Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32

Tabular Output Report in Format: HTML

Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+gasfurnace+heatedbsmt+IECC_2012

Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780

Simulation Timestamp: 2019-02-14 08:32:38


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 954736.55 24.48 32.47
Net Site Energy 954736.55 24.48 32.47
Total Source Energy 2163539.75 55.47 73.58
Net Source Energy 2163539.75 55.47 73.58


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 46151.78 0.00 0.00 0.00 0.00
Cooling 186285.60 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 261812.16 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 40786.48 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 202794.33 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 541817.25 412919.31 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 46151.78 0.00 0.00 0.00 0.00
Cooling General 186285.60 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 40786.48 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 202794.33 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.80 0.00 0.00 0.00 0.00 0.00
HVAC 7.72 8.47 0.00 0.00 0.00 12.85
Other 8.90 5.58 0.00 0.00 0.00 0.00
Total 18.43 14.04 0.00 0.00 0.00 12.85


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 5.82 6.38 0.00 0.00 0.00 9.68
Other 6.71 4.20 0.00 0.00 0.00 0.00
Total 13.89 10.59 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 541817.248 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 541817.248 100.00
     
Total On-Site and Utility Electric Sources 541817.248 100.00
Total Electricity End Uses 541817.248 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 147.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 48.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
RunPeriod ANNUAL
Weather File Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Latitude [deg] 33.45
Longitude [deg] -112.0
Elevation [ft] 1105.70
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.3689 1083.48 2.4729
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.4894 816.79 3.2803
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 16-JUL-19:15 31-JAN-07:30 - - - 07-JAN-08:15
Heating 0.00 91.34 0.00 0.00 0.00 0.00
Cooling 69.58 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.15 0.00 0.00 0.00 0.00 0.00
Interior Equipment 42.91 16.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 12.24 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 147.20 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 141.28 254.95 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 91.34 0.00 0.00 0.00 0.00
Cooling General 69.58 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.53 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.03 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.62 6.47 0.00 0.00 0.00 0.00
  gas_range 0.00 7.84 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 23.39 2.10 0.00 0.00 0.00 0.00
  IECC_adj 9.69 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 12.24 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 147.20 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 50028.53 0.00 0.00 0.00
Cooling 589966.50 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 829159.12 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 129170.77 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 219829.06 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1715935.23 447604.53 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 1.70 0.00 0.00 0.00
Cooling 20.06 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 28.20 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.39 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.48 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 58.36 15.22 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 1.70 0.00 0.00 0.00
Cooling 20.06 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 28.20 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.39 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.48 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 58.36 15.22 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 38.66 0.00 38.66 Wetbulb [F] 334.66 100.00
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 110.12 21.60 69.98 Wetbulb [F] 807.13 260.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.400 0.219 0.882              
North Total or Average           531.68 0.400 0.219 0.882              
Non-North Total or Average           1595.05 0.400 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   26525.49 21005.50 5519.99 0.79 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10821.07 8302.07 2519.00 0.77 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13574.88 10242.68 3332.20 0.75 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15651.02 12195.74 3455.28 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10518.77 8124.45 2394.32 0.77 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12574.35 9692.02 2882.33 0.77 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15376.73 11974.30 3402.42 0.78 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10305.22 7927.71 2377.51 0.77 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12461.56 9602.08 2859.48 0.77 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15183.98 11817.42 3366.56 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10161.53 7840.94 2320.59 0.77 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12187.11 9414.38 2772.73 0.77 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17740.68 13896.70 3843.98 0.78 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12616.18 9835.95 2780.23 0.78 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14692.93 11459.33 3233.59 0.78 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17744.45 13899.77 3844.68 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12643.85 9858.57 2785.29 0.78 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14699.65 11464.82 3234.83 0.78 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   14706.23 11218.96 3487.27 0.76 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.1 3.27 11.16 11.82 11.34
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.32 11.32 11.99 11.59
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.1 3.34 11.40 12.08 11.72
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.2 3.30 11.24 11.91 11.47
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.8 3.31 11.29 11.96 11.54
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.0 3.31 11.30 11.97 11.55
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.30 11.25 11.91 11.47
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.31 11.31 11.98 11.57
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.0 3.31 11.30 11.97 11.56
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.2 3.30 11.25 11.91 11.48
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.31 11.29 11.96 11.55
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.0 3.31 11.29 11.96 11.54
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.4 3.29 11.22 11.88 11.43
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.0 3.29 11.24 11.91 11.46
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.2 3.29 11.24 11.90 11.46
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.4 3.29 11.22 11.88 11.43
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.0 3.29 11.24 11.90 11.46
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.2 3.29 11.24 11.90 11.46
DX COOLING COIL_UNITHEATEDBSMT   1.2 3.33 11.35 12.02 11.64
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   3900.50 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   4987.90 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   6468.57 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   6478.21 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   5110.35 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   6472.42 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   5685.48 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   4584.15 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   6002.78 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   6007.11 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   4612.91 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   6002.22 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   7477.64 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   6113.51 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   7521.94 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   7523.99 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   6119.67 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   7520.48 0.80
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel   7550.64 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 976.71 368.41 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 371.19 140.01 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 448.09 169.02 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 556.06 209.74 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 366.37 138.19 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 435.91 164.42 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 545.53 205.77 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 355.68 134.16 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 431.69 162.83 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 538.00 202.93 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 353.15 133.21 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 424.61 160.16 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 637.72 240.54 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 448.76 169.27 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 523.06 197.30 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 637.87 240.60 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 449.85 169.68 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 523.33 197.39 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 497.95 187.82 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 22045.94 22045.94 18.36 976.711 976.711 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00803 105.48 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8378.45 8378.45 6.98 371.195 371.195 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00808 104.13 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10114.34 10114.34 8.42 448.095 448.095 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00798 110.12 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12551.28 12551.28 10.45 556.065 556.065 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00804 104.94 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8269.43 8269.43 6.89 366.366 366.366 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00812 102.51 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9839.19 9839.19 8.20 435.910 435.910 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00805 104.94 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12313.53 12313.53 10.26 545.534 545.534 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00807 104.94 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8028.29 8028.29 6.69 355.684 355.684 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00816 102.51 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9743.98 9743.98 8.12 431.693 431.693 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00808 104.94 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12143.57 12143.57 10.11 538.004 538.004 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00807 104.94 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7971.09 7971.09 6.64 353.150 353.150 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00816 101.70 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9584.11 9584.11 7.98 424.611 424.611 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00810 104.13 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11812.29 11812.29 9.84 523.326 523.326 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00806 104.13 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11806.34 11806.34 9.83 523.062 523.062 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00806 104.13 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14394.35 14394.35 11.99 637.719 637.719 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00804 104.94 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 10153.69 10153.69 8.46 449.846 449.846 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00810 102.51 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 10129.07 10129.07 8.44 448.755 448.755 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00810 102.51 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14397.67 14397.67 11.99 637.867 637.867 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00804 104.94 0.00720 44.995 0.00
HEATEDBSMT 11239.62 11239.62 1.44 497.952 497.952 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 74.98 74.98 0.00800 108.82 0.00720 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3478.53 3478.53 2.90 65.900 65.900 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00684 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4981.12 4981.12 4.15 94.365 94.365 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00699 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4990.90 4990.90 4.16 94.550 94.550 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00699 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3602.80 3602.80 3.00 68.254 68.254 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00686 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4985.03 4985.03 4.15 94.439 94.439 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00699 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4186.40 4186.40 3.49 79.311 79.311 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00712 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3068.76 3068.76 2.56 58.138 58.138 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 10:00:00 72.00 71.99 0.00708 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4508.39 4508.39 3.76 85.411 85.411 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00716 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4512.79 4512.79 3.76 85.494 85.494 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00716 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3097.95 3097.95 2.58 58.691 58.691 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 10:15:00 72.00 71.99 0.00707 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4507.83 4507.83 3.75 85.401 85.401 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00716 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6048.59 6048.59 5.04 114.587 114.587 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6050.07 6050.07 5.04 114.615 114.615 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6005.11 6005.11 5.00 113.764 113.764 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4627.05 4627.05 3.85 87.658 87.658 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00699 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4620.79 4620.79 3.85 87.539 87.539 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00699 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6052.15 6052.15 5.04 114.655 114.655 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
HEATEDBSMT 6078.99 6078.99 0.78 115.173 115.173 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 06:30:00 72.00 72.00 0.00800 38.66 0.00513 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 976.71 976.71 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 371.19 371.19 65.90 65.90
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 448.09 448.09 94.37 94.37
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 556.06 556.06 94.55 94.55
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 366.37 366.37 68.25 68.25
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 435.91 435.91 94.44 94.44
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 545.53 545.53 79.31 79.31
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 355.68 355.68 58.14 58.14
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 431.69 431.69 85.41 85.41
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 538.00 538.00 85.49 85.49
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 353.15 353.15 58.69 58.69
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 424.61 424.61 85.40 85.40
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 637.72 637.72 113.76 113.76
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 448.76 448.76 87.54 87.54
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 523.06 523.06 114.62 114.62
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 637.87 637.87 114.65 114.65
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 449.85 449.85 87.66 87.66
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 523.33 523.33 114.59 114.59
CENTRAL SYSTEM_UNITHEATEDBSMT 497.95 497.95 115.17 115.17


