Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2018-10-19 09:20:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1724.94 550.29 610.82
Net Site Energy 1724.94 550.29 610.82
Total Source Energy 5455.11 1740.28 1931.71
Net Source Energy 5455.11 1740.28 1931.71


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 3.74 0.00 0.00 0.00 0.00
Cooling 421.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 287.25 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 296.75 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1721.20 3.74 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 3.74 0.00 0.00 0.00 0.00
Cooling General 421.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 287.25 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 296.75 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.39 0.00 0.00 0.00 0.00 0.00
HVAC 356.00 1.32 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 609.50 1.32 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.22 0.00 0.00 0.00 0.00 0.00
HVAC 320.72 1.19 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 549.10 1.19 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1721.20 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1721.20 100.00
     
Total On-Site and Utility Electric Sources 1721.20 100.00
Total Electricity End Uses 1721.20 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 7.75
Time Setpoint Not Met During Occupied Cooling 1.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 1524.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 02-JUL-17:30 03-JAN-06:00 - - - 01-JAN-07:15
Heating 0.00 9905.98 0.00 0.00 0.00 0.00
Cooling 35966.53 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9108.76 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 15912.74 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 96017.22 9905.98 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 9905.98 0.00 0.00 0.00 0.00
Cooling General 35966.53 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 9108.76 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 15912.74 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 4.05 0.00 0.00 0.00
Cooling 1334.38 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.89 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 909.73 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 939.82 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 5451.05 4.05 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.44 0.00 0.00 0.00
Cooling 472.52 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 322.15 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 332.80 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1930.28 1.44 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.44 0.00 0.00 0.00
Cooling 472.52 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 322.15 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 332.80 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1930.28 1.44 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 5.778 0.306 0.155     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 5.778 0.306 0.155     No M EWALL C 270.00 90.00 W
Total or Average           306.92 5.778 0.306 0.155              
North Total or Average           112.97 5.778 0.306 0.155              
Non-North Total or Average           193.95 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.76 83.76 39.44
Exterior Lighting Total 2508.33           39.44



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4787.41 3548.88 1238.53 0.74 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4827.14 3586.73 1240.41 0.74 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8586.16 6752.13 1834.03 0.79 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4138.71 3065.55 1073.16 0.74 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3225.69 2360.12 865.57 0.73 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3216.07 2352.54 863.53 0.73 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3110.44 2269.47 840.97 0.73 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3089.66 2266.79 822.87 0.73 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   11406.94 8543.32 2863.61 0.75 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   11506.03 8635.70 2870.33 0.75 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   10449.59 7708.13 2741.47 0.74 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   10168.75 7599.12 2569.62 0.75 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   7801.55 5781.99 2019.56 0.74 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   7786.21 5769.89 2016.32 0.74 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   7527.09 5565.66 1961.43 0.74 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   7511.93 5553.71 1958.23 0.74 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   7165.97 5399.39 1766.58 0.75 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   7178.43 5417.87 1760.56 0.75 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   6661.12 4969.13 1691.99 0.75 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6508.76 4857.01 1651.75 0.75 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5082.05 3785.85 1296.21 0.74 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5066.30 3773.49 1292.81 0.74 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5213.79 3847.13 1366.66 0.74 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5216.14 3848.97 1367.18 0.74 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4595.7 3.23 11.02 11.46 10.88
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4632.7 3.23 11.01 11.45 10.86
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8193.0 3.15 10.74 11.17 10.48
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3973.2 3.23 11.02 11.47 10.89
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3100.4 3.25 11.08 11.53 10.97
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3091.3 3.25 11.08 11.53 10.97
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2990.5 3.25 11.09 11.54 10.99
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2968.9 3.24 11.06 11.52 10.95
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 10938.9 3.21 10.97 11.41 10.81
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 11031.7 3.21 10.96 11.40 10.80
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 10035.9 3.24 11.04 11.49 10.91
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 9753.7 3.22 10.98 11.42 10.83
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 7489.2 3.23 11.02 11.46 10.88
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 7474.6 3.23 11.02 11.47 10.88
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 7227.4 3.23 11.03 11.48 10.90
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 7212.9 3.23 11.03 11.48 10.90
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6867.9 3.21 10.94 11.38 10.77
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 6878.6 3.20 10.93 11.37 10.76
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 6390.3 3.22 10.99 11.43 10.84
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6244.0 3.22 10.99 11.43 10.84
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4876.1 3.22 10.99 11.44 10.85
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4861.1 3.22 10.99 11.44 10.85
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5007.2 3.23 11.04 11.49 10.91
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5009.5 3.23 11.04 11.49 10.91
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1386.44 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   2768.38 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1337.71 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2675.42 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   1908.62 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   1909.49 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   1903.43 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   1904.30 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1424.96 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1424.81 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1422.53 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1422.38 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 273.40 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 277.22 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 561.62 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 235.90 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 178.50 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 177.87 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.95 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.11 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.60 667.53 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.60 676.67 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.53 589.75 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.53 591.97 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 445.30 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 444.30 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 427.26 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 426.26 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 425.30 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 427.72 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 386.17 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 377.61 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 293.64 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 292.62 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 294.47 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 294.62 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2531.92 3038.31 0.203 0.244 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
G NW APARTMENT 2567.25 3080.70 0.206 0.247 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
OFFICE 5089.97 6107.97 0.418 0.501 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 09:00:00 36.66 0.00911
G NE APARTMENT 2184.68 2621.61 0.176 0.211 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
G N1 APARTMENT 1653.04 1983.64 0.133 0.159 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
G N2 APARTMENT 1647.19 1976.63 0.132 0.159 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
G S1 APARTMENT 1583.20 1899.83 0.127 0.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
G S2 APARTMENT 1593.89 1912.67 0.128 0.154 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:30:00 38.94 0.00911
M SW APARTMENT 6181.82 7418.19 0.497 0.596 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
M NW APARTMENT 6266.47 7519.77 0.503 0.604 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:00:00 40.64 0.00911
M SE APARTMENT 5461.56 6553.88 0.439 0.527 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
M NE APARTMENT 5482.10 6578.53 0.440 0.528 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:15:00 40.40 0.00911
M N1 APARTMENT 4123.92 4948.70 0.331 0.398 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
M N2 APARTMENT 4114.57 4937.48 0.331 0.397 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
M S1 APARTMENT 3956.82 4748.18 0.318 0.381 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
M S2 APARTMENT 3947.58 4737.10 0.317 0.381 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
T SW APARTMENT 3938.65 4726.38 0.316 0.380 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
T NW APARTMENT 3961.00 4753.20 0.318 0.382 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03 0.00911
T SE APARTMENT 3576.18 4291.42 0.287 0.345 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
T NE APARTMENT 3496.99 4196.39 0.281 0.337 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:15:00 41.85 0.00911
T N1 APARTMENT 2719.37 3263.25 0.218 0.262 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
T N2 APARTMENT 2709.89 3251.87 0.218 0.261 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
T S1 APARTMENT 2727.05 3272.46 0.219 0.263 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
T S2 APARTMENT 2728.45 3274.14 0.219 0.263 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 704.84 845.81 0.021 0.027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
G NW APARTMENT 703.15 843.78 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
OFFICE 1812.01 2174.41 0.051 0.061 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 09:00:00 6.30 0.00607
G NE APARTMENT 700.18 840.22 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
G N1 APARTMENT 355.80 426.96 0.011 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
G N2 APARTMENT 355.72 426.87 0.011 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
G S1 APARTMENT 358.40 430.07 0.011 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
G S2 APARTMENT 421.09 505.31 0.012 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M SW APARTMENT 1344.20 1613.04 0.040 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M NW APARTMENT 1345.04 1614.05 0.040 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M SE APARTMENT 1335.85 1603.02 0.039 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M NE APARTMENT 1336.72 1604.07 0.039 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M N1 APARTMENT 454.06 544.88 0.013 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M N2 APARTMENT 453.81 544.57 0.013 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M S1 APARTMENT 453.03 543.63 0.013 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
M S2 APARTMENT 452.77 543.32 0.013 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T SW APARTMENT 1215.36 1458.44 0.036 0.043 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T NW APARTMENT 1216.10 1459.31 0.036 0.043 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T SE APARTMENT 1210.97 1453.17 0.036 0.043 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T NE APARTMENT 1211.70 1454.04 0.036 0.043 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T N1 APARTMENT 806.35 967.62 0.024 0.029 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T N2 APARTMENT 806.23 967.47 0.024 0.029 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T S1 APARTMENT 804.29 965.15 0.024 0.028 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607
T S2 APARTMENT 804.17 965.00 0.024 0.028 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 04:00:00 6.30 0.00607


