Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2018-10-19 09:20:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2168.95 | 691.93 | 768.05 |
Net Site Energy | 2168.95 | 691.93 | 768.05 |
Total Source Energy | 5419.88 | 1729.04 | 1919.24 |
Net Source Energy | 5419.88 | 1729.04 | 1919.24 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 695.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 218.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 443.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1473.23 | 695.71 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 695.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 95.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 218.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 443.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 268.21 | 246.36 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 521.69 | 246.36 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 241.63 | 221.95 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.99 | 221.95 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1473.23 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1473.23 | 100.00 |
Total On-Site and Utility Electric Sources | 1473.23 | 100.00 |
Total Electricity End Uses | 1473.23 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 33.00 |
Time Setpoint Not Met During Occupied Cooling | 0.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3849.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-JUN-17:15 | 09-DEC-01:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 161934.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23160.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6938.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24352.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89480.82 | 161934.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 161934.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23160.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6938.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24352.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 754.15 | 0.00 | 0.00 | 0.00 |
Cooling | 301.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 692.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1404.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4665.73 | 754.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 267.05 | 0.00 | 0.00 | 0.00 |
Cooling | 106.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 497.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1652.18 | 267.05 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 267.05 | 0.00 | 0.00 | 0.00 |
Cooling | 106.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 497.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1652.18 | 267.05 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.66 | 83.66 | 39.39 | |
Exterior Lighting Total | 2508.33 | 39.39 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3408.32 | 2521.77 | 886.56 | 0.74 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3257.70 | 2407.51 | 850.19 | 0.74 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7490.66 | 5976.67 | 1513.99 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2470.90 | 1773.74 | 697.17 | 0.72 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2119.95 | 1506.64 | 613.30 | 0.71 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2101.60 | 1491.69 | 609.92 | 0.71 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2374.37 | 1669.06 | 705.31 | 0.70 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2420.03 | 1708.07 | 711.96 | 0.71 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9016.57 | 6820.41 | 2196.16 | 0.76 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8582.65 | 6467.71 | 2114.94 | 0.75 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8294.07 | 6138.57 | 2155.50 | 0.74 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6859.31 | 5074.98 | 1784.33 | 0.74 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5686.62 | 4175.71 | 1510.91 | 0.73 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5656.05 | 4150.49 | 1505.56 | 0.73 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6456.43 | 4702.41 | 1754.02 | 0.73 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6477.86 | 4720.12 | 1757.75 | 0.73 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5804.97 | 4416.72 | 1388.25 | 0.76 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5388.14 | 4106.48 | 1281.67 | 0.76 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5499.07 | 4145.83 | 1353.24 | 0.75 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4556.49 | 3367.43 | 1189.06 | 0.74 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3583.88 | 2669.09 | 914.79 | 0.74 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3549.81 | 2640.93 | 908.88 | 0.74 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4543.01 | 3411.25 | 1131.76 | 0.75 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4557.29 | 3423.12 | 1134.18 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3272.4 | 3.23 | 11.02 | 11.47 | 10.89 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3128.2 | 3.23 | 11.03 | 11.48 | 10.90 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7136.8 | 3.13 | 10.68 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2379.3 | 3.27 | 11.16 | 11.62 | 11.10 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2043.3 | 3.28 | 11.21 | 11.67 | 11.17 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2025.8 | 3.29 | 11.21 | 11.68 | 11.18 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2290.8 | 3.30 | 11.26 | 11.73 | 11.24 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2334.0 | 3.29 | 11.24 | 11.71 | 11.21 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8638.1 | 3.20 | 10.92 | 11.36 | 10.74 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8225.5 | 3.21 | 10.94 | 11.38 | 10.77 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7963.1 | 3.23 | 11.02 | 11.47 | 10.89 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6585.8 | 3.23 | 11.03 | 11.47 | 10.89 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5463.9 | 3.24 | 11.06 | 11.51 | 10.94 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5434.9 | 3.24 | 11.06 | 11.51 | 10.95 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6208.5 | 3.25 | 11.10 | 11.55 | 11.00 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6228.8 | 3.25 | 11.09 | 11.55 | 11.00 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5558.0 | 3.19 | 10.90 | 11.33 | 10.70 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5158.1 | 3.19 | 10.89 | 11.32 | 10.69 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5270.0 | 3.21 | 10.94 | 11.38 | 10.77 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4375.3 | 3.23 | 11.03 | 11.48 | 10.90 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3438.8 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3406.4 | 3.22 | 11.00 | 11.45 | 10.86 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4355.5 | 3.21 | 10.96 | 11.40 | 10.79 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4369.1 | 3.21 | 10.96 | 11.40 | 10.79 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 4222.88 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 4195.31 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 7146.45 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 4180.16 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 3162.08 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 3161.74 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 3140.81 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 3277.19 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 8577.73 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 8640.80 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 8538.68 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 8601.73 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 6043.00 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 6042.09 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 5982.45 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 5981.54 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 6222.45 