Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2018-10-19 09:20:28


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1900.88 606.42 673.12
Net Site Energy 1900.88 606.42 673.12
Total Source Energy 5051.88 1611.64 1788.92
Net Source Energy 5051.88 1611.64 1788.92


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 464.81 0.00 0.00 0.00 0.00
Cooling 89.46 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.36 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 207.70 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 423.12 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1436.07 464.81 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 464.81 0.00 0.00 0.00 0.00
Cooling General 89.46 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.36 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 207.70 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 423.12 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.37 0.00 0.00 0.00 0.00 0.00
HVAC 255.06 164.60 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 508.53 164.60 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.20 0.00 0.00 0.00 0.00 0.00
HVAC 229.78 148.28 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 458.13 148.28 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1436.07 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1436.07 100.00
     
Total On-Site and Utility Electric Sources 1436.07 100.00
Total Electricity End Uses 1436.07 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 39.25
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2897.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-SEP-17:30 06-FEB-09:00 - - - 01-JAN-07:15
Heating 0.00 107780.22 0.00 0.00 0.00 0.00
Cooling 16341.16 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6586.28 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 29698.25 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 87654.88 107780.22 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 107780.22 0.00 0.00 0.00 0.00
Cooling General 16341.16 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6586.28 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 29698.25 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 503.86 0.00 0.00 0.00
Cooling 283.31 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.67 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 657.80 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1340.02 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4548.02 503.86 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 178.42 0.00 0.00 0.00
Cooling 100.32 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.15 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 232.93 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 474.52 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1610.50 178.42 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 178.42 0.00 0.00 0.00
Cooling 100.32 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.15 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 232.93 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 474.52 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1610.50 178.42 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.60 83.60 39.36
Exterior Lighting Total 2508.33           39.36



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3083.65 2321.23 762.42 0.75 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   2915.02 2193.39 721.63 0.75 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7219.71 5766.06 1453.65 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2221.52 1631.17 590.35 0.73 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1902.71 1385.63 517.08 0.73 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1886.48 1372.37 514.11 0.73 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2131.51 1533.43 598.07 0.72 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2178.83 1572.47 606.36 0.72 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   8201.57 6297.52 1904.05 0.77 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   7735.53 5924.59 1810.93 0.77 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7489.06 5648.04 1841.01 0.75 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6245.67 4712.32 1533.35 0.75 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5162.41 3870.29 1292.12 0.75 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5135.19 3847.83 1287.35 0.75 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5844.01 4341.92 1502.09 0.74 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5864.15 4358.54 1505.60 0.74 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5291.41 4093.26 1198.14 0.77 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4907.28 3794.90 1112.38 0.77 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5013.69 3844.89 1168.80 0.77 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4038.03 3076.46 961.57 0.76 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3289.32 2494.07 795.24 0.76 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3259.06 2469.13 789.93 0.76 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4165.21 3179.58 985.63 0.76 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4178.91 3190.93 987.98 0.76 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2955.6 3.21 10.95 11.39 10.78
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2794.1 3.21 10.95 11.39 10.78
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6877.9 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2134.5 3.24 11.06 11.51 10.95
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1829.7 3.25 11.10 11.55 11.00
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1814.2 3.25 11.10 11.56 11.01
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2052.1 3.27 11.15 11.61 11.08
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2097.0 3.26 11.14 11.60 11.06
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7845.4 3.18 10.85 11.29 10.64
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7401.5 3.18 10.87 11.30 10.66
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7176.8 3.21 10.94 11.38 10.76
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 5985.0 3.20 10.94 11.38 10.76
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4950.1 3.21 10.96 11.41 10.80
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4924.3 3.21 10.97 11.41 10.81
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5608.7 3.23 11.01 11.45 10.87
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5627.8 3.23 11.00 11.45 10.86
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5057.8 3.17 10.82 11.25 10.59
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4690.8 3.17 10.82 11.25 10.59
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4796.6 3.18 10.86 11.29 10.65
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3865.7 3.19 10.89 11.33 10.70
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3150.5 3.20 10.91 11.35 10.73
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3121.8 3.20 10.92 11.35 10.73
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3986.7 3.19 10.88 11.32 10.68
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3999.7 3.19 10.88 11.32 10.68
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   3204.85 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   3164.77 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   5789.98 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   3154.66 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   2376.95 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   2376.71 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   2377.78 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   2504.39 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   6444.49 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   6448.06 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   6418.12 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   6421.67 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   4468.65 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   4468.00 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   4467.39 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   4466.74 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   4763.33 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   4766.82 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   4749.57 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   4753.05 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   3694.67 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   3694.31 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   3689.64 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   3689.28 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 182.61 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.45 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.44 488.53 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 123.99 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.09 104.09 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.09 102.94 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 113.14 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 116.57 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 508.46 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 476.79 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 445.44 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 371.85 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.81 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 300.84 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 335.54 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 337.01 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 333.62 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 309.17 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 309.93 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.90 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.10 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 195.91 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.79 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.79 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1691.22 2029.46 0.136 0.163 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.30 0.01335
G NW APARTMENT 1597.19 1916.63 0.128 0.154 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 27.72 0.01335
OFFICE 4437.43 5324.92 0.363 0.436 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 25.18 0.01335
G NE APARTMENT 1148.27 1377.92 0.092 0.111 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.11 0.01335
G N1 APARTMENT 964.05 1156.86 0.077 0.093 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 26.67 0.01335
G N2 APARTMENT 953.37 1144.04 0.077 0.092 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 26.67 0.01335
G S1 APARTMENT 1047.86 1257.44 0.084 0.101 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
G S2 APARTMENT 1079.64 1295.56 0.087 0.104 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
M SW APARTMENT 4709.04 5650.84 0.378 0.454 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.30 0.01335
M NW APARTMENT 4415.72 5298.87 0.355 0.426 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 27.72 0.01335
M SE APARTMENT 4125.24 4950.29 0.331 0.398 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.07 0.01335
M NE APARTMENT 3443.71 4132.46 0.277 0.332 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 27.46 0.01335
M N1 APARTMENT 2804.50 3365.40 0.225 0.270 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 26.67 0.01335
M N2 APARTMENT 2786.23 3343.48 0.224 0.269 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 26.67 0.01335
M S1 APARTMENT 3107.59 3729.11 0.250 0.300 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
M S2 APARTMENT 3121.14 3745.37 0.251 0.301 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
T SW APARTMENT 3089.50 3707.40 0.248 0.298 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 29.37 0.01335
T NW APARTMENT 2863.33 3435.99 0.230 0.276 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.30 0.01335
T SE APARTMENT 2870.18 3444.22 0.231 0.277 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
T NE APARTMENT 2277.17 2732.60 0.183 0.220 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 28.39 0.01335
T N1 APARTMENT 1834.74 2201.69 0.147 0.177 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.07 0.01335
T N2 APARTMENT 1814.45 2177.34 0.146 0.175 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.07 0.01335
T S1 APARTMENT 2359.64 2831.57 0.190 0.227 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30 0.01335
T S2 APARTMENT 2368.92 2842.71 0.190 0.228 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30 0.01335


