Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2018-10-19 09:20:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1920.93 | 612.81 | 680.22 |
Net Site Energy | 1920.93 | 612.81 | 680.22 |
Total Source Energy | 5171.88 | 1649.93 | 1831.42 |
Net Source Energy | 5171.88 | 1649.93 | 1831.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 437.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 80.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 438.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1483.24 | 437.68 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 437.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 80.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 438.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 271.77 | 154.99 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 525.23 | 154.99 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 244.83 | 139.63 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 473.18 | 139.63 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1483.24 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1483.24 | 100.00 |
Total On-Site and Utility Electric Sources | 1483.24 | 100.00 |
Total Electricity End Uses | 1483.24 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 41.25 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2873.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-17:30 | 10-JAN-23:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 127311.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19649.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7884.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28486.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 91049.64 | 127311.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 127311.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19649.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7884.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28486.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 474.45 | 0.00 | 0.00 | 0.00 |
Cooling | 254.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 787.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1388.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4697.43 | 474.45 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 168.01 | 0.00 | 0.00 | 0.00 |
Cooling | 90.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 491.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1663.41 | 168.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 168.01 | 0.00 | 0.00 | 0.00 |
Cooling | 90.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 491.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1663.41 | 168.01 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.60 | 83.60 | 39.36 | |
Exterior Lighting Total | 2508.33 | 39.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3315.72 | 2648.12 | 667.60 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3040.94 | 2428.66 | 612.28 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8036.78 | 6418.62 | 1618.16 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2113.03 | 1687.59 | 425.45 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1756.90 | 1403.15 | 353.74 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1734.99 | 1385.66 | 349.33 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2119.77 | 1692.97 | 426.80 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2176.53 | 1738.29 | 438.23 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9206.45 | 7352.78 | 1853.67 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8363.39 | 6679.47 | 1683.93 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8199.04 | 6548.20 | 1650.83 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6259.16 | 4998.91 | 1260.25 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5117.06 | 4086.77 | 1030.29 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5079.57 | 4056.83 | 1022.75 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6229.75 | 4975.42 | 1254.33 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6253.72 | 4994.56 | 1259.15 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6080.76 | 4856.43 | 1224.33 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5453.53 | 4355.49 | 1098.04 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5656.54 | 4517.63 | 1138.92 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4244.24 | 3389.69 | 854.56 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3387.86 | 2705.73 | 682.13 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3350.06 | 2675.54 | 674.52 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4668.40 | 3728.44 | 939.96 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4683.89 | 3740.81 | 943.08 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3158.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2897.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7656.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2013.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1673.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1652.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2019.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2073.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8770.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7967.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7810.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5962.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4874.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4839.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5934.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5957.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5792.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5195.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5388.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4043.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3227.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3191.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4447.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4462.1 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 3715.45 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 3650.10 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 6578.63 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 3638.22 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2785.46 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2785.18 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2805.01 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2940.84 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 7233.34 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 7190.91 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 7202.18 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 7159.71 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 5079.33 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 5078.58 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 5124.95 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 5124.21 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 5405.92 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 5385.11 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 5389.39 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 5368.56 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 4288.08 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 4287.66 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 4307.84 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 4307.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 224.36 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.77 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 543.81 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 142.98 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.88 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 117.40 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 143.44 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 147.28 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 622.96 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 565.92 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 554.79 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 423.53 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.25 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 343.71 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 421.54 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 423.16 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 411.46 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 369.02 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 382.75 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 287.19 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 229.24 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.68 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 315.89 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 316.94 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1864.25 | 2237.10 | 0.167 | 0.200 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
