Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2018-10-19 09:20:28


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1535.24 489.77 543.64
Net Site Energy 1535.24 489.77 543.64
Total Source Energy 4799.14 1531.01 1699.43
Net Source Energy 4799.14 1531.01 1699.43


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 30.23 0.00 0.00 0.00 0.00
Cooling 199.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 238.58 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 351.40 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1505.01 30.23 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 30.23 0.00 0.00 0.00 0.00
Cooling General 199.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.44 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 238.58 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 351.40 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.40 0.00 0.00 0.00 0.00 0.00
HVAC 279.45 10.70 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 532.94 10.70 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.22 0.00 0.00 0.00 0.00 0.00
HVAC 251.75 9.64 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 480.13 9.64 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1505.01 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1505.01 100.00
     
Total On-Site and Utility Electric Sources 1505.01 100.00
Total Electricity End Uses 1505.01 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 27.75
Time Setpoint Not Met During Occupied Cooling 1.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 751.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod El Paso International Ap Ut TX USA TMY3 WMO#=722700
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JUL-17:15 27-DEC-07:15 - - - 01-JAN-07:15
Heating 0.00 28542.98 0.00 0.00 0.00 0.00
Cooling 22280.92 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7565.25 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19149.85 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 84025.21 28542.98 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 28542.98 0.00 0.00 0.00 0.00
Cooling General 22280.92 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7565.25 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 19149.85 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 32.77 0.00 0.00 0.00
Cooling 630.79 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.92 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 755.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1112.87 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4766.37 32.77 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 11.60 0.00 0.00 0.00
Cooling 223.37 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 267.56 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 394.08 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1687.82 11.60 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 11.60 0.00 0.00 0.00
Cooling 223.37 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.23 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 267.56 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 394.08 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1687.82 11.60 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.62_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 2.848 0.287 0.200     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 2.848 0.287 0.200     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.848 0.287 0.200              
North Total or Average           112.97 2.848 0.287 0.200              
Non-North Total or Average           193.95 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.77 83.77 39.44
Exterior Lighting Total 2508.33           39.44



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3205.77 2560.31 645.47 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3204.89 2559.60 645.29 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8146.35 6506.12 1640.22 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2590.47 2068.89 521.58 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2093.23 1671.77 421.46 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2081.15 1662.12 419.03 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2042.14 1630.97 411.17 0.80 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2076.92 1658.74 418.18 0.80 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   8143.66 6503.98 1639.68 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8122.01 6486.68 1635.32 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   6918.74 5525.69 1393.05 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6795.03 5426.88 1368.14 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5425.79 4333.34 1092.45 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5405.61 4317.22 1088.39 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5333.47 4259.60 1073.87 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5313.38 4243.56 1069.82 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5390.20 4304.91 1085.29 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5307.39 4238.78 1068.62 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4799.58 3833.21 966.37 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4476.52 3575.20 901.32 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3636.06 2903.96 732.10 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3612.21 2884.91 727.30 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3838.12 3065.34 772.79 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3844.61 3070.51 774.09 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3054.0 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3053.2 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7760.7 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2467.8 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1994.1 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1982.6 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1945.5 3.13 10.67 11.09 10.38
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1978.6 3.13 10.67 11.09 10.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7758.1 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7737.5 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 6591.2 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6473.3 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5168.9 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5149.7 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5081.0 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5061.8 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5135.0 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5056.1 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4572.4 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4264.6 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3463.9 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3441.2 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3656.4 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3662.6 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1752.44 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1732.44 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   3438.36 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1737.15 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1503.38 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1503.38 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1503.38 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1503.38 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   3335.95 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   3358.43 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   3348.81 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   3371.28 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3006.76 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3006.76 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3006.76 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3006.76 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   2694.81 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   2707.94 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   2701.57 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   2714.70 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2131.78 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2131.98 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2116.68 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2116.88 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 216.92 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 216.86 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 551.23 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.29 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 141.64 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 140.82 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 138.18 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 140.54 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 551.05 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 549.58 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.42 468.16 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.41 459.79 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 367.14 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 365.77 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 360.89 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 359.53 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 364.73 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 359.13 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.77 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.91 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 246.04 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 244.42 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.71 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 260.15 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1787.35 2144.82 0.161 0.194 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
G NW APARTMENT 1786.86 2144.23 0.161 0.194 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 35.63 0.00682
OFFICE 4323.61 5188.34 0.410 0.492 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 32.05 0.00682
G NE APARTMENT 1444.29 1733.15 0.130 0.156 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
G N1 APARTMENT 1167.05 1400.46 0.105 0.126 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 34.01 0.00682
G N2 APARTMENT 1160.32 1392.38 0.105 0.126 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 34.01 0.00682
G S1 APARTMENT 1138.57 1366.29 0.103 0.123 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 34.01 0.00682
G S2 APARTMENT 1157.95 1389.55 0.105 0.125 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 33.03 0.00682
M SW APARTMENT 4540.44 5448.53 0.410 0.492 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
M NW APARTMENT 4528.36 5434.04 0.409 0.491 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 35.63 0.00682
M SE APARTMENT 3857.50 4629.00 0.348 0.418 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
M NE APARTMENT 3788.51 4546.21 0.342 0.410 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
M N1 APARTMENT 3025.09 3630.11 0.273 0.328 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 34.49 0.00682
M N2 APARTMENT 3013.84 3616.61 0.272 0.327 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 34.49 0.00682
M S1 APARTMENT 2973.62 3568.34 0.268 0.322 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
M S2 APARTMENT 2962.42 3554.90 0.267 0.321 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
T SW APARTMENT 3005.29 3606.35 0.271 0.326 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80 0.00682
T NW APARTMENT 2959.12 3550.94 0.267 0.321 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 36.28 0.00682
T SE APARTMENT 2676.00 3211.19 0.242 0.290 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
T NE APARTMENT 2495.87 2995.05 0.225 0.270 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 38.10 0.00682
T N1 APARTMENT 2027.25 2432.70 0.183 0.220 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 35.30 0.00682
T N2 APARTMENT 2013.96 2416.75 0.182 0.218 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 35.30 0.00682
T S1 APARTMENT 2139.92 2567.90 0.193 0.232 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 38.10 0.00682
T S2 APARTMENT 2143.53 2572.24 0.194 0.232 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 38.10 0.00682


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 839.84 1007.81 0.028 0.033 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
G NW APARTMENT 845.50 1014.59 0.028 0.034 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
OFFICE 2043.77 2452.53 0.065 0.078 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G NE APARTMENT 849.48 1019.38 0.028 0.034 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
G N1 APARTMENT 461.26 553.51 0.015 0.026 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
G N2 APARTMENT 461.36 553.63 0.015 0.026 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
G S1 APARTMENT 456.69 548.03 0.015 0.026 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
G S2 APARTMENT 531.86 638.24 0.018 0.026 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M SW APARTMENT 1581.99 1898.39 0.052 0.063 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M NW APARTMENT 1601.00 1921.20 0.053 0.064 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M SE APARTMENT 1592.86 1911.43 0.053 0.063 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M NE APARTMENT 1611.86 1934.24 0.053 0.064 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M N1 APARTMENT 631.57 757.88 0.021 0.052 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M N2 APARTMENT 631.90 758.28 0.021 0.052 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M S1 APARTMENT 611.55 733.86 0.020 0.052 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
M S2 APARTMENT 611.89 734.26 0.020 0.052 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T SW APARTMENT 1659.34 1991.21 0.055 0.066 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T NW APARTMENT 1670.45 2004.54 0.055 0.067 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T SE APARTMENT 1665.06 1998.07 0.055 0.066 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T NE APARTMENT 1676.17 2011.40 0.056 0.067 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T N1 APARTMENT 1183.20 1419.84 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T N2 APARTMENT 1183.37 1420.05 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T S1 APARTMENT 1170.44 1404.52 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281
T S2 APARTMENT 1170.60 1404.72 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -5.20 0.00281


