Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2018-10-19 09:20:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1732.99 | 552.86 | 613.67 |
Net Site Energy | 1732.99 | 552.86 | 613.67 |
Total Source Energy | 4922.19 | 1570.27 | 1743.00 |
Net Source Energy | 4922.19 | 1570.27 | 1743.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 271.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 140.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 395.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1461.18 | 271.81 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 271.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 140.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 209.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 395.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 263.94 | 96.25 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 517.42 | 96.25 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 237.78 | 86.71 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 466.14 | 86.71 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1461.18 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1461.18 | 100.00 |
Total On-Site and Utility Electric Sources | 1461.18 | 100.00 |
Total Electricity End Uses | 1461.18 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 56.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2726.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-17:15 | 06-FEB-00:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 96027.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23653.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6655.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22292.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87630.49 | 96027.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 96027.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23653.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6655.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22292.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 294.64 | 0.00 | 0.00 | 0.00 |
Cooling | 443.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 664.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1252.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4627.55 | 294.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 104.34 | 0.00 | 0.00 | 0.00 |
Cooling | 157.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 443.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1638.66 | 104.34 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 104.34 | 0.00 | 0.00 | 0.00 |
Cooling | 157.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 443.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1638.66 | 104.34 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.67 | 83.67 | 39.40 | |
Exterior Lighting Total | 2508.33 | 39.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3301.07 | 2409.28 | 891.79 | 0.73 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3178.56 | 2321.08 | 857.48 | 0.73 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7420.69 | 5836.80 | 1583.89 | 0.79 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2545.49 | 1827.28 | 718.21 | 0.72 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2158.89 | 1522.14 | 636.75 | 0.71 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2144.45 | 1510.53 | 633.92 | 0.70 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2331.21 | 1632.97 | 698.24 | 0.70 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2376.19 | 1670.34 | 705.85 | 0.70 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8606.40 | 6417.00 | 2189.40 | 0.75 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8271.52 | 6154.32 | 2117.20 | 0.74 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7953.02 | 5848.37 | 2104.64 | 0.74 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6901.78 | 5075.86 | 1825.92 | 0.74 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5668.17 | 4114.03 | 1554.13 | 0.73 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5643.92 | 4094.38 | 1549.54 | 0.73 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6202.63 | 4482.55 | 1720.08 | 0.72 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6219.92 | 4496.59 | 1723.33 | 0.72 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5656.25 | 4258.18 | 1398.08 | 0.75 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5279.04 | 3968.04 | 1311.00 | 0.75 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5330.97 | 3995.49 | 1335.48 | 0.75 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4492.73 | 3346.80 | 1145.93 | 0.74 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3620.15 | 2673.47 | 946.69 | 0.74 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3699.59 | 2707.54 | 992.05 | 0.73 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4419.73 | 3292.63 | 1127.10 | 0.74 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4430.74 | 3301.62 | 1129.13 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3173.7 | 3.25 | 11.09 | 11.54 | 10.99 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3055.7 | 3.25 | 11.08 | 11.54 | 10.98 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7080.8 | 3.15 | 10.74 | 11.17 | 10.48 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2451.1 | 3.27 | 11.16 | 11.62 | 11.10 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2082.4 | 3.30 | 11.24 | 11.71 | 11.22 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2068.6 | 3.30 | 11.25 | 11.72 | 11.23 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2249.9 | 3.30 | 11.27 | 11.74 | 11.27 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2292.6 | 3.30 | 11.26 | 11.73 | 11.24 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8257.0 | 3.22 | 10.99 | 11.43 | 10.84 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7937.3 | 3.22 | 11.00 | 11.45 | 10.86 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7640.5 | 3.24 | 11.05 | 11.50 | 10.94 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6630.5 | 3.24 | 11.05 | 11.50 | 10.93 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5452.3 | 3.26 | 11.11 | 11.57 | 11.02 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5429.2 | 3.26 | 11.11 | 11.57 | 11.03 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5968.9 | 3.26 | 11.13 | 11.59 | 11.05 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5985.3 | 3.26 | 11.13 | 11.59 | 11.05 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5421.4 | 3.21 | 10.95 | 11.39 | 10.78 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5060.6 | 3.21 | 10.95 | 11.39 | 10.79 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5111.9 | 3.21 | 10.97 | 11.41 | 10.81 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4310.7 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3476.4 | 3.23 | 11.03 | 11.48 | 10.91 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3555.8 | 3.25 | 11.07 | 11.53 | 10.97 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4240.6 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4251.1 | 3.22 | 10.99 | 11.44 | 10.85 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2893.16 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2872.01 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5311.56 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2863.02 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2107.32 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2107.10 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2094.42 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2219.95 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 6029.00 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 6067.62 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 6005.62 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 6044.25 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 4108.05 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 4107.45 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 4071.26 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 4070.66 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4449.35 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4470.85 