Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32

Tabular Output Report in Format: HTML

Building: MF+CZ3BWH+USA_TX_El.Paso.Intl.AP.722700+oilfurnace+slab+IECC_2009

Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2019-02-14 08:32:41


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 900986.99 28.87 41.69
Net Site Energy 900986.99 28.87 41.69
Total Source Energy 1993213.60 63.86 92.24
Net Source Energy 1993213.60 63.86 92.24


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.78
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 152490.81 0.00 0.00 0.00 0.00
Cooling 98125.39 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28240.86 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 260477.12 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 488019.06 412967.94 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 152490.81 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 98125.39 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 28240.86 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 260477.12 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 5.85 19.11 0.00 0.00 0.00 19.42
Other 13.95 0.00 0.00 0.00 0.00 0.00
Total 22.58 19.11 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.93 0.00 0.00 0.00 0.00 0.00
HVAC 4.05 13.23 0.00 0.00 0.00 13.45
Other 9.66 0.00 0.00 0.00 0.00 0.00
Total 15.64 13.23 0.00 0.00 0.00 13.45


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 488019.057 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 488019.057 100.00
     
Total On-Site and Utility Electric Sources 488019.057 100.00
Total Electricity End Uses 488019.057 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1284.50
Time Setpoint Not Met During Occupied Cooling 2.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1071.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
RunPeriod ANNUAL
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [ft] 3891.27
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 31210.78     267087.66   16177.97 0.00 2126.74 2126.74 0.5202 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 2.9092
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 14-JUN-18:15 03-FEB-07:15 - - - 01-JAN-08:15
Heating 0.00 156.32 0.00 0.00 0.00 0.00
Cooling 51.82 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 10.40 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 114.82 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 130.67 271.14 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 156.32 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 51.82 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 10.40 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 114.82 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 165300.04 0.00 0.00 0.00
Cooling 310763.12 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 89438.79 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 282357.20 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1545556.35 447657.24 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 7.65 0.00 0.00 0.00
Cooling 14.38 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.14 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.07 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 71.52 20.72 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 7.65 0.00 0.00 0.00
Cooling 14.38 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.14 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.07 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 71.52 20.72 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 22.64 0.00 22.64 Wetbulb [F] 433.09 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 100.58 23.40 64.58 Wetbulb [F] 767.75 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.258 0.882              
North Total or Average           531.68 0.501 0.258 0.882              
Non-North Total or Average           1595.05 0.501 0.258 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 431022.82 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   26387.43 21074.46 5312.97 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8150.95 6509.80 1641.15 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10805.58 8629.93 2175.65 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13964.40 11152.74 2811.66 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8047.33 6427.04 1620.29 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10320.50 8242.53 2077.98 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13776.23 11002.46 2773.77 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7932.27 6335.15 1597.12 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10415.87 8318.69 2097.18 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13543.21 10816.35 2726.85 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7896.24 6306.37 1589.87 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9973.99 7965.78 2008.21 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16733.38 13364.20 3369.18 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10826.16 8646.37 2179.79 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13087.46 10452.37 2635.09 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16729.73 13361.29 3368.44 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10854.06 8668.65 2185.41 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13041.70 10415.83 2625.88 0.80 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.1 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.26 11.12 11.77 11.27
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 48556.04 52173.26 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 16442.54 16910.91 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 21119.04 22060.27 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 26683.43 28179.66 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 16260.01 16709.63 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 20264.56 21119.92 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 26350.43 27811.07 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 16056.52 16483.63 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 20431.44 21301.58 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 25939.99 27359.80 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 15993.05 16413.64 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 19653.10 20444.93 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 31561.19 33537.57 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 21155.00 22100.00 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 25138.73 26479.48 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 31554.77 33530.50 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 21204.14 22154.06 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 25058.13 26390.86 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 989.82 373.35 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 305.75 115.33 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 405.33 152.89 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 523.82 197.58 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 301.86 113.86 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 387.13 146.02 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 516.76 194.92 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 297.55 112.23 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 390.71 147.37 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 508.02 191.62 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 296.20 111.72 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 374.13 141.12 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 627.68 236.76 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 406.10 153.18 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 490.92 185.17 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 627.55 236.71 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 407.15 153.57 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 489.21 184.53 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 43.342664 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20167.00 20167.00 16.80 989.817 989.817 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 74.98 74.98 0.00798 97.30 0.00682 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6229.45 6229.45 5.19 305.750 305.750 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00803 95.55 0.00682 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8258.49 8258.49 6.88 405.327 405.327 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00790 100.58 0.00682 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10672.49 10672.49 8.89 523.817 523.817 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00798 96.72 0.00682 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6150.24 6150.24 5.12 301.863 301.863 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00806 94.09 0.00682 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7887.76 7887.76 6.57 387.132 387.132 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00790 100.58 0.00682 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10528.62 10528.62 8.77 516.759 516.759 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00802 96.72 0.00682 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6062.27 6062.27 5.05 297.547 297.547 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00814 94.09 0.00682 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7960.50 7960.50 6.63 390.709 390.709 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 74.98 74.98 0.00796 100.23 0.00682 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10350.51 10350.51 8.62 508.018 508.018 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00805 96.13 0.00682 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6034.72 6034.72 5.03 296.195 296.195 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00818 92.33 0.00682 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7622.79 7622.79 6.35 374.134 374.134 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 74.98 74.98 0.00796 100.23 0.00682 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9967.41 9967.41 8.30 489.206 489.206 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00792 99.53 0.00682 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10002.38 10002.38 8.33 490.923 490.923 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00793 99.53 0.00682 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12788.72 12788.72 10.65 627.685 627.685 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00798 96.72 0.00682 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8295.30 8295.30 6.91 407.146 407.146 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00805 94.09 0.00682 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8273.99 8273.99 6.89 406.099 406.099 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00804 94.96 0.00682 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12785.94 12785.94 10.65 627.548 627.548 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00798 96.72 0.00682 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7359.95 7359.95 6.13 154.446 154.446 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00619 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9796.71 9796.71 8.16 205.576 205.576 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00642 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9804.14 9804.14 8.17 205.732 205.732 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00642 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7383.09 7383.09 6.15 154.932 154.932 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00620 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9794.36 9794.36 8.16 205.527 205.527 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00642 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8473.38 8473.38 7.06 177.819 177.819 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00669 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6085.75 6085.75 5.07 127.716 127.716 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00648 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8538.59 8538.59 7.11 179.188 179.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00670 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8540.66 8540.66 7.11 179.231 179.231 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00670 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6092.05 6092.05 5.07 127.848 127.848 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00649 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8535.89 8535.89 7.11 179.131 179.131 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00670 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11535.39 11535.39 9.61 242.060 242.060 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00659 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11536.86 11536.86 9.61 242.091 242.091 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00659 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11522.87 11522.87 9.60 241.798 241.798 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00658 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9102.91 9102.91 7.58 191.021 191.021 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00642 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9100.77 9100.77 7.58 190.976 190.976 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00642 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11536.06 11536.06 9.61 242.074 242.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00659 22.64 0.00281 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 989.82 989.82 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 305.75 305.75 154.45 154.45
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 405.33 405.33 205.58 205.58
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 523.82 523.82 205.73 205.73
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 301.86 301.86 154.93 154.93
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 387.13 387.13 205.53 205.53
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 516.76 516.76 177.82 177.82
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 297.55 297.55 127.72 127.72
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 390.71 390.71 179.19 179.19
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 508.02 508.02 179.23 179.23
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 296.20 296.20 127.85 127.85
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 374.13 374.13 179.13 179.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 627.68 627.68 241.80 241.80
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 406.10 406.10 190.98 190.98
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 490.92 490.92 242.09 242.09
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 627.55 627.55 242.07 242.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.15 407.15 191.02 191.02
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 489.21 489.21 242.06 242.06


