Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2018-10-19 09:20:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1538.62 | 490.85 | 544.84 |
Net Site Energy | 1538.62 | 490.85 | 544.84 |
Total Source Energy | 4548.89 | 1451.18 | 1610.81 |
Net Source Energy | 4548.89 | 1451.18 | 1610.81 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 155.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 420.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1383.11 | 155.51 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 155.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 197.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 420.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 236.31 | 55.07 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 489.77 | 55.07 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 212.89 | 49.61 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.24 | 49.61 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1383.11 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1383.11 | 100.00 |
Total On-Site and Utility Electric Sources | 1383.11 | 100.00 |
Total Electricity End Uses | 1383.11 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 91.75 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 569.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | William R Fairchild WA USA TMY3 WMO#=727885 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-17:15 | 30-DEC-01:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 44835.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16519.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6253.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25686.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83488.51 | 44835.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 44835.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16519.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6253.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25686.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 168.57 | 0.00 | 0.00 | 0.00 |
Cooling | 155.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 624.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1333.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4380.31 | 168.57 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.69 | 0.00 | 0.00 | 0.00 |
Cooling | 55.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 472.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1551.12 | 59.69 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.69 | 0.00 | 0.00 | 0.00 |
Cooling | 55.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 472.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1551.12 | 59.69 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.58 | 83.58 | 39.35 | |
Exterior Lighting Total | 2508.33 | 39.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2694.87 | 2152.27 | 542.60 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2123.72 | 1696.12 | 427.60 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7085.50 | 5658.87 | 1426.63 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1404.99 | 1122.11 | 282.89 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1165.14 | 930.55 | 234.59 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1147.37 | 916.36 | 231.02 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1961.07 | 1566.22 | 394.85 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2013.97 | 1608.47 | 405.50 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7670.58 | 6126.15 | 1544.43 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6060.53 | 4840.28 | 1220.26 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7027.33 | 5612.42 | 1414.92 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4473.92 | 3573.12 | 900.80 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3576.85 | 2856.67 | 720.18 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3543.37 | 2829.93 | 713.44 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5767.92 | 4606.58 | 1161.34 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5788.45 | 4622.98 | 1165.47 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5005.65 | 3997.79 | 1007.86 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3866.33 | 3087.87 | 778.47 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4655.56 | 3718.19 | 937.37 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2813.22 | 2246.79 | 566.43 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2236.79 | 1786.42 | 450.37 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2226.85 | 1778.48 | 448.36 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4045.65 | 3231.08 | 814.57 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4060.37 | 3242.84 | 817.53 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2567.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2023.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6750.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1338.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1110.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1093.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1868.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1918.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7307.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5773.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6694.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4262.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3407.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3375.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5494.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5514.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4768.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3683.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4435.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2680.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2130.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2121.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3854.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3868.1 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1770.69 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1737.15 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 3496.66 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1740.13 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1687.09 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1687.09 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1687.09 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1687.09 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3374.19 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2591.37 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2588.12 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2595.69 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2592.44 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2084.35 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2084.47 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2085.84 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2085.96 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 182.35 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 143.70 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 479.45 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.08 | 95.07 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.07 | 78.84 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.07 | 77.64 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 132.70 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 136.28 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 519.04 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 410.09 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 475.51 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.73 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 242.03 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 239.76 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 390.29 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 391.68 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 338.71 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.62 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 315.02 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.36 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 151.35 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 150.68 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 273.75 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 274.75 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1714.03 | 2056.83 | 0.136 | 0.163 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49 | 0.00838 |
