Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2018-10-19 09:20:32


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1538.62 490.85 544.84
Net Site Energy 1538.62 490.85 544.84
Total Source Energy 4548.89 1451.18 1610.81
Net Source Energy 4548.89 1451.18 1610.81


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 155.51 0.00 0.00 0.00 0.00
Cooling 49.14 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.35 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 197.21 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 420.99 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1383.11 155.51 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 155.51 0.00 0.00 0.00 0.00
Cooling General 49.14 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.35 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 197.21 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 420.99 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.36 0.00 0.00 0.00 0.00 0.00
HVAC 236.31 55.07 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 489.77 55.07 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.19 0.00 0.00 0.00 0.00 0.00
HVAC 212.89 49.61 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 441.24 49.61 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1383.11 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1383.11 100.00
     
Total On-Site and Utility Electric Sources 1383.11 100.00
Total Electricity End Uses 1383.11 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 91.75
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 569.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod William R Fairchild WA USA TMY3 WMO#=727885
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 22-JUL-17:15 30-DEC-01:00 - - - 01-JAN-07:15
Heating 0.00 44835.57 0.00 0.00 0.00 0.00
Cooling 16519.66 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6253.40 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25686.27 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 83488.51 44835.57 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 44835.57 0.00 0.00 0.00 0.00
Cooling General 16519.66 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6253.40 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 25686.27 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 168.57 0.00 0.00 0.00
Cooling 155.62 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 124.63 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 624.55 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1333.29 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4380.31 168.57 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 59.69 0.00 0.00 0.00
Cooling 55.11 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.13 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 221.16 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 472.13 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1551.12 59.69 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 59.69 0.00 0.00 0.00
Cooling 55.11 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.13 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 221.16 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 472.13 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1551.12 59.69 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.48_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.48_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.58 83.58 39.35
Exterior Lighting Total 2508.33           39.35



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   2694.87 2152.27 542.60 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   2123.72 1696.12 427.60 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7085.50 5658.87 1426.63 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   1404.99 1122.11 282.89 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1165.14 930.55 234.59 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1147.37 916.36 231.02 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1961.07 1566.22 394.85 0.80 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2013.97 1608.47 405.50 0.80 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   7670.58 6126.15 1544.43 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6060.53 4840.28 1220.26 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7027.33 5612.42 1414.92 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4473.92 3573.12 900.80 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3576.85 2856.67 720.18 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3543.37 2829.93 713.44 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5767.92 4606.58 1161.34 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5788.45 4622.98 1165.47 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5005.65 3997.79 1007.86 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3866.33 3087.87 778.47 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4655.56 3718.19 937.37 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2813.22 2246.79 566.43 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2236.79 1786.42 450.37 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2226.85 1778.48 448.36 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4045.65 3231.08 814.57 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4060.37 3242.84 817.53 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2567.3 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2023.2 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6750.1 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1338.5 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1110.0 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1093.1 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1868.2 3.13 10.67 11.09 10.38
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1918.6 3.13 10.67 11.09 10.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7307.4 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5773.6 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 6694.6 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4262.1 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3407.5 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3375.6 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5494.9 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5514.4 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4768.7 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3683.3 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4435.2 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2680.0 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2130.9 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2121.4 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3854.1 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3868.1 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1770.69 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1737.15 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   3496.66 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1740.13 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1687.09 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1687.09 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1687.09 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1687.09 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3374.19 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   2591.37 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   2588.12 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   2595.69 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   2592.44 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2084.35 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2084.47 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2085.84 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2085.96 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 182.35 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 143.70 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 479.45 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.08 95.07 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.07 78.84 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.07 77.64 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 132.70 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 136.28 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 519.04 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 410.09 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.42 475.51 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.73 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.03 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.76 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 390.29 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 391.68 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 338.71 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.62 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 315.02 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 190.36 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 151.35 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 150.68 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 273.75 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 274.75 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1714.03 2056.83 0.136 0.163 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 25.49 0.00838
G NW APARTMENT 1350.76 1620.91 0.107 0.128 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.22 0.00838
OFFICE 4418.05 5301.66 0.357 0.428 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 21.39 0.00838
G NE APARTMENT 893.58 1072.30 0.071 0.085 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 22.56 0.00838
G N1 APARTMENT 741.07 889.28 0.059 0.070 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.85 0.00838
G N2 APARTMENT 729.77 875.72 0.058 0.069 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.85 0.00838
G S1 APARTMENT 1247.30 1496.76 0.099 0.118 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 26.29 0.00838
G S2 APARTMENT 1280.95 1537.14 0.101 0.122 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17 0.00838
M SW APARTMENT 4878.75 5854.50 0.386 0.463 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 25.49 0.00838
M NW APARTMENT 3854.71 4625.65 0.305 0.366 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.22 0.00838
M SE APARTMENT 4469.62 5363.54 0.354 0.425 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17 0.00838
M NE APARTMENT 2845.52 3414.63 0.225 0.270 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:15:00 23.28 0.00838
M N1 APARTMENT 2275.00 2730.00 0.180 0.216 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.85 0.00838
M N2 APARTMENT 2253.70 2704.44 0.178 0.214 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.85 0.00838
M S1 APARTMENT 3668.59 4402.31 0.290 0.348 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40 0.00838
M S2 APARTMENT 3681.65 4417.98 0.291 0.350 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 26.29 0.00838
T SW APARTMENT 3183.76 3820.51 0.252 0.302 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 25.99 0.00838
T NW APARTMENT 2459.12 2950.95 0.195 0.234 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 24.67 0.00838
T SE APARTMENT 2961.09 3553.31 0.234 0.281 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 26.29 0.00838
T NE APARTMENT 1789.29 2147.15 0.142 0.170 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 24.53 0.00838
T N1 APARTMENT 1422.67 1707.21 0.113 0.135 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 25.31 0.00838
T N2 APARTMENT 1416.35 1699.62 0.112 0.135 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 26.26 0.00838
T S1 APARTMENT 2573.17 3087.80 0.204 0.244 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40 0.00838
T S2 APARTMENT 2582.53 3099.04 0.204 0.245 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40 0.00838


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 789.36 947.24 0.023 0.028 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
G NW APARTMENT 785.89 943.07 0.023 0.027 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
OFFICE 2009.83 2411.80 0.056 0.067 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -4.30 0.00266
G NE APARTMENT 788.41 946.09 0.023 0.028 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
G N1 APARTMENT 440.26 528.31 0.013 0.026 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
G N2 APARTMENT 440.32 528.38 0.013 0.026 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
G S1 APARTMENT 444.72 533.66 0.013 0.026 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
G S2 APARTMENT 518.01 621.62 0.015 0.026 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M SW APARTMENT 1294.15 1552.98 0.038 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M NW APARTMENT 1285.95 1543.14 0.037 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M SE APARTMENT 1301.07 1561.28 0.038 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M NE APARTMENT 1292.88 1551.45 0.038 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M N1 APARTMENT 387.74 465.29 0.011 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M N2 APARTMENT 387.96 465.55 0.011 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M S1 APARTMENT 399.74 479.68 0.012 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
M S2 APARTMENT 399.96 479.95 0.012 0.052 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T SW APARTMENT 1508.28 1809.93 0.044 0.053 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T NW APARTMENT 1505.52 1806.63 0.044 0.053 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T SE APARTMENT 1511.93 1814.31 0.044 0.053 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T NE APARTMENT 1509.18 1811.01 0.044 0.053 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T N1 APARTMENT 1079.50 1295.40 0.031 0.038 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T N2 APARTMENT 1079.60 1295.52 0.031 0.038 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T S1 APARTMENT 1080.76 1296.91 0.031 0.038 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266
T S2 APARTMENT 1080.86 1297.04 0.031 0.038 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -4.30 0.00266