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3000.75 3056.25 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2571.75 2916.00 31.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3218.25 2902.25 32.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2941.25 3658.50 41.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2259.00 3775.75 35.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2973.25 3534.50 36.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3521.75 2809.00 17.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2826.50 2598.50 6.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3504.75 2666.25 14.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3144.50 3419.75 20.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2472.75 3433.75 9.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3167.50 3299.25 17.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3446.75 3286.75 26.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 3657.50 2854.00 25.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 3632.25 3030.75 29.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2917.50 3424.25 24.25
LIVING_UNIT2_FRONTROW_TOPFLOOR 3118.00 2896.75 23.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3423.00 3415.50 30.75
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4091.50 4070.25 48.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 103.75 0.00 103.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 36.00 0.00 36.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 7.50 0.00 7.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 68.75 0.00 68.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 46.50 0.00 46.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 37.25 0.00 37.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 59.50 0.00 59.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 31.75 0.00 31.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 29.25 0.00 29.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 58.25 0.00 58.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 31.00 0.00 31.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 28.75 0.00 28.75
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 73.75 0.00 73.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 74.00 0.00 74.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 87.50 0.00 87.50
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 72.75 0.00 72.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 74.25 0.00 74.25
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 89.50 0.00 89.50
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 147.75 0.00 147.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.147 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.128 0.000 0.265
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.265
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.265
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.128 0.000 0.265
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.265
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.265
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.265
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.265
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.265
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.265
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.265
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.265
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.265
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.265
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.128 0.000 0.265
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.128 0.000 0.265
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.265
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1900
Defaulted Fields 509
Fields with Defaults 4982
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
Electricity:Building 89625.89 7014.87 02-JAN-03:15 16912.36 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 76678.43 6519.25 02-JAN-04:15 12694.94 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
Fans:Electricity 11945.37 110.80 04-APR-01:00 3591.46 16-JUL-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
ElectricityPurchased:Plant 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
Cogeneration:ElectricityPurchased 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
ElectricityNet:Plant 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
Cogeneration:ElectricityNet 158685.13 8057.34 05-APR-03:45 41377.51 16-JUL-19:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 66503.90 522.58 04-APR-01:15 24356.04 16-JUL-18:00
General:Fans:Electricity 11945.37 110.80 04-APR-01:00 3591.46 16-JUL-17:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 54558.53 134.89 31-JAN-07:30 20764.58 16-JUL-18:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 4129.19 2644.47 05-APR-03:15 254766.28 31-JAN-07:30
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 2027.94 0.00 01-JAN-00:15 147477.13 21-JAN-09:00
WaterSystems:Gas 2027.94 0.00 01-JAN-00:15 147477.13 21-JAN-09:00
Water Heater:WaterSystems:Gas 2027.94 0.00 01-JAN-00:15 147477.13 21-JAN-09:00
Gas:HVAC 461.52 0.00 23-FEB-15:45 93543.21 31-JAN-07:15
Heating:Gas 461.52 0.00 23-FEB-15:45 93543.21 31-JAN-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
Water:Plant 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
MainsWater:Plant 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 07-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
PlantLoopHeatingDemand:Plant 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
WaterSystems:PlantLoopHeatingDemand 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1508803.72 16020.59 05-APR-02:45 453195.63 10-AUG-18:30
EnergyTransfer:Building 677518.28 7087.01 04-APR-01:00 215853.76 02-JUL-18:45
EnergyTransfer:Zone:HEATEDBSMT 38707.59 0.00 23-FEB-15:45 11404.33 16-JUL-18:30
Heating:EnergyTransfer 40476.69 0.00 23-FEB-15:45 82142.71 31-JAN-07:15
Heating:EnergyTransfer:Zone:HEATEDBSMT 7937.93 0.00 23-FEB-15:45 6291.80 31-JAN-07:15
Cooling:EnergyTransfer 637041.59 2458.09 31-JAN-07:30 215853.76 02-JUL-18:45
Cooling:EnergyTransfer:Zone:HEATEDBSMT 30769.67 0.00 01-JAN-00:15 11404.33 16-JUL-18:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 105931.14 2458.09 31-JAN-07:30 21935.94 04-JUN-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 105931.14 2458.09 31-JAN-07:30 21935.94 04-JUN-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 26977.27 0.00 01-JAN-00:15 8751.80 02-JUL-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1055.38 0.00 01-JAN-00:15 3286.56 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 25921.89 0.00 01-JAN-00:15 8751.80 02-JUL-19:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 33813.32 0.00 01-JAN-00:15 10770.47 16-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1959.44 0.00 01-JAN-00:15 4920.35 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31853.89 0.00 01-JAN-00:15 10770.47 16-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 30953.30 0.00 01-JAN-00:15 12770.91 18-JUN-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2750.60 0.00 01-JAN-00:15 5046.74 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 28202.70 0.00 01-JAN-00:15 12770.91 18-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23397.18 0.00 01-JAN-00:15 8595.61 16-JUL-21:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1625.85 0.00 01-JAN-00:15 3647.66 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21771.33 0.00 01-JAN-00:15 8595.61 16-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 30222.13 0.00 01-JAN-00:15 10189.58 16-JUL-20:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2432.79 0.00 01-JAN-00:15 4968.41 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 27789.33 0.00 01-JAN-00:15 10189.58 16-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 34102.33 0.00 01-JAN-00:15 12675.60 29-SEP-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1337.26 0.00 01-JAN-00:15 3868.56 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 32765.07 0.00 01-JAN-00:15 12675.60 29-SEP-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27032.86 0.00 01-JAN-00:15 8418.05 16-JUL-20:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 628.68 0.00 01-JAN-00:15 2673.64 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26404.18 0.00 01-JAN-00:15 8418.05 16-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 33732.41 0.00 01-JAN-00:15 10072.96 16-JUL-20:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1355.04 0.00 01-JAN-00:15 4257.21 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 32377.37 0.00 01-JAN-00:15 10072.96 16-JUL-20:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 30598.90 0.00 01-JAN-00:15 12425.10 18-JUN-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2035.86 0.00 01-JAN-00:15 4436.32 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 28563.04 0.00 01-JAN-00:15 12425.10 18-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23180.82 0.00 01-JAN-00:15 8337.13 16-JUL-21:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1034.29 0.00 01-JAN-00:15 3006.42 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 22146.53 0.00 01-JAN-00:15 8337.13 16-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 30016.56 0.00 01-JAN-00:15 9944.63 16-JUL-20:45
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1767.19 0.00 01-JAN-00:15 4315.63 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 28249.37 0.00 01-JAN-00:15 9944.63 16-JUL-20:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 35818.46 0.00 01-JAN-00:15 11991.23 16-JUL-21:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2875.70 0.00 01-JAN-00:15 5919.08 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 32942.76 0.00 01-JAN-00:15 11991.23 16-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 37847.27 0.00 01-JAN-00:15 11981.71 16-JUL-21:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2355.45 0.00 01-JAN-00:15 5873.19 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 35491.82 0.00 01-JAN-00:15 11981.71 16-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 38518.73 0.00 01-JAN-00:15 14486.32 27-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2602.05 0.00 01-JAN-00:15 5754.81 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 35916.68 0.00 01-JAN-00:15 14486.32 27-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 28986.43 0.00 01-JAN-00:15 10427.45 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2018.11 0.00 01-JAN-00:15 4578.35 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 26968.32 0.00 01-JAN-00:15 10427.45 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 31078.82 0.00 01-JAN-00:15 10404.19 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1477.04 0.00 01-JAN-00:15 4283.58 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 29601.78 0.00 01-JAN-00:15 10404.19 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 36602.75 0.00 01-JAN-00:15 14532.52 04-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 3228.03 0.00 01-JAN-00:15 6029.00 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 33374.72 0.00 01-JAN-00:15 14532.52 04-JUN-18:15
EnergyTransfer:Plant 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
WaterSystems:EnergyTransfer 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 84127.29 388.56 21-JUL-03:00 28620.89 21-JAN-08:30
EnergyTransfer:HVAC 747158.16 7465.05 04-APR-01:00 248534.53 10-AUG-18:45
HeatingCoils:EnergyTransfer 36921.42 0.00 23-FEB-15:45 74834.56 31-JAN-07:15
CoolingCoils:EnergyTransfer 710236.73 2587.78 31-JAN-07:30 248534.53 10-AUG-18:45



