Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2018-10-19 09:20:29


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1594.69 508.74 564.70
Net Site Energy 1594.69 508.74 564.70
Total Source Energy 5032.80 1605.56 1782.17
Net Source Energy 5032.80 1605.56 1782.17


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 8.45 0.00 0.00 0.00 0.00
Cooling 275.40 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.43 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 273.07 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 321.92 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1586.25 8.45 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 8.45 0.00 0.00 0.00 0.00
Cooling General 275.40 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.43 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 273.07 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 321.92 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.39 0.00 0.00 0.00 0.00 0.00
HVAC 308.22 2.99 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 561.71 2.99 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.22 0.00 0.00 0.00 0.00 0.00
HVAC 277.67 2.69 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 506.04 2.69 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1586.25 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1586.25 100.00
     
Total On-Site and Utility Electric Sources 1586.25 100.00
Total Electricity End Uses 1586.25 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 5.50
Time Setpoint Not Met During Occupied Cooling 11.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 257.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-JUN-17:30 07-DEC-04:00 - - - 01-JAN-07:15
Heating 0.00 22397.96 0.00 0.00 0.00 0.00
Cooling 28729.72 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8659.09 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 18074.25 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 90492.25 22397.96 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 22397.96 0.00 0.00 0.00 0.00
Cooling General 28729.72 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 8659.09 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 18074.25 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 9.16 0.00 0.00 0.00
Cooling 872.20 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.87 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 864.82 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1019.53 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 5023.65 9.16 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 3.24 0.00 0.00 0.00
Cooling 308.85 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.22 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 306.24 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 361.03 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1778.93 3.24 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 3.24 0.00 0.00 0.00
Cooling 308.85 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.22 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 306.24 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 361.03 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1778.93 3.24 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.72_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 4.600 0.293 0.130     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 4.600 0.293 0.130     No M EWALL C 270.00 90.00 W
Total or Average           306.92 4.600 0.293 0.130              
North Total or Average           112.97 4.600 0.293 0.130              
Non-North Total or Average           193.95 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.74 83.74 39.43
Exterior Lighting Total 2508.33           39.43



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4056.05 3225.69 830.37 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4026.93 3216.13 810.80 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8645.68 6904.92 1740.76 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3236.96 2585.22 651.74 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2454.13 1960.01 494.13 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2442.10 1950.40 491.70 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2616.46 2009.66 606.80 0.77 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2662.27 2046.46 615.81 0.77 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9571.43 7644.27 1927.16 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   9550.45 7627.51 1922.93 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8325.66 6649.33 1676.33 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7897.57 6307.44 1590.13 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5928.05 4734.47 1193.58 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5909.22 4719.43 1189.79 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6321.49 4904.10 1417.39 0.78 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6336.70 4916.33 1420.37 0.78 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6185.05 4939.73 1245.33 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6068.31 4846.49 1221.82 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5583.73 4414.60 1169.13 0.79 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5118.57 4040.59 1077.98 0.79 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3984.44 3182.20 802.25 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3962.40 3164.59 797.81 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4470.70 3505.11 965.60 0.78 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4479.25 3511.96 967.28 0.78 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3865.8 3.13 10.69 11.11 10.41
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3836.3 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8236.4 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3083.7 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2337.9 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2326.5 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2502.8 3.18 10.85 11.29 10.64
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2546.4 3.18 10.85 11.28 10.64
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 9118.3 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 9098.3 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7931.5 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7523.7 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5647.4 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5629.5 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6040.6 3.17 10.81 11.24 10.57
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6055.1 3.17 10.81 11.24 10.57
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5892.2 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5781.0 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5325.1 3.14 10.72 11.14 10.45
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4882.3 3.14 10.73 11.15 10.46
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3795.8 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3774.8 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4267.4 3.15 10.76 11.18 10.50
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4275.5 3.15 10.76 11.18 10.50
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1597.54 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1563.28 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   3186.88 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1571.49 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1411.22 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1411.22 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1411.22 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1411.22 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2944.04 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2913.99 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2965.14 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2935.09 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2822.44 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2822.44 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2822.44 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2822.44 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   2327.97 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   2312.80 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   2339.37 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   2324.21 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1757.84 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1758.04 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1772.94 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1773.14 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 271.93 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 272.48 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.52 585.02 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 219.03 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.06 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.25 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 162.32 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.46 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.58 647.66 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.58 646.24 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 563.36 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 534.39 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 401.13 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 399.85 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 401.14 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 402.18 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 418.52 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 410.62 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 369.57 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 337.63 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.61 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 268.12 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 290.47 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 291.05 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2345.52 2814.63 0.202 0.243 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.94 0.00558
G NW APARTMENT 2350.25 2820.30 0.203 0.243 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 37.94 0.00558
OFFICE 4803.42 5764.10 0.435 0.522 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 34.62 0.00558
G NE APARTMENT 1889.22 2267.06 0.163 0.196 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
G N1 APARTMENT 1432.30 1718.76 0.124 0.148 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61 0.00558
G N2 APARTMENT 1425.28 1710.33 0.123 0.148 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61 0.00558
G S1 APARTMENT 1400.07 1680.09 0.121 0.145 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
G S2 APARTMENT 1427.15 1712.58 0.123 0.148 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
M SW APARTMENT 5586.32 6703.58 0.482 0.578 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.94 0.00558
M NW APARTMENT 5574.00 6688.79 0.481 0.577 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 37.94 0.00558
M SE APARTMENT 4859.24 5831.09 0.419 0.503 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
M NE APARTMENT 4609.38 5531.26 0.398 0.477 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
M N1 APARTMENT 3459.80 4151.76 0.298 0.358 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
M N2 APARTMENT 3448.80 4138.56 0.297 0.357 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
M S1 APARTMENT 3459.93 4151.91 0.298 0.358 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
M S2 APARTMENT 3468.93 4162.71 0.299 0.359 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
T SW APARTMENT 3609.93 4331.91 0.311 0.374 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47 0.00558
T NW APARTMENT 3541.76 4250.11 0.305 0.367 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
T SE APARTMENT 3187.73 3825.27 0.275 0.330 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558
T NE APARTMENT 2912.25 3494.70 0.251 0.301 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
T N1 APARTMENT 2325.46 2790.55 0.201 0.241 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
T N2 APARTMENT 2312.59 2775.11 0.199 0.239 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
T S1 APARTMENT 2505.40 3006.48 0.216 0.259 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 40.80 0.00558
T S2 APARTMENT 2510.44 3012.53 0.217 0.260 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 40.80 0.00558


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 821.22 985.47 0.026 0.031 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
G NW APARTMENT 810.87 973.05 0.026 0.031 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
OFFICE 1994.07 2392.89 0.061 0.073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 0.50 0.00432
G NE APARTMENT 817.82 981.38 0.026 0.031 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
G N1 APARTMENT 426.24 511.48 0.014 0.026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
G N2 APARTMENT 426.33 511.60 0.014 0.026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
G S1 APARTMENT 438.69 526.43 0.014 0.026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
G S2 APARTMENT 509.12 610.95 0.016 0.026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M SW APARTMENT 1467.42 1760.90 0.047 0.056 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M NW APARTMENT 1442.01 1730.41 0.046 0.055 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M SE APARTMENT 1485.26 1782.31 0.047 0.056 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M NE APARTMENT 1459.85 1751.82 0.046 0.056 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M N1 APARTMENT 495.27 594.33 0.016 0.052 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M N2 APARTMENT 495.62 594.74 0.016 0.052 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M S1 APARTMENT 526.26 631.51 0.017 0.052 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
M S2 APARTMENT 526.60 631.92 0.017 0.052 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T SW APARTMENT 1457.55 1749.06 0.046 0.055 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T NW APARTMENT 1444.72 1733.66 0.046 0.055 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T SE APARTMENT 1467.19 1760.62 0.047 0.056 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T NE APARTMENT 1454.37 1745.24 0.046 0.055 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T N1 APARTMENT 975.41 1170.49 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T N2 APARTMENT 975.58 1170.70 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T S1 APARTMENT 988.18 1185.81 0.031 0.038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432
T S2 APARTMENT 988.35 1186.02 0.031 0.038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 0.50 0.00432


