Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2018-10-19 09:20:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1900.88 | 606.42 | 673.12 |
Net Site Energy | 1900.88 | 606.42 | 673.12 |
Total Source Energy | 5051.88 | 1611.64 | 1788.92 |
Net Source Energy | 5051.88 | 1611.64 | 1788.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 165.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 423.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1436.07 | 464.81 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 89.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 207.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 423.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 255.06 | 164.60 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 508.53 | 164.60 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.78 | 148.28 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 458.13 | 148.28 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1436.07 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1436.07 | 100.00 |
Total On-Site and Utility Electric Sources | 1436.07 | 100.00 |
Total Electricity End Uses | 1436.07 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 39.25 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2897.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20 |
RunPeriod | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 8.5250 | 208.0991 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 8.5250 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 14.1058 | 39.93 | 11.1646 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 14.7196 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 8.5250 | 52.0248 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-SEP-17:30 | 06-FEB-09:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 107780.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16341.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6586.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29698.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87654.88 | 107780.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 107780.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16341.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 7168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1404.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6586.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 29698.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 503.86 | 0.00 | 0.00 | 0.00 |
Cooling | 283.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 522.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 124.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1619.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 657.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1340.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4548.02 | 503.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 178.42 | 0.00 | 0.00 | 0.00 |
Cooling | 100.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 232.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 474.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1610.50 | 178.42 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 178.42 | 0.00 | 0.00 | 0.00 |
Cooling | 100.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 185.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 573.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 232.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 474.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1610.50 | 178.42 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.48_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.48_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 11.5174 | 176.50 | 2032.80 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 11.5174 | 88.25 | 1016.40 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 8.5250 | 155.32 | 1324.09 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 8.5250 | 77.66 | 662.05 | GeneralLights | LTG_COR_SCH | 137.36 | 168.00 | 137.36 | 0.0000 | N | 17.07 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 11.9479 | 88.25 | 1054.40 | GeneralLights-plugin | LTG_OFF_SCH | 56.36 | 168.00 | 55.36 | 0.0000 | Y | 10.96 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 2.9063 | 176.50 | 512.95 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.4206 | 5958.59 | 44216.13 | 128.63 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2508.33 | AstronomicalClock | - | 83.60 | 83.60 | 39.36 | |
Exterior Lighting Total | 2508.33 | 39.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3083.65 | 2321.23 | 762.42 | 0.75 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2915.02 | 2193.39 | 721.63 | 0.75 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7219.71 | 5766.06 | 1453.65 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2221.52 | 1631.17 | 590.35 | 0.73 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1902.71 | 1385.63 | 517.08 | 0.73 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1886.48 | 1372.37 | 514.11 | 0.73 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2131.51 | 1533.43 | 598.07 | 0.72 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2178.83 | 1572.47 | 606.36 | 0.72 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8201.57 | 6297.52 | 1904.05 | 0.77 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7735.53 | 5924.59 | 1810.93 | 0.77 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7489.06 | 5648.04 | 1841.01 | 0.75 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6245.67 | 4712.32 | 1533.35 | 0.75 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5162.41 | 3870.29 | 1292.12 | 0.75 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5135.19 | 3847.83 | 1287.35 | 0.75 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5844.01 | 4341.92 | 1502.09 | 0.74 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5864.15 | 4358.54 | 1505.60 | 0.74 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5291.41 | 4093.26 | 1198.14 | 0.77 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4907.28 | 3794.90 | 1112.38 | 0.77 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5013.69 | 3844.89 | 1168.80 | 0.77 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4038.03 | 3076.46 | 961.57 | 0.76 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3289.32 | 2494.07 | 795.24 | 0.76 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3259.06 | 2469.13 | 789.93 | 0.76 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4165.21 | 3179.58 | 985.63 | 0.76 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4178.91 | 3190.93 | 987.98 | 0.76 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2955.6 | 3.21 | 10.95 | 11.39 | 10.78 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2794.1 | 3.21 | 10.95 | 11.39 | 10.78 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6877.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2134.5 | 3.24 | 11.06 | 11.51 | 10.95 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1829.7 | 3.25 | 11.10 | 11.55 | 11.00 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1814.2 | 3.25 | 11.10 | 11.56 | 11.01 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2052.1 | 3.27 | 11.15 | 11.61 | 11.08 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2097.0 | 3.26 | 11.14 | 11.60 | 11.06 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7845.4 | 3.18 | 10.85 | 11.29 | 10.64 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7401.5 | 3.18 | 10.87 | 11.30 | 10.66 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7176.8 | 3.21 | 10.94 | 11.38 | 10.76 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5985.0 | 3.20 | 10.94 | 11.38 | 10.76 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4950.1 | 3.21 | 10.96 | 11.41 | 10.80 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4924.3 | 3.21 | 10.97 | 11.41 | 10.81 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5608.7 | 3.23 | 11.01 | 11.45 | 10.87 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5627.8 | 3.23 | 11.00 | 11.45 | 10.86 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5057.8 | 3.17 | 10.82 | 11.25 | 10.59 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4690.8 | 3.17 | 10.82 | 11.25 | 10.59 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4796.6 | 3.18 | 10.86 | 11.29 | 10.65 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3865.7 | 3.19 | 10.89 | 11.33 | 10.70 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3150.5 | 3.20 | 10.91 | 11.35 | 10.73 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3121.8 | 3.20 | 10.92 | 11.35 | 10.73 