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.19 0.19 0.03 0.03
SPLIT GNW 0.19 0.19 0.03 0.03
SPLIT OFFICE 0.49 0.49 0.08 0.08
SPLIT GNE 0.16 0.16 0.03 0.03
SPLIT GN1 0.13 0.13 0.03 0.03
SPLIT GN2 0.13 0.13 0.03 0.03
SPLIT GS1 0.12 0.12 0.03 0.03
SPLIT GS2 0.13 0.13 0.03 0.03
SPLIT MSW 0.49 0.49 0.06 0.06
SPLIT MNW 0.49 0.49 0.06 0.06
SPLIT MSE 0.42 0.42 0.06 0.06
SPLIT MNE 0.41 0.41 0.06 0.06
SPLIT MN1 0.33 0.33 0.05 0.05
SPLIT MN2 0.33 0.33 0.05 0.05
SPLIT MS1 0.32 0.32 0.05 0.05
SPLIT MS2 0.32 0.32 0.05 0.05
SPLIT TSW 0.33 0.33 0.07 0.07
SPLIT TNW 0.32 0.32 0.07 0.07
SPLIT TSE 0.29 0.29 0.07 0.07
SPLIT TNE 0.27 0.27 0.07 0.07
SPLIT TN1 0.22 0.22 0.05 0.05
SPLIT TN2 0.22 0.22 0.05 0.05
SPLIT TS1 0.23 0.23 0.05 0.05
SPLIT TS2 0.23 0.23 0.05 0.05



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2724.25 5167.25 227.50
G NW APARTMENT 2757.50 5476.50 404.00
OFFICE 698.50 1248.25 0.50
G NE APARTMENT 2759.00 5515.50 428.25
G N1 APARTMENT 2415.00 5756.00 366.25
G N2 APARTMENT 2417.00 5761.25 370.00
G S1 APARTMENT 2477.75 5452.00 249.25
G S2 APARTMENT 2549.25 5356.50 211.25
M SW APARTMENT 3516.25 2213.50 66.50
M NW APARTMENT 3243.00 3534.50 65.25
M SE APARTMENT 3478.75 2224.00 68.50
M NE APARTMENT 3238.50 3562.25 68.00
M N1 APARTMENT 3042.00 3545.00 79.25
M N2 APARTMENT 3041.75 3547.75 80.25
M S1 APARTMENT 3314.75 1633.25 82.75
M S2 APARTMENT 3315.50 1641.00 82.75
T SW APARTMENT 3776.50 3482.25 257.00
T NW APARTMENT 3760.25 4207.50 507.75
T SE APARTMENT 3789.75 3451.25 268.25
T NE APARTMENT 3787.50 4231.00 517.25
T N1 APARTMENT 3431.00 4301.00 370.50
T N2 APARTMENT 3434.25 4306.75 376.50
T S1 APARTMENT 3516.75 3437.50 171.50
T S2 APARTMENT 3518.25 3435.75 171.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4444.25 5814.50 751.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.50 0.00 3.50 0.00
G NW APARTMENT 3.75 0.50 3.75 0.50
OFFICE 0.00 19.50 0.00 0.00
G NE APARTMENT 7.25 0.00 7.25 0.00
G N1 APARTMENT 2.75 0.00 2.75 0.00
G N2 APARTMENT 2.50 0.25 2.50 0.25
G S1 APARTMENT 0.75 0.00 0.75 0.00
G S2 APARTMENT 1.50 0.00 1.50 0.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.50 0.00 0.50 0.00
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.00 0.00 0.00 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.00 0.00 0.00 0.00
T NW APARTMENT 0.00 0.25 0.00 0.25
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 1.75 0.00 1.75 0.00
T N2 APARTMENT 1.00 0.00 1.00 0.00
T S1 APARTMENT 1.50 0.00 1.50 0.00
T S2 APARTMENT 2.75 0.00 2.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 27.75 20.50 27.75 1.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.367 0.091 0.000 0.085
G NW APARTMENT 1.71 2.50 268.97 0.353 0.091 0.000 0.082
OFFICE 0.94 1.00 268.97 0.518 0.098 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.353 0.091 0.000 0.082
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.055 0.000 0.081
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.055 0.000 0.081
G S1 APARTMENT 1.71 2.50 268.97 0.354 0.055 0.000 0.085
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.055 0.000 0.085
M SW APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.105
M NW APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.103
M SE APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.105
M NE APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.102
M N1 APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.103
M N2 APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.103
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.105
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.105
T SW APARTMENT 1.71 2.50 268.97 0.354 0.173 0.000 0.126
T NW APARTMENT 1.71 2.50 268.97 0.354 0.172 0.000 0.123
T SE APARTMENT 1.71 2.50 268.97 0.354 0.173 0.000 0.126
T NE APARTMENT 1.71 2.50 268.97 0.354 0.172 0.000 0.123
T N1 APARTMENT 1.71 2.50 268.97 0.354 0.104 0.000 0.122
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.104 0.000 0.122
T S1 APARTMENT 1.71 2.50 268.97 0.354 0.104 0.000 0.126
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.104 0.000 0.126
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.356 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.505 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.382 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.377 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.381 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.376 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.379 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.379 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.385 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.385 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1505.01 20935.55 01-JAN-03:45 84025.21 26-JUL-17:15
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 351.40 0.00 01-JAN-00:15 32133.44 01-JAN-08:30
WaterSystems:Electricity 351.40 0.00 01-JAN-00:15 32133.44 01-JAN-08:30
Water Heater:WaterSystems:Electricity 351.40 0.00 01-JAN-00:15 32133.44 01-JAN-08:30
Fans:Electricity 238.58 7565.25 01-JAN-17:15 7565.25 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
ElectricityPurchased:Plant 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
Cogeneration:ElectricityPurchased 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
ElectricityNet:Plant 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
Cogeneration:ElectricityNet 1505.01 20935.55 16-JAN-04:00 84025.21 26-JUL-17:15
ExteriorLights:Electricity 39.44 0.00 01-JAN-07:15 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.44 0.00 01-JAN-07:15 2508.33 01-JAN-00:15
Electricity:HVAC 437.75 7565.25 28-JAN-08:30 30994.86 05-JUN-17:00
General:Fans:Electricity 238.58 7565.25 01-JAN-17:15 7565.25 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 199.18 0.00 01-JAN-03:45 23429.61 05-JUN-17:00


