Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Honolulu Intl Arpt HI USA TMY3 WMO#=911820

Simulation Timestamp: 2018-10-19 09:20:28


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1636.84 522.18 579.62
Net Site Energy 1636.84 522.18 579.62
Total Source Energy 5183.87 1653.75 1835.66
Net Source Energy 5183.87 1653.75 1835.66


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 404.82 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 220.22 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 295.89 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1636.84 0.00 0.00 0.00 0.00 1874.72


End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 404.82 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 138.97 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 26.03 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 511.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 220.22 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 295.89 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 72.41 0.00 0.00 0.00 0.00 0.00
HVAC 326.11 0.00 0.00 0.00 0.00 0.66
Other 181.10 0.00 0.00 0.00 0.00 0.00
Total 579.62 0.00 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.23 0.00 0.00 0.00 0.00 0.00
HVAC 293.80 0.00 0.00 0.00 0.00 0.60
Other 163.15 0.00 0.00 0.00 0.00 0.00
Total 522.18 0.00 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1636.84 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1636.84 100.00
     
Total On-Site and Utility Electric Sources 1636.84 100.00
Total Electricity End Uses 1636.84 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 112.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2852.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:20
RunPeriod Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Latitude [deg] 21.32
Longitude [deg] -157.9
Elevation [m] 2.00
Time Zone -10.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 14.4236 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 8.5250   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 8.5250   208.0991
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 8.5250   0.0000
Total 3134.61     9553.84   1542.04 306.92 14.1058 39.93 11.1646
Conditioned Total 2823.98     8607.06   1501.17 300.26 14.7196 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 8.5250   52.0248
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 05-SEP-17:45 - - - - 01-JAN-07:15
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 24976.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8572.78 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6983.10 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22083.37 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 89071.84 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 24976.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7168.38 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1404.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26456.41 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6983.10 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 22083.37 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 1282.08 0.00 0.00 0.00 0.00
Interior Lighting 522.56 0.00 0.00 0.00 0.00
Exterior Lighting 125.04 0.00 0.00 0.00 0.00
Interior Equipment 1619.66 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 697.43 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 937.09 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 5183.87 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 454.00 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.28 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 246.97 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 331.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1835.66 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 454.00 0.00 0.00 0.00 0.00
Interior Lighting 185.05 0.00 0.00 0.00 0.00
Exterior Lighting 44.28 0.00 0.00 0.00 0.00
Interior Equipment 573.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 246.97 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 331.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1835.66 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 16.20 0.00 16.20 Wetbulb [C] 1.90 320.00
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 32.20 7.10 23.30 Wetbulb [C] 6.70 60.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 5.778 0.306 0.155     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 5.778 0.306 0.155     No M EWALL C 270.00 90.00 W
Total or Average           306.92 5.778 0.306 0.155              
North Total or Average           112.97 5.778 0.306 0.155              
Non-North Total or Average           193.95 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GNW G NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_HARDWIRED_GNE G NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSW M SW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNW M NW APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MSE M SE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MNE M NE APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 11.5174 176.50 2032.80 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSW T SW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNW T NW APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TSE T SE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TNE T NE APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 11.5174 88.25 1016.40 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
LIGHTING_HARDWIRED_GC G CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_MC M CORRIDOR 8.5250 155.32 1324.09 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_HARDWIRED_TC T CORRIDOR 8.5250 77.66 662.05 GeneralLights LTG_COR_SCH 137.36 168.00 137.36 0.0000 N 17.07
LIGHTING_PLUGIN_GSW G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GNW G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_OFFICE OFFICE 11.9479 88.25 1054.40 GeneralLights-plugin LTG_OFF_SCH 56.36 168.00 55.36 0.0000 Y 10.96
LIGHTING_PLUGIN_GNE G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSW M SW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNW M NW APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MSE M SE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MNE M NE APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 2.9063 176.50 512.95 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSW T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNW T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TSE T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TNE T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.4206 5958.59 44216.13               128.63


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2508.33 AstronomicalClock -   83.86 83.86 39.48
Exterior Lighting Total 2508.33           39.48



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4117.17 3051.06 1066.11 0.74 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4056.69 3011.64 1045.05 0.74 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7717.34 6049.38 1667.96 0.78 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3177.03 2304.68 872.34 0.73 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2427.09 1719.93 707.17 0.71 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2408.06 1704.67 703.39 0.71 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2417.48 1708.35 709.13 0.71 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2410.01 1708.18 701.83 0.71 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9769.43 7308.69 2460.74 0.75 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   9646.28 7213.20 2433.08 0.75 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8071.79 5927.27 2144.52 0.73 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7717.59 5663.41 2054.18 0.73 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5889.20 4246.72 1642.48 0.72 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5857.57 4221.27 1636.31 0.72 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5919.19 4261.79 1657.40 0.72 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5889.71 4238.14 1651.56 0.72 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5923.40 4461.56 1461.84 0.75 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5793.45 4363.06 1430.38 0.75 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5000.01 3688.78 1311.22 0.74 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4665.57 3445.11 1220.46 0.74 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3621.04 2649.53 971.50 0.73 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3588.01 2622.90 965.11 0.73 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3994.70 2922.43 1072.27 0.73 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4002.57 2928.88 1073.70 0.73 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3952.4 3.23 11.02 11.47 10.88
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3893.6 3.23 11.01 11.46 10.87
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7366.5 3.15 10.76 11.18 10.50
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3056.2 3.26 11.11 11.57 11.03
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2339.9 3.29 11.22 11.69 11.19
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2321.8 3.29 11.23 11.69 11.19
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2331.3 3.29 11.23 11.70 11.21
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2323.4 3.29 11.22 11.69 11.19
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 9369.7 3.22 10.97 11.42 10.82
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 9252.0 3.22 10.98 11.42 10.82
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7755.6 3.24 11.06 11.51 10.94
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7415.8 3.24 11.06 11.51 10.95
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5668.4 3.27 11.14 11.60 11.07
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5638.3 3.27 11.14 11.60 11.07
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5698.1 3.27 11.15 11.61 11.08
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5670.0 3.27 11.15 11.61 11.08
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5677.2 3.21 10.94 11.38 10.77
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5552.7 3.21 10.94 11.38 10.77
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4802.0 3.23 11.04 11.49 10.91
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4480.4 3.23 11.03 11.48 10.91
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3480.4 3.25 11.08 11.53 10.97
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3449.0 3.25 11.08 11.53 10.98
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3839.6 3.25 11.08 11.53 10.97
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3847.1 3.25 11.08 11.53 10.97
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1099.98 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   1558.20 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2122.63 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1061.31 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1061.31 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 234.95 1120.11 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.49 1120.11 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 501.20 1120.11 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.15 1120.11 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 124.02 1120.11 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 122.72 1120.11 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 122.65 1120.11 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 123.21 1120.11 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 570.19 1120.11 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 562.38 1120.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 450.61 1120.11 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 430.14 1120.11 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 314.44 1120.11 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 312.26 1120.11 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 314.83 1120.11 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 312.82 1120.11 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 351.27 1120.11 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 343.45 1120.11 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.29 1120.11 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 263.97 1120.11 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 200.40 1120.11 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.12 1120.11 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 220.99 1120.11 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 221.55 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.89