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3986.7 | 3.19 | 10.88 | 11.32 | 10.68 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3999.7 | 3.19 | 10.88 | 11.32 | 10.68 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 3204.85 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 3164.77 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5789.98 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 3154.66 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2376.95 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2376.71 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2377.78 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2504.39 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 6444.49 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 6448.06 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 6418.12 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 6421.67 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 4468.65 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 4468.00 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 4467.39 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 4466.74 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4763.33 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4766.82 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4749.57 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4753.05 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3694.67 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3694.31 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3689.64 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3689.28 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 182.61 | 1120.11 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.45 | 1120.11 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 488.53 | 1120.11 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 123.99 | 1120.11 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.09 | 104.09 | 1120.11 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.09 | 102.94 | 1120.11 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 113.14 | 1120.11 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 116.57 | 1120.11 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 508.46 | 1120.11 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 476.79 | 1120.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 445.44 | 1120.11 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 371.85 | 1120.11 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.81 | 1120.11 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 300.84 | 1120.11 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 335.54 | 1120.11 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 337.01 | 1120.11 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 333.62 | 1120.11 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 309.17 | 1120.11 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 309.93 | 1120.11 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.90 | 1120.11 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.10 | 1120.11 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.91 | 1120.11 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.79 | 1120.11 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.79 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.89 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1691.22 | 2029.46 | 0.136 | 0.163 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.30 | 0.01335 |
G NW APARTMENT | 1597.19 | 1916.63 | 0.128 | 0.154 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 27.72 | 0.01335 |
OFFICE | 4437.43 | 5324.92 | 0.363 | 0.436 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18 | 0.01335 |
G NE APARTMENT | 1148.27 | 1377.92 | 0.092 | 0.111 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.11 | 0.01335 |
G N1 APARTMENT | 964.05 | 1156.86 | 0.077 | 0.093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67 | 0.01335 |
G N2 APARTMENT | 953.37 | 1144.04 | 0.077 | 0.092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67 | 0.01335 |
G S1 APARTMENT | 1047.86 | 1257.44 | 0.084 | 0.101 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
G S2 APARTMENT | 1079.64 | 1295.56 | 0.087 | 0.104 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
M SW APARTMENT | 4709.04 | 5650.84 | 0.378 | 0.454 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.30 | 0.01335 |
M NW APARTMENT | 4415.72 | 5298.87 | 0.355 | 0.426 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 27.72 | 0.01335 |
M SE APARTMENT | 4125.24 | 4950.29 | 0.331 | 0.398 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.07 | 0.01335 |
M NE APARTMENT | 3443.71 | 4132.46 | 0.277 | 0.332 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 27.46 | 0.01335 |
M N1 APARTMENT | 2804.50 | 3365.40 | 0.225 | 0.270 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67 | 0.01335 |
M N2 APARTMENT | 2786.23 | 3343.48 | 0.224 | 0.269 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67 | 0.01335 |
M S1 APARTMENT | 3107.59 | 3729.11 | 0.250 | 0.300 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
M S2 APARTMENT | 3121.14 | 3745.37 | 0.251 | 0.301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
T SW APARTMENT | 3089.50 | 3707.40 | 0.248 | 0.298 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 29.37 | 0.01335 |
T NW APARTMENT | 2863.33 | 3435.99 | 0.230 | 0.276 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.30 | 0.01335 |
T SE APARTMENT | 2870.18 | 3444.22 | 0.231 | 0.277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
T NE APARTMENT | 2277.17 | 2732.60 | 0.183 | 0.220 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 28.39 | 0.01335 |
T N1 APARTMENT | 1834.74 | 2201.69 | 0.147 | 0.177 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
T N2 APARTMENT | 1814.45 | 2177.34 | 0.146 | 0.175 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
T S1 APARTMENT | 2359.64 | 2831.57 | 0.190 | 0.227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
T S2 APARTMENT | 2368.92 | 2842.71 | 0.190 | 0.228 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1690.57 | 2028.68 | 0.050 | 0.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G NW APARTMENT | 1692.51 | 2031.01 | 0.050 | 0.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
OFFICE | 3504.10 | 4204.92 | 0.100 | 0.120 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G NE APARTMENT | 1683.96 | 2020.75 | 0.050 | 0.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G N1 APARTMENT | 1026.28 | 1231.53 | 0.030 | 0.036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G N2 APARTMENT | 1026.08 | 1231.29 | 0.030 | 0.036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G S1 APARTMENT | 1026.99 | 1232.38 | 0.030 | 0.036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
G S2 APARTMENT | 1134.05 | 1360.86 | 0.033 | 0.040 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
M SW APARTMENT | 3482.36 | 4178.83 | 0.103 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M NW APARTMENT | 3485.38 | 4182.46 | 0.103 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M SE APARTMENT | 3460.06 | 4152.07 | 0.102 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M NE APARTMENT | 3463.06 | 4155.68 | 0.102 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M N1 APARTMENT | 1811.42 | 2173.71 | 0.053 | 0.064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M N2 APARTMENT | 1810.87 | 2173.04 | 0.053 | 0.064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M S1 APARTMENT | 1810.36 | 2172.43 | 0.053 | 0.064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
M S2 APARTMENT | 1809.80 | 2171.77 | 0.053 | 0.064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T SW APARTMENT | 3044.44 | 3653.33 | 0.090 | 0.108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T NW APARTMENT | 3047.39 | 3656.87 | 0.090 | 0.108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T SE APARTMENT | 3032.80 | 3639.36 | 0.090 | 0.107 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T NE APARTMENT | 3035.74 | 3642.89 | 0.090 | 0.108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T N1 APARTMENT | 2140.67 | 2568.81 | 0.063 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T N2 APARTMENT | 2140.36 | 2568.44 | 0.063 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T S1 APARTMENT | 2136.42 | 2563.71 | 0.063 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
T S2 APARTMENT | 2136.11 | 2563.34 | 0.063 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -16.30 | 0.00092 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.16 | 0.16 | 0.06 | 0.06 |
SPLIT GNW | 0.15 | 0.15 | 0.06 | 0.06 |