G NW APARTMENT | 1709.75 | 2051.70 | 0.153 | 0.184 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36 | 0.00627 |
OFFICE | 4421.10 | 5305.32 | 0.405 | 0.486 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60 | 0.00627 |
G NE APARTMENT | 1188.04 | 1425.65 | 0.106 | 0.128 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.16 | 0.00627 |
G N1 APARTMENT | 987.80 | 1185.35 | 0.088 | 0.106 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
G N2 APARTMENT | 975.48 | 1170.58 | 0.087 | 0.105 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
G S1 APARTMENT | 1191.83 | 1430.20 | 0.107 | 0.128 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
G S2 APARTMENT | 1223.74 | 1468.49 | 0.110 | 0.131 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
M SW APARTMENT | 5176.31 | 6211.57 | 0.463 | 0.556 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
M NW APARTMENT | 4702.29 | 5642.75 | 0.421 | 0.505 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.76 | 0.00627 |
M SE APARTMENT | 4609.94 | 5531.93 | 0.413 | 0.495 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
M NE APARTMENT | 3519.23 | 4223.08 | 0.315 | 0.378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
M N1 APARTMENT | 2877.02 | 3452.42 | 0.258 | 0.309 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
M N2 APARTMENT | 2855.94 | 3427.13 | 0.256 | 0.307 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
M S1 APARTMENT | 3502.67 | 4203.20 | 0.314 | 0.376 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
M S2 APARTMENT | 3516.14 | 4219.37 | 0.315 | 0.378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
T SW APARTMENT | 3418.97 | 4102.76 | 0.306 | 0.367 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 32.12 | 0.00627 |
T NW APARTMENT | 3066.25 | 3679.51 | 0.275 | 0.329 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
T SE APARTMENT | 3180.45 | 3816.54 | 0.285 | 0.342 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
T NE APARTMENT | 2386.37 | 2863.65 | 0.214 | 0.256 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40 | 0.00627 |
T N1 APARTMENT | 1904.81 | 2285.78 | 0.171 | 0.205 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
T N2 APARTMENT | 1883.56 | 2260.27 | 0.169 | 0.202 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
T S1 APARTMENT | 2624.82 | 3149.78 | 0.235 | 0.282 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40 | 0.00627 |
T S2 APARTMENT | 2633.52 | 3160.23 | 0.236 | 0.283 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1955.24 | 2346.29 | 0.064 | 0.077 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G NW APARTMENT | 1941.69 | 2330.03 | 0.064 | 0.077 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
OFFICE | 3924.79 | 4709.75 | 0.125 | 0.150 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G NE APARTMENT | 1931.65 | 2317.98 | 0.064 | 0.076 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G N1 APARTMENT | 1210.50 | 1452.60 | 0.040 | 0.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G N2 APARTMENT | 1210.27 | 1452.32 | 0.040 | 0.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G S1 APARTMENT | 1227.03 | 1472.44 | 0.040 | 0.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G S2 APARTMENT | 1341.90 | 1610.28 | 0.044 | 0.053 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
M SW APARTMENT | 3826.91 | 4592.29 | 0.126 | 0.151 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M NW APARTMENT | 3791.03 | 4549.23 | 0.125 | 0.150 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M SE APARTMENT | 3800.55 | 4560.67 | 0.125 | 0.150 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M NE APARTMENT | 3764.64 | 4517.57 | 0.124 | 0.149 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M N1 APARTMENT | 2005.32 | 2406.39 | 0.066 | 0.079 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M N2 APARTMENT | 2004.70 | 2405.64 | 0.066 | 0.079 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M S1 APARTMENT | 2043.90 | 2452.69 | 0.067 | 0.081 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
M S2 APARTMENT | 2043.28 | 2451.94 | 0.067 | 0.081 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T SW APARTMENT | 3426.55 | 4111.86 | 0.113 | 0.135 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T NW APARTMENT | 3408.96 | 4090.75 | 0.112 | 0.135 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T SE APARTMENT | 3412.57 | 4095.09 | 0.112 | 0.135 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T NE APARTMENT | 3394.96 | 4073.95 | 0.112 | 0.134 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T N1 APARTMENT | 2481.22 | 2977.47 | 0.082 | 0.098 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T N2 APARTMENT | 2480.87 | 2977.04 | 0.082 | 0.098 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T S1 APARTMENT | 2497.94 | 2997.52 | 0.082 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
T S2 APARTMENT | 2497.58 | 2997.10 | 0.082 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -27.60 | 0.00034 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.20 | 0.20 | 0.08 | 0.08 |
SPLIT GNW | 0.18 | 0.18 | 0.08 | 0.08 |
SPLIT OFFICE | 0.49 | 0.49 | 0.15 | 0.15 |
SPLIT GNE | 0.13 | 0.13 | 0.08 | 0.08 |
SPLIT GN1 | 0.11 | 0.11 | 0.05 | 0.05 |
SPLIT GN2 | 0.10 | 0.10 | 0.05 | 0.05 |
SPLIT GS1 | 0.13 | 0.13 | 0.05 | 0.05 |
SPLIT GS2 | 0.13 | 0.13 | 0.05 | 0.05 |
SPLIT MSW | 0.56 | 0.56 | 0.15 | 0.15 |
SPLIT MNW | 0.51 | 0.51 | 0.15 | 0.15 |
SPLIT MSE | 0.50 | 0.50 | 0.15 | 0.15 |
SPLIT MNE | 0.38 | 0.38 | 0.15 | 0.15 |
SPLIT MN1 | 0.31 | 0.31 | 0.08 | 0.08 |
SPLIT MN2 | 0.31 | 0.31 | 0.08 | 0.08 |
SPLIT MS1 | 0.38 | 0.38 | 0.08 | 0.08 |
SPLIT MS2 | 0.38 | 0.38 | 0.08 | 0.08 |
SPLIT TSW | 0.37 | 0.37 | 0.14 | 0.14 |
SPLIT TNW | 0.33 | 0.33 | 0.13 | 0.13 |
SPLIT TSE | 0.34 | 0.34 | 0.13 | 0.13 |
SPLIT TNE | 0.26 | 0.26 | 0.13 | 0.13 |
SPLIT TN1 | 0.20 | 0.20 | 0.10 | 0.10 |
SPLIT TN2 | 0.20 | 0.20 | 0.10 | 0.10 |
SPLIT TS1 | 0.28 | 0.28 | 0.10 | 0.10 |
SPLIT TS2 | 0.28 | 0.28 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2298.00 | 6553.50 | 1540.50 |
G NW APARTMENT | 2622.25 | 6818.75 | 2180.50 |
OFFICE | 327.50 | 1711.75 | 268.25 |
G NE APARTMENT | 2654.50 | 6839.50 | 2171.00 |
G N1 APARTMENT | 1850.00 | 6981.25 | 1594.25 |
G N2 APARTMENT | 1850.50 | 6981.75 | 1593.00 |
G S1 APARTMENT | 1486.75 | 6595.25 | 983.75 |
G S2 APARTMENT | 1554.00 | 6622.25 | 1076.75 |
M SW APARTMENT | 2233.50 | 5018.50 | 671.50 |
M NW APARTMENT | 2304.00 | 5810.50 | 1141.25 |
M SE APARTMENT | 2267.75 | 5020.50 | 662.75 |
M NE APARTMENT | 2348.75 | 5861.75 | 1119.75 |
M N1 APARTMENT | 1522.75 | 5786.25 | 676.00 |
M N2 APARTMENT | 1526.50 | 5794.25 | 676.00 |
M S1 APARTMENT | 1677.75 | 4730.50 | 348.25 |
M S2 APARTMENT | 1680.50 | 4732.00 | 348.25 |
T SW APARTMENT | 3558.50 | 5808.00 | 2054.75 |
T NW APARTMENT | 3980.75 | 6327.25 | 2735.75 |
T SE APARTMENT | 3587.75 | 5769.00 | 2038.50 |
T NE APARTMENT | 4002.00 | 6325.75 | 2702.50 |
T N1 APARTMENT | 3424.50 | 6395.75 | 2342.25 |
T N2 APARTMENT | 3429.00 | 6397.75 | 2344.00 |
T S1 APARTMENT | 2981.00 | 5739.00 | 1598.00 |
T S2 APARTMENT | 2983.50 | 5733.00 | 1598.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4852.25 | 7087.75 | 2873.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.50 | 0.00 | 4.50 | 0.00 |
G NW APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
