Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2018-10-19 09:20:31


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1389.81 443.37 492.14
Net Site Energy 1389.81 443.37 492.14
Total Source Energy 4387.40 1399.66 1553.62
Net Source Energy 4387.40 1399.66 1553.62


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 6.78 0.00 0.00 0.00 0.00
Cooling 119.06 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 181.59 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 366.52 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1383.03 6.78 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 6.78 0.00 0.00 0.00 0.00
Cooling General 119.06 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 181.59 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 366.52 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.40 0.00 0.00 0.00 0.00 0.00
HVAC 236.25 2.40 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 489.75 2.40 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.22 0.00 0.00 0.00 0.00 0.00
HVAC 212.84 2.16 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 441.21 2.16 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1383.03 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1383.03 100.00
     
Total On-Site and Utility Electric Sources 1383.03 100.00
Total Electricity End Uses 1383.03 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 20.25
Time Setpoint Not Met During Occupied Cooling 19.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 364.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-SEP-17:30 30-MAR-02:00 - - - 01-JAN-07:15
Heating 0.00 14058.44 0.00 0.00 0.00 0.00
Cooling 13788.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5758.08 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22172.32 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 76747.59 14058.44 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 14058.44 0.00 0.00 0.00 0.00
Cooling General 13788.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 5758.08 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 22172.32 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 7.34 0.00 0.00 0.00
Cooling 377.06 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.91 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 575.09 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1160.77 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4380.06 7.34 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 2.60 0.00 0.00 0.00
Cooling 133.52 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 203.64 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 411.04 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1551.02 2.60 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 2.60 0.00 0.00 0.00
Cooling 133.52 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 203.64 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 411.04 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1551.02 2.60 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.62_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 2.848 0.287 0.200     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 2.848 0.287 0.200     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.848 0.287 0.200              
North Total or Average           112.97 2.848 0.287 0.200              
Non-North Total or Average           193.95 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 E SEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 E SEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 0.00 1.00 1.00 1.00
TWINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
ENTRANCE DOOR 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.77 83.77 39.44
Exterior Lighting Total 2508.33           39.44



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   2468.85 1967.16 501.70 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   2259.51 1804.57 454.94 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7076.98 5652.07 1424.91 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   1729.50 1381.27 348.23 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1389.20 1097.67 291.53 0.79 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1378.14 1088.54 289.60 0.79 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1670.39 1298.61 371.78 0.78 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1717.20 1337.33 379.87 0.78 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6549.17 5230.53 1318.64 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6030.69 4816.44 1214.25 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5745.13 4583.67 1161.46 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4855.53 3877.89 977.64 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3837.87 3064.01 773.86 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3818.02 3047.58 770.44 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4538.16 3584.55 953.62 0.79 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4554.27 3597.85 956.42 0.79 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4210.92 3363.07 847.85 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3827.76 3057.06 770.70 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   3792.87 3029.19 763.67 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3051.75 2432.67 619.09 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2472.37 1953.78 518.59 0.79 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2474.52 1955.57 518.95 0.79 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3136.98 2503.74 633.25 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3143.28 2510.40 632.88 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2352.6 3.13 10.68 11.10 10.39
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2152.5 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6741.9 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1647.6 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1324.9 3.14 10.72 11.14 10.45
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1314.4 3.14 10.72 11.14 10.45
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1595.8 3.16 10.80 11.22 10.56
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1640.2 3.16 10.79 11.22 10.55
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6239.1 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5745.2 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5473.7 3.13 10.68 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4625.7 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3656.3 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3637.5 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4328.4 3.14 10.72 11.14 10.45
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4343.7 3.14 10.72 11.14 10.45
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4011.6 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3646.5 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 3613.3 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2907.9 3.13 10.68 11.10 10.39
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2358.0 3.14 10.72 11.14 10.45
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2360.0 3.14 10.72 11.14 10.45
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2988.7 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2994.5 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1475.74 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   2489.99 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2847.74 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   1823.72 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   1821.15 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   1827.14 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   1824.58 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1423.87 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1423.87 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.21 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 152.89 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 478.87 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 117.03 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.08 91.83 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.08 91.02 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 106.50 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 109.92 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 443.15 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 408.07 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 387.88 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.55 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.48 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.04 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 299.74 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 300.91 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.93 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.01 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.65 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 205.65 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.47 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.63 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 211.97 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 212.69 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1549.72 1859.67 0.124 0.148 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 30.23 0.00820
G NW APARTMENT 1425.55 1710.66 0.114 0.136 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 29.61 0.00820
OFFICE 4250.34 5100.40 0.356 0.428 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16 0.00820
G NE APARTMENT 1091.14 1309.36 0.087 0.104 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
G N1 APARTMENT 856.18 1027.41 0.068 0.082 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 28.50 0.00820
G N2 APARTMENT 848.69 1018.42 0.068 0.081 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 28.50 0.00820
G S1 APARTMENT 993.02 1191.62 0.079 0.095 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
G S2 APARTMENT 1024.85 1229.82 0.082 0.098 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
M SW APARTMENT 4131.95 4958.35 0.330 0.396 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 30.23 0.00820
M NW APARTMENT 3804.85 4565.82 0.304 0.364 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 29.61 0.00820
M SE APARTMENT 3616.59 4339.91 0.289 0.346 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
M NE APARTMENT 3063.37 3676.04 0.244 0.293 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
M N1 APARTMENT 2419.43 2903.32 0.193 0.232 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
M N2 APARTMENT 2405.91 2887.10 0.192 0.230 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
M S1 APARTMENT 2794.74 3353.69 0.223 0.268 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
M S2 APARTMENT 2805.66 3366.79 0.224 0.269 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
T SW APARTMENT 2656.72 3188.06 0.212 0.254 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 31.03 0.00820
T NW APARTMENT 2414.97 2897.97 0.193 0.231 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 30.23 0.00820
T SE APARTMENT 2392.96 2871.55 0.191 0.229 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
T NE APARTMENT 1917.44 2300.93 0.153 0.184 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 31.19 0.00820
T N1 APARTMENT 1524.18 1829.01 0.122 0.146 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30 0.00820
T N2 APARTMENT 1525.65 1830.78 0.122 0.146 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30 0.00820
T S1 APARTMENT 1976.36 2371.63 0.158 0.189 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 31.19 0.00820
T S2 APARTMENT 1983.13 2379.76 0.158 0.190 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.08 0.00820


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 512.77 615.33 0.015 0.027 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
G NW APARTMENT 509.99 611.99 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
OFFICE 1471.68 1766.02 0.041 0.050 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 3.80 0.00506
G NE APARTMENT 512.04 614.44 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
G N1 APARTMENT 225.49 270.59 0.007 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
G N2 APARTMENT 225.54 270.65 0.007 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
G S1 APARTMENT 229.50 275.40 0.007 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
G S2 APARTMENT 288.48 346.18 0.008 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
M SW APARTMENT 769.99 923.99 0.023 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
M NW APARTMENT 760.49 912.58 0.022 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
M SE APARTMENT 776.00 931.20 0.023 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
M NE APARTMENT 766.58 919.89 0.022 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
M N1 APARTMENT 0.00 0.00 0.000 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB   3.80 0.00506
M N2 APARTMENT 0.00 0.00 0.000 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB   3.80 0.00506
M S1 APARTMENT 0.00 0.00 0.000 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB   3.80 0.00506
M S2 APARTMENT 0.00 0.00 0.000 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB   3.80 0.00506
T SW APARTMENT 1075.73 1290.87 0.032 0.038 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T NW APARTMENT 1073.56 1288.27 0.031 0.038 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T SE APARTMENT 1078.62 1294.34 0.032 0.038 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T NE APARTMENT 1076.45 1291.74 0.032 0.038 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T N1 APARTMENT 710.73 852.87 0.021 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T N2 APARTMENT 710.81 852.98 0.021 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T S1 APARTMENT 711.35 853.62 0.021 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506
T S2 APARTMENT 711.44 853.72 0.021 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.80 0.00506