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.24 0.24 0.03 0.03
SPLIT GNW 0.25 0.25 0.03 0.03
SPLIT OFFICE 0.50 0.50 0.06 0.06
SPLIT GNE 0.21 0.21 0.03 0.03
SPLIT GN1 0.16 0.16 0.03 0.03
SPLIT GN2 0.16 0.16 0.03 0.03
SPLIT GS1 0.15 0.15 0.03 0.03
SPLIT GS2 0.15 0.15 0.03 0.03
SPLIT MSW 0.60 0.60 0.05 0.05
SPLIT MNW 0.60 0.60 0.05 0.05
SPLIT MSE 0.53 0.53 0.05 0.05
SPLIT MNE 0.53 0.53 0.05 0.05
SPLIT MN1 0.40 0.40 0.05 0.05
SPLIT MN2 0.40 0.40 0.05 0.05
SPLIT MS1 0.38 0.38 0.05 0.05
SPLIT MS2 0.38 0.38 0.05 0.05
SPLIT TSW 0.38 0.38 0.04 0.04
SPLIT TNW 0.38 0.38 0.04 0.04
SPLIT TSE 0.34 0.34 0.04 0.04
SPLIT TNE 0.34 0.34 0.04 0.04
SPLIT TN1 0.26 0.26 0.03 0.03
SPLIT TN2 0.26 0.26 0.03 0.03
SPLIT TS1 0.26 0.26 0.03 0.03
SPLIT TS2 0.26 0.26 0.03 0.03