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1826.50 4551.25 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2548.75 5070.25 525.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2821.00 4794.00 449.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2964.75 5415.50 754.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2307.75 5591.25 457.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2685.00 5299.75 476.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2962.75 4581.50 381.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2589.50 4670.00 313.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2983.00 4517.00 340.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3012.00 5153.75 601.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2460.00 5228.00 333.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2839.75 5023.00 369.50
LIVING_UNIT3_BACKROW_TOPFLOOR 3154.75 5081.00 581.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 3212.25 4746.75 537.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 3213.00 4857.25 651.25
LIVING_UNIT2_BACKROW_TOPFLOOR 2709.50 5297.25 449.25
LIVING_UNIT2_FRONTROW_TOPFLOOR 2779.75 4940.50 423.75
LIVING_UNIT1_BACKROW_TOPFLOOR 3233.75 5198.00 765.75
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3872.50 5901.50 1071.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.50 0.00 91.50 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.00 0.00 172.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 443.25 2.25 443.25 2.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 71.00 0.00 71.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 72.25 0.00 72.25 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 48.75 0.00 48.75 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.75 0.00 1.75 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 219.50 0.00 219.50 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 431.50 0.00 431.50 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 42.00 0.00 42.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 113.25 0.00 113.25 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 40.00 0.00 40.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 100.25 0.00 100.25 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 129.50 0.00 129.50 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23.00 0.00 23.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.50 0.00 0.50 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 325.25 0.00 325.25 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1284.50 2.25 1284.50 2.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.252 0.000 0.270
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.218 0.000 0.270
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.248 0.000 0.270
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.246 0.000 0.270
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.217 0.000 0.270
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.247 0.000 0.270
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.109 0.000 0.270
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.079 0.000 0.270
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.109 0.000 0.270
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.108 0.000 0.270
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.079 0.000 0.270
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.108 0.000 0.270
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.247 0.000 0.270
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.248 0.000 0.270
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.247 0.000 0.270
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.217 0.000 0.270
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.218 0.000 0.270
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.247 0.000 0.270
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1855
Defaulted Fields 436
Fields with Defaults 4694
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 90
Autocalculatable Fields 269