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.15 0.15 0.03 0.03
SPLIT GNW 0.14 0.14 0.03 0.03
SPLIT OFFICE 0.43 0.43 0.05 0.05
SPLIT GNE 0.10 0.10 0.03 0.03
SPLIT GN1 0.08 0.08 0.03 0.03
SPLIT GN2 0.08 0.08 0.03 0.03
SPLIT GS1 0.10 0.10 0.03 0.03
SPLIT GS2 0.10 0.10 0.03 0.03
SPLIT MSW 0.40 0.40 0.05 0.05
SPLIT MNW 0.36 0.36 0.05 0.05
SPLIT MSE 0.35 0.35 0.05 0.05
SPLIT MNE 0.29 0.29 0.05 0.05
SPLIT MN1 0.23 0.23 0.05 0.05
SPLIT MN2 0.23 0.23 0.05 0.05
SPLIT MS1 0.27 0.27 0.05 0.05
SPLIT MS2 0.27 0.27 0.05 0.05
SPLIT TSW 0.25 0.25 0.04 0.04
SPLIT TNW 0.23 0.23 0.04 0.04
SPLIT TSE 0.23 0.23 0.04 0.04
SPLIT TNE 0.18 0.18 0.04 0.04
SPLIT TN1 0.15 0.15 0.03 0.03
SPLIT TN2 0.15 0.15 0.03 0.03
SPLIT TS1 0.19 0.19 0.03 0.03
SPLIT TS2 0.19 0.19 0.03 0.03



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2702.75 5057.50 182.25
G NW APARTMENT 2522.25 5796.25 247.50
OFFICE 132.75 1431.75 0.00
G NE APARTMENT 2438.00 6029.00 328.75
G N1 APARTMENT 2374.75 6096.75 343.25
G N2 APARTMENT 2362.25 6105.50 346.50
G S1 APARTMENT 2529.25 5479.25 244.50
G S2 APARTMENT 2479.00 5523.25 272.50
M SW APARTMENT 5746.50 495.75 0.00
M NW APARTMENT 4855.75 1383.00 1.00
M SE APARTMENT 5750.75 533.50 0.00
M NE APARTMENT 4802.25 1470.50 2.00
M N1 APARTMENT 4915.50 1074.75 2.00
M N2 APARTMENT 4912.50 1079.50 2.00
M S1 APARTMENT 5853.75 236.50 0.00
M S2 APARTMENT 5853.00 239.50 0.00
T SW APARTMENT 4400.25 2420.00 12.00
T NW APARTMENT 3701.50 3439.00 21.25
T SE APARTMENT 4393.50 2425.00 13.00
T NE APARTMENT 3659.25 3586.50 37.50
T N1 APARTMENT 3648.25 3481.25 32.25
T N2 APARTMENT 3637.75 3489.00 32.50
T S1 APARTMENT 4501.50 2113.50 13.75
T S2 APARTMENT 4500.50 2118.00 13.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6192.25 6238.25 364.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 1.00 0.00 1.00 0.00
G NW APARTMENT 6.50 0.00 6.50 0.00
OFFICE 0.00 0.00 0.00 0.00
G NE APARTMENT 8.25 0.00 8.25 0.00
G N1 APARTMENT 0.00 0.00 0.00 0.00
G N2 APARTMENT 0.00 0.00 0.00 0.00
G S1 APARTMENT 0.00 3.75 0.00 3.75
G S2 APARTMENT 0.00 3.00 0.00 3.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 11.25 0.00 11.25
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.00 0.00 0.00 0.00
M S1 APARTMENT 0.00 18.50 0.00 18.50
M S2 APARTMENT 0.00 18.50 0.00 18.50
T SW APARTMENT 0.00 0.00 0.00 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 6.25 0.00 6.25
T NE APARTMENT 0.50 0.00 0.50 0.00
T N1 APARTMENT 2.25 0.00 2.25 0.00
T N2 APARTMENT 1.50 0.00 1.50 0.00
T S1 APARTMENT 0.25 10.25 0.25 10.25
T S2 APARTMENT 0.25 10.75 0.25 10.75
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 20.25 19.00 20.25 19.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.368 0.064 0.000 0.150
G NW APARTMENT 1.71 2.50 268.97 0.355 0.064 0.000 0.145
OFFICE 0.94 1.00 268.97 0.521 0.088 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.355 0.064 0.000 0.144
G N1 APARTMENT 1.71 2.50 268.97 0.355 0.039 0.000 0.142
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.039 0.000 0.142
G S1 APARTMENT 1.71 2.50 268.97 0.355 0.039 0.000 0.149
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.039 0.000 0.149
M SW APARTMENT 1.71 2.50 268.97 0.356 0.092 0.000 0.174
M NW APARTMENT 1.71 2.50 268.97 0.356 0.092 0.000 0.172
M SE APARTMENT 1.71 2.50 268.97 0.356 0.092 0.000 0.174
M NE APARTMENT 1.71 2.50 268.97 0.356 0.092 0.000 0.172
M N1 APARTMENT 1.71 2.50 268.97 0.356 0.056 0.000 0.172
M N2 APARTMENT 1.71 2.50 268.97 0.356 0.056 0.000 0.172
M S1 APARTMENT 1.71 2.50 268.97 0.356 0.056 0.000 0.174
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.056 0.000 0.174
T SW APARTMENT 1.71 2.50 268.97 0.356 0.122 0.000 0.200
T NW APARTMENT 1.71 2.50 268.97 0.356 0.122 0.000 0.197
T SE APARTMENT 1.71 2.50 268.97 0.356 0.122 0.000 0.200
T NE APARTMENT 1.71 2.50 268.97 0.356 0.122 0.000 0.197
T N1 APARTMENT 1.71 2.50 268.97 0.356 0.073 0.000 0.196
T N2 APARTMENT 1.71 2.50 268.97 0.356 0.073 0.000 0.196
T S1 APARTMENT 1.71 2.50 268.97 0.356 0.073 0.000 0.200
T S2 APARTMENT 1.71 2.50 268.97 0.356 0.073 0.000 0.200
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.358 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.508 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.390 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.387 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.390 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.386 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.389 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.389 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 366.52 0.00 01-JAN-00:15 32120.45 01-JAN-08:00
WaterSystems:Electricity 366.52 0.00 01-JAN-00:15 32120.45 01-JAN-08:00
Water Heater:WaterSystems:Electricity 366.52 0.00 01-JAN-00:15 32120.45 01-JAN-08:00
Fans:Electricity 181.59 5758.08 03-JAN-07:15 5758.08 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
ElectricityPurchased:Plant 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
Cogeneration:ElectricityPurchased 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
ElectricityNet:Plant 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
Cogeneration:ElectricityNet 1383.03 19128.38 01-JAN-03:15 76747.59 29-SEP-17:30
ExteriorLights:Electricity 39.44 0.00 01-JAN-07:00 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.44 0.00 01-JAN-07:00 2508.33 01-JAN-00:15
Electricity:HVAC 300.65 5758.08 03-JAN-07:15 24684.91 29-SEP-13:00
General:Fans:Electricity 181.59 5758.08 03-JAN-07:15 5758.08 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 119.06 0.00 01-JAN-00:15 18926.83 29-SEP-13:00