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 5195.50 3308.25 1149.75
G NW APARTMENT 4655.50 4061.75 1161.75
OFFICE 1420.00 470.25 25.50
G NE APARTMENT 4676.00 4080.00 1164.50
G N1 APARTMENT 4329.75 4615.25 1518.75
G N2 APARTMENT 4329.50 4615.25 1516.75
G S1 APARTMENT 4892.75 3579.25 1372.00
G S2 APARTMENT 5022.50 3376.75 1218.00
M SW APARTMENT 6984.25 910.00 531.50
M NW APARTMENT 6160.00 1561.25 554.25
M SE APARTMENT 6982.00 857.75 462.25
M NE APARTMENT 6187.00 1555.00 555.25
M N1 APARTMENT 6138.75 1449.25 710.50
M N2 APARTMENT 6140.25 1451.50 711.25
M S1 APARTMENT 7207.00 816.50 653.75
M S2 APARTMENT 7206.25 817.50 653.50
T SW APARTMENT 6400.00 1932.75 672.75
T NW APARTMENT 5814.50 2476.00 695.25
T SE APARTMENT 6419.00 1905.00 647.00
T NE APARTMENT 5823.75 2460.50 671.00
T N1 APARTMENT 5808.75 2467.00 785.75
T N2 APARTMENT 5807.25 2469.50 786.25
T S1 APARTMENT 6501.00 1734.25 698.75
T S2 APARTMENT 6502.50 1737.25 699.50
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 7346.25 4643.00 1524.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.50 0.00 0.50 0.00
G NW APARTMENT 0.00 0.75 0.00 0.75
OFFICE 0.00 49.75 0.00 0.00
G NE APARTMENT 0.00 0.00 0.00 0.00
G N1 APARTMENT 5.25 0.00 5.25 0.00
G N2 APARTMENT 5.00 0.25 5.00 0.25
G S1 APARTMENT 0.00 0.00 0.00 0.00
G S2 APARTMENT 0.00 0.00 0.00 0.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.00 0.00 0.00 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.00 0.00 0.00 0.00
T NW APARTMENT 0.00 0.75 0.00 0.75
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 0.00 0.00 0.00 0.00
T N2 APARTMENT 0.00 0.00 0.00 0.00
T S1 APARTMENT 0.00 0.00 0.00 0.00
T S2 APARTMENT 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 7.75 51.50 7.75 1.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.372 0.036 0.000 0.060
G NW APARTMENT 1.71 2.50 268.97 0.359 0.036 0.000 0.057
OFFICE 0.94 1.00 268.97 0.526 0.051 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.359 0.036 0.000 0.057
G N1 APARTMENT 1.71 2.50 268.97 0.359 0.022 0.000 0.056
G N2 APARTMENT 1.71 2.50 268.97 0.359 0.022 0.000 0.056
G S1 APARTMENT 1.71 2.50 268.97 0.359 0.022 0.000 0.060
G S2 APARTMENT 1.71 2.50 268.97 0.359 0.022 0.000 0.060
M SW APARTMENT 1.71 2.50 268.97 0.359 0.051 0.000 0.066
M NW APARTMENT 1.71 2.50 268.97 0.359 0.051 0.000 0.065
M SE APARTMENT 1.71 2.50 268.97 0.359 0.051 0.000 0.066
M NE APARTMENT 1.71 2.50 268.97 0.359 0.051 0.000 0.065
M N1 APARTMENT 1.71 2.50 268.97 0.359 0.031 0.000 0.065
M N2 APARTMENT 1.71 2.50 268.97 0.359 0.031 0.000 0.065
M S1 APARTMENT 1.71 2.50 268.97 0.359 0.031 0.000 0.066
M S2 APARTMENT 1.71 2.50 268.97 0.359 0.031 0.000 0.066
T SW APARTMENT 1.71 2.50 268.97 0.359 0.068 0.000 0.072
T NW APARTMENT 1.71 2.50 268.97 0.359 0.068 0.000 0.070
T SE APARTMENT 1.71 2.50 268.97 0.359 0.068 0.000 0.072
T NE APARTMENT 1.71 2.50 268.97 0.359 0.068 0.000 0.070
T N1 APARTMENT 1.71 2.50 268.97 0.359 0.041 0.000 0.070
T N2 APARTMENT 1.71 2.50 268.97 0.359 0.041 0.000 0.070
T S1 APARTMENT 1.71 2.50 268.97 0.359 0.041 0.000 0.072
T S2 APARTMENT 1.71 2.50 268.97 0.359 0.041 0.000 0.072
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.508 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.321 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.316 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.321 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.318 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.318 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.318 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.321 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.321 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 296.75 0.00 01-JAN-00:15 29647.28 01-JAN-06:15
WaterSystems:Electricity 296.75 0.00 01-JAN-00:15 29647.28 01-JAN-06:15
Water Heater:WaterSystems:Electricity 296.75 0.00 01-JAN-00:15 29647.28 01-JAN-06:15
Fans:Electricity 287.25 9108.76 15-JAN-21:45 9108.76 01-JAN-18:30
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
ElectricityPurchased:Plant 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
Cogeneration:ElectricityPurchased 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
ElectricityNet:Plant 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
Cogeneration:ElectricityNet 1721.20 22479.06 01-JAN-03:15 96017.22 02-JUL-17:30
ExteriorLights:Electricity 39.44 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.44 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
Electricity:HVAC 708.59 9108.76 01-JAN-08:30 46714.02 10-JUN-16:15
General:Fans:Electricity 287.25 9108.76 15-JAN-21:45 9108.76 01-JAN-18:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 421.34 0.00 01-JAN-00:15 37605.26 10-JUN-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 3.74 0.00 01-JAN-11:15 9905.98 03-JAN-07:00
Gas:HVAC 3.74 0.00 01-JAN-11:15 9905.98 03-JAN-07:00
Heating:Gas 3.74 0.00 01-JAN-11:15 9905.98 03-JAN-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2605.60 1669.70 10-FEB-15:00 210547.25 06-JUN-15:15
EnergyTransfer:Building 989.45 1669.70 10-FEB-15:00 90737.52 06-JUN-15:15
EnergyTransfer:Zone:G SW APARTMENT 23.87 0.01 10-FEB-11:15 3038.43 06-JUN-16:15
Heating:EnergyTransfer 12.89 0.00 20-FEB-15:15 5005.58 02-JAN-05:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.16 0.00 01-JAN-08:00 214.69 02-JAN-05:00
Cooling:EnergyTransfer 976.56 136.34 29-DEC-06:30 90737.52 06-JUN-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 23.71 0.00 01-JAN-00:15 3038.43 06-JUN-16:15
EnergyTransfer:Zone:G NW APARTMENT 19.86 0.03 29-JAN-19:15 3050.87 06-JUN-16:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 0.72 0.00 01-JAN-10:45 352.93 02-JAN-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 19.13 0.00 01-JAN-00:15 3050.87 06-JUN-16:30
EnergyTransfer:Zone:OFFICE 34.63 0.03 06-DEC-01:45 4836.39 12-JUN-09:45
Heating:EnergyTransfer:Zone:OFFICE 7.11 0.00 01-JAN-00:15 996.69 02-MAY-17:30
Cooling:EnergyTransfer:Zone:OFFICE 27.52 0.00 01-JAN-11:30 4836.39 12-JUN-09:45
EnergyTransfer:Zone:G NE APARTMENT 19.61 0.01 17-OCT-04:00 2459.05 12-JUN-17:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.51 0.00 01-JAN-09:30 378.42 02-JAN-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 19.10 0.00 01-JAN-00:15 2459.05 12-JUN-17:15
EnergyTransfer:Zone:G N1 APARTMENT 14.40 0.00 19-JAN-11:15 1869.04 12-JUN-17:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.26 0.00 01-JAN-06:15 270.05 21-DEC-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 14.14 0.00 01-JAN-00:15 1869.04 12-JUN-17:15
EnergyTransfer:Zone:G N2 APARTMENT 14.40 0.00 16-DEC-08:00 1859.78 12-JUN-17:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.26 0.00 01-JAN-06:15 254.88 23-DEC-02:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 14.14 0.00 01-JAN-00:15 1859.78 12-JUN-17:15
EnergyTransfer:Zone:G S1 APARTMENT 18.74 0.08 18-MAR-24:00 1894.43 27-SEP-14:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.01 0.00 01-JAN-00:15 81.90 19-FEB-24:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 18.74 0.00 02-JAN-16:00 1894.43 27-SEP-14:15
EnergyTransfer:Zone:G S2 APARTMENT 19.75 0.01 25-FEB-00:45 1919.42 22-SEP-14:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 69.89 01-FEB-15:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 19.74 0.00 02-JAN-16:00 1919.42 22-SEP-14:15
EnergyTransfer:Zone:M SW APARTMENT 81.48 1.39 12-JAN-03:15 7361.48 05-MAY-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.02 0.00 01-JAN-00:15 266.45 29-DEC-18:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 81.46 0.00 12-JAN-03:15 7361.48 05-MAY-16:15
