Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2018-10-19 09:20:29


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1599.12 510.15 566.27
Net Site Energy 1599.12 510.15 566.27
Total Source Energy 4899.11 1562.91 1734.83
Net Source Energy 4899.11 1562.91 1734.83


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 79.36 0.00 0.00 0.00 0.00
Cooling 163.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.41 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 255.34 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 385.56 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1519.76 79.36 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 79.36 0.00 0.00 0.00 0.00
Cooling General 163.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.41 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 255.34 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 385.56 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.39 0.00 0.00 0.00 0.00 0.00
HVAC 284.68 28.10 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 538.16 28.10 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.21 0.00 0.00 0.00 0.00 0.00
HVAC 256.47 25.32 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 484.83 25.32 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1519.76 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1519.76 100.00
     
Total On-Site and Utility Electric Sources 1519.76 100.00
Total Electricity End Uses 1519.76 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 39.75
Time Setpoint Not Met During Occupied Cooling 0.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 1322.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 20-AUG-17:30 18-JAN-01:15 - - - 01-JAN-07:15
Heating 0.00 42678.60 0.00 0.00 0.00 0.00
Cooling 21666.84 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8096.82 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23202.95 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 87995.81 42678.60 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 42678.60 0.00 0.00 0.00 0.00
Cooling General 21666.84 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 8096.82 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 23202.95 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 86.02 0.00 0.00 0.00
Cooling 516.30 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.82 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 808.67 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1221.08 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4813.09 86.02 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 30.46 0.00 0.00 0.00
Cooling 182.83 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.20 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 286.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 432.40 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1704.37 30.46 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 30.46 0.00 0.00 0.00
Cooling 182.83 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.20 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 286.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 432.40 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1704.37 30.46 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.70 83.70 39.41
Exterior Lighting Total 2508.33           39.41



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3407.97 2721.79 686.18 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3397.93 2713.77 684.16 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8514.37 6800.05 1714.32 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2509.14 2003.94 505.20 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2053.06 1639.69 413.37 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2032.55 1623.31 409.24 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1995.51 1593.73 401.79 0.80 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2026.42 1618.41 408.01 0.80 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9076.89 7249.30 1827.58 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8993.35 7182.59 1810.76 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7471.10 5966.83 1504.27 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7005.45 5594.94 1410.51 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5615.31 4484.70 1130.61 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5580.82 4457.15 1123.67 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5547.64 4430.65 1116.99 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5513.46 4403.35 1110.11 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6157.85 4918.00 1239.85 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5998.02 4790.35 1207.67 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5437.43 4342.63 1094.80 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4852.86 3875.76 977.10 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3869.94 3090.75 779.19 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3838.70 3065.80 772.90 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4376.16 3495.05 881.12 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4387.26 3503.91 883.35 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3246.6 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3237.1 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8111.3 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2390.3 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1955.9 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1936.3 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1901.0 3.13 10.67 11.09 10.38
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1930.5 3.13 10.67 11.09 10.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8647.2 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 8567.6 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7117.4 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6673.8 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5349.5 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5316.6 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5285.0 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5252.4 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5866.3 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5714.1 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5180.0 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4623.1 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3686.7 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3657.0 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4169.0 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4179.6 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1938.43 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1918.34 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   3769.06 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1918.34 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1495.50 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1495.50 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1495.50 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1495.97 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   3799.60 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   3824.72 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   3799.60 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   3824.72 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2990.99 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2990.99 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2990.99 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2990.99 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   3053.00 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   3067.67 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   3053.00 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   3067.67 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2398.91 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2398.91 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2382.27 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2382.27 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.60 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 229.92 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 576.13 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.78 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 138.92 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 137.53 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 135.03 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 137.12 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.55 614.19 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.54 608.54 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 505.54 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.42 474.03 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 379.96 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 377.63 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 375.39 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 373.07 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 416.68 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 405.86 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 367.93 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.37 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.86 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.75 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 296.12 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 296.87 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1801.99 2162.39 0.172 0.206 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
G NW APARTMENT 1796.68 2156.01 0.171 0.205 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
OFFICE 4285.67 5142.81 0.429 0.514 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 28.82 0.00565
G NE APARTMENT 1326.72 1592.07 0.126 0.152 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
G N1 APARTMENT 1085.56 1302.67 0.103 0.124 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 30.34 0.00565
G N2 APARTMENT 1074.72 1289.66 0.102 0.123 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 30.34 0.00565
G S1 APARTMENT 1055.13 1266.16 0.100 0.121 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
G S2 APARTMENT 1071.47 1285.76 0.102 0.122 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 29.84 0.00565
M SW APARTMENT 4799.51 5759.41 0.457 0.548 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
M NW APARTMENT 4755.31 5706.38 0.453 0.543 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
M SE APARTMENT 3950.46 4740.55 0.376 0.451 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.76 0.00565
M NE APARTMENT 3704.19 4445.03 0.353 0.423 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
M N1 APARTMENT 2969.12 3562.94 0.283 0.339 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 30.34 0.00565
M N2 APARTMENT 2950.88 3541.05 0.281 0.337 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 30.34 0.00565
M S1 APARTMENT 2933.34 3520.01 0.279 0.335 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
M S2 APARTMENT 2915.27 3498.32 0.278 0.333 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
T SW APARTMENT 3256.10 3907.32 0.310 0.372 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.48 0.00565
T NW APARTMENT 3171.56 3805.87 0.302 0.362 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
T SE APARTMENT 2875.16 3450.20 0.274 0.328 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
T NE APARTMENT 2566.06 3079.27 0.244 0.293 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
T N1 APARTMENT 2046.26 2455.51 0.195 0.234 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
T N2 APARTMENT 2029.76 2435.72 0.193 0.232 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
T S1 APARTMENT 2313.95 2776.74 0.220 0.264 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565
T S2 APARTMENT 2319.82 2783.78 0.221 0.265 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 969.17 1163.00 0.034 0.041 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
G NW APARTMENT 975.73 1170.88 0.034 0.041 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
OFFICE 2281.41 2737.69 0.077 0.092 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G NE APARTMENT 975.73 1170.88 0.034 0.041 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
G N1 APARTMENT 541.76 650.11 0.019 0.026 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
G N2 APARTMENT 541.76 650.11 0.019 0.026 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
G S1 APARTMENT 536.47 643.76 0.019 0.026 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
G S2 APARTMENT 618.54 742.25 0.022 0.026 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M SW APARTMENT 1920.13 2304.15 0.067 0.081 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M NW APARTMENT 1941.37 2329.64 0.068 0.082 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M SE APARTMENT 1920.13 2304.15 0.067 0.081 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M NE APARTMENT 1941.37 2329.64 0.068 0.082 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M N1 APARTMENT 850.86 1021.03 0.030 0.052 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M N2 APARTMENT 850.86 1021.03 0.030 0.052 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M S1 APARTMENT 831.08 997.30 0.029 0.052 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
M S2 APARTMENT 831.08 997.30 0.029 0.052 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T SW APARTMENT 1935.28 2322.34 0.068 0.081 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T NW APARTMENT 1947.69 2337.23 0.068 0.082 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T SE APARTMENT 1935.28 2322.34 0.068 0.081 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T NE APARTMENT 1947.69 2337.23 0.068 0.082 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T N1 APARTMENT 1382.13 1658.56 0.048 0.058 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T N2 APARTMENT 1382.13 1658.56 0.048 0.058 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T S1 APARTMENT 1368.06 1641.67 0.048 0.057 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234
T S2 APARTMENT 1368.06 1641.67 0.048 0.057 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90 0.00234


