Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
Tabular Output Report in Format: HTML
Building: MF+CZ1A+USA_FL_Miami.Intl.AP.722020+hp+unheatedbsmt+IECC_2009
Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2019-02-14 08:32:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 669570.21 | 17.17 | 30.98 |
Net Site Energy | 669570.21 | 17.17 | 30.98 |
Total Source Energy | 2120528.86 | 54.37 | 98.13 |
Net Source Energy | 2120528.86 | 54.37 | 98.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 4109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 171849.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27611.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 104346.13 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 669570.21 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 4109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 171849.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27611.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 104346.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 30.98 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 669570.210 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 669570.210 | 100.00 |
Total On-Site and Utility Electric Sources | 669570.210 | 100.00 |
Total Electricity End Uses | 669570.210 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 24.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4304.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32 |
RunPeriod | ANNUAL |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [ft] | 36.09 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58419.71 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 141767.99 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 27-JUL-18:45 | - | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 116.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 239.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 47.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 116.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 13015.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 544248.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 87446.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 330464.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2120528.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 47.66 | 0.00 | 47.66 | Wetbulb [F] | 748.07 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 91.76 | 12.06 | 77.54 | Wetbulb [F] | 885.87 | 140.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.066 | 0.070 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 1.027 | 0.258 | 0.881 | ||||||||||||
North Total or Average | 531.68 | 1.027 | 0.258 | 0.881 | ||||||||||||
Non-North Total or Average | 1595.05 | 1.027 | 0.258 | 0.881 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 18203.45 | 13030.50 | 5172.95 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8710.69 | 5889.15 | 2821.54 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12969.18 | 8922.17 | 4047.01 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 16295.14 | 11496.31 | 4798.84 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9223.42 | 6235.80 | 2987.62 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13109.07 | 9033.38 | 4075.68 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15689.53 | 11227.88 | 4461.64 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9228.72 | 6239.38 | 2989.34 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12541.95 | 8750.57 | 3791.38 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15847.75 | 11353.41 | 4494.34 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9708.99 | 6564.09 | 3144.90 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12647.31 | 8844.64 | 3802.67 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 18519.14 | 13285.07 | 5234.07 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12272.17 | 8376.17 | 3896.00 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14360.92 | 9927.32 | 4433.59 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 18636.29 | 13378.83 | 5257.46 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12523.51 | 8569.67 | 3953.85 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14281.01 | 9902.34 | 4378.67 | 0.69 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.5 | 3.41 | 11.65 | 12.22 | 11.67 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.50 | 11.93 | 12.52 | 12.10 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | 3.47 | 11.84 | 12.43 | 11.97 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.3 | 3.44 | 11.72 | 12.30 | 11.78 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.50 | 11.93 | 12.52 | 12.10 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.1 | 3.47 | 11.84 | 12.42 | 11.96 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.42 | 11.65 | 12.22 | 11.68 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.50 | 11.93 | 12.52 | 12.10 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.0 | 3.45 | 11.78 | 12.36 | 11.87 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.3 | 3.41 | 11.65 | 12.21 | 11.67 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.8 | 3.50 | 11.93 | 12.52 | 12.10 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.0 | 3.45 | 11.76 | 12.34 | 11.85 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.5 | 3.41 | 11.64 | 12.21 | 11.66 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.0 | 3.48 | 11.88 | 12.47 | 12.03 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.2 | 3.46 | 11.82 | 12.40 | 11.93 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.5 | 3.41 | 11.64 | 12.20 | 11.65 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.0 | 3.48 | 11.87 | 12.46 | 12.01 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 3.46 | 11.81 | 12.39 | 11.91 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 18884.3 | 10432.6 | 7.99 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 8992.5 | 4948.2 | 8.06 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 13408.3 | 7386.8 | 8.03 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 16883.3 | 9317.5 | 8.08 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9521.8 | 5239.4 | 8.07 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 13554.9 | 7468.4 | 8.03 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 16276.0 | 8991.4 | 8.05 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9527.3 | 5242.5 | 8.07 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 12982.2 | 7159.0 | 7.98 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 16441.7 | 9083.6 | 8.06 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 10023.1 | 5515.3 | 8.09 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 13093.9 | 7221.8 | 7.99 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19215.4 | 10617.1 | 8.00 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12679.3 | 6981.4 | 7.97 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 14853.3 | 8185.6 | 8.06 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 19338.2 | 10685.5 | 8.00 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12941.7 | 7127.1 | 8.00 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 14774.5 | 8143.9 | 8.05 | 4 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 18203.45 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 5086.32 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 8710.69 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 5210.90 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 12969.18 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 6997.88 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 16295.14 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 7020.32 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9223.42 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 5218.13 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 13109.07 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 6999.63 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 15689.53 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 6202.00 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9228.72 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 4357.26 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 12541.95 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 6179.95 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 15847.75 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 6218.43 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9708.99 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 4369.40 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 12647.31 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 6186.80 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 18519.14 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 7636.79 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12272.17 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 5790.46 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 14360.92 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 7607.63 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 18636.29 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 7657.28 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12523.51 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 5808.31 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 14281.01 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 7621.25 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 528.99 | 199.53 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 217.81 | 82.16 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 340.00 | 128.25 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 456.38 | 172.14 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 230.63 | 86.99 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 345.20 | 130.21 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 455.62 | 171.86 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 230.77 | 87.04 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 341.28 | 128.73 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 461.47 | 174.06 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 242.78 | 91.57 