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1690.57 2028.68 0.050 0.060 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G NW APARTMENT 1692.51 2031.01 0.050 0.060 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
OFFICE 3504.10 4204.92 0.100 0.120 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G NE APARTMENT 1683.96 2020.75 0.050 0.060 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G N1 APARTMENT 1026.28 1231.53 0.030 0.036 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G N2 APARTMENT 1026.08 1231.29 0.030 0.036 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G S1 APARTMENT 1026.99 1232.38 0.030 0.036 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
G S2 APARTMENT 1134.05 1360.86 0.033 0.040 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
M SW APARTMENT 3482.36 4178.83 0.103 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M NW APARTMENT 3485.38 4182.46 0.103 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M SE APARTMENT 3460.06 4152.07 0.102 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M NE APARTMENT 3463.06 4155.68 0.102 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M N1 APARTMENT 1811.42 2173.71 0.053 0.064 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M N2 APARTMENT 1810.87 2173.04 0.053 0.064 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M S1 APARTMENT 1810.36 2172.43 0.053 0.064 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
M S2 APARTMENT 1809.80 2171.77 0.053 0.064 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T SW APARTMENT 3044.44 3653.33 0.090 0.108 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T NW APARTMENT 3047.39 3656.87 0.090 0.108 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T SE APARTMENT 3032.80 3639.36 0.090 0.107 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T NE APARTMENT 3035.74 3642.89 0.090 0.108 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T N1 APARTMENT 2140.67 2568.81 0.063 0.076 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T N2 APARTMENT 2140.36 2568.44 0.063 0.076 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T S1 APARTMENT 2136.42 2563.71 0.063 0.076 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092
T S2 APARTMENT 2136.11 2563.34 0.063 0.076 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -16.30 0.00092


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.16 0.16 0.06 0.06
SPLIT GNW 0.15 0.15 0.06 0.06
SPLIT OFFICE 0.44 0.44 0.12 0.12
SPLIT GNE 0.11 0.11 0.06 0.06
SPLIT GN1 0.09 0.09 0.04 0.04
SPLIT GN2 0.09 0.09 0.04 0.04
SPLIT GS1 0.10 0.10 0.04 0.04
SPLIT GS2 0.10 0.10 0.04 0.04
SPLIT MSW 0.45 0.45 0.12 0.12
SPLIT MNW 0.43 0.43 0.12 0.12
SPLIT MSE 0.40 0.40 0.12 0.12
SPLIT MNE 0.33 0.33 0.12 0.12
SPLIT MN1 0.27 0.27 0.06 0.06
SPLIT MN2 0.27 0.27 0.06 0.06
SPLIT MS1 0.30 0.30 0.06 0.06
SPLIT MS2 0.30 0.30 0.06 0.06
SPLIT TSW 0.30 0.30 0.11 0.11
SPLIT TNW 0.28 0.28 0.11 0.11
SPLIT TSE 0.28 0.28 0.11 0.11
SPLIT TNE 0.22 0.22 0.11 0.11
SPLIT TN1 0.18 0.18 0.08 0.08
SPLIT TN2 0.17 0.17 0.08 0.08
SPLIT TS1 0.23 0.23 0.08 0.08
SPLIT TS2 0.23 0.23 0.08 0.08



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3421.00 6422.75 1796.00
G NW APARTMENT 3591.25 6611.50 2184.00
OFFICE 617.75 1599.50 391.25
G NE APARTMENT 3577.50 6635.50 2214.75
G N1 APARTMENT 3078.75 6747.75 1885.25
G N2 APARTMENT 3081.00 6750.75 1888.50
G S1 APARTMENT 2760.25 6449.00 1302.50
G S2 APARTMENT 2927.50 6486.00 1515.00
M SW APARTMENT 3388.25 4718.00 611.75
M NW APARTMENT 3533.25 5080.50 1105.25
M SE APARTMENT 3343.25 4719.25 576.00
M NE APARTMENT 3463.50 5126.50 1062.00
M N1 APARTMENT 2735.00 4985.50 452.75
M N2 APARTMENT 2734.00 4989.25 452.25
M S1 APARTMENT 2756.50 4467.25 119.25
M S2 APARTMENT 2759.50 4468.75 119.75
T SW APARTMENT 4498.50 5498.50 2163.75
T NW APARTMENT 4708.75 5803.25 2581.25
T SE APARTMENT 4509.00 5483.50 2151.50
T NE APARTMENT 4694.00 5849.50 2588.50
T N1 APARTMENT 4187.25 5812.25 2150.50
T N2 APARTMENT 4188.75 5815.25 2151.25
T S1 APARTMENT 4005.00 5386.75 1677.50
T S2 APARTMENT 4007.25 5383.25 1676.50
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 5552.25 6871.25 2897.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.75 0.00 3.75 0.00
G NW APARTMENT 6.25 0.00 6.25 0.00
OFFICE 18.25 0.00 0.00 0.00
G NE APARTMENT 4.25 0.00 4.25 0.00
G N1 APARTMENT 2.50 0.00 2.50 0.00
G N2 APARTMENT 2.50 0.00 2.50 0.00
G S1 APARTMENT 1.50 0.00 1.50 0.00
G S2 APARTMENT 1.00 0.00 1.00 0.00
M SW APARTMENT 0.75 0.00 0.75 0.00
M NW APARTMENT 3.00 0.00 3.00 0.00
M SE APARTMENT 1.75 0.00 1.75 0.00
M NE APARTMENT 1.75 0.00 1.75 0.00
M N1 APARTMENT 1.25 0.00 1.25 0.00
M N2 APARTMENT 1.25 0.00 1.25 0.00
M S1 APARTMENT 1.25 0.00 1.25 0.00
M S2 APARTMENT 1.00 0.00 1.00 0.00
T SW APARTMENT 0.25 0.00 0.25 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.25 0.00 0.25 0.00
T NE APARTMENT 1.50 0.00 1.50 0.00
T N1 APARTMENT 2.75 0.00 2.75 0.00
T N2 APARTMENT 3.75 0.00 3.75 0.00
T S1 APARTMENT 1.25 0.00 1.25 0.00
T S2 APARTMENT 2.25 0.00 2.25 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 57.50 0.00 39.25 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.366 0.133 0.000 0.087
G NW APARTMENT 1.71 2.50 268.97 0.353 0.133 0.000 0.085
OFFICE 0.94 1.00 268.97 0.519 0.150 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.353 0.133 0.000 0.085
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.084
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.084
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.087
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.087
M SW APARTMENT 1.71 2.50 268.97 0.353 0.191 0.000 0.111
M NW APARTMENT 1.71 2.50 268.97 0.353 0.191 0.000 0.108
M SE APARTMENT 1.71 2.50 268.97 0.353 0.191 0.000 0.111
M NE APARTMENT 1.71 2.50 268.97 0.353 0.191 0.000 0.108
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.115 0.000 0.108
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.115 0.000 0.108
M S1 APARTMENT 1.71 2.50 268.97 0.353 0.115 0.000 0.111
M S2 APARTMENT 1.71 2.50 268.97 0.353 0.115 0.000 0.111
T SW APARTMENT 1.71 2.50 268.97 0.353 0.252 0.000 0.135
T NW APARTMENT 1.71 2.50 268.97 0.353 0.252 0.000 0.131
T SE APARTMENT 1.71 2.50 268.97 0.353 0.252 0.000 0.135
T NE APARTMENT 1.71 2.50 268.97 0.353 0.252 0.000 0.131
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.152 0.000 0.131
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.152 0.000 0.131
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.152 0.000 0.135
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.152 0.000 0.135
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.351 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.495 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.353 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.338 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 423.12 0.00 01-JAN-00:15 32760.80 11-FEB-07:30
WaterSystems:Electricity 423.12 0.00 01-JAN-00:15 32760.80 11-FEB-07:30
Water Heater:WaterSystems:Electricity 423.12 0.00 01-JAN-00:15 32760.80 11-FEB-07:30
Fans:Electricity 207.70 6586.28 01-JAN-03:00 6586.28 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
ElectricityPurchased:Plant 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
Cogeneration:ElectricityPurchased 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
ElectricityNet:Plant 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
Cogeneration:ElectricityNet 1436.07 19956.58 01-JAN-03:15 87654.88 16-SEP-17:30
ExteriorLights:Electricity 39.36 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.36 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
Electricity:HVAC 297.16 6586.28 01-JAN-03:00 29128.54 27-JUN-16:45
General:Fans:Electricity 207.70 6586.28 01-JAN-03:00 6586.28 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 89.46 0.00 01-JAN-00:15 22542.26 27-JUN-16:45