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2231.72 2678.07 0.175 0.210 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
G NW APARTMENT 2208.37 2650.04 0.173 0.208 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
OFFICE 4531.68 5438.02 0.373 0.447 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 28.90 0.01435
G NE APARTMENT 1635.15 1962.18 0.128 0.154 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
G N1 APARTMENT 1178.07 1413.68 0.092 0.111 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
G N2 APARTMENT 1165.74 1398.89 0.091 0.110 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
G S1 APARTMENT 1165.07 1398.09 0.091 0.109 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
G S2 APARTMENT 1170.40 1404.48 0.092 0.110 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
M SW APARTMENT 5416.02 6499.23 0.424 0.509 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
M NW APARTMENT 5341.87 6410.25 0.418 0.502 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
M SE APARTMENT 4279.87 5135.84 0.335 0.402 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 30.92 0.01435
M NE APARTMENT 4085.46 4902.55 0.320 0.384 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
M N1 APARTMENT 2986.82 3584.19 0.234 0.281 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
M N2 APARTMENT 2966.16 3559.39 0.232 0.279 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
M S1 APARTMENT 2990.60 3588.71 0.234 0.281 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
M S2 APARTMENT 2971.47 3565.76 0.233 0.279 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
T SW APARTMENT 3336.29 4003.55 0.261 0.314 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 31.03 0.01435
T NW APARTMENT 3262.18 3914.62 0.256 0.307 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
T SE APARTMENT 2681.03 3217.24 0.210 0.252 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 32.11 0.01435
T NE APARTMENT 2507.03 3008.44 0.196 0.236 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 30.92 0.01435
T N1 APARTMENT 1903.57 2284.29 0.149 0.179 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
T N2 APARTMENT 1881.90 2258.29 0.147 0.177 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
T S1 APARTMENT 2098.98 2518.78 0.164 0.197 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 32.20 0.01435
T S2 APARTMENT 2104.32 2525.19 0.165 0.198 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 32.20 0.01435


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 0.67 0.81 0.000 0.027 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
G NW APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
OFFICE 414.78 497.73 0.012 0.038 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 09:00:00 16.20 0.01152
G NE APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M SW APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M NW APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M SE APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M NE APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M N1 APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M N2 APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M S1 APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M S2 APARTMENT 0.00 0.00 0.000 0.052 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
T SW APARTMENT 244.36 293.23 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T NW APARTMENT 244.35 293.22 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T SE APARTMENT 245.17 294.20 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T NE APARTMENT 245.15 294.18 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T N1 APARTMENT 18.38 22.05 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T N2 APARTMENT 18.44 22.13 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T S1 APARTMENT 13.26 15.91 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152
T S2 APARTMENT 13.37 16.04 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 04:00:00 16.20 0.01152


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.21 0.21 0.03 0.03
SPLIT GNW 0.21 0.21 0.03 0.03
SPLIT OFFICE 0.45 0.45 0.04 0.04
SPLIT GNE 0.15 0.15 0.03 0.03
SPLIT GN1 0.11 0.11 0.03 0.03
SPLIT GN2 0.11 0.11 0.03 0.03
SPLIT GS1 0.11 0.11 0.03 0.03
SPLIT GS2 0.11 0.11 0.03 0.03
SPLIT MSW 0.51 0.51 0.05 0.05
SPLIT MNW 0.50 0.50 0.05 0.05
SPLIT MSE 0.40 0.40 0.05 0.05
SPLIT MNE 0.38 0.38 0.05 0.05
SPLIT MN1 0.28 0.28 0.05 0.05
SPLIT MN2 0.28 0.28 0.05 0.05
SPLIT MS1 0.28 0.28 0.05 0.05
SPLIT MS2 0.28 0.28 0.05 0.05
SPLIT TSW 0.31 0.31 0.03 0.03
SPLIT TNW 0.31 0.31 0.03 0.03
SPLIT TSE 0.25 0.25 0.03 0.03
SPLIT TNE 0.24 0.24 0.03 0.03
SPLIT TN1 0.18 0.18 0.03 0.03
SPLIT TN2 0.18 0.18 0.03 0.03
SPLIT TS1 0.20 0.20 0.03 0.03
SPLIT TS2 0.20 0.20 0.03 0.03