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 346.25 | 130.60 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 541.08 | 204.09 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 314.94 | 118.79 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 381.35 | 143.84 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 545.50 | 205.76 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 323.63 | 122.07 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 382.32 | 144.21 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12410.04 | 12410.04 | 10.34 | 528.993 | 528.993 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 74.98 | 74.98 | 0.00938 | 89.77 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5110.16 | 5110.16 | 4.26 | 217.813 | 217.813 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.01076 | 88.41 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7976.81 | 7976.81 | 6.64 | 340.002 | 340.002 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 74.98 | 74.98 | 0.00993 | 88.53 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10706.68 | 10706.68 | 8.92 | 456.379 | 456.379 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00958 | 89.47 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5410.95 | 5410.95 | 4.51 | 230.634 | 230.634 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.01069 | 87.96 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8098.70 | 8098.70 | 6.75 | 345.197 | 345.197 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 74.98 | 74.98 | 0.00991 | 88.53 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10689.44 | 10689.44 | 8.90 | 455.624 | 455.624 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00923 | 89.47 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5414.25 | 5414.25 | 4.51 | 230.766 | 230.766 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01016 | 87.06 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8007.05 | 8007.05 | 6.67 | 341.281 | 341.281 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 74.98 | 74.98 | 0.00951 | 88.99 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10826.65 | 10826.65 | 9.02 | 461.473 | 461.473 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00922 | 89.47 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5696.00 | 5696.00 | 4.74 | 242.775 | 242.775 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.01008 | 87.51 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8123.55 | 8123.55 | 6.77 | 346.245 | 346.245 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 74.98 | 74.98 | 0.00950 | 88.53 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8969.32 | 8969.32 | 7.47 | 382.320 | 382.320 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00981 | 89.47 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8944.79 | 8944.79 | 7.45 | 381.355 | 381.355 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00976 | 91.40 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12693.83 | 12693.83 | 10.57 | 541.084 | 541.084 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00937 | 89.47 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7592.80 | 7592.80 | 6.32 | 323.634 | 323.634 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.01006 | 87.96 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7388.95 | 7388.95 | 6.15 | 314.945 | 314.945 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.01010 | 87.96 | 0.01715 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12797.40 | 12797.40 | 10.66 | 545.499 | 545.499 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00936 | 89.47 | 0.01715 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3960.00 | 3960.00 | 3.30 | 72.170 | 72.170 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00770 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4086.42 | 4086.42 | 3.40 | 74.474 | 74.474 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00773 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5899.83 | 5899.83 | 4.91 | 107.522 | 107.522 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5922.59 | 5922.59 | 4.93 | 107.937 | 107.937 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4093.75 | 4093.75 | 3.41 | 74.607 | 74.607 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00773 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5901.60 | 5901.60 | 4.92 | 107.554 | 107.554 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5092.15 | 5092.15 | 4.24 | 92.804 | 92.804 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3220.14 | 3220.14 | 2.68 | 58.687 | 58.687 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5069.78 | 5069.78 | 4.22 | 92.396 | 92.396 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5108.83 | 5108.83 | 4.26 | 93.107 | 93.107 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3232.45 | 3232.45 | 2.69 | 58.911 | 58.911 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5076.72 | 5076.72 | 4.23 | 92.522 | 92.522 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00786 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6532.41 | 6532.41 | 5.44 | 119.051 | 119.051 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00777 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6518.59 | 6518.59 | 5.43 | 118.799 | 118.799 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00777 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 6548.18 | 6548.18 | 5.45 | 119.338 | 119.338 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00777 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4692.66 | 4692.66 | 3.91 | 85.522 | 85.522 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00775 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 4674.55 | 4674.55 | 3.89 | 85.192 | 85.192 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00775 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6568.97 | 6568.97 | 5.47 | 119.717 | 119.717 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00777 | 47.66 | 0.00699 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 | 528.99 | 72.17 | 72.17 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 | 217.81 | 74.47 | 74.47 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 | 340.00 | 107.52 | 107.52 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 | 456.38 | 107.94 | 107.94 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 | 230.63 | 74.61 | 74.61 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 | 345.20 | 107.55 | 107.55 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 | 455.62 | 92.80 | 92.80 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 | 230.77 | 58.69 | 58.69 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 | 341.28 | 92.40 | 92.40 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 | 461.47 | 93.11 | 93.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 | 242.78 | 58.91 | 58.91 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 | 346.25 | 92.52 | 92.52 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 541.08 | 541.08 | 119.34 | 119.34 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 314.94 | 314.94 | 85.19 | 85.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 381.35 | 381.35 | 118.80 | 118.80 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 545.50 | 545.50 | 119.72 | 119.72 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 323.63 | 323.63 | 85.52 | 85.52 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 382.32 | 382.32 | 119.05 | 119.05 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6599.25 | 1870.50 | 872.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7249.50 | 4542.00 | 3674.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7318.50 | 4023.50 | 3102.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7199.00 | 4831.75 | 3678.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7095.75 | 5263.00 | 4085.25 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7169.75 | 4415.50 | 3283.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7431.75 | 3093.75 | 2262.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7283.50 | 2477.00 | 1784.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7363.00 | 2670.50 | 1883.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7269.75 | 3426.50 | 2410.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7138.75 | 2918.25 | 1967.50 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7229.00 | 2975.50 | 1994.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7303.00 | 3389.00 | 2384.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7426.50 | 3154.00 | 2293.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7458.00 | 3686.25 | 2773.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7252.50 | 3647.50 | 2662.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7396.75 | 3307.75 | 2498.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7347.25 | 3923.00 | 2879.75 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7592.50 | 5580.25 | 4304.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23.25 | 0.00 | 23.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 1.25 | 0.00 | 1.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 1.25 | 0.00 | 1.25 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 24.50 | 0.00 | 24.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.224 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.197 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.196 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.098 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.071 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.098 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.098 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.071 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.098 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.223 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.197 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.197 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.223 | 0.000 | 0.264 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1842 |
Defaulted Fields | 518 |
Fields with Defaults | 4740 |
Autosized Fields | 324 |
Autosizable Fields | 450 |
Autocalculated Fields | 98 |
Autocalculatable Fields | 286 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Electricity:Plant | 30560.45 | 0.00 | 01-JAN-00:15 | 35872.35 | 21-JAN-08:15 |
