Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39

Tabular Output Report in Format: HTML

Building: MF+CZ4BWH+USA_NM_Albuquerque.Intl.AP.723650+oilfurnace+unheatedbsmt+IECC_2009

Environment: ANNUAL ** Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650

Simulation Timestamp: 2019-02-14 08:39:43


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 990721.33 25.40 45.85
Net Site Energy 990721.33 25.40 45.85
Total Source Energy 2021148.45 51.82 93.53
Net Source Energy 2021148.45 51.82 93.53


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 241535.35 0.00 0.00 0.00 0.00
Cooling 68286.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24792.84 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 294454.09 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 454731.89 535989.43 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 241535.35 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 68286.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 24792.84 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 294454.09 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 4.31 24.80 0.00 0.00 0.00 19.42
Other 13.95 0.00 0.00 0.00 0.00 0.00
Total 21.04 24.80 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 2.39 13.74 0.00 0.00 0.00 10.76
Other 7.73 0.00 0.00 0.00 0.00 0.00
Total 11.66 13.74 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 454731.892 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 454731.892 100.00
     
Total On-Site and Utility Electric Sources 454731.892 100.00
Total Electricity End Uses 454731.892 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1736.00
Time Setpoint Not Met During Occupied Cooling 2.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 1242.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39
RunPeriod ANNUAL
Weather File Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [ft] 5311.94
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 18953.34 7014.93 2461.74 7014.93 2461.74
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 11.22 7.58 21.60 7.58 21.60
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
UNHEATEDBSMT 7794.39 No Yes 58419.71 1.00 185.02 2590.34 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 39005.17     325507.37   16363.00 2590.34 2126.74 2126.74 0.4163 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 2.9092
Unconditioned Total 17395.21     141767.99   1066.39 2590.34 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 21-JUL-18:15 17-JAN-08:30 - - - 01-JAN-08:15
Heating 0.00 173.53 0.00 0.00 0.00 0.00
Cooling 48.62 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.91 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 115.84 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 126.99 289.37 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 173.53 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 48.62 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 9.91 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 115.84 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 261824.32 0.00 0.00 0.00
Cooling 216262.53 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 78518.93 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 319188.23 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1440135.90 581012.55 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 12.12 0.00 0.00 0.00
Cooling 10.01 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.63 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.77 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 66.64 26.89 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 12.12 0.00 0.00 0.00
Cooling 10.01 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.63 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.77 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 66.64 26.89 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 17.78 0.00 17.78 Wetbulb [F] 629.95 0.00
ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 95.18 24.30 60.26 Wetbulb [F] 866.18 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.330 0.882              
North Total or Average           531.68 0.350 0.330 0.882              
Non-North Total or Average           1595.05 0.350 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 395589.55 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   27746.95 22160.25 5586.70 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7117.04 5684.06 1432.98 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9592.93 7661.44 1931.49 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14546.92 11617.98 2928.95 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6912.93 5521.05 1391.88 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9323.62 7446.36 1877.26 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14761.64 11789.46 2972.18 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7273.12 5808.71 1464.40 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9627.26 7688.86 1938.40 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14432.67 11526.73 2905.94 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7169.50 5725.96 1443.54 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9266.17 7400.47 1865.69 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16813.69 13428.35 3385.35 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9376.00 7488.19 1887.81 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11261.56 8994.10 2267.45 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16796.17 13414.35 3381.82 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9388.31 7498.02 1890.29 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11117.10 8878.73 2238.37 0.80 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.2 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.2 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.9 3.26 11.12 11.77 11.27
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 48515.54 52207.50 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 14061.43 14234.38 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 18198.01 18797.45 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 26474.41 27907.85 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 13720.44 13857.38 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 17748.09 18301.57 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 26831.22 28297.75 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 14321.32 14520.36 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 18254.18 18858.92 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 26281.68 27693.48 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 14148.23 14329.09 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 17650.97 18192.95 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 30261.43 32069.37 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 17835.31 18398.07 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 20985.73 21867.83 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 30232.15 32037.18 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 17855.87 18420.73 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 20744.39 21602.14 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1040.81 392.59 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 266.97 100.70 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 359.84 135.73 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 545.67 205.82 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 259.31 97.81 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 349.74 131.92 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 553.72 208.86 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 272.82 102.91 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 361.13 136.21 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 541.38 204.21 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 268.93 101.44 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 347.58 131.11 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 630.70 237.89 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 351.70 132.66 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 422.43 159.34 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 630.04 237.65 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 352.16 132.83 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 417.01 157.29 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 39.779575 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20111.47 20111.47 16.75 1040.814 1040.814 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00792 90.56 0.00565 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5158.51 5158.51 4.30 266.967 266.967 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00776 89.35 0.00565 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6953.52 6953.52 5.79 359.840 359.840 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.99 0.00767 95.18 0.00565 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10543.86 10543.86 8.78 545.669 545.669 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00784 90.56 0.00565 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5010.53 5010.53 4.17 259.310 259.310 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00784 86.61 0.00565 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6757.88 6757.88 5.63 349.738 349.738 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00770 84.91 0.00565 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10699.36 10699.36 8.91 553.723 553.723 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00793 90.56 0.00565 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5271.57 5271.57 4.39 272.821 272.821 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00797 87.53 0.00565 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6978.19 6978.19 5.81 361.127 361.127 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.99 0.00779 95.18 0.00565 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10460.90 10460.90 8.71 541.383 541.383 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00794 89.96 0.00565 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5196.45 5196.45 4.33 268.935 268.935 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00800 85.70 0.00565 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6716.19 6716.19 5.59 347.582 347.582 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 74.98 74.98 0.00780 85.95 0.00565 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8058.09 8058.09 6.71 417.013 417.013 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00771 94.09 0.00565 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8162.86 8162.86 6.80 422.431 422.431 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 74.98 74.99 0.00771 94.45 0.00565 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12186.81 12186.81 10.15 630.697 630.697 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00788 89.96 0.00565 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6804.70 6804.70 5.67 352.164 352.164 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00788 86.61 0.00565 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6795.80 6795.80 5.66 351.702 351.702 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00786 87.53 0.00565 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12174.11 12174.11 10.14 630.040 630.040 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00788 89.96 0.00565 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 362.53 362.53 0.30 8.023 44.995 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00317 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8060.25 8060.25 6.71 178.344 178.344 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00611 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10332.75 10332.75 8.61 228.621 228.621 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00631 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10333.20 10333.20 8.61 228.631 228.631 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00631 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8062.53 8062.53 6.72 178.394 178.394 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00611 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10330.85 10330.85 8.61 228.579 228.579 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00631 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8614.85 8614.85 7.18 190.627 190.627 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00658 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6332.06 6332.06 5.27 140.117 140.117 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00639 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8623.43 8623.43 7.18 190.817 190.817 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00658 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8623.25 8623.25 7.18 190.813 190.813 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00658 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6332.72 6332.72 5.27 140.132 140.132 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00639 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8621.04 8621.04 7.18 190.764 190.764 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00658 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11638.86 11638.86 9.69 257.519 257.519 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00644 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11638.67 11638.67 9.69 257.515 257.515 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00644 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11635.24 11635.24 9.69 257.439 257.439 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00644 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9357.31 9357.31 7.79 207.043 207.043 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00628 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9355.30 9355.30 7.79 206.998 206.998 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00628 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11640.46 11640.46 9.70 257.554 257.554 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00644 17.78 0.00234 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81 1040.81 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 266.97 266.97 178.34 178.34
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 359.84 359.84 228.62 228.62
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 545.67 545.67 228.63 228.63
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 259.31 259.31 178.39 178.39
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 349.74 349.74 228.58 228.58
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 553.72 553.72 190.63 190.63
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 272.82 272.82 140.12 140.12
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 361.13 361.13 190.82 190.82
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.38 541.38 190.81 190.81
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 268.93 268.93 140.13 140.13
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 347.58 347.58 190.76 190.76
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 630.70 630.70 257.44 257.44
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 351.70 351.70 207.00 207.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 422.43 422.43 257.51 257.51
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 630.04 630.04 257.55 257.55
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 352.16 352.16 207.04 207.04
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 417.01 417.01 257.52 257.52