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.16 0.16 0.03 0.03
SPLIT GNW 0.13 0.13 0.03 0.03
SPLIT OFFICE 0.43 0.43 0.07 0.07
SPLIT GNE 0.08 0.08 0.03 0.03
SPLIT GN1 0.07 0.07 0.03 0.03
SPLIT GN2 0.07 0.07 0.03 0.03
SPLIT GS1 0.12 0.12 0.03 0.03
SPLIT GS2 0.12 0.12 0.03 0.03
SPLIT MSW 0.46 0.46 0.05 0.05
SPLIT MNW 0.37 0.37 0.05 0.05
SPLIT MSE 0.42 0.42 0.05 0.05
SPLIT MNE 0.27 0.27 0.05 0.05
SPLIT MN1 0.22 0.22 0.05 0.05
SPLIT MN2 0.21 0.21 0.05 0.05
SPLIT MS1 0.35 0.35 0.05 0.05
SPLIT MS2 0.35 0.35 0.05 0.05
SPLIT TSW 0.30 0.30 0.05 0.05
SPLIT TNW 0.23 0.23 0.05 0.05
SPLIT TSE 0.28 0.28 0.05 0.05
SPLIT TNE 0.17 0.17 0.05 0.05
SPLIT TN1 0.14 0.14 0.04 0.04
SPLIT TN2 0.13 0.13 0.04 0.04
SPLIT TS1 0.24 0.24 0.04 0.04
SPLIT TS2 0.25 0.25 0.04 0.04



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 847.25 6703.50 60.75
G NW APARTMENT 503.00 7309.25 121.75
OFFICE 42.00 1706.00 15.00
G NE APARTMENT 446.00 7289.50 124.25
G N1 APARTMENT 160.00 7540.75 49.75
G N2 APARTMENT 159.00 7542.00 49.75
G S1 APARTMENT 638.75 6638.50 9.75
G S2 APARTMENT 611.25 6671.25 14.25
M SW APARTMENT 2227.00 4341.75 0.00
M NW APARTMENT 1730.75 5125.25 14.50
M SE APARTMENT 2288.75 4359.25 0.00
M NE APARTMENT 1727.25 5162.75 13.50
M N1 APARTMENT 1588.75 4953.00 0.00
M N2 APARTMENT 1589.75 4954.00 0.00
M S1 APARTMENT 2219.50 3804.75 0.00
M S2 APARTMENT 2223.75 3814.00 0.00
T SW APARTMENT 1919.25 5923.00 318.25
T NW APARTMENT 1727.50 6569.25 538.50
T SE APARTMENT 1971.75 5888.50 318.00
T NE APARTMENT 1771.75 6595.25 539.25
T N1 APARTMENT 1256.00 6656.75 194.25
T N2 APARTMENT 1257.25 6654.25 195.75
T S1 APARTMENT 1660.25 5739.50 99.25
T S2 APARTMENT 1663.25 5735.00 99.00
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 3150.75 7683.75 569.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 14.25 0.00 14.25 0.00
G NW APARTMENT 17.00 0.00 17.00 0.00
OFFICE 3.25 0.00 0.00 0.00
G NE APARTMENT 10.75 0.00 10.75 0.00
G N1 APARTMENT 2.50 0.00 2.50 0.00
G N2 APARTMENT 2.25 0.00 2.25 0.00
G S1 APARTMENT 3.75 0.00 3.75 0.00
G S2 APARTMENT 3.75 0.00 3.75 0.00
M SW APARTMENT 1.75 0.00 1.75 0.00
M NW APARTMENT 3.75 0.00 3.75 0.00
M SE APARTMENT 1.50 0.00 1.50 0.00
M NE APARTMENT 0.75 0.00 0.75 0.00
M N1 APARTMENT 0.25 0.00 0.25 0.00
M N2 APARTMENT 0.50 0.00 0.50 0.00
M S1 APARTMENT 0.25 0.00 0.25 0.00
M S2 APARTMENT 0.25 0.00 0.25 0.00
T SW APARTMENT 0.25 0.00 0.25 0.00
T NW APARTMENT 1.50 0.00 1.50 0.00
T SE APARTMENT 0.25 0.00 0.25 0.00
T NE APARTMENT 9.00 0.00 9.00 0.00
T N1 APARTMENT 12.25 0.00 12.25 0.00
T N2 APARTMENT 11.75 0.00 11.75 0.00
T S1 APARTMENT 3.75 0.00 3.75 0.00
T S2 APARTMENT 3.75 0.00 3.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 95.00 0.00 91.75 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.365 0.057 0.000 0.046
G NW APARTMENT 1.71 2.50 268.97 0.352 0.057 0.000 0.045
OFFICE 0.94 1.00 268.97 0.519 0.061 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.352 0.057 0.000 0.046
G N1 APARTMENT 1.71 2.50 268.97 0.352 0.034 0.000 0.045
G N2 APARTMENT 1.71 2.50 268.97 0.352 0.034 0.000 0.045
G S1 APARTMENT 1.71 2.50 268.97 0.352 0.034 0.000 0.046
G S2 APARTMENT 1.71 2.50 268.97 0.352 0.034 0.000 0.046
M SW APARTMENT 1.71 2.50 268.97 0.353 0.082 0.000 0.051
M NW APARTMENT 1.71 2.50 268.97 0.353 0.082 0.000 0.051
M SE APARTMENT 1.71 2.50 268.97 0.353 0.082 0.000 0.051
M NE APARTMENT 1.71 2.50 268.97 0.353 0.082 0.000 0.051
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.049 0.000 0.051
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.049 0.000 0.051
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.050 0.000 0.051
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.050 0.000 0.051
T SW APARTMENT 1.71 2.50 268.97 0.353 0.108 0.000 0.057
T NW APARTMENT 1.71 2.50 268.97 0.352 0.108 0.000 0.057
T SE APARTMENT 1.71 2.50 268.97 0.353 0.108 0.000 0.057
T NE APARTMENT 1.71 2.50 268.97 0.352 0.108 0.000 0.057
T N1 APARTMENT 1.71 2.50 268.97 0.352 0.065 0.000 0.057
T N2 APARTMENT 1.71 2.50 268.97 0.352 0.065 0.000 0.057
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.065 0.000 0.057
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.065 0.000 0.057
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.353 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.364 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.362 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.364 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.362 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 420.99 0.00 01-JAN-00:15 32349.32 01-JAN-07:00
WaterSystems:Electricity 420.99 0.00 01-JAN-00:15 32349.32 01-JAN-07:00
Water Heater:WaterSystems:Electricity 420.99 0.00 01-JAN-00:15 32349.32 01-JAN-07:00
Fans:Electricity 197.21 6253.40 01-JAN-00:15 6253.40 02-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
ElectricityPurchased:Plant 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
Cogeneration:ElectricityPurchased 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
ElectricityNet:Plant 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
Cogeneration:ElectricityNet 1383.11 19623.69 01-JAN-03:15 83488.51 22-JUL-17:15
ExteriorLights:Electricity 39.35 0.00 01-JAN-08:15 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.35 0.00 01-JAN-08:15 2508.33 01-JAN-00:15
Electricity:HVAC 246.34 6253.40 01-JAN-00:15 22843.10 22-JUL-18:00
General:Fans:Electricity 197.21 6253.40 01-JAN-00:15 6253.40 02-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 49.14 0.00 01-JAN-00:15 16589.71 22-JUL-18:00


