Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
Tabular Output Report in Format: HTML
Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+oilfurnace+heatedbsmt+IECC_2012
Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Simulation Timestamp: 2019-02-14 08:32:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 822571.31 | 21.09 | 27.97 |
Net Site Energy | 822571.31 | 21.09 | 27.97 |
Total Source Energy | 2061957.22 | 52.86 | 70.12 |
Net Source Energy | 2061957.22 | 52.86 | 70.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 57946.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 171985.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36999.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 202796.15 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 561829.05 | 260742.26 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 57946.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 171985.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 36999.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 202796.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 7.11 | 8.87 | 0.00 | 0.00 | 0.00 | 12.85 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 19.11 | 8.87 | 0.00 | 0.00 | 0.00 | 12.85 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 5.36 | 6.68 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.40 | 6.68 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 561829.052 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 561829.052 | 100.00 |
Total On-Site and Utility Electric Sources | 561829.052 | 100.00 |
Total Electricity End Uses | 561829.052 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 628.75 |
Time Setpoint Not Met During Occupied Cooling | 137.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 109.75 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32 |
RunPeriod | ANNUAL |
Weather File | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Latitude [deg] | 33.45 |
Longitude [deg] | -112.0 |
Elevation [ft] | 1105.70 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4894 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 16-JUL-18:15 | 31-JAN-07:15 | - | - | - | 01-JAN-08:30 |
Heating | 0.00 | 107.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.23 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 146.87 | 220.64 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 107.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 67.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 62813.59 | 0.00 | 0.00 | 0.00 |
Cooling | 544679.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117178.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 219831.02 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1779312.61 | 282644.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 2.14 | 0.00 | 0.00 | 0.00 |
Cooling | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.48 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 60.51 | 9.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 2.14 | 0.00 | 0.00 | 0.00 |
Cooling | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.48 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 60.51 | 9.61 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 38.66 | 0.00 | 38.66 | Wetbulb [F] | 334.66 | 100.00 |
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 110.12 | 21.60 | 69.98 | Wetbulb [F] | 807.13 | 260.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.400 | 0.219 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.400 | 0.219 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.400 | 0.219 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 496569.28 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 25842.09 | 20407.93 | 5434.16 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10026.40 | 7621.73 | 2404.67 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13073.64 | 9841.09 | 3232.54 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14889.51 | 11548.36 | 3341.15 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9656.26 | 7406.43 | 2249.83 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12607.57 | 9467.75 | 3139.81 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14635.96 | 11331.95 | 3304.01 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9504.57 | 7235.12 | 2269.45 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12496.11 | 9395.56 | 3100.55 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14362.11 | 11128.46 | 3233.65 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9288.38 | 7113.32 | 2175.06 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12064.89 | 9049.86 | 3015.03 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16954.93 | 13226.93 | 3728.00 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11805.02 | 9127.43 | 2677.59 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14120.49 | 10894.56 | 3225.93 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16951.30 | 13223.98 | 3727.32 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11751.79 | 9114.16 | 2637.63 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14107.06 | 10883.67 | 3223.39 | 0.77 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 14598.73 | 11132.47 | 3466.26 | 0.76 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.1 | 3.28 | 11.18 | 11.83 | 11.36 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.8 | 3.33 | 11.37 | 12.04 | 11.66 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | 3.35 | 11.42 | 12.10 | 11.74 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.30 | 11.27 | 11.93 | 11.50 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.8 | 3.32 | 11.32 | 12.00 | 11.59 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.0 | 3.35 | 11.43 | 12.11 | 11.76 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.30 | 11.28 | 11.94 | 11.52 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.8 | 3.33 | 11.36 | 12.04 | 11.65 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.0 | 3.35 | 11.42 | 12.10 | 11.75 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.30 | 11.27 | 11.94 | 11.51 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.32 | 11.33 | 12.00 | 11.61 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.0 | 3.35 | 11.43 | 12.12 | 11.77 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.29 | 11.24 | 11.90 | 11.46 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.9 | 3.31 | 11.28 | 11.95 | 11.53 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | 3.31 | 11.29 | 11.96 | 11.55 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.29 | 11.24 | 11.90 | 11.46 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.9 | 3.30 | 11.27 | 11.93 | 11.51 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 3.31 | 11.29 | 11.96 | 11.55 | |
DX COOLING COIL_UNITHEATEDBSMT | 1.2 | 3.33 | 11.35 | 12.03 | 11.64 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 50753.25 | 54842.83 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19075.35 | 20096.01 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 23883.80 | 25376.59 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 28790.93 | 30764.22 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 18779.39 | 19770.59 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 22968.50 | 24371.42 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 28221.88 | 30138.22 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18216.90 | 19151.23 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 22839.92 | 24228.77 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 27768.34 | 29639.87 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 18065.00 | 18984.24 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 21991.63 | 23297.14 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 32975.05 | 35355.31 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 22997.96 | 24403.81 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 27080.24 | 28884.93 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 32967.69 | 35347.16 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 23049.32 | 24460.21 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 27053.14 | 28855.19 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 27246.84 | 29057.62 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 945.79 | 356.75 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 336.73 | 127.01 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 429.16 | 161.88 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 523.50 | 197.46 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 331.04 | 124.86 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 411.57 | 155.24 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 512.57 | 193.34 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 320.23 | 120.79 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 409.10 | 154.31 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 503.85 | 190.05 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 317.31 | 119.69 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 392.79 | 148.16 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 603.94 | 227.80 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 412.14 | 155.45 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 490.61 | 185.06 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 603.80 | 227.75 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 413.12 | 155.83 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 490.09 | 184.86 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 493.86 | 186.28 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 49.933864 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21348.07 | 21348.07 | 17.78 | 945.793 | 945.793 