Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
Tabular Output Report in Format: HTML
Building: MF+CZ1AT+USA_HI_Honolulu.Intl.AP.911820+oilfurnace+heatedbsmt+IECC_2009
Environment: ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2019-02-14 08:32:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 794380.47 | 20.37 | 27.02 |
Net Site Energy | 794380.47 | 20.37 | 27.02 |
Total Source Energy | 2087450.61 | 53.52 | 70.99 |
Net Source Energy | 2087450.61 | 53.52 | 70.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 102.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 192888.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34197.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 205539.86 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 588738.45 | 205642.02 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 102.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 192888.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 34197.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 205539.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 7.72 | 6.99 | 0.00 | 0.00 | 0.00 | 14.27 |
Other | 10.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 20.02 | 6.99 | 0.00 | 0.00 | 0.00 | 14.27 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 5.82 | 5.27 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 15.09 | 5.27 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 588738.446 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 588738.446 | 100.00 |
Total On-Site and Utility Electric Sources | 588738.446 | 100.00 |
Total Electricity End Uses | 588738.446 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 12.00 |
Time Setpoint Not Met During Occupied Cooling | 192.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2553.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32 |
RunPeriod | ANNUAL |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [ft] | 6.56 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.5522 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 02-SEP-18:15 | 12-FEB-07:15 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 27.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 111.94 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 126.38 | 139.90 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 27.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 48.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 110.74 | 0.00 | 0.00 | 0.00 |
Cooling | 610877.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 108303.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 222805.21 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1864534.66 | 222915.95 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 63.41 | 7.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 63.41 | 7.58 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 61.16 | 0.00 | 61.16 | Wetbulb [F] | 374.03 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 89.96 | 12.78 | 73.94 | Wetbulb [F] | 1318.96 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 1.027 | 0.258 | 0.881 | ||||||||||||
North Total or Average | 531.68 | 1.027 | 0.258 | 0.881 | ||||||||||||
Non-North Total or Average | 1595.05 | 1.027 | 0.258 | 0.881 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 392878.92 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 25423.75 | 19520.94 | 5902.81 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8640.19 | 5949.89 | 2690.30 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11919.56 | 8528.17 | 3391.39 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15342.70 | 11233.88 | 4108.82 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8556.15 | 5905.35 | 2650.80 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11833.79 | 8476.06 | 3357.73 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14487.83 | 10735.43 | 3752.40 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8040.44 | 5610.12 | 2430.32 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10906.85 | 7869.34 | 3037.51 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14361.63 | 10631.82 | 3729.81 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8023.24 | 5604.67 | 2418.57 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10852.44 | 7826.53 | 3025.91 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16811.95 | 12430.44 | 4381.52 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10386.85 | 7313.09 | 3073.75 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12441.77 | 8838.57 | 3603.20 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16823.76 | 12440.18 | 4383.58 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10418.89 | 7351.31 | 3067.58 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12373.31 | 8790.95 | 3582.36 | 0.71 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 7042.03 | 5158.60 | 1883.43 | 0.73 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.0 | 3.32 | 11.32 | 11.99 | 11.58 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.47 | 11.85 | 12.58 | 12.46 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | 3.42 | 11.66 | 12.37 | 12.15 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.39 | 11.55 | 12.25 | 11.96 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.47 | 11.84 | 12.56 | 12.44 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.0 | 3.42 | 11.66 | 12.37 | 12.14 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.37 | 11.49 | 12.18 | 11.87 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.45 | 11.79 | 12.51 | 12.36 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.41 | 11.62 | 12.33 | 12.08 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.37 | 11.50 | 12.19 | 11.88 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.45 | 11.78 | 12.50 | 12.35 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.41 | 11.63 | 12.33 | 12.09 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.37 | 11.50 | 12.20 | 11.89 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.44 | 11.74 | 12.46 | 12.28 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.43 | 11.70 | 12.41 | 12.21 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.37 | 11.50 | 12.19 | 11.89 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.44 | 11.73 | 12.45 | 12.26 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.43 | 11.70 | 12.41 | 12.21 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.6 | 3.38 | 11.55 | 12.25 | 11.96 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 47819.08 | 52150.10 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 12820.25 | 13757.76 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19252.43 | 20805.53 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 26046.41 | 28245.49 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 12774.19 | 13707.71 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 19168.79 | 20713.96 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 25328.81 | 27457.93 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 12371.41 | 13265.71 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18024.66 | 19461.15 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 25056.88 | 27162.19 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 12382.25 | 13277.71 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 17917.75 | 19344.06 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29156.74 | 31654.83 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 16190.70 | 17451.29 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19723.40 | 21323.77 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 29182.42 | 31683.26 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 16325.47 | 17598.92 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 19623.37 | 21214.20 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 12254.84 | 13154.69 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 873.69 | 329.55 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 227.11 | 85.66 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 345.96 | 130.49 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 471.49 | 177.84 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 226.26 | 85.34 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 344.41 | 129.91 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 458.22 | 172.84 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 218.82 | 82.54 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 323.27 | 121.94 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 453.20 | 170.94 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 219.02 | 82.61 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 321.30 | 121.19 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 528.96 | 199.52 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 289.39 | 109.15 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 354.66 | 133.78 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 529.43 | 199.