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.21 0.21 0.04 0.04
SPLIT GNW 0.21 0.21 0.04 0.04
SPLIT OFFICE 0.51 0.51 0.09 0.09
SPLIT GNE 0.15 0.15 0.04 0.04
SPLIT GN1 0.12 0.12 0.03 0.03
SPLIT GN2 0.12 0.12 0.03 0.03
SPLIT GS1 0.12 0.12 0.03 0.03
SPLIT GS2 0.12 0.12 0.03 0.03
SPLIT MSW 0.55 0.55 0.08 0.08
SPLIT MNW 0.54 0.54 0.08 0.08
SPLIT MSE 0.45 0.45 0.08 0.08
SPLIT MNE 0.42 0.42 0.08 0.08
SPLIT MN1 0.34 0.34 0.05 0.05
SPLIT MN2 0.34 0.34 0.05 0.05
SPLIT MS1 0.34 0.34 0.05 0.05
SPLIT MS2 0.33 0.33 0.05 0.05
SPLIT TSW 0.37 0.37 0.08 0.08
SPLIT TNW 0.36 0.36 0.08 0.08
SPLIT TSE 0.33 0.33 0.08 0.08
SPLIT TNE 0.29 0.29 0.08 0.08
SPLIT TN1 0.23 0.23 0.06 0.06
SPLIT TN2 0.23 0.23 0.06 0.06
SPLIT TS1 0.26 0.26 0.06 0.06
SPLIT TS2 0.27 0.27 0.06 0.06