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Fans:Electricity 8271.06 111.47 20-FEB-23:00 3093.25 05-JUN-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
ElectricityPurchased:Plant 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
Cogeneration:ElectricityPurchased 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
ElectricityNet:Plant 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
Cogeneration:ElectricityNet 142928.94 7464.15 08-MAY-03:15 38271.33 14-JUN-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 37009.61 508.62 20-FEB-23:00 18645.96 05-JUN-17:00
General:Fans:Electricity 8271.06 111.47 20-FEB-23:00 3093.25 05-JUN-17:15
Cooling:Electricity 28738.55 0.00 05-JAN-04:15 15556.58 05-JUN-17:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 4129.68 0.00 02-JAN-18:15 270945.32 03-FEB-07:15
Gas:Plant 4129.68 0.00 02-JAN-18:15 270945.32 03-FEB-07:15
WaterSystems:Gas 2604.77 0.00 01-JAN-00:15 115020.47 28-JAN-08:30
Water Heater:WaterSystems:Gas 2604.77 0.00 01-JAN-00:15 115020.47 28-JAN-08:30
Heating:Gas 1524.91 0.00 02-JAN-17:15 160321.45 03-FEB-07:00
Boiler:Heating:Gas 1524.91 0.00 02-JAN-17:15 160321.45 03-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 24-JAN-03:00 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 251374.50 969.90 31-JUL-03:00 159246.14 03-FEB-07:15
PlantLoopHeatingDemand:Plant 130221.78 969.90 31-JUL-03:00 36906.65 29-JAN-08:45
WaterSystems:PlantLoopHeatingDemand 130221.78 969.90 31-JUL-03:00 36906.65 29-JAN-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1260196.33 15453.83 22-APR-02:45 413642.98 03-FEB-07:00
EnergyTransfer:Building 478605.92 6598.67 22-MAR-21:45 179990.93 05-JUN-17:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 127317.29 0.00 03-JAN-15:00 130056.74 03-FEB-07:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 351288.63 0.00 05-JAN-04:15 179990.93 05-JUN-17:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 83462.94 0.00 05-JAN-04:15 21522.68 15-JUN-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 83462.94 0.00 05-JAN-04:15 21522.68 15-JUN-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17393.41 0.00 01-JAN-10:45 11158.42 02-MAR-09:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4571.15 0.00 01-JAN-10:45 11158.42 02-MAR-09:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12822.26 0.00 01-JAN-00:15 6751.10 14-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 24375.23 0.00 01-JAN-10:15 8907.95 03-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7345.36 0.00 01-JAN-10:15 8907.95 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 17029.87 0.00 01-JAN-00:15 8484.81 15-JUN-10:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 24473.83 0.00 01-JAN-14:45 11647.20 15-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9507.56 0.00 01-JAN-14:45 8778.85 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14966.27 0.00 01-JAN-00:15 11647.20 15-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 17658.04 0.00 02-JAN-17:15 6750.07 05-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7182.42 0.00 02-JAN-17:15 6452.89 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10475.63 0.00 01-JAN-00:15 6750.07 05-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 24007.62 0.00 03-JAN-13:30 8787.63 03-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9382.28 0.00 03-JAN-13:30 8787.63 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14625.34 0.00 01-JAN-00:15 8608.77 15-JUN-10:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23781.45 0.00 01-JAN-11:00 11433.78 15-JUN-17:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5405.37 0.00 01-JAN-11:00 7007.25 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18376.08 0.00 01-JAN-00:15 11433.78 15-JUN-17:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16853.89 0.00 01-JAN-00:15 6439.85 14-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3280.79 0.00 01-JAN-00:15 5337.43 02-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13573.10 0.00 01-JAN-00:15 6439.85 14-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23123.74 0.00 01-JAN-10:30 8102.75 19-SEP-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5373.77 0.00 01-JAN-10:30 7379.60 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17749.97 0.00 01-JAN-00:15 8102.75 19-SEP-14:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22842.45 0.00 01-JAN-14:45 11312.20 15-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7336.87 0.00 01-JAN-14:45 7428.13 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15505.58 0.00 01-JAN-00:15 11312.20 15-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16113.06 0.00 01-JAN-18:15 6557.17 14-JUN-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5026.60 0.00 01-JAN-18:15 5102.73 27-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11086.46 0.00 01-JAN-00:15 6557.17 14-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22426.56 0.00 02-JAN-15:15 8106.50 15-JUN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7165.43 0.00 02-JAN-15:15 7447.91 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15261.14 0.00 01-JAN-00:15 8106.50 15-JUN-10:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 29008.49 0.00 02-JAN-14:30 10612.05 05-JUN-17:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 10810.90 0.00 02-JAN-14:30 10365.57 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18197.59 0.00 01-JAN-00:15 10612.05 05-JUN-17:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28618.57 0.00 01-JAN-11:15 10619.84 05-JUN-17:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 9027.07 0.00 01-JAN-11:15 10310.50 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19591.50 0.00 01-JAN-00:15 10619.84 05-JUN-17:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 29760.10 0.00 01-JAN-11:45 13873.76 15-JUN-17:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 9539.90 0.00 01-JAN-11:45 10222.84 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 20220.20 0.00 01-JAN-00:15 13873.76 15-JUN-17:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22647.85 0.00 01-JAN-17:15 9019.06 05-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 8499.81 0.00 01-JAN-17:15 8008.23 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14148.04 0.00 01-JAN-00:15 9019.06 05-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 22194.72 0.00 01-JAN-11:30 8945.43 14-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 6639.69 0.00 01-JAN-11:30 7896.88 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15555.03 0.00 01-JAN-00:15 8945.43 14-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 29863.96 0.00 01-JAN-14:00 13875.48 15-JUN-17:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 11222.33 0.00 01-JAN-14:00 10350.31 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18641.62 0.00 01-JAN-00:15 13875.48 15-JUN-17:45
EnergyTransfer:Plant 252214.44 969.90 31-JUL-03:00 160147.57 03-FEB-07:15
WaterSystems:EnergyTransfer 130221.78 969.90 31-JUL-03:00 36906.65 29-JAN-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 130221.78 969.90 31-JUL-03:00 36906.65 29-JAN-08:45
EnergyTransfer:HVAC 529375.97 6810.66 22-MAR-21:45 197732.61 26-JUL-17:30
HeatingCoils:EnergyTransfer 121152.71 0.00 02-JAN-17:15 125869.43 03-FEB-07:00
PlantLoopHeatingDemand:HVAC 121152.71 0.00 02-JAN-17:15 125869.43 03-FEB-07:00
HeatingCoils:PlantLoopHeatingDemand 121152.71 0.00 02-JAN-17:15 125869.43 03-FEB-07:00
CoolingCoils:EnergyTransfer 408223.26 0.00 05-JAN-04:15 197732.61 26-JUL-17:30
Boilers:EnergyTransfer 121992.65 0.00 02-JAN-17:15 128257.16 03-FEB-07:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -6950.59 0.000 0.000 2874.311 2771.241 10464.601 10719.427 0.000 1859.445 70855.465 0.000 -5749.28 0.000 -10332.35 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 4571.109 -1067.80 0.000 0.000 2993.934 2771.241 10464.601 4656.403 0.000 1750.492 0.013 0.000 -2199.95 0.000 -8791.19 -3394.46
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 7345.297 -1418.20 0.000 0.000 3001.908 2771.241 10464.601 10798.513 0.000 1859.351 0.000 0.000 -5206.12 0.000 -9354.06 -4650.96
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 9507.483 -1246.35 0.000 0.000 3017.843 2771.241 10464.601 7903.606 0.000 1859.974 0.000 0.000 -5644.22 0.000 -9065.12 -5849.27
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 7182.359 -872.38 0.000 0.000 3009.720 2771.241 10464.601 1457.075 0.000 1750.930 0.000 0.000 -2373.76 0.000 -8609.65 -5176.92
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 9382.213 -1217.96 0.000 0.000 3016.035 2771.241 10464.601 7662.235 0.000 1859.349 0.000 0.000 -5269.36 0.000 -9170.15 -6090.90
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 5405.320 -1530.31 0.000 0.000 2983.012 2771.241 10464.601 10799.175 0.000 1342.453 0.084 0.000 -5596.80 0.000 -6813.07 -2980.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 3280.752 -1130.33 0.000 0.000 2968.265 2771.241 10464.601 4637.424 0.000 1233.959 0.144 0.000 -2257.98 0.000 -6310.36 -3214.85
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 5373.715 -1478.17 0.000 0.000 2988.748 2771.241 10464.601 10749.612 0.000 1342.389 0.087 0.000 -5328.73 0.000 -6814.70 -3796.98
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 7336.805 -1291.26 0.000 0.000 3005.745 2771.241 10464.601 7879.306 0.000 1343.286 0.000 0.000 -5768.21 0.000 -6607.79 -4919.49
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 5026.554 -923.25 0.000 0.000 2995.317 2771.241 10464.601 1457.493 0.000 1234.415 0.000 0.000 -2426.07 0.000 -6129.36 -4307.73
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 7165.369 -1270.91 0.000 0.000 3005.987 2771.241 10464.601 7628.922 0.000 1342.398 0.000 0.000 -5380.35 0.000 -6670.99 -5066.08
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 10810.817 -1515.45 0.000 0.000 3011.702 2771.241 10464.601 7577.869 0.000 1846.506 0.000 0.000 -5385.47 0.000 -9229.66 -3670.10
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 9026.992 -1631.53 0.000 0.000 3001.354 2771.241 10464.601 10739.056 0.000 1846.460 0.000 0.000 -5285.00 0.000 -9356.20 -3617.11
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 9539.815 -1683.88 0.000 0.000 3000.322 2771.241 10464.601 10798.472 0.000 1847.229 0.000 0.000 -5506.62 0.000 -9323.63 -3371.41
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 8499.746 -1178.21 0.000 0.000 3004.571 2771.241 10464.601 1430.028 0.000 1739.218 0.046 0.000 -2417.14 0.000 -8684.51 -2659.79
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 6639.631 -1295.38 0.000 0.000 2989.059 2771.241 10464.601 4629.441 0.000 1738.790 0.004 0.000 -2226.61 0.000 -8840.42 -2610.80
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 11222.249 -1552.42 0.000 0.000 3012.138 2771.241 10464.601 7785.533 0.000 1847.863 0.000 0.000 -5740.07 0.000 -9171.94 -3550.15
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5474.774 54176.307 0.000 0.000 0.000 -59651.08 -0.09
Total Facility 0.000 0.000 127316.227 -29254.36 0.000 0.000 53879.972 49882.340 188362.826 129309.591 0.000 35119.281 125032.150 0.000 -79761.76 0.000 -208926.22 -68927.08


