Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2018-10-19 09:20:28


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1579.69 503.95 559.38
Net Site Energy 1579.69 503.95 559.38
Total Source Energy 4778.96 1524.58 1692.28
Net Source Energy 4778.96 1524.58 1692.28


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 107.49 0.00 0.00 0.00 0.00
Cooling 188.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 205.66 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 362.28 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1472.19 107.49 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 107.49 0.00 0.00 0.00 0.00
Cooling General 188.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 205.66 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 362.28 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.41 0.00 0.00 0.00 0.00 0.00
HVAC 267.82 38.06 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 521.32 38.06 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.23 0.00 0.00 0.00 0.00 0.00
HVAC 241.27 34.29 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 469.66 34.29 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1472.19 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1472.19 100.00
     
Total On-Site and Utility Electric Sources 1472.19 100.00
Total Electricity End Uses 1472.19 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 34.75
Time Setpoint Not Met During Occupied Cooling 0.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 2280.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 01-AUG-17:15 12-FEB-07:15 - - - 01-JAN-07:15
Heating 0.00 84110.63 0.00 0.00 0.00 0.00
Cooling 25323.25 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6521.51 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 18523.94 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 85397.89 84110.63 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 84110.63 0.00 0.00 0.00 0.00
Cooling General 25323.25 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6521.51 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 18523.94 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 116.52 0.00 0.00 0.00
Cooling 596.54 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.99 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 651.33 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1147.34 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4662.43 116.52 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 41.26 0.00 0.00 0.00
Cooling 211.24 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.26 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 230.64 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 406.29 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1651.02 41.26 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 41.26 0.00 0.00 0.00
Cooling 211.24 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.26 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 230.64 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 406.29 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1651.02 41.26 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.62_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 2.848 0.287 0.200     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 2.848 0.287 0.200     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.848 0.287 0.200              
North Total or Average           112.97 2.848 0.287 0.200              
Non-North Total or Average           193.95 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.82 83.82 39.47
Exterior Lighting Total 2508.33           39.47



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3390.62 2489.86 900.75 0.73 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3326.98 2450.15 876.83 0.74 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7312.29 5782.82 1529.47 0.79 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2728.93 1966.90 762.03 0.72 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2321.54 1656.95 664.59 0.71 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2310.28 1647.81 662.48 0.71 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2296.78 1633.53 663.25 0.71 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2319.89 1656.90 662.99 0.71 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   8316.59 6219.58 2097.01 0.75 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8213.23 6132.88 2080.35 0.75 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7319.87 5377.81 1942.06 0.73 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6906.20 5085.71 1820.48 0.74 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5770.56 4218.05 1552.51 0.73 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5752.48 4203.27 1549.21 0.73 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5809.54 4221.02 1588.52 0.73 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5792.26 4206.96 1585.30 0.73 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5227.83 3952.51 1275.32 0.76 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5095.31 3854.48 1240.83 0.76 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4832.27 3590.26 1242.01 0.74 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4320.77 3210.15 1110.62 0.74 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3662.48 2715.04 947.44 0.74 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3642.29 2698.56 943.73 0.74 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3990.48 2936.74 1053.73 0.74 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3999.39 2944.03 1055.37 0.74 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3257.8 3.24 11.06 11.51 10.94
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3195.8 3.24 11.05 11.50 10.93
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6973.4 3.14 10.72 11.14 10.44
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2626.7 3.27 11.14 11.60 11.07
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2236.7 3.28 11.19 11.65 11.14
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2226.0 3.28 11.19 11.65 11.14
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2213.6 3.28 11.20 11.67 11.16
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2234.9 3.28 11.19 11.65 11.13
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7976.6 3.22 10.98 11.42 10.82
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7878.6 3.22 10.98 11.43 10.83
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7032.8 3.24 11.06 11.51 10.94
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6633.9 3.24 11.05 11.50 10.93
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5547.0 3.25 11.08 11.53 10.98
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5529.8 3.25 11.08 11.54 10.98
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5587.7 3.26 11.11 11.56 11.02
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5571.3 3.26 11.11 11.56 11.02
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5008.6 3.20 10.93 11.37 10.75
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4881.4 3.20 10.92 11.36 10.74
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4637.7 3.23 11.01 11.45 10.87
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4146.8 3.23 11.01 11.45 10.87
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3515.8 3.23 11.02 11.46 10.88
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3496.6 3.23 11.02 11.47 10.88
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3833.4 3.24 11.05 11.50 10.93
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3841.8 3.24 11.05 11.50 10.93
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   2269.31 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   2249.76 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   4326.87 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   2242.48 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1704.60 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1704.60 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1704.60 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1758.92 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   4497.02 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   4529.19 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   4477.68 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   4509.86 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3409.21 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3409.21 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3409.21 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3409.21 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   3405.25 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   3423.37 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   3395.20 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   3413.33 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2614.39 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2614.11 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2594.26 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2593.97 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 189.29 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.03 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 484.27 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 145.53 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 120.80 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 120.01 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 118.46 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 120.92 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 484.99 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 477.23 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 409.13 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 388.18 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 318.57 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 317.29 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 316.03 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 314.81 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 312.75 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 305.22 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 277.46 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 248.08 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 209.17 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 207.74 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 223.96 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 224.59 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1733.83 2080.59 0.141 0.169 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
G NW APARTMENT 1713.12 2055.74 0.139 0.167 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.76 0.01445
OFFICE 4222.28 5066.73 0.360 0.432 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 29.98 0.01445
G NE APARTMENT 1332.99 1599.58 0.108 0.130 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.41 0.01445
G N1 APARTMENT 1106.50 1327.80 0.090 0.108 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.70 0.01445
G N2 APARTMENT 1099.26 1319.11 0.089 0.107 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.70 0.01445
G S1 APARTMENT 1085.01 1302.01 0.088 0.106 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
G S2 APARTMENT 1107.61 1329.14 0.090 0.108 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.70 0.01445
M SW APARTMENT 4442.17 5330.60 0.361 0.433 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
M NW APARTMENT 4371.11 5245.33 0.355 0.426 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
M SE APARTMENT 3747.17 4496.60 0.304 0.365 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
M NE APARTMENT 3555.47 4266.57 0.289 0.347 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.41 0.01445
M N1 APARTMENT 2917.97 3501.57 0.237 0.284 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.70 0.01445
M N2 APARTMENT 2906.20 3487.44 0.236 0.283 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.70 0.01445
M S1 APARTMENT 2894.66 3473.59 0.235 0.282 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.76 0.01445
M S2 APARTMENT 2883.52 3460.23 0.234 0.281 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.76 0.01445
T SW APARTMENT 2864.48 3437.37 0.233 0.279 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.83 0.01445
T NW APARTMENT 2795.60 3354.72 0.227 0.272 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.36 0.01445
T SE APARTMENT 2541.16 3049.40 0.206 0.248 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
T NE APARTMENT 2272.03 2726.44 0.185 0.221 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
T N1 APARTMENT 1915.89 2299.06 0.156 0.187 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
T N2 APARTMENT 1902.77 2283.32 0.155 0.185 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
T S1 APARTMENT 2051.24 2461.49 0.167 0.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 34.40 0.01445
T S2 APARTMENT 2057.04 2468.45 0.167 0.201 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 34.40 0.01445