OFFICE | 10.25 | 0.00 | 0.25 | 0.00 |
G NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G N1 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
G N2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
G S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
G S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NW APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M SE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M NE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M N1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M N2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M S1 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M S2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
T SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T N1 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
T N2 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
T S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 51.25 | 0.50 | 41.25 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.365 | 0.133 | 0.000 | 0.066 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.132 | 0.000 | 0.065 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.518 | 0.151 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.132 | 0.000 | 0.065 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.065 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.065 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.066 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.066 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.083 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.191 | 0.000 | 0.083 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.083 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.191 | 0.000 | 0.083 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.115 | 0.000 | 0.083 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.115 | 0.000 | 0.083 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.083 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.083 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.101 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.101 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.101 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.101 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.101 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.101 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.101 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.101 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.500 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1483.24 | 21255.26 | 12-JAN-03:30 | 91049.64 | 07-AUG-17:30 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 438.33 | 0.00 | 01-JAN-00:15 | 32883.59 | 23-FEB-07:15 |
WaterSystems:Electricity | 438.33 | 0.00 | 01-JAN-00:15 | 32883.59 | 23-FEB-07:15 |
Water Heater:WaterSystems:Electricity | 438.33 | 0.00 | 01-JAN-00:15 | 32883.59 | 23-FEB-07:15 |
Fans:Electricity | 248.66 | 7884.96 | 03-JAN-06:15 | 7884.96 | 04-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
ElectricityPurchased:Plant | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
Cogeneration:ElectricityPurchased | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
ElectricityNet:Plant | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
Cogeneration:ElectricityNet | 1483.24 | 21255.26 | 01-JAN-03:15 | 91049.64 | 07-AUG-17:30 |
ExteriorLights:Electricity | 39.36 | 0.00 | 01-JAN-08:30 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.36 | 0.00 | 01-JAN-08:30 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 329.13 | 7884.96 | 03-JAN-06:15 | 32139.29 | 17-JUL-16:15 |
General:Fans:Electricity | 248.66 | 7884.96 | 03-JAN-06:15 | 7884.96 | 04-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 80.47 | 0.00 | 01-JAN-00:15 | 24254.33 | 17-JUL-16:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 437.68 | 0.00 | 20-FEB-15:45 | 127311.21 | 10-JAN-23:15 |
Gas:HVAC | 437.68 | 0.00 | 20-FEB-15:45 | 127311.21 | 10-JAN-23:15 |
Heating:Gas | 437.68 | 0.00 | 20-FEB-15:45 | 127311.21 | 10-JAN-23:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1198.48 | 1541.09 | 01-APR-12:30 | 163075.42 | 10-JAN-23:15 |
EnergyTransfer:Building | 534.84 | 1520.94 | 01-APR-12:30 | 67185.01 | 17-JUL-16:15 |
EnergyTransfer:Zone:G SW APARTMENT | 13.20 | 0.09 | 17-NOV-09:00 | 2164.05 | 02-SEP-15:15 |
Heating:EnergyTransfer | 188.68 | 0.00 | 20-FEB-18:30 | 61435.04 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 6.27 | 0.00 | 01-JAN-10:30 | 2026.20 | 11-JAN-08:15 |
Cooling:EnergyTransfer | 346.16 | 0.00 | 05-JAN-08:00 | 67185.01 | 17-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.93 | 0.00 | 01-JAN-00:15 | 2164.05 | 02-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.40 | 0.02 | 30-MAY-04:00 | 2034.72 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 8.75 | 0.00 | 14-JAN-15:15 | 2034.72 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.65 | 0.00 | 01-JAN-00:15 | 1924.24 | 17-JUL-17:45 |
EnergyTransfer:Zone:OFFICE | 20.28 | 0.01 | 04-NOV-00:30 | 4177.56 | 31-DEC-07:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.75 | 0.00 | 01-JAN-00:15 | 4177.56 | 31-DEC-07:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 19.53 | 0.00 | 02-JAN-07:45 | 3562.37 | 10-AUG-13:00 |
EnergyTransfer:Zone:G NE APARTMENT | 13.57 | 0.01 | 30-MAY-11:30 | 2027.78 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 8.55 | 0.00 | 12-FEB-16:15 | 2027.78 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.02 | 0.00 | 01-JAN-00:15 | 1387.37 | 17-JUL-18:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.83 | 0.00 | 28-MAY-09:15 | 1249.37 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 4.27 | 0.00 | 01-JAN-17:15 | 1249.37 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.56 | 0.00 | 01-JAN-00:15 | 1106.22 | 17-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.83 | 0.14 | 18-AUG-12:00 | 1249.43 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 4.26 | 0.00 | 01-JAN-17:15 | 1249.43 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.57 | 0.00 | 01-JAN-00:15 | 1094.51 | 17-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 9.70 | 0.01 | 23-OCT-11:45 | 1522.58 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 2.54 | 0.00 | 01-JAN-09:15 | 1242.43 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.16 | 0.00 | 01-JAN-00:15 | 1522.58 | 02-SEP-14:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 9.94 | 0.07 | 17-NOV-15:15 | 1505.24 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 2.98 | 0.00 | 01-JAN-09:30 | 1344.02 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 6.96 | 0.00 | 01-JAN-00:15 | 1505.24 | 02-SEP-14:15 |
EnergyTransfer:Zone:M SW APARTMENT | 36.91 | 0.03 | 16-NOV-22:30 | 5909.30 | 02-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 7.20 | 0.00 | 01-JAN-00:15 | 4006.80 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 29.71 | 0.00 | 03-JAN-05:45 | 5909.30 | 02-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 32.12 | 0.03 | 07-NOV-20:45 | 5196.11 | 14-JUL-18:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 12.46 | 0.00 | 01-JAN-14:30 | 4131.69 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 19.66 | 0.00 | 01-JAN-00:15 | 5196.11 | 14-JUL-18:30 |
EnergyTransfer:Zone:M SE APARTMENT | 37.85 | 0.00 | 12-APR-11:30 | 5403.79 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 7.08 | 0.00 | 01-JAN-00:15 | 3984.46 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 30.77 | 0.00 | 03-JAN-05:30 | 5403.79 | 02-SEP-14:15 |