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 15-JUN-17:08 0.00 0.00 0.00 -1.8 0.00 0.00 263.31 604.65 1664.02 6764.40 0.00 2377.09 9906.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14-JUN-18:33 0.00 0.00 0.00 -0.6 0.00 0.00 426.79 813.96 1724.99 497.15 0.00 1920.67 1383.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15-JUN-09:48 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1096.02 4734.89 0.00 1857.06 566.30 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15-JUN-18:24 0.00 0.00 0.00 -1.0 0.00 0.00 423.16 813.96 1724.99 4602.57 0.00 1751.58 2343.26 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 05-JUN-19:03 0.00 0.00 0.00 -0.6 0.00 0.00 425.27 902.05 1664.78 416.24 0.00 1846.47 1507.85 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15-JUN-09:48 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1096.02 4672.73 0.00 1857.12 752.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 15-JUN-17:45 0.00 0.00 0.00 -1.0 0.00 0.00 261.70 604.65 1664.02 5883.42 0.00 1422.71 1602.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14-JUN-18:02 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 813.96 1724.99 629.46 0.00 1348.43 1497.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 19-SEP-14:00 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1084.63 3569.43 0.00 998.98 2217.85 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15-JUN-18:24 0.00 0.00 0.00 -0.9 0.00 0.00 424.46 813.96 1724.99 4607.21 0.00 1239.48 2515.68 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14-JUN-18:33 0.00 0.00 0.00 -0.5 0.00 0.00 426.70 813.96 1724.99 689.19 0.00 1268.68 1638.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15-JUN-09:48 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1096.02 4674.91 0.00 1265.66 839.20 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 05-JUN-16:47 0.00 0.00 0.00 -0.9 0.00 0.00 140.43 434.11 1350.56 2220.88 0.00 2726.33 3740.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 05-JUN-16:47 0.00 0.00 0.00 -0.9 0.00 0.00 140.43 434.11 1350.56 2112.31 0.00 2726.33 3857.18 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 15-JUN-17:45 0.00 0.00 0.00 -1.2 0.00 0.00 261.85 604.65 1664.02 5824.59 0.00 2099.18 3429.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 05-JUN-18:48 0.00 0.00 0.00 -0.8 0.00 0.00 427.01 813.96 1724.99 622.59 0.00 2018.11 3412.35 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 14-JUN-18:06 0.00 0.00 0.00 -0.7 0.00 0.00 427.01 813.96 1724.99 609.80 0.00 2066.15 3303.70 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 15-JUN-17:45 0.00 0.00 0.00 -1.2 0.00 0.00 261.74 604.65 1664.02 6131.21 0.00 2095.52 3126.26 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-JUN-17:15 0.00 0.00 0.00 -15.0 0.00 0.00 4726.78 10883.76 29952.39 55723.84 0.00 38534.81 55953.69 0.00 0.00 0.00 -15290.0 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-MAR-08:51 0.00 0.00 16157.33 0.00 0.00 0.00 270.77 170.54 1155.86 294.43 0.00 0.00 0.00 0.00 0.00 0.00 -2475.7 -15573.2
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 26-DEC-06:28 0.00 0.00 16471.07 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2462.0 0.00 -4173.8 -11873.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 21-NOV-10:33 0.00 0.00 21508.71 0.00 0.00 0.00 140.45 116.28 1089.80 100.32 0.00 0.00 0.00 0.00 0.00 0.00 -969.7 -21985.9
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 02-FEB-17:21 0.00 0.00 14775.92 0.00 0.00 0.00 305.65 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -579.8 0.00 -1595.1 -15175.4
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 03-FEB-07:00 0.00 0.00 8787.66 0.00 0.00 0.00 526.30 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2934.0 0.00 -4866.1 -3025.9
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23-APR-08:29 0.00 0.00 10693.99 0.00 0.00 0.00 220.29 170.54 1179.68 208.03 0.00 0.00 0.00 0.00 0.00 0.00 -791.0 -11681.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 02-FEB-07:15 0.00 0.00 5337.48 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1157.6 0.00 -2961.5 -3281.5
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-DEC-22:23 0.00 0.00 12280.65 0.00 0.00 0.00 558.29 379.85 1340.18 0.00 0.00 0.00 0.00 0.00 -2213.9 0.00 -2227.0 -10118.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 07-DEC-10:00 0.00 0.00 20743.52 0.00 0.00 0.00 127.31 116.28 1096.02 0.00 0.00 0.00 0.00 0.00 -800.3 0.00 -1604.1 -19678.8
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 02-FEB-17:36 0.00 0.00 10614.67 0.00 0.00 0.00 301.21 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -630.4 0.00 -1269.1 -11285.0
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 03-FEB-07:00 0.00 0.00 7447.97 0.00 0.00 0.00 526.30 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2959.4 0.00 -3440.5 -3086.5
LIVING_UNIT3_BACKROW_TOPFLOOR 03-FEB-07:00 0.00 0.00 10365.60 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2934.4 0.00 -4874.0 -4595.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 03-FEB-07:00 0.00 0.00 10310.53 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2942.7 0.00 -4874.0 -4532.3
LIVING_UNIT1_FRONTROW_TOPFLOOR 23-MAR-11:06 0.00 0.00 21089.24 0.00 0.00 0.00 140.75 116.28 1092.38 1278.64 0.00 0.00 0.00 0.00 0.00 0.00 -2113.3 -21604.0
LIVING_UNIT2_BACKROW_TOPFLOOR 27-JAN-17:51 0.00 0.00 9162.04 0.00 0.00 0.00 299.38 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -714.8 0.00 -1964.7 -9050.5
LIVING_UNIT2_FRONTROW_TOPFLOOR 03-FEB-07:00 0.00 0.00 7896.91 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -1203.1 0.00 -4569.9 -4162.3
LIVING_UNIT1_BACKROW_TOPFLOOR 03-NOV-10:24 0.00 0.00 14946.19 0.00 0.00 0.00 134.41 116.28 1089.80 488.54 0.00 0.00 0.00 0.00 0.00 0.00 -742.6 -16032.6
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-FEB-07:00 0.00 0.00 130057.38 0.00 0.00 0.00 9564.05 7813.98 19403.66 0.00 0.00 1830.06 0.00 0.00 -42661.5 0.00 -76498.4 -49509.2



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 989.817 2.00 2.00 1.00 44.9950 989.817 0.045 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 305.750 2.00 2.00 1.00 44.9950 305.750 0.147 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 405.327 2.00 2.00 1.00 44.9950 405.327 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 523.817 2.00 2.00 1.00 44.9950 523.817 0.086 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 301.863 2.00 2.00 1.00 44.9950 301.863 0.149 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 387.132 2.00 2.00 1.00 44.9950 387.132 0.116 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 516.759 2.00 2.00 1.00 44.9950 516.759 0.087 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 297.547 2.00 2.00 1.00 44.9950 297.547 0.151 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 390.709 2.00 2.00 1.00 44.9950 390.709 0.115 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 508.018 2.00 2.00 1.00 44.9950 508.018 0.089 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 296.195 2.00 2.00 1.00 44.9950 296.195 0.152 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 374.134 2.00 2.00 1.00 44.9950 374.134 0.120 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 627.685 2.00 2.00 1.00 44.9950 627.685 0.072 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 406.099 2.00 2.00 1.00 44.9950 406.099 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 490.923 2.00 2.00 1.00 44.9950 490.923 0.092 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 627.548 2.00 2.00 1.00 44.9950 627.548 0.072 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.146 2.00 2.00 1.00 44.9950 407.146 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 489.206 2.00 2.00 1.00 44.9950 489.206 0.092 1.000 44.9950 0.09


