Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2018-10-19 09:20:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1728.52 | 551.43 | 612.09 |
Net Site Energy | 1728.52 | 551.43 | 612.09 |
Total Source Energy | 5018.22 | 1600.90 | 1777.00 |
Net Source Energy | 5018.22 | 1600.90 | 1777.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 218.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 414.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1509.60 | 218.92 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 218.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 123.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 255.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 414.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 281.09 | 77.52 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 534.57 | 77.52 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.23 | 69.84 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 481.59 | 69.84 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1509.60 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1509.60 | 100.00 |
Total On-Site and Utility Electric Sources | 1509.60 | 100.00 |
Total Electricity End Uses | 1509.60 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 48.00 |
Time Setpoint Not Met During Occupied Cooling | 2.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1939.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JUN-17:00 | 22-DEC-03:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 96671.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19196.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8108.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29773.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 92107.98 | 96671.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 96671.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19196.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8108.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 29773.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 237.31 | 0.00 | 0.00 | 0.00 |
Cooling | 389.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 809.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1314.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4780.91 | 237.31 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.03 | 0.00 | 0.00 | 0.00 |
Cooling | 138.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 465.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1692.97 | 84.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.03 | 0.00 | 0.00 | 0.00 |
Cooling | 138.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 465.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1692.97 | 84.03 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.67 | 83.67 | 39.40 | |
Exterior Lighting Total | 2508.33 | 39.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3419.77 | 2731.22 | 688.55 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3304.49 | 2639.15 | 665.34 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8629.62 | 6892.09 | 1737.53 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2319.27 | 1852.29 | 466.97 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1926.64 | 1538.72 | 387.92 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1903.47 | 1520.22 | 383.25 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1995.40 | 1593.63 | 401.76 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2056.47 | 1642.41 | 414.06 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9343.68 | 7462.38 | 1881.30 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8949.36 | 7147.46 | 1801.91 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7802.80 | 6231.75 | 1571.05 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6688.75 | 5342.01 | 1346.74 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5465.22 | 4364.83 | 1100.39 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5424.87 | 4332.60 | 1092.27 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5827.43 | 4654.11 | 1173.32 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5849.43 | 4671.68 | 1177.75 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6262.32 | 5001.43 | 1260.88 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5901.14 | 4712.98 | 1188.16 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5592.45 | 4466.44 | 1126.01 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4593.47 | 3668.60 | 924.87 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3703.13 | 2957.52 | 745.61 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3665.56 | 2927.52 | 738.04 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4599.95 | 3673.77 | 926.18 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4613.35 | 3684.48 | 928.87 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3257.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3148.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8221.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2209.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1835.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1813.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1900.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1959.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8901.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8525.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7433.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6372.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5206.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5168.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5551.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5572.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5965.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5621.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5327.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4376.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3527.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3492.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4382.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4394.9 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2691.84 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2644.46 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5028.11 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2644.46 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1975.43 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1975.43 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1988.82 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2104.98 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 5276.97 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 5248.86 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 5276.97 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 5248.86 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3608.60 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3608.60 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3639.29 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3639.29 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4094.63 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4081.50 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4094.63 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4081.50 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3239.53 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3239.53 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3251.41 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3251.41 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.40 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 223.60 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 583.93 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.93 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.37 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 128.80 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 135.02 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 139.15 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 632.25 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.54 | 605.57 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 527.98 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 452.60 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 369.81 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 367.08 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 394.32 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 395.81 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 423.74 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 399.30 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 378.42 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 310.82 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 250.58 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 248.03 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 311.26 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 312.17 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1784.54 | 2141.45 | 0.172 | 0.207 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.09 | 0.00543 |