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 7998.25 1865.75 1725.25
G NW APARTMENT 7663.75 2454.00 2170.00
OFFICE 1408.25 49.00 0.00
G NE APARTMENT 7736.50 2399.00 2105.50
G N1 APARTMENT 7448.75 3076.25 2708.25
G N2 APARTMENT 7451.50 3064.00 2697.25
G S1 APARTMENT 7813.50 2172.75 2014.25
G S2 APARTMENT 7787.25 2298.00 2119.00
M SW APARTMENT 8742.50 129.75 129.75
M NW APARTMENT 8693.50 192.75 192.75
M SE APARTMENT 8742.50 117.00 117.00
M NE APARTMENT 8710.25 169.25 169.25
M N1 APARTMENT 8705.75 167.00 167.00
M N2 APARTMENT 8705.50 165.75 165.75
M S1 APARTMENT 8749.75 99.75 99.75
M S2 APARTMENT 8749.75 98.50 98.50
T SW APARTMENT 8563.25 406.00 390.75
T NW APARTMENT 8485.75 578.25 554.75
T SE APARTMENT 8575.00 375.25 357.75
T NE APARTMENT 8505.00 586.50 559.00
T N1 APARTMENT 8576.00 553.75 536.25
T N2 APARTMENT 8575.75 552.00 534.00
T S1 APARTMENT 8640.50 329.50 321.75
T S2 APARTMENT 8640.50 327.50 319.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 8749.75 3241.75 2852.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 0.00 0.00 0.00
G NW APARTMENT 0.00 0.00 0.00 0.00
OFFICE 0.00 0.00 0.00 0.00
G NE APARTMENT 0.00 0.50 0.00 0.50
G N1 APARTMENT 0.00 0.00 0.00 0.00
G N2 APARTMENT 0.00 0.00 0.00 0.00
G S1 APARTMENT 0.00 0.00 0.00 0.00
G S2 APARTMENT 0.00 0.00 0.00 0.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.50 0.00 0.50
M N1 APARTMENT 0.00 0.00 0.00 0.00
M N2 APARTMENT 0.00 0.00 0.00 0.00
M S1 APARTMENT 0.00 101.50 0.00 101.50
M S2 APARTMENT 0.00 111.50 0.00 111.50
T SW APARTMENT 0.00 0.00 0.00 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 0.00 0.00 0.00 0.00
T N2 APARTMENT 0.00 0.00 0.00 0.00
T S1 APARTMENT 0.00 9.00 0.00 9.00
T S2 APARTMENT 0.00 9.00 0.00 9.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 0.00 112.00 0.00 112.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.371 0.114 0.000 0.105
G NW APARTMENT 1.71 2.50 268.97 0.358 0.114 0.000 0.114
OFFICE 0.94 1.00 268.97 0.523 0.137 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.358 0.114 0.000 0.115
G N1 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.114
G N2 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.114
G S1 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.105
G S2 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.105
M SW APARTMENT 1.71 2.50 268.97 0.357 0.164 0.000 0.137
M NW APARTMENT 1.71 2.50 268.97 0.357 0.164 0.000 0.151
M SE APARTMENT 1.71 2.50 268.97 0.357 0.164 0.000 0.137
M NE APARTMENT 1.71 2.50 268.97 0.357 0.164 0.000 0.151
M N1 APARTMENT 1.71 2.50 268.97 0.357 0.099 0.000 0.151
M N2 APARTMENT 1.71 2.50 268.97 0.357 0.099 0.000 0.151
M S1 APARTMENT 1.71 2.50 268.97 0.357 0.099 0.000 0.137
M S2 APARTMENT 1.71 2.50 268.97 0.357 0.099 0.000 0.137
T SW APARTMENT 1.71 2.50 268.97 0.357 0.217 0.000 0.180
T NW APARTMENT 1.71 2.50 268.97 0.357 0.217 0.000 0.201
T SE APARTMENT 1.71 2.50 268.97 0.357 0.217 0.000 0.180
T NE APARTMENT 1.71 2.50 268.97 0.357 0.217 0.000 0.201
T N1 APARTMENT 1.71 2.50 268.97 0.357 0.131 0.000 0.201
T N2 APARTMENT 1.71 2.50 268.97 0.357 0.131 0.000 0.201
T S1 APARTMENT 1.71 2.50 268.97 0.357 0.131 0.000 0.180
T S2 APARTMENT 1.71 2.50 268.97 0.357 0.131 0.000 0.180
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.363 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.514 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.401 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.400 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1425
Defaulted Fields 439
Fields with Defaults 3748
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
Electricity:Building 676.42 10861.97 01-JAN-03:15 35029.19 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity 165.00 2991.26 01-JAN-00:15 9689.08 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 138.97 2711.50 01-JAN-00:15 8059.76 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.45 508.27 01-JAN-00:15 2167.25 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.91 379.58 01-JAN-00:15 1622.34 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 29.25 476.16 01-JAN-03:15 1566.15 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 4.83 28.81 01-JAN-00:15 460.92 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.08 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 142.36 1349.33 01-JAN-00:15 8621.71 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 34.14 1082.58 01-JAN-00:15 1082.58 01-JAN-00:15
Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 17.07 541.29 01-JAN-00:15 541.29 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 26.03 279.76 01-JAN-00:15 1629.32 01-JAN-19:15
InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 511.42 7870.70 01-JAN-03:15 26522.71 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.53 128.69 01-JAN-00:15 544.92 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 125.29 808.04 01-JAN-00:15 8080.42 01-JAN-07:15
Electricity:Plant 295.89 0.00 01-JAN-00:15 24818.74 13-DEC-07:30
WaterSystems:Electricity 295.89 0.00 01-JAN-00:15 24818.74 13-DEC-07:30
Water Heater:WaterSystems:Electricity 295.89 0.00 01-JAN-00:15 24818.74 13-DEC-07:30
Fans:Electricity 220.22 6983.10 01-JAN-00:15 6983.10 05-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
ElectricityPurchased:Plant 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
Cogeneration:ElectricityPurchased 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
ElectricityNet:Plant 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
Cogeneration:ElectricityNet 1636.84 20896.40 12-FEB-03:30 89071.84 05-SEP-17:45
ExteriorLights:Electricity 39.48 0.00 01-JAN-07:15 2508.33 01-JAN-00:15
General:ExteriorLights:Electricity 39.48 0.00 01-JAN-07:15 2508.33 01-JAN-00:15
Electricity:HVAC 625.04 7110.75 11-FEB-06:15 34444.44 03-SEP-16:15
General:Fans:Electricity 220.22 6983.10 01-JAN-00:15 6983.10 05-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 404.82 127.65 11-FEB-06:15 27461.34 03-SEP-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Gas:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Gas 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2670.58 2970.69 11-FEB-06:15 179498.55 03-SEP-16:15
EnergyTransfer:Building 991.45 2334.10 11-FEB-07:00 70709.58 03-SEP-16:15
EnergyTransfer:Zone:G SW APARTMENT 21.28 0.05 09-DEC-06:15 2538.11 22-SEP-16:30
Heating:EnergyTransfer 1.17 0.00 01-JAN-09:45 1640.87 27-APR-05:45
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.18 0.00 01-JAN-00:15 157.78 27-MAR-08:45
Cooling:EnergyTransfer 990.28 1706.03 11-FEB-07:00 70709.58 03-SEP-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 21.10 0.00 01-JAN-01:45 2538.11 22-SEP-16:30
EnergyTransfer:Zone:G NW APARTMENT 17.31 0.09 29-MAY-02:15 2258.45 04-SEP-17:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 0.37 0.00 01-JAN-09:30 204.59 26-MAR-09:30
Cooling:EnergyTransfer:Zone:G NW APARTMENT 16.94 0.00 01-JAN-00:15 2258.45 04-SEP-17:15
EnergyTransfer:Zone:OFFICE 38.96 0.24 27-MAR-05:15 3755.81 16-OCT-10:30
Heating:EnergyTransfer:Zone:OFFICE 0.01 0.00 01-JAN-00:15 209.55 27-APR-05:45
Cooling:EnergyTransfer:Zone:OFFICE 38.94 0.00 07-JAN-07:00 3755.81 16-OCT-10:30
EnergyTransfer:Zone:G NE APARTMENT 18.62 0.03 15-JAN-05:15 2075.42 25-JUN-06:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.17 0.00 01-JAN-07:30 144.29 17-FEB-01:15
Cooling:EnergyTransfer:Zone:G NE APARTMENT 18.44 0.00 01-JAN-00:15 2075.42 25-JUN-06:00
EnergyTransfer:Zone:G N1 APARTMENT 12.32 0.03 08-DEC-06:00 1284.55 09-JUL-17:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.10 0.00 01-JAN-01:00 152.48 28-JAN-10:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 12.22 0.00 01-JAN-00:15 1284.55 09-JUL-17:15
EnergyTransfer:Zone:G N2 APARTMENT 12.37 0.00 28-APR-00:45 1278.52 09-JUL-17:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.09 0.00 01-JAN-01:00 141.94 28-MAR-09:45