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 154.446 2.00 2.00 1.00 44.9950 154.446 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 205.576 2.00 2.00 1.00 44.9950 205.576 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 205.732 2.00 2.00 1.00 44.9950 205.732 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 154.932 2.00 2.00 1.00 44.9950 154.932 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 205.527 2.00 2.00 1.00 44.9950 205.527 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 177.819 2.00 2.00 1.00 44.9950 177.819 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 127.716 2.00 2.00 1.00 44.9950 127.716 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 179.188 2.00 2.00 1.00 44.9950 179.188 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 179.231 2.00 2.00 1.00 44.9950 179.231 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 127.848 2.00 2.00 1.00 44.9950 127.848 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 179.131 2.00 2.00 1.00 44.9950 179.131 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 241.798 2.00 2.00 1.00 44.9950 241.798 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.976 2.00 2.00 1.00 44.9950 190.976 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 242.091 2.00 2.00 1.00 44.9950 242.091 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 242.074 2.00 2.00 1.00 44.9950 242.074 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 191.021 2.00 2.00 1.00 44.9950 191.021 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 242.060 2.00 2.00 1.00 44.9950 242.060 1.000 1.000 44.9950 0.19


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   989.817 989.8167 197.9633 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   305.750 305.7497 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   405.327 405.3271 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   523.817 523.8174 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   301.863 301.8628 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   387.132 387.1317 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   516.759 516.7590 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   297.547 297.5469 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   390.709 390.7089 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   508.018 508.0182 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   296.195 296.1953 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   374.134 374.1336 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   489.206 489.2063 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   490.923 490.9228 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   627.685 627.6845 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   407.146 407.1457 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   406.099 406.0994 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   627.548 627.5478 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 989.82 989.817 989.82 197.9633 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 305.75 305.750 305.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 405.33 405.327 405.33 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 523.82 523.817 523.82 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 301.86 301.863 301.86 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 387.13 387.132 387.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 516.76 516.759 516.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 297.55 297.547 297.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 390.71 390.709 390.71 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 508.02 508.018 508.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 296.20 296.195 296.20 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 374.13 374.134 374.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 627.68 627.685 627.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 406.10 406.099 406.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 490.92 490.923 490.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 627.55 627.548 627.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.15 407.146 407.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 489.21 489.206 489.21 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   154.446 154.446 154.446 44.9950 0.291 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   205.576 205.576 205.576 44.9950 0.219 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   205.732 205.732 205.732 44.9950 0.219 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   154.932 154.932 154.932 44.9950 0.290 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   205.527 205.527 205.527 44.9950 0.219 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   177.819 177.819 177.819 44.9950 0.253 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   127.716 127.716 127.716 44.9950 0.352 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   179.188 179.188 179.188 44.9950 0.251 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   179.231 179.231 179.231 44.9950 0.251 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   127.848 127.848 127.848 44.9950 0.352 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   179.131 179.131 179.131 44.9950 0.251 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   242.060 242.060 242.060 44.9950 0.186 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   242.091 242.091 242.091 44.9950 0.186 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   241.798 241.798 241.798 44.9950 0.186 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   191.021 191.021 191.021 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   190.976 190.976 190.976 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   242.074 242.074 242.074 44.9950 0.186 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 154.45 154.446 154.45 154.45 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 205.58 205.576 205.58 205.58 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 205.73 205.732 205.73 205.73 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 154.93 154.932 154.93 154.93 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 205.53 205.527 205.53 205.53 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 177.82 177.819 177.82 177.82 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 127.72 127.716 127.72 127.72 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 179.19 179.188 179.19 179.19 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 179.23 179.231 179.23 179.23 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 127.85 127.848 127.85 127.85 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 179.13 179.131 179.13 179.13 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 241.80 241.798 241.80 241.80 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.98 190.976 190.98 190.98 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 242.09 242.091 242.09 242.09 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 242.07 242.074 242.07 242.07 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 191.02 191.021 191.02 191.02 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 242.06 242.060 242.06 242.06 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Sec1.1A-General Information

Data
Weather File ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [ft2] 31210.78
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 31210.78 21609.96 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1284.50
Number of hours cooling loads not met 2.25
Number of hours not met 1286.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 1524.91 156211.20 0.00 0.00
Space Cooling 28738.55 15175.90 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8271.06 3046.51 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2604.77 114734.12 0.00 0.00
Receptacle Equipment 88303.07 15031.50 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 142928.94   4129.68   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 488019.06
Natural Gas 0.00 412967.94
Additional 0.00 0.00
Total 301503.54 900986.99


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.47
Space Heating 0.00
Space Cooling 0.92
Fans-Interior 0.27
Service Water Heating 0.00
Receptacle Equipment 2.83
Miscellaneous 0.10
Subtotal 4.58


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 1.43
Service Water Heating 2.44
Miscellaneous -0.0
Subtotal 3.88


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.54
Space Heating 16.92
Space Cooling 10.89
Fans-Interior 3.13
Service Water Heating 28.91
Receptacle Equipment 33.46
Miscellaneous 1.14



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 989.82
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 305.75
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 405.33
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 523.82
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 301.86
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 387.13
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 516.76
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 297.55
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 390.71
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 508.02
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 296.20
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 374.13
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 489.21
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 490.92
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 627.68
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 407.15
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 406.10
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 627.55
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 989.82
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 305.75
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 405.33
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 523.82
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 301.86
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 387.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 516.76
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 297.55
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 390.71
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 508.02
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 296.20
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 374.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 627.68
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 406.10
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 490.92
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 627.55
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 489.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 989.82 2.20 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 305.75 0.679246 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 405.33 0.900464 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 523.82 1.16 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 301.86 0.670611 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 387.13 0.860042 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 516.76 1.15 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 297.55 0.661023 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 390.71 0.867989 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 508.02 1.13 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 296.20 0.658020 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 374.13 0.831166 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 627.68 1.39 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 406.10 0.902180 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 490.92 1.09 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 627.55 1.39 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 407.15 0.904505 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 489.21 1.09 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 989.82 989.82 989.82 2.20 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 305.75 305.75 305.75 0.679246 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 405.33 405.33 405.33 0.900464 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 523.82 523.82 523.82 1.16 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 301.86 301.86 301.86 0.670611 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 387.13 387.13 387.13 0.860042 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 516.76 516.76 516.76 1.15 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 297.55 297.55 297.55 0.661023 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 390.71 390.71 390.71 0.867989 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 508.02 508.02 508.02 1.13 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 296.20 296.20 296.20 0.658020 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 374.13 374.13 374.13 0.831166 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 627.68 627.68 627.68 1.39 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 406.10 406.10 406.10 0.902180 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 490.92 490.92 490.92 1.09 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 627.55 627.55 627.55 1.39 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 407.15 407.15 407.15 0.904505 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 489.21 489.21 489.21 1.09 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 48556.04 4.90 691.84
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 16442.54 1.66 227.36
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 21119.04 2.13 295.20
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 26683.43 2.69 375.84
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 16260.01 1.64 224.71
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 20264.56 2.05 282.81
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 26350.43 2.66 370.96
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 16056.52 1.62 221.72
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 20431.44 2.06 285.18
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 25939.99 2.62 365.01
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 15993.05 1.61 220.80
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 19653.10 1.98 273.89
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 31561.19 3.19 446.45
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 21155.00 2.14 295.72
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 25138.73 2.54 353.42
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 31554.77 3.18 446.36
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 21204.14 2.14 296.43
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 25058.13 2.53 352.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 989.82
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 305.75
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 405.33
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 523.82
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 301.86
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 387.13
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 516.76
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 297.55
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 390.71
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 508.02
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 296.20
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 374.13
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 627.68
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 406.10
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 490.92
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 627.55
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 407.15
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 489.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.79 108.64
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.79
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 431022.82 43.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:41