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2224.25 5597.75 117.75
G NW APARTMENT 2538.25 5810.00 610.50
OFFICE 376.75 1472.25 3.25
G NE APARTMENT 2572.00 5779.75 606.75
G N1 APARTMENT 1894.25 5965.75 249.25
G N2 APARTMENT 1897.50 5964.00 250.00
G S1 APARTMENT 1999.00 5786.00 74.50
G S2 APARTMENT 1959.00 5808.00 84.50
M SW APARTMENT 3008.75 2904.00 0.50
M NW APARTMENT 2825.75 4296.50 11.75
M SE APARTMENT 3019.25 2905.00 1.00
M NE APARTMENT 2836.00 4291.75 12.75
M N1 APARTMENT 2597.75 4352.50 3.25
M N2 APARTMENT 2602.00 4349.75 3.00
M S1 APARTMENT 2826.50 2408.25 3.25
M S2 APARTMENT 2830.75 2422.25 3.25
T SW APARTMENT 3417.75 3957.75 414.75
T NW APARTMENT 3752.00 4773.25 1066.75
T SE APARTMENT 3424.75 3872.75 424.50
T NE APARTMENT 3760.25 4779.75 1069.50
T N1 APARTMENT 3315.25 4904.50 753.50
T N2 APARTMENT 3326.25 4902.50 763.00
T S1 APARTMENT 2978.75 3930.25 183.00
T S2 APARTMENT 2984.25 3927.25 185.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4821.75 6053.00 1322.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 4.25 0.00 4.25 0.00
G NW APARTMENT 6.00 0.25 6.00 0.25
OFFICE 0.75 1.75 0.00 0.00
G NE APARTMENT 8.25 0.00 8.25 0.00
G N1 APARTMENT 3.75 0.00 3.75 0.00
G N2 APARTMENT 3.50 0.00 3.50 0.00
G S1 APARTMENT 0.00 0.00 0.00 0.00
G S2 APARTMENT 0.25 0.00 0.25 0.00
M SW APARTMENT 0.50 0.00 0.50 0.00
M NW APARTMENT 2.50 0.00 2.50 0.00
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 1.25 0.00 1.25 0.00
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.25 0.00 0.25 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.00 0.25 0.00 0.25
T NW APARTMENT 0.00 0.25 0.00 0.25
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 2.75 0.00 2.75 0.00
T N2 APARTMENT 2.25 0.00 2.25 0.00
T S1 APARTMENT 2.75 0.00 2.75 0.00
T S2 APARTMENT 4.00 0.00 4.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 40.50 2.50 39.75 0.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.365 0.097 0.000 0.081
G NW APARTMENT 1.71 2.50 268.97 0.352 0.097 0.000 0.077
OFFICE 0.94 1.00 268.97 0.517 0.100 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.351 0.097 0.000 0.077
G N1 APARTMENT 1.71 2.50 268.97 0.351 0.058 0.000 0.076
G N2 APARTMENT 1.71 2.50 268.97 0.351 0.058 0.000 0.076
G S1 APARTMENT 1.71 2.50 268.97 0.352 0.058 0.000 0.081
G S2 APARTMENT 1.71 2.50 268.97 0.352 0.058 0.000 0.081
M SW APARTMENT 1.71 2.50 268.97 0.353 0.139 0.000 0.100
M NW APARTMENT 1.71 2.50 268.97 0.352 0.139 0.000 0.096
M SE APARTMENT 1.71 2.50 268.97 0.353 0.139 0.000 0.100
M NE APARTMENT 1.71 2.50 268.97 0.352 0.139 0.000 0.096
M N1 APARTMENT 1.71 2.50 268.97 0.352 0.084 0.000 0.096
M N2 APARTMENT 1.71 2.50 268.97 0.352 0.084 0.000 0.096
M S1 APARTMENT 1.71 2.50 268.97 0.353 0.084 0.000 0.100
M S2 APARTMENT 1.71 2.50 268.97 0.353 0.084 0.000 0.100
T SW APARTMENT 1.71 2.50 268.97 0.352 0.184 0.000 0.122
T NW APARTMENT 1.71 2.50 268.97 0.352 0.184 0.000 0.116
T SE APARTMENT 1.71 2.50 268.97 0.352 0.184 0.000 0.122
T NE APARTMENT 1.71 2.50 268.97 0.352 0.184 0.000 0.116
T N1 APARTMENT 1.71 2.50 268.97 0.352 0.111 0.000 0.116
T N2 APARTMENT 1.71 2.50 268.97 0.352 0.111 0.000 0.116
T S1 APARTMENT 1.71 2.50 268.97 0.352 0.111 0.000 0.122
T S2 APARTMENT 1.71 2.50 268.97 0.352 0.111 0.000 0.122
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.355 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.372 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.372 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.375 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.375 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1519.76 21467.12 01-JAN-03:15 87995.81 20-AUG-17:30
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 385.56 0.00 01-JAN-00:15 32443.48 01-JAN-07:45
WaterSystems:Electricity 385.56 0.00 01-JAN-00:15 32443.48 01-JAN-07:45
Water Heater:WaterSystems:Electricity 385.56 0.00 01-JAN-00:15 32443.48 01-JAN-07:45
Fans:Electricity 255.34 8096.82 07-JAN-02:00 8096.82 07-JAN-17:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
ElectricityPurchased:Plant 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
Cogeneration:ElectricityPurchased 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
ElectricityNet:Plant 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
Cogeneration:ElectricityNet 1519.76 21467.12 13-DEC-04:00 87995.81 20-AUG-17:30
ExteriorLights:Electricity 39.41 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.41 0.00 01-JAN-07:30 2508.33 01-JAN-00:15
Electricity:HVAC 418.37 8096.82 07-JAN-02:00 32262.75 28-JUN-16:15
General:Fans:Electricity 255.34 8096.82 07-JAN-02:00 8096.82 07-JAN-17:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 163.03 0.00 01-JAN-00:15 24165.93 28-JUN-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 79.36 0.00 01-JAN-12:30 42678.60 18-JAN-01:15
Gas:HVAC 79.36 0.00 01-JAN-12:30 42678.60 18-JAN-01:15
Heating:Gas 79.36 0.00 01-JAN-12:30 42678.60 18-JAN-01:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1308.61 2739.67 10-NOV-14:15 149303.32 04-JUL-17:15
EnergyTransfer:Building 611.61 1627.68 21-MAY-05:45 65888.42 04-JUL-17:15
EnergyTransfer:Zone:G SW APARTMENT 11.98 0.00 11-MAY-13:15 2129.27 21-JUL-17:15
Heating:EnergyTransfer 31.67 0.00 02-JAN-18:15 22568.40 18-JAN-01:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.79 0.00 01-JAN-00:15 839.45 18-JAN-01:15
Cooling:EnergyTransfer 579.94 334.15 18-JAN-02:00 65888.42 04-JUL-17:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 11.18 0.00 01-JAN-01:45 2129.27 21-JUL-17:15
EnergyTransfer:Zone:G NW APARTMENT 10.21 0.02 03-OCT-10:30 2119.25 04-JUL-17:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 2.19 0.00 01-JAN-12:00 995.74 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 8.02 0.00 01-JAN-00:15 2119.25 04-JUL-17:30
EnergyTransfer:Zone:OFFICE 25.37 0.01 23-OCT-04:00 3442.03 21-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 0.26 0.00 01-JAN-00:15 1300.83 17-JAN-07:15
Cooling:EnergyTransfer:Zone:OFFICE 25.12 0.00 01-JAN-17:15 3442.03 21-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 10.56 0.02 11-MAY-12:30 1506.44 04-JUL-17:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.96 0.00 01-JAN-08:45 1014.31 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 8.60 0.00 01-JAN-00:15 1506.44 04-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 7.81 0.00 19-FEB-14:15 1207.04 04-JUL-18:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.75 0.00 01-JAN-10:15 537.54 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 7.06 0.00 01-JAN-00:15 1207.04 04-JUL-18:15
EnergyTransfer:Zone:G N2 APARTMENT 7.83 0.01 02-OCT-00:45 1193.69 04-JUL-18:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.75 0.00 01-JAN-10:15 539.22 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 7.07 0.00 01-JAN-00:15 1193.69 04-JUL-18:15
EnergyTransfer:Zone:G S1 APARTMENT 10.64 0.03 19-MAY-24:00 1420.65 21-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.13 0.00 01-JAN-00:15 423.33 18-JAN-01:15
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 10.51 0.00 07-JAN-02:45 1420.65 21-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 10.42 0.01 19-MAY-06:45 1408.26 21-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.15 0.00 01-JAN-00:15 447.38 18-JAN-01:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 10.27 0.00 07-JAN-02:30 1408.26 21-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 51.74 0.21 19-JAN-07:45 5709.27 20-SEP-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.07 0.00 01-JAN-00:15 1223.07 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 51.68 0.00 17-JAN-01:30 5709.27 20-SEP-16:15
EnergyTransfer:Zone:M NW APARTMENT 35.89 0.11 24-DEC-16:15 5518.09 04-JUL-17:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.85 0.00 01-JAN-00:15 1816.37 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 35.04 0.00 01-JAN-12:30 5518.09 04-JUL-17:30
EnergyTransfer:Zone:M SE APARTMENT 53.61 3.02 19-JAN-11:15 4761.81 21-SEP-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.08 0.00 01-JAN-00:15 1284.53 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 53.53 0.00 16-JAN-24:00 4761.81 21-SEP-13:30
EnergyTransfer:Zone:M NE APARTMENT 38.16 0.01 18-JAN-10:00 4200.43 04-JUL-17:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.91 0.00 01-JAN-00:15 1952.01 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 37.25 0.00 01-JAN-03:00 4200.43 04-JUL-17:15
EnergyTransfer:Zone:M N1 APARTMENT 32.73 0.24 05-JAN-15:45 3288.89 04-JUL-18:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.07 0.00 01-JAN-00:15 646.34 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 32.66 0.00 01-JAN-14:00 3288.89 04-JUL-18:15
EnergyTransfer:Zone:M N2 APARTMENT 32.78 0.31 28-OCT-13:00 3266.93 04-JUL-18:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.08 0.00 01-JAN-00:15 665.71 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 32.70 0.00 01-JAN-14:00 3266.93 04-JUL-18:15
EnergyTransfer:Zone:M S1 APARTMENT 50.03 4.72 09-NOV-15:45 4134.62 11-OCT-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 50.03 4.72 09-NOV-15:45 4134.62 11-OCT-12:45
EnergyTransfer:Zone:M S2 APARTMENT 50.08 7.42 09-NOV-15:45 4140.94 11-OCT-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 50.08 7.42 09-NOV-15:45 4140.94 11-OCT-12:45
EnergyTransfer:Zone:T SW APARTMENT 25.50 0.01 28-OCT-01:00 3725.97 21-JUL-16:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 2.77 0.00 01-JAN-00:15 1750.24 17-JAN-04:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 22.73 0.00 01-JAN-01:30 3725.97 21-JUL-16:30
EnergyTransfer:Zone:T NW APARTMENT 21.50 0.00 10-MAR-20:30 3696.65 28-JUN-16:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 5.08 0.00 02-JAN-15:15 2007.05 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 16.42 0.00 01-JAN-00:15 3696.65 28-JUN-16:30
EnergyTransfer:Zone:T SE APARTMENT 26.02 0.00 07-JAN-22:45 3332.27 03-SEP-13:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 2.67 0.00 01-JAN-00:15 1765.71 17-JAN-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 23.34 0.00 01-JAN-01:15 3332.27 03-SEP-13:30
EnergyTransfer:Zone:T NE APARTMENT 21.75 0.01 16-MAR-22:45 2964.59 29-JUN-15:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 4.75 0.00 01-JAN-09:30 2055.14 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 17.00 0.00 01-JAN-00:15 2964.59 29-JUN-15:15
EnergyTransfer:Zone:T N1 APARTMENT 16.69 0.00 18-MAY-02:30 2354.84 28-JUN-16:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 2.65 0.00 01-JAN-10:30 1279.97 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 14.04 0.00 01-JAN-00:15 2354.84 28-JUN-16:30
EnergyTransfer:Zone:T N2 APARTMENT 16.75 0.03 30-OCT-21:30 2349.09 29-JUN-15:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 2.67 0.00 01-JAN-10:15 1285.43 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 14.08 0.00 01-JAN-00:15 2349.09 29-JUN-15:15
EnergyTransfer:Zone:T S1 APARTMENT 21.74 0.01 19-NOV-07:00 2811.64 03-SEP-13:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 1.01 0.00 01-JAN-00:15 1109.16 18-JAN-02:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 20.73 0.00 01-JAN-03:00 2811.64 03-SEP-13:30
EnergyTransfer:Zone:T S2 APARTMENT 21.80 0.00 15-JAN-01:00 2819.82 03-SEP-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 1.02 0.00 01-JAN-00:15 1109.71 18-JAN-02:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 20.78 0.00 01-JAN-03:00 2819.82 03-SEP-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 697.00 0.00 16-APR-06:00 83949.43 21-JUL-17:15
HeatingCoils:EnergyTransfer 63.49 0.00 01-JAN-12:30 34142.88 18-JAN-01:15
CoolingCoils:EnergyTransfer 633.52 0.00 01-JAN-00:15 83949.43 21-JUL-17:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.794 -11.184 0.000 0.000 3.751 2.413 12.213 18.684 0.000 0.198 0.000 0.000 -6.427 0.000 -2.941 -17.501
G NW APARTMENT 2.186 -8.024 0.000 0.000 3.797 2.413 12.213 9.420 0.000 0.195 0.000 0.000 -6.532 0.000 -2.814 -12.853
OFFICE 0.259 -25.115 0.000 0.000 0.518 21.914 7.534 19.256 0.000 0.187 0.000 0.000 -6.224 0.000 -2.177 -16.151
G NE APARTMENT 1.962 -8.597 0.000 0.000 3.809 2.413 12.213 9.796 0.000 0.195 0.000 0.000 -6.225 0.000 -2.799 -12.767
G N1 APARTMENT 0.754 -7.059 0.000 0.000 3.812 2.413 12.213 3.135 0.000 0.130 0.000 0.000 -4.010 0.000 -1.918 -9.469
G N2 APARTMENT 0.752 -7.074 0.000 0.000 3.813 2.413 12.213 3.133 0.000 0.130 0.000 0.000 -4.008 0.000 -1.918 -9.453
G S1 APARTMENT 0.130 -10.513 0.000 0.000 3.755 2.413 12.213 12.496 0.000 0.132 0.000 0.000 -3.886 0.000 -2.052 -14.688
G S2 APARTMENT 0.151 -10.274 0.000 0.000 3.756 2.413 12.213 12.498 0.000 0.132 0.001 0.000 -3.879 0.000 -2.053 -14.956
M SW APARTMENT 0.068 -51.676 0.000 0.000 3.586 2.413 12.213 18.133 0.000 0.278 26.484 0.000 -7.201 0.000 -4.297 0.000
M NW APARTMENT 0.853 -35.041 0.000 0.000 3.668 2.413 12.213 8.981 0.000 0.275 18.018 0.000 -7.232 0.000 -4.149 -0.000
M SE APARTMENT 0.085 -53.527 0.000 0.000 3.595 2.413 12.213 18.636 0.000 0.278 27.611 0.000 -7.014 0.000 -4.290 0.000
M NE APARTMENT 0.913 -37.249 0.000 0.000 3.684 2.413 12.213 9.336 0.000 0.275 19.419 0.000 -6.876 0.000 -4.129 -0.001
M N1 APARTMENT 0.070 -32.658 0.000 0.000 3.657 2.413 12.213 2.873 0.000 0.181 18.635 0.000 -4.521 0.000 -2.863 0.000
M N2 APARTMENT 0.079 -32.698 0.000 0.000 3.658 2.413 12.213 2.873 0.000 0.181 18.660 0.000 -4.517 0.000 -2.862 0.000
M S1 APARTMENT 0.000 -50.031 0.000 0.000 3.560 2.413 12.213 12.142 0.000 0.184 26.880 0.000 -4.385 0.000 -2.977 0.000
M S2 APARTMENT 0.000 -50.075 0.000 0.000 3.561 2.413 12.213 12.142 0.000 0.184 26.922 0.000 -4.384 0.000 -2.976 0.000
T SW APARTMENT 2.770 -22.733 0.000 0.000 3.692 2.413 12.213 18.019 0.000 0.376 0.000 0.000 -6.703 0.000 -5.351 -4.696
T NW APARTMENT 5.076 -16.424 0.000 0.000 3.737 2.413 12.213 8.886 0.000 0.370 0.000 0.000 -6.784 0.000 -5.197 -4.291
T SE APARTMENT 2.675 -23.344 0.000 0.000 3.699 2.413 12.213 18.526 0.000 0.376 0.000 0.000 -6.542 0.000 -5.351 -4.665
T NE APARTMENT 4.748 -17.003 0.000 0.000 3.751 2.413 12.213 9.280 0.000 0.370 0.000 0.000 -6.485 0.000 -5.181 -4.105
T N1 APARTMENT 2.647 -14.041 0.000 0.000 3.742 2.413 12.213 2.862 0.000 0.247 0.000 0.000 -4.196 0.000 -3.517 -2.371
T N2 APARTMENT 2.665 -14.083 0.000 0.000 3.743 2.413 12.213 2.859 0.000 0.247 0.000 0.000 -4.193 0.000 -3.517 -2.348
T S1 APARTMENT 1.011 -20.729 0.000 0.000 3.679 2.413 12.213 12.093 0.000 0.253 0.000 0.000 -4.088 0.000 -3.657 -3.188
T S2 APARTMENT 1.019 -20.781 0.000 0.000 3.680 2.413 12.213 12.090 0.000 0.253 0.000 0.000 -4.086 0.000 -3.657 -3.143
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.174 0.000 0.020 0.000 0.000 -0.762 0.000 -0.827 -15.675
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.620 0.000 0.750 0.000 0.000 -1.982 0.000 -14.641 -8.081
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.177 0.000 0.019 0.000 0.000 -0.854 0.000 -0.688 -15.724
Total Facility 31.667 -579.935 0.000 0.000 85.705 128.627 294.692 259.121 0.000 6.415 182.631 0.000 -133.995 0.000 -98.801 -176.127


