Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2018-10-19 09:20:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1535.24 | 489.77 | 543.64 |
Net Site Energy | 1535.24 | 489.77 | 543.64 |
Total Source Energy | 4799.14 | 1531.01 | 1699.43 |
Net Source Energy | 4799.14 | 1531.01 | 1699.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 30.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 199.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 238.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 351.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1505.01 | 30.23 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 30.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 199.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 238.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 351.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 279.45 | 10.70 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 532.94 | 10.70 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 251.75 | 9.64 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 480.13 | 9.64 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1505.01 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1505.01 | 100.00 |
Total On-Site and Utility Electric Sources | 1505.01 | 100.00 |
Total Electricity End Uses | 1505.01 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 27.75 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 751.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-17:15 | 27-DEC-07:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 28542.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22280.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7565.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84025.21 | 28542.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28542.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22280.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7565.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 19149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 32.77 | 0.00 | 0.00 | 0.00 |
Cooling | 630.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 755.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1112.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4766.37 | 32.77 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 11.60 | 0.00 | 0.00 | 0.00 |
Cooling | 223.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 267.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 394.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1687.82 | 11.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 11.60 | 0.00 | 0.00 | 0.00 |
Cooling | 223.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 267.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 394.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1687.82 | 11.60 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.62_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 112.97 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 193.95 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.77 | 83.77 | 39.44 | |
Exterior Lighting Total | 2508.33 | 39.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3205.77 | 2560.31 | 645.47 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3204.89 | 2559.60 | 645.29 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8146.35 | 6506.12 | 1640.22 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2590.47 | 2068.89 | 521.58 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2093.23 | 1671.77 | 421.46 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2081.15 | 1662.12 | 419.03 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2042.14 | 1630.97 | 411.17 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2076.92 | 1658.74 | 418.18 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8143.66 | 6503.98 | 1639.68 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8122.01 | 6486.68 | 1635.32 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6918.74 | 5525.69 | 1393.05 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6795.03 | 5426.88 | 1368.14 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5425.79 | 4333.34 | 1092.45 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5405.61 | 4317.22 | 1088.39 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5333.47 | 4259.60 | 1073.87 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5313.38 | 4243.56 | 1069.82 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5390.20 | 4304.91 | 1085.29 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5307.39 | 4238.78 | 1068.62 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4799.58 | 3833.21 | 966.37 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4476.52 | 3575.20 | 901.32 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3636.06 | 2903.96 | 732.10 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3612.21 | 2884.91 | 727.30 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3838.12 | 3065.34 | 772.79 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3844.61 | 3070.51 | 774.09 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3054.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3053.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7760.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2467.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1994.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1982.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1945.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1978.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7758.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7737.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6591.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6473.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5168.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5149.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5081.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5061.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5135.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5056.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4572.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4264.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3463.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3441.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3656.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3662.6 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1752.44 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1732.44 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 3438.36 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1737.15 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 3335.95 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 3358.43 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 3348.81 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 3371.28 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2694.81 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2707.94 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2701.57 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2714.70 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2131.78 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2131.98 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2116.68 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2116.88 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 216.92 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 216.86 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 551.23 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.29 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 141.64 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 140.82 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 138.18 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 140.54 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 551.05 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 549.58 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 468.16 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 459.79 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 367.14 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.77 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.89 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 359.53 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.73 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 359.13 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.77 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.91 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.04 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 244.42 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.71 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 260.15 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1787.35 | 2144.82 | 0.161 | 0.194 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
