIN BRANCH | 0.281055 |
SPLIT TSW MAIN BRANCH | 0.279217 |
SPLIT TNW MAIN BRANCH | 0.272495 |
SPLIT TSE MAIN BRANCH | 0.247708 |
SPLIT TNE MAIN BRANCH | 0.221475 |
SPLIT TN1 MAIN BRANCH | 0.186742 |
SPLIT TN2 MAIN BRANCH | 0.185463 |
SPLIT TS1 MAIN BRANCH | 0.199942 |
SPLIT TS2 MAIN BRANCH | 0.200507 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.168996 |
SPLIT GNW | 0.166977 |
SPLIT OFFICE | 0.432340 |
SPLIT GNE | 0.129926 |
SPLIT GN1 | 0.107849 |
SPLIT GN2 | 0.107143 |
SPLIT GS1 | 0.105754 |
SPLIT GS2 | 0.107958 |
SPLIT MSW | 0.432982 |
SPLIT MNW | 0.426056 |
SPLIT MSE | 0.365256 |
SPLIT MNE | 0.346556 |
SPLIT MN1 | 0.284413 |
SPLIT MN2 | 0.283265 |
SPLIT MS1 | 0.282140 |
SPLIT MS2 | 0.281055 |
SPLIT TSW | 0.279217 |
SPLIT TNW | 0.272495 |
SPLIT TSE | 0.247708 |
SPLIT TNE | 0.221475 |
SPLIT TN1 | 0.186742 |
SPLIT TN2 | 0.185463 |
SPLIT TS1 | 0.199942 |
SPLIT TS2 | 0.200507 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.168996 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.166977 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.432340 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.129926 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.107849 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.107143 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.105754 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.107958 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.432982 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.426056 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.365256 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.346556 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.284413 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.283265 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.282140 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.281055 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.279217 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.272495 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.247708 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.221475 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.186742 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.185463 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.199942 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.200507 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.168996 | 3390.62 | 0.734340 |
SPLIT GNW COOLING COIL | 0.166977 | 3326.98 | 0.736450 |
SPLIT OFFICE COOLING COIL | 0.432340 | 7312.29 | 0.790835 |
SPLIT GNE COOLING COIL | 0.129926 | 2728.93 | 0.720759 |
SPLIT GN1 COOLING COIL | 0.107849 | 2321.54 | 0.713730 |
SPLIT GN2 COOLING COIL | 0.107143 | 2310.28 | 0.713248 |
SPLIT GS1 COOLING COIL | 0.105754 | 2296.78 | 0.711226 |
SPLIT GS2 COOLING COIL | 0.107958 | 2319.89 | 0.714216 |
SPLIT MSW COOLING COIL | 0.432982 | 8316.59 | 0.747852 |
SPLIT MNW COOLING COIL | 0.426056 | 8213.23 | 0.746708 |
SPLIT MSE COOLING COIL | 0.365256 | 7319.87 | 0.734687 |
SPLIT MNE COOLING COIL | 0.346556 | 6906.20 | 0.736399 |
SPLIT MN1 COOLING COIL | 0.284413 | 5770.56 | 0.730960 |
SPLIT MN2 COOLING COIL | 0.283265 | 5752.48 | 0.730688 |
SPLIT MS1 COOLING COIL | 0.282140 | 5809.54 | 0.726566 |
SPLIT MS2 COOLING COIL | 0.281055 | 5792.26 | 0.726307 |
SPLIT TSW COOLING COIL | 0.279217 | 5227.83 | 0.756052 |
SPLIT TNW COOLING COIL | 0.272495 | 5095.31 | 0.756476 |
SPLIT TSE COOLING COIL | 0.247708 | 4832.27 | 0.742976 |
SPLIT TNE COOLING COIL | 0.221475 | 4320.77 | 0.742958 |
SPLIT TN1 COOLING COIL | 0.186742 | 3662.48 | 0.741312 |
SPLIT TN2 COOLING COIL | 0.185463 | 3642.29 | 0.740896 |
SPLIT TS1 COOLING COIL | 0.199942 | 3990.48 | 0.735938 |