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 21-JUL-17:06 0.00 -2130.85 0.00 0.00 141.81 194.45 588.62 2121.88 0.00 71.14 0.00 0.00 0.00 0.00 0.00 -987.05
G NW APARTMENT 04-JUL-17:23 0.00 -2119.52 0.00 0.00 141.80 194.45 588.62 2243.83 0.00 140.74 0.00 0.00 0.00 0.00 0.00 -1189.93
OFFICE 21-SEP-13:30 0.00 -3442.15 0.00 0.00 67.31 1622.34 544.92 2187.09 0.00 22.85 0.00 0.00 0.00 0.00 0.00 -1002.35
G NE APARTMENT 04-JUL-17:08 0.00 -1507.13 0.00 0.00 141.81 194.45 588.62 748.60 0.00 157.79 0.00 0.00 0.00 0.00 0.00 -324.14
G N1 APARTMENT 04-JUL-18:15 0.00 -1206.91 0.00 0.00 141.81 230.46 547.42 628.00 0.00 60.79 0.00 0.00 0.00 0.00 0.00 -401.57
G N2 APARTMENT 04-JUL-18:15 0.00 -1193.56 0.00 0.00 141.81 230.46 547.42 628.21 0.00 60.79 0.00 0.00 0.00 0.00 0.00 -415.13
G S1 APARTMENT 21-SEP-13:30 0.00 -1420.66 0.00 0.00 40.75 28.81 382.60 1936.85 0.00 12.71 0.00 0.00 0.00 0.00 0.00 -981.06
G S2 APARTMENT 21-SEP-13:30 0.00 -1408.27 0.00 0.00 40.75 28.81 382.60 1937.03 0.00 12.71 0.00 0.00 0.00 0.00 0.00 -993.63
M SW APARTMENT 20-SEP-16:10 0.00 -5709.91 0.00 0.00 84.76 144.04 588.62 2383.44 0.00 34.72 2474.33 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 04-JUL-17:23 0.00 -5518.19 0.00 0.00 141.80 194.45 588.62 2228.06 0.00 201.88 2163.37 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 21-SEP-13:30 0.00 -4761.86 0.00 0.00 40.75 28.81 382.60 2162.42 0.00 30.17 2117.10 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 04-JUL-17:08 0.00 -4201.61 0.00 0.00 141.81 194.45 588.62 739.73 0.00 226.36 2310.64 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 04-JUL-18:15 0.00 -3288.56 0.00 0.00 141.81 230.46 547.42 619.66 0.00 87.17 1662.05 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 04-JUL-18:15 0.00 -3266.60 0.00 0.00 141.81 230.46 547.42 619.79 0.00 87.17 1639.95 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 11-OCT-12:45 0.00 -4132.29 0.00 0.00 40.75 28.81 388.49 2063.35 0.00 259.61 1351.27 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 11-OCT-12:45 0.00 -4138.61 0.00 0.00 40.75 28.81 388.49 2063.31 0.00 259.62 1357.63 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 21-JUL-16:23 0.00 -3725.70 0.00 0.00 84.76 144.04 588.62 2207.44 0.00 162.27 538.57 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 28-JUN-16:23 0.00 -3696.40 0.00 0.00 84.76 144.04 588.62 2348.21 0.00 139.00 391.78 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 03-SEP-13:30 0.00 -3332.28 0.00 0.00 40.75 28.81 382.60 2138.08 0.00 88.68 653.36 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 29-JUN-15:15 0.00 -2963.84 0.00 0.00 48.90 100.83 470.90 990.43 0.00 267.51 1085.28 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 28-JUN-16:23 0.00 -2354.70 0.00 0.00 84.76 144.04 588.62 511.23 0.00 83.84 942.20 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-15:15 0.00 -2348.51 0.00 0.00 48.90 100.83 470.90 604.52 0.00 161.36 962.00 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 03-SEP-13:30 0.00 -2811.65 0.00 0.00 40.75 28.81 382.60 1786.99 0.00 53.49 519.01 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 03-SEP-13:30 0.00 -2819.83 0.00 0.00 40.75 28.81 382.60 1786.86 0.00 53.49 527.32 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-JUL-17:08 0.00 -65892.68 0.00 0.00 3261.56 6475.86 14071.03 21752.31 0.00 4748.75 15583.17 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 16-JAN-07:01 1638.61 0.00 0.00 0.00 163.25 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -488.85 0.00 -162.39 -1626.85
G NW APARTMENT 14-DEC-04:00 995.60 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -642.36 0.00 -653.32 -127.67
OFFICE 11-JAN-07:01 3426.25 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -548.84 0.00 -266.90 -3185.08
G NE APARTMENT 17-NOV-07:01 1026.05 0.00 0.00 0.00 161.40 93.63 382.60 497.27 0.00 0.00 0.00 0.00 0.00 0.00 -16.39 -2144.56
G N1 APARTMENT 01-MAR-07:01 1078.19 0.00 0.00 0.00 161.39 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -226.42 0.00 -56.05 -1433.34
G N2 APARTMENT 22-FEB-07:01 1070.60 0.00 0.00 0.00 161.38 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -294.16 0.00 -79.10 -1334.96
G S1 APARTMENT 20-JAN-07:10 831.96 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -385.52 0.00 -11.53 -1072.35
G S2 APARTMENT 10-DEC-07:01 1004.71 0.00 0.00 0.00 161.41 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -371.83 0.00 -58.31 -1212.22
M SW APARTMENT 18-JAN-01:15 1222.99 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -664.63 0.00 -619.49 -384.28
M NW APARTMENT 14-DEC-04:00 1816.10 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -669.72 0.00 -939.69 -634.44
M SE APARTMENT 18-JAN-01:15 1284.43 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -673.65 0.00 -619.49 -436.71
M NE APARTMENT 14-DEC-04:00 1951.69 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -656.86 0.00 -939.69 -782.89
M N1 APARTMENT 04-FEB-07:15 1654.36 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -445.08 0.00 -223.36 -1623.37
M N2 APARTMENT 22-DEC-06:08 1365.10 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -444.79 0.00 -183.65 -1345.02
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 17-JAN-04:00 1750.21 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -653.88 0.00 -827.61 -696.48
T NW APARTMENT 14-DEC-04:00 2006.75 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -643.92 0.00 -1245.08 -545.50
T SE APARTMENT 17-JAN-04:00 1765.68 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -665.03 0.00 -827.61 -700.80
T NE APARTMENT 14-DEC-04:00 2054.80 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -632.78 0.00 -1245.08 -604.70
T N1 APARTMENT 14-DEC-04:00 1279.79 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -390.05 0.00 -751.03 -566.46
T N2 APARTMENT 14-DEC-04:00 1285.25 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -389.95 0.00 -751.03 -572.03
T S1 APARTMENT 02-DEC-07:01 1431.87 0.00 0.00 0.00 162.66 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -329.86 0.00 -83.97 -1656.93
T S2 APARTMENT 25-MAR-06:01 1692.66 0.00 0.00 0.00 162.95 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -349.40 0.00 -164.70 -1817.73
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 18-JAN-01:15 22198.29 0.00 0.00 0.00 4362.43 2334.74 5719.80 0.00 0.00 0.00 0.00 0.00 -12826.04 0.00 -12282.44 -9506.79



