Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
Tabular Output Report in Format: HTML
Building: MF+CZ1AT+USA_HI_Honolulu.Intl.AP.911820+oilfurnace+crawlspace+IECC_2009
Environment: ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2019-02-14 08:27:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 783531.21 | 20.09 | 36.26 |
Net Site Energy | 783531.21 | 20.09 | 36.26 |
Total Source Energy | 2052965.07 | 52.63 | 95.00 |
Net Source Energy | 2052965.07 | 52.63 | 95.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 162.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 183719.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32456.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 205539.93 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 577828.73 | 205702.48 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 162.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 183719.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 32456.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 205539.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.00 | 9.52 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 26.74 | 9.52 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 5.54 | 5.27 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.81 | 5.27 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 577828.727 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 577828.727 | 100.00 |
Total On-Site and Utility Electric Sources | 577828.727 | 100.00 |
Total Electricity End Uses | 577828.727 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 16.50 |
Time Setpoint Not Met During Occupied Cooling | 187.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3238.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27 |
RunPeriod | ANNUAL |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [ft] | 6.56 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19407.54 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 286495.20 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 102755.82 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 02-SEP-18:15 | 12-FEB-07:15 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 27.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 111.94 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 124.46 | 138.99 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 27.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 46.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 176.20 | 0.00 | 0.00 | 0.00 |
Cooling | 581840.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102789.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 222805.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1829983.58 | 222981.49 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 |
Cooling | 26.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.31 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84.68 | 10.32 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 |
Cooling | 26.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.31 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84.68 | 10.32 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 61.16 | 0.00 | 61.16 | Wetbulb [F] | 374.03 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 89.96 | 12.78 | 73.94 | Wetbulb [F] | 1318.96 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 1.027 | 0.258 | 0.881 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 1.027 | 0.258 | 0.881 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 1.027 | 0.258 | 0.881 | ||||||||||||
North Total or Average | 531.68 | 1.027 | 0.258 | 0.881 | ||||||||||||
Non-North Total or Average | 1595.05 | 1.027 | 0.258 | 0.881 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.594 | 1.200 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 375570.67 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 25138.13 | 19284.06 | 5854.07 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8321.18 | 5704.28 | 2616.91 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11455.72 | 8156.05 | 3299.67 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15045.53 | 10992.68 | 4052.85 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8237.31 | 5659.39 | 2577.92 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11363.73 | 8098.00 | 3265.73 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14452.31 | 10706.29 | 3746.02 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8001.27 | 5579.22 | 2422.05 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10850.16 | 7823.14 | 3027.02 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14325.82 | 10602.44 | 3723.37 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7984.24 | 5573.86 | 2410.38 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10796.12 | 7780.67 | 3015.45 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16806.55 | 12426.02 | 4380.53 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10380.38 | 7307.98 | 3072.40 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12435.99 | 8833.97 | 3602.02 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16818.33 | 12435.74 | 4382.59 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10412.53 | 7346.27 | 3066.26 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12367.64 | 8786.44 | 3581.20 | 0.71 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.0 | 3.32 | 11.32 | 11.99 | 11.59 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.48 | 11.87 | 12.60 | 12.50 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.43 | 11.69 | 12.40 | 12.19 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.39 | 11.56 | 12.26 | 11.98 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.48 | 11.86 | 12.59 | 12.48 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.42 | 11.68 | 12.39 | 12.18 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.37 | 11.49 | 12.18 | 11.87 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.46 | 11.79 | 12.51 | 12.36 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.41 | 11.63 | 12.33 | 12.09 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.37 | 11.50 | 12.19 | 11.88 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.45 | 11.78 | 12.50 | 12.35 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.41 | 11.63 | 12.33 | 12.09 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.37 | 11.50 | 12.20 | 11.89 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.44 | 11.74 | 12.46 | 12.28 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.43 | 11.70 | 12.41 | 12.21 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.37 | 11.50 | 12.19 | 11.89 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.44 | 11.73 | 12.45 | 12.27 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.43 | 11.70 | 12.41 | 12.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 47190.77 | 51461.24 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 12223.05 | 13104.84 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 18301.39 | 19765.48 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 25421.58 | 27563.40 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 12174.76 | 13052.31 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 18199.75 | 19654.18 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 25252.43 | 27374.64 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 12294.00 | 13181.22 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 17904.45 | 19329.76 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 24979.89 | 27078.27 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 12304.91 | 13193.30 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 17798.54 | 19213.77 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29145.22 | 31642.27 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 16177.88 | 17437.32 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19711.74 | 21311.04 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 29170.84 | 31670.63 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 16312.77 | 17585.09 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 19611.94 | 21201.72 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 862.08 | 325.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 216.08 | 81.50 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 328.39 | 123.87 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 459.95 | 173.49 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 215.19 | 81.