SPLIT TS2 COOLING COIL | 0.200507 | 3999.39 | 0.736118 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.168996 | 0.168996 | 0.168996 | 0.168996 | 2269.31 | 3390.62 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.166977 | 0.166977 | 0.166977 | 0.166977 | 2249.76 | 3326.98 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.432340 | 0.432340 | 0.432340 | 0.432340 | 4326.87 | 7312.29 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.129926 | 0.129926 | 0.129926 | 0.129926 | 2242.48 | 2728.93 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.107849 | 0.107849 | 0.107849 | 0.107849 | 1704.60 | 2321.54 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.107143 | 0.107143 | 0.107143 | 0.107143 | 1704.60 | 2310.28 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.105754 | 0.105754 | 0.105754 | 0.105754 | 1704.60 | 2296.78 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.107958 | 0.107958 | 0.107958 | 0.107958 | 1758.92 | 2319.89 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.432982 | 0.432982 | 0.432982 | 0.432982 | 4497.02 | 8316.59 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.426056 | 0.426056 | 0.426056 | 0.426056 | 4529.19 | 8213.23 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.365256 | 0.365256 | 0.365256 | 0.365256 | 4477.68 | 7319.87 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.346556 | 0.346556 | 0.346556 | 0.346556 | 4509.86 | 6906.20 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.284413 | 0.284413 | 0.284413 | 0.284413 | 3409.21 | 5770.56 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.283265 | 0.283265 | 0.283265 | 0.283265 | 3409.21 | 5752.48 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.282140 | 0.282140 | 0.282140 | 0.282140 | 3409.21 | 5809.54 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.281055 | 0.281055 | 0.281055 | 0.281055 | 3409.21 | 5792.26 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.279217 | 0.279217 | 0.279217 | 0.279217 | 3405.25 | 5227.83 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.272495 | 0.272495 | 0.272495 | 0.272495 | 3423.37 | 5095.31 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.247708 | 0.247708 | 0.247708 | 0.247708 | 3395.20 | 4832.27 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.221475 | 0.221475 | 0.221475 | 0.221475 | 3413.33 | 4320.77 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.186742 | 0.186742 | 0.186742 | 0.186742 | 2614.39 | 3662.48 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.185463 | 0.185463 | 0.185463 | 0.185463 | 2614.11 | 3642.29 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.199942 | 0.199942 | 0.199942 | 0.199942 | 2594.26 | 3990.48 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.200507 | 0.200507 | 0.200507 | 0.200507 | 2593.97 | 3999.39 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.168996 |
SPLIT GNW SUPPLY FAN | 0.166977 |
SPLIT OFFICE SUPPLY FAN | 0.432340 |
SPLIT GNE SUPPLY FAN | 0.129926 |
SPLIT GN1 SUPPLY FAN | 0.107849 |
SPLIT GN2 SUPPLY FAN | 0.107143 |
SPLIT GS1 SUPPLY FAN | 0.105754 |
SPLIT GS2 SUPPLY FAN | 0.107958 |
SPLIT MSW SUPPLY FAN | 0.432982 |
SPLIT MNW SUPPLY FAN | 0.426056 |
SPLIT MSE SUPPLY FAN | 0.365256 |
SPLIT MNE SUPPLY FAN | 0.346556 |
SPLIT MN1 SUPPLY FAN | 0.284413 |
SPLIT MN2 SUPPLY FAN | 0.283265 |
SPLIT MS1 SUPPLY FAN | 0.282140 |
SPLIT MS2 SUPPLY FAN | 0.281055 |
SPLIT TSW SUPPLY FAN | 0.279217 |
SPLIT TNW SUPPLY FAN | 0.272495 |
SPLIT TSE SUPPLY FAN | 0.247708 |
SPLIT TNE SUPPLY FAN | 0.221475 |
SPLIT TN1 SUPPLY FAN | 0.186742 |
SPLIT TN2 SUPPLY FAN | 0.185463 |
SPLIT TS1 SUPPLY FAN | 0.199942 |
SPLIT TS2 SUPPLY FAN | 0.200507 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2269.31 |
SPLIT GNW HEATING COIL | 2249.76 |
SPLIT OFFICE HEATING COIL | 4326.87 |
SPLIT GNE HEATING COIL | 2242.48 |
SPLIT GN1 HEATING COIL | 1704.60 |
SPLIT GN2 HEATING COIL | 1704.60 |
SPLIT GS1 HEATING COIL | 1704.60 |
SPLIT GS2 HEATING COIL | 1758.92 |
SPLIT MSW HEATING COIL | 4497.02 |
SPLIT MNW HEATING COIL | 4529.19 |
SPLIT MSE HEATING COIL | 4477.68 |
SPLIT MNE HEATING COIL | 4509.86 |
SPLIT MN1 HEATING COIL | 3409.21 |
SPLIT MN2 HEATING COIL | 3409.21 |
SPLIT MS1 HEATING COIL | 3409.21 |
SPLIT MS2 HEATING COIL | 3409.21 |
SPLIT TSW HEATING COIL | 3405.25 |
SPLIT TNW HEATING COIL | 3423.37 |
SPLIT TSE HEATING COIL | 3395.20 |
SPLIT TNE HEATING COIL | 3413.33 |
SPLIT TN1 HEATING COIL | 2614.39 |
SPLIT TN2 HEATING COIL | 2614.11 |
SPLIT TS1 HEATING COIL | 2594.26 |
SPLIT TS2 HEATING COIL | 2593.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 3.96 |
February | 22.23 | 7.94 |
March | 22.97 | 13.76 |
April | 23.55 | 17.21 |
May | 24.05 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.52 | 16.03 |
November | 22.84 | 11.94 |
December | 22.18 | 7.70 |
Annual Sum or Average | 23.41 | 16.65 |
Minimum of Months | 21.90 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 22.00 | 7.94 |