EnergyTransfer:Zone:M NE APARTMENT | 33.02 | 0.15 | 28-MAR-03:15 | 4109.01 | 10-JAN-23:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 12.18 | 0.00 | 01-JAN-16:15 | 4109.01 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 20.84 | 0.00 | 01-JAN-00:15 | 3987.85 | 17-JUL-18:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 24.51 | 0.03 | 24-APR-13:45 | 3163.63 | 17-JUL-18:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 3.94 | 0.00 | 01-JAN-00:15 | 2135.79 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 20.58 | 0.00 | 01-JAN-01:00 | 3163.63 | 17-JUL-18:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 24.52 | 0.01 | 15-OCT-10:00 | 3144.58 | 17-JUL-18:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 3.93 | 0.00 | 01-JAN-00:15 | 2135.81 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 20.59 | 0.00 | 01-JAN-01:00 | 3144.58 | 17-JUL-18:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 34.59 | 0.26 | 07-APR-08:45 | 4398.59 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.71 | 0.00 | 01-JAN-00:15 | 2027.03 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 32.89 | 0.00 | 05-JAN-04:00 | 4398.59 | 02-SEP-14:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 34.60 | 0.48 | 07-APR-08:45 | 4408.02 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.71 | 0.00 | 01-JAN-00:15 | 2027.07 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 32.90 | 0.00 | 05-JAN-04:00 | 4408.02 | 02-SEP-14:15 |
EnergyTransfer:Zone:T SW APARTMENT | 26.03 | 0.00 | 16-AUG-24:00 | 3913.68 | 17-JUL-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 13.98 | 0.00 | 01-JAN-11:00 | 3762.98 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.06 | 0.00 | 01-JAN-00:15 | 3913.68 | 17-JUL-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 26.16 | 0.00 | 15-MAY-11:30 | 3791.72 | 10-JAN-23:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 17.80 | 0.00 | 12-FEB-16:00 | 3791.72 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 8.36 | 0.00 | 01-JAN-00:15 | 3543.63 | 17-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 25.89 | 0.01 | 04-JUL-03:45 | 3745.68 | 10-JAN-23:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 13.69 | 0.00 | 01-JAN-10:15 | 3745.68 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 12.20 | 0.00 | 01-JAN-00:15 | 3538.13 | 02-SEP-14:15 |
EnergyTransfer:Zone:T NE APARTMENT | 26.03 | 0.02 | 09-SEP-03:30 | 3774.36 | 10-JAN-23:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 17.43 | 0.00 | 12-FEB-15:30 | 3774.36 | 10-JAN-23:15 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 8.60 | 0.00 | 01-JAN-00:15 | 2824.46 | 17-JUL-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 18.34 | 0.05 | 10-SEP-06:45 | 2681.46 | 11-JAN-01:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 10.92 | 0.00 | 01-JAN-18:15 | 2681.46 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 7.42 | 0.00 | 01-JAN-00:15 | 2317.41 | 17-JUL-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 18.36 | 0.01 | 07-JUN-14:00 | 2681.17 | 11-JAN-01:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 10.92 | 0.00 | 01-JAN-18:15 | 2681.17 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 7.44 | 0.00 | 01-JAN-00:15 | 2305.61 | 17-JUL-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.06 | 0.05 | 18-AUG-00:30 | 3006.25 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 7.69 | 0.00 | 01-JAN-10:00 | 2661.19 | 11-JAN-00:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 11.37 | 0.00 | 01-JAN-00:15 | 3006.25 | 02-SEP-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.09 | 0.02 | 03-MAY-01:15 | 3011.86 | 02-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 7.69 | 0.00 | 01-JAN-10:00 | 2660.90 | 11-JAN-00:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 11.40 | 0.00 | 01-JAN-00:15 | 3011.86 | 02-SEP-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 663.64 | 0.00 | 11-MAR-17:00 | 101848.97 | 10-JAN-23:15 |
HeatingCoils:EnergyTransfer | 350.15 | 0.00 | 20-FEB-15:45 | 101848.97 | 10-JAN-23:15 |
CoolingCoils:EnergyTransfer | 313.49 | 0.00 | 01-JAN-00:15 | 86380.42 | 17-JUL-16:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 6.271 | -6.928 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 14.039 | 0.000 | 0.090 | 0.000 | 0.000 | -9.448 | 0.000 | -5.779 | -16.746 |
G NW APARTMENT | 8.754 | -4.650 | 0.000 | 0.000 | 3.900 | 2.413 | 12.213 | 6.258 | 0.000 | 0.090 | 0.000 | 0.000 | -9.897 | 0.000 | -5.667 | -13.414 |
OFFICE | 0.749 | -19.532 | 0.000 | 0.000 | 0.531 | 21.914 | 7.534 | 14.286 | 0.000 | 0.082 | 0.000 | 0.000 | -8.840 | 0.000 | -4.872 | -11.852 |
G NE APARTMENT | 8.548 | -5.022 | 0.000 | 0.000 | 3.911 | 2.413 | 12.213 | 6.380 | 0.000 | 0.090 | 0.000 | 0.000 | -9.600 | 0.000 | -5.654 | -13.280 |
G N1 APARTMENT | 4.267 | -4.558 | 0.000 | 0.000 | 3.907 | 2.413 | 12.213 | 2.079 | 0.000 | 0.062 | 0.000 | 0.000 | -6.152 | 0.000 | -3.655 | -10.575 |
G N2 APARTMENT | 4.263 | -4.565 | 0.000 | 0.000 | 3.907 | 2.413 | 12.213 | 2.078 | 0.000 | 0.062 | 0.000 | 0.000 | -6.150 | 0.000 | -3.655 | -10.565 |
G S1 APARTMENT | 2.541 | -7.162 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 9.967 | 0.000 | 0.062 | 0.000 | 0.000 | -5.739 | 0.000 | -3.771 | -14.396 |
G S2 APARTMENT | 2.975 | -6.963 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 9.969 | 0.000 | 0.062 | 0.000 | 0.000 | -5.728 | 0.000 | -3.771 | -15.040 |
M SW APARTMENT | 7.201 | -29.708 | 0.000 | 0.000 | 3.761 | 2.413 | 12.213 | 13.580 | 0.000 | 0.127 | 9.024 | 0.000 | -10.160 | 0.000 | -8.451 | -0.001 |
M NW APARTMENT | 12.457 | -19.665 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 5.938 | 0.000 | 0.126 | 1.461 | 0.000 | -10.504 | 0.000 | -8.259 | -0.000 |
M SE APARTMENT | 7.081 | -30.766 | 0.000 | 0.000 | 3.768 | 2.413 | 12.213 | 13.761 | 0.000 | 0.127 | 9.753 | 0.000 | -9.904 | 0.000 | -8.445 | -0.001 |
M NE APARTMENT | 12.179 | -20.838 | 0.000 | 0.000 | 3.833 | 2.413 | 12.213 | 6.056 | 0.000 | 0.126 | 2.426 | 0.000 | -10.170 | 0.000 | -8.239 | -0.000 |
M N1 APARTMENT | 3.935 | -20.580 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 1.888 | 0.000 | 0.085 | 8.189 | 0.000 | -6.595 | 0.000 | -5.357 | -0.000 |
M N2 APARTMENT | 3.930 | -20.588 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 1.887 | 0.000 | 0.085 | 8.198 | 0.000 | -6.593 | 0.000 | -5.356 | -0.000 |
M S1 APARTMENT | 1.708 | -32.886 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 9.660 | 0.000 | 0.086 | 14.834 | 0.000 | -6.224 | 0.000 | -5.530 | -0.000 |
M S2 APARTMENT | 1.706 | -32.899 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 9.659 | 0.000 | 0.086 | 14.849 | 0.000 | -6.223 | 0.000 | -5.530 | -0.000 |
T SW APARTMENT | 13.977 | -12.056 | 0.000 | 0.000 | 3.839 | 2.413 | 12.213 | 13.518 | 0.000 | 0.169 | 0.000 | 0.000 | -9.627 | 0.000 | -10.823 | -13.624 |
T NW APARTMENT | 17.798 | -8.359 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 5.906 | 0.000 | 0.169 | 0.000 | 0.000 | -10.024 | 0.000 | -10.633 | -13.354 |
T SE APARTMENT | 13.690 | -12.199 | 0.000 | 0.000 | 3.843 | 2.413 | 12.213 | 13.715 | 0.000 | 0.169 | 0.000 | 0.000 | -9.400 | 0.000 | -10.838 | -13.607 |
T NE APARTMENT | 17.431 | -8.596 | 0.000 | 0.000 | 3.884 | 2.413 | 12.213 | 6.046 | 0.000 | 0.169 | 0.000 | 0.000 | -9.720 | 0.000 | -10.628 | -13.212 |
T N1 APARTMENT | 10.919 | -7.423 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 1.903 | 0.000 | 0.115 | 0.000 | 0.000 | -6.242 | 0.000 | -6.807 | -10.964 |
T N2 APARTMENT | 10.923 | -7.441 | 0.000 | 0.000 | 3.875 | 2.413 | 12.213 | 1.901 | 0.000 | 0.115 | 0.000 | 0.000 | -6.240 | 0.000 | -6.808 | -10.951 |
T S1 APARTMENT | 7.688 | -11.372 | 0.000 | 0.000 | 3.823 | 2.413 | 12.213 | 9.641 | 0.000 | 0.116 | 0.000 | 0.000 | -5.883 | 0.000 | -6.998 | -11.641 |
T S2 APARTMENT | 7.693 | -11.399 | 0.000 | 0.000 | 3.823 | 2.413 | 12.213 | 9.639 | 0.000 | 0.116 | 0.000 | 0.000 | -5.881 | 0.000 | -7.000 | -11.616 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.079 | 0.000 | 0.009 | 0.000 | 0.000 | -1.184 | 0.000 | -1.737 | -14.237 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.292 | 0.000 | 0.296 | 3.543 | 0.000 | -3.196 | 0.000 | -24.270 | -0.001 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.079 | 0.000 | 0.008 | 0.000 | 0.000 | -1.302 | 0.000 | -1.439 | -14.416 |
Total Facility | 188.684 | -346.157 | 0.000 | 0.000 | 88.857 | 128.627 | 294.692 | 190.205 | 0.000 | 2.900 | 72.277 | 0.000 | -196.625 | 0.000 | -189.969 | -233.495 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 02-SEP-15:15 | 0.00 | -2163.92 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2851.31 | 0.00 | 122.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1430.13 |
G NW APARTMENT | 17-JUL-17:23 | 0.00 | -1924.35 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 2088.60 | 0.00 | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1149.89 |
OFFICE | 10-AUG-13:00 | 0.00 | -3561.64 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2236.76 | 0.00 | 133.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1042.91 |