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 6257.13 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 6202.04 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 6236.72 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 4836.41 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 4835.90 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 4799.91 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 4799.41 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.76 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 184.68 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 505.80 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.45 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 109.13 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 107.83 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.84 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 122.40 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 540.04 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 509.55 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 471.86 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 389.92 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 317.44 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 315.22 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 353.31 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 354.87 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 352.41 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.37 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 326.82 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.33 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 206.95 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.47 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.46 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 268.51 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1755.70 | 2106.84 | 0.144 | 0.173 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
G NW APARTMENT | 1673.40 | 2008.08 | 0.137 | 0.165 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
OFFICE | 4492.77 | 5391.32 | 0.376 | 0.452 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37 | 0.01534 |
G NE APARTMENT | 1182.00 | 1418.40 | 0.097 | 0.116 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
G N1 APARTMENT | 988.86 | 1186.63 | 0.081 | 0.097 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
G N2 APARTMENT | 977.10 | 1172.52 | 0.080 | 0.096 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
G S1 APARTMENT | 1076.81 | 1292.17 | 0.088 | 0.106 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
G S2 APARTMENT | 1109.05 | 1330.86 | 0.091 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
M SW APARTMENT | 4893.31 | 5871.97 | 0.402 | 0.482 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
M NW APARTMENT | 4616.99 | 5540.39 | 0.379 | 0.455 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
M SE APARTMENT | 4275.24 | 5130.29 | 0.351 | 0.421 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
M NE APARTMENT | 3532.79 | 4239.35 | 0.290 | 0.348 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
M N1 APARTMENT | 2876.39 | 3451.67 | 0.236 | 0.283 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
M N2 APARTMENT | 2856.30 | 3427.56 | 0.235 | 0.281 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
M S1 APARTMENT | 3201.30 | 3841.56 | 0.263 | 0.315 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
M S2 APARTMENT | 3215.43 | 3858.51 | 0.264 | 0.317 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
T SW APARTMENT | 3192.74 | 3831.29 | 0.262 | 0.315 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.35 | 0.01534 |
T NW APARTMENT | 2975.28 | 3570.34 | 0.244 | 0.293 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
T SE APARTMENT | 2960.89 | 3553.07 | 0.243 | 0.292 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
T NE APARTMENT | 2340.36 | 2808.44 | 0.192 | 0.231 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 31.20 | 0.01534 |
T N1 APARTMENT | 1875.18 | 2250.21 | 0.154 | 0.185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
T N2 APARTMENT | 1852.71 | 2223.25 | 0.152 | 0.183 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
T S1 APARTMENT | 2423.31 | 2907.98 | 0.199 | 0.239 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20 | 0.01534 |
T S2 APARTMENT | 2432.83 | 2919.40 | 0.200 | 0.240 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20 | 0.01534 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2313.61 | 2776.33 | 0.070 | 0.084 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G NW APARTMENT | 2334.48 | 2801.38 | 0.070 | 0.085 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
OFFICE | 4308.53 | 5170.24 | 0.126 | 0.151 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G NE APARTMENT | 2321.67 | 2786.01 | 0.070 | 0.084 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G N1 APARTMENT | 1460.72 | 1752.86 | 0.044 | 0.053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G N2 APARTMENT | 1460.43 | 1752.52 | 0.044 | 0.053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G S1 APARTMENT | 1442.74 | 1731.28 | 0.044 | 0.052 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G S2 APARTMENT | 1558.06 | 1869.67 | 0.047 | 0.056 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
M SW APARTMENT | 4827.37 | 5792.85 | 0.146 | 0.175 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M NW APARTMENT | 4880.70 | 5856.84 | 0.147 | 0.177 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M SE APARTMENT | 4794.34 | 5753.21 | 0.145 | 0.174 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M NE APARTMENT | 4847.66 | 5817.20 | 0.146 | 0.175 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M N1 APARTMENT | 2683.78 | 3220.54 | 0.081 | 0.097 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M N2 APARTMENT | 2683.01 | 3219.61 | 0.081 | 0.097 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M S1 APARTMENT | 2632.58 | 3159.10 | 0.079 | 0.095 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
M S2 APARTMENT | 2631.81 | 3158.17 | 0.079 | 0.095 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T SW APARTMENT | 4048.87 | 4858.64 | 0.122 | 0.147 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T NW APARTMENT | 4078.20 | 4893.83 | 0.123 | 0.148 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T SE APARTMENT | 4031.61 | 4837.93 | 0.122 | 0.146 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T NE APARTMENT | 4060.94 | 4873.12 | 0.122 | 0.147 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T N1 APARTMENT | 2876.70 | 3452.04 | 0.087 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T N2 APARTMENT | 2876.27 | 3451.52 | 0.087 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T S1 APARTMENT | 2845.84 | 3415.00 | 0.086 | 0.103 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
T S2 APARTMENT | 2845.41 | 3414.49 | 0.086 | 0.103 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -26.20 | 0.00036 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.17 | 0.17 | 0.08 | 0.08 |
SPLIT GNW | 0.16 | 0.16 | 0.08 | 0.08 |
SPLIT OFFICE | 0.45 | 0.45 | 0.15 | 0.15 |
SPLIT GNE | 0.12 | 0.12 | 0.08 | 0.08 |
SPLIT GN1 | 0.10 | 0.10 | 0.05 | 0.05 |
SPLIT GN2 | 0.10 | 0.10 | 0.05 | 0.05 |
SPLIT GS1 | 0.11 | 0.11 | 0.05 | 0.05 |
SPLIT GS2 | 0.11 | 0.11 | 0.06 | 0.06 |
SPLIT MSW | 0.48 | 0.48 | 0.17 | 0.17 |
SPLIT MNW | 0.45 | 0.45 | 0.18 | 0.18 |
SPLIT MSE | 0.42 | 0.42 | 0.17 | 0.17 |
SPLIT MNE | 0.35 | 0.35 | 0.18 | 0.18 |
SPLIT MN1 | 0.28 | 0.28 | 0.10 | 0.10 |
SPLIT MN2 | 0.28 | 0.28 | 0.10 | 0.10 |
SPLIT MS1 | 0.32 | 0.32 | 0.10 | 0.10 |
SPLIT MS2 | 0.32 | 0.32 | 0.10 | 0.10 |
SPLIT TSW | 0.31 | 0.31 | 0.15 | 0.15 |
SPLIT TNW | 0.29 | 0.29 | 0.15 | 0.15 |
SPLIT TSE | 0.29 | 0.29 | 0.15 | 0.15 |
SPLIT TNE | 0.23 | 0.23 | 0.15 | 0.15 |
SPLIT TN1 | 0.18 | 0.18 | 0.10 | 0.10 |
SPLIT TN2 | 0.18 | 0.18 | 0.10 | 0.10 |
SPLIT TS1 | 0.24 | 0.24 | 0.10 | 0.10 |
SPLIT TS2 | 0.24 | 0.24 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4390.00 | 6566.25 | 2677.25 |
G NW APARTMENT | 4713.50 | 6740.75 | 3176.50 |
OFFICE | 873.75 | 1581.75 | 570.00 |
G NE APARTMENT | 4677.25 | 6792.25 | 3188.50 |
G N1 APARTMENT | 4038.75 | 6890.75 | 2781.50 |