G NW APARTMENT | 1350.76 | 1620.91 | 0.107 | 0.128 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
OFFICE | 4418.05 | 5301.66 | 0.357 | 0.428 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39 | 0.00838 |
G NE APARTMENT | 893.58 | 1072.30 | 0.071 | 0.085 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 22.56 | 0.00838 |
G N1 APARTMENT | 741.07 | 889.28 | 0.059 | 0.070 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
G N2 APARTMENT | 729.77 | 875.72 | 0.058 | 0.069 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
G S1 APARTMENT | 1247.30 | 1496.76 | 0.099 | 0.118 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
G S2 APARTMENT | 1280.95 | 1537.14 | 0.101 | 0.122 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
M SW APARTMENT | 4878.75 | 5854.50 | 0.386 | 0.463 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49 | 0.00838 |
M NW APARTMENT | 3854.71 | 4625.65 | 0.305 | 0.366 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
M SE APARTMENT | 4469.62 | 5363.54 | 0.354 | 0.425 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
M NE APARTMENT | 2845.52 | 3414.63 | 0.225 | 0.270 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 23.28 | 0.00838 |
M N1 APARTMENT | 2275.00 | 2730.00 | 0.180 | 0.216 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
M N2 APARTMENT | 2253.70 | 2704.44 | 0.178 | 0.214 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
M S1 APARTMENT | 3668.59 | 4402.31 | 0.290 | 0.348 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
M S2 APARTMENT | 3681.65 | 4417.98 | 0.291 | 0.350 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
T SW APARTMENT | 3183.76 | 3820.51 | 0.252 | 0.302 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
T NW APARTMENT | 2459.12 | 2950.95 | 0.195 | 0.234 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 24.67 | 0.00838 |
T SE APARTMENT | 2961.09 | 3553.31 | 0.234 | 0.281 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
T NE APARTMENT | 1789.29 | 2147.15 | 0.142 | 0.170 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 24.53 | 0.00838 |
T N1 APARTMENT | 1422.67 | 1707.21 | 0.113 | 0.135 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 25.31 | 0.00838 |
T N2 APARTMENT | 1416.35 | 1699.62 | 0.112 | 0.135 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 26.26 | 0.00838 |
T S1 APARTMENT | 2573.17 | 3087.80 | 0.204 | 0.244 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
T S2 APARTMENT | 2582.53 | 3099.04 | 0.204 | 0.245 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 789.36 | 947.24 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
G NW APARTMENT | 785.89 | 943.07 | 0.023 | 0.027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
OFFICE | 2009.83 | 2411.80 | 0.056 | 0.067 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G NE APARTMENT | 788.41 | 946.09 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
G N1 APARTMENT | 440.26 | 528.31 | 0.013 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
G N2 APARTMENT | 440.32 | 528.38 | 0.013 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
G S1 APARTMENT | 444.72 | 533.66 | 0.013 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
G S2 APARTMENT | 518.01 | 621.62 | 0.015 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M SW APARTMENT | 1294.15 | 1552.98 | 0.038 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M NW APARTMENT | 1285.95 | 1543.14 | 0.037 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M SE APARTMENT | 1301.07 | 1561.28 | 0.038 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M NE APARTMENT | 1292.88 | 1551.45 | 0.038 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M N1 APARTMENT | 387.74 | 465.29 | 0.011 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M N2 APARTMENT | 387.96 | 465.55 | 0.011 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M S1 APARTMENT | 399.74 | 479.68 | 0.012 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
M S2 APARTMENT | 399.96 | 479.95 | 0.012 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T SW APARTMENT | 1508.28 | 1809.93 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T NW APARTMENT | 1505.52 | 1806.63 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T SE APARTMENT | 1511.93 | 1814.31 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T NE APARTMENT | 1509.18 | 1811.01 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T N1 APARTMENT | 1079.50 | 1295.40 | 0.031 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T N2 APARTMENT | 1079.60 | 1295.52 | 0.031 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T S1 APARTMENT | 1080.76 | 1296.91 | 0.031 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
T S2 APARTMENT | 1080.86 | 1297.04 | 0.031 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -4.30 | 0.00266 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.16 | 0.16 | 0.03 | 0.03 |
SPLIT GNW | 0.13 | 0.13 | 0.03 | 0.03 |
SPLIT OFFICE | 0.43 | 0.43 | 0.07 | 0.07 |
SPLIT GNE | 0.08 | 0.08 | 0.03 | 0.03 |
SPLIT GN1 | 0.07 | 0.07 | 0.03 | 0.03 |
SPLIT GN2 | 0.07 | 0.07 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT MSW | 0.46 | 0.46 | 0.05 | 0.05 |
SPLIT MNW | 0.37 | 0.37 | 0.05 | 0.05 |
SPLIT MSE | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT MNE | 0.27 | 0.27 | 0.05 | 0.05 |
SPLIT MN1 | 0.22 | 0.22 | 0.05 | 0.05 |
SPLIT MN2 | 0.21 | 0.21 | 0.05 | 0.05 |
SPLIT MS1 | 0.35 | 0.35 | 0.05 | 0.05 |
SPLIT MS2 | 0.35 | 0.35 | 0.05 | 0.05 |
SPLIT TSW | 0.30 | 0.30 | 0.05 | 0.05 |
SPLIT TNW | 0.23 | 0.23 | 0.05 | 0.05 |
SPLIT TSE | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TNE | 0.17 | 0.17 | 0.05 | 0.05 |
SPLIT TN1 | 0.14 | 0.14 | 0.04 | 0.04 |
SPLIT TN2 | 0.13 | 0.13 | 0.04 | 0.04 |
SPLIT TS1 | 0.24 | 0.24 | 0.04 | 0.04 |
SPLIT TS2 | 0.25 | 0.25 | 0.04 | 0.04 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 847.25 | 6703.50 | 60.75 |
G NW APARTMENT | 503.00 | 7309.25 | 121.75 |
OFFICE | 42.00 | 1706.00 | 15.00 |
G NE APARTMENT | 446.00 | 7289.50 | 124.25 |
G N1 APARTMENT | 160.00 | 7540.75 | 49.75 |
G N2 APARTMENT | 159.00 | 7542.00 | 49.75 |
G S1 APARTMENT | 638.75 | 6638.50 | 9.75 |
G S2 APARTMENT | 611.25 | 6671.25 | 14.25 |
M SW APARTMENT | 2227.00 | 4341.75 | 0.00 |
M NW APARTMENT | 1730.75 | 5125.25 | 14.50 |
M SE APARTMENT | 2288.75 | 4359.25 | 0.00 |
M NE APARTMENT | 1727.25 | 5162.75 | 13.50 |
M N1 APARTMENT | 1588.75 | 4953.00 | 0.00 |
M N2 APARTMENT | 1589.75 | 4954.00 | 0.00 |
M S1 APARTMENT | 2219.50 | 3804.75 | 0.00 |
M S2 APARTMENT | 2223.75 | 3814.00 | 0.00 |
T SW APARTMENT | 1919.25 | 5923.00 | 318.25 |
T NW APARTMENT | 1727.50 | 6569.25 | 538.50 |
T SE APARTMENT | 1971.75 | 5888.50 | 318.00 |
T NE APARTMENT | 1771.75 | 6595.25 | 539.25 |
T N1 APARTMENT | 1256.00 | 6656.75 | 194.25 |
T N2 APARTMENT | 1257.25 | 6654.25 | 195.75 |
T S1 APARTMENT | 1660.25 | 5739.50 | 99.25 |
T S2 APARTMENT | 1663.25 | 5735.00 | 99.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 3150.75 | 7683.75 | 569.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 14.25 | 0.00 | 14.25 | 0.00 |
G NW APARTMENT | 17.00 | 0.00 | 17.00 | 0.00 |
OFFICE | 3.25 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 10.75 | 0.00 | 10.75 | 0.00 |
G N1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
G N2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G S1 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G S2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
M SW APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M NW APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
M SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M N1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M N2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M S1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M S2 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NE APARTMENT | 9.00 | 0.00 | 9.00 | 0.00 |
T N1 APARTMENT | 12.25 | 0.00 | 12.25 | 0.00 |
T N2 APARTMENT | 11.75 | 0.00 | 11.75 | 0.00 |
T S1 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T S2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 95.00 | 0.00 | 91.75 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.365 | 0.057 | 0.000 | 0.046 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.057 | 0.000 | 0.045 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.061 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.057 | 0.000 | 0.046 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.034 | 0.000 | 0.045 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.034 | 0.000 | 0.045 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.034 | 0.000 | 0.046 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.034 | 0.000 | 0.046 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.082 | 0.000 | 0.051 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.082 | 0.000 | 0.051 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.082 | 0.000 | 0.051 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.082 | 0.000 | 0.051 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.049 | 0.000 | 0.051 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.049 | 0.000 | 0.051 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.050 | 0.000 | 0.051 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.050 | 0.000 | 0.051 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.108 | 0.000 | 0.057 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.108 | 0.000 | 0.057 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.108 | 0.000 | 0.057 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.108 | 0.000 | 0.057 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.065 | 0.000 | 0.057 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.065 | 0.000 | 0.057 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.065 | 0.000 | 0.057 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.065 | 0.000 | 0.057 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.362 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.364 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.362 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 420.99 | 0.00 | 01-JAN-00:15 | 32349.32 | 01-JAN-07:00 |
WaterSystems:Electricity | 420.99 | 0.00 | 01-JAN-00:15 | 32349.32 | 01-JAN-07:00 |
Water Heater:WaterSystems:Electricity | 420.99 | 0.00 | 01-JAN-00:15 | 32349.32 | 01-JAN-07:00 |
Fans:Electricity | 197.21 | 6253.40 | 01-JAN-00:15 | 6253.40 | 02-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
ElectricityPurchased:Plant | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
Cogeneration:ElectricityPurchased | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
ElectricityNet:Plant | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
Cogeneration:ElectricityNet | 1383.11 | 19623.69 | 01-JAN-03:15 | 83488.51 | 22-JUL-17:15 |
ExteriorLights:Electricity | 39.35 | 0.00 | 01-JAN-08:15 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.35 | 0.00 | 01-JAN-08:15 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 246.34 | 6253.40 | 01-JAN-00:15 | 22843.10 | 22-JUL-18:00 |
General:Fans:Electricity | 197.21 | 6253.40 | 01-JAN-00:15 | 6253.40 | 02-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 49.14 | 0.00 | 01-JAN-00:15 | 16589.71 | 22-JUL-18:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 155.51 | 0.00 | 18-MAR-16:15 | 44835.57 | 30-DEC-02:00 |
Gas:HVAC | 155.51 | 0.00 | 18-MAR-16:15 | 44835.57 | 30-DEC-02:00 |
Heating:Gas | 155.51 | 0.00 | 18-MAR-16:15 | 44835.57 | 30-DEC-02:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 710.95 | 2347.10 | 24-NOV-12:15 | 121132.78 | 22-JUL-17:15 |
EnergyTransfer:Building | 389.48 | 2132.25 | 24-NOV-12:15 | 55024.57 | 22-JUL-16:15 |
EnergyTransfer:Zone:G SW APARTMENT | 8.10 | 0.01 | 09-JAN-16:45 | 1702.71 | 22-JUL-17:15 |
Heating:EnergyTransfer | 41.11 | 0.00 | 06-JAN-16:15 | 18703.88 | 30-DEC-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.67 | 0.00 | 01-JAN-09:30 | 689.43 | 28-DEC-02:00 |
Cooling:EnergyTransfer | 348.37 | 204.34 | 03-DEC-04:45 | 55024.57 | 22-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.43 | 0.00 | 01-JAN-00:15 | 1702.71 | 22-JUL-17:15 |
EnergyTransfer:Zone:G NW APARTMENT | 6.83 | 0.01 | 04-APR-04:45 | 1503.42 | 22-JUL-18:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.54 | 0.00 | 01-JAN-21:00 | 746.38 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.29 | 0.00 | 01-JAN-00:15 | 1503.42 | 22-JUL-18:15 |
EnergyTransfer:Zone:OFFICE | 17.96 | 0.35 | 31-MAY-20:45 | 3086.44 | 27-SEP-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.10 | 0.00 | 01-JAN-00:15 | 1463.73 | 10-JAN-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 17.86 | 0.00 | 02-JAN-07:45 | 3086.44 | 27-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 7.02 | 0.03 | 01-MAR-14:15 | 1076.27 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.47 | 0.00 | 01-JAN-21:00 | 753.44 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.55 | 0.00 | 01-JAN-00:15 | 1076.27 | 22-JUL-18:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 6.00 | 0.15 | 13-JAN-15:15 | 887.95 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.77 | 0.00 | 01-JAN-16:45 | 393.72 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 5.23 | 0.00 | 01-JAN-00:15 | 887.95 | 22-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 6.01 | 0.04 | 06-NOV-04:00 | 877.61 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.77 | 0.00 | 01-JAN-16:45 | 394.42 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.24 | 0.00 | 01-JAN-00:15 | 877.61 | 22-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.69 | 0.08 | 21-NOV-02:00 | 1110.76 | 27-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.38 | 0.00 | 01-JAN-01:00 | 367.33 | 11-JAN-09:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.32 | 0.00 | 01-JAN-00:15 | 1110.76 | 27-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.62 | 0.05 | 25-FEB-06:45 | 1102.10 | 27-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.45 | 0.00 | 01-JAN-05:15 | 396.04 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.16 | 0.00 | 01-JAN-00:15 | 1102.10 | 27-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 31.07 | 1.27 | 16-FEB-09:15 | 4895.14 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 996.66 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 30.67 | 0.00 | 03-JAN-23:45 | 4895.14 | 14-AUG-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 22.35 | 0.16 | 15-JAN-05:45 | 4401.37 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.16 | 0.00 | 01-JAN-01:00 | 1248.07 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 21.19 | 0.00 | 01-JAN-00:15 | 4401.37 | 13-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 31.85 | 0.17 | 03-JAN-23:45 | 4173.95 | 22-JUL-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 982.27 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 31.46 | 0.00 | 03-JAN-24:00 | 4173.95 | 22-JUL-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 23.32 | 0.01 | 25-DEC-10:30 | 3314.50 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.14 | 0.00 | 01-JAN-01:00 | 1251.20 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 22.18 | 0.00 | 01-JAN-00:15 | 3314.50 | 22-JUL-18:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 24.84 | 0.37 | 26-DEC-23:15 | 2741.42 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 766.45 | 11-JAN-09:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 24.78 | 0.00 | 04-JAN-02:15 | 2741.42 | 22-JUL-18:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 24.83 | 0.07 | 09-DEC-03:15 | 2723.60 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 767.32 | 11-JAN-09:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 24.78 | 0.00 | 04-JAN-02:15 | 2723.60 | 22-JUL-18:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 34.21 | 0.80 | 29-DEC-03:45 | 3660.30 | 27-SEP-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 512.29 | 31-DEC-03:30 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 34.21 | 0.00 | 03-DEC-03:00 | 3660.30 | 27-SEP-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 34.20 | 4.04 | 29-DEC-03:45 | 3667.64 | 27-SEP-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 493.34 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 34.20 | 0.00 | 03-DEC-03:00 | 3667.64 | 27-SEP-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 13.89 | 0.01 | 27-MAY-08:15 | 3187.39 | 21-JUL-16:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.06 | 0.00 | 01-JAN-10:00 | 1409.27 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 9.83 | 0.00 | 01-JAN-00:15 | 3187.39 | 21-JUL-16:30 |