G NE APARTMENT | 17-JUL-18:30 | 0.00 | -1387.37 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 827.85 | 0.00 | 35.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -395.83 |
G N1 APARTMENT | 17-JUL-18:30 | 0.00 | -1106.22 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 621.27 | 0.00 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -456.25 |
G N2 APARTMENT | 17-JUL-18:30 | 0.00 | -1094.51 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 621.43 | 0.00 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -468.12 |
G S1 APARTMENT | 02-SEP-14:15 | 0.00 | -1522.39 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1901.25 | 0.00 | 85.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.66 |
G S2 APARTMENT | 02-SEP-14:15 | 0.00 | -1505.05 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1901.55 | 0.00 | 85.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.31 |
M SW APARTMENT | 02-SEP-15:15 | 0.00 | -5908.97 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2829.54 | 0.00 | 175.14 | 2283.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 14-JUL-18:30 | 0.00 | -5196.51 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 2175.05 | 0.00 | 83.63 | 2018.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 02-SEP-14:15 | 0.00 | -5403.10 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2161.35 | 0.00 | 203.03 | 2547.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 17-JUL-18:30 | 0.00 | -3987.82 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 817.40 | 0.00 | 51.16 | 2199.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 17-JUL-18:30 | 0.00 | -3163.61 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 613.57 | 0.00 | 30.86 | 1599.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 17-JUL-18:30 | 0.00 | -3144.56 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 613.68 | 0.00 | 30.86 | 1580.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 02-SEP-14:15 | 0.00 | -4398.06 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1885.94 | 0.00 | 122.46 | 1898.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 02-SEP-14:15 | 0.00 | -4407.49 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1885.88 | 0.00 | 122.46 | 1907.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 17-JUL-16:04 | 0.00 | -3914.76 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2240.48 | 0.00 | 187.46 | 669.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 17-JUL-17:06 | 0.00 | -3544.39 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2057.24 | 0.00 | 130.01 | 432.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 02-SEP-14:15 | 0.00 | -3537.69 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2123.76 | 0.00 | 267.43 | 655.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 17-JUL-16:09 | 0.00 | -2824.96 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 769.33 | 0.00 | 187.46 | 1050.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 17-JUL-16:13 | 0.00 | -2318.52 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 467.79 | 0.00 | 113.07 | 920.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 17-JUL-16:11 | 0.00 | -2306.65 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 467.93 | 0.00 | 113.07 | 908.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 02-SEP-14:15 | 0.00 | -3005.91 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1860.20 | 0.00 | 161.32 | 492.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 02-SEP-14:15 | 0.00 | -3011.52 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1860.10 | 0.00 | 161.32 | 498.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-16:04 | 0.00 | -67206.73 | 0.00 | 0.00 | 1949.42 | 5316.35 | 14137.32 | 25202.78 | 0.00 | 5377.52 | 15223.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-JAN-08:15 | 2027.07 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -975.30 | 0.00 | -577.02 | -980.43 |
G NW APARTMENT | 11-JAN-08:14 | 2035.48 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -953.37 | 0.00 | -577.02 | -1010.76 |
OFFICE | 12-FEB-07:01 | 6197.32 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -364.63 | 0.00 | -280.36 | -6126.89 |
G NE APARTMENT | 11-JAN-08:14 | 2028.54 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -939.92 | 0.00 | -577.02 | -1017.27 |
G N1 APARTMENT | 11-JAN-08:14 | 1250.14 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.40 | 0.00 | -348.05 | -835.37 |
G N2 APARTMENT | 11-JAN-08:14 | 1250.19 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.39 | 0.00 | -348.05 | -835.43 |
G S1 APARTMENT | 29-JAN-18:38 | 1468.02 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -677.38 | 0.00 | 0.00 | -1738.73 |
G S2 APARTMENT | 11-JAN-08:15 | 1344.89 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.60 | 0.00 | -348.05 | -908.91 |
M SW APARTMENT | 10-JAN-23:15 | 4006.79 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1405.80 | 0.00 | -731.80 | -2436.28 |
M NW APARTMENT | 10-JAN-23:15 | 4131.68 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1373.62 | 0.00 | -731.80 | -2593.35 |
M SE APARTMENT | 10-JAN-23:15 | 3984.46 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1386.05 | 0.00 | -731.80 | -2433.69 |
M NE APARTMENT | 10-JAN-23:15 | 4109.00 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1353.94 | 0.00 | -731.80 | -2590.35 |
M N1 APARTMENT | 08-MAY-06:01 | 2440.88 | 0.00 | 0.00 | 0.00 | 161.42 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -329.42 | 0.00 | -315.62 | -2433.49 |
M N2 APARTMENT | 16-DEC-18:14 | 2258.17 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -534.72 | 0.00 | -177.44 | -2494.10 |
M S1 APARTMENT | 11-JAN-01:00 | 2027.04 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -820.23 | 0.00 | -379.76 | -1296.01 |
M S2 APARTMENT | 11-JAN-01:00 | 2027.08 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -820.22 | 0.00 | -379.76 | -1296.06 |
T SW APARTMENT | 10-JAN-23:15 | 3762.97 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1379.76 | 0.00 | -968.65 | -1981.64 |
T NW APARTMENT | 10-JAN-23:15 | 3791.70 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1345.14 | 0.00 | -968.65 | -2044.99 |
T SE APARTMENT | 10-JAN-23:15 | 3745.67 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1358.73 | 0.00 | -968.65 | -1985.37 |
T NE APARTMENT | 10-JAN-23:15 | 3774.35 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1324.14 | 0.00 | -968.65 | -2048.64 |
T N1 APARTMENT | 11-JAN-01:00 | 2681.47 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.13 | 0.00 | -502.70 | -1875.59 |
T N2 APARTMENT | 11-JAN-01:00 | 2681.18 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.14 | 0.00 | -502.70 | -1875.29 |
T S1 APARTMENT | 11-JAN-00:45 | 2661.20 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -806.24 | 0.00 | -504.59 | -1819.33 |
T S2 APARTMENT | 11-JAN-00:45 | 2660.91 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -806.24 | 0.00 | -504.59 | -1819.04 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JAN-08:15 | 61453.23 | 0.00 | 0.00 | 0.00 | 1779.34 | 4240.08 | 9884.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18972.91 | 0.00 | -18111.02 | -40272.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Sec1.1A-General InformationData | |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 41.25 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 41.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 437.68 | 127311.21 | 0.00 | 0.00 |
Space Cooling | 80.47 | 19649.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 248.66 | 7884.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 438.33 | 28486.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1483.24 | 437.68 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1483.24 |
Natural Gas | 0.00 | 437.68 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1920.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 25.67 |
Fans-Interior | 79.33 |
Service Water Heating | 139.83 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.56 |
Subtotal | 473.18 |
Natural Gas [MJ/m2] | |
Space Heating | 139.63 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 139.63 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.59 |
Space Heating | 22.79 |