G NW APARTMENT | 1786.86 | 2144.23 | 0.161 | 0.194 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63 | 0.00682 |
OFFICE | 4323.61 | 5188.34 | 0.410 | 0.492 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 32.05 | 0.00682 |
G NE APARTMENT | 1444.29 | 1733.15 | 0.130 | 0.156 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
G N1 APARTMENT | 1167.05 | 1400.46 | 0.105 | 0.126 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.01 | 0.00682 |
G N2 APARTMENT | 1160.32 | 1392.38 | 0.105 | 0.126 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.01 | 0.00682 |
G S1 APARTMENT | 1138.57 | 1366.29 | 0.103 | 0.123 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.01 | 0.00682 |
G S2 APARTMENT | 1157.95 | 1389.55 | 0.105 | 0.125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03 | 0.00682 |
M SW APARTMENT | 4540.44 | 5448.53 | 0.410 | 0.492 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
M NW APARTMENT | 4528.36 | 5434.04 | 0.409 | 0.491 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63 | 0.00682 |
M SE APARTMENT | 3857.50 | 4629.00 | 0.348 | 0.418 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
M NE APARTMENT | 3788.51 | 4546.21 | 0.342 | 0.410 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M N1 APARTMENT | 3025.09 | 3630.11 | 0.273 | 0.328 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
M N2 APARTMENT | 3013.84 | 3616.61 | 0.272 | 0.327 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
M S1 APARTMENT | 2973.62 | 3568.34 | 0.268 | 0.322 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M S2 APARTMENT | 2962.42 | 3554.90 | 0.267 | 0.321 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
T SW APARTMENT | 3005.29 | 3606.35 | 0.271 | 0.326 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
T NW APARTMENT | 2959.12 | 3550.94 | 0.267 | 0.321 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
T SE APARTMENT | 2676.00 | 3211.19 | 0.242 | 0.290 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T NE APARTMENT | 2495.87 | 2995.05 | 0.225 | 0.270 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T N1 APARTMENT | 2027.25 | 2432.70 | 0.183 | 0.220 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 35.30 | 0.00682 |
T N2 APARTMENT | 2013.96 | 2416.75 | 0.182 | 0.218 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 35.30 | 0.00682 |
T S1 APARTMENT | 2139.92 | 2567.90 | 0.193 | 0.232 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
T S2 APARTMENT | 2143.53 | 2572.24 | 0.194 | 0.232 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 839.84 | 1007.81 | 0.028 | 0.033 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
G NW APARTMENT | 845.50 | 1014.59 | 0.028 | 0.034 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
OFFICE | 2043.77 | 2452.53 | 0.065 | 0.078 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G NE APARTMENT | 849.48 | 1019.38 | 0.028 | 0.034 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
G N1 APARTMENT | 461.26 | 553.51 | 0.015 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
G N2 APARTMENT | 461.36 | 553.63 | 0.015 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
G S1 APARTMENT | 456.69 | 548.03 | 0.015 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
G S2 APARTMENT | 531.86 | 638.24 | 0.018 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M SW APARTMENT | 1581.99 | 1898.39 | 0.052 | 0.063 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M NW APARTMENT | 1601.00 | 1921.20 | 0.053 | 0.064 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M SE APARTMENT | 1592.86 | 1911.43 | 0.053 | 0.063 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M NE APARTMENT | 1611.86 | 1934.24 | 0.053 | 0.064 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M N1 APARTMENT | 631.57 | 757.88 | 0.021 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M N2 APARTMENT | 631.90 | 758.28 | 0.021 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M S1 APARTMENT | 611.55 | 733.86 | 0.020 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M S2 APARTMENT | 611.89 | 734.26 | 0.020 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T SW APARTMENT | 1659.34 | 1991.21 | 0.055 | 0.066 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T NW APARTMENT | 1670.45 | 2004.54 | 0.055 | 0.067 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T SE APARTMENT | 1665.06 | 1998.07 | 0.055 | 0.066 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T NE APARTMENT | 1676.17 | 2011.40 | 0.056 | 0.067 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T N1 APARTMENT | 1183.20 | 1419.84 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T N2 APARTMENT | 1183.37 | 1420.05 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T S1 APARTMENT | 1170.44 | 1404.52 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T S2 APARTMENT | 1170.60 | 1404.72 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.19 | 0.19 | 0.03 | 0.03 |
SPLIT GNW | 0.19 | 0.19 | 0.03 | 0.03 |
SPLIT OFFICE | 0.49 | 0.49 | 0.08 | 0.08 |
SPLIT GNE | 0.16 | 0.16 | 0.03 | 0.03 |
SPLIT GN1 | 0.13 | 0.13 | 0.03 | 0.03 |
SPLIT GN2 | 0.13 | 0.13 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS2 | 0.13 | 0.13 | 0.03 | 0.03 |
SPLIT MSW | 0.49 | 0.49 | 0.06 | 0.06 |
SPLIT MNW | 0.49 | 0.49 | 0.06 | 0.06 |
SPLIT MSE | 0.42 | 0.42 | 0.06 | 0.06 |
SPLIT MNE | 0.41 | 0.41 | 0.06 | 0.06 |
SPLIT MN1 | 0.33 | 0.33 | 0.05 | 0.05 |
SPLIT MN2 | 0.33 | 0.33 | 0.05 | 0.05 |
SPLIT MS1 | 0.32 | 0.32 | 0.05 | 0.05 |
SPLIT MS2 | 0.32 | 0.32 | 0.05 | 0.05 |
SPLIT TSW | 0.33 | 0.33 | 0.07 | 0.07 |
SPLIT TNW | 0.32 | 0.32 | 0.07 | 0.07 |
SPLIT TSE | 0.29 | 0.29 | 0.07 | 0.07 |
SPLIT TNE | 0.27 | 0.27 | 0.07 | 0.07 |
SPLIT TN1 | 0.22 | 0.22 | 0.05 | 0.05 |
SPLIT TN2 | 0.22 | 0.22 | 0.05 | 0.05 |
SPLIT TS1 | 0.23 | 0.23 | 0.05 | 0.05 |
SPLIT TS2 | 0.23 | 0.23 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2724.25 | 5167.25 | 227.50 |
G NW APARTMENT | 2757.50 | 5476.50 | 404.00 |
OFFICE | 698.50 | 1248.25 | 0.50 |
G NE APARTMENT | 2759.00 | 5515.50 | 428.25 |
G N1 APARTMENT | 2415.00 | 5756.00 | 366.25 |
G N2 APARTMENT | 2417.00 | 5761.25 | 370.00 |
G S1 APARTMENT | 2477.75 | 5452.00 | 249.25 |
G S2 APARTMENT | 2549.25 | 5356.50 | 211.25 |
M SW APARTMENT | 3516.25 | 2213.50 | 66.50 |
M NW APARTMENT | 3243.00 | 3534.50 | 65.25 |
M SE APARTMENT | 3478.75 | 2224.00 | 68.50 |
M NE APARTMENT | 3238.50 | 3562.25 | 68.00 |
M N1 APARTMENT | 3042.00 | 3545.00 | 79.25 |
M N2 APARTMENT | 3041.75 | 3547.75 | 80.25 |
M S1 APARTMENT | 3314.75 | 1633.25 | 82.75 |
M S2 APARTMENT | 3315.50 | 1641.00 | 82.75 |
T SW APARTMENT | 3776.50 | 3482.25 | 257.00 |
T NW APARTMENT | 3760.25 | 4207.50 | 507.75 |
T SE APARTMENT | 3789.75 | 3451.25 | 268.25 |
T NE APARTMENT | 3787.50 | 4231.00 | 517.25 |
T N1 APARTMENT | 3431.00 | 4301.00 | 370.50 |
T N2 APARTMENT | 3434.25 | 4306.75 | 376.50 |