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 155.51 0.00 18-MAR-16:15 44835.57 30-DEC-02:00
Gas:HVAC 155.51 0.00 18-MAR-16:15 44835.57 30-DEC-02:00
Heating:Gas 155.51 0.00 18-MAR-16:15 44835.57 30-DEC-02:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 710.95 2347.10 24-NOV-12:15 121132.78 22-JUL-17:15
EnergyTransfer:Building 389.48 2132.25 24-NOV-12:15 55024.57 22-JUL-16:15
EnergyTransfer:Zone:G SW APARTMENT 8.10 0.01 09-JAN-16:45 1702.71 22-JUL-17:15
Heating:EnergyTransfer 41.11 0.00 06-JAN-16:15 18703.88 30-DEC-02:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 1.67 0.00 01-JAN-09:30 689.43 28-DEC-02:00
Cooling:EnergyTransfer 348.37 204.34 03-DEC-04:45 55024.57 22-JUL-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 6.43 0.00 01-JAN-00:15 1702.71 22-JUL-17:15
EnergyTransfer:Zone:G NW APARTMENT 6.83 0.01 04-APR-04:45 1503.42 22-JUL-18:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 2.54 0.00 01-JAN-21:00 746.38 26-DEC-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 4.29 0.00 01-JAN-00:15 1503.42 22-JUL-18:15
EnergyTransfer:Zone:OFFICE 17.96 0.35 31-MAY-20:45 3086.44 27-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 0.10 0.00 01-JAN-00:15 1463.73 10-JAN-07:15
Cooling:EnergyTransfer:Zone:OFFICE 17.86 0.00 02-JAN-07:45 3086.44 27-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 7.02 0.03 01-MAR-14:15 1076.27 22-JUL-18:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 2.47 0.00 01-JAN-21:00 753.44 30-DEC-02:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 4.55 0.00 01-JAN-00:15 1076.27 22-JUL-18:30
EnergyTransfer:Zone:G N1 APARTMENT 6.00 0.15 13-JAN-15:15 887.95 22-JUL-18:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.77 0.00 01-JAN-16:45 393.72 30-DEC-02:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 5.23 0.00 01-JAN-00:15 887.95 22-JUL-18:30
EnergyTransfer:Zone:G N2 APARTMENT 6.01 0.04 06-NOV-04:00 877.61 22-JUL-18:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.77 0.00 01-JAN-16:45 394.42 30-DEC-02:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 5.24 0.00 01-JAN-00:15 877.61 22-JUL-18:30
EnergyTransfer:Zone:G S1 APARTMENT 7.69 0.08 21-NOV-02:00 1110.76 27-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.38 0.00 01-JAN-01:00 367.33 11-JAN-09:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.32 0.00 01-JAN-00:15 1110.76 27-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 7.62 0.05 25-FEB-06:45 1102.10 27-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.45 0.00 01-JAN-05:15 396.04 30-DEC-04:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.16 0.00 01-JAN-00:15 1102.10 27-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 31.07 1.27 16-FEB-09:15 4895.14 14-AUG-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.40 0.00 01-JAN-00:15 996.66 28-DEC-02:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 30.67 0.00 03-JAN-23:45 4895.14 14-AUG-16:15
EnergyTransfer:Zone:M NW APARTMENT 22.35 0.16 15-JAN-05:45 4401.37 13-JUN-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 1.16 0.00 01-JAN-01:00 1248.07 26-DEC-04:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 21.19 0.00 01-JAN-00:15 4401.37 13-JUN-17:15
EnergyTransfer:Zone:M SE APARTMENT 31.85 0.17 03-JAN-23:45 4173.95 22-JUL-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.40 0.00 01-JAN-00:15 982.27 28-DEC-02:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 31.46 0.00 03-JAN-24:00 4173.95 22-JUL-13:30
EnergyTransfer:Zone:M NE APARTMENT 23.32 0.01 25-DEC-10:30 3314.50 22-JUL-18:30
Heating:EnergyTransfer:Zone:M NE APARTMENT 1.14 0.00 01-JAN-01:00 1251.20 30-DEC-02:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 22.18 0.00 01-JAN-00:15 3314.50 22-JUL-18:30
EnergyTransfer:Zone:M N1 APARTMENT 24.84 0.37 26-DEC-23:15 2741.42 22-JUL-18:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.06 0.00 01-JAN-00:15 766.45 11-JAN-09:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 24.78 0.00 04-JAN-02:15 2741.42 22-JUL-18:30
EnergyTransfer:Zone:M N2 APARTMENT 24.83 0.07 09-DEC-03:15 2723.60 22-JUL-18:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.05 0.00 01-JAN-00:15 767.32 11-JAN-09:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 24.78 0.00 04-JAN-02:15 2723.60 22-JUL-18:30
EnergyTransfer:Zone:M S1 APARTMENT 34.21 0.80 29-DEC-03:45 3660.30 27-SEP-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.01 0.00 01-JAN-00:15 512.29 31-DEC-03:30
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 34.21 0.00 03-DEC-03:00 3660.30 27-SEP-13:30
EnergyTransfer:Zone:M S2 APARTMENT 34.20 4.04 29-DEC-03:45 3667.64 27-SEP-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.01 0.00 01-JAN-00:15 493.34 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 34.20 0.00 03-DEC-03:00 3667.64 27-SEP-13:30
EnergyTransfer:Zone:T SW APARTMENT 13.89 0.01 27-MAY-08:15 3187.39 21-JUL-16:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 4.06 0.00 01-JAN-10:00 1409.27 30-DEC-02:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 9.83 0.00 01-JAN-00:15 3187.39 21-JUL-16:30
EnergyTransfer:Zone:T NW APARTMENT 12.05 0.00 13-JUN-03:00 2915.99 13-JUN-17:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 5.68 0.00 06-JAN-12:00 1495.10 30-DEC-02:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 6.37 0.00 01-JAN-00:15 2915.99 13-JUN-17:15
EnergyTransfer:Zone:T SE APARTMENT 14.06 0.10 12-OCT-22:30 2846.84 22-JUL-13:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 4.03 0.00 01-JAN-09:15 1423.10 30-DEC-02:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 10.04 0.00 01-JAN-00:15 2846.84 22-JUL-13:30
EnergyTransfer:Zone:T NE APARTMENT 12.31 0.18 08-OCT-13:15 2146.22 22-JUL-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 5.62 0.00 06-JAN-11:15 1507.28 30-DEC-01:45
Cooling:EnergyTransfer:Zone:T NE APARTMENT 6.69 0.00 01-JAN-00:15 2146.22 22-JUL-16:15
EnergyTransfer:Zone:T N1 APARTMENT 9.62 0.06 06-NOV-11:45 1833.89 13-JUN-17:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 2.91 0.00 01-JAN-21:00 1004.77 30-DEC-02:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 6.71 0.00 01-JAN-00:15 1833.89 13-JUN-17:15
EnergyTransfer:Zone:T N2 APARTMENT 9.62 0.09 03-MAR-16:00 1812.95 13-JUN-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 2.92 0.00 01-JAN-21:00 1005.90 30-DEC-01:45
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 6.70 0.00 01-JAN-00:15 1812.95 13-JUN-16:15
EnergyTransfer:Zone:T S1 APARTMENT 12.00 0.01 16-OCT-01:45 2410.88 22-JUL-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 1.76 0.00 01-JAN-09:00 928.00 30-DEC-04:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.24 0.00 01-JAN-00:15 2410.88 22-JUL-14:15
EnergyTransfer:Zone:T S2 APARTMENT 12.01 0.14 05-MAR-10:30 2417.81 22-JUL-13:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 1.76 0.00 01-JAN-09:00 929.17 30-DEC-04:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.25 0.00 01-JAN-00:15 2417.81 22-JUL-13:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 321.47 0.00 18-MAR-16:15 66511.92 13-JUN-16:15
HeatingCoils:EnergyTransfer 124.41 0.00 18-MAR-16:15 35868.45 30-DEC-02:00
CoolingCoils:EnergyTransfer 197.06 0.00 01-JAN-00:15 66511.92 13-JUN-16:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 1.673 -6.432 0.000 0.000 3.896 2.413 12.213 11.044 0.000 0.003 0.000 0.000 -7.670 0.000 -2.806 -14.333
G NW APARTMENT 2.536 -4.294 0.000 0.000 3.927 2.413 12.213 5.300 0.000 0.003 0.000 0.000 -7.698 0.000 -2.733 -11.666
OFFICE 0.105 -17.858 0.000 0.000 0.522 21.914 7.534 11.089 0.000 0.002 0.001 0.000 -7.481 0.000 -1.978 -13.848
G NE APARTMENT 2.473 -4.547 0.000 0.000 3.939 2.413 12.213 5.318 0.000 0.003 0.000 0.000 -7.508 0.000 -2.735 -11.568
G N1 APARTMENT 0.767 -5.231 0.000 0.000 3.935 2.413 12.213 1.744 0.000 0.002 0.000 0.000 -4.721 0.000 -1.919 -9.204
G N2 APARTMENT 0.768 -5.238 0.000 0.000 3.936 2.413 12.213 1.744 0.000 0.002 0.000 0.000 -4.720 0.000 -1.919 -9.199
G S1 APARTMENT 0.377 -7.317 0.000 0.000 3.891 2.413 12.213 7.550 0.000 0.002 0.000 0.000 -4.708 0.000 -2.010 -12.411
G S2 APARTMENT 0.452 -7.165 0.000 0.000 3.891 2.413 12.213 7.550 0.000 0.002 0.000 0.000 -4.703 0.000 -2.011 -12.643
M SW APARTMENT 0.400 -30.672 0.000 0.000 3.708 2.413 12.213 10.568 0.000 0.004 13.857 0.000 -8.540 0.000 -3.950 -0.000
M NW APARTMENT 1.160 -21.189 0.000 0.000 3.782 2.413 12.213 4.878 0.000 0.004 9.039 0.000 -8.408 0.000 -3.891 -0.000
M SE APARTMENT 0.396 -31.457 0.000 0.000 3.716 2.413 12.213 10.623 0.000 0.004 14.408 0.000 -8.369 0.000 -3.946 -0.000
M NE APARTMENT 1.140 -22.181 0.000 0.000 3.797 2.413 12.213 4.893 0.000 0.004 9.784 0.000 -8.179 0.000 -3.882 -0.000
M N1 APARTMENT 0.058 -24.778 0.000 0.000 3.762 2.413 12.213 1.477 0.000 0.003 12.819 0.000 -5.247 0.000 -2.720 0.000
M N2 APARTMENT 0.054 -24.776 0.000 0.000 3.763 2.413 12.213 1.477 0.000 0.003 12.815 0.000 -5.244 0.000 -2.719 0.000
M S1 APARTMENT 0.006 -34.205 0.000 0.000 3.660 2.413 12.213 7.247 0.000 0.003 16.745 0.000 -5.314 0.000 -2.767 0.000
M S2 APARTMENT 0.005 -34.197 0.000 0.000 3.660 2.413 12.213 7.247 0.000 0.003 16.735 0.000 -5.313 0.000 -2.767 0.000
T SW APARTMENT 4.057 -9.831 0.000 0.000 3.840 2.413 12.213 10.598 0.000 0.005 0.000 0.000 -7.872 0.000 -4.900 -10.524
T NW APARTMENT 5.677 -6.375 0.000 0.000 3.890 2.413 12.213 4.931 0.000 0.005 0.000 0.000 -7.816 0.000 -4.815 -10.122
T SE APARTMENT 4.029 -10.035 0.000 0.000 3.847 2.413 12.213 10.673 0.000 0.005 0.000 0.000 -7.737 0.000 -4.902 -10.504
T NE APARTMENT 5.621 -6.691 0.000 0.000 3.905 2.413 12.213 4.970 0.000 0.005 0.000 0.000 -7.627 0.000 -4.813 -9.996
T N1 APARTMENT 2.914 -6.705 0.000 0.000 3.892 2.413 12.213 1.544 0.000 0.004 0.000 0.000 -4.814 0.000 -3.293 -8.168
T N2 APARTMENT 2.920 -6.704 0.000 0.000 3.893 2.413 12.213 1.542 0.000 0.004 0.000 0.000 -4.811 0.000 -3.294 -8.175
T S1 APARTMENT 1.762 -10.238 0.000 0.000 3.820 2.413 12.213 7.288 0.000 0.003 0.000 0.000 -4.873 0.000 -3.374 -9.014
T S2 APARTMENT 1.764 -10.249 0.000 0.000 3.820 2.413 12.213 7.286 0.000 0.003 0.000 0.000 -4.871 0.000 -3.374 -9.004
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.026 0.000 0.000 0.000 0.000 -0.973 0.000 -0.732 -15.391
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 0.122 0.000 0.007 1.268 0.000 -2.575 0.000 -22.157 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.024 0.000 0.000 0.000 0.000 -1.095 0.000 -0.610 -15.389
Total Facility 41.113 -348.367 0.000 0.000 88.692 128.627 294.692 148.752 0.000 0.083 107.471 0.000 -158.886 0.000 -101.017 -201.159