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 30.23 0.00 01-JAN-10:15 28542.98 27-DEC-07:15
Gas:HVAC 30.23 0.00 01-JAN-10:15 28542.98 27-DEC-07:15
Heating:Gas 30.23 0.00 01-JAN-10:15 28542.98 27-DEC-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1454.62 1469.55 04-MAY-06:00 147752.45 15-JUN-17:15
EnergyTransfer:Building 656.46 1469.55 04-MAY-06:00 65394.56 15-JUN-17:15
EnergyTransfer:Zone:G SW APARTMENT 13.60 0.00 01-MAY-03:45 2094.85 19-SEP-16:15
Heating:EnergyTransfer 17.82 0.00 01-JAN-09:00 11409.52 27-DEC-06:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.32 0.00 01-JAN-00:15 502.42 27-DEC-02:00
Cooling:EnergyTransfer 638.64 1.23 10-NOV-06:15 64695.39 15-JUN-17:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 13.28 0.00 02-JAN-06:00 2094.85 19-SEP-16:15
EnergyTransfer:Zone:G NW APARTMENT 11.56 0.00 20-NOV-11:00 2140.81 15-JUN-17:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.04 0.00 01-JAN-05:15 597.03 09-FEB-01:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 10.52 0.00 01-JAN-00:15 2140.81 15-JUN-17:15
EnergyTransfer:Zone:OFFICE 26.02 0.05 07-APR-02:30 3940.97 27-AUG-10:30
Heating:EnergyTransfer:Zone:OFFICE 5.07 0.00 01-JAN-00:15 855.11 05-JUN-17:45
Cooling:EnergyTransfer:Zone:OFFICE 20.94 0.00 01-JAN-02:45 3940.97 27-AUG-10:30
EnergyTransfer:Zone:G NE APARTMENT 11.65 0.04 26-OCT-21:45 1616.10 15-JUN-17:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.89 0.00 01-JAN-08:30 620.89 28-JAN-06:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 10.75 0.00 01-JAN-00:15 1616.10 15-JUN-17:15
EnergyTransfer:Zone:G N1 APARTMENT 9.06 0.00 26-MAY-02:00 1289.26 15-JUN-17:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.33 0.00 01-JAN-00:15 271.24 20-DEC-03:45
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 8.73 0.00 01-JAN-04:00 1289.26 15-JUN-17:30
EnergyTransfer:Zone:G N2 APARTMENT 9.06 0.02 03-OCT-03:30 1279.45 15-JUN-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.32 0.00 01-JAN-00:15 273.63 20-DEC-03:45
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 8.73 0.00 01-JAN-04:00 1279.45 15-JUN-17:30
EnergyTransfer:Zone:G S1 APARTMENT 11.60 0.04 05-MAY-00:15 1404.66 19-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.04 0.00 01-JAN-00:15 316.64 02-MAR-04:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 11.55 0.00 03-JAN-15:30 1404.66 19-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 12.13 0.03 10-APR-01:15 1417.91 19-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.04 0.00 01-JAN-00:15 312.60 02-MAR-04:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 12.09 0.00 03-JAN-15:30 1417.91 19-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 55.68 16.90 05-MAY-05:15 5276.73 19-SEP-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 239.10 10-NOV-06:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 55.67 0.00 31-JAN-16:30 5276.73 19-SEP-16:15
EnergyTransfer:Zone:M NW APARTMENT 42.30 0.03 13-JAN-12:00 5478.86 15-JUN-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.12 0.00 01-JAN-00:15 465.55 28-DEC-05:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 42.18 0.00 01-JAN-14:00 5478.86 15-JUN-17:15
EnergyTransfer:Zone:M SE APARTMENT 56.14 0.89 31-JAN-16:30 4478.13 19-SEP-13:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 160.79 10-NOV-06:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 56.14 0.00 31-JAN-16:30 4478.13 19-SEP-13:15
EnergyTransfer:Zone:M NE APARTMENT 42.94 0.09 28-MAR-12:00 4362.23 15-JUN-17:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.10 0.00 01-JAN-00:15 583.41 28-JAN-06:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 42.84 0.00 01-JAN-14:00 4362.23 15-JUN-17:15
EnergyTransfer:Zone:M N1 APARTMENT 37.45 0.20 03-JAN-19:15 3459.88 15-JUN-17:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.01 0.00 01-JAN-00:15 159.63 05-FEB-16:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 37.44 0.00 02-JAN-15:00 3459.88 15-JUN-17:30
EnergyTransfer:Zone:M N2 APARTMENT 37.45 0.14 10-DEC-15:45 3444.18 15-JUN-17:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.01 0.00 01-JAN-00:15 159.87 05-FEB-16:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 37.44 0.00 02-JAN-15:00 3444.18 15-JUN-17:30
EnergyTransfer:Zone:M S1 APARTMENT 51.67 2.66 10-NOV-07:00 3757.62 18-OCT-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 20.75 10-NOV-06:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 51.67 0.00 10-NOV-06:15 3757.62 18-OCT-13:30
EnergyTransfer:Zone:M S2 APARTMENT 51.68 4.11 10-NOV-07:00 3762.56 18-OCT-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 19.52 10-NOV-06:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 51.68 0.00 10-NOV-06:15 3762.56 18-OCT-13:30
EnergyTransfer:Zone:T SW APARTMENT 25.98 0.01 30-JAN-21:45 3418.70 15-JUN-16:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.17 0.00 01-JAN-00:15 1262.82 27-DEC-06:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 24.81 0.00 01-JAN-02:30 3418.70 15-JUN-16:30
EnergyTransfer:Zone:T NW APARTMENT 22.15 0.03 22-MAR-18:45 3522.68 15-JUN-17:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 2.43 0.00 01-JAN-00:15 1335.41 28-JAN-06:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 19.72 0.00 01-JAN-01:00 3522.68 15-JUN-17:15