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 729.961 68.415 0.000 0.000 68.415
February 644.719 70.975 0.000 0.000 70.975
March 737.150 88.948 0.000 0.000 88.948
April 720.000 119.005 0.000 0.000 119.005
May 744.000 147.831 0.000 0.000 147.831
June 720.000 166.258 0.000 0.000 166.258
July 744.000 178.256 0.000 0.000 178.256
August 744.000 168.266 0.000 0.000 168.266
September 720.000 151.851 0.000 0.000 151.851
October 744.000 127.362 0.000 0.000 127.362
November 718.000 84.375 0.000 0.000 84.375
December 710.837 62.566 0.000 0.000 62.566
           
Annual Sum or Average 8676.668 1434.109 0.000 0.000 1434.109
Minimum of Months 644.719 62.566 0.000 0.000 62.566
Maximum of Months 744.000 178.256 0.000 0.000 178.256



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 100.690 1.868 441.903 5.158 8.645
February 131.025 3.813 328.125 3.444 10.403
March 189.513 4.544 338.050 2.947 8.281
April 386.555 14.832 105.667 0.657 15.489
May 606.992 26.740 8.250 0.023 26.762
June 710.042 41.459 0.000 0.000 41.459
July 743.750 47.393 0.000 0.000 47.393
August 732.067 41.338 0.000 0.000 41.338
September 633.208 33.507 6.750 0.015 33.523
October 414.911 18.715 92.589 0.304 19.019
November 207.853 6.754 335.033 3.226 10.211
December 90.773 1.351 441.347 5.863 11.039
           
Annual Sum or Average 4947.378 242.314 2097.715 21.638 273.562
Minimum of Months 90.773 1.351 0.000 0.000 8.281
Maximum of Months 743.750 47.393 441.903 5.863 47.393



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 77.624 1.504 444.127 15.405 24.948
February 128.248 4.412 330.690 10.928 22.191
March 203.359 6.435 298.112 8.390 22.949
April 421.710 21.273 76.625 1.700 28.329
May 612.594 37.939 5.000 0.065 39.249
June 695.917 56.535 0.000 0.000 56.535
July 740.250 62.371 0.000 0.000 62.371
August 718.213 53.933 0.000 0.000 53.933
September 608.887 43.036 5.333 0.078 44.446
October 405.108 22.454 82.714 1.319 32.532
November 194.083 7.349 317.062 9.552 25.329
December 66.035 1.031 462.885 17.928 26.442
           
Annual Sum or Average 4872.026 318.272 2022.549 65.365 439.253
Minimum of Months 66.035 1.031 0.000 0.000 22.191
Maximum of Months 740.250 62.371 462.885 17.928 62.371



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 2.196 0.018 529.105 19.508 44.680
February 51.233 1.239 409.652 13.811 35.246
March 132.171 3.966 377.353 10.174 27.707
April 355.737 19.041 124.915 2.247 29.562
May 565.421 37.578 15.965 0.127 38.982
June 694.003 56.912 0.000 0.000 56.912
July 739.589 62.405 0.000 0.000 62.405
August 715.179 51.844 0.000 0.000 51.844
September 574.629 37.174 17.619 0.153 38.064
October 319.353 15.513 171.454 1.963 24.666
November 74.937 1.601 426.782 12.133 27.751
December 0.000 0.000 548.731 22.648 50.449
           
Annual Sum or Average 4224.449 287.292 2621.576 82.764 488.269
Minimum of Months 0.000 0.000 0.000 0.000 24.666
Maximum of Months 739.589 62.405 548.731 22.648 62.405



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 660.905 9.781 15.311
February 27.321 0.210 499.405 6.816 9.185
March 71.475 0.798 420.865 4.774 8.833
April 360.775 11.609 125.039 0.967 12.990
May 605.071 25.928 8.792 0.032 25.964
June 710.500 41.708 0.000 0.000 41.708
July 744.000 47.166 0.000 0.000 47.166
August 731.292 39.053 0.000 0.000 39.053
September 623.788 26.871 7.675 0.026 26.899
October 320.579 8.954 141.879 0.599 9.692
November 19.479 0.273 475.938 5.698 8.836
December 0.000 0.000 693.946 11.349 15.669
           
Annual Sum or Average 4214.279 202.568 3034.443 40.042 261.306
Minimum of Months 0.000 0.000 0.000 0.000 8.833
Maximum of Months 744.000 47.166 693.946 11.349 47.166



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 710.188 20.551 22.029
February 36.375 0.445 486.610 13.575 17.984
March 117.085 1.925 376.062 9.494 16.947
April 406.137 17.970 86.333 1.798 24.538
May 613.523 36.988 5.375 0.069 38.194
June 696.917 56.353 0.000 0.000 56.353
July 740.250 61.704 0.000 0.000 61.704
August 718.127 51.469 0.000 0.000 51.469
September 605.206 36.653 6.000 0.088 38.036
October 354.823 12.674 111.583 1.570 22.283
November 35.143 0.560 465.318 11.970 18.569
December 0.000 0.000 733.126 23.681 24.565
           
Annual Sum or Average 4323.584 276.741 2980.596 82.795 392.672
Minimum of Months 0.000 0.000 0.000 0.000 16.947
Maximum of Months 740.250 61.704 733.126 23.681 61.704



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 129.342 4.085 453.142 11.709 15.794
February 156.165 6.448 340.500 8.378 16.101
March 227.778 9.743 292.902 6.164 22.585
April 415.547 24.298 81.089 1.190 30.118
May 610.238 40.398 5.883 0.044 40.994
June 709.554 57.197 0.000 0.000 57.197
July 742.700 62.775 0.000 0.000 62.775
August 724.179 54.809 0.000 0.000 54.809
September 609.235 44.644 8.178 0.064 45.101
October 421.869 26.444 100.250 0.875 28.977
November 216.062 10.332 338.517 7.369 18.212
December 114.720 3.088 469.350 13.876 16.964
           
Annual Sum or Average 5077.389 344.261 2089.811 49.671 409.626
Minimum of Months 114.720 3.088 0.000 0.000 15.794
Maximum of Months 742.700 62.775 469.350 13.876 62.775