March | 22.62 | 13.76 |
April | 23.42 | 17.21 |
May | 24.04 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.22 | 16.03 |
November | 22.38 | 11.94 |
December | 21.86 | 7.70 |
Annual Sum or Average | 23.24 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | 3.96 |
February | 21.98 | 7.94 |
March | 23.29 | 13.76 |
April | 23.65 | 17.21 |
May | 23.87 | 20.84 |
June | 23.90 | 24.80 |
July | 23.90 | 26.06 |
August | 23.90 | 26.55 |
September | 23.90 | 22.53 |
October | 23.63 | 16.03 |
November | 23.05 | 11.94 |
December | 21.99 | 7.70 |
Annual Sum or Average | 23.19 | 16.65 |
Minimum of Months | 21.17 | 3.96 |
Maximum of Months | 23.90 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.96 |
February | 21.96 | 7.94 |
March | 22.52 | 13.76 |
April | 23.37 | 17.21 |
May | 24.01 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.37 | 22.53 |
October | 23.17 | 16.03 |
November | 22.28 | 11.94 |
December | 21.81 | 7.70 |
Annual Sum or Average | 23.21 | 16.65 |
Minimum of Months | 21.74 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 21.95 | 7.94 |
March | 22.46 | 13.76 |
April | 23.29 | 17.21 |
May | 23.95 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.18 | 16.03 |
November | 22.30 | 11.94 |
December | 21.84 | 7.70 |
Annual Sum or Average | 23.20 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.96 |
February | 21.95 | 7.94 |
March | 22.46 | 13.76 |
April | 23.28 | 17.21 |
May | 23.95 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.17 | 16.03 |
November | 22.29 | 11.94 |
December | 21.84 | 7.70 |
Annual Sum or Average | 23.19 | 16.65 |
Minimum of Months | 21.74 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 3.96 |
February | 22.24 | 7.94 |
March | 22.92 | 13.76 |
April | 23.47 | 17.21 |
May | 23.98 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.56 | 16.03 |
November | 22.88 | 11.94 |
December | 22.22 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 21.91 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 3.96 |
February | 22.25 | 7.94 |
March | 22.92 | 13.76 |
April | 23.47 | 17.21 |
May | 23.98 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.56 | 16.03 |
November | 22.88 | 11.94 |
December | 22.22 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 21.91 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.42 | 3.96 |
February | 23.04 | 7.94 |
March | 24.18 | 13.76 |
April | 24.33 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.31 | 16.03 |
November | 24.01 | 11.94 |
December | 23.04 | 7.70 |
Annual Sum or Average | 23.95 | 16.65 |
Minimum of Months | 22.42 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 3.96 |
February | 22.73 | 7.94 |
March | 23.98 | 13.76 |
April | 24.29 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.23 | 16.03 |
November | 23.58 | 11.94 |
December | 22.32 | 7.70 |
Annual Sum or Average | 23.76 | 16.65 |
Minimum of Months | 21.95 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.36 | 3.96 |
February | 22.99 | 7.94 |
March | 24.15 | 13.76 |
April | 24.33 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.30 | 16.03 |
November | 23.99 | 11.94 |
December | 22.99 | 7.70 |
Annual Sum or Average | 23.93 | 16.65 |
Minimum of Months | 22.36 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 3.96 |
February | 22.70 | 7.94 |
March | 23.94 | 13.76 |
April | 24.29 | 17.21 |
May | 24.39 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.19 | 16.03 |
November | 23.53 | 11.94 |
December | 22.24 | 7.70 |
Annual Sum or Average | 23.74 | 16.65 |
Minimum of Months | 21.90 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 3.96 |
February | 22.84 | 7.94 |
March | 24.12 | 13.76 |
April | 24.33 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.31 | 16.03 |
November | 23.77 | 11.94 |
December | 22.51 | 7.70 |
Annual Sum or Average | 23.83 | 16.65 |
Minimum of Months | 22.03 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 3.96 |
February | 22.84 | 7.94 |
March | 24.12 | 13.76 |
April | 24.33 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.31 | 16.03 |
November | 23.76 | 11.94 |
December | 22.50 | 7.70 |
Annual Sum or Average | 23.83 | 16.65 |
Minimum of Months | 22.03 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 3.96 |
February | 23.25 | 7.94 |
March | 24.28 | 13.76 |
April | 24.36 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.37 | 16.03 |