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4437.30 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4458.80 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3379.40 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3379.07 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3355.89 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3355.56 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.57 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.05 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 485.60 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 134.39 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 108.89 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 107.90 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 115.62 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.93 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 498.33 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 476.55 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 445.51 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 386.72 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.55 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.86 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.98 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 334.19 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 335.03 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 311.55 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 312.48 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.59 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.88 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.85 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.41 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.19 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1724.06 | 2068.88 | 0.135 | 0.162 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.69 | 0.01410 |
G NW APARTMENT | 1662.21 | 1994.65 | 0.130 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.32 | 0.01410 |
OFFICE | 4389.25 | 5267.10 | 0.361 | 0.434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.66 | 0.01410 |
G NE APARTMENT | 1275.97 | 1531.16 | 0.100 | 0.120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 28.97 | 0.01410 |
G N1 APARTMENT | 1034.01 | 1240.81 | 0.081 | 0.097 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
G N2 APARTMENT | 1024.60 | 1229.52 | 0.080 | 0.096 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
G S1 APARTMENT | 1097.88 | 1317.45 | 0.086 | 0.103 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
G S2 APARTMENT | 1129.31 | 1355.17 | 0.088 | 0.106 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
M SW APARTMENT | 4731.84 | 5678.21 | 0.371 | 0.445 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.69 | 0.01410 |
M NW APARTMENT | 4525.06 | 5430.07 | 0.355 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.32 | 0.01410 |
M SE APARTMENT | 4230.08 | 5076.09 | 0.331 | 0.398 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73 | 0.01410 |
M NE APARTMENT | 3671.82 | 4406.19 | 0.288 | 0.345 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.57 | 0.01410 |
M N1 APARTMENT | 2920.41 | 3504.49 | 0.229 | 0.275 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
M N2 APARTMENT | 2904.33 | 3485.19 | 0.228 | 0.273 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
M S1 APARTMENT | 3161.76 | 3794.11 | 0.248 | 0.297 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
M S2 APARTMENT | 3173.27 | 3807.93 | 0.249 | 0.298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
T SW APARTMENT | 3180.91 | 3817.10 | 0.249 | 0.299 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 31.88 | 0.01410 |
T NW APARTMENT | 2958.01 | 3549.61 | 0.232 | 0.278 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
T SE APARTMENT | 2966.87 | 3560.25 | 0.232 | 0.279 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
T NE APARTMENT | 2464.62 | 2957.55 | 0.193 | 0.232 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 30.40 | 0.01410 |
T N1 APARTMENT | 1945.42 | 2334.50 | 0.152 | 0.183 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.32 | 0.01410 |
T N2 APARTMENT | 1945.03 | 2334.04 | 0.152 | 0.183 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10 | 0.01410 |
T S1 APARTMENT | 2425.11 | 2910.13 | 0.190 | 0.228 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 32.01 | 0.01410 |
T S2 APARTMENT | 2432.52 | 2919.02 | 0.191 | 0.229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 32.01 | 0.01410 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1555.28 | 1866.34 | 0.045 | 0.054 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G NW APARTMENT | 1568.72 | 1882.47 | 0.045 | 0.054 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
OFFICE | 3280.26 | 3936.31 | 0.091 | 0.109 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G NE APARTMENT | 1561.13 | 1873.35 | 0.045 | 0.054 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G N1 APARTMENT | 922.06 | 1106.47 | 0.027 | 0.032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.70 | 0.00150 |
G N2 APARTMENT | 921.87 | 1106.25 | 0.027 | 0.032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.70 | 0.00150 |
G S1 APARTMENT | 911.15 | 1093.38 | 0.026 | 0.031 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.70 | 0.00150 |
G S2 APARTMENT | 1017.34 | 1220.80 | 0.029 | 0.035 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M SW APARTMENT | 3378.61 | 4054.33 | 0.097 | 0.117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M NW APARTMENT | 3411.28 | 4093.53 | 0.098 | 0.118 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M SE APARTMENT | 3358.84 | 4030.61 | 0.097 | 0.116 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M NE APARTMENT | 3391.51 | 4069.81 | 0.098 | 0.117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M N1 APARTMENT | 1754.07 | 2104.89 | 0.050 | 0.061 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M N2 APARTMENT | 1753.56 | 2104.28 | 0.050 | 0.061 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M S1 APARTMENT | 1722.96 | 2067.55 | 0.050 | 0.060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
M S2 APARTMENT | 1722.45 | 2066.94 | 0.050 | 0.060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T SW APARTMENT | 2902.74 | 3483.29 | 0.084 | 0.100 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T NW APARTMENT | 2920.92 | 3505.11 | 0.084 | 0.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T SE APARTMENT | 2892.55 | 3471.06 | 0.083 | 0.100 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T NE APARTMENT | 2910.73 | 3492.87 | 0.084 | 0.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T N1 APARTMENT | 1997.87 | 2397.44 | 0.058 | 0.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T N2 APARTMENT | 1997.59 | 2397.11 | 0.058 | 0.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T S1 APARTMENT | 1977.99 | 2373.59 | 0.057 | 0.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
T S2 APARTMENT | 1977.71 | 2373.25 | 0.057 | 0.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.70 | 0.00150 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.16 | 0.16 | 0.05 | 0.05 |
SPLIT GNW | 0.16 | 0.16 | 0.05 | 0.05 |
SPLIT OFFICE | 0.43 | 0.43 | 0.11 | 0.11 |
SPLIT GNE | 0.12 | 0.12 | 0.05 | 0.05 |
SPLIT GN1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GN2 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GS1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GS2 | 0.11 | 0.11 | 0.04 | 0.04 |
SPLIT MSW | 0.44 | 0.44 | 0.12 | 0.12 |
SPLIT MNW | 0.43 | 0.43 | 0.12 | 0.12 |
SPLIT MSE | 0.40 | 0.40 | 0.12 | 0.12 |
SPLIT MNE | 0.35 | 0.35 | 0.12 | 0.12 |
SPLIT MN1 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MN2 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MS1 | 0.30 | 0.30 | 0.06 | 0.06 |
SPLIT MS2 | 0.30 | 0.30 | 0.06 | 0.06 |
SPLIT TSW | 0.30 | 0.30 | 0.10 | 0.10 |
SPLIT TNW | 0.28 | 0.28 | 0.10 | 0.10 |
SPLIT TSE | 0.28 | 0.28 | 0.10 | 0.10 |
SPLIT TNE | 0.23 | 0.23 | 0.10 | 0.10 |
SPLIT TN1 | 0.18 | 0.18 | 0.07 | 0.07 |
SPLIT TN2 | 0.18 | 0.18 | 0.07 | 0.07 |
SPLIT TS1 | 0.23 | 0.23 | 0.07 | 0.07 |