G N2 APARTMENT | 4032.25 | 6897.50 | 2781.25 |
G S1 APARTMENT | 3571.75 | 6626.25 | 2028.50 |
G S2 APARTMENT | 3784.75 | 6672.00 | 2294.50 |
M SW APARTMENT | 3960.25 | 4996.00 | 1158.50 |
M NW APARTMENT | 4448.00 | 5410.75 | 1778.50 |
M SE APARTMENT | 3936.25 | 5008.00 | 1122.25 |
M NE APARTMENT | 4445.25 | 5456.25 | 1767.75 |
M N1 APARTMENT | 3762.75 | 5328.25 | 1150.50 |
M N2 APARTMENT | 3763.50 | 5337.50 | 1149.25 |
M S1 APARTMENT | 3330.50 | 4774.75 | 540.75 |
M S2 APARTMENT | 3328.75 | 4776.75 | 539.00 |
T SW APARTMENT | 5281.75 | 5695.00 | 2860.25 |
T NW APARTMENT | 5614.75 | 5998.50 | 3362.00 |
T SE APARTMENT | 5279.25 | 5680.00 | 2847.25 |
T NE APARTMENT | 5609.50 | 6032.75 | 3367.00 |
T N1 APARTMENT | 5281.25 | 6020.25 | 3046.75 |
T N2 APARTMENT | 5279.00 | 6023.75 | 3048.50 |
T S1 APARTMENT | 4856.75 | 5595.00 | 2446.00 |
T S2 APARTMENT | 4860.50 | 5595.50 | 2445.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6323.75 | 7009.00 | 3849.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G NW APARTMENT | 2.75 | 0.25 | 2.75 | 0.25 |
OFFICE | 22.25 | 0.50 | 0.25 | 0.00 |
G NE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
G N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
G N2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M NW APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M SE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
M NE APARTMENT | 5.50 | 0.00 | 5.50 | 0.00 |
M N1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M N2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T SW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T NW APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
T SE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T NE APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
T N1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
T N2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 55.00 | 0.75 | 33.00 | 0.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.145 | 0.000 | 0.076 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.145 | 0.000 | 0.070 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.161 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.145 | 0.000 | 0.070 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.087 | 0.000 | 0.070 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.087 | 0.000 | 0.070 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.087 | 0.000 | 0.076 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.087 | 0.000 | 0.076 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.208 | 0.000 | 0.097 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.208 | 0.000 | 0.089 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.208 | 0.000 | 0.097 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.208 | 0.000 | 0.089 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.126 | 0.000 | 0.089 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.126 | 0.000 | 0.088 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.126 | 0.000 | 0.097 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.126 | 0.000 | 0.097 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.275 | 0.000 | 0.120 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.275 | 0.000 | 0.108 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.275 | 0.000 | 0.120 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.275 | 0.000 | 0.108 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.166 | 0.000 | 0.108 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.166 | 0.000 | 0.108 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.166 | 0.000 | 0.120 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.166 | 0.000 | 0.120 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.365 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 443.57 | 0.00 | 01-JAN-00:15 | 32953.17 | 08-FEB-07:30 |
WaterSystems:Electricity | 443.57 | 0.00 | 01-JAN-00:15 | 32953.17 | 08-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 443.57 | 0.00 | 01-JAN-00:15 | 32953.17 | 08-FEB-07:30 |
Fans:Electricity | 218.81 | 6938.42 | 07-DEC-08:00 | 6938.42 | 02-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
ElectricityPurchased:Plant | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
Cogeneration:ElectricityPurchased | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
ElectricityNet:Plant | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
Cogeneration:ElectricityNet | 1473.23 | 20308.72 | 01-JAN-03:15 | 89480.82 | 11-JUN-17:15 |
ExteriorLights:Electricity | 39.39 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.39 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 313.85 | 6938.42 | 07-DEC-08:00 | 33687.12 | 04-AUG-15:15 |
General:Fans:Electricity | 218.81 | 6938.42 | 07-DEC-08:00 | 6938.42 | 02-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 95.04 | 0.00 | 01-JAN-00:15 | 26748.70 | 04-AUG-15:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 695.71 | 0.00 | 18-MAR-15:15 | 161934.13 | 09-DEC-02:00 |
Gas:HVAC | 695.71 | 0.00 | 18-MAR-15:15 | 161934.13 | 09-DEC-02:00 |
Heating:Gas | 695.71 | 0.00 | 18-MAR-15:15 | 161934.13 | 09-DEC-02:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1580.87 | 1311.18 | 14-APR-11:45 | 223811.23 | 09-DEC-02:00 |
EnergyTransfer:Building | 634.63 | 1311.18 | 14-APR-11:45 | 94263.93 | 09-DEC-02:00 |
EnergyTransfer:Zone:G SW APARTMENT | 16.44 | 0.02 | 23-MAR-15:45 | 3020.23 | 09-DEC-02:00 |
Heating:EnergyTransfer | 301.23 | 0.00 | 18-MAR-18:15 | 94263.93 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 9.87 | 0.00 | 02-JAN-13:15 | 3020.23 | 09-DEC-02:00 |
Cooling:EnergyTransfer | 333.40 | 0.00 | 02-JAN-07:30 | 60760.21 | 25-JUN-17:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.57 | 0.00 | 01-JAN-00:15 | 1951.34 | 07-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 17.51 | 0.05 | 08-MAY-19:15 | 3049.27 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 12.55 | 0.00 | 20-FEB-16:15 | 3049.27 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.96 | 0.00 | 01-JAN-00:15 | 1730.38 | 25-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 21.22 | 0.07 | 21-MAY-18:30 | 4733.93 | 29-JAN-07:30 |
Heating:EnergyTransfer:Zone:OFFICE | 1.28 | 0.00 | 01-JAN-00:15 | 4733.93 | 29-JAN-07:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 19.94 | 0.00 | 02-JAN-07:30 | 3447.42 | 07-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 17.53 | 0.01 | 01-OCT-15:15 | 2984.59 | 09-DEC-09:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 12.45 | 0.00 | 18-MAR-14:15 | 2984.59 | 09-DEC-09:30 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.08 | 0.00 | 01-JAN-00:15 | 1237.78 | 25-JUN-18:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 11.32 | 0.02 | 16-APR-22:00 | 1841.08 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 6.72 | 0.00 | 13-JAN-17:15 | 1841.08 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.59 | 0.00 | 01-JAN-00:15 | 990.29 | 25-JUN-18:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 11.32 | 0.03 | 04-MAY-19:00 | 1840.75 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 6.73 | 0.00 | 13-JAN-17:15 | 1840.75 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.59 | 0.00 | 01-JAN-00:15 | 980.09 | 25-JUN-18:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.00 | 0.02 | 27-MAY-11:15 | 1802.14 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 4.54 | 0.00 | 02-JAN-10:30 | 1802.14 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 6.46 | 0.00 | 01-JAN-00:15 | 1380.76 | 07-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.59 | 0.01 | 21-OCT-15:30 | 1951.73 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 5.33 | 0.00 | 02-JAN-10:45 | 1951.73 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 6.26 | 0.00 | 01-JAN-00:15 | 1369.05 | 07-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 42.61 | 0.41 | 14-MAR-14:15 | 6544.42 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 15.33 | 0.00 | 02-JAN-12:30 | 6544.42 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 27.27 | 0.00 | 01-JAN-00:15 | 5433.49 | 06-SEP-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 42.80 | 0.04 | 10-JUL-12:30 | 6588.42 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 21.83 | 0.00 | 11-JAN-19:00 | 6588.42 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 20.97 | 0.00 | 01-JAN-00:15 | 5001.40 | 25-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 42.57 | 0.17 | 09-MAY-11:15 | 6435.09 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 15.23 | 0.00 | 02-JAN-12:15 | 6435.09 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 27.34 | 0.00 | 01-JAN-00:15 | 4845.38 | 07-SEP-13:45 |