T S1 APARTMENT | 3516.75 | 3437.50 | 171.50 |
T S2 APARTMENT | 3518.25 | 3435.75 | 171.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4444.25 | 5814.50 | 751.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
G NW APARTMENT | 3.75 | 0.50 | 3.75 | 0.50 |
OFFICE | 0.00 | 19.50 | 0.00 | 0.00 |
G NE APARTMENT | 7.25 | 0.00 | 7.25 | 0.00 |
G N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
G N2 APARTMENT | 2.50 | 0.25 | 2.50 | 0.25 |
G S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T N2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T S1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T S2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 27.75 | 20.50 | 27.75 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.367 | 0.091 | 0.000 | 0.085 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.082 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.518 | 0.098 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.082 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.081 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.081 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.055 | 0.000 | 0.085 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.055 | 0.000 | 0.085 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.105 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.103 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.105 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.102 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.079 | 0.000 | 0.103 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.079 | 0.000 | 0.103 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.079 | 0.000 | 0.105 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.079 | 0.000 | 0.105 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.173 | 0.000 | 0.126 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.172 | 0.000 | 0.123 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.173 | 0.000 | 0.126 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.172 | 0.000 | 0.123 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.104 | 0.000 | 0.122 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.104 | 0.000 | 0.122 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.104 | 0.000 | 0.126 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.104 | 0.000 | 0.126 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.505 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.382 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.376 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.379 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.379 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.385 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.385 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1505.01 | 20935.55 | 01-JAN-03:45 | 84025.21 | 26-JUL-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 351.40 | 0.00 | 01-JAN-00:15 | 32133.44 | 01-JAN-08:30 |
WaterSystems:Electricity | 351.40 | 0.00 | 01-JAN-00:15 | 32133.44 | 01-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 351.40 | 0.00 | 01-JAN-00:15 | 32133.44 | 01-JAN-08:30 |
Fans:Electricity | 238.58 | 7565.25 | 01-JAN-17:15 | 7565.25 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
ElectricityPurchased:Plant | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
Cogeneration:ElectricityPurchased | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
ElectricityNet:Plant | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
Cogeneration:ElectricityNet | 1505.01 | 20935.55 | 16-JAN-04:00 | 84025.21 | 26-JUL-17:15 |
ExteriorLights:Electricity | 39.44 | 0.00 | 01-JAN-07:15 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.44 | 0.00 | 01-JAN-07:15 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 437.75 | 7565.25 | 28-JAN-08:30 | 30994.86 | 05-JUN-17:00 |
General:Fans:Electricity | 238.58 | 7565.25 | 01-JAN-17:15 | 7565.25 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 199.18 | 0.00 | 01-JAN-03:45 | 23429.61 | 05-JUN-17:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 30.23 | 0.00 | 01-JAN-10:15 | 28542.98 | 27-DEC-07:15 |
Gas:HVAC | 30.23 | 0.00 | 01-JAN-10:15 | 28542.98 | 27-DEC-07:15 |
Heating:Gas | 30.23 | 0.00 | 01-JAN-10:15 | 28542.98 | 27-DEC-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1454.62 | 1469.55 | 04-MAY-06:00 | 147752.45 | 15-JUN-17:15 |
EnergyTransfer:Building | 656.46 | 1469.55 | 04-MAY-06:00 | 65394.56 | 15-JUN-17:15 |
EnergyTransfer:Zone:G SW APARTMENT | 13.60 | 0.00 | 01-MAY-03:45 | 2094.85 | 19-SEP-16:15 |
Heating:EnergyTransfer | 17.82 | 0.00 | 01-JAN-09:00 | 11409.52 | 27-DEC-06:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 502.42 | 27-DEC-02:00 |
Cooling:EnergyTransfer | 638.64 | 1.23 | 10-NOV-06:15 | 64695.39 | 15-JUN-17:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 13.28 | 0.00 | 02-JAN-06:00 | 2094.85 | 19-SEP-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 11.56 | 0.00 | 20-NOV-11:00 | 2140.81 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.04 | 0.00 | 01-JAN-05:15 | 597.03 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 10.52 | 0.00 | 01-JAN-00:15 | 2140.81 | 15-JUN-17:15 |
EnergyTransfer:Zone:OFFICE | 26.02 | 0.05 | 07-APR-02:30 | 3940.97 | 27-AUG-10:30 |
Heating:EnergyTransfer:Zone:OFFICE | 5.07 | 0.00 | 01-JAN-00:15 | 855.11 | 05-JUN-17:45 |
Cooling:EnergyTransfer:Zone:OFFICE | 20.94 | 0.00 | 01-JAN-02:45 | 3940.97 | 27-AUG-10:30 |
EnergyTransfer:Zone:G NE APARTMENT | 11.65 | 0.04 | 26-OCT-21:45 | 1616.10 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.89 | 0.00 | 01-JAN-08:30 | 620.89 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 10.75 | 0.00 | 01-JAN-00:15 | 1616.10 | 15-JUN-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.06 | 0.00 | 26-MAY-02:00 | 1289.26 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 271.24 | 20-DEC-03:45 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 8.73 | 0.00 | 01-JAN-04:00 | 1289.26 | 15-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.06 | 0.02 | 03-OCT-03:30 | 1279.45 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 273.63 | 20-DEC-03:45 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 8.73 | 0.00 | 01-JAN-04:00 | 1279.45 | 15-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.60 | 0.04 | 05-MAY-00:15 | 1404.66 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 316.64 | 02-MAR-04:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 11.55 | 0.00 | 03-JAN-15:30 | 1404.66 | 19-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.13 | 0.03 | 10-APR-01:15 | 1417.91 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 312.60 | 02-MAR-04:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 12.09 | 0.00 | 03-JAN-15:30 | 1417.91 | 19-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 55.68 | 16.90 | 05-MAY-05:15 | 5276.73 | 19-SEP-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 239.10 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 55.67 | 0.00 | 31-JAN-16:30 | 5276.73 | 19-SEP-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 42.30 | 0.03 | 13-JAN-12:00 | 5478.86 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 465.55 | 28-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 42.18 | 0.00 | 01-JAN-14:00 | 5478.86 | 15-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 56.14 | 0.89 | 31-JAN-16:30 | 4478.13 | 19-SEP-13:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 160.79 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 56.14 | 0.00 | 31-JAN-16:30 | 4478.13 | 19-SEP-13:15 |