EnergyTransfer:Zone:T SE APARTMENT 25.95 0.03 23-DEC-01:30 2906.37 19-SEP-13:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.10 0.00 01-JAN-00:15 1269.81 27-DEC-06:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 24.85 0.00 01-JAN-06:00 2906.37 19-SEP-13:15
EnergyTransfer:Zone:T NE APARTMENT 21.93 0.01 11-JAN-21:30 2803.96 15-JUN-17:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 2.17 0.00 01-JAN-08:45 1404.12 28-JAN-06:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 19.76 0.00 01-JAN-00:15 2803.96 15-JUN-17:15
EnergyTransfer:Zone:T N1 APARTMENT 17.74 0.01 21-DEC-11:00 2366.53 15-JUN-17:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 1.01 0.00 01-JAN-00:15 873.09 28-JAN-06:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 16.73 0.00 01-JAN-04:00 2366.53 15-JUN-17:15
EnergyTransfer:Zone:T N2 APARTMENT 17.76 0.01 29-NOV-14:45 2349.08 15-JUN-17:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 1.02 0.00 01-JAN-00:15 880.93 28-JAN-06:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 16.74 0.00 01-JAN-03:45 2349.08 15-JUN-17:15
EnergyTransfer:Zone:T S1 APARTMENT 22.48 0.00 11-DEC-13:15 2494.77 19-SEP-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.31 0.00 01-JAN-00:15 813.66 27-DEC-06:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 22.17 0.00 02-JAN-06:00 2494.77 19-SEP-14:15
EnergyTransfer:Zone:T S2 APARTMENT 22.50 0.00 08-APR-05:45 2498.93 19-SEP-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.31 0.00 01-JAN-00:15 813.71 27-DEC-06:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 22.19 0.00 02-JAN-06:00 2498.93 19-SEP-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 798.16 0.00 23-FEB-18:45 83081.14 15-JUN-17:00
HeatingCoils:EnergyTransfer 24.18 0.00 01-JAN-10:15 22834.38 27-DEC-07:15
CoolingCoils:EnergyTransfer 773.97 0.00 01-JAN-03:45 83081.14 15-JUN-17:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.318 -13.285 0.000 0.000 3.694 2.413 12.213 15.338 0.000 0.364 0.000 0.000 -4.921 0.000 -2.220 -13.915
G NW APARTMENT 1.040 -10.521 0.000 0.000 3.737 2.413 12.213 8.757 0.000 0.362 0.000 0.000 -4.990 0.000 -2.059 -10.953
OFFICE 5.074 -20.944 0.000 0.000 0.518 21.914 7.534 14.974 0.000 0.202 0.000 0.000 -5.235 0.000 -1.589 -22.449
G NE APARTMENT 0.893 -10.753 0.000 0.000 3.748 2.413 12.213 8.636 0.000 0.362 0.000 0.000 -4.747 0.000 -2.046 -10.720
G N1 APARTMENT 0.329 -8.729 0.000 0.000 3.748 2.413 12.213 3.166 0.000 0.235 0.000 0.000 -3.046 0.000 -1.464 -8.864
G N2 APARTMENT 0.325 -8.731 0.000 0.000 3.749 2.413 12.213 3.165 0.000 0.235 0.000 0.000 -3.044 0.000 -1.464 -8.860
G S1 APARTMENT 0.045 -11.551 0.000 0.000 3.693 2.413 12.213 9.820 0.000 0.235 0.000 0.000 -2.972 0.000 -1.642 -12.254
G S2 APARTMENT 0.042 -12.088 0.000 0.000 3.691 2.413 12.213 9.810 0.000 0.235 0.000 0.000 -2.979 0.000 -1.646 -11.691
M SW APARTMENT 0.004 -55.670 0.000 0.000 3.552 2.413 12.213 14.725 0.000 0.514 31.078 0.000 -5.622 0.000 -3.207 0.000
M NW APARTMENT 0.118 -42.178 0.000 0.000 3.597 2.413 12.213 8.259 0.000 0.512 23.931 0.000 -5.738 0.000 -3.126 0.000
M SE APARTMENT 0.001 -56.137 0.000 0.000 3.558 2.413 12.213 14.711 0.000 0.514 31.423 0.000 -5.492 0.000 -3.203 0.000
M NE APARTMENT 0.096 -42.841 0.000 0.000 3.608 2.413 12.213 8.110 0.000 0.512 24.459 0.000 -5.458 0.000 -3.113 0.000
M N1 APARTMENT 0.008 -37.440 0.000 0.000 3.577 2.413 12.213 2.882 0.000 0.328 21.914 0.000 -3.611 0.000 -2.284 0.000
M N2 APARTMENT 0.008 -37.443 0.000 0.000 3.578 2.413 12.213 2.881 0.000 0.328 21.913 0.000 -3.608 0.000 -2.283 0.000
M S1 APARTMENT 0.000 -51.673 0.000 0.000 3.535 2.413 12.213 9.428 0.000 0.331 29.506 0.000 -3.414 0.000 -2.339 0.000
M S2 APARTMENT 0.000 -51.677 0.000 0.000 3.536 2.413 12.213 9.428 0.000 0.331 29.508 0.000 -3.413 0.000 -2.339 0.000
T SW APARTMENT 1.173 -24.806 0.000 0.000 3.644 2.413 12.213 14.556 0.000 0.681 0.001 0.000 -5.201 0.000 -3.907 -0.765
T NW APARTMENT 2.425 -19.724 0.000 0.000 3.680 2.413 12.213 8.151 0.000 0.678 0.000 0.000 -5.277 0.000 -3.771 -0.789
T SE APARTMENT 1.098 -24.853 0.000 0.000 3.649 2.413 12.213 14.544 0.000 0.681 0.000 0.000 -5.084 0.000 -3.910 -0.751
T NE APARTMENT 2.170 -19.761 0.000 0.000 3.692 2.413 12.213 8.045 0.000 0.678 0.000 0.000 -5.041 0.000 -3.764 -0.644
T N1 APARTMENT 1.014 -16.727 0.000 0.000 3.681 2.413 12.213 2.866 0.000 0.437 0.040 0.000 -3.261 0.000 -2.675 -0.000
T N2 APARTMENT 1.022 -16.739 0.000 0.000 3.682 2.413 12.213 2.864 0.000 0.437 0.042 0.000 -3.258 0.000 -2.676 -0.000
T S1 APARTMENT 0.307 -22.173 0.000 0.000 3.631 2.413 12.213 9.339 0.000 0.440 0.000 0.000 -3.171 0.000 -2.811 -0.188
T S2 APARTMENT 0.310 -22.194 0.000 0.000 3.631 2.413 12.213 9.337 0.000 0.440 0.000 0.000 -3.170 0.000 -2.811 -0.169
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.204 0.000 0.047 0.000 0.000 -0.570 0.000 -0.559 -16.193
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.717 0.000 1.496 0.000 0.000 -1.456 0.000 -10.407 -13.685
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.209 0.000 0.041 0.000 0.000 -0.650 0.000 -0.475 -16.195
Total Facility 17.818 -638.636 0.000 0.000 84.412 128.627 294.692 214.922 0.000 11.657 213.815 0.000 -104.429 0.000 -73.790 -149.085