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 326.51 | 123.16 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 456.81 | 172.31 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 217.39 | 82.00 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 321.05 | 121.10 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 451.78 | 170.41 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 217.59 | 82.07 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 319.09 | 120.36 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 528.75 | 199.44 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 289.15 | 109.07 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 354.45 | 133.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 529.22 | 199.62 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 291.64 | 110.01 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 352.61 | 133.00 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 37.766522 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 20246.27 | 20246.27 | 16.86 | 862.084 | 862.084 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00875 | 87.53 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5074.89 | 5074.89 | 4.23 | 216.078 | 216.078 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.01022 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7712.67 | 7712.67 | 6.42 | 328.389 | 328.389 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00959 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10802.12 | 10802.12 | 9.00 | 459.945 | 459.945 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00929 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5053.99 | 5053.99 | 4.21 | 215.187 | 215.187 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.01026 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7668.62 | 7668.62 | 6.39 | 326.511 | 326.511 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 74.98 | 74.98 | 0.00960 | 86.54 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10728.98 | 10728.98 | 8.94 | 456.812 | 456.812 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00899 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5105.82 | 5105.82 | 4.25 | 217.387 | 217.387 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00977 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7540.58 | 7540.58 | 6.28 | 321.052 | 321.052 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00924 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10610.78 | 10610.78 | 8.84 | 451.779 | 451.779 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00900 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5110.57 | 5110.57 | 4.26 | 217.589 | 217.589 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00979 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7494.63 | 7494.63 | 6.24 | 319.095 | 319.095 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 74.98 | 74.98 | 0.00924 | 87.02 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8279.90 | 8279.90 | 6.90 | 352.605 | 352.605 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 74.98 | 74.98 | 0.00949 | 89.58 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8322.90 | 8322.90 | 6.93 | 354.449 | 354.449 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 74.98 | 74.98 | 0.00949 | 89.77 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12417.94 | 12417.94 | 10.34 | 528.747 | 528.747 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00915 | 87.21 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6849.56 | 6849.56 | 5.71 | 291.642 | 291.642 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00980 | 85.93 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6791.00 | 6791.00 | 5.66 | 289.150 | 289.150 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00980 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12429.06 | 12429.06 | 10.35 | 529.221 | 529.221 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00915 | 87.21 | 0.01435 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 61.16 | 0.01152 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1135.12 | 1135.12 | 0.95 | 20.667 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01124 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2075.19 | 2075.19 | 1.73 | 37.784 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01073 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2081.89 | 2081.89 | 1.73 | 37.906 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01072 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1242.37 | 1242.37 | 1.03 | 22.620 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01117 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2078.60 | 2078.60 | 1.73 | 37.846 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01072 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1404.63 | 1404.63 | 1.17 | 25.574 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01101 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 817.67 | 817.67 | 0.68 | 14.887 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01150 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1671.26 | 1671.26 | 1.39 | 30.429 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01084 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1673.63 | 1673.63 | 1.39 | 30.472 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01084 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 844.85 | 844.85 | 0.70 | 15.382 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01147 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1669.86 | 1669.86 | 1.39 | 30.403 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01084 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2296.54 | 2296.54 | 1.91 | 41.814 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2299.46 | 2299.46 | 1.92 | 41.867 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2249.88 | 2249.88 | 1.87 | 40.964 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01065 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1445.21 | 1445.21 | 1.20 | 26.313 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01104 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1436.54 | 1436.54 | 1.20 | 26.155 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01105 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2299.79 | 2299.79 | 1.92 | 41.873 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01063 | 61.16 | 0.01152 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 | 862.08 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 | 216.08 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 | 328.39 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 | 459.95 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 | 215.19 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 | 326.51 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 | 456.81 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 | 217.39 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.05 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 | 451.78 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 | 217.59 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 | 319.09 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.75 | 528.75 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.15 | 289.15 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.45 | 354.45 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.22 | 529.22 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.64 | 291.64 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.61 | 352.61 | 44.99 | 44.99 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4056.25 | 1563.25 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7932.00 | 2663.00 | 2442.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8033.50 | 2625.75 | 2309.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7898.75 | 3399.75 | 3000.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7761.25 | 2973.25 | 2706.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7944.50 | 2741.25 | 2415.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8071.50 | 1708.75 | 1519.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7967.75 | 821.00 | 742.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8063.25 | 1288.25 | 1116.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7981.25 | 1867.75 | 1643.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7814.00 | 1018.50 | 922.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7994.50 | 1351.50 | 1173.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8096.00 | 1783.75 | 1532.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8128.75 | 1736.00 | 1493.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8102.75 | 2301.75 | 2022.