G NW APARTMENT | 1724.39 | 2069.26 | 0.166 | 0.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
OFFICE | 4404.30 | 5285.16 | 0.434 | 0.521 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76 | 0.00543 |
G NE APARTMENT | 1210.26 | 1452.32 | 0.117 | 0.140 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.24 | 0.00543 |
G N1 APARTMENT | 1005.37 | 1206.44 | 0.097 | 0.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
G N2 APARTMENT | 993.28 | 1191.94 | 0.096 | 0.115 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
G S1 APARTMENT | 1041.26 | 1249.51 | 0.100 | 0.121 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
G S2 APARTMENT | 1073.13 | 1287.75 | 0.104 | 0.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
M SW APARTMENT | 4875.86 | 5851.03 | 0.470 | 0.564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.09 | 0.00543 |
M NW APARTMENT | 4670.07 | 5604.09 | 0.451 | 0.541 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
M SE APARTMENT | 4071.80 | 4886.16 | 0.393 | 0.471 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
M NE APARTMENT | 3490.41 | 4188.49 | 0.337 | 0.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.24 | 0.00543 |
M N1 APARTMENT | 2851.90 | 3422.28 | 0.275 | 0.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
M N2 APARTMENT | 2830.85 | 3397.02 | 0.273 | 0.328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
M S1 APARTMENT | 3040.94 | 3649.13 | 0.293 | 0.352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
M S2 APARTMENT | 3052.43 | 3662.91 | 0.294 | 0.353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
T SW APARTMENT | 3267.95 | 3921.54 | 0.315 | 0.378 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.42 | 0.00543 |
T NW APARTMENT | 3079.44 | 3695.33 | 0.297 | 0.356 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.09 | 0.00543 |
T SE APARTMENT | 2918.39 | 3502.07 | 0.282 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
T NE APARTMENT | 2397.08 | 2876.49 | 0.231 | 0.277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.90 | 0.00543 |
T N1 APARTMENT | 1932.41 | 2318.89 | 0.186 | 0.224 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
T N2 APARTMENT | 1912.82 | 2295.39 | 0.185 | 0.221 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 33.68 | 0.00543 |
T S1 APARTMENT | 2400.42 | 2880.50 | 0.232 | 0.278 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90 | 0.00543 |
T S2 APARTMENT | 2407.41 | 2888.90 | 0.232 | 0.279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90 | 0.00543 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1391.64 | 1669.97 | 0.049 | 0.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G NW APARTMENT | 1382.67 | 1659.20 | 0.049 | 0.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
OFFICE | 3041.32 | 3649.58 | 0.104 | 0.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G NE APARTMENT | 1382.67 | 1659.20 | 0.049 | 0.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G N1 APARTMENT | 816.90 | 980.28 | 0.029 | 0.035 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G N2 APARTMENT | 816.90 | 980.28 | 0.029 | 0.035 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G S1 APARTMENT | 828.22 | 993.87 | 0.029 | 0.035 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G S2 APARTMENT | 926.45 | 1111.74 | 0.033 | 0.039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
M SW APARTMENT | 2755.28 | 3306.34 | 0.098 | 0.117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M NW APARTMENT | 2731.51 | 3277.81 | 0.097 | 0.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M SE APARTMENT | 2755.28 | 3306.34 | 0.098 | 0.117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M NE APARTMENT | 2731.51 | 3277.81 | 0.097 | 0.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M N1 APARTMENT | 1344.39 | 1613.27 | 0.048 | 0.057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M N2 APARTMENT | 1344.39 | 1613.27 | 0.048 | 0.057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M S1 APARTMENT | 1370.35 | 1644.41 | 0.049 | 0.058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
M S2 APARTMENT | 1370.35 | 1644.41 | 0.049 | 0.058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T SW APARTMENT | 2609.04 | 3130.85 | 0.092 | 0.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T NW APARTMENT | 2597.94 | 3117.53 | 0.092 | 0.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T SE APARTMENT | 2609.04 | 3130.85 | 0.092 | 0.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T NE APARTMENT | 2597.94 | 3117.53 | 0.092 | 0.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T N1 APARTMENT | 1885.90 | 2263.08 | 0.067 | 0.080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T N2 APARTMENT | 1885.90 | 2263.08 | 0.067 | 0.080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T S1 APARTMENT | 1895.96 | 2275.15 | 0.067 | 0.081 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
T S2 APARTMENT | 1895.96 | 2275.15 | 0.067 | 0.081 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -17.90 | 0.00096 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.21 | 0.21 | 0.06 | 0.06 |
SPLIT GNW | 0.20 | 0.20 | 0.06 | 0.06 |
SPLIT OFFICE | 0.52 | 0.52 | 0.13 | 0.13 |
SPLIT GNE | 0.14 | 0.14 | 0.06 | 0.06 |
SPLIT GN1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GN2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.04 | 0.04 |
SPLIT GS2 | 0.12 | 0.12 | 0.04 | 0.04 |
SPLIT MSW | 0.56 | 0.56 | 0.12 | 0.12 |
SPLIT MNW | 0.54 | 0.54 | 0.12 | 0.12 |
SPLIT MSE | 0.47 | 0.47 | 0.12 | 0.12 |
SPLIT MNE | 0.40 | 0.40 | 0.12 | 0.12 |
SPLIT MN1 | 0.33 | 0.33 | 0.06 | 0.06 |
SPLIT MN2 | 0.33 | 0.33 | 0.06 | 0.06 |
SPLIT MS1 | 0.35 | 0.35 | 0.06 | 0.06 |
SPLIT MS2 | 0.35 | 0.35 | 0.06 | 0.06 |
SPLIT TSW | 0.38 | 0.38 | 0.11 | 0.11 |
SPLIT TNW | 0.36 | 0.36 | 0.11 | 0.11 |
SPLIT TSE | 0.34 | 0.34 | 0.11 | 0.11 |
SPLIT TNE | 0.28 | 0.28 | 0.11 | 0.11 |
SPLIT TN1 | 0.22 | 0.22 | 0.08 | 0.08 |
SPLIT TN2 | 0.22 | 0.22 | 0.08 | 0.08 |
SPLIT TS1 | 0.28 | 0.28 | 0.08 | 0.08 |
SPLIT TS2 | 0.28 | 0.28 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1808.25 | 6003.75 | 711.25 |
G NW APARTMENT | 2130.25 | 6229.75 | 1242.25 |
OFFICE | 164.50 | 1552.00 | 115.00 |
G NE APARTMENT | 2207.25 | 6243.75 | 1242.00 |
G N1 APARTMENT | 1507.50 | 6372.25 | 796.75 |
G N2 APARTMENT | 1509.25 | 6373.50 | 795.50 |
G S1 APARTMENT | 1287.50 | 6109.25 | 395.50 |
G S2 APARTMENT | 1320.25 | 6135.00 | 455.50 |
M SW APARTMENT | 2164.75 | 3712.75 | 146.25 |
M NW APARTMENT | 2060.00 | 5043.75 | 348.50 |
M SE APARTMENT | 2224.50 | 3749.75 | 155.75 |
M NE APARTMENT | 2106.75 | 5057.50 | 349.00 |
M N1 APARTMENT | 1576.75 | 5007.00 | 151.00 |
M N2 APARTMENT | 1579.50 | 5006.25 | 151.00 |
M S1 APARTMENT | 1737.75 | 3264.75 | 35.25 |
M S2 APARTMENT | 1742.75 | 3273.25 | 35.50 |
T SW APARTMENT | 3346.50 | 4693.00 | 1089.25 |
T NW APARTMENT | 3541.00 | 5469.25 | 1678.50 |
T SE APARTMENT | 3371.75 | 4678.25 | 1104.25 |
T NE APARTMENT | 3607.75 | 5502.50 | 1705.25 |
T N1 APARTMENT | 3043.25 | 5563.50 | 1346.75 |
T N2 APARTMENT | 3047.50 | 5561.00 | 1350.25 |
T S1 APARTMENT | 2813.00 | 4617.50 | 763.25 |
T S2 APARTMENT | 2814.75 | 4609.25 | 761.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4616.25 | 6499.25 | 1939.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