EnergyTransfer:Zone:M NW APARTMENT 65.71 0.12 16-DEC-03:15 7323.18 06-JUN-16:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.17 0.00 01-JAN-00:15 428.40 24-DEC-12:30
Cooling:EnergyTransfer:Zone:M NW APARTMENT 65.53 0.00 01-JAN-12:00 7323.18 06-JUN-16:15
EnergyTransfer:Zone:M SE APARTMENT 81.78 1.46 29-DEC-23:45 6130.89 15-APR-14:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.01 0.00 01-JAN-00:15 225.69 29-DEC-17:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 81.77 0.00 15-JAN-09:30 6130.89 15-APR-14:15
EnergyTransfer:Zone:M NE APARTMENT 65.80 0.13 11-JAN-13:00 6036.36 06-JUN-16:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.08 0.00 01-JAN-00:15 379.38 04-JAN-14:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 65.72 0.00 01-JAN-12:30 6036.36 06-JUN-16:15
EnergyTransfer:Zone:M N1 APARTMENT 53.41 0.09 03-FEB-10:30 4471.37 12-JUN-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.02 0.00 01-JAN-00:15 221.64 04-JAN-13:45
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 53.40 0.00 01-JAN-13:30 4471.37 12-JUN-17:15
EnergyTransfer:Zone:M N2 APARTMENT 53.43 0.27 22-JAN-11:45 4456.69 12-JUN-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.01 0.00 01-JAN-00:15 221.57 04-JAN-13:45
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 53.41 0.00 01-JAN-13:30 4456.69 12-JUN-17:15
EnergyTransfer:Zone:M S1 APARTMENT 70.03 39.08 09-FEB-13:30 4942.37 17-OCT-14:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 70.03 39.08 09-FEB-13:30 4942.37 17-OCT-14:15
EnergyTransfer:Zone:M S2 APARTMENT 70.04 39.81 09-FEB-13:30 4943.47 17-OCT-14:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 70.04 39.81 09-FEB-13:30 4943.47 17-OCT-14:15
EnergyTransfer:Zone:T SW APARTMENT 42.15 0.02 30-DEC-20:30 4681.62 06-JUN-16:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 0.59 0.00 01-JAN-10:00 593.90 03-JAN-07:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 41.56 0.00 01-JAN-00:15 4681.62 06-JUN-16:15
EnergyTransfer:Zone:T NW APARTMENT 35.70 0.01 12-JAN-12:15 4700.77 06-JUN-16:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 1.12 0.00 03-JAN-14:45 732.25 03-JAN-07:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 34.58 0.00 01-JAN-00:15 4700.77 06-JUN-16:15
EnergyTransfer:Zone:T SE APARTMENT 41.98 0.04 04-JAN-01:15 4007.39 15-APR-14:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.44 0.00 01-JAN-09:00 603.20 03-JAN-07:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 41.55 0.00 01-JAN-00:15 4007.39 15-APR-14:15
EnergyTransfer:Zone:T NE APARTMENT 35.22 0.07 02-DEC-02:00 3898.05 06-JUN-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 0.83 0.00 01-JAN-10:30 761.05 02-JAN-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 34.39 0.00 01-JAN-00:15 3898.05 06-JUN-16:15
EnergyTransfer:Zone:T N1 APARTMENT 28.26 0.03 01-NOV-03:00 3077.62 06-JUN-16:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.25 0.00 01-JAN-10:15 400.92 02-JAN-05:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 28.01 0.00 01-JAN-00:15 3077.62 06-JUN-16:15
EnergyTransfer:Zone:T N2 APARTMENT 28.26 0.00 31-DEC-02:30 3062.96 06-JUN-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.24 0.00 01-JAN-10:15 406.11 02-JAN-05:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 28.02 0.00 01-JAN-00:15 3062.96 06-JUN-16:15
EnergyTransfer:Zone:T S1 APARTMENT 35.47 0.01 14-JAN-06:00 3201.73 02-OCT-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.04 0.00 01-JAN-00:15 213.32 02-JAN-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 35.43 0.00 01-JAN-02:15 3201.73 02-OCT-14:15
EnergyTransfer:Zone:T S2 APARTMENT 35.49 0.02 18-JAN-04:00 3206.41 02-OCT-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.04 0.00 01-JAN-00:15 215.03 02-JAN-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 35.44 0.00 01-JAN-02:15 3206.41 02-OCT-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1616.15 0.00 15-JAN-13:15 135126.67 01-JUL-16:15
HeatingCoils:EnergyTransfer 2.99 0.00 01-JAN-11:15 7924.78 03-JAN-07:00
CoolingCoils:EnergyTransfer 1613.15 0.00 01-JAN-00:15 135126.67 01-JUL-16:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.162 -23.710 0.000 0.000 3.596 2.413 12.213 19.256 0.000 0.506 0.000 0.000 -3.770 0.000 -0.841 -9.825
G NW APARTMENT 0.721 -19.135 0.000 0.000 3.622 2.413 12.213 13.005 0.000 0.505 0.000 0.000 -3.755 0.000 -0.733 -8.857
OFFICE 7.111 -27.518 0.000 0.000 0.517 21.914 7.534 18.038 0.000 0.332 0.000 0.000 -4.292 0.000 -0.217 -23.419
G NE APARTMENT 0.510 -19.100 0.000 0.000 3.630 2.413 12.213 12.850 0.000 0.505 0.000 0.000 -3.555 0.000 -0.735 -8.731
G N1 APARTMENT 0.258 -14.141 0.000 0.000 3.629 2.413 12.213 6.272 0.000 0.319 0.000 0.000 -2.263 0.000 -0.635 -8.065
G N2 APARTMENT 0.255 -14.144 0.000 0.000 3.629 2.413 12.213 6.272 0.000 0.319 0.000 0.000 -2.262 0.000 -0.635 -8.061
G S1 APARTMENT 0.006 -18.737 0.000 0.000 3.592 2.413 12.213 12.584 0.000 0.319 0.000 0.000 -2.271 0.000 -0.772 -9.348
G S2 APARTMENT 0.005 -19.743 0.000 0.000 3.591 2.413 12.213 12.556 0.000 0.319 0.000 0.000 -2.280 0.000 -0.774 -8.300
M SW APARTMENT 0.019 -81.462 0.000 0.000 3.527 2.413 12.213 18.631 0.000 0.713 49.366 0.000 -4.401 0.000 -1.019 -0.000
M NW APARTMENT 0.172 -65.533 0.000 0.000 3.540 2.413 12.213 12.406 0.000 0.712 39.546 0.000 -4.470 0.000 -0.999 -0.000
M SE APARTMENT 0.011 -81.767 0.000 0.000 3.529 2.413 12.213 18.572 0.000 0.713 49.623 0.000 -4.288 0.000 -1.019 -0.000
M NE APARTMENT 0.085 -65.718 0.000 0.000 3.543 2.413 12.213 12.225 0.000 0.712 39.770 0.000 -4.240 0.000 -1.003 -0.000
M N1 APARTMENT 0.015 -53.397 0.000 0.000 3.532 2.413 12.213 5.864 0.000 0.446 32.591 0.000 -2.777 0.000 -0.899 0.000
M N2 APARTMENT 0.014 -53.411 0.000 0.000 3.532 2.413 12.213 5.863 0.000 0.446 32.607 0.000 -2.777 0.000 -0.899 0.000
M S1 APARTMENT 0.000 -70.025 0.000 0.000 3.521 2.413 12.213 12.176 0.000 0.446 42.822 0.000 -2.652 0.000 -0.914 0.000
M S2 APARTMENT 0.000 -70.037 0.000 0.000 3.521 2.413 12.213 12.176 0.000 0.446 42.833 0.000 -2.652 0.000 -0.914 0.000
T SW APARTMENT 0.589 -41.558 0.000 0.000 3.567 2.413 12.213 18.244 0.000 0.932 8.805 0.000 -4.080 0.000 -1.124 -0.000
T NW APARTMENT 1.121 -34.578 0.000 0.000 3.582 2.413 12.213 12.100 0.000 0.931 7.399 0.000 -4.112 0.000 -1.068 -0.001
T SE APARTMENT 0.436 -41.546 0.000 0.000 3.570 2.413 12.213 18.206 0.000 0.932 8.881 0.000 -3.980 0.000 -1.125 -0.000
T NE APARTMENT 0.827 -34.390 0.000 0.000 3.586 2.413 12.213 11.963 0.000 0.931 7.460 0.000 -3.918 0.000 -1.085 -0.000
T N1 APARTMENT 0.247 -28.008 0.000 0.000 3.577 2.413 12.213 5.759 0.000 0.580 6.685 0.000 -2.529 0.000 -0.936 -0.000
T N2 APARTMENT 0.243 -28.018 0.000 0.000 3.577 2.413 12.213 5.757 0.000 0.580 6.700 0.000 -2.528 0.000 -0.937 -0.000
T S1 APARTMENT 0.041 -35.431 0.000 0.000 3.558 2.413 12.213 11.968 0.000 0.581 8.136 0.000 -2.486 0.000 -0.994 -0.000
T S2 APARTMENT 0.041 -35.443 0.000 0.000 3.558 2.413 12.213 11.967 0.000 0.581 8.148 0.000 -2.485 0.000 -0.994 -0.000
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.487 0.000 0.084 0.000 0.000 -0.416 0.000 -0.077 -17.148
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 1.609 0.000 6.242 0.001 0.000 -0.974 0.000 -6.505 -23.707
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.511 0.000 0.070 0.000 0.000 -0.474 0.000 -0.066 -17.111
Total Facility 12.891 -976.552 0.000 0.000 82.623 128.627 294.692 297.317 0.000 20.204 391.375 0.000 -80.685 0.000 -27.920 -142.575