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8034.50 | 1753.25 | 1582.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8116.75 | 1608.75 | 1464.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8050.50 | 2417.00 | 2108.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 8262.75 | 3844.00 | 3238.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 117.25 | 0.00 | 117.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5.75 | 81.00 | 5.75 | 81.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.75 | 0.00 | 1.75 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5.00 | 4.50 | 5.00 | 4.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 89.25 | 0.00 | 89.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5.25 | 97.50 | 5.25 | 97.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5.75 | 5.50 | 5.75 | 5.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 4.25 | 9.75 | 4.25 | 9.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 4.25 | 59.50 | 4.25 | 59.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.50 | 0.00 | 0.50 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 16.25 | 0.00 | 16.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.00 | 0.00 | 1.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 16.50 | 187.50 | 16.50 | 187.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.244 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.078 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.078 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.214 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.243 | 0.000 | 0.264 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1867 |
Defaulted Fields | 446 |
Fields with Defaults | 4736 |
Autosized Fields | 328 |
Autosizable Fields | 438 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 9505.66 | 115.27 | 25-MAR-02:00 | 2509.60 | 03-SEP-16:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
ElectricityPurchased:Plant | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
Cogeneration:ElectricityPurchased | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
ElectricityNet:Plant | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
Cogeneration:ElectricityNet | 169232.02 | 7560.49 | 28-MAR-03:30 | 36450.89 | 02-SEP-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 63312.68 | 617.82 | 12-FEB-00:15 | 17731.58 | 03-SEP-16:15 |
General:Fans:Electricity | 9505.66 | 115.27 | 25-MAR-02:00 | 2509.60 | 03-SEP-16:15 |
Cooling:Electricity | 53807.03 | 353.64 | 12-FEB-07:00 | 15223.88 | 03-SEP-15:45 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2057.02 | 0.00 | 01-JAN-00:15 | 138891.44 | 12-FEB-07:15 |
Gas:Plant | 2057.02 | 0.00 | 01-JAN-00:15 | 138891.44 | 12-FEB-07:15 |
WaterSystems:Gas | 2055.40 | 0.00 | 01-JAN-00:15 | 112046.33 | 15-JAN-08:45 |
Water Heater:WaterSystems:Gas | 2055.40 | 0.00 | 01-JAN-00:15 | 112046.33 | 15-JAN-08:45 |
Heating:Gas | 1.63 | 0.00 | 01-JAN-00:15 | 28500.11 | 12-FEB-07:00 |
Boiler:Heating:Gas | 1.63 | 0.00 | 01-JAN-00:15 | 28500.11 | 12-FEB-07:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 10-APR-02:15 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 86478.63 | 814.59 | 19-JUL-02:30 | 45518.03 | 12-FEB-07:15 |
PlantLoopHeatingDemand:Plant | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1445258.63 | 16656.39 | 27-NOV-03:15 | 385027.98 | 03-SEP-16:15 |
EnergyTransfer:Building | 554119.63 | 6917.47 | 27-NOV-03:15 | 160353.94 | 03-SEP-16:15 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 262.41 | 0.00 | 01-JAN-00:15 | 29777.76 | 12-FEB-07:00 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 553857.22 | 5080.13 | 12-FEB-07:15 | 160353.94 | 03-SEP-16:15 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103441.51 | 5080.13 | 12-FEB-07:15 | 19883.89 | 11-OCT-14:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103441.51 | 5080.13 | 12-FEB-07:15 | 19883.89 | 11-OCT-14:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20162.16 | 0.00 | 01-JAN-02:45 | 6144.56 | 07-JAN-13:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5.55 | 0.00 | 01-JAN-00:15 | 1113.31 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20156.61 | 0.00 | 01-JAN-02:45 | 6144.56 | 07-JAN-13:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 28388.39 | 0.00 | 01-JAN-01:00 | 8803.80 | 15-DEC-11:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 32.47 | 0.00 | 01-JAN-00:15 | 2446.31 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 28355.92 | 0.00 | 01-JAN-01:00 | 8803.80 | 15-DEC-11:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22881.40 | 0.00 | 01-JAN-01:00 | 10542.56 | 04-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 41.63 | 0.00 | 01-JAN-00:15 | 2404.76 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22839.77 | 0.00 | 01-JAN-01:00 | 10542.56 | 04-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17069.39 | 0.00 | 01-JAN-02:30 | 5400.39 | 03-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7.98 | 0.00 | 01-JAN-00:15 | 1211.97 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17061.41 | 0.00 | 01-JAN-02:30 | 5400.39 | 03-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25284.34 | 0.00 | 01-JAN-01:00 | 8581.07 | 12-JUL-10:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 34.81 | 0.00 | 01-JAN-00:15 | 2479.33 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25249.53 | 0.00 | 01-JAN-01:00 | 8581.07 | 12-JUL-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28704.41 | 0.00 | 01-JAN-02:45 | 10714.11 | 03-SEP-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8.01 | 0.00 | 01-JAN-00:15 | 1414.31 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28696.40 | 0.00 | 01-JAN-02:45 | 10714.11 | 03-SEP-16:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23396.50 | 0.00 | 05-JAN-05:00 | 6151.85 | 29-JAN-15:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.37 | 0.00 | 01-JAN-00:15 | 375.42 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23396.13 | 0.00 | 05-JAN-05:00 | 6151.85 | 29-JAN-15:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31300.59 | 0.00 | 01-JAN-02:45 | 8621.81 | 27-OCT-13:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6.62 | 0.00 | 01-JAN-00:15 | 2532.41 | 12-FEB-06:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31293.97 | 0.00 | 01-JAN-02:45 | 8621.81 | 27-OCT-13:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25701.30 | 0.00 | 01-JAN-02:45 | 10194.77 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11.66 | 0.00 | 01-JAN-00:15 | 1593.96 | 12-FEB-06:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25689.64 | 0.00 | 01-JAN-02:45 | 10194.77 | 05-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20263.76 | 0.00 | 05-JAN-05:00 | 5284.30 | 03-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.78 | 0.00 | 01-JAN-00:15 | 463.03 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20262.98 | 0.00 | 05-JAN-05:00 | 5284.30 | 03-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28236.01 | 0.00 | 01-JAN-02:45 | 8411.38 | 08-JUL-10:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8.02 | 0.00 | 01-JAN-00:15 | 2572.45 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28227.99 | 0.00 | 01-JAN-02:45 | 8411.38 | 08-JUL-10:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32147.09 | 0.00 | 01-JAN-02:30 | 9149.32 | 12-JUL-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 21.74 | 0.00 | 01-JAN-00:15 | 2615.92 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32125.35 | 0.00 | 01-JAN-02:30 | 9149.32 | 12-JUL-10:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34310.37 | 0.00 | 01-JAN-02:30 | 9621.78 | 27-OCT-13:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 20.37 | 0.00 | 01-JAN-00:15 | 2591.77 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34290.00 | 0.00 | 01-JAN-02:30 | 9621.78 | 27-OCT-13:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31879.22 | 0.00 | 01-JAN-02:30 | 12463.99 | 03-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24.40 | 0.00 | 01-JAN-00:15 | 2526.72 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31854.82 | 0.00 | 01-JAN-02:30 | 12463.99 | 03-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24464.85 | 0.00 | 01-JAN-04:00 | 7213.84 | 03-SEP-17:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5.55 | 0.00 | 01-JAN-00:15 | 1260.75 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24459.30 | 0.00 | 01-JAN-04:00 | 7213.84 | 03-SEP-17:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26691.15 | 0.00 | 01-JAN-04:15 | 7790.56 | 13-DEC-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4.35 | 0.00 | 01-JAN-00:15 | 1214.92 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26686.80 | 0.00 | 01-JAN-04:15 | 7790.56 | 13-DEC-16:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29797.20 | 0.00 | 01-JAN-02:30 | 12362.51 | 03-SEP-16:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 28.11 | 0.00 | 01-JAN-00:15 | 2527.57 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29769.09 | 0.00 | 01-JAN-02:30 | 12362.51 | 03-SEP-16:15 |