G NW APARTMENT | 5.50 | 0.50 | 5.50 | 0.50 |
OFFICE | 7.25 | 0.75 | 0.00 | 0.00 |
G NE APARTMENT | 7.50 | 0.00 | 7.50 | 0.00 |
G N1 APARTMENT | 7.00 | 0.00 | 7.00 | 0.00 |
G N2 APARTMENT | 6.25 | 0.00 | 6.25 | 0.00 |
G S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M NW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M N1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M N2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
T NW APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
T SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NE APARTMENT | 0.25 | 0.25 | 0.25 | 0.25 |
T N1 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
T N2 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
T S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 55.25 | 2.75 | 48.00 | 2.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.365 | 0.098 | 0.000 | 0.070 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.098 | 0.000 | 0.067 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.516 | 0.102 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.098 | 0.000 | 0.067 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.059 | 0.000 | 0.066 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.059 | 0.000 | 0.066 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.059 | 0.000 | 0.069 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.059 | 0.000 | 0.069 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.142 | 0.000 | 0.085 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.141 | 0.000 | 0.082 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.142 | 0.000 | 0.085 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.141 | 0.000 | 0.082 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.085 | 0.000 | 0.082 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.085 | 0.000 | 0.082 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.085 | 0.000 | 0.085 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.085 | 0.000 | 0.085 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.187 | 0.000 | 0.102 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.187 | 0.000 | 0.099 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.187 | 0.000 | 0.102 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.187 | 0.000 | 0.099 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.113 | 0.000 | 0.098 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.113 | 0.000 | 0.098 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.113 | 0.000 | 0.102 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.113 | 0.000 | 0.102 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.376 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.376 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.372 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.372 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.372 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1509.60 | 21479.23 | 09-JAN-03:30 | 92107.98 | 14-JUN-18:00 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 414.94 | 0.00 | 01-JAN-00:15 | 32646.39 | 16-JAN-08:00 |
WaterSystems:Electricity | 414.94 | 0.00 | 01-JAN-00:15 | 32646.39 | 16-JAN-08:00 |
Water Heater:WaterSystems:Electricity | 414.94 | 0.00 | 01-JAN-00:15 | 32646.39 | 16-JAN-08:00 |
Fans:Electricity | 255.72 | 8108.93 | 01-JAN-07:15 | 8108.93 | 01-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
ElectricityPurchased:Plant | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
Cogeneration:ElectricityPurchased | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
ElectricityNet:Plant | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
Cogeneration:ElectricityNet | 1509.60 | 21479.23 | 01-JAN-03:15 | 92107.98 | 14-JUN-18:00 |
ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 378.84 | 8108.93 | 01-JAN-07:15 | 32242.10 | 26-JUN-17:15 |
General:Fans:Electricity | 255.72 | 8108.93 | 01-JAN-07:15 | 8108.93 | 01-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 123.12 | 0.00 | 01-JAN-00:15 | 24133.17 | 26-JUN-17:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 218.92 | 0.00 | 09-JAN-11:45 | 96671.03 | 22-DEC-04:00 |
Gas:HVAC | 218.92 | 0.00 | 09-JAN-11:45 | 96671.03 | 22-DEC-04:00 |
Heating:Gas | 218.92 | 0.00 | 09-JAN-11:45 | 96671.03 | 22-DEC-04:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1212.75 | 2802.72 | 18-APR-07:30 | 149595.29 | 26-JUN-17:15 |
EnergyTransfer:Building | 561.24 | 1775.27 | 28-APR-15:00 | 65192.92 | 26-JUN-17:15 |
EnergyTransfer:Zone:G SW APARTMENT | 12.08 | 0.05 | 01-JUN-01:30 | 2122.67 | 16-AUG-16:30 |
Heating:EnergyTransfer | 91.83 | 0.00 | 09-JAN-19:15 | 49979.49 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.99 | 0.00 | 01-JAN-08:30 | 1665.98 | 19-MAR-08:00 |
Cooling:EnergyTransfer | 469.41 | 0.00 | 05-FEB-07:30 | 65192.92 | 26-JUN-17:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.10 | 0.00 | 01-JAN-00:15 | 2122.67 | 16-AUG-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 11.14 | 0.02 | 17-FEB-12:15 | 1949.02 | 26-JUN-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 5.00 | 0.00 | 01-JAN-15:00 | 1678.86 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.14 | 0.00 | 01-JAN-00:15 | 1949.02 | 26-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 22.57 | 0.02 | 08-DEC-13:45 | 3485.12 | 28-SEP-12:45 |
Heating:EnergyTransfer:Zone:OFFICE | 0.41 | 0.00 | 01-JAN-00:15 | 3455.40 | 24-DEC-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 22.16 | 0.00 | 03-JAN-07:45 | 3485.12 | 28-SEP-12:45 |
EnergyTransfer:Zone:G NE APARTMENT | 11.44 | 0.00 | 18-NOV-22:00 | 1693.75 | 21-DEC-23:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.82 | 0.00 | 01-JAN-10:00 | 1693.75 | 21-DEC-23:15 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.62 | 0.00 | 01-JAN-00:15 | 1401.41 | 26-JUN-18:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 7.91 | 0.02 | 19-MAY-16:00 | 1122.30 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.18 | 0.00 | 01-JAN-16:15 | 986.17 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 5.72 | 0.00 | 01-JAN-00:15 | 1122.30 | 26-JUN-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 7.92 | 0.07 | 09-MAR-14:15 | 1110.20 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.19 | 0.00 | 01-JAN-16:15 | 987.12 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.74 | 0.00 | 01-JAN-00:15 | 1110.20 | 26-JUN-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 10.13 | 0.01 | 19-MAY-15:15 | 1471.60 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.04 | 0.00 | 01-JAN-00:15 | 943.06 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.10 | 0.00 | 01-JAN-03:00 | 1471.60 | 28-SEP-13:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 10.06 | 0.02 | 13-MAY-07:00 | 1461.99 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.20 | 0.00 | 01-JAN-00:15 | 1025.33 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.86 | 0.00 | 01-JAN-02:30 | 1461.99 | 28-SEP-13:00 |
EnergyTransfer:Zone:M SW APARTMENT | 43.66 | 0.40 | 01-MAY-13:00 | 5656.73 | 16-AUG-16:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 2.09 | 0.00 | 01-JAN-00:15 | 3076.07 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 41.57 | 0.00 | 04-JAN-16:00 | 5656.73 | 16-AUG-16:30 |
EnergyTransfer:Zone:M NW APARTMENT | 31.82 | 0.11 | 15-NOV-15:45 | 5366.42 | 26-JUN-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 4.89 | 0.00 | 01-JAN-09:45 | 3472.60 | 21-DEC-23:15 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 26.93 | 0.00 | 01-JAN-00:15 | 5366.42 | 26-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 45.24 | 0.56 | 13-DEC-03:00 | 4920.99 | 28-SEP-13:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 2.15 | 0.00 | 01-JAN-00:15 | 3125.58 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 43.10 | 0.00 | 04-JAN-15:45 | 4920.99 | 28-SEP-13:15 |