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 291.88 | 110.09 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 352.82 | 133.08 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 216.65 | 81.72 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 39.507000 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 20518.88 | 20518.88 | 17.09 | 873.692 | 873.692 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00874 | 87.53 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5333.98 | 5333.98 | 4.44 | 227.110 | 227.110 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.01014 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8125.31 | 8125.31 | 6.77 | 345.959 | 345.959 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00952 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11073.17 | 11073.17 | 9.22 | 471.486 | 471.486 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00926 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5314.08 | 5314.08 | 4.43 | 226.261 | 226.261 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.01018 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8089.07 | 8089.07 | 6.74 | 344.413 | 344.413 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 74.98 | 74.98 | 0.00953 | 86.54 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10762.12 | 10762.12 | 8.96 | 458.223 | 458.223 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00899 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5139.41 | 5139.41 | 4.28 | 218.817 | 218.817 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00976 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7592.75 | 7592.75 | 6.32 | 323.272 | 323.272 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00923 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10644.17 | 10644.17 | 8.87 | 453.201 | 453.201 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00900 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5144.13 | 5144.13 | 4.28 | 219.018 | 219.018 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00978 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7546.36 | 7546.36 | 6.29 | 321.297 | 321.297 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00924 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8284.86 | 8284.86 | 6.90 | 352.816 | 352.816 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 74.98 | 74.98 | 0.00949 | 89.58 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8327.96 | 8327.96 | 6.94 | 354.664 | 354.664 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 74.98 | 74.98 | 0.00949 | 89.77 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12422.93 | 12422.93 | 10.35 | 528.960 | 528.960 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00915 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6855.07 | 6855.07 | 5.71 | 291.877 | 291.877 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00980 | 85.93 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6796.56 | 6796.56 | 5.66 | 289.387 | 289.387 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00980 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12434.09 | 12434.09 | 10.36 | 529.435 | 529.435 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00915 | 87.21 | 0.01435 | 44.995 | 0.00 |
HEATEDBSMT | 5089.16 | 5089.16 | 0.65 | 216.654 | 216.654 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 74.98 | 74.98 | 0.00800 | 88.68 | 0.01435 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 61.16 | 0.01152 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 841.18 | 841.18 | 0.70 | 15.315 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01145 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1714.49 | 1714.49 | 1.43 | 31.216 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01090 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1721.79 | 1721.79 | 1.43 | 31.349 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01090 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 923.98 | 923.98 | 0.77 | 16.823 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01139 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1718.86 | 1718.86 | 1.43 | 31.296 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01090 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1361.55 | 1361.55 | 1.13 | 24.790 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01104 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 761.42 | 761.42 | 0.63 | 13.863 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01156 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1617.03 | 1617.03 | 1.35 | 29.441 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01087 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1620.01 | 1620.01 | 1.35 | 29.496 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01087 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 786.51 | 786.51 | 0.66 | 14.320 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01153 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1616.27 | 1616.27 | 1.35 | 29.428 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01087 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2287.11 | 2287.11 | 1.91 | 41.642 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2289.84 | 2289.84 | 1.91 | 41.692 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2240.93 | 2240.93 | 1.87 | 40.801 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01065 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1429.10 | 1429.10 | 1.19 | 26.020 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01105 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1419.23 | 1419.23 | 1.18 | 25.840 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01106 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2290.36 | 2290.36 | 1.91 | 41.702 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
HEATEDBSMT | 1357.24 | 1357.24 | 0.17 | 24.709 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 06:45:00 | 72.00 | 72.00 | 0.00811 | 61.16 | 0.01152 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 | 873.69 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 | 227.11 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 | 345.96 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 | 471.49 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 | 226.26 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 | 344.41 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 | 458.22 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 | 218.82 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 | 323.27 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 | 453.20 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 | 219.02 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 | 321.30 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.96 | 528.96 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.39 | 289.39 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.66 | 354.66 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.43 | 529.43 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.88 | 291.88 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.82 | 352.82 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 216.65 | 216.65 | 44.99 | 44.99 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4517.25 | 1048.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8062.75 | 1715.50 | 1589.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8120.00 | 2038.25 | 1794.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8003.50 | 2664.25 | 2361.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7887.00 | 1938.75 | 1784.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8047.50 | 2127.25 | 1876.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8085.00 | 1608.00 | 1431.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7989.25 | 710.50 | 646.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8076.75 | 1213.00 | 1051.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7998.50 | 1764.25 | 1556.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7837.75 | 887.25 | 807.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8010.00 | 1274.50 | 1108.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8097.75 | 1773.50 | 1525.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8130.50 | 1727.50 | 1485.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8105.00 | 2292.75 | 2015.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8038.25 | 1739.00 | 1569.