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Sec1.1A-General Information

Data
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 39.75
Number of hours cooling loads not met 0.75
Number of hours not met 40.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.41 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 79.36 42678.60 0.00 0.00
Space Cooling 163.03 21666.84 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 255.34 8096.82 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 385.56 23202.95 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1519.76   79.36   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1519.76
Natural Gas 0.00 79.36
Additional 0.00 0.00
Total 511.42 1599.12


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 52.01
Fans-Interior 81.46
Service Water Heating 123.00
Receptacle Equipment 163.15
Miscellaneous 12.57
Subtotal 484.83


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 25.32
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 25.32


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.32
Space Heating 4.96
Space Cooling 10.19
Fans-Interior 15.97
Service Water Heating 24.11
Receptacle Equipment 31.98
Miscellaneous 2.46



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.205876
G NW APARTMENT DIRECT AIR 0.205269
OFFICE DIRECT AIR 0.514353
G NE APARTMENT DIRECT AIR 0.151577
G N1 APARTMENT DIRECT AIR 0.124026
G N2 APARTMENT DIRECT AIR 0.122786
G S1 APARTMENT DIRECT AIR 0.120549
G S2 APARTMENT DIRECT AIR 0.122416
M SW APARTMENT DIRECT AIR 0.548335
M NW APARTMENT DIRECT AIR 0.543288
M SE APARTMENT DIRECT AIR 0.451329
M NE APARTMENT DIRECT AIR 0.423199
M N1 APARTMENT DIRECT AIR 0.339221
M N2 APARTMENT DIRECT AIR 0.337137
M S1 APARTMENT DIRECT AIR 0.335133
M S2 APARTMENT DIRECT AIR 0.333068
T SW APARTMENT DIRECT AIR 0.371996
T NW APARTMENT DIRECT AIR 0.362340
T SE APARTMENT DIRECT AIR 0.328475
T NE APARTMENT DIRECT AIR 0.293161
T N1 APARTMENT DIRECT AIR 0.233783
T N2 APARTMENT DIRECT AIR 0.231896
T S1 APARTMENT DIRECT AIR 0.264364
T S2 APARTMENT DIRECT AIR 0.265034