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1176.06 1411.28 0.035 0.042 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
G NW APARTMENT 1185.65 1422.77 0.035 0.042 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
OFFICE 2656.76 3188.11 0.076 0.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G NE APARTMENT 1179.49 1415.39 0.035 0.042 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
G N1 APARTMENT 687.16 824.59 0.021 0.026 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
G N2 APARTMENT 687.01 824.42 0.021 0.026 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
G S1 APARTMENT 679.10 814.92 0.020 0.026 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
G S2 APARTMENT 770.54 924.65 0.023 0.028 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M SW APARTMENT 2369.22 2843.06 0.071 0.085 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M NW APARTMENT 2396.42 2875.71 0.072 0.086 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M SE APARTMENT 2352.86 2823.44 0.070 0.084 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M NE APARTMENT 2380.07 2856.09 0.071 0.085 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M N1 APARTMENT 1127.37 1352.85 0.034 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M N2 APARTMENT 1126.94 1352.32 0.034 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M S1 APARTMENT 1101.56 1321.87 0.033 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
M S2 APARTMENT 1101.13 1321.35 0.033 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T SW APARTMENT 2162.83 2595.40 0.065 0.077 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T NW APARTMENT 2178.16 2613.79 0.065 0.078 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T SE APARTMENT 2154.34 2585.20 0.064 0.077 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T NE APARTMENT 2169.66 2603.60 0.065 0.078 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T N1 APARTMENT 1494.01 1792.81 0.045 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T N2 APARTMENT 1493.77 1792.52 0.045 0.053 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T S1 APARTMENT 1476.98 1772.37 0.044 0.053 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230
T S2 APARTMENT 1476.74 1772.09 0.044 0.053 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -6.30 0.00230


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.17 0.17 0.04 0.04
SPLIT GNW 0.17 0.17 0.04 0.04
SPLIT OFFICE 0.43 0.43 0.09 0.09
SPLIT GNE 0.13 0.13 0.04 0.04
SPLIT GN1 0.11 0.11 0.03 0.03
SPLIT GN2 0.11 0.11 0.03 0.03
SPLIT GS1 0.11 0.11 0.03 0.03
SPLIT GS2 0.11 0.11 0.03 0.03
SPLIT MSW 0.43 0.43 0.08 0.08
SPLIT MNW 0.43 0.43 0.09 0.09
SPLIT MSE 0.37 0.37 0.08 0.08
SPLIT MNE 0.35 0.35 0.09 0.09
SPLIT MN1 0.28 0.28 0.05 0.05
SPLIT MN2 0.28 0.28 0.05 0.05
SPLIT MS1 0.28 0.28 0.05 0.05
SPLIT MS2 0.28 0.28 0.05 0.05
SPLIT TSW 0.28 0.28 0.08 0.08
SPLIT TNW 0.27 0.27 0.08 0.08
SPLIT TSE 0.25 0.25 0.08 0.08
SPLIT TNE 0.22 0.22 0.08 0.08
SPLIT TN1 0.19 0.19 0.05 0.05
SPLIT TN2 0.19 0.19 0.05 0.05
SPLIT TS1 0.20 0.20 0.05 0.05
SPLIT TS2 0.20 0.20 0.05 0.05