EnergyTransfer:Zone:T NW APARTMENT | 12.05 | 0.00 | 13-JUN-03:00 | 2915.99 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 5.68 | 0.00 | 06-JAN-12:00 | 1495.10 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 6.37 | 0.00 | 01-JAN-00:15 | 2915.99 | 13-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 14.06 | 0.10 | 12-OCT-22:30 | 2846.84 | 22-JUL-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 4.03 | 0.00 | 01-JAN-09:15 | 1423.10 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 10.04 | 0.00 | 01-JAN-00:15 | 2846.84 | 22-JUL-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 12.31 | 0.18 | 08-OCT-13:15 | 2146.22 | 22-JUL-16:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 5.62 | 0.00 | 06-JAN-11:15 | 1507.28 | 30-DEC-01:45 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 6.69 | 0.00 | 01-JAN-00:15 | 2146.22 | 22-JUL-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 9.62 | 0.06 | 06-NOV-11:45 | 1833.89 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 2.91 | 0.00 | 01-JAN-21:00 | 1004.77 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.71 | 0.00 | 01-JAN-00:15 | 1833.89 | 13-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 9.62 | 0.09 | 03-MAR-16:00 | 1812.95 | 13-JUN-16:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 2.92 | 0.00 | 01-JAN-21:00 | 1005.90 | 30-DEC-01:45 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.70 | 0.00 | 01-JAN-00:15 | 1812.95 | 13-JUN-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 12.00 | 0.01 | 16-OCT-01:45 | 2410.88 | 22-JUL-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.76 | 0.00 | 01-JAN-09:00 | 928.00 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.24 | 0.00 | 01-JAN-00:15 | 2410.88 | 22-JUL-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 12.01 | 0.14 | 05-MAR-10:30 | 2417.81 | 22-JUL-13:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.76 | 0.00 | 01-JAN-09:00 | 929.17 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.25 | 0.00 | 01-JAN-00:15 | 2417.81 | 22-JUL-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 321.47 | 0.00 | 18-MAR-16:15 | 66511.92 | 13-JUN-16:15 |
HeatingCoils:EnergyTransfer | 124.41 | 0.00 | 18-MAR-16:15 | 35868.45 | 30-DEC-02:00 |
CoolingCoils:EnergyTransfer | 197.06 | 0.00 | 01-JAN-00:15 | 66511.92 | 13-JUN-16:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.673 | -6.432 | 0.000 | 0.000 | 3.896 | 2.413 | 12.213 | 11.044 | 0.000 | 0.003 | 0.000 | 0.000 | -7.670 | 0.000 | -2.806 | -14.333 |
G NW APARTMENT | 2.536 | -4.294 | 0.000 | 0.000 | 3.927 | 2.413 | 12.213 | 5.300 | 0.000 | 0.003 | 0.000 | 0.000 | -7.698 | 0.000 | -2.733 | -11.666 |
OFFICE | 0.105 | -17.858 | 0.000 | 0.000 | 0.522 | 21.914 | 7.534 | 11.089 | 0.000 | 0.002 | 0.001 | 0.000 | -7.481 | 0.000 | -1.978 | -13.848 |
G NE APARTMENT | 2.473 | -4.547 | 0.000 | 0.000 | 3.939 | 2.413 | 12.213 | 5.318 | 0.000 | 0.003 | 0.000 | 0.000 | -7.508 | 0.000 | -2.735 | -11.568 |
G N1 APARTMENT | 0.767 | -5.231 | 0.000 | 0.000 | 3.935 | 2.413 | 12.213 | 1.744 | 0.000 | 0.002 | 0.000 | 0.000 | -4.721 | 0.000 | -1.919 | -9.204 |
G N2 APARTMENT | 0.768 | -5.238 | 0.000 | 0.000 | 3.936 | 2.413 | 12.213 | 1.744 | 0.000 | 0.002 | 0.000 | 0.000 | -4.720 | 0.000 | -1.919 | -9.199 |
G S1 APARTMENT | 0.377 | -7.317 | 0.000 | 0.000 | 3.891 | 2.413 | 12.213 | 7.550 | 0.000 | 0.002 | 0.000 | 0.000 | -4.708 | 0.000 | -2.010 | -12.411 |
G S2 APARTMENT | 0.452 | -7.165 | 0.000 | 0.000 | 3.891 | 2.413 | 12.213 | 7.550 | 0.000 | 0.002 | 0.000 | 0.000 | -4.703 | 0.000 | -2.011 | -12.643 |
M SW APARTMENT | 0.400 | -30.672 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 10.568 | 0.000 | 0.004 | 13.857 | 0.000 | -8.540 | 0.000 | -3.950 | -0.000 |
M NW APARTMENT | 1.160 | -21.189 | 0.000 | 0.000 | 3.782 | 2.413 | 12.213 | 4.878 | 0.000 | 0.004 | 9.039 | 0.000 | -8.408 | 0.000 | -3.891 | -0.000 |
M SE APARTMENT | 0.396 | -31.457 | 0.000 | 0.000 | 3.716 | 2.413 | 12.213 | 10.623 | 0.000 | 0.004 | 14.408 | 0.000 | -8.369 | 0.000 | -3.946 | -0.000 |
M NE APARTMENT | 1.140 | -22.181 | 0.000 | 0.000 | 3.797 | 2.413 | 12.213 | 4.893 | 0.000 | 0.004 | 9.784 | 0.000 | -8.179 | 0.000 | -3.882 | -0.000 |
M N1 APARTMENT | 0.058 | -24.778 | 0.000 | 0.000 | 3.762 | 2.413 | 12.213 | 1.477 | 0.000 | 0.003 | 12.819 | 0.000 | -5.247 | 0.000 | -2.720 | 0.000 |
M N2 APARTMENT | 0.054 | -24.776 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 1.477 | 0.000 | 0.003 | 12.815 | 0.000 | -5.244 | 0.000 | -2.719 | 0.000 |
M S1 APARTMENT | 0.006 | -34.205 | 0.000 | 0.000 | 3.660 | 2.413 | 12.213 | 7.247 | 0.000 | 0.003 | 16.745 | 0.000 | -5.314 | 0.000 | -2.767 | 0.000 |
M S2 APARTMENT | 0.005 | -34.197 | 0.000 | 0.000 | 3.660 | 2.413 | 12.213 | 7.247 | 0.000 | 0.003 | 16.735 | 0.000 | -5.313 | 0.000 | -2.767 | 0.000 |
T SW APARTMENT | 4.057 | -9.831 | 0.000 | 0.000 | 3.840 | 2.413 | 12.213 | 10.598 | 0.000 | 0.005 | 0.000 | 0.000 | -7.872 | 0.000 | -4.900 | -10.524 |
T NW APARTMENT | 5.677 | -6.375 | 0.000 | 0.000 | 3.890 | 2.413 | 12.213 | 4.931 | 0.000 | 0.005 | 0.000 | 0.000 | -7.816 | 0.000 | -4.815 | -10.122 |
T SE APARTMENT | 4.029 | -10.035 | 0.000 | 0.000 | 3.847 | 2.413 | 12.213 | 10.673 | 0.000 | 0.005 | 0.000 | 0.000 | -7.737 | 0.000 | -4.902 | -10.504 |
T NE APARTMENT | 5.621 | -6.691 | 0.000 | 0.000 | 3.905 | 2.413 | 12.213 | 4.970 | 0.000 | 0.005 | 0.000 | 0.000 | -7.627 | 0.000 | -4.813 | -9.996 |
T N1 APARTMENT | 2.914 | -6.705 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 1.544 | 0.000 | 0.004 | 0.000 | 0.000 | -4.814 | 0.000 | -3.293 | -8.168 |
T N2 APARTMENT | 2.920 | -6.704 | 0.000 | 0.000 | 3.893 | 2.413 | 12.213 | 1.542 | 0.000 | 0.004 | 0.000 | 0.000 | -4.811 | 0.000 | -3.294 | -8.175 |
T S1 APARTMENT | 1.762 | -10.238 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 7.288 | 0.000 | 0.003 | 0.000 | 0.000 | -4.873 | 0.000 | -3.374 | -9.014 |
T S2 APARTMENT | 1.764 | -10.249 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 7.286 | 0.000 | 0.003 | 0.000 | 0.000 | -4.871 | 0.000 | -3.374 | -9.004 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.026 | 0.000 | 0.000 | 0.000 | 0.000 | -0.973 | 0.000 | -0.732 | -15.391 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.122 | 0.000 | 0.007 | 1.268 | 0.000 | -2.575 | 0.000 | -22.157 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.024 | 0.000 | 0.000 | 0.000 | 0.000 | -1.095 | 0.000 | -0.610 | -15.389 |
Total Facility | 41.113 | -348.367 | 0.000 | 0.000 | 88.692 | 128.627 | 294.692 | 148.752 | 0.000 | 0.083 | 107.471 | 0.000 | -158.886 | 0.000 | -101.017 | -201.159 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 22-JUL-17:15 | 0.00 | -1702.97 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1634.61 | 0.00 | 19.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.26 |
G NW APARTMENT | 22-JUL-18:15 | 0.00 | -1503.43 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 1555.74 | 0.00 | 7.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -979.24 |
OFFICE | 27-SEP-13:30 | 0.00 | -3086.23 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2243.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13.39 | -1378.38 |
G NE APARTMENT | 22-JUL-18:30 | 0.00 | -1076.29 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 579.84 | 0.00 | 13.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -437.05 |
G N1 APARTMENT | 22-JUL-18:30 | 0.00 | -887.97 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 448.23 | 0.00 | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -488.28 |
G N2 APARTMENT | 22-JUL-18:30 | 0.00 | -877.63 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 448.41 | 0.00 | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -498.81 |