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8118.00 | 1595.50 | 1453.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8054.00 | 2406.25 | 2099.25 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 8265.50 | 3078.00 | 2553.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 122.00 | 0.00 | 122.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8.25 | 76.75 | 8.25 | 76.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6.00 | 5.25 | 6.00 | 5.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 90.75 | 0.00 | 90.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4.50 | 98.25 | 4.50 | 98.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5.25 | 5.75 | 5.25 | 5.75 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 4.25 | 9.75 | 4.25 | 9.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 4.50 | 59.75 | 4.50 | 59.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.50 | 0.00 | 0.50 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 16.25 | 0.00 | 16.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.75 | 0.00 | 0.75 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 12.00 | 192.00 | 12.00 | 192.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.244 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.078 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.078 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 10015.59 | 112.18 | 08-MAR-02:30 | 2611.68 | 03-SEP-16:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
ElectricityPurchased:Plant | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
Cogeneration:ElectricityPurchased | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
ElectricityNet:Plant | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
Cogeneration:ElectricityNet | 172427.21 | 7566.44 | 25-MAR-03:45 | 37014.24 | 02-SEP-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 66507.88 | 594.32 | 08-MAR-02:30 | 18387.62 | 03-SEP-16:15 |
General:Fans:Electricity | 10015.59 | 112.18 | 08-MAR-02:30 | 2611.68 | 03-SEP-16:15 |
Cooling:Electricity | 56492.29 | 374.09 | 12-FEB-07:00 | 15782.07 | 03-SEP-15:45 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2056.42 | 0.00 | 01-JAN-00:15 | 139803.30 | 12-FEB-07:15 |
Gas:Plant | 2056.42 | 0.00 | 01-JAN-00:15 | 139803.30 | 12-FEB-07:15 |
WaterSystems:Gas | 2055.40 | 0.00 | 01-JAN-00:15 | 112046.32 | 15-JAN-08:45 |
Water Heater:WaterSystems:Gas | 2055.40 | 0.00 | 01-JAN-00:15 | 112046.32 | 15-JAN-08:45 |
Heating:Gas | 1.02 | 0.00 | 01-JAN-00:15 | 33842.09 | 12-FEB-07:00 |
Boiler:Heating:Gas | 1.02 | 0.00 | 01-JAN-00:15 | 33842.09 | 12-FEB-07:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 12-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 86444.25 | 814.59 | 19-JUL-02:30 | 44780.95 | 12-FEB-07:15 |
PlantLoopHeatingDemand:Plant | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1518540.32 | 16020.52 | 08-MAR-02:45 | 399448.53 | 03-SEP-16:15 |
EnergyTransfer:Building | 587439.47 | 6938.85 | 08-MAR-02:45 | 167325.04 | 03-SEP-16:15 |
EnergyTransfer:Zone:HEATEDBSMT | 13515.13 | 0.00 | 01-JAN-00:15 | 5158.64 | 30-AUG-15:00 |
Heating:EnergyTransfer | 226.72 | 0.00 | 01-JAN-00:15 | 28190.03 | 12-FEB-07:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 39.29 | 0.00 | 01-JAN-00:15 | 1338.35 | 12-FEB-07:15 |
Cooling:EnergyTransfer | 587212.75 | 5427.51 | 12-FEB-07:00 | 167325.04 | 03-SEP-16:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 13475.84 | 0.00 | 01-JAN-00:15 | 5158.64 | 30-AUG-15:00 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 106346.03 | 5427.51 | 12-FEB-07:00 | 20209.97 | 11-OCT-14:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 106346.03 | 5427.51 | 12-FEB-07:00 | 20209.97 | 11-OCT-14:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23096.80 | 0.00 | 01-JAN-03:30 | 6450.35 | 07-JAN-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.63 | 0.00 | 01-JAN-00:15 | 788.74 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23095.17 | 0.00 | 01-JAN-03:30 | 6450.35 | 07-JAN-13:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 31189.12 | 0.00 | 01-JAN-02:00 | 9232.16 | 27-OCT-10:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 13.57 | 0.00 | 01-JAN-00:15 | 2544.15 | 12-FEB-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 31175.55 | 0.00 | 01-JAN-02:00 | 9232.16 | 27-OCT-10:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 25562.29 | 0.00 | 01-JAN-02:00 | 10778.96 | 03-SEP-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 20.75 | 0.00 | 01-JAN-00:15 | 2006.66 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 25541.54 | 0.00 | 01-JAN-02:00 | 10778.96 | 03-SEP-16:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19956.94 | 0.00 | 01-JAN-03:15 | 5647.71 | 03-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2.78 | 0.00 | 01-JAN-00:15 | 910.45 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19954.16 | 0.00 | 01-JAN-03:15 | 5647.71 | 03-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28061.52 | 0.00 | 01-JAN-02:00 | 9010.09 | 12-JUL-10:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15.73 | 0.00 | 01-JAN-00:15 | 2273.50 | 08-MAR-06:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28045.78 | 0.00 | 01-JAN-02:00 | 9010.09 | 12-JUL-10:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29087.48 | 0.00 | 01-JAN-03:00 | 10748.25 | 03-SEP-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7.33 | 0.00 | 01-JAN-00:15 | 1371.84 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29080.14 | 0.00 | 01-JAN-03:00 | 10748.25 | 03-SEP-16:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23830.22 | 0.00 | 05-JAN-06:00 | 6198.61 | 29-JAN-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.21 | 0.00 | 01-JAN-00:15 | 336.86 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23830.01 | 0.00 | 05-JAN-06:00 | 6198.61 | 29-JAN-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31696.10 | 0.00 | 01-JAN-03:00 | 8674.75 | 27-OCT-13:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5.77 | 0.00 | 01-JAN-00:15 | 2454.31 | 12-FEB-06:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31690.33 | 0.00 | 01-JAN-03:00 | 8674.75 | 27-OCT-13:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26107.76 | 0.00 | 01-JAN-02:45 | 10224.00 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10.49 | 0.00 | 01-JAN-00:15 | 1876.03 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26097.27 | 0.00 | 01-JAN-02:45 | 10224.00 | 05-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20709.08 | 0.00 | 05-JAN-05:00 | 5317.95 | 03-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.51 | 0.00 | 01-JAN-00:15 | 362.98 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20708.57 | 0.00 | 05-JAN-05:00 | 5317.95 | 03-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28636.12 | 0.00 | 01-JAN-02:45 | 8464.78 | 08-JUL-10:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6.73 | 0.00 | 01-JAN-00:15 | 2533.48 | 12-FEB-06:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28629.39 | 0.00 | 01-JAN-02:45 | 8464.78 | 08-JUL-10:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32203.58 | 0.00 | 01-JAN-02:30 | 9156.61 | 12-JUL-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 21.14 | 0.00 | 01-JAN-00:15 | 2601.39 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32182.43 | 0.00 | 01-JAN-02:30 | 9156.61 | 12-JUL-10:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34365.10 | 0.00 | 01-JAN-02:30 | 9630.63 | 27-OCT-13:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 19.66 | 0.00 | 01-JAN-00:15 | 2576.41 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34345.44 | 0.00 | 01-JAN-02:30 | 9630.63 | 27-OCT-13:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31932.90 | 0.00 | 01-JAN-02:30 | 12468.85 | 03-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24.09 | 0.00 | 01-JAN-00:15 | 2863.53 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31908.81 | 0.00 | 01-JAN-02:30 | 12468.85 | 03-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24531.41 | 0.00 | 01-JAN-04:00 | 7219.23 | 03-SEP-17:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5.39 | 0.00 | 01-JAN-00:15 | 1245.54 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24526.02 | 0.00 | 01-JAN-04:00 | 7219.23 | 03-SEP-17:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26753.96 | 0.00 | 01-JAN-04:15 | 7796.63 | 13-DEC-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4.25 | 0.00 | 01-JAN-00:15 | 1201.44 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26749.72 | 0.00 | 01-JAN-04:15 | 7796.63 | 13-DEC-16:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29857.95 | 0.00 | 01-JAN-02:30 | 12368.16 | 03-SEP-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 27.40 | 0.00 | 01-JAN-00:15 | 2514.32 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29830.54 | 0.00 | 01-JAN-02:30 | 12368.16 | 03-SEP-16:15 |