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 12.28 0.00 01-JAN-00:15 1278.52 09-JUL-17:15
EnergyTransfer:Zone:G S1 APARTMENT 16.46 0.00 20-APR-05:00 1601.33 21-NOV-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.03 0.00 01-JAN-00:15 100.45 17-FEB-03:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 16.43 0.00 08-JAN-04:00 1601.33 21-NOV-13:30
EnergyTransfer:Zone:G S2 APARTMENT 16.12 0.01 29-MAR-01:15 1589.91 21-NOV-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.04 0.00 01-JAN-00:15 108.02 17-FEB-02:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 16.08 0.00 06-JAN-03:00 1589.91 21-NOV-13:30
EnergyTransfer:Zone:M SW APARTMENT 79.63 16.47 08-MAR-07:15 6404.36 06-NOV-14:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 79.63 16.47 08-MAR-07:15 6404.36 06-NOV-14:30
EnergyTransfer:Zone:M NW APARTMENT 67.54 3.38 08-MAR-07:30 5474.10 04-SEP-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 73.42 12-FEB-08:30
Cooling:EnergyTransfer:Zone:M NW APARTMENT 67.53 0.00 08-FEB-07:30 5474.10 04-SEP-17:15
EnergyTransfer:Zone:M SE APARTMENT 83.99 38.06 15-FEB-06:15 6181.18 15-DEC-11:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 83.99 38.06 15-FEB-06:15 6181.18 15-DEC-11:30
EnergyTransfer:Zone:M NE APARTMENT 71.87 39.53 15-FEB-07:00 5346.33 27-MAY-06:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 71.87 39.53 15-FEB-07:00 5346.33 27-MAY-06:00
EnergyTransfer:Zone:M N1 APARTMENT 56.15 179.32 12-FEB-08:30 3316.60 09-JUL-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 56.15 179.32 12-FEB-08:30 3316.60 09-JUL-17:15
EnergyTransfer:Zone:M N2 APARTMENT 56.30 180.85 12-FEB-08:30 3309.30 09-JUL-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 56.30 180.85 12-FEB-08:30 3309.30 09-JUL-17:15
EnergyTransfer:Zone:M S1 APARTMENT 68.34 348.15 08-MAR-07:15 4773.58 23-DEC-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 68.34 348.15 08-MAR-07:15 4773.58 23-DEC-13:30
EnergyTransfer:Zone:M S2 APARTMENT 68.48 349.52 08-MAR-07:15 4758.22 23-DEC-13:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 68.48 349.52 08-MAR-07:15 4758.22 23-DEC-13:45
EnergyTransfer:Zone:T SW APARTMENT 40.77 0.37 26-DEC-02:30 3898.61 11-OCT-14:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 0.04 0.00 01-JAN-00:15 230.08 27-APR-05:45
Cooling:EnergyTransfer:Zone:T SW APARTMENT 40.73 0.00 01-JAN-06:15 3898.61 11-OCT-14:30
EnergyTransfer:Zone:T NW APARTMENT 35.06 0.02 29-DEC-05:00 3427.63 03-SEP-16:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 0.07 0.00 01-JAN-00:15 245.13 27-APR-06:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 34.99 0.00 01-JAN-06:15 3427.63 03-SEP-16:15
EnergyTransfer:Zone:T SE APARTMENT 42.75 0.13 12-FEB-04:30 3716.12 15-DEC-11:45
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.02 0.00 01-JAN-00:15 174.97 27-APR-05:45
Cooling:EnergyTransfer:Zone:T SE APARTMENT 42.72 0.00 01-JAN-06:15 3716.12 15-DEC-11:45
EnergyTransfer:Zone:T NE APARTMENT 36.99 0.01 08-FEB-05:15 2918.95 12-JUL-10:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 0.03 0.00 01-JAN-00:15 167.81 27-APR-06:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 36.95 0.00 01-JAN-06:15 2918.95 12-JUL-10:15
EnergyTransfer:Zone:T N1 APARTMENT 29.55 0.02 27-FEB-06:45 2192.82 03-SEP-16:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 85.29 27-APR-06:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 29.55 0.00 05-JAN-06:30 2192.82 03-SEP-16:15
EnergyTransfer:Zone:T N2 APARTMENT 29.64 0.15 17-JAN-06:45 2179.37 03-SEP-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 83.14 27-APR-06:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 29.63 0.00 05-JAN-06:30 2179.37 03-SEP-16:15
EnergyTransfer:Zone:T S1 APARTMENT 35.45 0.23 28-MAR-06:00 3051.09 15-DEC-12:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 90.05 27-APR-05:45
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 35.44 0.00 07-JAN-06:15 3051.09 15-DEC-12:30
EnergyTransfer:Zone:T S2 APARTMENT 35.53 0.16 11-FEB-06:45 3060.09 15-DEC-12:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 90.67 27-APR-05:45
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 35.52 0.00 07-JAN-06:15 3060.09 15-DEC-12:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1679.13 491.28 11-FEB-06:15 111379.80 15-SEP-17:15
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
CoolingCoils:EnergyTransfer 1679.13 491.28 11-FEB-06:15 111379.80 15-SEP-17:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.184 -21.095 0.000 0.000 3.521 2.413 12.213 16.167 0.000 0.806 0.000 0.000 -2.169 0.000 -0.529 -11.510
G NW APARTMENT 0.368 -16.939 0.000 0.000 3.525 2.413 12.213 11.470 0.000 0.823 0.000 0.000 -2.055 0.000 -0.537 -11.281
OFFICE 0.012 -38.943 0.000 0.000 0.517 21.914 7.534 18.350 0.000 0.742 0.000 0.000 -1.871 0.000 -0.167 -8.087
G NE APARTMENT 0.174 -18.443 0.000 0.000 3.529 2.413 12.213 13.321 0.000 0.823 0.000 0.000 -1.997 0.000 -0.536 -11.497
G N1 APARTMENT 0.099 -12.219 0.000 0.000 3.531 2.413 12.213 5.498 0.000 0.573 0.000 0.000 -1.155 0.000 -0.445 -10.508
G N2 APARTMENT 0.094 -12.276 0.000 0.000 3.531 2.413 12.213 5.496 0.000 0.573 0.000 0.000 -1.155 0.000 -0.445 -10.444
G S1 APARTMENT 0.026 -16.430 0.000 0.000 3.524 2.413 12.213 10.212 0.000 0.556 0.000 0.000 -1.277 0.000 -0.441 -10.796
G S2 APARTMENT 0.037 -16.084 0.000 0.000 3.525 2.413 12.213 10.218 0.000 0.556 0.000 0.000 -1.266 0.000 -0.440 -11.172
M SW APARTMENT 0.000 -79.633 0.000 0.000 3.517 2.413 12.213 15.580 0.000 1.130 48.165 0.000 -2.687 0.000 -0.697 0.000
M NW APARTMENT 0.001 -67.534 0.000 0.000 3.517 2.413 12.213 10.885 0.000 1.155 40.707 0.000 -2.632 0.000 -0.725 0.000
M SE APARTMENT 0.000 -83.989 0.000 0.000 3.517 2.413 12.213 17.397 0.000 1.130 50.664 0.000 -2.648 0.000 -0.697 0.000
M NE APARTMENT 0.000 -71.871 0.000 0.000 3.517 2.413 12.213 12.680 0.000 1.156 43.192 0.000 -2.575 0.000 -0.724 0.000
M N1 APARTMENT 0.000 -56.148 0.000 0.000 3.517 2.413 12.213 5.098 0.000 0.799 34.272 0.000 -1.565 0.000 -0.600 0.000
M N2 APARTMENT 0.000 -56.298 0.000 0.000 3.517 2.413 12.213 5.096 0.000 0.799 34.425 0.000 -1.565 0.000 -0.600 0.000
M S1 APARTMENT 0.000 -68.342 0.000 0.000 3.516 2.413 12.213 9.826 0.000 0.771 41.773 0.000 -1.598 0.000 -0.573 0.000
M S2 APARTMENT 0.000 -68.477 0.000 0.000 3.516 2.413 12.213 9.824 0.000 0.771 41.912 0.000 -1.599 0.000 -0.573 0.000
T SW APARTMENT 0.043 -40.730 0.000 0.000 3.517 2.413 12.213 15.098 0.000 1.510 9.430 0.000 -2.615 0.000 -0.879 -0.001
T NW APARTMENT 0.068 -34.989 0.000 0.000 3.518 2.413 12.213 10.474 0.000 1.548 8.220 0.000 -2.548 0.000 -0.916 -0.000
T SE APARTMENT 0.025 -42.722 0.000 0.000 3.518 2.413 12.213 16.851 0.000 1.511 9.636 0.000 -2.566 0.000 -0.878 -0.001
T NE APARTMENT 0.034 -36.954 0.000 0.000 3.518 2.413 12.213 12.208 0.000 1.549 8.417 0.000 -2.482 0.000 -0.915 -0.001
T N1 APARTMENT 0.003 -29.550 0.000 0.000 3.518 2.413 12.213 4.914 0.000 1.083 7.649 0.000 -1.492 0.000 -0.750 -0.000
T N2 APARTMENT 0.003 -29.632 0.000 0.000 3.518 2.413 12.213 4.910 0.000 1.083 7.732 0.000 -1.492 0.000 -0.749 -0.000
T S1 APARTMENT 0.002 -35.443 0.000 0.000 3.517 2.413 12.213 9.557 0.000 1.045 8.986 0.000 -1.578 0.000 -0.712 -0.000
T S2 APARTMENT 0.002 -35.523 0.000 0.000 3.517 2.413 12.213 9.555 0.000 1.045 9.068 0.000 -1.578 0.000 -0.712 -0.000
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.292 0.000 0.047 0.000 0.000 -0.270 0.000 -0.211 -16.928
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 6.264 1.131 0.000 2.018 0.000 0.000 -0.470 0.000 -3.299 -22.714
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 17.070 0.000 0.311 0.000 0.047 0.000 0.000 -0.282 0.000 -0.164 -16.983
Total Facility 1.175 -990.266 0.000 0.000 81.476 128.627 294.692 262.419 0.000 25.651 404.248 0.000 -47.185 0.000 -18.917 -141.923