SPLIT TS2 | 0.23 | 0.23 | 0.07 | 0.07 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3385.75 | 6273.25 | 1433.50 |
G NW APARTMENT | 3600.00 | 6574.50 | 1925.25 |
OFFICE | 575.75 | 1417.00 | 124.00 |
G NE APARTMENT | 3566.00 | 6604.00 | 1923.50 |
G N1 APARTMENT | 3120.50 | 6744.00 | 1697.75 |
G N2 APARTMENT | 3118.00 | 6744.50 | 1696.25 |
G S1 APARTMENT | 2952.25 | 6406.75 | 1164.00 |
G S2 APARTMENT | 3013.75 | 6450.25 | 1277.50 |
M SW APARTMENT | 3756.50 | 4108.00 | 313.75 |
M NW APARTMENT | 3853.50 | 4596.50 | 704.50 |
M SE APARTMENT | 3753.50 | 4120.50 | 308.50 |
M NE APARTMENT | 3853.00 | 4641.75 | 706.25 |
M N1 APARTMENT | 3371.50 | 4526.00 | 346.00 |
M N2 APARTMENT | 3370.00 | 4528.25 | 344.25 |
M S1 APARTMENT | 3559.25 | 3912.25 | 199.25 |
M S2 APARTMENT | 3560.50 | 3917.75 | 201.50 |
T SW APARTMENT | 4570.50 | 4949.75 | 1613.25 |
T NW APARTMENT | 4880.75 | 5382.00 | 2174.75 |
T SE APARTMENT | 4574.25 | 4991.25 | 1641.25 |
T NE APARTMENT | 4855.25 | 5473.00 | 2202.50 |
T N1 APARTMENT | 4383.75 | 5382.25 | 1766.75 |
T N2 APARTMENT | 4378.75 | 5366.25 | 1747.00 |
T S1 APARTMENT | 4131.50 | 4797.25 | 1166.00 |
T S2 APARTMENT | 4128.25 | 4798.25 | 1169.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5629.75 | 6823.00 | 2726.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
G NW APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
OFFICE | 7.75 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 6.75 | 0.00 | 6.75 | 0.00 |
G N1 APARTMENT | 7.50 | 0.00 | 7.50 | 0.00 |
G N2 APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
G S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
G S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NW APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M SE APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M NE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M N1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M N2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M S1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T N1 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
T N2 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
T S1 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
T S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 64.25 | 0.00 | 56.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.123 | 0.000 | 0.087 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.123 | 0.000 | 0.084 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.133 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.123 | 0.000 | 0.084 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.083 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.083 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.087 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.087 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.177 | 0.000 | 0.111 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.177 | 0.000 | 0.108 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.177 | 0.000 | 0.111 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.177 | 0.000 | 0.108 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.108 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.108 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.111 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.111 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.234 | 0.000 | 0.138 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.234 | 0.000 | 0.132 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.234 | 0.000 | 0.138 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.234 | 0.000 | 0.132 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.141 | 0.000 | 0.132 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.141 | 0.000 | 0.132 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.141 | 0.000 | 0.138 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.141 | 0.000 | 0.138 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.497 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.356 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 395.34 | 0.00 | 01-JAN-00:15 | 32590.92 | 07-FEB-07:15 |
WaterSystems:Electricity | 395.34 | 0.00 | 01-JAN-00:15 | 32590.92 | 07-FEB-07:15 |
Water Heater:WaterSystems:Electricity | 395.34 | 0.00 | 01-JAN-00:15 | 32590.92 | 07-FEB-07:15 |
Fans:Electricity | 209.89 | 6655.60 | 29-JAN-05:45 | 6655.60 | 01-JAN-07:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
ElectricityPurchased:Plant | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
Cogeneration:ElectricityPurchased | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
ElectricityNet:Plant | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
Cogeneration:ElectricityNet | 1461.18 | 20025.90 | 01-JAN-03:15 | 87630.49 | 04-AUG-17:15 |
ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.40 | 0.00 | 01-JAN-07:30 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 350.02 | 6655.60 | 29-JAN-05:45 | 31944.31 | 16-AUG-15:15 |
General:Fans:Electricity | 209.89 | 6655.60 | 29-JAN-05:45 | 6655.60 | 01-JAN-07:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 140.13 | 0.00 | 01-JAN-00:15 | 25288.71 | 16-AUG-15:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 271.81 | 0.00 | 01-MAR-11:30 | 96027.50 | 06-FEB-01:00 |
Gas:HVAC | 271.81 | 0.00 | 01-MAR-11:30 | 96027.50 | 06-FEB-01:00 |
Heating:Gas | 271.81 | 0.00 | 01-MAR-11:30 | 96027.50 | 06-FEB-01:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1355.96 | 1707.67 | 02-MAR-21:00 | 161175.27 | 16-AUG-15:15 |
EnergyTransfer:Building | 556.83 | 1679.13 | 02-MAR-21:00 | 62091.86 | 24-AUG-15:15 |
EnergyTransfer:Zone:G SW APARTMENT | 12.53 | 0.00 | 29-MAY-08:00 | 1985.94 | 18-AUG-16:15 |
Heating:EnergyTransfer | 101.51 | 0.00 | 17-JAN-13:15 | 48871.73 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.41 | 0.00 | 04-JAN-13:30 | 1531.31 | 06-FEB-01:00 |
Cooling:EnergyTransfer | 455.32 | 0.00 | 02-JAN-07:15 | 62091.86 | 24-AUG-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.12 | 0.00 | 01-JAN-00:15 | 1985.94 | 18-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 11.90 | 0.01 | 27-APR-13:45 | 1712.08 | 12-JUL-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 5.04 | 0.00 | 12-JAN-16:15 | 1685.56 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.86 | 0.00 | 01-JAN-00:15 | 1712.08 | 12-JUL-17:15 |
EnergyTransfer:Zone:OFFICE | 22.52 | 0.00 | 27-APR-18:15 | 3512.49 | 06-FEB-07:15 |
Heating:EnergyTransfer:Zone:OFFICE | 0.34 | 0.00 | 01-JAN-00:15 | 3512.49 | 06-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 22.18 | 0.00 | 02-JAN-07:15 | 3358.91 | 22-AUG-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 11.85 | 0.04 | 21-OCT-16:00 | 1669.39 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.90 | 0.00 | 12-JAN-20:00 | 1669.39 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.95 | 0.00 | 01-JAN-00:15 | 1338.43 | 19-JUN-17:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.39 | 0.03 | 28-MAY-08:45 | 1061.85 | 10-JUL-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.12 | 0.00 | 03-JAN-16:15 | 978.92 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.26 | 0.00 | 01-JAN-00:15 | 1061.85 | 10-JUL-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.39 | 0.00 | 11-OCT-15:00 | 1056.15 | 10-JUL-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.12 | 0.00 | 03-JAN-16:15 | 978.18 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.26 | 0.00 | 01-JAN-00:15 | 1056.15 | 10-JUL-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 9.98 | 0.08 | 05-MAY-13:30 | 1363.29 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.11 | 0.00 | 01-JAN-12:15 | 828.89 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 8.86 | 0.00 | 01-JAN-00:15 | 1363.29 | 01-SEP-13:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 9.94 | 0.12 | 25-APR-12:30 | 1346.00 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.33 | 0.00 | 02-JAN-10:45 | 927.30 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.61 | 0.00 | 01-JAN-00:15 | 1346.00 | 01-SEP-13:00 |