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -8821.70 0.000 0.000 2872.377 2456.001 14468.945 11942.923 0.000 4762.186 77486.073 0.000 -2963.37 0.000 -5094.02 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 1055.373 -2158.72 0.000 0.000 2925.578 2456.001 14468.945 5106.969 0.000 4544.493 1025.088 0.000 -1147.13 0.000 -4513.41 -0.35
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 1959.418 -2652.72 0.000 0.000 2938.825 2456.001 14468.945 11915.410 0.000 4770.234 714.646 0.000 -2703.25 0.000 -4666.35 -0.13
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 2750.578 -2348.66 0.000 0.000 2947.420 2456.001 14468.945 9113.207 0.000 4765.148 0.133 0.000 -2947.59 0.000 -4536.42 -814.57
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 1625.837 -1813.07 0.000 0.000 2938.804 2456.001 14468.945 2078.393 0.000 4543.874 0.069 0.000 -1224.85 0.000 -4379.71 -735.92
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 2432.774 -2314.23 0.000 0.000 2949.905 2456.001 14468.945 8908.413 0.000 4767.696 0.172 0.000 -2691.62 0.000 -4552.07 -950.70
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 1337.245 -2728.60 0.000 0.000 2926.682 2456.001 14468.945 11985.776 0.000 3707.378 2544.649 0.000 -2912.75 0.000 -3748.85 -0.03
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 628.669 -2198.88 0.000 0.000 2912.626 2456.001 14468.945 5103.909 0.000 3486.026 2126.552 0.000 -1172.77 0.000 -3605.74 -0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 1355.026 -2696.31 0.000 0.000 2927.354 2456.001 14468.945 11897.910 0.000 3709.048 2093.529 0.000 -2764.99 0.000 -3765.44 -0.14
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 2035.846 -2378.67 0.000 0.000 2936.256 2456.001 14468.945 9122.378 0.000 3707.878 513.454 0.000 -3011.70 0.000 -3665.98 -0.06
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 1034.277 -1844.32 0.000 0.000 2925.515 2456.001 14468.945 2090.732 0.000 3486.076 444.607 0.000 -1250.85 0.000 -3508.70 -0.04
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 1767.179 -2352.54 0.000 0.000 2939.173 2456.001 14468.945 8904.876 0.000 3709.007 429.098 0.000 -2747.08 0.000 -3677.80 -0.32
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 2875.678 -2743.40 0.000 0.000 2945.738 2456.001 14468.945 8843.416 0.000 4744.864 3936.052 0.000 -2745.74 0.000 -4582.16 -0.02
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 2355.428 -2955.68 0.000 0.000 2936.622 2456.001 14468.945 11862.626 0.000 4744.834 4086.284 0.000 -2745.97 0.000 -4672.93 -0.30
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 2602.026 -2991.06 0.000 0.000 2937.236 2456.001 14468.945 11960.188 0.000 4743.340 4268.421 0.000 -2878.08 0.000 -4641.37 -0.07
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 2018.087 -2245.86 0.000 0.000 2935.236 2456.001 14468.945 2064.492 0.000 4523.142 4159.418 0.000 -1243.04 0.000 -4413.89 -0.13
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 1477.022 -2465.17 0.000 0.000 2925.440 2456.001 14468.945 5089.451 0.000 4522.739 4332.404 0.000 -1160.81 0.000 -4509.36 -0.30
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 3227.997 -2779.37 0.000 0.000 2943.760 2456.001 14468.945 9047.541 0.000 4743.846 4049.105 0.000 -2992.03 0.000 -4570.40 -0.26
HEATEDBSMT 0.000 0.000 7937.927 -2562.43 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22831.739 0.000 0.000 0.000 0.000 -0.28
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7488.830 52476.666 0.000 0.000 0.000 -59965.50 -0.48
Total Facility 0.000 0.000 40476.388 -53051.38 0.000 0.000 52764.546 44208.020 260441.015 147038.609 0.000 85470.639 187518.161 0.000 -41303.59 0.000 -137070.10 -2504.12


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 04-JUN-17:18 0.00 0.00 0.00 -1.8 0.00 0.00 263.02 535.87 2778.60 6118.21 0.00 2304.02 9957.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-JUL-19:03 0.00 0.00 0.00 -0.7 0.00 0.00 425.59 799.44 2339.22 537.75 0.00 2365.47 2356.91 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16-JUL-19:30 0.00 0.00 0.00 -0.9 0.00 0.00 422.10 799.44 2339.22 1458.37 0.00 2680.98 3086.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18-JUN-19:18 0.00 0.00 0.00 -1.1 0.00 0.00 425.40 799.44 2339.22 2192.45 0.00 2090.18 4954.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 02-JUL-19:21 0.00 0.00 0.00 -0.7 0.00 0.00 424.14 799.44 2339.22 489.61 0.00 2163.04 2455.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16-JUL-20:35 0.00 0.00 0.00 -0.9 0.00 0.00 424.80 799.44 2186.99 1108.13 0.00 2103.87 3620.08 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-SEP-17:03 0.00 0.00 0.00 -1.1 0.00 0.00 263.32 535.87 2749.11 5350.94 0.00 1463.74 2313.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16-JUL-20:35 0.00 0.00 0.00 -0.7 0.00 0.00 424.59 799.44 2186.99 465.18 0.00 1518.14 3032.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-JUL-20:19 0.00 0.00 0.00 -0.8 0.00 0.00 425.50 799.44 2186.99 1180.51 0.00 1688.09 3810.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 18-JUN-19:18 0.00 0.00 0.00 -1.0 0.00 0.00 424.46 799.44 2339.22 2209.02 0.00 1559.47 5128.33 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16-JUL-21:10 0.00 0.00 0.00 -0.7 0.00 0.00 474.01 604.57 2054.44 435.27 0.00 1456.19 3330.26 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16-JUL-20:35 0.00 0.00 0.00 -0.8 0.00 0.00 422.01 799.44 2186.99 1114.25 0.00 1610.26 3825.52 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 02-JUL-19:21 0.00 0.00 0.00 -1.0 0.00 0.00 423.71 799.44 2339.22 1151.10 0.00 2288.56 5090.57 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 02-JUL-19:18 0.00 0.00 0.00 -1.0 0.00 0.00 424.61 799.44 2339.22 1132.50 0.00 2285.13 5065.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 27-AUG-17:18 0.00 0.00 0.00 -1.2 0.00 0.00 259.33 535.87 2778.60 6054.19 0.00 2209.93 2688.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 02-JUL-19:33 0.00 0.00 0.00 -0.9 0.00 0.00 424.99 799.44 2339.22 427.47 0.00 1961.73 4548.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUL-19:33 0.00 0.00 0.00 -0.9 0.00 0.00 425.47 799.44 2339.22 410.36 0.00 1964.26 4540.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 04-JUN-18:03 0.00 0.00 0.00 -1.2 0.00 0.00 427.02 721.37 2685.69 5177.93 0.00 2203.02 3330.16 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 16-JUL-18:34 0.00 0.00 0.00 -1.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11435.29 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JUL-18:51 0.00 0.00 0.00 -18.0 0.00 0.00 7589.06 12984.58 48342.42 27549.48 0.00 43174.15 82009.81 0.00 0.00 0.00 -5688.9 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 3286.62 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -745.8 0.00 -2912.0 -2113.3
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 4920.44 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1818.5 0.00 -3068.7 -2517.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31-JAN-08:08 0.00 0.00 5046.61 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1552.5 0.00 -2979.9 -2493.8
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 31-JAN-08:08 0.00 0.00 3647.56 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -636.6 0.00 -2829.5 -2161.1
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 4968.50 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1816.1 0.00 -3068.7 -2568.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 3868.66 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1845.5 0.00 -2333.8 -2173.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 31-JAN-08:08 0.00 0.00 2673.58 0.00 0.00 0.00 215.05 151.14 1613.42 105.68 0.00 0.00 0.00 0.00 0.00 0.00 -2123.5 -2635.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 4257.32 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1835.5 0.00 -2333.8 -2572.5
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31-JAN-08:08 0.00 0.00 4436.22 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1565.8 0.00 -2274.1 -2575.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 31-JAN-08:08 0.00 0.00 3006.35 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -643.8 0.00 -2123.5 -2218.7
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 4315.74 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1830.4 0.00 -2333.8 -2635.9
LIVING_UNIT3_BACKROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 5919.19 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1814.5 0.00 -3075.2 -3513.9
LIVING_UNIT3_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 5873.30 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1820.1 0.00 -3075.2 -3462.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 5754.92 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -1817.5 0.00 -3075.2 -3346.6
LIVING_UNIT2_BACKROW_TOPFLOOR 31-JAN-08:08 0.00 0.00 4578.23 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -636.3 0.00 -2835.5 -3086.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 4283.66 0.00 0.00 0.00 464.78 343.51 1676.14 0.00 0.00 0.00 0.00 0.00 -743.8 0.00 -2918.2 -3106.2
LIVING_UNIT1_BACKROW_TOPFLOOR 31-JAN-08:08 0.00 0.00 6028.85 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1548.6 0.00 -2986.4 -3473.4
HEATEDBSMT 31-JAN-07:15 0.00 0.00 6291.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -6291.8
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-07:15 -2640.2 0.22 82144.27 -0.2 0.00 0.00 8321.72 6183.13 30170.56 0.00 0.00 3045.77 0.00 0.00 -26462.5 0.00 -50230.4 -50532.3