EnergyTransfer:Zone:M NE APARTMENT | 42.98 | 0.15 | 20-OCT-18:30 | 6417.44 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 21.73 | 0.00 | 11-JAN-19:00 | 6417.44 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.25 | 0.00 | 01-JAN-00:15 | 3875.42 | 25-JUN-17:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 29.01 | 0.43 | 19-MAR-13:30 | 3736.46 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 8.61 | 0.00 | 01-JAN-12:00 | 3736.46 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 20.40 | 0.00 | 01-JAN-00:15 | 3134.76 | 25-JUN-18:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 28.99 | 0.13 | 15-MAR-10:15 | 3733.44 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 8.61 | 0.00 | 01-JAN-12:00 | 3733.44 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 20.38 | 0.00 | 01-JAN-00:15 | 3117.41 | 25-JUN-18:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 33.21 | 0.00 | 23-DEC-20:00 | 4005.79 | 07-SEP-13:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 4.51 | 0.00 | 01-JAN-10:00 | 3677.70 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 28.70 | 0.00 | 01-JAN-00:15 | 4005.79 | 07-SEP-13:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 33.19 | 0.05 | 23-NOV-14:45 | 4014.25 | 07-SEP-13:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 4.51 | 0.00 | 01-JAN-10:00 | 3678.41 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 28.68 | 0.00 | 01-JAN-00:15 | 4014.25 | 07-SEP-13:45 |
EnergyTransfer:Zone:T SW APARTMENT | 31.71 | 0.01 | 27-MAY-04:30 | 5324.14 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 20.05 | 0.00 | 02-JAN-13:45 | 5324.14 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 11.66 | 0.00 | 01-JAN-00:15 | 3550.29 | 07-SEP-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 33.16 | 0.00 | 08-MAY-00:45 | 5333.65 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 23.92 | 0.00 | 20-FEB-16:15 | 5333.65 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 9.24 | 0.00 | 01-JAN-00:15 | 3287.32 | 25-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 31.42 | 0.01 | 14-APR-08:15 | 5275.87 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 19.90 | 0.00 | 12-JAN-10:45 | 5275.87 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.52 | 0.00 | 01-JAN-00:15 | 3332.08 | 07-SEP-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 32.99 | 0.01 | 01-OCT-20:15 | 5234.51 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 23.75 | 0.00 | 24-FEB-13:00 | 5234.51 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 9.24 | 0.00 | 01-JAN-00:15 | 2680.96 | 11-JUN-15:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 23.46 | 0.00 | 29-AUG-05:45 | 3724.69 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 15.19 | 0.00 | 24-FEB-12:45 | 3724.69 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 8.26 | 0.00 | 01-JAN-00:15 | 2124.60 | 11-JUN-15:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 23.46 | 0.04 | 02-OCT-14:45 | 3721.98 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 15.20 | 0.00 | 24-FEB-12:30 | 3721.98 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 8.26 | 0.00 | 01-JAN-00:15 | 2120.06 | 11-JUN-15:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.57 | 0.01 | 10-APR-23:15 | 3739.07 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 11.69 | 0.00 | 02-JAN-11:45 | 3739.07 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.87 | 0.00 | 01-JAN-00:15 | 2894.96 | 07-SEP-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.57 | 0.01 | 12-SEP-05:45 | 3739.52 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 11.70 | 0.00 | 02-JAN-11:45 | 3739.52 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.88 | 0.00 | 01-JAN-00:15 | 2902.76 | 07-SEP-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 946.24 | 0.00 | 19-MAR-18:00 | 129547.30 | 09-DEC-02:00 |
HeatingCoils:EnergyTransfer | 556.57 | 0.00 | 18-MAR-15:15 | 129547.30 | 09-DEC-02:00 |
CoolingCoils:EnergyTransfer | 389.67 | 0.00 | 01-JAN-00:15 | 104353.26 | 04-AUG-16:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 9.870 | -6.569 | 0.000 | 0.000 | 3.879 | 2.413 | 12.213 | 11.970 | 0.000 | 0.103 | 0.000 | 0.000 | -9.672 | 0.000 | -7.685 | -16.521 |
G NW APARTMENT | 12.551 | -4.959 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 6.019 | 0.000 | 0.100 | 0.000 | 0.000 | -10.367 | 0.000 | -7.579 | -14.284 |
OFFICE | 1.278 | -19.944 | 0.000 | 0.000 | 0.541 | 21.914 | 7.534 | 11.885 | 0.000 | 0.085 | 0.001 | 0.000 | -8.859 | 0.000 | -6.375 | -8.061 |
G NE APARTMENT | 12.449 | -5.080 | 0.000 | 0.000 | 3.902 | 2.413 | 12.213 | 5.802 | 0.000 | 0.100 | 0.000 | 0.000 | -10.189 | 0.000 | -7.561 | -14.048 |
G N1 APARTMENT | 6.725 | -4.594 | 0.000 | 0.000 | 3.897 | 2.413 | 12.213 | 2.143 | 0.000 | 0.072 | 0.000 | 0.000 | -6.534 | 0.000 | -4.830 | -11.505 |
G N2 APARTMENT | 6.726 | -4.594 | 0.000 | 0.000 | 3.898 | 2.413 | 12.213 | 2.143 | 0.000 | 0.072 | 0.000 | 0.000 | -6.533 | 0.000 | -4.830 | -11.508 |
G S1 APARTMENT | 4.537 | -6.465 | 0.000 | 0.000 | 3.879 | 2.413 | 12.213 | 8.157 | 0.000 | 0.074 | 0.000 | 0.000 | -5.858 | 0.000 | -4.936 | -14.015 |
G S2 APARTMENT | 5.328 | -6.257 | 0.000 | 0.000 | 3.880 | 2.413 | 12.213 | 8.161 | 0.000 | 0.074 | 0.000 | 0.000 | -5.843 | 0.000 | -4.936 | -15.032 |
M SW APARTMENT | 15.331 | -27.274 | 0.000 | 0.000 | 3.792 | 2.413 | 12.213 | 11.568 | 0.000 | 0.144 | 3.281 | 0.000 | -10.307 | 0.000 | -11.161 | -0.001 |
M NW APARTMENT | 21.834 | -20.965 | 0.000 | 0.000 | 3.826 | 2.413 | 12.213 | 5.719 | 0.000 | 0.139 | 0.000 | 0.000 | -10.959 | 0.000 | -10.964 | -3.256 |
M SE APARTMENT | 15.232 | -27.342 | 0.000 | 0.000 | 3.798 | 2.413 | 12.213 | 11.367 | 0.000 | 0.144 | 3.463 | 0.000 | -10.136 | 0.000 | -11.151 | -0.001 |
M NE APARTMENT | 21.732 | -21.247 | 0.000 | 0.000 | 3.835 | 2.413 | 12.213 | 5.499 | 0.000 | 0.139 | 0.000 | 0.000 | -10.756 | 0.000 | -10.939 | -2.890 |
M N1 APARTMENT | 8.609 | -20.405 | 0.000 | 0.000 | 3.818 | 2.413 | 12.213 | 1.960 | 0.000 | 0.098 | 5.254 | 0.000 | -6.961 | 0.000 | -7.000 | -0.001 |
M N2 APARTMENT | 8.612 | -20.382 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 1.960 | 0.000 | 0.098 | 5.225 | 0.000 | -6.959 | 0.000 | -6.999 | -0.001 |
M S1 APARTMENT | 4.510 | -28.698 | 0.000 | 0.000 | 3.774 | 2.413 | 12.213 | 7.897 | 0.000 | 0.103 | 11.247 | 0.000 | -6.276 | 0.000 | -7.183 | -0.000 |
M S2 APARTMENT | 4.510 | -28.678 | 0.000 | 0.000 | 3.774 | 2.413 | 12.213 | 7.897 | 0.000 | 0.103 | 11.226 | 0.000 | -6.275 | 0.000 | -7.183 | -0.000 |
T SW APARTMENT | 20.055 | -11.659 | 0.000 | 0.000 | 3.843 | 2.413 | 12.213 | 11.489 | 0.000 | 0.200 | 0.000 | 0.000 | -9.869 | 0.000 | -14.464 | -14.220 |
T NW APARTMENT | 23.922 | -9.241 | 0.000 | 0.000 | 3.863 | 2.413 | 12.213 | 5.666 | 0.000 | 0.192 | 0.000 | 0.000 | -10.548 | 0.000 | -14.249 | -14.230 |
T SE APARTMENT | 19.896 | -11.521 | 0.000 | 0.000 | 3.848 | 2.413 | 12.213 | 11.304 | 0.000 | 0.200 | 0.000 | 0.000 | -9.717 | 0.000 | -14.465 | -14.170 |
T NE APARTMENT | 23.749 | -9.242 | 0.000 | 0.000 | 3.873 | 2.413 | 12.213 | 5.465 | 0.000 | 0.192 | 0.000 | 0.000 | -10.363 | 0.000 | -14.225 | -14.075 |
T N1 APARTMENT | 15.191 | -8.264 | 0.000 | 0.000 | 3.863 | 2.413 | 12.213 | 1.960 | 0.000 | 0.138 | 0.000 | 0.000 | -6.663 | 0.000 | -9.019 | -11.831 |
T N2 APARTMENT | 15.196 | -8.265 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 1.959 | 0.000 | 0.138 | 0.000 | 0.000 | -6.660 | 0.000 | -9.018 | -11.840 |
T S1 APARTMENT | 11.694 | -10.874 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 7.865 | 0.000 | 0.147 | 0.000 | 0.000 | -6.007 | 0.000 | -9.237 | -12.046 |