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.24 0.24 0.03 0.03
SPLIT GNW 0.24 0.24 0.03 0.03
SPLIT OFFICE 0.52 0.52 0.07 0.07
SPLIT GNE 0.20 0.20 0.03 0.03
SPLIT GN1 0.15 0.15 0.03 0.03
SPLIT GN2 0.15 0.15 0.03 0.03
SPLIT GS1 0.14 0.14 0.03 0.03
SPLIT GS2 0.15 0.15 0.03 0.03
SPLIT MSW 0.58 0.58 0.06 0.06
SPLIT MNW 0.58 0.58 0.05 0.05
SPLIT MSE 0.50 0.50 0.06 0.06
SPLIT MNE 0.48 0.48 0.06 0.06
SPLIT MN1 0.36 0.36 0.05 0.05
SPLIT MN2 0.36 0.36 0.05 0.05
SPLIT MS1 0.36 0.36 0.05 0.05
SPLIT MS2 0.36 0.36 0.05 0.05
SPLIT TSW 0.37 0.37 0.06 0.06
SPLIT TNW 0.37 0.37 0.05 0.05
SPLIT TSE 0.33 0.33 0.06 0.06
SPLIT TNE 0.30 0.30 0.06 0.06
SPLIT TN1 0.24 0.24 0.04 0.04
SPLIT TN2 0.24 0.24 0.04 0.04
SPLIT TS1 0.26 0.26 0.04 0.04
SPLIT TS2 0.26 0.26 0.04 0.04



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2107.75 5085.75 129.75
G NW APARTMENT 2078.25 5548.00 176.25
OFFICE 579.50 1282.75 0.00
G NE APARTMENT 2059.50 5588.00 175.00
G N1 APARTMENT 1920.75 5787.25 165.50
G N2 APARTMENT 1921.75 5786.50 165.25
G S1 APARTMENT 1958.00 5491.50 126.50
G S2 APARTMENT 2005.25 5423.00 115.25
M SW APARTMENT 2870.75 1202.50 55.50
M NW APARTMENT 2471.00 2439.50 61.75
M SE APARTMENT 2920.25 1227.75 62.00
M NE APARTMENT 2513.75 2518.25 70.50
M N1 APARTMENT 2391.50 2292.50 72.00
M N2 APARTMENT 2391.50 2297.75 72.25
M S1 APARTMENT 2714.25 757.25 43.00
M S2 APARTMENT 2715.25 760.75 43.00
T SW APARTMENT 3471.50 2792.00 113.75
T NW APARTMENT 3006.50 3576.25 170.25
T SE APARTMENT 3430.50 2722.75 118.00
T NE APARTMENT 2987.75 3627.00 178.00
T N1 APARTMENT 2612.00 3694.50 149.75
T N2 APARTMENT 2614.50 3692.75 151.25
T S1 APARTMENT 3018.25 2629.25 90.75
T S2 APARTMENT 3021.75 2627.50 90.50
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4122.50 5814.25 257.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.50 0.00 0.50 0.00
G NW APARTMENT 0.00 5.75 0.00 5.75
OFFICE 0.00 24.50 0.00 0.00
G NE APARTMENT 0.25 0.50 0.25 0.50
G N1 APARTMENT 3.00 8.25 3.00 8.25
G N2 APARTMENT 2.25 7.75 2.25 7.75
G S1 APARTMENT 0.00 0.00 0.00 0.00
G S2 APARTMENT 0.00 0.00 0.00 0.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 2.25 0.00 2.25
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 0.00 6.25 0.00 6.25
M N2 APARTMENT 0.00 6.25 0.00 6.25
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.00 0.00 0.00 0.00
T NW APARTMENT 0.00 1.75 0.00 1.75
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 0.00 5.00 0.00 5.00
T N2 APARTMENT 0.00 5.25 0.00 5.25
T S1 APARTMENT 0.50 0.00 0.50 0.00
T S2 APARTMENT 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 5.50 36.00 5.50 11.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.368 0.079 0.000 0.081
G NW APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.075
OFFICE 0.94 1.00 268.97 0.520 0.081 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.075
G N1 APARTMENT 1.71 2.50 268.97 0.354 0.048 0.000 0.074
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.048 0.000 0.074
G S1 APARTMENT 1.71 2.50 268.97 0.355 0.048 0.000 0.081
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.048 0.000 0.081
M SW APARTMENT 1.71 2.50 268.97 0.355 0.114 0.000 0.097
M NW APARTMENT 1.71 2.50 268.97 0.355 0.114 0.000 0.091
M SE APARTMENT 1.71 2.50 268.97 0.355 0.114 0.000 0.097
M NE APARTMENT 1.71 2.50 268.97 0.355 0.114 0.000 0.091
M N1 APARTMENT 1.71 2.50 268.97 0.355 0.069 0.000 0.091
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.069 0.000 0.091
M S1 APARTMENT 1.71 2.50 268.97 0.355 0.069 0.000 0.097
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.069 0.000 0.097
T SW APARTMENT 1.71 2.50 268.97 0.355 0.151 0.000 0.114
T NW APARTMENT 1.71 2.50 268.97 0.355 0.151 0.000 0.106
T SE APARTMENT 1.71 2.50 268.97 0.355 0.151 0.000 0.114
T NE APARTMENT 1.71 2.50 268.97 0.355 0.151 0.000 0.106
T N1 APARTMENT 1.71 2.50 268.97 0.355 0.091 0.000 0.105
T N2 APARTMENT 1.71 2.50 268.97 0.355 0.091 0.000 0.105
T S1 APARTMENT 1.71 2.50 268.97 0.355 0.091 0.000 0.114
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.091 0.000 0.114
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.359 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.509 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.394 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.388 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.393 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.387 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.390 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.390 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.396 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.396 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 321.92 0.00 01-JAN-00:15 32014.34 01-JAN-07:15
WaterSystems:Electricity 321.92 0.00 01-JAN-00:15 32014.34 01-JAN-07:15
Water Heater:WaterSystems:Electricity 321.92 0.00 01-JAN-00:15 32014.34 01-JAN-07:15
Fans:Electricity 273.07 8659.09 01-JAN-00:15 8659.09 01-JAN-07:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
ElectricityPurchased:Plant 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
Cogeneration:ElectricityPurchased 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
ElectricityNet:Plant 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
Cogeneration:ElectricityNet 1586.25 22029.39 01-JAN-03:15 90492.25 29-JUN-17:30
ExteriorLights:Electricity 39.43 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.43 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
Electricity:HVAC 548.47 8659.09 01-JAN-00:15 39062.79 28-JUN-15:30
General:Fans:Electricity 273.07 8659.09 01-JAN-00:15 8659.09 01-JAN-07:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 275.40 0.00 01-JAN-00:15 30403.70 28-JUN-15:30