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 976.711 2.00 2.00 1.00 44.9950 976.711 0.046 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 371.195 2.00 2.00 1.00 44.9950 371.195 0.121 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 448.095 2.00 2.00 1.00 44.9950 448.095 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 556.065 2.00 2.00 1.00 44.9950 556.065 0.081 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 366.366 2.00 2.00 1.00 44.9950 366.366 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 435.910 2.00 2.00 1.00 44.9950 435.910 0.103 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 545.534 2.00 2.00 1.00 44.9950 545.534 0.082 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 355.684 2.00 2.00 1.00 44.9950 355.684 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 431.693 2.00 2.00 1.00 44.9950 431.693 0.104 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 538.004 2.00 2.00 1.00 44.9950 538.004 0.084 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 353.150 2.00 2.00 1.00 44.9950 353.150 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 424.611 2.00 2.00 1.00 44.9950 424.611 0.106 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 637.719 2.00 2.00 1.00 44.9950 637.719 0.071 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 448.755 2.00 2.00 1.00 44.9950 448.755 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 523.062 2.00 2.00 1.00 44.9950 523.062 0.086 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 637.867 2.00 2.00 1.00 44.9950 637.867 0.071 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 449.846 2.00 2.00 1.00 44.9950 449.846 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 523.326 2.00 2.00 1.00 44.9950 523.326 0.086 1.000 44.9950 0.09
CENTRAL SYSTEM_UNITHEATEDBSMT 497.952 0.00 0.00 1.00 44.9950 497.952 0.090 1.000 44.9950 0.09


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 65.900 2.00 2.00 1.00 44.9950 65.900 1.000 1.000 44.9950 0.68
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 94.365 2.00 2.00 1.00 44.9950 94.365 1.000 1.000 44.9950 0.48
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 94.550 2.00 2.00 1.00 44.9950 94.550 1.000 1.000 44.9950 0.48
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 68.254 2.00 2.00 1.00 44.9950 68.254 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 94.439 2.00 2.00 1.00 44.9950 94.439 1.000 1.000 44.9950 0.48
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 79.311 2.00 2.00 1.00 44.9950 79.311 1.000 1.000 44.9950 0.57
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 58.138 2.00 2.00 1.00 44.9950 58.138 1.000 1.000 44.9950 0.77
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 85.411 2.00 2.00 1.00 44.9950 85.411 1.000 1.000 44.9950 0.53
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 85.494 2.00 2.00 1.00 44.9950 85.494 1.000 1.000 44.9950 0.53
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 58.691 2.00 2.00 1.00 44.9950 58.691 1.000 1.000 44.9950 0.77
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 85.401 2.00 2.00 1.00 44.9950 85.401 1.000 1.000 44.9950 0.53
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 113.764 2.00 2.00 1.00 44.9950 113.764 1.000 1.000 44.9950 0.40
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 87.539 2.00 2.00 1.00 44.9950 87.539 1.000 1.000 44.9950 0.51
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 114.615 2.00 2.00 1.00 44.9950 114.615 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 114.655 2.00 2.00 1.00 44.9950 114.655 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 87.658 2.00 2.00 1.00 44.9950 87.658 1.000 1.000 44.9950 0.51
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 114.587 2.00 2.00 1.00 44.9950 114.587 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNITHEATEDBSMT 115.173 0.00 0.00 1.00 44.9950 115.173 1.000 1.000 44.9950 0.39


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   976.711 976.7105 195.3421 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   371.195 371.1949 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   448.095 448.0949 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   556.065 556.0650 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   366.366 366.3660 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   435.910 435.9097 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   545.534 545.5339 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   355.684 355.6839 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   431.693 431.6934 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   538.004 538.0038 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   353.150 353.1497 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   424.611 424.6109 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   523.326 523.3260 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   523.062 523.0621 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   637.719 637.7194 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   449.846 449.8456 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   448.755 448.7552 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   637.867 637.8667 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   497.952 497.9521 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 976.71 976.711 976.71 195.3421 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 371.19 371.195 371.19 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 448.09 448.095 448.09 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 556.06 556.065 556.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 366.37 366.366 366.37 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 435.91 435.910 435.91 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 545.53 545.534 545.53 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 355.68 355.684 355.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 431.69 431.693 431.69 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 538.00 538.004 538.00 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 353.15 353.150 353.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 424.61 424.611 424.61 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 637.72 637.719 637.72 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 448.76 448.755 448.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 523.06 523.062 523.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 637.87 637.867 637.87 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 449.85 449.846 449.85 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 523.33 523.326 523.33 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 497.95 497.952 497.95 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   65.900 65.900 65.900 44.9950 0.683 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   94.365 94.365 94.365 44.9950 0.477 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   94.550 94.550 94.550 44.9950 0.476 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   68.254 68.254 68.254 44.9950 0.659 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   94.439 94.439 94.439 44.9950 0.476 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   79.311 79.311 79.311 44.9950 0.567 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   58.138 58.138 58.138 44.9950 0.774 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   85.411 85.411 85.411 44.9950 0.527 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   85.494 85.494 85.494 44.9950 0.526 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   58.691 58.691 58.691 44.9950 0.767 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   85.401 85.401 85.401 44.9950 0.527 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   114.587 114.587 114.587 44.9950 0.393 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   114.615 114.615 114.615 44.9950 0.393 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   113.764 113.764 113.764 44.9950 0.396 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   87.658 87.658 87.658 44.9950 0.513 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   87.539 87.539 87.539 44.9950 0.514 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   114.655 114.655 114.655 44.9950 0.392 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   115.173 115.173 115.173 44.9950 0.391 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 65.90 65.900 65.90 65.90 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 94.37 94.365 94.37 94.37 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 94.55 94.550 94.55 94.55 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 68.25 68.254 68.25 68.25 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 94.44 94.439 94.44 94.44 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 79.31 79.311 79.31 79.31 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 58.14 58.138 58.14 58.14 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 85.41 85.411 85.41 85.41 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 85.49 85.494 85.49 85.49 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 58.69 58.691 58.69 58.69 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 85.40 85.401 85.40 85.40 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 113.76 113.764 113.76 113.76 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 87.54 87.539 87.54 87.54 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 114.62 114.615 114.62 114.62 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 114.65 114.655 114.65 114.65 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 87.66 87.658 87.66 87.66 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 114.59 114.587 114.59 114.59 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 115.17 115.173 115.17 115.17 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Sec1.1A-General Information