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 06-JUN-16:02 0.00 -3040.70 0.00 0.00 84.76 144.04 588.62 2404.08 0.00 164.17 0.00 0.00 0.00 0.00 0.00 -344.96
G NW APARTMENT 06-JUN-16:25 0.00 -3051.01 0.00 0.00 84.76 144.04 588.62 2483.87 0.00 149.84 0.00 0.00 0.00 0.00 0.00 -400.11
OFFICE 07-MAY-06:01 0.00 -7558.25 0.00 0.00 0.00 379.58 194.98 314.45 0.00 10.55 6658.69 0.00 0.00 0.00 0.00 0.00
G NE APARTMENT 12-JUN-17:08 0.00 -2459.94 0.00 0.00 141.80 194.45 588.62 1352.39 0.00 59.07 123.60 0.00 0.00 0.00 0.00 0.00
G N1 APARTMENT 12-JUN-17:03 0.00 -1869.63 0.00 0.00 141.80 194.45 588.62 927.15 0.00 35.63 0.00 0.00 0.00 0.00 0.00 -18.03
G N2 APARTMENT 12-JUN-17:03 0.00 -1860.37 0.00 0.00 141.80 194.45 588.62 927.35 0.00 35.63 0.00 0.00 0.00 0.00 0.00 -27.49
G S1 APARTMENT 27-SEP-14:15 0.00 -1894.47 0.00 0.00 40.75 50.41 400.26 1579.47 0.00 48.19 0.00 0.00 0.00 0.00 0.00 -224.62
G S2 APARTMENT 22-SEP-14:15 0.00 -1919.44 0.00 0.00 40.75 50.41 400.26 1438.81 0.00 53.92 0.00 0.00 0.00 0.00 0.00 -64.72
M SW APARTMENT 05-MAY-16:02 0.00 -7365.95 0.00 0.00 84.76 144.04 588.62 2332.67 0.00 290.16 3925.71 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 06-JUN-16:02 0.00 -7327.49 0.00 0.00 84.76 144.04 588.62 2529.32 0.00 235.68 3745.07 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 15-APR-14:15 0.00 -6131.47 0.00 0.00 40.75 50.41 400.26 1820.55 0.00 303.05 3516.45 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 06-JUN-16:02 0.00 -6040.61 0.00 0.00 84.76 144.04 588.62 1457.72 0.00 235.68 3529.79 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 12-JUN-17:12 0.00 -4473.58 0.00 0.00 141.80 194.45 588.62 923.36 0.00 51.15 2574.20 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 12-JUN-17:12 0.00 -4458.91 0.00 0.00 141.80 194.45 588.62 923.49 0.00 51.15 2559.39 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 17-OCT-14:15 0.00 -4942.10 0.00 0.00 40.75 50.41 400.26 1772.34 0.00 74.50 2603.83 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 17-OCT-14:15 0.00 -4943.21 0.00 0.00 40.75 50.41 400.26 1772.31 0.00 74.50 2604.97 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 06-JUN-16:02 0.00 -4683.44 0.00 0.00 84.76 144.04 588.62 2325.28 0.00 311.09 1229.66 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 06-JUN-16:02 0.00 -4702.61 0.00 0.00 84.76 144.04 588.62 2462.87 0.00 311.09 1111.23 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 15-APR-14:15 0.00 -4007.73 0.00 0.00 40.75 50.41 400.26 1767.49 0.00 399.83 1348.99 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 06-JUN-16:02 0.00 -3899.76 0.00 0.00 84.76 144.04 588.62 1414.65 0.00 311.09 1356.60 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 06-JUN-16:02 0.00 -3079.62 0.00 0.00 84.76 144.04 588.62 925.53 0.00 187.65 1149.01 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 06-JUN-16:02 0.00 -3064.96 0.00 0.00 84.76 144.04 588.62 925.84 0.00 187.65 1134.04 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 02-OCT-14:15 0.00 -3201.70 0.00 0.00 40.75 50.41 400.26 1631.47 0.00 49.51 1029.30 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 02-OCT-13:30 0.00 -3206.35 0.00 0.00 40.75 28.81 382.60 1832.86 0.00 42.30 879.03 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JUN-16:07 0.00 -90873.45 0.00 0.00 1949.43 5316.35 14137.32 33834.46 0.00 9960.14 25675.76 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 08-JAN-07:01 1126.66 0.00 0.00 0.00 162.69 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -722.84 0.00 0.00 -1042.74
G NW APARTMENT 02-JAN-04:00 352.91 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -679.53 0.00 0.00 -101.13
OFFICE 03-JAN-07:01 1955.68 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -738.16 0.00 -20.12 -1771.96
G NE APARTMENT 06-JAN-08:02 451.16 0.00 0.00 0.00 74.03 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -36.96 0.00 -2.48 -917.45
G N1 APARTMENT 01-JAN-07:01 1054.57 0.00 0.00 0.00 162.98 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -394.79 0.00 0.00 -1299.00
G N2 APARTMENT 02-JAN-07:01 1039.53 0.00 0.00 0.00 163.06 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -407.11 0.00 0.00 -1271.71
G S1 APARTMENT 19-FEB-24:00 81.89 0.00 0.00 0.00 162.99 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -129.11 0.00 -3.78 -489.40
G S2 APARTMENT 01-FEB-15:00 69.89 0.00 0.00 0.00 40.75 28.81 382.60 488.89 0.00 0.00 0.00 0.00 0.00 0.00 -63.19 -947.75
M SW APARTMENT 29-DEC-18:00 266.53 0.00 0.00 0.00 84.76 144.04 588.62 0.00 0.00 0.00 215.59 0.00 -738.46 0.00 -561.07 0.00
M NW APARTMENT 24-DEC-12:30 428.39 0.00 0.00 0.00 41.20 28.81 406.15 342.28 0.00 0.00 0.00 0.00 0.00 0.00 -118.09 -1128.73
M SE APARTMENT 29-DEC-17:00 225.75 0.00 0.00 0.00 48.90 100.83 470.90 0.00 0.00 0.00 400.44 0.00 -737.40 0.00 -509.42 0.00
M NE APARTMENT 04-JAN-14:15 379.33 0.00 0.00 0.00 40.89 28.81 382.60 308.88 0.00 0.00 0.00 0.00 0.00 0.00 -75.77 -1064.74
M N1 APARTMENT 04-JAN-13:45 221.61 0.00 0.00 0.00 41.04 28.81 388.49 196.36 0.00 0.00 0.00 0.00 0.00 0.00 -78.99 -797.32
M N2 APARTMENT 04-JAN-13:45 221.54 0.00 0.00 0.00 41.06 28.81 388.49 196.56 0.00 0.00 0.00 0.00 0.00 0.00 -78.71 -797.75
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 03-JAN-07:00 593.86 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -764.25 0.00 -35.04 -402.93
T NW APARTMENT 03-JAN-07:00 732.19 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -754.39 0.00 -35.04 -551.11
T SE APARTMENT 03-JAN-07:00 603.16 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -756.17 0.00 -35.04 -420.30
T NE APARTMENT 02-JAN-05:00 761.01 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -671.75 0.00 0.00 -545.81
T N1 APARTMENT 02-JAN-05:00 400.90 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -411.74 0.00 0.00 -445.72
T N2 APARTMENT 02-JAN-05:00 406.09 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -411.58 0.00 0.00 -451.07
T S1 APARTMENT 21-JAN-07:01 1186.17 0.00 0.00 0.00 162.38 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -443.98 0.00 0.00 -1380.80
T S2 APARTMENT 08-JAN-07:01 1195.97 0.00 0.00 0.00 162.31 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -436.17 0.00 0.00 -1398.34
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-07:01 3787.33 0.00 0.00 0.00 3654.50 4156.84 9398.91 0.00 0.00 0.00 909.45 0.00 -13627.16 0.00 -8279.87 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Sec1.1A-General Information