SPLIT OFFICE | 0.44 | 0.44 | 0.12 | 0.12 |
SPLIT GNE | 0.11 | 0.11 | 0.06 | 0.06 |
SPLIT GN1 | 0.09 | 0.09 | 0.04 | 0.04 |
SPLIT GN2 | 0.09 | 0.09 | 0.04 | 0.04 |
SPLIT GS1 | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT GS2 | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT MSW | 0.45 | 0.45 | 0.12 | 0.12 |
SPLIT MNW | 0.43 | 0.43 | 0.12 | 0.12 |
SPLIT MSE | 0.40 | 0.40 | 0.12 | 0.12 |
SPLIT MNE | 0.33 | 0.33 | 0.12 | 0.12 |
SPLIT MN1 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MN2 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MS1 | 0.30 | 0.30 | 0.06 | 0.06 |
SPLIT MS2 | 0.30 | 0.30 | 0.06 | 0.06 |
SPLIT TSW | 0.30 | 0.30 | 0.11 | 0.11 |
SPLIT TNW | 0.28 | 0.28 | 0.11 | 0.11 |
SPLIT TSE | 0.28 | 0.28 | 0.11 | 0.11 |
SPLIT TNE | 0.22 | 0.22 | 0.11 | 0.11 |
SPLIT TN1 | 0.18 | 0.18 | 0.08 | 0.08 |
SPLIT TN2 | 0.17 | 0.17 | 0.08 | 0.08 |
SPLIT TS1 | 0.23 | 0.23 | 0.08 | 0.08 |
SPLIT TS2 | 0.23 | 0.23 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3421.00 | 6422.75 | 1796.00 |
G NW APARTMENT | 3591.25 | 6611.50 | 2184.00 |
OFFICE | 617.75 | 1599.50 | 391.25 |
G NE APARTMENT | 3577.50 | 6635.50 | 2214.75 |
G N1 APARTMENT | 3078.75 | 6747.75 | 1885.25 |
G N2 APARTMENT | 3081.00 | 6750.75 | 1888.50 |
G S1 APARTMENT | 2760.25 | 6449.00 | 1302.50 |
G S2 APARTMENT | 2927.50 | 6486.00 | 1515.00 |
M SW APARTMENT | 3388.25 | 4718.00 | 611.75 |
M NW APARTMENT | 3533.25 | 5080.50 | 1105.25 |
M SE APARTMENT | 3343.25 | 4719.25 | 576.00 |
M NE APARTMENT | 3463.50 | 5126.50 | 1062.00 |
M N1 APARTMENT | 2735.00 | 4985.50 | 452.75 |
M N2 APARTMENT | 2734.00 | 4989.25 | 452.25 |
M S1 APARTMENT | 2756.50 | 4467.25 | 119.25 |
M S2 APARTMENT | 2759.50 | 4468.75 | 119.75 |
T SW APARTMENT | 4498.50 | 5498.50 | 2163.75 |
T NW APARTMENT | 4708.75 | 5803.25 | 2581.25 |
T SE APARTMENT | 4509.00 | 5483.50 | 2151.50 |
T NE APARTMENT | 4694.00 | 5849.50 | 2588.50 |
T N1 APARTMENT | 4187.25 | 5812.25 | 2150.50 |
T N2 APARTMENT | 4188.75 | 5815.25 | 2151.25 |
T S1 APARTMENT | 4005.00 | 5386.75 | 1677.50 |
T S2 APARTMENT | 4007.25 | 5383.25 | 1676.50 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5552.25 | 6871.25 | 2897.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G NW APARTMENT | 6.25 | 0.00 | 6.25 | 0.00 |
OFFICE | 18.25 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
G N1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
G N2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
G S1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M NW APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M NE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M N1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M N2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T N2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 57.50 | 0.00 | 39.25 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.133 | 0.000 | 0.087 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.085 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.150 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.085 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.084 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.084 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.087 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.087 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.111 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.108 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.111 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.108 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.108 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.108 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.111 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.111 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.252 | 0.000 | 0.135 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.252 | 0.000 | 0.131 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.252 | 0.000 | 0.135 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.252 | 0.000 | 0.131 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.152 | 0.000 | 0.131 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.152 | 0.000 | 0.131 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.152 | 0.000 | 0.135 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.152 | 0.000 | 0.135 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.495 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.353 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1425 |
Defaulted Fields | 439 |
Fields with Defaults | 3748 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
Electricity:Building | 676.42 | 10861.97 | 01-JAN-03:15 | 35029.19 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity | 165.00 | 2991.26 | 01-JAN-00:15 | 9689.08 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 138.97 | 2711.50 | 01-JAN-00:15 | 8059.76 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.45 | 508.27 | 01-JAN-00:15 | 2167.25 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.91 | 379.58 | 01-JAN-00:15 | 1622.34 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 29.25 | 476.16 | 01-JAN-03:15 | 1566.15 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 4.83 | 28.81 | 01-JAN-00:15 | 460.92 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.08 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 142.36 | 1349.33 | 01-JAN-00:15 | 8621.71 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 34.14 | 1082.58 | 01-JAN-00:15 | 1082.58 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 17.07 | 541.29 | 01-JAN-00:15 | 541.29 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 26.03 | 279.76 | 01-JAN-00:15 | 1629.32 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 511.42 | 7870.70 | 01-JAN-03:15 | 26522.71 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.53 | 128.69 | 01-JAN-00:15 | 544.92 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 125.29 | 808.04 | 01-JAN-00:15 | 8080.42 | 01-JAN-07:15 |
Electricity:Plant | 423.12 | 0.00 | 01-JAN-00:15 | 32760.80 | 11-FEB-07:30 |
WaterSystems:Electricity | 423.12 | 0.00 | 01-JAN-00:15 | 32760.80 | 11-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 423.12 | 0.00 | 01-JAN-00:15 | 32760.80 | 11-FEB-07:30 |
Fans:Electricity | 207.70 | 6586.28 | 01-JAN-03:00 | 6586.28 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
ElectricityPurchased:Plant | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
Cogeneration:ElectricityPurchased | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
ElectricityNet:Plant | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
Cogeneration:ElectricityNet | 1436.07 | 19956.58 | 01-JAN-03:15 | 87654.88 | 16-SEP-17:30 |
ExteriorLights:Electricity | 39.36 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.36 | 0.00 | 01-JAN-08:00 | 2508.33 | 01-JAN-00:15 |
Electricity:HVAC | 297.16 | 6586.28 | 01-JAN-03:00 | 29128.54 | 27-JUN-16:45 |
General:Fans:Electricity | 207.70 | 6586.28 | 01-JAN-03:00 | 6586.28 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 89.46 | 0.00 | 01-JAN-00:15 | 22542.26 | 27-JUN-16:45 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 464.81 | 0.00 | 12-MAR-12:30 | 107780.22 | 06-FEB-10:00 |
Gas:HVAC | 464.81 | 0.00 | 12-MAR-12:30 | 107780.22 | 06-FEB-10:00 |
Heating:Gas | 464.81 | 0.00 | 12-MAR-12:30 | 107780.22 | 06-FEB-10:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1268.34 | 1206.44 | 07-APR-10:45 | 157461.39 | 27-JUN-17:15 |
EnergyTransfer:Building | 528.29 | 1130.95 | 07-APR-11:15 | 57834.95 | 09-AUG-15:15 |
EnergyTransfer:Zone:G SW APARTMENT | 13.00 | 0.00 | 05-JAN-13:45 | 1911.79 | 21-SEP-15:15 |
Heating:EnergyTransfer | 185.70 | 0.00 | 09-MAR-16:45 | 56259.00 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 6.50 | 0.00 | 05-JAN-13:30 | 1831.27 | 06-FEB-10:00 |
Cooling:EnergyTransfer | 342.59 | 0.00 | 02-JAN-07:15 | 57834.95 | 09-AUG-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.50 | 0.00 | 01-JAN-00:15 | 1911.79 | 21-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.19 | 0.03 | 08-JUN-10:00 | 1879.57 | 07-FEB-08:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 8.19 | 0.00 | 22-FEB-17:15 | 1879.57 | 07-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.99 | 0.00 | 01-JAN-00:15 | 1580.96 | 10-JUL-18:30 |
EnergyTransfer:Zone:OFFICE | 20.67 | 0.09 | 30-MAY-00:30 | 3868.99 | 13-FEB-07:15 |