EnergyTransfer:Zone:M NE APARTMENT | 33.54 | 0.03 | 18-APR-09:00 | 4133.23 | 26-JUN-18:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 4.87 | 0.00 | 01-JAN-08:15 | 3585.77 | 21-DEC-23:15 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 28.67 | 0.00 | 01-JAN-00:15 | 4133.23 | 26-JUN-18:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 28.00 | 0.30 | 13-APR-13:15 | 3340.88 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.12 | 0.00 | 01-JAN-00:15 | 1753.39 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.88 | 0.00 | 02-JAN-02:45 | 3340.88 | 26-JUN-18:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 28.02 | 0.10 | 27-APR-10:00 | 3319.14 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.12 | 0.00 | 01-JAN-00:15 | 1751.72 | 24-DEC-03:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.90 | 0.00 | 02-JAN-02:45 | 3319.14 | 26-JUN-18:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 43.49 | 3.39 | 03-APR-08:30 | 4425.15 | 11-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1379.76 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 43.14 | 0.00 | 05-JAN-23:45 | 4425.15 | 11-OCT-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 43.50 | 0.46 | 05-FEB-07:45 | 4430.77 | 11-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1383.20 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 43.15 | 0.00 | 05-JAN-23:45 | 4430.77 | 11-OCT-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 25.18 | 0.01 | 17-DEC-22:45 | 3831.86 | 16-AUG-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 7.35 | 0.00 | 01-JAN-09:00 | 3140.69 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 17.82 | 0.00 | 01-JAN-00:15 | 3831.86 | 16-AUG-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 22.58 | 0.00 | 17-DEC-20:45 | 3639.38 | 26-JUN-17:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 10.41 | 0.00 | 01-JAN-14:30 | 3232.18 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 12.17 | 0.00 | 01-JAN-00:15 | 3639.38 | 26-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 25.41 | 0.00 | 10-MAR-03:15 | 3399.13 | 16-AUG-13:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 7.21 | 0.00 | 01-JAN-08:30 | 3150.02 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 18.20 | 0.00 | 01-JAN-00:15 | 3399.13 | 16-AUG-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 22.73 | 0.01 | 19-OCT-14:00 | 3244.81 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 10.13 | 0.00 | 01-JAN-10:00 | 3244.81 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 12.60 | 0.00 | 01-JAN-00:15 | 2795.54 | 26-JUN-17:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 16.87 | 0.01 | 12-MAR-13:45 | 2365.98 | 26-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 6.17 | 0.00 | 01-JAN-12:45 | 2294.33 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 10.69 | 0.00 | 01-JAN-00:15 | 2365.98 | 26-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 16.91 | 0.01 | 09-JAN-23:45 | 2344.00 | 26-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 6.19 | 0.00 | 01-JAN-12:30 | 2295.46 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 10.72 | 0.00 | 01-JAN-00:15 | 2344.00 | 26-JUN-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 20.51 | 0.12 | 21-MAY-02:30 | 2892.16 | 28-SEP-13:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 3.80 | 0.00 | 01-JAN-00:15 | 2196.41 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 16.70 | 0.00 | 01-JAN-01:15 | 2892.16 | 28-SEP-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 20.55 | 0.15 | 20-SEP-02:15 | 2901.94 | 28-SEP-13:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 3.81 | 0.00 | 01-JAN-00:15 | 2197.72 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 16.74 | 0.00 | 01-JAN-01:15 | 2901.94 | 28-SEP-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 651.51 | 0.00 | 23-MAR-16:15 | 84402.37 | 26-JUN-17:15 |
HeatingCoils:EnergyTransfer | 175.13 | 0.00 | 09-JAN-11:45 | 77336.83 | 22-DEC-04:00 |
CoolingCoils:EnergyTransfer | 476.37 | 0.00 | 01-JAN-00:15 | 84402.37 | 26-JUN-17:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 2.987 | -9.095 | 0.000 | 0.000 | 3.816 | 2.413 | 12.213 | 17.077 | 0.000 | 0.140 | 0.000 | 0.000 | -8.315 | 0.000 | -3.702 | -17.533 |
G NW APARTMENT | 4.995 | -6.141 | 0.000 | 0.000 | 3.853 | 2.413 | 12.213 | 7.762 | 0.000 | 0.139 | 0.000 | 0.000 | -8.440 | 0.000 | -3.585 | -13.208 |
OFFICE | 0.412 | -22.160 | 0.000 | 0.000 | 0.524 | 21.914 | 7.534 | 17.557 | 0.000 | 0.130 | 0.001 | 0.000 | -8.017 | 0.000 | -2.937 | -14.957 |
G NE APARTMENT | 4.822 | -6.622 | 0.000 | 0.000 | 3.865 | 2.413 | 12.213 | 8.157 | 0.000 | 0.139 | 0.000 | 0.000 | -8.276 | 0.000 | -3.569 | -13.140 |
G N1 APARTMENT | 2.184 | -5.724 | 0.000 | 0.000 | 3.866 | 2.413 | 12.213 | 2.665 | 0.000 | 0.093 | 0.000 | 0.000 | -5.249 | 0.000 | -2.368 | -10.092 |
G N2 APARTMENT | 2.185 | -5.736 | 0.000 | 0.000 | 3.866 | 2.413 | 12.213 | 2.664 | 0.000 | 0.093 | 0.000 | 0.000 | -5.248 | 0.000 | -2.367 | -10.083 |
G S1 APARTMENT | 1.035 | -9.098 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 12.027 | 0.000 | 0.094 | 0.000 | 0.000 | -5.066 | 0.000 | -2.492 | -14.945 |
G S2 APARTMENT | 1.198 | -8.862 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 12.029 | 0.000 | 0.094 | 0.000 | 0.000 | -5.058 | 0.000 | -2.493 | -15.352 |
M SW APARTMENT | 2.090 | -41.568 | 0.000 | 0.000 | 3.668 | 2.413 | 12.213 | 16.592 | 0.000 | 0.197 | 18.869 | 0.000 | -9.111 | 0.000 | -5.363 | -0.000 |
M NW APARTMENT | 4.888 | -26.929 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 7.403 | 0.000 | 0.195 | 10.383 | 0.000 | -9.106 | 0.000 | -5.210 | -0.000 |
M SE APARTMENT | 2.149 | -43.095 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 16.999 | 0.000 | 0.197 | 19.759 | 0.000 | -8.960 | 0.000 | -5.355 | 0.000 |
M NE APARTMENT | 4.870 | -28.673 | 0.000 | 0.000 | 3.767 | 2.413 | 12.213 | 7.782 | 0.000 | 0.195 | 11.528 | 0.000 | -8.904 | 0.000 | -5.190 | -0.000 |
M N1 APARTMENT | 1.119 | -26.880 | 0.000 | 0.000 | 3.742 | 2.413 | 12.213 | 2.452 | 0.000 | 0.129 | 14.010 | 0.000 | -5.736 | 0.000 | -3.461 | -0.000 |
M N2 APARTMENT | 1.124 | -26.896 | 0.000 | 0.000 | 3.743 | 2.413 | 12.213 | 2.451 | 0.000 | 0.129 | 14.015 | 0.000 | -5.732 | 0.000 | -3.460 | -0.000 |
M S1 APARTMENT | 0.347 | -43.138 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 11.708 | 0.000 | 0.131 | 21.874 | 0.000 | -5.595 | 0.000 | -3.592 | 0.000 |
M S2 APARTMENT | 0.350 | -43.146 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 11.708 | 0.000 | 0.131 | 21.878 | 0.000 | -5.594 | 0.000 | -3.591 | 0.000 |
T SW APARTMENT | 7.353 | -17.822 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 16.485 | 0.000 | 0.255 | 0.000 | 0.000 | -8.569 | 0.000 | -6.831 | -9.260 |
T NW APARTMENT | 10.405 | -12.172 | 0.000 | 0.000 | 3.805 | 2.413 | 12.213 | 7.319 | 0.000 | 0.253 | 0.000 | 0.000 | -8.644 | 0.000 | -6.689 | -8.903 |
T SE APARTMENT | 7.210 | -18.196 | 0.000 | 0.000 | 3.770 | 2.413 | 12.213 | 16.892 | 0.000 | 0.255 | 0.000 | 0.000 | -8.445 | 0.000 | -6.834 | -9.278 |
T NE APARTMENT | 10.132 | -12.595 | 0.000 | 0.000 | 3.818 | 2.413 | 12.213 | 7.724 | 0.000 | 0.253 | 0.000 | 0.000 | -8.493 | 0.000 | -6.680 | -8.785 |
T N1 APARTMENT | 6.175 | -10.691 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 2.439 | 0.000 | 0.167 | 0.000 | 0.000 | -5.401 | 0.000 | -4.391 | -6.731 |
T N2 APARTMENT | 6.187 | -10.718 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 2.436 | 0.000 | 0.167 | 0.000 | 0.000 | -5.398 | 0.000 | -4.392 | -6.718 |
T S1 APARTMENT | 3.804 | -16.704 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 11.659 | 0.000 | 0.169 | 0.000 | 0.000 | -5.260 | 0.000 | -4.527 | -7.516 |
T S2 APARTMENT | 3.812 | -16.741 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 11.656 | 0.000 | 0.169 | 0.000 | 0.000 | -5.258 | 0.000 | -4.527 | -7.486 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.126 | 0.000 | 0.015 | 0.000 | 0.000 | -1.007 | 0.000 | -1.073 | -15.131 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.455 | 0.000 | 0.494 | 0.000 | 0.000 | -2.684 | 0.000 | -18.816 | -2.783 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.127 | 0.000 | 0.013 | 0.000 | 0.000 | -1.109 | 0.000 | -0.885 | -15.216 |
Total Facility | 91.833 | -469.403 | 0.000 | 0.000 | 87.330 | 128.627 | 294.692 | 234.350 | 0.000 | 4.432 | 132.316 | 0.000 | -172.674 | 0.000 | -124.382 | -207.121 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 16-AUG-16:30 | 0.00 | -2123.13 | 0.00 | 0.00 | 84.75 | 144.04 | 588.62 | 2257.79 | 0.00 | 58.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1010.58 |
G NW APARTMENT | 26-JUN-17:23 | 0.00 | -1949.14 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 2136.83 | 0.00 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1198.00 |