WaterSystems:Electricity | 30560.45 | 0.00 | 01-JAN-00:15 | 35872.35 | 21-JAN-08:15 |
Water Heater:WaterSystems:Electricity | 30560.45 | 0.00 | 01-JAN-00:15 | 35872.35 | 21-JAN-08:15 |
Fans:Electricity | 8086.86 | 0.00 | 24-JAN-01:45 | 2430.46 | 29-JUL-16:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
ElectricityPurchased:Plant | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
Cogeneration:ElectricityPurchased | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
ElectricityNet:Plant | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
Cogeneration:ElectricityNet | 196100.87 | 6934.58 | 05-JAN-03:30 | 70233.76 | 27-JUL-18:45 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 59621.09 | 0.00 | 24-JAN-01:45 | 19135.26 | 29-JUL-16:15 |
General:Fans:Electricity | 8086.86 | 0.00 | 24-JAN-01:45 | 2430.46 | 29-JUL-16:15 |
Cooling:Electricity | 50330.63 | 0.00 | 05-JAN-04:00 | 16704.79 | 29-JUL-16:15 |
Heating:Electricity | 1203.59 | 0.00 | 01-JAN-00:15 | 13606.63 | 04-FEB-07:00 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 06-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
PlantLoopHeatingDemand:Plant | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
WaterSystems:PlantLoopHeatingDemand | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1322839.42 | 1166.51 | 28-FEB-03:00 | 395697.92 | 29-JUL-16:15 |
EnergyTransfer:Building | 480466.48 | 0.00 | 24-JAN-01:45 | 167755.50 | 29-JUL-16:15 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 13613.05 | 0.00 | 01-JAN-00:15 | 114727.54 | 04-FEB-07:00 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 466853.43 | 0.00 | 05-JAN-04:00 | 167755.50 | 29-JUL-16:15 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 39653.01 | 0.00 | 05-JAN-04:00 | 12924.46 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 287.57 | 0.00 | 01-JAN-00:15 | 5580.68 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 39365.44 | 0.00 | 05-JAN-04:00 | 12924.46 | 29-JUL-16:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 19735.52 | 0.00 | 01-JAN-02:15 | 6432.80 | 07-NOV-14:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 482.66 | 0.00 | 01-JAN-00:15 | 5042.55 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 19252.87 | 0.00 | 01-JAN-02:15 | 6432.80 | 07-NOV-14:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 26450.66 | 0.00 | 01-JAN-00:45 | 8869.90 | 14-OCT-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 913.40 | 0.00 | 01-JAN-00:15 | 7515.46 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 25537.26 | 0.00 | 01-JAN-00:45 | 8869.90 | 14-OCT-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23770.95 | 0.00 | 01-JAN-00:45 | 11037.50 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1277.60 | 0.00 | 01-JAN-00:15 | 7564.15 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22493.36 | 0.00 | 01-JAN-00:45 | 11037.50 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16929.44 | 0.00 | 01-JAN-02:00 | 6066.57 | 29-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 705.76 | 0.00 | 01-JAN-00:15 | 5139.86 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16223.68 | 0.00 | 01-JAN-02:00 | 6066.57 | 29-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23564.57 | 0.00 | 01-JAN-00:45 | 8876.46 | 25-JUL-10:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1093.62 | 0.00 | 01-JAN-00:15 | 7572.79 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22470.94 | 0.00 | 01-JAN-00:45 | 8876.46 | 25-JUL-10:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29145.20 | 0.00 | 01-JAN-02:15 | 11146.07 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 627.30 | 0.00 | 01-JAN-00:15 | 6132.06 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28517.89 | 0.00 | 01-JAN-02:15 | 11146.07 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22816.67 | 0.00 | 05-JAN-02:00 | 6718.52 | 07-NOV-14:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 216.63 | 0.00 | 01-JAN-00:15 | 3620.62 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22600.04 | 0.00 | 05-JAN-02:00 | 6718.52 | 07-NOV-14:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29234.50 | 0.00 | 01-JAN-02:15 | 9020.12 | 14-OCT-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 554.58 | 0.00 | 01-JAN-00:15 | 6178.34 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 28679.92 | 0.00 | 01-JAN-02:15 | 9020.12 | 14-OCT-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26360.04 | 0.00 | 01-JAN-02:15 | 11069.12 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 840.99 | 0.00 | 01-JAN-00:15 | 6245.61 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25519.05 | 0.00 | 01-JAN-02:15 | 11069.12 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 19778.38 | 0.00 | 01-JAN-07:15 | 6267.63 | 29-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 360.06 | 0.00 | 01-JAN-00:15 | 3756.47 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 19418.32 | 0.00 | 01-JAN-07:15 | 6267.63 | 29-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 26243.87 | 0.00 | 01-JAN-02:15 | 8930.97 | 25-JUL-10:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 686.45 | 0.00 | 01-JAN-00:15 | 6261.15 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25557.42 | 0.00 | 01-JAN-02:15 | 8930.97 | 25-JUL-10:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 30496.83 | 0.00 | 01-JAN-01:30 | 10302.94 | 29-JUL-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 1081.95 | 0.00 | 01-JAN-00:15 | 8248.30 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29414.88 | 0.00 | 01-JAN-01:30 | 10302.94 | 29-JUL-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32528.98 | 0.00 | 01-JAN-01:45 | 10344.97 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 928.92 | 0.00 | 01-JAN-00:15 | 8164.76 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 31600.06 | 0.00 | 01-JAN-01:45 | 10344.97 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32607.54 | 0.00 | 01-JAN-01:45 | 13334.21 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 1073.15 | 0.00 | 01-JAN-00:15 | 8130.45 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31534.40 | 0.00 | 01-JAN-01:45 | 13334.21 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24170.43 | 0.00 | 01-JAN-03:30 | 8533.26 | 29-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 688.11 | 0.00 | 01-JAN-00:15 | 5733.85 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 23482.32 | 0.00 | 01-JAN-03:30 | 8533.26 | 29-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26237.95 | 0.00 | 01-JAN-03:30 | 8514.99 | 29-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 514.31 | 0.00 | 01-JAN-00:15 | 5605.27 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 25723.64 | 0.00 | 01-JAN-03:30 | 8514.99 | 29-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30741.94 | 0.00 | 01-JAN-01:45 | 13351.14 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 1280.01 | 0.00 | 01-JAN-00:15 | 8235.16 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29461.93 | 0.00 | 01-JAN-01:45 | 13351.14 | 29-JUL-16:30 |
EnergyTransfer:Plant | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
WaterSystems:EnergyTransfer | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 88967.14 | 744.40 | 21-JUL-02:15 | 23549.06 | 21-JAN-08:45 |
EnergyTransfer:HVAC | 753405.80 | 0.00 | 24-JAN-01:45 | 222790.79 | 27-JUL-16:15 |
CoolingCoils:EnergyTransfer | 740266.37 | 0.00 | 05-JAN-04:00 | 222790.79 | 27-JUL-16:15 |
HeatingCoils:EnergyTransfer | 13139.43 | 0.00 | 01-JAN-00:15 | 109393.64 | 04-FEB-07:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 287.566 | -3278.26 | 0.000 | 0.000 | 2888.637 | 2771.241 | 10464.601 | 13044.259 | 0.000 | 3009.770 | 11644.104 | 0.000 | -2684.06 | 0.000 | -2060.70 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 482.645 | -1603.33 | 0.000 | 0.000 | 2899.476 | 2771.241 | 10464.601 | 5574.912 | 0.000 | 2835.647 | 0.003 | 0.000 | -1066.27 | 0.000 | -1862.82 | -2846.56 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 913.372 | -2126.68 | 0.000 | 0.000 | 2908.873 | 2771.241 | 10464.601 | 13320.312 | 0.000 | 3009.346 | 0.024 | 0.000 | -2500.59 | 0.000 | -1930.26 | -3419.62 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 1277.565 | -1873.18 | 0.000 | 0.000 | 2913.165 | 2771.241 | 10464.601 | 10548.415 | 0.000 | 3012.291 | 0.089 | 0.000 | -2653.91 | 0.000 | -1857.70 | -3982.51 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 705.744 | -1351.08 | 0.000 | 0.000 | 2906.295 | 2771.241 | 10464.601 | 2911.176 | 0.000 | 2840.618 | 0.000 | 0.000 | -1112.32 | 0.000 | -1786.24 | -3477.35 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 1093.597 | -1871.33 | 0.000 | 0.000 | 2913.712 | 2771.241 | 10464.601 | 10733.282 | 0.000 | 3009.248 | 0.062 | 0.000 | -2478.21 | 0.000 | -1871.00 | -4165.45 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 627.290 | -2374.89 | 0.000 | 0.000 | 2899.408 | 2771.241 | 10464.601 | 12651.824 | 0.000 | 2192.600 | 1232.946 | 0.000 | -2858.86 | 0.000 | -1463.32 | -0.02 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 216.628 | -1882.08 | 0.000 | 0.000 | 2890.351 | 2771.241 | 10464.601 | 5389.365 | 0.000 | 2022.435 | 1399.898 | 0.000 | -1158.86 | 0.000 | -1395.55 | -0.02 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 554.566 | -2388.40 | 0.000 | 0.000 | 2899.559 | 2771.241 | 10464.601 | 12866.416 | 0.000 | 2192.658 | 1134.333 | 0.000 | -2728.33 | 0.000 | -1475.04 | -0.04 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 840.972 | -2125.16 | 0.000 | 0.000 | 2903.647 | 2771.241 | 10464.601 | 10208.854 | 0.000 | 2194.450 | 468.137 | 0.000 | -2907.07 | 0.000 | -1425.85 | -0.18 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 360.057 | -1617.13 | 0.000 | 0.000 | 2895.801 | 2771.241 | 10464.601 | 2806.193 | 0.000 | 2023.722 | 665.507 | 0.000 | -1218.27 | 0.000 | -1350.37 | -0.11 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 686.433 | -2128.37 | 0.000 | 0.000 | 2904.049 | 2771.241 | 10464.601 | 10353.987 | 0.000 | 2192.608 | 333.245 | 0.000 | -2711.22 | 0.000 | -1437.38 | -0.05 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 1081.924 | -2449.62 | 0.000 | 0.000 | 2907.531 | 2771.241 | 10464.601 | 10081.005 | 0.000 | 2978.515 | 3828.505 | 0.000 | -2768.08 | 0.000 | -1930.19 | -0.09 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 928.898 | -2631.59 | 0.000 | 0.000 | 2904.417 | 2771.241 | 10464.601 | 12594.355 | 0.000 | 2978.608 | 3682.231 | 0.000 | -2754.37 | 0.000 | -1969.79 | -0.12 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 1073.121 | -2626.10 | 0.000 | 0.000 | 2904.869 | 2771.241 | 10464.601 | 12389.340 | 0.000 | 2978.844 | 3771.233 | 0.000 | -2869.54 | 0.000 | -1949.47 | -0.05 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 688.095 | -1955.56 | 0.000 | 0.000 | 2900.037 | 2771.241 | 10464.601 | 2710.887 | 0.000 | 2811.410 | 4228.059 | 0.000 | -1240.71 | 0.000 | -1851.17 | -0.29 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 514.298 | -2142.21 | 0.000 | 0.000 | 2896.319 | 2771.241 | 10464.601 | 5273.820 | 0.000 | 2809.443 | 4057.288 | 0.000 | -1166.67 | 0.000 | -1896.62 | -0.08 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 1279.982 | -2453.51 | 0.000 | 0.000 | 2907.539 | 2771.241 | 10464.601 | 9930.583 | 0.000 | 2981.446 | 3983.465 | 0.000 | -2942.16 | 0.000 | -1914.90 | -0.00 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5878.816 | 48081.921 | 0.000 | 0.000 | 0.000 | -53960.74 | -0.99 |