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 19-SEP-16:10 0.00 -2095.46 0.00 0.00 84.76 144.04 588.62 1900.00 0.00 27.88 0.00 0.00 0.00 0.00 0.00 -649.84
G NW APARTMENT 15-JUN-17:06 0.00 -2141.28 0.00 0.00 141.80 194.45 588.62 1873.20 0.00 168.89 0.00 0.00 0.00 0.00 0.00 -825.69
OFFICE 18-JUN-06:01 0.00 -7349.33 0.00 0.00 0.00 379.58 194.98 647.74 0.00 0.00 6149.65 0.00 0.00 0.00 -22.62 0.00
G NE APARTMENT 15-JUN-17:06 0.00 -1616.57 0.00 0.00 141.80 194.45 588.62 816.18 0.00 168.89 0.00 0.00 0.00 0.00 0.00 -293.38
G N1 APARTMENT 15-JUN-17:25 0.00 -1289.46 0.00 0.00 141.80 194.45 588.62 628.24 0.00 91.62 0.00 0.00 0.00 0.00 0.00 -355.28
G N2 APARTMENT 15-JUN-17:20 0.00 -1279.65 0.00 0.00 141.80 194.45 588.62 628.40 0.00 91.62 0.00 0.00 0.00 0.00 0.00 -365.25
G S1 APARTMENT 19-SEP-13:30 0.00 -1404.52 0.00 0.00 40.75 28.81 382.60 1513.53 0.00 32.77 0.00 0.00 0.00 0.00 0.00 -593.95
G S2 APARTMENT 19-SEP-13:30 0.00 -1417.76 0.00 0.00 40.75 28.81 382.60 1513.26 0.00 32.77 0.00 0.00 0.00 0.00 0.00 -580.44
M SW APARTMENT 19-SEP-16:15 0.00 -5278.96 0.00 0.00 84.76 144.04 588.62 1880.86 0.00 39.98 2540.69 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 15-JUN-17:06 0.00 -5480.38 0.00 0.00 141.80 194.45 588.62 1846.18 0.00 242.33 2467.00 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 19-SEP-13:15 0.00 -4477.78 0.00 0.00 40.75 28.81 382.60 1790.02 0.00 78.40 2157.21 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 15-JUN-17:06 0.00 -4363.74 0.00 0.00 141.80 194.45 588.62 804.28 0.00 242.33 2392.26 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 15-JUN-17:25 0.00 -3460.73 0.00 0.00 141.80 194.45 588.62 617.95 0.00 131.46 1786.45 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 15-JUN-17:25 0.00 -3445.04 0.00 0.00 141.80 194.45 588.62 618.04 0.00 131.46 1770.66 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 18-OCT-13:30 0.00 -3757.29 0.00 0.00 40.75 28.81 382.60 1651.62 0.00 19.48 1634.03 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 18-OCT-13:30 0.00 -3762.23 0.00 0.00 40.75 28.81 382.60 1651.59 0.00 19.48 1639.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 15-JUN-16:25 0.00 -3418.97 0.00 0.00 84.76 144.04 588.62 1714.38 0.00 339.63 547.54 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 15-JUN-17:06 0.00 -3523.08 0.00 0.00 141.80 194.45 588.62 1802.83 0.00 319.50 475.88 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 19-SEP-13:15 0.00 -2906.17 0.00 0.00 40.75 28.81 382.60 1749.52 0.00 103.22 601.26 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 15-JUN-17:06 0.00 -2804.31 0.00 0.00 141.80 194.45 588.62 781.05 0.00 319.50 778.88 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 15-JUN-17:06 0.00 -2366.98 0.00 0.00 141.80 194.45 588.62 588.28 0.00 192.72 661.10 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 15-JUN-17:06 0.00 -2349.53 0.00 0.00 141.80 194.45 588.62 588.52 0.00 192.72 643.40 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 19-SEP-14:15 0.00 -2494.55 0.00 0.00 40.75 50.41 400.26 1291.15 0.00 54.93 657.05 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 19-SEP-13:30 0.00 -2498.72 0.00 0.00 40.75 28.81 382.60 1465.98 0.00 61.88 518.70 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-JUN-17:06 0.00 -64046.08 0.00 0.00 3261.48 6475.86 14071.03 19878.98 0.00 5062.58 15296.15 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 03-DEC-07:01 1402.10 0.00 0.00 0.00 163.32 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -129.40 0.00 -14.28 -1897.96
G NW APARTMENT 28-FEB-07:01 1465.89 0.00 0.00 0.00 162.93 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -302.54 0.00 -88.67 -1713.83
OFFICE 10-JAN-07:01 3036.11 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -593.87 0.00 -172.21 -2844.60
G NE APARTMENT 05-FEB-07:14 632.22 0.00 0.00 0.00 161.22 93.63 382.60 167.40 0.00 0.00 0.00 0.00 0.00 0.00 -101.35 -1335.72
G N1 APARTMENT 11-JAN-07:01 1009.34 0.00 0.00 0.00 161.37 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -333.55 0.00 -91.32 -1222.07
G N2 APARTMENT 25-JAN-07:01 1214.66 0.00 0.00 0.00 163.21 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -247.52 0.00 -123.13 -1483.46
G S1 APARTMENT 27-JAN-06:25 714.67 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -447.36 0.00 -105.20 -770.46
G S2 APARTMENT 27-JAN-06:08 727.05 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -440.77 0.00 -99.53 -795.11
M SW APARTMENT 10-NOV-06:10 246.86 0.00 0.00 0.00 162.99 100.83 317.86 0.00 0.00 0.00 363.66 0.00 -263.77 0.00 -928.43 0.00
M NW APARTMENT 31-DEC-08:28 924.52 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -432.02 0.00 -169.17 -829.00
M SE APARTMENT 10-NOV-06:10 169.16 0.00 0.00 0.00 162.99 100.83 317.86 0.00 0.00 0.00 433.22 0.00 -263.04 0.00 -921.02 0.00
M NE APARTMENT 28-DEC-06:25 1078.93 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -695.70 0.00 0.00 -991.58
M N1 APARTMENT 05-FEB-16:00 159.62 0.00 0.00 0.00 41.50 50.41 400.26 36.46 0.00 0.00 0.00 0.00 0.00 0.00 -147.84 -540.41
M N2 APARTMENT 05-FEB-16:00 159.86 0.00 0.00 0.00 41.54 50.41 400.26 36.78 0.00 0.00 0.00 0.00 0.00 0.00 -146.96 -541.89
M S1 APARTMENT 10-NOV-06:10 24.26 0.00 0.00 0.00 162.99 100.83 317.86 0.00 0.00 0.00 382.10 0.00 -160.26 0.00 -827.77 0.00
M S2 APARTMENT 10-NOV-06:10 23.05 0.00 0.00 0.00 162.99 100.83 317.86 0.00 0.00 0.00 383.15 0.00 -160.25 0.00 -827.63 0.00
T SW APARTMENT 27-DEC-06:00 1262.80 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -696.85 0.00 -255.81 -846.54
T NW APARTMENT 28-JAN-06:00 1335.39 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -723.25 0.00 -449.39 -699.15
T SE APARTMENT 27-DEC-06:00 1269.79 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -704.64 0.00 -255.81 -845.75
T NE APARTMENT 28-JAN-06:00 1404.10 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -720.62 0.00 -449.39 -770.49
T N1 APARTMENT 17-JAN-07:01 1439.06 0.00 0.00 0.00 162.62 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -265.02 0.00 0.00 -1812.89
T N2 APARTMENT 26-DEC-18:01 1155.02 0.00 0.00 0.00 166.83 194.45 588.62 0.00 0.00 0.00 0.00 0.00 -301.32 0.00 0.00 -1803.61
T S1 APARTMENT 25-MAR-06:01 1642.50 0.00 0.00 0.00 162.81 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -284.41 0.00 -94.41 -1902.72
T S2 APARTMENT 27-DEC-06:00 813.70 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -429.98 0.00 -154.31 -765.81
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-DEC-07:01 9263.64 0.00 0.00 0.00 3702.63 4156.84 9398.91 0.00 0.00 0.00 162.75 0.00 -14387.37 0.00 -12297.40 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sec1.1A-General Information