G S1 APARTMENT | 27-SEP-13:30 | 0.00 | -1110.61 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2100.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.64 | -1366.04 |
G S2 APARTMENT | 27-SEP-13:30 | 0.00 | -1101.95 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2100.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.64 | -1374.84 |
M SW APARTMENT | 14-AUG-16:15 | 0.00 | -4894.44 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1992.45 | 0.00 | 68.30 | 2016.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 13-JUN-17:15 | 0.00 | -4401.15 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1892.81 | 0.00 | 62.54 | 1520.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 22-JUL-13:30 | 0.00 | -4173.64 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1793.67 | 0.00 | 38.88 | 1888.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 22-JUL-18:30 | 0.00 | -3314.58 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 566.21 | 0.00 | 19.77 | 1808.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 22-JUL-18:30 | 0.00 | -2741.47 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 438.08 | 0.00 | 11.93 | 1371.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 22-JUL-18:30 | 0.00 | -2723.65 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 438.19 | 0.00 | 11.93 | 1353.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 27-SEP-13:30 | 0.00 | -3659.83 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2087.21 | 0.00 | 0.00 | 1208.80 | 0.00 | 0.00 | 0.00 | -88.34 | 0.00 |
M S2 APARTMENT | 27-SEP-13:30 | 0.00 | -3667.17 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2087.16 | 0.00 | 0.00 | 1216.19 | 0.00 | 0.00 | 0.00 | -88.34 | 0.00 |
T SW APARTMENT | 21-JUL-16:30 | 0.00 | -3187.36 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2014.89 | 0.00 | 16.97 | 338.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 13-JUN-17:15 | 0.00 | -2915.86 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1862.73 | 0.00 | 75.93 | 52.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 22-JUL-13:30 | 0.00 | -2846.66 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1762.13 | 0.00 | 50.85 | 581.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 22-JUL-16:15 | 0.00 | -2146.40 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 612.52 | 0.00 | 46.87 | 669.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 13-JUN-17:15 | 0.00 | -1833.81 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 329.00 | 0.00 | 67.20 | 512.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 13-JUN-16:15 | 0.00 | -1812.86 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 327.89 | 0.00 | 112.36 | 555.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 22-JUL-14:15 | 0.00 | -2410.76 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1258.51 | 0.00 | 31.66 | 629.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 22-JUL-13:45 | 0.00 | -2417.66 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1424.08 | 0.00 | 30.67 | 510.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-16:15 | 0.00 | -55024.69 | 0.00 | 0.00 | 1949.42 | 5316.35 | 14071.03 | 20309.95 | 0.00 | 1213.55 | 12164.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 17-OCT-06:01 | 1455.86 | 0.00 | 0.00 | 0.00 | 163.11 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -397.16 | 0.00 | -57.44 | -1640.60 |
G NW APARTMENT | 25-OCT-06:01 | 1408.56 | 0.00 | 0.00 | 0.00 | 163.32 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -382.47 | 0.00 | -53.54 | -1612.09 |
OFFICE | 24-DEC-07:01 | 3135.76 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -389.79 | 0.00 | -51.60 | -3268.94 |
G NE APARTMENT | 26-JAN-17:01 | 1384.17 | 0.00 | 0.00 | 0.00 | 99.98 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -346.21 | 0.00 | -35.45 | -1835.15 |
G N1 APARTMENT | 28-FEB-07:01 | 1212.18 | 0.00 | 0.00 | 0.00 | 161.32 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.82 | 0.00 | -35.82 | -1583.09 |
G N2 APARTMENT | 28-FEB-07:01 | 1211.23 | 0.00 | 0.00 | 0.00 | 161.32 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.75 | 0.00 | -35.82 | -1582.21 |
G S1 APARTMENT | 15-NOV-07:01 | 1371.73 | 0.00 | 0.00 | 0.00 | 163.31 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -215.78 | 0.00 | -158.66 | -1636.83 |
G S2 APARTMENT | 01-FEB-07:01 | 1343.15 | 0.00 | 0.00 | 0.00 | 163.32 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -227.56 | 0.00 | -38.44 | -1716.71 |
M SW APARTMENT | 26-FEB-07:01 | 2122.47 | 0.00 | 0.00 | 0.00 | 161.44 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.33 | 0.00 | -193.71 | -2003.10 |
M NW APARTMENT | 29-NOV-17:01 | 2561.73 | 0.00 | 0.00 | 0.00 | 100.00 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -482.16 | 0.00 | -124.62 | -2787.61 |
M SE APARTMENT | 08-JAN-08:02 | 1193.37 | 0.00 | 0.00 | 0.00 | 74.05 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -254.33 | 0.00 | -312.45 | -1132.34 |
M NE APARTMENT | 03-DEC-17:01 | 2052.51 | 0.00 | 0.00 | 0.00 | 98.72 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -496.08 | 0.00 | -185.00 | -2202.81 |
M N1 APARTMENT | 11-JAN-08:19 | 1990.65 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.32 | 0.00 | -78.03 | -2039.97 |
M N2 APARTMENT | 11-JAN-08:19 | 1988.78 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.31 | 0.00 | -78.03 | -2038.12 |
M S1 APARTMENT | 31-DEC-03:30 | 1024.59 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -342.79 | 0.00 | -75.76 | -1033.78 |
M S2 APARTMENT | 17-DEC-01:30 | 829.89 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -321.52 | 0.00 | -125.98 | -827.80 |
T SW APARTMENT | 03-APR-06:01 | 1603.27 | 0.00 | 0.00 | 0.00 | 162.59 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -394.58 | 0.00 | 0.00 | -1847.51 |
T NW APARTMENT | 14-APR-06:01 | 2229.18 | 0.00 | 0.00 | 0.00 | 163.11 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.14 | 0.00 | 0.00 | -2587.39 |
T SE APARTMENT | 30-DEC-02:00 | 1423.07 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.01 | 0.00 | -432.62 | -808.85 |
T NE APARTMENT | 30-DEC-01:45 | 1507.25 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.49 | 0.00 | -432.62 | -907.56 |
T N1 APARTMENT | 30-DEC-02:00 | 1004.75 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -371.54 | 0.00 | -260.95 | -817.67 |
T N2 APARTMENT | 30-DEC-01:45 | 1005.88 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.33 | 0.00 | -260.95 | -818.00 |
T S1 APARTMENT | 12-NOV-07:01 | 1559.31 | 0.00 | 0.00 | 0.00 | 162.54 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.07 | 0.00 | -86.48 | -1859.52 |
T S2 APARTMENT | 12-NOV-07:01 | 1558.97 | 0.00 | 0.00 | 0.00 | 162.53 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.05 | 0.00 | -86.48 | -1859.20 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-DEC-02:00 | 18259.68 | 0.00 | 0.00 | 0.00 | 4362.43 | 2334.74 | 5719.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12432.00 | 0.00 | -6462.97 | -11781.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Sec1.1A-General InformationData | |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 91.75 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 91.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 155.51 | 44835.57 | 0.00 | 0.00 |
Space Cooling | 49.14 | 16519.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 197.21 | 6253.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 420.99 | 25686.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1383.11 | 155.51 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1383.11 |
Natural Gas | 0.00 | 155.51 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1538.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 15.68 |
Fans-Interior | 62.91 |
Service Water Heating | 134.30 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.55 |
Subtotal | 441.24 |
Natural Gas [MJ/m2] | |
Space Heating | 49.61 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 49.61 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.72 |
Space Heating | 10.11 |
Space Cooling | 3.19 |
Fans-Interior | 12.82 |
Service Water Heating | 27.36 |
Receptacle Equipment | 33.24 |
Miscellaneous | 2.56 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.162797 |
G NW APARTMENT DIRECT AIR | 0.128294 |
OFFICE DIRECT AIR | 0.428035 |
G NE APARTMENT DIRECT AIR | 0.084876 |