EnergyTransfer:Zone:M SW APARTMENT | 41.33 | 0.18 | 31-JAN-24:00 | 5315.47 | 18-AUG-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 3.45 | 0.00 | 02-JAN-10:45 | 3053.29 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 37.88 | 0.00 | 01-JAN-00:15 | 5315.47 | 18-AUG-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 35.25 | 0.17 | 10-NOV-07:45 | 4824.65 | 19-JUN-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 6.73 | 0.00 | 03-JAN-19:00 | 3604.33 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 28.52 | 0.00 | 01-JAN-00:15 | 4824.65 | 19-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 41.44 | 0.45 | 11-DEC-18:00 | 4738.68 | 18-AUG-12:45 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 3.38 | 0.00 | 02-JAN-10:30 | 3009.38 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 38.06 | 0.00 | 01-JAN-00:15 | 4738.68 | 18-AUG-12:45 |
EnergyTransfer:Zone:M NE APARTMENT | 35.12 | 0.15 | 25-DEC-21:45 | 3990.76 | 19-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 6.50 | 0.00 | 03-JAN-19:00 | 3541.45 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 28.62 | 0.00 | 01-JAN-00:15 | 3990.76 | 19-JUN-17:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 29.21 | 0.12 | 16-APR-11:15 | 3174.13 | 19-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.60 | 0.00 | 02-JAN-17:15 | 1777.94 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 27.61 | 0.00 | 01-JAN-00:15 | 3174.13 | 19-JUN-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 29.20 | 0.09 | 23-MAR-10:15 | 3159.00 | 19-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.59 | 0.00 | 02-JAN-17:15 | 1774.22 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 27.60 | 0.00 | 01-JAN-00:15 | 3159.00 | 19-JUN-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 39.28 | 0.02 | 01-MAR-03:00 | 3846.99 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.50 | 0.00 | 01-JAN-09:15 | 1344.41 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.78 | 0.00 | 01-JAN-00:15 | 3846.99 | 01-SEP-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 39.26 | 0.14 | 01-DEC-23:45 | 3855.63 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.49 | 0.00 | 01-JAN-09:15 | 1342.07 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.76 | 0.00 | 01-JAN-00:15 | 3855.63 | 01-SEP-13:00 |
EnergyTransfer:Zone:T SW APARTMENT | 24.71 | 0.02 | 24-SEP-00:30 | 3552.04 | 18-AUG-15:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 8.03 | 0.00 | 04-JAN-14:30 | 3064.17 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 16.68 | 0.00 | 01-JAN-00:15 | 3552.04 | 18-AUG-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 23.83 | 0.01 | 06-OCT-03:15 | 3260.02 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 10.63 | 0.00 | 17-JAN-12:45 | 3260.02 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 13.20 | 0.00 | 01-JAN-00:15 | 3193.14 | 19-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 24.50 | 0.01 | 25-SEP-01:30 | 3299.19 | 18-AUG-12:45 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 7.89 | 0.00 | 02-JAN-11:00 | 3043.46 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 16.61 | 0.00 | 01-JAN-00:15 | 3299.19 | 18-AUG-12:45 |
EnergyTransfer:Zone:T NE APARTMENT | 23.60 | 0.08 | 25-OCT-03:45 | 3240.82 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 10.43 | 0.00 | 17-JAN-12:00 | 3240.82 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 13.16 | 0.00 | 01-JAN-00:15 | 2759.48 | 19-JUN-14:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.72 | 0.07 | 02-NOV-15:30 | 2231.74 | 19-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 5.99 | 0.00 | 12-JAN-20:00 | 2162.96 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 11.73 | 0.00 | 01-JAN-00:15 | 2231.74 | 19-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.72 | 0.04 | 03-OCT-08:45 | 2217.83 | 19-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 5.99 | 0.00 | 12-JAN-20:00 | 2162.00 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 11.73 | 0.00 | 01-JAN-00:15 | 2217.83 | 19-JUN-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.59 | 0.01 | 02-MAY-10:15 | 2749.68 | 18-AUG-13:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 3.96 | 0.00 | 02-JAN-11:00 | 1985.44 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 15.63 | 0.00 | 01-JAN-00:15 | 2749.68 | 18-AUG-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.59 | 0.02 | 26-APR-08:45 | 2757.67 | 18-AUG-13:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 3.96 | 0.00 | 02-JAN-11:00 | 1984.57 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 15.63 | 0.00 | 01-JAN-00:15 | 2757.67 | 18-AUG-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 799.13 | 0.00 | 02-MAR-19:45 | 102139.95 | 02-AUG-15:15 |
HeatingCoils:EnergyTransfer | 217.45 | 0.00 | 01-MAR-11:30 | 76822.00 | 06-FEB-01:00 |
CoolingCoils:EnergyTransfer | 581.68 | 0.00 | 01-JAN-00:15 | 102139.95 | 02-AUG-15:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 3.413 | -9.121 | 0.000 | 0.000 | 3.828 | 2.413 | 12.213 | 13.265 | 0.000 | 0.164 | 0.000 | 0.000 | -6.457 | 0.000 | -4.960 | -14.758 |
G NW APARTMENT | 5.041 | -6.861 | 0.000 | 0.000 | 3.847 | 2.413 | 12.213 | 6.909 | 0.000 | 0.162 | 0.000 | 0.000 | -6.700 | 0.000 | -4.850 | -12.174 |
OFFICE | 0.339 | -22.180 | 0.000 | 0.000 | 0.526 | 21.914 | 7.534 | 13.277 | 0.000 | 0.134 | 0.002 | 0.000 | -6.165 | 0.000 | -3.916 | -11.463 |
G NE APARTMENT | 4.897 | -6.954 | 0.000 | 0.000 | 3.855 | 2.413 | 12.213 | 6.784 | 0.000 | 0.162 | 0.000 | 0.000 | -6.553 | 0.000 | -4.836 | -11.980 |
G N1 APARTMENT | 2.124 | -6.262 | 0.000 | 0.000 | 3.855 | 2.413 | 12.213 | 2.598 | 0.000 | 0.118 | 0.000 | 0.000 | -4.181 | 0.000 | -3.201 | -9.677 |
G N2 APARTMENT | 2.122 | -6.264 | 0.000 | 0.000 | 3.856 | 2.413 | 12.213 | 2.598 | 0.000 | 0.118 | 0.000 | 0.000 | -4.180 | 0.000 | -3.200 | -9.674 |
G S1 APARTMENT | 1.115 | -8.862 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 8.991 | 0.000 | 0.119 | 0.000 | 0.000 | -3.925 | 0.000 | -3.318 | -12.576 |
G S2 APARTMENT | 1.334 | -8.608 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 8.994 | 0.000 | 0.119 | 0.000 | 0.000 | -3.917 | 0.000 | -3.319 | -13.059 |
M SW APARTMENT | 3.449 | -37.880 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 12.830 | 0.000 | 0.229 | 17.363 | 0.000 | -7.092 | 0.000 | -7.250 | -0.000 |
M NW APARTMENT | 6.725 | -28.521 | 0.000 | 0.000 | 3.760 | 2.413 | 12.213 | 6.555 | 0.000 | 0.226 | 11.022 | 0.000 | -7.287 | 0.000 | -7.106 | -0.000 |
M SE APARTMENT | 3.376 | -38.063 | 0.000 | 0.000 | 3.731 | 2.413 | 12.213 | 12.783 | 0.000 | 0.229 | 17.582 | 0.000 | -7.019 | 0.000 | -7.244 | -0.000 |
M NE APARTMENT | 6.497 | -28.624 | 0.000 | 0.000 | 3.767 | 2.413 | 12.213 | 6.425 | 0.000 | 0.226 | 11.306 | 0.000 | -7.127 | 0.000 | -7.096 | -0.001 |
M N1 APARTMENT | 1.599 | -27.612 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 2.381 | 0.000 | 0.162 | 14.451 | 0.000 | -4.618 | 0.000 | -4.737 | -0.000 |
M N2 APARTMENT | 1.594 | -27.603 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 2.381 | 0.000 | 0.162 | 14.444 | 0.000 | -4.617 | 0.000 | -4.736 | -0.000 |
M S1 APARTMENT | 0.500 | -38.782 | 0.000 | 0.000 | 3.700 | 2.413 | 12.213 | 8.710 | 0.000 | 0.165 | 20.304 | 0.000 | -4.357 | 0.000 | -4.866 | -0.001 |
M S2 APARTMENT | 0.494 | -38.764 | 0.000 | 0.000 | 3.700 | 2.413 | 12.213 | 8.709 | 0.000 | 0.165 | 20.291 | 0.000 | -4.356 | 0.000 | -4.866 | -0.000 |
T SW APARTMENT | 8.030 | -16.677 | 0.000 | 0.000 | 3.778 | 2.413 | 12.213 | 12.708 | 0.000 | 0.314 | 0.000 | 0.000 | -6.701 | 0.000 | -9.257 | -6.820 |
T NW APARTMENT | 10.628 | -13.200 | 0.000 | 0.000 | 3.801 | 2.413 | 12.213 | 6.477 | 0.000 | 0.309 | 0.000 | 0.000 | -6.925 | 0.000 | -9.087 | -6.629 |
T SE APARTMENT | 7.894 | -16.605 | 0.000 | 0.000 | 3.781 | 2.413 | 12.213 | 12.671 | 0.000 | 0.314 | 0.000 | 0.000 | -6.641 | 0.000 | -9.259 | -6.781 |
T NE APARTMENT | 10.434 | -13.164 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 6.367 | 0.000 | 0.309 | 0.000 | 0.000 | -6.782 | 0.000 | -9.079 | -6.520 |
T N1 APARTMENT | 5.989 | -11.731 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 2.369 | 0.000 | 0.226 | 0.000 | 0.000 | -4.346 | 0.000 | -5.965 | -4.966 |
T N2 APARTMENT | 5.991 | -11.726 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 2.367 | 0.000 | 0.226 | 0.000 | 0.000 | -4.345 | 0.000 | -5.966 | -4.973 |