EnergyTransfer:Zone:M NE APARTMENT | 42.94 | 0.09 | 28-MAR-12:00 | 4362.23 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 583.41 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 42.84 | 0.00 | 01-JAN-14:00 | 4362.23 | 15-JUN-17:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 37.45 | 0.20 | 03-JAN-19:15 | 3459.88 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 159.63 | 05-FEB-16:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 37.44 | 0.00 | 02-JAN-15:00 | 3459.88 | 15-JUN-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 37.45 | 0.14 | 10-DEC-15:45 | 3444.18 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 159.87 | 05-FEB-16:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 37.44 | 0.00 | 02-JAN-15:00 | 3444.18 | 15-JUN-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 51.67 | 2.66 | 10-NOV-07:00 | 3757.62 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 20.75 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 51.67 | 0.00 | 10-NOV-06:15 | 3757.62 | 18-OCT-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 51.68 | 4.11 | 10-NOV-07:00 | 3762.56 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 19.52 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 51.68 | 0.00 | 10-NOV-06:15 | 3762.56 | 18-OCT-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 25.98 | 0.01 | 30-JAN-21:45 | 3418.70 | 15-JUN-16:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.17 | 0.00 | 01-JAN-00:15 | 1262.82 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 24.81 | 0.00 | 01-JAN-02:30 | 3418.70 | 15-JUN-16:30 |
EnergyTransfer:Zone:T NW APARTMENT | 22.15 | 0.03 | 22-MAR-18:45 | 3522.68 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.43 | 0.00 | 01-JAN-00:15 | 1335.41 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 19.72 | 0.00 | 01-JAN-01:00 | 3522.68 | 15-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 25.95 | 0.03 | 23-DEC-01:30 | 2906.37 | 19-SEP-13:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.10 | 0.00 | 01-JAN-00:15 | 1269.81 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 24.85 | 0.00 | 01-JAN-06:00 | 2906.37 | 19-SEP-13:15 |
EnergyTransfer:Zone:T NE APARTMENT | 21.93 | 0.01 | 11-JAN-21:30 | 2803.96 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.17 | 0.00 | 01-JAN-08:45 | 1404.12 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 19.76 | 0.00 | 01-JAN-00:15 | 2803.96 | 15-JUN-17:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.74 | 0.01 | 21-DEC-11:00 | 2366.53 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.01 | 0.00 | 01-JAN-00:15 | 873.09 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.73 | 0.00 | 01-JAN-04:00 | 2366.53 | 15-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.76 | 0.01 | 29-NOV-14:45 | 2349.08 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 880.93 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.74 | 0.00 | 01-JAN-03:45 | 2349.08 | 15-JUN-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.48 | 0.00 | 11-DEC-13:15 | 2494.77 | 19-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 813.66 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 22.17 | 0.00 | 02-JAN-06:00 | 2494.77 | 19-SEP-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.50 | 0.00 | 08-APR-05:45 | 2498.93 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 813.71 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 22.19 | 0.00 | 02-JAN-06:00 | 2498.93 | 19-SEP-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 798.16 | 0.00 | 23-FEB-18:45 | 83081.14 | 15-JUN-17:00 |
HeatingCoils:EnergyTransfer | 24.18 | 0.00 | 01-JAN-10:15 | 22834.38 | 27-DEC-07:15 |
CoolingCoils:EnergyTransfer | 773.97 | 0.00 | 01-JAN-03:45 | 83081.14 | 15-JUN-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.318 | -13.285 | 0.000 | 0.000 | 3.694 | 2.413 | 12.213 | 15.338 | 0.000 | 0.364 | 0.000 | 0.000 | -4.921 | 0.000 | -2.220 | -13.915 |
G NW APARTMENT | 1.040 | -10.521 | 0.000 | 0.000 | 3.737 | 2.413 | 12.213 | 8.757 | 0.000 | 0.362 | 0.000 | 0.000 | -4.990 | 0.000 | -2.059 | -10.953 |
OFFICE | 5.074 | -20.944 | 0.000 | 0.000 | 0.518 | 21.914 | 7.534 | 14.974 | 0.000 | 0.202 | 0.000 | 0.000 | -5.235 | 0.000 | -1.589 | -22.449 |
G NE APARTMENT | 0.893 | -10.753 | 0.000 | 0.000 | 3.748 | 2.413 | 12.213 | 8.636 | 0.000 | 0.362 | 0.000 | 0.000 | -4.747 | 0.000 | -2.046 | -10.720 |
G N1 APARTMENT | 0.329 | -8.729 | 0.000 | 0.000 | 3.748 | 2.413 | 12.213 | 3.166 | 0.000 | 0.235 | 0.000 | 0.000 | -3.046 | 0.000 | -1.464 | -8.864 |
G N2 APARTMENT | 0.325 | -8.731 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 3.165 | 0.000 | 0.235 | 0.000 | 0.000 | -3.044 | 0.000 | -1.464 | -8.860 |
G S1 APARTMENT | 0.045 | -11.551 | 0.000 | 0.000 | 3.693 | 2.413 | 12.213 | 9.820 | 0.000 | 0.235 | 0.000 | 0.000 | -2.972 | 0.000 | -1.642 | -12.254 |
G S2 APARTMENT | 0.042 | -12.088 | 0.000 | 0.000 | 3.691 | 2.413 | 12.213 | 9.810 | 0.000 | 0.235 | 0.000 | 0.000 | -2.979 | 0.000 | -1.646 | -11.691 |
M SW APARTMENT | 0.004 | -55.670 | 0.000 | 0.000 | 3.552 | 2.413 | 12.213 | 14.725 | 0.000 | 0.514 | 31.078 | 0.000 | -5.622 | 0.000 | -3.207 | 0.000 |
M NW APARTMENT | 0.118 | -42.178 | 0.000 | 0.000 | 3.597 | 2.413 | 12.213 | 8.259 | 0.000 | 0.512 | 23.931 | 0.000 | -5.738 | 0.000 | -3.126 | 0.000 |
M SE APARTMENT | 0.001 | -56.137 | 0.000 | 0.000 | 3.558 | 2.413 | 12.213 | 14.711 | 0.000 | 0.514 | 31.423 | 0.000 | -5.492 | 0.000 | -3.203 | 0.000 |
M NE APARTMENT | 0.096 | -42.841 | 0.000 | 0.000 | 3.608 | 2.413 | 12.213 | 8.110 | 0.000 | 0.512 | 24.459 | 0.000 | -5.458 | 0.000 | -3.113 | 0.000 |
M N1 APARTMENT | 0.008 | -37.440 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 2.882 | 0.000 | 0.328 | 21.914 | 0.000 | -3.611 | 0.000 | -2.284 | 0.000 |
M N2 APARTMENT | 0.008 | -37.443 | 0.000 | 0.000 | 3.578 | 2.413 | 12.213 | 2.881 | 0.000 | 0.328 | 21.913 | 0.000 | -3.608 | 0.000 | -2.283 | 0.000 |
M S1 APARTMENT | 0.000 | -51.673 | 0.000 | 0.000 | 3.535 | 2.413 | 12.213 | 9.428 | 0.000 | 0.331 | 29.506 | 0.000 | -3.414 | 0.000 | -2.339 | 0.000 |
M S2 APARTMENT | 0.000 | -51.677 | 0.000 | 0.000 | 3.536 | 2.413 | 12.213 | 9.428 | 0.000 | 0.331 | 29.508 | 0.000 | -3.413 | 0.000 | -2.339 | 0.000 |
T SW APARTMENT | 1.173 | -24.806 | 0.000 | 0.000 | 3.644 | 2.413 | 12.213 | 14.556 | 0.000 | 0.681 | 0.001 | 0.000 | -5.201 | 0.000 | -3.907 | -0.765 |
T NW APARTMENT | 2.425 | -19.724 | 0.000 | 0.000 | 3.680 | 2.413 | 12.213 | 8.151 | 0.000 | 0.678 | 0.000 | 0.000 | -5.277 | 0.000 | -3.771 | -0.789 |
T SE APARTMENT | 1.098 | -24.853 | 0.000 | 0.000 | 3.649 | 2.413 | 12.213 | 14.544 | 0.000 | 0.681 | 0.000 | 0.000 | -5.084 | 0.000 | -3.910 | -0.751 |
T NE APARTMENT | 2.170 | -19.761 | 0.000 | 0.000 | 3.692 | 2.413 | 12.213 | 8.045 | 0.000 | 0.678 | 0.000 | 0.000 | -5.041 | 0.000 | -3.764 | -0.644 |
T N1 APARTMENT | 1.014 | -16.727 | 0.000 | 0.000 | 3.681 | 2.413 | 12.213 | 2.866 | 0.000 | 0.437 | 0.040 | 0.000 | -3.261 | 0.000 | -2.675 | -0.000 |
T N2 APARTMENT | 1.022 | -16.739 | 0.000 | 0.000 | 3.682 | 2.413 | 12.213 | 2.864 | 0.000 | 0.437 | 0.042 | 0.000 | -3.258 | 0.000 | -2.676 | -0.000 |
T S1 APARTMENT | 0.307 | -22.173 | 0.000 | 0.000 | 3.631 | 2.413 | 12.213 | 9.339 | 0.000 | 0.440 | 0.000 | 0.000 | -3.171 | 0.000 | -2.811 | -0.188 |
T S2 APARTMENT | 0.310 | -22.194 | 0.000 | 0.000 | 3.631 | 2.413 | 12.213 | 9.337 | 0.000 | 0.440 | 0.000 | 0.000 | -3.170 | 0.000 | -2.811 | -0.169 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.204 | 0.000 | 0.047 | 0.000 | 0.000 | -0.570 | 0.000 | -0.559 | -16.193 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.717 | 0.000 | 1.496 | 0.000 | 0.000 | -1.456 | 0.000 | -10.407 | -13.685 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.209 | 0.000 | 0.041 | 0.000 | 0.000 | -0.650 | 0.000 | -0.475 | -16.195 |
Total Facility | 17.818 | -638.636 | 0.000 | 0.000 | 84.412 | 128.627 | 294.692 | 214.922 | 0.000 | 11.657 | 213.815 | 0.000 | -104.429 | 0.000 | -73.790 | -149.085 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 19-SEP-16:10 | 0.00 | -2095.46 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1900.00 | 0.00 | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -649.84 |
G NW APARTMENT | 15-JUN-17:06 | 0.00 | -2141.28 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1873.20 | 0.00 | 168.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -825.69 |