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1191.50 5550.25 8.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1748.25 5794.00 454.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2065.00 5421.25 313.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2230.25 6073.50 758.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1278.75 6207.50 224.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1921.50 5882.00 331.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2095.75 5151.75 193.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1744.75 5343.00 133.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2201.25 5053.50 180.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2294.00 5727.75 566.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1537.25 5806.25 137.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2094.50 5548.25 200.25
LIVING_UNIT3_BACKROW_TOPFLOOR 2544.00 5578.75 502.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 2523.75 5337.75 431.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 2495.50 5464.50 573.25
LIVING_UNIT2_BACKROW_TOPFLOOR 1850.75 5857.00 219.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1909.00 5604.75 184.75
LIVING_UNIT1_BACKROW_TOPFLOOR 2694.25 5779.75 855.25
UNHEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3545.75 6661.50 1242.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 254.50 0.00 254.50 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 149.00 0.00 149.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 560.75 0.75 560.75 0.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 162.00 0.00 162.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 32.50 2.00 32.50 2.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 89.50 0.50 89.50 0.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2.50 0.00 2.50 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 193.00 0.00 193.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 593.25 0.25 593.25 0.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 125.50 0.00 125.50 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 61.75 1.00 61.75 1.00
LIVING_UNIT3_BACKROW_TOPFLOOR 32.75 0.00 32.75 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 96.50 0.00 96.50 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 206.75 0.75 206.75 0.75
LIVING_UNIT2_BACKROW_TOPFLOOR 87.75 0.00 87.75 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 22.75 0.00 22.75 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 458.75 0.75 458.75 0.75
UNHEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1736.00 2.75 1736.00 2.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.279 0.000 0.274
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.241 0.000 0.273
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.274 0.000 0.274
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.272 0.000 0.273
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.240 0.000 0.273
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.273 0.000 0.273
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.120 0.000 0.274
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.088 0.000 0.274
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.120 0.000 0.274
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.119 0.000 0.273
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.087 0.000 0.274
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.120 0.000 0.274
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.274 0.000 0.274
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.274 0.000 0.274
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.274 0.000 0.274
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.241 0.000 0.274
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.241 0.000 0.274
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.273 0.000 0.273
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1867
Defaulted Fields 446
Fields with Defaults 4744
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Fans:Electricity 7261.22 104.87 11-OCT-23:00 2955.23 21-JUL-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
ElectricityPurchased:Plant 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
Cogeneration:ElectricityPurchased 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
ElectricityNet:Plant 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
Cogeneration:ElectricityNet 133179.94 7459.22 27-APR-04:00 37192.37 21-JUL-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 27260.61 477.86 11-OCT-23:00 17918.21 28-JUN-16:30
General:Fans:Electricity 7261.22 104.87 11-OCT-23:00 2955.23 21-JUL-17:15
Cooling:Electricity 19999.38 0.00 07-JAN-03:00 14968.98 28-JUN-16:30
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 5359.89 0.00 12-FEB-14:30 289161.49 17-JAN-08:30
Gas:Plant 5359.89 0.00 12-FEB-14:30 289161.49 17-JAN-08:30
WaterSystems:Gas 2944.54 0.00 01-JAN-00:15 116206.08 05-FEB-08:30
Water Heater:WaterSystems:Gas 2944.54 0.00 01-JAN-00:15 116206.08 05-FEB-08:30
Heating:Gas 2415.35 0.00 12-FEB-14:30 173404.46 17-JAN-08:30
Boiler:Heating:Gas 2415.35 0.00 12-FEB-14:30 173404.46 17-JAN-08:30