T S1 APARTMENT | 3.963 | -15.628 | 0.000 | 0.000 | 3.766 | 2.413 | 12.213 | 8.650 | 0.000 | 0.230 | 0.000 | 0.000 | -4.107 | 0.000 | -6.126 | -5.374 |
T S2 APARTMENT | 3.961 | -15.628 | 0.000 | 0.000 | 3.766 | 2.413 | 12.213 | 8.648 | 0.000 | 0.230 | 0.000 | 0.000 | -4.106 | 0.000 | -6.127 | -5.371 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.097 | 0.000 | 0.008 | 0.000 | 0.000 | -0.847 | 0.000 | -1.479 | -14.849 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.366 | 0.000 | 0.242 | 0.001 | 0.000 | -2.196 | 0.000 | -18.914 | -2.833 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.100 | 0.000 | 0.008 | 0.000 | 0.000 | -0.930 | 0.000 | -1.217 | -15.031 |
Total Facility | 101.506 | -455.321 | 0.000 | 0.000 | 87.606 | 128.627 | 294.692 | 185.011 | 0.000 | 5.078 | 126.764 | 0.000 | -136.479 | 0.000 | -161.976 | -175.509 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 18-AUG-16:08 | 0.00 | -1986.63 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1848.49 | 0.00 | 90.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -769.66 |
G NW APARTMENT | 12-JUL-17:15 | 0.00 | -1712.75 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1793.99 | 0.00 | 103.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1109.39 |
OFFICE | 22-AUG-12:30 | 0.00 | -3358.85 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 1865.09 | 0.00 | 83.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -824.38 |
G NE APARTMENT | 19-JUN-17:23 | 0.00 | -1338.46 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 758.54 | 0.00 | 108.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -453.26 |
G N1 APARTMENT | 10-JUL-17:30 | 0.00 | -1061.88 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 412.75 | 0.00 | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -321.66 |
G N2 APARTMENT | 10-JUL-17:30 | 0.00 | -1056.18 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 412.84 | 0.00 | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -327.45 |
G S1 APARTMENT | 01-SEP-13:00 | 0.00 | -1363.11 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1777.43 | 0.00 | 44.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -916.94 |
G S2 APARTMENT | 01-SEP-13:00 | 0.00 | -1345.81 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1777.69 | 0.00 | 44.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -934.50 |
M SW APARTMENT | 18-AUG-16:11 | 0.00 | -5316.92 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1837.06 | 0.00 | 129.56 | 2532.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 19-JUN-17:30 | 0.00 | -4824.59 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1661.25 | 0.00 | 155.26 | 2083.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 18-AUG-12:45 | 0.00 | -4738.64 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1899.56 | 0.00 | 162.46 | 2218.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 19-JUN-17:15 | 0.00 | -3991.50 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 736.46 | 0.00 | 166.71 | 2163.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 19-JUN-17:30 | 0.00 | -3174.14 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 541.11 | 0.00 | 93.65 | 1614.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 19-JUN-17:30 | 0.00 | -3159.01 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 541.21 | 0.00 | 93.65 | 1599.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 01-SEP-13:00 | 0.00 | -3846.64 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1767.30 | 0.00 | 63.85 | 1557.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 01-SEP-13:00 | 0.00 | -3855.29 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1767.25 | 0.00 | 63.84 | 1566.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 18-AUG-15:15 | 0.00 | -3552.08 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2131.99 | 0.00 | 209.13 | 590.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 19-JUN-17:10 | 0.00 | -3194.05 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1644.98 | 0.00 | 219.50 | 404.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 18-AUG-12:45 | 0.00 | -3299.15 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 1865.31 | 0.00 | 213.92 | 761.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 19-JUN-14:30 | 0.00 | -2759.38 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1094.83 | 0.00 | 191.57 | 981.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 19-JUN-17:10 | 0.00 | -2232.35 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 504.14 | 0.00 | 132.40 | 670.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 19-JUN-17:10 | 0.00 | -2218.44 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 504.33 | 0.00 | 132.40 | 656.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 18-AUG-13:15 | 0.00 | -2749.65 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1456.35 | 0.00 | 133.43 | 707.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 18-AUG-13:15 | 0.00 | -2757.65 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1456.24 | 0.00 | 133.43 | 715.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-AUG-15:15 | 0.00 | -62079.75 | 0.00 | 0.00 | 1192.03 | 5565.24 | 11658.39 | 23607.04 | 0.00 | 4920.70 | 15136.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-FEB-01:00 | 1531.29 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -930.29 | 0.00 | -835.06 | -234.89 |
G NW APARTMENT | 06-FEB-01:00 | 1685.53 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -944.34 | 0.00 | -835.06 | -375.08 |
OFFICE | 26-NOV-07:01 | 4951.39 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -363.08 | 0.00 | -309.54 | -4853.34 |
G NE APARTMENT | 20-FEB-17:01 | 2407.94 | 0.00 | 0.00 | 0.00 | 99.99 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -379.07 | 0.00 | -121.55 | -2739.97 |
G N1 APARTMENT | 22-FEB-17:01 | 1206.81 | 0.00 | 0.00 | 0.00 | 98.71 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -273.96 | 0.00 | -122.91 | -1641.30 |
G N2 APARTMENT | 28-DEC-17:01 | 1274.47 | 0.00 | 0.00 | 0.00 | 98.71 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -324.34 | 0.00 | -67.45 | -1714.05 |
G S1 APARTMENT | 26-FEB-18:01 | 1128.81 | 0.00 | 0.00 | 0.00 | 165.18 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -354.58 | 0.00 | -93.61 | -1628.86 |
G S2 APARTMENT | 11-JAN-17:14 | 1144.02 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -456.44 | 0.00 | -289.99 | -1228.88 |
M SW APARTMENT | 05-DEC-17:01 | 3257.13 | 0.00 | 0.00 | 0.00 | 99.60 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -499.58 | 0.00 | -508.83 | -3080.98 |
M NW APARTMENT | 06-FEB-01:00 | 3604.27 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -967.94 | 0.00 | -1200.74 | -1904.55 |
M SE APARTMENT | 06-FEB-01:00 | 3009.33 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -941.69 | 0.00 | -1200.74 | -1335.85 |
M NE APARTMENT | 15-MAR-06:01 | 5239.53 | 0.00 | 0.00 | 0.00 | 163.44 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -480.09 | 0.00 | -192.90 | -5206.21 |
M N1 APARTMENT | 07-FEB-18:19 | 1949.12 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.16 | 0.00 | -292.07 | -2160.99 |
M N2 APARTMENT | 02-JAN-18:01 | 2691.24 | 0.00 | 0.00 | 0.00 | 165.26 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -438.33 | 0.00 | -194.82 | -3006.42 |
M S1 APARTMENT | 23-NOV-07:01 | 2766.16 | 0.00 | 0.00 | 0.00 | 161.45 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -320.11 | 0.00 | -284.60 | -2799.13 |
M S2 APARTMENT | 02-DEC-07:01 | 2325.03 | 0.00 | 0.00 | 0.00 | 161.40 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20.02 | 0.00 | -339.35 | -2603.30 |
T SW APARTMENT | 06-FEB-01:00 | 3064.12 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -929.71 | 0.00 | -1590.02 | -1013.36 |
T NW APARTMENT | 06-FEB-01:00 | 3259.97 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -945.65 | 0.00 | -1590.02 | -1193.26 |
T SE APARTMENT | 06-FEB-01:00 | 3043.42 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.72 | 0.00 | -1590.02 | -1007.63 |
T NE APARTMENT | 06-FEB-01:00 | 3240.77 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -930.74 | 0.00 | -1590.02 | -1188.97 |
T N1 APARTMENT | 06-FEB-01:15 | 2162.94 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -573.89 | 0.00 | -934.63 | -1099.83 |