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.205876
SPLIT GNW MAIN BRANCH 0.205269
SPLIT OFFICE MAIN BRANCH 0.514353
SPLIT GNE MAIN BRANCH 0.151577
SPLIT GN1 MAIN BRANCH 0.124026
SPLIT GN2 MAIN BRANCH 0.122786
SPLIT GS1 MAIN BRANCH 0.120549
SPLIT GS2 MAIN BRANCH 0.122416
SPLIT MSW MAIN BRANCH 0.548335
SPLIT MNW MAIN BRANCH 0.543288
SPLIT MSE MAIN BRANCH 0.451329
SPLIT MNE MAIN BRANCH 0.423199
SPLIT MN1 MAIN BRANCH 0.339221
SPLIT MN2 MAIN BRANCH 0.337137
SPLIT MS1 MAIN BRANCH 0.335133
SPLIT MS2 MAIN BRANCH 0.333068
SPLIT TSW MAIN BRANCH 0.371996
SPLIT TNW MAIN BRANCH 0.362340
SPLIT TSE MAIN BRANCH 0.328475
SPLIT TNE MAIN BRANCH 0.293161
SPLIT TN1 MAIN BRANCH 0.233783
SPLIT TN2 MAIN BRANCH 0.231896
SPLIT TS1 MAIN BRANCH 0.264364
SPLIT TS2 MAIN BRANCH 0.265034


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.205876
SPLIT GNW 0.205269
SPLIT OFFICE 0.514353
SPLIT GNE 0.151577
SPLIT GN1 0.124026
SPLIT GN2 0.122786
SPLIT GS1 0.120549
SPLIT GS2 0.122416
SPLIT MSW 0.548335
SPLIT MNW 0.543288
SPLIT MSE 0.451329
SPLIT MNE 0.423199
SPLIT MN1 0.339221
SPLIT MN2 0.337137
SPLIT MS1 0.335133
SPLIT MS2 0.333068
SPLIT TSW 0.371996
SPLIT TNW 0.362340
SPLIT TSE 0.328475
SPLIT TNE 0.293161
SPLIT TN1 0.233783
SPLIT TN2 0.231896
SPLIT TS1 0.264364
SPLIT TS2 0.265034


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.205876 0.026898
SPLIT GNW OA CONTROLLER 0.205269 0.025953
SPLIT OFFICE OA CONTROLLER 0.514353 0.038104
SPLIT GNE OA CONTROLLER 0.151577 0.025953
SPLIT GN1 OA CONTROLLER 0.124026 0.025953
SPLIT GN2 OA CONTROLLER 0.122786 0.025953
SPLIT GS1 OA CONTROLLER 0.120549 0.025953
SPLIT GS2 OA CONTROLLER 0.122416 0.025953
SPLIT MSW OA CONTROLLER 0.548335 0.051906
SPLIT MNW OA CONTROLLER 0.543288 0.051906
SPLIT MSE OA CONTROLLER 0.451329 0.051906
SPLIT MNE OA CONTROLLER 0.423199 0.051906
SPLIT MN1 OA CONTROLLER 0.339221 0.051906
SPLIT MN2 OA CONTROLLER 0.337137 0.051906
SPLIT MS1 OA CONTROLLER 0.335133 0.051906
SPLIT MS2 OA CONTROLLER 0.333068 0.051906
SPLIT TSW OA CONTROLLER 0.371996 0.025953
SPLIT TNW OA CONTROLLER 0.362340 0.025953
SPLIT TSE OA CONTROLLER 0.328475 0.025953
SPLIT TNE OA CONTROLLER 0.293161 0.025953
SPLIT TN1 OA CONTROLLER 0.233783 0.025953
SPLIT TN2 OA CONTROLLER 0.231896 0.025953
SPLIT TS1 OA CONTROLLER 0.264364 0.025953
SPLIT TS2 OA CONTROLLER 0.265034 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.205876 3407.97 0.798655
SPLIT GNW COOLING COIL 0.205269 3397.93 0.798655
SPLIT OFFICE COOLING COIL 0.514353 8514.37 0.798655
SPLIT GNE COOLING COIL 0.151577 2509.14 0.798655
SPLIT GN1 COOLING COIL 0.124026 2053.06 0.798655
SPLIT GN2 COOLING COIL 0.122786 2032.55 0.798655
SPLIT GS1 COOLING COIL 0.120549 1995.51 0.798655
SPLIT GS2 COOLING COIL 0.122416 2026.42 0.798655
SPLIT MSW COOLING COIL 0.548335 9076.89 0.798655
SPLIT MNW COOLING COIL 0.543288 8993.35 0.798655
SPLIT MSE COOLING COIL 0.451329 7471.10 0.798655
SPLIT MNE COOLING COIL 0.423199 7005.45 0.798655
SPLIT MN1 COOLING COIL 0.339221 5615.31 0.798655
SPLIT MN2 COOLING COIL 0.337137 5580.82 0.798655
SPLIT MS1 COOLING COIL 0.335133 5547.64 0.798655
SPLIT MS2 COOLING COIL 0.333068 5513.46 0.798655
SPLIT TSW COOLING COIL 0.371996 6157.85 0.798655
SPLIT TNW COOLING COIL 0.362340 5998.02 0.798655
SPLIT TSE COOLING COIL 0.328475 5437.43 0.798655
SPLIT TNE COOLING COIL 0.293161 4852.86 0.798655
SPLIT TN1 COOLING COIL 0.233783 3869.94 0.798655
SPLIT TN2 COOLING COIL 0.231896 3838.70 0.798655
SPLIT TS1 COOLING COIL 0.264364 4376.16 0.798655
SPLIT TS2 COOLING COIL 0.265034 4387.26 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.205876 0.205876 0.205876 0.205876 1938.43 3407.97 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.205269 0.205269 0.205269 0.205269 1918.34 3397.93 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.514353 0.514353 0.514353 0.514353 3769.06 8514.37 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.151577 0.151577 0.151577 0.151577 1918.34 2509.14 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.124026 0.124026 0.124026 0.124026 1495.50 2053.06 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.122786 0.122786 0.122786 0.122786 1495.50 2032.55 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.120549 0.120549 0.120549 0.120549 1495.50 1995.51 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.122416 0.122416 0.122416 0.122416 1495.97 2026.42 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.548335 0.548335 0.548335 0.548335 3799.60 9076.89 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.543288 0.543288 0.543288 0.543288 3824.72 8993.35 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.451329 0.451329 0.451329 0.451329 3799.60 7471.10 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.423199 0.423199 0.423199 0.423199 3824.72 7005.45 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.339221 0.339221 0.339221 0.339221 2990.99 5615.31 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.337137 0.337137 0.337137 0.337137 2990.99 5580.82 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.335133 0.335133 0.335133 0.335133 2990.99 5547.64 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.333068 0.333068 0.333068 0.333068 2990.99 5513.46 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.371996 0.371996 0.371996 0.371996 3053.00 6157.85 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.362340 0.362340 0.362340 0.362340 3067.67 5998.02 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.328475 0.328475 0.328475 0.328475 3053.00 5437.43 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.293161 0.293161 0.293161 0.293161 3067.67 4852.86 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.233783 0.233783 0.233783 0.233783 2398.91 3869.94 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.231896 0.231896 0.231896 0.231896 2398.91 3838.70 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.264364 0.264364 0.264364 0.264364 2382.27 4376.16 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.265034 0.265034 0.265034 0.265034 2382.27 4387.26 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.205876
SPLIT GNW SUPPLY FAN 0.205269
SPLIT OFFICE SUPPLY FAN 0.514353
SPLIT GNE SUPPLY FAN 0.151577
SPLIT GN1 SUPPLY FAN 0.124026
SPLIT GN2 SUPPLY FAN 0.122786
SPLIT GS1 SUPPLY FAN 0.120549
SPLIT GS2 SUPPLY FAN 0.122416
SPLIT MSW SUPPLY FAN 0.548335
SPLIT MNW SUPPLY FAN 0.543288
SPLIT MSE SUPPLY FAN 0.451329
SPLIT MNE SUPPLY FAN 0.423199
SPLIT MN1 SUPPLY FAN 0.339221
SPLIT MN2 SUPPLY FAN 0.337137
SPLIT MS1 SUPPLY FAN 0.335133
SPLIT MS2 SUPPLY FAN 0.333068
SPLIT TSW SUPPLY FAN 0.371996
SPLIT TNW SUPPLY FAN 0.362340
SPLIT TSE SUPPLY FAN 0.328475
SPLIT TNE SUPPLY FAN 0.293161
SPLIT TN1 SUPPLY FAN 0.233783
SPLIT TN2 SUPPLY FAN 0.231896
SPLIT TS1 SUPPLY FAN 0.264364
SPLIT TS2 SUPPLY FAN 0.265034