Total Facility | 0.000 | 0.000 | 13612.752 | -38878.50 | 0.000 | 0.000 | 52243.684 | 49882.340 | 188362.826 | 163388.985 | 0.000 | 53952.475 | 88511.051 | 0.000 | -39819.50 | 0.000 | -85389.11 | -17893.52 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 7156.28 | 0.00 | 1845.96 | 1979.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-NOV-14:45 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.92 | 116.28 | 1091.85 | 3397.13 | 0.00 | 557.00 | 1154.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14-OCT-13:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.21 | 116.28 | 1109.73 | 5471.55 | 0.00 | 1292.65 | 763.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 29-JUL-16:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 7123.76 | 0.00 | 1793.12 | 177.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 29-JUL-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.05 | 813.96 | 1748.06 | 803.76 | 0.00 | 1523.99 | 753.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25-JUL-10:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.01 | 116.28 | 1089.80 | 6658.23 | 0.00 | 1299.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -368.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-JUL-16:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6893.95 | 0.00 | 1305.34 | 1003.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 07-NOV-14:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 3500.97 | 0.00 | 447.02 | 1446.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 14-OCT-13:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.20 | 116.28 | 1109.73 | 5357.46 | 0.00 | 947.19 | 1373.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 29-JUL-16:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.45 | 434.11 | 1371.36 | 7003.39 | 0.00 | 1305.33 | 816.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 29-JUL-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.05 | 813.96 | 1748.06 | 806.74 | 0.00 | 1040.63 | 1434.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25-JUL-10:48 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.17 | 116.28 | 1089.80 | 5478.68 | 0.00 | 1029.08 | 1146.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 29-JUL-17:03 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 260.53 | 604.65 | 1685.13 | 2455.38 | 0.00 | 1645.55 | 3668.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 29-JUL-17:03 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 260.89 | 604.65 | 1685.13 | 2365.42 | 0.00 | 1649.24 | 3795.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 29-JUL-16:23 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6742.19 | 0.00 | 1787.22 | 2861.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 29-JUL-18:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 427.06 | 813.96 | 1748.06 | 765.72 | 0.00 | 1518.16 | 3263.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 29-JUL-18:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 427.06 | 813.96 | 1748.06 | 723.12 | 0.00 | 1518.16 | 3288.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 29-JUL-16:23 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6844.99 | 0.00 | 1787.22 | 2775.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-16:05 | 0.00 | 0.00 | 0.00 | -14.0 | 0.00 | 0.00 | 2522.32 | 7813.98 | 24684.52 | 72699.13 | 0.00 | 29411.80 | 53710.23 | 0.00 | 0.00 | 0.00 | -23084.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 5580.61 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3644.5 | 0.00 | -3742.7 | -239.4 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 5042.48 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1476.6 | 0.00 | -3488.5 | -2123.5 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 7515.34 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3642.2 | 0.00 | -3742.7 | -2176.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 7564.02 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3684.2 | 0.00 | -3742.7 | -2183.2 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 5139.79 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1520.4 | 0.00 | -3488.5 | -2177.0 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 7572.67 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3683.5 | 0.00 | -3742.7 | -2192.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 6131.88 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3760.7 | 0.00 | -2549.2 | -1868.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 3620.52 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1517.2 | 0.00 | -2294.7 | -1854.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 6178.16 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3757.3 | 0.00 | -2549.2 | -1917.7 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 6245.42 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3814.7 | 0.00 | -2549.2 | -1927.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 3756.36 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1577.0 | 0.00 | -2294.7 | -1930.8 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 6260.97 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3813.4 | 0.00 | -2549.2 | -1944.5 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 8248.16 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3826.8 | 0.00 | -3751.3 | -2716.1 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 8164.63 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3763.1 | 0.00 | -3751.3 | -2696.3 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 8130.31 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3765.5 | 0.00 | -3751.3 | -2659.6 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 5733.76 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1579.9 | 0.00 | -3496.5 | -2703.5 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 5605.18 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1511.9 | 0.00 | -3496.5 | -2642.9 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 04-FEB-07:00 | 0.00 | 0.00 | 8235.01 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3827.9 | 0.00 | -3751.3 | -2701.9 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-07:00 | 0.00 | 0.00 | 114725.28 | 0.00 | 0.00 | 0.00 | 9473.51 | 7813.98 | 19542.30 | 0.00 | 0.00 | 1202.86 | 0.00 | 0.00 | -54166.8 | 0.00 | -58732.4 | -39858.7 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 528.993 | 2.00 | 2.00 | 1.00 | 44.9950 | 528.993 | 0.085 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 217.813 | 2.00 | 2.00 | 1.00 | 44.9950 | 217.813 | 0.207 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 340.002 | 2.00 | 2.00 | 1.00 | 44.9950 | 340.002 | 0.132 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 456.379 | 2.00 | 2.00 | 1.00 | 44.9950 | 456.379 | 0.099 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 230.634 | 2.00 | 2.00 | 1.00 | 44.9950 | 230.634 | 0.195 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 345.197 | 2.00 | 2.00 | 1.00 | 44.9950 | 345.197 | 0.130 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 455.624 | 2.00 | 2.00 | 1.00 | 44.9950 | 455.624 | 0.099 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 230.766 | 2.00 | 2.00 | 1.00 | 44.9950 | 230.766 | 0.195 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 341.281 | 2.00 | 2.00 | 1.00 | 44.9950 | 341.281 | 0.132 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 461.473 | 2.00 | 2.00 | 1.00 | 44.9950 | 461.473 | 0.098 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 242.775 | 2.00 | 2.00 | 1.00 | 44.9950 | 242.775 | 0.185 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 346.245 | 2.00 | 2.00 | 1.00 | 44.9950 | 346.245 | 0.130 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 541.084 | 2.00 | 2.00 | 1.00 | 44.9950 | 541.084 | 0.083 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 314.945 | 2.00 | 2.00 | 1.00 | 44.9950 | 314.945 | 0.143 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 381.355 | 2.00 | 2.00 | 1.00 | 44.9950 | 381.355 | 0.118 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 545.499 | 2.00 | 2.00 | 1.00 | 44.9950 | 545.499 | 0.082 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 323.634 | 2.00 | 2.00 | 1.00 | 44.9950 | 323.634 | 0.139 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 382.320 | 2.00 | 2.00 | 1.00 | 44.9950 | 382.320 | 0.118 | 1.000 | 44.9950 | 0.12 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 72.170 | 2.00 | 2.00 | 1.00 | 44.9950 | 72.170 | 1.000 | 1.000 | 44.9950 | 0.62 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 74.474 | 2.00 | 2.00 | 1.00 | 44.9950 | 74.474 | 1.000 | 1.000 | 44.9950 | 0.60 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 107.522 | 2.00 | 2.00 | 1.00 | 44.9950 | 107.522 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 107.937 | 2.00 | 2.00 | 1.00 | 44.9950 | 107.937 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 74.607 | 2.00 | 2.00 | 1.00 | 44.9950 | 74.607 | 1.000 | 1.000 | 44.9950 | 0.60 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 107.554 | 2.00 | 2.00 | 1.00 | 44.9950 | 107.554 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 92.804 | 2.00 | 2.00 | 1.00 | 44.9950 | 92.804 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 58.687 | 2.00 | 2.00 | 1.00 | 44.9950 | 58.687 | 1.000 | 1.000 | 44.9950 | 0.