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3744.00 5819.00 1492.25
G NW APARTMENT 3945.75 6108.50 1845.00
OFFICE 653.50 1313.25 31.25
G NE APARTMENT 3931.50 6061.00 1766.50
G N1 APARTMENT 3679.25 6357.25 1804.00
G N2 APARTMENT 3677.75 6357.25 1802.00
G S1 APARTMENT 3463.00 6045.25 1385.00
G S2 APARTMENT 3477.00 6115.00 1473.75
M SW APARTMENT 4720.00 2891.50 391.25
M NW APARTMENT 4554.75 3609.50 516.75
M SE APARTMENT 4727.50 2869.50 343.50
M NE APARTMENT 4523.50 3644.75 480.00
M N1 APARTMENT 4361.50 3356.00 361.25
M N2 APARTMENT 4360.75 3361.00 360.25
M S1 APARTMENT 4694.25 2448.00 312.00
M S2 APARTMENT 4696.25 2452.00 311.50
T SW APARTMENT 4872.00 4096.75 1112.75
T NW APARTMENT 4965.00 4580.75 1464.00
T SE APARTMENT 4860.50 4071.25 1072.25
T NE APARTMENT 4954.75 4624.50 1473.75
T N1 APARTMENT 4822.25 4549.25 1301.25
T N2 APARTMENT 4821.75 4553.50 1301.75
T S1 APARTMENT 4743.25 3919.50 918.00
T S2 APARTMENT 4742.00 3916.50 917.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 5773.25 6477.25 2280.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.75 0.00 3.75 0.00
G NW APARTMENT 4.00 0.00 4.00 0.00
OFFICE 4.50 1.00 0.00 0.00
G NE APARTMENT 5.50 0.00 5.50 0.00
G N1 APARTMENT 2.75 0.50 2.75 0.50
G N2 APARTMENT 2.25 0.50 2.25 0.50
G S1 APARTMENT 0.50 0.00 0.50 0.00
G S2 APARTMENT 0.75 0.00 0.75 0.00
M SW APARTMENT 0.50 0.00 0.50 0.00
M NW APARTMENT 1.75 0.00 1.75 0.00
M SE APARTMENT 0.50 0.00 0.50 0.00
M NE APARTMENT 2.00 0.00 2.00 0.00
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.50 0.00 0.50 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.25 0.00 0.25 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.75 0.00 0.75 0.00
T NE APARTMENT 1.25 0.00 1.25 0.00
T N1 APARTMENT 2.75 0.00 2.75 0.00
T N2 APARTMENT 3.75 0.00 3.75 0.00
T S1 APARTMENT 2.25 0.00 2.25 0.00
T S2 APARTMENT 2.50 0.00 2.50 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 39.25 1.75 34.75 0.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.367 0.100 0.000 0.093
G NW APARTMENT 1.71 2.50 268.97 0.354 0.100 0.000 0.090
OFFICE 0.94 1.00 268.97 0.520 0.109 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.354 0.100 0.000 0.089
G N1 APARTMENT 1.71 2.50 268.97 0.354 0.060 0.000 0.089
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.060 0.000 0.089
G S1 APARTMENT 1.71 2.50 268.97 0.354 0.060 0.000 0.093
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.060 0.000 0.093
M SW APARTMENT 1.71 2.50 268.97 0.354 0.144 0.000 0.116
M NW APARTMENT 1.71 2.50 268.97 0.354 0.144 0.000 0.113
M SE APARTMENT 1.71 2.50 268.97 0.354 0.144 0.000 0.116
M NE APARTMENT 1.71 2.50 268.97 0.354 0.144 0.000 0.112
M N1 APARTMENT 1.71 2.50 268.97 0.354 0.087 0.000 0.113
M N2 APARTMENT 1.71 2.50 268.97 0.354 0.087 0.000 0.113
M S1 APARTMENT 1.71 2.50 268.97 0.355 0.087 0.000 0.116
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.087 0.000 0.116
T SW APARTMENT 1.71 2.50 268.97 0.354 0.190 0.000 0.140
T NW APARTMENT 1.71 2.50 268.97 0.354 0.190 0.000 0.135
T SE APARTMENT 1.71 2.50 268.97 0.354 0.190 0.000 0.140
T NE APARTMENT 1.71 2.50 268.97 0.354 0.190 0.000 0.135
T N1 APARTMENT 1.71 2.50 268.97 0.354 0.115 0.000 0.135
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.115 0.000 0.135
T S1 APARTMENT 1.71 2.50 268.97 0.354 0.115 0.000 0.140
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.115 0.000 0.140
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.352 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.498 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 362.28 0.00 01-JAN-00:15 32310.28 01-JAN-07:30
WaterSystems:Electricity 362.28 0.00 01-JAN-00:15 32310.28 01-JAN-07:30
Water Heater:WaterSystems:Electricity 362.28 0.00 01-JAN-00:15 32310.28 01-JAN-07:30
Fans:Electricity 205.66 6521.51 02-JAN-08:15 6521.51 06-JAN-18:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
ElectricityPurchased:Plant 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
Cogeneration:ElectricityPurchased 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
ElectricityNet:Plant 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
Cogeneration:ElectricityNet 1472.19 19891.81 01-JAN-03:15 85397.89 01-AUG-17:15
ExteriorLights:Electricity 39.47 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.47 0.00 01-JAN-08:00 2508.33 01-JAN-00:15
Electricity:HVAC 394.02 6521.51 02-JAN-08:15 31899.37 08-JUL-16:15
General:Fans:Electricity 205.66 6521.51 02-JAN-08:15 6521.51 06-JAN-18:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 188.36 0.00 01-JAN-00:15 25377.86 08-JUL-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 107.49 0.00 01-JAN-11:45 84110.63 12-FEB-07:15
Gas:HVAC 107.49 0.00 01-JAN-11:45 84110.63 12-FEB-07:15
Heating:Gas 107.49 0.00 01-JAN-11:45 84110.63 12-FEB-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1438.06 1199.03 20-JAN-14:45 157898.05 01-AUG-17:15
EnergyTransfer:Building 583.96 1083.76 20-JAN-15:00 61580.33 01-AUG-17:15
EnergyTransfer:Zone:G SW APARTMENT 12.06 0.02 24-MAY-10:00 1967.09 18-AUG-17:15
Heating:EnergyTransfer 40.00 0.00 12-JAN-16:15 40692.82 12-FEB-06:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 1.36 0.00 01-JAN-09:30 1360.75 12-FEB-06:00
Cooling:EnergyTransfer 543.96 0.00 08-JAN-07:15 61580.33 01-AUG-17:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 10.70 0.00 01-JAN-00:15 1967.09 18-AUG-17:15
EnergyTransfer:Zone:G NW APARTMENT 11.07 0.01 21-FEB-21:00 1843.02 01-AUG-17:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 2.36 0.00 01-JAN-10:00 1410.31 12-FEB-06:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 8.71 0.00 01-JAN-00:15 1843.02 01-AUG-17:15
EnergyTransfer:Zone:OFFICE 24.56 0.01 18-APR-07:00 3316.75 25-SEP-11:00
Heating:EnergyTransfer:Zone:OFFICE 0.35 0.00 01-JAN-00:15 3128.67 12-FEB-07:15
Cooling:EnergyTransfer:Zone:OFFICE 24.21 0.00 01-JAN-01:15 3316.75 25-SEP-11:00
EnergyTransfer:Zone:G NE APARTMENT 11.15 0.02 06-OCT-13:15 1478.08 01-AUG-17:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 2.20 0.00 01-JAN-09:30 1404.15 12-FEB-01:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 8.95 0.00 01-JAN-00:15 1478.08 01-AUG-17:15
EnergyTransfer:Zone:G N1 APARTMENT 8.60 0.00 14-APR-20:45 1157.95 01-AUG-17:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.97 0.00 01-JAN-05:15 784.27 12-FEB-01:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 7.62 0.00 01-JAN-00:15 1157.95 01-AUG-17:15
EnergyTransfer:Zone:G N2 APARTMENT 8.60 0.00 19-JAN-11:45 1152.77 01-AUG-17:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.97 0.00 01-JAN-05:15 785.53 12-FEB-01:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 7.63 0.00 01-JAN-00:15 1152.77 01-AUG-17:15
EnergyTransfer:Zone:G S1 APARTMENT 10.19 0.07 04-APR-08:30 1313.10 23-SEP-15:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.40 0.00 01-JAN-04:15 714.70 12-FEB-06:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 9.79 0.00 01-JAN-00:15 1313.10 23-SEP-15:15
EnergyTransfer:Zone:G S2 APARTMENT 10.03 0.01 08-MAR-19:45 1290.15 23-SEP-15:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.48 0.00 01-JAN-05:15 817.65 12-FEB-06:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 9.55 0.00 01-JAN-00:15 1290.15 23-SEP-15:15
EnergyTransfer:Zone:M SW APARTMENT 45.42 0.38 30-JAN-12:15 4972.99 11-OCT-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.77 0.00 01-JAN-00:15 2604.98 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 44.65 0.00 03-JAN-01:15 4972.99 11-OCT-16:15