Data
Weather File ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 147.75
Number of hours not met 147.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 4217.42 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 629.94 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 461.52 91279.93 0.00 0.00
Space Cooling 54558.53 20377.81 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 11945.37 3585.54 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2027.94 147095.70 0.00 0.00
Receptacle Equipment 76678.43 12566.80 1639.73 16390.65 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 158685.13   4129.19   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 261812.16 541817.25
Natural Gas 163973.19 412919.31
Additional 0.00 0.00
Total 425785.36 954736.55


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 1.40
Fans-Interior 0.31
Service Water Heating 0.00
Receptacle Equipment 1.97
Miscellaneous 0.07
Subtotal 4.07


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.35
Service Water Heating 1.52
Miscellaneous 1.23
Subtotal 3.10


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.63
Space Heating 4.83
Space Cooling 19.51
Fans-Interior 4.27
Service Water Heating 21.24
Receptacle Equipment 44.60
Miscellaneous 0.91



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 497.95
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 976.71
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 371.19
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 448.09
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 556.06
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 366.37
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 435.91
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 545.53
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 355.68
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 431.69
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 538.00
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 353.15
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 424.61
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 523.33
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 523.06
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 637.72
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 449.85
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 448.76
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 637.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 976.71
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 371.19
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 448.09
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 556.06
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 366.37
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 435.91
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 545.53
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 355.68
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 431.69
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 538.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 353.15
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 424.61
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 637.72
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 448.76
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 523.06
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 637.87
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 449.85
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 523.33
CENTRAL SYSTEM_UNITHEATEDBSMT 497.95
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 976.71 2.21 0.791899
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 371.19 0.901756 0.767213
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 448.09 1.13 0.754532
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 556.06 1.30 0.779230
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 366.37 0.876564 0.772376
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 435.91 1.05 0.770777
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 545.53 1.28 0.778729
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 355.68 0.858768 0.769291
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 431.69 1.04 0.770536
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 538.00 1.27 0.778282
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 353.15 0.846794 0.771630
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 424.61 1.02 0.772486
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 637.72 1.48 0.783324
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 448.76 1.05 0.779630
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 523.06 1.22 0.779922
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 637.87 1.48 0.783331
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 449.85 1.05 0.779712
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 523.33 1.22 0.779938
DX COOLING COIL_UNITHEATEDBSMT 497.95 1.23 0.762871
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 976.71 976.71 976.71 3900.50 2.21 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 371.19 371.19 371.19 4987.90 0.901756 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 448.09 448.09 448.09 6468.57 1.13 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 556.06 556.06 556.06 6478.21 1.30 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 366.37 366.37 366.37 5110.35 0.876564 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 435.91 435.91 435.91 6472.42 1.05 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 545.53 545.53 545.53 5685.48 1.28 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 355.68 355.68 355.68 4584.15 0.858768 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 431.69 431.69 431.69 6002.78 1.04 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 538.00 538.00 538.00 6007.11 1.27 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 353.15 353.15 353.15 4612.91 0.846794 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 424.61 424.61 424.61 6002.22 1.02 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 637.72 637.72 637.72 7477.64 1.48 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 448.76 448.76 448.76 6113.51 1.05 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 523.06 523.06 523.06 7521.94 1.22 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 637.87 637.87 637.87 7523.99 1.48 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 449.85 449.85 449.85 6119.67 1.05 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 523.33 523.33 523.33 7520.48 1.22 1.00
ACANDF_UNITHEATEDBSMT 497.95 497.95 497.95 7550.64 1.23 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 976.71
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 371.19
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 448.09
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 556.06
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 366.37
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 435.91
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 545.53
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 355.68
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 431.69
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 538.00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 353.15
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 424.61
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 637.72
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 448.76
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 523.06
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 637.87
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 449.85
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 523.33
SUPPLY FAN_UNITHEATEDBSMT 497.95
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 3900.50
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 4987.90
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 6468.57
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 6478.21
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 5110.35
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 6472.42
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 5685.48
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 4584.15
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 6002.78
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 6007.11
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 4612.91
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 6002.22
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 7477.64
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 6113.51
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 7521.94
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 7523.99
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 6119.67
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 7520.48
MAIN FUEL HEATING COIL_UNITHEATEDBSMT 7550.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:38

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 744.000 97.574 0.000 0.000 97.574
February 672.000 99.592 0.000 0.000 99.592
March 744.000 117.628 0.000 0.000 117.628
April 720.000 141.560 0.000 0.000 141.560
May 744.000 165.120 0.000 0.000 165.120
June 720.000 192.114 0.000 0.000 192.114
July 744.000 212.985 0.000 0.000 212.985
August 744.000 203.752 0.000 0.000 203.752
September 720.000 177.813 0.000 0.000 177.813
October 744.000 156.699 0.000 0.000 156.699
November 720.000 119.270 0.000 0.000 119.270
December 744.000 92.390 0.000 0.000 92.390
           
Annual Sum or Average 8760.000 1776.498 0.000 0.000 1776.498
Minimum of Months 672.000 92.390 0.000 0.000 92.390
Maximum of Months 744.000 212.985 0.000 0.000 212.985



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 289.086 8.907 228.750 7.351 16.258
February 320.520 13.334 157.792 4.976 18.309
March 402.703 15.829 104.250 3.142 18.971
April 589.733 29.895 26.500 0.871 30.766
May 724.641 41.311 0.000 0.000 41.311
June 720.000 61.514 0.000 0.000 61.514
July 744.000 74.691 0.000 0.000 74.691
August 744.000 68.791 0.000 0.000 68.791
September 720.000 54.845 0.000 0.000 54.845
October 693.655 40.790 1.500 0.007 40.797
November 469.025 19.849 48.475 0.723 20.572
December 259.844 7.759 281.875 9.947 17.706
           
Annual Sum or Average 6677.208 437.516 849.142 27.016 464.532
Minimum of Months 259.844 7.759 0.000 0.000 16.258
Maximum of Months 744.000 74.691 281.875 9.947 74.691



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 256.371 8.020 295.188 12.906 20.926
February 304.414 14.403 197.000 8.370 22.773
March 405.974 18.480 134.542 5.417 23.897
April 580.472 37.021 41.250 1.385 38.406
May 715.812 51.225 0.000 0.000 51.225
June 720.000 76.100 0.000 0.000 76.100
July 744.000 90.628 0.000 0.000 90.628
August 744.000 83.027 0.000 0.000 83.027
September 720.000 64.830 0.000 0.000 64.830
October 686.490 46.060 14.000 0.193 46.253
November 448.106 20.544 90.000 2.227 22.772
December 224.348 6.875 329.875 16.475 23.350
           
Annual Sum or Average 6549.987 517.213 1101.854 46.973 564.186
Minimum of Months 224.348 6.875 0.000 0.000 20.926
Maximum of Months 744.000 90.628 329.875 16.475 90.628



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 135.079 3.016 399.604 22.233 25.248
February 215.358 9.241 270.750 14.013 23.254
March 319.672 15.041 179.997 8.019 23.060
April 534.102 35.929 57.090 2.346 38.275
May 707.110 54.248 0.000 0.000 54.248
June 720.000 82.230 0.000 0.000 82.230
July 744.000 97.214 0.000 0.000 97.214
August 744.000 87.330 0.000 0.000 87.330
September 720.000 63.991 0.000 0.000 63.991
October 661.720 39.571 25.308 0.449 40.020
November 340.839 11.913 153.795 4.477 16.390
December 96.783 1.917 462.583 28.601 30.518
           