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 6.78 0.00 01-JAN-10:00 14058.44 30-MAR-03:00
Gas:HVAC 6.78 0.00 01-JAN-10:00 14058.44 30-MAR-03:00
Heating:Gas 6.78 0.00 01-JAN-10:00 14058.44 30-MAR-03:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 984.60 1593.79 18-DEC-07:15 124631.61 29-SEP-15:15
EnergyTransfer:Building 490.56 1533.19 18-DEC-07:15 55201.37 29-SEP-15:15
EnergyTransfer:Zone:G SW APARTMENT 8.52 0.00 06-OCT-04:00 1901.48 29-SEP-15:30
Heating:EnergyTransfer 2.04 0.00 01-JAN-07:30 5566.65 30-MAR-03:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.05 0.00 01-JAN-00:15 283.69 30-MAR-03:00
Cooling:EnergyTransfer 488.52 727.40 11-FEB-16:00 55201.37 29-SEP-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 8.47 0.00 01-JAN-00:30 1901.48 29-SEP-15:30
EnergyTransfer:Zone:G NW APARTMENT 6.20 0.00 27-OCT-15:15 1370.88 29-SEP-16:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 0.26 0.00 01-JAN-06:15 312.87 30-MAR-03:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 5.95 0.00 01-JAN-00:15 1370.88 29-SEP-16:15
EnergyTransfer:Zone:OFFICE 22.97 0.01 22-MAY-01:15 3192.26 16-OCT-12:15
Heating:EnergyTransfer:Zone:OFFICE 0.16 0.00 01-JAN-00:15 262.49 12-FEB-04:00
Cooling:EnergyTransfer:Zone:OFFICE 22.81 0.00 01-JAN-10:00 3192.26 16-OCT-12:15
EnergyTransfer:Zone:G NE APARTMENT 6.40 0.02 08-APR-16:00 1008.81 19-JUL-09:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.20 0.00 01-JAN-06:15 360.90 30-MAR-03:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 6.20 0.00 01-JAN-00:15 1008.81 19-JUL-09:30
EnergyTransfer:Zone:G N1 APARTMENT 6.15 0.00 04-OCT-08:30 810.87 18-JUL-17:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.10 0.00 01-JAN-00:15 278.95 08-JAN-03:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 6.05 0.00 02-JAN-02:30 810.87 18-JUL-17:30
EnergyTransfer:Zone:G N2 APARTMENT 6.15 0.02 17-JAN-15:30 805.26 18-JUL-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.10 0.00 01-JAN-00:15 300.80 08-JAN-04:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 6.05 0.00 02-JAN-02:30 805.26 18-JUL-17:30
EnergyTransfer:Zone:G S1 APARTMENT 8.06 0.03 05-OCT-03:15 1278.54 30-SEP-11:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.01 0.00 01-JAN-00:15 262.08 29-MAR-24:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 8.04 0.00 15-JAN-08:45 1278.54 30-SEP-11:30
EnergyTransfer:Zone:G S2 APARTMENT 7.85 0.07 13-APR-10:45 1301.05 30-SEP-11:45
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.01 0.00 01-JAN-00:15 258.61 29-MAR-24:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.84 0.00 15-JAN-08:45 1301.05 30-SEP-11:45
EnergyTransfer:Zone:M SW APARTMENT 45.87 0.01 12-FEB-13:30 5254.68 16-OCT-14:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 54.87 12-FEB-07:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 45.87 0.00 11-FEB-16:00 5254.68 16-OCT-14:30
EnergyTransfer:Zone:M NW APARTMENT 31.79 0.14 06-FEB-11:15 3706.32 29-SEP-16:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 149.66 18-DEC-08:45
Cooling:EnergyTransfer:Zone:M NW APARTMENT 31.79 0.00 03-JAN-11:30 3706.32 29-SEP-16:15
EnergyTransfer:Zone:M SE APARTMENT 45.41 2.48 12-FEB-06:30 4724.49 17-OCT-11:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 15.07 11-FEB-16:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 45.41 0.00 11-FEB-16:00 4724.49 17-OCT-11:45
EnergyTransfer:Zone:M NE APARTMENT 31.40 1.56 04-JAN-13:00 3136.83 16-OCT-10:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 9.90 04-JAN-13:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 31.40 0.00 04-JAN-13:00 3136.83 16-OCT-10:00
EnergyTransfer:Zone:M N1 APARTMENT 30.17 42.92 18-DEC-08:15 2413.79 18-JUL-17:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 30.17 42.92 18-DEC-08:15 2413.79 18-JUL-17:30
EnergyTransfer:Zone:M N2 APARTMENT 30.14 44.47 18-DEC-08:15 2402.21 18-JUL-17:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 30.14 44.47 18-DEC-08:15 2402.21 18-JUL-17:30
EnergyTransfer:Zone:M S1 APARTMENT 44.70 81.32 17-APR-13:45 4052.07 31-OCT-14:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 44.70 81.32 17-APR-13:45 4052.07 31-OCT-14:15
EnergyTransfer:Zone:M S2 APARTMENT 44.67 80.36 17-APR-13:45 4042.39 31-OCT-14:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 44.67 80.36 17-APR-13:45 4042.39 31-OCT-14:00
EnergyTransfer:Zone:T SW APARTMENT 17.65 0.05 18-DEC-00:45 3289.85 16-OCT-13:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 0.16 0.00 01-JAN-00:15 638.96 30-MAR-04:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 17.49 0.00 01-JAN-05:00 3289.85 16-OCT-13:30
EnergyTransfer:Zone:T NW APARTMENT 12.05 0.01 11-SEP-03:30 2455.71 29-SEP-15:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 0.39 0.00 01-JAN-07:30 688.05 30-MAR-04:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 11.66 0.00 01-JAN-00:15 2455.71 29-SEP-15:30
EnergyTransfer:Zone:T SE APARTMENT 17.39 0.03 17-SEP-06:00 3036.84 15-OCT-12:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.12 0.00 01-JAN-00:15 707.49 30-MAR-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 17.27 0.00 01-JAN-06:00 3036.84 15-OCT-12:30
EnergyTransfer:Zone:T NE APARTMENT 11.86 0.01 18-JAN-08:00 2064.37 29-SEP-13:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 0.30 0.00 01-JAN-07:15 767.99 30-MAR-03:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 11.56 0.00 01-JAN-00:15 2064.37 29-SEP-13:00
EnergyTransfer:Zone:T N1 APARTMENT 10.94 0.02 23-JAN-11:30 1588.89 29-SEP-15:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.07 0.00 01-JAN-00:15 384.48 30-MAR-03:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 10.87 0.00 02-JAN-02:30 1588.89 29-SEP-15:15
EnergyTransfer:Zone:T N2 APARTMENT 10.91 0.13 28-DEC-13:30 1583.48 29-SEP-14:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.07 0.00 01-JAN-00:15 394.64 30-MAR-03:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 10.84 0.00 02-JAN-02:30 1583.48 29-SEP-14:15
EnergyTransfer:Zone:T S1 APARTMENT 16.65 0.01 13-FEB-15:00 2530.50 16-OCT-14:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.01 0.00 01-JAN-00:15 317.76 30-MAR-04:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 16.64 0.00 03-JAN-03:45 2530.50 16-OCT-14:45
EnergyTransfer:Zone:T S2 APARTMENT 16.65 0.01 24-FEB-14:45 2535.39 16-OCT-14:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.02 0.00 01-JAN-00:15 325.86 30-MAR-04:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 16.63 0.00 03-JAN-03:45 2535.39 16-OCT-14:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 494.04 0.00 17-JAN-06:15 69613.90 29-SEP-14:15
HeatingCoils:EnergyTransfer 5.42 0.00 01-JAN-10:00 11246.75 30-MAR-03:00
CoolingCoils:EnergyTransfer 488.62 0.00 01-JAN-00:15 69613.90 29-SEP-14:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.053 -8.468 0.000 0.000 3.713 2.413 12.213 13.522 0.000 0.027 0.000 0.000 -5.122 0.000 -3.357 -14.994
G NW APARTMENT 0.257 -5.948 0.000 0.000 3.770 2.413 12.213 7.217 0.000 0.029 0.000 0.000 -5.017 0.000 -3.091 -11.843
OFFICE 0.155 -22.812 0.000 0.000 0.517 21.914 7.534 13.160 0.000 0.021 0.000 0.000 -5.089 0.000 -1.222 -14.179
G NE APARTMENT 0.204 -6.200 0.000 0.000 3.790 2.413 12.213 6.726 0.000 0.029 0.000 0.000 -4.850 0.000 -3.057 -11.268
G N1 APARTMENT 0.102 -6.052 0.000 0.000 3.792 2.413 12.213 2.366 0.000 0.024 0.000 0.000 -3.026 0.000 -2.511 -9.322
G N2 APARTMENT 0.101 -6.049 0.000 0.000 3.793 2.413 12.213 2.365 0.000 0.024 0.000 0.000 -3.023 0.000 -2.509 -9.329
G S1 APARTMENT 0.013 -8.043 0.000 0.000 3.716 2.413 12.213 8.753 0.000 0.020 0.000 0.000 -3.133 0.000 -2.821 -13.130
G S2 APARTMENT 0.014 -7.838 0.000 0.000 3.717 2.413 12.213 8.754 0.000 0.020 0.000 0.000 -3.128 0.000 -2.822 -13.344
M SW APARTMENT 0.000 -45.867 0.000 0.000 3.527 2.413 12.213 12.846 0.000 0.038 25.262 0.000 -5.942 0.000 -4.490 0.000
M NW APARTMENT 0.004 -31.785 0.000 0.000 3.544 2.413 12.213 6.551 0.000 0.037 17.419 0.000 -5.955 0.000 -4.440 0.000
M SE APARTMENT 0.000 -45.411 0.000 0.000 3.530 2.413 12.213 12.453 0.000 0.037 25.130 0.000 -5.878 0.000 -4.488 0.000
M NE APARTMENT 0.000 -31.402 0.000 0.000 3.550 2.413 12.213 6.058 0.000 0.037 17.352 0.000 -5.785 0.000 -4.437 0.000
M N1 APARTMENT 0.000 -30.173 0.000 0.000 3.533 2.413 12.213 1.967 0.000 0.027 17.394 0.000 -3.688 0.000 -3.686 0.000
M N2 APARTMENT 0.000 -30.138 0.000 0.000 3.534 2.413 12.213 1.966 0.000 0.027 17.357 0.000 -3.687 0.000 -3.686 0.000
M S1 APARTMENT 0.000 -44.699 0.000 0.000 3.521 2.413 12.213 8.339 0.000 0.027 25.561 0.000 -3.648 0.000 -3.726 0.000
M S2 APARTMENT 0.000 -44.671 0.000 0.000 3.521 2.413 12.213 8.338 0.000 0.027 25.532 0.000 -3.648 0.000 -3.726 0.000
T SW APARTMENT 0.158 -17.488 0.000 0.000 3.612 2.413 12.213 12.679 0.000 0.048 0.000 0.000 -5.556 0.000 -5.320 -2.758
T NW APARTMENT 0.392 -11.658 0.000 0.000 3.649 2.413 12.213 6.482 0.000 0.048 0.000 0.000 -5.481 0.000 -5.155 -2.902
T SE APARTMENT 0.121 -17.270 0.000 0.000 3.619 2.413 12.213 12.327 0.000 0.047 0.000 0.000 -5.499 0.000 -5.323 -2.649
T NE APARTMENT 0.302 -11.558 0.000 0.000 3.666 2.413 12.213 6.059 0.000 0.048 0.000 0.000 -5.328 0.000 -5.151 -2.663
T N1 APARTMENT 0.069 -10.871 0.000 0.000 3.646 2.413 12.213 1.984 0.000 0.035 0.000 0.000 -3.364 0.000 -4.172 -1.952
T N2 APARTMENT 0.069 -10.845 0.000 0.000 3.647 2.413 12.213 1.982 0.000 0.035 0.000 0.000 -3.361 0.000 -4.174 -1.979
T S1 APARTMENT 0.015 -16.640 0.000 0.000 3.593 2.413 12.213 8.251 0.000 0.034 0.000 0.000 -3.449 0.000 -4.361 -2.069
T S2 APARTMENT 0.015 -16.633 0.000 0.000 3.593 2.413 12.213 8.250 0.000 0.034 0.000 0.000 -3.447 0.000 -4.362 -2.078
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.076 0.000 0.002 0.000 0.000 -0.644 0.000 -0.523 -15.982
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.340 0.000 0.075 0.000 0.000 -1.543 0.000 -12.610 -9.597
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.073 0.000 0.002 0.000 0.000 -0.716 0.000 -0.435 -15.994
Total Facility 2.043 -488.519 0.000 0.000 84.091 128.627 294.692 179.886 0.000 0.863 171.010 0.000 -109.005 0.000 -105.653 -158.033