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 22-SEP-16:30 0.00 -2538.04 0.00 0.00 84.76 144.04 588.62 2244.83 0.00 71.25 0.00 0.00 0.00 0.00 0.00 -595.45
G NW APARTMENT 04-SEP-17:15 0.00 -2259.04 0.00 0.00 141.82 194.45 588.62 1688.61 0.00 127.21 0.00 0.00 0.00 0.00 0.00 -481.67
OFFICE 16-OCT-10:30 0.00 -3755.72 0.00 0.00 67.31 1622.34 544.92 2982.34 0.00 43.78 0.00 0.00 0.00 0.00 0.00 -1504.97
G NE APARTMENT 25-JUN-06:00 0.00 -2074.33 0.00 0.00 162.99 100.83 317.86 5445.35 0.00 0.95 0.00 0.00 0.00 0.00 0.00 -3953.65
G N1 APARTMENT 09-JUL-17:15 0.00 -1285.00 0.00 0.00 141.81 194.45 588.62 475.84 0.00 44.91 0.00 0.00 0.00 0.00 0.00 -160.65
G N2 APARTMENT 09-JUL-17:15 0.00 -1278.97 0.00 0.00 141.81 194.45 588.62 475.99 0.00 44.91 0.00 0.00 0.00 0.00 0.00 -166.82
G S1 APARTMENT 21-NOV-13:30 0.00 -1601.29 0.00 0.00 40.75 28.81 388.49 2101.04 0.00 60.80 0.00 0.00 0.00 0.00 0.00 -1018.60
G S2 APARTMENT 21-NOV-13:30 0.00 -1589.88 0.00 0.00 40.75 28.81 388.49 2101.36 0.00 60.80 0.00 0.00 0.00 0.00 0.00 -1030.33
M SW APARTMENT 06-NOV-14:30 0.00 -6403.99 0.00 0.00 40.75 28.81 382.60 2852.31 0.00 142.69 2956.83 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 04-SEP-17:15 0.00 -5474.38 0.00 0.00 141.82 194.45 588.62 1665.79 0.00 182.24 2701.45 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 15-DEC-11:30 0.00 -6180.96 0.00 0.00 40.66 28.81 412.04 2806.99 0.00 104.08 2788.39 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 27-MAY-06:00 0.00 -5343.34 0.00 0.00 162.99 100.83 317.86 5611.33 0.00 0.00 0.00 0.00 0.00 0.00 -55.40 -794.26
M N1 APARTMENT 09-JUL-17:15 0.00 -3317.15 0.00 0.00 141.81 194.45 588.62 460.92 0.00 64.28 1867.06 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 09-JUL-17:15 0.00 -3309.85 0.00 0.00 141.81 194.45 588.62 460.99 0.00 64.28 1859.69 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 23-DEC-13:30 0.00 -4773.26 0.00 0.00 40.75 28.81 388.49 1973.81 0.00 58.72 2282.68 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 23-DEC-13:45 0.00 -4757.96 0.00 0.00 40.71 28.81 388.49 1895.01 0.00 61.54 2343.40 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 11-OCT-14:30 0.00 -3898.59 0.00 0.00 40.75 50.41 400.26 2541.48 0.00 146.18 719.50 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 03-SEP-16:06 0.00 -3430.46 0.00 0.00 84.77 144.04 588.62 1698.76 0.00 239.32 674.96 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 15-DEC-11:45 0.00 -3715.96 0.00 0.00 40.75 28.81 412.04 2606.95 0.00 138.37 489.05 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 12-JUL-10:15 0.00 -2918.89 0.00 0.00 40.75 28.81 412.04 1640.27 0.00 138.46 658.57 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 03-SEP-16:06 0.00 -2194.91 0.00 0.00 84.76 144.04 588.62 482.30 0.00 144.35 750.84 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 03-SEP-16:06 0.00 -2181.46 0.00 0.00 84.76 144.04 588.62 482.62 0.00 144.35 737.06 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 15-DEC-12:30 0.00 -3051.04 0.00 0.00 40.60 28.81 406.15 2038.05 0.00 81.99 455.45 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 15-DEC-12:30 0.00 -3060.05 0.00 0.00 40.57 28.81 406.15 2037.49 0.00 81.82 465.21 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-SEP-16:06 0.00 -70768.94 0.00 0.00 1949.54 5316.35 14071.03 22762.10 0.00 5466.77 21203.14 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 27-MAR-08:45 157.78 0.00 0.00 0.00 40.81 28.81 394.38 470.38 0.00 0.00 0.00 0.00 0.00 0.00 -35.85 -1056.31
G NW APARTMENT 26-MAR-09:30 204.58 0.00 0.00 0.00 40.75 28.81 406.15 428.27 0.00 7.07 0.00 0.00 0.00 0.00 0.00 -1115.64
OFFICE 07-JAN-07:04 210.19 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 0.00 0.00 -329.12 0.00 -23.35 -365.99
G NE APARTMENT 17-FEB-01:15 144.33 0.00 0.00 0.00 162.99 14.40 241.34 0.00 0.00 0.00 0.00 0.00 -8.53 0.00 -1.74 -552.79
G N1 APARTMENT 28-JAN-10:15 152.46 0.00 0.00 0.00 40.75 28.81 406.15 280.20 0.00 25.17 0.00 0.00 0.00 0.00 0.00 -933.53
G N2 APARTMENT 28-MAR-09:45 141.93 0.00 0.00 0.00 40.75 28.81 406.15 356.71 0.00 22.01 0.00 0.00 0.00 0.00 0.00 -996.36
G S1 APARTMENT 17-FEB-03:30 100.47 0.00 0.00 0.00 162.99 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -12.70 0.00 -2.61 -486.23
G S2 APARTMENT 17-FEB-02:15 108.04 0.00 0.00 0.00 162.99 14.40 229.56 0.00 0.00 0.00 0.00 0.00 -6.04 0.00 -0.75 -508.21
M SW APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 08-FEB-08:02 122.15 0.00 0.00 0.00 63.59 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -197.42 0.00 -287.74 -132.28
M SE APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 27-APR-05:45 230.08 0.00 0.00 0.00 163.42 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -278.77 0.00 -512.89 -20.53
T NW APARTMENT 27-APR-06:00 245.12 0.00 0.00 0.00 163.76 100.83 317.86 0.00 0.00 0.00 52.10 0.00 -277.36 0.00 -602.31 0.00
T SE APARTMENT 27-APR-05:45 174.97 0.00 0.00 0.00 164.05 100.83 317.86 0.00 0.00 0.00 22.95 0.00 -280.78 0.00 -499.87 0.00
T NE APARTMENT 27-APR-06:00 167.80 0.00 0.00 0.00 165.17 100.83 317.86 0.00 0.00 0.00 105.54 0.00 -277.46 0.00 -579.73 0.00
T N1 APARTMENT 27-APR-06:00 85.29 0.00 0.00 0.00 163.75 100.83 317.86 0.00 0.00 0.00 39.58 0.00 -170.68 0.00 -536.63 0.00
T N2 APARTMENT 27-APR-06:00 83.14 0.00 0.00 0.00 163.80 100.83 317.86 0.00 0.00 0.00 40.86 0.00 -170.59 0.00 -535.89 0.00
T S1 APARTMENT 27-APR-05:45 90.05 0.00 0.00 0.00 163.34 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -174.45 0.00 -455.13 -42.49
T S2 APARTMENT 27-APR-05:45 90.67 0.00 0.00 0.00 163.34 100.83 317.86 0.00 0.00 0.00 0.00 0.00 -174.41 0.00 -455.10 -43.17
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-APR-05:45 -1337.82 0.00 0.00 0.00 3786.98 4322.48 7762.60 0.00 0.00 0.00 0.00 0.00 -5301.72 0.00 -8739.89 -492.63