Annual Sum or Average 5938.664 501.641 1549.128 80.138 581.779
Minimum of Months 96.783 1.917 0.000 0.000 16.390
Maximum of Months 744.000 97.214 462.583 28.601 97.214



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 100.148 1.361 357.108 11.427 12.788
February 219.514 6.250 227.439 7.156 13.406
March 339.176 9.658 125.898 3.714 13.373
April 577.153 26.428 34.500 1.027 27.454
May 724.471 40.956 0.000 0.000 40.956
June 720.000 62.332 0.000 0.000 62.332
July 744.000 74.863 0.000 0.000 74.863
August 744.000 67.046 0.000 0.000 67.046
September 720.000 49.262 0.000 0.000 49.262
October 679.260 31.742 3.750 0.023 31.765
November 377.054 8.684 79.562 1.328 10.012
December 61.504 0.687 438.417 15.547 16.235
           
Annual Sum or Average 6006.281 379.271 1266.675 40.223 419.494
Minimum of Months 61.504 0.687 0.000 0.000 10.012
Maximum of Months 744.000 74.863 438.417 15.547 74.863



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 86.747 1.303 400.250 16.199 17.502
February 229.216 7.869 246.896 9.764 17.633
March 375.380 12.973 145.742 5.614 18.587
April 575.404 34.862 43.917 1.420 36.283
May 715.848 52.380 0.000 0.000 52.380
June 720.000 78.899 0.000 0.000 78.899
July 744.000 92.889 0.000 0.000 92.889
August 744.000 83.391 0.000 0.000 83.391
September 720.000 61.310 0.000 0.000 61.310
October 680.772 38.700 14.750 0.209 38.909
November 392.782 10.022 100.125 2.453 12.475
December 56.054 0.619 470.725 21.171 21.791
           
Annual Sum or Average 6040.202 475.218 1422.404 56.831 532.049
Minimum of Months 56.054 0.619 0.000 0.000 12.475
Maximum of Months 744.000 92.889 470.725 21.171 92.889



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 288.496 12.108 249.794 11.687 23.795
February 319.794 17.898 169.750 7.738 25.637
March 408.707 23.103 113.458 4.888 27.990
April 583.841 41.196 30.268 1.402 42.598
May 717.486 55.624 0.000 0.000 55.624
June 720.000 81.201 0.000 0.000 81.201
July 744.000 95.492 0.000 0.000 95.492
August 744.000 88.403 0.000 0.000 88.403
September 720.000 70.224 0.000 0.000 70.224
October 682.958 49.715 7.275 0.084 49.799
November 453.777 24.471 64.319 1.645 26.116
December 259.772 10.522 301.042 15.603 26.125
           
Annual Sum or Average 6642.830 569.957 935.906 43.047 613.004
Minimum of Months 259.772 10.522 0.000 0.000 23.795
Maximum of Months 744.000 95.492 301.042 15.603 95.492



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 325.071 10.185 166.151 4.327 14.511
February 371.225 15.020 106.229 3.149 18.169
March 475.884 17.951 77.187 2.098 20.049
April 633.464 31.577 20.750 0.569 32.147
May 731.297 41.850 0.000 0.000 41.850
June 720.000 60.461 0.000 0.000 60.461
July 744.000 72.367 0.000 0.000 72.367
August 744.000 67.397 0.000 0.000 67.397
September 720.000 54.911 0.000 0.000 54.911
October 700.036 41.596 0.000 0.000 41.596
November 520.873 21.816 21.833 0.179 21.994
December 298.709 8.984 213.623 6.395 15.379
           
Annual Sum or Average 6984.559 444.115 605.774 16.716 460.831
Minimum of Months 298.709 8.984 0.000 0.000 14.511
Maximum of Months 744.000 72.367 213.623 6.395 72.367



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 289.835 9.372 243.917 9.123 18.495
February 338.279 16.386 162.042 6.025 22.412
March 448.367 21.231 103.833 3.951 25.182
April 613.874 40.244 24.750 0.923 41.167
May 725.098 53.896 0.000 0.000 53.896
June 720.000 78.138 0.000 0.000 78.138
July 744.000 91.495 0.000 0.000 91.495
August 744.000 84.563 0.000 0.000 84.563
September 720.000 67.358 0.000 0.000 67.358
October 692.078 48.522 5.750 0.064 48.585
November 481.628 23.016 54.938 1.181 24.198
December 251.796 8.092 288.183 12.351 20.443
           
Annual Sum or Average 6768.955 542.314 883.412 33.619 575.933
Minimum of Months 251.796 8.092 0.000 0.000 18.495
Maximum of Months 744.000 91.495 288.183 12.351 91.495



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 164.650 3.409 351.250 17.147 20.556
February 247.384 10.227 230.753 10.767 20.994
March 356.793 16.574 140.873 5.876 22.450
April 573.612 37.325 40.500 1.705 39.030
May 716.833 54.643 0.000 0.000 54.643
June 720.000 81.096 0.000 0.000 81.096
July 744.000 94.754 0.000 0.000 94.754
August 744.000 85.887 0.000 0.000 85.887
September 720.000 64.116 0.000 0.000 64.116
October 666.729 40.251 17.250 0.234 40.485
November 372.221 13.019 103.932 2.817 15.836
December 118.650 2.188 419.392 23.076 25.264
           
Annual Sum or Average 6144.872 503.488 1303.950 61.623 565.110
Minimum of Months 118.650 2.188 0.000 0.000 15.836
Maximum of Months 744.000 94.754 419.392 23.076 94.754



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 139.314 1.917 281.208 7.611 9.528
February 275.711 7.576 171.330 4.791 12.367
March 421.916 11.707 94.000 2.453 14.160
April 622.602 28.121 25.000 0.665 28.786
May 731.234 41.296 0.000 0.000 41.296
June 720.000 60.936 0.000 0.000 60.936
July 744.000 72.221 0.000 0.000 72.221
August 744.000 65.413 0.000 0.000 65.413
September 720.000 49.205 0.000 0.000 49.205
October 684.554 32.441 0.000 0.000 32.441
November 427.589 10.306 46.804 0.531 10.837
December 82.692 1.055 365.583 11.118 12.173
           
Annual Sum or Average 6313.611 382.196 983.926 27.169 409.365
Minimum of Months 82.692 1.055 0.000 0.000 9.528
Maximum of Months 744.000 72.221 365.583 11.118 72.221



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 106.073 1.656 344.167 12.284 13.940
February 259.765 9.104 205.375 7.382 16.486
March 417.763 15.049 112.278 4.162 19.211
April 608.356 36.820 26.271 0.948 37.768
May 725.202 53.234 0.000 0.000 53.234
June 720.000 78.375 0.000 0.000 78.375
July 744.000 91.154 0.000 0.000 91.154
August 744.000 82.547 0.000 0.000 82.547
September 720.000 61.874 0.000 0.000 61.874
October 686.390 39.689 6.500 0.075 39.765
November 425.580 11.565 63.583 1.395 12.959
December 67.458 0.876 428.230 16.942 17.818
           
Annual Sum or Average 6224.588 481.942 1186.403 43.189 525.131
Minimum of Months 67.458 0.876 0.000 0.000 12.959
Maximum of Months 744.000 91.154 428.230 16.942 91.154



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 238.364 10.266 325.517 20.385 30.651
February 282.984 17.619 224.417 13.417 31.036
March 366.957 23.804 158.792 8.533 32.337
April 550.980 45.571 53.965 2.556 48.127
May 703.179 63.281 0.000 0.000 63.281
June 720.000 95.127 0.000 0.000 95.127
July 744.000 112.479 0.000 0.000 112.479
August 744.000 102.291 0.000 0.000 102.291
September 720.000 79.051 0.000 0.000 79.051
October 666.513 53.119 26.583 0.575 53.694
November 411.040 23.559 121.986 4.104 27.663
December 204.758 8.562 367.506 25.800 34.362
           
Annual Sum or Average 6352.775 634.729 1278.765 75.370 710.099
Minimum of Months 204.758 8.562 0.000 0.000 27.663
Maximum of Months 744.000 112.479 367.506 25.800 112.479