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 138.657 2.558 402.521 4.373 7.080
February 160.520 4.505 295.821 3.117 7.632
March 223.542 5.604 274.653 2.331 8.118
April 443.774 16.529 67.327 0.425 16.969
May 660.518 28.872 4.375 0.006 28.879
June 720.000 41.900 0.000 0.000 41.900
July 744.000 47.435 0.000 0.000 47.435
August 741.563 42.023 0.000 0.000 42.023
September 667.919 34.675 3.167 0.004 34.679
October 459.425 20.360 51.524 0.185 20.550
November 249.983 7.790 289.863 2.642 10.716
December 127.311 1.956 418.671 5.330 7.435
           
Annual Sum or Average 5337.209 254.208 1807.921 18.414 273.417
Minimum of Months 127.311 1.956 0.000 0.000 7.080
Maximum of Months 744.000 47.435 418.671 5.330 47.435



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 98.983 1.928 392.424 11.408 22.630
February 151.530 5.022 270.592 7.653 21.474
March 238.884 7.522 230.708 5.574 22.509
April 468.133 23.141 43.192 0.888 28.552
May 650.887 40.096 1.500 0.018 40.655
June 709.375 56.943 0.000 0.000 56.943
July 743.750 62.360 0.000 0.000 62.360
August 726.304 54.533 0.000 0.000 54.533
September 630.531 43.996 2.458 0.031 44.801
October 440.804 23.824 46.375 0.674 31.777
November 220.847 8.138 273.889 7.032 23.761
December 86.191 1.346 409.379 13.561 24.442
           
Annual Sum or Average 5166.218 328.849 1670.517 46.839 434.437
Minimum of Months 86.191 1.346 0.000 0.000 21.474
Maximum of Months 743.750 62.360 409.379 13.561 62.360



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 3.717 0.025 492.334 15.336 40.654
February 65.312 1.465 366.239 10.421 32.225
March 159.883 4.693 325.265 7.288 25.874
April 393.165 20.606 87.715 1.299 28.990
May 607.336 39.424 5.933 0.046 40.192
June 709.625 57.344 0.000 0.000 57.344
July 742.917 62.515 0.000 0.000 62.515
August 723.369 52.631 0.000 0.000 52.631
September 598.354 38.332 10.878 0.076 39.096
October 352.352 16.781 123.206 1.164 24.246
November 93.125 1.815 385.028 9.434 24.859
December 0.000 0.000 513.899 18.176 46.957
           
Annual Sum or Average 4449.156 295.632 2310.497 63.242 475.583
Minimum of Months 0.000 0.000 0.000 0.000 24.246
Maximum of Months 742.917 62.515 513.899 18.176 62.515



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 626.258 7.060 11.913
February 42.921 0.487 444.410 4.694 6.741
March 117.304 1.530 354.788 3.047 6.294
April 415.221 13.450 78.865 0.490 14.071
May 659.809 28.210 4.375 0.005 28.215
June 720.000 42.192 0.000 0.000 42.192
July 744.000 47.284 0.000 0.000 47.284
August 741.313 39.918 0.000 0.000 39.918
September 659.579 28.390 4.050 0.006 28.396
October 366.398 10.643 78.659 0.278 11.001
November 37.492 0.464 427.949 4.030 6.933
December 0.000 0.000 662.094 8.499 12.468
           
Annual Sum or Average 4504.037 212.568 2681.448 28.109 255.426
Minimum of Months 0.000 0.000 0.000 0.000 6.294
Maximum of Months 744.000 47.284 662.094 8.499 47.284



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 675.906 15.955 19.968
February 53.437 0.716 422.520 9.936 16.889
March 152.582 2.765 294.542 6.418 17.327
April 444.755 19.896 49.142 0.948 25.038
May 651.982 39.231 1.500 0.017 39.758
June 709.625 56.784 0.000 0.000 56.784
July 743.750 61.752 0.000 0.000 61.752
August 725.470 52.220 0.000 0.000 52.220
September 628.085 37.895 3.042 0.033 38.709
October 385.076 14.131 60.789 0.822 22.173
November 53.215 0.802 415.029 9.038 16.618
December 0.000 0.000 697.040 18.857 22.479
           
Annual Sum or Average 4547.979 286.191 2619.509 62.022 389.715
Minimum of Months 0.000 0.000 0.000 0.000 16.618
Maximum of Months 743.750 61.752 697.040 18.857 61.752



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 87.187 2.558 532.206 23.525 26.083
February 121.792 5.538 392.933 16.998 27.011
March 183.358 8.923 321.336 12.717 38.272
April 377.558 26.573 98.423 2.745 43.718
May 571.921 45.971 15.964 0.158 48.835
June 692.181 67.227 0.000 0.000 67.227
July 738.878 73.341 0.000 0.000 73.341
August 708.702 62.663 0.000 0.000 62.663
September 564.503 49.260 12.510 0.218 52.267
October 373.954 27.188 120.420 2.443 43.260
November 175.558 8.909 396.375 15.316 27.441
December 65.196 1.564 545.792 27.258 28.838
           
Annual Sum or Average 4660.789 379.715 2435.959 101.378 538.957
Minimum of Months 65.196 1.564 0.000 0.000 26.083
Maximum of Months 738.878 73.341 545.792 27.258 73.341



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 76.925 1.348 495.381 9.238 10.822
February 122.967 3.905 378.857 6.702 11.348
March 186.454 5.299 361.123 5.360 11.791
April 385.986 19.160 125.307 1.208 20.473
May 605.851 34.559 10.583 0.055 34.635
June 712.096 52.183 0.000 0.000 52.183
July 742.667 58.400 0.000 0.000 58.400
August 724.989 50.176 0.000 0.000 50.176
September 606.051 39.343 12.586 0.062 39.421
October 400.894 21.287 137.489 0.820 22.120
November 187.580 6.513 369.750 5.894 12.604
December 60.162 0.665 510.687 10.865 12.142
           
Annual Sum or Average 4812.622 292.838 2401.763 40.205 336.115
Minimum of Months 60.162 0.665 0.000 0.000 10.822
Maximum of Months 742.667 58.400 510.687 10.865 58.400



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 58.508 1.008 487.521 17.982 26.668
February 120.239 4.332 363.887 12.613 23.268
March 193.132 6.814 330.124 9.684 24.223
April 419.354 25.171 90.375 1.990 32.051
May 618.695 45.339 6.500 0.091 46.549
June 696.343 66.966 0.000 0.000 66.966
July 739.917 73.008 0.000 0.000 73.008
August 712.448 62.521 0.000 0.000 62.521
September 598.045 48.600 9.000 0.143 50.489
October 394.856 24.587 119.104 1.912 34.173
November 175.189 6.859 354.646 11.469 25.761
December 38.508 0.402 508.362 21.022 29.048
           
Annual Sum or Average 4765.233 365.608 2269.519 76.905 494.725
Minimum of Months 38.508 0.402 0.000 0.000 23.268
Maximum of Months 739.917 73.008 508.362 21.022 73.008