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 06-JAN-02:30 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 349832.71 1275.00 08-AUG-03:00 179730.26 17-JAN-08:30
PlantLoopHeatingDemand:Plant 157360.25 1275.00 08-AUG-03:00 42533.93 05-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 157360.25 1275.00 08-AUG-03:00 42533.93 05-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1298056.03 16033.79 11-MAY-03:00 462244.70 17-JAN-08:30
EnergyTransfer:Building 460485.09 6513.28 11-OCT-23:00 171488.85 21-JUL-17:15
EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 201366.32 0.00 12-FEB-16:00 143790.88 17-JAN-08:30
Heating:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 259118.77 0.00 07-JAN-03:00 171488.85 21-JUL-17:15
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 72508.18 0.00 07-JAN-03:00 21975.63 21-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.11 0.00 01-JAN-00:15 236.18 17-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 72508.07 0.00 07-JAN-03:00 21975.63 21-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15920.86 0.00 01-JAN-10:45 12965.52 20-JAN-11:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7798.82 0.00 01-JAN-10:45 12965.52 20-JAN-11:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8122.04 0.00 01-JAN-00:15 6052.52 28-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 24023.47 0.00 01-JAN-10:00 10010.38 17-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11854.06 0.00 01-JAN-10:00 10010.38 17-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12169.41 0.00 01-JAN-00:15 7929.41 29-JUN-14:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 25167.63 0.00 01-JAN-15:00 12235.77 04-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15232.54 0.00 01-JAN-15:00 9764.43 14-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9935.08 0.00 01-JAN-00:15 12235.77 04-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 18728.98 0.00 12-FEB-16:00 7701.89 14-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12583.03 0.00 12-FEB-16:00 7701.89 14-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6145.95 0.00 01-JAN-00:15 5946.00 28-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 25085.08 0.00 12-FEB-13:45 9754.59 14-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15094.88 0.00 12-FEB-13:45 9754.59 14-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9990.21 0.00 01-JAN-00:15 7882.45 21-JUL-08:45
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 22345.20 0.00 01-JAN-11:00 12349.64 21-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8323.55 0.00 01-JAN-11:00 7662.95 15-DEC-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14021.65 0.00 01-JAN-00:15 12349.64 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 15344.82 0.00 01-JAN-10:45 6357.85 17-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5788.64 0.00 01-JAN-10:45 6357.85 17-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9556.18 0.00 01-JAN-00:15 6051.33 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22044.16 0.00 01-JAN-10:00 7944.77 15-DEC-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8341.11 0.00 01-JAN-10:00 7944.77 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13703.05 0.00 01-JAN-00:15 7884.37 29-JUN-15:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22382.87 0.00 01-JAN-15:15 12101.85 20-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11336.23 0.00 01-JAN-15:15 7992.45 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11046.64 0.00 01-JAN-00:15 12101.85 20-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 15979.79 0.00 10-FEB-18:15 5935.22 28-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8651.33 0.00 10-FEB-18:15 5783.21 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7328.46 0.00 01-JAN-00:15 5935.22 28-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22481.02 0.00 10-FEB-16:15 8016.35 15-DEC-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11194.43 0.00 10-FEB-16:15 8016.35 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11286.58 0.00 01-JAN-00:15 7824.69 21-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 29260.29 0.00 10-FEB-15:15 10839.03 15-DEC-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 16404.69 0.00 10-FEB-15:15 10839.03 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 12855.60 0.00 01-JAN-00:15 9345.24 28-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 27445.49 0.00 01-JAN-11:00 10767.43 15-DEC-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 13442.99 0.00 01-JAN-11:00 10767.43 15-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 14002.50 0.00 01-JAN-00:15 9388.49 29-JUN-15:45