OFFICE | 18-JUN-06:01 | 0.00 | -7349.33 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 647.74 | 0.00 | 0.00 | 6149.65 | 0.00 | 0.00 | 0.00 | -22.62 | 0.00 |
G NE APARTMENT | 15-JUN-17:06 | 0.00 | -1616.57 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 816.18 | 0.00 | 168.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -293.38 |
G N1 APARTMENT | 15-JUN-17:25 | 0.00 | -1289.46 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 628.24 | 0.00 | 91.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -355.28 |
G N2 APARTMENT | 15-JUN-17:20 | 0.00 | -1279.65 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 628.40 | 0.00 | 91.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -365.25 |
G S1 APARTMENT | 19-SEP-13:30 | 0.00 | -1404.52 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1513.53 | 0.00 | 32.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.95 |
G S2 APARTMENT | 19-SEP-13:30 | 0.00 | -1417.76 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1513.26 | 0.00 | 32.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -580.44 |
M SW APARTMENT | 19-SEP-16:15 | 0.00 | -5278.96 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1880.86 | 0.00 | 39.98 | 2540.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 15-JUN-17:06 | 0.00 | -5480.38 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1846.18 | 0.00 | 242.33 | 2467.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 19-SEP-13:15 | 0.00 | -4477.78 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1790.02 | 0.00 | 78.40 | 2157.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 15-JUN-17:06 | 0.00 | -4363.74 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 804.28 | 0.00 | 242.33 | 2392.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 15-JUN-17:25 | 0.00 | -3460.73 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 617.95 | 0.00 | 131.46 | 1786.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 15-JUN-17:25 | 0.00 | -3445.04 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 618.04 | 0.00 | 131.46 | 1770.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 18-OCT-13:30 | 0.00 | -3757.29 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1651.62 | 0.00 | 19.48 | 1634.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 18-OCT-13:30 | 0.00 | -3762.23 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1651.59 | 0.00 | 19.48 | 1639.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 15-JUN-16:25 | 0.00 | -3418.97 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1714.38 | 0.00 | 339.63 | 547.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 15-JUN-17:06 | 0.00 | -3523.08 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1802.83 | 0.00 | 319.50 | 475.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 19-SEP-13:15 | 0.00 | -2906.17 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1749.52 | 0.00 | 103.22 | 601.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 15-JUN-17:06 | 0.00 | -2804.31 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 781.05 | 0.00 | 319.50 | 778.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 15-JUN-17:06 | 0.00 | -2366.98 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 588.28 | 0.00 | 192.72 | 661.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 15-JUN-17:06 | 0.00 | -2349.53 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 588.52 | 0.00 | 192.72 | 643.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 19-SEP-14:15 | 0.00 | -2494.55 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1291.15 | 0.00 | 54.93 | 657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 19-SEP-13:30 | 0.00 | -2498.72 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1465.98 | 0.00 | 61.88 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-17:06 | 0.00 | -64046.08 | 0.00 | 0.00 | 3261.48 | 6475.86 | 14071.03 | 19878.98 | 0.00 | 5062.58 | 15296.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 03-DEC-07:01 | 1402.10 | 0.00 | 0.00 | 0.00 | 163.32 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -129.40 | 0.00 | -14.28 | -1897.96 |
G NW APARTMENT | 28-FEB-07:01 | 1465.89 | 0.00 | 0.00 | 0.00 | 162.93 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -302.54 | 0.00 | -88.67 | -1713.83 |
OFFICE | 10-JAN-07:01 | 3036.11 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.87 | 0.00 | -172.21 | -2844.60 |
G NE APARTMENT | 05-FEB-07:14 | 632.22 | 0.00 | 0.00 | 0.00 | 161.22 | 93.63 | 382.60 | 167.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.35 | -1335.72 |
G N1 APARTMENT | 11-JAN-07:01 | 1009.34 | 0.00 | 0.00 | 0.00 | 161.37 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -333.55 | 0.00 | -91.32 | -1222.07 |
G N2 APARTMENT | 25-JAN-07:01 | 1214.66 | 0.00 | 0.00 | 0.00 | 163.21 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -247.52 | 0.00 | -123.13 | -1483.46 |
G S1 APARTMENT | 27-JAN-06:25 | 714.67 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -447.36 | 0.00 | -105.20 | -770.46 |
G S2 APARTMENT | 27-JAN-06:08 | 727.05 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -440.77 | 0.00 | -99.53 | -795.11 |
M SW APARTMENT | 10-NOV-06:10 | 246.86 | 0.00 | 0.00 | 0.00 | 162.99 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 363.66 | 0.00 | -263.77 | 0.00 | -928.43 | 0.00 |
M NW APARTMENT | 31-DEC-08:28 | 924.52 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -432.02 | 0.00 | -169.17 | -829.00 |
M SE APARTMENT | 10-NOV-06:10 | 169.16 | 0.00 | 0.00 | 0.00 | 162.99 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 433.22 | 0.00 | -263.04 | 0.00 | -921.02 | 0.00 |
M NE APARTMENT | 28-DEC-06:25 | 1078.93 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -695.70 | 0.00 | 0.00 | -991.58 |
M N1 APARTMENT | 05-FEB-16:00 | 159.62 | 0.00 | 0.00 | 0.00 | 41.50 | 50.41 | 400.26 | 36.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.84 | -540.41 |
M N2 APARTMENT | 05-FEB-16:00 | 159.86 | 0.00 | 0.00 | 0.00 | 41.54 | 50.41 | 400.26 | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146.96 | -541.89 |
M S1 APARTMENT | 10-NOV-06:10 | 24.26 | 0.00 | 0.00 | 0.00 | 162.99 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 382.10 | 0.00 | -160.26 | 0.00 | -827.77 | 0.00 |
M S2 APARTMENT | 10-NOV-06:10 | 23.05 | 0.00 | 0.00 | 0.00 | 162.99 | 100.83 | 317.86 | 0.00 | 0.00 | 0.00 | 383.15 | 0.00 | -160.25 | 0.00 | -827.63 | 0.00 |
T SW APARTMENT | 27-DEC-06:00 | 1262.80 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.85 | 0.00 | -255.81 | -846.54 |
T NW APARTMENT | 28-JAN-06:00 | 1335.39 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.25 | 0.00 | -449.39 | -699.15 |
T SE APARTMENT | 27-DEC-06:00 | 1269.79 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -704.64 | 0.00 | -255.81 | -845.75 |
T NE APARTMENT | 28-JAN-06:00 | 1404.10 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -720.62 | 0.00 | -449.39 | -770.49 |
T N1 APARTMENT | 17-JAN-07:01 | 1439.06 | 0.00 | 0.00 | 0.00 | 162.62 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -265.02 | 0.00 | 0.00 | -1812.89 |
T N2 APARTMENT | 26-DEC-18:01 | 1155.02 | 0.00 | 0.00 | 0.00 | 166.83 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -301.32 | 0.00 | 0.00 | -1803.61 |
T S1 APARTMENT | 25-MAR-06:01 | 1642.50 | 0.00 | 0.00 | 0.00 | 162.81 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -284.41 | 0.00 | -94.41 | -1902.72 |
T S2 APARTMENT | 27-DEC-06:00 | 813.70 | 0.00 | 0.00 | 0.00 | 189.67 | 93.63 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -429.98 | 0.00 | -154.31 | -765.81 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-DEC-07:01 | 9263.64 | 0.00 | 0.00 | 0.00 | 3702.63 | 4156.84 | 9398.91 | 0.00 | 0.00 | 0.00 | 162.75 | 0.00 | -14387.37 | 0.00 | -12297.40 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sec1.1A-General InformationData | |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 27.75 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 28.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 30.23 | 28542.98 | 0.00 | 0.00 |