Heating:EnergyTransfer:Zone:OFFICE | 0.72 | 0.00 | 01-JAN-00:15 | 3868.99 | 13-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 19.95 | 0.00 | 02-JAN-07:15 | 3297.21 | 21-SEP-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 13.21 | 0.07 | 01-MAY-24:00 | 1842.59 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 8.06 | 0.00 | 09-MAR-16:15 | 1842.59 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.15 | 0.00 | 01-JAN-00:15 | 1195.87 | 21-JUL-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.77 | 0.05 | 21-MAY-14:15 | 1139.34 | 07-FEB-08:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.92 | 0.00 | 01-JAN-21:15 | 1139.34 | 07-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.85 | 0.00 | 01-JAN-00:15 | 1004.42 | 16-JUL-18:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.77 | 0.04 | 24-OCT-01:00 | 1137.36 | 07-FEB-08:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.92 | 0.00 | 01-JAN-21:15 | 1137.36 | 07-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.85 | 0.00 | 01-JAN-00:15 | 995.94 | 16-JUL-18:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 9.22 | 0.04 | 22-OCT-10:15 | 1360.80 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 2.65 | 0.00 | 01-JAN-17:15 | 1063.03 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 6.57 | 0.00 | 01-JAN-00:15 | 1360.80 | 21-SEP-14:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 9.53 | 0.15 | 05-NOV-10:00 | 1346.01 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 3.17 | 0.00 | 04-JAN-11:00 | 1139.83 | 13-FEB-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 6.36 | 0.00 | 01-JAN-00:15 | 1346.01 | 21-SEP-14:15 |
EnergyTransfer:Zone:M SW APARTMENT | 36.80 | 0.02 | 04-NOV-18:45 | 5357.19 | 21-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 8.99 | 0.00 | 05-JAN-12:45 | 3839.31 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 27.82 | 0.00 | 01-JAN-00:15 | 5357.19 | 21-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 34.36 | 0.14 | 21-MAY-08:45 | 4455.03 | 27-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 12.76 | 0.00 | 11-JAN-18:00 | 4032.51 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 21.60 | 0.00 | 01-JAN-00:15 | 4455.03 | 27-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 36.97 | 0.41 | 26-OCT-08:30 | 4601.78 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 8.80 | 0.00 | 04-JAN-12:45 | 3776.26 | 13-FEB-04:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 28.17 | 0.00 | 01-JAN-00:15 | 4601.78 | 21-SEP-14:15 |
EnergyTransfer:Zone:M NE APARTMENT | 34.45 | 0.10 | 10-OCT-13:45 | 3956.44 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 12.50 | 0.00 | 11-JAN-18:00 | 3956.44 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.95 | 0.00 | 01-JAN-00:15 | 3564.83 | 27-JUN-17:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 25.73 | 0.08 | 16-NOV-12:00 | 2997.47 | 27-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 3.88 | 0.00 | 01-JAN-04:00 | 2016.44 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 21.85 | 0.00 | 01-JAN-00:15 | 2997.47 | 27-JUN-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 25.71 | 0.43 | 29-MAR-05:30 | 2981.84 | 27-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 3.87 | 0.00 | 01-JAN-04:00 | 2014.63 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 21.84 | 0.00 | 01-JAN-00:15 | 2981.84 | 27-JUN-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 31.65 | 0.15 | 27-NOV-07:00 | 4069.79 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.98 | 0.00 | 01-JAN-04:00 | 1870.78 | 13-FEB-04:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 29.67 | 0.00 | 01-JAN-00:15 | 4069.79 | 21-SEP-14:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 31.64 | 0.06 | 05-NOV-15:00 | 4073.56 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.98 | 0.00 | 01-JAN-04:00 | 1870.04 | 13-FEB-04:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 29.66 | 0.00 | 01-JAN-00:15 | 4073.56 | 21-SEP-14:15 |
EnergyTransfer:Zone:T SW APARTMENT | 25.34 | 0.03 | 27-OCT-17:00 | 3343.93 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 13.73 | 0.00 | 06-JAN-11:00 | 3343.93 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 11.61 | 0.00 | 01-JAN-00:15 | 3325.69 | 21-SEP-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 25.40 | 0.02 | 18-SEP-01:45 | 3383.66 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 16.19 | 0.00 | 08-MAR-13:30 | 3383.66 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 9.21 | 0.00 | 01-JAN-00:15 | 2897.40 | 27-JUN-16:45 |
EnergyTransfer:Zone:T SE APARTMENT | 25.20 | 0.02 | 26-NOV-20:30 | 3319.59 | 13-FEB-04:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 13.56 | 0.00 | 06-JAN-10:45 | 3319.59 | 13-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.64 | 0.00 | 01-JAN-00:15 | 2920.15 | 09-AUG-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 25.25 | 0.02 | 28-MAR-10:30 | 3339.33 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 15.98 | 0.00 | 08-MAR-12:30 | 3339.33 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 9.28 | 0.00 | 01-JAN-00:15 | 2383.33 | 12-JUN-11:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 18.10 | 0.04 | 03-OCT-13:45 | 2238.32 | 06-FEB-03:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 9.65 | 0.00 | 22-FEB-17:15 | 2238.32 | 06-FEB-03:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 8.46 | 0.00 | 01-JAN-00:15 | 1964.94 | 16-JUL-18:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 18.11 | 0.04 | 20-NOV-12:45 | 2237.68 | 06-FEB-03:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 9.65 | 0.00 | 22-FEB-17:15 | 2237.68 | 06-FEB-03:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 8.46 | 0.00 | 01-JAN-00:15 | 1953.14 | 12-JUN-16:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 18.60 | 0.01 | 20-MAR-18:15 | 2611.88 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 7.54 | 0.00 | 04-JAN-12:30 | 2185.32 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 11.06 | 0.00 | 01-JAN-00:15 | 2611.88 | 21-SEP-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 18.60 | 0.00 | 18-APR-08:45 | 2613.20 | 21-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 7.54 | 0.00 | 04-JAN-12:30 | 2186.46 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 11.07 | 0.00 | 01-JAN-00:15 | 2613.20 | 21-SEP-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 740.05 | 0.00 | 12-MAR-18:45 | 101303.97 | 27-JUN-17:15 |
HeatingCoils:EnergyTransfer | 371.85 | 0.00 | 12-MAR-12:30 | 86224.18 | 06-FEB-10:00 |
CoolingCoils:EnergyTransfer | 368.20 | 0.00 | 01-JAN-00:15 | 101303.97 | 27-JUN-17:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 6.499 | -6.505 | 0.000 | 0.000 | 3.870 | 2.413 | 12.213 | 10.691 | 0.000 | 0.082 | 0.000 | 0.000 | -7.976 | 0.000 | -6.346 | -14.941 |
G NW APARTMENT | 8.192 | -4.994 | 0.000 | 0.000 | 3.884 | 2.413 | 12.213 | 5.802 | 0.000 | 0.082 | 0.000 | 0.000 | -8.323 | 0.000 | -6.255 | -13.014 |
OFFICE | 0.721 | -19.945 | 0.000 | 0.000 | 0.537 | 21.914 | 7.534 | 10.757 | 0.000 | 0.061 | 0.000 | 0.000 | -7.405 | 0.000 | -5.042 | -9.130 |
G NE APARTMENT | 8.060 | -5.153 | 0.000 | 0.000 | 3.893 | 2.413 | 12.213 | 5.729 | 0.000 | 0.082 | 0.000 | 0.000 | -8.135 | 0.000 | -6.245 | -12.857 |
G N1 APARTMENT | 3.919 | -4.850 | 0.000 | 0.000 | 3.890 | 2.413 | 12.213 | 2.140 | 0.000 | 0.063 | 0.000 | 0.000 | -5.177 | 0.000 | -4.095 | -10.516 |
G N2 APARTMENT | 3.918 | -4.852 | 0.000 | 0.000 | 3.891 | 2.413 | 12.213 | 2.139 | 0.000 | 0.063 | 0.000 | 0.000 | -5.176 | 0.000 | -4.095 | -10.514 |
G S1 APARTMENT | 2.649 | -6.573 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 7.083 | 0.000 | 0.062 | 0.000 | 0.000 | -4.852 | 0.000 | -4.189 | -12.678 |
G S2 APARTMENT | 3.165 | -6.364 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 7.086 | 0.000 | 0.062 | 0.000 | 0.000 | -4.840 | 0.000 | -4.191 | -13.415 |
M SW APARTMENT | 8.989 | -27.816 | 0.000 | 0.000 | 3.773 | 2.413 | 12.213 | 10.277 | 0.000 | 0.114 | 7.888 | 0.000 | -8.621 | 0.000 | -9.230 | -0.000 |
M NW APARTMENT | 12.759 | -21.598 | 0.000 | 0.000 | 3.802 | 2.413 | 12.213 | 5.471 | 0.000 | 0.113 | 2.847 | 0.000 | -8.928 | 0.000 | -9.093 | -0.001 |
M SE APARTMENT | 8.802 | -28.171 | 0.000 | 0.000 | 3.778 | 2.413 | 12.213 | 10.263 | 0.000 | 0.114 | 8.286 | 0.000 | -8.477 | 0.000 | -9.221 | -0.001 |
M NE APARTMENT | 12.499 | -21.952 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 5.396 | 0.000 | 0.113 | 3.308 | 0.000 | -8.719 | 0.000 | -9.080 | -0.001 |
M N1 APARTMENT | 3.880 | -21.852 | 0.000 | 0.000 | 3.790 | 2.413 | 12.213 | 1.937 | 0.000 | 0.085 | 9.133 | 0.000 | -5.618 | 0.000 | -5.981 | -0.000 |
M N2 APARTMENT | 3.871 | -21.843 | 0.000 | 0.000 | 3.791 | 2.413 | 12.213 | 1.937 | 0.000 | 0.085 | 9.131 | 0.000 | -5.617 | 0.000 | -5.981 | -0.000 |
M S1 APARTMENT | 1.979 | -29.674 | 0.000 | 0.000 | 3.754 | 2.413 | 12.213 | 6.818 | 0.000 | 0.085 | 13.802 | 0.000 | -5.283 | 0.000 | -6.106 | -0.000 |