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 8.45 0.00 01-JAN-11:45 22397.96 07-DEC-05:00
Gas:HVAC 8.45 0.00 01-JAN-11:45 22397.96 07-DEC-05:00
Heating:Gas 8.45 0.00 01-JAN-11:45 22397.96 07-DEC-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1852.04 2474.10 06-MAR-05:00 178035.86 30-JUN-17:15
EnergyTransfer:Building 810.37 2395.98 10-FEB-14:15 77876.41 29-JUN-17:30
EnergyTransfer:Zone:G SW APARTMENT 19.04 0.02 22-DEC-01:00 2704.86 22-JUL-17:30
Heating:EnergyTransfer 14.45 0.00 01-FEB-14:30 10780.94 07-DEC-05:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.34 0.00 01-JAN-08:30 470.07 07-DEC-05:00
Cooling:EnergyTransfer 795.92 19.80 10-FEB-09:15 77637.43 30-JUN-17:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 18.70 0.00 01-JAN-00:15 2704.86 22-JUL-17:30
EnergyTransfer:Zone:G NW APARTMENT 15.35 0.00 07-DEC-21:30 2756.88 30-JUN-17:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.03 0.00 01-JAN-11:45 666.59 07-DEC-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 14.33 0.00 01-JAN-00:15 2756.88 30-JUN-17:30
EnergyTransfer:Zone:OFFICE 31.98 0.00 20-JAN-07:45 4603.18 18-SEP-10:30
Heating:EnergyTransfer:Zone:OFFICE 6.55 0.00 01-JAN-00:15 943.96 27-JUN-17:30
Cooling:EnergyTransfer:Zone:OFFICE 25.43 0.00 01-JAN-11:45 4603.18 18-SEP-10:30
EnergyTransfer:Zone:G NE APARTMENT 15.52 0.01 16-APR-05:00 2110.35 29-JUN-18:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.80 0.00 01-JAN-08:45 701.21 07-DEC-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 14.72 0.00 01-JAN-00:15 2110.35 29-JUN-18:00
EnergyTransfer:Zone:G N1 APARTMENT 11.26 0.00 12-JAN-11:45 1595.53 30-JUN-18:45
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.38 0.00 01-JAN-10:15 314.05 07-DEC-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 10.88 0.00 01-JAN-00:15 1595.53 30-JUN-18:45
EnergyTransfer:Zone:G N2 APARTMENT 11.27 0.00 11-OCT-02:45 1586.16 30-JUN-18:45
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.38 0.00 01-JAN-10:15 316.33 07-DEC-04:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 10.89 0.00 01-JAN-00:15 1586.16 30-JUN-18:45
EnergyTransfer:Zone:G S1 APARTMENT 15.06 0.01 14-FEB-14:45 1850.18 28-SEP-13:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.04 0.00 01-JAN-00:15 253.55 06-DEC-01:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 15.02 0.00 02-JAN-18:00 1850.18 28-SEP-13:15
EnergyTransfer:Zone:G S2 APARTMENT 15.79 0.02 13-NOV-11:15 1873.99 28-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.04 0.00 01-JAN-00:15 250.19 06-DEC-05:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 15.76 0.00 02-JAN-17:45 1873.99 28-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 68.33 0.42 08-MAR-10:00 6489.37 10-OCT-15:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.01 0.00 01-JAN-00:15 259.05 10-FEB-09:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 68.32 0.00 24-JAN-05:00 6489.37 10-OCT-15:30
EnergyTransfer:Zone:M NW APARTMENT 52.10 0.03 12-DEC-04:45 6620.58 29-JUN-18:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.15 0.00 01-JAN-00:15 407.67 08-DEC-16:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 51.96 0.00 01-JAN-12:15 6620.58 29-JUN-18:30
EnergyTransfer:Zone:M SE APARTMENT 69.57 1.16 11-FEB-11:30 5455.69 28-SEP-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.01 0.00 01-JAN-00:15 220.05 12-NOV-11:30
Cooling:EnergyTransfer:Zone:M SE APARTMENT 69.57 0.00 10-FEB-06:15 5455.69 28-SEP-13:30
EnergyTransfer:Zone:M NE APARTMENT 53.22 0.01 18-DEC-11:30 5293.53 29-JUN-18:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.07 0.00 01-JAN-00:15 333.15 09-DEC-13:45
Cooling:EnergyTransfer:Zone:M NE APARTMENT 53.15 0.00 01-JAN-02:15 5293.53 29-JUN-18:00
EnergyTransfer:Zone:M N1 APARTMENT 43.50 0.05 29-MAR-11:30 3986.67 30-JUN-18:45
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.01 0.00 01-JAN-00:15 209.71 09-DEC-13:45
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 43.49 0.00 02-JAN-10:30 3986.67 30-JUN-18:45
EnergyTransfer:Zone:M N2 APARTMENT 43.53 0.02 03-FEB-14:45 3971.94 30-JUN-18:45
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.01 0.00 01-JAN-00:15 208.75 09-DEC-13:45
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 43.52 0.00 02-JAN-10:30 3971.94 30-JUN-18:45
EnergyTransfer:Zone:M S1 APARTMENT 60.47 8.46 08-MAR-11:15 4907.87 20-NOV-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 60.47 8.46 08-MAR-11:15 4907.87 20-NOV-13:30
EnergyTransfer:Zone:M S2 APARTMENT 60.50 7.26 08-MAR-11:15 4913.60 20-NOV-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 60.50 7.26 08-MAR-11:15 4913.60 20-NOV-13:30
EnergyTransfer:Zone:T SW APARTMENT 33.91 0.03 26-JAN-05:30 4111.02 28-JUN-17:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 0.77 0.00 01-JAN-09:00 1078.72 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 33.14 0.00 01-JAN-00:15 4111.02 28-JUN-17:15
EnergyTransfer:Zone:T NW APARTMENT 27.77 0.01 25-DEC-11:45 4253.12 29-JUN-17:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 1.45 0.00 01-JAN-15:30 1302.82 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 26.32 0.00 01-JAN-00:15 4253.12 29-JUN-17:30