T N2 APARTMENT | 06-FEB-01:15 | 2161.97 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -573.91 | 0.00 | -934.63 | -1098.85 |
T S1 APARTMENT | 06-FEB-05:00 | 1985.47 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -551.04 | 0.00 | -803.33 | -1087.66 |
T S2 APARTMENT | 06-FEB-05:00 | 1984.59 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -551.05 | 0.00 | -803.33 | -1086.77 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-01:00 | 48039.19 | 0.00 | 0.00 | 0.00 | 4362.43 | 2334.74 | 6261.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18445.97 | 0.00 | -23726.49 | -18825.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Sec1.1A-General InformationData | |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 56.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 56.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 271.81 | 96027.50 | 0.00 | 0.00 |
Space Cooling | 140.13 | 23653.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 209.89 | 6655.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 395.34 | 22292.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1461.18 | 271.81 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1461.18 |
Natural Gas | 0.00 | 271.81 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1732.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 44.70 |
Fans-Interior | 66.96 |
Service Water Heating | 126.12 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.57 |
Subtotal | 466.14 |
Natural Gas [MJ/m2] | |
Space Heating | 86.71 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 86.71 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.52 |
Space Heating | 15.68 |
Space Cooling | 8.09 |
Fans-Interior | 12.11 |
Service Water Heating | 22.81 |
Receptacle Equipment | 29.51 |
Miscellaneous | 2.27 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.162097 |
G NW APARTMENT DIRECT AIR | 0.156281 |
OFFICE DIRECT AIR | 0.433533 |
G NE APARTMENT DIRECT AIR | 0.119975 |
G N1 APARTMENT DIRECT AIR | 0.097216 |
G N2 APARTMENT DIRECT AIR | 0.096331 |
G S1 APARTMENT DIRECT AIR | 0.103223 |
G S2 APARTMENT DIRECT AIR | 0.106179 |
M SW APARTMENT DIRECT AIR | 0.444896 |
M NW APARTMENT DIRECT AIR | 0.425451 |
M SE APARTMENT DIRECT AIR | 0.397736 |
M NE APARTMENT DIRECT AIR | 0.345250 |
M N1 APARTMENT DIRECT AIR | 0.274573 |
M N2 APARTMENT DIRECT AIR | 0.273062 |
M S1 APARTMENT DIRECT AIR | 0.297275 |
M S2 APARTMENT DIRECT AIR | 0.298357 |
T SW APARTMENT DIRECT AIR | 0.299101 |
T NW APARTMENT DIRECT AIR | 0.278142 |
T SE APARTMENT DIRECT AIR | 0.278975 |
T NE APARTMENT DIRECT AIR | 0.231750 |
T N1 APARTMENT DIRECT AIR | 0.182908 |
T N2 APARTMENT DIRECT AIR | 0.182881 |
T S1 APARTMENT DIRECT AIR | 0.228019 |
T S2 APARTMENT DIRECT AIR | 0.228716 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.162097 |
SPLIT GNW MAIN BRANCH | 0.156281 |
SPLIT OFFICE MAIN BRANCH | 0.433533 |
SPLIT GNE MAIN BRANCH | 0.119975 |
SPLIT GN1 MAIN BRANCH | 0.097216 |
SPLIT GN2 MAIN BRANCH | 0.096331 |
SPLIT GS1 MAIN BRANCH | 0.103223 |
SPLIT GS2 MAIN BRANCH | 0.106179 |
SPLIT MSW MAIN BRANCH | 0.444896 |
SPLIT MNW MAIN BRANCH | 0.425451 |
SPLIT MSE MAIN BRANCH | 0.397736 |
SPLIT MNE MAIN BRANCH | 0.345250 |
SPLIT MN1 MAIN BRANCH | 0.274573 |
SPLIT MN2 MAIN BRANCH | 0.273062 |
SPLIT MS1 MAIN BRANCH | 0.297275 |
SPLIT MS2 MAIN BRANCH | 0.298357 |
SPLIT TSW MAIN BRANCH | 0.299101 |
SPLIT TNW MAIN BRANCH | 0.278142 |
SPLIT TSE MAIN BRANCH | 0.278975 |
SPLIT TNE MAIN BRANCH | 0.231750 |
SPLIT TN1 MAIN BRANCH | 0.182908 |
SPLIT TN2 MAIN BRANCH | 0.182881 |
SPLIT TS1 MAIN BRANCH | 0.228019 |
SPLIT TS2 MAIN BRANCH | 0.228716 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.162097 |
SPLIT GNW | 0.156281 |
SPLIT OFFICE | 0.433533 |
SPLIT GNE | 0.119975 |
SPLIT GN1 | 0.097216 |
SPLIT GN2 | 0.096331 |
SPLIT GS1 | 0.103223 |
SPLIT GS2 | 0.106179 |
SPLIT MSW | 0.444896 |
SPLIT MNW | 0.425451 |
SPLIT MSE | 0.397736 |
SPLIT MNE | 0.345250 |
SPLIT MN1 | 0.274573 |
SPLIT MN2 | 0.273062 |
SPLIT MS1 | 0.297275 |
SPLIT MS2 | 0.298357 |
SPLIT TSW | 0.299101 |
SPLIT TNW | 0.278142 |
SPLIT TSE | 0.278975 |
SPLIT TNE | 0.231750 |
SPLIT TN1 | 0.182908 |
SPLIT TN2 | 0.182881 |
SPLIT TS1 | 0.228019 |
SPLIT TS2 | 0.228716 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.162097 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.156281 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.433533 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.119975 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.097216 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.096331 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.103223 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.106179 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.444896 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.425451 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.397736 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.345250 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.274573 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.273062 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.297275 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.298357 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.299101 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.278142 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.278975 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.231750 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.182908 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.182881 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.228019 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.228716 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.162097 | 3301.07 | 0.729849 |
SPLIT GNW COOLING COIL | 0.156281 | 3178.56 | 0.730231 |
SPLIT OFFICE COOLING COIL | 0.433533 | 7420.69 | 0.786557 |
SPLIT GNE COOLING COIL | 0.119975 | 2545.49 | 0.717849 |
SPLIT GN1 COOLING COIL | 0.097216 | 2158.89 | 0.705056 |
SPLIT GN2 COOLING COIL | 0.096331 | 2144.45 | 0.704389 |
SPLIT GS1 COOLING COIL | 0.103223 | 2331.21 | 0.700482 |
SPLIT GS2 COOLING COIL | 0.106179 | 2376.19 | 0.702949 |
SPLIT MSW COOLING COIL | 0.444896 | 8606.40 | 0.745607 |
SPLIT MNW COOLING COIL | 0.425451 | 8271.52 | 0.744037 |
SPLIT MSE COOLING COIL | 0.397736 | 7953.02 | 0.735365 |
SPLIT MNE COOLING COIL | 0.345250 | 6901.78 | 0.735442 |
SPLIT MN1 COOLING COIL | 0.274573 | 5668.17 | 0.725813 |
SPLIT MN2 COOLING COIL | 0.273062 | 5643.92 | 0.725450 |
SPLIT MS1 COOLING COIL | 0.297275 | 6202.63 | 0.722685 |
SPLIT MS2 COOLING COIL | 0.298357 | 6219.92 | 0.722933 |
SPLIT TSW COOLING COIL | 0.299101 | 5656.25 | 0.752826 |
SPLIT TNW COOLING COIL | 0.278142 | 5279.04 | 0.751659 |
SPLIT TSE COOLING COIL | 0.278975 | 5330.97 | 0.749487 |
SPLIT TNE COOLING COIL | 0.231750 | 4492.73 | 0.744936 |
SPLIT TN1 COOLING COIL | 0.182908 | 3620.15 | 0.738495 |
SPLIT TN2 COOLING COIL | 0.182881 | 3699.59 | 0.731848 |
SPLIT TS1 COOLING COIL | 0.228019 | 4419.73 | 0.744985 |