EnergyTransfer:Plant | 86423.06 | 814.59 | 19-JUL-02:30 | 41675.05 | 12-FEB-07:15 |
WaterSystems:EnergyTransfer | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 86293.02 | 814.59 | 19-JUL-02:30 | 20977.03 | 15-JAN-09:00 |
EnergyTransfer:HVAC | 804715.94 | 8183.53 | 08-MAR-03:00 | 215371.34 | 03-SEP-16:15 |
HeatingCoils:EnergyTransfer | 185.61 | 0.00 | 01-JAN-00:15 | 28972.75 | 12-FEB-07:00 |
PlantLoopHeatingDemand:HVAC | 185.61 | 0.00 | 01-JAN-00:15 | 28972.75 | 12-FEB-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 185.61 | 0.00 | 01-JAN-00:15 | 28972.75 | 12-FEB-07:00 |
CoolingCoils:EnergyTransfer | 804530.33 | 6159.97 | 12-FEB-07:15 | 215371.34 | 03-SEP-16:15 |
Boilers:EnergyTransfer | 130.04 | 0.00 | 01-JAN-00:15 | 22800.09 | 12-FEB-07:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8614.36 | 0.000 | 0.000 | 2874.154 | 2771.241 | 10464.601 | 12705.374 | 0.000 | 2998.787 | 74983.252 | 0.000 | -2314.76 | 0.000 | -1041.18 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 5.551 | -1678.59 | 0.000 | 0.000 | 2880.079 | 2771.241 | 10464.601 | 5463.269 | 0.000 | 2793.899 | 0.000 | 0.000 | -932.99 | 0.000 | -954.70 | -2334.41 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 32.469 | -2361.40 | 0.000 | 0.000 | 2889.461 | 2771.241 | 10464.601 | 15257.041 | 0.000 | 2989.810 | 0.186 | 0.000 | -2197.18 | 0.000 | -956.10 | -2895.61 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 41.630 | -1902.02 | 0.000 | 0.000 | 2891.977 | 2771.241 | 10464.601 | 10336.142 | 0.000 | 2999.958 | 0.065 | 0.000 | -2245.21 | 0.000 | -936.03 | -3484.82 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 7.981 | -1420.84 | 0.000 | 0.000 | 2881.658 | 2771.241 | 10464.601 | 2991.042 | 0.000 | 2805.829 | 0.000 | 0.000 | -925.03 | 0.000 | -946.06 | -2989.84 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 34.811 | -2102.71 | 0.000 | 0.000 | 2890.303 | 2771.241 | 10464.601 | 12860.963 | 0.000 | 2997.118 | 0.059 | 0.000 | -2166.26 | 0.000 | -952.86 | -3650.53 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 8.011 | -2389.75 | 0.000 | 0.000 | 2880.072 | 2771.241 | 10464.601 | 12349.899 | 0.000 | 2077.767 | 1452.430 | 0.000 | -2524.59 | 0.000 | -783.26 | -0.04 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.368 | -1948.38 | 0.000 | 0.000 | 2874.840 | 2771.241 | 10464.601 | 5305.239 | 0.000 | 1880.806 | 1877.774 | 0.000 | -1024.87 | 0.000 | -753.85 | -0.06 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6.617 | -2606.08 | 0.000 | 0.000 | 2879.785 | 2771.241 | 10464.601 | 14769.949 | 0.000 | 2071.145 | 1551.932 | 0.000 | -2437.01 | 0.000 | -784.38 | -0.13 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11.658 | -2139.36 | 0.000 | 0.000 | 2881.248 | 2771.241 | 10464.601 | 10022.072 | 0.000 | 2078.386 | 738.608 | 0.000 | -2501.96 | 0.000 | -776.36 | -0.06 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.780 | -1687.46 | 0.000 | 0.000 | 2875.468 | 2771.241 | 10464.601 | 2889.887 | 0.000 | 1886.110 | 1145.533 | 0.000 | -1018.48 | 0.000 | -752.07 | -0.01 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8.016 | -2350.76 | 0.000 | 0.000 | 2880.473 | 2771.241 | 10464.601 | 12429.179 | 0.000 | 2077.198 | 783.200 | 0.000 | -2403.05 | 0.000 | -782.91 | -0.14 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 21.740 | -2675.32 | 0.000 | 0.000 | 2884.335 | 2771.241 | 10464.601 | 12112.731 | 0.000 | 2963.129 | 4379.209 | 0.000 | -2471.01 | 0.000 | -1000.62 | -0.06 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 20.369 | -2855.59 | 0.000 | 0.000 | 2883.782 | 2771.241 | 10464.601 | 14467.356 | 0.000 | 2957.759 | 4218.503 | 0.000 | -2490.90 | 0.000 | -1002.73 | -0.17 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 24.403 | -2652.77 | 0.000 | 0.000 | 2884.763 | 2771.241 | 10464.601 | 12099.852 | 0.000 | 2964.517 | 4206.983 | 0.000 | -2566.84 | 0.000 | -994.95 | -0.03 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 5.550 | -2036.92 | 0.000 | 0.000 | 2878.049 | 2771.241 | 10464.601 | 2792.155 | 0.000 | 2773.649 | 4804.972 | 0.000 | -1048.84 | 0.000 | -982.05 | -0.11 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4.351 | -2222.41 | 0.000 | 0.000 | 2877.506 | 2771.241 | 10464.601 | 5198.087 | 0.000 | 2771.802 | 4634.767 | 0.000 | -1049.59 | 0.000 | -985.98 | -0.04 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 28.108 | -2479.08 | 0.000 | 0.000 | 2885.603 | 2771.241 | 10464.601 | 9755.870 | 0.000 | 2965.599 | 4441.851 | 0.000 | -2556.19 | 0.000 | -987.82 | -0.05 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44223.261 | 0.000 | 0.000 | 0.000 | 0.000 | -139.92 | -44083.34 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5572.749 | 54325.501 | 0.000 | 0.000 | 0.000 | -59898.25 | -0.50 |
Total Facility | 0.000 | 0.000 | 262.414 | -46123.80 | 0.000 | 0.000 | 51873.556 | 49882.340 | 188362.826 | 173806.107 | 0.000 | 96849.277 | 163544.825 | 0.000 | -34874.78 | 0.000 | -76412.08 | -59439.95 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11-OCT-14:25 | 0.00 | 0.00 | 0.00 | -1.7 | 0.00 | 0.00 | 115.18 | 116.28 | 1091.85 | 7994.78 | 0.00 | 1308.70 | 9291.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-JAN-13:45 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.17 | 116.28 | 1109.73 | 3712.32 | 0.00 | 696.86 | 394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15-DEC-11:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 114.03 | 116.28 | 1092.38 | 6774.45 | 0.00 | 1021.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -313.0 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 04-SEP-17:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.38 | 604.65 | 1664.02 | 6858.71 | 0.00 | 1616.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -463.8 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 03-SEP-17:06 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 263.35 | 604.65 | 1685.13 | 758.43 | 0.00 | 1489.97 | 602.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 08-JUL-10:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.03 | 116.28 | 1121.12 | 5872.07 | 0.00 | 1193.89 | 171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 03-SEP-16:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6914.13 | 0.00 | 1194.98 | 659.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 29-JAN-15:15 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.19 | 201.55 | 1168.29 | 3054.88 | 0.00 | 284.47 | 1327.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27-OCT-12:53 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 113.92 | 116.28 | 1090.63 | 4438.10 | 0.00 | 776.25 | 2090.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 05-SEP-17:23 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.35 | 604.65 | 1664.02 | 6334.68 | 0.00 | 1033.61 | 294.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 03-SEP-17:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 263.34 | 604.65 | 1685.13 | 761.56 | 0.00 | 951.69 | 1018.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 08-JUL-10:45 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 114.83 | 116.28 | 1121.12 | 5323.88 | 0.00 | 841.72 | 903.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-JUL-09:49 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.17 | 116.28 | 1096.02 | 6306.83 | 0.00 | 1153.54 | 364.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-OCT-13:15 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.18 | 116.28 | 1084.63 | 4326.58 | 0.00 | 1128.69 | 2850.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 03-SEP-16:19 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.14 | 434.11 | 1371.36 | 6239.69 | 0.00 | 1756.00 | 2529.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 03-SEP-16:34 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 139.18 | 434.11 | 1371.36 | 952.06 | 0.00 | 1576.40 | 2748.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 13-DEC-16:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 139.99 | 434.11 | 1350.56 | 1464.19 | 0.00 | 786.11 | 3637.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 03-SEP-16:05 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.46 | 434.11 | 1371.36 | 6665.87 | 0.00 | 1789.72 | 1961.