Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2018-10-19 09:20:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2168.95 691.93 768.05
Net Site Energy 2168.95 691.93 768.05
Total Source Energy 5419.88 1729.04 1919.24
Net Source Energy 5419.88 1729.04 1919.24


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 695.71 0.00 0.00 0.00 0.00
Cooling 95.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.39 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 218.81 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 443.57 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1473.23 695.71 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 695.71 0.00 0.00 0.00 0.00
Cooling General 95.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.39 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 218.81 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 443.57 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.38 0.00 0.00 0.00 0.00 0.00
HVAC 268.21 246.36 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 521.69 246.36 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.21 0.00 0.00 0.00 0.00 0.00
HVAC 241.63 221.95 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 469.99 221.95 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1473.23 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1473.23 100.00
     
Total On-Site and Utility Electric Sources 1473.23 100.00
Total Electricity End Uses 1473.23 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 33.00
Time Setpoint Not Met During Occupied Cooling 0.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 3849.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Rochester International Arpt MN USA TMY3 WMO#=726440
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [m] 398.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 11-JUN-17:15 09-DEC-01:00 - - - 01-JAN-07:15
Heating 0.00 161934.13 0.00 0.00 0.00 0.00
Cooling 23160.77 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6938.42 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24352.45 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 89480.82 161934.13 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 161934.13 0.00 0.00 0.00 0.00
Cooling General 23160.77 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6938.42 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 24352.45 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 754.15 0.00 0.00 0.00
Cooling 301.00 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.76 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 692.97 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1404.77 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4665.73 754.15 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 267.05 0.00 0.00 0.00
Cooling 106.59 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.18 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 245.39 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 497.44 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1652.18 267.05 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 267.05 0.00 0.00 0.00
Cooling 106.59 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.18 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 245.39 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 497.44 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1652.18 267.05 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -26.20 0.00 -26.20 Wetbulb [C] 5.70 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 31.20 10.60 23.10 Wetbulb [C] 6.70 200.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.66 83.66 39.39
Exterior Lighting Total 2508.33           39.39



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3408.32 2521.77 886.56 0.74 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3257.70 2407.51 850.19 0.74 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7490.66 5976.67 1513.99 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2470.90 1773.74 697.17 0.72 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2119.95 1506.64 613.30 0.71 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2101.60 1491.69 609.92 0.71 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2374.37 1669.06 705.31 0.70 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2420.03 1708.07 711.96 0.71 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9016.57 6820.41 2196.16 0.76 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8582.65 6467.71 2114.94 0.75 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8294.07 6138.57 2155.50 0.74 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6859.31 5074.98 1784.33 0.74 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5686.62 4175.71 1510.91 0.73 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5656.05 4150.49 1505.56 0.73 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6456.43 4702.41 1754.02 0.73 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6477.86 4720.12 1757.75 0.73 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5804.97 4416.72 1388.25 0.76 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5388.14 4106.48 1281.67 0.76 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5499.07 4145.83 1353.24 0.75 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4556.49 3367.43 1189.06 0.74 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3583.88 2669.09 914.79 0.74 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3549.81 2640.93 908.88 0.74 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4543.01 3411.25 1131.76 0.75 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4557.29 3423.12 1134.18 0.75 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3272.4 3.23 11.02 11.47 10.89
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3128.2 3.23 11.03 11.48 10.90
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7136.8 3.13 10.68 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2379.3 3.27 11.16 11.62 11.10
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2043.3 3.28 11.21 11.67 11.17
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2025.8 3.29 11.21 11.68 11.18
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2290.8 3.30 11.26 11.73 11.24
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2334.0 3.29 11.24 11.71 11.21
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8638.1 3.20 10.92 11.36 10.74
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 8225.5 3.21 10.94 11.38 10.77
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7963.1 3.23 11.02 11.47 10.89
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6585.8 3.23 11.03 11.47 10.89
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5463.9 3.24 11.06 11.51 10.94
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5434.9 3.24 11.06 11.51 10.95
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6208.5 3.25 11.10 11.55 11.00
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6228.8 3.25 11.09 11.55 11.00
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5558.0 3.19 10.90 11.33 10.70
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5158.1 3.19 10.89 11.32 10.69
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5270.0 3.21 10.94 11.38 10.77
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4375.3 3.23 11.03 11.48 10.90
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3438.8 3.22 10.99 11.44 10.85
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3406.4 3.22 11.00 11.45 10.86
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4355.5 3.21 10.96 11.40 10.79
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4369.1 3.21 10.96 11.40 10.79
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   4222.88 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   4195.31 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   7146.45 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   4180.16 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   3162.08 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   3161.74 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   3140.81 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   3277.19 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   8577.73 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   8640.80 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   8538.68 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   8601.73 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   6043.00 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   6042.09 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   5982.45 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   5981.54 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   6222.45 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   6257.13 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   6202.04 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   6236.72 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   4836.41 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   4835.90 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   4799.91 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   4799.41 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 193.76 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 184.68 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 505.80 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.45 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 109.13 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.10 107.83 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 118.84 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 122.40 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 540.04 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 509.55 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.42 471.86 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 389.92 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 317.44 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 315.22 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 353.31 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 354.87 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 352.41 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.37 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 326.82 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.33 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 206.95 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 204.47 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.46 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 268.51 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1755.70 2106.84 0.144 0.173 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
G NW APARTMENT 1673.40 2008.08 0.137 0.165 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
OFFICE 4492.77 5391.32 0.376 0.452 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 25.37 0.01534
G NE APARTMENT 1182.00 1418.40 0.097 0.116 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
G N1 APARTMENT 988.86 1186.63 0.081 0.097 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
G N2 APARTMENT 977.10 1172.52 0.080 0.096 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
G S1 APARTMENT 1076.81 1292.17 0.088 0.106 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
G S2 APARTMENT 1109.05 1330.86 0.091 0.109 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
M SW APARTMENT 4893.31 5871.97 0.402 0.482 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
M NW APARTMENT 4616.99 5540.39 0.379 0.455 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
M SE APARTMENT 4275.24 5130.29 0.351 0.421 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
M NE APARTMENT 3532.79 4239.35 0.290 0.348 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
M N1 APARTMENT 2876.39 3451.67 0.236 0.283 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
M N2 APARTMENT 2856.30 3427.56 0.235 0.281 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
M S1 APARTMENT 3201.30 3841.56 0.263 0.315 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
M S2 APARTMENT 3215.43 3858.51 0.264 0.317 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
T SW APARTMENT 3192.74 3831.29 0.262 0.315 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 30.35 0.01534
T NW APARTMENT 2975.28 3570.34 0.244 0.293 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
T SE APARTMENT 2960.89 3553.07 0.243 0.292 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
T NE APARTMENT 2340.36 2808.44 0.192 0.231 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 31.20 0.01534
T N1 APARTMENT 1875.18 2250.21 0.154 0.185 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
T N2 APARTMENT 1852.71 2223.25 0.152 0.183 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
T S1 APARTMENT 2423.31 2907.98 0.199 0.239 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 31.20 0.01534
T S2 APARTMENT 2432.83 2919.40 0.200 0.240 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 31.20 0.01534