EnergyTransfer:Zone:M NW APARTMENT 38.05 0.04 18-FEB-13:45 4645.74 01-AUG-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 2.10 0.00 01-JAN-00:15 2843.82 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 35.94 0.00 02-JAN-02:30 4645.74 01-AUG-17:15
EnergyTransfer:Zone:M SE APARTMENT 46.07 0.02 28-JAN-01:30 4256.71 10-OCT-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.79 0.00 01-JAN-00:15 2635.50 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 45.27 0.00 03-JAN-00:15 4256.71 10-OCT-13:30
EnergyTransfer:Zone:M NE APARTMENT 38.48 0.04 31-JAN-19:15 3896.77 01-AUG-17:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 1.99 0.00 01-JAN-00:15 2848.10 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 36.48 0.00 02-JAN-02:00 3896.77 01-AUG-17:15
EnergyTransfer:Zone:M N1 APARTMENT 34.23 0.04 26-JAN-15:15 3062.30 06-JUN-17:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.35 0.00 01-JAN-00:15 1268.59 12-FEB-01:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 33.88 0.00 04-JAN-05:00 3062.30 06-JUN-17:30
EnergyTransfer:Zone:M N2 APARTMENT 34.24 0.07 15-NOV-12:30 3054.33 06-JUN-17:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.36 0.00 01-JAN-00:15 1271.88 12-FEB-01:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 33.88 0.00 04-JAN-05:00 3054.33 06-JUN-17:30
EnergyTransfer:Zone:M S1 APARTMENT 43.70 1.25 19-JAN-21:30 3838.42 11-OCT-15:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.08 0.00 01-JAN-00:15 1043.92 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 43.62 0.00 05-JAN-04:45 3838.42 11-OCT-15:30
EnergyTransfer:Zone:M S2 APARTMENT 43.71 0.67 19-JAN-21:30 3833.89 11-OCT-15:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.08 0.00 01-JAN-00:15 1046.91 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 43.62 0.00 05-JAN-04:45 3833.89 11-OCT-15:30
EnergyTransfer:Zone:T SW APARTMENT 23.19 0.00 06-DEC-19:30 3243.90 18-AUG-16:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 3.36 0.00 01-JAN-15:15 2715.36 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 19.82 0.00 01-JAN-00:15 3243.90 18-AUG-16:15
EnergyTransfer:Zone:T NW APARTMENT 21.55 0.00 04-OCT-11:15 3092.84 01-AUG-17:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 4.92 0.00 01-JAN-15:15 2737.06 12-FEB-01:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 16.63 0.00 01-JAN-00:15 3092.84 01-AUG-17:00
EnergyTransfer:Zone:T SE APARTMENT 23.20 0.00 18-SEP-03:00 2752.50 18-AUG-13:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 3.26 0.00 01-JAN-09:45 2674.64 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 19.95 0.00 01-JAN-00:15 2752.50 18-AUG-13:00
EnergyTransfer:Zone:T NE APARTMENT 21.48 0.02 09-MAR-05:00 2709.77 12-FEB-01:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 4.71 0.00 01-JAN-10:15 2709.77 12-FEB-01:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 16.76 0.00 01-JAN-00:15 2590.25 08-JUL-16:15
EnergyTransfer:Zone:T N1 APARTMENT 17.37 0.01 05-MAR-15:30 2148.55 01-AUG-17:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 2.58 0.00 01-JAN-06:15 1811.11 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 14.79 0.00 01-JAN-00:15 2148.55 01-AUG-17:15
EnergyTransfer:Zone:T N2 APARTMENT 17.38 0.04 22-FEB-12:15 2139.99 08-JUL-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 2.58 0.00 01-JAN-06:15 1809.61 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 14.79 0.00 01-JAN-00:15 2139.99 08-JUL-16:15
EnergyTransfer:Zone:T S1 APARTMENT 19.83 0.08 22-APR-06:45 2338.36 10-OCT-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 1.48 0.00 01-JAN-05:15 1797.54 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 18.35 0.00 01-JAN-00:15 2338.36 10-OCT-14:15
EnergyTransfer:Zone:T S2 APARTMENT 19.84 0.00 20-JAN-01:00 2340.82 10-OCT-14:15
Heating:EnergyTransfer:Zone:T S2 APARTMENT 1.48 0.00 01-JAN-05:15 1798.05 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 18.36 0.00 01-JAN-00:15 2340.82 10-OCT-14:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 854.10 0.00 01-JAN-11:45 96644.70 20-AUG-15:30
HeatingCoils:EnergyTransfer 85.99 0.00 01-JAN-11:45 67288.51 12-FEB-07:15
CoolingCoils:EnergyTransfer 768.10 0.00 01-JAN-00:15 96644.70 20-AUG-15:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 1.360 -10.704 0.000 0.000 3.744 2.413 12.213 11.988 0.000 0.237 0.000 0.000 -5.099 0.000 -3.248 -12.904
G NW APARTMENT 2.361 -8.707 0.000 0.000 3.770 2.413 12.213 7.171 0.000 0.236 0.000 0.000 -5.311 0.000 -3.099 -11.046
OFFICE 0.346 -24.214 0.000 0.000 0.520 21.914 7.534 12.072 0.000 0.223 0.000 0.000 -4.903 0.000 -2.276 -11.216
G NE APARTMENT 2.197 -8.954 0.000 0.000 3.781 2.413 12.213 7.074 0.000 0.236 0.000 0.000 -5.063 0.000 -3.075 -10.822
G N1 APARTMENT 0.973 -7.622 0.000 0.000 3.779 2.413 12.213 2.922 0.000 0.160 0.000 0.000 -3.282 0.000 -2.154 -9.401
G N2 APARTMENT 0.971 -7.626 0.000 0.000 3.779 2.413 12.213 2.921 0.000 0.160 0.000 0.000 -3.281 0.000 -2.153 -9.398
G S1 APARTMENT 0.402 -9.789 0.000 0.000 3.745 2.413 12.213 7.788 0.000 0.159 0.000 0.000 -3.076 0.000 -2.311 -11.543
G S2 APARTMENT 0.476 -9.552 0.000 0.000 3.745 2.413 12.213 7.790 0.000 0.159 0.000 0.000 -3.070 0.000 -2.312 -11.862
M SW APARTMENT 0.765 -44.651 0.000 0.000 3.622 2.413 12.213 11.434 0.000 0.332 24.449 0.000 -5.796 0.000 -4.781 -0.000
M NW APARTMENT 2.102 -35.943 0.000 0.000 3.657 2.413 12.213 6.719 0.000 0.330 19.169 0.000 -6.013 0.000 -4.647 -0.000
M SE APARTMENT 0.794 -45.271 0.000 0.000 3.628 2.413 12.213 11.450 0.000 0.332 24.867 0.000 -5.654 0.000 -4.771 -0.001
M NE APARTMENT 1.992 -36.484 0.000 0.000 3.664 2.413 12.213 6.600 0.000 0.330 19.636 0.000 -5.733 0.000 -4.631 -0.000
M N1 APARTMENT 0.355 -33.875 0.000 0.000 3.641 2.413 12.213 2.652 0.000 0.218 19.480 0.000 -3.801 0.000 -3.295 0.000
M N2 APARTMENT 0.359 -33.877 0.000 0.000 3.642 2.413 12.213 2.651 0.000 0.218 19.475 0.000 -3.800 0.000 -3.295 0.000
M S1 APARTMENT 0.084 -43.617 0.000 0.000 3.598 2.413 12.213 7.429 0.000 0.220 24.603 0.000 -3.534 0.000 -3.409 0.000
M S2 APARTMENT 0.085 -43.623 0.000 0.000 3.598 2.413 12.213 7.428 0.000 0.220 24.606 0.000 -3.532 0.000 -3.408 0.000
T SW APARTMENT 3.364 -19.821 0.000 0.000 3.687 2.413 12.213 11.289 0.000 0.443 0.000 0.000 -5.429 0.000 -5.923 -2.236
T NW APARTMENT 4.924 -16.625 0.000 0.000 3.713 2.413 12.213 6.615 0.000 0.440 0.000 0.000 -5.643 0.000 -5.747 -2.302
T SE APARTMENT 3.257 -19.946 0.000 0.000 3.693 2.413 12.213 11.317 0.000 0.443 0.001 0.000 -5.303 0.000 -5.918 -2.170
T NE APARTMENT 4.712 -16.762 0.000 0.000 3.723 2.413 12.213 6.530 0.000 0.440 0.000 0.000 -5.390 0.000 -5.727 -2.152
T N1 APARTMENT 2.580 -14.785 0.000 0.000 3.708 2.413 12.213 2.630 0.000 0.294 0.000 0.000 -3.524 0.000 -3.974 -1.554
T N2 APARTMENT 2.583 -14.793 0.000 0.000 3.709 2.413 12.213 2.629 0.000 0.294 0.000 0.000 -3.521 0.000 -3.974 -1.552
T S1 APARTMENT 1.478 -18.349 0.000 0.000 3.674 2.413 12.213 7.358 0.000 0.297 0.000 0.000 -3.310 0.000 -4.146 -1.627
T S2 APARTMENT 1.482 -18.359 0.000 0.000 3.674 2.413 12.213 7.357 0.000 0.297 0.000 0.000 -3.309 0.000 -4.146 -1.621
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.139 0.000 0.024 0.000 0.000 -0.655 0.000 -0.877 -15.701
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.516 0.000 0.961 0.000 0.000 -1.644 0.000 -12.633 -10.535
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.142 0.000 0.022 0.000 0.000 -0.727 0.000 -0.734 -15.773
Total Facility 40.002 -543.952 0.000 0.000 85.495 128.627 294.692 172.611 0.000 7.726 176.286 0.000 -109.403 0.000 -106.665 -145.418