OFFICE | 28-SEP-12:45 | 0.00 | -3484.96 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2573.06 | 0.00 | 10.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1332.79 |
G NE APARTMENT | 26-JUN-18:15 | 0.00 | -1401.36 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 843.49 | 0.00 | 73.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.20 |
G N1 APARTMENT | 26-JUN-18:30 | 0.00 | -1122.27 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 660.00 | 0.00 | 47.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -504.83 |
G N2 APARTMENT | 26-JUN-18:30 | 0.00 | -1110.17 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 660.19 | 0.00 | 47.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -517.12 |
G S1 APARTMENT | 28-SEP-13:00 | 0.00 | -1471.49 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2288.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1274.87 |
G S2 APARTMENT | 28-SEP-13:00 | 0.00 | -1461.89 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2288.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1284.62 |
M SW APARTMENT | 16-AUG-16:23 | 0.00 | -5657.32 | 0.00 | 0.00 | 84.75 | 144.04 | 588.62 | 2247.72 | 0.00 | 83.94 | 2508.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 26-JUN-17:23 | 0.00 | -5366.32 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 2121.48 | 0.00 | 122.58 | 2197.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 28-SEP-13:15 | 0.00 | -4920.71 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2412.58 | 0.00 | 17.44 | 2038.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 26-JUN-18:15 | 0.00 | -4133.06 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 832.43 | 0.00 | 105.29 | 2275.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 26-JUN-18:30 | 0.00 | -3340.75 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 651.60 | 0.00 | 68.02 | 1701.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 26-JUN-18:30 | 0.00 | -3319.02 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 651.72 | 0.00 | 68.02 | 1679.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 11-OCT-13:30 | 0.00 | -4424.90 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2189.98 | 0.00 | 82.08 | 1700.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 11-OCT-13:30 | 0.00 | -4430.52 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2189.94 | 0.00 | 82.08 | 1706.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 16-AUG-16:13 | 0.00 | -3832.96 | 0.00 | 0.00 | 84.75 | 144.04 | 588.62 | 2241.87 | 0.00 | 98.04 | 675.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 26-JUN-17:06 | 0.00 | -3640.30 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2130.78 | 0.00 | 178.67 | 405.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 16-AUG-13:00 | 0.00 | -3398.16 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1894.33 | 0.00 | 152.79 | 892.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 26-JUN-17:06 | 0.00 | -2796.49 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 812.25 | 0.00 | 178.67 | 880.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 26-JUN-17:06 | 0.00 | -2367.03 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 580.40 | 0.00 | 107.77 | 753.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 26-JUN-17:06 | 0.00 | -2345.05 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 580.69 | 0.00 | 107.77 | 731.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 28-SEP-13:15 | 0.00 | -2891.99 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2172.27 | 0.00 | 13.83 | 253.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 28-SEP-13:15 | 0.00 | -2901.78 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2172.13 | 0.00 | 13.83 | 263.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-17:12 | 0.00 | -65205.48 | 0.00 | 0.00 | 3261.57 | 6475.86 | 14071.03 | 22643.51 | 0.00 | 3064.21 | 15689.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 19-MAR-07:55 | 1666.58 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.73 | 0.00 | -742.24 | -436.29 |
G NW APARTMENT | 19-MAR-07:50 | 1679.05 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.30 | 0.00 | -742.24 | -451.18 |
OFFICE | 26-DEC-07:01 | 4749.39 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.89 | 0.00 | -107.81 | -4843.25 |
G NE APARTMENT | 21-DEC-23:15 | 1693.79 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1020.07 | 0.00 | -609.87 | -630.94 |
G N1 APARTMENT | 01-MAY-06:01 | 1527.23 | 0.00 | 0.00 | 0.00 | 163.29 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.45 | 0.00 | -95.58 | -2010.72 |
G N2 APARTMENT | 01-MAY-06:01 | 1534.67 | 0.00 | 0.00 | 0.00 | 163.30 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.46 | 0.00 | -95.58 | -2018.16 |
G S1 APARTMENT | 23-OCT-07:01 | 1223.32 | 0.00 | 0.00 | 0.00 | 74.07 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -363.61 | 0.00 | -88.43 | -1277.06 |
G S2 APARTMENT | 01-MAY-06:01 | 1486.20 | 0.00 | 0.00 | 0.00 | 163.22 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.69 | 0.00 | -95.58 | -1922.38 |
M SW APARTMENT | 22-DEC-04:00 | 3076.06 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.54 | 0.00 | -659.39 | -1703.88 |
M NW APARTMENT | 21-DEC-23:15 | 3472.68 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1025.94 | 0.00 | -876.87 | -2136.95 |
M SE APARTMENT | 22-DEC-04:00 | 3125.57 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1123.87 | 0.00 | -659.39 | -1770.06 |
M NE APARTMENT | 21-DEC-23:15 | 3585.86 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1040.51 | 0.00 | -876.87 | -2235.57 |
M N1 APARTMENT | 05-MAR-07:06 | 2008.99 | 0.00 | 0.00 | 0.00 | 161.22 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -414.06 | 0.00 | -129.71 | -2102.67 |
M N2 APARTMENT | 02-FEB-08:01 | 2446.15 | 0.00 | 0.00 | 0.00 | 74.11 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -356.77 | 0.00 | -133.45 | -2461.75 |
M S1 APARTMENT | 19-DEC-22:06 | 1933.45 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.43 | 0.00 | -304.10 | -1710.93 |
M S2 APARTMENT | 19-DEC-22:06 | 1934.69 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.42 | 0.00 | -304.10 | -1712.19 |
T SW APARTMENT | 22-DEC-04:00 | 3140.68 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1113.59 | 0.00 | -872.97 | -1581.87 |
T NW APARTMENT | 22-DEC-04:00 | 3232.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1084.22 | 0.00 | -872.97 | -1702.73 |
T SE APARTMENT | 22-DEC-04:00 | 3150.01 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1096.44 | 0.00 | -872.97 | -1608.35 |
T NE APARTMENT | 21-DEC-23:00 | 3244.86 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.41 | 0.00 | -1264.52 | -1669.95 |
T N1 APARTMENT | 22-DEC-04:00 | 2294.32 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -648.97 | 0.00 | -526.57 | -1546.53 |
T N2 APARTMENT | 22-DEC-04:00 | 2295.46 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -648.95 | 0.00 | -526.57 | -1547.68 |
T S1 APARTMENT | 22-DEC-04:00 | 2196.41 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.35 | 0.00 | -526.57 | -1419.23 |
T S2 APARTMENT | 22-DEC-04:00 | 2197.71 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.33 | 0.00 | -526.57 | -1420.56 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-DEC-04:00 | 49446.11 | 0.00 | 0.00 | 0.00 | 4362.44 | 2334.74 | 5313.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21661.06 | 0.00 | -13038.80 | -26757.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Sec1.1A-General InformationData | |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 48.00 |
Number of hours cooling loads not met | 2.00 |
Number of hours not met | 50.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 218.92 | 96671.03 | 0.00 | 0.00 |
Space Cooling | 123.12 | 19196.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 255.72 | 8108.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 414.94 | 29773.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1509.60 | 218.92 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1509.60 |
Natural Gas | 0.00 | 218.92 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1728.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 39.28 |
Fans-Interior | 81.58 |
Service Water Heating | 132.37 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.57 |