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-SEP-15:30 0.00 -1901.54 0.00 0.00 48.85 100.83 470.90 1982.18 0.00 67.88 0.00 0.00 0.00 0.00 0.00 -769.10
G NW APARTMENT 29-SEP-16:08 0.00 -1371.39 0.00 0.00 84.76 144.04 588.62 1189.93 0.00 48.82 0.00 0.00 0.00 0.00 0.00 -684.78
OFFICE 16-OCT-12:15 0.00 -3192.55 0.00 0.00 67.31 1622.34 544.92 2181.08 0.00 131.19 0.00 0.00 0.00 0.00 0.00 -1354.28
G NE APARTMENT 19-JUL-09:30 0.00 -1008.75 0.00 0.00 40.75 28.81 406.15 1227.18 0.00 62.61 0.00 0.00 0.00 0.00 0.00 -756.75
G N1 APARTMENT 18-JUL-17:30 0.00 -810.86 0.00 0.00 141.81 194.45 588.62 350.68 0.00 0.00 0.00 0.00 0.00 0.00 -7.42 -457.28
G N2 APARTMENT 18-JUL-17:30 0.00 -805.25 0.00 0.00 141.81 194.45 588.62 350.82 0.00 0.00 0.00 0.00 0.00 0.00 -7.42 -463.03
G S1 APARTMENT 30-SEP-11:30 0.00 -1278.66 0.00 0.00 40.75 28.81 406.15 1625.32 0.00 35.96 0.00 0.00 0.00 0.00 0.00 -858.33
G S2 APARTMENT 30-SEP-11:45 0.00 -1301.09 0.00 0.00 40.75 28.81 406.15 1609.98 0.00 37.29 0.00 0.00 0.00 0.00 0.00 -821.89
M SW APARTMENT 16-OCT-14:30 0.00 -5255.00 0.00 0.00 40.67 50.41 400.26 2268.17 0.00 79.88 2415.61 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 29-SEP-16:15 0.00 -3708.22 0.00 0.00 84.76 144.04 588.62 1170.58 0.00 69.96 1650.26 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 17-OCT-11:45 0.00 -4725.25 0.00 0.00 40.61 28.81 406.15 2048.19 0.00 69.33 2132.15 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 16-OCT-10:00 0.00 -3137.03 0.00 0.00 40.75 28.81 406.15 1129.16 0.00 207.67 1324.49 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 18-JUL-17:30 0.00 -2413.78 0.00 0.00 141.81 194.45 588.62 335.88 0.00 0.00 1163.69 0.00 0.00 0.00 -10.67 0.00
M N2 APARTMENT 18-JUL-17:30 0.00 -2402.19 0.00 0.00 141.81 194.45 588.62 335.96 0.00 0.00 1152.02 0.00 0.00 0.00 -10.67 0.00
M S1 APARTMENT 31-OCT-14:15 0.00 -4052.72 0.00 0.00 40.62 50.41 400.26 1478.45 0.00 34.70 2048.28 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 31-OCT-14:00 0.00 -4043.07 0.00 0.00 40.52 28.81 382.60 1577.58 0.00 49.53 1964.03 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 16-OCT-13:30 0.00 -3289.92 0.00 0.00 40.75 28.81 382.60 2369.26 0.00 162.24 306.25 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 29-SEP-15:30 0.00 -2455.77 0.00 0.00 48.90 100.83 470.90 1465.23 0.00 128.19 241.73 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 15-OCT-12:30 0.00 -3037.07 0.00 0.00 40.73 28.81 388.49 2021.13 0.00 158.81 399.11 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 29-SEP-13:00 0.00 -2064.44 0.00 0.00 40.75 28.81 388.49 762.73 0.00 182.08 661.58 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-SEP-15:15 0.00 -1588.96 0.00 0.00 48.90 100.83 470.90 307.07 0.00 84.52 576.74 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-SEP-14:15 0.00 -1583.60 0.00 0.00 40.75 50.41 400.26 385.93 0.00 107.97 598.26 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 16-OCT-14:45 0.00 -2530.73 0.00 0.00 40.03 50.41 400.26 1068.38 0.00 53.94 917.70 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 16-OCT-14:45 0.00 -2535.63 0.00 0.00 40.00 50.41 400.26 1068.09 0.00 53.88 922.99 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-SEP-15:15 0.00 -55203.74 0.00 0.00 1123.47 4322.48 11242.16 22121.35 0.00 2361.27 14033.02 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 08-JAN-06:45 535.70 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -603.67 0.00 -132.00 -408.39
G NW APARTMENT 23-DEC-06:10 464.56 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -491.86 0.00 -86.25 -494.81
OFFICE 30-MAR-06:01 2158.75 0.00 0.00 0.00 0.00 379.58 194.98 271.28 0.00 0.00 0.00 0.00 0.00 0.00 -140.54 -2864.06
G NE APARTMENT 08-JAN-07:14 763.99 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -49.70 0.00 -126.95 -1224.79
G N1 APARTMENT 08-JAN-03:30 557.87 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -313.61 0.00 -49.44 -622.57
G N2 APARTMENT 08-JAN-04:30 601.58 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -323.75 0.00 -65.01 -669.38
G S1 APARTMENT 29-MAR-24:00 524.14 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -301.53 0.00 -78.10 -613.47
G S2 APARTMENT 29-MAR-24:00 517.22 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -301.65 0.00 -78.10 -606.43
M SW APARTMENT 12-FEB-07:00 54.87 0.00 0.00 0.00 163.05 100.83 317.86 0.00 0.00 0.00 1.78 0.00 -191.49 0.00 -446.89 0.00
M NW APARTMENT 18-DEC-08:38 157.15 0.00 0.00 0.00 63.99 43.21 388.49 43.53 0.00 0.00 0.00 0.00 0.00 0.00 -384.20 -312.19
M SE APARTMENT 11-FEB-16:00 18.35 0.00 0.00 0.00 40.75 50.41 400.26 0.00 0.00 0.00 181.02 0.00 -191.59 0.00 -499.21 0.00
M NE APARTMENT 18-DEC-08:04 24.75 0.00 0.00 0.00 63.59 43.21 388.49 628.48 0.00 0.00 0.00 0.00 0.00 0.00 -445.19 -703.34
M N1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 31-DEC-07:01 695.46 0.00 0.00 0.00 162.00 93.63 382.60 5.27 0.00 0.00 0.00 0.00 0.00 0.00 -202.24 -1136.72
T NW APARTMENT 11-MAR-06:01 941.24 0.00 0.00 0.00 162.17 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -386.20 0.00 -213.32 -980.11
T SE APARTMENT 30-MAR-04:00 707.47 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -511.65 0.00 -305.91 -346.47
T NE APARTMENT 30-MAR-03:00 767.96 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -508.42 0.00 -313.42 -373.87
T N1 APARTMENT 05-JAN-07:14 506.81 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -250.94 0.00 -109.89 -783.43
T N2 APARTMENT 05-JAN-07:14 509.73 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -250.89 0.00 -109.89 -786.40
T S1 APARTMENT 09-JAN-06:25 448.40 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -354.74 0.00 -143.85 -558.16
T S2 APARTMENT 29-MAR-06:01 1161.03 0.00 0.00 0.00 162.80 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -198.47 0.00 -123.36 -1478.23
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-MAR-03:00 -1217.04 0.00 0.00 0.00 4288.54 2334.74 5313.65 0.00 0.00 0.00 4552.81 0.00 -10493.17 0.00 -4779.53 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Sec1.1A-General Information