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2313.61 2776.33 0.070 0.084 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G NW APARTMENT 2334.48 2801.38 0.070 0.085 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
OFFICE 4308.53 5170.24 0.126 0.151 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G NE APARTMENT 2321.67 2786.01 0.070 0.084 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G N1 APARTMENT 1460.72 1752.86 0.044 0.053 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G N2 APARTMENT 1460.43 1752.52 0.044 0.053 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G S1 APARTMENT 1442.74 1731.28 0.044 0.052 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G S2 APARTMENT 1558.06 1869.67 0.047 0.056 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
M SW APARTMENT 4827.37 5792.85 0.146 0.175 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M NW APARTMENT 4880.70 5856.84 0.147 0.177 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M SE APARTMENT 4794.34 5753.21 0.145 0.174 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M NE APARTMENT 4847.66 5817.20 0.146 0.175 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M N1 APARTMENT 2683.78 3220.54 0.081 0.097 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M N2 APARTMENT 2683.01 3219.61 0.081 0.097 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M S1 APARTMENT 2632.58 3159.10 0.079 0.095 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
M S2 APARTMENT 2631.81 3158.17 0.079 0.095 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T SW APARTMENT 4048.87 4858.64 0.122 0.147 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T NW APARTMENT 4078.20 4893.83 0.123 0.148 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T SE APARTMENT 4031.61 4837.93 0.122 0.146 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T NE APARTMENT 4060.94 4873.12 0.122 0.147 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T N1 APARTMENT 2876.70 3452.04 0.087 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T N2 APARTMENT 2876.27 3451.52 0.087 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T S1 APARTMENT 2845.84 3415.00 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036
T S2 APARTMENT 2845.41 3414.49 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -26.20 0.00036