M S2 APARTMENT | 1.975 | -29.664 | 0.000 | 0.000 | 3.754 | 2.413 | 12.213 | 6.817 | 0.000 | 0.085 | 13.795 | 0.000 | -5.282 | 0.000 | -6.106 | -0.000 |
T SW APARTMENT | 13.731 | -11.612 | 0.000 | 0.000 | 3.828 | 2.413 | 12.213 | 10.200 | 0.000 | 0.156 | 0.000 | 0.000 | -8.211 | 0.000 | -11.848 | -10.869 |
T NW APARTMENT | 16.190 | -9.206 | 0.000 | 0.000 | 3.846 | 2.413 | 12.213 | 5.425 | 0.000 | 0.156 | 0.000 | 0.000 | -8.535 | 0.000 | -11.703 | -10.798 |
T SE APARTMENT | 13.564 | -11.636 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 10.202 | 0.000 | 0.156 | 0.000 | 0.000 | -8.086 | 0.000 | -11.851 | -10.807 |
T NE APARTMENT | 15.975 | -9.278 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 5.370 | 0.000 | 0.156 | 0.000 | 0.000 | -8.343 | 0.000 | -11.694 | -10.667 |
T N1 APARTMENT | 9.647 | -8.457 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 1.941 | 0.000 | 0.119 | 0.000 | 0.000 | -5.326 | 0.000 | -7.595 | -8.799 |
T N2 APARTMENT | 9.647 | -8.464 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 1.940 | 0.000 | 0.119 | 0.000 | 0.000 | -5.324 | 0.000 | -7.595 | -8.794 |
T S1 APARTMENT | 7.535 | -11.060 | 0.000 | 0.000 | 3.816 | 2.413 | 12.213 | 6.784 | 0.000 | 0.120 | 0.000 | 0.000 | -5.030 | 0.000 | -7.744 | -9.047 |
T S2 APARTMENT | 7.536 | -11.066 | 0.000 | 0.000 | 3.816 | 2.413 | 12.213 | 6.783 | 0.000 | 0.120 | 0.000 | 0.000 | -5.029 | 0.000 | -7.745 | -9.040 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.062 | 0.000 | 0.002 | 0.000 | 0.000 | -1.053 | 0.000 | -1.877 | -14.205 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 6.264 | 0.249 | 0.000 | 0.079 | 2.726 | 0.000 | -2.778 | 0.000 | -23.611 | -0.001 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | 0.000 | 0.063 | 0.000 | 0.003 | 0.000 | 0.000 | -1.148 | 0.000 | -1.538 | -14.450 |
Total Facility | 185.702 | -342.584 | 0.000 | 0.000 | 88.637 | 128.627 | 294.692 | 149.363 | 0.000 | 2.537 | 70.918 | 0.000 | -167.292 | 0.000 | -206.060 | -204.546 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 21-SEP-15:15 | 0.00 | -1911.73 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2770.90 | 0.00 | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1524.22 |
G NW APARTMENT | 10-JUL-18:30 | 0.00 | -1580.89 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 1641.93 | 0.00 | 70.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1051.61 |
OFFICE | 21-SEP-13:15 | 0.00 | -3297.18 | 0.00 | 0.00 | 67.31 | 1622.34 | 544.92 | 2349.52 | 0.00 | 10.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1297.69 |
G NE APARTMENT | 21-JUL-17:15 | 0.00 | -1195.91 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 406.54 | 0.00 | 63.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -199.03 |
G N1 APARTMENT | 16-JUL-18:15 | 0.00 | -1004.62 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 366.72 | 0.00 | 72.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -354.33 |
G N2 APARTMENT | 16-JUL-18:15 | 0.00 | -996.14 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 366.87 | 0.00 | 72.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -362.96 |
G S1 APARTMENT | 21-SEP-14:15 | 0.00 | -1360.74 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1840.67 | 0.00 | 36.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1008.22 |
G S2 APARTMENT | 21-SEP-14:15 | 0.00 | -1345.96 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1840.89 | 0.00 | 36.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.23 |
M SW APARTMENT | 21-SEP-15:15 | 0.00 | -5357.07 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2749.08 | 0.00 | 55.78 | 1931.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 27-JUN-17:15 | 0.00 | -4454.72 | 0.00 | 0.00 | 141.84 | 194.45 | 588.62 | 1492.48 | 0.00 | 190.18 | 1847.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 21-SEP-14:15 | 0.00 | -4601.67 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1997.34 | 0.00 | 54.46 | 2058.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 27-JUN-17:15 | 0.00 | -3564.60 | 0.00 | 0.00 | 141.84 | 194.45 | 588.62 | 505.50 | 0.00 | 190.17 | 1944.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 27-JUN-17:15 | 0.00 | -2997.14 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 346.46 | 0.00 | 168.89 | 1556.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 27-JUN-17:15 | 0.00 | -2981.52 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 346.56 | 0.00 | 168.89 | 1541.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 21-SEP-14:15 | 0.00 | -4069.66 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1825.20 | 0.00 | 48.44 | 1704.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 21-SEP-14:15 | 0.00 | -4073.44 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1825.16 | 0.00 | 48.44 | 1708.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 21-SEP-15:15 | 0.00 | -3325.62 | 0.00 | 0.00 | 48.90 | 100.83 | 470.90 | 2711.18 | 0.00 | 67.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.90 |
T NW APARTMENT | 27-JUN-16:45 | 0.00 | -2897.45 | 0.00 | 0.00 | 84.79 | 144.04 | 588.62 | 1620.28 | 0.00 | 248.95 | 210.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 09-AUG-13:30 | 0.00 | -2919.96 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1820.26 | 0.00 | 100.63 | 546.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 12-JUN-11:30 | 0.00 | -2383.27 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1020.37 | 0.00 | 203.15 | 684.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 16-JUL-18:00 | 0.00 | -1965.80 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 349.52 | 0.00 | 170.00 | 521.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 12-JUN-16:30 | 0.00 | -1953.94 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 326.43 | 0.00 | 136.33 | 673.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 21-SEP-14:15 | 0.00 | -2611.80 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1802.85 | 0.00 | 60.03 | 257.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 21-SEP-14:15 | 0.00 | -2613.12 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1802.81 | 0.00 | 60.03 | 258.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-15:15 | 0.00 | -57833.54 | 0.00 | 0.00 | 1191.97 | 5565.24 | 11658.39 | 26755.47 | 0.00 | 1623.18 | 11039.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-FEB-10:00 | 1831.23 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -514.20 | 0.00 | -963.70 | -823.94 |
G NW APARTMENT | 07-FEB-08:21 | 1880.65 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -730.75 | 0.00 | -803.89 | -851.68 |
OFFICE | 13-NOV-07:01 | 5366.53 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -367.42 | 0.00 | -241.11 | -5332.56 |
G NE APARTMENT | 06-FEB-10:00 | 1842.55 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.95 | 0.00 | -963.70 | -842.51 |
G N1 APARTMENT | 22-NOV-17:01 | 1303.25 | 0.00 | 0.00 | 0.00 | 98.71 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -331.44 | 0.00 | -83.53 | -1719.65 |
G N2 APARTMENT | 07-FEB-08:21 | 1138.45 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -434.98 | 0.00 | -484.89 | -724.26 |
G S1 APARTMENT | 03-MAR-18:01 | 1632.47 | 0.00 | 0.00 | 0.00 | 168.44 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -439.91 | 0.00 | -316.27 | -1827.81 |
G S2 APARTMENT | 24-JAN-17:12 | 1246.46 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.12 | 0.00 | -144.93 | -1461.71 |
M SW APARTMENT | 06-FEB-10:00 | 3839.25 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -545.67 | 0.00 | -1385.67 | -2378.52 |
M NW APARTMENT | 06-FEB-10:00 | 4032.44 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -601.43 | 0.00 | -1385.67 | -2515.95 |
M SE APARTMENT | 13-FEB-04:00 | 3776.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -826.19 | 0.00 | -1422.43 | -1955.35 |
M NE APARTMENT | 06-FEB-10:00 | 3956.38 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -531.16 | 0.00 | -1385.67 | -2510.16 |
M N1 APARTMENT | 18-JAN-07:01 | 2390.75 | 0.00 | 0.00 | 0.00 | 161.39 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -305.51 | 0.00 | -258.17 | -2464.69 |
M N2 APARTMENT | 18-JAN-07:01 | 2397.61 | 0.00 | 0.00 | 0.00 | 161.39 | 93.63 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -305.51 | 0.00 | -258.17 | -2471.55 |
M S1 APARTMENT | 31-JAN-18:18 | 2563.74 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.05 | 0.00 | -382.17 | -2602.61 |
M S2 APARTMENT | 31-JAN-18:27 | 2560.41 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.06 | 0.00 | -382.17 | -2599.26 |
T SW APARTMENT | 06-FEB-10:00 | 3343.89 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -529.75 | 0.00 | -1834.80 | -1449.95 |
T NW APARTMENT | 06-FEB-10:00 | 3383.62 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -584.32 | 0.00 | -1834.80 | -1435.10 |