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28340.90 0.00 01-JAN-12:00 14076.83 20-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 14033.31 0.00 01-JAN-12:00 10705.49 15-DEC-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 14307.58 0.00 01-JAN-00:15 14076.83 20-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22917.72 0.00 10-FEB-16:00 8749.65 15-DEC-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 13805.33 0.00 10-FEB-16:00 8749.65 15-DEC-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 9112.39 0.00 01-JAN-00:15 8074.06 28-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20821.39 0.00 01-JAN-11:30 8563.86 17-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10645.83 0.00 01-JAN-11:30 8563.86 17-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10175.56 0.00 01-JAN-00:15 8015.38 28-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 29687.24 0.00 01-JAN-15:15 14062.81 20-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 16835.44 0.00 01-JAN-15:15 10849.75 15-DEC-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 12851.81 0.00 01-JAN-00:15 14062.81 20-JUL-18:15
EnergyTransfer:Plant 350588.53 1275.00 08-AUG-03:00 179067.01 17-JAN-08:30
WaterSystems:EnergyTransfer 157360.25 1275.00 08-AUG-03:00 42533.93 05-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 157360.25 1275.00 08-AUG-03:00 42533.93 05-FEB-09:00
EnergyTransfer:HVAC 486982.42 6773.24 11-OCT-23:15 181403.13 21-JUL-17:15
HeatingCoils:EnergyTransfer 192472.46 0.00 12-FEB-14:30 139386.81 17-JAN-08:30
PlantLoopHeatingDemand:HVAC 192472.46 0.00 12-FEB-14:30 139386.81 17-JAN-08:30
HeatingCoils:PlantLoopHeatingDemand 192472.46 0.00 12-FEB-14:30 139386.81 17-JAN-08:30
CoolingCoils:EnergyTransfer 294509.95 0.00 07-JAN-03:00 181403.13 21-JUL-17:15
Boilers:EnergyTransfer 193228.28 0.00 12-FEB-14:30 138723.57 17-JAN-08:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.109 -6038.30 0.000 0.000 2876.529 2771.241 10464.601 11828.809 0.000 932.172 64866.614 0.000 -5792.17 0.000 -15439.91 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 7798.762 -676.38 0.000 0.000 3050.043 2771.241 10464.601 5441.093 0.000 877.128 0.000 0.000 -2207.91 0.000 -13104.29 -6968.73
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 11853.974 -1013.43 0.000 0.000 3036.601 2771.241 10464.601 12515.280 0.000 932.094 0.000 0.000 -5287.58 0.000 -14190.93 -9926.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 15232.448 -827.36 0.000 0.000 3057.790 2771.241 10464.601 8104.408 0.000 932.341 0.000 0.000 -5680.26 0.000 -13810.40 -11137.24
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 12582.955 -511.82 0.000 0.000 3049.104 2771.241 10464.601 1335.988 0.000 877.313 0.000 0.000 -2370.79 0.000 -13064.75 -9499.77
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 15094.790 -831.95 0.000 0.000 3050.096 2771.241 10464.601 8482.314 0.000 932.042 0.000 0.000 -5345.45 0.000 -13991.90 -11467.63
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 8323.474 -1167.68 0.000 0.000 3013.362 2771.241 10464.601 11925.452 0.000 670.801 0.007 0.000 -5663.42 0.000 -10140.67 -7343.35
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 5788.589 -795.81 0.000 0.000 3001.145 2771.241 10464.601 5421.986 0.000 616.061 0.088 0.000 -2275.61 0.000 -9298.55 -6933.34
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 8341.036 -1141.15 0.000 0.000 3017.363 2771.241 10464.601 12473.847 0.000 670.815 0.000 0.000 -5408.26 0.000 -10161.39 -8466.30
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 11336.150 -919.93 0.000 0.000 3040.689 2771.241 10464.601 8074.745 0.000 670.947 0.000 0.000 -5798.38 0.000 -9881.52 -9631.93
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 8651.274 -610.30 0.000 0.000 3030.478 2771.241 10464.601 1327.171 0.000 616.135 0.000 0.000 -2418.80 0.000 -9097.71 -8015.95
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 11194.367 -939.91 0.000 0.000 3034.879 2771.241 10464.601 8444.147 0.000 670.772 0.000 0.000 -5452.46 0.000 -10000.07 -9840.96
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 16404.592 -1070.58 0.000 0.000 3042.518 2771.241 10464.601 8446.684 0.000 924.881 0.000 0.000 -5453.31 0.000 -14074.64 -9671.08
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 13442.899 -1166.09 0.000 0.000 3032.123 2771.241 10464.601 12520.428 0.000 924.915 0.000 0.000 -5375.92 0.000 -14214.63 -9563.28
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 14033.211 -1191.49 0.000 0.000 3034.156 2771.241 10464.601 11989.086 0.000 924.979 0.000 0.000 -5593.32 0.000 -14135.87 -9180.67
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 13805.246 -758.85 0.000 0.000 3039.329 2771.241 10464.601 1321.230 0.000 870.476 0.000 0.000 -2413.75 0.000 -13170.40 -7575.65
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 10645.750 -847.39 0.000 0.000 3023.681 2771.241 10464.601 5437.368 0.000 870.419 0.000 0.000 -2253.52 0.000 -13335.31 -7448.76
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 16835.330 -1070.26 0.000 0.000 3047.088 2771.241 10464.601 8048.311 0.000 925.161 0.000 0.000 -5785.19 0.000 -13956.52 -9498.37
UNHEATEDBSMT 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4516.268 52535.156 0.000 0.000 0.000 -57051.42 -0.01
Total Facility 0.000 0.000 201364.956 -21578.65 0.000 0.000 54476.975 49882.340 188362.826 143138.347 0.000 19355.719 117401.864 0.000 -80576.12 0.000 -282120.88 -152169.02