EnergyTransfer:Zone:T SE APARTMENT 34.03 0.00 03-JAN-00:45 3441.45 28-SEP-13:45
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.54 0.00 01-JAN-08:30 1097.39 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 33.48 0.00 01-JAN-00:15 3441.45 28-SEP-13:45
EnergyTransfer:Zone:T NE APARTMENT 27.37 0.00 31-JAN-01:45 3387.81 30-JUN-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 0.97 0.00 01-JAN-10:30 1350.20 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 26.40 0.00 01-JAN-00:15 3387.81 30-JUN-16:15
EnergyTransfer:Zone:T N1 APARTMENT 21.73 0.01 16-DEC-13:00 2713.87 29-JUN-18:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.36 0.00 01-JAN-11:15 814.87 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 21.37 0.00 01-JAN-00:15 2713.87 29-JUN-18:30
EnergyTransfer:Zone:T N2 APARTMENT 21.75 0.01 07-JAN-07:00 2696.86 29-JUN-18:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.35 0.00 01-JAN-11:15 819.42 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 21.40 0.00 01-JAN-00:15 2696.86 29-JUN-18:30
EnergyTransfer:Zone:T S1 APARTMENT 28.64 0.01 19-NOV-05:30 2937.26 28-SEP-13:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.10 0.00 01-JAN-00:15 566.40 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 28.53 0.00 01-JAN-02:15 2937.26 28-SEP-13:30
EnergyTransfer:Zone:T S2 APARTMENT 28.67 0.01 07-JAN-00:30 2943.53 28-SEP-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.10 0.00 01-JAN-00:15 566.32 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 28.56 0.00 01-JAN-02:15 2943.53 28-SEP-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1041.67 0.00 10-FEB-09:00 101266.82 28-JUN-17:00
HeatingCoils:EnergyTransfer 6.76 0.00 01-JAN-11:45 17918.37 07-DEC-05:00
CoolingCoils:EnergyTransfer 1034.91 0.00 01-JAN-00:15 101266.82 28-JUN-17:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.338 -18.698 0.000 0.000 3.648 2.413 12.213 18.632 0.000 0.663 0.000 0.000 -5.000 0.000 -1.704 -12.505
G NW APARTMENT 1.026 -14.328 0.000 0.000 3.685 2.413 12.213 11.218 0.000 0.660 0.000 0.000 -5.019 0.000 -1.534 -10.335
OFFICE 6.547 -25.432 0.000 0.000 0.517 21.914 7.534 18.202 0.000 0.429 0.000 0.000 -5.498 0.000 -0.991 -23.222
G NE APARTMENT 0.797 -14.723 0.000 0.000 3.697 2.413 12.213 11.337 0.000 0.660 0.000 0.000 -4.699 0.000 -1.523 -10.172
G N1 APARTMENT 0.383 -10.877 0.000 0.000 3.698 2.413 12.213 4.482 0.000 0.415 0.000 0.000 -3.016 0.000 -1.147 -8.564
G N2 APARTMENT 0.379 -10.890 0.000 0.000 3.698 2.413 12.213 4.481 0.000 0.415 0.000 0.000 -3.014 0.000 -1.147 -8.547
G S1 APARTMENT 0.040 -15.021 0.000 0.000 3.645 2.413 12.213 11.981 0.000 0.415 0.000 0.000 -3.023 0.000 -1.362 -11.302
G S2 APARTMENT 0.036 -15.756 0.000 0.000 3.643 2.413 12.213 11.968 0.000 0.415 0.000 0.000 -3.033 0.000 -1.367 -10.532
M SW APARTMENT 0.010 -68.322 0.000 0.000 3.534 2.413 12.213 18.030 0.000 0.943 39.236 0.000 -5.722 0.000 -2.334 0.000
M NW APARTMENT 0.145 -51.956 0.000 0.000 3.553 2.413 12.213 10.713 0.000 0.939 30.090 0.000 -5.837 0.000 -2.274 -0.000
M SE APARTMENT 0.007 -69.565 0.000 0.000 3.537 2.413 12.213 18.285 0.000 0.943 40.056 0.000 -5.557 0.000 -2.331 0.000
M NE APARTMENT 0.067 -53.154 0.000 0.000 3.559 2.413 12.213 10.772 0.000 0.939 30.929 0.000 -5.470 0.000 -2.269 -0.000
M N1 APARTMENT 0.011 -43.489 0.000 0.000 3.541 2.413 12.213 4.189 0.000 0.584 25.908 0.000 -3.602 0.000 -1.768 0.000
M N2 APARTMENT 0.011 -43.519 0.000 0.000 3.541 2.413 12.213 4.189 0.000 0.584 25.938 0.000 -3.601 0.000 -1.768 0.000
M S1 APARTMENT 0.000 -60.474 0.000 0.000 3.524 2.413 12.213 11.601 0.000 0.588 35.424 0.000 -3.470 0.000 -1.819 0.000
M S2 APARTMENT 0.000 -60.501 0.000 0.000 3.524 2.413 12.213 11.600 0.000 0.588 35.451 0.000 -3.470 0.000 -1.819 0.000
T SW APARTMENT 0.772 -33.141 0.000 0.000 3.599 2.413 12.213 17.725 0.000 1.235 3.383 0.000 -5.384 0.000 -2.815 -0.000
T NW APARTMENT 1.452 -26.322 0.000 0.000 3.623 2.413 12.213 10.511 0.000 1.229 2.986 0.000 -5.425 0.000 -2.681 -0.000
T SE APARTMENT 0.543 -33.484 0.000 0.000 3.605 2.413 12.213 17.994 0.000 1.235 3.521 0.000 -5.226 0.000 -2.814 -0.000
T NE APARTMENT 0.968 -26.403 0.000 0.000 3.632 2.413 12.213 10.631 0.000 1.229 3.121 0.000 -5.111 0.000 -2.693 -0.000
T N1 APARTMENT 0.357 -21.369 0.000 0.000 3.616 2.413 12.213 4.139 0.000 0.762 3.220 0.000 -3.318 0.000 -2.033 -0.000
T N2 APARTMENT 0.353 -21.396 0.000 0.000 3.617 2.413 12.213 4.137 0.000 0.762 3.251 0.000 -3.316 0.000 -2.034 -0.000
T S1 APARTMENT 0.103 -28.532 0.000 0.000 3.584 2.413 12.213 11.431 0.000 0.768 3.483 0.000 -3.293 0.000 -2.171 -0.000
T S2 APARTMENT 0.104 -28.561 0.000 0.000 3.585 2.413 12.213 11.430 0.000 0.768 3.511 0.000 -3.291 0.000 -2.171 -0.000
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.358 0.000 0.116 0.000 0.000 -0.549 0.000 -0.346 -16.649
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 1.157 0.000 4.876 0.000 0.000 -1.264 0.000 -10.203 -17.902
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.369 0.000 0.096 0.000 0.000 -0.621 0.000 -0.295 -16.620
Total Facility 14.451 -795.914 0.000 0.000 83.405 128.627 294.692 271.563 0.000 23.256 289.508 0.000 -105.828 0.000 -57.408 -146.352