T SE APARTMENT | 13-FEB-04:00 | 3319.55 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -805.76 | 0.00 | -1883.87 | -1057.67 |
T NE APARTMENT | 06-FEB-10:00 | 3339.29 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -513.17 | 0.00 | -1834.80 | -1461.92 |
T N1 APARTMENT | 06-FEB-03:00 | 2238.27 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.29 | 0.00 | -921.46 | -1176.15 |
T N2 APARTMENT | 06-FEB-03:00 | 2237.63 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.30 | 0.00 | -921.46 | -1175.50 |
T S1 APARTMENT | 07-FEB-05:00 | 2185.33 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.83 | 0.00 | -808.63 | -1239.43 |
T S2 APARTMENT | 07-FEB-05:00 | 2186.46 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.81 | 0.00 | -808.63 | -1240.57 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-10:00 | 56258.03 | 0.00 | 0.00 | 0.00 | 1168.60 | 3908.79 | 9898.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10455.88 | 0.00 | -29358.56 | -31419.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Sec1.1A-General InformationData | |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 39.25 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 39.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 165.00 | 8572.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 464.81 | 107780.22 | 0.00 | 0.00 |
Space Cooling | 89.46 | 16341.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 207.70 | 6586.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 423.12 | 29698.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 511.42 | 26456.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1436.07 | 464.81 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 511.42 | 1436.07 |
Natural Gas | 0.00 | 464.81 |
Additional | 0.00 | 0.00 |
Total | 511.42 | 1900.88 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 52.64 |
Space Heating | 0.00 |
Space Cooling | 28.54 |
Fans-Interior | 66.26 |
Service Water Heating | 134.98 |
Receptacle Equipment | 163.15 |
Miscellaneous | 12.56 |
Subtotal | 458.13 |
Natural Gas [MJ/m2] | |
Space Heating | 148.28 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 148.28 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.68 |
Space Heating | 24.45 |
Space Cooling | 4.71 |
Fans-Interior | 10.93 |
Service Water Heating | 22.26 |
Receptacle Equipment | 26.90 |
Miscellaneous | 2.07 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.163025 |
G NW APARTMENT DIRECT AIR | 0.153963 |
OFFICE DIRECT AIR | 0.436143 |
G NE APARTMENT DIRECT AIR | 0.110696 |
G N1 APARTMENT DIRECT AIR | 0.092929 |
G N2 APARTMENT DIRECT AIR | 0.091899 |
G S1 APARTMENT DIRECT AIR | 0.101011 |
G S2 APARTMENT DIRECT AIR | 0.104073 |
M SW APARTMENT DIRECT AIR | 0.453934 |
M NW APARTMENT DIRECT AIR | 0.425662 |
M SE APARTMENT DIRECT AIR | 0.397677 |
M NE APARTMENT DIRECT AIR | 0.331981 |
M N1 APARTMENT DIRECT AIR | 0.270340 |
M N2 APARTMENT DIRECT AIR | 0.268578 |
M S1 APARTMENT DIRECT AIR | 0.299564 |
M S2 APARTMENT DIRECT AIR | 0.300870 |
T SW APARTMENT DIRECT AIR | 0.297842 |
T NW APARTMENT DIRECT AIR | 0.276021 |
T SE APARTMENT DIRECT AIR | 0.276699 |
T NE APARTMENT DIRECT AIR | 0.219531 |
T N1 APARTMENT DIRECT AIR | 0.176861 |
T N2 APARTMENT DIRECT AIR | 0.174905 |
T S1 APARTMENT DIRECT AIR | 0.227469 |
T S2 APARTMENT DIRECT AIR | 0.228364 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.163025 |
SPLIT GNW MAIN BRANCH | 0.153963 |
SPLIT OFFICE MAIN BRANCH | 0.436143 |
SPLIT GNE MAIN BRANCH | 0.110696 |
SPLIT GN1 MAIN BRANCH | 0.092929 |
SPLIT GN2 MAIN BRANCH | 0.091899 |
SPLIT GS1 MAIN BRANCH | 0.101011 |
SPLIT GS2 MAIN BRANCH | 0.104073 |
SPLIT MSW MAIN BRANCH | 0.453934 |
SPLIT MNW MAIN BRANCH | 0.425662 |
SPLIT MSE MAIN BRANCH | 0.397677 |
SPLIT MNE MAIN BRANCH | 0.331981 |
SPLIT MN1 MAIN BRANCH | 0.270340 |
SPLIT MN2 MAIN BRANCH | 0.268578 |
SPLIT MS1 MAIN BRANCH | 0.299564 |
SPLIT MS2 MAIN BRANCH | 0.300870 |
SPLIT TSW MAIN BRANCH | 0.297842 |
SPLIT TNW MAIN BRANCH | 0.276021 |
SPLIT TSE MAIN BRANCH | 0.276699 |
SPLIT TNE MAIN BRANCH | 0.219531 |
SPLIT TN1 MAIN BRANCH | 0.176861 |
SPLIT TN2 MAIN BRANCH | 0.174905 |
SPLIT TS1 MAIN BRANCH | 0.227469 |
SPLIT TS2 MAIN BRANCH | 0.228364 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.163025 |
SPLIT GNW | 0.153963 |
SPLIT OFFICE | 0.436143 |
SPLIT GNE | 0.110696 |
SPLIT GN1 | 0.092929 |
SPLIT GN2 | 0.091899 |
SPLIT GS1 | 0.101011 |
SPLIT GS2 | 0.104073 |
SPLIT MSW | 0.453934 |
SPLIT MNW | 0.425662 |
SPLIT MSE | 0.397677 |
SPLIT MNE | 0.331981 |
SPLIT MN1 | 0.270340 |
SPLIT MN2 | 0.268578 |
SPLIT MS1 | 0.299564 |
SPLIT MS2 | 0.300870 |
SPLIT TSW | 0.297842 |
SPLIT TNW | 0.276021 |
SPLIT TSE | 0.276699 |
SPLIT TNE | 0.219531 |
SPLIT TN1 | 0.176861 |
SPLIT TN2 | 0.174905 |
SPLIT TS1 | 0.227469 |
SPLIT TS2 | 0.228364 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.163025 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.153963 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.436143 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.110696 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.092929 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.091899 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.101011 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.104073 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.453934 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.425662 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.397677 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.331981 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.270340 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.268578 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.299564 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.300870 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.297842 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.276021 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.276699 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.219531 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.176861 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.174905 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.227469 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.228364 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.163025 | 3083.65 | 0.752753 |
SPLIT GNW COOLING COIL | 0.153963 | 2915.02 | 0.752444 |
SPLIT OFFICE COOLING COIL | 0.436143 | 7219.71 | 0.798655 |
SPLIT GNE COOLING COIL | 0.110696 | 2221.52 | 0.734258 |
SPLIT GN1 COOLING COIL | 0.092929 | 1902.71 | 0.728243 |
SPLIT GN2 COOLING COIL | 0.091899 | 1886.48 | 0.727478 |
SPLIT GS1 COOLING COIL | 0.101011 | 2131.51 | 0.719412 |
SPLIT GS2 COOLING COIL | 0.104073 | 2178.83 | 0.721702 |
SPLIT MSW COOLING COIL | 0.453934 | 8201.57 | 0.767844 |
SPLIT MNW COOLING COIL | 0.425662 | 7735.53 | 0.765894 |
SPLIT MSE COOLING COIL | 0.397677 | 7489.06 | 0.754173 |
SPLIT MNE COOLING COIL | 0.331981 | 6245.67 | 0.754494 |
SPLIT MN1 COOLING COIL | 0.270340 | 5162.41 | 0.749705 |
SPLIT MN2 COOLING COIL | 0.268578 | 5135.19 | 0.749308 |
SPLIT MS1 COOLING COIL | 0.299564 | 5844.01 | 0.742969 |
SPLIT MS2 COOLING COIL | 0.300870 | 5864.15 | 0.743253 |
SPLIT TSW COOLING COIL | 0.297842 | 5291.41 | 0.773568 |
SPLIT TNW COOLING COIL | 0.276021 | 4907.28 | 0.773321 |
SPLIT TSE COOLING COIL | 0.276699 | 5013.69 | 0.766878 |
SPLIT TNE COOLING COIL | 0.219531 | 4038.03 | 0.761872 |
SPLIT TN1 COOLING COIL | 0.176861 | 3289.32 | 0.758235 |
SPLIT TN2 COOLING COIL | 0.174905 | 3259.06 | 0.757621 |
SPLIT TS1 COOLING COIL | 0.227469 | 4165.21 | 0.763366 |