T S2 APARTMENT | 11.699 | -10.875 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 7.863 | 0.000 | 0.147 | 0.000 | 0.000 | -6.006 | 0.000 | -9.237 | -12.049 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.074 | 0.000 | 0.005 | 0.000 | 0.000 | -1.240 | 0.000 | -2.323 | -13.586 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.280 | 0.000 | 0.178 | 7.217 | 0.000 | -3.317 | 0.000 | -27.693 | -0.001 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.075 | 0.000 | 0.005 | 0.000 | 0.000 | -1.347 | 0.000 | -1.903 | -13.899 |
Total Facility | 301.233 | -333.393 | 0.000 | 0.000 | 89.020 | 128.627 | 294.692 | 164.149 | 0.000 | 3.188 | 46.915 | 0.000 | -204.221 | 0.000 | -247.144 | -243.072 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 07-SEP-15:15 | 0.00 | -1951.32 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2511.44 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1197.24 |
G NW APARTMENT | 25-JUN-17:30 | 0.00 | -1730.38 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1940.47 | 0.00 | 141.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1276.60 |
OFFICE | 07-SEP-13:30 | 0.00 | -3447.33 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2207.30 | 0.00 | 25.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1019.60 |
G NE APARTMENT | 25-JUN-18:15 | 0.00 | -1237.74 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 697.87 | 0.00 | 112.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -492.49 |
G N1 APARTMENT | 25-JUN-18:15 | 0.00 | -990.22 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 566.47 | 0.00 | 67.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.89 |
G N2 APARTMENT | 25-JUN-18:15 | 0.00 | -980.02 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 566.64 | 0.00 | 67.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.27 |
G S1 APARTMENT | 07-SEP-13:30 | 0.00 | -1380.61 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1917.50 | 0.00 | 14.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1003.23 |
G S2 APARTMENT | 07-SEP-13:30 | 0.00 | -1368.91 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1917.67 | 0.00 | 14.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1015.11 |
M SW APARTMENT | 06-SEP-16:10 | 0.00 | -5435.08 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2011.73 | 0.00 | 126.52 | 2479.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 25-JUN-17:23 | 0.00 | -5001.73 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1918.72 | 0.00 | 202.96 | 1955.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 07-SEP-13:45 | 0.00 | -4845.29 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2092.04 | 0.00 | 51.37 | 2249.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 25-JUN-17:45 | 0.00 | -3875.39 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 648.69 | 0.00 | 191.20 | 2110.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 25-JUN-18:15 | 0.00 | -3134.61 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 554.61 | 0.00 | 97.34 | 1562.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 25-JUN-18:15 | 0.00 | -3117.26 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 554.71 | 0.00 | 97.34 | 1545.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 07-SEP-13:45 | 0.00 | -4005.63 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1819.66 | 0.00 | 30.98 | 1702.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 07-SEP-13:45 | 0.00 | -4014.10 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1819.61 | 0.00 | 30.98 | 1711.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 07-SEP-15:15 | 0.00 | -3550.29 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2463.28 | 0.00 | 31.10 | 435.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 25-JUN-17:10 | 0.00 | -3288.78 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 1875.24 | 0.00 | 282.87 | 205.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 07-SEP-13:30 | 0.00 | -3331.97 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2148.36 | 0.00 | 44.34 | 687.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 11-JUN-15:15 | 0.00 | -2681.50 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 901.26 | 0.00 | 337.51 | 822.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 11-JUN-15:15 | 0.00 | -2124.91 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 551.45 | 0.00 | 203.56 | 749.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 11-JUN-15:15 | 0.00 | -2120.38 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 551.50 | 0.00 | 203.56 | 744.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 07-SEP-13:30 | 0.00 | -2894.80 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1888.03 | 0.00 | 26.74 | 527.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 07-SEP-13:30 | 0.00 | -2902.60 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1887.92 | 0.00 | 26.74 | 535.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUN-17:10 | 0.00 | -60791.40 | 0.00 | 0.00 | 3261.76 | 6475.86 | 14071.03 | 18632.96 | 0.00 | 4411.55 | 13938.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-DEC-02:00 | 3020.20 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1142.46 | 0.00 | -1792.63 | -530.52 |
G NW APARTMENT | 09-DEC-02:00 | 3049.24 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.13 | 0.00 | -1792.02 | -530.50 |
OFFICE | 12-MAR-06:01 | 6624.74 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.05 | 0.00 | -163.88 | -6634.38 |
G NE APARTMENT | 09-DEC-02:00 | 2984.55 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1150.68 | 0.00 | -1790.39 | -488.89 |
G N1 APARTMENT | 09-DEC-08:53 | 1841.11 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -666.11 | 0.00 | -1015.75 | -664.92 |
G N2 APARTMENT | 09-DEC-08:53 | 1840.84 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -666.12 | 0.00 | -1015.75 | -664.65 |
G S1 APARTMENT | 09-DEC-09:00 | 1802.24 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -635.52 | 0.00 | -1015.75 | -656.64 |
G S2 APARTMENT | 09-DEC-09:00 | 1951.76 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -633.45 | 0.00 | -1015.75 | -808.23 |
M SW APARTMENT | 09-DEC-02:00 | 6544.35 | 0.00 | 0.00 | 0.00 | 190.85 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1168.38 | 0.00 | -2560.80 | -3261.76 |
M NW APARTMENT | 09-DEC-02:00 | 6588.35 | 0.00 | 0.00 | 0.00 | 192.21 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1196.78 | 0.00 | -2551.20 | -3288.31 |
M SE APARTMENT | 09-DEC-02:00 | 6435.03 | 0.00 | 0.00 | 0.00 | 191.33 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1143.89 | 0.00 | -2557.01 | -3181.20 |
M NE APARTMENT | 09-DEC-02:00 | 6417.37 | 0.00 | 0.00 | 0.00 | 193.06 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1171.81 | 0.00 | -2545.26 | -3149.09 |
M N1 APARTMENT | 09-DEC-02:00 | 3736.42 | 0.00 | 0.00 | 0.00 | 190.62 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -730.70 | 0.00 | -1546.95 | -1905.14 |
M N2 APARTMENT | 09-DEC-02:00 | 3733.40 | 0.00 | 0.00 | 0.00 | 190.64 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -730.67 | 0.00 | -1546.84 | -1902.28 |
M S1 APARTMENT | 09-DEC-02:00 | 3677.66 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -698.77 | 0.00 | -1553.68 | -1870.62 |
M S2 APARTMENT | 09-DEC-02:00 | 3678.38 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -698.76 | 0.00 | -1553.68 | -1871.34 |
T SW APARTMENT | 09-DEC-02:00 | 5324.09 | 0.00 | 0.00 | 0.00 | 192.15 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.74 | 0.00 | -3375.15 | -1256.08 |
T NW APARTMENT | 09-DEC-02:00 | 5333.59 | 0.00 | 0.00 | 0.00 | 192.60 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.96 | 0.00 | -3370.70 | -1238.27 |
T SE APARTMENT | 09-DEC-02:00 | 5275.82 | 0.00 | 0.00 | 0.00 | 192.48 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1116.02 | 0.00 | -3371.88 | -1236.13 |
T NE APARTMENT | 09-DEC-02:00 | 5234.45 | 0.00 | 0.00 | 0.00 | 193.51 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1147.07 | 0.00 | -3361.84 | -1174.79 |
T N1 APARTMENT | 09-DEC-02:00 | 3724.66 | 0.00 | 0.00 | 0.00 | 189.70 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -715.99 | 0.00 | -2054.80 | -1399.31 |
T N2 APARTMENT | 09-DEC-02:00 | 3721.95 | 0.00 | 0.00 | 0.00 | 189.72 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -715.97 | 0.00 | -2054.62 | -1396.81 |
T S1 APARTMENT | 09-DEC-02:00 | 3739.04 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -682.51 | 0.00 | -2057.26 | -1444.68 |