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 4.912 0.088 541.675 23.003 44.997
February 71.687 2.201 413.220 16.259 35.412
March 155.808 6.218 371.724 11.994 31.549
April 371.209 25.189 124.978 2.685 38.107
May 571.819 45.886 16.965 0.159 48.143
June 693.236 67.589 0.000 0.000 67.589
July 738.969 73.637 0.000 0.000 73.637
August 708.792 62.142 0.000 0.000 62.142
September 559.433 46.374 22.679 0.250 47.929
October 333.718 20.789 183.275 2.605 32.380
November 97.579 2.793 422.141 14.572 32.358
December 0.000 0.000 564.630 26.903 51.399
           
Annual Sum or Average 4307.163 352.906 2661.288 98.430 565.642
Minimum of Months 0.000 0.000 0.000 0.000 31.549
Maximum of Months 738.969 73.637 564.630 26.903 73.637



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 1.283 0.006 642.186 12.321 16.975
February 54.948 0.958 473.157 8.494 11.177
March 136.646 2.730 400.973 6.043 10.637
April 377.692 17.923 134.535 1.279 19.311
May 606.332 34.558 10.500 0.054 34.612
June 713.117 52.595 0.000 0.000 52.595
July 742.858 58.730 0.000 0.000 58.730
August 724.953 49.659 0.000 0.000 49.659
September 601.621 36.416 13.767 0.067 36.490
October 349.908 14.539 169.353 1.030 15.739
November 54.333 0.831 463.664 7.545 10.391
December 0.000 0.000 675.388 14.482 18.936
           
Annual Sum or Average 4363.690 268.945 2983.523 51.317 335.252
Minimum of Months 0.000 0.000 0.000 0.000 10.391
Maximum of Months 742.858 58.730 675.388 14.482 58.730



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.175 0.000 677.943 22.573 26.180
February 59.950 1.267 463.921 14.970 21.009
March 150.458 4.091 368.001 10.480 21.250
April 411.240 23.954 94.750 2.058 30.566
May 619.580 45.290 6.500 0.090 46.470
June 696.546 67.253 0.000 0.000 67.253
July 739.917 73.201 0.000 0.000 73.201
August 712.804 61.967 0.000 0.000 61.967
September 595.851 45.812 9.375 0.151 47.698
October 353.212 17.857 135.271 2.112 27.807
November 62.049 1.164 455.896 13.741 20.565
December 0.000 0.000 709.695 26.338 29.031
           
Annual Sum or Average 4401.782 341.857 2921.351 92.512 472.997
Minimum of Months 0.000 0.000 0.000 0.000 20.565
Maximum of Months 739.917 73.201 709.695 26.338 73.201



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.50
February 0.00 0.00 0.57
March 0.00 0.00 0.64
April 0.00 0.00 0.87
May 0.00 0.00 1.04
June 0.00 0.00 1.20
July 0.00 0.00 1.28
August 0.00 0.00 1.20
September 0.00 0.00 1.14
October 0.00 0.00 0.93
November 0.00 0.00 0.64
December 0.00 0.00 0.46
       
Annual Sum or Average 0.00 0.00 0.88
Minimum of Months 0.00 0.00 0.46
Maximum of Months 0.00 0.00 1.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.18
June 0.00 0.00 0.30
July 0.00 0.00 0.34
August 0.00 0.00 0.30
September 0.00 0.00 0.25
October 0.00 0.00 0.13
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.15
May 0.00 0.00 0.26
June 0.00 0.00 0.40
July 0.00 0.00 0.45
August 0.00 0.00 0.38
September 0.00 0.00 0.32
October 0.00 0.00 0.16
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.13
May 0.00 0.00 0.25
June 0.00 0.00 0.40
July 0.00 0.00 0.44
August 0.00 0.00 0.36
September 0.00 0.00 0.27
October 0.00 0.00 0.11
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.08
May 0.00 0.00 0.18
June 0.00 0.00 0.30
July 0.00 0.00 0.34
August 0.00 0.00 0.28
September 0.00 0.00 0.20
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.13
May 0.00 0.00 0.25
June 0.00 0.00 0.41
July 0.00 0.00 0.45
August 0.00 0.00 0.37
September 0.00 0.00 0.27
October 0.00 0.00 0.09
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.17
May 0.00 0.00 0.28
June 0.00 0.00 0.40
July 0.00 0.00 0.44
August 0.00 0.00 0.38
September 0.00 0.00 0.33
October 0.00 0.00 0.19
November 0.00 0.00 0.08
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.12
May 0.00 0.00 0.20
June 0.00 0.00 0.30
July 0.00 0.00 0.34
August 0.00 0.00 0.30
September 0.00 0.00 0.26
October 0.00 0.00 0.15
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.16
May 0.00 0.00 0.28
June 0.00 0.00 0.41
July 0.00 0.00 0.45
August 0.00 0.00 0.39
September 0.00 0.00 0.33
October 0.00 0.00 0.17
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.14
May 0.00 0.00 0.27
June 0.00 0.00 0.40
July 0.00 0.00 0.44
August 0.00 0.00 0.37
September 0.00 0.00 0.28
October 0.00 0.00 0.12
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.09
May 0.00 0.00 0.19
June 0.00 0.00 0.30
July 0.00 0.00 0.34
August 0.00 0.00 0.28
September 0.00 0.00 0.21
October 0.00 0.00 0.08
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.14
May 0.00 0.00 0.27
June 0.00 0.00 0.41
July 0.00 0.00 0.45
August 0.00 0.00 0.37
September 0.00 0.00 0.28
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.06
April 0.00 0.00 0.19
May 0.00 0.00 0.31
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.44
September 0.00 0.00 0.36
October 0.00 0.00 0.19
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.13
May 0.00 0.00 0.24
June 0.00 0.00 0.37
July 0.00 0.00 0.42
August 0.00 0.00 0.36
September 0.00 0.00 0.29
October 0.00 0.00 0.15
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.18
May 0.00 0.00 0.31
June 0.00 0.00 0.48
July 0.00 0.00 0.52
August 0.00 0.00 0.44
September 0.00 0.00 0.36
October 0.00 0.00 0.17
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.18
May 0.00 0.00 0.31
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.43
September 0.00 0.00 0.34
October 0.00 0.00 0.14
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.13
May 0.00 0.00 0.24
June 0.00 0.00 0.37
July 0.00 0.00 0.42
August 0.00 0.00 0.35
September 0.00 0.00 0.27
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.17
May 0.00 0.00 0.31
June 0.00 0.00 0.48
July 0.00 0.00 0.53
August 0.00 0.00 0.44
September 0.00 0.00 0.34
October 0.00 0.00 0.12
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:41

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1562.72 1163.49
February 0.00 0.00 1564.94 1052.39
March 0.00 0.00 1500.57 1117.21
April 0.00 0.00 1392.98 1003.66
May 0.00 0.00 1260.15 938.21
June 0.00 0.00 1146.42 826.00
July 0.00 0.00 1082.12 805.67
August 0.00 0.00 1075.51 800.74
September 0.00 0.00 1142.82 823.42
October 0.00 0.00 1253.31 933.12
November 0.00 0.00 1383.64 996.93
December 0.00 0.00 1498.82 1115.91
         
Annual Sum or Average 0.00 0.00 1320.61 11576.76
Minimum of Months 0.00 0.00 1075.51 800.74
Maximum of Months 0.00 0.00 1564.94 1163.49