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 464.81 0.00 12-MAR-12:30 107780.22 06-FEB-10:00
Gas:HVAC 464.81 0.00 12-MAR-12:30 107780.22 06-FEB-10:00
Heating:Gas 464.81 0.00 12-MAR-12:30 107780.22 06-FEB-10:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1268.34 1206.44 07-APR-10:45 157461.39 27-JUN-17:15
EnergyTransfer:Building 528.29 1130.95 07-APR-11:15 57834.95 09-AUG-15:15
EnergyTransfer:Zone:G SW APARTMENT 13.00 0.00 05-JAN-13:45 1911.79 21-SEP-15:15
Heating:EnergyTransfer 185.70 0.00 09-MAR-16:45 56259.00 06-FEB-10:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 6.50 0.00 05-JAN-13:30 1831.27 06-FEB-10:00
Cooling:EnergyTransfer 342.59 0.00 02-JAN-07:15 57834.95 09-AUG-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 6.50 0.00 01-JAN-00:15 1911.79 21-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 13.19 0.03 08-JUN-10:00 1879.57 07-FEB-08:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 8.19 0.00 22-FEB-17:15 1879.57 07-FEB-08:30
Cooling:EnergyTransfer:Zone:G NW APARTMENT 4.99 0.00 01-JAN-00:15 1580.96 10-JUL-18:30
EnergyTransfer:Zone:OFFICE 20.67 0.09 30-MAY-00:30 3868.99 13-FEB-07:15
Heating:EnergyTransfer:Zone:OFFICE 0.72 0.00 01-JAN-00:15 3868.99 13-FEB-07:15
Cooling:EnergyTransfer:Zone:OFFICE 19.95 0.00 02-JAN-07:15 3297.21 21-SEP-13:15
EnergyTransfer:Zone:G NE APARTMENT 13.21 0.07 01-MAY-24:00 1842.59 06-FEB-10:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 8.06 0.00 09-MAR-16:15 1842.59 06-FEB-10:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 5.15 0.00 01-JAN-00:15 1195.87 21-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 8.77 0.05 21-MAY-14:15 1139.34 07-FEB-08:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.92 0.00 01-JAN-21:15 1139.34 07-FEB-08:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.85 0.00 01-JAN-00:15 1004.42 16-JUL-18:15
EnergyTransfer:Zone:G N2 APARTMENT 8.77 0.04 24-OCT-01:00 1137.36 07-FEB-08:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.92 0.00 01-JAN-21:15 1137.36 07-FEB-08:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.85 0.00 01-JAN-00:15 995.94 16-JUL-18:15
EnergyTransfer:Zone:G S1 APARTMENT 9.22 0.04 22-OCT-10:15 1360.80 21-SEP-14:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 2.65 0.00 01-JAN-17:15 1063.03 06-FEB-10:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 6.57 0.00 01-JAN-00:15 1360.80 21-SEP-14:15
EnergyTransfer:Zone:G S2 APARTMENT 9.53 0.15 05-NOV-10:00 1346.01 21-SEP-14:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 3.17 0.00 04-JAN-11:00 1139.83 13-FEB-04:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 6.36 0.00 01-JAN-00:15 1346.01 21-SEP-14:15
EnergyTransfer:Zone:M SW APARTMENT 36.80 0.02 04-NOV-18:45 5357.19 21-SEP-15:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 8.99 0.00 05-JAN-12:45 3839.31 06-FEB-10:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 27.82 0.00 01-JAN-00:15 5357.19 21-SEP-15:15
EnergyTransfer:Zone:M NW APARTMENT 34.36 0.14 21-MAY-08:45 4455.03 27-JUN-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 12.76 0.00 11-JAN-18:00 4032.51 06-FEB-10:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 21.60 0.00 01-JAN-00:15 4455.03 27-JUN-17:15
EnergyTransfer:Zone:M SE APARTMENT 36.97 0.41 26-OCT-08:30 4601.78 21-SEP-14:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 8.80 0.00 04-JAN-12:45 3776.26 13-FEB-04:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 28.17 0.00 01-JAN-00:15 4601.78 21-SEP-14:15
EnergyTransfer:Zone:M NE APARTMENT 34.45 0.10 10-OCT-13:45 3956.44 06-FEB-10:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 12.50 0.00 11-JAN-18:00 3956.44 06-FEB-10:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 21.95 0.00 01-JAN-00:15 3564.83 27-JUN-17:15
EnergyTransfer:Zone:M N1 APARTMENT 25.73 0.08 16-NOV-12:00 2997.47 27-JUN-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 3.88 0.00 01-JAN-04:00 2016.44 06-FEB-10:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 21.85 0.00 01-JAN-00:15 2997.47 27-JUN-17:15
EnergyTransfer:Zone:M N2 APARTMENT 25.71 0.43 29-MAR-05:30 2981.84 27-JUN-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 3.87 0.00 01-JAN-04:00 2014.63 06-FEB-10:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 21.84 0.00 01-JAN-00:15 2981.84 27-JUN-17:15
EnergyTransfer:Zone:M S1 APARTMENT 31.65 0.15 27-NOV-07:00 4069.79 21-SEP-14:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 1.98 0.00 01-JAN-04:00 1870.78 13-FEB-04:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 29.67 0.00 01-JAN-00:15 4069.79 21-SEP-14:15
EnergyTransfer:Zone:M S2 APARTMENT 31.64 0.06 05-NOV-15:00 4073.56 21-SEP-14:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 1.98 0.00 01-JAN-04:00 1870.04 13-FEB-04:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 29.66 0.00 01-JAN-00:15 4073.56 21-SEP-14:15
EnergyTransfer:Zone:T SW APARTMENT 25.34 0.03 27-OCT-17:00 3343.93 06-FEB-10:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 13.73 0.00 06-JAN-11:00 3343.93 06-FEB-10:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 11.61 0.00 01-JAN-00:15 3325.69 21-SEP-15:15
EnergyTransfer:Zone:T NW APARTMENT 25.40 0.02 18-SEP-01:45 3383.66 06-FEB-10:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 16.19 0.00 08-MAR-13:30 3383.66 06-FEB-10:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 9.21 0.00 01-JAN-00:15 2897.40 27-JUN-16:45
EnergyTransfer:Zone:T SE APARTMENT 25.20 0.02 26-NOV-20:30 3319.59 13-FEB-04:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 13.56 0.00 06-JAN-10:45 3319.59 13-FEB-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 11.64 0.00 01-JAN-00:15 2920.15 09-AUG-13:30
EnergyTransfer:Zone:T NE APARTMENT 25.25 0.02 28-MAR-10:30 3339.33 06-FEB-10:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 15.98 0.00 08-MAR-12:30 3339.33 06-FEB-10:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 9.28 0.00 01-JAN-00:15 2383.33 12-JUN-11:30
EnergyTransfer:Zone:T N1 APARTMENT 18.10 0.04 03-OCT-13:45 2238.32 06-FEB-03:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 9.65 0.00 22-FEB-17:15 2238.32 06-FEB-03:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 8.46 0.00 01-JAN-00:15 1964.94 16-JUL-18:00
EnergyTransfer:Zone:T N2 APARTMENT 18.11 0.04 20-NOV-12:45 2237.68 06-FEB-03:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 9.65 0.00 22-FEB-17:15 2237.68 06-FEB-03:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 8.46 0.00 01-JAN-00:15 1953.14 12-JUN-16:30
EnergyTransfer:Zone:T S1 APARTMENT 18.60 0.01 20-MAR-18:15 2611.88 21-SEP-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 7.54 0.00 04-JAN-12:30 2185.32 07-FEB-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 11.06 0.00 01-JAN-00:15 2611.88 21-SEP-14:15
EnergyTransfer:Zone:T S2 APARTMENT 18.60 0.00 18-APR-08:45 2613.20 21-SEP-14:15
Heating:EnergyTransfer:Zone:T S2 APARTMENT 7.54 0.00 04-JAN-12:30 2186.46 07-FEB-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 11.07 0.00 01-JAN-00:15 2613.20 21-SEP-14:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 740.05 0.00 12-MAR-18:45 101303.97 27-JUN-17:15
HeatingCoils:EnergyTransfer 371.85 0.00 12-MAR-12:30 86224.18 06-FEB-10:00
CoolingCoils:EnergyTransfer 368.20 0.00 01-JAN-00:15 101303.97 27-JUN-17:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 6.499 -6.505 0.000 0.000 3.870 2.413 12.213 10.691 0.000 0.082 0.000 0.000 -7.976 0.000 -6.346 -14.941
G NW APARTMENT 8.192 -4.994 0.000 0.000 3.884 2.413 12.213 5.802 0.000 0.082 0.000 0.000 -8.323 0.000 -6.255 -13.014
OFFICE 0.721 -19.945 0.000 0.000 0.537 21.914 7.534 10.757 0.000 0.061 0.000 0.000 -7.405 0.000 -5.042 -9.130
G NE APARTMENT 8.060 -5.153 0.000 0.000 3.893 2.413 12.213 5.729 0.000 0.082 0.000 0.000 -8.135 0.000 -6.245 -12.857
G N1 APARTMENT 3.919 -4.850 0.000 0.000 3.890 2.413 12.213 2.140 0.000 0.063 0.000 0.000 -5.177 0.000 -4.095 -10.516
G N2 APARTMENT 3.918 -4.852 0.000 0.000 3.891 2.413 12.213 2.139 0.000 0.063 0.000 0.000 -5.176 0.000 -4.095 -10.514
G S1 APARTMENT 2.649 -6.573 0.000 0.000 3.872 2.413 12.213 7.083 0.000 0.062 0.000 0.000 -4.852 0.000 -4.189 -12.678
G S2 APARTMENT 3.165 -6.364 0.000 0.000 3.872 2.413 12.213 7.086 0.000 0.062 0.000 0.000 -4.840 0.000 -4.191 -13.415
M SW APARTMENT 8.989 -27.816 0.000 0.000 3.773 2.413 12.213 10.277 0.000 0.114 7.888 0.000 -8.621 0.000 -9.230 -0.000
M NW APARTMENT 12.759 -21.598 0.000 0.000 3.802 2.413 12.213 5.471 0.000 0.113 2.847 0.000 -8.928 0.000 -9.093 -0.001
M SE APARTMENT 8.802 -28.171 0.000 0.000 3.778 2.413 12.213 10.263 0.000 0.114 8.286 0.000 -8.477 0.000 -9.221 -0.001
M NE APARTMENT 12.499 -21.952 0.000 0.000 3.809 2.413 12.213 5.396 0.000 0.113 3.308 0.000 -8.719 0.000 -9.080 -0.001
M N1 APARTMENT 3.880 -21.852 0.000 0.000 3.790 2.413 12.213 1.937 0.000 0.085 9.133 0.000 -5.618 0.000 -5.981 -0.000
M N2 APARTMENT 3.871 -21.843 0.000 0.000 3.791 2.413 12.213 1.937 0.000 0.085 9.131 0.000 -5.617 0.000 -5.981 -0.000
M S1 APARTMENT 1.979 -29.674 0.000 0.000 3.754 2.413 12.213 6.818 0.000 0.085 13.802 0.000 -5.283 0.000 -6.106 -0.000
M S2 APARTMENT 1.975 -29.664 0.000 0.000 3.754 2.413 12.213 6.817 0.000 0.085 13.795 0.000 -5.282 0.000 -6.106 -0.000
T SW APARTMENT 13.731 -11.612 0.000 0.000 3.828 2.413 12.213 10.200 0.000 0.156 0.000 0.000 -8.211 0.000 -11.848 -10.869
T NW APARTMENT 16.190 -9.206 0.000 0.000 3.846 2.413 12.213 5.425 0.000 0.156 0.000 0.000 -8.535 0.000 -11.703 -10.798
T SE APARTMENT 13.564 -11.636 0.000 0.000 3.832 2.413 12.213 10.202 0.000 0.156 0.000 0.000 -8.086 0.000 -11.851 -10.807
T NE APARTMENT 15.975 -9.278 0.000 0.000 3.854 2.413 12.213 5.370 0.000 0.156 0.000 0.000 -8.343 0.000 -11.694 -10.667
T N1 APARTMENT 9.647 -8.457 0.000 0.000 3.844 2.413 12.213 1.941 0.000 0.119 0.000 0.000 -5.326 0.000 -7.595 -8.799
T N2 APARTMENT 9.647 -8.464 0.000 0.000 3.844 2.413 12.213 1.940 0.000 0.119 0.000 0.000 -5.324 0.000 -7.595 -8.794
T S1 APARTMENT 7.535 -11.060 0.000 0.000 3.816 2.413 12.213 6.784 0.000 0.120 0.000 0.000 -5.030 0.000 -7.744 -9.047
T S2 APARTMENT 7.536 -11.066 0.000 0.000 3.816 2.413 12.213 6.783 0.000 0.120 0.000 0.000 -5.029 0.000 -7.745 -9.040
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.062 0.000 0.002 0.000 0.000 -1.053 0.000 -1.877 -14.205
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.249 0.000 0.079 2.726 0.000 -2.778 0.000 -23.611 -0.001
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.063 0.000 0.003 0.000 0.000 -1.148 0.000 -1.538 -14.450
Total Facility 185.702 -342.584 0.000 0.000 88.637 128.627 294.692 149.363 0.000 2.537 70.918 0.000 -167.292 0.000 -206.060 -204.546