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1938.43
SPLIT GNW HEATING COIL 1918.34
SPLIT OFFICE HEATING COIL 3769.06
SPLIT GNE HEATING COIL 1918.34
SPLIT GN1 HEATING COIL 1495.50
SPLIT GN2 HEATING COIL 1495.50
SPLIT GS1 HEATING COIL 1495.50
SPLIT GS2 HEATING COIL 1495.97
SPLIT MSW HEATING COIL 3799.60
SPLIT MNW HEATING COIL 3824.72
SPLIT MSE HEATING COIL 3799.60
SPLIT MNE HEATING COIL 3824.72
SPLIT MN1 HEATING COIL 2990.99
SPLIT MN2 HEATING COIL 2990.99
SPLIT MS1 HEATING COIL 2990.99
SPLIT MS2 HEATING COIL 2990.99
SPLIT TSW HEATING COIL 3053.00
SPLIT TNW HEATING COIL 3067.67
SPLIT TSE HEATING COIL 3053.00
SPLIT TNE HEATING COIL 3067.67
SPLIT TN1 HEATING COIL 2398.91
SPLIT TN2 HEATING COIL 2398.91
SPLIT TS1 HEATING COIL 2382.27
SPLIT TS2 HEATING COIL 2382.27



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:29

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.32 2.60
February 22.46 4.29
March 22.69 8.77
April 23.41 13.91
May 23.80 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.71 13.71
November 22.85 6.96
December 22.32 2.07
     
Annual Sum or Average 23.43 13.68
Minimum of Months 22.32 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 2.60
February 21.91 4.29
March 22.23 8.77
April 23.15 13.91
May 23.77 17.82
June 24.37 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.28 13.71
November 22.06 6.96
December 21.75 2.07
     
Annual Sum or Average 23.13 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 2.60
February 22.33 4.29
March 22.98 8.77
April 23.61 13.91
May 23.81 17.82
June 23.90 23.21
July 23.90 25.63
August 23.90 24.08
September 23.90 20.49
October 23.66 13.71
November 22.96 6.96
December 22.07 2.07
     
Annual Sum or Average 23.26 13.68
Minimum of Months 22.02 2.07
Maximum of Months 23.90 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 2.60
February 21.82 4.29
March 22.15 8.77
April 23.15 13.91
May 23.75 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.20 13.71
November 21.93 6.96
December 21.70 2.07
     
Annual Sum or Average 23.09 13.68
Minimum of Months 21.70 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 2.60
February 21.81 4.29
March 22.05 8.77
April 22.89 13.91
May 23.60 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.13 13.71
November 21.95 6.96
December 21.71 2.07
     
Annual Sum or Average 23.04 13.68
Minimum of Months 21.71 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 2.60
February 21.81 4.29
March 22.05 8.77
April 22.89 13.91
May 23.60 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.13 13.71
November 21.95 6.96
December 21.71 2.07
     
Annual Sum or Average 23.04 13.68
Minimum of Months 21.71 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.36 2.60
February 22.46 4.29
March 22.63 8.77
April 23.28 13.91
May 23.67 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.73 13.71
November 22.91 6.96
December 22.37 2.07
     
Annual Sum or Average 23.42 13.68
Minimum of Months 22.36 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.35 2.60
February 22.46 4.29
March 22.64 8.77
April 23.28 13.91
May 23.67 17.82
June 24.35 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.73 13.71
November 22.91 6.96
December 22.36 2.07
     
Annual Sum or Average 23.42 13.68
Minimum of Months 22.35 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.47 2.60
February 23.70 4.29
March 24.14 8.77
April 24.36 13.91
May 24.38 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.31 13.71
November 24.17 6.96
December 23.55 2.07
     
Annual Sum or Average 24.14 13.68
Minimum of Months 23.47 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 2.60
February 22.68 4.29
March 23.79 8.77
April 24.32 13.91
May 24.38 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.19 13.71
November 23.52 6.96
December 22.09 2.07
     
Annual Sum or Average 23.73 13.68
Minimum of Months 22.09 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 2.60
February 23.62 4.29
March 24.11 8.77
April 24.35 13.91
May 24.39 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.30 13.71
November 24.12 6.96
December 23.47 2.07
     
Annual Sum or Average 24.11 13.68
Minimum of Months 23.39 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.09 2.60
February 22.49 4.29
March 23.74 8.77
April 24.31 13.91
May 24.38 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.16 13.71
November 23.35 6.96
December 21.93 2.07
     
Annual Sum or Average 23.68 13.68
Minimum of Months 21.93 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.23 2.60
February 22.75 4.29
March 23.93 8.77
April 24.34 13.91
May 24.39 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.25 13.71
November 23.68 6.96
December 22.12 2.07
     
Annual Sum or Average 23.78 13.68
Minimum of Months 22.12 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 2.60
February 22.73 4.29
March 23.92 8.77
April 24.34 13.91
May 24.39 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.25 13.71
November 23.66 6.96
December 22.10 2.07
     
Annual Sum or Average 23.77 13.68
Minimum of Months 22.10 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.73 2.60
February 23.97 4.29
March 24.26 8.77
April 24.38 13.91
May 24.39 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.35 13.71
November 24.29 6.96
December 23.89 2.07
     
Annual Sum or Average 24.24 13.68
Minimum of Months 23.73 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.73 2.60
February 23.96 4.29
March 24.26 8.77
April 24.38 13.91
May 24.39 17.82
June 24.40 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.35 13.71
November 24.29 6.96
December 23.88 2.07
     
Annual Sum or Average 24.24 13.68
Minimum of Months 23.73 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.68 2.60
February 22.89 4.29
March 23.24 8.77
April 23.97 13.91
May 24.24 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.92 13.71
November 23.25 6.96
December 22.71 2.07
     
Annual Sum or Average 23.71 13.68
Minimum of Months 22.68 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.07 2.60
February 22.35 4.29
March 22.93 8.77
April 23.86 13.91
May 24.23 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.70 13.71
November 22.62 6.96
December 21.93 2.07
     