G N1 APARTMENT DIRECT AIR | 0.070386 |
G N2 APARTMENT DIRECT AIR | 0.069313 |
G S1 APARTMENT DIRECT AIR | 0.118468 |
G S2 APARTMENT DIRECT AIR | 0.121664 |
M SW APARTMENT DIRECT AIR | 0.463380 |
M NW APARTMENT DIRECT AIR | 0.366117 |
M SE APARTMENT DIRECT AIR | 0.424521 |
M NE APARTMENT DIRECT AIR | 0.270270 |
M N1 APARTMENT DIRECT AIR | 0.216077 |
M N2 APARTMENT DIRECT AIR | 0.214055 |
M S1 APARTMENT DIRECT AIR | 0.348440 |
M S2 APARTMENT DIRECT AIR | 0.349681 |
T SW APARTMENT DIRECT AIR | 0.302391 |
T NW APARTMENT DIRECT AIR | 0.233565 |
T SE APARTMENT DIRECT AIR | 0.281242 |
T NE APARTMENT DIRECT AIR | 0.169947 |
T N1 APARTMENT DIRECT AIR | 0.135124 |
T N2 APARTMENT DIRECT AIR | 0.134524 |
T S1 APARTMENT DIRECT AIR | 0.244398 |
T S2 APARTMENT DIRECT AIR | 0.245287 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.162797 |
SPLIT GNW MAIN BRANCH | 0.128294 |
SPLIT OFFICE MAIN BRANCH | 0.428035 |
SPLIT GNE MAIN BRANCH | 0.084876 |
SPLIT GN1 MAIN BRANCH | 0.070386 |
SPLIT GN2 MAIN BRANCH | 0.069313 |
SPLIT GS1 MAIN BRANCH | 0.118468 |
SPLIT GS2 MAIN BRANCH | 0.121664 |
SPLIT MSW MAIN BRANCH | 0.463380 |
SPLIT MNW MAIN BRANCH | 0.366117 |
SPLIT MSE MAIN BRANCH | 0.424521 |
SPLIT MNE MAIN BRANCH | 0.270270 |
SPLIT MN1 MAIN BRANCH | 0.216077 |
SPLIT MN2 MAIN BRANCH | 0.214055 |
SPLIT MS1 MAIN BRANCH | 0.348440 |
SPLIT MS2 MAIN BRANCH | 0.349681 |
SPLIT TSW MAIN BRANCH | 0.302391 |
SPLIT TNW MAIN BRANCH | 0.233565 |
SPLIT TSE MAIN BRANCH | 0.281242 |
SPLIT TNE MAIN BRANCH | 0.169947 |
SPLIT TN1 MAIN BRANCH | 0.135124 |
SPLIT TN2 MAIN BRANCH | 0.134524 |
SPLIT TS1 MAIN BRANCH | 0.244398 |
SPLIT TS2 MAIN BRANCH | 0.245287 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.162797 |
SPLIT GNW | 0.128294 |
SPLIT OFFICE | 0.428035 |
SPLIT GNE | 0.084876 |
SPLIT GN1 | 0.070386 |
SPLIT GN2 | 0.069313 |
SPLIT GS1 | 0.118468 |
SPLIT GS2 | 0.121664 |
SPLIT MSW | 0.463380 |
SPLIT MNW | 0.366117 |
SPLIT MSE | 0.424521 |
SPLIT MNE | 0.270270 |
SPLIT MN1 | 0.216077 |
SPLIT MN2 | 0.214055 |
SPLIT MS1 | 0.348440 |
SPLIT MS2 | 0.349681 |
SPLIT TSW | 0.302391 |
SPLIT TNW | 0.233565 |
SPLIT TSE | 0.281242 |
SPLIT TNE | 0.169947 |
SPLIT TN1 | 0.135124 |
SPLIT TN2 | 0.134524 |
SPLIT TS1 | 0.244398 |
SPLIT TS2 | 0.245287 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.162797 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.128294 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.428035 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.084876 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.070386 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.069313 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.118468 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.121664 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.463380 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.366117 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.424521 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.270270 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.216077 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.214055 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.348440 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.349681 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.302391 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.233565 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.281242 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.169947 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.135124 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.134524 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.244398 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.245287 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.162797 | 2694.87 | 0.798655 |
SPLIT GNW COOLING COIL | 0.128294 | 2123.72 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.428035 | 7085.50 | 0.798655 |
SPLIT GNE COOLING COIL | 0.084876 | 1404.99 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.070386 | 1165.14 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.069313 | 1147.37 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.118468 | 1961.07 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.121664 | 2013.97 | 0.798655 |
SPLIT MSW COOLING COIL | 0.463380 | 7670.58 | 0.798655 |
SPLIT MNW COOLING COIL | 0.366117 | 6060.53 | 0.798655 |
SPLIT MSE COOLING COIL | 0.424521 | 7027.33 | 0.798655 |
SPLIT MNE COOLING COIL | 0.270270 | 4473.92 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.216077 | 3576.85 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.214055 | 3543.37 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.348440 | 5767.92 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.349681 | 5788.45 | 0.798655 |
SPLIT TSW COOLING COIL | 0.302391 | 5005.65 | 0.798655 |
SPLIT TNW COOLING COIL | 0.233565 | 3866.33 | 0.798655 |
SPLIT TSE COOLING COIL | 0.281242 | 4655.56 | 0.798655 |
SPLIT TNE COOLING COIL | 0.169947 | 2813.22 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.135124 | 2236.79 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.134524 | 2226.85 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.244398 | 4045.65 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.245287 | 4060.37 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.162797 | 0.162797 | 0.162797 | 0.162797 | 1770.69 | 2694.87 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.128294 | 0.128294 | 0.128294 | 0.128294 | 1737.15 | 2123.72 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.428035 | 0.428035 | 0.428035 | 0.428035 | 3496.66 | 7085.50 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.084876 | 0.084876 | 0.084876 | 0.084876 | 1740.13 | 1404.99 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.070386 | 0.070386 | 0.070386 | 0.070386 | 1687.09 | 1165.14 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.069313 | 0.069313 | 0.069313 | 0.069313 | 1687.09 | 1147.37 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.118468 | 0.118468 | 0.118468 | 0.118468 | 1687.09 | 1961.07 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.121664 | 0.121664 | 0.121664 | 0.121664 | 1687.09 | 2013.97 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.463380 | 0.463380 | 0.463380 | 0.463380 | 3374.19 | 7670.58 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.366117 | 0.366117 | 0.366117 | 0.366117 | 3374.19 | 6060.53 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.424521 | 0.424521 | 0.424521 | 0.424521 | 3374.19 | 7027.33 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.270270 | 0.270270 | 0.270270 | 0.270270 | 3374.19 | 4473.92 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.216077 | 0.216077 | 0.216077 | 0.216077 | 3374.19 | 3576.85 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.214055 | 0.214055 | 0.214055 | 0.214055 | 3374.19 | 3543.37 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.348440 | 0.348440 | 0.348440 | 0.348440 | 3374.19 | 5767.92 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.349681 | 0.349681 | 0.349681 | 0.349681 | 3374.19 | 5788.45 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.302391 | 0.302391 | 0.302391 | 0.302391 | 2591.37 | 5005.65 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.233565 | 0.233565 | 0.233565 | 0.233565 | 2588.12 | 3866.33 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.281242 | 0.281242 | 0.281242 | 0.281242 | 2595.69 | 4655.56 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.169947 | 0.169947 | 0.169947 | 0.169947 | 2592.44 | 2813.22 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.135124 | 0.135124 | 0.135124 | 0.135124 | 2084.35 | 2236.79 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.134524 | 0.134524 | 0.134524 | 0.134524 | 2084.47 | 2226.85 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.244398 | 0.244398 | 0.244398 | 0.244398 | 2085.84 | 4045.65 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.245287 | 0.245287 | 0.245287 | 0.245287 | 2085.96 | 4060.37 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.162797 |
SPLIT GNW SUPPLY FAN | 0.128294 |
SPLIT OFFICE SUPPLY FAN | 0.428035 |
SPLIT GNE SUPPLY FAN | 0.084876 |
SPLIT GN1 SUPPLY FAN | 0.070386 |
SPLIT GN2 SUPPLY FAN | 0.069313 |