Data
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 20.25
Number of hours cooling loads not met 19.00
Number of hours not met 39.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 6.78 14058.44 0.00 0.00
Space Cooling 119.06 13788.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 181.59 5758.08 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 366.52 22172.32 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1383.03   6.78   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1383.03
Natural Gas 0.00 6.78
Additional 0.00 0.00
Total 511.42 1389.81


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 37.98
Fans-Interior 57.93
Service Water Heating 116.93
Receptacle Equipment 163.15
Miscellaneous 12.58
Subtotal 441.21


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 2.16
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 2.16


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 11.87
Space Heating 0.49
Space Cooling 8.57
Fans-Interior 13.07
Service Water Heating 26.37
Receptacle Equipment 36.80
Miscellaneous 2.84



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.148386
G NW APARTMENT DIRECT AIR 0.136497
OFFICE DIRECT AIR 0.427520
G NE APARTMENT DIRECT AIR 0.104479
G N1 APARTMENT DIRECT AIR 0.081979
G N2 APARTMENT DIRECT AIR 0.081262
G S1 APARTMENT DIRECT AIR 0.095082
G S2 APARTMENT DIRECT AIR 0.098130
M SW APARTMENT DIRECT AIR 0.395636
M NW APARTMENT DIRECT AIR 0.364314
M SE APARTMENT DIRECT AIR 0.346289
M NE APARTMENT DIRECT AIR 0.293323
M N1 APARTMENT DIRECT AIR 0.231661
M N2 APARTMENT DIRECT AIR 0.230366
M S1 APARTMENT DIRECT AIR 0.267597
M S2 APARTMENT DIRECT AIR 0.268643
T SW APARTMENT DIRECT AIR 0.254382
T NW APARTMENT DIRECT AIR 0.231235
T SE APARTMENT DIRECT AIR 0.229127
T NE APARTMENT DIRECT AIR 0.183595
T N1 APARTMENT DIRECT AIR 0.145940
T N2 APARTMENT DIRECT AIR 0.146082
T S1 APARTMENT DIRECT AIR 0.189237
T S2 APARTMENT DIRECT AIR 0.189885


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.148386
SPLIT GNW MAIN BRANCH 0.136497
SPLIT OFFICE MAIN BRANCH 0.427520
SPLIT GNE MAIN BRANCH 0.104479
SPLIT GN1 MAIN BRANCH 0.081979
SPLIT GN2 MAIN BRANCH 0.081262
SPLIT GS1 MAIN BRANCH 0.095082
SPLIT GS2 MAIN BRANCH 0.098130
SPLIT MSW MAIN BRANCH 0.395636
SPLIT MNW MAIN BRANCH 0.364314
SPLIT MSE MAIN BRANCH 0.346289
SPLIT MNE MAIN BRANCH 0.293323
SPLIT MN1 MAIN BRANCH 0.231661
SPLIT MN2 MAIN BRANCH 0.230366
SPLIT MS1 MAIN BRANCH 0.267597
SPLIT MS2 MAIN BRANCH 0.268643
SPLIT TSW MAIN BRANCH 0.254382
SPLIT TNW MAIN BRANCH 0.231235
SPLIT TSE MAIN BRANCH 0.229127
SPLIT TNE MAIN BRANCH 0.183595
SPLIT TN1 MAIN BRANCH 0.145940
SPLIT TN2 MAIN BRANCH 0.146082
SPLIT TS1 MAIN BRANCH 0.189237
SPLIT TS2 MAIN BRANCH 0.189885