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 22-JUL-17:25 0.00 -2705.09 0.00 0.00 141.80 194.45 588.62 1981.13 0.00 248.20 0.00 0.00 0.00 0.00 0.00 -449.12
G NW APARTMENT 30-JUN-17:25 0.00 -2756.89 0.00 0.00 141.80 194.45 588.62 2174.23 0.00 252.27 0.00 0.00 0.00 0.00 0.00 -594.50
OFFICE 30-JUL-06:01 0.00 -7772.75 0.00 0.00 0.00 379.58 194.98 545.57 0.00 0.00 6664.53 0.00 0.00 0.00 -11.91 0.00
G NE APARTMENT 29-JUN-17:45 0.00 -2110.30 0.00 0.00 141.80 194.45 588.62 1193.20 0.00 211.62 0.00 0.00 0.00 0.00 0.00 -219.40
G N1 APARTMENT 30-JUN-18:45 0.00 -1595.39 0.00 0.00 141.06 230.46 547.42 727.47 0.00 117.70 0.00 0.00 0.00 0.00 0.00 -168.73
G N2 APARTMENT 30-JUN-18:45 0.00 -1586.02 0.00 0.00 141.05 230.46 547.42 727.58 0.00 117.69 0.00 0.00 0.00 0.00 0.00 -178.17
G S1 APARTMENT 28-SEP-13:15 0.00 -1849.84 0.00 0.00 40.75 28.81 382.60 1898.69 0.00 28.53 0.00 0.00 0.00 0.00 0.00 -529.55
G S2 APARTMENT 28-SEP-13:30 0.00 -1873.63 0.00 0.00 40.75 28.81 382.60 1880.90 0.00 33.18 0.00 0.00 0.00 0.00 0.00 -492.61
M SW APARTMENT 10-OCT-15:30 0.00 -6488.41 0.00 0.00 48.90 100.83 470.90 2814.44 0.00 162.11 2891.24 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 29-JUN-18:30 0.00 -6620.21 0.00 0.00 141.06 230.46 547.42 2089.27 0.00 268.77 3343.24 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 28-SEP-13:30 0.00 -5454.72 0.00 0.00 40.75 28.81 382.60 2224.69 0.00 78.96 2698.91 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 29-JUN-18:00 0.00 -5293.25 0.00 0.00 141.80 194.45 588.62 1192.26 0.00 298.46 2877.65 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 30-JUN-18:45 0.00 -3986.33 0.00 0.00 141.12 230.46 547.42 717.75 0.00 168.86 2180.72 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 30-JUN-18:45 0.00 -3971.60 0.00 0.00 141.11 230.46 547.42 717.82 0.00 168.85 2165.94 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 20-NOV-13:30 0.00 -4907.19 0.00 0.00 40.75 28.81 388.49 2341.69 0.00 46.71 2060.74 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 20-NOV-13:30 0.00 -4912.92 0.00 0.00 40.75 28.81 388.49 2341.66 0.00 46.71 2066.51 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 28-JUN-17:04 0.00 -4111.48 0.00 0.00 141.80 194.45 588.62 2110.28 0.00 320.40 755.92 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 29-JUN-17:20 0.00 -4253.51 0.00 0.00 141.80 194.45 588.62 2307.07 0.00 407.67 613.89 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 28-SEP-13:45 0.00 -3440.83 0.00 0.00 40.75 28.81 382.60 2125.06 0.00 119.65 743.96 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 30-JUN-16:03 0.00 -3388.99 0.00 0.00 84.76 144.04 588.62 1059.32 0.00 532.85 979.40 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-JUN-18:30 0.00 -2713.73 0.00 0.00 140.77 230.46 547.42 873.98 0.00 213.09 708.01 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-18:30 0.00 -2696.71 0.00 0.00 140.76 230.46 547.42 874.22 0.00 213.09 690.76 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 28-SEP-13:30 0.00 -2936.75 0.00 0.00 40.75 28.81 382.60 1843.27 0.00 62.78 578.54 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 28-SEP-13:30 0.00 -2943.03 0.00 0.00 40.75 28.81 382.60 1843.17 0.00 62.78 584.91 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-JUN-17:04 0.00 -77674.40 0.00 0.00 3261.35 6475.86 14071.03 24847.77 0.00 7954.64 21063.76 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 08-FEB-07:01 1369.05 0.00 0.00 0.00 162.55 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -568.09 0.00 -35.94 -1403.80
G NW APARTMENT 27-NOV-07:01 815.24 0.00 0.00 0.00 162.09 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -512.51 0.00 -72.36 -868.69
OFFICE 18-DEC-07:01 2863.01 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -707.29 0.00 -109.66 -2620.62
G NE APARTMENT 23-JAN-07:01 784.72 0.00 0.00 0.00 162.07 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -460.75 0.00 -96.53 -865.73
G N1 APARTMENT 05-DEC-07:08 728.18 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -504.22 0.00 -21.13 -840.28
G N2 APARTMENT 05-DEC-06:06 592.88 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -482.09 0.00 -16.32 -702.82
G S1 APARTMENT 07-DEC-06:23 616.32 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -533.78 0.00 -78.77 -612.13
G S2 APARTMENT 06-DEC-05:15 500.38 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -525.30 0.00 -60.73 -450.75
M SW APARTMENT 10-FEB-09:00 259.03 0.00 0.00 0.00 63.78 43.21 388.49 0.00 0.00 0.00 34.21 0.00 -195.49 0.00 -593.24 0.00
M NW APARTMENT 08-DEC-16:00 407.65 0.00 0.00 0.00 40.94 50.41 400.26 242.38 0.00 0.00 0.00 0.00 0.00 0.00 -167.17 -974.47
M SE APARTMENT 12-NOV-11:30 220.05 0.00 0.00 0.00 40.75 28.81 412.04 0.00 0.00 0.00 0.00 0.00 -331.13 0.00 -326.21 -44.30
M NE APARTMENT 09-DEC-13:45 333.16 0.00 0.00 0.00 41.10 28.81 388.49 226.13 0.00 0.00 0.00 0.00 0.00 0.00 -72.73 -944.96
M N1 APARTMENT 09-DEC-13:45 209.71 0.00 0.00 0.00 41.02 28.81 388.49 134.86 0.00 0.00 0.00 0.00 0.00 0.00 -68.37 -734.52
M N2 APARTMENT 09-DEC-13:45 208.76 0.00 0.00 0.00 41.01 28.81 388.49 134.79 0.00 0.00 0.00 0.00 0.00 0.00 -68.44 -733.41
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 07-DEC-05:00 1078.72 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -913.46 0.00 -285.53 -336.28
T NW APARTMENT 07-DEC-05:00 1302.82 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -881.74 0.00 -285.53 -592.11
T SE APARTMENT 07-DEC-05:00 1097.39 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -928.40 0.00 -285.53 -340.01
T NE APARTMENT 07-DEC-05:00 1350.20 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -895.73 0.00 -285.53 -625.49
T N1 APARTMENT 31-MAR-06:01 1431.86 0.00 0.00 0.00 162.56 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -404.95 0.00 -150.63 -1515.07
T N2 APARTMENT 31-MAR-06:01 1446.92 0.00 0.00 0.00 162.57 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -404.91 0.00 -150.63 -1530.18
T S1 APARTMENT 07-DEC-05:00 566.40 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -565.07 0.00 -172.23 -285.66
T S2 APARTMENT 07-DEC-05:00 566.32 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -565.06 0.00 -172.23 -285.59
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 07-DEC-07:01 6540.35 0.00 0.00 0.00 3680.84 4156.84 9398.91 0.00 0.00 0.00 6601.77 0.00 -16120.72 0.00 -14257.98 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Sec1.1A-General Information