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 92.396 | 2.00 | 2.00 | 1.00 | 44.9950 | 92.396 | 1.000 | 1.000 | 44.9950 | 0.49 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.107 | 2.00 | 2.00 | 1.00 | 44.9950 | 93.107 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 58.911 | 2.00 | 2.00 | 1.00 | 44.9950 | 58.911 | 1.000 | 1.000 | 44.9950 | 0.76 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 92.522 | 2.00 | 2.00 | 1.00 | 44.9950 | 92.522 | 1.000 | 1.000 | 44.9950 | 0.49 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 119.338 | 2.00 | 2.00 | 1.00 | 44.9950 | 119.338 | 1.000 | 1.000 | 44.9950 | 0.38 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 85.192 | 2.00 | 2.00 | 1.00 | 44.9950 | 85.192 | 1.000 | 1.000 | 44.9950 | 0.53 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 118.799 | 2.00 | 2.00 | 1.00 | 44.9950 | 118.799 | 1.000 | 1.000 | 44.9950 | 0.38 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 119.717 | 2.00 | 2.00 | 1.00 | 44.9950 | 119.717 | 1.000 | 1.000 | 44.9950 | 0.38 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 85.522 | 2.00 | 2.00 | 1.00 | 44.9950 | 85.522 | 1.000 | 1.000 | 44.9950 | 0.53 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 119.051 | 2.00 | 2.00 | 1.00 | 44.9950 | 119.051 | 1.000 | 1.000 | 44.9950 | 0.38 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 528.993 | 528.9931 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 217.813 | 217.8128 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 340.002 | 340.0017 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 456.379 | 456.3789 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 230.634 | 230.6335 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 345.197 | 345.1972 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 455.624 | 455.6237 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 230.766 | 230.7660 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 341.281 | 341.2808 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 461.473 | 461.4728 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 242.775 | 242.7754 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 346.245 | 346.2453 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 382.320 | 382.3198 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 381.355 | 381.3550 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 541.084 | 541.0842 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 323.634 | 323.6342 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 314.945 | 314.9449 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 545.499 | 545.4991 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 | 528.993 | 528.99 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 | 217.813 | 217.81 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 | 340.002 | 340.00 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 | 456.379 | 456.38 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 | 230.634 | 230.63 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 | 345.197 | 345.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 | 455.624 | 455.62 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 | 230.766 | 230.77 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 | 341.281 | 341.28 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 | 461.473 | 461.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 | 242.775 | 242.78 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 | 346.245 | 346.25 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 541.08 | 541.084 | 541.08 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 314.94 | 314.945 | 314.94 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 381.35 | 381.355 | 381.35 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 545.50 | 545.499 | 545.50 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 323.63 | 323.634 | 323.63 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 382.32 | 382.320 | 382.32 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 72.170 | 72.170 | 72.170 | 44.9950 | 0.623 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 74.474 | 74.474 | 74.474 | 44.9950 | 0.604 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 107.522 | 107.522 | 107.522 | 44.9950 | 0.418 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 107.937 | 107.937 | 107.937 | 44.9950 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 74.607 | 74.607 | 74.607 | 44.9950 | 0.603 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 107.554 | 107.554 | 107.554 | 44.9950 | 0.418 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 92.804 | 92.804 | 92.804 | 44.9950 | 0.485 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 58.687 | 58.687 | 58.687 | 44.9950 | 0.767 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 92.396 | 92.396 | 92.396 | 44.9950 | 0.487 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.107 | 93.107 | 93.107 | 44.9950 | 0.483 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 58.911 | 58.911 | 58.911 | 44.9950 | 0.764 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 92.522 | 92.522 | 92.522 | 44.9950 | 0.486 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 119.051 | 119.051 | 119.051 | 44.9950 | 0.378 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 118.799 | 118.799 | 118.799 | 44.9950 | 0.379 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 119.338 | 119.338 | 119.338 | 44.9950 | 0.377 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 85.522 | 85.522 | 85.522 | 44.9950 | 0.526 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 85.192 | 85.192 | 85.192 | 44.9950 | 0.528 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 119.717 | 119.717 | 119.717 | 44.9950 | 0.376 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 72.17 | 72.170 | 72.17 | 72.17 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 74.47 | 74.474 | 74.47 | 74.47 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 107.52 | 107.522 | 107.52 | 107.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 107.94 | 107.937 | 107.94 | 107.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 74.61 | 74.607 | 74.61 | 74.61 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 107.55 | 107.554 | 107.55 | 107.55 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 92.80 | 92.804 | 92.80 | 92.80 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 58.69 | 58.687 | 58.69 | 58.69 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 92.40 | 92.396 | 92.40 | 92.40 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.11 | 93.107 | 93.11 | 93.11 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 58.91 | 58.911 | 58.91 | 58.91 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 92.52 | 92.522 | 92.52 | 92.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 119.34 | 119.338 | 119.34 | 119.34 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 85.19 | 85.192 | 85.19 | 85.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 118.80 | 118.799 | 118.80 | 118.80 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 119.72 | 119.717 | 119.72 | 119.72 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 85.52 | 85.522 | 85.52 | 85.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 119.05 | 119.051 | 119.05 | 119.05 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 24.50 |
Number of hours not met | 24.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 1203.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Cooling | 50330.63 | 13908.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 8086.86 | 2116.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 30560.45 | 34159.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15031.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 196100.87 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 669570.21 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 669570.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.03 |
Space Cooling | 1.29 |
Fans-Interior | 0.21 |
Service Water Heating | 0.78 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 5.03 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.45 |
Space Heating | 0.61 |
Space Cooling | 25.67 |
Fans-Interior | 4.12 |
Service Water Heating | 15.58 |
Receptacle Equipment | 45.03 |
Miscellaneous | 1.53 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 382.32 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 381.35 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 541.08 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 323.63 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 314.94 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 545.50 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 541.