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 18-AUG-17:08 0.00 -1968.30 0.00 0.00 141.81 194.45 588.62 1461.06 0.00 83.72 0.00 0.00 0.00 0.00 0.00 -501.36
G NW APARTMENT 01-AUG-17:08 0.00 -1844.17 0.00 0.00 141.81 194.45 588.62 1455.87 0.00 113.58 0.00 0.00 0.00 0.00 0.00 -650.18
OFFICE 25-SEP-11:00 0.00 -3316.47 0.00 0.00 67.31 1622.34 544.92 2225.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1144.03
G NE APARTMENT 01-AUG-17:08 0.00 -1479.07 0.00 0.00 141.81 194.45 588.62 672.29 0.00 113.58 0.00 0.00 0.00 0.00 0.00 -231.69
G N1 APARTMENT 01-AUG-17:11 0.00 -1158.33 0.00 0.00 141.81 194.45 588.62 427.98 0.00 68.51 0.00 0.00 0.00 0.00 0.00 -263.05
G N2 APARTMENT 01-AUG-17:08 0.00 -1153.13 0.00 0.00 141.81 194.45 588.62 428.06 0.00 68.51 0.00 0.00 0.00 0.00 0.00 -268.32
G S1 APARTMENT 23-SEP-15:15 0.00 -1313.10 0.00 0.00 48.90 100.83 470.90 1108.76 0.00 31.70 0.00 0.00 0.00 0.00 0.00 -447.98
G S2 APARTMENT 23-SEP-15:15 0.00 -1290.15 0.00 0.00 48.90 100.83 470.90 1109.13 0.00 31.70 0.00 0.00 0.00 0.00 0.00 -471.31
M SW APARTMENT 11-OCT-16:15 0.00 -4970.88 0.00 0.00 84.77 144.04 588.62 1883.80 0.00 60.86 2208.79 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 01-AUG-17:08 0.00 -4648.64 0.00 0.00 141.81 194.45 588.62 1440.22 0.00 162.91 2120.63 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 10-OCT-13:30 0.00 -4256.43 0.00 0.00 40.75 28.81 382.60 1978.61 0.00 43.63 1782.02 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 01-AUG-17:08 0.00 -3899.48 0.00 0.00 141.81 194.45 588.62 661.61 0.00 162.91 2150.08 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 06-JUN-17:23 0.00 -3062.90 0.00 0.00 141.81 194.45 588.62 464.80 0.00 122.42 1550.81 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 06-JUN-17:23 0.00 -3054.95 0.00 0.00 141.81 194.45 588.62 464.85 0.00 122.42 1542.80 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 11-OCT-15:30 0.00 -3838.12 0.00 0.00 48.90 100.83 470.90 1125.31 0.00 104.84 1987.34 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 11-OCT-15:30 0.00 -3833.59 0.00 0.00 48.90 100.83 470.90 1125.33 0.00 104.84 1982.79 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 18-AUG-16:05 0.00 -3245.39 0.00 0.00 84.76 144.04 588.62 1691.87 0.00 147.35 588.75 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 01-AUG-17:00 0.00 -3093.05 0.00 0.00 84.76 144.04 588.62 1474.17 0.00 249.51 551.94 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 18-AUG-13:00 0.00 -2752.29 0.00 0.00 40.75 28.81 388.49 1370.72 0.00 79.75 843.76 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 08-JUL-16:05 0.00 -2591.55 0.00 0.00 84.76 144.04 588.62 813.66 0.00 92.97 867.51 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 01-AUG-17:08 0.00 -2149.29 0.00 0.00 141.81 194.45 588.62 407.34 0.00 129.46 687.59 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 08-JUL-16:05 0.00 -2141.15 0.00 0.00 84.76 144.04 588.62 497.13 0.00 56.08 770.52 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 10-OCT-14:15 0.00 -2338.23 0.00 0.00 40.75 50.41 400.26 1467.57 0.00 39.16 340.07 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 10-OCT-14:15 0.00 -2340.70 0.00 0.00 40.75 50.41 400.26 1467.52 0.00 39.16 342.59 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 01-AUG-17:08 0.00 -61607.42 0.00 0.00 3261.64 6475.86 14071.03 17224.20 0.00 3495.24 17079.45 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 21-DEC-17:01 1939.88 0.00 0.00 0.00 99.77 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -305.94 0.00 -208.96 -2257.41
G NW APARTMENT 26-MAR-06:01 1923.82 0.00 0.00 0.00 163.28 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -477.08 0.00 -99.91 -1986.35
OFFICE 31-DEC-07:01 3936.87 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -412.61 0.00 -177.44 -3921.39
G NE APARTMENT 12-FEB-01:00 1404.08 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -905.41 0.00 -703.17 -264.46
G N1 APARTMENT 24-FEB-07:01 1249.49 0.00 0.00 0.00 161.37 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -336.97 0.00 -104.76 -1445.37
G N2 APARTMENT 24-FEB-07:01 1248.84 0.00 0.00 0.00 161.37 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -336.95 0.00 -104.76 -1444.73
G S1 APARTMENT 06-JAN-17:01 1133.43 0.00 0.00 0.00 98.73 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -306.74 0.00 -91.49 -1566.58
G S2 APARTMENT 18-MAR-07:02 964.99 0.00 0.00 0.00 74.05 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -244.91 0.00 -191.74 -1034.09
M SW APARTMENT 12-FEB-06:00 2604.95 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -978.86 0.00 -962.36 -1200.12
M NW APARTMENT 12-FEB-06:00 2843.78 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -997.08 0.00 -962.36 -1420.74
M SE APARTMENT 12-FEB-06:00 2635.46 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -962.53 0.00 -962.36 -1246.97
M NE APARTMENT 12-FEB-06:00 2848.07 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -980.86 0.00 -961.98 -1441.63
M N1 APARTMENT 10-JAN-10:30 1276.37 0.00 0.00 0.00 47.42 28.81 406.15 0.00 0.00 0.00 0.00 0.00 -199.46 0.00 -114.80 -1444.48
M N2 APARTMENT 09-FEB-07:02 2052.39 0.00 0.00 0.00 161.22 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -484.45 0.00 -156.15 -2049.24
M S1 APARTMENT 11-FEB-22:23 1863.51 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -523.38 0.00 -378.26 -1655.89
M S2 APARTMENT 10-JAN-06:23 1694.62 0.00 0.00 0.00 189.67 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -433.27 0.00 -175.36 -1694.34
T SW APARTMENT 12-FEB-06:00 2715.33 0.00 0.00 0.00 189.96 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -950.96 0.00 -1270.43 -1030.63
T NW APARTMENT 12-FEB-01:00 2736.93 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -922.20 0.00 -1339.11 -944.58
T SE APARTMENT 12-FEB-06:00 2674.60 0.00 0.00 0.00 190.36 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -933.83 0.00 -1267.99 -1009.88
T NE APARTMENT 12-FEB-01:00 2709.64 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -906.07 0.00 -1337.58 -934.95
T N1 APARTMENT 12-FEB-06:00 1811.08 0.00 0.00 0.00 190.07 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -589.86 0.00 -766.29 -991.73
T N2 APARTMENT 06-MAR-07:01 2203.22 0.00 0.00 0.00 163.43 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -315.30 0.00 -145.61 -2381.97
T S1 APARTMENT 12-FEB-06:00 1797.51 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -569.72 0.00 -768.04 -996.16
T S2 APARTMENT 12-FEB-06:00 1798.02 0.00 0.00 0.00 189.67 93.63 253.11 0.00 0.00 0.00 0.00 0.00 -569.70 0.00 -768.03 -996.70
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-FEB-06:00 39960.63 0.00 0.00 0.00 4366.67 4156.84 6111.77 0.00 0.00 0.00 0.00 0.00 -18922.97 0.00 -18982.29 -16690.65