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.17 0.17 0.08 0.08
SPLIT GNW 0.16 0.16 0.08 0.08
SPLIT OFFICE 0.45 0.45 0.15 0.15
SPLIT GNE 0.12 0.12 0.08 0.08
SPLIT GN1 0.10 0.10 0.05 0.05
SPLIT GN2 0.10 0.10 0.05 0.05
SPLIT GS1 0.11 0.11 0.05 0.05
SPLIT GS2 0.11 0.11 0.06 0.06
SPLIT MSW 0.48 0.48 0.17 0.17
SPLIT MNW 0.45 0.45 0.18 0.18
SPLIT MSE 0.42 0.42 0.17 0.17
SPLIT MNE 0.35 0.35 0.18 0.18
SPLIT MN1 0.28 0.28 0.10 0.10
SPLIT MN2 0.28 0.28 0.10 0.10
SPLIT MS1 0.32 0.32 0.10 0.10
SPLIT MS2 0.32 0.32 0.10 0.10
SPLIT TSW 0.31 0.31 0.15 0.15
SPLIT TNW 0.29 0.29 0.15 0.15
SPLIT TSE 0.29 0.29 0.15 0.15
SPLIT TNE 0.23 0.23 0.15 0.15
SPLIT TN1 0.18 0.18 0.10 0.10
SPLIT TN2 0.18 0.18 0.10 0.10
SPLIT TS1 0.24 0.24 0.10 0.10
SPLIT TS2 0.24 0.24 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4390.00 6566.25 2677.25
G NW APARTMENT 4713.50 6740.75 3176.50
OFFICE 873.75 1581.75 570.00
G NE APARTMENT 4677.25 6792.25 3188.50
G N1 APARTMENT 4038.75 6890.75 2781.50
G N2 APARTMENT 4032.25 6897.50 2781.25
G S1 APARTMENT 3571.75 6626.25 2028.50
G S2 APARTMENT 3784.75 6672.00 2294.50
M SW APARTMENT 3960.25 4996.00 1158.50
M NW APARTMENT 4448.00 5410.75 1778.50
M SE APARTMENT 3936.25 5008.00 1122.25
M NE APARTMENT 4445.25 5456.25 1767.75
M N1 APARTMENT 3762.75 5328.25 1150.50
M N2 APARTMENT 3763.50 5337.50 1149.25
M S1 APARTMENT 3330.50 4774.75 540.75
M S2 APARTMENT 3328.75 4776.75 539.00
T SW APARTMENT 5281.75 5695.00 2860.25
T NW APARTMENT 5614.75 5998.50 3362.00
T SE APARTMENT 5279.25 5680.00 2847.25
T NE APARTMENT 5609.50 6032.75 3367.00
T N1 APARTMENT 5281.25 6020.25 3046.75
T N2 APARTMENT 5279.00 6023.75 3048.50
T S1 APARTMENT 4856.75 5595.00 2446.00
T S2 APARTMENT 4860.50 5595.50 2445.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6323.75 7009.00 3849.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.75 0.00 3.75 0.00
G NW APARTMENT 2.75 0.25 2.75 0.25
OFFICE 22.25 0.50 0.25 0.00
G NE APARTMENT 3.25 0.00 3.25 0.00
G N1 APARTMENT 2.75 0.00 2.75 0.00
G N2 APARTMENT 1.50 0.00 1.50 0.00
G S1 APARTMENT 1.00 0.00 1.00 0.00
G S2 APARTMENT 1.25 0.00 1.25 0.00
M SW APARTMENT 1.25 0.00 1.25 0.00
M NW APARTMENT 3.00 0.00 3.00 0.00
M SE APARTMENT 3.25 0.00 3.25 0.00
M NE APARTMENT 5.50 0.00 5.50 0.00
M N1 APARTMENT 0.75 0.00 0.75 0.00
M N2 APARTMENT 0.75 0.00 0.75 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.50 0.00 0.50 0.00
T SW APARTMENT 2.75 0.00 2.75 0.00
T NW APARTMENT 3.00 0.00 3.00 0.00
T SE APARTMENT 2.75 0.00 2.75 0.00
T NE APARTMENT 4.00 0.00 4.00 0.00
T N1 APARTMENT 2.00 0.00 2.00 0.00
T N2 APARTMENT 1.75 0.00 1.75 0.00
T S1 APARTMENT 2.25 0.00 2.25 0.00
T S2 APARTMENT 2.50 0.00 2.50 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 55.00 0.75 33.00 0.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.366 0.145 0.000 0.076
G NW APARTMENT 1.71 2.50 268.97 0.353 0.145 0.000 0.070
OFFICE 0.94 1.00 268.97 0.519 0.161 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.353 0.145 0.000 0.070
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.087 0.000 0.070
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.087 0.000 0.070
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.087 0.000 0.076
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.087 0.000 0.076
M SW APARTMENT 1.71 2.50 268.97 0.354 0.208 0.000 0.097
M NW APARTMENT 1.71 2.50 268.97 0.353 0.208 0.000 0.089
M SE APARTMENT 1.71 2.50 268.97 0.354 0.208 0.000 0.097
M NE APARTMENT 1.71 2.50 268.97 0.353 0.208 0.000 0.089
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.126 0.000 0.089
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.126 0.000 0.088
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.126 0.000 0.097
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.126 0.000 0.097
T SW APARTMENT 1.71 2.50 268.97 0.353 0.275 0.000 0.120
T NW APARTMENT 1.71 2.50 268.97 0.353 0.275 0.000 0.108
T SE APARTMENT 1.71 2.50 268.97 0.353 0.275 0.000 0.120
T NE APARTMENT 1.71 2.50 268.97 0.353 0.275 0.000 0.108
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.166 0.000 0.108
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.166 0.000 0.108
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.166 0.000 0.120
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.166 0.000 0.120
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.354 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.364 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.365 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 443.57 0.00 01-JAN-00:15 32953.17 08-FEB-07:30
WaterSystems:Electricity 443.57 0.00 01-JAN-00:15 32953.17 08-FEB-07:30
Water Heater:WaterSystems:Electricity 443.57 0.00 01-JAN-00:15 32953.17 08-FEB-07:30
Fans:Electricity 218.81 6938.42 07-DEC-08:00 6938.42 02-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
ElectricityPurchased:Plant 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
Cogeneration:ElectricityPurchased 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
ElectricityNet:Plant 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
Cogeneration:ElectricityNet 1473.23 20308.72 01-JAN-03:15 89480.82 11-JUN-17:15
ExteriorLights:Electricity 39.39 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.39 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
Electricity:HVAC 313.85 6938.42 07-DEC-08:00 33687.12 04-AUG-15:15
General:Fans:Electricity 218.81 6938.42 07-DEC-08:00 6938.42 02-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 95.04 0.00 01-JAN-00:15 26748.70 04-AUG-15:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 695.71 0.00 18-MAR-15:15 161934.13 09-DEC-02:00
Gas:HVAC 695.71 0.00 18-MAR-15:15 161934.13 09-DEC-02:00
Heating:Gas 695.71 0.00 18-MAR-15:15 161934.13 09-DEC-02:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1580.87 1311.18 14-APR-11:45 223811.23 09-DEC-02:00
EnergyTransfer:Building 634.63 1311.18 14-APR-11:45 94263.93 09-DEC-02:00
EnergyTransfer:Zone:G SW APARTMENT 16.44 0.02 23-MAR-15:45 3020.23 09-DEC-02:00
Heating:EnergyTransfer 301.23 0.00 18-MAR-18:15 94263.93 09-DEC-02:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 9.87 0.00 02-JAN-13:15 3020.23 09-DEC-02:00
Cooling:EnergyTransfer 333.40 0.00 02-JAN-07:30 60760.21 25-JUN-17:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 6.57 0.00 01-JAN-00:15 1951.34 07-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 17.51 0.05 08-MAY-19:15 3049.27 09-DEC-02:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 12.55 0.00 20-FEB-16:15 3049.27 09-DEC-02:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 4.96 0.00 01-JAN-00:15 1730.38 25-JUN-17:30
EnergyTransfer:Zone:OFFICE 21.22 0.07 21-MAY-18:30 4733.93 29-JAN-07:30
Heating:EnergyTransfer:Zone:OFFICE 1.28 0.00 01-JAN-00:15 4733.93 29-JAN-07:30
Cooling:EnergyTransfer:Zone:OFFICE 19.94 0.00 02-JAN-07:30 3447.42 07-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 17.53 0.01 01-OCT-15:15 2984.59 09-DEC-09:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 12.45 0.00 18-MAR-14:15 2984.59 09-DEC-09:30
Cooling:EnergyTransfer:Zone:G NE APARTMENT 5.08 0.00 01-JAN-00:15 1237.78 25-JUN-18:15
EnergyTransfer:Zone:G N1 APARTMENT 11.32 0.02 16-APR-22:00 1841.08 09-DEC-09:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 6.72 0.00 13-JAN-17:15 1841.08 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.59 0.00 01-JAN-00:15 990.29 25-JUN-18:15
EnergyTransfer:Zone:G N2 APARTMENT 11.32 0.03 04-MAY-19:00 1840.75 09-DEC-09:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 6.73 0.00 13-JAN-17:15 1840.75 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.59 0.00 01-JAN-00:15 980.09 25-JUN-18:15