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00803 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7600.44 | 7600.44 | 6.33 | 336.727 | 336.727 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00810 | 104.94 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9687.02 | 9687.02 | 8.07 | 429.164 | 429.164 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00798 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11816.25 | 11816.25 | 9.84 | 523.501 | 523.501 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00806 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7471.98 | 7471.98 | 6.22 | 331.037 | 331.037 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00815 | 102.51 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9289.85 | 9289.85 | 7.74 | 411.568 | 411.568 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00798 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11569.50 | 11569.50 | 9.64 | 512.571 | 512.571 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00809 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7228.01 | 7228.01 | 6.02 | 320.229 | 320.229 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00819 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9234.13 | 9234.13 | 7.69 | 409.103 | 409.103 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 74.98 | 74.98 | 0.00801 | 109.80 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11372.66 | 11372.66 | 9.47 | 503.851 | 503.851 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00810 | 104.94 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7162.08 | 7162.08 | 5.97 | 317.308 | 317.308 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00821 | 101.70 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8866.02 | 8866.02 | 7.38 | 392.795 | 392.795 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 74.98 | 74.98 | 0.00801 | 109.80 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 11062.16 | 11062.16 | 9.21 | 490.091 | 490.091 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00804 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 11073.92 | 11073.92 | 9.22 | 490.612 | 490.612 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00804 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 13631.81 | 13631.81 | 11.35 | 603.937 | 603.937 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00806 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9324.79 | 9324.79 | 7.77 | 413.123 | 413.123 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00813 | 102.51 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9302.51 | 9302.51 | 7.75 | 412.136 | 412.136 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00812 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 13628.61 | 13628.61 | 11.35 | 603.795 | 603.795 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00806 | 105.48 | 0.00720 | 44.995 | 0.00 |
HEATEDBSMT | 11147.15 | 11147.15 | 1.43 | 493.855 | 493.855 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 74.98 | 74.98 | 0.00800 | 108.82 | 0.00720 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 38.66 | 0.00513 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3872.26 | 3872.26 | 3.23 | 73.359 | 73.359 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00687 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5394.01 | 5394.01 | 4.49 | 102.187 | 102.187 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5403.41 | 5403.41 | 4.50 | 102.365 | 102.365 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4004.50 | 4004.50 | 3.34 | 75.864 | 75.864 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00689 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5397.56 | 5397.56 | 4.50 | 102.254 | 102.254 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4590.76 | 4590.76 | 3.82 | 86.971 | 86.971 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00713 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3472.22 | 3472.22 | 2.89 | 65.781 | 65.781 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00705 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4922.25 | 4922.25 | 4.10 | 93.251 | 93.251 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00717 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4926.40 | 4926.40 | 4.10 | 93.330 | 93.330 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00717 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3501.23 | 3501.23 | 2.92 | 66.331 | 66.331 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00705 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4921.46 | 4921.46 | 4.10 | 93.236 | 93.236 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00717 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6469.22 | 6469.22 | 5.39 | 122.556 | 122.556 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6470.80 | 6470.80 | 5.39 | 122.585 | 122.585 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 6426.21 | 6426.21 | 5.35 | 121.741 | 121.741 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5048.94 | 5048.94 | 4.21 | 95.650 | 95.650 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5043.18 | 5043.18 | 4.20 | 95.541 | 95.541 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6472.76 | 6472.76 | 5.39 | 122.623 | 122.623 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
HEATEDBSMT | 6142.41 | 6142.41 | 0.79 | 116.375 | 116.375 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 72.00 | 72.00 | 0.00800 | 38.66 | 0.00513 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 | 945.79 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 | 336.73 | 73.36 | 73.36 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 | 429.16 | 102.19 | 102.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 | 523.50 | 102.36 | 102.36 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 | 331.04 | 75.86 | 75.86 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 | 411.57 | 102.25 | 102.25 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 | 512.57 | 86.97 | 86.97 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 | 320.23 | 65.78 | 65.78 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 | 409.10 | 93.25 | 93.25 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 | 503.85 | 93.33 | 93.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 | 317.31 | 66.33 | 66.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 | 392.79 | 93.24 | 93.24 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 603.94 | 603.94 | 121.74 | 121.74 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 412.14 | 412.14 | 95.54 | 95.54 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 490.61 | 490.61 | 122.59 | 122.59 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 603.80 | 603.80 | 122.62 | 122.62 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 413.12 | 413.12 | 95.65 | 95.65 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 490.09 | 490.09 | 122.56 | 122.56 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 493.86 | 493.86 | 116.37 | 116.37 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2734.25 | 3327.25 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2315.25 | 3323.50 | 44.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2995.50 | 3185.75 | 47.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2782.25 | 3960.75 | 100.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2038.25 | 4172.75 | 48.25 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2742.25 | 3845.25 | 49.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3271.75 | 3101.25 | 36.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2491.75 | 3016.75 | 22.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3182.50 | 2962.50 | 24.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2949.75 | 3750.00 | 67.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2205.25 | 3852.50 | 28.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2937.50 | 3592.00 | 26.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3237.00 | 3542.00 | 43.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3409.50 | 3113.00 | 41.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3409.75 | 3279.75 | 45.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2679.50 | 3758.75 | 39.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2836.75 | 3230.25 | 35.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3216.75 | 3694.00 | 58.75 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3876.00 | 4419.75 | 109.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 88.75 | 0.00 | 88.75 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 36.00 | 0.00 | 36.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 82.00 | 0.00 | 82.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 214.75 | 64.75 | 214.75 | 64.75 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13.25 | 44.50 | 13.25 | 44.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 33.50 | 5.25 | 33.50 | 5.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11.50 | 51.00 | 11.50 | 51.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 26.75 | 0.00 | 26.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 117.00 | 0.00 | 117.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 205.00 | 54.25 | 205.00 | 54.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5.50 | 27.75 | 5.50 | 27.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 84.75 | 1.25 | 84.75 | 1.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21.00 | 53.25 | 21.00 | 53.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.50 | 52.50 | 44.50 | 52.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 45.75 | 79.50 | 45.75 | 79.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.00 | 75.25 | 1.00 | 75.25 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 69.00 | 0.00 | 69.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 217.75 | 81.75 | 217.75 | 81.75 |