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 22-JUL-17:15 0.00 -1702.97 0.00 0.00 141.81 194.45 588.62 1634.61 0.00 19.73 0.00 0.00 0.00 0.00 0.00 -876.26
G NW APARTMENT 22-JUL-18:15 0.00 -1503.43 0.00 0.00 141.81 230.46 547.42 1555.74 0.00 7.24 0.00 0.00 0.00 0.00 0.00 -979.24
OFFICE 27-SEP-13:30 0.00 -3086.23 0.00 0.00 67.31 1622.34 544.92 2243.44 0.00 0.00 0.00 0.00 0.00 0.00 -13.39 -1378.38
G NE APARTMENT 22-JUL-18:30 0.00 -1076.29 0.00 0.00 141.81 230.46 547.42 579.84 0.00 13.81 0.00 0.00 0.00 0.00 0.00 -437.05
G N1 APARTMENT 22-JUL-18:30 0.00 -887.97 0.00 0.00 141.81 230.46 547.42 448.23 0.00 8.33 0.00 0.00 0.00 0.00 0.00 -488.28
G N2 APARTMENT 22-JUL-18:30 0.00 -877.63 0.00 0.00 141.81 230.46 547.42 448.41 0.00 8.33 0.00 0.00 0.00 0.00 0.00 -498.81
G S1 APARTMENT 27-SEP-13:30 0.00 -1110.61 0.00 0.00 40.75 28.81 382.60 2100.12 0.00 0.00 0.00 0.00 0.00 0.00 -75.64 -1366.04
G S2 APARTMENT 27-SEP-13:30 0.00 -1101.95 0.00 0.00 40.75 28.81 382.60 2100.26 0.00 0.00 0.00 0.00 0.00 0.00 -75.64 -1374.84
M SW APARTMENT 14-AUG-16:15 0.00 -4894.44 0.00 0.00 84.76 144.04 588.62 1992.45 0.00 68.30 2016.27 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 13-JUN-17:15 0.00 -4401.15 0.00 0.00 141.81 194.45 588.62 1892.81 0.00 62.54 1520.92 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 22-JUL-13:30 0.00 -4173.64 0.00 0.00 40.75 28.81 382.60 1793.67 0.00 38.88 1888.93 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 22-JUL-18:30 0.00 -3314.58 0.00 0.00 141.81 230.46 547.42 566.21 0.00 19.77 1808.91 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 22-JUL-18:30 0.00 -2741.47 0.00 0.00 141.81 230.46 547.42 438.08 0.00 11.93 1371.78 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 22-JUL-18:30 0.00 -2723.65 0.00 0.00 141.81 230.46 547.42 438.19 0.00 11.93 1353.85 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 27-SEP-13:30 0.00 -3659.83 0.00 0.00 40.75 28.81 382.60 2087.21 0.00 0.00 1208.80 0.00 0.00 0.00 -88.34 0.00
M S2 APARTMENT 27-SEP-13:30 0.00 -3667.17 0.00 0.00 40.75 28.81 382.60 2087.16 0.00 0.00 1216.19 0.00 0.00 0.00 -88.34 0.00
T SW APARTMENT 21-JUL-16:30 0.00 -3187.36 0.00 0.00 84.76 144.04 588.62 2014.89 0.00 16.97 338.08 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 13-JUN-17:15 0.00 -2915.86 0.00 0.00 141.81 194.45 588.62 1862.73 0.00 75.93 52.31 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 22-JUL-13:30 0.00 -2846.66 0.00 0.00 40.75 28.81 382.60 1762.13 0.00 50.85 581.52 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 22-JUL-16:15 0.00 -2146.40 0.00 0.00 84.76 144.04 588.62 612.52 0.00 46.87 669.59 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 13-JUN-17:15 0.00 -1833.81 0.00 0.00 141.81 194.45 588.62 329.00 0.00 67.20 512.73 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 13-JUN-16:15 0.00 -1812.86 0.00 0.00 84.76 144.04 588.62 327.89 0.00 112.36 555.19 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 22-JUL-14:15 0.00 -2410.76 0.00 0.00 40.75 50.41 400.26 1258.51 0.00 31.66 629.17 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 22-JUL-13:45 0.00 -2417.66 0.00 0.00 40.75 28.81 382.60 1424.08 0.00 30.67 510.76 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-JUL-16:15 0.00 -55024.69 0.00 0.00 1949.42 5316.35 14071.03 20309.95 0.00 1213.55 12164.39 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 17-OCT-06:01 1455.86 0.00 0.00 0.00 163.11 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -397.16 0.00 -57.44 -1640.60
G NW APARTMENT 25-OCT-06:01 1408.56 0.00 0.00 0.00 163.32 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -382.47 0.00 -53.54 -1612.09
OFFICE 24-DEC-07:01 3135.76 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -389.79 0.00 -51.60 -3268.94
G NE APARTMENT 26-JAN-17:01 1384.17 0.00 0.00 0.00 99.98 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -346.21 0.00 -35.45 -1835.15
G N1 APARTMENT 28-FEB-07:01 1212.18 0.00 0.00 0.00 161.32 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -230.82 0.00 -35.82 -1583.09
G N2 APARTMENT 28-FEB-07:01 1211.23 0.00 0.00 0.00 161.32 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -230.75 0.00 -35.82 -1582.21
G S1 APARTMENT 15-NOV-07:01 1371.73 0.00 0.00 0.00 163.31 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -215.78 0.00 -158.66 -1636.83
G S2 APARTMENT 01-FEB-07:01 1343.15 0.00 0.00 0.00 163.32 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -227.56 0.00 -38.44 -1716.71
M SW APARTMENT 26-FEB-07:01 2122.47 0.00 0.00 0.00 161.44 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -563.33 0.00 -193.71 -2003.10
M NW APARTMENT 29-NOV-17:01 2561.73 0.00 0.00 0.00 100.00 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -482.16 0.00 -124.62 -2787.61
M SE APARTMENT 08-JAN-08:02 1193.37 0.00 0.00 0.00 74.05 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -254.33 0.00 -312.45 -1132.34
M NE APARTMENT 03-DEC-17:01 2052.51 0.00 0.00 0.00 98.72 144.04 588.62 0.00 0.00 0.00 0.00 0.00 -496.08 0.00 -185.00 -2202.81
M N1 APARTMENT 11-JAN-08:19 1990.65 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -378.32 0.00 -78.03 -2039.97
M N2 APARTMENT 11-JAN-08:19 1988.78 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -378.31 0.00 -78.03 -2038.12
M S1 APARTMENT 31-DEC-03:30 1024.59 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -342.79 0.00 -75.76 -1033.78
M S2 APARTMENT 17-DEC-01:30 829.89 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -321.52 0.00 -125.98 -827.80
T SW APARTMENT 03-APR-06:01 1603.27 0.00 0.00 0.00 162.59 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -394.58 0.00 0.00 -1847.51
T NW APARTMENT 14-APR-06:01 2229.18 0.00 0.00 0.00 163.11 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -281.14 0.00 0.00 -2587.39
T SE APARTMENT 30-DEC-02:00 1423.07 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -627.01 0.00 -432.62 -808.85
T NE APARTMENT 30-DEC-01:45 1507.25 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -612.49 0.00 -432.62 -907.56
T N1 APARTMENT 30-DEC-02:00 1004.75 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -371.54 0.00 -260.95 -817.67
T N2 APARTMENT 30-DEC-01:45 1005.88 0.00 0.00 0.00 189.67 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -372.33 0.00 -260.95 -818.00
T S1 APARTMENT 12-NOV-07:01 1559.31 0.00 0.00 0.00 162.54 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -252.07 0.00 -86.48 -1859.52
T S2 APARTMENT 12-NOV-07:01 1558.97 0.00 0.00 0.00 162.53 93.63 382.60 0.00 0.00 0.00 0.00 0.00 -252.05 0.00 -86.48 -1859.20
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-DEC-02:00 18259.68 0.00 0.00 0.00 4362.43 2334.74 5719.80 0.00 0.00 0.00 0.00 0.00 -12432.00 0.00 -6462.97 -11781.69