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 314.94 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 381.35 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 545.50 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 323.63 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 382.32 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 | 1.52 | 0.715826 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 | 0.725891 | 0.676083 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 | 1.08 | 0.687952 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 | 1.36 | 0.705505 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 | 0.768618 | 0.676083 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 | 1.09 | 0.689094 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 | 1.31 | 0.715629 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 | 0.769059 | 0.676083 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 | 1.05 | 0.697704 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 | 1.32 | 0.716405 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 | 0.809082 | 0.676083 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 | 1.05 | 0.699330 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 541.08 | 1.54 | 0.717370 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 314.94 | 1.02 | 0.682534 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 381.35 | 1.20 | 0.691274 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 545.50 | 1.55 | 0.717891 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 323.63 | 1.04 | 0.684286 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 382.32 | 1.19 | 0.693392 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 | 528.99 | 528.99 | 18203.45 | 1.52 | 5086.32 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 | 217.81 | 217.81 | 8710.69 | 0.725891 | 5210.90 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 | 340.00 | 340.00 | 12969.18 | 1.08 | 6997.88 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 | 456.38 | 456.38 | 16295.14 | 1.36 | 7020.32 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 | 230.63 | 230.63 | 9223.42 | 0.768618 | 5218.13 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 | 345.20 | 345.20 | 13109.07 | 1.09 | 6999.63 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 | 455.62 | 455.62 | 15689.53 | 1.31 | 6202.00 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 | 230.77 | 230.77 | 9228.72 | 0.769059 | 4357.26 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 | 341.28 | 341.28 | 12541.95 | 1.05 | 6179.95 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 | 461.47 | 461.47 | 15847.75 | 1.32 | 6218.43 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 | 242.78 | 242.78 | 9708.99 | 0.809082 | 4369.40 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 | 346.25 | 346.25 | 12647.31 | 1.05 | 6186.80 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | 541.08 | 541.08 | 541.08 | 18519.14 | 1.54 | 7636.79 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | 314.94 | 314.94 | 314.94 | 12272.17 | 1.02 | 5790.46 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | 381.35 | 381.35 | 381.35 | 14360.92 | 1.20 | 7607.63 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | 545.50 | 545.50 | 545.50 | 18636.29 | 1.55 | 7657.28 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | 323.63 | 323.63 | 323.63 | 12523.51 | 1.04 | 5808.31 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | 382.32 | 382.32 | 382.32 | 14281.01 | 1.19 | 7621.25 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 541.08 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 314.94 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 381.35 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 545.50 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 323.63 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 382.32 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Heating Capacity [Btu/h] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 528.99 | 18203.45 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 217.81 | 8710.69 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 340.00 | 12969.18 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 456.38 | 16295.14 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 230.63 | 9223.42 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 345.20 | 13109.07 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 455.62 | 15689.53 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 230.77 | 9228.72 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 341.28 | 12541.95 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 461.47 | 15847.75 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 242.78 | 9708.99 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 346.25 | 12647.31 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 541.08 | 18519.14 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 314.94 | 12272.17 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 381.35 | 14360.92 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 545.50 | 18636.29 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 323.63 | 12523.51 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 382.32 | 14281.01 |
Design Size Nominal Capacity [Btu/h] | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 5086.32 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 5210.90 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 6997.88 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 7020.32 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 5218.13 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 6999.63 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 6202.00 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 4357.26 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 6179.95 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 6218.43 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 4369.40 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 6186.80 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 7636.79 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 5790.46 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 7607.63 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 7657.28 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 5808.31 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 7621.25 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 565.568 | 30.966 | 52.250 | 0.495 | 31.461 |
February | 553.762 | 34.103 | 43.625 | 0.921 | 35.025 |
March | 645.658 | 42.372 | 40.775 | 0.705 | 43.077 |
April | 708.057 | 52.171 | 0.000 | 0.000 | 52.171 |
May | 744.000 | 67.583 | 0.000 | 0.000 | 67.583 |
June | 720.000 | 71.859 | 0.000 | 0.000 | 71.859 |
July | 744.000 | 76.864 | 0.000 | 0.000 | 76.864 |
August | 744.000 | 76.552 | 0.000 | 0.000 | 76.552 |
September | 720.000 | 72.822 | 0.000 | 0.000 | 72.822 |
October | 744.000 | 68.493 | 0.000 | 0.000 | 68.493 |
November | 676.900 | 51.342 | 18.250 | 0.225 | 51.567 |
December | 625.415 | 36.801 | 53.000 | 0.961 | 37.763 |
Annual Sum or Average | 8191.361 | 681.929 | 207.900 | 3.308 | 685.237 |
Minimum of Months | 553.762 | 30.966 | 0.000 | 0.000 | 31.461 |
Maximum of Months | 744.000 | 76.864 | 53.000 | 0.961 | 76.864 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 436.911 | 12.643 | 103.975 | 1.024 | 13.667 |
February | 448.659 | 14.035 | 65.542 | 1.048 | 15.084 |
March | 576.813 | 16.583 | 72.250 | 0.963 | 17.546 |
April | 683.218 | 21.577 | 4.250 | 0.013 | 21.591 |
May | 744.000 | 31.191 | 0.000 | 0.000 | 31.191 |
June | 720.000 | 35.366 | 0.000 | 0.000 | 35.366 |
July | 744.000 | 37.791 | 0.000 | 0.000 | 37.791 |
August | 744.000 | 37.942 | 0.000 | 0.000 | 37.942 |
September | 720.000 | 36.767 | 0.000 | 0.000 | 36.767 |
October | 744.000 | 34.256 | 0.000 | 0.000 | 34.256 |
November | 620.027 | 24.434 | 29.625 | 0.363 | 24.797 |
December | 482.483 | 15.429 | 75.875 | 1.157 | 16.586 |
Annual Sum or Average | 7664.111 | 318.013 | 351.517 | 4.569 | 322.582 |
Minimum of Months | 436.911 | 12.643 | 0.000 | 0.000 | 13.667 |
Maximum of Months | 744.000 | 37.942 | 103.975 | 1.157 | 37.942 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 403.053 | 15.369 | 151.792 | 2.291 | 17.659 |
February | 432.627 | 17.809 | 104.208 | 2.033 | 19.841 |
March | 554.585 | 22.002 | 72.125 | 1.519 | 23.521 |
April | 649.690 | 30.299 | 9.250 | 0.083 | 30.382 |
May | 737.250 | 43.336 | 0.000 | 0.000 | 43.336 |
June | 720.000 | 49.276 | 0.000 | 0.000 | 49.276 |
July | 744.000 | 52.859 | 0.000 | 0.000 | 52.859 |
August | 744.000 | 51.355 | 0.000 | 0.000 | 51.355 |
September | 720.000 | 49.602 | 0.000 | 0.000 | 49.602 |
October | 737.500 | 44.509 | 0.000 | 0.000 | 44.509 |
November | 588.714 | 30.288 | 37.125 | 0.705 | 30.993 |
December | 438.368 | 17.838 | 117.892 | 2.295 | 20.133 |
Annual Sum or Average | 7469.787 | 424.541 | 492.392 | 8.926 | 433.467 |
Minimum of Months | 403.053 | 15.369 | 0.000 | 0.000 | 17.659 |
Maximum of Months | 744.000 | 52.859 | 151.792 | 2.295 | 52.859 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 306.393 | 9.251 | 212.770 | 3.534 | 12.784 |
February | 375.721 | 13.771 | 136.104 | 2.801 | 16.571 |
March | 515.264 | 20.572 | 104.250 | 2.478 | 23.050 |
April | 638.421 | 30.018 | 11.313 | 0.094 | 30.112 |
May | 736.667 | 46.200 | 0.000 | 0.000 | 46.200 |
June | 720.000 | 52.088 | 0.000 | 0.000 | 52.088 |
July | 744.000 | 56.242 | 0.000 | 0.000 | 56.242 |
August | 744.000 | 54.326 | 0.000 | 0.000 | 54.326 |
September | 720.000 | 49.176 | 0.000 | 0.000 | 49.176 |
October | 737.250 | 41.344 | 0.000 | 0.000 | 41.344 |
November | 554.672 | 25.712 | 47.333 | 0.968 | 26.680 |
December | 371.787 | 13.638 | 160.658 | 3.273 | 16.911 |
Annual Sum or Average | 7164.174 | 412.337 | 672.428 | 13.148 | 425.485 |
Minimum of Months | 306.393 | 9.251 | 0.000 | 0.000 | 12.784 |
Maximum of Months | 744.000 | 56.242 | 212.770 | 3.534 | 56.242 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 308.675 | 6.054 | 169.755 | 1.644 | 7.698 |
February | 396.137 | 8.684 | 97.417 | 1.413 | 10.097 |
March | 533.187 | 12.965 | 95.944 | 1.279 | 14.244 |
April | 679.945 | 19.424 | 4.500 | 0.015 | 19.439 |
May | 744.000 | 31.419 | 0.000 | 0.000 | 31.419 |
June | 720.000 | 36.303 | 0.000 | 0.000 | 36.303 |
July | 744.000 | 38.468 | 0.000 | 0.000 | 38.468 |
August | 744.000 | 37.306 | 0.000 | 0.000 | 37.306 |
September | 720.000 | 34.163 | 0.000 | 0.000 | 34.163 |
October | 744.000 | 28.937 | 0.000 | 0.000 | 28.937 |
November | 592.937 | 18.097 | 37.750 | 0.458 | 18.555 |
December | 378.162 | 8.956 | 122.354 | 1.722 | 10.678 |
Annual Sum or Average | 7305.044 | 280.775 | 527.719 | 6.532 | 287.307 |
Minimum of Months | 308.675 | 6.054 | 0.000 | 0.000 | 7.698 |
Maximum of Months | 744.000 | 38.468 | 169.755 | 1.722 | 38.468 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 311.415 | 8.495 | 189.292 | 2.819 | 11.314 |
February | 406.413 | 12.311 | 119.667 | 2.368 | 14.679 |
March | 528.993 | 18.257 | 93.483 | 1.709 | 19.966 |
April | 649.590 | 28.250 | 9.250 | 0.084 | 28.334 |
May | 737.500 | 43.516 | 0.000 | 0.000 | 43.516 |
June | 720.000 | 50.094 | 0.000 | 0.000 | 50.094 |
July | 744.000 | 53.426 | 0.000 | 0.000 | 53.426 |
August | 744.000 | 50.724 | 0.000 | 0.000 | 50.724 |
September | 720.000 | 47.020 | 0.000 | 0.000 | 47.020 |
October | 737.250 | 39.312 | 0.000 | 0.000 | 39.312 |
November | 575.983 | 23.993 | 42.625 | 0.777 | 24.770 |
December | 358.429 | 11.465 | 160.375 | 2.894 | 14.359 |