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 21-SEP-15:15 0.00 -1911.73 0.00 0.00 48.90 100.83 470.90 2770.90 0.00 44.42 0.00 0.00 0.00 0.00 0.00 -1524.22
G NW APARTMENT 10-JUL-18:30 0.00 -1580.89 0.00 0.00 141.81 230.46 547.42 1641.93 0.00 70.88 0.00 0.00 0.00 0.00 0.00 -1051.61
OFFICE 21-SEP-13:15 0.00 -3297.18 0.00 0.00 67.31 1622.34 544.92 2349.52 0.00 10.79 0.00 0.00 0.00 0.00 0.00 -1297.69
G NE APARTMENT 21-JUL-17:15 0.00 -1195.91 0.00 0.00 141.81 194.45 588.62 406.54 0.00 63.51 0.00 0.00 0.00 0.00 0.00 -199.03
G N1 APARTMENT 16-JUL-18:15 0.00 -1004.62 0.00 0.00 141.81 230.46 547.42 366.72 0.00 72.54 0.00 0.00 0.00 0.00 0.00 -354.33
G N2 APARTMENT 16-JUL-18:15 0.00 -996.14 0.00 0.00 141.81 230.46 547.42 366.87 0.00 72.54 0.00 0.00 0.00 0.00 0.00 -362.96
G S1 APARTMENT 21-SEP-14:15 0.00 -1360.74 0.00 0.00 40.75 50.41 400.26 1840.67 0.00 36.87 0.00 0.00 0.00 0.00 0.00 -1008.22
G S2 APARTMENT 21-SEP-14:15 0.00 -1345.96 0.00 0.00 40.75 50.41 400.26 1840.89 0.00 36.87 0.00 0.00 0.00 0.00 0.00 -1023.23
M SW APARTMENT 21-SEP-15:15 0.00 -5357.07 0.00 0.00 48.90 100.83 470.90 2749.08 0.00 55.78 1931.58 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 27-JUN-17:15 0.00 -4454.72 0.00 0.00 141.84 194.45 588.62 1492.48 0.00 190.18 1847.15 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 21-SEP-14:15 0.00 -4601.67 0.00 0.00 40.75 50.41 400.26 1997.34 0.00 54.46 2058.44 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 27-JUN-17:15 0.00 -3564.60 0.00 0.00 141.84 194.45 588.62 505.50 0.00 190.17 1944.03 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 27-JUN-17:15 0.00 -2997.14 0.00 0.00 141.83 194.45 588.62 346.46 0.00 168.89 1556.88 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 27-JUN-17:15 0.00 -2981.52 0.00 0.00 141.83 194.45 588.62 346.56 0.00 168.89 1541.16 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 21-SEP-14:15 0.00 -4069.66 0.00 0.00 40.75 50.41 400.26 1825.20 0.00 48.44 1704.60 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 21-SEP-14:15 0.00 -4073.44 0.00 0.00 40.75 50.41 400.26 1825.16 0.00 48.44 1708.42 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 21-SEP-15:15 0.00 -3325.62 0.00 0.00 48.90 100.83 470.90 2711.18 0.00 67.71 0.00 0.00 0.00 0.00 0.00 -73.90
T NW APARTMENT 27-JUN-16:45 0.00 -2897.45 0.00 0.00 84.79 144.04 588.62 1620.28 0.00 248.95 210.77 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 09-AUG-13:30 0.00 -2919.96 0.00 0.00 40.75 28.81 382.60 1820.26 0.00 100.63 546.91 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 12-JUN-11:30 0.00 -2383.27 0.00 0.00 40.75 28.81 406.15 1020.37 0.00 203.15 684.05 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 16-JUL-18:00 0.00 -1965.80 0.00 0.00 141.81 194.45 588.62 349.52 0.00 170.00 521.39 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 12-JUN-16:30 0.00 -1953.94 0.00 0.00 84.76 144.04 588.62 326.43 0.00 136.33 673.76 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 21-SEP-14:15 0.00 -2611.80 0.00 0.00 40.75 50.41 400.26 1802.85 0.00 60.03 257.49 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 21-SEP-14:15 0.00 -2613.12 0.00 0.00 40.75 50.41 400.26 1802.81 0.00 60.03 258.85 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-AUG-15:15 0.00 -57833.54 0.00 0.00 1191.97 5565.24 11658.39 26755.47 0.00 1623.18 11039.30 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 06-FEB-10:00 1831.23 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -514.20 0.00 -963.70 -823.94
G NW APARTMENT 07-FEB-08:21 1880.65 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -730.75 0.00 -803.89 -851.68
OFFICE 13-NOV-07:01 5366.53 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -367.42 0.00 -241.11 -5332.56
G NE APARTMENT 06-FEB-10:00 1842.55 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -506.95 0.00 -963.70 -842.51
G N1 APARTMENT 22-NOV-17:01 1303.25 0.00 0.00 0.00 98.71 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -331.44 0.00 -83.53 -1719.65
G N2 APARTMENT 07-FEB-08:21 1138.45 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -434.98 0.00 -484.89 -724.26
G S1 APARTMENT 03-MAR-18:01 1632.47 0.00 0.00 0.00 168.44 194.45 588.62 0.00 0.00 0.00 0.00 0.00 -439.91 0.00 -316.27 -1827.81
G S2 APARTMENT 24-JAN-17:12 1246.46 0.00 0.00 0.00 98.63 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -471.12 0.00 -144.93 -1461.71
M SW APARTMENT 06-FEB-10:00 3839.25 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -545.67 0.00 -1385.67 -2378.52
M NW APARTMENT 06-FEB-10:00 4032.44 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -601.43 0.00 -1385.67 -2515.95
M SE APARTMENT 13-FEB-04:00 3776.22 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -826.19 0.00 -1422.43 -1955.35
M NE APARTMENT 06-FEB-10:00 3956.38 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -531.16 0.00 -1385.67 -2510.16
M N1 APARTMENT 18-JAN-07:01 2390.75 0.00 0.00 0.00 161.39 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -305.51 0.00 -258.17 -2464.69
M N2 APARTMENT 18-JAN-07:01 2397.61 0.00 0.00 0.00 161.39 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -305.51 0.00 -258.17 -2471.55
M S1 APARTMENT 31-JAN-18:18 2563.74 0.00 0.00 0.00 165.01 194.45 588.62 0.00 0.00 0.00 0.00 0.00 -527.05 0.00 -382.17 -2602.61
M S2 APARTMENT 31-JAN-18:27 2560.41 0.00 0.00 0.00 165.01 194.45 588.62 0.00 0.00 0.00 0.00 0.00 -527.06 0.00 -382.17 -2599.26
T SW APARTMENT 06-FEB-10:00 3343.89 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -529.75 0.00 -1834.80 -1449.95
T NW APARTMENT 06-FEB-10:00 3383.62 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -584.32 0.00 -1834.80 -1435.10
T SE APARTMENT 13-FEB-04:00 3319.55 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -805.76 0.00 -1883.87 -1057.67
T NE APARTMENT 06-FEB-10:00 3339.29 0.00 0.00 0.00 47.42 28.81 394.38 0.00 0.00 0.00 0.00 0.00 -513.17 0.00 -1834.80 -1461.92
T N1 APARTMENT 06-FEB-03:00 2238.27 0.00 0.00 0.00 189.67 14.40 229.56 0.00 0.00 0.00 0.00 0.00 -574.29 0.00 -921.46 -1176.15
T N2 APARTMENT 06-FEB-03:00 2237.63 0.00 0.00 0.00 189.67 14.40 229.56 0.00 0.00 0.00 0.00 0.00 -574.30 0.00 -921.46 -1175.50
T S1 APARTMENT 07-FEB-05:00 2185.33 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -593.83 0.00 -808.63 -1239.43
T S2 APARTMENT 07-FEB-05:00 2186.46 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -593.81 0.00 -808.63 -1240.57
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-FEB-10:00 56258.03 0.00 0.00 0.00 1168.60 3908.79 9898.41 0.00 0.00 0.00 0.00 0.00 -10455.88 0.00 -29358.56 -31419.39