EnergyTransfer:Plant | 86374.74 | 814.59 | 19-JUL-02:30 | 43485.49 | 12-FEB-07:00 |
WaterSystems:EnergyTransfer | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
EnergyTransfer:HVAC | 844726.10 | 7993.22 | 12-FEB-01:15 | 222820.79 | 03-SEP-16:15 |
HeatingCoils:EnergyTransfer | 151.23 | 0.00 | 01-JAN-00:15 | 27456.69 | 12-FEB-07:00 |
PlantLoopHeatingDemand:HVAC | 151.23 | 0.00 | 01-JAN-00:15 | 27456.69 | 12-FEB-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 151.23 | 0.00 | 01-JAN-00:15 | 27456.69 | 12-FEB-07:00 |
CoolingCoils:EnergyTransfer | 844574.87 | 6550.37 | 12-FEB-07:00 | 222820.79 | 03-SEP-16:15 |
Boilers:EnergyTransfer | 81.73 | 0.00 | 01-JAN-00:15 | 27073.67 | 12-FEB-07:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8856.25 | 0.000 | 0.000 | 2874.140 | 2771.241 | 10464.601 | 12596.054 | 0.000 | 2998.740 | 78125.190 | 0.000 | -2442.76 | 0.000 | -1041.22 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1.626 | -1923.31 | 0.000 | 0.000 | 2876.597 | 2771.241 | 10464.601 | 5414.470 | 0.000 | 2793.436 | 735.558 | 0.000 | -988.69 | 0.000 | -973.66 | -0.02 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 13.566 | -2596.21 | 0.000 | 0.000 | 2883.937 | 2771.241 | 10464.601 | 15146.260 | 0.000 | 2990.330 | 229.970 | 0.000 | -2339.09 | 0.000 | -985.41 | -0.01 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 20.747 | -2127.02 | 0.000 | 0.000 | 2885.581 | 2771.241 | 10464.601 | 10212.433 | 0.000 | 2998.454 | 0.056 | 0.000 | -2393.30 | 0.000 | -972.69 | -445.73 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 2.778 | -1661.74 | 0.000 | 0.000 | 2877.686 | 2771.241 | 10464.601 | 2938.416 | 0.000 | 2805.128 | 46.661 | 0.000 | -983.17 | 0.000 | -969.13 | -0.04 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 15.732 | -2335.58 | 0.000 | 0.000 | 2884.559 | 2771.241 | 10464.601 | 12745.157 | 0.000 | 2997.096 | 0.426 | 0.000 | -2309.85 | 0.000 | -983.45 | -539.40 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 7.335 | -2421.71 | 0.000 | 0.000 | 2879.539 | 2771.241 | 10464.601 | 12332.802 | 0.000 | 2077.756 | 1872.675 | 0.000 | -2540.44 | 0.000 | -785.58 | -0.02 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.212 | -1984.51 | 0.000 | 0.000 | 2874.582 | 2771.241 | 10464.601 | 5297.496 | 0.000 | 1880.663 | 2327.473 | 0.000 | -1031.32 | 0.000 | -754.90 | -0.06 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5.772 | -2639.09 | 0.000 | 0.000 | 2879.160 | 2771.241 | 10464.601 | 14753.018 | 0.000 | 2071.108 | 1985.756 | 0.000 | -2453.47 | 0.000 | -786.95 | -0.08 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 10.490 | -2173.31 | 0.000 | 0.000 | 2880.492 | 2771.241 | 10464.601 | 10001.346 | 0.000 | 2078.201 | 1190.675 | 0.000 | -2520.05 | 0.000 | -779.87 | -0.09 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.513 | -1724.57 | 0.000 | 0.000 | 2875.155 | 2771.241 | 10464.601 | 2881.289 | 0.000 | 1886.053 | 1608.907 | 0.000 | -1025.60 | 0.000 | -753.50 | -0.02 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 6.726 | -2384.19 | 0.000 | 0.000 | 2879.811 | 2771.241 | 10464.601 | 12411.288 | 0.000 | 2077.185 | 1224.301 | 0.000 | -2420.16 | 0.000 | -785.64 | -0.09 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 21.144 | -2680.08 | 0.000 | 0.000 | 2884.223 | 2771.241 | 10464.601 | 12109.745 | 0.000 | 2963.129 | 4442.850 | 0.000 | -2473.20 | 0.000 | -1001.30 | -0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 19.657 | -2860.21 | 0.000 | 0.000 | 2883.683 | 2771.241 | 10464.601 | 14464.538 | 0.000 | 2957.735 | 4280.226 | 0.000 | -2492.92 | 0.000 | -1003.34 | -0.14 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 24.087 | -2657.27 | 0.000 | 0.000 | 2884.660 | 2771.241 | 10464.601 | 12096.868 | 0.000 | 2964.499 | 4267.053 | 0.000 | -2568.86 | 0.000 | -995.59 | -0.07 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 5.391 | -2042.47 | 0.000 | 0.000 | 2877.975 | 2771.241 | 10464.601 | 2790.679 | 0.000 | 2773.605 | 4874.924 | 0.000 | -1049.85 | 0.000 | -982.52 | -0.06 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4.246 | -2227.65 | 0.000 | 0.000 | 2877.446 | 2771.241 | 10464.601 | 5196.791 | 0.000 | 2771.779 | 4700.384 | 0.000 | -1050.44 | 0.000 | -986.34 | -0.04 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 27.405 | -2484.20 | 0.000 | 0.000 | 2885.478 | 2771.241 | 10464.601 | 9752.149 | 0.000 | 2965.510 | 4511.132 | 0.000 | -2558.57 | 0.000 | -988.62 | -0.06 |
HEATEDBSMT | 0.000 | 0.000 | 39.294 | -1122.24 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13436.542 | 0.000 | 0.000 | 0.000 | 0.000 | -0.03 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5573.221 | 54327.067 | 0.000 | 0.000 | 0.000 | -59900.29 | -0.50 |
Total Facility | 0.000 | 0.000 | 226.722 | -48901.60 | 0.000 | 0.000 | 51844.705 | 49882.340 | 188362.826 | 173140.800 | 0.000 | 52623.628 | 184187.827 | 0.000 | -35641.75 | 0.000 | -76430.02 | -986.45 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11-OCT-14:25 | 0.00 | 0.00 | 0.00 | -1.7 | 0.00 | 0.00 | 115.18 | 116.28 | 1091.85 | 7978.00 | 0.00 | 1308.70 | 9634.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-JAN-13:30 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.18 | 116.28 | 1109.73 | 3847.63 | 0.00 | 677.68 | 585.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-OCT-10:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 112.58 | 116.28 | 1089.80 | 7944.51 | 0.00 | 856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -878.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 03-SEP-16:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6939.81 | 0.00 | 1796.83 | 96.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 03-SEP-16:34 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 140.40 | 434.11 | 1371.36 | 1005.19 | 0.00 | 1611.18 | 1093.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 08-JUL-10:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 114.96 | 116.28 | 1121.12 | 5845.79 | 0.00 | 1192.84 | 627.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 03-SEP-16:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6912.25 | 0.00 | 1194.98 | 695.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.16 | 116.28 | 1113.97 | 3226.37 | 0.00 | 285.89 | 1340.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27-OCT-12:53 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 113.88 | 116.28 | 1090.63 | 4433.81 | 0.00 | 775.57 | 2148.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 05-SEP-17:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.35 | 604.65 | 1664.02 | 6332.96 | 0.00 | 1033.61 | 325.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 03-SEP-17:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 263.34 | 604.65 | 1685.13 | 760.60 | 0.00 | 951.69 | 1053.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 08-JUL-10:45 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 114.81 | 116.28 | 1121.12 | 5320.17 | 0.00 | 841.43 | 960.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-JUL-09:49 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.17 | 116.28 | 1096.02 | 6306.39 | 0.00 | 1153.54 | 372.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-OCT-13:15 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.18 | 116.28 | 1084.63 | 4326.07 | 0.00 | 1128.69 | 2860.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 03-SEP-16:19 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.14 | 434.11 | 1371.36 | 6239.35 | 0.00 | 1755.94 | 2534.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 03-SEP-16:34 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 139.18 | 434.11 | 1371.36 | 951.86 | 0.00 | 1576.30 | 2753.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 13-DEC-16:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 139.97 | 434.11 | 1350.56 | 1463.92 | 0.00 | 785.87 | 3643.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 03-SEP-16:05 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6665.55 | 0.00 | 1789.72 | 1967.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 30-AUG-15:00 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5158.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-SEP-16:10 | 0.00 | 0.00 | 0.00 | -13.9 | 0.00 | 0.00 | 2508.36 | 7813.98 | 24684.52 | 65095.68 | 0.00 | 27478.44 | 62395.31 | 0.00 | 0.00 | 0.00 | -22629.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 788.74 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -805.9 | 0.00 | -1378.0 | -650.9 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-FEB-04:00 | 0.00 | 0.00 | 6680.18 | 0.00 | 0.00 | 0.00 | 545.87 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1688.5 | 0.00 | -1151.9 | -5296.2 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-FEB-04:30 | 0.00 | 0.00 | 2238.31 | 0.00 | 0.00 | 0.00 | 526.31 | 186.05 | 833.