EnergyTransfer:Zone:G S1 APARTMENT 11.00 0.02 27-MAY-11:15 1802.14 09-DEC-09:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 4.54 0.00 02-JAN-10:30 1802.14 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 6.46 0.00 01-JAN-00:15 1380.76 07-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 11.59 0.01 21-OCT-15:30 1951.73 09-DEC-09:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 5.33 0.00 02-JAN-10:45 1951.73 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 6.26 0.00 01-JAN-00:15 1369.05 07-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 42.61 0.41 14-MAR-14:15 6544.42 09-DEC-02:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 15.33 0.00 02-JAN-12:30 6544.42 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 27.27 0.00 01-JAN-00:15 5433.49 06-SEP-16:15
EnergyTransfer:Zone:M NW APARTMENT 42.80 0.04 10-JUL-12:30 6588.42 09-DEC-02:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 21.83 0.00 11-JAN-19:00 6588.42 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 20.97 0.00 01-JAN-00:15 5001.40 25-JUN-17:30
EnergyTransfer:Zone:M SE APARTMENT 42.57 0.17 09-MAY-11:15 6435.09 09-DEC-02:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 15.23 0.00 02-JAN-12:15 6435.09 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 27.34 0.00 01-JAN-00:15 4845.38 07-SEP-13:45
EnergyTransfer:Zone:M NE APARTMENT 42.98 0.15 20-OCT-18:30 6417.44 09-DEC-02:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 21.73 0.00 11-JAN-19:00 6417.44 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 21.25 0.00 01-JAN-00:15 3875.42 25-JUN-17:45
EnergyTransfer:Zone:M N1 APARTMENT 29.01 0.43 19-MAR-13:30 3736.46 09-DEC-02:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 8.61 0.00 01-JAN-12:00 3736.46 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 20.40 0.00 01-JAN-00:15 3134.76 25-JUN-18:15
EnergyTransfer:Zone:M N2 APARTMENT 28.99 0.13 15-MAR-10:15 3733.44 09-DEC-02:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 8.61 0.00 01-JAN-12:00 3733.44 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 20.38 0.00 01-JAN-00:15 3117.41 25-JUN-18:15
EnergyTransfer:Zone:M S1 APARTMENT 33.21 0.00 23-DEC-20:00 4005.79 07-SEP-13:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 4.51 0.00 01-JAN-10:00 3677.70 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 28.70 0.00 01-JAN-00:15 4005.79 07-SEP-13:45
EnergyTransfer:Zone:M S2 APARTMENT 33.19 0.05 23-NOV-14:45 4014.25 07-SEP-13:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 4.51 0.00 01-JAN-10:00 3678.41 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 28.68 0.00 01-JAN-00:15 4014.25 07-SEP-13:45
EnergyTransfer:Zone:T SW APARTMENT 31.71 0.01 27-MAY-04:30 5324.14 09-DEC-02:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 20.05 0.00 02-JAN-13:45 5324.14 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 11.66 0.00 01-JAN-00:15 3550.29 07-SEP-15:15
EnergyTransfer:Zone:T NW APARTMENT 33.16 0.00 08-MAY-00:45 5333.65 09-DEC-02:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 23.92 0.00 20-FEB-16:15 5333.65 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 9.24 0.00 01-JAN-00:15 3287.32 25-JUN-17:15
EnergyTransfer:Zone:T SE APARTMENT 31.42 0.01 14-APR-08:15 5275.87 09-DEC-02:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 19.90 0.00 12-JAN-10:45 5275.87 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 11.52 0.00 01-JAN-00:15 3332.08 07-SEP-13:30
EnergyTransfer:Zone:T NE APARTMENT 32.99 0.01 01-OCT-20:15 5234.51 09-DEC-02:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 23.75 0.00 24-FEB-13:00 5234.51 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 9.24 0.00 01-JAN-00:15 2680.96 11-JUN-15:15
EnergyTransfer:Zone:T N1 APARTMENT 23.46 0.00 29-AUG-05:45 3724.69 09-DEC-02:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 15.19 0.00 24-FEB-12:45 3724.69 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 8.26 0.00 01-JAN-00:15 2124.60 11-JUN-15:15
EnergyTransfer:Zone:T N2 APARTMENT 23.46 0.04 02-OCT-14:45 3721.98 09-DEC-02:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 15.20 0.00 24-FEB-12:30 3721.98 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 8.26 0.00 01-JAN-00:15 2120.06 11-JUN-15:15
EnergyTransfer:Zone:T S1 APARTMENT 22.57 0.01 10-APR-23:15 3739.07 09-DEC-02:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 11.69 0.00 02-JAN-11:45 3739.07 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.87 0.00 01-JAN-00:15 2894.96 07-SEP-13:30
EnergyTransfer:Zone:T S2 APARTMENT 22.57 0.01 12-SEP-05:45 3739.52 09-DEC-02:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 11.70 0.00 02-JAN-11:45 3739.52 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.88 0.00 01-JAN-00:15 2902.76 07-SEP-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 946.24 0.00 19-MAR-18:00 129547.30 09-DEC-02:00
HeatingCoils:EnergyTransfer 556.57 0.00 18-MAR-15:15 129547.30 09-DEC-02:00
CoolingCoils:EnergyTransfer 389.67 0.00 01-JAN-00:15 104353.26 04-AUG-16:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 9.870 -6.569 0.000 0.000 3.879 2.413 12.213 11.970 0.000 0.103 0.000 0.000 -9.672 0.000 -7.685 -16.521
G NW APARTMENT 12.551 -4.959 0.000 0.000 3.892 2.413 12.213 6.019 0.000 0.100 0.000 0.000 -10.367 0.000 -7.579 -14.284
OFFICE 1.278 -19.944 0.000 0.000 0.541 21.914 7.534 11.885 0.000 0.085 0.001 0.000 -8.859 0.000 -6.375 -8.061
G NE APARTMENT 12.449 -5.080 0.000 0.000 3.902 2.413 12.213 5.802 0.000 0.100 0.000 0.000 -10.189 0.000 -7.561 -14.048
G N1 APARTMENT 6.725 -4.594 0.000 0.000 3.897 2.413 12.213 2.143 0.000 0.072 0.000 0.000 -6.534 0.000 -4.830 -11.505
G N2 APARTMENT 6.726 -4.594 0.000 0.000 3.898 2.413 12.213 2.143 0.000 0.072 0.000 0.000 -6.533 0.000 -4.830 -11.508
G S1 APARTMENT 4.537 -6.465 0.000 0.000 3.879 2.413 12.213 8.157 0.000 0.074 0.000 0.000 -5.858 0.000 -4.936 -14.015
G S2 APARTMENT 5.328 -6.257 0.000 0.000 3.880 2.413 12.213 8.161 0.000 0.074 0.000 0.000 -5.843 0.000 -4.936 -15.032
M SW APARTMENT 15.331 -27.274 0.000 0.000 3.792 2.413 12.213 11.568 0.000 0.144 3.281 0.000 -10.307 0.000 -11.161 -0.001
M NW APARTMENT 21.834 -20.965 0.000 0.000 3.826 2.413 12.213 5.719 0.000 0.139 0.000 0.000 -10.959 0.000 -10.964 -3.256
M SE APARTMENT 15.232 -27.342 0.000 0.000 3.798 2.413 12.213 11.367 0.000 0.144 3.463 0.000 -10.136 0.000 -11.151 -0.001
M NE APARTMENT 21.732 -21.247 0.000 0.000 3.835 2.413 12.213 5.499 0.000 0.139 0.000 0.000 -10.756 0.000 -10.939 -2.890
M N1 APARTMENT 8.609 -20.405 0.000 0.000 3.818 2.413 12.213 1.960 0.000 0.098 5.254 0.000 -6.961 0.000 -7.000 -0.001
M N2 APARTMENT 8.612 -20.382 0.000 0.000 3.819 2.413 12.213 1.960 0.000 0.098 5.225 0.000 -6.959 0.000 -6.999 -0.001
M S1 APARTMENT 4.510 -28.698 0.000 0.000 3.774 2.413 12.213 7.897 0.000 0.103 11.247 0.000 -6.276 0.000 -7.183 -0.000
M S2 APARTMENT 4.510 -28.678 0.000 0.000 3.774 2.413 12.213 7.897 0.000 0.103 11.226 0.000 -6.275 0.000 -7.183 -0.000
T SW APARTMENT 20.055 -11.659 0.000 0.000 3.843 2.413 12.213 11.489 0.000 0.200 0.000 0.000 -9.869 0.000 -14.464 -14.220
T NW APARTMENT 23.922 -9.241 0.000 0.000 3.863 2.413 12.213 5.666 0.000 0.192 0.000 0.000 -10.548 0.000 -14.249 -14.230
T SE APARTMENT 19.896 -11.521 0.000 0.000 3.848 2.413 12.213 11.304 0.000 0.200 0.000 0.000 -9.717 0.000 -14.465 -14.170
T NE APARTMENT 23.749 -9.242 0.000 0.000 3.873 2.413 12.213 5.465 0.000 0.192 0.000 0.000 -10.363 0.000 -14.225 -14.075
T N1 APARTMENT 15.191 -8.264 0.000 0.000 3.863 2.413 12.213 1.960 0.000 0.138 0.000 0.000 -6.663 0.000 -9.019 -11.831
T N2 APARTMENT 15.196 -8.265 0.000 0.000 3.864 2.413 12.213 1.959 0.000 0.138 0.000 0.000 -6.660 0.000 -9.018 -11.840
T S1 APARTMENT 11.694 -10.874 0.000 0.000 3.832 2.413 12.213 7.865 0.000 0.147 0.000 0.000 -6.007 0.000 -9.237 -12.046
T S2 APARTMENT 11.699 -10.875 0.000 0.000 3.832 2.413 12.213 7.863 0.000 0.147 0.000 0.000 -6.006 0.000 -9.237 -12.049
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.074 0.000 0.005 0.000 0.000 -1.240 0.000 -2.323 -13.586
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.280 0.000 0.178 7.217 0.000 -3.317 0.000 -27.693 -0.001
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.075 0.000 0.005 0.000 0.000 -1.347 0.000 -1.903 -13.899
Total Facility 301.233 -333.393 0.000 0.000 89.020 128.627 294.692 164.149 0.000 3.188 46.915 0.000 -204.221 0.000 -247.144 -243.072