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Sec1.1A-General Information

Data
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 112.00
Number of hours not met 112.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 165.00 8572.78 0.00 0.00 0.00 0.00
Exterior Lighting 39.48 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 0.00 0.00 0.00 0.00
Space Cooling 404.82 24976.18 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 220.22 6983.10 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 295.89 22083.37 0.00 0.00 0.00 0.00
Receptacle Equipment 511.42 26456.41 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1636.84   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 511.42 1636.84
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 511.42 1636.84


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 52.64
Space Heating 0.00
Space Cooling 129.15
Fans-Interior 70.25
Service Water Heating 94.40
Receptacle Equipment 163.15
Miscellaneous 12.60
Subtotal 522.18


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.08
Space Heating 0.00
Space Cooling 24.73
Fans-Interior 13.45
Service Water Heating 18.08
Receptacle Equipment 31.24
Miscellaneous 2.41



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.209754
G NW APARTMENT DIRECT AIR 0.207559
OFFICE DIRECT AIR 0.447454
G NE APARTMENT DIRECT AIR 0.153694
G N1 APARTMENT DIRECT AIR 0.110721
G N2 APARTMENT DIRECT AIR 0.109563
G S1 APARTMENT DIRECT AIR 0.109500
G S2 APARTMENT DIRECT AIR 0.110000
M SW APARTMENT DIRECT AIR 0.509048
M NW APARTMENT DIRECT AIR 0.502079
M SE APARTMENT DIRECT AIR 0.402289
M NE APARTMENT DIRECT AIR 0.384017
M N1 APARTMENT DIRECT AIR 0.280722
M N2 APARTMENT DIRECT AIR 0.278780
M S1 APARTMENT DIRECT AIR 0.281075
M S2 APARTMENT DIRECT AIR 0.279277
T SW APARTMENT DIRECT AIR 0.313601
T NW APARTMENT DIRECT AIR 0.306620
T SE APARTMENT DIRECT AIR 0.252018
T NE APARTMENT DIRECT AIR 0.235664
T N1 APARTMENT DIRECT AIR 0.178913
T N2 APARTMENT DIRECT AIR 0.176877
T S1 APARTMENT DIRECT AIR 0.197291
T S2 APARTMENT DIRECT AIR 0.197793


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.209754
SPLIT GNW MAIN BRANCH 0.207559
SPLIT OFFICE MAIN BRANCH 0.447454
SPLIT GNE MAIN BRANCH 0.153694
SPLIT GN1 MAIN BRANCH 0.110721
SPLIT GN2 MAIN BRANCH 0.109563
SPLIT GS1 MAIN BRANCH 0.109500
SPLIT GS2 MAIN BRANCH 0.110000
SPLIT MSW MAIN BRANCH 0.509048
SPLIT MNW MAIN BRANCH 0.502079
SPLIT MSE MAIN BRANCH 0.402289
SPLIT MNE MAIN BRANCH 0.384017
SPLIT MN1 MAIN BRANCH 0.280722
SPLIT MN2 MAIN BRANCH 0.278780
SPLIT MS1 MAIN BRANCH 0.281075
SPLIT MS2 MAIN BRANCH 0.279277
SPLIT TSW MAIN BRANCH 0.313601
SPLIT TNW MAIN BRANCH 0.306620
SPLIT TSE MAIN BRANCH 0.252018
SPLIT TNE MAIN BRANCH 0.235664
SPLIT TN1 MAIN BRANCH 0.178913
SPLIT TN2 MAIN BRANCH 0.176877
SPLIT TS1 MAIN BRANCH 0.197291
SPLIT TS2 MAIN BRANCH 0.197793


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.209754
SPLIT GNW 0.207559
SPLIT OFFICE 0.447454
SPLIT GNE 0.153694
SPLIT GN1 0.110721
SPLIT GN2 0.109563
SPLIT GS1 0.109500
SPLIT GS2 0.110000
SPLIT MSW 0.509048
SPLIT MNW 0.502079
SPLIT MSE 0.402289
SPLIT MNE 0.384017
SPLIT MN1 0.280722
SPLIT MN2 0.278780
SPLIT MS1 0.281075
SPLIT MS2 0.279277
SPLIT TSW 0.313601
SPLIT TNW 0.306620
SPLIT TSE 0.252018
SPLIT TNE 0.235664
SPLIT TN1 0.178913
SPLIT TN2 0.176877
SPLIT TS1 0.197291
SPLIT TS2 0.197793