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sec1.1A-General Information

Data
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 34.75
Number of hours cooling loads not met 0.75
Number of hours not met 35.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.47 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 107.49 84110.63 0.00 0.00
Space Cooling 188.36 25323.25 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 205.66 6521.51 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 362.28 18523.94 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1472.19   107.49   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1472.19
Natural Gas 0.00 107.49
Additional 0.00 0.00
Total 511.42 1579.69


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 60.09
Fans-Interior 65.61
Service Water Heating 115.57
Receptacle Equipment 163.15
Miscellaneous 12.59
Subtotal 469.66


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 34.29
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 34.29


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.45
Space Heating 6.80
Space Cooling 11.92
Fans-Interior 13.02
Service Water Heating 22.93
Receptacle Equipment 32.37
Miscellaneous 2.50



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.168996
G NW APARTMENT DIRECT AIR 0.166977
OFFICE DIRECT AIR 0.432340
G NE APARTMENT DIRECT AIR 0.129926
G N1 APARTMENT DIRECT AIR 0.107849
G N2 APARTMENT DIRECT AIR 0.107143
G S1 APARTMENT DIRECT AIR 0.105754
G S2 APARTMENT DIRECT AIR 0.107958
M SW APARTMENT DIRECT AIR 0.432982
M NW APARTMENT DIRECT AIR 0.426056
M SE APARTMENT DIRECT AIR 0.365256
M NE APARTMENT DIRECT AIR 0.346556
M N1 APARTMENT DIRECT AIR 0.284413
M N2 APARTMENT DIRECT AIR 0.283265
M S1 APARTMENT DIRECT AIR 0.282140
M S2 APARTMENT DIRECT AIR 0.281055
T SW APARTMENT DIRECT AIR 0.279217
T NW APARTMENT DIRECT AIR 0.272495
T SE APARTMENT DIRECT AIR 0.247708
T NE APARTMENT DIRECT AIR 0.221475
T N1 APARTMENT DIRECT AIR 0.186742
T N2 APARTMENT DIRECT AIR 0.185463
T S1 APARTMENT DIRECT AIR 0.199942
T S2 APARTMENT DIRECT AIR 0.200507


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.168996
SPLIT GNW MAIN BRANCH 0.166977
SPLIT OFFICE MAIN BRANCH 0.432340
SPLIT GNE MAIN BRANCH 0.129926
SPLIT GN1 MAIN BRANCH 0.107849
SPLIT GN2 MAIN BRANCH 0.107143
SPLIT GS1 MAIN BRANCH 0.105754
SPLIT GS2 MAIN BRANCH 0.107958
SPLIT MSW MAIN BRANCH 0.432982
SPLIT MNW MAIN BRANCH 0.426056
SPLIT MSE MAIN BRANCH 0.365256
SPLIT MNE MAIN BRANCH 0.346556
SPLIT MN1 MAIN BRANCH 0.284413
SPLIT MN2 MAIN BRANCH 0.283265
SPLIT MS1 MAIN BRANCH 0.282140
SPLIT MS2 MAIN BRANCH 0.281055
SPLIT TSW MAIN BRANCH 0.279217
SPLIT TNW MAIN BRANCH 0.272495
SPLIT TSE MAIN BRANCH 0.247708
SPLIT TNE MAIN BRANCH 0.221475
SPLIT TN1 MAIN BRANCH 0.186742
SPLIT TN2 MAIN BRANCH 0.185463
SPLIT TS1 MAIN BRANCH 0.199942
SPLIT TS2 MAIN BRANCH 0.200507


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.168996
SPLIT GNW 0.166977
SPLIT OFFICE 0.432340
SPLIT GNE 0.129926
SPLIT GN1 0.107849
SPLIT GN2 0.107143
SPLIT GS1 0.105754
SPLIT GS2 0.107958
SPLIT MSW 0.432982
SPLIT MNW 0.426056
SPLIT MSE 0.365256
SPLIT MNE 0.346556
SPLIT MN1 0.284413
SPLIT MN2 0.283265
SPLIT MS1 0.282140
SPLIT MS2 0.281055
SPLIT TSW 0.279217
SPLIT TNW 0.272495
SPLIT TSE 0.247708
SPLIT TNE 0.221475
SPLIT TN1 0.186742
SPLIT TN2 0.185463
SPLIT TS1 0.199942
SPLIT TS2 0.200507


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.168996 0.026898
SPLIT GNW OA CONTROLLER 0.166977 0.025953
SPLIT OFFICE OA CONTROLLER 0.432340 0.038104
SPLIT GNE OA CONTROLLER 0.129926 0.025953
SPLIT GN1 OA CONTROLLER 0.107849 0.025953
SPLIT GN2 OA CONTROLLER 0.107143 0.025953
SPLIT GS1 OA CONTROLLER 0.105754 0.025953
SPLIT GS2 OA CONTROLLER 0.107958 0.025953
SPLIT MSW OA CONTROLLER 0.432982 0.051906
SPLIT MNW OA CONTROLLER 0.426056 0.051906
SPLIT MSE OA CONTROLLER 0.365256 0.051906
SPLIT MNE OA CONTROLLER 0.346556 0.051906
SPLIT MN1 OA CONTROLLER 0.284413 0.051906
SPLIT MN2 OA CONTROLLER 0.283265 0.051906
SPLIT MS1 OA CONTROLLER 0.282140 0.051906
SPLIT MS2 OA CONTROLLER 0.281055 0.051906
SPLIT TSW OA CONTROLLER 0.279217 0.025953
SPLIT TNW OA CONTROLLER 0.272495 0.025953
SPLIT TSE OA CONTROLLER 0.247708 0.025953
SPLIT TNE OA CONTROLLER 0.221475 0.025953
SPLIT TN1 OA CONTROLLER 0.186742 0.025953
SPLIT TN2 OA CONTROLLER 0.185463 0.025953
SPLIT TS1 OA CONTROLLER 0.199942 0.025953
SPLIT TS2 OA CONTROLLER 0.200507 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.168996 3390.62 0.734340
SPLIT GNW COOLING COIL 0.166977 3326.98 0.736450
SPLIT OFFICE COOLING COIL 0.432340 7312.29 0.790835
SPLIT GNE COOLING COIL 0.129926 2728.93 0.720759
SPLIT GN1 COOLING COIL 0.107849 2321.54 0.713730
SPLIT GN2 COOLING COIL 0.107143 2310.28 0.713248
SPLIT GS1 COOLING COIL 0.105754 2296.78 0.711226
SPLIT GS2 COOLING COIL 0.107958 2319.89 0.714216
SPLIT MSW COOLING COIL 0.432982 8316.59 0.747852
SPLIT MNW COOLING COIL 0.426056 8213.23 0.746708
SPLIT MSE COOLING COIL 0.365256 7319.87 0.734687
SPLIT MNE COOLING COIL 0.346556 6906.20 0.736399
SPLIT MN1 COOLING COIL 0.284413 5770.56 0.730960
SPLIT MN2 COOLING COIL 0.283265 5752.48 0.730688
SPLIT MS1 COOLING COIL 0.282140 5809.54 0.726566
SPLIT MS2 COOLING COIL 0.281055 5792.26 0.726307
SPLIT TSW COOLING COIL 0.279217 5227.83 0.756052
SPLIT TNW COOLING COIL 0.272495 5095.31 0.756476
SPLIT TSE COOLING COIL 0.247708 4832.27 0.742976
SPLIT TNE COOLING COIL 0.221475 4320.77 0.742958
SPLIT TN1 COOLING COIL 0.186742 3662.48 0.741312
SPLIT TN2 COOLING COIL 0.185463 3642.29 0.740896
SPLIT TS1 COOLING COIL 0.199942 3990.48 0.735938
SPLIT TS2 COOLING COIL 0.200507 3999.39 0.736118