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.148386
SPLIT GNW 0.136497
SPLIT OFFICE 0.427520
SPLIT GNE 0.104479
SPLIT GN1 0.081979
SPLIT GN2 0.081262
SPLIT GS1 0.095082
SPLIT GS2 0.098130
SPLIT MSW 0.395636
SPLIT MNW 0.364314
SPLIT MSE 0.346289
SPLIT MNE 0.293323
SPLIT MN1 0.231661
SPLIT MN2 0.230366
SPLIT MS1 0.267597
SPLIT MS2 0.268643
SPLIT TSW 0.254382
SPLIT TNW 0.231235
SPLIT TSE 0.229127
SPLIT TNE 0.183595
SPLIT TN1 0.145940
SPLIT TN2 0.146082
SPLIT TS1 0.189237
SPLIT TS2 0.189885


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.148386 0.026898
SPLIT GNW OA CONTROLLER 0.136497 0.025953
SPLIT OFFICE OA CONTROLLER 0.427520 0.038104
SPLIT GNE OA CONTROLLER 0.104479 0.025953
SPLIT GN1 OA CONTROLLER 0.081979 0.025953
SPLIT GN2 OA CONTROLLER 0.081262 0.025953
SPLIT GS1 OA CONTROLLER 0.095082 0.025953
SPLIT GS2 OA CONTROLLER 0.098130 0.025953
SPLIT MSW OA CONTROLLER 0.395636 0.051906
SPLIT MNW OA CONTROLLER 0.364314 0.051906
SPLIT MSE OA CONTROLLER 0.346289 0.051906
SPLIT MNE OA CONTROLLER 0.293323 0.051906
SPLIT MN1 OA CONTROLLER 0.231661 0.051906
SPLIT MN2 OA CONTROLLER 0.230366 0.051906
SPLIT MS1 OA CONTROLLER 0.267597 0.051906
SPLIT MS2 OA CONTROLLER 0.268643 0.051906
SPLIT TSW OA CONTROLLER 0.254382 0.025953
SPLIT TNW OA CONTROLLER 0.231235 0.025953
SPLIT TSE OA CONTROLLER 0.229127 0.025953
SPLIT TNE OA CONTROLLER 0.183595 0.025953
SPLIT TN1 OA CONTROLLER 0.145940 0.025953
SPLIT TN2 OA CONTROLLER 0.146082 0.025953
SPLIT TS1 OA CONTROLLER 0.189237 0.025953
SPLIT TS2 OA CONTROLLER 0.189885 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.148386 2468.85 0.796789
SPLIT GNW COOLING COIL 0.136497 2259.51 0.798655
SPLIT OFFICE COOLING COIL 0.427520 7076.98 0.798655
SPLIT GNE COOLING COIL 0.104479 1729.50 0.798655
SPLIT GN1 COOLING COIL 0.081979 1389.20 0.790146
SPLIT GN2 COOLING COIL 0.081262 1378.14 0.789860
SPLIT GS1 COOLING COIL 0.095082 1670.39 0.777429
SPLIT GS2 COOLING COIL 0.098130 1717.20 0.778786
SPLIT MSW COOLING COIL 0.395636 6549.17 0.798655
SPLIT MNW COOLING COIL 0.364314 6030.69 0.798655
SPLIT MSE COOLING COIL 0.346289 5745.13 0.797836
SPLIT MNE COOLING COIL 0.293323 4855.53 0.798655
SPLIT MN1 COOLING COIL 0.231661 3837.87 0.798362
SPLIT MN2 COOLING COIL 0.230366 3818.02 0.798209
SPLIT MS1 COOLING COIL 0.267597 4538.16 0.789867
SPLIT MS2 COOLING COIL 0.268643 4554.27 0.789994
SPLIT TSW COOLING COIL 0.254382 4210.92 0.798655
SPLIT TNW COOLING COIL 0.231235 3827.76 0.798655
SPLIT TSE COOLING COIL 0.229127 3792.87 0.798655
SPLIT TNE COOLING COIL 0.183595 3051.75 0.797138
SPLIT TN1 COOLING COIL 0.145940 2472.37 0.790248
SPLIT TN2 COOLING COIL 0.146082 2474.52 0.790283
SPLIT TS1 COOLING COIL 0.189237 3136.98 0.798135
SPLIT TS2 COOLING COIL 0.189885 3143.28 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.148386 0.148386 0.148386 0.148386 1475.74 2468.85 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.136497 0.136497 0.136497 0.136497 1423.87 2259.51 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.427520 0.427520 0.427520 0.427520 2489.99 7076.98 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.104479 0.104479 0.104479 0.104479 1423.87 1729.50 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.081979 0.081979 0.081979 0.081979 1423.87 1389.20 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.081262 0.081262 0.081262 0.081262 1423.87 1378.14 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.095082 0.095082 0.095082 0.095082 1423.87 1670.39 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.098130 0.098130 0.098130 0.098130 1423.87 1717.20 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.395636 0.395636 0.395636 0.395636 2847.74 6549.17 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.364314 0.364314 0.364314 0.364314 2847.74 6030.69 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.346289 0.346289 0.346289 0.346289 2847.74 5745.13 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.293323 0.293323 0.293323 0.293323 2847.74 4855.53 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.231661 0.231661 0.231661 0.231661 2847.74 3837.87 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.230366 0.230366 0.230366 0.230366 2847.74 3818.02 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.267597 0.267597 0.267597 0.267597 2847.74 4538.16 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.268643 0.268643 0.268643 0.268643 2847.74 4554.27 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.254382 0.254382 0.254382 0.254382 1823.72 4210.92 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.231235 0.231235 0.231235 0.231235 1821.15 3827.76 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.229127 0.229127 0.229127 0.229127 1827.14 3792.87 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.183595 0.183595 0.183595 0.183595 1824.58 3051.75 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.145940 0.145940 0.145940 0.145940 1423.87 2472.37 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.146082 0.146082 0.146082 0.146082 1423.87 2474.52 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.189237 0.189237 0.189237 0.189237 1423.87 3136.98 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.189885 0.189885 0.189885 0.189885 1423.87 3143.28 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.148386
SPLIT GNW SUPPLY FAN 0.136497
SPLIT OFFICE SUPPLY FAN 0.427520
SPLIT GNE SUPPLY FAN 0.104479
SPLIT GN1 SUPPLY FAN 0.081979
SPLIT GN2 SUPPLY FAN 0.081262
SPLIT GS1 SUPPLY FAN 0.095082
SPLIT GS2 SUPPLY FAN 0.098130
SPLIT MSW SUPPLY FAN 0.395636
SPLIT MNW SUPPLY FAN 0.364314
SPLIT MSE SUPPLY FAN 0.346289
SPLIT MNE SUPPLY FAN 0.293323
SPLIT MN1 SUPPLY FAN 0.231661
SPLIT MN2 SUPPLY FAN 0.230366
SPLIT MS1 SUPPLY FAN 0.267597
SPLIT MS2 SUPPLY FAN 0.268643
SPLIT TSW SUPPLY FAN 0.254382
SPLIT TNW SUPPLY FAN 0.231235
SPLIT TSE SUPPLY FAN 0.229127
SPLIT TNE SUPPLY FAN 0.183595
SPLIT TN1 SUPPLY FAN 0.145940
SPLIT TN2 SUPPLY FAN 0.146082
SPLIT TS1 SUPPLY FAN 0.189237
SPLIT TS2 SUPPLY FAN 0.189885