HEATEDBSMT | 583.75 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1202.75 | 137.25 | 628.75 | 137.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.147 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.128 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.145 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.144 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.127 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.145 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.064 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.064 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.063 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.063 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.145 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.145 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.145 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.127 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.128 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.144 | 0.000 | 0.265 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Fans:Electricity | 10836.38 | 108.69 | 04-APR-00:15 | 3372.55 | 16-JUL-17:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
ElectricityPurchased:Plant | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
Cogeneration:ElectricityPurchased | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
ElectricityNet:Plant | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
Cogeneration:ElectricityNet | 164546.10 | 7362.81 | 11-APR-04:00 | 43013.82 | 16-JUL-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 61206.85 | 523.57 | 04-APR-00:15 | 23252.97 | 16-JUL-18:00 |
General:Fans:Electricity | 10836.38 | 108.69 | 04-APR-00:15 | 3372.55 | 16-JUL-17:15 |
Cooling:Electricity | 50370.47 | 112.92 | 31-JAN-07:15 | 19880.42 | 16-JUL-18:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2607.42 | 0.00 | 01-JAN-15:00 | 220479.27 | 31-JAN-07:15 |
Gas:Plant | 2607.42 | 0.00 | 01-JAN-15:00 | 220479.27 | 31-JAN-07:15 |
WaterSystems:Gas | 2027.96 | 0.00 | 01-JAN-00:15 | 113439.85 | 21-JAN-08:15 |
Water Heater:WaterSystems:Gas | 2027.96 | 0.00 | 01-JAN-00:15 | 113439.85 | 21-JAN-08:15 |
Heating:Gas | 579.46 | 0.00 | 01-JAN-14:30 | 107326.07 | 31-JAN-07:15 |
Boiler:Heating:Gas | 579.46 | 0.00 | 01-JAN-14:30 | 107326.07 | 31-JAN-07:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
Water:Plant | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
WaterSystems:Water | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
MainsWater:Plant | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 23-FEB-03:00 | 0.18 | 01-JAN-08:30 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 129547.35 | 388.54 | 21-JUL-03:00 | 112711.34 | 31-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 84127.22 | 388.54 | 21-JUL-03:00 | 28621.01 | 21-JAN-08:30 |
WaterSystems:PlantLoopHeatingDemand | 84127.22 | 388.54 | 21-JUL-03:00 | 28621.01 | 21-JAN-08:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1458410.12 | 15554.62 | 05-APR-03:00 | 426494.36 | 02-JUL-18:30 |
EnergyTransfer:Building | 630913.97 | 6977.21 | 04-APR-00:15 | 203931.13 | 02-JUL-18:30 |
EnergyTransfer:Zone:HEATEDBSMT | 37983.83 | 0.00 | 08-JAN-02:00 | 13298.87 | 03-JAN-23:00 |
Heating:EnergyTransfer | 48847.72 | 0.00 | 08-JAN-14:00 | 87938.44 | 31-JAN-07:15 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 7623.92 | 0.00 | 08-JAN-02:00 | 13298.87 | 03-JAN-23:00 |
Cooling:EnergyTransfer | 582066.25 | 2050.91 | 31-JAN-07:15 | 203931.13 | 02-JUL-18:30 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 30359.91 | 0.00 | 01-JAN-00:15 | 11287.61 | 16-JUL-18:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 102243.79 | 2050.91 | 31-JAN-07:15 | 21335.76 | 29-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 102243.79 | 2050.91 | 31-JAN-07:15 | 21335.76 | 29-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24269.68 | 0.00 | 01-JAN-00:15 | 8103.58 | 16-JUL-20:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1425.89 | 0.00 | 01-JAN-00:15 | 3624.55 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 22843.79 | 0.00 | 01-JAN-00:15 | 8103.58 | 16-JUL-20:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 31270.50 | 0.00 | 01-JAN-00:15 | 10264.22 | 16-JUL-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2391.37 | 0.00 | 01-JAN-00:15 | 5254.91 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 28879.13 | 0.00 | 01-JAN-00:15 | 10264.22 | 16-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 28756.04 | 0.00 | 01-JAN-14:30 | 12138.00 | 18-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3276.23 | 0.00 | 01-JAN-14:30 | 5399.22 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 25479.81 | 0.00 | 01-JAN-00:15 | 12138.00 | 18-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21331.82 | 0.00 | 01-JAN-00:15 | 7883.92 | 02-JUL-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2262.29 | 0.00 | 01-JAN-00:15 | 3988.80 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19069.53 | 0.00 | 01-JAN-00:15 | 7883.92 | 02-JUL-19:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28211.42 | 0.00 | 01-JAN-12:15 | 10015.51 | 16-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3095.94 | 0.00 | 01-JAN-12:15 | 5292.29 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25115.48 | 0.00 | 01-JAN-00:15 | 10015.51 | 16-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31303.09 | 0.00 | 01-JAN-00:15 | 12003.23 | 29-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1712.57 | 0.00 | 01-JAN-00:15 | 4216.31 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29590.52 | 0.00 | 01-JAN-00:15 | 12003.23 | 29-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23976.34 | 0.00 | 01-JAN-00:15 | 7726.27 | 16-JUL-20:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 933.25 | 0.00 | 01-JAN-00:15 | 3032.58 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23043.09 | 0.00 | 01-JAN-00:15 | 7726.27 | 16-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 30886.78 | 0.00 | 01-JAN-00:15 | 9828.49 | 16-JUL-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1710.34 | 0.00 | 01-JAN-00:15 | 4599.68 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29176.45 | 0.00 | 01-JAN-00:15 | 9828.49 | 16-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 28143.90 | 0.00 | 01-JAN-00:15 | 11757.01 | 18-JUN-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2526.36 | 0.00 | 01-JAN-00:15 | 4789.78 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25617.54 | 0.00 | 01-JAN-00:15 | 11757.01 | 18-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20770.53 | 0.00 | 01-JAN-00:15 | 7628.75 | 16-JUL-21:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1583.29 | 0.00 | 01-JAN-00:15 | 3351.47 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 19187.24 | 0.00 | 01-JAN-00:15 | 7628.75 | 16-JUL-21:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 27712.96 | 0.00 | 01-JAN-00:15 | 9608.72 | 16-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2352.87 | 0.00 | 01-JAN-00:15 | 4644.16 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25360.09 | 0.00 | 01-JAN-00:15 | 9608.72 | 16-JUL-19:30 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 33631.42 | 0.00 | 01-JAN-13:15 | 11474.85 | 16-JUL-20:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 3573.35 | 0.00 | 01-JAN-13:15 | 6244.00 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 30058.08 | 0.00 | 01-JAN-00:15 | 11474.85 | 16-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 35240.32 | 0.00 | 01-JAN-00:15 | 11448.69 | 16-JUL-20:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2847.00 | 0.00 | 01-JAN-00:15 | 6207.83 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32393.32 | 0.00 | 01-JAN-00:15 | 11448.69 | 16-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 35935.62 | 0.00 | 01-JAN-00:15 | 13842.63 | 12-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 3106.11 | 0.00 | 01-JAN-00:15 | 6105.95 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32829.50 | 0.00 | 01-JAN-00:15 | 13842.63 | 12-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 26701.54 | 0.00 | 01-JAN-00:15 | 9673.45 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2695.59 | 0.00 | 01-JAN-00:15 | 4936.69 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24005.95 | 0.00 | 01-JAN-00:15 | 9673.45 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 28304.91 | 0.00 | 01-JAN-00:15 | 9658.22 | 16-JUL-21:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1923.49 | 0.00 | 01-JAN-00:15 | 4645.96 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26381.42 | 0.00 | 01-JAN-00:15 | 9658.22 | 16-JUL-21:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 34239.47 | 0.00 | 01-JAN-00:15 | 13848.18 | 18-JUN-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 3807.84 | 0.00 | 01-JAN-00:15 | 6386.11 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30431.63 | 0.00 | 01-JAN-00:15 | 13848.18 | 18-JUN-19:15 |
EnergyTransfer:Plant | 130484.12 | 388.54 | 21-JUL-03:00 | 112851.56 | 31-JAN-07:15 |
WaterSystems:EnergyTransfer | 84127.22 | 388.54 | 21-JUL-03:00 | 28621.01 | 21-JAN-08:30 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 84127.22 | 388.54 | 21-JUL-03:00 | 28621.01 | 21-JAN-08:30 |
EnergyTransfer:HVAC | 697012.04 | 6969.20 | 11-APR-07:00 | 233240.52 | 10-AUG-18:30 |
HeatingCoils:EnergyTransfer | 45420.12 | 0.00 | 01-JAN-14:30 | 85720.65 | 31-JAN-07:15 |
PlantLoopHeatingDemand:HVAC | 45420.12 | 0.00 | 01-JAN-14:30 | 85720.65 | 31-JAN-07:15 |
HeatingCoils:PlantLoopHeatingDemand | 45420.12 | 0.00 | 01-JAN-14:30 | 85720.65 | 31-JAN-07:15 |
CoolingCoils:EnergyTransfer | 651591.91 | 2158.86 | 31-JAN-07:15 | 233240.52 | 10-AUG-18:30 |