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Sec1.1A-General Information

Data
Weather File William R Fairchild WA USA TMY3 WMO#=727885
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 91.75
Number of hours cooling loads not met 0.00
Number of hours not met 91.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.35 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 155.51 44835.57 0.00 0.00
Space Cooling 49.14 16519.66 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 197.21 6253.40 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 420.99 25686.27 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1383.11   155.51   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1383.11
Natural Gas 0.00 155.51
Additional 0.00 0.00
Total 511.42 1538.62


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 15.68
Fans-Interior 62.91
Service Water Heating 134.30
Receptacle Equipment 163.15
Miscellaneous 12.55
Subtotal 441.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 49.61
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 49.61


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.72
Space Heating 10.11
Space Cooling 3.19
Fans-Interior 12.82
Service Water Heating 27.36
Receptacle Equipment 33.24
Miscellaneous 2.56



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.162797
G NW APARTMENT DIRECT AIR 0.128294
OFFICE DIRECT AIR 0.428035
G NE APARTMENT DIRECT AIR 0.084876
G N1 APARTMENT DIRECT AIR 0.070386
G N2 APARTMENT DIRECT AIR 0.069313
G S1 APARTMENT DIRECT AIR 0.118468
G S2 APARTMENT DIRECT AIR 0.121664
M SW APARTMENT DIRECT AIR 0.463380
M NW APARTMENT DIRECT AIR 0.366117
M SE APARTMENT DIRECT AIR 0.424521
M NE APARTMENT DIRECT AIR 0.270270
M N1 APARTMENT DIRECT AIR 0.216077
M N2 APARTMENT DIRECT AIR 0.214055
M S1 APARTMENT DIRECT AIR 0.348440
M S2 APARTMENT DIRECT AIR 0.349681
T SW APARTMENT DIRECT AIR 0.302391
T NW APARTMENT DIRECT AIR 0.233565
T SE APARTMENT DIRECT AIR 0.281242
T NE APARTMENT DIRECT AIR 0.169947
T N1 APARTMENT DIRECT AIR 0.135124
T N2 APARTMENT DIRECT AIR 0.134524
T S1 APARTMENT DIRECT AIR 0.244398
T S2 APARTMENT DIRECT AIR 0.245287


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.162797
SPLIT GNW MAIN BRANCH 0.128294
SPLIT OFFICE MAIN BRANCH 0.428035
SPLIT GNE MAIN BRANCH 0.084876
SPLIT GN1 MAIN BRANCH 0.070386
SPLIT GN2 MAIN BRANCH 0.069313
SPLIT GS1 MAIN BRANCH 0.118468
SPLIT GS2 MAIN BRANCH 0.121664
SPLIT MSW MAIN BRANCH 0.463380
SPLIT MNW MAIN BRANCH 0.366117
SPLIT MSE MAIN BRANCH 0.424521
SPLIT MNE MAIN BRANCH 0.270270
SPLIT MN1 MAIN BRANCH 0.216077
SPLIT MN2 MAIN BRANCH 0.214055
SPLIT MS1 MAIN BRANCH 0.348440
SPLIT MS2 MAIN BRANCH 0.349681
SPLIT TSW MAIN BRANCH 0.302391
SPLIT TNW MAIN BRANCH 0.233565
SPLIT TSE MAIN BRANCH 0.281242
SPLIT TNE MAIN BRANCH 0.169947
SPLIT TN1 MAIN BRANCH 0.135124
SPLIT TN2 MAIN BRANCH 0.134524
SPLIT TS1 MAIN BRANCH 0.244398
SPLIT TS2 MAIN BRANCH 0.245287