Data
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 7.75
Number of hours cooling loads not met 1.75
Number of hours not met 9.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 3.74 9905.98 0.00 0.00
Space Cooling 421.34 35966.53 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 287.25 9108.76 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 296.75 15912.74 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1721.20   3.74   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1721.20
Natural Gas 0.00 3.74
Additional 0.00 0.00
Total 511.42 1724.94


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 134.42
Fans-Interior 91.64
Service Water Heating 94.67
Receptacle Equipment 163.15
Miscellaneous 12.58
Subtotal 549.10


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.19
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 1.19


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 9.57
Space Heating 0.22
Space Cooling 24.43
Fans-Interior 16.65
Service Water Heating 17.20
Receptacle Equipment 29.65
Miscellaneous 2.29



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.244085
G NW APARTMENT DIRECT AIR 0.247491
OFFICE DIRECT AIR 0.501396
G NE APARTMENT DIRECT AIR 0.210608
G N1 APARTMENT DIRECT AIR 0.159356
G N2 APARTMENT DIRECT AIR 0.158793
G S1 APARTMENT DIRECT AIR 0.152624
G S2 APARTMENT DIRECT AIR 0.153655
M SW APARTMENT DIRECT AIR 0.595947
M NW APARTMENT DIRECT AIR 0.604108
M SE APARTMENT DIRECT AIR 0.526512
M NE APARTMENT DIRECT AIR 0.528490
M N1 APARTMENT DIRECT AIR 0.397555
M N2 APARTMENT DIRECT AIR 0.396654
M S1 APARTMENT DIRECT AIR 0.381446
M S2 APARTMENT DIRECT AIR 0.380556
T SW APARTMENT DIRECT AIR 0.379700
T NW APARTMENT DIRECT AIR 0.381855
T SE APARTMENT DIRECT AIR 0.344757
T NE APARTMENT DIRECT AIR 0.337123
T N1 APARTMENT DIRECT AIR 0.262156
T N2 APARTMENT DIRECT AIR 0.261242
T S1 APARTMENT DIRECT AIR 0.262896
T S2 APARTMENT DIRECT AIR 0.263031


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.244085
SPLIT GNW MAIN BRANCH 0.247491
SPLIT OFFICE MAIN BRANCH 0.501396
SPLIT GNE MAIN BRANCH 0.210608
SPLIT GN1 MAIN BRANCH 0.159356
SPLIT GN2 MAIN BRANCH 0.158793
SPLIT GS1 MAIN BRANCH 0.152624
SPLIT GS2 MAIN BRANCH 0.153655
SPLIT MSW MAIN BRANCH 0.595947
SPLIT MNW MAIN BRANCH 0.604108
SPLIT MSE MAIN BRANCH 0.526512
SPLIT MNE MAIN BRANCH 0.528490
SPLIT MN1 MAIN BRANCH 0.397555
SPLIT MN2 MAIN BRANCH 0.396654
SPLIT MS1 MAIN BRANCH 0.381446
SPLIT MS2 MAIN BRANCH 0.380556
SPLIT TSW MAIN BRANCH 0.379700
SPLIT TNW MAIN BRANCH 0.381855
SPLIT TSE MAIN BRANCH 0.344757
SPLIT TNE MAIN BRANCH 0.337123
SPLIT TN1 MAIN BRANCH 0.262156
SPLIT TN2 MAIN BRANCH 0.261242
SPLIT TS1 MAIN BRANCH 0.262896
SPLIT TS2 MAIN BRANCH 0.263031


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.244085
SPLIT GNW 0.247491
SPLIT OFFICE 0.501396
SPLIT GNE 0.210608
SPLIT GN1 0.159356
SPLIT GN2 0.158793
SPLIT GS1 0.152624
SPLIT GS2 0.153655
SPLIT MSW 0.595947
SPLIT MNW 0.604108
SPLIT MSE 0.526512
SPLIT MNE 0.528490
SPLIT MN1 0.397555
SPLIT MN2 0.396654
SPLIT MS1 0.381446
SPLIT MS2 0.380556
SPLIT TSW 0.379700
SPLIT TNW 0.381855
SPLIT TSE 0.344757
SPLIT TNE 0.337123
SPLIT TN1 0.262156
SPLIT TN2 0.261242
SPLIT TS1 0.262896
SPLIT TS2 0.263031


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.244085 0.026898
SPLIT GNW OA CONTROLLER 0.247491 0.025953
SPLIT OFFICE OA CONTROLLER 0.501396 0.038104
SPLIT GNE OA CONTROLLER 0.210608 0.025953
SPLIT GN1 OA CONTROLLER 0.159356 0.025953
SPLIT GN2 OA CONTROLLER 0.158793 0.025953
SPLIT GS1 OA CONTROLLER 0.152624 0.025953
SPLIT GS2 OA CONTROLLER 0.153655 0.025953
SPLIT MSW OA CONTROLLER 0.595947 0.051906
SPLIT MNW OA CONTROLLER 0.604108 0.051906
SPLIT MSE OA CONTROLLER 0.526512 0.051906
SPLIT MNE OA CONTROLLER 0.528490 0.051906
SPLIT MN1 OA CONTROLLER 0.397555 0.051906
SPLIT MN2 OA CONTROLLER 0.396654 0.051906
SPLIT MS1 OA CONTROLLER 0.381446 0.051906
SPLIT MS2 OA CONTROLLER 0.380556 0.051906
SPLIT TSW OA CONTROLLER 0.379700 0.025953
SPLIT TNW OA CONTROLLER 0.381855 0.025953
SPLIT TSE OA CONTROLLER 0.344757 0.025953
SPLIT TNE OA CONTROLLER 0.337123 0.025953
SPLIT TN1 OA CONTROLLER 0.262156 0.025953
SPLIT TN2 OA CONTROLLER 0.261242 0.025953
SPLIT TS1 OA CONTROLLER 0.262896 0.025953
SPLIT TS2 OA CONTROLLER 0.263031 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.244085 4787.41 0.741293
SPLIT GNW COOLING COIL 0.247491 4827.14 0.743034
SPLIT OFFICE COOLING COIL 0.501396 8586.16 0.786397
SPLIT GNE COOLING COIL 0.210608 4138.71 0.740701
SPLIT GN1 COOLING COIL 0.159356 3225.69 0.731662
SPLIT GN2 COOLING COIL 0.158793 3216.07 0.731495
SPLIT GS1 COOLING COIL 0.152624 3110.44 0.729629
SPLIT GS2 COOLING COIL 0.153655 3089.66 0.733669
SPLIT MSW COOLING COIL 0.595947 11406.94 0.748959
SPLIT MNW COOLING COIL 0.604108 11506.03 0.750537
SPLIT MSE COOLING COIL 0.526512 10449.59 0.737649
SPLIT MNE COOLING COIL 0.528490 10168.75 0.747302
SPLIT MN1 COOLING COIL 0.397555 7801.55 0.741133
SPLIT MN2 COOLING COIL 0.396654 7786.21 0.741040
SPLIT MS1 COOLING COIL 0.381446 7527.09 0.739417
SPLIT MS2 COOLING COIL 0.380556 7511.93 0.739318
SPLIT TSW COOLING COIL 0.379700 7165.97 0.753476
SPLIT TNW COOLING COIL 0.381855 7178.43 0.754743
SPLIT TSE COOLING COIL 0.344757 6661.12 0.745991
SPLIT TNE COOLING COIL 0.337123 6508.76 0.746226
SPLIT TN1 COOLING COIL 0.262156 5082.05 0.744944
SPLIT TN2 COOLING COIL 0.261242 5066.30 0.744822
SPLIT TS1 COOLING COIL 0.262896 5213.79 0.737876
SPLIT TS2 COOLING COIL 0.263031 5216.14 0.737895