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-SEP-16:10 | 0.00 | 0.00 | 0.00 | -13.4 | 0.00 | 0.00 | 2507.32 | 7813.98 | 24684.52 | 65154.59 | 0.00 | 41811.43 | 41031.91 | 0.00 | 0.00 | 0.00 | -22627.5 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1113.30 | 0.00 | 0.00 | 0.00 | 526.30 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -788.2 | 0.00 | -1378.1 | -993.2 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-FEB-02:55 | 0.00 | 0.00 | 6601.41 | 0.00 | 0.00 | 0.00 | 545.65 | 62.02 | 868.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1708.8 | 0.00 | -1191.5 | -5176.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 2404.73 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1874.3 | 0.00 | -1456.3 | -1120.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1211.95 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -784.2 | 0.00 | -1378.0 | -1095.8 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-FEB-02:23 | 0.00 | 0.00 | 4188.84 | 0.00 | 0.00 | 0.00 | 544.00 | 62.02 | 868.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1745.0 | 0.00 | -1195.5 | -2722.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1414.32 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1979.1 | 0.00 | -1090.3 | -391.0 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 375.43 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -821.7 | 0.00 | -1011.9 | -587.9 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12-FEB-06:25 | 0.00 | 0.00 | 7169.59 | 0.00 | 0.00 | 0.00 | 548.83 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1745.8 | 0.00 | -975.5 | -6516.9 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-FEB-06:45 | 0.00 | 0.00 | 1593.97 | 0.00 | 0.00 | 0.00 | 528.83 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1888.0 | 0.00 | -1036.3 | -718.2 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 463.04 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -826.1 | 0.00 | -1011.9 | -671.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-FEB-06:00 | 0.00 | 0.00 | 6875.19 | 0.00 | 0.00 | 0.00 | 547.66 | 387.60 | 919.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1635.7 | 0.00 | -881.4 | -6213.2 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-FEB-03:40 | 0.00 | 0.00 | 6218.22 | 0.00 | 0.00 | 0.00 | 544.48 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1725.9 | 0.00 | -1170.0 | -4777.4 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12-FEB-03:50 | 0.00 | 0.00 | 6426.71 | 0.00 | 0.00 | 0.00 | 545.94 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1708.5 | 0.00 | -1160.0 | -5014.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12-FEB-06:20 | 0.00 | 0.00 | 2608.58 | 0.00 | 0.00 | 0.00 | 531.57 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1798.5 | 0.00 | -1286.9 | -1574.6 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1260.74 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -813.8 | 0.00 | -1384.0 | -1109.0 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1214.92 | 0.00 | 0.00 | 0.00 | 526.31 | 434.11 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -804.8 | 0.00 | -1384.0 | -1072.2 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12-FEB-04:00 | 0.00 | 0.00 | 2527.61 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.1 | 0.00 | -1175.6 | -1013.9 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-06:25 | -4939.7 | 0.41 | 30052.52 | -0.4 | 0.00 | 0.00 | 9449.48 | 7813.98 | 19542.30 | 0.00 | 0.00 | 2457.22 | 0.00 | 0.00 | -26226.8 | 0.00 | -24130.8 | -14018.3 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 862.084 | 2.00 | 2.00 | 1.00 | 44.9950 | 862.084 | 0.052 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 216.078 | 2.00 | 2.00 | 1.00 | 44.9950 | 216.078 | 0.208 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 328.389 | 2.00 | 2.00 | 1.00 | 44.9950 | 328.389 | 0.137 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 459.945 | 2.00 | 2.00 | 1.00 | 44.9950 | 459.945 | 0.098 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 215.187 | 2.00 | 2.00 | 1.00 | 44.9950 | 215.187 | 0.209 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 326.511 | 2.00 | 2.00 | 1.00 | 44.9950 | 326.511 | 0.138 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 456.812 | 2.00 | 2.00 | 1.00 | 44.9950 | 456.812 | 0.098 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 217.387 | 2.00 | 2.00 | 1.00 | 44.9950 | 217.387 | 0.207 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.052 | 2.00 | 2.00 | 1.00 | 44.9950 | 321.052 | 0.140 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 451.779 | 2.00 | 2.00 | 1.00 | 44.9950 | 451.779 | 0.100 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 217.589 | 2.00 | 2.00 | 1.00 | 44.9950 | 217.589 | 0.207 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 319.095 | 2.00 | 2.00 | 1.00 | 44.9950 | 319.095 | 0.141 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.747 | 2.00 | 2.00 | 1.00 | 44.9950 | 528.747 | 0.085 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.150 | 2.00 | 2.00 | 1.00 | 44.9950 | 289.150 | 0.156 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.449 | 2.00 | 2.00 | 1.00 | 44.9950 | 354.449 | 0.127 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.221 | 2.00 | 2.00 | 1.00 | 44.9950 | 529.221 | 0.085 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.642 | 2.00 | 2.00 | 1.00 | 44.9950 | 291.642 | 0.154 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.605 | 2.00 | 2.00 | 1.00 | 44.9950 | 352.605 | 0.128 | 1.000 | 44.9950 | 0.13 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 862.084 | 862.0837 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 216.078 | 216.0783 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 328.389 | 328.3893 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 459.945 | 459.9453 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 215.187 | 215.1866 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 326.511 | 326.5115 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 456.812 | 456.8120 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 217.387 | 217.3871 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.052 | 321.0516 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 451.779 | 451.7792 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 217.589 | 217.5887 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 319.095 | 319.0948 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.605 | 352.6051 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.449 | 354.4491 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.747 | 528.7468 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.642 | 291.6422 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.150 | 289.1498 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.221 | 529.2207 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 | 862.084 | 862.08 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 | 216.078 | 216.08 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 | 328.389 | 328.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 | 459.945 | 459.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 | 215.187 | 215.19 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 | 326.511 | 326.51 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 | 456.812 | 456.81 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 | 217.387 | 217.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.052 | 321.05 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 | 451.779 | 451.78 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 | 217.589 | 217.59 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 | 319.095 | 319.09 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.75 | 528.747 | 528.75 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.15 | 289.150 | 289.15 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.45 | 354.449 | 354.45 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.22 | 529.221 | 529.22 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.64 | 291.642 | 291.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.61 | 352.605 | 352.61 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 16.50 |
Number of hours cooling loads not met | 187.50 |
Number of hours not met | 204.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1.63 | 27027.00 | 0.00 | 0.00 |
Space Cooling | 53807.03 | 13624.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 9505.66 | 2312.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2055.40 | 111864.44 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15497.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 169232.02 | 2057.02 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 577828.73 |