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1716.2 | 0.00 | -1149.0 | -919.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 910.44 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -803.2 | 0.00 | -1378.0 | -775.3 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-FEB-03:35 | 0.00 | 0.00 | 6066.49 | 0.00 | 0.00 | 0.00 | 545.64 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1691.3 | 0.00 | -1163.1 | -4668.3 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1371.85 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1985.1 | 0.00 | -1090.3 | -342.6 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 336.86 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -825.9 | 0.00 | -1011.9 | -545.1 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12-FEB-06:35 | 0.00 | 0.00 | 7362.93 | 0.00 | 0.00 | 0.00 | 549.65 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1804.6 | 0.00 | -1026.1 | -6601.7 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1876.04 | 0.00 | 0.00 | 0.00 | 532.69 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1951.3 | 0.00 | -1087.7 | -889.5 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 362.99 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.3 | 0.00 | -1011.9 | -566.9 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-FEB-06:25 | 0.00 | 0.00 | 7176.16 | 0.00 | 0.00 | 0.00 | 548.55 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1749.1 | 0.00 | -975.4 | -6519.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-FEB-03:40 | 0.00 | 0.00 | 6235.56 | 0.00 | 0.00 | 0.00 | 544.65 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1726.0 | 0.00 | -1169.8 | -4795.0 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12-FEB-03:50 | 0.00 | 0.00 | 6406.76 | 0.00 | 0.00 | 0.00 | 545.92 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1709.5 | 0.00 | -1160.0 | -4993.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12-FEB-06:40 | 0.00 | 0.00 | 5451.44 | 0.00 | 0.00 | 0.00 | 530.66 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1862.1 | 0.00 | -1365.1 | -4274.7 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1245.53 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -814.5 | 0.00 | -1384.0 | -1093.1 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1201.44 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -805.4 | 0.00 | -1384.0 | -1058.1 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 2514.31 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1942.2 | 0.00 | -1462.6 | -1155.6 |
HEATEDBSMT | 08-FEB-06:08 | 0.00 | 0.00 | 1885.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1885.6 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-06:35 | -5654.8 | 0.47 | 29314.73 | -0.5 | 0.00 | 0.00 | 9443.97 | 7813.98 | 19542.30 | 0.00 | 0.00 | 2451.07 | 0.00 | 0.00 | -27321.9 | 0.00 | -22485.7 | -13103.7 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 873.692 | 2.00 | 2.00 | 1.00 | 44.9950 | 873.692 | 0.051 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.110 | 2.00 | 2.00 | 1.00 | 44.9950 | 227.110 | 0.198 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 345.959 | 2.00 | 2.00 | 1.00 | 44.9950 | 345.959 | 0.130 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 471.486 | 2.00 | 2.00 | 1.00 | 44.9950 | 471.486 | 0.095 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 226.261 | 2.00 | 2.00 | 1.00 | 44.9950 | 226.261 | 0.199 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 344.413 | 2.00 | 2.00 | 1.00 | 44.9950 | 344.413 | 0.131 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 458.223 | 2.00 | 2.00 | 1.00 | 44.9950 | 458.223 | 0.098 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 218.817 | 2.00 | 2.00 | 1.00 | 44.9950 | 218.817 | 0.206 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 323.272 | 2.00 | 2.00 | 1.00 | 44.9950 | 323.272 | 0.139 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 453.201 | 2.00 | 2.00 | 1.00 | 44.9950 | 453.201 | 0.099 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 219.018 | 2.00 | 2.00 | 1.00 | 44.9950 | 219.018 | 0.205 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 321.297 | 2.00 | 2.00 | 1.00 | 44.9950 | 321.297 | 0.140 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.960 | 2.00 | 2.00 | 1.00 | 44.9950 | 528.960 | 0.085 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.387 | 2.00 | 2.00 | 1.00 | 44.9950 | 289.387 | 0.155 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.664 | 2.00 | 2.00 | 1.00 | 44.9950 | 354.664 | 0.127 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.435 | 2.00 | 2.00 | 1.00 | 44.9950 | 529.435 | 0.085 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.877 | 2.00 | 2.00 | 1.00 | 44.9950 | 291.877 | 0.154 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.816 | 2.00 | 2.00 | 1.00 | 44.9950 | 352.816 | 0.128 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 216.654 | 0.00 | 0.00 | 1.00 | 44.9950 | 216.654 | 0.208 | 1.000 | 44.9950 | 0.21 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 0.00 | 0.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 873.692 | 873.6915 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.110 | 227.1102 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 345.959 | 345.9587 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 471.486 | 471.4865 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 226.261 | 226.2611 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 344.413 | 344.4134 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 458.223 | 458.2230 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 218.817 | 218.8172 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 323.272 | 323.2724 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 453.201 | 453.2012 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 219.018 | 219.0175 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 321.297 | 321.2971 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.816 | 352.8162 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.664 | 354.6644 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.960 | 528.9596 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.877 | 291.8766 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.387 | 289.3866 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.435 | 529.4346 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 216.654 | 216.6539 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 | 873.692 | 873.69 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 | 227.110 | 227.11 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 | 345.959 | 345.96 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 | 471.486 | 471.49 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 | 226.261 | 226.26 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 | 344.413 | 344.41 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 | 458.223 | 458.22 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 | 218.817 | 218.82 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 | 323.272 | 323.27 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 | 453.201 | 453.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 | 219.018 | 219.02 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 | 321.297 | 321.30 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.96 | 528.960 | 528.96 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.39 | 289.387 | 289.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.66 | 354.664 | 354.66 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.43 | 529.435 | 529.43 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.88 | 291.877 | 291.88 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.82 | 352.816 | 352.82 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 216.65 | 216.654 | 216.65 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 12.00 |
Number of hours cooling loads not met | 192.00 |
Number of hours not met | 204.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1.02 | 27938.88 | 0.00 | 0.00 |
Space Cooling | 56492.29 | 14097.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 10015.59 | 2402.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2055.40 | 111864.43 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15497.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 172427.21 | 2056.42 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 588738.45 |
Natural Gas | 0.00 | 205642.02 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 794380.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 1.45 |