T S2 APARTMENT | 09-DEC-02:00 | 3739.48 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -682.51 | 0.00 | -2057.28 | -1445.10 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-DEC-02:00 | 94262.97 | 0.00 | 0.00 | 0.00 | 4385.24 | 2334.74 | 5719.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22706.70 | 0.00 | -50652.93 | -33343.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Sec1.1A-General InformationData | |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 33.00 |
Number of hours cooling loads not met | 0.25 |
Number of hours not met | 33.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 695.71 | 161934.13 | 0.00 | 0.00 |
Space Cooling | 95.04 | 23160.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 218.81 | 6938.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 443.57 | 24352.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1473.23 | 695.71 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1473.23 |
Natural Gas | 0.00 | 695.71 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 2168.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 30.32 |
Fans-Interior | 69.80 |
Service Water Heating | 141.51 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.57 |
Subtotal | 469.99 |
Natural Gas [MJ/m2] | |
Space Heating | 221.95 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 221.95 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.61 |
Space Heating | 32.08 |
Space Cooling | 4.38 |
Fans-Interior | 10.09 |
Service Water Heating | 20.45 |
Receptacle Equipment | 23.58 |
Miscellaneous | 1.82 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.172984 |
G NW APARTMENT DIRECT AIR | 0.164877 |
OFFICE DIRECT AIR | 0.451561 |
G NE APARTMENT DIRECT AIR | 0.116460 |
G N1 APARTMENT DIRECT AIR | 0.097428 |
G N2 APARTMENT DIRECT AIR | 0.096270 |
G S1 APARTMENT DIRECT AIR | 0.106097 |
G S2 APARTMENT DIRECT AIR | 0.109274 |
M SW APARTMENT DIRECT AIR | 0.482134 |
M NW APARTMENT DIRECT AIR | 0.454912 |
M SE APARTMENT DIRECT AIR | 0.421266 |
M NE APARTMENT DIRECT AIR | 0.348114 |
M N1 APARTMENT DIRECT AIR | 0.283400 |
M N2 APARTMENT DIRECT AIR | 0.281421 |
M S1 APARTMENT DIRECT AIR | 0.315427 |
M S2 APARTMENT DIRECT AIR | 0.316818 |
T SW APARTMENT DIRECT AIR | 0.314620 |
T NW APARTMENT DIRECT AIR | 0.293162 |
T SE APARTMENT DIRECT AIR | 0.291773 |
T NE APARTMENT DIRECT AIR | 0.230625 |
T N1 APARTMENT DIRECT AIR | 0.184758 |
T N2 APARTMENT DIRECT AIR | 0.182544 |
T S1 APARTMENT DIRECT AIR | 0.238780 |
T S2 APARTMENT DIRECT AIR | 0.239718 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.172984 |
SPLIT GNW MAIN BRANCH | 0.164877 |
SPLIT OFFICE MAIN BRANCH | 0.451561 |
SPLIT GNE MAIN BRANCH | 0.116460 |
SPLIT GN1 MAIN BRANCH | 0.097428 |
SPLIT GN2 MAIN BRANCH | 0.096270 |
SPLIT GS1 MAIN BRANCH | 0.106097 |
SPLIT GS2 MAIN BRANCH | 0.109274 |
SPLIT MSW MAIN BRANCH | 0.482134 |
SPLIT MNW MAIN BRANCH | 0.454912 |
SPLIT MSE MAIN BRANCH | 0.421266 |
SPLIT MNE MAIN BRANCH | 0.348114 |
SPLIT MN1 MAIN BRANCH | 0.283400 |
SPLIT MN2 MAIN BRANCH | 0.281421 |
SPLIT MS1 MAIN BRANCH | 0.315427 |
SPLIT MS2 MAIN BRANCH | 0.316818 |
SPLIT TSW MAIN BRANCH | 0.314620 |
SPLIT TNW MAIN BRANCH | 0.293162 |
SPLIT TSE MAIN BRANCH | 0.291773 |
SPLIT TNE MAIN BRANCH | 0.230625 |
SPLIT TN1 MAIN BRANCH | 0.184758 |
SPLIT TN2 MAIN BRANCH | 0.182544 |
SPLIT TS1 MAIN BRANCH | 0.238780 |
SPLIT TS2 MAIN BRANCH | 0.239718 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.172984 |
SPLIT GNW | 0.164877 |
SPLIT OFFICE | 0.451561 |
SPLIT GNE | 0.116460 |
SPLIT GN1 | 0.097428 |
SPLIT GN2 | 0.096270 |
SPLIT GS1 | 0.106097 |
SPLIT GS2 | 0.109274 |
SPLIT MSW | 0.482134 |
SPLIT MNW | 0.454912 |
SPLIT MSE | 0.421266 |
SPLIT MNE | 0.348114 |
SPLIT MN1 | 0.283400 |
SPLIT MN2 | 0.281421 |
SPLIT MS1 | 0.315427 |
SPLIT MS2 | 0.316818 |
SPLIT TSW | 0.314620 |
SPLIT TNW | 0.293162 |
SPLIT TSE | 0.291773 |
SPLIT TNE | 0.230625 |
SPLIT TN1 | 0.184758 |
SPLIT TN2 | 0.182544 |
SPLIT TS1 | 0.238780 |
SPLIT TS2 | 0.239718 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.172984 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.164877 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.451561 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.116460 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.097428 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.096270 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.106097 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.109274 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.482134 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.454912 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.421266 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.348114 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.283400 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.281421 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.315427 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.316818 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.314620 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.293162 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.291773 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.230625 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.184758 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.182544 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.238780 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.239718 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.172984 | 3408.32 | 0.739885 |
SPLIT GNW COOLING COIL | 0.164877 | 3257.70 | 0.739021 |
SPLIT OFFICE COOLING COIL | 0.451561 | 7490.66 | 0.797883 |
SPLIT GNE COOLING COIL | 0.116460 | 2470.90 | 0.717849 |
SPLIT GN1 COOLING COIL | 0.097428 | 2119.95 | 0.710699 |
SPLIT GN2 COOLING COIL | 0.096270 | 2101.60 | 0.709785 |
SPLIT GS1 COOLING COIL | 0.106097 | 2374.37 | 0.702950 |
SPLIT GS2 COOLING COIL | 0.109274 | 2420.03 | 0.705807 |
SPLIT MSW COOLING COIL | 0.482134 | 9016.57 | 0.756430 |
SPLIT MNW COOLING COIL | 0.454912 | 8582.65 | 0.753580 |
SPLIT MSE COOLING COIL | 0.421266 | 8294.07 | 0.740115 |
SPLIT MNE COOLING COIL | 0.348114 | 6859.31 | 0.739868 |
SPLIT MN1 COOLING COIL | 0.283400 | 5686.62 | 0.734304 |
SPLIT MN2 COOLING COIL | 0.281421 | 5656.05 | 0.733814 |
SPLIT MS1 COOLING COIL | 0.315427 | 6456.43 | 0.728330 |
SPLIT MS2 COOLING COIL | 0.316818 | 6477.86 | 0.728653 |
SPLIT TSW COOLING COIL | 0.314620 | 5804.97 | 0.760851 |
SPLIT TNW COOLING COIL | 0.293162 | 5388.14 | 0.762132 |
SPLIT TSE COOLING COIL | 0.291773 | 5499.07 | 0.753915 |
SPLIT TNE COOLING COIL | 0.230625 | 4556.49 | 0.739041 |
SPLIT TN1 COOLING COIL | 0.184758 | 3583.88 | 0.744748 |
SPLIT TN2 COOLING COIL | 0.182544 | 3549.81 | 0.743964 |
SPLIT TS1 COOLING COIL | 0.238780 | 4543.01 | 0.750879 |
SPLIT TS2 COOLING COIL | 0.239718 | 4557.29 | 0.751129 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.172984 | 0.172984 | 0.172984 | 0.172984 | 4222.88 | 3408.32 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.164877 | 0.164877 | 0.164877 | 0.164877 | 4195.31 | 3257.70 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.451561 | 0.451561 | 0.451561 | 0.451561 | 7146.45 | 7490.66 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.116460 | 0.116460 | 0.116460 | 0.116460 | 4180.16 | 2470.90 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.097428 | 0.097428 | 0.097428 | 0.097428 | 3162.08 | 2119.95 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.096270 | 0.096270 | 0.096270 | 0.096270 | 3161.74 | 2101.60 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.106097 | 0.106097 | 0.106097 | 0.106097 | 3140.81 | 2374.37 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.109274 | 0.109274 | 0.109274 | 0.109274 | 3277.19 | 2420.03 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.482134 | 0.482134 | 0.482134 | 0.482134 | 8577.73 | 9016.57 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.454912 | 0.454912 | 0.454912 | 0.454912 | 8640.80 | 8582.65 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.421266 | 0.421266 | 0.421266 | 0.421266 | 8538.68 | 8294.07 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.348114 | 0.348114 | 0.348114 | 0.348114 | 8601.73 | 6859.31 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.283400 | 0.283400 | 0.283400 | 0.283400 | 6043.00 | 5686.62 