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.209754 0.026898
SPLIT GNW OA CONTROLLER 0.207559 0.025953
SPLIT OFFICE OA CONTROLLER 0.447454 0.038104
SPLIT GNE OA CONTROLLER 0.153694 0.025953
SPLIT GN1 OA CONTROLLER 0.110721 0.025953
SPLIT GN2 OA CONTROLLER 0.109563 0.025953
SPLIT GS1 OA CONTROLLER 0.109500 0.025953
SPLIT GS2 OA CONTROLLER 0.110000 0.025953
SPLIT MSW OA CONTROLLER 0.509048 0.051906
SPLIT MNW OA CONTROLLER 0.502079 0.051906
SPLIT MSE OA CONTROLLER 0.402289 0.051906
SPLIT MNE OA CONTROLLER 0.384017 0.051906
SPLIT MN1 OA CONTROLLER 0.280722 0.051906
SPLIT MN2 OA CONTROLLER 0.278780 0.051906
SPLIT MS1 OA CONTROLLER 0.281075 0.051906
SPLIT MS2 OA CONTROLLER 0.279277 0.051906
SPLIT TSW OA CONTROLLER 0.313601 0.025953
SPLIT TNW OA CONTROLLER 0.306620 0.025953
SPLIT TSE OA CONTROLLER 0.252018 0.025953
SPLIT TNE OA CONTROLLER 0.235664 0.025953
SPLIT TN1 OA CONTROLLER 0.178913 0.025953
SPLIT TN2 OA CONTROLLER 0.176877 0.025953
SPLIT TS1 OA CONTROLLER 0.197291 0.025953
SPLIT TS2 OA CONTROLLER 0.197793 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.209754 4117.17 0.741058
SPLIT GNW COOLING COIL 0.207559 4056.69 0.742388
SPLIT OFFICE COOLING COIL 0.447454 7717.34 0.783868
SPLIT GNE COOLING COIL 0.153694 3177.03 0.725421
SPLIT GN1 COOLING COIL 0.110721 2427.09 0.708637
SPLIT GN2 COOLING COIL 0.109563 2408.06 0.707903
SPLIT GS1 COOLING COIL 0.109500 2417.48 0.706666
SPLIT GS2 COOLING COIL 0.110000 2410.01 0.708784
SPLIT MSW COOLING COIL 0.509048 9769.43 0.748118
SPLIT MNW COOLING COIL 0.502079 9646.28 0.747770
SPLIT MSE COOLING COIL 0.402289 8071.79 0.734319
SPLIT MNE COOLING COIL 0.384017 7717.59 0.733831
SPLIT MN1 COOLING COIL 0.280722 5889.20 0.721103
SPLIT MN2 COOLING COIL 0.278780 5857.57 0.720651
SPLIT MS1 COOLING COIL 0.281075 5919.19 0.719995
SPLIT MS2 COOLING COIL 0.279277 5889.71 0.719585
SPLIT TSW COOLING COIL 0.313601 5923.40 0.753209
SPLIT TNW COOLING COIL 0.306620 5793.45 0.753103
SPLIT TSE COOLING COIL 0.252018 5000.01 0.737756
SPLIT TNE COOLING COIL 0.235664 4665.57 0.738412
SPLIT TN1 COOLING COIL 0.178913 3621.04 0.731706
SPLIT TN2 COOLING COIL 0.176877 3588.01 0.731018
SPLIT TS1 COOLING COIL 0.197291 3994.70 0.731576
SPLIT TS2 COOLING COIL 0.197793 4002.57 0.731748


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.209754 0.209754 0.209754 0.209754 1099.98 4117.17 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.207559 0.207559 0.207559 0.207559 1061.31 4056.69 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.447454 0.447454 0.447454 0.447454 1558.20 7717.34 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.153694 0.153694 0.153694 0.153694 1061.31 3177.03 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.110721 0.110721 0.110721 0.110721 1061.31 2427.09 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.109563 0.109563 0.109563 0.109563 1061.31 2408.06 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.109500 0.109500 0.109500 0.109500 1061.31 2417.48 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.110000 0.110000 0.110000 0.110000 1061.31 2410.01 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.509048 0.509048 0.509048 0.509048 2122.63 9769.43 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.502079 0.502079 0.502079 0.502079 2122.63 9646.28 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.402289 0.402289 0.402289 0.402289 2122.63 8071.79 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.384017 0.384017 0.384017 0.384017 2122.63 7717.59 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.280722 0.280722 0.280722 0.280722 2122.63 5889.20 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.278780 0.278780 0.278780 0.278780 2122.63 5857.57 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.281075 0.281075 0.281075 0.281075 2122.63 5919.19 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.279277 0.279277 0.279277 0.279277 2122.63 5889.71 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.313601 0.313601 0.313601 0.313601 1061.31 5923.40 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.306620 0.306620 0.306620 0.306620 1061.31 5793.45 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.252018 0.252018 0.252018 0.252018 1061.31 5000.01 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.235664 0.235664 0.235664 0.235664 1061.31 4665.57 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.178913 0.178913 0.178913 0.178913 1061.31 3621.04 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.176877 0.176877 0.176877 0.176877 1061.31 3588.01 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.197291 0.197291 0.197291 0.197291 1061.31 3994.70 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.197793 0.197793 0.197793 0.197793 1061.31 4002.57 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.209754
SPLIT GNW SUPPLY FAN 0.207559
SPLIT OFFICE SUPPLY FAN 0.447454
SPLIT GNE SUPPLY FAN 0.153694
SPLIT GN1 SUPPLY FAN 0.110721
SPLIT GN2 SUPPLY FAN 0.109563
SPLIT GS1 SUPPLY FAN 0.109500
SPLIT GS2 SUPPLY FAN 0.110000
SPLIT MSW SUPPLY FAN 0.509048
SPLIT MNW SUPPLY FAN 0.502079
SPLIT MSE SUPPLY FAN 0.402289
SPLIT MNE SUPPLY FAN 0.384017
SPLIT MN1 SUPPLY FAN 0.280722
SPLIT MN2 SUPPLY FAN 0.278780
SPLIT MS1 SUPPLY FAN 0.281075
SPLIT MS2 SUPPLY FAN 0.279277
SPLIT TSW SUPPLY FAN 0.313601
SPLIT TNW SUPPLY FAN 0.306620
SPLIT TSE SUPPLY FAN 0.252018
SPLIT TNE SUPPLY FAN 0.235664
SPLIT TN1 SUPPLY FAN 0.178913
SPLIT TN2 SUPPLY FAN 0.176877
SPLIT TS1 SUPPLY FAN 0.197291
SPLIT TS2 SUPPLY FAN 0.197793