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.162797
SPLIT GNW 0.128294
SPLIT OFFICE 0.428035
SPLIT GNE 0.084876
SPLIT GN1 0.070386
SPLIT GN2 0.069313
SPLIT GS1 0.118468
SPLIT GS2 0.121664
SPLIT MSW 0.463380
SPLIT MNW 0.366117
SPLIT MSE 0.424521
SPLIT MNE 0.270270
SPLIT MN1 0.216077
SPLIT MN2 0.214055
SPLIT MS1 0.348440
SPLIT MS2 0.349681
SPLIT TSW 0.302391
SPLIT TNW 0.233565
SPLIT TSE 0.281242
SPLIT TNE 0.169947
SPLIT TN1 0.135124
SPLIT TN2 0.134524
SPLIT TS1 0.244398
SPLIT TS2 0.245287


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.162797 0.026898
SPLIT GNW OA CONTROLLER 0.128294 0.025953
SPLIT OFFICE OA CONTROLLER 0.428035 0.038104
SPLIT GNE OA CONTROLLER 0.084876 0.025953
SPLIT GN1 OA CONTROLLER 0.070386 0.025953
SPLIT GN2 OA CONTROLLER 0.069313 0.025953
SPLIT GS1 OA CONTROLLER 0.118468 0.025953
SPLIT GS2 OA CONTROLLER 0.121664 0.025953
SPLIT MSW OA CONTROLLER 0.463380 0.051906
SPLIT MNW OA CONTROLLER 0.366117 0.051906
SPLIT MSE OA CONTROLLER 0.424521 0.051906
SPLIT MNE OA CONTROLLER 0.270270 0.051906
SPLIT MN1 OA CONTROLLER 0.216077 0.051906
SPLIT MN2 OA CONTROLLER 0.214055 0.051906
SPLIT MS1 OA CONTROLLER 0.348440 0.051906
SPLIT MS2 OA CONTROLLER 0.349681 0.051906
SPLIT TSW OA CONTROLLER 0.302391 0.025953
SPLIT TNW OA CONTROLLER 0.233565 0.025953
SPLIT TSE OA CONTROLLER 0.281242 0.025953
SPLIT TNE OA CONTROLLER 0.169947 0.025953
SPLIT TN1 OA CONTROLLER 0.135124 0.025953
SPLIT TN2 OA CONTROLLER 0.134524 0.025953
SPLIT TS1 OA CONTROLLER 0.244398 0.025953
SPLIT TS2 OA CONTROLLER 0.245287 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.162797 2694.87 0.798655
SPLIT GNW COOLING COIL 0.128294 2123.72 0.798655
SPLIT OFFICE COOLING COIL 0.428035 7085.50 0.798655
SPLIT GNE COOLING COIL 0.084876 1404.99 0.798655
SPLIT GN1 COOLING COIL 0.070386 1165.14 0.798655
SPLIT GN2 COOLING COIL 0.069313 1147.37 0.798655
SPLIT GS1 COOLING COIL 0.118468 1961.07 0.798655
SPLIT GS2 COOLING COIL 0.121664 2013.97 0.798655
SPLIT MSW COOLING COIL 0.463380 7670.58 0.798655
SPLIT MNW COOLING COIL 0.366117 6060.53 0.798655
SPLIT MSE COOLING COIL 0.424521 7027.33 0.798655
SPLIT MNE COOLING COIL 0.270270 4473.92 0.798655
SPLIT MN1 COOLING COIL 0.216077 3576.85 0.798655
SPLIT MN2 COOLING COIL 0.214055 3543.37 0.798655
SPLIT MS1 COOLING COIL 0.348440 5767.92 0.798655
SPLIT MS2 COOLING COIL 0.349681 5788.45 0.798655
SPLIT TSW COOLING COIL 0.302391 5005.65 0.798655
SPLIT TNW COOLING COIL 0.233565 3866.33 0.798655
SPLIT TSE COOLING COIL 0.281242 4655.56 0.798655
SPLIT TNE COOLING COIL 0.169947 2813.22 0.798655
SPLIT TN1 COOLING COIL 0.135124 2236.79 0.798655
SPLIT TN2 COOLING COIL 0.134524 2226.85 0.798655
SPLIT TS1 COOLING COIL 0.244398 4045.65 0.798655
SPLIT TS2 COOLING COIL 0.245287 4060.37 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.162797 0.162797 0.162797 0.162797 1770.69 2694.87 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.128294 0.128294 0.128294 0.128294 1737.15 2123.72 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.428035 0.428035 0.428035 0.428035 3496.66 7085.50 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.084876 0.084876 0.084876 0.084876 1740.13 1404.99 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.070386 0.070386 0.070386 0.070386 1687.09 1165.14 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.069313 0.069313 0.069313 0.069313 1687.09 1147.37 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.118468 0.118468 0.118468 0.118468 1687.09 1961.07 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.121664 0.121664 0.121664 0.121664 1687.09 2013.97 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.463380 0.463380 0.463380 0.463380 3374.19 7670.58 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.366117 0.366117 0.366117 0.366117 3374.19 6060.53 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.424521 0.424521 0.424521 0.424521 3374.19 7027.33 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.270270 0.270270 0.270270 0.270270 3374.19 4473.92 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.216077 0.216077 0.216077 0.216077 3374.19 3576.85 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.214055 0.214055 0.214055 0.214055 3374.19 3543.37 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.348440 0.348440 0.348440 0.348440 3374.19 5767.92 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.349681 0.349681 0.349681 0.349681 3374.19 5788.45 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.302391 0.302391 0.302391 0.302391 2591.37 5005.65 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.233565 0.233565 0.233565 0.233565 2588.12 3866.33 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.281242 0.281242 0.281242 0.281242 2595.69 4655.56 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.169947 0.169947 0.169947 0.169947 2592.44 2813.22 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.135124 0.135124 0.135124 0.135124 2084.35 2236.79 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.134524 0.134524 0.134524 0.134524 2084.47 2226.85 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.244398 0.244398 0.244398 0.244398 2085.84 4045.65 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.245287 0.245287 0.245287 0.245287 2085.96 4060.37 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.162797
SPLIT GNW SUPPLY FAN 0.128294
SPLIT OFFICE SUPPLY FAN 0.428035
SPLIT GNE SUPPLY FAN 0.084876
SPLIT GN1 SUPPLY FAN 0.070386
SPLIT GN2 SUPPLY FAN 0.069313
SPLIT GS1 SUPPLY FAN 0.118468
SPLIT GS2 SUPPLY FAN 0.121664
SPLIT MSW SUPPLY FAN 0.463380
SPLIT MNW SUPPLY FAN 0.366117
SPLIT MSE SUPPLY FAN 0.424521
SPLIT MNE SUPPLY FAN 0.270270
SPLIT MN1 SUPPLY FAN 0.216077
SPLIT MN2 SUPPLY FAN 0.214055
SPLIT MS1 SUPPLY FAN 0.348440
SPLIT MS2 SUPPLY FAN 0.349681
SPLIT TSW SUPPLY FAN 0.302391
SPLIT TNW SUPPLY FAN 0.233565
SPLIT TSE SUPPLY FAN 0.281242
SPLIT TNE SUPPLY FAN 0.169947
SPLIT TN1 SUPPLY FAN 0.135124
SPLIT TN2 SUPPLY FAN 0.134524
SPLIT TS1 SUPPLY FAN 0.244398
SPLIT TS2 SUPPLY FAN 0.245287