SPLIT GS1 SUPPLY FAN | 0.118468 |
SPLIT GS2 SUPPLY FAN | 0.121664 |
SPLIT MSW SUPPLY FAN | 0.463380 |
SPLIT MNW SUPPLY FAN | 0.366117 |
SPLIT MSE SUPPLY FAN | 0.424521 |
SPLIT MNE SUPPLY FAN | 0.270270 |
SPLIT MN1 SUPPLY FAN | 0.216077 |
SPLIT MN2 SUPPLY FAN | 0.214055 |
SPLIT MS1 SUPPLY FAN | 0.348440 |
SPLIT MS2 SUPPLY FAN | 0.349681 |
SPLIT TSW SUPPLY FAN | 0.302391 |
SPLIT TNW SUPPLY FAN | 0.233565 |
SPLIT TSE SUPPLY FAN | 0.281242 |
SPLIT TNE SUPPLY FAN | 0.169947 |
SPLIT TN1 SUPPLY FAN | 0.135124 |
SPLIT TN2 SUPPLY FAN | 0.134524 |
SPLIT TS1 SUPPLY FAN | 0.244398 |
SPLIT TS2 SUPPLY FAN | 0.245287 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1770.69 |
SPLIT GNW HEATING COIL | 1737.15 |
SPLIT OFFICE HEATING COIL | 3496.66 |
SPLIT GNE HEATING COIL | 1740.13 |
SPLIT GN1 HEATING COIL | 1687.09 |
SPLIT GN2 HEATING COIL | 1687.09 |
SPLIT GS1 HEATING COIL | 1687.09 |
SPLIT GS2 HEATING COIL | 1687.09 |
SPLIT MSW HEATING COIL | 3374.19 |
SPLIT MNW HEATING COIL | 3374.19 |
SPLIT MSE HEATING COIL | 3374.19 |
SPLIT MNE HEATING COIL | 3374.19 |
SPLIT MN1 HEATING COIL | 3374.19 |
SPLIT MN2 HEATING COIL | 3374.19 |
SPLIT MS1 HEATING COIL | 3374.19 |
SPLIT MS2 HEATING COIL | 3374.19 |
SPLIT TSW HEATING COIL | 2591.37 |
SPLIT TNW HEATING COIL | 2588.12 |
SPLIT TSE HEATING COIL | 2595.69 |
SPLIT TNE HEATING COIL | 2592.44 |
SPLIT TN1 HEATING COIL | 2084.35 |
SPLIT TN2 HEATING COIL | 2084.47 |
SPLIT TS1 HEATING COIL | 2085.84 |
SPLIT TS2 HEATING COIL | 2085.96 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.18 |
February | 21.80 | 4.25 |
March | 21.76 | 5.90 |
April | 22.50 | 8.96 |
May | 22.49 | 9.99 |
June | 23.87 | 13.31 |
July | 24.13 | 15.02 |
August | 24.22 | 15.65 |
September | 24.02 | 13.43 |
October | 22.32 | 9.33 |
November | 21.79 | 6.66 |
December | 21.71 | 4.10 |
Annual Sum or Average | 22.70 | 9.26 |
Minimum of Months | 21.71 | 4.10 |
Maximum of Months | 24.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.71 | 5.90 |
April | 22.08 | 8.96 |
May | 22.19 | 9.99 |
June | 23.71 | 13.31 |
July | 24.02 | 15.02 |
August | 24.07 | 15.65 |
September | 23.69 | 13.43 |
October | 21.91 | 9.33 |
November | 21.70 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.52 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.07 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.40 | 4.18 |
February | 21.46 | 4.25 |
March | 21.82 | 5.90 |
April | 22.80 | 8.96 |
May | 22.87 | 9.99 |
June | 23.80 | 13.31 |
July | 23.87 | 15.02 |
August | 23.90 | 15.65 |
September | 23.84 | 13.43 |
October | 22.74 | 9.33 |
November | 21.90 | 6.66 |
December | 20.97 | 4.10 |
Annual Sum or Average | 22.62 | 9.26 |
Minimum of Months | 20.97 | 4.10 |
Maximum of Months | 23.90 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.70 | 5.90 |
April | 22.04 | 8.96 |
May | 22.12 | 9.99 |
June | 23.63 | 13.31 |
July | 23.99 | 15.02 |
August | 24.05 | 15.65 |
September | 23.68 | 13.43 |
October | 21.87 | 9.33 |
November | 21.70 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.49 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.05 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.71 | 5.90 |
April | 21.92 | 8.96 |
May | 21.99 | 9.99 |
June | 23.60 | 13.31 |
July | 23.96 | 15.02 |
August | 24.02 | 15.65 |
September | 23.68 | 13.43 |
October | 21.88 | 9.33 |
November | 21.71 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.47 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.02 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.71 | 5.90 |
April | 21.92 | 8.96 |
May | 21.99 | 9.99 |
June | 23.60 | 13.31 |
July | 23.96 | 15.02 |
August | 24.02 | 15.65 |
September | 23.68 | 13.43 |
October | 21.88 | 9.33 |
November | 21.71 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.47 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.02 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.81 | 4.25 |
March | 21.77 | 5.90 |
April | 22.44 | 8.96 |
May | 22.40 | 9.99 |
June | 23.91 | 13.31 |
July | 24.17 | 15.02 |
August | 24.26 | 15.65 |
September | 24.12 | 13.43 |
October | 22.41 | 9.33 |
November | 21.83 | 6.66 |
December | 21.72 | 4.10 |
Annual Sum or Average | 22.72 | 9.26 |
Minimum of Months | 21.72 | 4.10 |
Maximum of Months | 24.26 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.81 | 4.25 |
March | 21.78 | 5.90 |
April | 22.45 | 8.96 |
May | 22.41 | 9.99 |
June | 23.90 | 13.31 |
July | 24.16 | 15.02 |
August | 24.25 | 15.65 |
September | 24.11 | 13.43 |
October | 22.42 | 9.33 |
November | 21.84 | 6.66 |
December | 21.72 | 4.10 |
Annual Sum or Average | 22.72 | 9.26 |
Minimum of Months | 21.72 | 4.10 |
Maximum of Months | 24.25 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 4.18 |
February | 22.63 | 4.25 |
March | 22.81 | 5.90 |
April | 24.19 | 8.96 |
May | 24.23 | 9.99 |
June | 24.38 | 13.31 |
July | 24.39 | 15.02 |
August | 24.40 | 15.65 |
September | 24.38 | 13.43 |
October | 24.00 | 9.33 |
November | 22.95 | 6.66 |
December | 21.85 | 4.10 |
Annual Sum or Average | 23.57 | 9.26 |
Minimum of Months | 21.85 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 4.18 |
February | 21.80 | 4.25 |
March | 22.16 | 5.90 |
April | 23.82 | 8.96 |
May | 24.07 | 9.99 |
June | 24.36 | 13.31 |
July | 24.38 | 15.02 |
August | 24.40 | 15.65 |
September | 24.29 | 13.43 |
October | 23.37 | 9.33 |
November | 22.03 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 23.19 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.52 | 4.18 |
February | 22.53 | 4.25 |
March | 22.73 | 5.90 |
April | 24.19 | 8.96 |
May | 24.22 | 9.99 |
June | 24.37 | 13.31 |
July | 24.39 | 15.02 |
August | 24.40 | 15.65 |
September | 24.37 | 13.43 |
October | 23.97 | 9.33 |
November | 22.89 | 6.66 |
December | 21.85 | 4.10 |
Annual Sum or Average | 23.54 | 9.26 |
Minimum of Months | 21.85 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.74 | 4.25 |
March | 22.02 | 5.90 |
April | 23.79 | 8.96 |
May | 24.03 | 9.99 |
June | 24.33 | 13.31 |
July | 24.36 | 15.02 |
August | 24.39 | 15.65 |
September | 24.28 | 13.43 |
October | 23.21 | 9.33 |
November | 21.91 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 23.14 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.39 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.18 |
February | 21.83 | 4.25 |
March | 22.32 | 5.90 |
April | 23.89 | 8.96 |
May | 24.16 | 9.99 |
June | 24.37 | 13.31 |
July | 24.39 | 15.02 |
August | 24.40 | 15.65 |
September | 24.34 | 13.43 |
October | 23.67 | 9.33 |
November | 22.27 | 6.66 |
December | 21.72 | 4.10 |
Annual Sum or Average | 23.28 | 9.26 |
Minimum of Months | 21.72 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 4.18 |
February | 21.83 | 4.25 |
March | 22.30 | 5.90 |
April | 23.89 | 8.96 |
May | 24.16 | 9.99 |
June | 24.37 | 13.31 |
July | 24.39 | 15.02 |
August | 24.40 | 15.65 |
September | 24.34 | 13.43 |
October | 23.65 | 9.33 |
November | 22.25 | 6.66 |
December | 21.72 | 4.10 |
Annual Sum or Average | 23.27 | 9.26 |
Minimum of Months | 21.72 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 4.18 |
February | 23.13 | 4.25 |
March | 23.26 | 5.90 |
April | 24.29 | 8.96 |
May | 24.32 | 9.99 |
June | 24.39 | 13.31 |
July | 24.40 | 15.02 |
August | 24.40 | 15.65 |
September | 24.40 | 13.43 |
October | 24.23 | 9.33 |
November | 23.51 | 6.66 |
December | 22.07 | 4.10 |
Annual Sum or Average | 23.79 | 9.26 |
Minimum of Months | 22.07 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 4.18 |
February | 23.12 | 4.25 |
March | 23.26 | 5.90 |
April | 24.29 | 8.96 |
May | 24.32 | 9.99 |
June | 24.39 | 13.31 |
July | 24.40 | 15.02 |
August | 24.40 | 15.65 |
September | 24.40 | 13.43 |
October | 24.23 | 9.33 |
November | 23.51 | 6.66 |
December | 22.07 | 4.10 |
Annual Sum or Average | 23.78 | 9.26 |
Minimum of Months | 22.07 | 4.10 |
Maximum of Months | 24.40 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.18 |
February | 22.14 | 4.25 |
March | 22.16 | 5.90 |
April | 23.34 | 8.96 |
May | 23.38 | 9.99 |
June | 24.05 | 13.31 |
July | 24.18 | 15.02 |
August | 24.25 | 15.65 |
September | 23.93 | 13.43 |
October | 22.77 | 9.33 |
November | 22.04 | 6.66 |
December | 21.78 | 4.10 |
Annual Sum or Average | 23.00 | 9.26 |
Minimum of Months | 21.78 | 4.10 |
Maximum of Months | 24.25 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.73 | 4.25 |