Annual Sum or Average 23.44 13.68
Minimum of Months 21.93 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.66 2.60
February 22.89 4.29
March 23.25 8.77
April 23.98 13.91
May 24.25 17.82
June 24.37 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.91 13.71
November 23.24 6.96
December 22.72 2.07
     
Annual Sum or Average 23.71 13.68
Minimum of Months 22.66 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.96 2.60
February 22.26 4.29
March 22.94 8.77
April 23.88 13.91
May 24.22 17.82
June 24.37 23.21
July 24.40 25.63
August 24.40 24.08
September 24.38 20.49
October 23.68 13.71
November 22.49 6.96
December 21.80 2.07
     
Annual Sum or Average 23.40 13.68
Minimum of Months 21.80 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 2.60
February 22.24 4.29
March 22.92 8.77
April 23.87 13.91
May 24.24 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.70 13.71
November 22.50 6.96
December 21.81 2.07
     
Annual Sum or Average 23.40 13.68
Minimum of Months 21.81 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 2.60
February 22.24 4.29
March 22.92 8.77
April 23.87 13.91
May 24.24 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.39 20.49
October 23.70 13.71
November 22.49 6.96
December 21.80 2.07
     
Annual Sum or Average 23.40 13.68
Minimum of Months 21.80 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 2.60
February 22.98 4.29
March 23.36 8.77
April 24.03 13.91
May 24.27 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.99 13.71
November 23.36 6.96
December 22.81 2.07
     
Annual Sum or Average 23.77 13.68
Minimum of Months 22.76 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 2.60
February 22.98 4.29
March 23.36 8.77
April 24.03 13.91
May 24.27 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 23.99 13.71
November 23.36 6.96
December 22.81 2.07
     
Annual Sum or Average 23.77 13.68
Minimum of Months 22.76 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.51 2.60
February 23.02 4.29
March 24.02 8.77
April 25.44 13.91
May 26.14 17.82
June 26.88 23.21
July 27.23 25.63
August 27.12 24.08
September 26.63 20.49
October 25.26 13.71
November 23.60 6.96
December 22.40 2.07
     
Annual Sum or Average 25.03 13.68
Minimum of Months 22.40 2.07
Maximum of Months 27.23 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 2.60
February 21.41 4.29
March 22.26 8.77
April 23.41 13.91
May 24.22 17.82
June 26.20 23.21
July 26.72 25.63
August 26.56 24.08
September 26.08 20.49
October 23.80 13.71
November 22.09 6.96
December 21.00 2.07
     
Annual Sum or Average 23.74 13.68
Minimum of Months 21.00 2.07
Maximum of Months 26.72 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:29

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.69 2.60
February 25.10 4.29
March 26.01 8.77
April 26.63 13.91
May 26.79 17.82
June 27.05 23.21
July 27.17 25.63
August 27.14 24.08
September 26.99 20.49
October 26.57 13.71
November 25.88 6.96
December 24.68 2.07
     
Annual Sum or Average 26.23 13.68
Minimum of Months 24.68 2.07
Maximum of Months 27.17 25.63



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:29

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.121780E+12 77947.251 01-JAN-18:15 8572.775 26456.413 8096.825 0.000 1952.177 2508.330 0.000 0.000 0.000 0.000 0.000 30360.731 0.000 0.000 0.000
February 0.110571E+12 76538.522 13-FEB-18:30 8572.775 26456.413 8096.825 0.000 4625.361 2508.330 0.000 0.000 0.000 0.000 0.000 26278.819 0.000 0.000 0.000
March 0.122817E+12 76883.433 07-MAR-18:00 8572.775 26456.413 8096.825 0.000 4573.492 2508.330 0.000 0.000 0.000 0.000 0.000 26675.599 0.000 0.000 0.000
April 0.122772E+12 79063.449 13-APR-17:45 8572.775 26456.413 8096.825 0.000 12626.408 0.000 0.000 0.000 0.000 0.000 0.000 23311.028 0.000 0.000 0.000
May 0.129156E+12 85666.575 15-MAY-17:45 8572.775 26456.413 8096.825 0.000 15471.399 0.000 0.000 0.000 0.000 0.000 0.000 27069.163 0.000 0.000 0.000
June 0.133879E+12 85738.739 28-JUN-17:15 8572.775 26456.413 8096.825 0.000 23234.149 0.000 0.000 0.000 0.000 0.000 0.000 19378.577 0.000 0.000 0.000
July 0.144076E+12 85971.598 21-JUL-17:30 8572.775 26456.413 8096.825 0.000 23571.567 0.000 0.000 0.000 0.000 0.000 0.000 19274.018 0.000 0.000 0.000
August 0.141423E+12 87995.807 20-AUG-17:30 8572.775 26456.413 8096.825 0.000 21666.844 0.000 0.000 0.000 0.000 0.000 0.000 23202.951 0.000 0.000 0.000
September 0.130392E+12 83719.169 02-SEP-17:45 8572.775 26456.413 8096.825 0.000 17314.244 0.000 0.000 0.000 0.000 0.000 0.000 23278.912 0.000 0.000 0.000
October 0.125748E+12 81282.467 05-OCT-17:45 8572.775 26456.413 8096.825 0.000 12302.018 2508.330 0.000 0.000 0.000 0.000 0.000 23346.107 0.000 0.000 0.000
November 0.116763E+12 73748.722 30-NOV-18:45 8572.775 26456.413 8096.825 0.000 1448.687 2508.330 0.000 0.000 0.000 0.000 0.000 26665.692 0.000 0.000 0.000
December 0.120386E+12 75394.089 17-DEC-18:15 8572.775 26456.413 8096.825 0.000 1664.582 2508.330 0.000 0.000 0.000 0.000 0.000 28095.164 0.000 0.000 0.000
                                     
Annual Sum or Average 0.151976E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.110571E+12 73748.722   8572.775 26456.413 8096.825 0.000 1448.687 0.000 0.000 0.000 0.000 0.000 0.000 19274.018 0.000 0.000 0.000
Maximum of Months 0.144076E+12 87995.807   8572.775 26456.413 8096.825 0.000 23571.567 2508.330 0.000 0.000 0.000 0.000 0.000 30360.731 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:29

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.245242E+11 42678.597 18-JAN-01:15 42678.597 0.000 0.000 0.000 0.000 0.000 42678.597
February 0.163179E+11 41162.252 06-FEB-04:00 41162.252 0.000 0.000 0.000 0.000 0.000 41162.252
March 0.525124E+10 20037.465 04-MAR-04:00 20037.465 0.000 0.000 0.000 0.000 0.000 20037.465
April 0.616234E+09 8970.924 08-APR-02:00 8970.924 0.000 0.000 0.000 0.000 0.000 8970.924
May 0.775585E+08 2847.439 05-MAY-04:00 2847.439 0.000 0.000 0.000 0.000 0.000 2847.439
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.156829E+10 18418.290 26-OCT-03:00 18418.290 0.000 0.000 0.000 0.000 0.000 18418.290
November 0.664624E+10 21795.054 28-NOV-04:00 21795.054 0.000 0.000 0.000 0.000 0.000 21795.054
December 0.243555E+11 36248.454 22-DEC-06:00 36248.454 0.000 0.000 0.000 0.000 0.000 36248.454
                     
Annual Sum or Average 0.793572E+11       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.245242E+11 42678.597   42678.597 0.000 0.000 0.000 0.000 0.000 42678.597