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.244085 0.244085 0.244085 0.244085 1386.44 4787.41 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.247491 0.247491 0.247491 0.247491 1337.71 4827.14 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.501396 0.501396 0.501396 0.501396 2768.38 8586.16 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.210608 0.210608 0.210608 0.210608 1337.71 4138.71 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.159356 0.159356 0.159356 0.159356 1337.71 3225.69 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.158793 0.158793 0.158793 0.158793 1337.71 3216.07 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.152624 0.152624 0.152624 0.152624 1337.71 3110.44 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.153655 0.153655 0.153655 0.153655 1337.71 3089.66 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.595947 0.595947 0.595947 0.595947 2675.42 11406.94 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.604108 0.604108 0.604108 0.604108 2675.42 11506.03 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.526512 0.526512 0.526512 0.526512 2675.42 10449.59 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.528490 0.528490 0.528490 0.528490 2675.42 10168.75 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.397555 0.397555 0.397555 0.397555 2675.42 7801.55 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.396654 0.396654 0.396654 0.396654 2675.42 7786.21 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.381446 0.381446 0.381446 0.381446 2675.42 7527.09 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.380556 0.380556 0.380556 0.380556 2675.42 7511.93 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.379700 0.379700 0.379700 0.379700 1908.62 7165.97 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.381855 0.381855 0.381855 0.381855 1909.49 7178.43 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.344757 0.344757 0.344757 0.344757 1903.43 6661.12 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.337123 0.337123 0.337123 0.337123 1904.30 6508.76 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.262156 0.262156 0.262156 0.262156 1424.96 5082.05 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.261242 0.261242 0.261242 0.261242 1424.81 5066.30 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.262896 0.262896 0.262896 0.262896 1422.53 5213.79 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.263031 0.263031 0.263031 0.263031 1422.38 5216.14 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.244085
SPLIT GNW SUPPLY FAN 0.247491
SPLIT OFFICE SUPPLY FAN 0.501396
SPLIT GNE SUPPLY FAN 0.210608
SPLIT GN1 SUPPLY FAN 0.159356
SPLIT GN2 SUPPLY FAN 0.158793
SPLIT GS1 SUPPLY FAN 0.152624
SPLIT GS2 SUPPLY FAN 0.153655
SPLIT MSW SUPPLY FAN 0.595947
SPLIT MNW SUPPLY FAN 0.604108
SPLIT MSE SUPPLY FAN 0.526512
SPLIT MNE SUPPLY FAN 0.528490
SPLIT MN1 SUPPLY FAN 0.397555
SPLIT MN2 SUPPLY FAN 0.396654
SPLIT MS1 SUPPLY FAN 0.381446
SPLIT MS2 SUPPLY FAN 0.380556
SPLIT TSW SUPPLY FAN 0.379700
SPLIT TNW SUPPLY FAN 0.381855
SPLIT TSE SUPPLY FAN 0.344757
SPLIT TNE SUPPLY FAN 0.337123
SPLIT TN1 SUPPLY FAN 0.262156
SPLIT TN2 SUPPLY FAN 0.261242
SPLIT TS1 SUPPLY FAN 0.262896
SPLIT TS2 SUPPLY FAN 0.263031


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1386.44
SPLIT GNW HEATING COIL 1337.71
SPLIT OFFICE HEATING COIL 2768.38
SPLIT GNE HEATING COIL 1337.71
SPLIT GN1 HEATING COIL 1337.71
SPLIT GN2 HEATING COIL 1337.71
SPLIT GS1 HEATING COIL 1337.71
SPLIT GS2 HEATING COIL 1337.71
SPLIT MSW HEATING COIL 2675.42
SPLIT MNW HEATING COIL 2675.42
SPLIT MSE HEATING COIL 2675.42
SPLIT MNE HEATING COIL 2675.42
SPLIT MN1 HEATING COIL 2675.42
SPLIT MN2 HEATING COIL 2675.42
SPLIT MS1 HEATING COIL 2675.42
SPLIT MS2 HEATING COIL 2675.42
SPLIT TSW HEATING COIL 1908.62
SPLIT TNW HEATING COIL 1909.49
SPLIT TSE HEATING COIL 1903.43
SPLIT TNE HEATING COIL 1904.30
SPLIT TN1 HEATING COIL 1424.96
SPLIT TN2 HEATING COIL 1424.81
SPLIT TS1 HEATING COIL 1422.53
SPLIT TS2 HEATING COIL 1422.38



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.10 13.39
February 23.62 16.97
March 24.25 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.11 19.63
December 23.39 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 23.10 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 13.39
February 23.32 16.97
March 24.18 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 23.91 19.63
December 22.81 14.52
     
Annual Sum or Average 23.96 24.88
Minimum of Months 22.54 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.55 13.39
February 24.41 16.97
March 25.61 22.37
April 26.83 29.13
May 27.25 32.98
June 27.57 33.60
July 27.61 31.67
August 27.37 30.03
September 27.47 28.75
October 26.36 25.09
November 25.33 19.63
December 23.93 14.52
     
Annual Sum or Average 26.11 24.88
Minimum of Months 23.55 13.39
Maximum of Months 27.61 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 13.39
February 23.32 16.97
March 24.17 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 23.89 19.63
December 22.74 14.52
     
Annual Sum or Average 23.95 24.88
Minimum of Months 22.46 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 13.39
February 23.22 16.97
March 24.14 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 23.88 19.63
December 22.69 14.52
     
Annual Sum or Average 23.93 24.88
Minimum of Months 22.39 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 13.39
February 23.22 16.97
March 24.14 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 23.88 19.63
December 22.68 14.52
     
Annual Sum or Average 23.92 24.88
Minimum of Months 22.39 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.16 13.39
February 23.66 16.97
March 24.23 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.13 19.63
December 23.49 14.52
     
Annual Sum or Average 24.12 24.88
Minimum of Months 23.16 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.17 13.39
February 23.68 16.97
March 24.24 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.15 19.63
December 23.50 14.52
     
Annual Sum or Average 24.13 24.88
Minimum of Months 23.17 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 13.39
February 24.34 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.29 14.52
     