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sec1.1A-General Information

Data
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 39.25
Number of hours cooling loads not met 0.00
Number of hours not met 39.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.36 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 464.81 107780.22 0.00 0.00
Space Cooling 89.46 16341.16 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 207.70 6586.28 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 423.12 29698.25 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1436.07   464.81   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1436.07
Natural Gas 0.00 464.81
Additional 0.00 0.00
Total 511.42 1900.88


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 28.54
Fans-Interior 66.26
Service Water Heating 134.98
Receptacle Equipment 163.15
Miscellaneous 12.56
Subtotal 458.13


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 148.28
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 148.28


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 8.68
Space Heating 24.45
Space Cooling 4.71
Fans-Interior 10.93
Service Water Heating 22.26
Receptacle Equipment 26.90
Miscellaneous 2.07



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.163025
G NW APARTMENT DIRECT AIR 0.153963
OFFICE DIRECT AIR 0.436143
G NE APARTMENT DIRECT AIR 0.110696
G N1 APARTMENT DIRECT AIR 0.092929
G N2 APARTMENT DIRECT AIR 0.091899
G S1 APARTMENT DIRECT AIR 0.101011
G S2 APARTMENT DIRECT AIR 0.104073
M SW APARTMENT DIRECT AIR 0.453934
M NW APARTMENT DIRECT AIR 0.425662
M SE APARTMENT DIRECT AIR 0.397677
M NE APARTMENT DIRECT AIR 0.331981
M N1 APARTMENT DIRECT AIR 0.270340
M N2 APARTMENT DIRECT AIR 0.268578
M S1 APARTMENT DIRECT AIR 0.299564
M S2 APARTMENT DIRECT AIR 0.300870
T SW APARTMENT DIRECT AIR 0.297842
T NW APARTMENT DIRECT AIR 0.276021
T SE APARTMENT DIRECT AIR 0.276699
T NE APARTMENT DIRECT AIR 0.219531
T N1 APARTMENT DIRECT AIR 0.176861
T N2 APARTMENT DIRECT AIR 0.174905
T S1 APARTMENT DIRECT AIR 0.227469
T S2 APARTMENT DIRECT AIR 0.228364