Fans-Interior | 0.26 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 4.42 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 1.54 |
Miscellaneous | -0.0 |
Subtotal | 1.54 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.28 |
Space Heating | 0.01 |
Space Cooling | 24.28 |
Fans-Interior | 4.30 |
Service Water Heating | 25.87 |
Receptacle Equipment | 37.95 |
Miscellaneous | 1.29 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 216.65 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 352.82 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 354.66 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 528.96 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 291.88 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 289.39 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 529.43 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.96 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.66 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.43 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.88 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.82 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 216.65 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 | 2.12 | 0.767823 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 | 0.720016 | 0.688630 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 | 0.993296 | 0.715477 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 | 1.28 | 0.732197 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 | 0.713013 | 0.690188 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 | 0.986149 | 0.716259 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 | 1.21 | 0.740996 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 | 0.670036 | 0.697738 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 | 0.908904 | 0.721504 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 | 1.20 | 0.740293 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 | 0.668604 | 0.698554 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 | 0.904370 | 0.721177 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 528.96 | 1.40 | 0.739381 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 289.39 | 0.865570 | 0.704072 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 354.66 | 1.04 | 0.710395 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 529.43 | 1.40 | 0.739441 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 291.88 | 0.868241 | 0.705575 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 352.82 | 1.03 | 0.710477 |
DX COOLING COIL_UNITHEATEDBSMT | 216.65 | 0.586835 | 0.732545 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 | 873.69 | 873.69 | 2.12 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 | 227.11 | 227.11 | 0.720016 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 | 345.96 | 345.96 | 0.993296 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 | 471.49 | 471.49 | 1.28 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 | 226.26 | 226.26 | 0.713013 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 | 344.41 | 344.41 | 0.986149 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 | 458.22 | 458.22 | 1.21 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 | 218.82 | 218.82 | 0.670036 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 | 323.27 | 323.27 | 0.908904 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 | 453.20 | 453.20 | 1.20 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 | 219.02 | 219.02 | 0.668604 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 | 321.30 | 321.30 | 0.904370 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 528.96 | 528.96 | 528.96 | 1.40 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 289.39 | 289.39 | 289.39 | 0.865570 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 354.66 | 354.66 | 354.66 | 1.04 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 529.43 | 529.43 | 529.43 | 1.40 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 291.88 | 291.88 | 291.88 | 0.868241 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 352.82 | 352.82 | 352.82 | 1.03 | 1.00 |
ACANDF_UNITHEATEDBSMT | 216.65 | 216.65 | 216.65 | 0.586835 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 47819.08 | 4.83 | 688.65 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 12820.25 | 1.29 | 182.28 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19252.43 | 1.94 | 275.16 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 26046.41 | 2.63 | 373.19 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 12774.19 | 1.29 | 181.63 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 19168.79 | 1.93 | 273.95 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 25328.81 | 2.56 | 362.80 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 12371.41 | 1.25 | 175.80 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 18024.66 | 1.82 | 257.45 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 25056.88 | 2.53 | 358.92 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 12382.25 | 1.25 | 175.96 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 17917.75 | 1.81 | 255.91 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29156.74 | 2.94 | 418.13 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16190.70 | 1.63 | 230.96 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19723.40 | 1.99 | 282.01 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 29182.42 | 2.95 | 418.51 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16325.47 | 1.65 | 232.90 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19623.37 | 1.98 | 280.56 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 12254.84 | 1.24 | 174.47 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 873.69 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 227.11 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 345.96 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 471.49 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 226.26 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 344.41 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 458.22 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 218.82 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 323.27 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 453.20 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 219.02 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 321.30 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 528.96 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 289.39 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 354.66 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 529.43 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 291.88 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 352.82 |
SUPPLY FAN_UNITHEATEDBSMT | 216.65 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.28 | 99.03 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.28 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 392878.92 | 39.51 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 134.756 | 0.000 | 0.000 | 134.756 |
February | 672.000 | 128.140 | 0.000 | 0.000 | 128.140 |
March | 744.000 | 140.299 | 0.000 | 0.000 | 140.299 |
April | 720.000 | 135.735 | 0.000 | 0.000 | 135.735 |
May | 744.000 | 151.158 | 0.000 | 0.000 | 151.158 |
June | 720.000 | 152.016 | 0.000 | 0.000 | 152.016 |
July | 744.000 | 165.547 | 0.000 | 0.000 | 165.547 |
August | 744.000 | 166.422 | 0.000 | 0.000 | 166.422 |
September | 720.000 | 165.392 | 0.000 | 0.000 | 165.392 |
October | 744.000 | 162.521 | 0.000 | 0.000 | 162.521 |
November | 720.000 | 149.009 | 0.000 | 0.000 | 149.009 |
December | 744.000 | 144.747 | 0.000 | 0.000 | 144.747 |
Annual Sum or Average | 8760.000 | 1795.741 | 0.000 | 0.000 | 1795.741 |
Minimum of Months | 672.000 | 128.140 | 0.000 | 0.000 | 128.140 |
Maximum of Months | 744.000 | 166.422 | 0.000 | 0.000 | 166.422 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 651.650 | 23.257 | 0.000 | 0.000 | 23.257 |
February | 599.994 | 22.771 | 4.208 | 0.006 | 22.777 |
March | 655.353 | 23.349 | 0.000 | 0.000 | 23.349 |
April | 704.634 | 22.368 | 0.000 | 0.000 | 22.368 |
May | 744.000 | 29.934 | 0.000 | 0.000 | 29.934 |
June | 720.000 | 31.742 | 0.000 | 0.000 | 31.742 |
July | 744.000 | 37.511 | 0.000 | 0.000 | 37.511 |
August | 744.000 | 38.331 | 0.000 | 0.000 | 38.331 |
September | 720.000 | 39.212 | 0.000 | 0.000 | 39.212 |
October | 744.000 | 38.600 | 0.000 | 0.000 | 38.600 |
November | 698.425 | 32.473 | 0.000 | 0.000 | 32.473 |
December | 717.587 | 29.098 | 0.000 | 0.000 | 29.098 |