SPLIT TS2 COOLING COIL | 0.228364 | 4178.91 | 0.763580 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.163025 | 0.163025 | 0.163025 | 0.163025 | 3204.85 | 3083.65 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.153963 | 0.153963 | 0.153963 | 0.153963 | 3164.77 | 2915.02 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.436143 | 0.436143 | 0.436143 | 0.436143 | 5789.98 | 7219.71 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.110696 | 0.110696 | 0.110696 | 0.110696 | 3154.66 | 2221.52 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.092929 | 0.092929 | 0.092929 | 0.092929 | 2376.95 | 1902.71 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.091899 | 0.091899 | 0.091899 | 0.091899 | 2376.71 | 1886.48 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.101011 | 0.101011 | 0.101011 | 0.101011 | 2377.78 | 2131.51 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.104073 | 0.104073 | 0.104073 | 0.104073 | 2504.39 | 2178.83 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.453934 | 0.453934 | 0.453934 | 0.453934 | 6444.49 | 8201.57 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.425662 | 0.425662 | 0.425662 | 0.425662 | 6448.06 | 7735.53 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.397677 | 0.397677 | 0.397677 | 0.397677 | 6418.12 | 7489.06 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.331981 | 0.331981 | 0.331981 | 0.331981 | 6421.67 | 6245.67 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.270340 | 0.270340 | 0.270340 | 0.270340 | 4468.65 | 5162.41 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.268578 | 0.268578 | 0.268578 | 0.268578 | 4468.00 | 5135.19 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.299564 | 0.299564 | 0.299564 | 0.299564 | 4467.39 | 5844.01 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.300870 | 0.300870 | 0.300870 | 0.300870 | 4466.74 | 5864.15 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.297842 | 0.297842 | 0.297842 | 0.297842 | 4763.33 | 5291.41 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.276021 | 0.276021 | 0.276021 | 0.276021 | 4766.82 | 4907.28 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.276699 | 0.276699 | 0.276699 | 0.276699 | 4749.57 | 5013.69 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.219531 | 0.219531 | 0.219531 | 0.219531 | 4753.05 | 4038.03 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.176861 | 0.176861 | 0.176861 | 0.176861 | 3694.67 | 3289.32 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.174905 | 0.174905 | 0.174905 | 0.174905 | 3694.31 | 3259.06 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.227469 | 0.227469 | 0.227469 | 0.227469 | 3689.64 | 4165.21 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.228364 | 0.228364 | 0.228364 | 0.228364 | 3689.28 | 4178.91 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.163025 |
SPLIT GNW SUPPLY FAN | 0.153963 |
SPLIT OFFICE SUPPLY FAN | 0.436143 |
SPLIT GNE SUPPLY FAN | 0.110696 |
SPLIT GN1 SUPPLY FAN | 0.092929 |
SPLIT GN2 SUPPLY FAN | 0.091899 |
SPLIT GS1 SUPPLY FAN | 0.101011 |
SPLIT GS2 SUPPLY FAN | 0.104073 |
SPLIT MSW SUPPLY FAN | 0.453934 |
SPLIT MNW SUPPLY FAN | 0.425662 |
SPLIT MSE SUPPLY FAN | 0.397677 |
SPLIT MNE SUPPLY FAN | 0.331981 |
SPLIT MN1 SUPPLY FAN | 0.270340 |
SPLIT MN2 SUPPLY FAN | 0.268578 |
SPLIT MS1 SUPPLY FAN | 0.299564 |
SPLIT MS2 SUPPLY FAN | 0.300870 |
SPLIT TSW SUPPLY FAN | 0.297842 |
SPLIT TNW SUPPLY FAN | 0.276021 |
SPLIT TSE SUPPLY FAN | 0.276699 |
SPLIT TNE SUPPLY FAN | 0.219531 |
SPLIT TN1 SUPPLY FAN | 0.176861 |
SPLIT TN2 SUPPLY FAN | 0.174905 |
SPLIT TS1 SUPPLY FAN | 0.227469 |
SPLIT TS2 SUPPLY FAN | 0.228364 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 3204.85 |
SPLIT GNW HEATING COIL | 3164.77 |
SPLIT OFFICE HEATING COIL | 5789.98 |
SPLIT GNE HEATING COIL | 3154.66 |
SPLIT GN1 HEATING COIL | 2376.95 |
SPLIT GN2 HEATING COIL | 2376.71 |
SPLIT GS1 HEATING COIL | 2377.78 |
SPLIT GS2 HEATING COIL | 2504.39 |
SPLIT MSW HEATING COIL | 6444.49 |
SPLIT MNW HEATING COIL | 6448.06 |
SPLIT MSE HEATING COIL | 6418.12 |
SPLIT MNE HEATING COIL | 6421.67 |
SPLIT MN1 HEATING COIL | 4468.65 |
SPLIT MN2 HEATING COIL | 4468.00 |
SPLIT MS1 HEATING COIL | 4467.39 |
SPLIT MS2 HEATING COIL | 4466.74 |
SPLIT TSW HEATING COIL | 4763.33 |
SPLIT TNW HEATING COIL | 4766.82 |
SPLIT TSE HEATING COIL | 4749.57 |
SPLIT TNE HEATING COIL | 4753.05 |
SPLIT TN1 HEATING COIL | 3694.67 |
SPLIT TN2 HEATING COIL | 3694.31 |
SPLIT TS1 HEATING COIL | 3689.64 |
SPLIT TS2 HEATING COIL | 3689.28 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:20:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.89 | 2.67 |
April | 22.09 | 7.47 |
May | 22.82 | 13.73 |
June | 24.20 | 18.63 |
July | 24.39 | 22.03 |
August | 24.37 | 20.69 |
September | 24.18 | 16.55 |
October | 22.42 | 9.72 |
November | 21.84 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.78 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.83 | 2.67 |
April | 21.90 | 7.47 |
May | 22.62 | 13.73 |
June | 24.18 | 18.63 |
July | 24.39 | 22.03 |
August | 24.37 | 20.69 |
September | 24.06 | 16.55 |
October | 22.09 | 9.72 |
November | 21.74 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.69 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.01 | -3.4 |
February | 18.87 | -4.2 |
March | 20.89 | 2.67 |
April | 22.10 | 7.47 |
May | 23.34 | 13.73 |
June | 23.88 | 18.63 |
July | 23.90 | 22.03 |
August | 23.90 | 20.69 |
September | 23.87 | 16.55 |
October | 22.71 | 9.72 |
November | 21.48 | 6.03 |
December | 19.16 | -2.2 |
Annual Sum or Average | 21.94 | 9.05 |
Minimum of Months | 18.87 | -4.2 |
Maximum of Months | 23.90 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.82 | 2.67 |
April | 21.86 | 7.47 |
May | 22.53 | 13.73 |
June | 24.16 | 18.63 |
July | 24.38 | 22.03 |
August | 24.35 | 20.69 |
September | 24.03 | 16.55 |
October | 22.02 | 9.72 |
November | 21.73 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.67 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.81 | 2.67 |
April | 21.82 | 7.47 |
May | 22.40 | 13.73 |
June | 24.13 | 18.63 |
July | 24.38 | 22.03 |
August | 24.36 | 20.69 |
September | 24.07 | 16.55 |
October | 22.06 | 9.72 |
November | 21.74 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.66 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.81 | 2.67 |
April | 21.82 | 7.47 |
May | 22.39 | 13.73 |
June | 24.13 | 18.63 |
July | 24.38 | 22.03 |
August | 24.36 | 20.69 |
September | 24.07 | 16.55 |
October | 22.05 | 9.72 |
November | 21.74 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.66 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.88 | 2.67 |
April | 22.02 | 7.47 |
May | 22.67 | 13.73 |
June | 24.18 | 18.63 |
July | 24.38 | 22.03 |
August | 24.37 | 20.69 |
September | 24.22 | 16.55 |
October | 22.47 | 9.72 |
November | 21.87 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.77 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.89 | 2.67 |
April | 22.03 | 7.47 |
May | 22.68 | 13.73 |
June | 24.18 | 18.63 |
July | 24.38 | 22.03 |
August | 24.37 | 20.69 |
September | 24.22 | 16.55 |
October | 22.48 | 9.72 |
November | 21.87 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.77 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -3.4 |
February | 21.72 | -4.2 |
March | 22.30 | 2.67 |
April | 23.23 | 7.47 |
May | 24.33 | 13.73 |
June | 24.39 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.37 | 16.55 |
October | 23.67 | 9.72 |
November | 22.36 | 6.03 |
December | 21.71 | -2.2 |
Annual Sum or Average | 23.22 | 9.05 |
Minimum of Months | 21.71 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.09 | 2.67 |
April | 22.82 | 7.47 |
May | 24.29 | 13.73 |
June | 24.39 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.35 | 16.55 |
October | 23.08 | 9.72 |
November | 21.91 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 23.08 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -3.4 |
February | 21.71 | -4.2 |
March | 22.25 | 2.67 |
April | 23.19 | 7.47 |
May | 24.31 | 13.73 |
June | 24.39 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.37 | 16.55 |
October | 23.64 | 9.72 |
November | 22.32 | 6.03 |
December | 21.71 | -2.2 |
Annual Sum or Average | 23.21 | 9.05 |
Minimum of Months | 21.71 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.06 | 2.67 |
April | 22.75 | 7.47 |
May | 24.26 | 13.73 |
June | 24.38 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.33 | 16.55 |
October | 23.00 | 9.72 |
November | 21.87 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 23.05 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.15 | 2.67 |
April | 22.90 | 7.47 |
May | 24.33 | 13.73 |
June | 24.39 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.37 | 16.55 |
October | 23.37 | 9.72 |
November | 22.01 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 23.13 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.15 | 2.67 |
April | 22.89 | 7.47 |
May | 24.32 | 13.73 |
June | 24.39 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.37 | 16.55 |
October | 23.36 | 9.72 |
November | 22.00 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 23.13 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -3.4 |
February | 21.74 | -4.2 |
March | 22.48 | 2.67 |
April | 23.43 | 7.47 |
May | 24.36 | 13.73 |
June | 24.40 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.39 | 16.55 |
October | 23.99 | 9.72 |
November | 22.65 | 6.03 |
December | 21.73 | -2.2 |
Annual Sum or Average | 23.32 | 9.05 |
Minimum of Months | 21.73 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -3.4 |
February | 21.74 | -4.2 |
March | 22.47 | 2.67 |
April | 23.43 | 7.47 |
May | 24.36 | 13.73 |
June | 24.40 | 18.63 |
July | 24.40 | 22.03 |
August | 24.40 | 20.69 |
September | 24.39 | 16.55 |