November | 24.19 | 11.94 |
December | 23.45 | 7.70 |
Annual Sum or Average | 24.05 | 16.65 |
Minimum of Months | 22.72 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 3.96 |
February | 23.24 | 7.94 |
March | 24.28 | 13.76 |
April | 24.36 | 17.21 |
May | 24.40 | 20.84 |
June | 24.40 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.40 | 22.53 |
October | 24.37 | 16.03 |
November | 24.19 | 11.94 |
December | 23.45 | 7.70 |
Annual Sum or Average | 24.05 | 16.65 |
Minimum of Months | 22.71 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 3.96 |
February | 22.66 | 7.94 |
March | 23.52 | 13.76 |
April | 24.06 | 17.21 |
May | 24.33 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.37 | 22.53 |
October | 23.81 | 16.03 |
November | 23.29 | 11.94 |
December | 22.49 | 7.70 |
Annual Sum or Average | 23.66 | 16.65 |
Minimum of Months | 22.15 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 3.96 |
February | 22.40 | 7.94 |
March | 23.28 | 13.76 |
April | 23.99 | 17.21 |
May | 24.33 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.36 | 22.53 |
October | 23.59 | 16.03 |
November | 22.90 | 11.94 |
December | 22.07 | 7.70 |
Annual Sum or Average | 23.50 | 16.65 |
Minimum of Months | 21.87 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 3.96 |
February | 22.62 | 7.94 |
March | 23.51 | 13.76 |
April | 24.06 | 17.21 |
May | 24.33 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.36 | 22.53 |
October | 23.78 | 16.03 |
November | 23.28 | 11.94 |
December | 22.46 | 7.70 |
Annual Sum or Average | 23.65 | 16.65 |
Minimum of Months | 22.11 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 3.96 |
February | 22.35 | 7.94 |
March | 23.23 | 13.76 |
April | 23.98 | 17.21 |
May | 24.32 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.35 | 22.53 |
October | 23.54 | 16.03 |
November | 22.82 | 11.94 |
December | 22.00 | 7.70 |
Annual Sum or Average | 23.47 | 16.65 |
Minimum of Months | 21.84 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 3.96 |
February | 22.44 | 7.94 |
March | 23.32 | 13.76 |
April | 24.02 | 17.21 |
May | 24.34 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.36 | 22.53 |
October | 23.66 | 16.03 |
November | 22.91 | 11.94 |
December | 22.07 | 7.70 |
Annual Sum or Average | 23.52 | 16.65 |
Minimum of Months | 21.86 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 3.96 |
February | 22.43 | 7.94 |
March | 23.31 | 13.76 |
April | 24.02 | 17.21 |
May | 24.34 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.36 | 22.53 |
October | 23.66 | 16.03 |
November | 22.90 | 11.94 |
December | 22.06 | 7.70 |
Annual Sum or Average | 23.52 | 16.65 |
Minimum of Months | 21.86 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 3.96 |
February | 22.76 | 7.94 |
March | 23.64 | 13.76 |
April | 24.11 | 17.21 |
May | 24.35 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.93 | 16.03 |
November | 23.42 | 11.94 |
December | 22.61 | 7.70 |
Annual Sum or Average | 23.72 | 16.65 |
Minimum of Months | 22.22 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 3.96 |
February | 22.76 | 7.94 |
March | 23.64 | 13.76 |
April | 24.11 | 17.21 |
May | 24.35 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.38 | 22.53 |
October | 23.93 | 16.03 |
November | 23.42 | 11.94 |
December | 22.61 | 7.70 |
Annual Sum or Average | 23.72 | 16.65 |
Minimum of Months | 22.22 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 3.96 |
February | 23.02 | 7.94 |
March | 24.70 | 13.76 |
April | 25.75 | 17.21 |
May | 26.51 | 20.84 |
June | 27.00 | 24.80 |
July | 27.16 | 26.06 |
August | 27.21 | 26.55 |
September | 26.60 | 22.53 |
October | 25.23 | 16.03 |
November | 24.07 | 11.94 |
December | 22.70 | 7.70 |
Annual Sum or Average | 25.18 | 16.65 |
Minimum of Months | 22.03 | 3.96 |
Maximum of Months | 27.21 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | 3.96 |
February | 21.41 | 7.94 |
March | 22.87 | 13.76 |
April | 23.85 | 17.21 |
May | 24.71 | 20.84 |
June | 26.37 | 24.80 |
July | 26.69 | 26.06 |
August | 26.80 | 26.55 |
September | 26.14 | 22.53 |
October | 23.81 | 16.03 |
November | 22.58 | 11.94 |
December | 21.40 | 7.70 |
Annual Sum or Average | 23.94 | 16.65 |
Minimum of Months | 20.55 | 3.96 |
Maximum of Months | 26.80 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.79 | 3.96 |