Annual Sum or Average | 8443.644 | 368.647 | 4.208 | 0.006 | 368.653 |
Minimum of Months | 599.994 | 22.368 | 0.000 | 0.000 | 22.368 |
Maximum of Months | 744.000 | 39.212 | 4.208 | 0.006 | 39.212 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 578.296 | 31.001 | 0.000 | 0.000 | 31.067 |
February | 534.320 | 29.602 | 3.833 | 0.057 | 30.894 |
March | 603.284 | 32.101 | 0.000 | 0.000 | 32.883 |
April | 656.000 | 33.374 | 0.000 | 0.000 | 33.374 |
May | 733.875 | 45.317 | 0.000 | 0.000 | 45.317 |
June | 720.000 | 47.300 | 0.000 | 0.000 | 47.300 |
July | 744.000 | 55.507 | 0.000 | 0.000 | 55.507 |
August | 744.000 | 56.774 | 0.000 | 0.000 | 56.774 |
September | 720.000 | 54.277 | 0.000 | 0.000 | 54.277 |
October | 735.500 | 54.262 | 0.000 | 0.000 | 54.262 |
November | 675.292 | 43.452 | 0.000 | 0.000 | 43.452 |
December | 667.958 | 38.191 | 0.000 | 0.000 | 38.191 |
Annual Sum or Average | 8112.525 | 521.157 | 3.833 | 0.057 | 523.298 |
Minimum of Months | 534.320 | 29.602 | 0.000 | 0.000 | 30.894 |
Maximum of Months | 744.000 | 56.774 | 3.833 | 0.057 | 56.774 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 529.002 | 19.778 | 1.750 | 0.002 | 19.781 |
February | 505.613 | 24.977 | 15.406 | 0.117 | 25.523 |
March | 579.580 | 29.756 | 7.906 | 0.037 | 29.969 |
April | 645.659 | 30.686 | 0.000 | 0.000 | 30.686 |
May | 734.250 | 44.322 | 0.000 | 0.000 | 44.322 |
June | 720.000 | 48.652 | 0.000 | 0.000 | 48.652 |
July | 744.000 | 57.336 | 0.000 | 0.000 | 57.336 |
August | 744.000 | 56.584 | 0.000 | 0.000 | 56.584 |
September | 720.000 | 55.884 | 0.000 | 0.000 | 55.884 |
October | 734.650 | 47.215 | 0.000 | 0.000 | 47.215 |
November | 664.133 | 35.756 | 0.000 | 0.000 | 35.762 |
December | 647.512 | 27.415 | 0.000 | 0.000 | 27.415 |
Annual Sum or Average | 7968.399 | 478.359 | 25.062 | 0.157 | 479.127 |
Minimum of Months | 505.613 | 19.778 | 0.000 | 0.000 | 19.781 |
Maximum of Months | 744.000 | 57.336 | 15.406 | 0.117 | 57.336 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 624.673 | 14.963 | 0.000 | 0.000 | 14.963 |
February | 585.866 | 16.748 | 6.500 | 0.013 | 16.761 |
March | 649.789 | 19.590 | 0.625 | 0.000 | 19.590 |
April | 704.987 | 21.310 | 0.000 | 0.000 | 21.310 |
May | 744.000 | 31.197 | 0.000 | 0.000 | 31.197 |
June | 720.000 | 33.735 | 0.000 | 0.000 | 33.735 |
July | 744.000 | 39.163 | 0.000 | 0.000 | 39.163 |
August | 744.000 | 38.396 | 0.000 | 0.000 | 38.396 |
September | 720.000 | 36.735 | 0.000 | 0.000 | 36.735 |
October | 744.000 | 33.490 | 0.000 | 0.000 | 33.490 |
November | 693.570 | 25.569 | 0.000 | 0.000 | 25.569 |
December | 707.590 | 20.576 | 0.000 | 0.000 | 20.576 |
Annual Sum or Average | 8382.475 | 331.475 | 7.125 | 0.013 | 331.488 |
Minimum of Months | 585.866 | 14.963 | 0.000 | 0.000 | 14.963 |
Maximum of Months | 744.000 | 39.163 | 6.500 | 0.013 | 39.163 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 572.867 | 22.782 | 0.000 | 0.000 | 22.887 |
February | 524.454 | 23.498 | 5.542 | 0.074 | 24.664 |
March | 599.673 | 28.323 | 0.500 | 0.006 | 29.050 |
April | 656.250 | 32.172 | 0.000 | 0.000 | 32.172 |
May | 734.250 | 46.184 | 0.000 | 0.000 | 46.184 |
June | 720.000 | 48.896 | 0.000 | 0.000 | 48.896 |
July | 744.000 | 56.778 | 0.000 | 0.000 | 56.778 |
August | 744.000 | 56.559 | 0.000 | 0.000 | 56.559 |
September | 720.000 | 51.637 | 0.000 | 0.000 | 51.637 |
October | 735.375 | 49.215 | 0.000 | 0.000 | 49.215 |
November | 673.479 | 36.261 | 0.000 | 0.000 | 36.261 |
December | 664.479 | 29.565 | 0.000 | 0.000 | 29.565 |
Annual Sum or Average | 8088.827 | 481.872 | 6.042 | 0.080 | 483.870 |
Minimum of Months | 524.454 | 22.782 | 0.000 | 0.000 | 22.887 |
Maximum of Months | 744.000 | 56.778 | 5.542 | 0.074 | 56.778 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 619.916 | 31.518 | 0.000 | 0.000 | 31.518 |
February | 569.044 | 33.349 | 7.792 | 0.045 | 33.507 |
March | 622.405 | 35.728 | 2.875 | 0.011 | 35.779 |
April | 687.279 | 34.067 | 0.000 | 0.000 | 34.067 |
May | 738.708 | 43.531 | 0.000 | 0.000 | 43.531 |
June | 720.000 | 46.214 | 0.000 | 0.000 | 46.214 |
July | 744.000 | 54.575 | 0.000 | 0.000 | 54.575 |
August | 744.000 | 55.729 | 0.000 | 0.000 | 55.729 |
September | 720.000 | 57.746 | 0.000 | 0.000 | 57.746 |
October | 741.000 | 53.394 | 0.000 | 0.000 | 53.394 |
November | 686.706 | 44.767 | 0.000 | 0.000 | 44.767 |
December | 699.174 | 39.370 | 0.000 | 0.000 | 39.370 |
Annual Sum or Average | 8292.233 | 529.990 | 10.667 | 0.056 | 530.199 |
Minimum of Months | 569.044 | 31.518 | 0.000 | 0.000 | 31.518 |
Maximum of Months | 744.000 | 57.746 | 7.792 | 0.045 | 57.746 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 718.554 | 25.886 | 0.000 | 0.000 | 25.886 |
February | 631.168 | 24.776 | 1.000 | 0.001 | 24.777 |
March | 692.026 | 25.368 | 0.000 | 0.000 | 25.368 |
April | 717.771 | 24.475 | 0.000 | 0.000 | 24.475 |
May | 744.000 | 30.444 | 0.000 | 0.000 | 30.444 |
June | 720.000 | 31.540 | 0.000 | 0.000 | 31.540 |
July | 744.000 | 36.660 | 0.000 | 0.000 | 36.660 |
August | 744.000 | 37.535 | 0.000 | 0.000 | 37.535 |
September | 720.000 | 38.387 | 0.000 | 0.000 | 38.387 |
October | 744.000 | 38.638 | 0.000 | 0.000 | 38.638 |
November | 710.083 | 33.436 | 0.000 | 0.000 | 33.436 |
December | 731.042 | 31.086 | 0.000 | 0.000 | 31.086 |
Annual Sum or Average | 8616.644 | 378.231 | 1.000 | 0.001 | 378.232 |
Minimum of Months | 631.168 | 24.475 | 0.000 | 0.000 | 24.475 |
Maximum of Months | 744.000 | 38.638 | 1.000 | 0.001 | 38.638 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 632.621 | 32.866 | 0.000 | 0.000 | 32.866 |
February | 575.295 | 31.000 | 0.833 | 0.012 | 31.905 |
March | 636.044 | 33.478 | 0.000 | 0.000 | 33.833 |
April | 691.208 | 34.976 | 0.000 | 0.000 | 34.976 |
May | 739.250 | 45.343 | 0.000 | 0.000 | 45.343 |
June | 720.000 | 46.438 | 0.000 | 0.000 | 46.438 |
July | 744.000 | 53.884 | 0.000 | 0.000 | 53.884 |
August | 744.000 | 55.267 | 0.000 | 0.000 | 55.267 |
September | 720.000 | 52.665 | 0.000 | 0.000 | 52.665 |
October | 740.875 | 53.520 | 0.000 | 0.000 | 53.520 |
November | 689.792 | 43.695 | 0.000 | 0.000 | 43.695 |
December | 703.917 | 39.604 | 0.000 | 0.000 | 39.604 |
Annual Sum or Average | 8337.002 | 522.735 | 0.833 | 0.012 | 523.995 |
Minimum of Months | 575.295 | 31.000 | 0.000 | 0.000 | 31.905 |
Maximum of Months | 744.000 | 55.267 | 0.833 | 0.012 | 55.267 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 588.790 | 21.954 | 0.000 | 0.000 | 21.954 |
February | 552.761 | 26.758 | 9.133 | 0.060 | 27.220 |
March | 613.628 | 31.546 | 3.125 | 0.016 | 31.627 |
April | 687.311 | 32.777 | 0.000 | 0.000 | 32.777 |
May | 739.500 | 44.709 | 0.000 | 0.000 | 44.709 |
June | 720.000 | 48.133 | 0.000 | 0.000 | 48.133 |
July | 744.000 | 56.079 | 0.000 | 0.000 | 56.079 |
August | 744.000 | 55.517 | 0.000 | 0.000 | 55.517 |
September | 720.000 | 54.758 | 0.000 | 0.000 | 54.758 |
October | 740.417 | 47.077 | 0.000 | 0.000 | 47.077 |
November | 680.553 | 36.600 | 0.000 | 0.000 | 36.600 |
December | 687.942 | 29.457 | 0.000 | 0.000 | 29.457 |
Annual Sum or Average | 8218.901 | 485.365 | 12.258 | 0.076 | 485.907 |
Minimum of Months | 552.761 | 21.954 | 0.000 | 0.000 | 21.954 |
Maximum of Months | 744.000 | 56.079 | 9.133 | 0.060 | 56.079 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 705.967 | 17.672 | 0.000 | 0.000 | 17.672 |
February | 620.274 | 18.920 | 2.167 | 0.002 | 18.923 |
March | 686.956 | 21.760 | 0.000 | 0.000 | 21.760 |
April | 718.083 | 23.451 | 0.000 | 0.000 | 23.451 |
May | 744.000 | 31.622 | 0.000 | 0.000 | 31.622 |
June | 720.000 | 33.379 | 0.000 | 0.000 | 33.379 |
July | 744.000 | 38.177 | 0.000 | 0.000 | 38.177 |
August | 744.000 | 37.553 | 0.000 | 0.000 | 37.553 |
September | 720.000 | 35.904 | 0.000 | 0.000 | 35.904 |
October | 744.000 | 33.460 | 0.000 | 0.000 | 33.460 |
November | 707.440 | 26.561 | 0.000 | 0.000 | 26.561 |
December | 724.593 | 22.707 | 0.000 | 0.000 | 22.707 |
Annual Sum or Average | 8579.314 | 341.167 | 2.167 | 0.002 | 341.169 |
Minimum of Months | 620.274 | 17.672 | 0.000 | 0.000 | 17.672 |
Maximum of Months | 744.000 | 38.177 | 2.167 | 0.002 | 38.177 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 627.442 | 24.784 | 0.000 | 0.000 | 24.784 |
February | 569.910 | 25.069 | 1.500 | 0.020 | 26.000 |
March | 633.839 | 29.810 | 0.000 | 0.000 | 30.168 |
April | 691.292 | 33.752 | 0.000 | 0.000 | 33.752 |
May | 739.250 | 46.040 | 0.000 | 0.000 | 46.040 |
June | 720.000 | 47.794 | 0.000 | 0.000 | 47.794 |
July | 744.000 | 54.919 | 0.000 | 0.000 | 54.919 |
August | 744.000 | 54.917 | 0.000 | 0.000 | 54.917 |
September | 720.000 | 50.007 | 0.000 | 0.000 | 50.007 |
October | 740.875 | 48.603 | 0.000 | 0.000 | 48.603 |
November | 689.146 | 36.665 | 0.000 | 0.000 | 36.665 |