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 264.603 8.589 259.225 10.100 18.690
February 317.858 14.933 175.625 6.865 21.798
March 402.460 18.915 115.537 4.335 23.250
April 591.796 36.344 35.152 1.226 37.570
May 718.274 50.085 0.000 0.000 50.085
June 720.000 75.187 0.000 0.000 75.187
July 744.000 90.080 0.000 0.000 90.080
August 744.000 82.077 0.000 0.000 82.077
September 720.000 64.511 0.000 0.000 64.511
October 684.723 45.656 6.983 0.054 45.710
November 455.062 21.174 62.125 1.274 22.448
December 229.960 7.196 309.708 13.484 20.680
           
Annual Sum or Average 6592.737 514.749 964.356 37.338 552.087
Minimum of Months 229.960 7.196 0.000 0.000 18.690
Maximum of Months 744.000 90.080 309.708 13.484 90.080



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 231.379 7.937 309.500 15.609 23.546
February 300.031 16.317 202.982 10.041 26.358
March 407.945 22.002 137.000 6.357 28.359
April 588.210 44.972 45.750 1.686 46.658
May 714.405 62.157 0.000 0.000 62.157
June 720.000 92.998 0.000 0.000 92.998
July 744.000 109.343 0.000 0.000 109.343
August 744.000 99.398 0.000 0.000 99.398
September 720.000 77.040 0.000 0.000 77.040
October 678.085 52.557 18.000 0.320 52.877
November 441.857 22.376 94.750 2.702 25.078
December 201.626 6.557 350.042 19.950 26.507
           
Annual Sum or Average 6491.539 613.653 1158.024 56.666 670.319
Minimum of Months 201.626 6.557 0.000 0.000 23.546
Maximum of Months 744.000 109.343 350.042 19.950 109.343



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 150.717 4.005 400.217 25.715 29.720
February 233.214 12.248 265.771 16.047 28.295
March 341.691 20.286 175.519 9.140 29.425
April 546.807 44.147 59.625 2.733 46.880
May 703.548 63.352 0.000 0.000 63.352
June 720.000 95.639 0.000 0.000 95.639
July 744.000 112.649 0.000 0.000 112.649
August 744.000 101.679 0.000 0.000 101.679
September 720.000 76.201 0.000 0.000 76.201
October 653.073 46.512 34.375 0.790 47.302
November 349.491 14.861 162.986 5.595 20.456
December 108.358 2.619 454.188 32.984 35.603
           
Annual Sum or Average 6014.899 594.197 1552.680 93.003 687.200
Minimum of Months 108.358 2.619 0.000 0.000 20.456
Maximum of Months 744.000 112.649 454.188 32.984 112.649



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 125.958 2.306 357.882 14.420 16.726
February 249.689 9.425 226.958 8.948 18.373
March 369.253 15.312 128.187 4.745 20.057
April 587.276 34.957 40.652 1.323 36.280
May 718.356 50.202 0.000 0.000 50.202
June 720.000 75.764 0.000 0.000 75.764
July 744.000 90.310 0.000 0.000 90.310
August 744.000 81.522 0.000 0.000 81.522
September 720.000 61.666 0.000 0.000 61.666
October 672.275 38.914 14.500 0.130 39.044
November 382.767 11.950 89.708 2.024 13.974
December 79.687 1.306 432.000 19.493 20.799
           
Annual Sum or Average 6113.261 473.635 1289.888 51.083 524.717
Minimum of Months 79.687 1.306 0.000 0.000 13.974
Maximum of Months 744.000 90.310 432.000 19.493 90.310



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 103.473 2.105 401.072 19.767 21.872
February 242.423 10.953 243.544 11.782 22.735
March 388.291 18.446 143.500 6.627 25.073
April 584.890 43.613 47.114 1.739 45.352
May 714.547 62.211 0.000 0.000 62.211
June 720.000 93.454 0.000 0.000 93.454
July 744.000 109.471 0.000 0.000 109.471
August 744.000 98.821 0.000 0.000 98.821
September 720.000 74.335 0.000 0.000 74.335
October 669.491 46.065 19.750 0.356 46.421
November 387.455 13.134 111.583 3.140 16.275
December 67.375 1.192 475.099 25.815 27.007
           
Annual Sum or Average 6085.945 573.800 1441.661 69.226 643.027
Minimum of Months 67.375 1.192 0.000 0.000 16.275
Maximum of Months 744.000 109.471 475.099 25.815 109.471



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 62.378 62.378
February 0.000 0.000 638.794 39.040 39.040
March 0.000 0.000 476.043 15.494 15.494
April 17.836 0.091 26.750 0.446 0.538
May 742.625 47.225 0.000 0.000 47.225
June 720.000 97.207 0.000 0.000 97.207
July 744.000 112.644 0.000 0.000 112.644
August 744.000 103.325 0.000 0.000 103.325
September 720.000 81.662 0.000 0.000 81.662
October 744.000 45.959 0.000 0.000 45.959
November 0.500 0.012 194.917 3.144 3.156
December 0.000 0.000 744.000 61.379 61.379
           
Annual Sum or Average 4432.961 488.126 2824.503 181.881 670.007
Minimum of Months 0.000 0.000 0.000 0.000 0.538
Maximum of Months 744.000 112.644 744.000 62.378 112.644



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 351.98 0.00
February 0.00 263.78 0.00
March 0.00 150.44 0.00
April 0.00 43.10 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.32 0.00
November 0.00 35.75 0.00
December 0.00 476.30 0.00
       
Annual Sum or Average 0.00 109.87 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 476.30 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 663.91 0.00
February 0.00 476.69 0.00
March 0.00 278.66 0.00
April 0.00 73.62 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 9.91 0.00
November 0.00 118.39 0.00
December 0.00 847.46 0.00
       
Annual Sum or Average 0.00 205.22 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 847.46 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 922.97 0.00
February 0.00 644.04 0.00
March 0.00 332.92 0.00
April 0.00 100.63 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 18.66 0.00
November 0.00 192.07 0.00
December 0.00 1187.34 0.00
       
Annual Sum or Average 0.00 282.56 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1187.34 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 567.97 0.00
February 0.00 393.79 0.00
March 0.00 184.63 0.00
April 0.00 52.73 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 1.14 0.00
November 0.00 68.23 0.00
December 0.00 772.78 0.00
       
Annual Sum or Average 0.00 169.80 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 772.78 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 857.08 0.00
February 0.00 571.96 0.00
March 0.00 297.04 0.00
April 0.00 77.65 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 11.06 0.00
November 0.00 134.12 0.00
December 0.00 1120.17 0.00
       
Annual Sum or Average 0.00 255.38 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1120.17 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 434.02 0.00
February 0.00 318.17 0.00
March 0.00 181.52 0.00
April 0.00 53.80 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 3.13 0.00
November 0.00 63.13 0.00
December 0.00 579.44 0.00
       
Annual Sum or Average 0.00 135.78 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 579.44 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 198.70 0.00
February 0.00 160.10 0.00
March 0.00 96.37 0.00
April 0.00 27.02 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 8.48 0.00
December 0.00 293.69 0.00
       
Annual Sum or Average 0.00 65.20 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 293.69 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 452.04 0.00
February 0.00 330.55 0.00
March 0.00 195.79 0.00
April 0.00 47.27 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 3.15 0.00
November 0.00 60.48 0.00
December 0.00 611.97 0.00
       
Annual Sum or Average 0.00 141.48 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 611.97 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 682.24 0.00
February 0.00 474.29 0.00
March 0.00 233.78 0.00
April 0.00 70.11 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 9.32 0.00
November 0.00 115.82 0.00
December 0.00 918.15 0.00
       
Annual Sum or Average 0.00 208.23 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 918.15 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 354.26 0.00
February 0.00 246.88 0.00
March 0.00 114.16 0.00
April 0.00 31.99 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 25.54 0.00
December 0.00 517.49 0.00
       
Annual Sum or Average 0.00 107.40 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 517.49 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 618.78 0.00
February 0.00 411.70 0.00
March 0.00 209.64 0.00
April 0.00 49.35 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 3.80 0.00
November 0.00 72.59 0.00
December 0.00 853.40 0.00
       
Annual Sum or Average 0.00 184.77 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 853.40 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 851.75 0.00
February 0.00 620.66 0.00
March 0.00 356.53 0.00
April 0.00 110.37 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 24.04 0.00
November 0.00 177.18 0.00
December 0.00 1078.00 0.00
       