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1770.69
SPLIT GNW HEATING COIL 1737.15
SPLIT OFFICE HEATING COIL 3496.66
SPLIT GNE HEATING COIL 1740.13
SPLIT GN1 HEATING COIL 1687.09
SPLIT GN2 HEATING COIL 1687.09
SPLIT GS1 HEATING COIL 1687.09
SPLIT GS2 HEATING COIL 1687.09
SPLIT MSW HEATING COIL 3374.19
SPLIT MNW HEATING COIL 3374.19
SPLIT MSE HEATING COIL 3374.19
SPLIT MNE HEATING COIL 3374.19
SPLIT MN1 HEATING COIL 3374.19
SPLIT MN2 HEATING COIL 3374.19
SPLIT MS1 HEATING COIL 3374.19
SPLIT MS2 HEATING COIL 3374.19
SPLIT TSW HEATING COIL 2591.37
SPLIT TNW HEATING COIL 2588.12
SPLIT TSE HEATING COIL 2595.69
SPLIT TNE HEATING COIL 2592.44
SPLIT TN1 HEATING COIL 2084.35
SPLIT TN2 HEATING COIL 2084.47
SPLIT TS1 HEATING COIL 2085.84
SPLIT TS2 HEATING COIL 2085.96



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:32

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.18
February 21.80 4.25
March 21.76 5.90
April 22.50 8.96
May 22.49 9.99
June 23.87 13.31
July 24.13 15.02
August 24.22 15.65
September 24.02 13.43
October 22.32 9.33
November 21.79 6.66
December 21.71 4.10
     
Annual Sum or Average 22.70 9.26
Minimum of Months 21.71 4.10
Maximum of Months 24.22 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 4.18
February 21.70 4.25
March 21.71 5.90
April 22.08 8.96
May 22.19 9.99
June 23.71 13.31
July 24.02 15.02
August 24.07 15.65
September 23.69 13.43
October 21.91 9.33
November 21.70 6.66
December 21.70 4.10
     
Annual Sum or Average 22.52 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.07 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.40 4.18
February 21.46 4.25
March 21.82 5.90
April 22.80 8.96
May 22.87 9.99
June 23.80 13.31
July 23.87 15.02
August 23.90 15.65
September 23.84 13.43
October 22.74 9.33
November 21.90 6.66
December 20.97 4.10
     
Annual Sum or Average 22.62 9.26
Minimum of Months 20.97 4.10
Maximum of Months 23.90 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 4.18
February 21.70 4.25
March 21.70 5.90
April 22.04 8.96
May 22.12 9.99
June 23.63 13.31
July 23.99 15.02
August 24.05 15.65
September 23.68 13.43
October 21.87 9.33
November 21.70 6.66
December 21.70 4.10
     
Annual Sum or Average 22.49 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.05 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 4.18
February 21.70 4.25
March 21.71 5.90
April 21.92 8.96
May 21.99 9.99
June 23.60 13.31
July 23.96 15.02
August 24.02 15.65
September 23.68 13.43
October 21.88 9.33
November 21.71 6.66
December 21.70 4.10
     
Annual Sum or Average 22.47 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.02 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 4.18
February 21.70 4.25
March 21.71 5.90
April 21.92 8.96
May 21.99 9.99
June 23.60 13.31
July 23.96 15.02
August 24.02 15.65
September 23.68 13.43
October 21.88 9.33
November 21.71 6.66
December 21.70 4.10
     
Annual Sum or Average 22.47 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.02 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.18
February 21.81 4.25
March 21.77 5.90
April 22.44 8.96
May 22.40 9.99
June 23.91 13.31
July 24.17 15.02
August 24.26 15.65
September 24.12 13.43
October 22.41 9.33
November 21.83 6.66
December 21.72 4.10
     
Annual Sum or Average 22.72 9.26
Minimum of Months 21.72 4.10
Maximum of Months 24.26 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.18
February 21.81 4.25
March 21.78 5.90
April 22.45 8.96
May 22.41 9.99
June 23.90 13.31
July 24.16 15.02
August 24.25 15.65
September 24.11 13.43
October 22.42 9.33
November 21.84 6.66
December 21.72 4.10
     
Annual Sum or Average 22.72 9.26
Minimum of Months 21.72 4.10
Maximum of Months 24.25 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.57 4.18
February 22.63 4.25
March 22.81 5.90
April 24.19 8.96
May 24.23 9.99
June 24.38 13.31
July 24.39 15.02
August 24.40 15.65
September 24.38 13.43
October 24.00 9.33
November 22.95 6.66
December 21.85 4.10
     
Annual Sum or Average 23.57 9.26
Minimum of Months 21.85 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 4.18
February 21.80 4.25
March 22.16 5.90
April 23.82 8.96
May 24.07 9.99
June 24.36 13.31
July 24.38 15.02
August 24.40 15.65
September 24.29 13.43
October 23.37 9.33
November 22.03 6.66
December 21.70 4.10
     
Annual Sum or Average 23.19 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.52 4.18
February 22.53 4.25
March 22.73 5.90
April 24.19 8.96
May 24.22 9.99
June 24.37 13.31
July 24.39 15.02
August 24.40 15.65
September 24.37 13.43
October 23.97 9.33
November 22.89 6.66
December 21.85 4.10
     
Annual Sum or Average 23.54 9.26
Minimum of Months 21.85 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.18
February 21.74 4.25
March 22.02 5.90
April 23.79 8.96
May 24.03 9.99
June 24.33 13.31
July 24.36 15.02
August 24.39 15.65
September 24.28 13.43
October 23.21 9.33
November 21.91 6.66
December 21.70 4.10
     
Annual Sum or Average 23.14 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.39 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 4.18
February 21.83 4.25
March 22.32 5.90
April 23.89 8.96
May 24.16 9.99
June 24.37 13.31
July 24.39 15.02
August 24.40 15.65
September 24.34 13.43
October 23.67 9.33
November 22.27 6.66
December 21.72 4.10
     
Annual Sum or Average 23.28 9.26
Minimum of Months 21.72 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 4.18
February 21.83 4.25
March 22.30 5.90
April 23.89 8.96
May 24.16 9.99
June 24.37 13.31
July 24.39 15.02
August 24.40 15.65
September 24.34 13.43
October 23.65 9.33
November 22.25 6.66
December 21.72 4.10
     
Annual Sum or Average 23.27 9.26
Minimum of Months 21.72 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 4.18
February 23.13 4.25
March 23.26 5.90
April 24.29 8.96
May 24.32 9.99
June 24.39 13.31
July 24.40 15.02
August 24.40 15.65
September 24.40 13.43
October 24.23 9.33
November 23.51 6.66
December 22.07 4.10
     
Annual Sum or Average 23.79 9.26
Minimum of Months 22.07 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 4.18
February 23.12 4.25
March 23.26 5.90
April 24.29 8.96
May 24.32 9.99
June 24.39 13.31
July 24.40 15.02
August 24.40 15.65
September 24.40 13.43
October 24.23 9.33
November 23.51 6.66
December 22.07 4.10
     
Annual Sum or Average 23.78 9.26
Minimum of Months 22.07 4.10
Maximum of Months 24.40 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 4.18
February 22.14 4.25
March 22.16 5.90
April 23.34 8.96
May 23.38 9.99
June 24.05 13.31
July 24.18 15.02
August 24.25 15.65
September 23.93 13.43
October 22.77 9.33
November 22.04 6.66
December 21.78 4.10
     
Annual Sum or Average 23.00 9.26
Minimum of Months 21.78 4.10
Maximum of Months 24.25 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 4.18
February 21.73 4.25
March 21.87 5.90
April 22.95 8.96
May 23.09 9.99
June 23.92 13.31
July 24.09 15.02
August 24.10 15.65
September 23.56 13.43
October 22.25 9.33
November 21.74 6.66
December 21.70 4.10
     