Annual Sum or Average | 7233.573 | 386.863 | 614.692 | 10.651 | 397.514 |
Minimum of Months | 311.415 | 8.495 | 0.000 | 0.000 | 11.314 |
Maximum of Months | 744.000 | 53.426 | 189.292 | 2.894 | 53.426 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 440.442 | 19.412 | 115.833 | 1.660 | 21.072 |
February | 466.251 | 22.540 | 72.375 | 1.539 | 24.079 |
March | 596.208 | 28.587 | 75.250 | 1.404 | 29.991 |
April | 687.889 | 37.036 | 4.750 | 0.024 | 37.060 |
May | 744.000 | 50.158 | 0.000 | 0.000 | 50.158 |
June | 720.000 | 54.957 | 0.000 | 0.000 | 54.957 |
July | 744.000 | 59.942 | 0.000 | 0.000 | 59.942 |
August | 744.000 | 58.889 | 0.000 | 0.000 | 58.889 |
September | 720.000 | 56.068 | 0.000 | 0.000 | 56.068 |
October | 744.000 | 51.626 | 0.000 | 0.000 | 51.626 |
November | 620.556 | 36.403 | 30.750 | 0.526 | 36.929 |
December | 498.323 | 24.063 | 81.958 | 1.758 | 25.821 |
Annual Sum or Average | 7725.670 | 499.683 | 380.917 | 6.911 | 506.594 |
Minimum of Months | 440.442 | 19.412 | 0.000 | 0.000 | 21.072 |
Maximum of Months | 744.000 | 59.942 | 115.833 | 1.758 | 59.942 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 527.029 | 15.780 | 62.750 | 0.415 | 16.195 |
February | 509.275 | 16.959 | 41.875 | 0.534 | 17.493 |
March | 621.337 | 20.141 | 44.125 | 0.426 | 20.567 |
April | 701.508 | 25.353 | 0.000 | 0.000 | 25.353 |
May | 744.000 | 33.894 | 0.000 | 0.000 | 33.894 |
June | 720.000 | 37.569 | 0.000 | 0.000 | 37.569 |
July | 744.000 | 40.333 | 0.000 | 0.000 | 40.333 |
August | 744.000 | 40.070 | 0.000 | 0.000 | 40.070 |
September | 720.000 | 39.146 | 0.000 | 0.000 | 39.146 |
October | 744.000 | 37.227 | 0.000 | 0.000 | 37.227 |
November | 655.854 | 27.601 | 18.750 | 0.148 | 27.749 |
December | 566.356 | 18.793 | 53.062 | 0.591 | 19.384 |
Annual Sum or Average | 7997.359 | 352.868 | 220.562 | 2.113 | 354.981 |
Minimum of Months | 509.275 | 15.780 | 0.000 | 0.000 | 16.195 |
Maximum of Months | 744.000 | 40.333 | 62.750 | 0.591 | 40.333 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 461.937 | 18.400 | 104.375 | 1.411 | 19.811 |
February | 478.226 | 20.819 | 64.125 | 1.332 | 22.151 |
March | 608.731 | 25.890 | 55.625 | 0.961 | 26.851 |
April | 694.646 | 34.689 | 5.250 | 0.029 | 34.718 |
May | 744.000 | 47.075 | 0.000 | 0.000 | 47.075 |
June | 720.000 | 52.683 | 0.000 | 0.000 | 52.683 |
July | 744.000 | 56.785 | 0.000 | 0.000 | 56.785 |
August | 744.000 | 54.808 | 0.000 | 0.000 | 54.808 |
September | 720.000 | 53.160 | 0.000 | 0.000 | 53.160 |
October | 744.000 | 48.615 | 0.000 | 0.000 | 48.615 |
November | 628.268 | 34.045 | 27.500 | 0.439 | 34.485 |
December | 500.423 | 21.124 | 78.250 | 1.567 | 22.691 |
Annual Sum or Average | 7788.232 | 468.094 | 335.125 | 5.740 | 473.834 |
Minimum of Months | 461.937 | 18.400 | 0.000 | 0.000 | 19.811 |
Maximum of Months | 744.000 | 56.785 | 104.375 | 1.567 | 56.785 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 363.638 | 11.777 | 163.350 | 2.382 | 14.159 |
February | 424.229 | 16.772 | 95.542 | 1.938 | 18.711 |
March | 574.646 | 24.725 | 89.000 | 1.739 | 26.463 |
April | 686.326 | 34.913 | 6.000 | 0.030 | 34.943 |
May | 744.000 | 50.427 | 0.000 | 0.000 | 50.427 |
June | 720.000 | 55.936 | 0.000 | 0.000 | 55.936 |
July | 744.000 | 60.637 | 0.000 | 0.000 | 60.637 |
August | 744.000 | 58.238 | 0.000 | 0.000 | 58.238 |
September | 720.000 | 53.280 | 0.000 | 0.000 | 53.280 |
October | 744.000 | 46.038 | 0.000 | 0.000 | 46.038 |
November | 603.131 | 29.720 | 37.875 | 0.653 | 30.373 |
December | 429.964 | 16.773 | 114.750 | 2.378 | 19.151 |
Annual Sum or Average | 7497.934 | 459.237 | 506.517 | 9.120 | 468.356 |
Minimum of Months | 363.638 | 11.777 | 0.000 | 0.000 | 14.159 |
Maximum of Months | 744.000 | 60.637 | 163.350 | 2.382 | 60.637 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 409.526 | 8.620 | 107.796 | 0.801 | 9.421 |
February | 461.239 | 11.578 | 65.125 | 0.779 | 12.357 |
March | 578.371 | 16.547 | 65.079 | 0.635 | 17.183 |
April | 700.229 | 23.379 | 0.000 | 0.000 | 23.379 |
May | 744.000 | 34.121 | 0.000 | 0.000 | 34.121 |
June | 720.000 | 38.445 | 0.000 | 0.000 | 38.445 |
July | 744.000 | 40.959 | 0.000 | 0.000 | 40.959 |
August | 744.000 | 39.477 | 0.000 | 0.000 | 39.477 |
September | 720.000 | 36.611 | 0.000 | 0.000 | 36.611 |
October | 744.000 | 32.120 | 0.000 | 0.000 | 32.120 |
November | 634.612 | 21.425 | 24.542 | 0.204 | 21.629 |
December | 472.095 | 11.905 | 90.250 | 0.990 | 12.895 |
Annual Sum or Average | 7672.071 | 315.188 | 352.791 | 3.410 | 318.598 |
Minimum of Months | 409.526 | 8.620 | 0.000 | 0.000 | 9.421 |
Maximum of Months | 744.000 | 40.959 | 107.796 | 0.990 | 40.959 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 379.769 | 11.028 | 135.750 | 1.800 | 12.828 |
February | 456.843 | 15.327 | 84.542 | 1.621 | 16.948 |
March | 578.680 | 22.158 | 62.825 | 1.084 | 23.242 |
April | 694.239 | 32.812 | 5.500 | 0.029 | 32.841 |
May | 744.000 | 47.353 | 0.000 | 0.000 | 47.353 |
June | 720.000 | 53.573 | 0.000 | 0.000 | 53.573 |
July | 744.000 | 57.449 | 0.000 | 0.000 | 57.449 |
August | 744.000 | 54.313 | 0.000 | 0.000 | 54.313 |
September | 720.000 | 50.765 | 0.000 | 0.000 | 50.765 |
October | 744.000 | 43.641 | 0.000 | 0.000 | 43.641 |
November | 618.025 | 27.874 | 31.625 | 0.498 | 28.372 |
December | 416.238 | 14.339 | 108.975 | 2.056 | 16.395 |
Annual Sum or Average | 7559.794 | 430.632 | 429.217 | 7.087 | 437.719 |
Minimum of Months | 379.769 | 11.028 | 0.000 | 0.000 | 12.828 |
Maximum of Months | 744.000 | 57.449 | 135.750 | 2.056 | 57.449 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 403.472 | 19.782 | 155.175 | 2.992 | 22.774 |
February | 431.940 | 23.623 | 103.125 | 2.545 | 26.168 |
March | 567.358 | 30.796 | 87.750 | 2.319 | 33.115 |
April | 665.276 | 41.309 | 9.722 | 0.079 | 41.388 |
May | 741.125 | 58.451 | 0.000 | 0.000 | 58.451 |
June | 720.000 | 64.830 | 0.000 | 0.000 | 64.830 |
July | 744.000 | 70.467 | 0.000 | 0.000 | 70.467 |
August | 744.000 | 68.598 | 0.000 | 0.000 | 68.598 |
September | 720.000 | 64.762 | 0.000 | 0.000 | 64.762 |
October | 744.000 | 58.014 | 0.000 | 0.000 | 58.014 |
November | 597.435 | 39.700 | 36.750 | 0.895 | 40.596 |
December | 459.306 | 24.844 | 113.312 | 2.862 | 27.706 |
Annual Sum or Average | 7537.912 | 565.177 | 505.835 | 11.693 | 576.870 |
Minimum of Months | 403.472 | 19.782 | 0.000 | 0.000 | 22.774 |
Maximum of Months | 744.000 | 70.467 | 155.175 | 2.992 | 70.467 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 463.471 | 16.281 | 99.549 | 1.159 | 17.441 |
February | 471.897 | 18.314 | 61.583 | 1.142 | 19.456 |
March | 601.458 | 22.653 | 69.000 | 1.031 | 23.685 |
April | 693.593 | 29.885 | 3.250 | 0.009 | 29.894 |
May | 744.000 | 42.183 | 0.000 | 0.000 | 42.183 |
June | 720.000 | 47.287 | 0.000 | 0.000 | 47.287 |
July | 744.000 | 50.718 | 0.000 | 0.000 | 50.718 |
August | 744.000 | 49.701 | 0.000 | 0.000 | 49.701 |
September | 720.000 | 47.868 | 0.000 | 0.000 | 47.868 |
October | 744.000 | 43.947 | 0.000 | 0.000 | 43.947 |
November | 631.448 | 31.210 | 27.375 | 0.378 | 31.588 |
December | 510.365 | 19.834 | 72.792 | 1.304 | 21.138 |
Annual Sum or Average | 7788.233 | 419.882 | 333.549 | 5.024 | 424.906 |
Minimum of Months | 463.471 | 16.281 | 0.000 | 0.000 | 17.441 |
Maximum of Months | 744.000 | 50.718 | 99.549 | 1.304 | 50.718 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 426.456 | 18.135 | 137.100 | 2.370 | 20.505 |
February | 451.411 | 21.211 | 93.475 | 2.100 | 23.311 |
March | 581.430 | 27.082 | 69.875 | 1.561 | 28.643 |
April | 673.229 | 37.628 | 7.875 | 0.067 | 37.695 |
May | 741.500 | 53.196 | 0.000 | 0.000 | 53.196 |
June | 720.000 | 59.957 | 0.000 | 0.000 | 59.957 |
July | 744.000 | 64.528 | 0.000 | 0.000 | 64.528 |
August | 744.000 | 61.907 | 0.000 | 0.000 | 61.907 |
September | 720.000 | 59.437 | 0.000 | 0.000 | 59.437 |
October | 744.000 | 53.041 | 0.000 | 0.000 | 53.041 |
November | 609.167 | 36.085 | 33.625 | 0.719 | 36.804 |
December | 458.848 | 21.338 | 106.875 | 2.421 | 23.759 |
Annual Sum or Average | 7614.041 | 513.545 | 448.825 | 9.239 | 522.783 |
Minimum of Months | 426.456 | 18.135 | 0.000 | 0.000 | 20.505 |
Maximum of Months | 744.000 | 64.528 | 137.100 | 2.421 | 64.528 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 350.543 | 13.908 | 189.208 | 3.713 | 17.621 |
February | 408.262 | 19.460 | 120.625 | 2.940 | 22.400 |
March | 556.354 | 28.483 | 94.750 | 2.560 | 31.043 |
April | 664.512 | 40.248 | 10.000 | 0.081 | 40.329 |
May | 741.250 | 58.754 | 0.000 | 0.000 | 58.754 |
June | 720.000 | 65.496 | 0.000 | 0.000 | 65.496 |
July | 744.000 | 71.009 | 0.000 | 0.000 | 71.009 |
August | 744.000 | 68.365 | 0.000 | 0.000 | 68.365 |
September | 720.000 | 63.233 | 0.000 | 0.000 | 63.233 |
October | 744.000 | 54.121 | 0.000 | 0.000 | 54.121 |
November | 583.829 | 34.421 | 42.125 | 1.017 | 35.438 |
December | 406.646 | 19.075 | 140.708 | 3.493 | 22.568 |
Annual Sum or Average | 7383.397 | 536.574 | 597.417 | 13.804 | 550.378 |
Minimum of Months | 350.543 | 13.908 | 0.000 | 0.000 | 17.621 |
Maximum of Months | 744.000 | 71.009 | 189.208 | 3.713 | 71.009 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 379.692 | 10.528 | 137.107 | 1.679 | 12.207 |
February | 440.571 | 14.324 | 82.523 | 1.452 | 15.776 |
March | 578.796 | 20.509 | 79.375 | 1.237 | 21.746 |
April | 692.854 | 29.018 | 3.500 | 0.009 | 29.027 |
May | 744.000 | 42.667 | 0.000 | 0.000 | 42.667 |
June | 720.000 | 48.144 | 0.000 | 0.000 | 48.144 |
July | 744.000 | 51.479 | 0.000 | 0.000 | 51.479 |
August | 744.000 | 49.736 | 0.000 | 0.000 | 49.736 |
September | 720.000 | 46.696 | 0.000 | 0.000 | 46.696 |
October | 744.000 | 40.508 | 0.000 | 0.000 | 40.508 |
November | 616.029 | 26.259 | 34.000 | 0.467 | 26.726 |
December | 436.557 | 14.191 | 107.458 | 1.804 | 15.995 |
Annual Sum or Average | 7560.499 | 394.059 | 443.963 | 6.647 | 400.706 |
Minimum of Months | 379.692 | 10.528 | 0.000 | 0.000 | 12.207 |
Maximum of Months | 744.000 | 51.479 | 137.107 | 1.804 | 51.479 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 363.999 | 12.515 | 166.812 | 2.820 | 15.335 |
February | 433.684 | 17.308 | 105.946 | 2.413 | 19.721 |
March | 564.665 | 24.997 | 79.530 | 1.707 | 26.704 |
April | 672.951 | 36.838 | 7.875 | 0.068 | 36.906 |