Boilers:EnergyTransfer | 46356.89 | 0.00 | 01-JAN-14:30 | 85860.86 | 31-JAN-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8514.62 | 0.000 | 0.000 | 2872.562 | 2456.001 | 10405.511 | 11935.506 | 0.000 | 4763.342 | 77857.765 | 0.000 | -2952.91 | 0.000 | -5094.02 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1425.879 | -1902.38 | 0.000 | 0.000 | 2934.577 | 2456.001 | 10405.511 | 5109.780 | 0.000 | 4544.697 | 1557.429 | 0.000 | -1135.27 | 0.000 | -4454.81 | -0.07 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 2391.354 | -2404.98 | 0.000 | 0.000 | 2948.053 | 2456.001 | 10405.511 | 11916.038 | 0.000 | 4770.777 | 1273.162 | 0.000 | -2673.82 | 0.000 | -4607.97 | -0.03 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3276.207 | -2121.90 | 0.000 | 0.000 | 2959.533 | 2456.001 | 10405.511 | 9129.175 | 0.000 | 4766.944 | 0.380 | 0.000 | -2905.04 | 0.000 | -4436.90 | -171.61 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 2262.273 | -1588.07 | 0.000 | 0.000 | 2952.599 | 2456.001 | 10405.511 | 2084.176 | 0.000 | 4544.852 | 0.051 | 0.000 | -1203.65 | 0.000 | -4291.74 | -140.45 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3095.920 | -2091.56 | 0.000 | 0.000 | 2961.534 | 2456.001 | 10405.511 | 8915.996 | 0.000 | 4770.518 | 0.021 | 0.000 | -2650.50 | 0.000 | -4477.97 | -361.52 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1712.557 | -2464.23 | 0.000 | 0.000 | 2934.484 | 2456.001 | 10405.511 | 11990.269 | 0.000 | 3707.952 | 2978.199 | 0.000 | -2886.74 | 0.000 | -3707.71 | -0.06 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 933.242 | -1918.98 | 0.000 | 0.000 | 2921.557 | 2456.001 | 10405.511 | 5108.768 | 0.000 | 3486.315 | 2452.185 | 0.000 | -1159.68 | 0.000 | -3560.79 | -0.04 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1710.324 | -2429.75 | 0.000 | 0.000 | 2937.430 | 2456.001 | 10405.511 | 11903.544 | 0.000 | 3710.722 | 2502.470 | 0.000 | -2732.17 | 0.000 | -3717.38 | -0.09 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2526.342 | -2133.37 | 0.000 | 0.000 | 2949.013 | 2456.001 | 10405.511 | 9141.413 | 0.000 | 3709.371 | 981.991 | 0.000 | -2964.67 | 0.000 | -3587.40 | -0.04 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 1583.277 | -1597.87 | 0.000 | 0.000 | 2940.431 | 2456.001 | 10405.511 | 2097.824 | 0.000 | 3487.186 | 879.972 | 0.000 | -1226.92 | 0.000 | -3435.99 | -0.30 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2352.857 | -2111.93 | 0.000 | 0.000 | 2952.309 | 2456.001 | 10405.511 | 8915.991 | 0.000 | 3710.589 | 879.218 | 0.000 | -2699.74 | 0.000 | -3612.62 | -0.08 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3573.324 | -2503.17 | 0.000 | 0.000 | 2956.116 | 2456.001 | 10405.511 | 8850.831 | 0.000 | 4746.626 | 4291.317 | 0.000 | -2705.84 | 0.000 | -4515.78 | -0.11 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 2846.982 | -2697.64 | 0.000 | 0.000 | 2945.305 | 2456.001 | 10405.511 | 11867.431 | 0.000 | 4746.670 | 4458.520 | 0.000 | -2716.34 | 0.000 | -4616.74 | -0.08 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3106.088 | -2733.97 | 0.000 | 0.000 | 2944.645 | 2456.001 | 10405.511 | 11966.070 | 0.000 | 4744.123 | 4648.800 | 0.000 | -2852.79 | 0.000 | -4588.94 | -0.18 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 2695.573 | -1999.16 | 0.000 | 0.000 | 2947.104 | 2456.001 | 10405.511 | 2069.934 | 0.000 | 4524.145 | 4469.941 | 0.000 | -1223.03 | 0.000 | -4339.18 | -0.02 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 1923.474 | -2196.99 | 0.000 | 0.000 | 2933.887 | 2456.001 | 10405.511 | 5094.059 | 0.000 | 4523.310 | 4646.219 | 0.000 | -1148.32 | 0.000 | -4452.69 | -0.27 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3807.816 | -2534.28 | 0.000 | 0.000 | 2954.332 | 2456.001 | 10405.511 | 9064.952 | 0.000 | 4745.835 | 4437.133 | 0.000 | -2954.15 | 0.000 | -4485.77 | -0.09 |
HEATEDBSMT | 0.000 | 0.000 | 7623.924 | -2528.30 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22735.984 | 0.000 | 0.000 | 0.000 | 0.000 | -0.06 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7518.006 | 52404.513 | 0.000 | 0.000 | 0.000 | -59922.52 | -0.15 |
Total Facility | 0.000 | 0.000 | 48847.414 | -48473.14 | 0.000 | 0.000 | 52945.471 | 44208.020 | 187299.191 | 147161.757 | 0.000 | 85521.980 | 193455.271 | 0.000 | -40791.59 | 0.000 | -135906.91 | -675.23 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-SEP-16:25 | 0.00 | 0.00 | 0.00 | -1.8 | 0.00 | 0.00 | 140.43 | 384.73 | 1343.91 | 6544.92 | 0.00 | 1939.99 | 10987.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16-JUL-20:19 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 425.73 | 799.44 | 1638.87 | 482.24 | 0.00 | 2100.68 | 2673.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-JUL-19:00 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 424.59 | 721.37 | 1735.60 | 1818.55 | 0.00 | 2964.48 | 2607.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 18-JUN-19:08 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 421.84 | 799.44 | 1674.43 | 3304.71 | 0.00 | 2245.33 | 3703.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16-JUL-20:55 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 423.49 | 799.44 | 1638.87 | 433.15 | 0.00 | 1923.58 | 2687.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16-JUL-19:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 422.02 | 799.44 | 1674.43 | 1475.36 | 0.00 | 2678.52 | 2978.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-SEP-16:20 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.44 | 384.73 | 1343.91 | 6541.38 | 0.00 | 1543.61 | 2049.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16-JUL-20:35 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.00 | 799.44 | 1638.87 | 469.18 | 0.00 | 1527.32 | 2915.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-JUL-19:00 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 425.40 | 721.37 | 1735.60 | 1840.50 | 0.00 | 2144.76 | 2966.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 18-JUN-19:18 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.84 | 799.44 | 1674.43 | 2214.67 | 0.00 | 1569.12 | 5106.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-JUL-21:05 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 474.76 | 604.57 | 1566.93 | 437.94 | 0.00 | 1455.01 | 3102.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16-JUL-19:38 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 425.24 | 799.44 | 1674.43 | 1347.86 | 0.00 | 1895.18 | 3515.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 16-JUL-20:35 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 423.28 | 799.44 | 1638.87 | 1086.41 | 0.00 | 2091.48 | 5459.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 16-JUL-20:35 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 424.74 | 799.44 | 1638.87 | 1091.22 | 0.00 | 2099.18 | 5452.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11-JUN-19:17 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 424.22 | 799.44 | 1674.43 | 1799.10 | 0.00 | 1907.66 | 7243.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-JUL-19:21 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 422.41 | 799.44 | 1674.43 | 486.16 | 0.00 | 2146.95 | 4173.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 02-JUL-19:18 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.23 | 799.44 | 1674.43 | 465.93 | 0.00 | 2151.11 | 4205.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 18-JUN-19:18 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 424.84 | 799.44 | 1674.43 | 2179.49 | 0.00 | 2083.02 | 6723.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-18:19 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11319.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JUL-18:18 | 0.00 | 0.00 | 0.00 | -17.0 | 0.00 | 0.00 | 7592.38 | 12984.58 | 31240.86 | 34904.83 | 0.00 | 43580.43 | 82909.73 | 0.00 | 0.00 | 0.00 | -9165.3 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 3624.60 | 0.00 | 0.00 | 0.00 | 464.76 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.0 | 0.00 | -2912.2 | -1979.6 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 26-DEC-00:10 | 0.00 | 0.00 | 5650.28 | 0.00 | 0.00 | 0.00 | 541.27 | 54.96 | 960.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1472.5 | 0.00 | -2013.9 | -3720.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 07-FEB-13:38 | 0.00 | 0.00 | 23674.07 | 0.00 | 0.00 | 0.00 | 138.85 | 103.05 | 1076.60 | 550.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1197.3 | -24345.7 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 30-JAN-17:42 | 0.00 | 0.00 | 12350.90 | 0.00 | 0.00 | 0.00 | 304.93 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -454.1 | 0.00 | -1963.0 | -12430.9 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30-JAN-17:51 | 0.00 | 0.00 | 7099.91 | 0.00 | 0.00 | 0.00 | 293.14 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1241.5 | 0.00 | -2180.3 | -6163.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 4216.42 | 0.00 | 0.00 | 0.00 | 464.77 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1847.4 | 0.00 | -2333.9 | -2048.3 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 31-JAN-08:08 | 0.00 | 0.00 | 3032.58 | 0.00 | 0.00 | 0.00 | 215.05 | 151.14 | 1145.90 | 106.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2123.4 | -2527.4 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 14-DEC-00:10 | 0.00 | 0.00 | 7373.95 | 0.00 | 0.00 | 0.00 | 546.95 | 54.96 | 960.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1656.5 | 0.00 | -1924.9 | -5355.2 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20-JAN-13:23 | 0.00 | 0.00 | 22675.61 | 0.00 | 0.00 | 0.00 | 138.02 | 103.05 | 1076.60 | 257.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -946.7 | -23304.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 30-JAN-17:54 | 0.00 | 0.00 | 8646.43 | 0.00 | 0.00 | 0.00 | 301.16 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -500.2 | 0.00 | -1459.8 | -9179.8 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 01-JAN-02:00 | 0.00 | 0.00 | 4776.11 | 0.00 | 0.00 | 0.00 | 537.25 | 54.96 | 892.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1355.8 | 0.00 | -1470.8 | -3434.6 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 6244.10 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1818.1 | 0.00 | -3075.2 | -3363.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 6207.93 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1823.4 | 0.00 | -3075.2 | -3322.5 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 6106.05 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1820.2 | 0.00 | -3075.2 | -3223.8 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 31-JAN-08:08 | 0.00 | 0.00 | 4936.61 | 0.00 | 0.00 | 0.00 | 215.05 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -637.0 | 0.00 | -2835.5 | -2976.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 4646.04 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -744.3 | 0.00 | -2918.1 | -2996.8 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 09-NOV-10:43 | 0.00 | 0.00 | 12132.82 | 0.00 | 0.00 | 0.00 | 131.23 | 103.05 | 1079.31 | 401.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -406.1 | -13441.5 |