Data
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 27.75
Number of hours cooling loads not met 1.00
Number of hours not met 28.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.44 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 30.23 28542.98 0.00 0.00
Space Cooling 199.18 22280.92 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 238.58 7565.25 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 351.40 19149.85 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1505.01   30.23   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1505.01
Natural Gas 0.00 30.23
Additional 0.00 0.00
Total 511.42 1535.24


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 63.54
Fans-Interior 76.11
Service Water Heating 112.10
Receptacle Equipment 163.15
Miscellaneous 12.58
Subtotal 480.13


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 9.64
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 9.64


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.75
Space Heating 1.97
Space Cooling 12.97
Fans-Interior 15.54
Service Water Heating 22.89
Receptacle Equipment 33.31
Miscellaneous 2.57



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.193661
G NW APARTMENT DIRECT AIR 0.193607
OFFICE DIRECT AIR 0.492121
G NE APARTMENT DIRECT AIR 0.156490
G N1 APARTMENT DIRECT AIR 0.126452
G N2 APARTMENT DIRECT AIR 0.125722
G S1 APARTMENT DIRECT AIR 0.123366
G S2 APARTMENT DIRECT AIR 0.125466
M SW APARTMENT DIRECT AIR 0.491959
M NW APARTMENT DIRECT AIR 0.490650
M SE APARTMENT DIRECT AIR 0.417961
M NE APARTMENT DIRECT AIR 0.410488
M N1 APARTMENT DIRECT AIR 0.327772
M N2 APARTMENT DIRECT AIR 0.326553
M S1 APARTMENT DIRECT AIR 0.322195
M S2 APARTMENT DIRECT AIR 0.320981
T SW APARTMENT DIRECT AIR 0.325622
T NW APARTMENT DIRECT AIR 0.320619
T SE APARTMENT DIRECT AIR 0.289943
T NE APARTMENT DIRECT AIR 0.270427
T N1 APARTMENT DIRECT AIR 0.219654
T N2 APARTMENT DIRECT AIR 0.218214
T S1 APARTMENT DIRECT AIR 0.231861
T S2 APARTMENT DIRECT AIR 0.232253


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.193661
SPLIT GNW MAIN BRANCH 0.193607
SPLIT OFFICE MAIN BRANCH 0.492121
SPLIT GNE MAIN BRANCH 0.156490
SPLIT GN1 MAIN BRANCH 0.126452
SPLIT GN2 MAIN BRANCH 0.125722
SPLIT GS1 MAIN BRANCH 0.123366
SPLIT GS2 MAIN BRANCH 0.125466
SPLIT MSW MAIN BRANCH 0.491959
SPLIT MNW MAIN BRANCH 0.490650
SPLIT MSE MAIN BRANCH 0.417961
SPLIT MNE MAIN BRANCH 0.410488
SPLIT MN1 MAIN BRANCH 0.327772
SPLIT MN2 MAIN BRANCH 0.326553
SPLIT MS1 MAIN BRANCH 0.322195
SPLIT MS2 MAIN BRANCH 0.320981
SPLIT TSW MAIN BRANCH 0.325622
SPLIT TNW MAIN BRANCH 0.320619
SPLIT TSE MAIN BRANCH 0.289943
SPLIT TNE MAIN BRANCH 0.270427
SPLIT TN1 MAIN BRANCH 0.219654
SPLIT TN2 MAIN BRANCH 0.218214
SPLIT TS1 MAIN BRANCH 0.231861
SPLIT TS2 MAIN BRANCH 0.232253


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.193661
SPLIT GNW 0.193607
SPLIT OFFICE 0.492121
SPLIT GNE 0.156490
SPLIT GN1 0.126452
SPLIT GN2 0.125722
SPLIT GS1 0.123366
SPLIT GS2 0.125466
SPLIT MSW 0.491959
SPLIT MNW 0.490650
SPLIT MSE 0.417961
SPLIT MNE 0.410488
SPLIT MN1 0.327772
SPLIT MN2 0.326553
SPLIT MS1 0.322195
SPLIT MS2 0.320981
SPLIT TSW 0.325622
SPLIT TNW 0.320619
SPLIT TSE 0.289943
SPLIT TNE 0.270427
SPLIT TN1 0.219654
SPLIT TN2 0.218214
SPLIT TS1 0.231861
SPLIT TS2 0.232253


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.193661 0.026898
SPLIT GNW OA CONTROLLER 0.193607 0.025953
SPLIT OFFICE OA CONTROLLER 0.492121 0.038104
SPLIT GNE OA CONTROLLER 0.156490 0.025953
SPLIT GN1 OA CONTROLLER 0.126452 0.025953
SPLIT GN2 OA CONTROLLER 0.125722 0.025953
SPLIT GS1 OA CONTROLLER 0.123366 0.025953
SPLIT GS2 OA CONTROLLER 0.125466 0.025953
SPLIT MSW OA CONTROLLER 0.491959 0.051906
SPLIT MNW OA CONTROLLER 0.490650 0.051906
SPLIT MSE OA CONTROLLER 0.417961 0.051906
SPLIT MNE OA CONTROLLER 0.410488 0.051906
SPLIT MN1 OA CONTROLLER 0.327772 0.051906
SPLIT MN2 OA CONTROLLER 0.326553 0.051906
SPLIT MS1 OA CONTROLLER 0.322195 0.051906
SPLIT MS2 OA CONTROLLER 0.320981 0.051906
SPLIT TSW OA CONTROLLER 0.325622 0.025953
SPLIT TNW OA CONTROLLER 0.320619 0.025953
SPLIT TSE OA CONTROLLER 0.289943 0.025953
SPLIT TNE OA CONTROLLER 0.270427 0.025953
SPLIT TN1 OA CONTROLLER 0.219654 0.025953
SPLIT TN2 OA CONTROLLER 0.218214 0.025953
SPLIT TS1 OA CONTROLLER 0.231861 0.025953
SPLIT TS2 OA CONTROLLER 0.232253 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.193661 3205.77 0.798655
SPLIT GNW COOLING COIL 0.193607 3204.89 0.798655
SPLIT OFFICE COOLING COIL 0.492121 8146.35 0.798655
SPLIT GNE COOLING COIL 0.156490 2590.47 0.798655
SPLIT GN1 COOLING COIL 0.126452 2093.23 0.798655
SPLIT GN2 COOLING COIL 0.125722 2081.15 0.798655
SPLIT GS1 COOLING COIL 0.123366 2042.14 0.798655
SPLIT GS2 COOLING COIL 0.125466 2076.92 0.798655
SPLIT MSW COOLING COIL 0.491959 8143.66 0.798655
SPLIT MNW COOLING COIL 0.490650 8122.01 0.798655
SPLIT MSE COOLING COIL 0.417961 6918.74 0.798655
SPLIT MNE COOLING COIL 0.410488 6795.03 0.798655
SPLIT MN1 COOLING COIL 0.327772 5425.79 0.798655
SPLIT MN2 COOLING COIL 0.326553 5405.61 0.798655
SPLIT MS1 COOLING COIL 0.322195 5333.47 0.798655
SPLIT MS2 COOLING COIL 0.320981 5313.38 0.798655
SPLIT TSW COOLING COIL 0.325622 5390.20 0.798655
SPLIT TNW COOLING COIL 0.320619 5307.39 0.798655
SPLIT TSE COOLING COIL 0.289943 4799.58 0.798655
SPLIT TNE COOLING COIL 0.270427 4476.52 0.798655
SPLIT TN1 COOLING COIL 0.219654 3636.06 0.798655
SPLIT TN2 COOLING COIL 0.218214 3612.21 0.798655
SPLIT TS1 COOLING COIL 0.231861 3838.12 0.798655
SPLIT TS2 COOLING COIL 0.232253 3844.61 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.193661 0.193661 0.193661 0.193661 1752.44 3205.77 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.193607 0.193607 0.193607 0.193607 1732.44 3204.89 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.492121 0.492121 0.492121 0.492121 3438.36 8146.35 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.156490 0.156490 0.156490 0.156490 1737.15 2590.47 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.126452 0.126452 0.126452 0.126452 1503.38 2093.23 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.125722 0.125722 0.125722 0.125722 1503.38 2081.15 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.123366 0.123366 0.123366 0.123366 1503.38 2042.14 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.125466 0.125466 0.125466 0.125466 1503.38 2076.92 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.491959 0.491959 0.491959 0.491959 3335.95 8143.66 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.490650 0.490650 0.490650 0.490650 3358.43 8122.01 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.417961 0.417961 0.417961 0.417961 3348.81 6918.74 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.410488 0.410488 0.410488 0.410488 3371.28 6795.03 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.327772 0.327772 0.327772 0.327772 3006.76 5425.79 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.326553 0.326553 0.326553 0.326553 3006.76 5405.61 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.322195 0.322195 0.322195 0.322195 3006.76 5333.47 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.320981 0.320981 0.320981 0.320981 3006.76 5313.38 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.325622 0.325622 0.325622 0.325622 2694.81 5390.20 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.320619 0.320619 0.320619 0.320619 2707.94 5307.39 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.289943 0.289943 0.289943 0.289943 2701.57 4799.58 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.270427 0.270427 0.270427 0.270427 2714.70 4476.52 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.219654 0.219654 0.219654 0.219654 2131.78 3636.06 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.218214 0.218214 0.218214 0.218214 2131.98 3612.21 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.231861 0.231861 0.231861 0.231861 2116.68 3838.12 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.232253 0.232253 0.232253 0.232253 2116.88 3844.61 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.193661
SPLIT GNW SUPPLY FAN 0.193607
SPLIT OFFICE SUPPLY FAN 0.492121
SPLIT GNE SUPPLY FAN 0.156490
SPLIT GN1 SUPPLY FAN 0.126452
SPLIT GN2 SUPPLY FAN 0.125722
SPLIT GS1 SUPPLY FAN 0.123366
SPLIT GS2 SUPPLY FAN 0.125466
SPLIT MSW SUPPLY FAN 0.491959
SPLIT MNW SUPPLY FAN 0.490650
SPLIT MSE SUPPLY FAN 0.417961
SPLIT MNE SUPPLY FAN 0.410488
SPLIT MN1 SUPPLY FAN 0.327772
SPLIT MN2 SUPPLY FAN 0.326553
SPLIT MS1 SUPPLY FAN 0.322195
SPLIT MS2 SUPPLY FAN 0.320981
SPLIT TSW SUPPLY FAN 0.325622
SPLIT TNW SUPPLY FAN 0.320619
SPLIT TSE SUPPLY FAN 0.289943
SPLIT TNE SUPPLY FAN 0.270427
SPLIT TN1 SUPPLY FAN 0.219654
SPLIT TN2 SUPPLY FAN 0.218214
SPLIT TS1 SUPPLY FAN 0.231861
SPLIT TS2 SUPPLY FAN 0.232253