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1099.98
SPLIT GNW HEATING COIL 1061.31
SPLIT OFFICE HEATING COIL 1558.20
SPLIT GNE HEATING COIL 1061.31
SPLIT GN1 HEATING COIL 1061.31
SPLIT GN2 HEATING COIL 1061.31
SPLIT GS1 HEATING COIL 1061.31
SPLIT GS2 HEATING COIL 1061.31
SPLIT MSW HEATING COIL 2122.63
SPLIT MNW HEATING COIL 2122.63
SPLIT MSE HEATING COIL 2122.63
SPLIT MNE HEATING COIL 2122.63
SPLIT MN1 HEATING COIL 2122.63
SPLIT MN2 HEATING COIL 2122.63
SPLIT MS1 HEATING COIL 2122.63
SPLIT MS2 HEATING COIL 2122.63
SPLIT TSW HEATING COIL 1061.31
SPLIT TNW HEATING COIL 1061.31
SPLIT TSE HEATING COIL 1061.31
SPLIT TNE HEATING COIL 1061.31
SPLIT TN1 HEATING COIL 1061.31
SPLIT TN2 HEATING COIL 1061.31
SPLIT TS1 HEATING COIL 1061.31
SPLIT TS2 HEATING COIL 1061.31



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:20:28

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.35 22.80
March 24.34 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.38 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 22.49
February 24.31 22.80
March 24.31 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.38 24.76
December 24.37 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.29 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.90 22.49
February 23.90 22.80
March 23.90 23.17
April 23.90 23.76
May 23.90 25.23
June 23.90 25.87
July 23.90 26.90
August 23.90 27.06
September 23.90 26.87
October 23.90 26.22
November 23.90 24.76
December 23.90 23.69
     
Annual Sum or Average 23.90 24.91
Minimum of Months 23.90 22.49
Maximum of Months 23.90 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.27 22.49
February 24.27 22.80
March 24.28 23.17
April 24.38 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.37 24.76
December 24.35 23.69
     
Annual Sum or Average 24.36 24.91
Minimum of Months 24.27 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.24 22.49
February 24.25 22.80
March 24.27 23.17
April 24.36 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.37 24.76
December 24.34 23.69
     
Annual Sum or Average 24.35 24.91
Minimum of Months 24.24 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.24 22.49
February 24.25 22.80
March 24.27 23.17
April 24.36 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.37 24.76
December 24.34 23.69
     
Annual Sum or Average 24.35 24.91
Minimum of Months 24.24 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.33 22.80
March 24.31 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.38 23.69
     
Annual Sum or Average 24.38 24.91
Minimum of Months 24.31 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.33 22.49
February 24.32 22.80
March 24.30 23.17
April 24.37 23.76
May 24.39 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.38 24.76
December 24.38 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.30 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.41 26.22
November 24.43 24.76
December 24.42 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.40 22.80
March 24.40 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.41 26.22
November 24.43 24.76
December 24.42 23.69
     
Annual Sum or Average 24.41 24.91
Minimum of Months 24.40 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.39 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.38 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.38 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 22.49
February 24.37 22.80
March 24.38 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.38 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.38 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.39 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 22.49
February 24.39 22.80
March 24.39 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.61 22.49
February 26.68 22.80
March 26.73 23.17
April 26.83 23.76
May 27.09 25.23
June 27.18 25.87
July 27.33 26.90
August 27.31 27.06
September 27.33 26.87
October 27.18 26.22
November 26.98 24.76
December 26.80 23.69
     
Annual Sum or Average 27.00 24.91
Minimum of Months 26.61 22.49
Maximum of Months 27.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.02 22.49
February 25.11 22.80
March 25.20 23.17
April 25.33 23.76
May 25.72 25.23
June 26.62 25.87
July 26.97 26.90
August 27.01 27.06
September 26.99 26.87
October 26.11 26.22
November 25.66 24.76
December 25.36 23.69
     
Annual Sum or Average 25.93 24.91
Minimum of Months 25.02 22.49
Maximum of Months 27.01 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:20:28

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.89 22.49
February 26.92 22.80
March 26.93 23.17
April 26.95 23.76
May 27.07 25.23
June 27.13 25.87
July 27.20 26.90
August 27.19 27.06
September 27.23 26.87
October 27.18 26.22
November 27.08 24.76
December 26.99 23.69
     
Annual Sum or Average 27.06 24.91
Minimum of Months 26.89 22.49
Maximum of Months 27.23 27.06



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.130850E+12 82992.168 03-JAN-18:15 8572.775 26456.413 6983.097 0.000 15314.754 2508.330 0.000 0.000 0.000 0.000 0.000 23156.799 0.000 0.000 0.000
February 0.120839E+12 79091.474 17-FEB-18:30 8572.775 26456.413 6983.097 0.000 17392.887 2508.330 0.000 0.000 0.000 0.000 0.000 17177.971 0.000 0.000 0.000
March 0.132566E+12 82583.420 17-MAR-17:15 8572.775 26456.413 6983.097 0.000 19426.334 0.000 0.000 0.000 0.000 0.000 0.000 21144.801 0.000 0.000 0.000
April 0.127966E+12 78496.495 10-APR-17:00 8572.775 26456.413 6983.097 0.000 16616.369 0.000 0.000 0.000 0.000 0.000 0.000 19867.841 0.000 0.000 0.000
May 0.137465E+12 78776.686 26-MAY-17:45 8572.775 26456.413 6983.097 0.000 17658.335 0.000 0.000 0.000 0.000 0.000 0.000 19106.067 0.000 0.000 0.000
June 0.137183E+12 82158.201 26-JUN-17:30 8572.775 26456.413 6983.097 0.000 20805.585 0.000 0.000 0.000 0.000 0.000 0.000 19340.331 0.000 0.000 0.000
July 0.145764E+12 84816.614 05-JUL-17:15 8572.775 26456.413 6983.097 0.000 21952.455 0.000 0.000 0.000 0.000 0.000 0.000 20851.874 0.000 0.000 0.000
August 0.146061E+12 85493.256 28-AUG-17:15 8572.775 26456.413 6983.097 0.000 21530.479 0.000 0.000 0.000 0.000 0.000 0.000 21950.492 0.000 0.000 0.000
September 0.143167E+12 89071.835 05-SEP-17:45 8572.775 26456.413 6983.097 0.000 24976.184 0.000 0.000 0.000 0.000 0.000 0.000 22083.366 0.000 0.000 0.000
October 0.143774E+12 84049.270 13-OCT-16:15 7009.952 26456.413 6983.097 0.000 22610.535 0.000 0.000 0.000 0.000 0.000 0.000 20989.273 0.000 0.000 0.000
November 0.135342E+12 83802.867 06-NOV-18:15 8572.775 26456.413 6983.097 0.000 17151.485 2508.330 0.000 0.000 0.000 0.000 0.000 22130.767 0.000 0.000 0.000
December 0.135862E+12 82875.477 12-DEC-18:15 8572.775 26456.413 6983.097 0.000 16200.638 2508.330 0.000 0.000 0.000 0.000 0.000 22154.223 0.000 0.000 0.000
                                     
Annual Sum or Average 0.163684E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.120839E+12 78496.495   7009.952 26456.413 6983.097 0.000 15314.754 0.000 0.000 0.000 0.000 0.000 0.000 17177.971 0.000 0.000 0.000
Maximum of Months 0.146061E+12 89071.835   8572.775 26456.413 6983.097 0.000 24976.184 2508.330 0.000 0.000 0.000 0.000 0.000 23156.799 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:20:28

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.000 0.000 01-JAN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.000 0.000 01-FEB-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.000 0.000 01-MAR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.000 0.000 01-APR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 01-OCT-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.000 0.000 01-NOV-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.000 0.000 01-DEC-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                     
Annual Sum or Average 0.000       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000