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 21-JUL-17:08 0.00 0.00 0.00 -1.8 0.00 0.00 263.31 604.65 1664.02 8673.92 0.00 1791.42 9045.94 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 28-JUN-18:17 0.00 0.00 0.00 -0.5 0.00 0.00 426.65 813.96 1724.99 362.43 0.00 1557.93 1194.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUN-15:17 0.00 0.00 0.00 -0.7 0.00 0.00 114.76 201.55 1147.45 2658.11 0.00 2044.33 1786.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-JUL-17:19 0.00 0.00 0.00 -1.0 0.00 0.00 262.44 604.65 1664.02 8212.53 0.00 1944.16 0.00 0.00 0.00 0.00 0.00 -441.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 28-JUN-18:53 0.00 0.00 0.00 -0.5 0.00 0.00 426.17 813.96 1724.99 408.57 0.00 1442.44 1159.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21-JUL-08:45 0.00 0.00 0.00 -0.7 0.00 0.00 194.54 170.54 1155.86 7440.27 0.00 659.40 0.00 0.00 0.00 0.00 0.00 -1735.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21-JUL-18:15 0.00 0.00 0.00 -1.0 0.00 0.00 424.24 813.96 1724.99 5798.72 0.00 1098.72 2494.94 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 813.96 1724.99 400.22 0.00 1023.54 1663.05 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUN-14:49 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1091.85 2935.82 0.00 1545.25 2081.01 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 21-JUL-18:20 0.00 0.00 0.00 -1.0 0.00 0.00 425.03 813.96 1724.99 5105.57 0.00 1073.51 2961.01 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 28-JUN-18:02 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 813.96 1724.99 592.30 0.00 1023.46 1354.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21-JUL-09:00 0.00 0.00 0.00 -0.7 0.00 0.00 194.54 170.54 1155.86 7041.95 0.00 546.62 0.00 0.00 0.00 0.00 0.00 -1282.6
LIVING_UNIT3_BACKROW_TOPFLOOR 28-JUN-18:02 0.00 0.00 0.00 -0.8 0.00 0.00 427.01 813.96 1724.99 1141.70 0.00 1729.26 3520.48 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUN-15:47 0.00 0.00 0.00 -0.8 0.00 0.00 114.97 201.55 1147.45 2113.21 0.00 1803.28 4035.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-JUL-18:15 0.00 0.00 0.00 -1.2 0.00 0.00 426.25 813.96 1724.99 6315.73 0.00 1524.14 3275.64 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 28-JUN-18:48 0.00 0.00 0.00 -0.7 0.00 0.00 427.00 813.96 1724.99 392.83 0.00 1436.51 3318.74 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 28-JUN-18:34 0.00 0.00 0.00 -0.7 0.00 0.00 426.48 813.96 1724.99 301.79 0.00 1496.24 3295.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 20-JUL-18:17 0.00 0.00 0.00 -1.2 0.00 0.00 426.67 813.96 1724.99 5974.86 0.00 1457.16 3709.54 0.00 0.00 0.00 0.00 0.00
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-JUL-17:04 0.00 0.00 0.00 -14.3 0.00 0.00 4726.29 10883.76 29952.39 66048.32 0.00 28534.33 45004.49 0.00 0.00 0.00 -13572.5 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17-JAN-08:23 0.00 0.00 491.89 0.00 0.00 0.00 215.06 170.54 1155.86 0.00 0.00 0.00 5388.42 0.00 -1649.3 0.00 -5772.4 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17-JAN-07:48 0.00 0.00 13979.67 0.00 0.00 0.00 618.38 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -532.6 0.00 -3977.4 -11686.4
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 17-JAN-08:15 0.00 0.00 10010.08 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1672.0 0.00 -5891.3 -3988.2
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 27-DEC-13:23 0.00 0.00 19533.19 0.00 0.00 0.00 147.76 116.28 1084.63 519.27 0.00 0.00 0.00 0.00 0.00 0.00 -1647.9 -19753.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 22-FEB-17:20 0.00 0.00 12428.37 0.00 0.00 0.00 318.19 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -373.6 0.00 -2469.1 -12172.5
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14-DEC-04:00 0.00 0.00 9755.26 0.00 0.00 0.00 526.29 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2025.8 0.00 -6944.5 -2220.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24-APR-08:42 0.00 0.00 18590.97 0.00 0.00 0.00 227.77 170.54 1155.86 691.13 0.00 0.00 0.00 0.00 0.00 0.00 -1138.2 -19698.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17-JAN-08:15 0.00 0.00 6357.62 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -700.3 0.00 -3284.4 -3914.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 06-JAN-20:56 0.00 0.00 10766.41 0.00 0.00 0.00 497.68 902.05 1628.20 0.00 0.00 0.00 0.00 0.00 -1825.3 0.00 -2444.2 -9524.9
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 28-NOV-12:22 0.00 0.00 19353.30 0.00 0.00 0.00 145.53 116.28 1090.63 291.59 0.00 0.00 0.00 0.00 0.00 0.00 -1304.7 -19692.6
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 31-DEC-17:00 0.00 0.00 12746.74 0.00 0.00 0.00 162.47 434.11 1371.36 0.00 0.00 0.00 0.00 0.00 -464.3 0.00 -1273.1 -12977.2
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24-FEB-18:00 0.00 0.00 8578.30 0.00 0.00 0.00 291.10 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -1546.0 0.00 -2262.6 -7329.5
LIVING_UNIT3_BACKROW_TOPFLOOR 15-DEC-04:53 0.00 0.00 10839.12 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2412.3 0.00 -5488.1 -4483.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 15-DEC-04:53 0.00 0.00 10767.64 0.00 0.00 0.00 526.32 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2413.5 0.00 -5488.1 -4410.3
LIVING_UNIT1_FRONTROW_TOPFLOOR 24-APR-08:48 0.00 0.00 19351.12 0.00 0.00 0.00 236.38 170.54 1155.86 815.14 0.00 0.00 0.00 0.00 0.00 0.00 -1276.5 -20452.6
LIVING_UNIT2_BACKROW_TOPFLOOR 24-FEB-17:06 0.00 0.00 15627.32 0.00 0.00 0.00 312.47 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -412.4 0.00 -2867.2 -14928.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 15-APR-18:53 0.00 0.00 9875.09 0.00 0.00 0.00 472.90 813.96 1748.06 0.00 0.00 0.00 0.00 0.00 -501.4 0.00 -3194.4 -9214.2
LIVING_UNIT1_BACKROW_TOPFLOOR 29-DEC-13:36 0.00 0.00 22066.58 0.00 0.00 0.00 143.12 116.28 1084.63 1051.99 0.00 0.00 0.00 0.00 0.00 0.00 -1474.3 -22988.3
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-JAN-08:19 0.00 0.00 148828.96 0.00 0.00 0.00 3921.64 3069.78 20805.49 0.00 0.00 146.08 0.00 0.00 -24035.9 0.00 -87885.7 -64850.4