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 07-SEP-15:15 0.00 -1951.32 0.00 0.00 48.90 100.83 470.90 2511.44 0.00 16.50 0.00 0.00 0.00 0.00 0.00 -1197.24
G NW APARTMENT 25-JUN-17:30 0.00 -1730.38 0.00 0.00 141.81 194.45 588.62 1940.47 0.00 141.63 0.00 0.00 0.00 0.00 0.00 -1276.60
OFFICE 07-SEP-13:30 0.00 -3447.33 0.00 0.00 67.31 1622.34 544.92 2207.30 0.00 25.07 0.00 0.00 0.00 0.00 0.00 -1019.60
G NE APARTMENT 25-JUN-18:15 0.00 -1237.74 0.00 0.00 141.82 230.46 547.42 697.87 0.00 112.66 0.00 0.00 0.00 0.00 0.00 -492.49
G N1 APARTMENT 25-JUN-18:15 0.00 -990.22 0.00 0.00 141.81 230.46 547.42 566.47 0.00 67.95 0.00 0.00 0.00 0.00 0.00 -563.89
G N2 APARTMENT 25-JUN-18:15 0.00 -980.02 0.00 0.00 141.81 230.46 547.42 566.64 0.00 67.95 0.00 0.00 0.00 0.00 0.00 -574.27
G S1 APARTMENT 07-SEP-13:30 0.00 -1380.61 0.00 0.00 40.75 28.81 382.60 1917.50 0.00 14.18 0.00 0.00 0.00 0.00 0.00 -1003.23
G S2 APARTMENT 07-SEP-13:30 0.00 -1368.91 0.00 0.00 40.75 28.81 382.60 1917.67 0.00 14.18 0.00 0.00 0.00 0.00 0.00 -1015.11
M SW APARTMENT 06-SEP-16:10 0.00 -5435.08 0.00 0.00 84.76 144.04 588.62 2011.73 0.00 126.52 2479.40 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 25-JUN-17:23 0.00 -5001.73 0.00 0.00 141.81 194.45 588.62 1918.72 0.00 202.96 1955.16 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 07-SEP-13:45 0.00 -4845.29 0.00 0.00 40.75 28.81 382.60 2092.04 0.00 51.37 2249.73 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 25-JUN-17:45 0.00 -3875.39 0.00 0.00 141.81 194.45 588.62 648.69 0.00 191.20 2110.61 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 25-JUN-18:15 0.00 -3134.61 0.00 0.00 141.81 230.46 547.42 554.61 0.00 97.34 1562.96 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 25-JUN-18:15 0.00 -3117.26 0.00 0.00 141.81 230.46 547.42 554.71 0.00 97.34 1545.51 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 07-SEP-13:45 0.00 -4005.63 0.00 0.00 40.75 28.81 382.60 1819.66 0.00 30.98 1702.82 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 07-SEP-13:45 0.00 -4014.10 0.00 0.00 40.75 28.81 382.60 1819.61 0.00 30.98 1711.35 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 07-SEP-15:15 0.00 -3550.29 0.00 0.00 48.90 100.83 470.90 2463.28 0.00 31.10 435.28 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 25-JUN-17:10 0.00 -3288.78 0.00 0.00 141.82 194.45 588.62 1875.24 0.00 282.87 205.78 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 07-SEP-13:30 0.00 -3331.97 0.00 0.00 40.75 28.81 382.60 2148.36 0.00 44.34 687.11 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 11-JUN-15:15 0.00 -2681.50 0.00 0.00 48.90 100.83 470.90 901.26 0.00 337.51 822.10 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 11-JUN-15:15 0.00 -2124.91 0.00 0.00 48.90 100.83 470.90 551.45 0.00 203.56 749.27 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 11-JUN-15:15 0.00 -2120.38 0.00 0.00 48.90 100.83 470.90 551.50 0.00 203.56 744.70 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 07-SEP-13:30 0.00 -2894.80 0.00 0.00 40.75 28.81 382.60 1888.03 0.00 26.74 527.87 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 07-SEP-13:30 0.00 -2902.60 0.00 0.00 40.75 28.81 382.60 1887.92 0.00 26.74 535.78 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 25-JUN-17:10 0.00 -60791.40 0.00 0.00 3261.76 6475.86 14071.03 18632.96 0.00 4411.55 13938.24 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 09-DEC-02:00 3020.20 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1142.46 0.00 -1792.63 -530.52
G NW APARTMENT 09-DEC-02:00 3049.24 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1172.13 0.00 -1792.02 -530.50
OFFICE 12-MAR-06:01 6624.74 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -401.05 0.00 -163.88 -6634.38
G NE APARTMENT 09-DEC-02:00 2984.55 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1150.68 0.00 -1790.39 -488.89
G N1 APARTMENT 09-DEC-08:53 1841.11 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -666.11 0.00 -1015.75 -664.92
G N2 APARTMENT 09-DEC-08:53 1840.84 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -666.12 0.00 -1015.75 -664.65
G S1 APARTMENT 09-DEC-09:00 1802.24 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -635.52 0.00 -1015.75 -656.64
G S2 APARTMENT 09-DEC-09:00 1951.76 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -633.45 0.00 -1015.75 -808.23
M SW APARTMENT 09-DEC-02:00 6544.35 0.00 0.00 0.00 190.85 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1168.38 0.00 -2560.80 -3261.76
M NW APARTMENT 09-DEC-02:00 6588.35 0.00 0.00 0.00 192.21 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1196.78 0.00 -2551.20 -3288.31
M SE APARTMENT 09-DEC-02:00 6435.03 0.00 0.00 0.00 191.33 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1143.89 0.00 -2557.01 -3181.20
M NE APARTMENT 09-DEC-02:00 6417.37 0.00 0.00 0.00 193.06 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1171.81 0.00 -2545.26 -3149.09
M N1 APARTMENT 09-DEC-02:00 3736.42 0.00 0.00 0.00 190.62 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -730.70 0.00 -1546.95 -1905.14
M N2 APARTMENT 09-DEC-02:00 3733.40 0.00 0.00 0.00 190.64 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -730.67 0.00 -1546.84 -1902.28
M S1 APARTMENT 09-DEC-02:00 3677.66 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -698.77 0.00 -1553.68 -1870.62
M S2 APARTMENT 09-DEC-02:00 3678.38 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -698.76 0.00 -1553.68 -1871.34
T SW APARTMENT 09-DEC-02:00 5324.09 0.00 0.00 0.00 192.15 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1140.74 0.00 -3375.15 -1256.08
T NW APARTMENT 09-DEC-02:00 5333.59 0.00 0.00 0.00 192.60 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1172.96 0.00 -3370.70 -1238.27
T SE APARTMENT 09-DEC-02:00 5275.82 0.00 0.00 0.00 192.48 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1116.02 0.00 -3371.88 -1236.13
T NE APARTMENT 09-DEC-02:00 5234.45 0.00 0.00 0.00 193.51 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -1147.07 0.00 -3361.84 -1174.79
T N1 APARTMENT 09-DEC-02:00 3724.66 0.00 0.00 0.00 189.70 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -715.99 0.00 -2054.80 -1399.31
T N2 APARTMENT 09-DEC-02:00 3721.95 0.00 0.00 0.00 189.72 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -715.97 0.00 -2054.62 -1396.81
T S1 APARTMENT 09-DEC-02:00 3739.04 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -682.51 0.00 -2057.26 -1444.68
T S2 APARTMENT 09-DEC-02:00 3739.48 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -682.51 0.00 -2057.28 -1445.10
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-DEC-02:00 94262.97 0.00 0.00 0.00 4385.24 2334.74 5719.80 0.00 0.00 0.00 0.00 0.00 -22706.70 0.00 -50652.93 -33343.11