Natural Gas | 0.00 | 205702.48 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 783531.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 1.38 |
Fans-Interior | 0.24 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 4.34 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 1.54 |
Miscellaneous | -0.0 |
Subtotal | 1.54 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.37 |
Space Heating | 0.02 |
Space Cooling | 23.45 |
Fans-Interior | 4.14 |
Service Water Heating | 26.23 |
Receptacle Equipment | 38.48 |
Miscellaneous | 1.31 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 352.61 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 354.45 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 528.75 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 291.64 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 289.15 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 529.22 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 528.75 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 289.15 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 354.45 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 529.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 291.64 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 352.61 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 | 2.09 | 0.767124 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 | 0.693432 | 0.685512 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 | 0.954643 | 0.711963 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 | 1.25 | 0.730628 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 | 0.686442 | 0.687043 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 | 0.946977 | 0.712618 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 | 1.20 | 0.740801 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 | 0.666772 | 0.697292 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 0.904180 | 0.721016 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 | 1.19 | 0.740094 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 | 0.665353 | 0.698107 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 | 0.899677 | 0.720691 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 528.75 | 1.40 | 0.739356 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 289.15 | 0.865032 | 0.704019 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 354.45 | 1.04 | 0.710355 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 529.22 | 1.40 | 0.739416 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 291.64 | 0.867710 | 0.705522 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 352.61 | 1.03 | 0.710438 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 | 862.08 | 862.08 | 2.09 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 | 216.08 | 216.08 | 0.693432 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 | 328.39 | 328.39 | 0.954643 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 | 459.95 | 459.95 | 1.25 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 | 215.19 | 215.19 | 0.686442 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 | 326.51 | 326.51 | 0.946977 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 | 456.81 | 456.81 | 1.20 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 | 217.39 | 217.39 | 0.666772 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.05 | 321.05 | 0.904180 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 | 451.78 | 451.78 | 1.19 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 | 217.59 | 217.59 | 0.665353 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 | 319.09 | 319.09 | 0.899677 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 528.75 | 528.75 | 528.75 | 1.40 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 289.15 | 289.15 | 289.15 | 0.865032 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 354.45 | 354.45 | 354.45 | 1.04 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 529.22 | 529.22 | 529.22 | 1.40 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 291.64 | 291.64 | 291.64 | 0.867710 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 352.61 | 352.61 | 352.61 | 1.03 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 47190.77 | 4.76 | 679.57 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 12223.05 | 1.23 | 173.69 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 18301.39 | 1.85 | 261.47 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 25421.58 | 2.57 | 364.21 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 12174.76 | 1.23 | 173.00 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 18199.75 | 1.84 | 260.00 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 25252.43 | 2.55 | 361.70 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 12294.00 | 1.24 | 174.69 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 17904.45 | 1.81 | 255.72 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 24979.89 | 2.52 | 357.81 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 12304.91 | 1.24 | 174.85 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 17798.54 | 1.80 | 254.19 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29145.22 | 2.94 | 417.97 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16177.88 | 1.63 | 230.78 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19711.74 | 1.99 | 281.84 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 29170.84 | 2.94 | 418.34 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16312.77 | 1.65 | 232.72 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19611.94 | 1.98 | 280.40 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 862.08 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 216.08 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 328.39 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 459.95 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 215.19 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 326.51 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 456.81 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 217.39 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 451.78 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 217.59 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 319.09 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 528.75 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 289.15 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 354.45 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 529.22 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 291.64 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 352.61 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.05 | 94.67 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.05 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 375570.67 | 37.77 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 131.549 | 0.000 | 0.000 | 131.549 |
February | 672.000 | 125.237 | 0.000 | 0.000 | 125.237 |
March | 744.000 | 137.077 | 0.000 | 0.000 | 137.077 |
April | 720.000 | 132.601 | 0.000 | 0.000 | 132.601 |
May | 744.000 | 146.785 | 0.000 | 0.000 | 146.785 |
June | 720.000 | 147.842 | 0.000 | 0.000 | 147.842 |
July | 744.000 | 161.331 | 0.000 | 0.000 | 161.331 |
August | 744.000 | 162.136 | 0.000 | 0.000 | 162.136 |
September | 720.000 | 161.231 | 0.000 | 0.000 | 161.231 |
October | 744.000 | 158.074 | 0.000 | 0.000 | 158.074 |
November | 720.000 | 145.575 | 0.000 | 0.000 | 145.575 |
December | 744.000 | 141.438 | 0.000 | 0.000 | 141.438 |
Annual Sum or Average | 8760.000 | 1750.876 | 0.000 | 0.000 | 1750.876 |
Minimum of Months | 672.000 | 125.237 | 0.000 | 0.000 | 125.237 |
Maximum of Months | 744.000 | 162.136 | 0.000 | 0.000 | 162.136 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 596.011 | 20.219 | 0.000 | 0.000 | 20.219 |
February | 549.749 | 19.933 | 8.292 | 0.017 | 19.950 |
March | 605.148 | 20.324 | 3.125 | 0.004 | 20.328 |
April | 671.910 | 19.089 | 0.000 | 0.000 | 19.089 |
May | 735.164 | 25.388 | 0.000 | 0.000 | 25.388 |
June | 720.000 | 27.481 | 0.000 | 0.000 | 27.481 |
July | 744.000 | 33.274 | 0.000 | 0.000 | 33.274 |
August | 744.000 | 34.015 | 0.000 | 0.000 | 34.015 |
September | 720.000 | 35.029 | 0.000 | 0.000 | 35.029 |
October | 737.583 | 34.094 | 0.000 | 0.000 | 34.094 |
November | 681.031 | 28.984 | 0.000 | 0.000 | 28.984 |
December | 690.731 | 25.712 | 0.000 | 0.000 | 25.712 |