SPLIT TS2 COOLING COIL | 0.228716 | 4430.74 | 0.745161 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.162097 | 0.162097 | 0.162097 | 0.162097 | 2893.16 | 3301.07 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.156281 | 0.156281 | 0.156281 | 0.156281 | 2872.01 | 3178.56 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.433533 | 0.433533 | 0.433533 | 0.433533 | 5311.56 | 7420.69 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.119975 | 0.119975 | 0.119975 | 0.119975 | 2863.02 | 2545.49 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.097216 | 0.097216 | 0.097216 | 0.097216 | 2107.32 | 2158.89 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.096331 | 0.096331 | 0.096331 | 0.096331 | 2107.10 | 2144.45 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.103223 | 0.103223 | 0.103223 | 0.103223 | 2094.42 | 2331.21 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.106179 | 0.106179 | 0.106179 | 0.106179 | 2219.95 | 2376.19 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.444896 | 0.444896 | 0.444896 | 0.444896 | 6029.00 | 8606.40 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.425451 | 0.425451 | 0.425451 | 0.425451 | 6067.62 | 8271.52 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.397736 | 0.397736 | 0.397736 | 0.397736 | 6005.62 | 7953.02 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.345250 | 0.345250 | 0.345250 | 0.345250 | 6044.25 | 6901.78 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.274573 | 0.274573 | 0.274573 | 0.274573 | 4108.05 | 5668.17 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.273062 | 0.273062 | 0.273062 | 0.273062 | 4107.45 | 5643.92 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.297275 | 0.297275 | 0.297275 | 0.297275 | 4071.26 | 6202.63 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.298357 | 0.298357 | 0.298357 | 0.298357 | 4070.66 | 6219.92 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.299101 | 0.299101 | 0.299101 | 0.299101 | 4449.35 | 5656.25 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.278142 | 0.278142 | 0.278142 | 0.278142 | 4470.85 | 5279.04 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.278975 | 0.278975 | 0.278975 | 0.278975 | 4437.30 | 5330.97 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.231750 | 0.231750 | 0.231750 | 0.231750 | 4458.80 | 4492.73 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.182908 | 0.182908 | 0.182908 | 0.182908 | 3379.40 | 3620.15 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.182881 | 0.182881 | 0.182881 | 0.182881 | 3379.07 | 3699.59 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.228019 | 0.228019 | 0.228019 | 0.228019 | 3355.89 | 4419.73 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.228716 | 0.228716 | 0.228716 | 0.228716 | 3355.56 | 4430.74 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.162097 |
SPLIT GNW SUPPLY FAN | 0.156281 |
SPLIT OFFICE SUPPLY FAN | 0.433533 |
SPLIT GNE SUPPLY FAN | 0.119975 |
SPLIT GN1 SUPPLY FAN | 0.097216 |
SPLIT GN2 SUPPLY FAN | 0.096331 |
SPLIT GS1 SUPPLY FAN | 0.103223 |
SPLIT GS2 SUPPLY FAN | 0.106179 |
SPLIT MSW SUPPLY FAN | 0.444896 |
SPLIT MNW SUPPLY FAN | 0.425451 |
SPLIT MSE SUPPLY FAN | 0.397736 |
SPLIT MNE SUPPLY FAN | 0.345250 |
SPLIT MN1 SUPPLY FAN | 0.274573 |
SPLIT MN2 SUPPLY FAN | 0.273062 |
SPLIT MS1 SUPPLY FAN | 0.297275 |
SPLIT MS2 SUPPLY FAN | 0.298357 |
SPLIT TSW SUPPLY FAN | 0.299101 |
SPLIT TNW SUPPLY FAN | 0.278142 |
SPLIT TSE SUPPLY FAN | 0.278975 |
SPLIT TNE SUPPLY FAN | 0.231750 |
SPLIT TN1 SUPPLY FAN | 0.182908 |
SPLIT TN2 SUPPLY FAN | 0.182881 |
SPLIT TS1 SUPPLY FAN | 0.228019 |
SPLIT TS2 SUPPLY FAN | 0.228716 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2893.16 |
SPLIT GNW HEATING COIL | 2872.01 |
SPLIT OFFICE HEATING COIL | 5311.56 |
SPLIT GNE HEATING COIL | 2863.02 |
SPLIT GN1 HEATING COIL | 2107.32 |
SPLIT GN2 HEATING COIL | 2107.10 |
SPLIT GS1 HEATING COIL | 2094.42 |
SPLIT GS2 HEATING COIL | 2219.95 |
SPLIT MSW HEATING COIL | 6029.00 |
SPLIT MNW HEATING COIL | 6067.62 |
SPLIT MSE HEATING COIL | 6005.62 |
SPLIT MNE HEATING COIL | 6044.25 |
SPLIT MN1 HEATING COIL | 4108.05 |
SPLIT MN2 HEATING COIL | 4107.45 |
SPLIT MS1 HEATING COIL | 4071.26 |
SPLIT MS2 HEATING COIL | 4070.66 |
SPLIT TSW HEATING COIL | 4449.35 |
SPLIT TNW HEATING COIL | 4470.85 |
SPLIT TSE HEATING COIL | 4437.30 |
SPLIT TNE HEATING COIL | 4458.80 |
SPLIT TN1 HEATING COIL | 3379.40 |
SPLIT TN2 HEATING COIL | 3379.07 |
SPLIT TS1 HEATING COIL | 3355.89 |
SPLIT TS2 HEATING COIL | 3355.56 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 1.17 |
February | 21.74 | -0.2 |
March | 21.94 | 5.58 |
April | 22.46 | 10.94 |
May | 23.25 | 16.05 |
June | 24.37 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.34 | 19.96 |
October | 23.44 | 14.02 |
November | 22.02 | 7.31 |
December | 21.76 | 3.33 |
Annual Sum or Average | 22.99 | 12.55 |
Minimum of Months | 21.72 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.77 | 5.58 |
April | 22.22 | 10.94 |
May | 23.14 | 16.05 |
June | 24.37 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 22.90 | 14.02 |
November | 21.80 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.87 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.14 | 1.17 |
February | 20.24 | -0.2 |
March | 21.62 | 5.58 |
April | 22.59 | 10.94 |
May | 23.63 | 16.05 |
June | 23.90 | 21.71 |
July | 23.90 | 25.05 |
August | 23.90 | 24.79 |
September | 23.90 | 19.96 |
October | 23.51 | 14.02 |
November | 21.96 | 7.31 |
December | 20.80 | 3.33 |
Annual Sum or Average | 22.52 | 12.55 |
Minimum of Months | 20.14 | -0.2 |
Maximum of Months | 23.90 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.74 | 5.58 |
April | 22.16 | 10.94 |
May | 23.06 | 16.05 |
June | 24.37 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.30 | 19.96 |
October | 22.78 | 14.02 |
November | 21.78 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.85 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.74 | 5.58 |
April | 22.09 | 10.94 |
May | 22.93 | 16.05 |
June | 24.36 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 22.78 | 14.02 |
November | 21.79 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.83 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.74 | 5.58 |
April | 22.09 | 10.94 |
May | 22.92 | 16.05 |
June | 24.36 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 22.77 | 14.02 |
November | 21.79 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.83 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 1.17 |
February | 21.74 | -0.2 |
March | 21.92 | 5.58 |
April | 22.38 | 10.94 |
May | 23.11 | 16.05 |
June | 24.36 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.36 | 19.96 |
October | 23.48 | 14.02 |
November | 22.08 | 7.31 |
December | 21.78 | 3.33 |
Annual Sum or Average | 22.99 | 12.55 |
Minimum of Months | 21.73 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 1.17 |
February | 21.74 | -0.2 |
March | 21.92 | 5.58 |
April | 22.39 | 10.94 |
May | 23.13 | 16.05 |
June | 24.36 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.35 | 19.96 |
October | 23.47 | 14.02 |
November | 22.09 | 7.31 |
December | 21.78 | 3.33 |
Annual Sum or Average | 22.99 | 12.55 |
Minimum of Months | 21.73 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 1.17 |
February | 21.98 | -0.2 |
March | 22.72 | 5.58 |
April | 23.69 | 10.94 |
May | 24.38 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.31 | 14.02 |
November | 22.90 | 7.31 |
December | 22.05 | 3.33 |
Annual Sum or Average | 23.46 | 12.55 |
Minimum of Months | 21.86 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 1.17 |
February | 21.71 | -0.2 |
March | 22.11 | 5.58 |
April | 23.38 | 10.94 |
May | 24.36 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.10 | 14.02 |
November | 22.50 | 7.31 |
December | 21.71 | 3.33 |
Annual Sum or Average | 23.27 | 12.55 |
Minimum of Months | 21.71 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 1.17 |
February | 21.95 | -0.2 |
March | 22.64 | 5.58 |
April | 23.67 | 10.94 |
May | 24.37 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.30 | 14.02 |
November | 22.91 | 7.31 |
December | 22.04 | 3.33 |
Annual Sum or Average | 23.45 | 12.55 |
Minimum of Months | 21.84 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 22.02 | 5.58 |
April | 23.33 | 10.94 |
May | 24.35 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.39 | 19.96 |
October | 24.06 | 14.02 |
November | 22.45 | 7.31 |
December | 21.71 | 3.33 |
Annual Sum or Average | 23.25 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 1.17 |
February | 21.71 | -0.2 |
March | 22.18 | 5.58 |
April | 23.52 | 10.94 |
May | 24.38 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.20 | 14.02 |
November | 22.74 | 7.31 |
December | 21.73 | 3.33 |
Annual Sum or Average | 23.32 | 12.55 |
Minimum of Months | 21.71 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 1.17 |
February | 21.71 | -0.2 |
March | 22.17 | 5.58 |
April | 23.52 | 10.94 |
May | 24.38 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.20 | 14.02 |
November | 22.74 | 7.31 |
December | 21.73 | 3.33 |
Annual Sum or Average | 23.32 | 12.55 |
Minimum of Months | 21.71 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 1.17 |
February | 22.16 | -0.2 |
March | 22.98 | 5.58 |
April | 23.90 | 10.94 |
May | 24.39 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.36 | 14.02 |