Annual Sum or Average 0.00 267.47 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1078.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 490.32 0.00
February 0.00 368.97 0.00
March 0.00 210.44 0.00
April 0.00 61.49 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 2.64 0.00
November 0.00 63.89 0.00
December 0.00 654.59 0.00
       
Annual Sum or Average 0.00 153.95 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 654.59 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 799.87 0.00
February 0.00 569.66 0.00
March 0.00 325.75 0.00
April 0.00 89.29 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 16.39 0.00
November 0.00 143.10 0.00
December 0.00 1022.32 0.00
       
Annual Sum or Average 0.00 246.62 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1022.32 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1080.85 0.00
February 0.00 746.76 0.00
March 0.00 384.16 0.00
April 0.00 118.69 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 33.20 0.00
November 0.00 243.01 0.00
December 0.00 1386.37 0.00
       
Annual Sum or Average 0.00 332.01 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1386.37 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 699.04 0.00
February 0.00 480.24 0.00
March 0.00 230.00 0.00
April 0.00 66.27 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 6.31 0.00
November 0.00 101.39 0.00
December 0.00 944.93 0.00
       
Annual Sum or Average 0.00 210.32 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 944.93 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1012.23 0.00
February 0.00 667.98 0.00
March 0.00 339.35 0.00
April 0.00 92.02 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 18.24 0.00
November 0.00 166.17 0.00
December 0.00 1321.92 0.00
       
Annual Sum or Average 0.00 301.08 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1321.92 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3370.49 0.00
February 0.00 2335.45 0.00
March 0.00 837.20 0.00
April 0.00 24.92 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 175.52 0.00
December 0.00 3316.48 0.00
       
Annual Sum or Average 0.00 834.67 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3370.49 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.73
February 0.00 0.00 0.83
March 0.00 0.00 0.88
April 0.00 0.00 1.05
May 0.00 0.00 1.18
June 0.00 0.00 1.38
July 0.00 0.00 1.50
August 0.00 0.00 1.45
September 0.00 0.00 1.31
October 0.00 0.00 1.15
November 0.00 0.00 0.92
December 0.00 0.00 0.70
       
Annual Sum or Average 0.00 0.00 1.09
Minimum of Months 0.00 0.00 0.70
Maximum of Months 0.00 0.00 1.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.11
March 0.00 0.00 0.12
April 0.00 0.00 0.23
May 0.00 0.00 0.30
June 0.00 0.00 0.46
July 0.00 0.00 0.56
August 0.00 0.00 0.52
September 0.00 0.00 0.43
October 0.00 0.00 0.31
November 0.00 0.00 0.16
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.13
March 0.00 0.00 0.14
April 0.00 0.00 0.29
May 0.00 0.00 0.39
June 0.00 0.00 0.60
July 0.00 0.00 0.71
August 0.00 0.00 0.65
September 0.00 0.00 0.52
October 0.00 0.00 0.36
November 0.00 0.00 0.17
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.71



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.11
April 0.00 0.00 0.26
May 0.00 0.00 0.38
June 0.00 0.00 0.59
July 0.00 0.00 0.69
August 0.00 0.00 0.63
September 0.00 0.00 0.47
October 0.00 0.00 0.28
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.20
May 0.00 0.00 0.30
June 0.00 0.00 0.47
July 0.00 0.00 0.56
August 0.00 0.00 0.50
September 0.00 0.00 0.37
October 0.00 0.00 0.23
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.26
May 0.00 0.00 0.38
June 0.00 0.00 0.60
July 0.00 0.00 0.70
August 0.00 0.00 0.63
September 0.00 0.00 0.47
October 0.00 0.00 0.29
November 0.00 0.00 0.08
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.70



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.15
March 0.00 0.00 0.17
April 0.00 0.00 0.30
May 0.00 0.00 0.39
June 0.00 0.00 0.59
July 0.00 0.00 0.68
August 0.00 0.00 0.64
September 0.00 0.00 0.52
October 0.00 0.00 0.36
November 0.00 0.00 0.19
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.13
March 0.00 0.00 0.14
April 0.00 0.00 0.24
May 0.00 0.00 0.31
June 0.00 0.00 0.46
July 0.00 0.00 0.54
August 0.00 0.00 0.51
September 0.00 0.00 0.43
October 0.00 0.00 0.32
November 0.00 0.00 0.17
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.14
March 0.00 0.00 0.16
April 0.00 0.00 0.31
May 0.00 0.00 0.40
June 0.00 0.00 0.59
July 0.00 0.00 0.69
August 0.00 0.00 0.64
September 0.00 0.00 0.52
October 0.00 0.00 0.37
November 0.00 0.00 0.18
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.12
April 0.00 0.00 0.27
May 0.00 0.00 0.39
June 0.00 0.00 0.59
July 0.00 0.00 0.68
August 0.00 0.00 0.62
September 0.00 0.00 0.47
October 0.00 0.00 0.29
November 0.00 0.00 0.10
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.21
May 0.00 0.00 0.30
June 0.00 0.00 0.46
July 0.00 0.00 0.54
August 0.00 0.00 0.49
September 0.00 0.00 0.38
October 0.00 0.00 0.24
November 0.00 0.00 0.08
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.07
March 0.00 0.00 0.11
April 0.00 0.00 0.28
May 0.00 0.00 0.39
June 0.00 0.00 0.59
July 0.00 0.00 0.68
August 0.00 0.00 0.62
September 0.00 0.00 0.47
October 0.00 0.00 0.29
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.14
March 0.00 0.00 0.17
April 0.00 0.00 0.33
May 0.00 0.00 0.44
June 0.00 0.00 0.68
July 0.00 0.00 0.79
August 0.00 0.00 0.73
September 0.00 0.00 0.58
October 0.00 0.00 0.38
November 0.00 0.00 0.18
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.79



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.12
March 0.00 0.00 0.14
April 0.00 0.00 0.27
May 0.00 0.00 0.36
June 0.00 0.00 0.55
July 0.00 0.00 0.66
August 0.00 0.00 0.60
September 0.00 0.00 0.48
October 0.00 0.00 0.33
November 0.00 0.00 0.16
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.66



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.13
March 0.00 0.00 0.16
April 0.00 0.00 0.33
May 0.00 0.00 0.44
June 0.00 0.00 0.68
July 0.00 0.00 0.80
August 0.00 0.00 0.73
September 0.00 0.00 0.58
October 0.00 0.00 0.38
November 0.00 0.00 0.17
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.80



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.10
March 0.00 0.00 0.15
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.68
July 0.00 0.00 0.80
August 0.00 0.00 0.72
September 0.00 0.00 0.56
October 0.00 0.00 0.33
November 0.00 0.00 0.11
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.36
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.80



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.11
April 0.00 0.00 0.26
May 0.00 0.00 0.36
June 0.00 0.00 0.55
July 0.00 0.00 0.66
August 0.00 0.00 0.60
September 0.00 0.00 0.46
October 0.00 0.00 0.28
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.66



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.09
March 0.00 0.00 0.13
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.69
July 0.00 0.00 0.80
August 0.00 0.00 0.72
September 0.00 0.00 0.55
October 0.00 0.00 0.33
November 0.00 0.00 0.10
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.80



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.34
June 0.00 0.00 0.75
July 0.00 0.00 0.84
August 0.00 0.00 0.77
September 0.00 0.00 0.63
October 0.00 0.00 0.34
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72
Maximum of Months 0.00 0.00 1326.29 987.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1326.29 987.46
February 0.00 0.00 1301.80 875.43
March 0.00 0.00 1204.22 896.58
April 0.00 0.00 1062.95 765.87
May 0.00 0.00 906.00 674.55
June 0.00 0.00 785.33 565.84
July 0.00 0.00 728.95 542.72
August 0.00 0.00 754.98 562.10
September 0.00 0.00 853.15 614.70
October 0.00 0.00 1000.91 745.21
November 0.00 0.00 1155.38 832.46
December 0.00 0.00 1276.20 950.17
         
Annual Sum or Average 0.00 0.00 1028.16 9013.08
Minimum of Months 0.00 0.00 728.95 542.72