Annual Sum or Average | 8195.328 | 323.541 | 11.417 | 0.020 | 323.562 |
Minimum of Months | 549.749 | 19.089 | 0.000 | 0.000 | 19.089 |
Maximum of Months | 744.000 | 35.029 | 8.292 | 0.017 | 35.029 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 540.975 | 27.973 | 0.000 | 0.000 | 28.514 |
February | 500.949 | 26.793 | 7.708 | 0.115 | 28.398 |
March | 572.966 | 29.021 | 2.875 | 0.036 | 31.069 |
April | 615.208 | 30.045 | 0.000 | 0.000 | 30.045 |
May | 711.542 | 40.506 | 0.000 | 0.000 | 40.506 |
June | 715.000 | 42.677 | 0.000 | 0.000 | 42.677 |
July | 744.000 | 50.827 | 0.000 | 0.000 | 50.827 |
August | 742.250 | 52.021 | 0.000 | 0.000 | 52.021 |
September | 720.000 | 49.632 | 0.000 | 0.000 | 49.632 |
October | 719.250 | 49.345 | 0.000 | 0.000 | 49.345 |
November | 659.696 | 39.711 | 0.000 | 0.000 | 39.982 |
December | 638.146 | 34.711 | 0.000 | 0.000 | 34.876 |
Annual Sum or Average | 7879.982 | 473.263 | 10.583 | 0.151 | 477.894 |
Minimum of Months | 500.949 | 26.793 | 0.000 | 0.000 | 28.398 |
Maximum of Months | 744.000 | 52.021 | 7.708 | 0.115 | 52.021 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 476.997 | 16.975 | 9.500 | 0.018 | 17.024 |
February | 464.752 | 22.294 | 21.715 | 0.184 | 23.139 |
March | 544.478 | 26.793 | 23.601 | 0.100 | 27.387 |
April | 595.330 | 27.371 | 0.000 | 0.000 | 27.371 |
May | 709.231 | 39.368 | 0.000 | 0.000 | 39.368 |
June | 715.500 | 43.950 | 0.000 | 0.000 | 43.950 |
July | 744.000 | 52.657 | 0.000 | 0.000 | 52.657 |
August | 742.250 | 51.804 | 0.000 | 0.000 | 51.804 |
September | 720.000 | 51.232 | 0.000 | 0.000 | 51.232 |
October | 714.334 | 42.191 | 0.000 | 0.000 | 42.191 |
November | 643.912 | 32.082 | 5.562 | 0.009 | 32.200 |
December | 603.112 | 24.005 | 4.450 | 0.006 | 24.034 |
Annual Sum or Average | 7673.898 | 430.722 | 64.828 | 0.317 | 432.358 |
Minimum of Months | 464.752 | 16.975 | 0.000 | 0.000 | 17.024 |
Maximum of Months | 744.000 | 52.657 | 23.601 | 0.184 | 52.657 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 554.761 | 11.999 | 0.000 | 0.000 | 11.999 |
February | 526.366 | 13.920 | 11.592 | 0.031 | 13.953 |
March | 593.932 | 16.560 | 3.625 | 0.006 | 16.567 |
April | 672.224 | 17.999 | 0.000 | 0.000 | 17.999 |
May | 736.708 | 26.651 | 0.000 | 0.000 | 26.651 |
June | 720.000 | 29.489 | 0.000 | 0.000 | 29.489 |
July | 744.000 | 34.929 | 0.000 | 0.000 | 34.929 |
August | 744.000 | 34.072 | 0.000 | 0.000 | 34.072 |
September | 720.000 | 32.518 | 0.000 | 0.000 | 32.518 |
October | 736.314 | 28.867 | 0.000 | 0.000 | 28.867 |
November | 672.475 | 22.063 | 0.000 | 0.000 | 22.063 |
December | 673.951 | 17.170 | 0.000 | 0.000 | 17.170 |
Annual Sum or Average | 8094.731 | 286.237 | 15.217 | 0.038 | 286.276 |
Minimum of Months | 526.366 | 11.999 | 0.000 | 0.000 | 11.999 |
Maximum of Months | 744.000 | 34.929 | 11.592 | 0.031 | 34.929 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 529.961 | 19.773 | 0.000 | 0.000 | 20.412 |
February | 492.611 | 20.701 | 9.250 | 0.132 | 22.260 |
March | 570.523 | 25.237 | 2.875 | 0.035 | 27.363 |
April | 615.542 | 28.824 | 0.000 | 0.000 | 28.824 |
May | 712.417 | 41.340 | 0.000 | 0.000 | 41.340 |
June | 715.500 | 44.239 | 0.000 | 0.000 | 44.239 |
July | 744.000 | 52.058 | 0.000 | 0.000 | 52.058 |
August | 742.250 | 51.769 | 0.000 | 0.000 | 51.769 |
September | 720.000 | 46.970 | 0.000 | 0.000 | 46.970 |
October | 719.000 | 44.270 | 0.000 | 0.000 | 44.270 |
November | 657.150 | 32.542 | 0.000 | 0.000 | 32.858 |
December | 632.604 | 26.079 | 0.000 | 0.000 | 26.278 |
Annual Sum or Average | 7851.557 | 433.801 | 12.125 | 0.166 | 438.640 |
Minimum of Months | 492.611 | 19.773 | 0.000 | 0.000 | 20.412 |
Maximum of Months | 744.000 | 52.058 | 9.250 | 0.132 | 52.058 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 612.204 | 31.043 | 0.000 | 0.000 | 31.043 |
February | 560.035 | 32.917 | 8.500 | 0.053 | 33.013 |
March | 616.728 | 35.261 | 3.000 | 0.014 | 35.309 |
April | 682.568 | 33.552 | 0.000 | 0.000 | 33.552 |
May | 737.187 | 42.865 | 0.000 | 0.000 | 42.865 |
June | 720.000 | 45.620 | 0.000 | 0.000 | 45.620 |
July | 744.000 | 54.008 | 0.000 | 0.000 | 54.008 |
August | 744.000 | 55.144 | 0.000 | 0.000 | 55.144 |
September | 720.000 | 57.192 | 0.000 | 0.000 | 57.192 |
October | 737.917 | 52.746 | 0.000 | 0.000 | 52.746 |
November | 684.258 | 44.272 | 0.000 | 0.000 | 44.272 |
December | 695.626 | 38.865 | 0.000 | 0.000 | 38.865 |
Annual Sum or Average | 8254.524 | 523.484 | 11.500 | 0.066 | 523.629 |
Minimum of Months | 560.035 | 31.043 | 0.000 | 0.000 | 31.043 |
Maximum of Months | 744.000 | 57.192 | 8.500 | 0.053 | 57.192 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 710.029 | 25.338 | 0.000 | 0.000 | 25.338 |
February | 627.708 | 24.301 | 1.604 | 0.002 | 24.303 |
March | 684.920 | 24.831 | 0.000 | 0.000 | 24.831 |
April | 717.150 | 23.969 | 0.000 | 0.000 | 23.969 |
May | 744.000 | 29.826 | 0.000 | 0.000 | 29.826 |
June | 720.000 | 30.982 | 0.000 | 0.000 | 30.982 |
July | 744.000 | 36.118 | 0.000 | 0.000 | 36.118 |
August | 744.000 | 36.980 | 0.000 | 0.000 | 36.980 |
September | 720.000 | 37.857 | 0.000 | 0.000 | 37.857 |
October | 744.000 | 38.045 | 0.000 | 0.000 | 38.045 |
November | 707.358 | 32.945 | 0.000 | 0.000 | 32.945 |
December | 729.667 | 30.590 | 0.000 | 0.000 | 30.590 |
Annual Sum or Average | 8592.833 | 371.782 | 1.604 | 0.002 | 371.784 |
Minimum of Months | 627.708 | 23.969 | 0.000 | 0.000 | 23.969 |
Maximum of Months | 744.000 | 38.045 | 1.604 | 0.002 | 38.045 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 623.688 | 32.328 | 0.000 | 0.000 | 32.328 |
February | 566.689 | 30.525 | 1.333 | 0.019 | 31.421 |
March | 630.475 | 32.964 | 0.000 | 0.000 | 33.362 |
April | 687.500 | 34.465 | 0.000 | 0.000 | 34.465 |
May | 738.250 | 44.721 | 0.000 | 0.000 | 44.721 |
June | 720.000 | 45.874 | 0.000 | 0.000 | 45.874 |
July | 744.000 | 53.328 | 0.000 | 0.000 | 53.328 |
August | 744.000 | 54.697 | 0.000 | 0.000 | 54.697 |
September | 720.000 | 52.111 | 0.000 | 0.000 | 52.111 |
October | 738.250 | 52.894 | 0.000 | 0.000 | 52.894 |
November | 687.846 | 43.178 | 0.000 | 0.000 | 43.178 |
December | 701.208 | 39.085 | 0.000 | 0.000 | 39.085 |
Annual Sum or Average | 8301.905 | 516.169 | 1.333 | 0.019 | 517.462 |
Minimum of Months | 566.689 | 30.525 | 0.000 | 0.000 | 31.421 |
Maximum of Months | 744.000 | 54.697 | 1.333 | 0.019 | 54.697 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 575.484 | 21.351 | 0.000 | 0.000 | 21.351 |
February | 541.247 | 26.237 | 9.817 | 0.068 | 26.669 |
March | 606.506 | 30.999 | 3.562 | 0.019 | 31.101 |
April | 682.901 | 32.222 | 0.000 | 0.000 | 32.222 |
May | 738.208 | 44.049 | 0.000 | 0.000 | 44.049 |
June | 720.000 | 47.554 | 0.000 | 0.000 | 47.554 |
July | 744.000 | 55.522 | 0.000 | 0.000 | 55.522 |
August | 744.000 | 54.935 | 0.000 | 0.000 | 54.935 |
September | 720.000 | 54.197 | 0.000 | 0.000 | 54.197 |
October | 736.950 | 46.395 | 0.000 | 0.000 | 46.395 |
November | 677.095 | 36.048 | 0.000 | 0.000 | 36.048 |
December | 682.374 | 28.863 | 0.000 | 0.000 | 28.863 |
Annual Sum or Average | 8168.766 | 478.371 | 13.379 | 0.087 | 478.906 |
Minimum of Months | 541.247 | 21.351 | 0.000 | 0.000 | 21.351 |
Maximum of Months | 744.000 | 55.522 | 9.817 | 0.068 | 55.522 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 692.242 | 17.028 | 0.000 | 0.000 | 17.028 |
February | 615.535 | 18.392 | 2.833 | 0.004 | 18.396 |
March | 679.833 | 21.188 | 0.000 | 0.000 | 21.188 |
April | 717.521 | 22.936 | 0.000 | 0.000 | 22.936 |
May | 744.000 | 31.016 | 0.000 | 0.000 | 31.016 |
June | 720.000 | 32.834 | 0.000 | 0.000 | 32.834 |
July | 744.000 | 37.644 | 0.000 | 0.000 | 37.644 |
August | 744.000 | 37.000 | 0.000 | 0.000 | 37.000 |
September | 720.000 | 35.363 | 0.000 | 0.000 | 35.363 |
October | 744.000 | 32.837 | 0.000 | 0.000 | 32.837 |
November | 703.893 | 26.027 | 0.000 | 0.000 | 26.027 |
December | 720.339 | 22.146 | 0.000 | 0.000 | 22.146 |
Annual Sum or Average | 8545.363 | 334.411 | 2.833 | 0.004 | 334.414 |
Minimum of Months | 615.535 | 17.028 | 0.000 | 0.000 | 17.028 |
Maximum of Months | 744.000 | 37.644 | 2.833 | 0.004 | 37.644 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 617.298 | 24.217 | 0.000 | 0.000 | 24.217 |
February | 561.088 | 24.575 | 1.958 | 0.029 | 25.547 |
March | 628.700 | 29.286 | 0.000 | 0.000 | 29.687 |
April | 688.125 | 33.241 | 0.000 | 0.000 | 33.241 |
May | 738.250 | 45.425 | 0.000 | 0.000 | 45.425 |
June | 720.000 | 47.237 | 0.000 | 0.000 | 47.237 |
July | 744.000 | 54.368 | 0.000 | 0.000 | 54.368 |
August | 744.000 | 54.350 | 0.000 | 0.000 | 54.350 |