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1040.814 2.00 2.00 1.00 44.9950 1040.814 0.043 1.000 44.9950 0.04
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 266.967 2.00 2.00 1.00 44.9950 266.967 0.169 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 359.840 2.00 2.00 1.00 44.9950 359.840 0.125 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 545.669 2.00 2.00 1.00 44.9950 545.669 0.082 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 259.310 2.00 2.00 1.00 44.9950 259.310 0.174 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 349.738 2.00 2.00 1.00 44.9950 349.738 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 553.723 2.00 2.00 1.00 44.9950 553.723 0.081 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 272.821 2.00 2.00 1.00 44.9950 272.821 0.165 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 361.127 2.00 2.00 1.00 44.9950 361.127 0.125 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.383 2.00 2.00 1.00 44.9950 541.383 0.083 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 268.935 2.00 2.00 1.00 44.9950 268.935 0.167 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 347.582 2.00 2.00 1.00 44.9950 347.582 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 630.697 2.00 2.00 1.00 44.9950 630.697 0.071 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 351.702 2.00 2.00 1.00 44.9950 351.702 0.128 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 422.431 2.00 2.00 1.00 44.9950 422.431 0.107 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 630.040 2.00 2.00 1.00 44.9950 630.040 0.071 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 352.164 2.00 2.00 1.00 44.9950 352.164 0.128 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 417.013 2.00 2.00 1.00 44.9950 417.013 0.108 1.000 44.9950 0.11