Data
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 5.50
Number of hours cooling loads not met 11.50
Number of hours not met 17.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.43 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 8.45 22397.96 0.00 0.00
Space Cooling 275.40 28729.72 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 273.07 8659.09 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 321.92 18074.25 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1586.25   8.45   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1586.25
Natural Gas 0.00 8.45
Additional 0.00 0.00
Total 511.42 1594.69


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 87.86
Fans-Interior 87.12
Service Water Heating 102.70
Receptacle Equipment 163.15
Miscellaneous 12.58
Subtotal 506.04


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 2.69
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 2.69


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.35
Space Heating 0.53
Space Cooling 17.27
Fans-Interior 17.12
Service Water Heating 20.19
Receptacle Equipment 32.07
Miscellaneous 2.47



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.242775
G NW APARTMENT DIRECT AIR 0.243267
OFFICE DIRECT AIR 0.522286
G NE APARTMENT DIRECT AIR 0.195545
G N1 APARTMENT DIRECT AIR 0.148254
G N2 APARTMENT DIRECT AIR 0.147527
G S1 APARTMENT DIRECT AIR 0.144917
G S2 APARTMENT DIRECT AIR 0.147720
M SW APARTMENT DIRECT AIR 0.578210
M NW APARTMENT DIRECT AIR 0.576942
M SE APARTMENT DIRECT AIR 0.502953
M NE APARTMENT DIRECT AIR 0.477092
M N1 APARTMENT DIRECT AIR 0.358114
M N2 APARTMENT DIRECT AIR 0.356976
M S1 APARTMENT DIRECT AIR 0.358124
M S2 APARTMENT DIRECT AIR 0.359055
T SW APARTMENT DIRECT AIR 0.373639
T NW APARTMENT DIRECT AIR 0.366587
T SE APARTMENT DIRECT AIR 0.329940
T NE APARTMENT DIRECT AIR 0.301427
T N1 APARTMENT DIRECT AIR 0.240700
T N2 APARTMENT DIRECT AIR 0.239368
T S1 APARTMENT DIRECT AIR 0.259322
T S2 APARTMENT DIRECT AIR 0.259844


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.242775
SPLIT GNW MAIN BRANCH 0.243267
SPLIT OFFICE MAIN BRANCH 0.522286
SPLIT GNE MAIN BRANCH 0.195545
SPLIT GN1 MAIN BRANCH 0.148254
SPLIT GN2 MAIN BRANCH 0.147527
SPLIT GS1 MAIN BRANCH 0.144917
SPLIT GS2 MAIN BRANCH 0.147720
SPLIT MSW MAIN BRANCH 0.578210
SPLIT MNW MAIN BRANCH 0.576942
SPLIT MSE MAIN BRANCH 0.502953
SPLIT MNE MAIN BRANCH 0.477092
SPLIT MN1 MAIN BRANCH 0.358114
SPLIT MN2 MAIN BRANCH 0.356976
SPLIT MS1 MAIN BRANCH 0.358124
SPLIT MS2 MAIN BRANCH 0.359055
SPLIT TSW MAIN BRANCH 0.373639
SPLIT TNW MAIN BRANCH 0.366587
SPLIT TSE MAIN BRANCH 0.329940
SPLIT TNE MAIN BRANCH 0.301427
SPLIT TN1 MAIN BRANCH 0.240700
SPLIT TN2 MAIN BRANCH 0.239368
SPLIT TS1 MAIN BRANCH 0.259322
SPLIT TS2 MAIN BRANCH 0.259844


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.242775
SPLIT GNW 0.243267
SPLIT OFFICE 0.522286
SPLIT GNE 0.195545
SPLIT GN1 0.148254
SPLIT GN2 0.147527
SPLIT GS1 0.144917
SPLIT GS2 0.147720
SPLIT MSW 0.578210
SPLIT MNW 0.576942
SPLIT MSE 0.502953
SPLIT MNE 0.477092
SPLIT MN1 0.358114
SPLIT MN2 0.356976
SPLIT MS1 0.358124
SPLIT MS2 0.359055
SPLIT TSW 0.373639
SPLIT TNW 0.366587
SPLIT TSE 0.329940
SPLIT TNE 0.301427
SPLIT TN1 0.240700
SPLIT TN2 0.239368
SPLIT TS1 0.259322
SPLIT TS2 0.259844


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.242775 0.026898
SPLIT GNW OA CONTROLLER 0.243267 0.025953
SPLIT OFFICE OA CONTROLLER 0.522286 0.038104
SPLIT GNE OA CONTROLLER 0.195545 0.025953
SPLIT GN1 OA CONTROLLER 0.148254 0.025953
SPLIT GN2 OA CONTROLLER 0.147527 0.025953
SPLIT GS1 OA CONTROLLER 0.144917 0.025953
SPLIT GS2 OA CONTROLLER 0.147720 0.025953
SPLIT MSW OA CONTROLLER 0.578210 0.051906
SPLIT MNW OA CONTROLLER 0.576942 0.051906
SPLIT MSE OA CONTROLLER 0.502953 0.051906
SPLIT MNE OA CONTROLLER 0.477092 0.051906
SPLIT MN1 OA CONTROLLER 0.358114 0.051906
SPLIT MN2 OA CONTROLLER 0.356976 0.051906
SPLIT MS1 OA CONTROLLER 0.358124 0.051906
SPLIT MS2 OA CONTROLLER 0.359055 0.051906
SPLIT TSW OA CONTROLLER 0.373639 0.025953
SPLIT TNW OA CONTROLLER 0.366587 0.025953
SPLIT TSE OA CONTROLLER 0.329940 0.025953
SPLIT TNE OA CONTROLLER 0.301427 0.025953
SPLIT TN1 OA CONTROLLER 0.240700 0.025953
SPLIT TN2 OA CONTROLLER 0.239368 0.025953
SPLIT TS1 OA CONTROLLER 0.259322 0.025953
SPLIT TS2 OA CONTROLLER 0.259844 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.242775 4056.05 0.795277
SPLIT GNW COOLING COIL 0.243267 4026.93 0.798655
SPLIT OFFICE COOLING COIL 0.522286 8645.68 0.798655
SPLIT GNE COOLING COIL 0.195545 3236.96 0.798655
SPLIT GN1 COOLING COIL 0.148254 2454.13 0.798655
SPLIT GN2 COOLING COIL 0.147527 2442.10 0.798655
SPLIT GS1 COOLING COIL 0.144917 2616.46 0.768083
SPLIT GS2 COOLING COIL 0.147720 2662.27 0.768690
SPLIT MSW COOLING COIL 0.578210 9571.43 0.798655
SPLIT MNW COOLING COIL 0.576942 9550.45 0.798655
SPLIT MSE COOLING COIL 0.502953 8325.66 0.798655
SPLIT MNE COOLING COIL 0.477092 7897.57 0.798655
SPLIT MN1 COOLING COIL 0.358114 5928.05 0.798655
SPLIT MN2 COOLING COIL 0.356976 5909.22 0.798655
SPLIT MS1 COOLING COIL 0.358124 6321.49 0.775783
SPLIT MS2 COOLING COIL 0.359055 6336.70 0.775850
SPLIT TSW COOLING COIL 0.373639 6185.05 0.798655
SPLIT TNW COOLING COIL 0.366587 6068.31 0.798655
SPLIT TSE COOLING COIL 0.329940 5583.73 0.790619
SPLIT TNE COOLING COIL 0.301427 5118.57 0.789398
SPLIT TN1 COOLING COIL 0.240700 3984.44 0.798655
SPLIT TN2 COOLING COIL 0.239368 3962.40 0.798655
SPLIT TS1 COOLING COIL 0.259322 4470.70 0.784017
SPLIT TS2 COOLING COIL 0.259844 4479.25 0.784053