HEATEDBSMT | 28-JAN-22:45 | 0.00 | 0.00 | 26207.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26207.5 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JAN-07:15 | -2050.9 | 0.17 | 87939.99 | -0.2 | 0.00 | 0.00 | 8321.70 | 6183.13 | 21687.53 | 0.00 | 0.00 | 3054.39 | 0.00 | 0.00 | -26502.8 | 0.00 | -50230.6 | -48402.4 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 945.793 | 2.00 | 2.00 | 1.00 | 44.9950 | 945.793 | 0.048 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 336.727 | 2.00 | 2.00 | 1.00 | 44.9950 | 336.727 | 0.134 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 429.164 | 2.00 | 2.00 | 1.00 | 44.9950 | 429.164 | 0.105 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 523.501 | 2.00 | 2.00 | 1.00 | 44.9950 | 523.501 | 0.086 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 331.037 | 2.00 | 2.00 | 1.00 | 44.9950 | 331.037 | 0.136 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 411.568 | 2.00 | 2.00 | 1.00 | 44.9950 | 411.568 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 512.571 | 2.00 | 2.00 | 1.00 | 44.9950 | 512.571 | 0.088 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 320.229 | 2.00 | 2.00 | 1.00 | 44.9950 | 320.229 | 0.141 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 409.103 | 2.00 | 2.00 | 1.00 | 44.9950 | 409.103 | 0.110 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 503.851 | 2.00 | 2.00 | 1.00 | 44.9950 | 503.851 | 0.089 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.308 | 2.00 | 2.00 | 1.00 | 44.9950 | 317.308 | 0.142 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 392.795 | 2.00 | 2.00 | 1.00 | 44.9950 | 392.795 | 0.115 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 603.937 | 2.00 | 2.00 | 1.00 | 44.9950 | 603.937 | 0.075 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 412.136 | 2.00 | 2.00 | 1.00 | 44.9950 | 412.136 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 490.612 | 2.00 | 2.00 | 1.00 | 44.9950 | 490.612 | 0.092 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 603.795 | 2.00 | 2.00 | 1.00 | 44.9950 | 603.795 | 0.075 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 413.123 | 2.00 | 2.00 | 1.00 | 44.9950 | 413.123 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 490.091 | 2.00 | 2.00 | 1.00 | 44.9950 | 490.091 | 0.092 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 493.855 | 0.00 | 0.00 | 1.00 | 44.9950 | 493.855 | 0.091 | 1.000 | 44.9950 | 0.09 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 73.359 | 2.00 | 2.00 | 1.00 | 44.9950 | 73.359 | 1.000 | 1.000 | 44.9950 | 0.61 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 102.187 | 2.00 | 2.00 | 1.00 | 44.9950 | 102.187 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 102.365 | 2.00 | 2.00 | 1.00 | 44.9950 | 102.365 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 75.864 | 2.00 | 2.00 | 1.00 | 44.9950 | 75.864 | 1.000 | 1.000 | 44.9950 | 0.59 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 102.254 | 2.00 | 2.00 | 1.00 | 44.9950 | 102.254 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 86.971 | 2.00 | 2.00 | 1.00 | 44.9950 | 86.971 | 1.000 | 1.000 | 44.9950 | 0.52 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 65.781 | 2.00 | 2.00 | 1.00 | 44.9950 | 65.781 | 1.000 | 1.000 | 44.9950 | 0.68 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 93.251 | 2.00 | 2.00 | 1.00 | 44.9950 | 93.251 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.330 | 2.00 | 2.00 | 1.00 | 44.9950 | 93.330 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 66.331 | 2.00 | 2.00 | 1.00 | 44.9950 | 66.331 | 1.000 | 1.000 | 44.9950 | 0.68 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 93.236 | 2.00 | 2.00 | 1.00 | 44.9950 | 93.236 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 121.741 | 2.00 | 2.00 | 1.00 | 44.9950 | 121.741 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 95.541 | 2.00 | 2.00 | 1.00 | 44.9950 | 95.541 | 1.000 | 1.000 | 44.9950 | 0.47 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 122.585 | 2.00 | 2.00 | 1.00 | 44.9950 | 122.585 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 122.623 | 2.00 | 2.00 | 1.00 | 44.9950 | 122.623 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 95.650 | 2.00 | 2.00 | 1.00 | 44.9950 | 95.650 | 1.000 | 1.000 | 44.9950 | 0.47 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 122.556 | 2.00 | 2.00 | 1.00 | 44.9950 | 122.556 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 116.375 | 0.00 | 0.00 | 1.00 | 44.9950 | 116.375 | 1.000 | 1.000 | 44.9950 | 0.39 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 945.793 | 945.7933 | 189.1587 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 336.727 | 336.7266 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 429.164 | 429.1637 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 523.501 | 523.5008 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 331.037 | 331.0367 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 411.568 | 411.5676 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 512.571 | 512.5709 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 320.229 | 320.2286 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 409.103 | 409.1030 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 503.851 | 503.8512 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.308 | 317.3083 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 392.795 | 392.7946 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 490.091 | 490.0914 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 490.612 | 490.6122 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 603.937 | 603.9367 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 413.123 | 413.1234 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 412.136 | 412.1360 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 603.795 | 603.7951 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 493.855 | 493.8553 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 | 945.793 | 945.79 | 189.1587 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 | 336.727 | 336.73 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 | 429.164 | 429.16 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 | 523.501 | 523.50 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 | 331.037 | 331.04 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 | 411.568 | 411.57 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 | 512.571 | 512.57 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 | 320.229 | 320.23 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 | 409.103 | 409.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 | 503.851 | 503.85 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 | 317.308 | 317.31 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 | 392.795 | 392.79 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 603.94 | 603.937 | 603.94 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 412.14 | 412.136 | 412.14 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 490.61 | 490.612 | 490.61 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 603.80 | 603.795 | 603.80 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 413.12 | 413.123 | 413.12 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 490.09 | 490.091 | 490.09 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 493.86 | 493.855 | 493.86 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 73.359 | 73.359 | 73.359 | 44.9950 | 0.613 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 102.187 | 102.187 | 102.187 | 44.9950 | 0.440 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 102.365 | 102.365 | 102.365 | 44.9950 | 0.440 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 75.864 | 75.864 | 75.864 | 44.9950 | 0.593 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 102.254 | 102.254 | 102.254 | 44.9950 | 0.440 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 86.971 | 86.971 | 86.971 | 44.9950 | 0.517 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 65.781 | 65.781 | 65.781 | 44.9950 | 0.684 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 93.251 | 93.251 | 93.251 | 44.9950 | 0.483 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.330 | 93.330 | 93.330 | 44.9950 | 0.482 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 66.331 | 66.331 | 66.331 | 44.9950 | 0.678 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 93.236 | 93.236 | 93.236 | 44.9950 | 0.483 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 122.556 | 122.556 | 122.556 | 44.9950 | 0.367 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 122.585 | 122.585 | 122.585 | 44.9950 | 0.367 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 121.741 | 121.741 | 121.741 | 44.9950 | 0.370 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 95.650 | 95.650 | 95.650 | 44.9950 | 0.470 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 95.541 | 95.541 | 95.541 | 44.9950 | 0.471 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 122.623 | 122.623 | 122.623 | 44.9950 | 0.367 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 116.375 | 116.375 | 116.375 | 44.9950 | 0.387 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 73.36 | 73.359 | 73.36 | 73.36 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 102.19 | 102.187 | 102.19 | 102.