Subtotal | 481.59 |
Natural Gas [MJ/m2] | |
Space Heating | 69.84 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 69.84 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.55 |
Space Heating | 12.66 |
Space Cooling | 7.12 |
Fans-Interior | 14.79 |
Service Water Heating | 24.01 |
Receptacle Equipment | 29.59 |
Miscellaneous | 2.28 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.206588 |
G NW APARTMENT DIRECT AIR | 0.199625 |
OFFICE DIRECT AIR | 0.521315 |
G NE APARTMENT DIRECT AIR | 0.140107 |
G N1 APARTMENT DIRECT AIR | 0.116388 |
G N2 APARTMENT DIRECT AIR | 0.114989 |
G S1 APARTMENT DIRECT AIR | 0.120542 |
G S2 APARTMENT DIRECT AIR | 0.124231 |
M SW APARTMENT DIRECT AIR | 0.564452 |
M NW APARTMENT DIRECT AIR | 0.540631 |
M SE APARTMENT DIRECT AIR | 0.471367 |
M NE APARTMENT DIRECT AIR | 0.404067 |
M N1 APARTMENT DIRECT AIR | 0.330154 |
M N2 APARTMENT DIRECT AIR | 0.327716 |
M S1 APARTMENT DIRECT AIR | 0.352035 |
M S2 APARTMENT DIRECT AIR | 0.353364 |
T SW APARTMENT DIRECT AIR | 0.378307 |
T NW APARTMENT DIRECT AIR | 0.356488 |
T SE APARTMENT DIRECT AIR | 0.337840 |
T NE APARTMENT DIRECT AIR | 0.277491 |
T N1 APARTMENT DIRECT AIR | 0.223706 |
T N2 APARTMENT DIRECT AIR | 0.221436 |
T S1 APARTMENT DIRECT AIR | 0.277883 |
T S2 APARTMENT DIRECT AIR | 0.278693 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.206588 |
SPLIT GNW MAIN BRANCH | 0.199625 |
SPLIT OFFICE MAIN BRANCH | 0.521315 |
SPLIT GNE MAIN BRANCH | 0.140107 |
SPLIT GN1 MAIN BRANCH | 0.116388 |
SPLIT GN2 MAIN BRANCH | 0.114989 |
SPLIT GS1 MAIN BRANCH | 0.120542 |
SPLIT GS2 MAIN BRANCH | 0.124231 |
SPLIT MSW MAIN BRANCH | 0.564452 |
SPLIT MNW MAIN BRANCH | 0.540631 |
SPLIT MSE MAIN BRANCH | 0.471367 |
SPLIT MNE MAIN BRANCH | 0.404067 |
SPLIT MN1 MAIN BRANCH | 0.330154 |
SPLIT MN2 MAIN BRANCH | 0.327716 |
SPLIT MS1 MAIN BRANCH | 0.352035 |
SPLIT MS2 MAIN BRANCH | 0.353364 |
SPLIT TSW MAIN BRANCH | 0.378307 |
SPLIT TNW MAIN BRANCH | 0.356488 |
SPLIT TSE MAIN BRANCH | 0.337840 |
SPLIT TNE MAIN BRANCH | 0.277491 |
SPLIT TN1 MAIN BRANCH | 0.223706 |
SPLIT TN2 MAIN BRANCH | 0.221436 |
SPLIT TS1 MAIN BRANCH | 0.277883 |
SPLIT TS2 MAIN BRANCH | 0.278693 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.206588 |
SPLIT GNW | 0.199625 |
SPLIT OFFICE | 0.521315 |
SPLIT GNE | 0.140107 |
SPLIT GN1 | 0.116388 |
SPLIT GN2 | 0.114989 |
SPLIT GS1 | 0.120542 |
SPLIT GS2 | 0.124231 |
SPLIT MSW | 0.564452 |
SPLIT MNW | 0.540631 |
SPLIT MSE | 0.471367 |
SPLIT MNE | 0.404067 |
SPLIT MN1 | 0.330154 |
SPLIT MN2 | 0.327716 |
SPLIT MS1 | 0.352035 |
SPLIT MS2 | 0.353364 |
SPLIT TSW | 0.378307 |
SPLIT TNW | 0.356488 |
SPLIT TSE | 0.337840 |
SPLIT TNE | 0.277491 |
SPLIT TN1 | 0.223706 |
SPLIT TN2 | 0.221436 |
SPLIT TS1 | 0.277883 |
SPLIT TS2 | 0.278693 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.206588 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.199625 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.521315 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.140107 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.116388 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.114989 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.120542 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.124231 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.564452 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.540631 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.471367 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.404067 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.330154 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.327716 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.352035 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.353364 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.378307 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.356488 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.337840 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.277491 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.223706 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.221436 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.277883 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.278693 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.206588 | 3419.77 | 0.798655 |
SPLIT GNW COOLING COIL | 0.199625 | 3304.49 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.521315 | 8629.62 | 0.798655 |
SPLIT GNE COOLING COIL | 0.140107 | 2319.27 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.116388 | 1926.64 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.114989 | 1903.47 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.120542 | 1995.40 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.124231 | 2056.47 | 0.798655 |
SPLIT MSW COOLING COIL | 0.564452 | 9343.68 | 0.798655 |
SPLIT MNW COOLING COIL | 0.540631 | 8949.36 | 0.798655 |
SPLIT MSE COOLING COIL | 0.471367 | 7802.80 | 0.798655 |
SPLIT MNE COOLING COIL | 0.404067 | 6688.75 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.330154 | 5465.22 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.327716 | 5424.87 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.352035 | 5827.43 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.353364 | 5849.43 | 0.798655 |
SPLIT TSW COOLING COIL | 0.378307 | 6262.32 | 0.798655 |
SPLIT TNW COOLING COIL | 0.356488 | 5901.14 | 0.798655 |
SPLIT TSE COOLING COIL | 0.337840 | 5592.45 | 0.798655 |
SPLIT TNE COOLING COIL | 0.277491 | 4593.47 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.223706 | 3703.13 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.221436 | 3665.56 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.277883 | 4599.95 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.278693 | 4613.35 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.206588 | 0.206588 | 0.206588 | 0.206588 | 2691.84 | 3419.77 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.199625 | 0.199625 | 0.199625 | 0.199625 | 2644.46 | 3304.49 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.521315 | 0.521315 | 0.521315 | 0.521315 | 5028.11 | 8629.62 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.140107 | 0.140107 | 0.140107 | 0.140107 | 2644.46 | 2319.27 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.116388 | 0.116388 | 0.116388 | 0.116388 | 1975.43 | 1926.64 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.114989 | 0.114989 | 0.114989 | 0.114989 | 1975.43 | 1903.47 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.120542 | 0.120542 | 0.120542 | 0.120542 | 1988.82 | 1995.40 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.124231 | 0.124231 | 0.124231 | 0.124231 | 2104.98 | 2056.47 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.564452 | 0.564452 | 0.564452 | 0.564452 | 5276.97 | 9343.68 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.540631 | 0.540631 | 0.540631 | 0.540631 | 5248.86 | 8949.36 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.471367 | 0.471367 | 0.471367 | 0.471367 | 5276.97 | 7802.80 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.404067 | 0.404067 | 0.404067 | 0.404067 | 5248.86 | 6688.75 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.330154 | 0.330154 | 0.330154 | 0.330154 | 3608.60 | 5465.22 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.327716 | 0.327716 | 0.327716 | 0.327716 | 3608.60 | 5424.87 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.352035 | 0.352035 | 0.352035 | 0.352035 | 3639.29 | 5827.43 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.353364 | 0.353364 | 0.353364 | 0.353364 | 3639.29 | 5849.43 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.378307 | 0.378307 | 0.378307 | 0.378307 | 4094.63 | 6262.32 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.356488 | 0.356488 | 0.356488 | 0.356488 | 4081.50 | 5901.14 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.337840 | 0.337840 | 0.337840 | 0.337840 | 4094.63 | 5592.45 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.277491 | 0.277491 | 0.277491 | 0.277491 | 4081.50 | 4593.47 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.223706 | 0.223706 | 0.223706 | 0.223706 | 3239.53 | 3703.13 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.221436 | 0.221436 | 0.221436 | 0.221436 | 3239.53 | 3665.56 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.277883 | 0.277883 | 0.277883 | 0.277883 | 3251.41 | 4599.95 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.278693 | 0.278693 | 0.278693 | 0.278693 | 3251.41 | 4613.35 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.206588 |