February | 24.65 | 7.94 |
March | 26.20 | 13.76 |
April | 26.59 | 17.21 |
May | 26.84 | 20.84 |
June | 27.03 | 24.80 |
July | 27.08 | 26.06 |
August | 27.11 | 26.55 |
September | 26.88 | 22.53 |
October | 26.46 | 16.03 |
November | 25.84 | 11.94 |
December | 24.56 | 7.70 |
Annual Sum or Average | 26.09 | 16.65 |
Minimum of Months | 23.79 | 3.96 |
Maximum of Months | 27.11 | 26.55 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.114108E+12 | 73161.994 | 21-JAN-18:30 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29102.967 | 0.000 | 0.000 | 0.000 |
February | 0.104427E+12 | 72457.063 | 28-FEB-18:00 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 5863.822 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22534.215 | 0.000 | 0.000 | 0.000 |
March | 0.118093E+12 | 79650.844 | 30-MAR-17:45 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 14591.268 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23508.879 | 0.000 | 0.000 | 0.000 |
April | 0.117977E+12 | 77508.047 | 17-APR-17:15 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 14168.561 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21788.789 | 0.000 | 0.000 | 0.000 |
May | 0.127366E+12 | 79453.761 | 19-MAY-17:15 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 17501.666 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20401.398 | 0.000 | 0.000 | 0.000 |
June | 0.133480E+12 | 83349.019 | 06-JUN-17:00 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 21775.398 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20022.924 | 0.000 | 0.000 | 0.000 |
July | 0.141761E+12 | 83927.432 | 12-JUL-17:15 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 22188.349 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20188.386 | 0.000 | 0.000 | 0.000 |
August | 0.144380E+12 | 85397.890 | 01-AUG-17:15 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 25323.253 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18523.940 | 0.000 | 0.000 | 0.000 |
September | 0.127509E+12 | 82681.088 | 06-SEP-17:15 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 20924.700 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20205.691 | 0.000 | 0.000 | 0.000 |
October | 0.118502E+12 | 77278.890 | 18-OCT-18:45 | 9689.078 | 23563.017 | 6521.509 | 0.000 | 13828.561 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21168.395 | 0.000 | 0.000 | 0.000 |
November | 0.110838E+12 | 71475.166 | 19-NOV-18:30 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 6254.001 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21162.138 | 0.000 | 0.000 | 0.000 |
December | 0.113752E+12 | 69989.128 | 23-DEC-18:45 | 8572.775 | 26456.413 | 6521.509 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25930.101 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.147219E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.104427E+12 | 69989.128 | 8572.775 | 23563.017 | 6521.509 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18523.940 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.144380E+12 | 85397.890 | 9689.078 | 26456.413 | 6521.509 | 0.000 | 25323.253 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29102.967 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.467998E+11 | 61719.682 | 08-JAN-01:15 | 61719.682 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 61719.682 |
February | 0.276285E+11 | 84110.632 | 12-FEB-07:15 | 84110.632 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 84110.632 |
March | 0.290367E+10 | 15263.771 | 18-MAR-07:15 | 15263.771 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15263.771 |
April | 0.878903E+09 | 13673.346 | 06-APR-06:15 | 13673.346 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13673.346 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.715287E+09 | 12480.291 | 26-OCT-05:00 | 12480.291 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12480.291 |
November | 0.640840E+10 | 35454.116 | 22-NOV-05:00 | 35454.116 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35454.116 |
December | 0.221587E+11 | 40900.890 | 03-DEC-07:15 | 40900.890 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 40900.890 |
Annual Sum or Average | 0.107493E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.467998E+11 | 84110.632 | 84110.632 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 84110.632 |