Space Cooling | 199.18 | 22280.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 238.58 | 7565.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 351.40 | 19149.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1505.01 | 30.23 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1505.01 |
Natural Gas | 0.00 | 30.23 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1535.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 63.54 |
Fans-Interior | 76.11 |
Service Water Heating | 112.10 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.58 |
Subtotal | 480.13 |
Natural Gas [MJ/m2] | |
Space Heating | 9.64 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 9.64 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.75 |
Space Heating | 1.97 |
Space Cooling | 12.97 |
Fans-Interior | 15.54 |
Service Water Heating | 22.89 |
Receptacle Equipment | 33.31 |
Miscellaneous | 2.57 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.193661 |
G NW APARTMENT DIRECT AIR | 0.193607 |
OFFICE DIRECT AIR | 0.492121 |
G NE APARTMENT DIRECT AIR | 0.156490 |
G N1 APARTMENT DIRECT AIR | 0.126452 |
G N2 APARTMENT DIRECT AIR | 0.125722 |
G S1 APARTMENT DIRECT AIR | 0.123366 |
G S2 APARTMENT DIRECT AIR | 0.125466 |
M SW APARTMENT DIRECT AIR | 0.491959 |
M NW APARTMENT DIRECT AIR | 0.490650 |
M SE APARTMENT DIRECT AIR | 0.417961 |
M NE APARTMENT DIRECT AIR | 0.410488 |
M N1 APARTMENT DIRECT AIR | 0.327772 |
M N2 APARTMENT DIRECT AIR | 0.326553 |
M S1 APARTMENT DIRECT AIR | 0.322195 |
M S2 APARTMENT DIRECT AIR | 0.320981 |
T SW APARTMENT DIRECT AIR | 0.325622 |
T NW APARTMENT DIRECT AIR | 0.320619 |
T SE APARTMENT DIRECT AIR | 0.289943 |
T NE APARTMENT DIRECT AIR | 0.270427 |
T N1 APARTMENT DIRECT AIR | 0.219654 |
T N2 APARTMENT DIRECT AIR | 0.218214 |
T S1 APARTMENT DIRECT AIR | 0.231861 |
T S2 APARTMENT DIRECT AIR | 0.232253 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.193661 |
SPLIT GNW MAIN BRANCH | 0.193607 |
SPLIT OFFICE MAIN BRANCH | 0.492121 |
SPLIT GNE MAIN BRANCH | 0.156490 |
SPLIT GN1 MAIN BRANCH | 0.126452 |
SPLIT GN2 MAIN BRANCH | 0.125722 |
SPLIT GS1 MAIN BRANCH | 0.123366 |
SPLIT GS2 MAIN BRANCH | 0.125466 |
SPLIT MSW MAIN BRANCH | 0.491959 |
SPLIT MNW MAIN BRANCH | 0.490650 |
SPLIT MSE MAIN BRANCH | 0.417961 |
SPLIT MNE MAIN BRANCH | 0.410488 |
SPLIT MN1 MAIN BRANCH | 0.327772 |
SPLIT MN2 MAIN BRANCH | 0.326553 |
SPLIT MS1 MAIN BRANCH | 0.322195 |
SPLIT MS2 MAIN BRANCH | 0.320981 |
SPLIT TSW MAIN BRANCH | 0.325622 |
SPLIT TNW MAIN BRANCH | 0.320619 |
SPLIT TSE MAIN BRANCH | 0.289943 |
SPLIT TNE MAIN BRANCH | 0.270427 |
SPLIT TN1 MAIN BRANCH | 0.219654 |
SPLIT TN2 MAIN BRANCH | 0.218214 |
SPLIT TS1 MAIN BRANCH | 0.231861 |
SPLIT TS2 MAIN BRANCH | 0.232253 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.193661 |
SPLIT GNW | 0.193607 |
SPLIT OFFICE | 0.492121 |
SPLIT GNE | 0.156490 |
SPLIT GN1 | 0.126452 |
SPLIT GN2 | 0.125722 |
SPLIT GS1 | 0.123366 |
SPLIT GS2 | 0.125466 |
SPLIT MSW | 0.491959 |
SPLIT MNW | 0.490650 |
SPLIT MSE | 0.417961 |
SPLIT MNE | 0.410488 |
SPLIT MN1 | 0.327772 |
SPLIT MN2 | 0.326553 |
SPLIT MS1 | 0.322195 |
SPLIT MS2 | 0.320981 |
SPLIT TSW | 0.325622 |
SPLIT TNW | 0.320619 |
SPLIT TSE | 0.289943 |
SPLIT TNE | 0.270427 |
SPLIT TN1 | 0.219654 |
SPLIT TN2 | 0.218214 |
SPLIT TS1 | 0.231861 |
SPLIT TS2 | 0.232253 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.193661 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.193607 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.492121 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.156490 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.126452 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.125722 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.123366 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.125466 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.491959 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.490650 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.417961 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.410488 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.327772 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.326553 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.322195 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.320981 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.325622 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.320619 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.289943 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.270427 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.219654 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.218214 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.231861 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.232253 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.193661 | 3205.77 | 0.798655 |
SPLIT GNW COOLING COIL | 0.193607 | 3204.89 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.492121 | 8146.35 | 0.798655 |
SPLIT GNE COOLING COIL | 0.156490 | 2590.47 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.126452 | 2093.23 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.125722 | 2081.15 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.123366 | 2042.14 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.125466 | 2076.92 | 0.798655 |
SPLIT MSW COOLING COIL | 0.491959 | 8143.66 | 0.798655 |
SPLIT MNW COOLING COIL | 0.490650 | 8122.01 | 0.798655 |
SPLIT MSE COOLING COIL | 0.417961 | 6918.74 | 0.798655 |
SPLIT MNE COOLING COIL | 0.410488 | 6795.03 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.327772 | 5425.79 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.326553 | 5405.61 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.322195 | 5333.47 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.320981 | 5313.38 | 0.798655 |
SPLIT TSW COOLING COIL | 0.325622 | 5390.20 | 0.798655 |
SPLIT TNW COOLING COIL | 0.320619 | 5307.39 | 0.798655 |
SPLIT TSE COOLING COIL | 0.289943 | 4799.58 | 0.798655 |
SPLIT TNE COOLING COIL | 0.270427 | 4476.52 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.219654 | 3636.06 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.218214 | 3612.21 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.231861 | 3838.12 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.232253 | 3844.61 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.193661 | 0.193661 | 0.193661 | 0.193661 | 1752.44 | 3205.77 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.193607 | 0.193607 | 0.193607 | 0.193607 | 1732.44 | 3204.89 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.492121 | 0.492121 | 0.492121 | 0.492121 | 3438.36 | 8146.35 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.156490 | 0.156490 | 0.156490 | 0.156490 | 1737.15 | 2590.47 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.126452 | 0.126452 | 0.126452 | 0.126452 | 1503.38 | 2093.23 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.125722 | 0.125722 | 0.125722 | 0.125722 | 1503.38 | 2081.15 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.123366 | 0.123366 | 0.123366 | 0.123366 | 1503.38 | 2042.14 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.125466 | 0.125466 | 0.125466 | 0.125466 | 1503.38 | 2076.92 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.491959 | 0.491959 | 0.491959 | 0.491959 | 3335.95 | 8143.66 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.490650 | 0.490650 | 0.490650 | 0.490650 | 3358.43 | 8122.01 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.417961 | 0.417961 | 0.417961 | 0.417961 | 3348.81 | 6918.74 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.410488 | 0.410488 | 0.410488 | 0.410488 | 3371.28 | 6795.03 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.327772 | 0.327772 | 0.327772 | 0.327772 | 3006.76 | 