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Sec1.1A-General Information

Data
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 33.00
Number of hours cooling loads not met 0.25
Number of hours not met 33.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.39 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 695.71 161934.13 0.00 0.00
Space Cooling 95.04 23160.77 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 218.81 6938.42 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 443.57 24352.45 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1473.23   695.71   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1473.23
Natural Gas 0.00 695.71
Additional 0.00 0.00
Total 511.42 2168.95


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 30.32
Fans-Interior 69.80
Service Water Heating 141.51
Receptacle Equipment 163.15
Miscellaneous 12.57
Subtotal 469.99


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 221.95
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 221.95


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.61
Space Heating 32.08
Space Cooling 4.38
Fans-Interior 10.09
Service Water Heating 20.45
Receptacle Equipment 23.58
Miscellaneous 1.82



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.172984
G NW APARTMENT DIRECT AIR 0.164877
OFFICE DIRECT AIR 0.451561
G NE APARTMENT DIRECT AIR 0.116460
G N1 APARTMENT DIRECT AIR 0.097428
G N2 APARTMENT DIRECT AIR 0.096270
G S1 APARTMENT DIRECT AIR 0.106097
G S2 APARTMENT DIRECT AIR 0.109274
M SW APARTMENT DIRECT AIR 0.482134
M NW APARTMENT DIRECT AIR 0.454912
M SE APARTMENT DIRECT AIR 0.421266
M NE APARTMENT DIRECT AIR 0.348114
M N1 APARTMENT DIRECT AIR 0.283400
M N2 APARTMENT DIRECT AIR 0.281421
M S1 APARTMENT DIRECT AIR 0.315427
M S2 APARTMENT DIRECT AIR 0.316818
T SW APARTMENT DIRECT AIR 0.314620
T NW APARTMENT DIRECT AIR 0.293162
T SE APARTMENT DIRECT AIR 0.291773
T NE APARTMENT DIRECT AIR 0.230625
T N1 APARTMENT DIRECT AIR 0.184758
T N2 APARTMENT DIRECT AIR 0.182544
T S1 APARTMENT DIRECT AIR 0.238780
T S2 APARTMENT DIRECT AIR 0.239718


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.172984
SPLIT GNW MAIN BRANCH 0.164877
SPLIT OFFICE MAIN BRANCH 0.451561
SPLIT GNE MAIN BRANCH 0.116460
SPLIT GN1 MAIN BRANCH 0.097428
SPLIT GN2 MAIN BRANCH 0.096270
SPLIT GS1 MAIN BRANCH 0.106097
SPLIT GS2 MAIN BRANCH 0.109274
SPLIT MSW MAIN BRANCH 0.482134
SPLIT MNW MAIN BRANCH 0.454912
SPLIT MSE MAIN BRANCH 0.421266
SPLIT MNE MAIN BRANCH 0.348114
SPLIT MN1 MAIN BRANCH 0.283400
SPLIT MN2 MAIN BRANCH 0.281421
SPLIT MS1 MAIN BRANCH 0.315427
SPLIT MS2 MAIN BRANCH 0.316818
SPLIT TSW MAIN BRANCH 0.314620
SPLIT TNW MAIN BRANCH 0.293162
SPLIT TSE MAIN BRANCH 0.291773
SPLIT TNE MAIN BRANCH 0.230625
SPLIT TN1 MAIN BRANCH 0.184758
SPLIT TN2 MAIN BRANCH 0.182544
SPLIT TS1 MAIN BRANCH 0.238780
SPLIT TS2 MAIN BRANCH 0.239718


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.172984
SPLIT GNW 0.164877
SPLIT OFFICE 0.451561
SPLIT GNE 0.116460
SPLIT GN1 0.097428
SPLIT GN2 0.096270
SPLIT GS1 0.106097
SPLIT GS2 0.109274
SPLIT MSW 0.482134
SPLIT MNW 0.454912
SPLIT MSE 0.421266
SPLIT MNE 0.348114
SPLIT MN1 0.283400
SPLIT MN2 0.281421
SPLIT MS1 0.315427
SPLIT MS2 0.316818
SPLIT TSW 0.314620
SPLIT TNW 0.293162
SPLIT TSE 0.291773
SPLIT TNE 0.230625
SPLIT TN1 0.184758
SPLIT TN2 0.182544
SPLIT TS1 0.238780
SPLIT TS2 0.239718


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.172984 0.026898
SPLIT GNW OA CONTROLLER 0.164877 0.025953
SPLIT OFFICE OA CONTROLLER 0.451561 0.038104
SPLIT GNE OA CONTROLLER 0.116460 0.025953
SPLIT GN1 OA CONTROLLER 0.097428 0.025953
SPLIT GN2 OA CONTROLLER 0.096270 0.025953
SPLIT GS1 OA CONTROLLER 0.106097 0.025953
SPLIT GS2 OA CONTROLLER 0.109274 0.025953
SPLIT MSW OA CONTROLLER 0.482134 0.051906
SPLIT MNW OA CONTROLLER 0.454912 0.051906
SPLIT MSE OA CONTROLLER 0.421266 0.051906
SPLIT MNE OA CONTROLLER 0.348114 0.051906
SPLIT MN1 OA CONTROLLER 0.283400 0.051906
SPLIT MN2 OA CONTROLLER 0.281421 0.051906
SPLIT MS1 OA CONTROLLER 0.315427 0.051906
SPLIT MS2 OA CONTROLLER 0.316818 0.051906
SPLIT TSW OA CONTROLLER 0.314620 0.025953
SPLIT TNW OA CONTROLLER 0.293162 0.025953
SPLIT TSE OA CONTROLLER 0.291773 0.025953
SPLIT TNE OA CONTROLLER 0.230625 0.025953
SPLIT TN1 OA CONTROLLER 0.184758 0.025953
SPLIT TN2 OA CONTROLLER 0.182544 0.025953
SPLIT TS1 OA CONTROLLER 0.238780 0.025953
SPLIT TS2 OA CONTROLLER 0.239718 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.172984 3408.32 0.739885
SPLIT GNW COOLING COIL 0.164877 3257.70 0.739021
SPLIT OFFICE COOLING COIL 0.451561 7490.66 0.797883
SPLIT GNE COOLING COIL 0.116460 2470.90 0.717849
SPLIT GN1 COOLING COIL 0.097428 2119.95 0.710699
SPLIT GN2 COOLING COIL 0.096270 2101.60 0.709785
SPLIT GS1 COOLING COIL 0.106097 2374.37 0.702950
SPLIT GS2 COOLING COIL 0.109274 2420.03 0.705807
SPLIT MSW COOLING COIL 0.482134 9016.57 0.756430
SPLIT MNW COOLING COIL 0.454912 8582.65 0.753580
SPLIT MSE COOLING COIL 0.421266 8294.07 0.740115
SPLIT MNE COOLING COIL 0.348114 6859.31 0.739868
SPLIT MN1 COOLING COIL 0.283400 5686.62 0.734304
SPLIT MN2 COOLING COIL 0.281421 5656.05 0.733814
SPLIT MS1 COOLING COIL 0.315427 6456.43 0.728330
SPLIT MS2 COOLING COIL 0.316818 6477.86 0.728653
SPLIT TSW COOLING COIL 0.314620 5804.97 0.760851
SPLIT TNW COOLING COIL 0.293162 5388.14 0.762132
SPLIT TSE COOLING COIL 0.291773 5499.07 0.753915
SPLIT TNE COOLING COIL 0.230625 4556.49 0.739041
SPLIT TN1 COOLING COIL 0.184758 3583.88 0.744748
SPLIT TN2 COOLING COIL 0.182544 3549.81 0.743964
SPLIT TS1 COOLING COIL 0.238780 4543.01 0.750879
SPLIT TS2 COOLING COIL 0.239718 4557.29 0.751129