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.242775 0.242775 0.242775 0.242775 1597.54 4056.05 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.243267 0.243267 0.243267 0.243267 1563.28 4026.93 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.522286 0.522286 0.522286 0.522286 3186.88 8645.68 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.195545 0.195545 0.195545 0.195545 1571.49 3236.96 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.148254 0.148254 0.148254 0.148254 1411.22 2454.13 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.147527 0.147527 0.147527 0.147527 1411.22 2442.10 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.144917 0.144917 0.144917 0.144917 1411.22 2616.46 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.147720 0.147720 0.147720 0.147720 1411.22 2662.27 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.578210 0.578210 0.578210 0.578210 2944.04 9571.43 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.576942 0.576942 0.576942 0.576942 2913.99 9550.45 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.502953 0.502953 0.502953 0.502953 2965.14 8325.66 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.477092 0.477092 0.477092 0.477092 2935.09 7897.57 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.358114 0.358114 0.358114 0.358114 2822.44 5928.05 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.356976 0.356976 0.356976 0.356976 2822.44 5909.22 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.358124 0.358124 0.358124 0.358124 2822.44 6321.49 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.359055 0.359055 0.359055 0.359055 2822.44 6336.70 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.373639 0.373639 0.373639 0.373639 2327.97 6185.05 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.366587 0.366587 0.366587 0.366587 2312.80 6068.31 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.329940 0.329940 0.329940 0.329940 2339.37 5583.73 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.301427 0.301427 0.301427 0.301427 2324.21 5118.57 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.240700 0.240700 0.240700 0.240700 1757.84 3984.44 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.239368 0.239368 0.239368 0.239368 1758.04 3962.40 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.259322 0.259322 0.259322 0.259322 1772.94 4470.70 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.259844 0.259844 0.259844 0.259844 1773.14 4479.25 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.242775
SPLIT GNW SUPPLY FAN 0.243267
SPLIT OFFICE SUPPLY FAN 0.522286
SPLIT GNE SUPPLY FAN 0.195545
SPLIT GN1 SUPPLY FAN 0.148254
SPLIT GN2 SUPPLY FAN 0.147527
SPLIT GS1 SUPPLY FAN 0.144917
SPLIT GS2 SUPPLY FAN 0.147720
SPLIT MSW SUPPLY FAN 0.578210
SPLIT MNW SUPPLY FAN 0.576942
SPLIT MSE SUPPLY FAN 0.502953
SPLIT MNE SUPPLY FAN 0.477092
SPLIT MN1 SUPPLY FAN 0.358114
SPLIT MN2 SUPPLY FAN 0.356976
SPLIT MS1 SUPPLY FAN 0.358124
SPLIT MS2 SUPPLY FAN 0.359055
SPLIT TSW SUPPLY FAN 0.373639
SPLIT TNW SUPPLY FAN 0.366587
SPLIT TSE SUPPLY FAN 0.329940
SPLIT TNE SUPPLY FAN 0.301427
SPLIT TN1 SUPPLY FAN 0.240700
SPLIT TN2 SUPPLY FAN 0.239368
SPLIT TS1 SUPPLY FAN 0.259322
SPLIT TS2 SUPPLY FAN 0.259844


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1597.54
SPLIT GNW HEATING COIL 1563.28
SPLIT OFFICE HEATING COIL 3186.88
SPLIT GNE HEATING COIL 1571.49
SPLIT GN1 HEATING COIL 1411.22
SPLIT GN2 HEATING COIL 1411.22
SPLIT GS1 HEATING COIL 1411.22
SPLIT GS2 HEATING COIL 1411.22
SPLIT MSW HEATING COIL 2944.04
SPLIT MNW HEATING COIL 2913.99
SPLIT MSE HEATING COIL 2965.14
SPLIT MNE HEATING COIL 2935.09
SPLIT MN1 HEATING COIL 2822.44
SPLIT MN2 HEATING COIL 2822.44
SPLIT MS1 HEATING COIL 2822.44
SPLIT MS2 HEATING COIL 2822.44
SPLIT TSW HEATING COIL 2327.97
SPLIT TNW HEATING COIL 2312.80
SPLIT TSE HEATING COIL 2339.37
SPLIT TNE HEATING COIL 2324.21
SPLIT TN1 HEATING COIL 1757.84
SPLIT TN2 HEATING COIL 1758.04
SPLIT TS1 HEATING COIL 1772.94
SPLIT TS2 HEATING COIL 1773.14



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.47 14.83
February 23.08 12.72
March 23.37 15.42
April 24.22 23.31
May 24.36 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.12 20.87
November 23.64 15.43
December 23.13 11.86
     
Annual Sum or Average 23.92 21.71
Minimum of Months 23.08 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.94 14.83
February 22.52 12.72
March 23.10 15.42
April 24.19 23.31
May 24.37 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 23.96 20.87
November 23.20 15.43
December 22.48 11.86
     
Annual Sum or Average 23.70 21.71
Minimum of Months 22.48 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 14.83
February 23.52 12.72
March 24.09 15.42
April 25.75 23.31
May 26.21 26.31
June 27.33 31.20
July 27.43 30.42
August 27.16 29.82
September 27.29 27.75
October 25.52 20.87
November 24.28 15.43
December 23.55 11.86
     
Annual Sum or Average 25.53 21.71
Minimum of Months 23.52 11.86
Maximum of Months 27.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 14.83
February 22.46 12.72
March 23.09 15.42
April 24.18 23.31
May 24.36 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 23.95 20.87
November 23.12 15.43
December 22.41 11.86
     
Annual Sum or Average 23.68 21.71
Minimum of Months 22.41 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 14.83
February 22.35 12.72
March 22.94 15.42
April 24.13 23.31
May 24.35 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 23.92 20.87
November 23.04 15.43
December 22.33 11.86
     
Annual Sum or Average 23.63 21.71
Minimum of Months 22.33 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 14.83
February 22.35 12.72
March 22.94 15.42
April 24.13 23.31
May 24.35 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 23.92 20.87
November 23.03 15.43
December 22.33 11.86
     
Annual Sum or Average 23.62 21.71
Minimum of Months 22.33 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.54 14.83
February 23.10 12.72
March 23.35 15.42
April 24.18 23.31
May 24.34 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.14 20.87
November 23.68 15.43
December 23.20 11.86
     
Annual Sum or Average 23.93 21.71
Minimum of Months 23.10 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.55 14.83
February 23.11 12.72
March 23.37 15.42
April 24.20 23.31
May 24.35 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.15 20.87
November 23.70 15.43
December 23.21 11.86
     
Annual Sum or Average 23.94 21.71
Minimum of Months 23.11 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 14.83
February 24.31 12.72
March 24.27 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.39 20.87
November 24.34 15.43
December 24.13 11.86
     
Annual Sum or Average 24.34 21.71
Minimum of Months 24.13 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.10 14.83
February 24.18 12.72
March 24.20 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.37 20.87
November 24.22 15.43
December 23.74 11.86
     
Annual Sum or Average 24.27 21.71
Minimum of Months 23.74 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 14.83
February 24.28 12.72
March 24.26 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.38 20.87
November 24.32 15.43
December 24.10 11.86
     
Annual Sum or Average 24.33 21.71
Minimum of Months 24.10 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.06 14.83
February 24.15 12.72
March 24.19 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.36 20.87
November 24.19 15.43
December 23.70 11.86
     
Annual Sum or Average 24.25 21.71
Minimum of Months 23.70 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.19 14.83
February 24.28 12.72
March 24.28 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.39 20.87
November 24.29 15.43
December 23.93 11.86
     
Annual Sum or Average 24.31 21.71
Minimum of Months 23.93 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.19 14.83
February 24.27 12.72
March 24.28 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.39 20.87
November 24.29 15.43
December 23.93 11.86
     
Annual Sum or Average 24.31 21.71
Minimum of Months 23.93 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 14.83
February 24.37 12.72
March 24.33 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.40 20.87
November 24.38 15.43
December 24.27 11.86
     
Annual Sum or Average 24.38 21.71
Minimum of Months 24.27 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 14.83
February 24.37 12.72
March 24.33 15.42
April 24.40 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.40 20.87
November 24.38 15.43
December 24.27 11.86
     