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.168996 0.168996 0.168996 0.168996 2269.31 3390.62 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.166977 0.166977 0.166977 0.166977 2249.76 3326.98 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.432340 0.432340 0.432340 0.432340 4326.87 7312.29 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.129926 0.129926 0.129926 0.129926 2242.48 2728.93 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.107849 0.107849 0.107849 0.107849 1704.60 2321.54 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.107143 0.107143 0.107143 0.107143 1704.60 2310.28 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.105754 0.105754 0.105754 0.105754 1704.60 2296.78 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.107958 0.107958 0.107958 0.107958 1758.92 2319.89 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.432982 0.432982 0.432982 0.432982 4497.02 8316.59 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.426056 0.426056 0.426056 0.426056 4529.19 8213.23 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.365256 0.365256 0.365256 0.365256 4477.68 7319.87 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.346556 0.346556 0.346556 0.346556 4509.86 6906.20 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.284413 0.284413 0.284413 0.284413 3409.21 5770.56 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.283265 0.283265 0.283265 0.283265 3409.21 5752.48 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.282140 0.282140 0.282140 0.282140 3409.21 5809.54 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.281055 0.281055 0.281055 0.281055 3409.21 5792.26 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.279217 0.279217 0.279217 0.279217 3405.25 5227.83 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.272495 0.272495 0.272495 0.272495 3423.37 5095.31 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.247708 0.247708 0.247708 0.247708 3395.20 4832.27 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.221475 0.221475 0.221475 0.221475 3413.33 4320.77 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.186742 0.186742 0.186742 0.186742 2614.39 3662.48 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.185463 0.185463 0.185463 0.185463 2614.11 3642.29 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.199942 0.199942 0.199942 0.199942 2594.26 3990.48 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.200507 0.200507 0.200507 0.200507 2593.97 3999.39 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.168996
SPLIT GNW SUPPLY FAN 0.166977
SPLIT OFFICE SUPPLY FAN 0.432340
SPLIT GNE SUPPLY FAN 0.129926
SPLIT GN1 SUPPLY FAN 0.107849
SPLIT GN2 SUPPLY FAN 0.107143
SPLIT GS1 SUPPLY FAN 0.105754
SPLIT GS2 SUPPLY FAN 0.107958
SPLIT MSW SUPPLY FAN 0.432982
SPLIT MNW SUPPLY FAN 0.426056
SPLIT MSE SUPPLY FAN 0.365256
SPLIT MNE SUPPLY FAN 0.346556
SPLIT MN1 SUPPLY FAN 0.284413
SPLIT MN2 SUPPLY FAN 0.283265
SPLIT MS1 SUPPLY FAN 0.282140
SPLIT MS2 SUPPLY FAN 0.281055
SPLIT TSW SUPPLY FAN 0.279217
SPLIT TNW SUPPLY FAN 0.272495
SPLIT TSE SUPPLY FAN 0.247708
SPLIT TNE SUPPLY FAN 0.221475
SPLIT TN1 SUPPLY FAN 0.186742
SPLIT TN2 SUPPLY FAN 0.185463
SPLIT TS1 SUPPLY FAN 0.199942
SPLIT TS2 SUPPLY FAN 0.200507


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 2269.31
SPLIT GNW HEATING COIL 2249.76
SPLIT OFFICE HEATING COIL 4326.87
SPLIT GNE HEATING COIL 2242.48
SPLIT GN1 HEATING COIL 1704.60
SPLIT GN2 HEATING COIL 1704.60
SPLIT GS1 HEATING COIL 1704.60
SPLIT GS2 HEATING COIL 1758.92
SPLIT MSW HEATING COIL 4497.02
SPLIT MNW HEATING COIL 4529.19
SPLIT MSE HEATING COIL 4477.68
SPLIT MNE HEATING COIL 4509.86
SPLIT MN1 HEATING COIL 3409.21
SPLIT MN2 HEATING COIL 3409.21
SPLIT MS1 HEATING COIL 3409.21
SPLIT MS2 HEATING COIL 3409.21
SPLIT TSW HEATING COIL 3405.25
SPLIT TNW HEATING COIL 3423.37
SPLIT TSE HEATING COIL 3395.20
SPLIT TNE HEATING COIL 3413.33
SPLIT TN1 HEATING COIL 2614.39
SPLIT TN2 HEATING COIL 2614.11
SPLIT TS1 HEATING COIL 2594.26
SPLIT TS2 HEATING COIL 2593.97



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 3.96
February 22.23 7.94
March 22.97 13.76
April 23.55 17.21
May 24.05 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.52 16.03
November 22.84 11.94
December 22.18 7.70
     
Annual Sum or Average 23.41 16.65
Minimum of Months 21.90 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 22.00 7.94
March 22.62 13.76
April 23.42 17.21
May 24.04 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.22 16.03
November 22.38 11.94
December 21.86 7.70
     
Annual Sum or Average 23.24 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 3.96
February 21.98 7.94
March 23.29 13.76
April 23.65 17.21
May 23.87 20.84
June 23.90 24.80
July 23.90 26.06
August 23.90 26.55
September 23.90 22.53
October 23.63 16.03
November 23.05 11.94
December 21.99 7.70
     
Annual Sum or Average 23.19 16.65
Minimum of Months 21.17 3.96
Maximum of Months 23.90 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 3.96
February 21.96 7.94
March 22.52 13.76
April 23.37 17.21
May 24.01 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.37 22.53
October 23.17 16.03
November 22.28 11.94
December 21.81 7.70
     
Annual Sum or Average 23.21 16.65
Minimum of Months 21.74 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 21.95 7.94
March 22.46 13.76
April 23.29 17.21
May 23.95 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.18 16.03
November 22.30 11.94
December 21.84 7.70
     
Annual Sum or Average 23.20 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 3.96
February 21.95 7.94
March 22.46 13.76
April 23.28 17.21
May 23.95 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.17 16.03
November 22.29 11.94
December 21.84 7.70
     
Annual Sum or Average 23.19 16.65
Minimum of Months 21.74 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 3.96
February 22.24 7.94
March 22.92 13.76
April 23.47 17.21
May 23.98 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.56 16.03
November 22.88 11.94
December 22.22 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 21.91 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 3.96
February 22.25 7.94
March 22.92 13.76
April 23.47 17.21
May 23.98 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.56 16.03
November 22.88 11.94
December 22.22 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 21.91 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.42 3.96
February 23.04 7.94
March 24.18 13.76
April 24.33 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.31 16.03
November 24.01 11.94
December 23.04 7.70
     
Annual Sum or Average 23.95 16.65
Minimum of Months 22.42 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 3.96
February 22.73 7.94
March 23.98 13.76
April 24.29 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.23 16.03
November 23.58 11.94
December 22.32 7.70
     
Annual Sum or Average 23.76 16.65
Minimum of Months 21.95 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.36 3.96
February 22.99 7.94
March 24.15 13.76
April 24.33 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.30 16.03
November 23.99 11.94
December 22.99 7.70
     
Annual Sum or Average 23.93 16.65
Minimum of Months 22.36 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 3.96
February 22.70 7.94
March 23.94 13.76
April 24.29 17.21
May 24.39 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.19 16.03
November 23.53 11.94
December 22.24 7.70
     
Annual Sum or Average 23.74 16.65
Minimum of Months 21.90 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 3.96
February 22.84 7.94
March 24.12 13.76
April 24.33 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.31 16.03
November 23.77 11.94
December 22.51 7.70
     
Annual Sum or Average 23.83 16.65
Minimum of Months 22.03 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 3.96
February 22.84 7.94
March 24.12 13.76
April 24.33 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.31 16.03
November 23.76 11.94
December 22.50 7.70
     
Annual Sum or Average 23.83 16.65
Minimum of Months 22.03 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.72 3.96
February 23.25 7.94
March 24.28 13.76
April 24.36 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.37 16.03
November 24.19 11.94
December 23.45 7.70
     
Annual Sum or Average 24.05 16.65
Minimum of Months 22.72 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.71 3.96
February 23.24 7.94
March 24.28 13.76
April 24.36 17.21
May 24.40 20.84
June 24.40 24.80
July 24.40 26.06
August 24.40 26.55
September 24.40 22.53
October 24.37 16.03
November 24.19 11.94
December 23.45 7.70
     