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.172984 0.172984 0.172984 0.172984 4222.88 3408.32 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.164877 0.164877 0.164877 0.164877 4195.31 3257.70 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.451561 0.451561 0.451561 0.451561 7146.45 7490.66 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.116460 0.116460 0.116460 0.116460 4180.16 2470.90 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.097428 0.097428 0.097428 0.097428 3162.08 2119.95 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.096270 0.096270 0.096270 0.096270 3161.74 2101.60 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.106097 0.106097 0.106097 0.106097 3140.81 2374.37 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.109274 0.109274 0.109274 0.109274 3277.19 2420.03 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.482134 0.482134 0.482134 0.482134 8577.73 9016.57 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.454912 0.454912 0.454912 0.454912 8640.80 8582.65 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.421266 0.421266 0.421266 0.421266 8538.68 8294.07 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.348114 0.348114 0.348114 0.348114 8601.73 6859.31 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.283400 0.283400 0.283400 0.283400 6043.00 5686.62 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.281421 0.281421 0.281421 0.281421 6042.09 5656.05 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.315427 0.315427 0.315427 0.315427 5982.45 6456.43 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.316818 0.316818 0.316818 0.316818 5981.54 6477.86 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.314620 0.314620 0.314620 0.314620 6222.45 5804.97 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.293162 0.293162 0.293162 0.293162 6257.13 5388.14 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.291773 0.291773 0.291773 0.291773 6202.04 5499.07 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.230625 0.230625 0.230625 0.230625 6236.72 4556.49 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.184758 0.184758 0.184758 0.184758 4836.41 3583.88 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.182544 0.182544 0.182544 0.182544 4835.90 3549.81 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.238780 0.238780 0.238780 0.238780 4799.91 4543.01 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.239718 0.239718 0.239718 0.239718 4799.41 4557.29 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.172984
SPLIT GNW SUPPLY FAN 0.164877
SPLIT OFFICE SUPPLY FAN 0.451561
SPLIT GNE SUPPLY FAN 0.116460
SPLIT GN1 SUPPLY FAN 0.097428
SPLIT GN2 SUPPLY FAN 0.096270
SPLIT GS1 SUPPLY FAN 0.106097
SPLIT GS2 SUPPLY FAN 0.109274
SPLIT MSW SUPPLY FAN 0.482134
SPLIT MNW SUPPLY FAN 0.454912
SPLIT MSE SUPPLY FAN 0.421266
SPLIT MNE SUPPLY FAN 0.348114
SPLIT MN1 SUPPLY FAN 0.283400
SPLIT MN2 SUPPLY FAN 0.281421
SPLIT MS1 SUPPLY FAN 0.315427
SPLIT MS2 SUPPLY FAN 0.316818
SPLIT TSW SUPPLY FAN 0.314620
SPLIT TNW SUPPLY FAN 0.293162
SPLIT TSE SUPPLY FAN 0.291773
SPLIT TNE SUPPLY FAN 0.230625
SPLIT TN1 SUPPLY FAN 0.184758
SPLIT TN2 SUPPLY FAN 0.182544
SPLIT TS1 SUPPLY FAN 0.238780
SPLIT TS2 SUPPLY FAN 0.239718


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 4222.88
SPLIT GNW HEATING COIL 4195.31
SPLIT OFFICE HEATING COIL 7146.45
SPLIT GNE HEATING COIL 4180.16
SPLIT GN1 HEATING COIL 3162.08
SPLIT GN2 HEATING COIL 3161.74
SPLIT GS1 HEATING COIL 3140.81
SPLIT GS2 HEATING COIL 3277.19
SPLIT MSW HEATING COIL 8577.73
SPLIT MNW HEATING COIL 8640.80
SPLIT MSE HEATING COIL 8538.68
SPLIT MNE HEATING COIL 8601.73
SPLIT MN1 HEATING COIL 6043.00
SPLIT MN2 HEATING COIL 6042.09
SPLIT MS1 HEATING COIL 5982.45
SPLIT MS2 HEATING COIL 5981.54
SPLIT TSW HEATING COIL 6222.45
SPLIT TNW HEATING COIL 6257.13
SPLIT TSE HEATING COIL 6202.04
SPLIT TNE HEATING COIL 6236.72
SPLIT TN1 HEATING COIL 4836.41
SPLIT TN2 HEATING COIL 4835.90
SPLIT TS1 HEATING COIL 4799.91
SPLIT TS2 HEATING COIL 4799.41



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.72 -7.7
March 21.79 0.33
April 22.25 7.02
May 22.94 14.19
June 24.12 19.16
July 24.36 20.92
August 24.35 20.05
September 23.87 15.39
October 22.25 7.43
November 21.84 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.75 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.36 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.08 7.02
May 22.78 14.19
June 24.10 19.16
July 24.36 20.92
August 24.34 20.05
September 23.72 15.39
October 21.92 7.43
November 21.74 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.66 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.36 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.92 -12.6
February 18.86 -7.7
March 20.26 0.33
April 21.74 7.02
May 23.39 14.19
June 23.84 19.16
July 23.90 20.92
August 23.90 20.05
September 23.68 15.39
October 22.32 7.43
November 20.18 -0.0
December 18.43 -7.6
     
Annual Sum or Average 21.55 6.46
Minimum of Months 17.92 -12.6
Maximum of Months 23.90 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.71 0.33
April 22.03 7.02
May 22.69 14.19
June 24.06 19.16
July 24.34 20.92
August 24.31 20.05
September 23.67 15.39
October 21.84 7.43
November 21.72 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.63 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.34 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 22.00 7.02
May 22.57 14.19
June 24.09 19.16
July 24.35 20.92
August 24.33 20.05
September 23.77 15.39
October 21.87 7.43
November 21.74 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.63 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 21.99 7.02
May 22.57 14.19
June 24.09 19.16
July 24.35 20.92
August 24.33 20.05
September 23.77 15.39
October 21.87 7.43
November 21.74 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.63 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.72 -7.7
March 21.78 0.33
April 22.18 7.02
May 22.80 14.19
June 24.12 19.16
July 24.36 20.92
August 24.35 20.05
September 23.96 15.39
October 22.29 7.43
November 21.86 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.74 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.36 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.72 -7.7
March 21.78 0.33
April 22.18 7.02
May 22.81 14.19
June 24.12 19.16
July 24.35 20.92
August 24.35 20.05
September 23.96 15.39
October 22.29 7.43
November 21.86 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.74 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.79 -7.7
March 22.13 0.33
April 22.98 7.02
May 24.24 14.19
June 24.36 19.16
July 24.40 20.92
August 24.40 20.05
September 24.18 15.39
October 23.30 7.43
November 22.39 -0.0
December 21.72 -7.6
     
Annual Sum or Average 23.14 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.85 0.33
April 22.63 7.02
May 24.15 14.19
June 24.36 19.16
July 24.40 20.92
August 24.40 20.05
September 24.05 15.39
October 22.48 7.43
November 22.08 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.97 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.78 -7.7
March 22.09 0.33
April 22.90 7.02
May 24.25 14.19
June 24.36 19.16
July 24.40 20.92
August 24.40 20.05
September 24.18 15.39
October 23.27 7.43
November 22.36 -0.0
December 21.72 -7.6
     
Annual Sum or Average 23.13 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.81 0.33
April 22.52 7.02
May 24.14 14.19
June 24.35 19.16
July 24.40 20.92
August 24.40 20.05
September 24.02 15.39
October 22.32 7.43
November 22.01 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.93 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.87 0.33
April 22.64 7.02
May 24.18 14.19
June 24.38 19.16
July 24.40 20.92
August 24.40 20.05
September 24.15 15.39
October 22.62 7.43
November 22.16 -0.0
December 21.70 -7.6
     