5425.79 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.326553 | 0.326553 | 0.326553 | 0.326553 | 3006.76 | 5405.61 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.322195 | 0.322195 | 0.322195 | 0.322195 | 3006.76 | 5333.47 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.320981 | 0.320981 | 0.320981 | 0.320981 | 3006.76 | 5313.38 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.325622 | 0.325622 | 0.325622 | 0.325622 | 2694.81 | 5390.20 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.320619 | 0.320619 | 0.320619 | 0.320619 | 2707.94 | 5307.39 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.289943 | 0.289943 | 0.289943 | 0.289943 | 2701.57 | 4799.58 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.270427 | 0.270427 | 0.270427 | 0.270427 | 2714.70 | 4476.52 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.219654 | 0.219654 | 0.219654 | 0.219654 | 2131.78 | 3636.06 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.218214 | 0.218214 | 0.218214 | 0.218214 | 2131.98 | 3612.21 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.231861 | 0.231861 | 0.231861 | 0.231861 | 2116.68 | 3838.12 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.232253 | 0.232253 | 0.232253 | 0.232253 | 2116.88 | 3844.61 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.193661 |
SPLIT GNW SUPPLY FAN | 0.193607 |
SPLIT OFFICE SUPPLY FAN | 0.492121 |
SPLIT GNE SUPPLY FAN | 0.156490 |
SPLIT GN1 SUPPLY FAN | 0.126452 |
SPLIT GN2 SUPPLY FAN | 0.125722 |
SPLIT GS1 SUPPLY FAN | 0.123366 |
SPLIT GS2 SUPPLY FAN | 0.125466 |
SPLIT MSW SUPPLY FAN | 0.491959 |
SPLIT MNW SUPPLY FAN | 0.490650 |
SPLIT MSE SUPPLY FAN | 0.417961 |
SPLIT MNE SUPPLY FAN | 0.410488 |
SPLIT MN1 SUPPLY FAN | 0.327772 |
SPLIT MN2 SUPPLY FAN | 0.326553 |
SPLIT MS1 SUPPLY FAN | 0.322195 |
SPLIT MS2 SUPPLY FAN | 0.320981 |
SPLIT TSW SUPPLY FAN | 0.325622 |
SPLIT TNW SUPPLY FAN | 0.320619 |
SPLIT TSE SUPPLY FAN | 0.289943 |
SPLIT TNE SUPPLY FAN | 0.270427 |
SPLIT TN1 SUPPLY FAN | 0.219654 |
SPLIT TN2 SUPPLY FAN | 0.218214 |
SPLIT TS1 SUPPLY FAN | 0.231861 |
SPLIT TS2 SUPPLY FAN | 0.232253 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1752.44 |
SPLIT GNW HEATING COIL | 1732.44 |
SPLIT OFFICE HEATING COIL | 3438.36 |
SPLIT GNE HEATING COIL | 1737.15 |
SPLIT GN1 HEATING COIL | 1503.38 |
SPLIT GN2 HEATING COIL | 1503.38 |
SPLIT GS1 HEATING COIL | 1503.38 |
SPLIT GS2 HEATING COIL | 1503.38 |
SPLIT MSW HEATING COIL | 3335.95 |
SPLIT MNW HEATING COIL | 3358.43 |
SPLIT MSE HEATING COIL | 3348.81 |
SPLIT MNE HEATING COIL | 3371.28 |
SPLIT MN1 HEATING COIL | 3006.76 |
SPLIT MN2 HEATING COIL | 3006.76 |
SPLIT MS1 HEATING COIL | 3006.76 |
SPLIT MS2 HEATING COIL | 3006.76 |
SPLIT TSW HEATING COIL | 2694.81 |
SPLIT TNW HEATING COIL | 2707.94 |
SPLIT TSE HEATING COIL | 2701.57 |
SPLIT TNE HEATING COIL | 2714.70 |
SPLIT TN1 HEATING COIL | 2131.78 |
SPLIT TN2 HEATING COIL | 2131.98 |
SPLIT TS1 HEATING COIL | 2116.68 |
SPLIT TS2 HEATING COIL | 2116.88 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 8.14 |
February | 22.86 | 10.27 |
March | 23.07 | 12.55 |
April | 23.91 | 19.23 |
May | 24.29 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.11 | 18.30 |
November | 23.19 | 11.18 |
December | 22.58 | 6.79 |
Annual Sum or Average | 23.69 | 17.98 |
Minimum of Months | 22.58 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 8.14 |
February | 22.25 | 10.27 |
March | 22.66 | 12.55 |
April | 23.80 | 19.23 |
May | 24.29 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 23.93 | 18.30 |
November | 22.53 | 11.18 |
December | 21.92 | 6.79 |
Annual Sum or Average | 23.42 | 17.98 |
Minimum of Months | 21.92 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 8.14 |
February | 23.27 | 10.27 |
March | 23.63 | 12.55 |
April | 25.02 | 19.23 |
May | 25.77 | 23.84 |
June | 26.98 | 27.86 |
July | 27.13 | 27.54 |
August | 26.85 | 26.28 |
September | 26.85 | 23.38 |
October | 25.13 | 18.30 |
November | 23.79 | 11.18 |
December | 22.72 | 6.79 |
Annual Sum or Average | 25.00 | 17.98 |
Minimum of Months | 22.72 | 6.79 |
Maximum of Months | 27.13 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 8.14 |
February | 22.19 | 10.27 |
March | 22.61 | 12.55 |
April | 23.81 | 19.23 |
May | 24.29 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.87 | 18.30 |
November | 22.43 | 11.18 |
December | 21.84 | 6.79 |
Annual Sum or Average | 23.38 | 17.98 |
Minimum of Months | 21.84 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 8.14 |
February | 22.13 | 10.27 |
March | 22.47 | 12.55 |
April | 23.68 | 19.23 |
May | 24.25 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 23.86 | 18.30 |
November | 22.40 | 11.18 |
December | 21.85 | 6.79 |
Annual Sum or Average | 23.35 | 17.98 |
Minimum of Months | 21.85 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 8.14 |
February | 22.13 | 10.27 |
March | 22.46 | 12.55 |
April | 23.68 | 19.23 |
May | 24.25 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 23.85 | 18.30 |
November | 22.39 | 11.18 |
December | 21.85 | 6.79 |
Annual Sum or Average | 23.35 | 17.98 |
Minimum of Months | 21.85 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 8.14 |
February | 22.89 | 10.27 |
March | 23.04 | 12.55 |
April | 23.84 | 19.23 |
May | 24.25 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.11 | 18.30 |
November | 23.27 | 11.18 |
December | 22.62 | 6.79 |
Annual Sum or Average | 23.69 | 17.98 |
Minimum of Months | 22.62 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 8.14 |
February | 22.90 | 10.27 |
March | 23.05 | 12.55 |
April | 23.87 | 19.23 |
May | 24.27 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.12 | 18.30 |
November | 23.28 | 11.18 |
December | 22.63 | 6.79 |
Annual Sum or Average | 23.70 | 17.98 |
Minimum of Months | 22.63 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.01 | 8.14 |
February | 24.13 | 10.27 |
March | 24.26 | 12.55 |
April | 24.38 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.23 | 11.18 |
December | 23.86 | 6.79 |
Annual Sum or Average | 24.27 | 17.98 |
Minimum of Months | 23.86 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 8.14 |
February | 23.68 | 10.27 |
March | 24.11 | 12.55 |
April | 24.37 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 23.95 | 11.18 |
December | 22.94 | 6.79 |
Annual Sum or Average | 24.06 | 17.98 |
Minimum of Months | 22.94 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 8.14 |
February | 24.12 | 10.27 |
March | 24.24 | 12.55 |
April | 24.38 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.19 | 11.18 |
December | 23.82 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.82 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 8.14 |
February | 23.65 | 10.27 |
March | 24.09 | 12.55 |
April | 24.37 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.39 | 18.30 |
November | 23.90 | 11.18 |
December | 22.81 | 6.79 |
Annual Sum or Average | 24.03 | 17.98 |
Minimum of Months | 22.81 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.58 | 8.14 |
February | 23.86 | 10.27 |
March | 24.21 | 12.55 |
April | 24.38 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.10 | 11.18 |
December | 23.21 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.21 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.56 | 8.14 |
February | 23.85 | 10.27 |
March | 24.21 | 12.55 |
April | 24.38 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.10 | 11.18 |
December | 23.19 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.19 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.22 | 8.14 |
February | 24.27 | 10.27 |
March | 24.34 | 12.55 |
April | 24.39 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.32 | 11.18 |
December | 24.10 | 6.79 |
Annual Sum or Average | 24.34 | 17.98 |
Minimum of Months | 24.10 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.21 | 8.14 |
February | 24.27 | 10.27 |
March | 24.34 | 12.55 |
April | 24.39 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.32 | 11.18 |