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.281421 | 0.281421 | 0.281421 | 0.281421 | 6042.09 | 5656.05 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.315427 | 0.315427 | 0.315427 | 0.315427 | 5982.45 | 6456.43 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.316818 | 0.316818 | 0.316818 | 0.316818 | 5981.54 | 6477.86 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.314620 | 0.314620 | 0.314620 | 0.314620 | 6222.45 | 5804.97 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.293162 | 0.293162 | 0.293162 | 0.293162 | 6257.13 | 5388.14 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.291773 | 0.291773 | 0.291773 | 0.291773 | 6202.04 | 5499.07 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.230625 | 0.230625 | 0.230625 | 0.230625 | 6236.72 | 4556.49 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.184758 | 0.184758 | 0.184758 | 0.184758 | 4836.41 | 3583.88 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.182544 | 0.182544 | 0.182544 | 0.182544 | 4835.90 | 3549.81 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.238780 | 0.238780 | 0.238780 | 0.238780 | 4799.91 | 4543.01 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.239718 | 0.239718 | 0.239718 | 0.239718 | 4799.41 | 4557.29 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.172984 |
SPLIT GNW SUPPLY FAN | 0.164877 |
SPLIT OFFICE SUPPLY FAN | 0.451561 |
SPLIT GNE SUPPLY FAN | 0.116460 |
SPLIT GN1 SUPPLY FAN | 0.097428 |
SPLIT GN2 SUPPLY FAN | 0.096270 |
SPLIT GS1 SUPPLY FAN | 0.106097 |
SPLIT GS2 SUPPLY FAN | 0.109274 |
SPLIT MSW SUPPLY FAN | 0.482134 |
SPLIT MNW SUPPLY FAN | 0.454912 |
SPLIT MSE SUPPLY FAN | 0.421266 |
SPLIT MNE SUPPLY FAN | 0.348114 |
SPLIT MN1 SUPPLY FAN | 0.283400 |
SPLIT MN2 SUPPLY FAN | 0.281421 |
SPLIT MS1 SUPPLY FAN | 0.315427 |
SPLIT MS2 SUPPLY FAN | 0.316818 |
SPLIT TSW SUPPLY FAN | 0.314620 |
SPLIT TNW SUPPLY FAN | 0.293162 |
SPLIT TSE SUPPLY FAN | 0.291773 |
SPLIT TNE SUPPLY FAN | 0.230625 |
SPLIT TN1 SUPPLY FAN | 0.184758 |
SPLIT TN2 SUPPLY FAN | 0.182544 |
SPLIT TS1 SUPPLY FAN | 0.238780 |
SPLIT TS2 SUPPLY FAN | 0.239718 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 4222.88 |
SPLIT GNW HEATING COIL | 4195.31 |
SPLIT OFFICE HEATING COIL | 7146.45 |
SPLIT GNE HEATING COIL | 4180.16 |
SPLIT GN1 HEATING COIL | 3162.08 |
SPLIT GN2 HEATING COIL | 3161.74 |
SPLIT GS1 HEATING COIL | 3140.81 |
SPLIT GS2 HEATING COIL | 3277.19 |
SPLIT MSW HEATING COIL | 8577.73 |
SPLIT MNW HEATING COIL | 8640.80 |
SPLIT MSE HEATING COIL | 8538.68 |
SPLIT MNE HEATING COIL | 8601.73 |
SPLIT MN1 HEATING COIL | 6043.00 |
SPLIT MN2 HEATING COIL | 6042.09 |
SPLIT MS1 HEATING COIL | 5982.45 |
SPLIT MS2 HEATING COIL | 5981.54 |
SPLIT TSW HEATING COIL | 6222.45 |
SPLIT TNW HEATING COIL | 6257.13 |
SPLIT TSE HEATING COIL | 6202.04 |
SPLIT TNE HEATING COIL | 6236.72 |
SPLIT TN1 HEATING COIL | 4836.41 |
SPLIT TN2 HEATING COIL | 4835.90 |
SPLIT TS1 HEATING COIL | 4799.91 |
SPLIT TS2 HEATING COIL | 4799.41 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.72 | -7.7 |
March | 21.79 | 0.33 |
April | 22.25 | 7.02 |
May | 22.94 | 14.19 |
June | 24.12 | 19.16 |
July | 24.36 | 20.92 |
August | 24.35 | 20.05 |
September | 23.87 | 15.39 |
October | 22.25 | 7.43 |
November | 21.84 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.75 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.36 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.08 | 7.02 |
May | 22.78 | 14.19 |
June | 24.10 | 19.16 |
July | 24.36 | 20.92 |
August | 24.34 | 20.05 |
September | 23.72 | 15.39 |
October | 21.92 | 7.43 |
November | 21.74 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.66 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.36 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.92 | -12.6 |
February | 18.86 | -7.7 |
March | 20.26 | 0.33 |
April | 21.74 | 7.02 |
May | 23.39 | 14.19 |
June | 23.84 | 19.16 |
July | 23.90 | 20.92 |
August | 23.90 | 20.05 |
September | 23.68 | 15.39 |
October | 22.32 | 7.43 |
November | 20.18 | -0.0 |
December | 18.43 | -7.6 |
Annual Sum or Average | 21.55 | 6.46 |
Minimum of Months | 17.92 | -12.6 |
Maximum of Months | 23.90 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.71 | 0.33 |
April | 22.03 | 7.02 |
May | 22.69 | 14.19 |
June | 24.06 | 19.16 |
July | 24.34 | 20.92 |
August | 24.31 | 20.05 |
September | 23.67 | 15.39 |
October | 21.84 | 7.43 |
November | 21.72 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.63 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.34 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 22.00 | 7.02 |
May | 22.57 | 14.19 |
June | 24.09 | 19.16 |
July | 24.35 | 20.92 |
August | 24.33 | 20.05 |
September | 23.77 | 15.39 |
October | 21.87 | 7.43 |
November | 21.74 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.63 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 21.99 | 7.02 |
May | 22.57 | 14.19 |
June | 24.09 | 19.16 |
July | 24.35 | 20.92 |
August | 24.33 | 20.05 |
September | 23.77 | 15.39 |
October | 21.87 | 7.43 |
November | 21.74 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.63 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.72 | -7.7 |
March | 21.78 | 0.33 |
April | 22.18 | 7.02 |
May | 22.80 | 14.19 |
June | 24.12 | 19.16 |
July | 24.36 | 20.92 |
August | 24.35 | 20.05 |
September | 23.96 | 15.39 |
October | 22.29 | 7.43 |
November | 21.86 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.74 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.36 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.72 | -7.7 |
March | 21.78 | 0.33 |
April | 22.18 | 7.02 |
May | 22.81 | 14.19 |
June | 24.12 | 19.16 |
July | 24.35 | 20.92 |
August | 24.35 | 20.05 |
September | 23.96 | 15.39 |
October | 22.29 | 7.43 |
November | 21.86 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.74 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.79 | -7.7 |
March | 22.13 | 0.33 |
April | 22.98 | 7.02 |
May | 24.24 | 14.19 |
June | 24.36 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.18 | 15.39 |
October | 23.30 | 7.43 |
November | 22.39 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 23.14 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.85 | 0.33 |
April | 22.63 | 7.02 |
May | 24.15 | 14.19 |
June | 24.36 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.05 | 15.39 |
October | 22.48 | 7.43 |
November | 22.08 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.97 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.78 | -7.7 |
March | 22.09 | 0.33 |
April | 22.90 | 7.02 |
May | 24.25 | 14.19 |
June | 24.36 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.18 | 15.39 |
October | 23.27 | 7.43 |
November | 22.36 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 23.13 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.81 | 0.33 |
April | 22.52 | 7.02 |
May | 24.14 | 14.19 |
June | 24.35 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.02 | 15.39 |
October | 22.32 | 7.43 |
November | 22.01 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.93 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.87 | 0.33 |
April | 22.64 | 7.02 |
May | 24.18 | 14.19 |
June | 24.38 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.15 | 15.39 |
October | 22.62 | 7.43 |
November | 22.16 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 23.00 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.87 | 0.33 |
April | 22.63 | 7.02 |
May | 24.18 | 14.19 |
June | 24.38 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.15 | 15.39 |
October | 22.61 | 7.43 |
November | 22.15 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.99 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -12.6 |
February | 21.85 | -7.7 |
March | 22.26 | 0.33 |
April | 23.10 | 7.02 |
May | 24.29 | 14.19 |
June | 24.39 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.28 | 15.39 |
October | 23.71 | 7.43 |
November | 22.50 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.23 | 6.46 |
Minimum of Months | 21.73 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -12.6 |
February | 21.85 | -7.7 |
March | 22.26 | 0.33 |
April | 23.09 | 7.02 |
May | 24.30 | 14.19 |
June | 24.39 | 19.16 |
July | 24.40 | 20.92 |
August | 24.40 | 20.05 |
September | 24.29 | 15.39 |