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.163025
SPLIT GNW MAIN BRANCH 0.153963
SPLIT OFFICE MAIN BRANCH 0.436143
SPLIT GNE MAIN BRANCH 0.110696
SPLIT GN1 MAIN BRANCH 0.092929
SPLIT GN2 MAIN BRANCH 0.091899
SPLIT GS1 MAIN BRANCH 0.101011
SPLIT GS2 MAIN BRANCH 0.104073
SPLIT MSW MAIN BRANCH 0.453934
SPLIT MNW MAIN BRANCH 0.425662
SPLIT MSE MAIN BRANCH 0.397677
SPLIT MNE MAIN BRANCH 0.331981
SPLIT MN1 MAIN BRANCH 0.270340
SPLIT MN2 MAIN BRANCH 0.268578
SPLIT MS1 MAIN BRANCH 0.299564
SPLIT MS2 MAIN BRANCH 0.300870
SPLIT TSW MAIN BRANCH 0.297842
SPLIT TNW MAIN BRANCH 0.276021
SPLIT TSE MAIN BRANCH 0.276699
SPLIT TNE MAIN BRANCH 0.219531
SPLIT TN1 MAIN BRANCH 0.176861
SPLIT TN2 MAIN BRANCH 0.174905
SPLIT TS1 MAIN BRANCH 0.227469
SPLIT TS2 MAIN BRANCH 0.228364


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.163025
SPLIT GNW 0.153963
SPLIT OFFICE 0.436143
SPLIT GNE 0.110696
SPLIT GN1 0.092929
SPLIT GN2 0.091899
SPLIT GS1 0.101011
SPLIT GS2 0.104073
SPLIT MSW 0.453934
SPLIT MNW 0.425662
SPLIT MSE 0.397677
SPLIT MNE 0.331981
SPLIT MN1 0.270340
SPLIT MN2 0.268578
SPLIT MS1 0.299564
SPLIT MS2 0.300870
SPLIT TSW 0.297842
SPLIT TNW 0.276021
SPLIT TSE 0.276699
SPLIT TNE 0.219531
SPLIT TN1 0.176861
SPLIT TN2 0.174905
SPLIT TS1 0.227469
SPLIT TS2 0.228364


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.163025 0.026898
SPLIT GNW OA CONTROLLER 0.153963 0.025953
SPLIT OFFICE OA CONTROLLER 0.436143 0.038104
SPLIT GNE OA CONTROLLER 0.110696 0.025953
SPLIT GN1 OA CONTROLLER 0.092929 0.025953
SPLIT GN2 OA CONTROLLER 0.091899 0.025953
SPLIT GS1 OA CONTROLLER 0.101011 0.025953
SPLIT GS2 OA CONTROLLER 0.104073 0.025953
SPLIT MSW OA CONTROLLER 0.453934 0.051906
SPLIT MNW OA CONTROLLER 0.425662 0.051906
SPLIT MSE OA CONTROLLER 0.397677 0.051906
SPLIT MNE OA CONTROLLER 0.331981 0.051906
SPLIT MN1 OA CONTROLLER 0.270340 0.051906
SPLIT MN2 OA CONTROLLER 0.268578 0.051906
SPLIT MS1 OA CONTROLLER 0.299564 0.051906
SPLIT MS2 OA CONTROLLER 0.300870 0.051906
SPLIT TSW OA CONTROLLER 0.297842 0.025953
SPLIT TNW OA CONTROLLER 0.276021 0.025953
SPLIT TSE OA CONTROLLER 0.276699 0.025953
SPLIT TNE OA CONTROLLER 0.219531 0.025953
SPLIT TN1 OA CONTROLLER 0.176861 0.025953
SPLIT TN2 OA CONTROLLER 0.174905 0.025953
SPLIT TS1 OA CONTROLLER 0.227469 0.025953
SPLIT TS2 OA CONTROLLER 0.228364 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.163025 3083.65 0.752753
SPLIT GNW COOLING COIL 0.153963 2915.02 0.752444
SPLIT OFFICE COOLING COIL 0.436143 7219.71 0.798655
SPLIT GNE COOLING COIL 0.110696 2221.52 0.734258
SPLIT GN1 COOLING COIL 0.092929 1902.71 0.728243
SPLIT GN2 COOLING COIL 0.091899 1886.48 0.727478
SPLIT GS1 COOLING COIL 0.101011 2131.51 0.719412
SPLIT GS2 COOLING COIL 0.104073 2178.83 0.721702
SPLIT MSW COOLING COIL 0.453934 8201.57 0.767844
SPLIT MNW COOLING COIL 0.425662 7735.53 0.765894
SPLIT MSE COOLING COIL 0.397677 7489.06 0.754173
SPLIT MNE COOLING COIL 0.331981 6245.67 0.754494
SPLIT MN1 COOLING COIL 0.270340 5162.41 0.749705
SPLIT MN2 COOLING COIL 0.268578 5135.19 0.749308
SPLIT MS1 COOLING COIL 0.299564 5844.01 0.742969
SPLIT MS2 COOLING COIL 0.300870 5864.15 0.743253
SPLIT TSW COOLING COIL 0.297842 5291.41 0.773568
SPLIT TNW COOLING COIL 0.276021 4907.28 0.773321
SPLIT TSE COOLING COIL 0.276699 5013.69 0.766878
SPLIT TNE COOLING COIL 0.219531 4038.03 0.761872
SPLIT TN1 COOLING COIL 0.176861 3289.32 0.758235
SPLIT TN2 COOLING COIL 0.174905 3259.06 0.757621
SPLIT TS1 COOLING COIL 0.227469 4165.21 0.763366
SPLIT TS2 COOLING COIL 0.228364 4178.91 0.763580