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 178.344 2.00 2.00 1.00 44.9950 178.344 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 228.621 2.00 2.00 1.00 44.9950 228.621 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 228.631 2.00 2.00 1.00 44.9950 228.631 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 178.394 2.00 2.00 1.00 44.9950 178.394 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 228.579 2.00 2.00 1.00 44.9950 228.579 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 190.627 2.00 2.00 1.00 44.9950 190.627 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 140.117 2.00 2.00 1.00 44.9950 140.117 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 190.817 2.00 2.00 1.00 44.9950 190.817 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 190.813 2.00 2.00 1.00 44.9950 190.813 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 140.132 2.00 2.00 1.00 44.9950 140.132 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 190.764 2.00 2.00 1.00 44.9950 190.764 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 257.439 2.00 2.00 1.00 44.9950 257.439 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 206.998 2.00 2.00 1.00 44.9950 206.998 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 257.515 2.00 2.00 1.00 44.9950 257.515 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 257.554 2.00 2.00 1.00 44.9950 257.554 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 207.043 2.00 2.00 1.00 44.9950 207.043 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 257.519 2.00 2.00 1.00 44.9950 257.519 1.000 1.000 44.9950 0.17


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   1040.814 1040.8137 208.1627 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   266.967 266.9667 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   359.840 359.8397 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   545.669 545.6685 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   259.310 259.3103 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   349.738 349.7377 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   553.723 553.7227 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   272.821 272.8213 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   361.127 361.1274 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   541.383 541.3828 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   268.935 268.9346 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   347.582 347.5824 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   417.013 417.0126 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   422.431 422.4313 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   630.697 630.6972 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   352.164 352.1641 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   351.702 351.7024 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   630.040 630.0397 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81 1040.814 1040.81 208.1627 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 266.97 266.967 266.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 359.84 359.840 359.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 545.67 545.669 545.67 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 259.31 259.310 259.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 349.74 349.738 349.74 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 553.72 553.723 553.72 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 272.82 272.821 272.82 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 361.13 361.127 361.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.38 541.383 541.38 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 268.93 268.935 268.93 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 347.58 347.582 347.58 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 630.70 630.697 630.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 351.70 351.702 351.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 422.43 422.431 422.43 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 630.04 630.040 630.04 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 352.16 352.164 352.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 417.01 417.013 417.01 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   178.344 178.344 178.344 44.9950 0.252 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   228.621 228.621 228.621 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   228.631 228.631 228.631 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   178.394 178.394 178.394 44.9950 0.252 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   228.579 228.579 228.579 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   190.627 190.627 190.627 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   140.117 140.117 140.117 44.9950 0.321 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   190.817 190.817 190.817 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   190.813 190.813 190.813 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   140.132 140.132 140.132 44.9950 0.321 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   190.764 190.764 190.764 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   257.519 257.519 257.519 44.9950 0.175 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   257.515 257.515 257.515 44.9950 0.175 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   257.439 257.439 257.439 44.9950 0.175 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   207.043 207.043 207.043 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   206.998 206.998 206.998 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   257.554 257.554 257.554 44.9950 0.175 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 178.34 178.344 178.34 178.34 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 228.62 228.621 228.62 228.62 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 228.63 228.631 228.63 228.63 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 178.39 178.394 178.39 178.39 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 228.58 228.579 228.58 228.58 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 190.63 190.627 190.63 190.63 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 140.12 140.117 140.12 140.12 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 190.82 190.817 190.82 190.82 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 190.81 190.813 190.81 190.81 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 140.13 140.132 140.13 140.13 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 190.76 190.764 190.76 190.76 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 257.44 257.439 257.44 257.44 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 207.00 206.998 207.00 207.00 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 257.51 257.515 257.51 257.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 257.55 257.554 257.55 257.55 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 207.04 207.043 207.04 207.04 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 257.52 257.519 257.52 257.52 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Sec1.1A-General Information

Data
Weather File ANNUAL ** Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
UNHEATEDBSMT 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1736.00
Number of hours cooling loads not met 2.75
Number of hours not met 1738.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 2415.35 173404.46 0.00 0.00
Space Cooling 19999.38 14239.73 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 7261.22 2903.72 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2944.54 115757.03 0.00 0.00
Receptacle Equipment 88303.07 15031.50 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 133179.94   5359.89   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 454731.89
Natural Gas 0.00 535989.43
Additional 0.00 0.00
Total 301503.54 990721.33


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 0.51
Fans-Interior 0.19
Service Water Heating 0.00
Receptacle Equipment 2.26
Miscellaneous 0.08
Subtotal 3.41


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 1.81
Service Water Heating 2.21
Miscellaneous -0.0
Subtotal 4.02


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.03
Space Heating 24.38
Space Cooling 6.89
Fans-Interior 2.50
Service Water Heating 29.72
Receptacle Equipment 30.43
Miscellaneous 1.04