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 102.36 | 102.365 | 102.36 | 102.36 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 75.86 | 75.864 | 75.86 | 75.86 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 102.25 | 102.254 | 102.25 | 102.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 86.97 | 86.971 | 86.97 | 86.97 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 65.78 | 65.781 | 65.78 | 65.78 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 93.25 | 93.251 | 93.25 | 93.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 93.33 | 93.330 | 93.33 | 93.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 66.33 | 66.331 | 66.33 | 66.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 93.24 | 93.236 | 93.24 | 93.24 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 121.74 | 121.741 | 121.74 | 121.74 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 95.54 | 95.541 | 95.54 | 95.54 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 122.59 | 122.585 | 122.59 | 122.59 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 122.62 | 122.623 | 122.62 | 122.62 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 95.65 | 95.650 | 95.65 | 95.65 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 122.56 | 122.556 | 122.56 | 122.56 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 116.37 | 116.375 | 116.37 | 116.37 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 628.75 |
Number of hours cooling loads not met | 137.25 |
Number of hours not met | 766.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 579.46 | 107326.07 | 0.00 | 0.00 |
Space Cooling | 50370.47 | 19825.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 10836.38 | 3372.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2027.96 | 113153.20 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 15395.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 164546.10 | 2607.42 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 561829.05 |
Natural Gas | 0.00 | 260742.26 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 822571.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 1.29 |
Fans-Interior | 0.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 4.22 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.44 |
Service Water Heating | 1.52 |
Miscellaneous | -0.0 |
Subtotal | 1.96 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.37 |
Space Heating | 7.04 |
Space Cooling | 20.91 |
Fans-Interior | 4.50 |
Service Water Heating | 24.65 |
Receptacle Equipment | 36.46 |
Miscellaneous | 1.06 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 493.86 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 490.09 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 490.61 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 603.94 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 413.12 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 412.14 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 603.80 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 603.94 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 412.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 490.61 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 603.80 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 413.12 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 490.09 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 493.86 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 | 2.15 | 0.789717 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 | 0.835533 | 0.760166 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 | 1.09 | 0.752743 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 | 1.24 | 0.775604 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 | 0.804688 | 0.767008 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 | 1.05 | 0.750958 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 | 1.22 | 0.774254 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 | 0.792047 | 0.761226 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 | 1.04 | 0.751879 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 | 1.20 | 0.774849 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 | 0.774032 | 0.765830 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 | 1.01 | 0.750099 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 603.94 | 1.41 | 0.780123 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 412.14 | 0.983751 | 0.773182 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 490.61 | 1.18 | 0.771543 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 603.80 | 1.41 | 0.780116 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 413.12 | 0.979316 | 0.775555 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 490.09 | 1.18 | 0.771505 |
DX COOLING COIL_UNITHEATEDBSMT | 493.86 | 1.22 | 0.762564 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 | 945.79 | 945.79 | 2.15 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 | 336.73 | 336.73 | 0.835533 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 | 429.16 | 429.16 | 1.09 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 | 523.50 | 523.50 | 1.24 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 | 331.04 | 331.04 | 0.804688 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 | 411.57 | 411.57 | 1.05 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 | 512.57 | 512.57 | 1.22 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 | 320.23 | 320.23 | 0.792047 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 | 409.10 | 409.10 | 1.04 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 | 503.85 | 503.85 | 1.20 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 | 317.31 | 317.31 | 0.774032 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 | 392.79 | 392.79 | 1.01 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 603.94 | 603.94 | 603.94 | 1.41 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 412.14 | 412.14 | 412.14 | 0.983751 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 490.61 | 490.61 | 490.61 | 1.18 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 603.80 | 603.80 | 603.80 | 1.41 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 413.12 | 413.12 | 413.12 | 0.979316 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 490.09 | 490.09 | 490.09 | 1.18 | 1.00 |
ACANDF_UNITHEATEDBSMT | 493.86 | 493.86 | 493.86 | 1.22 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 50753.25 | 5.12 | 726.18 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 19075.35 | 1.93 | 268.22 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 23883.80 | 2.41 | 337.83 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 28790.93 | 2.91 | 408.86 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 18779.39 | 1.90 | 263.93 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 22968.50 | 2.32 | 324.58 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 28221.88 | 2.85 | 400.59 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 18216.90 | 1.84 | 255.76 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 22839.92 | 2.31 | 322.68 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 27768.34 | 2.80 | 394.02 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 18065.00 | 1.82 | 253.56 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 21991.63 | 2.22 | 310.40 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 32975.05 | 3.33 | 469.39 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 22997.96 | 2.32 | 325.00 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 27080.24 | 2.73 | 384.07 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 32967.69 | 3.33 | 469.28 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 23049.32 | 2.33 | 325.75 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 27053.14 | 2.73 | 383.68 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 27246.84 | 2.75 | 386.26 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 945.79 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 336.73 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 429.16 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 523.50 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 331.04 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 411.57 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 512.57 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 320.23 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 409.10 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 503.85 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 317.31 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 392.79 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 603.94 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 412.14 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 490.61 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 603.80 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 413.12 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 490.09 |