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1475.74
SPLIT GNW HEATING COIL 1423.87
SPLIT OFFICE HEATING COIL 2489.99
SPLIT GNE HEATING COIL 1423.87
SPLIT GN1 HEATING COIL 1423.87
SPLIT GN2 HEATING COIL 1423.87
SPLIT GS1 HEATING COIL 1423.87
SPLIT GS2 HEATING COIL 1423.87
SPLIT MSW HEATING COIL 2847.74
SPLIT MNW HEATING COIL 2847.74
SPLIT MSE HEATING COIL 2847.74
SPLIT MNE HEATING COIL 2847.74
SPLIT MN1 HEATING COIL 2847.74
SPLIT MN2 HEATING COIL 2847.74
SPLIT MS1 HEATING COIL 2847.74
SPLIT MS2 HEATING COIL 2847.74
SPLIT TSW HEATING COIL 1823.72
SPLIT TNW HEATING COIL 1821.15
SPLIT TSE HEATING COIL 1827.14
SPLIT TNE HEATING COIL 1824.58
SPLIT TN1 HEATING COIL 1423.87
SPLIT TN2 HEATING COIL 1423.87
SPLIT TS1 HEATING COIL 1423.87
SPLIT TS2 HEATING COIL 1423.87



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:31

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.17 13.22
February 22.95 13.28
March 22.81 12.64
April 23.41 15.30
May 23.32 15.56
June 24.27 17.67
July 24.39 19.43
August 24.39 19.66
September 24.37 18.47
October 24.00 18.77
November 23.40 14.32
December 23.23 13.59
     
Annual Sum or Average 23.65 16.01
Minimum of Months 22.81 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.40 13.22
February 22.33 13.28
March 22.39 12.64
April 23.09 15.30
May 23.25 15.56
June 24.27 17.67
July 24.39 19.43
August 24.39 19.66
September 24.34 18.47
October 23.77 18.77
November 22.65 14.32
December 22.47 13.59
     
Annual Sum or Average 23.32 16.01
Minimum of Months 22.33 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 13.22
February 23.32 13.28
March 23.22 12.64
April 23.63 15.30
May 23.65 15.56
June 23.90 17.67
July 23.90 19.43
August 23.90 19.66
September 23.90 18.47
October 23.85 18.77
November 23.57 14.32
December 23.37 13.59
     
Annual Sum or Average 23.63 16.01
Minimum of Months 23.22 12.64
Maximum of Months 23.90 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.34 13.22
February 22.23 13.28
March 22.32 12.64
April 22.99 15.30
May 23.12 15.56
June 24.22 17.67
July 24.38 19.43
August 24.38 19.66
September 24.31 18.47
October 23.69 18.77
November 22.54 14.32
December 22.38 13.59
     
Annual Sum or Average 23.25 16.01
Minimum of Months 22.23 12.64
Maximum of Months 24.38 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 13.22
February 22.19 13.28
March 22.22 12.64
April 22.77 15.30
May 22.94 15.56
June 24.22 17.67
July 24.38 19.43
August 24.38 19.66
September 24.32 18.47
October 23.64 18.77
November 22.49 14.32
December 22.34 13.59
     
Annual Sum or Average 23.19 16.01
Minimum of Months 22.19 12.64
Maximum of Months 24.38 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 13.22
February 22.19 13.28
March 22.22 12.64
April 22.77 15.30
May 22.93 15.56
June 24.22 17.67
July 24.38 19.43
August 24.38 19.66
September 24.32 18.47
October 23.63 18.77
November 22.48 14.32
December 22.34 13.59
     
Annual Sum or Average 23.18 16.01
Minimum of Months 22.19 12.64
Maximum of Months 24.38 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.22 13.22
February 22.96 13.28
March 22.76 12.64
April 23.26 15.30
May 23.08 15.56
June 24.24 17.67
July 24.38 19.43
August 24.39 19.66
September 24.37 18.47
October 24.00 18.77
November 23.43 14.32
December 23.30 13.59
     
Annual Sum or Average 23.62 16.01
Minimum of Months 22.76 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 13.22
February 22.97 13.28
March 22.77 12.64
April 23.26 15.30
May 23.09 15.56
June 24.23 17.67
July 24.38 19.43
August 24.39 19.66
September 24.36 18.47
October 23.99 18.77
November 23.43 14.32
December 23.30 13.59
     
Annual Sum or Average 23.62 16.01
Minimum of Months 22.77 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 13.22
February 24.34 13.28
March 24.26 12.64
April 24.38 15.30
May 24.39 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.40 18.77
November 24.37 14.32
December 24.33 13.59
     
Annual Sum or Average 24.36 16.01
Minimum of Months 24.26 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.07 13.22
February 24.22 13.28
March 24.16 12.64
April 24.37 15.30
May 24.39 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.39 18.77
November 24.28 14.32
December 24.15 13.59
     
Annual Sum or Average 24.30 16.01
Minimum of Months 24.07 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 13.22
February 24.32 13.28
March 24.24 12.64
April 24.38 15.30
May 24.38 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.40 18.77
November 24.36 14.32
December 24.32 13.59
     
Annual Sum or Average 24.36 16.01
Minimum of Months 24.24 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.06 13.22
February 24.18 13.28
March 24.12 12.64
April 24.36 15.30
May 24.38 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.38 18.77
November 24.26 14.32
December 24.12 13.59
     
Annual Sum or Average 24.29 16.01
Minimum of Months 24.06 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.31 13.28
March 24.25 12.64
April 24.38 15.30
May 24.39 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.40 18.77
November 24.34 14.32
December 24.25 13.59
     
Annual Sum or Average 24.34 16.01
Minimum of Months 24.18 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.30 13.28
March 24.25 12.64
April 24.38 15.30
May 24.39 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.40 18.77
November 24.33 14.32
December 24.24 13.59
     
Annual Sum or Average 24.34 16.01
Minimum of Months 24.18 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 13.22
February 24.39 13.28
March 24.33 12.64
April 24.39 15.30
May 24.40 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.41 18.77
November 24.40 14.32
December 24.38 13.59
     
Annual Sum or Average 24.39 16.01
Minimum of Months 24.33 12.64
Maximum of Months 24.41 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 13.22
February 24.39 13.28
March 24.33 12.64
April 24.39 15.30
May 24.39 15.56
June 24.40 17.67
July 24.40 19.43
August 24.40 19.66
September 24.40 18.47
October 24.41 18.77
November 24.40 14.32
December 24.38 13.59
     
Annual Sum or Average 24.39 16.01
Minimum of Months 24.33 12.64
Maximum of Months 24.41 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 13.22
February 23.65 13.28
March 23.60 12.64
April 24.13 15.30
May 24.15 15.56
June 24.36 17.67
July 24.40 19.43
August 24.40 19.66
September 24.37 18.47
October 24.26 18.77
November 23.94 14.32
December 23.72 13.59
     
Annual Sum or Average 24.06 16.01
Minimum of Months 23.60 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.23 13.22
February 23.28 13.28
March 23.37 12.64
April 24.04 15.30
May 24.12 15.56
June 24.36 17.67
July 24.40 19.43
August 24.39 19.66
September 24.35 18.47
October 24.16 18.77
November 23.58 14.32
December 23.25 13.59
     
Annual Sum or Average 23.88 16.01
Minimum of Months 23.23 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 13.22
February 23.60 13.28
March 23.58 12.64
April 24.11 15.30
May 24.13 15.56
June 24.35 17.67
July 24.39 19.43
August 24.40 19.66
September 24.36 18.47
October 24.25 18.77
November 23.92 14.32
December 23.71 13.59
     