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1752.44
SPLIT GNW HEATING COIL 1732.44
SPLIT OFFICE HEATING COIL 3438.36
SPLIT GNE HEATING COIL 1737.15
SPLIT GN1 HEATING COIL 1503.38
SPLIT GN2 HEATING COIL 1503.38
SPLIT GS1 HEATING COIL 1503.38
SPLIT GS2 HEATING COIL 1503.38
SPLIT MSW HEATING COIL 3335.95
SPLIT MNW HEATING COIL 3358.43
SPLIT MSE HEATING COIL 3348.81
SPLIT MNE HEATING COIL 3371.28
SPLIT MN1 HEATING COIL 3006.76
SPLIT MN2 HEATING COIL 3006.76
SPLIT MS1 HEATING COIL 3006.76
SPLIT MS2 HEATING COIL 3006.76
SPLIT TSW HEATING COIL 2694.81
SPLIT TNW HEATING COIL 2707.94
SPLIT TSE HEATING COIL 2701.57
SPLIT TNE HEATING COIL 2714.70
SPLIT TN1 HEATING COIL 2131.78
SPLIT TN2 HEATING COIL 2131.98
SPLIT TS1 HEATING COIL 2116.68
SPLIT TS2 HEATING COIL 2116.88



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.61 8.14
February 22.86 10.27
March 23.07 12.55
April 23.91 19.23
May 24.29 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.11 18.30
November 23.19 11.18
December 22.58 6.79
     
Annual Sum or Average 23.69 17.98
Minimum of Months 22.58 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 8.14
February 22.25 10.27
March 22.66 12.55
April 23.80 19.23
May 24.29 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 23.93 18.30
November 22.53 11.18
December 21.92 6.79
     
Annual Sum or Average 23.42 17.98
Minimum of Months 21.92 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.83 8.14
February 23.27 10.27
March 23.63 12.55
April 25.02 19.23
May 25.77 23.84
June 26.98 27.86
July 27.13 27.54
August 26.85 26.28
September 26.85 23.38
October 25.13 18.30
November 23.79 11.18
December 22.72 6.79
     
Annual Sum or Average 25.00 17.98
Minimum of Months 22.72 6.79
Maximum of Months 27.13 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 8.14
February 22.19 10.27
March 22.61 12.55
April 23.81 19.23
May 24.29 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 23.87 18.30
November 22.43 11.18
December 21.84 6.79
     
Annual Sum or Average 23.38 17.98
Minimum of Months 21.84 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 8.14
February 22.13 10.27
March 22.47 12.55
April 23.68 19.23
May 24.25 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 23.86 18.30
November 22.40 11.18
December 21.85 6.79
     
Annual Sum or Average 23.35 17.98
Minimum of Months 21.85 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 8.14
February 22.13 10.27
March 22.46 12.55
April 23.68 19.23
May 24.25 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 23.85 18.30
November 22.39 11.18
December 21.85 6.79
     
Annual Sum or Average 23.35 17.98
Minimum of Months 21.85 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.66 8.14
February 22.89 10.27
March 23.04 12.55
April 23.84 19.23
May 24.25 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.11 18.30
November 23.27 11.18
December 22.62 6.79
     
Annual Sum or Average 23.69 17.98
Minimum of Months 22.62 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.66 8.14
February 22.90 10.27
March 23.05 12.55
April 23.87 19.23
May 24.27 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.12 18.30
November 23.28 11.18
December 22.63 6.79
     
Annual Sum or Average 23.70 17.98
Minimum of Months 22.63 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.01 8.14
February 24.13 10.27
March 24.26 12.55
April 24.38 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.23 11.18
December 23.86 6.79
     
Annual Sum or Average 24.27 17.98
Minimum of Months 23.86 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.29 8.14
February 23.68 10.27
March 24.11 12.55
April 24.37 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 23.95 11.18
December 22.94 6.79
     
Annual Sum or Average 24.06 17.98
Minimum of Months 22.94 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.96 8.14
February 24.12 10.27
March 24.24 12.55
April 24.38 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.19 11.18
December 23.82 6.79
     
Annual Sum or Average 24.26 17.98
Minimum of Months 23.82 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.11 8.14
February 23.65 10.27
March 24.09 12.55
April 24.37 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.39 18.30
November 23.90 11.18
December 22.81 6.79
     
Annual Sum or Average 24.03 17.98
Minimum of Months 22.81 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.58 8.14
February 23.86 10.27
March 24.21 12.55
April 24.38 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.10 11.18
December 23.21 6.79
     
Annual Sum or Average 24.15 17.98
Minimum of Months 23.21 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.56 8.14
February 23.85 10.27
March 24.21 12.55
April 24.38 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.10 11.18
December 23.19 6.79
     
Annual Sum or Average 24.14 17.98
Minimum of Months 23.19 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 8.14
February 24.27 10.27
March 24.34 12.55
April 24.39 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.32 11.18
December 24.10 6.79
     
Annual Sum or Average 24.34 17.98
Minimum of Months 24.10 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 8.14
February 24.27 10.27
March 24.34 12.55
April 24.39 19.23
May 24.40 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.40 18.30
November 24.32 11.18
December 24.10 6.79
     