October | 23.71 | 7.43 |
November | 22.50 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.23 | 6.46 |
Minimum of Months | 21.73 | -12.6 |
Maximum of Months | 24.40 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.78 | -7.7 |
March | 22.02 | 0.33 |
April | 22.68 | 7.02 |
May | 23.83 | 14.19 |
June | 24.17 | 19.16 |
July | 24.37 | 20.92 |
August | 24.34 | 20.05 |
September | 23.70 | 15.39 |
October | 22.60 | 7.43 |
November | 22.04 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.92 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.83 | 0.33 |
April | 22.46 | 7.02 |
May | 23.75 | 14.19 |
June | 24.15 | 19.16 |
July | 24.37 | 20.92 |
August | 24.33 | 20.05 |
September | 23.52 | 15.39 |
October | 22.15 | 7.43 |
November | 21.88 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.99 | 0.33 |
April | 22.65 | 7.02 |
May | 23.86 | 14.19 |
June | 24.16 | 19.16 |
July | 24.37 | 20.92 |
August | 24.34 | 20.05 |
September | 23.71 | 15.39 |
October | 22.59 | 7.43 |
November | 22.02 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.91 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.79 | 0.33 |
April | 22.40 | 7.02 |
May | 23.74 | 14.19 |
June | 24.12 | 19.16 |
July | 24.35 | 20.92 |
August | 24.30 | 20.05 |
September | 23.48 | 15.39 |
October | 22.04 | 7.43 |
November | 21.82 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.77 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.82 | 0.33 |
April | 22.42 | 7.02 |
May | 23.78 | 14.19 |
June | 24.17 | 19.16 |
July | 24.37 | 20.92 |
August | 24.33 | 20.05 |
September | 23.54 | 15.39 |
October | 22.11 | 7.43 |
November | 21.88 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.81 | 0.33 |
April | 22.42 | 7.02 |
May | 23.78 | 14.19 |
June | 24.17 | 19.16 |
July | 24.37 | 20.92 |
August | 24.33 | 20.05 |
September | 23.54 | 15.39 |
October | 22.10 | 7.43 |
November | 21.87 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.80 | -7.7 |
March | 22.07 | 0.33 |
April | 22.74 | 7.02 |
May | 23.93 | 14.19 |
June | 24.22 | 19.16 |
July | 24.38 | 20.92 |
August | 24.36 | 20.05 |
September | 23.80 | 15.39 |
October | 22.74 | 7.43 |
November | 22.12 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 22.98 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.38 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.80 | -7.7 |
March | 22.07 | 0.33 |
April | 22.74 | 7.02 |
May | 23.93 | 14.19 |
June | 24.22 | 19.16 |
July | 24.38 | 20.92 |
August | 24.36 | 20.05 |
September | 23.80 | 15.39 |
October | 22.75 | 7.43 |
November | 22.12 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 22.98 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.38 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.86 | -12.6 |
February | 20.51 | -7.7 |
March | 21.70 | 0.33 |
April | 23.23 | 7.02 |
May | 25.42 | 14.19 |
June | 26.33 | 19.16 |
July | 26.71 | 20.92 |
August | 26.56 | 20.05 |
September | 25.20 | 15.39 |
October | 22.97 | 7.43 |
November | 21.48 | -0.0 |
December | 20.30 | -7.6 |
Annual Sum or Average | 23.37 | 6.46 |
Minimum of Months | 19.86 | -12.6 |
Maximum of Months | 26.71 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.73 | -12.6 |
February | 18.51 | -7.7 |
March | 19.92 | 0.33 |
April | 21.34 | 7.02 |
May | 23.03 | 14.19 |
June | 25.31 | 19.16 |
July | 25.92 | 20.92 |
August | 25.81 | 20.05 |
September | 24.80 | 15.39 |
October | 21.71 | 7.43 |
November | 19.97 | -0.0 |
December | 18.49 | -7.6 |
Annual Sum or Average | 21.89 | 6.46 |
Minimum of Months | 17.73 | -12.6 |
Maximum of Months | 25.92 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | -12.6 |
February | 22.74 | -7.7 |
March | 23.42 | 0.33 |
April | 24.63 | 7.02 |
May | 26.40 | 14.19 |
June | 26.85 | 19.16 |
July | 26.99 | 20.92 |
August | 26.91 | 20.05 |
September | 26.46 | 15.39 |
October | 24.82 | 7.43 |
November | 23.56 | -0.0 |
December | 22.50 | -7.6 |
Annual Sum or Average | 24.81 | 6.46 |
Minimum of Months | 22.33 | -12.6 |
Maximum of Months | 26.99 | 20.92 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:30
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.121600E+12 | 76961.249 | 31-JAN-18:30 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32485.309 | 0.000 | 0.000 | 0.000 |
February | 0.110218E+12 | 76970.897 | 07-FEB-18:45 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32494.956 | 0.000 | 0.000 | 0.000 |
March | 0.121358E+12 | 74884.690 | 11-MAR-18:45 | 9689.078 | 23563.017 | 6938.423 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32185.842 | 0.000 | 0.000 | 0.000 |
April | 0.118668E+12 | 88078.824 | 15-APR-17:15 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 17333.789 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28777.424 | 0.000 | 0.000 | 0.000 |
May | 0.125141E+12 | 83888.992 | 31-MAY-18:45 | 9689.078 | 23563.017 | 6938.423 | 0.000 | 16292.162 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27406.313 | 0.000 | 0.000 | 0.000 |
June | 0.131200E+12 | 89480.823 | 11-JUN-17:15 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 23160.766 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24352.447 | 0.000 | 0.000 | 0.000 |
July | 0.138376E+12 | 85984.775 | 03-JUL-17:45 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 22062.456 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21954.708 | 0.000 | 0.000 | 0.000 |
August | 0.135233E+12 | 89427.871 | 03-AUG-17:30 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 22494.450 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24965.810 | 0.000 | 0.000 | 0.000 |
September | 0.121442E+12 | 87684.981 | 06-SEP-17:30 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 18701.159 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27016.212 | 0.000 | 0.000 | 0.000 |
October | 0.116021E+12 | 72487.951 | 05-OCT-17:00 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28012.010 | 0.000 | 0.000 | 0.000 |
November | 0.114052E+12 | 72821.142 | 04-NOV-17:30 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 1332.098 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27013.103 | 0.000 | 0.000 | 0.000 |
December | 0.119923E+12 | 74876.893 | 24-DEC-18:30 | 8572.775 | 26456.413 | 6938.423 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30400.953 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.147323E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.110218E+12 | 72487.951 | 8572.775 | 23563.017 | 6938.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21954.708 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.138376E+12 | 89480.823 | 9689.078 | 26456.413 | 6938.423 | 0.000 | 23160.766 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32494.956 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:30
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.194007E+12 | 152595.868 | 19-JAN-04:00 | 152595.868 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 152595.868 |
February | 0.131318E+12 | 155301.196 | 02-FEB-03:00 | 155301.196 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 155301.196 |
March | 0.773181E+11 | 103274.412 | 06-MAR-07:15 | 103274.412 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 103274.412 |
April | 0.296365E+11 | 69604.914 | 03-APR-00:15 | 69604.914 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 69604.914 |
May | 0.179981E+10 | 21911.221 | 02-MAY-02:00 | 21911.221 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21911.221 |
June | 0.622868E+08 | 3032.335 | 03-JUN-03:00 | 3032.335 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3032.335 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.199763E+10 | 22414.294 | 30-SEP-03:00 | 22414.294 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22414.294 |
October | 0.173412E+11 | 34341.624 | 27-OCT-02:00 | 34341.624 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 34341.624 |
November | 0.863474E+11 | 121315.660 | 26-NOV-03:00 | 121315.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 121315.660 |
December | 0.155886E+12 | 161934.128 | 09-DEC-01:00 | 161934.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 161934.128 |
Annual Sum or Average | 0.695713E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.194007E+12 | 161934.128 | 161934.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 161934.128 |