September | 720.000 | 49.451 | 0.000 | 0.000 | 49.451 |
October | 738.000 | 47.967 | 0.000 | 0.000 | 47.967 |
November | 686.442 | 36.134 | 0.000 | 0.000 | 36.134 |
December | 698.604 | 30.635 | 0.000 | 0.000 | 30.635 |
Annual Sum or Average | 8284.507 | 476.884 | 1.958 | 0.029 | 478.257 |
Minimum of Months | 561.088 | 24.217 | 0.000 | 0.000 | 24.217 |
Maximum of Months | 744.000 | 54.368 | 1.958 | 0.029 | 54.368 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 560.781 | 32.323 | 0.000 | 0.000 | 32.440 |
February | 523.989 | 35.134 | 10.750 | 0.136 | 36.095 |
March | 584.877 | 38.434 | 3.625 | 0.042 | 39.186 |
April | 645.425 | 36.974 | 0.000 | 0.000 | 36.974 |
May | 729.320 | 49.206 | 0.000 | 0.000 | 49.206 |
June | 720.000 | 52.883 | 0.000 | 0.000 | 52.883 |
July | 744.000 | 63.136 | 0.000 | 0.000 | 63.136 |
August | 744.000 | 63.878 | 0.000 | 0.000 | 63.878 |
September | 720.000 | 65.159 | 0.000 | 0.000 | 65.159 |
October | 731.514 | 58.993 | 0.000 | 0.000 | 58.993 |
November | 668.037 | 48.370 | 0.000 | 0.000 | 48.402 |
December | 661.149 | 41.219 | 0.000 | 0.000 | 41.219 |
Annual Sum or Average | 8033.093 | 585.708 | 14.375 | 0.178 | 587.571 |
Minimum of Months | 523.989 | 32.323 | 0.000 | 0.000 | 32.440 |
Maximum of Months | 744.000 | 65.159 | 10.750 | 0.136 | 65.159 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 646.316 | 27.280 | 0.000 | 0.000 | 27.280 |
February | 597.008 | 27.123 | 6.625 | 0.019 | 27.142 |
March | 652.606 | 28.525 | 2.125 | 0.003 | 28.528 |
April | 702.206 | 27.872 | 0.000 | 0.000 | 27.872 |
May | 742.875 | 36.652 | 0.000 | 0.000 | 36.652 |
June | 720.000 | 38.677 | 0.000 | 0.000 | 38.677 |
July | 744.000 | 45.616 | 0.000 | 0.000 | 45.616 |
August | 744.000 | 46.157 | 0.000 | 0.000 | 46.157 |
September | 720.000 | 46.378 | 0.000 | 0.000 | 46.378 |
October | 743.250 | 45.176 | 0.000 | 0.000 | 45.176 |
November | 693.985 | 38.014 | 0.000 | 0.000 | 38.014 |
December | 711.573 | 33.981 | 0.000 | 0.000 | 33.981 |
Annual Sum or Average | 8417.819 | 441.451 | 8.750 | 0.022 | 441.473 |
Minimum of Months | 597.008 | 27.123 | 0.000 | 0.000 | 27.142 |
Maximum of Months | 744.000 | 46.378 | 6.625 | 0.019 | 46.378 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 585.766 | 32.680 | 0.000 | 0.000 | 32.832 |
February | 539.698 | 31.766 | 6.042 | 0.083 | 32.926 |
March | 605.528 | 34.920 | 2.125 | 0.022 | 35.655 |
April | 660.792 | 36.557 | 0.000 | 0.000 | 36.557 |
May | 731.292 | 49.000 | 0.000 | 0.000 | 49.000 |
June | 720.000 | 50.901 | 0.000 | 0.000 | 50.901 |
July | 744.000 | 59.741 | 0.000 | 0.000 | 59.741 |
August | 744.000 | 60.796 | 0.000 | 0.000 | 60.796 |
September | 720.000 | 57.592 | 0.000 | 0.000 | 57.592 |
October | 732.875 | 57.123 | 0.000 | 0.000 | 57.123 |
November | 674.800 | 45.666 | 0.000 | 0.000 | 45.692 |
December | 669.242 | 40.212 | 0.000 | 0.000 | 40.212 |
Annual Sum or Average | 8127.993 | 556.952 | 8.167 | 0.105 | 559.027 |
Minimum of Months | 539.698 | 31.766 | 0.000 | 0.000 | 32.832 |
Maximum of Months | 744.000 | 60.796 | 6.042 | 0.083 | 60.796 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 531.574 | 25.015 | 3.000 | 0.005 | 25.024 |
February | 511.370 | 30.619 | 16.047 | 0.155 | 31.462 |
March | 580.583 | 36.145 | 10.250 | 0.056 | 36.538 |
April | 646.748 | 36.448 | 0.000 | 0.000 | 36.448 |
May | 731.271 | 50.137 | 0.000 | 0.000 | 50.137 |
June | 720.000 | 54.263 | 0.000 | 0.000 | 54.263 |
July | 744.000 | 64.281 | 0.000 | 0.000 | 64.281 |
August | 744.000 | 64.080 | 0.000 | 0.000 | 64.080 |
September | 720.000 | 63.659 | 0.000 | 0.000 | 63.659 |
October | 730.263 | 55.037 | 0.000 | 0.000 | 55.037 |
November | 662.136 | 42.099 | 0.250 | 0.001 | 42.163 |
December | 644.023 | 33.255 | 0.000 | 0.000 | 33.262 |
Annual Sum or Average | 7965.968 | 555.039 | 29.547 | 0.217 | 556.354 |
Minimum of Months | 511.370 | 25.015 | 0.000 | 0.000 | 25.024 |
Maximum of Months | 744.000 | 64.281 | 16.047 | 0.155 | 64.281 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 618.975 | 20.568 | 0.000 | 0.000 | 20.568 |
February | 585.080 | 22.926 | 8.667 | 0.025 | 22.951 |
March | 649.174 | 26.526 | 2.375 | 0.003 | 26.529 |
April | 702.527 | 27.498 | 0.000 | 0.000 | 27.498 |
May | 743.250 | 37.651 | 0.000 | 0.000 | 37.651 |
June | 720.000 | 40.093 | 0.000 | 0.000 | 40.093 |
July | 744.000 | 46.855 | 0.000 | 0.000 | 46.855 |
August | 744.000 | 46.541 | 0.000 | 0.000 | 46.541 |
September | 720.000 | 45.210 | 0.000 | 0.000 | 45.210 |
October | 743.250 | 41.798 | 0.000 | 0.000 | 41.798 |
November | 689.078 | 32.397 | 0.000 | 0.000 | 32.397 |
December | 700.939 | 26.795 | 0.000 | 0.000 | 26.795 |
Annual Sum or Average | 8360.274 | 414.858 | 11.042 | 0.028 | 414.887 |
Minimum of Months | 585.080 | 20.568 | 0.000 | 0.000 | 20.568 |
Maximum of Months | 744.000 | 46.855 | 8.667 | 0.025 | 46.855 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 577.241 | 26.480 | 0.000 | 0.000 | 26.691 |
February | 533.714 | 27.744 | 6.458 | 0.088 | 28.961 |
March | 604.355 | 32.950 | 2.125 | 0.022 | 33.724 |
April | 660.958 | 36.026 | 0.000 | 0.000 | 36.026 |
May | 731.542 | 49.520 | 0.000 | 0.000 | 49.520 |
June | 720.000 | 51.793 | 0.000 | 0.000 | 51.793 |
July | 744.000 | 60.461 | 0.000 | 0.000 | 60.461 |
August | 744.000 | 60.801 | 0.000 | 0.000 | 60.801 |
September | 720.000 | 56.283 | 0.000 | 0.000 | 56.283 |
October | 732.875 | 54.095 | 0.000 | 0.000 | 54.095 |
November | 672.500 | 40.388 | 0.000 | 0.000 | 40.418 |
December | 666.579 | 33.513 | 0.000 | 0.000 | 33.516 |
Annual Sum or Average | 8107.763 | 530.054 | 8.583 | 0.110 | 532.289 |
Minimum of Months | 533.714 | 26.480 | 0.000 | 0.000 | 26.691 |
Maximum of Months | 744.000 | 60.801 | 6.458 | 0.088 | 60.801 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 1.08 |
February | 0.00 | 0.00 | 1.15 |
March | 0.00 | 0.00 | 1.13 |
April | 0.00 | 0.00 | 1.12 |
May | 0.00 | 0.00 | 1.20 |
June | 0.00 | 0.00 | 1.26 |
July | 0.00 | 0.00 | 1.33 |
August | 0.00 | 0.00 | 1.33 |
September | 0.00 | 0.00 | 1.38 |
October | 0.00 | 0.00 | 1.30 |
November | 0.00 | 0.00 | 1.25 |
December | 0.00 | 0.00 | 1.17 |
Annual Sum or Average | 0.00 | 0.00 | 1.23 |
Minimum of Months | 0.00 | 0.00 | 1.08 |
Maximum of Months | 0.00 | 0.00 | 1.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.22 |
February | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.39 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.00 | 0.42 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.15 |
February | 0.00 | 0.00 | 0.23 |
March | 0.00 | 0.00 | 0.24 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.30 |
December | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.15 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.18 |
April | 0.00 | 0.00 | 0.20 |
May | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.13 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.23 |
March | 0.00 | 0.00 | 0.25 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.00 | 0.00 | 0.42 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.31 |
February | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.22 |
March | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.23 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.28 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.00 | 0.45 |
December | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.33 |
February | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.58 |
November | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.22 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.00 | 0.00 | 0.59 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.21 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.26 |
February | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.00 | 0.33 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.00 | 0.55 |
November | 0.00 | 0.00 | 0.42 |
December | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |
Maximum of Months | 0.00 | 0.00 | 1106.29 | 823.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1106.29 | 823.67 |
February | 0.00 | 0.00 | 1102.04 | 741.09 |
March | 0.00 | 0.00 | 1078.75 | 803.16 |
April | 0.00 | 0.00 | 1047.23 | 754.54 |
May | 0.00 | 0.00 | 1012.22 | 753.63 |
June | 0.00 | 0.00 | 987.17 | 711.26 |
July | 0.00 | 0.00 | 976.61 | 727.11 |
August | 0.00 | 0.00 | 983.09 | 731.94 |
September | 0.00 | 0.00 | 1006.53 | 725.22 |
October | 0.00 | 0.00 | 1037.74 | 772.63 |
November | 0.00 | 0.00 | 1071.99 | 772.38 |
December | 0.00 | 0.00 | 1099.34 | 818.49 |
Annual Sum or Average | 0.00 | 0.00 | 1042.08 | 9135.11 |
Minimum of Months | 0.00 | 0.00 | 976.61 | 711.26 |