Annual Sum or Average 24.05 16.65
Minimum of Months 22.71 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.15 3.96
February 22.66 7.94
March 23.52 13.76
April 24.06 17.21
May 24.33 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.37 22.53
October 23.81 16.03
November 23.29 11.94
December 22.49 7.70
     
Annual Sum or Average 23.66 16.65
Minimum of Months 22.15 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 3.96
February 22.40 7.94
March 23.28 13.76
April 23.99 17.21
May 24.33 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.36 22.53
October 23.59 16.03
November 22.90 11.94
December 22.07 7.70
     
Annual Sum or Average 23.50 16.65
Minimum of Months 21.87 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.11 3.96
February 22.62 7.94
March 23.51 13.76
April 24.06 17.21
May 24.33 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.36 22.53
October 23.78 16.03
November 23.28 11.94
December 22.46 7.70
     
Annual Sum or Average 23.65 16.65
Minimum of Months 22.11 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 3.96
February 22.35 7.94
March 23.23 13.76
April 23.98 17.21
May 24.32 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.35 22.53
October 23.54 16.03
November 22.82 11.94
December 22.00 7.70
     
Annual Sum or Average 23.47 16.65
Minimum of Months 21.84 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 3.96
February 22.44 7.94
March 23.32 13.76
April 24.02 17.21
May 24.34 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.36 22.53
October 23.66 16.03
November 22.91 11.94
December 22.07 7.70
     
Annual Sum or Average 23.52 16.65
Minimum of Months 21.86 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 3.96
February 22.43 7.94
March 23.31 13.76
April 24.02 17.21
May 24.34 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.36 22.53
October 23.66 16.03
November 22.90 11.94
December 22.06 7.70
     
Annual Sum or Average 23.52 16.65
Minimum of Months 21.86 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 3.96
February 22.76 7.94
March 23.64 13.76
April 24.11 17.21
May 24.35 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.93 16.03
November 23.42 11.94
December 22.61 7.70
     
Annual Sum or Average 23.72 16.65
Minimum of Months 22.22 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 3.96
February 22.76 7.94
March 23.64 13.76
April 24.11 17.21
May 24.35 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.38 22.53
October 23.93 16.03
November 23.42 11.94
December 22.61 7.70
     
Annual Sum or Average 23.72 16.65
Minimum of Months 22.22 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 3.96
February 23.02 7.94
March 24.70 13.76
April 25.75 17.21
May 26.51 20.84
June 27.00 24.80
July 27.16 26.06
August 27.21 26.55
September 26.60 22.53
October 25.23 16.03
November 24.07 11.94
December 22.70 7.70
     
Annual Sum or Average 25.18 16.65
Minimum of Months 22.03 3.96
Maximum of Months 27.21 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.55 3.96
February 21.41 7.94
March 22.87 13.76
April 23.85 17.21
May 24.71 20.84
June 26.37 24.80
July 26.69 26.06
August 26.80 26.55
September 26.14 22.53
October 23.81 16.03
November 22.58 11.94
December 21.40 7.70
     
Annual Sum or Average 23.94 16.65
Minimum of Months 20.55 3.96
Maximum of Months 26.80 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.79 3.96
February 24.65 7.94
March 26.20 13.76
April 26.59 17.21
May 26.84 20.84
June 27.03 24.80
July 27.08 26.06
August 27.11 26.55
September 26.88 22.53
October 26.46 16.03
November 25.84 11.94
December 24.56 7.70
     
Annual Sum or Average 26.09 16.65
Minimum of Months 23.79 3.96
Maximum of Months 27.11 26.55



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.114108E+12 73161.994 21-JAN-18:30 8572.775 26456.413 6521.509 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 29102.967 0.000 0.000 0.000
February 0.104427E+12 72457.063 28-FEB-18:00 8572.775 26456.413 6521.509 0.000 5863.822 2508.330 0.000 0.000 0.000 0.000 0.000 22534.215 0.000 0.000 0.000
March 0.118093E+12 79650.844 30-MAR-17:45 8572.775 26456.413 6521.509 0.000 14591.268 0.000 0.000 0.000 0.000 0.000 0.000 23508.879 0.000 0.000 0.000
April 0.117977E+12 77508.047 17-APR-17:15 8572.775 26456.413 6521.509 0.000 14168.561 0.000 0.000 0.000 0.000 0.000 0.000 21788.789 0.000 0.000 0.000
May 0.127366E+12 79453.761 19-MAY-17:15 8572.775 26456.413 6521.509 0.000 17501.666 0.000 0.000 0.000 0.000 0.000 0.000 20401.398 0.000 0.000 0.000
June 0.133480E+12 83349.019 06-JUN-17:00 8572.775 26456.413 6521.509 0.000 21775.398 0.000 0.000 0.000 0.000 0.000 0.000 20022.924 0.000 0.000 0.000
July 0.141761E+12 83927.432 12-JUL-17:15 8572.775 26456.413 6521.509 0.000 22188.349 0.000 0.000 0.000 0.000 0.000 0.000 20188.386 0.000 0.000 0.000
August 0.144380E+12 85397.890 01-AUG-17:15 8572.775 26456.413 6521.509 0.000 25323.253 0.000 0.000 0.000 0.000 0.000 0.000 18523.940 0.000 0.000 0.000
September 0.127509E+12 82681.088 06-SEP-17:15 8572.775 26456.413 6521.509 0.000 20924.700 0.000 0.000 0.000 0.000 0.000 0.000 20205.691 0.000 0.000 0.000
October 0.118502E+12 77278.890 18-OCT-18:45 9689.078 23563.017 6521.509 0.000 13828.561 2508.330 0.000 0.000 0.000 0.000 0.000 21168.395 0.000 0.000 0.000
November 0.110838E+12 71475.166 19-NOV-18:30 8572.775 26456.413 6521.509 0.000 6254.001 2508.330 0.000 0.000 0.000 0.000 0.000 21162.138 0.000 0.000 0.000
December 0.113752E+12 69989.128 23-DEC-18:45 8572.775 26456.413 6521.509 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 25930.101 0.000 0.000 0.000
                                     
Annual Sum or Average 0.147219E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.104427E+12 69989.128   8572.775 23563.017 6521.509 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18523.940 0.000 0.000 0.000
Maximum of Months 0.144380E+12 85397.890   9689.078 26456.413 6521.509 0.000 25323.253 2508.330 0.000 0.000 0.000 0.000 0.000 29102.967 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.467998E+11 61719.682 08-JAN-01:15 61719.682 0.000 0.000 0.000 0.000 0.000 61719.682
February 0.276285E+11 84110.632 12-FEB-07:15 84110.632 0.000 0.000 0.000 0.000 0.000 84110.632
March 0.290367E+10 15263.771 18-MAR-07:15 15263.771 0.000 0.000 0.000 0.000 0.000 15263.771
April 0.878903E+09 13673.346 06-APR-06:15 13673.346 0.000 0.000 0.000 0.000 0.000 13673.346
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.715287E+09 12480.291 26-OCT-05:00 12480.291 0.000 0.000 0.000 0.000 0.000 12480.291
November 0.640840E+10 35454.116 22-NOV-05:00 35454.116 0.000 0.000 0.000 0.000 0.000 35454.116
December 0.221587E+11 40900.890 03-DEC-07:15 40900.890 0.000 0.000 0.000 0.000 0.000 40900.890
                     
Annual Sum or Average 0.107493E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.467998E+11 84110.632   84110.632 0.000 0.000 0.000 0.000 0.000 84110.632