December | 701.896 | 31.179 | 0.000 | 0.000 | 31.179 |
Annual Sum or Average | 8321.649 | 483.540 | 1.500 | 0.020 | 484.829 |
Minimum of Months | 569.910 | 24.784 | 0.000 | 0.000 | 24.784 |
Maximum of Months | 744.000 | 54.919 | 1.500 | 0.020 | 54.919 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 561.383 | 32.400 | 0.000 | 0.000 | 32.509 |
February | 524.824 | 35.201 | 9.583 | 0.129 | 36.309 |
March | 585.258 | 38.511 | 3.250 | 0.038 | 39.311 |
April | 645.654 | 37.047 | 0.000 | 0.000 | 37.047 |
May | 729.726 | 49.298 | 0.000 | 0.000 | 49.298 |
June | 720.000 | 52.963 | 0.000 | 0.000 | 52.963 |
July | 744.000 | 63.211 | 0.000 | 0.000 | 63.211 |
August | 744.000 | 63.956 | 0.000 | 0.000 | 63.956 |
September | 720.000 | 65.231 | 0.000 | 0.000 | 65.231 |
October | 731.314 | 59.079 | 0.000 | 0.000 | 59.079 |
November | 667.905 | 48.439 | 0.000 | 0.000 | 48.467 |
December | 661.730 | 41.292 | 0.000 | 0.000 | 41.292 |
Annual Sum or Average | 8035.795 | 586.627 | 12.833 | 0.167 | 588.673 |
Minimum of Months | 524.824 | 32.400 | 0.000 | 0.000 | 32.509 |
Maximum of Months | 744.000 | 65.231 | 9.583 | 0.129 | 65.231 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 646.816 | 27.366 | 0.000 | 0.000 | 27.366 |
February | 597.554 | 27.201 | 6.500 | 0.019 | 27.219 |
March | 652.909 | 28.615 | 2.000 | 0.003 | 28.618 |
April | 702.706 | 27.949 | 0.000 | 0.000 | 27.949 |
May | 743.125 | 36.743 | 0.000 | 0.000 | 36.743 |
June | 720.000 | 38.759 | 0.000 | 0.000 | 38.759 |
July | 744.000 | 45.694 | 0.000 | 0.000 | 45.694 |
August | 744.000 | 46.237 | 0.000 | 0.000 | 46.237 |
September | 720.000 | 46.453 | 0.000 | 0.000 | 46.453 |
October | 743.500 | 45.265 | 0.000 | 0.000 | 45.265 |
November | 694.427 | 38.088 | 0.000 | 0.000 | 38.088 |
December | 711.902 | 34.057 | 0.000 | 0.000 | 34.057 |
Annual Sum or Average | 8420.938 | 442.427 | 8.500 | 0.022 | 442.449 |
Minimum of Months | 597.554 | 27.201 | 0.000 | 0.000 | 27.219 |
Maximum of Months | 744.000 | 46.453 | 6.500 | 0.019 | 46.453 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 586.848 | 32.760 | 0.000 | 0.000 | 32.899 |
February | 540.310 | 31.836 | 5.792 | 0.082 | 32.992 |
March | 606.200 | 35.000 | 1.875 | 0.018 | 35.707 |
April | 661.000 | 36.624 | 0.000 | 0.000 | 36.624 |
May | 731.625 | 49.074 | 0.000 | 0.000 | 49.074 |
June | 720.000 | 50.969 | 0.000 | 0.000 | 50.969 |
July | 744.000 | 59.805 | 0.000 | 0.000 | 59.805 |
August | 744.000 | 60.862 | 0.000 | 0.000 | 60.862 |
September | 720.000 | 57.657 | 0.000 | 0.000 | 57.657 |
October | 732.875 | 57.200 | 0.000 | 0.000 | 57.200 |
November | 675.158 | 45.739 | 0.000 | 0.000 | 45.761 |
December | 669.917 | 40.280 | 0.000 | 0.000 | 40.280 |
Annual Sum or Average | 8131.933 | 557.806 | 7.667 | 0.100 | 559.831 |
Minimum of Months | 540.310 | 31.836 | 0.000 | 0.000 | 32.899 |
Maximum of Months | 744.000 | 60.862 | 5.792 | 0.082 | 60.862 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 532.582 | 25.130 | 2.875 | 0.005 | 25.136 |
February | 512.047 | 30.711 | 15.786 | 0.152 | 31.560 |
March | 581.231 | 36.243 | 9.653 | 0.053 | 36.638 |
April | 646.901 | 36.529 | 0.000 | 0.000 | 36.529 |
May | 731.583 | 50.228 | 0.000 | 0.000 | 50.228 |
June | 720.000 | 54.340 | 0.000 | 0.000 | 54.340 |
July | 744.000 | 64.354 | 0.000 | 0.000 | 64.354 |
August | 744.000 | 64.156 | 0.000 | 0.000 | 64.156 |
September | 720.000 | 63.733 | 0.000 | 0.000 | 63.733 |
October | 730.451 | 55.132 | 0.000 | 0.000 | 55.132 |
November | 663.132 | 42.185 | 0.250 | 0.001 | 42.245 |
December | 644.978 | 33.351 | 0.000 | 0.000 | 33.352 |
Annual Sum or Average | 7970.905 | 556.092 | 28.564 | 0.210 | 557.403 |
Minimum of Months | 512.047 | 25.130 | 0.000 | 0.000 | 25.136 |
Maximum of Months | 744.000 | 64.354 | 15.786 | 0.152 | 64.354 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 621.578 | 20.676 | 0.000 | 0.000 | 20.676 |
February | 585.731 | 23.019 | 8.667 | 0.025 | 23.044 |
March | 649.743 | 26.626 | 2.083 | 0.003 | 26.629 |
April | 703.076 | 27.577 | 0.000 | 0.000 | 27.577 |
May | 743.500 | 37.740 | 0.000 | 0.000 | 37.740 |
June | 720.000 | 40.172 | 0.000 | 0.000 | 40.172 |
July | 744.000 | 46.931 | 0.000 | 0.000 | 46.931 |
August | 744.000 | 46.620 | 0.000 | 0.000 | 46.620 |
September | 720.000 | 45.287 | 0.000 | 0.000 | 45.287 |
October | 743.250 | 41.891 | 0.000 | 0.000 | 41.891 |
November | 689.351 | 32.481 | 0.000 | 0.000 | 32.481 |
December | 701.111 | 26.886 | 0.000 | 0.000 | 26.886 |
Annual Sum or Average | 8365.340 | 415.906 | 10.750 | 0.027 | 415.933 |
Minimum of Months | 585.731 | 20.676 | 0.000 | 0.000 | 20.676 |
Maximum of Months | 744.000 | 46.931 | 8.667 | 0.025 | 46.931 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 578.246 | 26.565 | 0.000 | 0.000 | 26.758 |
February | 534.068 | 27.820 | 6.458 | 0.089 | 29.013 |
March | 605.253 | 33.033 | 1.875 | 0.018 | 33.780 |
April | 661.292 | 36.094 | 0.000 | 0.000 | 36.094 |
May | 732.125 | 49.593 | 0.000 | 0.000 | 49.593 |
June | 720.000 | 51.859 | 0.000 | 0.000 | 51.859 |
July | 744.000 | 60.525 | 0.000 | 0.000 | 60.525 |
August | 744.000 | 60.867 | 0.000 | 0.000 | 60.867 |
September | 720.000 | 56.349 | 0.000 | 0.000 | 56.349 |
October | 732.875 | 54.174 | 0.000 | 0.000 | 54.174 |
November | 673.658 | 40.466 | 0.000 | 0.000 | 40.492 |
December | 667.171 | 33.591 | 0.000 | 0.000 | 33.591 |
Annual Sum or Average | 8112.687 | 530.937 | 8.333 | 0.108 | 533.095 |
Minimum of Months | 534.068 | 26.565 | 0.000 | 0.000 | 26.758 |
Maximum of Months | 744.000 | 60.867 | 6.458 | 0.089 | 60.867 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 4.292 | 0.011 | 3.060 |
February | 0.000 | 0.000 | 16.542 | 0.070 | 2.084 |
March | 0.000 | 0.000 | 11.375 | 0.024 | 0.708 |
April | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 739.500 | 20.014 | 0.000 | 0.000 | 20.014 |
June | 720.000 | 27.703 | 0.000 | 0.000 | 27.703 |
July | 744.000 | 35.138 | 0.000 | 0.000 | 35.138 |
August | 744.000 | 37.763 | 0.000 | 0.000 | 37.763 |
September | 720.000 | 33.813 | 0.000 | 0.000 | 33.813 |
October | 744.000 | 31.097 | 0.000 | 0.000 | 31.097 |
November | 57.100 | 0.318 | 0.000 | 0.000 | 0.318 |
December | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 4468.600 | 185.846 | 32.208 | 0.104 | 191.698 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 744.000 | 37.763 | 16.542 | 0.070 | 37.763 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 1.11 |
February | 0.00 | 0.00 | 1.18 |
March | 0.00 | 0.00 | 1.16 |
April | 0.00 | 0.00 | 1.15 |
May | 0.00 | 0.00 | 1.24 |
June | 0.00 | 0.00 | 1.29 |
July | 0.00 | 0.00 | 1.36 |
August | 0.00 | 0.00 | 1.37 |
September | 0.00 | 0.00 | 1.42 |
October | 0.00 | 0.00 | 1.34 |
November | 0.00 | 0.00 | 1.27 |
December | 0.00 | 0.00 | 1.19 |
Annual Sum or Average | 0.00 | 0.00 | 1.26 |
Minimum of Months | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.00 | 0.00 | 1.42 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.25 |
February | 0.00 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.31 |
February | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.00 | 0.54 |
November | 0.00 | 0.00 | 0.45 |
December | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.20 |
March | 0.00 | 0.00 | 0.21 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.37 |
November | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.22 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.28 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.22 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.23 |
February | 0.00 | 0.00 | 0.27 |
March | 0.00 | 0.00 | 0.28 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.00 | 0.45 |
December | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.33 |
February | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.58 |
November | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.22 |
February | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.00 | 0.00 | 0.59 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.21 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.26 |
February | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.00 | 0.33 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.00 | 0.55 |
November | 0.00 | 0.00 | 0.42 |
December | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.17 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.33 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.62 |
June | 0.00 | 0.00 | 987.16 | 711.26 |
July | 0.00 | 0.00 | 976.60 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.21 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.35 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.10 |
Minimum of Months | 0.00 | 0.00 | 976.60 | 711.26 |