December | 24.10 | 6.79 |
Annual Sum or Average | 24.34 | 17.98 |
Minimum of Months | 24.10 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.33 | 10.27 |
March | 23.58 | 12.55 |
April | 24.20 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.30 | 18.30 |
November | 23.48 | 11.18 |
December | 22.95 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 22.95 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.40 | 8.14 |
February | 22.86 | 10.27 |
March | 23.34 | 12.55 |
April | 24.17 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.23 | 18.30 |
November | 23.08 | 11.18 |
December | 22.26 | 6.79 |
Annual Sum or Average | 23.69 | 17.98 |
Minimum of Months | 22.26 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.34 | 10.27 |
March | 23.60 | 12.55 |
April | 24.21 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.27 | 18.30 |
November | 23.45 | 11.18 |
December | 22.95 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 22.95 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 8.14 |
February | 22.81 | 10.27 |
March | 23.36 | 12.55 |
April | 24.17 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.19 | 18.30 |
November | 23.03 | 11.18 |
December | 22.12 | 6.79 |
Annual Sum or Average | 23.66 | 17.98 |
Minimum of Months | 22.12 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 8.14 |
February | 22.83 | 10.27 |
March | 23.36 | 12.55 |
April | 24.18 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.25 | 18.30 |
November | 23.07 | 11.18 |
December | 22.15 | 6.79 |
Annual Sum or Average | 23.68 | 17.98 |
Minimum of Months | 22.15 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 8.14 |
February | 22.83 | 10.27 |
March | 23.36 | 12.55 |
April | 24.18 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.25 | 18.30 |
November | 23.06 | 11.18 |
December | 22.14 | 6.79 |
Annual Sum or Average | 23.68 | 17.98 |
Minimum of Months | 22.14 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 8.14 |
February | 23.47 | 10.27 |
March | 23.69 | 12.55 |
April | 24.24 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.33 | 18.30 |
November | 23.58 | 11.18 |
December | 23.06 | 6.79 |
Annual Sum or Average | 23.96 | 17.98 |
Minimum of Months | 23.06 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 8.14 |
February | 23.47 | 10.27 |
March | 23.70 | 12.55 |
April | 24.24 | 19.23 |
May | 24.39 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.33 | 18.30 |
November | 23.58 | 11.18 |
December | 23.06 | 6.79 |
Annual Sum or Average | 23.96 | 17.98 |
Minimum of Months | 23.06 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 8.14 |
February | 23.92 | 10.27 |
March | 24.60 | 12.55 |
April | 26.02 | 19.23 |
May | 26.73 | 23.84 |
June | 27.25 | 27.86 |
July | 27.29 | 27.54 |
August | 27.12 | 26.28 |
September | 26.80 | 23.38 |
October | 26.05 | 18.30 |
November | 24.23 | 11.18 |
December | 22.99 | 6.79 |
Annual Sum or Average | 25.53 | 17.98 |
Minimum of Months | 22.99 | 6.79 |
Maximum of Months | 27.29 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 8.14 |
February | 22.39 | 10.27 |
March | 22.92 | 12.55 |
April | 24.44 | 19.23 |
May | 25.44 | 23.84 |
June | 27.02 | 27.86 |
July | 27.13 | 27.54 |
August | 26.96 | 26.28 |
September | 26.62 | 23.38 |
October | 24.71 | 18.30 |
November | 22.87 | 11.18 |
December | 21.72 | 6.79 |
Annual Sum or Average | 24.52 | 17.98 |
Minimum of Months | 21.72 | 6.79 |
Maximum of Months | 27.13 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.60 | 8.14 |
February | 25.92 | 10.27 |
March | 26.29 | 12.55 |
April | 26.74 | 19.23 |
May | 26.97 | 23.84 |
June | 27.17 | 27.86 |
July | 27.14 | 27.54 |
August | 27.09 | 26.28 |
September | 27.01 | 23.38 |
October | 26.76 | 18.30 |
November | 26.19 | 11.18 |
December | 25.34 | 6.79 |
Annual Sum or Average | 26.52 | 17.98 |
Minimum of Months | 25.34 | 6.79 |
Maximum of Months | 27.17 | 27.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.118238E+12 | 74448.041 | 12-JAN-18:45 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 2398.580 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26946.692 | 0.000 | 0.000 | 0.000 |
February | 0.107932E+12 | 74249.445 | 19-FEB-18:45 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 5424.362 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23722.313 | 0.000 | 0.000 | 0.000 |
March | 0.119804E+12 | 75011.258 | 26-MAR-17:30 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 7531.209 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24885.609 | 0.000 | 0.000 | 0.000 |
April | 0.122648E+12 | 78501.291 | 19-APR-17:15 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 15450.876 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20455.976 | 0.000 | 0.000 | 0.000 |
May | 0.132410E+12 | 80915.315 | 19-MAY-17:15 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 19274.119 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19046.756 | 0.000 | 0.000 | 0.000 |
June | 0.136020E+12 | 82150.137 | 14-JUN-17:30 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 22568.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16986.882 | 0.000 | 0.000 | 0.000 |
July | 0.142301E+12 | 84025.207 | 26-JUL-17:15 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 22280.919 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19149.848 | 0.000 | 0.000 | 0.000 |
August | 0.138364E+12 | 82622.114 | 27-AUG-17:15 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 19474.959 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20552.716 | 0.000 | 0.000 | 0.000 |
September | 0.130639E+12 | 82536.036 | 01-SEP-17:15 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 18175.176 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21766.420 | 0.000 | 0.000 | 0.000 |
October | 0.125420E+12 | 79239.882 | 18-OCT-17:45 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 11990.681 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22146.431 | 0.000 | 0.000 | 0.000 |
November | 0.114431E+12 | 70837.364 | 08-NOV-18:30 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 6345.313 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19389.282 | 0.000 | 0.000 | 0.000 |
December | 0.116805E+12 | 71356.731 | 12-DEC-18:45 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 455.460 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25798.502 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.150501E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.107932E+12 | 70837.364 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 455.460 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16986.882 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.142301E+12 | 84025.207 | 8572.775 | 26456.413 | 7565.251 | 0.000 | 22568.817 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26946.692 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.816920E+10 | 25494.703 | 28-JAN-05:00 | 25494.703 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25494.703 |
February | 0.497176E+10 | 23354.066 | 03-FEB-04:00 | 23354.066 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23354.066 |
March | 0.213595E+10 | 18850.893 | 02-MAR-05:00 | 18850.893 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18850.893 |
April | 0.109042E+09 | 5427.437 | 11-APR-03:00 | 5427.437 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5427.437 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 240313.905 | 114.124 | 25-OCT-05:00 | 114.124 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 114.124 |
November | 0.312108E+10 | 21567.716 | 28-NOV-04:00 | 21567.716 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21567.716 |
December | 0.117203E+11 | 28542.978 | 27-DEC-07:15 | 28542.978 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28542.978 |
Annual Sum or Average | 0.302276E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.117203E+11 | 28542.978 | 28542.978 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28542.978 |