March | 21.87 | 5.90 |
April | 22.95 | 8.96 |
May | 23.09 | 9.99 |
June | 23.92 | 13.31 |
July | 24.09 | 15.02 |
August | 24.10 | 15.65 |
September | 23.56 | 13.43 |
October | 22.25 | 9.33 |
November | 21.74 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.73 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.10 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 4.18 |
February | 22.10 | 4.25 |
March | 22.13 | 5.90 |
April | 23.39 | 8.96 |
May | 23.41 | 9.99 |
June | 24.03 | 13.31 |
July | 24.17 | 15.02 |
August | 24.23 | 15.65 |
September | 23.93 | 13.43 |
October | 22.76 | 9.33 |
November | 22.02 | 6.66 |
December | 21.78 | 4.10 |
Annual Sum or Average | 23.00 | 9.26 |
Minimum of Months | 21.78 | 4.10 |
Maximum of Months | 24.23 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.80 | 5.90 |
April | 22.98 | 8.96 |
May | 23.07 | 9.99 |
June | 23.84 | 13.31 |
July | 24.02 | 15.02 |
August | 24.03 | 15.65 |
September | 23.55 | 13.43 |
October | 22.18 | 9.33 |
November | 21.71 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.69 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.03 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.70 | 4.25 |
March | 21.82 | 5.90 |
April | 22.87 | 8.96 |
May | 23.07 | 9.99 |
June | 23.94 | 13.31 |
July | 24.11 | 15.02 |
August | 24.10 | 15.65 |
September | 23.57 | 13.43 |
October | 22.19 | 9.33 |
November | 21.73 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.71 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.70 | 4.25 |
March | 21.82 | 5.90 |
April | 22.88 | 8.96 |
May | 23.07 | 9.99 |
June | 23.93 | 13.31 |
July | 24.11 | 15.02 |
August | 24.09 | 15.65 |
September | 23.57 | 13.43 |
October | 22.18 | 9.33 |
November | 21.73 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.71 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.18 |
February | 22.19 | 4.25 |
March | 22.23 | 5.90 |
April | 23.45 | 8.96 |
May | 23.53 | 9.99 |
June | 24.14 | 13.31 |
July | 24.25 | 15.02 |
August | 24.31 | 15.65 |
September | 24.06 | 13.43 |
October | 22.92 | 9.33 |
November | 22.14 | 6.66 |
December | 21.81 | 4.10 |
Annual Sum or Average | 23.09 | 9.26 |
Minimum of Months | 21.81 | 4.10 |
Maximum of Months | 24.31 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.18 |
February | 22.19 | 4.25 |
March | 22.23 | 5.90 |
April | 23.45 | 8.96 |
May | 23.53 | 9.99 |
June | 24.14 | 13.31 |
July | 24.25 | 15.02 |
August | 24.31 | 15.65 |
September | 24.06 | 13.43 |
October | 22.93 | 9.33 |
November | 22.14 | 6.66 |
December | 21.81 | 4.10 |
Annual Sum or Average | 23.09 | 9.26 |
Minimum of Months | 21.81 | 4.10 |
Maximum of Months | 24.31 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 4.18 |
February | 22.17 | 4.25 |
March | 22.46 | 5.90 |
April | 24.36 | 8.96 |
May | 24.56 | 9.99 |
June | 25.66 | 13.31 |
July | 25.96 | 15.02 |
August | 25.93 | 15.65 |
September | 25.24 | 13.43 |
October | 23.28 | 9.33 |
November | 22.23 | 6.66 |
December | 21.66 | 4.10 |
Annual Sum or Average | 23.80 | 9.26 |
Minimum of Months | 21.66 | 4.10 |
Maximum of Months | 25.96 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | 4.18 |
February | 20.58 | 4.25 |
March | 20.87 | 5.90 |
April | 21.94 | 8.96 |
May | 22.17 | 9.99 |
June | 24.24 | 13.31 |
July | 24.84 | 15.02 |
August | 24.99 | 15.65 |
September | 24.48 | 13.43 |
October | 21.98 | 9.33 |
November | 20.98 | 6.66 |
December | 20.38 | 4.10 |
Annual Sum or Average | 22.34 | 9.26 |
Minimum of Months | 20.38 | 4.10 |
Maximum of Months | 24.99 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 4.18 |
February | 24.03 | 4.25 |
March | 24.33 | 5.90 |
April | 26.12 | 8.96 |
May | 26.32 | 9.99 |
June | 26.66 | 13.31 |
July | 26.75 | 15.02 |
August | 26.77 | 15.65 |
September | 26.60 | 13.43 |
October | 25.68 | 9.33 |
November | 24.38 | 6.66 |
December | 23.31 | 4.10 |
Annual Sum or Average | 25.41 | 9.26 |
Minimum of Months | 23.31 | 4.10 |
Maximum of Months | 26.77 | 15.65 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:32
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.115963E+12 | 73811.755 | 08-JAN-18:45 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30020.841 | 0.000 | 0.000 | 0.000 |
February | 0.104596E+12 | 72413.973 | 06-FEB-18:00 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28623.060 | 0.000 | 0.000 | 0.000 |
March | 0.115155E+12 | 72508.448 | 09-MAR-18:45 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28717.535 | 0.000 | 0.000 | 0.000 |
April | 0.114151E+12 | 75989.478 | 30-APR-18:15 | 9689.078 | 23563.017 | 6253.396 | 0.000 | 11321.604 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25162.384 | 0.000 | 0.000 | 0.000 |
May | 0.116634E+12 | 74428.958 | 02-MAY-17:00 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 3625.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29521.022 | 0.000 | 0.000 | 0.000 |
June | 0.116189E+12 | 80341.853 | 13-JUN-17:30 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 15069.115 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23990.155 | 0.000 | 0.000 | 0.000 |
July | 0.121657E+12 | 83488.510 | 22-JUL-17:15 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 16519.656 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25686.270 | 0.000 | 0.000 | 0.000 |
August | 0.121908E+12 | 80866.297 | 17-AUG-17:15 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 11604.508 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27979.206 | 0.000 | 0.000 | 0.000 |
September | 0.115957E+12 | 77875.028 | 13-SEP-17:15 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 11377.367 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25215.078 | 0.000 | 0.000 | 0.000 |
October | 0.114848E+12 | 71905.844 | 25-OCT-17:00 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 835.875 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27279.055 | 0.000 | 0.000 | 0.000 |
November | 0.110714E+12 | 73068.972 | 27-NOV-18:30 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29278.059 | 0.000 | 0.000 | 0.000 |
December | 0.115340E+12 | 71699.177 | 04-DEC-18:45 | 8572.775 | 26456.413 | 6253.396 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27908.263 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.138311E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.104596E+12 | 71699.177 | 8572.775 | 23563.017 | 6253.396 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23990.155 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.121908E+12 | 83488.510 | 9689.078 | 26456.413 | 6253.396 | 0.000 | 16519.656 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30020.841 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:32
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.321544E+11 | 43885.602 | 10-JAN-05:00 | 43885.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 43885.602 |
February | 0.259112E+11 | 39343.772 | 17-FEB-03:00 | 39343.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 39343.772 |
March | 0.178306E+11 | 23686.537 | 04-MAR-03:00 | 23686.537 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23686.537 |
April | 0.459242E+10 | 12496.826 | 01-APR-03:00 | 12496.826 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12496.826 |
May | 0.321431E+10 | 13358.111 | 05-MAY-03:00 | 13358.111 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13358.111 |
June | 0.687649E+08 | 4040.387 | 08-JUN-03:00 | 4040.387 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4040.387 |
July | 2035689.900 | 412.411 | 05-JUL-03:00 | 412.411 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 412.411 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.854254E+08 | 2185.844 | 20-SEP-03:00 | 2185.844 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2185.844 |
October | 0.613261E+10 | 11595.760 | 28-OCT-06:00 | 11595.760 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11595.760 |
November | 0.202654E+11 | 35620.526 | 29-NOV-03:00 | 35620.526 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35620.526 |
December | 0.452513E+11 | 44835.565 | 30-DEC-01:00 | 44835.565 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44835.565 |
Annual Sum or Average | 0.155509E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.452513E+11 | 44835.565 | 44835.565 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44835.565 |