May | 741.500 | 53.638 | 0.000 | 0.000 | 53.638 |
June | 720.000 | 60.722 | 0.000 | 0.000 | 60.722 |
July | 744.000 | 65.205 | 0.000 | 0.000 | 65.205 |
August | 744.000 | 61.945 | 0.000 | 0.000 | 61.945 |
September | 720.000 | 58.364 | 0.000 | 0.000 | 58.364 |
October | 744.000 | 49.863 | 0.000 | 0.000 | 49.863 |
November | 600.137 | 31.370 | 37.375 | 0.793 | 32.164 |
December | 404.547 | 16.009 | 136.437 | 2.969 | 18.979 |
Annual Sum or Average | 7453.484 | 488.774 | 533.976 | 10.771 | 499.545 |
Minimum of Months | 363.999 | 12.515 | 0.000 | 0.000 | 15.335 |
Maximum of Months | 744.000 | 65.205 | 166.812 | 2.969 | 65.205 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 57.11 | 0.00 | 0.00 |
February | 112.04 | 0.00 | 0.00 |
March | 78.63 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 27.16 | 0.00 | 0.00 |
December | 107.85 | 0.00 | 0.00 |
Annual Sum or Average | 31.52 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.04 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 143.93 | 0.00 | 0.00 |
February | 156.02 | 0.00 | 0.00 |
March | 132.11 | 0.00 | 0.00 |
April | 2.06 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 53.14 | 0.00 | 0.00 |
December | 156.94 | 0.00 | 0.00 |
Annual Sum or Average | 53.28 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.94 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 311.68 | 0.00 | 0.00 |
February | 293.91 | 0.00 | 0.00 |
March | 200.06 | 0.00 | 0.00 |
April | 12.32 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 98.79 | 0.00 | 0.00 |
December | 301.13 | 0.00 | 0.00 |
Annual Sum or Average | 100.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 311.68 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 455.29 | 0.00 | 0.00 |
February | 384.25 | 0.00 | 0.00 |
March | 309.81 | 0.00 | 0.00 |
April | 13.08 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 128.40 | 0.00 | 0.00 |
December | 406.61 | 0.00 | 0.00 |
Annual Sum or Average | 140.62 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.29 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 236.35 | 0.00 | 0.00 |
February | 215.76 | 0.00 | 0.00 |
March | 179.12 | 0.00 | 0.00 |
April | 2.36 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 67.97 | 0.00 | 0.00 |
December | 239.56 | 0.00 | 0.00 |
Annual Sum or Average | 77.96 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 383.63 | 0.00 | 0.00 |
February | 344.76 | 0.00 | 0.00 |
March | 225.23 | 0.00 | 0.00 |
April | 12.41 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 108.87 | 0.00 | 0.00 |
December | 382.40 | 0.00 | 0.00 |
Annual Sum or Average | 120.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.63 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 200.10 | 0.00 | 0.00 |
February | 195.12 | 0.00 | 0.00 |
March | 164.34 | 0.00 | 0.00 |
April | 3.23 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 65.46 | 0.00 | 0.00 |
December | 203.70 | 0.00 | 0.00 |
Annual Sum or Average | 68.87 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 203.70 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 56.91 | 0.00 | 0.00 |
February | 76.63 | 0.00 | 0.00 |
March | 56.24 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 21.12 | 0.00 | 0.00 |
December | 78.47 | 0.00 | 0.00 |
Annual Sum or Average | 23.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.47 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 181.91 | 0.00 | 0.00 |
February | 180.12 | 0.00 | 0.00 |
March | 119.16 | 0.00 | 0.00 |
April | 4.12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 58.32 | 0.00 | 0.00 |
December | 194.36 | 0.00 | 0.00 |
Annual Sum or Average | 61.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 194.36 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 291.82 | 0.00 | 0.00 |
February | 250.13 | 0.00 | 0.00 |
March | 206.32 | 0.00 | 0.00 |
April | 4.01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 82.24 | 0.00 | 0.00 |
December | 280.20 | 0.00 | 0.00 |
Annual Sum or Average | 92.38 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 291.82 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 113.09 | 0.00 | 0.00 |
February | 115.54 | 0.00 | 0.00 |
March | 86.48 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 29.64 | 0.00 | 0.00 |
December | 135.35 | 0.00 | 0.00 |
Annual Sum or Average | 39.75 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 135.35 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 231.65 | 0.00 | 0.00 |
February | 220.93 | 0.00 | 0.00 |
March | 133.98 | 0.00 | 0.00 |
April | 4.17 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 65.91 | 0.00 | 0.00 |
December | 256.48 | 0.00 | 0.00 |
Annual Sum or Average | 75.55 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 256.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 363.82 | 0.00 | 0.00 |
February | 327.95 | 0.00 | 0.00 |
March | 274.10 | 0.00 | 0.00 |
April | 10.56 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 112.32 | 0.00 | 0.00 |
December | 334.70 | 0.00 | 0.00 |
Annual Sum or Average | 117.86 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.82 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 158.23 | 0.00 | 0.00 |
February | 163.96 | 0.00 | 0.00 |
March | 136.75 | 0.00 | 0.00 |
April | 1.30 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 53.53 | 0.00 | 0.00 |
December | 171.61 | 0.00 | 0.00 |
Annual Sum or Average | 56.71 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.61 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 317.08 | 0.00 | 0.00 |
February | 297.68 | 0.00 | 0.00 |
March | 201.39 | 0.00 | 0.00 |
April | 9.78 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 99.13 | 0.00 | 0.00 |
December | 312.54 | 0.00 | 0.00 |
Annual Sum or Average | 102.37 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.08 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 456.48 | 0.00 | 0.00 |
February | 383.52 | 0.00 | 0.00 |
March | 304.44 | 0.00 | 0.00 |
April | 10.81 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 128.64 | 0.00 | 0.00 |
December | 413.64 | 0.00 | 0.00 |
Annual Sum or Average | 140.64 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 456.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 231.62 | 0.00 | 0.00 |
February | 211.50 | 0.00 | 0.00 |
March | 164.83 | 0.00 | 0.00 |
April | 1.33 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 66.59 | 0.00 | 0.00 |
December | 240.51 | 0.00 | 0.00 |
Annual Sum or Average | 75.91 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.51 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 375.65 | 0.00 | 0.00 |
February | 343.10 | 0.00 | 0.00 |
March | 219.04 | 0.00 | 0.00 |
April | 9.83 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 108.94 | 0.00 | 0.00 |
December | 384.27 | 0.00 | 0.00 |
Annual Sum or Average | 119.23 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.27 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.29 |
February | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.00 | 0.40 |
April | 0.00 | 0.00 | 0.51 |
May | 0.00 | 0.00 | 0.65 |
June | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.00 | 0.73 |
October | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.75 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.14 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.19 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.21 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.00 | 0.20 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.00 | 0.42 |
November | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.22 |
December | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.19 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.24 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.21 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.23 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.00 | 0.60 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.10 |
February | 0.00 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.18 |
April | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.10 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.00 | 0.30 |
December | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.60 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.24 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.68 |
August | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.00 | 0.65 |
October | 0.00 | 0.00 | 0.56 |
November | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.68 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.22 |
March | 0.00 | 0.00 | 0.25 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.24 |
March | 0.00 | 0.00 | 0.28 |
April | 0.00 | 0.00 | 0.41 |
May | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.00 | 0.57 |
November | 0.00 | 0.00 | 0.40 |
December | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.00 | 0.70 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.20 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.39 |
May | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.68 |
August | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.00 | 0.63 |
October | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.13 |
Maximum of Months | 0.00 | 0.00 | 0.68 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.00 | 0.30 |
December | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.20 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.00 | 0.65 |
October | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.13 |
Maximum of Months | 0.00 | 0.00 | 0.70 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |
Minimum of Months | 0.00 | 0.00 | 539.26 | 401.49 |
Maximum of Months | 0.00 | 0.00 | 783.21 | 583.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 783.21 | 583.12 |
February | 0.00 | 0.00 | 773.50 | 520.16 |
March | 0.00 | 0.00 | 733.26 | 545.93 |
April | 0.00 | 0.00 | 672.22 | 484.35 |
May | 0.00 | 0.00 | 607.72 | 452.47 |
June | 0.00 | 0.00 | 558.04 | 402.07 |
July | 0.00 | 0.00 | 539.26 | 401.49 |
August | 0.00 | 0.00 | 548.30 | 408.23 |
September | 0.00 | 0.00 | 593.39 | 427.54 |
October | 0.00 | 0.00 | 651.68 | 485.20 |
November | 0.00 | 0.00 | 715.93 | 515.83 |
December | 0.00 | 0.00 | 766.42 | 570.62 |
Annual Sum or Average | 0.00 | 0.00 | 661.29 | 5797.01 |