SPLIT GNW SUPPLY FAN | 0.199625 |
SPLIT OFFICE SUPPLY FAN | 0.521315 |
SPLIT GNE SUPPLY FAN | 0.140107 |
SPLIT GN1 SUPPLY FAN | 0.116388 |
SPLIT GN2 SUPPLY FAN | 0.114989 |
SPLIT GS1 SUPPLY FAN | 0.120542 |
SPLIT GS2 SUPPLY FAN | 0.124231 |
SPLIT MSW SUPPLY FAN | 0.564452 |
SPLIT MNW SUPPLY FAN | 0.540631 |
SPLIT MSE SUPPLY FAN | 0.471367 |
SPLIT MNE SUPPLY FAN | 0.404067 |
SPLIT MN1 SUPPLY FAN | 0.330154 |
SPLIT MN2 SUPPLY FAN | 0.327716 |
SPLIT MS1 SUPPLY FAN | 0.352035 |
SPLIT MS2 SUPPLY FAN | 0.353364 |
SPLIT TSW SUPPLY FAN | 0.378307 |
SPLIT TNW SUPPLY FAN | 0.356488 |
SPLIT TSE SUPPLY FAN | 0.337840 |
SPLIT TNE SUPPLY FAN | 0.277491 |
SPLIT TN1 SUPPLY FAN | 0.223706 |
SPLIT TN2 SUPPLY FAN | 0.221436 |
SPLIT TS1 SUPPLY FAN | 0.277883 |
SPLIT TS2 SUPPLY FAN | 0.278693 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2691.84 |
SPLIT GNW HEATING COIL | 2644.46 |
SPLIT OFFICE HEATING COIL | 5028.11 |
SPLIT GNE HEATING COIL | 2644.46 |
SPLIT GN1 HEATING COIL | 1975.43 |
SPLIT GN2 HEATING COIL | 1975.43 |
SPLIT GS1 HEATING COIL | 1988.82 |
SPLIT GS2 HEATING COIL | 2104.98 |
SPLIT MSW HEATING COIL | 5276.97 |
SPLIT MNW HEATING COIL | 5248.86 |
SPLIT MSE HEATING COIL | 5276.97 |
SPLIT MNE HEATING COIL | 5248.86 |
SPLIT MN1 HEATING COIL | 3608.60 |
SPLIT MN2 HEATING COIL | 3608.60 |
SPLIT MS1 HEATING COIL | 3639.29 |
SPLIT MS2 HEATING COIL | 3639.29 |
SPLIT TSW HEATING COIL | 4094.63 |
SPLIT TNW HEATING COIL | 4081.50 |
SPLIT TSE HEATING COIL | 4094.63 |
SPLIT TNE HEATING COIL | 4081.50 |
SPLIT TN1 HEATING COIL | 3239.53 |
SPLIT TN2 HEATING COIL | 3239.53 |
SPLIT TS1 HEATING COIL | 3251.41 |
SPLIT TS2 HEATING COIL | 3251.41 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 0.85 |
February | 22.18 | -0.2 |
March | 22.43 | 4.82 |
April | 22.33 | 6.08 |
May | 23.27 | 13.74 |
June | 24.38 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.29 | 18.54 |
October | 22.91 | 7.12 |
November | 22.47 | 3.03 |
December | 22.11 | -1.0 |
Annual Sum or Average | 23.12 | 10.02 |
Minimum of Months | 22.11 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 0.85 |
February | 21.77 | -0.2 |
March | 22.06 | 4.82 |
April | 22.09 | 6.08 |
May | 23.16 | 13.74 |
June | 24.38 | 22.16 |
July | 24.40 | 22.71 |
August | 24.39 | 21.74 |
September | 24.23 | 18.54 |
October | 22.43 | 7.12 |
November | 21.90 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 22.87 | 10.02 |
Minimum of Months | 21.77 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 0.85 |
February | 21.40 | -0.2 |
March | 22.11 | 4.82 |
April | 22.26 | 6.08 |
May | 23.54 | 13.74 |
June | 23.90 | 22.16 |
July | 23.90 | 22.71 |
August | 23.90 | 21.74 |
September | 23.87 | 18.54 |
October | 22.91 | 7.12 |
November | 22.18 | 3.03 |
December | 21.08 | -1.0 |
Annual Sum or Average | 22.74 | 10.02 |
Minimum of Months | 21.08 | -1.0 |
Maximum of Months | 23.90 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 0.85 |
February | 21.75 | -0.2 |
March | 22.00 | 4.82 |
April | 22.05 | 6.08 |
May | 23.06 | 13.74 |
June | 24.37 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.21 | 18.54 |
October | 22.33 | 7.12 |
November | 21.85 | 3.03 |
December | 21.74 | -1.0 |
Annual Sum or Average | 22.83 | 10.02 |
Minimum of Months | 21.74 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 0.85 |
February | 21.73 | -0.2 |
March | 21.92 | 4.82 |
April | 21.95 | 6.08 |
May | 22.91 | 13.74 |
June | 24.37 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.24 | 18.54 |
October | 22.29 | 7.12 |
November | 21.83 | 3.03 |
December | 21.74 | -1.0 |
Annual Sum or Average | 22.80 | 10.02 |
Minimum of Months | 21.73 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 0.85 |
February | 21.73 | -0.2 |
March | 21.91 | 4.82 |
April | 21.95 | 6.08 |
May | 22.91 | 13.74 |
June | 24.37 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.24 | 18.54 |
October | 22.28 | 7.12 |
November | 21.83 | 3.03 |
December | 21.74 | -1.0 |
Annual Sum or Average | 22.80 | 10.02 |
Minimum of Months | 21.73 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 0.85 |
February | 22.18 | -0.2 |
March | 22.39 | 4.82 |
April | 22.24 | 6.08 |
May | 23.10 | 13.74 |
June | 24.37 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.31 | 18.54 |
October | 22.95 | 7.12 |
November | 22.49 | 3.03 |
December | 22.14 | -1.0 |
Annual Sum or Average | 23.11 | 10.02 |
Minimum of Months | 22.14 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 0.85 |
February | 22.18 | -0.2 |
March | 22.39 | 4.82 |
April | 22.25 | 6.08 |
May | 23.11 | 13.74 |
June | 24.37 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.31 | 18.54 |
October | 22.95 | 7.12 |
November | 22.49 | 3.03 |
December | 22.14 | -1.0 |
Annual Sum or Average | 23.11 | 10.02 |
Minimum of Months | 22.14 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.48 | 0.85 |
February | 23.11 | -0.2 |
March | 23.17 | 4.82 |
April | 23.35 | 6.08 |
May | 24.30 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.38 | 18.54 |
October | 23.78 | 7.12 |
November | 23.52 | 3.03 |
December | 22.82 | -1.0 |
Annual Sum or Average | 23.76 | 10.02 |
Minimum of Months | 22.82 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 0.85 |
February | 22.16 | -0.2 |
March | 22.73 | 4.82 |
April | 23.05 | 6.08 |
May | 24.28 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.35 | 18.54 |
October | 23.46 | 7.12 |
November | 22.55 | 3.03 |
December | 21.98 | -1.0 |
Annual Sum or Average | 23.35 | 10.02 |
Minimum of Months | 21.98 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 0.85 |
February | 23.06 | -0.2 |
March | 23.16 | 4.82 |
April | 23.31 | 6.08 |
May | 24.29 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.37 | 18.54 |
October | 23.74 | 7.12 |
November | 23.45 | 3.03 |
December | 22.76 | -1.0 |
Annual Sum or Average | 23.73 | 10.02 |
Minimum of Months | 22.76 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 0.85 |
February | 22.09 | -0.2 |
March | 22.66 | 4.82 |
April | 22.98 | 6.08 |
May | 24.24 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.34 | 18.54 |
October | 23.39 | 7.12 |
November | 22.40 | 3.03 |
December | 21.89 | -1.0 |
Annual Sum or Average | 23.29 | 10.02 |
Minimum of Months | 21.89 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 0.85 |
February | 22.14 | -0.2 |
March | 22.72 | 4.82 |
April | 23.14 | 6.08 |
May | 24.32 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.37 | 18.54 |
October | 23.57 | 7.12 |
November | 22.61 | 3.03 |
December | 22.00 | -1.0 |
Annual Sum or Average | 23.38 | 10.02 |
Minimum of Months | 22.00 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.36 | 0.85 |
February | 22.14 | -0.2 |
March | 22.72 | 4.82 |
April | 23.14 | 6.08 |
May | 24.32 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.37 | 18.54 |
October | 23.56 | 7.12 |
November | 22.59 | 3.03 |
December | 21.99 | -1.0 |
Annual Sum or Average | 23.37 | 10.02 |
Minimum of Months | 21.99 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 0.85 |
February | 23.31 | -0.2 |
March | 23.34 | 4.82 |
April | 23.54 | 6.08 |
May | 24.34 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.39 | 18.54 |
October | 23.91 | 7.12 |
November | 23.75 | 3.03 |
December | 23.12 | -1.0 |
Annual Sum or Average | 23.89 | 10.02 |
Minimum of Months | 23.12 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 0.85 |
February | 23.30 | -0.2 |
March | 23.34 | 4.82 |
April | 23.54 | 6.08 |
May | 24.34 | 13.74 |
June | 24.40 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.39 | 18.54 |
October | 23.91 | 7.12 |
November | 23.74 | 3.03 |
December | 23.12 | -1.0 |
Annual Sum or Average | 23.89 | 10.02 |
Minimum of Months | 23.12 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 0.85 |
February | 22.58 | -0.2 |
March | 22.80 | 4.82 |
April | 22.80 | 6.08 |
May | 23.95 | 13.74 |
June | 24.39 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.24 | 18.54 |
October | 23.12 | 7.12 |
November | 22.84 | 3.03 |
December | 22.35 | -1.0 |