Space Cooling | 4.19 |
Fans-Interior | 12.94 |
Service Water Heating | 22.82 |
Receptacle Equipment | 26.62 |
Miscellaneous | 2.05 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.200303 |
G NW APARTMENT DIRECT AIR | 0.183703 |
OFFICE DIRECT AIR | 0.485502 |
G NE APARTMENT DIRECT AIR | 0.127648 |
G N1 APARTMENT DIRECT AIR | 0.106134 |
G N2 APARTMENT DIRECT AIR | 0.104811 |
G S1 APARTMENT DIRECT AIR | 0.128055 |
G S2 APARTMENT DIRECT AIR | 0.131484 |
M SW APARTMENT DIRECT AIR | 0.556162 |
M NW APARTMENT DIRECT AIR | 0.505233 |
M SE APARTMENT DIRECT AIR | 0.495304 |
M NE APARTMENT DIRECT AIR | 0.378116 |
M N1 APARTMENT DIRECT AIR | 0.309122 |
M N2 APARTMENT DIRECT AIR | 0.306857 |
M S1 APARTMENT DIRECT AIR | 0.376339 |
M S2 APARTMENT DIRECT AIR | 0.377787 |
T SW APARTMENT DIRECT AIR | 0.367339 |
T NW APARTMENT DIRECT AIR | 0.329448 |
T SE APARTMENT DIRECT AIR | 0.341712 |
T NE APARTMENT DIRECT AIR | 0.256395 |
T N1 APARTMENT DIRECT AIR | 0.204661 |
T N2 APARTMENT DIRECT AIR | 0.202377 |
T S1 APARTMENT DIRECT AIR | 0.282018 |
T S2 APARTMENT DIRECT AIR | 0.282954 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.200303 |
SPLIT GNW MAIN BRANCH | 0.183703 |
SPLIT OFFICE MAIN BRANCH | 0.485502 |
SPLIT GNE MAIN BRANCH | 0.127648 |
SPLIT GN1 MAIN BRANCH | 0.106134 |
SPLIT GN2 MAIN BRANCH | 0.104811 |
SPLIT GS1 MAIN BRANCH | 0.128055 |
SPLIT GS2 MAIN BRANCH | 0.131484 |
SPLIT MSW MAIN BRANCH | 0.556162 |
SPLIT MNW MAIN BRANCH | 0.505233 |
SPLIT MSE MAIN BRANCH | 0.495304 |
SPLIT MNE MAIN BRANCH | 0.378116 |
SPLIT MN1 MAIN BRANCH | 0.309122 |
SPLIT MN2 MAIN BRANCH | 0.306857 |
SPLIT MS1 MAIN BRANCH | 0.376339 |
SPLIT MS2 MAIN BRANCH | 0.377787 |
SPLIT TSW MAIN BRANCH | 0.367339 |
SPLIT TNW MAIN BRANCH | 0.329448 |
SPLIT TSE MAIN BRANCH | 0.341712 |
SPLIT TNE MAIN BRANCH | 0.256395 |
SPLIT TN1 MAIN BRANCH | 0.204661 |
SPLIT TN2 MAIN BRANCH | 0.202377 |
SPLIT TS1 MAIN BRANCH | 0.282018 |
SPLIT TS2 MAIN BRANCH | 0.282954 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.200303 |
SPLIT GNW | 0.183703 |
SPLIT OFFICE | 0.485502 |
SPLIT GNE | 0.127648 |
SPLIT GN1 | 0.106134 |
SPLIT GN2 | 0.104811 |
SPLIT GS1 | 0.128055 |
SPLIT GS2 | 0.131484 |
SPLIT MSW | 0.556162 |
SPLIT MNW | 0.505233 |
SPLIT MSE | 0.495304 |
SPLIT MNE | 0.378116 |
SPLIT MN1 | 0.309122 |
SPLIT MN2 | 0.306857 |
SPLIT MS1 | 0.376339 |
SPLIT MS2 | 0.377787 |
SPLIT TSW | 0.367339 |
SPLIT TNW | 0.329448 |
SPLIT TSE | 0.341712 |
SPLIT TNE | 0.256395 |
SPLIT TN1 | 0.204661 |
SPLIT TN2 | 0.202377 |
SPLIT TS1 | 0.282018 |
SPLIT TS2 | 0.282954 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.200303 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.183703 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.485502 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.127648 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.106134 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.104811 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.128055 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.131484 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.556162 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.505233 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.495304 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.378116 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.309122 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.306857 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.376339 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.377787 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.367339 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.329448 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.341712 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.256395 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.204661 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.202377 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.282018 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.282954 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.200303 | 3315.72 | 0.798655 |
SPLIT GNW COOLING COIL | 0.183703 | 3040.94 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.485502 | 8036.78 | 0.798655 |
SPLIT GNE COOLING COIL | 0.127648 | 2113.03 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.106134 | 1756.90 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.104811 | 1734.99 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.128055 | 2119.77 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.131484 | 2176.53 | 0.798655 |
SPLIT MSW COOLING COIL | 0.556162 | 9206.45 | 0.798655 |
SPLIT MNW COOLING COIL | 0.505233 | 8363.39 | 0.798655 |
SPLIT MSE COOLING COIL | 0.495304 | 8199.04 | 0.798655 |
SPLIT MNE COOLING COIL | 0.378116 | 6259.16 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.309122 | 5117.06 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.306857 | 5079.57 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.376339 | 6229.75 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.377787 | 6253.72 | 0.798655 |
SPLIT TSW COOLING COIL | 0.367339 | 6080.76 | 0.798655 |
SPLIT TNW COOLING COIL | 0.329448 | 5453.53 | 0.798655 |
SPLIT TSE COOLING COIL | 0.341712 | 5656.54 | 0.798655 |
SPLIT TNE COOLING COIL | 0.256395 | 4244.24 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.204661 | 3387.86 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.202377 | 3350.06 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.282018 | 4668.40 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.282954 | 4683.89 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.200303 | 0.200303 | 0.200303 | 0.200303 | 3715.45 | 3315.72 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.183703 | 0.183703 | 0.183703 | 0.183703 | 3650.10 | 3040.94 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.485502 | 0.485502 | 0.485502 | 0.485502 | 6578.63 | 8036.78 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.127648 | 0.127648 | 0.127648 | 0.127648 | 3638.22 | 2113.03 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.106134 | 0.106134 | 0.106134 | 0.106134 | 2785.46 | 1756.90 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.104811 | 0.104811 | 0.104811 | 0.104811 | 2785.18 | 1734.99 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.128055 | 0.128055 | 0.128055 | 0.128055 | 2805.01 | 2119.77 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.131484 | 0.131484 | 0.131484 | 0.131484 | 2940.84 | 2176.53 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.556162 | 0.556162 | 0.556162 | 0.556162 | 7233.34 | 9206.45 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.505233 | 0.505233 | 0.505233 | 0.505233 | 7190.91 | 8363.39 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.495304 | 0.495304 | 0.495304 | 0.495304 | 7202.18 | 8199.04 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.378116 | 0.378116 | 0.378116 | 0.378116 | 7159.71 | 6259.16 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.309122 | 0.309122 | 0.309122 | 0.309122 | 5079.33 | 5117.06 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.306857 | 0.306857 | 0.306857 | 0.306857 | 5078.58 | 5079.57 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.376339 | 0.376339 | 0.376339 | 0.376339 | 5124.95 | 6229.75 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.377787 | 0.377787 | 0.377787 | 0.377787 | 5124.21 | 6253.72 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.367339 | 0.367339 | 0.367339 | 0.367339 | 5405.92 | 6080.76 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.329448 | 0.329448 | 0.329448 | 0.329448 | 5385.11 | 5453.53 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.341712 | 0.341712 | 0.341712 | 0.341712 | 5389.39 | 5656.54 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.256395 | 0.256395 | 0.256395 | 0.256395 | 5368.56 | 4244.24 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.204661 | 0.204661 | 0.204661 | 0.204661 | 4288.08 | 3387.86 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.202377 | 0.202377 | 0.202377 | 0.202377 | 4287.66 | 3350.06 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.282018 | 0.282018 | 0.282018 | 0.282018 | 4307.84 | 4668.40 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.282954 | 0.282954 | 0.282954 | 0.282954 | 4307.43 | 4683.89 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.200303 |