Annual Sum or Average 23.00 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.87 0.33
April 22.63 7.02
May 24.18 14.19
June 24.38 19.16
July 24.40 20.92
August 24.40 20.05
September 24.15 15.39
October 22.61 7.43
November 22.15 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.99 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -12.6
February 21.85 -7.7
March 22.26 0.33
April 23.10 7.02
May 24.29 14.19
June 24.39 19.16
July 24.40 20.92
August 24.40 20.05
September 24.28 15.39
October 23.71 7.43
November 22.50 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.23 6.46
Minimum of Months 21.73 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -12.6
February 21.85 -7.7
March 22.26 0.33
April 23.09 7.02
May 24.30 14.19
June 24.39 19.16
July 24.40 20.92
August 24.40 20.05
September 24.29 15.39
October 23.71 7.43
November 22.50 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.23 6.46
Minimum of Months 21.73 -12.6
Maximum of Months 24.40 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.78 -7.7
March 22.02 0.33
April 22.68 7.02
May 23.83 14.19
June 24.17 19.16
July 24.37 20.92
August 24.34 20.05
September 23.70 15.39
October 22.60 7.43
November 22.04 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.92 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.83 0.33
April 22.46 7.02
May 23.75 14.19
June 24.15 19.16
July 24.37 20.92
August 24.33 20.05
September 23.52 15.39
October 22.15 7.43
November 21.88 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.99 0.33
April 22.65 7.02
May 23.86 14.19
June 24.16 19.16
July 24.37 20.92
August 24.34 20.05
September 23.71 15.39
October 22.59 7.43
November 22.02 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.91 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.79 0.33
April 22.40 7.02
May 23.74 14.19
June 24.12 19.16
July 24.35 20.92
August 24.30 20.05
September 23.48 15.39
October 22.04 7.43
November 21.82 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.77 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.82 0.33
April 22.42 7.02
May 23.78 14.19
June 24.17 19.16
July 24.37 20.92
August 24.33 20.05
September 23.54 15.39
October 22.11 7.43
November 21.88 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.81 0.33
April 22.42 7.02
May 23.78 14.19
June 24.17 19.16
July 24.37 20.92
August 24.33 20.05
September 23.54 15.39
October 22.10 7.43
November 21.87 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.80 -7.7
March 22.07 0.33
April 22.74 7.02
May 23.93 14.19
June 24.22 19.16
July 24.38 20.92
August 24.36 20.05
September 23.80 15.39
October 22.74 7.43
November 22.12 -0.0
December 21.73 -7.6
     
Annual Sum or Average 22.98 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.38 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.80 -7.7
March 22.07 0.33
April 22.74 7.02
May 23.93 14.19
June 24.22 19.16
July 24.38 20.92
August 24.36 20.05
September 23.80 15.39
October 22.75 7.43
November 22.12 -0.0
December 21.73 -7.6
     
Annual Sum or Average 22.98 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.38 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.86 -12.6
February 20.51 -7.7
March 21.70 0.33
April 23.23 7.02
May 25.42 14.19
June 26.33 19.16
July 26.71 20.92
August 26.56 20.05
September 25.20 15.39
October 22.97 7.43
November 21.48 -0.0
December 20.30 -7.6
     
Annual Sum or Average 23.37 6.46
Minimum of Months 19.86 -12.6
Maximum of Months 26.71 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.73 -12.6
February 18.51 -7.7
March 19.92 0.33
April 21.34 7.02
May 23.03 14.19
June 25.31 19.16
July 25.92 20.92
August 25.81 20.05
September 24.80 15.39
October 21.71 7.43
November 19.97 -0.0
December 18.49 -7.6
     
Annual Sum or Average 21.89 6.46
Minimum of Months 17.73 -12.6
Maximum of Months 25.92 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.33 -12.6
February 22.74 -7.7
March 23.42 0.33
April 24.63 7.02
May 26.40 14.19
June 26.85 19.16
July 26.99 20.92
August 26.91 20.05
September 26.46 15.39
October 24.82 7.43
November 23.56 -0.0
December 22.50 -7.6
     
Annual Sum or Average 24.81 6.46
Minimum of Months 22.33 -12.6
Maximum of Months 26.99 20.92



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:30

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.121600E+12 76961.249 31-JAN-18:30 8572.775 26456.413 6938.423 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 32485.309 0.000 0.000 0.000
February 0.110218E+12 76970.897 07-FEB-18:45 8572.775 26456.413 6938.423 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 32494.956 0.000 0.000 0.000
March 0.121358E+12 74884.690 11-MAR-18:45 9689.078 23563.017 6938.423 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 32185.842 0.000 0.000 0.000
April 0.118668E+12 88078.824 15-APR-17:15 8572.775 26456.413 6938.423 0.000 17333.789 0.000 0.000 0.000 0.000 0.000 0.000 28777.424 0.000 0.000 0.000
May 0.125141E+12 83888.992 31-MAY-18:45 9689.078 23563.017 6938.423 0.000 16292.162 0.000 0.000 0.000 0.000 0.000 0.000 27406.313 0.000 0.000 0.000
June 0.131200E+12 89480.823 11-JUN-17:15 8572.775 26456.413 6938.423 0.000 23160.766 0.000 0.000 0.000 0.000 0.000 0.000 24352.447 0.000 0.000 0.000
July 0.138376E+12 85984.775 03-JUL-17:45 8572.775 26456.413 6938.423 0.000 22062.456 0.000 0.000 0.000 0.000 0.000 0.000 21954.708 0.000 0.000 0.000
August 0.135233E+12 89427.871 03-AUG-17:30 8572.775 26456.413 6938.423 0.000 22494.450 0.000 0.000 0.000 0.000 0.000 0.000 24965.810 0.000 0.000 0.000
September 0.121442E+12 87684.981 06-SEP-17:30 8572.775 26456.413 6938.423 0.000 18701.159 0.000 0.000 0.000 0.000 0.000 0.000 27016.212 0.000 0.000 0.000
October 0.116021E+12 72487.951 05-OCT-17:00 8572.775 26456.413 6938.423 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 28012.010 0.000 0.000 0.000
November 0.114052E+12 72821.142 04-NOV-17:30 8572.775 26456.413 6938.423 0.000 1332.098 2508.330 0.000 0.000 0.000 0.000 0.000 27013.103 0.000 0.000 0.000
December 0.119923E+12 74876.893 24-DEC-18:30 8572.775 26456.413 6938.423 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 30400.953 0.000 0.000 0.000
                                     
Annual Sum or Average 0.147323E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.110218E+12 72487.951   8572.775 23563.017 6938.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 21954.708 0.000 0.000 0.000
Maximum of Months 0.138376E+12 89480.823   9689.078 26456.413 6938.423 0.000 23160.766 2508.330 0.000 0.000 0.000 0.000 0.000 32494.956 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:30

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.194007E+12 152595.868 19-JAN-04:00 152595.868 0.000 0.000 0.000 0.000 0.000 152595.868
February 0.131318E+12 155301.196 02-FEB-03:00 155301.196 0.000 0.000 0.000 0.000 0.000 155301.196
March 0.773181E+11 103274.412 06-MAR-07:15 103274.412 0.000 0.000 0.000 0.000 0.000 103274.412
April 0.296365E+11 69604.914 03-APR-00:15 69604.914 0.000 0.000 0.000 0.000 0.000 69604.914
May 0.179981E+10 21911.221 02-MAY-02:00 21911.221 0.000 0.000 0.000 0.000 0.000 21911.221
June 0.622868E+08 3032.335 03-JUN-03:00 3032.335 0.000 0.000 0.000 0.000 0.000 3032.335
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.199763E+10 22414.294 30-SEP-03:00 22414.294 0.000 0.000 0.000 0.000 0.000 22414.294
October 0.173412E+11 34341.624 27-OCT-02:00 34341.624 0.000 0.000 0.000 0.000 0.000 34341.624
November 0.863474E+11 121315.660 26-NOV-03:00 121315.660 0.000 0.000 0.000 0.000 0.000 121315.660
December 0.155886E+12 161934.128 09-DEC-01:00 161934.128 0.000 0.000 0.000 0.000 0.000 161934.128
                     
Annual Sum or Average 0.695713E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.194007E+12 161934.128   161934.128 0.000 0.000 0.000 0.000 0.000 161934.128