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.163025 0.163025 0.163025 0.163025 3204.85 3083.65 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.153963 0.153963 0.153963 0.153963 3164.77 2915.02 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.436143 0.436143 0.436143 0.436143 5789.98 7219.71 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.110696 0.110696 0.110696 0.110696 3154.66 2221.52 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.092929 0.092929 0.092929 0.092929 2376.95 1902.71 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.091899 0.091899 0.091899 0.091899 2376.71 1886.48 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.101011 0.101011 0.101011 0.101011 2377.78 2131.51 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.104073 0.104073 0.104073 0.104073 2504.39 2178.83 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.453934 0.453934 0.453934 0.453934 6444.49 8201.57 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.425662 0.425662 0.425662 0.425662 6448.06 7735.53 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.397677 0.397677 0.397677 0.397677 6418.12 7489.06 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.331981 0.331981 0.331981 0.331981 6421.67 6245.67 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.270340 0.270340 0.270340 0.270340 4468.65 5162.41 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.268578 0.268578 0.268578 0.268578 4468.00 5135.19 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.299564 0.299564 0.299564 0.299564 4467.39 5844.01 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.300870 0.300870 0.300870 0.300870 4466.74 5864.15 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.297842 0.297842 0.297842 0.297842 4763.33 5291.41 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.276021 0.276021 0.276021 0.276021 4766.82 4907.28 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.276699 0.276699 0.276699 0.276699 4749.57 5013.69 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.219531 0.219531 0.219531 0.219531 4753.05 4038.03 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.176861 0.176861 0.176861 0.176861 3694.67 3289.32 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.174905 0.174905 0.174905 0.174905 3694.31 3259.06 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.227469 0.227469 0.227469 0.227469 3689.64 4165.21 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.228364 0.228364 0.228364 0.228364 3689.28 4178.91 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.163025
SPLIT GNW SUPPLY FAN 0.153963
SPLIT OFFICE SUPPLY FAN 0.436143
SPLIT GNE SUPPLY FAN 0.110696
SPLIT GN1 SUPPLY FAN 0.092929
SPLIT GN2 SUPPLY FAN 0.091899
SPLIT GS1 SUPPLY FAN 0.101011
SPLIT GS2 SUPPLY FAN 0.104073
SPLIT MSW SUPPLY FAN 0.453934
SPLIT MNW SUPPLY FAN 0.425662
SPLIT MSE SUPPLY FAN 0.397677
SPLIT MNE SUPPLY FAN 0.331981
SPLIT MN1 SUPPLY FAN 0.270340
SPLIT MN2 SUPPLY FAN 0.268578
SPLIT MS1 SUPPLY FAN 0.299564
SPLIT MS2 SUPPLY FAN 0.300870
SPLIT TSW SUPPLY FAN 0.297842
SPLIT TNW SUPPLY FAN 0.276021
SPLIT TSE SUPPLY FAN 0.276699
SPLIT TNE SUPPLY FAN 0.219531
SPLIT TN1 SUPPLY FAN 0.176861
SPLIT TN2 SUPPLY FAN 0.174905
SPLIT TS1 SUPPLY FAN 0.227469
SPLIT TS2 SUPPLY FAN 0.228364


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 3204.85
SPLIT GNW HEATING COIL 3164.77
SPLIT OFFICE HEATING COIL 5789.98
SPLIT GNE HEATING COIL 3154.66
SPLIT GN1 HEATING COIL 2376.95
SPLIT GN2 HEATING COIL 2376.71
SPLIT GS1 HEATING COIL 2377.78
SPLIT GS2 HEATING COIL 2504.39
SPLIT MSW HEATING COIL 6444.49
SPLIT MNW HEATING COIL 6448.06
SPLIT MSE HEATING COIL 6418.12
SPLIT MNE HEATING COIL 6421.67
SPLIT MN1 HEATING COIL 4468.65
SPLIT MN2 HEATING COIL 4468.00
SPLIT MS1 HEATING COIL 4467.39
SPLIT MS2 HEATING COIL 4466.74
SPLIT TSW HEATING COIL 4763.33
SPLIT TNW HEATING COIL 4766.82
SPLIT TSE HEATING COIL 4749.57
SPLIT TNE HEATING COIL 4753.05
SPLIT TN1 HEATING COIL 3694.67
SPLIT TN2 HEATING COIL 3694.31
SPLIT TS1 HEATING COIL 3689.64
SPLIT TS2 HEATING COIL 3689.28



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.89 2.67
April 22.09 7.47
May 22.82 13.73
June 24.20 18.63
July 24.39 22.03
August 24.37 20.69
September 24.18 16.55
October 22.42 9.72
November 21.84 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.78 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.83 2.67
April 21.90 7.47
May 22.62 13.73
June 24.18 18.63
July 24.39 22.03
August 24.37 20.69
September 24.06 16.55
October 22.09 9.72
November 21.74 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.69 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.01 -3.4
February 18.87 -4.2
March 20.89 2.67
April 22.10 7.47
May 23.34 13.73
June 23.88 18.63
July 23.90 22.03
August 23.90 20.69
September 23.87 16.55
October 22.71 9.72
November 21.48 6.03
December 19.16 -2.2
     
Annual Sum or Average 21.94 9.05
Minimum of Months 18.87 -4.2
Maximum of Months 23.90 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.82 2.67
April 21.86 7.47
May 22.53 13.73
June 24.16 18.63
July 24.38 22.03
August 24.35 20.69
September 24.03 16.55
October 22.02 9.72
November 21.73 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.67 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.81 2.67
April 21.82 7.47
May 22.40 13.73
June 24.13 18.63
July 24.38 22.03
August 24.36 20.69
September 24.07 16.55
October 22.06 9.72
November 21.74 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.66 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.81 2.67
April 21.82 7.47
May 22.39 13.73
June 24.13 18.63
July 24.38 22.03
August 24.36 20.69
September 24.07 16.55
October 22.05 9.72
November 21.74 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.66 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.88 2.67
April 22.02 7.47
May 22.67 13.73
June 24.18 18.63
July 24.38 22.03
August 24.37 20.69
September 24.22 16.55
October 22.47 9.72
November 21.87 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.77 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.89 2.67
April 22.03 7.47
May 22.68 13.73
June 24.18 18.63
July 24.38 22.03
August 24.37 20.69
September 24.22 16.55
October 22.48 9.72
November 21.87 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.77 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -3.4
February 21.72 -4.2
March 22.30 2.67
April 23.23 7.47
May 24.33 13.73
June 24.39 18.63
July 24.40 22.03
August 24.40 20.69
September 24.37 16.55
October 23.67 9.72
November 22.36 6.03
December 21.71 -2.2
     
Annual Sum or Average 23.22 9.05
Minimum of Months 21.71 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.09 2.67
April 22.82 7.47
May 24.29 13.73
June 24.39 18.63
July 24.40 22.03
August 24.40 20.69
September 24.35 16.55
October 23.08 9.72
November 21.91 6.03
December 21.70 -2.2
     
Annual Sum or Average 23.08 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -3.4
February 21.71 -4.2
March 22.25 2.67
April 23.19 7.47
May 24.31 13.73
June 24.39 18.63
July 24.40 22.03
August 24.40 20.69
September 24.37 16.55
October 23.64 9.72
November 22.32 6.03
December 21.71 -2.2
     
Annual Sum or Average 23.21 9.05
Minimum of Months 21.71 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.06 2.67
April 22.75 7.47
May 24.26 13.73
June 24.38 18.63
July 24.40 22.03
August 24.40 20.69
September 24.33 16.55
October 23.00 9.72
November 21.87 6.03
December 21.70 -2.2
     
Annual Sum or Average 23.05 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.15 2.67
April 22.90 7.47
May 24.33 13.73
June 24.39 18.63
July 24.40 22.03
August 24.40 20.69
September 24.37 16.55
October 23.37 9.72
November 22.01 6.03
December 21.70 -2.2
     
Annual Sum or Average 23.13 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.15 2.67
April 22.89 7.47
May 24.32 13.73
June 24.39 18.63
July 24.40 22.03
August 24.40 20.69
September 24.37 16.55
October 23.36 9.72
November 22.00 6.03
December 21.70 -2.2
     
Annual Sum or Average 23.13 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -3.4
February 21.74 -4.2
March 22.48 2.67
April 23.43 7.47
May 24.36 13.73
June 24.40 18.63
July 24.40 22.03
August 24.40 20.69
September 24.39 16.55
October 23.99 9.72
November 22.65 6.03
December 21.73 -2.2
     
Annual Sum or Average 23.32 9.05
Minimum of Months 21.73 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -3.4
February 21.74 -4.2
March 22.47 2.67
April 23.43 7.47
May 24.36 13.73
June 24.40 18.63
July 24.40 22.03
August 24.40 20.69
September 24.39 16.55
October 23.99 9.72
November 22.65 6.03
December 21.73 -2.2
     
Annual Sum or Average 23.32 9.05
Minimum of Months 21.73 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -3.4
February 21.72 -4.2
March 22.16 2.67
April 22.64 7.47
May 23.80 13.73
June 24.27 18.63
July 24.39 22.03
August 24.38 20.69
September 24.12 16.55
October 22.86 9.72
November 22.05 6.03
December 21.71 -2.2
     