Annual Sum or Average 24.37 24.88
Minimum of Months 24.17 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.82 13.39
February 24.25 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.39 19.63
December 24.08 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.82 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 13.39
February 24.33 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.27 14.52
     
Annual Sum or Average 24.36 24.88
Minimum of Months 24.14 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.80 13.39
February 24.24 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.38 19.63
December 24.06 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.80 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.00 13.39
February 24.32 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.22 14.52
     
Annual Sum or Average 24.34 24.88
Minimum of Months 24.00 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.00 13.39
February 24.32 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.22 14.52
     
Annual Sum or Average 24.34 24.88
Minimum of Months 24.00 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 13.39
February 24.38 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.37 14.52
     
Annual Sum or Average 24.39 24.88
Minimum of Months 24.29 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 13.39
February 24.38 16.97
March 24.40 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.40 19.63
December 24.37 14.52
     
Annual Sum or Average 24.39 24.88
Minimum of Months 24.29 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.51 13.39
February 23.96 16.97
March 24.38 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.28 19.63
December 23.66 14.52
     
Annual Sum or Average 24.22 24.88
Minimum of Months 23.51 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 13.39
February 23.79 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.20 19.63
December 23.33 14.52
     
Annual Sum or Average 24.14 24.88
Minimum of Months 23.19 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 13.39
February 23.94 16.97
March 24.38 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.26 19.63
December 23.64 14.52
     
Annual Sum or Average 24.21 24.88
Minimum of Months 23.50 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 13.39
February 23.80 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.17 19.63
December 23.33 14.52
     
Annual Sum or Average 24.14 24.88
Minimum of Months 23.19 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 13.39
February 23.86 16.97
March 24.37 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.23 19.63
December 23.41 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.21 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 13.39
February 23.86 16.97
March 24.37 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.23 19.63
December 23.41 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.21 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.62 13.39
February 24.05 16.97
March 24.39 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.32 19.63
December 23.81 14.52
     
Annual Sum or Average 24.25 24.88
Minimum of Months 23.62 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.62 13.39
February 24.05 16.97
March 24.39 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.40 25.09
November 24.32 19.63
December 23.81 14.52
     
Annual Sum or Average 24.25 24.88
Minimum of Months 23.62 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 13.39
February 25.31 16.97
March 26.55 22.37
April 27.46 29.13
May 27.94 32.98
June 28.00 33.60
July 27.86 31.67
August 27.67 30.03
September 27.41 28.75
October 26.93 25.09
November 25.99 19.63
December 24.58 14.52
     
Annual Sum or Average 26.67 24.88
Minimum of Months 24.22 13.39
Maximum of Months 28.00 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 13.39
February 23.51 16.97
March 25.13 22.37
April 26.79 29.13
May 27.62 32.98
June 28.37 33.60
July 28.08 31.67
August 27.75 30.03
September 27.52 28.75
October 26.13 25.09
November 24.61 19.63
December 22.84 14.52
     
Annual Sum or Average 25.90 24.88
Minimum of Months 22.31 13.39
Maximum of Months 28.37 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.85 13.39
February 26.41 16.97
March 26.91 22.37
April 27.36 29.13
May 27.57 32.98
June 27.56 33.60
July 27.46 31.67
August 27.36 30.03
September 27.26 28.75
October 27.12 25.09
November 26.75 19.63
December 26.16 14.52
     
Annual Sum or Average 26.98 24.88
Minimum of Months 25.85 13.39
Maximum of Months 27.57 33.60



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:30

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.121006E+12 74834.112 14-JAN-18:15 8572.775 26456.413 9108.761 0.000 5856.411 2508.330 0.000 0.000 0.000 0.000 0.000 22331.422 0.000 0.000 0.000
February 0.114230E+12 80322.283 22-FEB-18:15 8572.775 26456.413 9108.761 0.000 11553.565 2508.330 0.000 0.000 0.000 0.000 0.000 22122.440 0.000 0.000 0.000
March 0.137170E+12 84654.625 28-MAR-17:15 8572.775 26456.413 9108.761 0.000 22309.380 0.000 0.000 0.000 0.000 0.000 0.000 18207.296 0.000 0.000 0.000
April 0.146945E+12 89479.280 28-APR-17:30 8572.775 26456.413 9108.761 0.000 28223.517 0.000 0.000 0.000 0.000 0.000 0.000 17117.814 0.000 0.000 0.000
May 0.162885E+12 93350.135 05-MAY-17:15 8572.775 26456.413 9108.761 0.000 33731.832 0.000 0.000 0.000 0.000 0.000 0.000 15480.354 0.000 0.000 0.000
June 0.162212E+12 95749.906 05-JUN-17:30 8572.775 26456.413 9108.761 0.000 34920.570 0.000 0.000 0.000 0.000 0.000 0.000 16691.387 0.000 0.000 0.000
July 0.166961E+12 96017.217 02-JUL-17:30 8572.775 26456.413 9108.761 0.000 35966.531 0.000 0.000 0.000 0.000 0.000 0.000 15912.737 0.000 0.000 0.000
August 0.163139E+12 92731.375 28-AUG-17:15 8572.775 26456.413 9108.761 0.000 30227.336 0.000 0.000 0.000 0.000 0.000 0.000 18366.090 0.000 0.000 0.000
September 0.152715E+12 91513.045 21-SEP-17:15 8572.775 26456.413 9108.761 0.000 27332.774 0.000 0.000 0.000 0.000 0.000 0.000 20042.323 0.000 0.000 0.000
October 0.144116E+12 87323.583 02-OCT-17:30 8572.775 26456.413 9108.761 0.000 22626.669 0.000 0.000 0.000 0.000 0.000 0.000 20558.965 0.000 0.000 0.000
November 0.127503E+12 78283.774 01-NOV-17:45 8572.775 26456.413 9108.761 0.000 12458.810 2508.330 0.000 0.000 0.000 0.000 0.000 19178.686 0.000 0.000 0.000
December 0.122323E+12 71817.437 27-DEC-18:30 8572.775 26456.413 9108.761 0.000 5857.078 2508.330 0.000 0.000 0.000 0.000 0.000 19314.081 0.000 0.000 0.000
                                     
Annual Sum or Average 0.172120E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.114230E+12 71817.437   8572.775 26456.413 9108.761 0.000 5856.411 0.000 0.000 0.000 0.000 0.000 0.000 15480.354 0.000 0.000 0.000
Maximum of Months 0.166961E+12 96017.217   8572.775 26456.413 9108.761 0.000 35966.531 2508.330 0.000 0.000 0.000 0.000 0.000 22331.422 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:30

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.256492E+10 9905.977 03-JAN-06:00 9905.977 0.000 0.000 0.000 0.000 0.000 9905.977
February 0.258739E+09 4079.127 02-FEB-06:00 4079.127 0.000 0.000 0.000 0.000 0.000 4079.127
March 0.000 0.000 01-MAR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.000 0.000 01-APR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 01-OCT-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.000 0.000 01-NOV-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.916578E+09 9153.974 23-DEC-04:00 9153.974 0.000 0.000 0.000 0.000 0.000 9153.974
                     
Annual Sum or Average 0.374024E+10       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.256492E+10 9905.977   9905.977 0.000 0.000 0.000 0.000 0.000 9905.977