Annual Sum or Average 24.38 21.71
Minimum of Months 24.27 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 14.83
February 23.70 12.72
March 23.82 15.42
April 24.36 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.23 20.87
November 23.92 15.43
December 23.42 11.86
     
Annual Sum or Average 24.10 21.71
Minimum of Months 23.42 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.44 14.83
February 23.40 12.72
March 23.69 15.42
April 24.36 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.14 20.87
November 23.67 15.43
December 22.99 11.86
     
Annual Sum or Average 23.98 21.71
Minimum of Months 22.99 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.73 14.83
February 23.66 12.72
March 23.81 15.42
April 24.36 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.22 20.87
November 23.89 15.43
December 23.41 11.86
     
Annual Sum or Average 24.09 21.71
Minimum of Months 23.41 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.45 14.83
February 23.36 12.72
March 23.69 15.42
April 24.34 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.14 20.87
November 23.65 15.43
December 22.96 11.86
     
Annual Sum or Average 23.97 21.71
Minimum of Months 22.96 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 14.83
February 23.44 12.72
March 23.76 15.42
April 24.36 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.17 20.87
November 23.71 15.43
December 22.97 11.86
     
Annual Sum or Average 24.00 21.71
Minimum of Months 22.97 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 14.83
February 23.44 12.72
March 23.75 15.42
April 24.36 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.17 20.87
November 23.70 15.43
December 22.97 11.86
     
Annual Sum or Average 23.99 21.71
Minimum of Months 22.97 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.90 14.83
February 23.84 12.72
March 23.92 15.42
April 24.37 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.27 20.87
November 24.02 15.43
December 23.55 11.86
     
Annual Sum or Average 24.16 21.71
Minimum of Months 23.55 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 14.83
February 23.84 12.72
March 23.92 15.42
April 24.37 23.31
May 24.40 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.27 20.87
November 24.02 15.43
December 23.55 11.86
     
Annual Sum or Average 24.16 21.71
Minimum of Months 23.55 11.86
Maximum of Months 24.40 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.89 14.83
February 24.66 12.72
March 25.16 15.42
April 26.60 23.31
May 26.92 26.31
June 27.53 31.20
July 27.51 30.42
August 27.40 29.82
September 27.20 27.75
October 26.13 20.87
November 25.17 15.43
December 24.10 11.86
     
Annual Sum or Average 26.11 21.71
Minimum of Months 24.10 11.86
Maximum of Months 27.53 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.07 14.83
February 22.23 12.72
March 23.14 15.42
April 25.29 23.31
May 26.04 26.31
June 27.82 31.20
July 27.76 30.42
August 27.64 29.82
September 27.29 27.75
October 24.95 20.87
November 23.34 15.43
December 22.25 11.86
     
Annual Sum or Average 25.08 21.71
Minimum of Months 22.23 11.86
Maximum of Months 27.82 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.36 14.83
February 26.26 12.72
March 26.38 15.42
April 26.94 23.31
May 27.06 26.31
June 27.30 31.20
July 27.24 30.42
August 27.20 29.82
September 27.12 27.75
October 26.81 20.87
November 26.47 15.43
December 26.00 11.86
     
Annual Sum or Average 26.77 21.71
Minimum of Months 26.00 11.86
Maximum of Months 27.30 31.20



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:29

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.126016E+12 76199.587 31-JAN-18:30 8572.775 26456.413 8659.089 0.000 9348.519 2508.330 0.000 0.000 0.000 0.000 0.000 20654.462 0.000 0.000 0.000
February 0.109523E+12 74272.834 27-FEB-18:15 8572.775 26456.413 8659.089 0.000 4340.082 2508.330 0.000 0.000 0.000 0.000 0.000 23736.145 0.000 0.000 0.000
March 0.122959E+12 77745.071 16-MAR-17:30 8572.775 26456.413 8659.089 0.000 13306.118 0.000 0.000 0.000 0.000 0.000 0.000 20750.677 0.000 0.000 0.000
April 0.131537E+12 83275.799 03-APR-17:15 8572.775 26456.413 8659.089 0.000 18742.657 0.000 0.000 0.000 0.000 0.000 0.000 20844.866 0.000 0.000 0.000
May 0.138836E+12 86534.124 07-MAY-17:15 8572.775 26456.413 8659.089 0.000 21938.304 0.000 0.000 0.000 0.000 0.000 0.000 20907.544 0.000 0.000 0.000
June 0.145410E+12 90492.248 29-JUN-17:30 8572.775 26456.413 8659.089 0.000 28729.722 0.000 0.000 0.000 0.000 0.000 0.000 18074.249 0.000 0.000 0.000
July 0.149664E+12 89326.785 20-JUL-17:15 8572.775 26456.413 8659.089 0.000 27578.332 0.000 0.000 0.000 0.000 0.000 0.000 18060.176 0.000 0.000 0.000
August 0.148523E+12 90054.025 26-AUG-17:30 8572.775 26456.413 8659.089 0.000 26650.013 0.000 0.000 0.000 0.000 0.000 0.000 19715.736 0.000 0.000 0.000
September 0.140929E+12 86453.894 06-SEP-17:15 8572.775 26456.413 8659.089 0.000 23097.647 0.000 0.000 0.000 0.000 0.000 0.000 19667.970 0.000 0.000 0.000
October 0.131192E+12 83638.027 04-OCT-17:30 8572.775 26456.413 8659.089 0.000 18836.140 0.000 0.000 0.000 0.000 0.000 0.000 21113.610 0.000 0.000 0.000
November 0.119967E+12 74053.256 09-NOV-18:30 8572.775 26456.413 8659.089 0.000 8594.257 2508.330 0.000 0.000 0.000 0.000 0.000 19262.393 0.000 0.000 0.000
December 0.121690E+12 72851.925 29-DEC-18:00 8572.775 26456.413 8659.089 0.000 4231.143 2508.330 0.000 0.000 0.000 0.000 0.000 22424.175 0.000 0.000 0.000
                                     
Annual Sum or Average 0.158625E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.109523E+12 72851.925   8572.775 26456.413 8659.089 0.000 4231.143 0.000 0.000 0.000 0.000 0.000 0.000 18060.176 0.000 0.000 0.000
Maximum of Months 0.149664E+12 90492.248   8572.775 26456.413 8659.089 0.000 28729.722 2508.330 0.000 0.000 0.000 0.000 0.000 23736.145 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:29

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.111521E+10 15468.029 01-JAN-04:00 15468.029 0.000 0.000 0.000 0.000 0.000 15468.029
February 0.922962E+09 7705.597 05-FEB-03:00 7705.597 0.000 0.000 0.000 0.000 0.000 7705.597
March 0.111478E+10 13225.625 26-MAR-06:15 13225.625 0.000 0.000 0.000 0.000 0.000 13225.625
April 0.000 0.000 01-APR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.176136E+08 1907.973 26-OCT-03:00 1907.973 0.000 0.000 0.000 0.000 0.000 1907.973
November 0.670683E+09 11076.773 23-NOV-06:00 11076.773 0.000 0.000 0.000 0.000 0.000 11076.773
December 0.460564E+10 22397.965 07-DEC-04:00 22397.965 0.000 0.000 0.000 0.000 0.000 22397.965
                     
Annual Sum or Average 0.844689E+10       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.460564E+10 22397.965   22397.965 0.000 0.000 0.000 0.000 0.000 22397.965