SPLIT GNW SUPPLY FAN | 0.183703 |
SPLIT OFFICE SUPPLY FAN | 0.485502 |
SPLIT GNE SUPPLY FAN | 0.127648 |
SPLIT GN1 SUPPLY FAN | 0.106134 |
SPLIT GN2 SUPPLY FAN | 0.104811 |
SPLIT GS1 SUPPLY FAN | 0.128055 |
SPLIT GS2 SUPPLY FAN | 0.131484 |
SPLIT MSW SUPPLY FAN | 0.556162 |
SPLIT MNW SUPPLY FAN | 0.505233 |
SPLIT MSE SUPPLY FAN | 0.495304 |
SPLIT MNE SUPPLY FAN | 0.378116 |
SPLIT MN1 SUPPLY FAN | 0.309122 |
SPLIT MN2 SUPPLY FAN | 0.306857 |
SPLIT MS1 SUPPLY FAN | 0.376339 |
SPLIT MS2 SUPPLY FAN | 0.377787 |
SPLIT TSW SUPPLY FAN | 0.367339 |
SPLIT TNW SUPPLY FAN | 0.329448 |
SPLIT TSE SUPPLY FAN | 0.341712 |
SPLIT TNE SUPPLY FAN | 0.256395 |
SPLIT TN1 SUPPLY FAN | 0.204661 |
SPLIT TN2 SUPPLY FAN | 0.202377 |
SPLIT TS1 SUPPLY FAN | 0.282018 |
SPLIT TS2 SUPPLY FAN | 0.282954 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 3715.45 |
SPLIT GNW HEATING COIL | 3650.10 |
SPLIT OFFICE HEATING COIL | 6578.63 |
SPLIT GNE HEATING COIL | 3638.22 |
SPLIT GN1 HEATING COIL | 2785.46 |
SPLIT GN2 HEATING COIL | 2785.18 |
SPLIT GS1 HEATING COIL | 2805.01 |
SPLIT GS2 HEATING COIL | 2940.84 |
SPLIT MSW HEATING COIL | 7233.34 |
SPLIT MNW HEATING COIL | 7190.91 |
SPLIT MSE HEATING COIL | 7202.18 |
SPLIT MNE HEATING COIL | 7159.71 |
SPLIT MN1 HEATING COIL | 5079.33 |
SPLIT MN2 HEATING COIL | 5078.58 |
SPLIT MS1 HEATING COIL | 5124.95 |
SPLIT MS2 HEATING COIL | 5124.21 |
SPLIT TSW HEATING COIL | 5405.92 |
SPLIT TNW HEATING COIL | 5385.11 |
SPLIT TSE HEATING COIL | 5389.39 |
SPLIT TNE HEATING COIL | 5368.56 |
SPLIT TN1 HEATING COIL | 4288.08 |
SPLIT TN2 HEATING COIL | 4287.66 |
SPLIT TS1 HEATING COIL | 4307.84 |
SPLIT TS2 HEATING COIL | 4307.43 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -8.8 |
February | 21.89 | -2.2 |
March | 21.92 | 0.30 |
April | 22.31 | 6.67 |
May | 22.73 | 10.10 |
June | 24.03 | 16.46 |
July | 24.33 | 20.57 |
August | 24.29 | 19.17 |
September | 23.85 | 14.69 |
October | 22.67 | 8.64 |
November | 21.99 | 2.84 |
December | 21.72 | -4.1 |
Annual Sum or Average | 22.79 | 7.07 |
Minimum of Months | 21.72 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.73 | 0.30 |
April | 22.00 | 6.67 |
May | 22.53 | 10.10 |
June | 23.99 | 16.46 |
July | 24.32 | 20.57 |
August | 24.25 | 19.17 |
September | 23.65 | 14.69 |
October | 22.16 | 8.64 |
November | 21.75 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.63 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.23 | -8.8 |
February | 20.21 | -2.2 |
March | 20.97 | 0.30 |
April | 22.21 | 6.67 |
May | 22.85 | 10.10 |
June | 23.80 | 16.46 |
July | 23.89 | 20.57 |
August | 23.89 | 19.17 |
September | 23.72 | 14.69 |
October | 22.89 | 8.64 |
November | 21.46 | 2.84 |
December | 19.77 | -4.1 |
Annual Sum or Average | 22.08 | 7.07 |
Minimum of Months | 19.23 | -8.8 |
Maximum of Months | 23.89 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.70 | -2.2 |
March | 21.71 | 0.30 |
April | 21.95 | 6.67 |
May | 22.43 | 10.10 |
June | 23.95 | 16.46 |
July | 24.30 | 20.57 |
August | 24.23 | 19.17 |
September | 23.60 | 14.69 |
October | 22.06 | 8.64 |
November | 21.72 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.59 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.70 | -2.2 |
March | 21.71 | 0.30 |
April | 21.88 | 6.67 |
May | 22.33 | 10.10 |
June | 23.95 | 16.46 |
July | 24.31 | 20.57 |
August | 24.25 | 19.17 |
September | 23.68 | 14.69 |
October | 22.09 | 8.64 |
November | 21.74 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.59 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.70 | -2.2 |
March | 21.71 | 0.30 |
April | 21.88 | 6.67 |
May | 22.33 | 10.10 |
June | 23.95 | 16.46 |
July | 24.31 | 20.57 |
August | 24.25 | 19.17 |
September | 23.68 | 14.69 |
October | 22.08 | 8.64 |
November | 21.74 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.59 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -8.8 |
February | 21.90 | -2.2 |
March | 21.92 | 0.30 |
April | 22.25 | 6.67 |
May | 22.60 | 10.10 |
June | 24.04 | 16.46 |
July | 24.34 | 20.57 |
August | 24.31 | 19.17 |
September | 23.97 | 14.69 |
October | 22.76 | 8.64 |
November | 22.05 | 2.84 |
December | 21.74 | -4.1 |
Annual Sum or Average | 22.80 | 7.07 |
Minimum of Months | 21.73 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -8.8 |
February | 21.90 | -2.2 |
March | 21.92 | 0.30 |
April | 22.25 | 6.67 |
May | 22.61 | 10.10 |
June | 24.03 | 16.46 |
July | 24.33 | 20.57 |
August | 24.31 | 19.17 |
September | 23.97 | 14.69 |
October | 22.76 | 8.64 |
November | 22.05 | 2.84 |
December | 21.74 | -4.1 |
Annual Sum or Average | 22.81 | 7.07 |
Minimum of Months | 21.73 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.22 | -2.2 |
March | 22.53 | 0.30 |
April | 23.44 | 6.67 |
May | 23.74 | 10.10 |
June | 24.36 | 16.46 |
July | 24.40 | 20.57 |
August | 24.38 | 19.17 |
September | 24.17 | 14.69 |
October | 23.87 | 8.64 |
November | 22.85 | 2.84 |
December | 21.84 | -4.1 |
Annual Sum or Average | 23.31 | 7.07 |
Minimum of Months | 21.84 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.80 | -2.2 |
March | 21.88 | 0.30 |
April | 22.97 | 6.67 |
May | 23.54 | 10.10 |
June | 24.35 | 16.46 |
July | 24.40 | 20.57 |
August | 24.37 | 19.17 |
September | 23.95 | 14.69 |
October | 23.26 | 8.64 |
November | 22.01 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 23.00 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | -8.8 |
February | 22.20 | -2.2 |
March | 22.54 | 0.30 |
April | 23.40 | 6.67 |
May | 23.72 | 10.10 |
June | 24.35 | 16.46 |
July | 24.40 | 20.57 |
August | 24.38 | 19.17 |
September | 24.17 | 14.69 |
October | 23.83 | 8.64 |
November | 22.81 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.29 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.78 | -2.2 |
March | 21.83 | 0.30 |
April | 22.88 | 6.67 |
May | 23.45 | 10.10 |
June | 24.33 | 16.46 |
July | 24.39 | 20.57 |
August | 24.37 | 19.17 |
September | 23.92 | 14.69 |
October | 23.12 | 8.64 |
November | 21.92 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.96 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.39 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -8.8 |
February | 21.80 | -2.2 |
March | 21.88 | 0.30 |
April | 23.09 | 6.67 |
May | 23.52 | 10.10 |
June | 24.37 | 16.46 |
July | 24.40 | 20.57 |
August | 24.39 | 19.17 |
September | 24.06 | 14.69 |
October | 23.46 | 8.64 |
November | 22.14 | 2.84 |
December | 21.72 | -4.1 |
Annual Sum or Average | 23.05 | 7.07 |
Minimum of Months | 21.71 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -8.8 |
February | 21.80 | -2.2 |
March | 21.88 | 0.30 |
April | 23.08 | 6.67 |
May | 23.51 | 10.10 |
June | 24.37 | 16.46 |
July | 24.40 | 20.57 |
August | 24.39 | 19.17 |
September | 24.06 | 14.69 |
October | 23.45 | 8.64 |
November | 22.13 | 2.84 |
December | 21.72 | -4.1 |
Annual Sum or Average | 23.05 | 7.07 |
Minimum of Months | 21.71 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | -8.8 |
February | 22.42 | -2.2 |
March | 22.86 | 0.30 |
April | 23.68 | 6.67 |
May | 23.83 | 10.10 |
June | 24.38 | 16.46 |
July | 24.40 | 20.57 |
August | 24.39 | 19.17 |
September | 24.28 | 14.69 |
October | 24.11 | 8.64 |
November | 23.24 | 2.84 |
December | 22.03 | -4.1 |
Annual Sum or Average | 23.48 | 7.07 |
Minimum of Months | 22.03 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | -8.8 |
February | 22.42 | -2.2 |
March | 22.87 | 0.30 |
April | 23.68 | 6.67 |
May | 23.83 | 10.10 |
June | 24.38 | 16.46 |
July | 24.40 | 20.57 |
August | 24.39 | 19.17 |
September | 24.28 | 14.69 |
October | 24.10 | 8.64 |
November | 23.24 | 2.84 |
December | 22.03 | -4.1 |
Annual Sum or Average | 23.48 | 7.07 |
Minimum of Months | 22.03 | -8.8 |
Maximum of Months | 24.40 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -8.8 |
February | 22.06 | -2.2 |
March | 22.22 | 0.30 |
April | 22.80 | 6.67 |
May | 23.37 | 10.10 |
June | 24.07 | 16.46 |
July | 24.34 | 20.57 |
August | 24.25 | 19.17 |
September | 23.70 | 14.69 |
October | 23.00 | 8.64 |
November | 22.27 | 2.84 |
December | 21.77 | -4.1 |
Annual Sum or Average | 22.97 | 7.07 |
Minimum of Months | 21.77 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.79 | -2.2 |