October | 23.99 | 9.72 |
November | 22.65 | 6.03 |
December | 21.73 | -2.2 |
Annual Sum or Average | 23.32 | 9.05 |
Minimum of Months | 21.73 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -3.4 |
February | 21.72 | -4.2 |
March | 22.16 | 2.67 |
April | 22.64 | 7.47 |
May | 23.80 | 13.73 |
June | 24.27 | 18.63 |
July | 24.39 | 22.03 |
August | 24.38 | 20.69 |
September | 24.12 | 16.55 |
October | 22.86 | 9.72 |
November | 22.05 | 6.03 |
December | 21.71 | -2.2 |
Annual Sum or Average | 22.99 | 9.05 |
Minimum of Months | 21.71 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.00 | 2.67 |
April | 22.41 | 7.47 |
May | 23.71 | 13.73 |
June | 24.26 | 18.63 |
July | 24.39 | 22.03 |
August | 24.37 | 20.69 |
September | 24.01 | 16.55 |
October | 22.48 | 9.72 |
November | 21.82 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.89 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -3.4 |
February | 21.71 | -4.2 |
March | 22.14 | 2.67 |
April | 22.64 | 7.47 |
May | 23.81 | 13.73 |
June | 24.28 | 18.63 |
July | 24.39 | 22.03 |
August | 24.38 | 20.69 |
September | 24.11 | 16.55 |
October | 22.87 | 9.72 |
November | 22.04 | 6.03 |
December | 21.71 | -2.2 |
Annual Sum or Average | 22.99 | 9.05 |
Minimum of Months | 21.71 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 21.97 | 2.67 |
April | 22.38 | 7.47 |
May | 23.67 | 13.73 |
June | 24.25 | 18.63 |
July | 24.39 | 22.03 |
August | 24.36 | 20.69 |
September | 23.97 | 16.55 |
October | 22.41 | 9.72 |
November | 21.79 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.86 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.01 | 2.67 |
April | 22.38 | 7.47 |
May | 23.74 | 13.73 |
June | 24.28 | 18.63 |
July | 24.39 | 22.03 |
August | 24.38 | 20.69 |
September | 24.03 | 16.55 |
October | 22.49 | 9.72 |
November | 21.83 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.89 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.70 | -4.2 |
March | 22.01 | 2.67 |
April | 22.38 | 7.47 |
May | 23.74 | 13.73 |
June | 24.28 | 18.63 |
July | 24.39 | 22.03 |
August | 24.38 | 20.69 |
September | 24.03 | 16.55 |
October | 22.49 | 9.72 |
November | 21.82 | 6.03 |
December | 21.70 | -2.2 |
Annual Sum or Average | 22.89 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 24.39 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -3.4 |
February | 21.73 | -4.2 |
March | 22.22 | 2.67 |
April | 22.74 | 7.47 |
May | 23.90 | 13.73 |
June | 24.30 | 18.63 |
July | 24.40 | 22.03 |
August | 24.39 | 20.69 |
September | 24.20 | 16.55 |
October | 23.03 | 9.72 |
November | 22.14 | 6.03 |
December | 21.72 | -2.2 |
Annual Sum or Average | 23.05 | 9.05 |
Minimum of Months | 21.72 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -3.4 |
February | 21.73 | -4.2 |
March | 22.22 | 2.67 |
April | 22.74 | 7.47 |
May | 23.90 | 13.73 |
June | 24.30 | 18.63 |
July | 24.40 | 22.03 |
August | 24.39 | 20.69 |
September | 24.20 | 16.55 |
October | 23.03 | 9.72 |
November | 22.15 | 6.03 |
December | 21.72 | -2.2 |
Annual Sum or Average | 23.05 | 9.05 |
Minimum of Months | 21.72 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | -3.4 |
February | 20.79 | -4.2 |
March | 22.20 | 2.67 |
April | 23.34 | 7.47 |
May | 25.29 | 13.73 |
June | 26.42 | 18.63 |
July | 26.91 | 22.03 |
August | 26.69 | 20.69 |
September | 25.81 | 16.55 |
October | 23.56 | 9.72 |
November | 22.18 | 6.03 |
December | 20.88 | -2.2 |
Annual Sum or Average | 23.75 | 9.05 |
Minimum of Months | 20.79 | -4.2 |
Maximum of Months | 26.91 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.09 | -3.4 |
February | 18.95 | -4.2 |
March | 20.36 | 2.67 |
April | 21.38 | 7.47 |
May | 22.87 | 13.73 |
June | 25.24 | 18.63 |
July | 26.06 | 22.03 |
August | 25.89 | 20.69 |
September | 25.06 | 16.55 |
October | 22.13 | 9.72 |
November | 20.95 | 6.03 |
December | 19.31 | -2.2 |
Annual Sum or Average | 22.29 | 9.05 |
Minimum of Months | 18.95 | -4.2 |
Maximum of Months | 26.06 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:20:28
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | -3.4 |
February | 22.75 | -4.2 |
March | 23.86 | 2.67 |
April | 24.92 | 7.47 |
May | 26.49 | 13.73 |
June | 26.87 | 18.63 |
July | 27.03 | 22.03 |
August | 26.95 | 20.69 |
September | 26.68 | 16.55 |
October | 25.42 | 9.72 |
November | 23.87 | 6.03 |
December | 22.75 | -2.2 |
Annual Sum or Average | 25.04 | 9.05 |
Minimum of Months | 22.75 | -4.2 |
Maximum of Months | 27.03 | 22.03 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.118612E+12 | 76448.302 | 30-JAN-18:45 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32324.505 | 0.000 | 0.000 | 0.000 |
February | 0.107311E+12 | 76459.789 | 15-FEB-18:15 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32335.993 | 0.000 | 0.000 | 0.000 |
March | 0.118743E+12 | 75976.698 | 15-MAR-17:45 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 9198.849 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25162.383 | 0.000 | 0.000 | 0.000 |
April | 0.113473E+12 | 71129.266 | 26-APR-17:30 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 2177.710 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27336.090 | 0.000 | 0.000 | 0.000 |
May | 0.119634E+12 | 77134.553 | 27-MAY-17:45 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 7519.191 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27999.895 | 0.000 | 0.000 | 0.000 |
June | 0.125102E+12 | 86135.018 | 17-JUN-17:15 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 19320.059 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25199.492 | 0.000 | 0.000 | 0.000 |
July | 0.137777E+12 | 84299.763 | 24-JUL-17:15 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 16699.755 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25984.541 | 0.000 | 0.000 | 0.000 |
August | 0.132745E+12 | 85803.639 | 13-AUG-17:15 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 19197.598 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24990.575 | 0.000 | 0.000 | 0.000 |
September | 0.119131E+12 | 87654.879 | 16-SEP-17:30 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 16341.159 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29698.253 | 0.000 | 0.000 | 0.000 |
October | 0.114752E+12 | 73140.285 | 22-OCT-17:30 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 4191.985 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24824.504 | 0.000 | 0.000 | 0.000 |
November | 0.111542E+12 | 72655.453 | 22-NOV-18:45 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28531.656 | 0.000 | 0.000 | 0.000 |
December | 0.117242E+12 | 72629.014 | 12-DEC-18:45 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 0.000 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28505.218 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.143607E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.107311E+12 | 71129.266 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24824.504 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.137777E+12 | 87654.879 | 8572.775 | 26456.413 | 6586.279 | 0.000 | 19320.059 | 2508.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32335.993 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:20:28
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.118983E+12 | 93635.514 | 24-JAN-04:00 | 93635.514 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 93635.514 |
February | 0.114205E+12 | 107780.221 | 06-FEB-09:00 | 107780.221 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 107780.221 |
March | 0.540167E+11 | 68391.071 | 07-MAR-04:00 | 68391.071 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68391.071 |
April | 0.177171E+11 | 52775.948 | 16-APR-03:00 | 52775.948 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 52775.948 |
May | 0.962905E+09 | 7592.506 | 07-MAY-04:00 | 7592.506 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7592.506 |
June | 9246959.444 | 1249.949 | 14-JUN-04:30 | 1249.949 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1249.949 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.108546E+09 | 3640.508 | 30-SEP-05:00 | 3640.508 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3640.508 |
October | 0.928017E+10 | 29709.395 | 30-OCT-04:00 | 29709.395 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29709.395 |
November | 0.348698E+11 | 44377.100 | 24-NOV-03:00 | 44377.100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44377.100 |
December | 0.114662E+12 | 95410.956 | 26-DEC-07:15 | 95410.956 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 95410.956 |
Annual Sum or Average | 0.464814E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.118983E+12 | 107780.221 | 107780.221 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 107780.221 |