Annual Sum or Average 22.73 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.10 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 4.18
February 22.10 4.25
March 22.13 5.90
April 23.39 8.96
May 23.41 9.99
June 24.03 13.31
July 24.17 15.02
August 24.23 15.65
September 23.93 13.43
October 22.76 9.33
November 22.02 6.66
December 21.78 4.10
     
Annual Sum or Average 23.00 9.26
Minimum of Months 21.78 4.10
Maximum of Months 24.23 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 4.18
February 21.70 4.25
March 21.80 5.90
April 22.98 8.96
May 23.07 9.99
June 23.84 13.31
July 24.02 15.02
August 24.03 15.65
September 23.55 13.43
October 22.18 9.33
November 21.71 6.66
December 21.70 4.10
     
Annual Sum or Average 22.69 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.03 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 4.18
February 21.70 4.25
March 21.82 5.90
April 22.87 8.96
May 23.07 9.99
June 23.94 13.31
July 24.11 15.02
August 24.10 15.65
September 23.57 13.43
October 22.19 9.33
November 21.73 6.66
December 21.70 4.10
     
Annual Sum or Average 22.71 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.11 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 4.18
February 21.70 4.25
March 21.82 5.90
April 22.88 8.96
May 23.07 9.99
June 23.93 13.31
July 24.11 15.02
August 24.09 15.65
September 23.57 13.43
October 22.18 9.33
November 21.73 6.66
December 21.70 4.10
     
Annual Sum or Average 22.71 9.26
Minimum of Months 21.70 4.10
Maximum of Months 24.11 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.06 4.18
February 22.19 4.25
March 22.23 5.90
April 23.45 8.96
May 23.53 9.99
June 24.14 13.31
July 24.25 15.02
August 24.31 15.65
September 24.06 13.43
October 22.92 9.33
November 22.14 6.66
December 21.81 4.10
     
Annual Sum or Average 23.09 9.26
Minimum of Months 21.81 4.10
Maximum of Months 24.31 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.06 4.18
February 22.19 4.25
March 22.23 5.90
April 23.45 8.96
May 23.53 9.99
June 24.14 13.31
July 24.25 15.02
August 24.31 15.65
September 24.06 13.43
October 22.93 9.33
November 22.14 6.66
December 21.81 4.10
     
Annual Sum or Average 23.09 9.26
Minimum of Months 21.81 4.10
Maximum of Months 24.31 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 4.18
February 22.17 4.25
March 22.46 5.90
April 24.36 8.96
May 24.56 9.99
June 25.66 13.31
July 25.96 15.02
August 25.93 15.65
September 25.24 13.43
October 23.28 9.33
November 22.23 6.66
December 21.66 4.10
     
Annual Sum or Average 23.80 9.26
Minimum of Months 21.66 4.10
Maximum of Months 25.96 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 4.18
February 20.58 4.25
March 20.87 5.90
April 21.94 8.96
May 22.17 9.99
June 24.24 13.31
July 24.84 15.02
August 24.99 15.65
September 24.48 13.43
October 21.98 9.33
November 20.98 6.66
December 20.38 4.10
     
Annual Sum or Average 22.34 9.26
Minimum of Months 20.38 4.10
Maximum of Months 24.99 15.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.95 4.18
February 24.03 4.25
March 24.33 5.90
April 26.12 8.96
May 26.32 9.99
June 26.66 13.31
July 26.75 15.02
August 26.77 15.65
September 26.60 13.43
October 25.68 9.33
November 24.38 6.66
December 23.31 4.10
     
Annual Sum or Average 25.41 9.26
Minimum of Months 23.31 4.10
Maximum of Months 26.77 15.65



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:32

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.115963E+12 73811.755 08-JAN-18:45 8572.775 26456.413 6253.396 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 30020.841 0.000 0.000 0.000
February 0.104596E+12 72413.973 06-FEB-18:00 8572.775 26456.413 6253.396 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 28623.060 0.000 0.000 0.000
March 0.115155E+12 72508.448 09-MAR-18:45 8572.775 26456.413 6253.396 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 28717.535 0.000 0.000 0.000
April 0.114151E+12 75989.478 30-APR-18:15 9689.078 23563.017 6253.396 0.000 11321.604 0.000 0.000 0.000 0.000 0.000 0.000 25162.384 0.000 0.000 0.000
May 0.116634E+12 74428.958 02-MAY-17:00 8572.775 26456.413 6253.396 0.000 3625.353 0.000 0.000 0.000 0.000 0.000 0.000 29521.022 0.000 0.000 0.000
June 0.116189E+12 80341.853 13-JUN-17:30 8572.775 26456.413 6253.396 0.000 15069.115 0.000 0.000 0.000 0.000 0.000 0.000 23990.155 0.000 0.000 0.000
July 0.121657E+12 83488.510 22-JUL-17:15 8572.775 26456.413 6253.396 0.000 16519.656 0.000 0.000 0.000 0.000 0.000 0.000 25686.270 0.000 0.000 0.000
August 0.121908E+12 80866.297 17-AUG-17:15 8572.775 26456.413 6253.396 0.000 11604.508 0.000 0.000 0.000 0.000 0.000 0.000 27979.206 0.000 0.000 0.000
September 0.115957E+12 77875.028 13-SEP-17:15 8572.775 26456.413 6253.396 0.000 11377.367 0.000 0.000 0.000 0.000 0.000 0.000 25215.078 0.000 0.000 0.000
October 0.114848E+12 71905.844 25-OCT-17:00 8572.775 26456.413 6253.396 0.000 835.875 2508.330 0.000 0.000 0.000 0.000 0.000 27279.055 0.000 0.000 0.000
November 0.110714E+12 73068.972 27-NOV-18:30 8572.775 26456.413 6253.396 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 29278.059 0.000 0.000 0.000
December 0.115340E+12 71699.177 04-DEC-18:45 8572.775 26456.413 6253.396 0.000 0.000 2508.330 0.000 0.000 0.000 0.000 0.000 27908.263 0.000 0.000 0.000
                                     
Annual Sum or Average 0.138311E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.104596E+12 71699.177   8572.775 23563.017 6253.396 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 23990.155 0.000 0.000 0.000
Maximum of Months 0.121908E+12 83488.510   9689.078 26456.413 6253.396 0.000 16519.656 2508.330 0.000 0.000 0.000 0.000 0.000 30020.841 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:32

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.321544E+11 43885.602 10-JAN-05:00 43885.602 0.000 0.000 0.000 0.000 0.000 43885.602
February 0.259112E+11 39343.772 17-FEB-03:00 39343.772 0.000 0.000 0.000 0.000 0.000 39343.772
March 0.178306E+11 23686.537 04-MAR-03:00 23686.537 0.000 0.000 0.000 0.000 0.000 23686.537
April 0.459242E+10 12496.826 01-APR-03:00 12496.826 0.000 0.000 0.000 0.000 0.000 12496.826
May 0.321431E+10 13358.111 05-MAY-03:00 13358.111 0.000 0.000 0.000 0.000 0.000 13358.111
June 0.687649E+08 4040.387 08-JUN-03:00 4040.387 0.000 0.000 0.000 0.000 0.000 4040.387
July 2035689.900 412.411 05-JUL-03:00 412.411 0.000 0.000 0.000 0.000 0.000 412.411
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.854254E+08 2185.844 20-SEP-03:00 2185.844 0.000 0.000 0.000 0.000 0.000 2185.844
October 0.613261E+10 11595.760 28-OCT-06:00 11595.760 0.000 0.000 0.000 0.000 0.000 11595.760
November 0.202654E+11 35620.526 29-NOV-03:00 35620.526 0.000 0.000 0.000 0.000 0.000 35620.526
December 0.452513E+11 44835.565 30-DEC-01:00 44835.565 0.000 0.000 0.000 0.000 0.000 44835.565
                     
Annual Sum or Average 0.155509E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.452513E+11 44835.565   44835.565 0.000 0.000 0.000 0.000 0.000 44835.565