SUPPLY FAN_UNITHEATEDBSMT | 493.86 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 6.67 | 125.16 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 6.67 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 496569.28 | 49.93 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 92.030 | 0.000 | 0.000 | 92.030 |
February | 672.000 | 94.600 | 0.000 | 0.000 | 94.600 |
March | 744.000 | 112.069 | 0.000 | 0.000 | 112.069 |
April | 720.000 | 135.882 | 0.000 | 0.000 | 135.882 |
May | 744.000 | 159.187 | 0.000 | 0.000 | 159.187 |
June | 720.000 | 186.001 | 0.000 | 0.000 | 186.001 |
July | 744.000 | 206.562 | 0.000 | 0.000 | 206.562 |
August | 744.000 | 197.464 | 0.000 | 0.000 | 197.464 |
September | 720.000 | 171.913 | 0.000 | 0.000 | 171.913 |
October | 744.000 | 150.950 | 0.000 | 0.000 | 150.950 |
November | 720.000 | 113.935 | 0.000 | 0.000 | 113.935 |
December | 744.000 | 86.980 | 0.000 | 0.000 | 86.980 |
Annual Sum or Average | 8760.000 | 1707.573 | 0.000 | 0.000 | 1707.573 |
Minimum of Months | 672.000 | 86.980 | 0.000 | 0.000 | 86.980 |
Maximum of Months | 744.000 | 206.562 | 0.000 | 0.000 | 206.562 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 230.668 | 6.065 | 276.001 | 1.639 | 7.704 |
February | 278.913 | 10.347 | 191.490 | 1.133 | 11.480 |
March | 356.775 | 12.209 | 132.718 | 0.723 | 12.932 |
April | 556.563 | 25.170 | 47.125 | 0.221 | 25.392 |
May | 712.371 | 35.727 | 0.000 | 0.000 | 35.727 |
June | 720.000 | 55.530 | 0.000 | 0.000 | 55.530 |
July | 744.000 | 68.171 | 0.000 | 0.000 | 68.171 |
August | 744.000 | 62.464 | 0.000 | 0.000 | 62.464 |
September | 720.000 | 49.096 | 0.000 | 0.000 | 49.096 |
October | 683.348 | 35.344 | 3.375 | 0.005 | 35.349 |
November | 431.598 | 15.673 | 66.481 | 0.212 | 15.885 |
December | 206.960 | 5.315 | 324.250 | 2.159 | 7.474 |
Annual Sum or Average | 6385.196 | 381.113 | 1041.440 | 6.093 | 387.206 |
Minimum of Months | 206.960 | 5.315 | 0.000 | 0.000 | 7.474 |
Maximum of Months | 744.000 | 68.171 | 324.250 | 2.159 | 68.171 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 201.987 | 5.773 | 262.607 | 5.061 | 20.804 |
February | 271.172 | 11.828 | 178.000 | 3.319 | 21.481 |
March | 371.967 | 15.163 | 114.083 | 2.100 | 23.427 |
April | 561.976 | 32.889 | 39.625 | 0.593 | 34.941 |
May | 705.644 | 46.489 | 0.000 | 0.000 | 46.489 |
June | 720.000 | 71.287 | 0.000 | 0.000 | 71.287 |
July | 744.000 | 85.511 | 0.000 | 0.000 | 85.511 |
August | 744.000 | 77.980 | 0.000 | 0.000 | 77.980 |
September | 720.000 | 60.111 | 0.000 | 0.000 | 60.111 |
October | 671.646 | 41.448 | 2.625 | 0.033 | 43.761 |
November | 419.910 | 16.900 | 59.250 | 0.794 | 24.883 |
December | 181.716 | 4.972 | 311.500 | 6.493 | 19.638 |
Annual Sum or Average | 6314.016 | 470.351 | 967.690 | 18.392 | 530.314 |
Minimum of Months | 181.716 | 4.972 | 0.000 | 0.000 | 19.638 |
Maximum of Months | 744.000 | 85.511 | 311.500 | 6.493 | 85.511 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 70.711 | 1.512 | 364.550 | 6.798 | 24.153 |
February | 181.860 | 6.963 | 247.414 | 4.286 | 22.186 |
March | 278.126 | 11.787 | 172.638 | 2.509 | 21.666 |
April | 506.519 | 31.421 | 56.301 | 0.745 | 34.444 |
May | 692.957 | 48.822 | 0.000 | 0.000 | 48.822 |
June | 720.000 | 76.492 | 0.000 | 0.000 | 76.492 |
July | 744.000 | 91.065 | 0.000 | 0.000 | 91.065 |
August | 744.000 | 81.336 | 0.000 | 0.000 | 81.336 |
September | 720.000 | 58.478 | 0.000 | 0.000 | 58.478 |
October | 639.783 | 34.455 | 24.944 | 0.151 | 36.280 |
November | 297.662 | 8.439 | 145.132 | 1.394 | 18.031 |
December | 54.679 | 0.860 | 411.089 | 8.593 | 28.941 |
Annual Sum or Average | 5650.297 | 451.631 | 1422.068 | 24.476 | 541.894 |
Minimum of Months | 54.679 | 0.860 | 0.000 | 0.000 | 18.031 |
Maximum of Months | 744.000 | 91.065 | 411.089 | 8.593 | 91.065 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 43.633 | 0.394 | 424.931 | 3.481 | 6.699 |
February | 168.110 | 4.091 | 271.537 | 2.160 | 7.503 |
March | 275.046 | 6.516 | 168.512 | 1.150 | 8.545 |
April | 538.761 | 21.867 | 54.817 | 0.351 | 22.270 |
May | 711.744 | 35.464 | 0.000 | 0.000 | 35.464 |
June | 720.000 | 56.495 | 0.000 | 0.000 | 56.495 |
July | 744.000 | 68.503 | 0.000 | 0.000 | 68.503 |
August | 744.000 | 60.911 | 0.000 | 0.000 | 60.911 |
September | 720.000 | 43.719 | 0.000 | 0.000 | 43.719 |
October | 664.513 | 26.528 | 12.273 | 0.023 | 26.567 |
November | 303.560 | 5.107 | 112.267 | 0.495 | 5.749 |
December | 15.833 | 0.123 | 495.556 | 4.563 | 7.592 |
Annual Sum or Average | 5649.200 | 329.718 | 1539.893 | 12.221 | 350.016 |
Minimum of Months | 15.833 | 0.123 | 0.000 | 0.000 | 5.749 |
Maximum of Months | 744.000 | 68.503 | 495.556 | 4.563 | 68.503 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 44.792 | 0.453 | 424.950 | 6.990 | 15.329 |
February | 188.619 | 5.487 | 252.767 | 4.133 | 14.449 |
March | 323.636 | 9.241 | 136.242 | 2.299 | 16.277 |
April | 552.475 | 29.063 | 42.250 | 0.624 | 30.821 |
May | 705.833 | 45.204 | 0.000 | 0.000 | 45.204 |
June | 720.000 | 70.618 | 0.000 | 0.000 | 70.618 |
July | 744.000 | 84.098 | 0.000 | 0.000 | 84.098 |
August | 744.000 | 74.992 | 0.000 | 0.000 | 74.992 |
September | 720.000 | 54.006 | 0.000 | 0.000 | 54.006 |
October | 663.032 | 32.439 | 4.750 | 0.053 | 34.538 |
November | 329.770 | 6.166 | 76.915 | 0.964 | 13.933 |
December | 17.562 | 0.124 | 504.658 | 8.921 | 16.550 |
Annual Sum or Average | 5753.719 | 411.892 | 1442.532 | 23.984 | 470.816 |
Minimum of Months | 17.562 | 0.124 | 0.000 | 0.000 | 13.933 |
Maximum of Months | 744.000 | 84.098 | 504.658 | 8.921 | 84.098 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 244.335 | 9.122 | 284.225 | 3.740 | 12.916 |
February | 283.915 | 14.788 | 191.062 | 2.497 | 18.219 |
March | 369.825 | 19.173 | 115.458 | 1.511 | 23.768 |
April | 554.628 | 36.227 | 34.458 | 0.420 | 38.185 |
May | 707.916 | 49.836 | 0.000 | 0.000 | 49.836 |
June | 720.000 | 75.121 | 0.000 | 0.000 | 75.121 |
July | 744.000 | 89.013 | 0.000 | 0.000 | 89.013 |
August | 744.000 | 82.067 | 0.000 | 0.000 | 82.067 |
September | 720.000 | 64.367 | 0.000 | 0.000 | 64.367 |
October | 673.857 | 44.172 | 10.625 | 0.043 | 44.783 |
November | 420.685 | 20.205 | 77.094 | 0.605 | 21.446 |
December | 217.074 | 7.925 | 334.869 | 4.913 | 12.838 |
Annual Sum or Average | 6400.235 | 512.016 | 1047.792 | 13.729 | 532.559 |
Minimum of Months | 217.074 | 7.925 | 0.000 | 0.000 | 12.838 |
Maximum of Months | 744.000 | 89.013 | 334.869 | 4.913 | 89.013 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 268.755 | 6.856 | 213.208 | 1.314 | 8.184 |
February | 321.043 | 11.508 | 150.020 | 0.957 | 12.465 |
March | 409.815 | 13.706 | 97.187 | 0.635 | 14.397 |
April | 603.837 | 26.365 | 28.500 | 0.183 | 26.598 |
May | 723.038 | 35.884 | 0.000 | 0.000 | 35.884 |
June | 720.000 | 54.125 | 0.000 | 0.000 | 54.125 |
July | 744.000 | 65.512 | 0.000 | 0.000 | 65.512 |
August | 744.000 | 60.726 | 0.000 | 0.000 | 60.726 |
September | 720.000 | 48.822 | 0.000 | 0.000 | 48.822 |
October | 692.192 | 35.791 | 1.250 | 0.001 | 35.792 |
November | 474.740 | 17.078 | 38.475 | 0.108 | 17.185 |
December | 238.555 | 6.046 | 269.142 | 1.866 | 7.918 |
Annual Sum or Average | 6659.973 | 382.417 | 797.782 | 5.064 | 387.607 |
Minimum of Months | 238.555 | 6.046 | 0.000 | 0.000 | 7.918 |
Maximum of Months | 744.000 | 65.512 | 269.142 | 1.866 | 65.512 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 229.647 | 6.325 | 200.383 | 3.438 | 21.449 |
February | 298.245 | 12.821 | 138.667 | 2.332 | 21.885 |
March | 409.505 | 16.611 | 87.250 | 1.504 | 23.221 |
April | 593.188 | 34.029 | 23.208 | 0.375 | 36.614 |
May | 718.054 | 46.603 | 0.000 | 0.000 | 46.603 |
June | 720.000 | 69.949 | 0.000 | 0.000 | 69.949 |
July | 744.000 | 82.794 | 0.000 | 0.000 | 82.794 |
August | 744.000 | 76.196 | 0.000 | 0.000 | 76.196 |
September | 720.000 | 59.829 | 0.000 | 0.000 | 59.829 |
October | 683.477 | 41.771 | 1.125 | 0.011 | 43.035 |
November | 447.909 | 18.041 | 32.500 | 0.378 | 23.687 |
December | 203.950 | 5.483 | 257.708 | 4.745 | 20.148 |
Annual Sum or Average | 6511.976 | 470.452 | 740.842 | 12.783 | 525.409 |
Minimum of Months | 203.950 | 5.483 | 0.000 | 0.000 | 20.148 |
Maximum of Months | 744.000 | 82.794 | 257.708 | 4.745 | 82.794 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 86.329 | 1.584 | 317.302 | 5.176 | 23.164 |
February | 202.232 | 7.623 | 208.923 | 3.265 | 21.626 |
March | 310.272 | 12.922 | 138.801 | 1.841 | 20.916 |
April | 543.208 | 32.480 | 48.160 | 0.536 | 34.997 |
May | 706.875 | 48.979 | 0.000 | 0.000 | 48.979 |
June | 720.000 | 75.187 | 0.000 | 0.000 | 75.187 |
July | 744.000 | 88.459 | 0.000 | 0.000 | 88.459 |
August | 744.000 | 79.739 | 0.000 | 0.000 | 79.739 |
September | 720.000 | 58.446 | 0.000 | 0.000 | 58.446 |
October | 654.773 | 34.913 | 18.191 | 0.080 | 36.726 |
November | 326.835 | 9.151 | 100.892 | 0.845 | 17.544 |
December | 63.737 | 0.912 | 371.435 | 6.830 | 28.007 |
Annual Sum or Average | 5822.260 | 450.395 | 1203.704 | 18.574 | 533.790 |
Minimum of Months | 63.737 | 0.912 | 0.000 | 0.000 | 17.544 |
Maximum of Months | 744.000 | 88.459 | 371.435 | 6.830 | 88.459 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 62.858 | 0.590 | 362.174 | 2.418 | 5.152 |
February | 209.689 | 4.958 | 229.736 | 1.497 | 7.401 |
March | 334.339 | 7.921 | 119.093 | 0.761 | 9.152 |
April | 589.746 | 23.148 | 43.056 | 0.222 | 23.402 |
May | 723.792 | 35.518 | 0.000 | 0.000 | 35.518 |
June | 720.000 | 54.859 | 0.000 | 0.000 | 54.859 |
July | 744.000 | 65.664 | 0.000 | 0.000 | 65.664 |
August | 744.000 | 59.053 | 0.000 | 0.000 | 59.053 |