Annual Sum or Average 22.99 9.05
Minimum of Months 21.71 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.00 2.67
April 22.41 7.47
May 23.71 13.73
June 24.26 18.63
July 24.39 22.03
August 24.37 20.69
September 24.01 16.55
October 22.48 9.72
November 21.82 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.89 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -3.4
February 21.71 -4.2
March 22.14 2.67
April 22.64 7.47
May 23.81 13.73
June 24.28 18.63
July 24.39 22.03
August 24.38 20.69
September 24.11 16.55
October 22.87 9.72
November 22.04 6.03
December 21.71 -2.2
     
Annual Sum or Average 22.99 9.05
Minimum of Months 21.71 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 21.97 2.67
April 22.38 7.47
May 23.67 13.73
June 24.25 18.63
July 24.39 22.03
August 24.36 20.69
September 23.97 16.55
October 22.41 9.72
November 21.79 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.86 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.01 2.67
April 22.38 7.47
May 23.74 13.73
June 24.28 18.63
July 24.39 22.03
August 24.38 20.69
September 24.03 16.55
October 22.49 9.72
November 21.83 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.89 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -3.4
February 21.70 -4.2
March 22.01 2.67
April 22.38 7.47
May 23.74 13.73
June 24.28 18.63
July 24.39 22.03
August 24.38 20.69
September 24.03 16.55
October 22.49 9.72
November 21.82 6.03
December 21.70 -2.2
     
Annual Sum or Average 22.89 9.05
Minimum of Months 21.70 -4.2
Maximum of Months 24.39 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -3.4
February 21.73 -4.2
March 22.22 2.67
April 22.74 7.47
May 23.90 13.73
June 24.30 18.63
July 24.40 22.03
August 24.39 20.69
September 24.20 16.55
October 23.03 9.72
November 22.14 6.03
December 21.72 -2.2
     
Annual Sum or Average 23.05 9.05
Minimum of Months 21.72 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -3.4
February 21.73 -4.2
March 22.22 2.67
April 22.74 7.47
May 23.90 13.73
June 24.30 18.63
July 24.40 22.03
August 24.39 20.69
September 24.20 16.55
October 23.03 9.72
November 22.15 6.03
December 21.72 -2.2
     
Annual Sum or Average 23.05 9.05
Minimum of Months 21.72 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -3.4
February 20.79 -4.2
March 22.20 2.67
April 23.34 7.47
May 25.29 13.73
June 26.42 18.63
July 26.91 22.03
August 26.69 20.69
September 25.81 16.55
October 23.56 9.72
November 22.18 6.03
December 20.88 -2.2
     
Annual Sum or Average 23.75 9.05
Minimum of Months 20.79 -4.2
Maximum of Months 26.91 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.09 -3.4
February 18.95 -4.2
March 20.36 2.67
April 21.38 7.47
May 22.87 13.73
June 25.24 18.63
July 26.06 22.03
August 25.89 20.69
September 25.06 16.55
October 22.13 9.72
November 20.95 6.03
December 19.31 -2.2
     
Annual Sum or Average 22.29 9.05
Minimum of Months 18.95 -4.2
Maximum of Months 26.06 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.75 -3.4
February 22.75 -4.2
March 23.86 2.67
April 24.92 7.47
May 26.49 13.73
June 26.87 18.63
July 27.03 22.03
August 26.95 20.69
September 26.68 16.55
October 25.42 9.72
November 23.87 6.03
December 22.75 -2.2
     
Annual Sum or Average 25.04 9.05
Minimum of Months 22.75 -4.2
Maximum of Months 27.03 22.03



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.118612E+12 76448.302 30-JAN-18:45 8572.775 26456.413 6586.279 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 32324.505 0.000 0.000 0.000
February 0.107311E+12 76459.789 15-FEB-18:15 8572.775 26456.413 6586.279 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 32335.993 0.000 0.000 0.000
March 0.118743E+12 75976.698 15-MAR-17:45 8572.775 26456.413 6586.279 0.000 9198.849 0.000 0.000 0.000 0.000 0.000 0.000 25162.383 0.000 0.000 0.000
April 0.113473E+12 71129.266 26-APR-17:30 8572.775 26456.413 6586.279 0.000 2177.710 0.000 0.000 0.000 0.000 0.000 0.000 27336.090 0.000 0.000 0.000
May 0.119634E+12 77134.553 27-MAY-17:45 8572.775 26456.413 6586.279 0.000 7519.191 0.000 0.000 0.000 0.000 0.000 0.000 27999.895 0.000 0.000 0.000
June 0.125102E+12 86135.018 17-JUN-17:15 8572.775 26456.413 6586.279 0.000 19320.059 0.000 0.000 0.000 0.000 0.000 0.000 25199.492 0.000 0.000 0.000
July 0.137777E+12 84299.763 24-JUL-17:15 8572.775 26456.413 6586.279 0.000 16699.755 0.000 0.000 0.000 0.000 0.000 0.000 25984.541 0.000 0.000 0.000
August 0.132745E+12 85803.639 13-AUG-17:15 8572.775 26456.413 6586.279 0.000 19197.598 0.000 0.000 0.000 0.000 0.000 0.000 24990.575 0.000 0.000 0.000
September 0.119131E+12 87654.879 16-SEP-17:30 8572.775 26456.413 6586.279 0.000 16341.159 0.000 0.000 0.000 0.000 0.000 0.000 29698.253 0.000 0.000 0.000
October 0.114752E+12 73140.285 22-OCT-17:30 8572.775 26456.413 6586.279 0.000 4191.985 2508.330 0.000 0.000 0.000 0.000 0.000 24824.504 0.000 0.000 0.000
November 0.111542E+12 72655.453 22-NOV-18:45 8572.775 26456.413 6586.279 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 28531.656 0.000 0.000 0.000
December 0.117242E+12 72629.014 12-DEC-18:45 8572.775 26456.413 6586.279 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 28505.218 0.000 0.000 0.000
                                     
Annual Sum or Average 0.143607E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.107311E+12 71129.266   8572.775 26456.413 6586.279 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 24824.504 0.000 0.000 0.000
Maximum of Months 0.137777E+12 87654.879   8572.775 26456.413 6586.279 0.000 19320.059 2508.330 0.000 0.000 0.000 0.000 0.000 32335.993 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.118983E+12 93635.514 24-JAN-04:00 93635.514 0.000 0.000 0.000 0.000 0.000 93635.514
February 0.114205E+12 107780.221 06-FEB-09:00 107780.221 0.000 0.000 0.000 0.000 0.000 107780.221
March 0.540167E+11 68391.071 07-MAR-04:00 68391.071 0.000 0.000 0.000 0.000 0.000 68391.071
April 0.177171E+11 52775.948 16-APR-03:00 52775.948 0.000 0.000 0.000 0.000 0.000 52775.948
May 0.962905E+09 7592.506 07-MAY-04:00 7592.506 0.000 0.000 0.000 0.000 0.000 7592.506
June 9246959.444 1249.949 14-JUN-04:30 1249.949 0.000 0.000 0.000 0.000 0.000 1249.949
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.108546E+09 3640.508 30-SEP-05:00 3640.508 0.000 0.000 0.000 0.000 0.000 3640.508
October 0.928017E+10 29709.395 30-OCT-04:00 29709.395 0.000 0.000 0.000 0.000 0.000 29709.395
November 0.348698E+11 44377.100 24-NOV-03:00 44377.100 0.000 0.000 0.000 0.000 0.000 44377.100
December 0.114662E+12 95410.956 26-DEC-07:15 95410.956 0.000 0.000 0.000 0.000 0.000 95410.956
                     
Annual Sum or Average 0.464814E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.118983E+12 107780.221   107780.221 0.000 0.000 0.000 0.000 0.000 107780.221