November | 23.26 | 7.31 |
December | 22.31 | 3.33 |
Annual Sum or Average | 23.59 | 12.55 |
Minimum of Months | 22.01 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 1.17 |
February | 22.16 | -0.2 |
March | 22.98 | 5.58 |
April | 23.90 | 10.94 |
May | 24.39 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.40 | 19.96 |
October | 24.36 | 14.02 |
November | 23.26 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.59 | 12.55 |
Minimum of Months | 22.01 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 1.17 |
February | 21.90 | -0.2 |
March | 22.30 | 5.58 |
April | 23.13 | 10.94 |
May | 24.13 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.35 | 19.96 |
October | 23.82 | 14.02 |
November | 22.33 | 7.31 |
December | 21.88 | 3.33 |
Annual Sum or Average | 23.24 | 12.55 |
Minimum of Months | 21.80 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 1.17 |
February | 21.71 | -0.2 |
March | 22.00 | 5.58 |
April | 22.93 | 10.94 |
May | 24.09 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 23.46 | 14.02 |
November | 21.99 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 1.17 |
February | 21.89 | -0.2 |
March | 22.28 | 5.58 |
April | 23.14 | 10.94 |
May | 24.12 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.34 | 19.96 |
October | 23.81 | 14.02 |
November | 22.35 | 7.31 |
December | 21.87 | 3.33 |
Annual Sum or Average | 23.24 | 12.55 |
Minimum of Months | 21.79 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.96 | 5.58 |
April | 22.90 | 10.94 |
May | 24.05 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.30 | 19.96 |
October | 23.39 | 14.02 |
November | 21.96 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.08 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.97 | 5.58 |
April | 22.93 | 10.94 |
May | 24.13 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.32 | 19.96 |
October | 23.47 | 14.02 |
November | 22.00 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.97 | 5.58 |
April | 22.93 | 10.94 |
May | 24.12 | 16.05 |
June | 24.39 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.32 | 19.96 |
October | 23.47 | 14.02 |
November | 22.00 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 1.17 |
February | 21.94 | -0.2 |
March | 22.39 | 5.58 |
April | 23.23 | 10.94 |
May | 24.21 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.37 | 19.96 |
October | 23.93 | 14.02 |
November | 22.48 | 7.31 |
December | 21.95 | 3.33 |
Annual Sum or Average | 23.30 | 12.55 |
Minimum of Months | 21.83 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 1.17 |
February | 21.95 | -0.2 |
March | 22.39 | 5.58 |
April | 23.23 | 10.94 |
May | 24.20 | 16.05 |
June | 24.40 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.37 | 19.96 |
October | 23.93 | 14.02 |
November | 22.49 | 7.31 |
December | 21.95 | 3.33 |
Annual Sum or Average | 23.30 | 12.55 |
Minimum of Months | 21.83 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.37 | 1.17 |
February | 21.44 | -0.2 |
March | 22.67 | 5.58 |
April | 24.12 | 10.94 |
May | 25.92 | 16.05 |
June | 26.84 | 21.71 |
July | 27.22 | 25.05 |
August | 27.15 | 24.79 |
September | 26.44 | 19.96 |
October | 25.10 | 14.02 |
November | 22.62 | 7.31 |
December | 21.66 | 3.33 |
Annual Sum or Average | 24.40 | 12.55 |
Minimum of Months | 21.37 | -0.2 |
Maximum of Months | 27.22 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.90 | 1.17 |
February | 19.77 | -0.2 |
March | 20.88 | 5.58 |
April | 22.10 | 10.94 |
May | 23.48 | 16.05 |
June | 25.81 | 21.71 |
July | 26.50 | 25.05 |
August | 26.55 | 24.79 |
September | 25.71 | 19.96 |
October | 23.41 | 14.02 |
November | 21.33 | 7.31 |
December | 20.36 | 3.33 |
Annual Sum or Average | 23.00 | 12.55 |
Minimum of Months | 19.77 | -0.2 |
Maximum of Months | 26.55 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.15 | 1.17 |
February | 23.34 | -0.2 |
March | 24.23 | 5.58 |
April | 25.57 | 10.94 |
May | 26.66 | 16.05 |
June | 26.98 | 21.71 |
July | 27.13 | 25.05 |
August | 27.15 | 24.79 |
September | 26.86 | 19.96 |
October | 26.47 | 14.02 |
November | 24.63 | 7.31 |
December | 23.45 | 3.33 |
Annual Sum or Average | 25.48 | 12.55 |
Minimum of Months | 23.15 | -0.2 |
Maximum of Months | 27.15 | 25.05 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:29
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.116949E+12 | 76353.639 | 12-JAN-18:30 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32160.519 | 0.000 | 0.000 | 0.000 |
February | 0.105673E+12 | 74361.807 | 08-FEB-18:15 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30168.687 | 0.000 | 0.000 | 0.000 |
March | 0.116347E+12 | 72484.251 | 01-MAR-18:00 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28291.132 | 0.000 | 0.000 | 0.000 |
April | 0.113329E+12 | 78321.980 | 07-APR-17:15 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 12327.271 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24309.919 | 0.000 | 0.000 | 0.000 |
May | 0.121088E+12 | 78851.961 | 31-MAY-17:00 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 13555.701 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23611.469 | 0.000 | 0.000 | 0.000 |
June | 0.130043E+12 | 87042.233 | 19-JUN-17:45 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 24270.863 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21086.580 | 0.000 | 0.000 | 0.000 |
July | 0.145212E+12 | 87119.148 | 19-JUL-17:30 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 20872.606 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24561.753 | 0.000 | 0.000 | 0.000 |
August | 0.142857E+12 | 87630.490 | 04-AUG-17:15 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 23653.214 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22292.487 | 0.000 | 0.000 | 0.000 |
September | 0.124427E+12 | 84345.838 | 07-SEP-17:15 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 20515.707 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22145.342 | 0.000 | 0.000 | 0.000 |
October | 0.119010E+12 | 75668.193 | 05-OCT-17:15 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 9976.095 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24007.309 | 0.000 | 0.000 | 0.000 |
November | 0.110579E+12 | 69158.400 | 08-NOV-18:45 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 1320.500 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23644.780 | 0.000 | 0.000 | 0.000 |
December | 0.115665E+12 | 72297.861 | 18-DEC-18:00 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28104.742 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.146118E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.105673E+12 | 69158.400 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21086.580 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.145212E+12 | 87630.490 | 8572.775 | 26456.413 | 6655.602 | 0.000 | 24270.863 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32160.519 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:29
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.783659E+11 | 85048.768 | 02-JAN-00:15 | 85048.768 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 85048.768 |
February | 0.699716E+11 | 96027.504 | 06-FEB-00:00 | 96027.504 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 96027.504 |
March | 0.299128E+11 | 54783.111 | 22-MAR-06:15 | 54783.111 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 54783.111 |
April | 0.806863E+10 | 27246.847 | 02-APR-02:00 | 27246.847 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27246.847 |
May | 0.176694E+09 | 4383.729 | 01-MAY-04:00 | 4383.729 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4383.729 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.174539E+10 | 10679.814 | 08-OCT-05:00 | 10679.814 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10679.814 |
November | 0.261998E+11 | 62636.282 | 23-NOV-01:00 | 62636.282 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 62636.282 |
December | 0.573694E+11 | 74319.028 | 31-DEC-23:00 | 74319.028 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 74319.028 |
Annual Sum or Average | 0.271810E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.783659E+11 | 96027.504 | 96027.504 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 96027.504 |