September | 720.000 | 43.432 | 0.000 | 0.000 | 43.432 |
October | 672.483 | 26.980 | 4.468 | 0.006 | 26.991 |
November | 350.213 | 6.227 | 75.520 | 0.255 | 6.607 |
December | 31.054 | 0.233 | 454.283 | 3.356 | 5.690 |
Annual Sum or Average | 5902.173 | 328.584 | 1288.330 | 8.516 | 342.921 |
Minimum of Months | 31.054 | 0.233 | 0.000 | 0.000 | 5.152 |
Maximum of Months | 744.000 | 65.664 | 454.283 | 3.356 | 65.664 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 56.833 | 0.585 | 352.246 | 5.178 | 16.716 |
February | 212.334 | 6.322 | 207.625 | 3.046 | 15.155 |
March | 367.783 | 10.713 | 100.375 | 1.625 | 17.364 |
April | 583.600 | 30.375 | 32.375 | 0.416 | 32.282 |
May | 718.014 | 45.394 | 0.000 | 0.000 | 45.394 |
June | 720.000 | 69.323 | 0.000 | 0.000 | 69.323 |
July | 744.000 | 81.471 | 0.000 | 0.000 | 81.471 |
August | 744.000 | 73.346 | 0.000 | 0.000 | 73.346 |
September | 720.000 | 53.922 | 0.000 | 0.000 | 53.922 |
October | 674.114 | 32.900 | 1.500 | 0.015 | 34.321 |
November | 362.772 | 7.174 | 47.900 | 0.518 | 12.806 |
December | 26.098 | 0.198 | 451.563 | 7.022 | 15.243 |
Annual Sum or Average | 5929.548 | 411.722 | 1193.584 | 17.820 | 467.343 |
Minimum of Months | 26.098 | 0.198 | 0.000 | 0.000 | 12.806 |
Maximum of Months | 744.000 | 81.471 | 451.563 | 7.022 | 81.471 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 198.710 | 7.665 | 348.250 | 7.765 | 16.778 |
February | 255.936 | 14.702 | 218.167 | 5.016 | 24.637 |
March | 334.865 | 20.039 | 133.352 | 2.948 | 32.678 |
April | 528.298 | 40.687 | 46.106 | 0.897 | 44.994 |
May | 691.530 | 57.538 | 0.000 | 0.000 | 57.629 |
June | 720.000 | 89.053 | 0.000 | 0.000 | 89.053 |
July | 744.000 | 105.997 | 0.000 | 0.000 | 105.997 |
August | 744.000 | 95.959 | 0.000 | 0.000 | 95.959 |
September | 720.000 | 73.198 | 0.000 | 0.000 | 73.198 |
October | 650.625 | 47.638 | 14.333 | 0.166 | 50.888 |
November | 380.198 | 19.498 | 91.150 | 1.483 | 29.318 |
December | 172.250 | 6.374 | 392.349 | 9.736 | 16.776 |
Annual Sum or Average | 6140.413 | 578.348 | 1243.707 | 28.012 | 637.906 |
Minimum of Months | 172.250 | 6.374 | 0.000 | 0.000 | 16.776 |
Maximum of Months | 744.000 | 105.997 | 392.349 | 9.736 | 105.997 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 205.451 | 5.738 | 302.143 | 2.946 | 9.176 |
February | 273.091 | 11.715 | 204.458 | 2.020 | 13.735 |
March | 359.906 | 14.927 | 142.207 | 1.296 | 16.378 |
April | 560.559 | 31.154 | 51.875 | 0.414 | 31.568 |
May | 707.838 | 43.996 | 0.000 | 0.000 | 43.996 |
June | 720.000 | 68.655 | 0.000 | 0.000 | 68.655 |
July | 744.000 | 83.026 | 0.000 | 0.000 | 83.026 |
August | 744.000 | 75.243 | 0.000 | 0.000 | 75.243 |
September | 720.000 | 58.284 | 0.000 | 0.000 | 58.284 |
October | 675.430 | 39.816 | 15.875 | 0.040 | 39.856 |
November | 422.020 | 16.683 | 81.633 | 0.444 | 17.128 |
December | 185.125 | 4.787 | 346.958 | 3.858 | 8.655 |
Annual Sum or Average | 6317.419 | 454.026 | 1145.150 | 11.018 | 465.701 |
Minimum of Months | 185.125 | 4.787 | 0.000 | 0.000 | 8.655 |
Maximum of Months | 744.000 | 83.026 | 346.958 | 3.858 | 83.026 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 178.136 | 5.504 | 289.957 | 5.891 | 20.401 |
February | 263.158 | 13.232 | 189.167 | 3.816 | 23.078 |
March | 373.624 | 17.916 | 122.125 | 2.382 | 25.472 |
April | 570.882 | 39.495 | 43.458 | 0.694 | 41.349 |
May | 706.141 | 55.726 | 0.000 | 0.000 | 55.730 |
June | 720.000 | 85.961 | 0.000 | 0.000 | 85.961 |
July | 744.000 | 101.846 | 0.000 | 0.000 | 101.846 |
August | 744.000 | 92.142 | 0.000 | 0.000 | 92.142 |
September | 720.000 | 70.465 | 0.000 | 0.000 | 70.465 |
October | 665.737 | 46.558 | 11.732 | 0.106 | 48.475 |
November | 414.278 | 17.961 | 69.986 | 0.976 | 25.979 |
December | 159.274 | 4.486 | 335.333 | 7.520 | 20.149 |
Annual Sum or Average | 6259.230 | 551.291 | 1061.759 | 21.386 | 611.047 |
Minimum of Months | 159.274 | 4.486 | 0.000 | 0.000 | 20.149 |
Maximum of Months | 744.000 | 101.846 | 335.333 | 7.520 | 101.846 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 95.001 | 2.157 | 361.234 | 8.008 | 27.250 |
February | 201.182 | 9.633 | 238.788 | 4.986 | 26.800 |
March | 307.740 | 16.604 | 157.448 | 2.843 | 28.508 |
April | 524.617 | 39.271 | 52.460 | 0.878 | 42.974 |
May | 691.347 | 57.594 | 0.167 | 0.000 | 57.671 |
June | 720.000 | 89.556 | 0.000 | 0.000 | 89.556 |
July | 744.000 | 106.161 | 0.000 | 0.000 | 106.161 |
August | 744.000 | 95.343 | 0.000 | 0.000 | 95.343 |
September | 720.000 | 70.348 | 0.000 | 0.000 | 70.348 |
October | 634.457 | 41.096 | 28.422 | 0.235 | 43.882 |
November | 312.271 | 11.030 | 139.463 | 1.662 | 24.104 |
December | 67.212 | 1.295 | 407.259 | 10.124 | 32.515 |
Annual Sum or Average | 5761.828 | 540.087 | 1385.240 | 28.735 | 645.109 |
Minimum of Months | 67.212 | 1.295 | 0.000 | 0.000 | 24.104 |
Maximum of Months | 744.000 | 106.161 | 407.259 | 10.124 | 106.161 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 67.880 | 0.942 | 418.450 | 4.364 | 7.054 |
February | 202.877 | 6.835 | 264.695 | 2.668 | 9.997 |
March | 321.083 | 11.555 | 162.912 | 1.434 | 13.358 |
April | 555.167 | 29.973 | 54.750 | 0.444 | 30.417 |
May | 707.608 | 44.359 | 0.000 | 0.000 | 44.359 |
June | 720.000 | 69.584 | 0.000 | 0.000 | 69.584 |
July | 744.000 | 83.627 | 0.000 | 0.000 | 83.627 |
August | 744.000 | 75.042 | 0.000 | 0.000 | 75.042 |
September | 720.000 | 55.752 | 0.000 | 0.000 | 55.752 |
October | 659.930 | 33.362 | 24.018 | 0.075 | 33.460 |
November | 329.593 | 7.915 | 130.505 | 0.712 | 8.774 |
December | 40.775 | 0.447 | 489.657 | 5.691 | 8.132 |
Annual Sum or Average | 5812.914 | 419.394 | 1544.986 | 15.387 | 439.555 |
Minimum of Months | 40.775 | 0.447 | 0.000 | 0.000 | 7.054 |
Maximum of Months | 744.000 | 83.627 | 489.657 | 5.691 | 83.627 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 62.640 | 0.989 | 419.753 | 7.881 | 16.783 |
February | 210.818 | 8.375 | 248.347 | 4.611 | 18.501 |
March | 344.038 | 14.497 | 133.322 | 2.523 | 22.140 |
April | 566.662 | 38.150 | 46.000 | 0.718 | 39.895 |
May | 706.147 | 55.758 | 0.000 | 0.000 | 55.762 |
June | 720.000 | 86.378 | 0.000 | 0.000 | 86.378 |
July | 744.000 | 101.922 | 0.000 | 0.000 | 101.922 |
August | 744.000 | 91.544 | 0.000 | 0.000 | 91.544 |
September | 720.000 | 67.780 | 0.000 | 0.000 | 67.780 |
October | 653.550 | 40.174 | 15.000 | 0.133 | 41.940 |
November | 341.938 | 9.088 | 96.115 | 1.209 | 17.472 |
December | 39.196 | 0.443 | 493.146 | 10.090 | 17.309 |
Annual Sum or Average | 5852.987 | 515.097 | 1451.683 | 27.164 | 577.425 |
Minimum of Months | 39.196 | 0.443 | 0.000 | 0.000 | 16.783 |
Maximum of Months | 744.000 | 101.922 | 493.146 | 10.090 | 101.922 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 528.428 | 17.306 | 56.145 |
February | 0.000 | 0.000 | 465.209 | 10.636 | 42.867 |
March | 0.000 | 0.000 | 276.037 | 3.685 | 43.417 |
April | 12.250 | 0.050 | 30.667 | 0.181 | 0.231 |
May | 742.625 | 46.107 | 0.000 | 0.000 | 46.107 |
June | 720.000 | 96.145 | 0.000 | 0.000 | 96.145 |
July | 744.000 | 111.513 | 0.000 | 0.000 | 111.513 |
August | 744.000 | 102.221 | 0.000 | 0.000 | 102.221 |
September | 720.000 | 80.617 | 0.000 | 0.000 | 80.617 |
October | 744.000 | 44.772 | 0.000 | 0.000 | 44.772 |
November | 0.500 | 0.011 | 135.300 | 0.966 | 9.755 |
December | 0.000 | 0.000 | 575.896 | 17.968 | 48.393 |
Annual Sum or Average | 4427.375 | 481.435 | 2011.537 | 50.743 | 682.182 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.231 |
Maximum of Months | 744.000 | 111.513 | 575.896 | 17.968 | 111.513 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.69 |
February | 0.00 | 0.00 | 0.79 |
March | 0.00 | 0.00 | 0.84 |
April | 0.00 | 0.00 | 1.01 |
May | 0.00 | 0.00 | 1.14 |
June | 0.00 | 0.00 | 1.34 |
July | 0.00 | 0.00 | 1.46 |
August | 0.00 | 0.00 | 1.41 |
September | 0.00 | 0.00 | 1.28 |
October | 0.00 | 0.00 | 1.11 |
November | 0.00 | 0.00 | 0.88 |
December | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.00 | 1.05 |
Minimum of Months | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.00 | 1.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.19 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.13 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.67 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.66 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.67 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.64 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.20 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.13 |
April | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.65 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.64 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.65 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.13 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.13 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.29 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.24 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.00 | 0.77 |
September | 0.00 | 0.00 | 0.62 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |
Maximum of Months | 0.00 | 0.00 | 1326.38 | 987.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1326.38 | 987.53 |
February | 0.00 | 0.00 | 1301.61 | 875.30 |
March | 0.00 | 0.00 | 1206.21 | 898.05 |
April | 0.00 | 0.00 | 1061.27 | 764.66 |
May | 0.00 | 0.00 | 905.49 | 674.16 |
June | 0.00 | 0.00 | 784.36 | 565.14 |
July | 0.00 | 0.00 | 730.16 | 543.63 |
August | 0.00 | 0.00 | 755.30 | 562.34 |
September | 0.00 | 0.00 | 854.17 | 615.44 |
October | 0.00 | 0.00 | 1001.89 | 745.94 |
November | 0.00 | 0.00 | 1153.57 | 831.16 |
December | 0.00 | 0.00 | 1275.74 | 949.82 |
Annual Sum or Average | 0.00 | 0.00 | 1028.17 | 9013.16 |
Minimum of Months | 0.00 | 0.00 | 730.16 | 543.63 |