March | 21.88 | 0.30 |
April | 22.53 | 6.67 |
May | 23.23 | 10.10 |
June | 24.05 | 16.46 |
July | 24.32 | 20.57 |
August | 24.21 | 19.17 |
September | 23.50 | 14.69 |
October | 22.50 | 8.64 |
November | 21.82 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.77 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | -8.8 |
February | 22.06 | -2.2 |
March | 22.23 | 0.30 |
April | 22.83 | 6.67 |
May | 23.38 | 10.10 |
June | 24.08 | 16.46 |
July | 24.33 | 20.57 |
August | 24.25 | 19.17 |
September | 23.72 | 14.69 |
October | 23.00 | 8.64 |
November | 22.24 | 2.84 |
December | 21.75 | -4.1 |
Annual Sum or Average | 22.98 | 7.07 |
Minimum of Months | 21.75 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.83 | 0.30 |
April | 22.52 | 6.67 |
May | 23.19 | 10.10 |
June | 24.02 | 16.46 |
July | 24.29 | 20.57 |
August | 24.19 | 19.17 |
September | 23.48 | 14.69 |
October | 22.40 | 8.64 |
November | 21.76 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.74 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.29 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.83 | 0.30 |
April | 22.48 | 6.67 |
May | 23.19 | 10.10 |
June | 24.07 | 16.46 |
July | 24.32 | 20.57 |
August | 24.22 | 19.17 |
September | 23.50 | 14.69 |
October | 22.46 | 8.64 |
November | 21.80 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.76 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.82 | 0.30 |
April | 22.48 | 6.67 |
May | 23.19 | 10.10 |
June | 24.06 | 16.46 |
July | 24.32 | 20.57 |
August | 24.22 | 19.17 |
September | 23.50 | 14.69 |
October | 22.45 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.76 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.14 | -2.2 |
March | 22.30 | 0.30 |
April | 22.89 | 6.67 |
May | 23.43 | 10.10 |
June | 24.14 | 16.46 |
July | 24.35 | 20.57 |
August | 24.29 | 19.17 |
September | 23.80 | 14.69 |
October | 23.18 | 8.64 |
November | 22.42 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.05 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.14 | -2.2 |
March | 22.30 | 0.30 |
April | 22.89 | 6.67 |
May | 23.43 | 10.10 |
June | 24.14 | 16.46 |
July | 24.35 | 20.57 |
August | 24.29 | 19.17 |
September | 23.80 | 14.69 |
October | 23.18 | 8.64 |
November | 22.42 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.05 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.38 | -8.8 |
February | 21.39 | -2.2 |
March | 21.96 | 0.30 |
April | 23.33 | 6.67 |
May | 24.42 | 10.10 |
June | 26.02 | 16.46 |
July | 26.67 | 20.57 |
August | 26.36 | 19.17 |
September | 25.15 | 14.69 |
October | 23.49 | 8.64 |
November | 21.93 | 2.84 |
December | 20.82 | -4.1 |
Annual Sum or Average | 23.50 | 7.07 |
Minimum of Months | 20.38 | -8.8 |
Maximum of Months | 26.67 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.67 | -8.8 |
February | 19.76 | -2.2 |
March | 20.31 | 0.30 |
April | 21.53 | 6.67 |
May | 22.35 | 10.10 |
June | 24.98 | 16.46 |
July | 25.96 | 20.57 |
August | 25.71 | 19.17 |
September | 24.74 | 14.69 |
October | 22.27 | 8.64 |
November | 20.76 | 2.84 |
December | 19.43 | -4.1 |
Annual Sum or Average | 22.22 | 7.07 |
Minimum of Months | 18.67 | -8.8 |
Maximum of Months | 25.96 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | -8.8 |
February | 23.37 | -2.2 |
March | 23.92 | 0.30 |
April | 25.16 | 6.67 |
May | 25.64 | 10.10 |
June | 26.78 | 16.46 |
July | 27.02 | 20.57 |
August | 26.91 | 19.17 |
September | 26.36 | 14.69 |
October | 25.59 | 8.64 |
November | 24.12 | 2.84 |
December | 22.96 | -4.1 |
Annual Sum or Average | 25.06 | 7.07 |
Minimum of Months | 22.77 | -8.8 |
Maximum of Months | 27.02 | 20.57 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:31
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.123525E+12 | 75664.040 | 13-JAN-18:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30241.565 | 0.000 | 0.000 | 0.000 |
February | 0.112219E+12 | 78219.550 | 27-FEB-18:15 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 1428.242 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31368.833 | 0.000 | 0.000 | 0.000 |
March | 0.123409E+12 | 76353.012 | 01-MAR-18:00 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 687.668 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30242.869 | 0.000 | 0.000 | 0.000 |
April | 0.119251E+12 | 76356.112 | 25-APR-17:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 6631.870 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26810.096 | 0.000 | 0.000 | 0.000 |
May | 0.124061E+12 | 80749.224 | 19-MAY-17:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 14992.641 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22842.438 | 0.000 | 0.000 | 0.000 |
June | 0.127217E+12 | 87809.513 | 20-JUN-17:15 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 18438.609 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26456.758 | 0.000 | 0.000 | 0.000 |
July | 0.137688E+12 | 89034.218 | 31-JUL-17:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 19147.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26972.747 | 0.000 | 0.000 | 0.000 |
August | 0.134057E+12 | 91049.636 | 07-AUG-17:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 19649.155 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28486.336 | 0.000 | 0.000 | 0.000 |
September | 0.122791E+12 | 84212.475 | 02-SEP-17:30 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 20468.647 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20829.683 | 0.000 | 0.000 | 0.000 |
October | 0.120490E+12 | 74748.018 | 19-OCT-17:45 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 3085.541 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26240.002 | 0.000 | 0.000 | 0.000 |
November | 0.116479E+12 | 74519.210 | 03-NOV-17:15 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 2393.963 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26702.773 | 0.000 | 0.000 | 0.000 |
December | 0.122057E+12 | 73317.216 | 19-DEC-18:00 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27894.741 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.148324E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.112219E+12 | 73317.216 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20829.683 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.137688E+12 | 91049.636 | 8572.775 | 26456.413 | 7884.957 | 0.000 | 20468.647 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31368.833 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:31
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.135734E+12 | 127311.206 | 10-JAN-23:15 | 127311.206 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 127311.206 |
February | 0.724979E+11 | 94640.483 | 04-FEB-02:00 | 94640.483 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 94640.483 |
March | 0.502315E+11 | 92815.240 | 05-MAR-00:15 | 92815.240 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 92815.240 |
April | 0.151799E+11 | 48345.307 | 29-APR-04:00 | 48345.307 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 48345.307 |
May | 0.104610E+11 | 39591.791 | 08-MAY-03:00 | 39591.791 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 39591.791 |
June | 0.200628E+09 | 8342.250 | 17-JUN-03:00 | 8342.250 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8342.250 |
July | 91233.415 | 60.106 | 08-JUL-04:30 | 60.106 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 60.106 |
August | 0.115558E+09 | 4665.820 | 18-AUG-04:00 | 4665.820 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4665.820 |
September | 0.192982E+10 | 13410.348 | 19-SEP-02:00 | 13410.348 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13410.348 |
October | 0.959378E+10 | 36194.055 | 10-OCT-06:15 | 36194.055 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36194.055 |
November | 0.438732E+11 | 82044.718 | 27-NOV-03:00 | 82044.718 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 82044.718 |
December | 0.978663E+11 | 114715.315 | 31-DEC-07:30 | 114715.315 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 114715.315 |
Annual Sum or Average | 0.437684E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 91233.415 | 60.106 | 60.106 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 60.106 | |
Maximum of Months | 0.135734E+12 | 127311.206 | 127311.206 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 127311.206 |