Annual Sum or Average 24.34 17.98
Minimum of Months 24.10 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 8.14
February 23.33 10.27
March 23.58 12.55
April 24.20 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.30 18.30
November 23.48 11.18
December 22.95 6.79
     
Annual Sum or Average 23.90 17.98
Minimum of Months 22.95 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.40 8.14
February 22.86 10.27
March 23.34 12.55
April 24.17 19.23
May 24.38 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.23 18.30
November 23.08 11.18
December 22.26 6.79
     
Annual Sum or Average 23.69 17.98
Minimum of Months 22.26 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 8.14
February 23.34 10.27
March 23.60 12.55
April 24.21 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.27 18.30
November 23.45 11.18
December 22.95 6.79
     
Annual Sum or Average 23.90 17.98
Minimum of Months 22.95 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.25 8.14
February 22.81 10.27
March 23.36 12.55
April 24.17 19.23
May 24.38 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.19 18.30
November 23.03 11.18
December 22.12 6.79
     
Annual Sum or Average 23.66 17.98
Minimum of Months 22.12 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.30 8.14
February 22.83 10.27
March 23.36 12.55
April 24.18 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.25 18.30
November 23.07 11.18
December 22.15 6.79
     
Annual Sum or Average 23.68 17.98
Minimum of Months 22.15 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 8.14
February 22.83 10.27
March 23.36 12.55
April 24.18 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.25 18.30
November 23.06 11.18
December 22.14 6.79
     
Annual Sum or Average 23.68 17.98
Minimum of Months 22.14 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 8.14
February 23.47 10.27
March 23.69 12.55
April 24.24 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.33 18.30
November 23.58 11.18
December 23.06 6.79
     
Annual Sum or Average 23.96 17.98
Minimum of Months 23.06 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 8.14
February 23.47 10.27
March 23.70 12.55
April 24.24 19.23
May 24.39 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.33 18.30
November 23.58 11.18
December 23.06 6.79
     
Annual Sum or Average 23.96 17.98
Minimum of Months 23.06 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.28 8.14
February 23.92 10.27
March 24.60 12.55
April 26.02 19.23
May 26.73 23.84
June 27.25 27.86
July 27.29 27.54
August 27.12 26.28
September 26.80 23.38
October 26.05 18.30
November 24.23 11.18
December 22.99 6.79
     
Annual Sum or Average 25.53 17.98
Minimum of Months 22.99 6.79
Maximum of Months 27.29 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.88 8.14
February 22.39 10.27
March 22.92 12.55
April 24.44 19.23
May 25.44 23.84
June 27.02 27.86
July 27.13 27.54
August 26.96 26.28
September 26.62 23.38
October 24.71 18.30
November 22.87 11.18
December 21.72 6.79
     
Annual Sum or Average 24.52 17.98
Minimum of Months 21.72 6.79
Maximum of Months 27.13 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.60 8.14
February 25.92 10.27
March 26.29 12.55
April 26.74 19.23
May 26.97 23.84
June 27.17 27.86
July 27.14 27.54
August 27.09 26.28
September 27.01 23.38
October 26.76 18.30
November 26.19 11.18
December 25.34 6.79
     
Annual Sum or Average 26.52 17.98
Minimum of Months 25.34 6.79
Maximum of Months 27.17 27.86



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.118238E+12 74448.041 12-JAN-18:45 8572.775 26456.413 7565.251 0.000 2398.580 2508.330 0.000 0.000 0.000 0.000 0.000 26946.692 0.000 0.000 0.000
February 0.107932E+12 74249.445 19-FEB-18:45 8572.775 26456.413 7565.251 0.000 5424.362 2508.330 0.000 0.000 0.000 0.000 0.000 23722.313 0.000 0.000 0.000
March 0.119804E+12 75011.258 26-MAR-17:30 8572.775 26456.413 7565.251 0.000 7531.209 0.000 0.000 0.000 0.000 0.000 0.000 24885.609 0.000 0.000 0.000
April 0.122648E+12 78501.291 19-APR-17:15 8572.775 26456.413 7565.251 0.000 15450.876 0.000 0.000 0.000 0.000 0.000 0.000 20455.976 0.000 0.000 0.000
May 0.132410E+12 80915.315 19-MAY-17:15 8572.775 26456.413 7565.251 0.000 19274.119 0.000 0.000 0.000 0.000 0.000 0.000 19046.756 0.000 0.000 0.000
June 0.136020E+12 82150.137 14-JUN-17:30 8572.775 26456.413 7565.251 0.000 22568.817 0.000 0.000 0.000 0.000 0.000 0.000 16986.882 0.000 0.000 0.000
July 0.142301E+12 84025.207 26-JUL-17:15 8572.775 26456.413 7565.251 0.000 22280.919 0.000 0.000 0.000 0.000 0.000 0.000 19149.848 0.000 0.000 0.000
August 0.138364E+12 82622.114 27-AUG-17:15 8572.775 26456.413 7565.251 0.000 19474.959 0.000 0.000 0.000 0.000 0.000 0.000 20552.716 0.000 0.000 0.000
September 0.130639E+12 82536.036 01-SEP-17:15 8572.775 26456.413 7565.251 0.000 18175.176 0.000 0.000 0.000 0.000 0.000 0.000 21766.420 0.000 0.000 0.000
October 0.125420E+12 79239.882 18-OCT-17:45 8572.775 26456.413 7565.251 0.000 11990.681 2508.330 0.000 0.000 0.000 0.000 0.000 22146.431 0.000 0.000 0.000
November 0.114431E+12 70837.364 08-NOV-18:30 8572.775 26456.413 7565.251 0.000 6345.313 2508.330 0.000 0.000 0.000 0.000 0.000 19389.282 0.000 0.000 0.000
December 0.116805E+12 71356.731 12-DEC-18:45 8572.775 26456.413 7565.251 0.000 455.460 2508.330 0.000 0.000 0.000 0.000 0.000 25798.502 0.000 0.000 0.000
                                     
Annual Sum or Average 0.150501E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.107932E+12 70837.364   8572.775 26456.413 7565.251 0.000 455.460 0.000 0.000 0.000 0.000 0.000 0.000 16986.882 0.000 0.000 0.000
Maximum of Months 0.142301E+12 84025.207   8572.775 26456.413 7565.251 0.000 22568.817 2508.330 0.000 0.000 0.000 0.000 0.000 26946.692 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.816920E+10 25494.703 28-JAN-05:00 25494.703 0.000 0.000 0.000 0.000 0.000 25494.703
February 0.497176E+10 23354.066 03-FEB-04:00 23354.066 0.000 0.000 0.000 0.000 0.000 23354.066
March 0.213595E+10 18850.893 02-MAR-05:00 18850.893 0.000 0.000 0.000 0.000 0.000 18850.893
April 0.109042E+09 5427.437 11-APR-03:00 5427.437 0.000 0.000 0.000 0.000 0.000 5427.437
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 240313.905 114.124 25-OCT-05:00 114.124 0.000 0.000 0.000 0.000 0.000 114.124
November 0.312108E+10 21567.716 28-NOV-04:00 21567.716 0.000 0.000 0.000 0.000 0.000 21567.716
December 0.117203E+11 28542.978 27-DEC-07:15 28542.978 0.000 0.000 0.000 0.000 0.000 28542.978
                     
Annual Sum or Average 0.302276E+11       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.117203E+11 28542.978   28542.978 0.000 0.000 0.000 0.000 0.000 28542.978