Annual Sum or Average 24.05 16.01
Minimum of Months 23.58 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 13.22
February 23.19 13.28
March 23.30 12.64
April 24.00 15.30
May 24.07 15.56
June 24.33 17.67
July 24.39 19.43
August 24.39 19.66
September 24.32 18.47
October 24.14 18.77
November 23.51 14.32
December 23.17 13.59
     
Annual Sum or Average 23.84 16.01
Minimum of Months 23.17 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 13.22
February 23.30 13.28
March 23.38 12.64
April 24.06 15.30
May 24.14 15.56
June 24.35 17.67
July 24.39 19.43
August 24.39 19.66
September 24.35 18.47
October 24.19 18.77
November 23.58 14.32
December 23.22 13.59
     
Annual Sum or Average 23.88 16.01
Minimum of Months 23.18 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 13.22
February 23.29 13.28
March 23.37 12.64
April 24.05 15.30
May 24.14 15.56
June 24.35 17.67
July 24.39 19.43
August 24.39 19.66
September 24.35 18.47
October 24.19 18.77
November 23.58 14.32
December 23.22 13.59
     
Annual Sum or Average 23.88 16.01
Minimum of Months 23.18 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 13.22
February 23.82 13.28
March 23.73 12.64
April 24.19 15.30
May 24.20 15.56
June 24.37 17.67
July 24.40 19.43
August 24.40 19.66
September 24.38 18.47
October 24.31 18.77
November 24.05 14.32
December 23.86 13.59
     
Annual Sum or Average 24.13 16.01
Minimum of Months 23.73 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 13.22
February 23.81 13.28
March 23.73 12.64
April 24.19 15.30
May 24.20 15.56
June 24.37 17.67
July 24.40 19.43
August 24.40 19.66
September 24.38 18.47
October 24.31 18.77
November 24.05 14.32
December 23.86 13.59
     
Annual Sum or Average 24.13 16.01
Minimum of Months 23.73 12.64
Maximum of Months 24.40 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.66 13.22
February 24.72 13.28
March 24.75 12.64
April 25.68 15.30
May 25.76 15.56
June 26.24 17.67
July 26.49 19.43
August 26.48 19.66
September 26.24 18.47
October 26.04 18.77
November 25.09 14.32
December 24.69 13.59
     
Annual Sum or Average 25.57 16.01
Minimum of Months 24.66 12.64
Maximum of Months 26.49 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.82 13.22
February 22.76 13.28
March 22.65 12.64
April 23.40 15.30
May 23.49 15.56
June 25.09 17.67
July 25.63 19.43
August 25.70 19.66
September 25.44 18.47
October 24.46 18.77
November 23.23 14.32
December 22.96 13.59
     
Annual Sum or Average 23.98 16.01
Minimum of Months 22.65 12.64
Maximum of Months 25.70 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:31

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.32 13.22
February 26.38 13.28
March 26.30 12.64
April 26.59 15.30
May 26.60 15.56
June 26.71 17.67
July 26.82 19.43
August 26.83 19.66
September 26.76 18.47
October 26.75 18.77
November 26.51 14.32
December 26.39 13.59
     
Annual Sum or Average 26.58 16.01
Minimum of Months 26.30 12.64
Maximum of Months 26.83 19.66



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:31

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.114987E+12 70888.106 18-JAN-18:15 8572.775 26456.413 5758.081 0.000 5707.397 2508.330 0.000 0.000 0.000 0.000 0.000 21885.111 0.000 0.000 0.000
February 0.102760E+12 71728.388 01-FEB-18:15 8572.775 26456.413 5758.081 0.000 4909.955 2508.330 0.000 0.000 0.000 0.000 0.000 23522.834 0.000 0.000 0.000
March 0.113187E+12 71967.214 21-MAR-17:00 8572.775 26456.413 5758.081 0.000 5017.906 2508.330 0.000 0.000 0.000 0.000 0.000 23653.710 0.000 0.000 0.000
April 0.112095E+12 71528.583 23-APR-17:00 8572.775 26456.413 5758.081 0.000 5683.851 0.000 0.000 0.000 0.000 0.000 0.000 25057.463 0.000 0.000 0.000
May 0.114087E+12 69600.701 03-MAY-17:45 8572.775 26456.413 5758.081 0.000 6233.202 0.000 0.000 0.000 0.000 0.000 0.000 22580.230 0.000 0.000 0.000
June 0.114294E+12 72518.816 29-JUN-17:45 8572.775 26456.413 5758.081 0.000 11923.317 0.000 0.000 0.000 0.000 0.000 0.000 19808.230 0.000 0.000 0.000
July 0.123346E+12 74625.922 18-JUL-17:30 8572.775 26456.413 5758.081 0.000 14012.989 0.000 0.000 0.000 0.000 0.000 0.000 19825.664 0.000 0.000 0.000
August 0.124529E+12 73782.725 15-AUG-17:15 8572.775 26456.413 5758.081 0.000 12795.433 0.000 0.000 0.000 0.000 0.000 0.000 20200.024 0.000 0.000 0.000
September 0.117040E+12 76747.587 29-SEP-17:30 8572.775 26456.413 5758.081 0.000 13787.998 0.000 0.000 0.000 0.000 0.000 0.000 22172.320 0.000 0.000 0.000
October 0.120650E+12 76615.716 14-OCT-17:30 8572.775 26456.413 5758.081 0.000 11240.884 2508.330 0.000 0.000 0.000 0.000 0.000 22079.233 0.000 0.000 0.000
November 0.110998E+12 72426.018 08-NOV-18:15 8572.775 26456.413 5758.081 0.000 4772.219 2508.330 0.000 0.000 0.000 0.000 0.000 24358.201 0.000 0.000 0.000
December 0.115057E+12 71121.295 19-DEC-18:30 8572.775 26456.413 5758.081 0.000 5168.226 2508.330 0.000 0.000 0.000 0.000 0.000 22657.470 0.000 0.000 0.000
                                     
Annual Sum or Average 0.138303E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.102760E+12 69600.701   8572.775 26456.413 5758.081 0.000 4772.219 0.000 0.000 0.000 0.000 0.000 0.000 19808.230 0.000 0.000 0.000
Maximum of Months 0.124529E+12 76747.587   8572.775 26456.413 5758.081 0.000 14012.989 2508.330 0.000 0.000 0.000 0.000 0.000 25057.463 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:31

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.213729E+10 11888.640 03-JAN-03:00 11888.640 0.000 0.000 0.000 0.000 0.000 11888.640
February 0.726243E+09 5062.655 05-FEB-05:00 5062.655 0.000 0.000 0.000 0.000 0.000 5062.655
March 0.188721E+10 14058.436 30-MAR-02:00 14058.436 0.000 0.000 0.000 0.000 0.000 14058.436
April 0.109457E+09 5097.723 01-APR-05:00 5097.723 0.000 0.000 0.000 0.000 0.000 5097.723
May 0.457217E+08 1427.002 14-MAY-03:00 1427.002 0.000 0.000 0.000 0.000 0.000 1427.002
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 264113.101 76.200 30-OCT-02:00 76.200 0.000 0.000 0.000 0.000 0.000 76.200
November 0.402300E+09 5126.012 24-NOV-03:00 5126.012 0.000 0.000 0.000 0.000 0.000 5126.012
December 0.146699E+10 9612.800 13-DEC-04:30 9612.800 0.000 0.000 0.000 0.000 0.000 9612.800
                     
Annual Sum or Average 0.677547E+10       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.213729E+10 14058.436   14058.436 0.000 0.000 0.000 0.000 0.000 14058.436