Annual Sum or Average | 23.38 | 10.02 |
Minimum of Months | 22.35 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 0.85 |
February | 22.02 | -0.2 |
March | 22.52 | 4.82 |
April | 22.62 | 6.08 |
May | 23.90 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.17 | 18.54 |
October | 22.83 | 7.12 |
November | 22.25 | 3.03 |
December | 21.92 | -1.0 |
Annual Sum or Average | 23.13 | 10.02 |
Minimum of Months | 21.92 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 0.85 |
February | 22.58 | -0.2 |
March | 22.81 | 4.82 |
April | 22.82 | 6.08 |
May | 23.94 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.23 | 18.54 |
October | 23.11 | 7.12 |
November | 22.81 | 3.03 |
December | 22.34 | -1.0 |
Annual Sum or Average | 23.38 | 10.02 |
Minimum of Months | 22.34 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 0.85 |
February | 21.97 | -0.2 |
March | 22.47 | 4.82 |
April | 22.61 | 6.08 |
May | 23.84 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.14 | 18.54 |
October | 22.79 | 7.12 |
November | 22.16 | 3.03 |
December | 21.87 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.87 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 0.85 |
February | 21.94 | -0.2 |
March | 22.46 | 4.82 |
April | 22.60 | 6.08 |
May | 23.92 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.17 | 18.54 |
October | 22.79 | 7.12 |
November | 22.15 | 3.03 |
December | 21.87 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.87 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 0.85 |
February | 21.94 | -0.2 |
March | 22.46 | 4.82 |
April | 22.60 | 6.08 |
May | 23.91 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.16 | 18.54 |
October | 22.79 | 7.12 |
November | 22.15 | 3.03 |
December | 21.86 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.86 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 0.85 |
February | 22.67 | -0.2 |
March | 22.88 | 4.82 |
April | 22.88 | 6.08 |
May | 24.02 | 13.74 |
June | 24.39 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.27 | 18.54 |
October | 23.22 | 7.12 |
November | 22.94 | 3.03 |
December | 22.44 | -1.0 |
Annual Sum or Average | 23.45 | 10.02 |
Minimum of Months | 22.44 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 0.85 |
February | 22.67 | -0.2 |
March | 22.89 | 4.82 |
April | 22.88 | 6.08 |
May | 24.02 | 13.74 |
June | 24.39 | 22.16 |
July | 24.40 | 22.71 |
August | 24.40 | 21.74 |
September | 24.27 | 18.54 |
October | 23.22 | 7.12 |
November | 22.94 | 3.03 |
December | 22.44 | -1.0 |
Annual Sum or Average | 23.45 | 10.02 |
Minimum of Months | 22.44 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.40 | 0.85 |
February | 22.25 | -0.2 |
March | 23.10 | 4.82 |
April | 23.36 | 6.08 |
May | 25.45 | 13.74 |
June | 26.87 | 22.16 |
July | 26.92 | 22.71 |
August | 26.81 | 21.74 |
September | 26.16 | 18.54 |
October | 23.72 | 7.12 |
November | 22.81 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 24.31 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 26.92 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | 0.85 |
February | 20.50 | -0.2 |
March | 21.38 | 4.82 |
April | 21.57 | 6.08 |
May | 23.33 | 13.74 |
June | 26.07 | 22.16 |
July | 26.30 | 22.71 |
August | 26.17 | 21.74 |
September | 25.70 | 18.54 |
October | 22.37 | 7.12 |
November | 21.23 | 3.03 |
December | 20.33 | -1.0 |
Annual Sum or Average | 22.99 | 10.02 |
Minimum of Months | 20.33 | -1.0 |
Maximum of Months | 26.30 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.69 | 0.85 |
February | 24.27 | -0.2 |
March | 24.79 | 4.82 |
April | 25.07 | 6.08 |
May | 26.51 | 13.74 |
June | 27.05 | 22.16 |
July | 27.06 | 22.71 |
August | 27.02 | 21.74 |
September | 26.85 | 18.54 |
October | 25.69 | 7.12 |
November | 24.85 | 3.03 |
December | 23.94 | -1.0 |
Annual Sum or Average | 25.66 | 10.02 |
Minimum of Months | 23.94 | -1.0 |
Maximum of Months | 27.06 | 22.71 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:29
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.123787E+12 | 76186.610 | 24-JAN-18:30 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 3276.078 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27264.087 | 0.000 | 0.000 | 0.000 |
February | 0.111660E+12 | 75266.471 | 18-FEB-18:15 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 3683.691 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25936.335 | 0.000 | 0.000 | 0.000 |
March | 0.124402E+12 | 78547.652 | 15-MAR-17:00 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 7664.076 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27745.460 | 0.000 | 0.000 | 0.000 |
April | 0.117798E+12 | 74914.936 | 08-APR-17:15 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 7183.001 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24593.821 | 0.000 | 0.000 | 0.000 |
May | 0.126566E+12 | 80163.307 | 17-MAY-17:30 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 11177.337 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25847.855 | 0.000 | 0.000 | 0.000 |
June | 0.136067E+12 | 92107.982 | 14-JUN-17:00 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 19196.011 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29773.856 | 0.000 | 0.000 | 0.000 |
July | 0.140370E+12 | 90061.562 | 18-JUL-17:45 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 18005.172 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28918.276 | 0.000 | 0.000 | 0.000 |
August | 0.138780E+12 | 88694.714 | 25-AUG-17:00 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 15857.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29699.092 | 0.000 | 0.000 | 0.000 |
September | 0.128802E+12 | 86015.242 | 08-SEP-17:30 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 14089.625 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28787.502 | 0.000 | 0.000 | 0.000 |
October | 0.122139E+12 | 79525.283 | 10-OCT-17:45 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 8595.651 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25283.187 | 0.000 | 0.000 | 0.000 |
November | 0.117512E+12 | 76170.468 | 07-NOV-18:15 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 4389.787 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26134.236 | 0.000 | 0.000 | 0.000 |
December | 0.121719E+12 | 74824.316 | 13-DEC-18:15 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 284.250 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28893.621 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.150960E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.111660E+12 | 74824.316 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 284.250 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24593.821 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.140370E+12 | 92107.982 | 8572.775 | 26456.413 | 8108.927 | 0.000 | 19196.011 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29773.856 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:29
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.321688E+11 | 62554.444 | 05-JAN-02:00 | 62554.444 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 62554.444 |
February | 0.404905E+11 | 75780.910 | 12-FEB-04:00 | 75780.910 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 75780.910 |
March | 0.263945E+11 | 84910.049 | 19-MAR-06:00 | 84910.049 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 84910.049 |
April | 0.186656E+11 | 48301.500 | 17-APR-02:00 | 48301.500 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 48301.500 |
May | 0.116688E+10 | 14316.451 | 03-MAY-02:00 | 14316.451 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14316.451 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.268916E+09 | 8917.349 | 22-SEP-04:00 | 8917.349 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8917.349 |
October | 0.158302E+11 | 52720.629 | 31-OCT-23:00 | 52720.629 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 52720.629 |
November | 0.252277E+11 | 66974.089 | 30-NOV-05:00 | 66974.089 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 66974.089 |
December | 0.587030E+11 | 96671.034 | 22-DEC-03:00 | 96671.034 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 96671.034 |
Annual Sum or Average | 0.218916E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.587030E+11 | 96671.034 | 96671.034 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 96671.034 |