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 266.97
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 359.84
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 545.67
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 259.31
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 349.74
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 553.72
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 272.82
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 361.13
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 541.38
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 268.93
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 347.58
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 417.01
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 422.43
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 630.70
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 352.16
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 351.70
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 630.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 266.97
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 359.84
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 545.67
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 259.31
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 349.74
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 553.72
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 272.82
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 361.13
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 541.38
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 268.93
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 347.58
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 630.70
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 351.70
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 422.43
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 630.04
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 352.16
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 417.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81 2.31 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 266.97 0.593086 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 359.84 0.799411 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 545.67 1.21 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 259.31 0.576077 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 349.74 0.776968 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 553.72 1.23 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 272.82 0.606093 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 361.13 0.802272 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 541.38 1.20 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 268.93 0.597458 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 347.58 0.772180 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 630.70 1.40 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 351.70 0.781333 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 422.43 0.938463 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 630.04 1.40 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 352.16 0.782359 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 417.01 0.926425 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81 1040.81 1040.81 2.31 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 266.97 266.97 266.97 0.593086 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 359.84 359.84 359.84 0.799411 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 545.67 545.67 545.67 1.21 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 259.31 259.31 259.31 0.576077 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 349.74 349.74 349.74 0.776968 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 553.72 553.72 553.72 1.23 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 272.82 272.82 272.82 0.606093 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 361.13 361.13 361.13 0.802272 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 541.38 541.38 541.38 1.20 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 268.93 268.93 268.93 0.597458 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 347.58 347.58 347.58 0.772180 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 630.70 630.70 630.70 1.40 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 351.70 351.70 351.70 0.781333 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 422.43 422.43 422.43 0.938463 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 630.04 630.04 630.04 1.40 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 352.16 352.16 352.16 0.782359 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 417.01 417.01 417.01 0.926425 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 48515.54 4.90 693.25
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 14061.43 1.42 192.29
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 18198.01 1.84 252.36
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 26474.41 2.67 372.39
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13720.44 1.38 187.33
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 17748.09 1.79 245.82
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 26831.22 2.71 377.50
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 14321.32 1.45 196.03
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 18254.18 1.84 253.15
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 26281.68 2.65 369.54
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 14148.23 1.43 193.52
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 17650.97 1.78 244.37
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 30261.43 3.05 427.22
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 17835.31 1.80 247.10
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 20985.73 2.12 292.80
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 30232.15 3.05 426.80
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 17855.87 1.80 247.39
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 20744.39 2.09 289.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 1040.81
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 266.97
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 359.84
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 545.67
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 259.31
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 349.74
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 553.72
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 272.82
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 361.13
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 541.38
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 268.93
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 347.58
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 630.70
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 351.70
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 422.43
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 630.04
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 352.16
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 417.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.32 99.71
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.32
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 395589.55 39.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:43

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 649.691 50.654 0.315 0.002 50.655
February 618.840 53.724 0.000 0.000 53.724
March 742.108 75.723 0.000 0.000 75.723
April 720.000 99.125 0.000 0.000 99.125
May 744.000 119.892 0.000 0.000 119.892
June 720.000 143.720 0.000 0.000 143.720
July 744.000 165.646 0.000 0.000 165.646
August 744.000 159.342 0.000 0.000 159.342
September 720.000 136.541 0.000 0.000 136.541
October 744.000 107.440 0.000 0.000 107.440
November 711.141 70.607 0.000 0.000 70.607
December 671.237 50.462 0.000 0.000 50.462
           
Annual Sum or Average 8529.018 1232.876 0.315 0.002 1232.878
Minimum of Months 618.840 50.462 0.000 0.000 50.462
Maximum of Months 744.000 165.646 0.315 0.002 165.646



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 78.156 1.780 466.752 8.822 20.067
February 75.979 2.025 424.320 7.048 14.426
March 107.938 2.248 482.608 5.666 8.104
April 226.936 5.906 255.583 2.070 7.976
May 338.753 10.881 140.659 0.785 11.667
June 538.175 24.000 23.658 0.091 24.091
July 723.389 35.352 0.000 0.000 35.352
August 673.064 31.190 0.000 0.000 31.190
September 491.810 21.034 10.125 0.010 21.044
October 316.428 11.801 232.667 2.308 14.109
November 111.955 2.553 414.958 5.188 8.633
December 47.541 0.808 473.045 8.687 16.822
           
Annual Sum or Average 3730.123 149.578 2924.376 40.677 213.482
Minimum of Months 47.541 0.808 0.000 0.000 7.976
Maximum of Months 723.389 35.352 482.608 8.822 35.352



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 75.148 1.875 547.019 26.741 32.337
February 73.931 2.416 455.699 20.348 26.468
March 135.255 3.775 428.500 13.551 21.198
April 304.566 11.228 179.361 4.487 21.489
May 407.759 18.862 97.021 1.674 25.513
June 560.547 37.833 15.875 0.254 40.193
July 705.533 51.020 0.000 0.000 51.020
August 660.825 45.314 0.000 0.000 45.314
September 497.074 29.488 8.625 0.093 33.229
October 328.628 15.521 203.133 6.003 26.456
November 102.675 2.751 394.811 14.010 22.812
December 33.130 0.561 538.937 25.591 31.989
           
Annual Sum or Average 3885.071 220.643 2868.982 112.753 378.018
Minimum of Months 33.130 0.561 0.000 0.000 21.198
Maximum of Months 705.533 51.020 547.019 26.741 51.020



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 621.279 35.858 52.732
February 18.990 0.496 514.568 27.131 44.248
March 64.021 2.002 491.804 17.880 36.074
April 202.454 9.293 261.518 6.381 32.396
May 324.686 17.583 142.258 2.537 27.954
June 512.092 36.814 39.983 0.458 38.688
July 699.935 48.422 0.000 0.000 48.422
August 631.501 41.049 0.000 0.000 41.049
September 419.570 22.937 45.259 0.298 25.222
October 195.945 8.528 303.026 8.763 27.627
November 7.729 0.109 498.411 20.888 47.221
December 0.000 0.000 608.610 36.220 61.643
           
Annual Sum or Average 3076.924 187.232 3526.716 156.415 483.278
Minimum of Months 0.000 0.000 0.000 0.000 25.222
Maximum of Months 699.935 48.422 621.279 36.220 61.643



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 703.470 15.739 19.536
February 0.000 0.000 599.956 12.102 16.145
March 7.542 0.037 577.597 7.627 12.201
April 164.237 3.359 305.025 2.775 8.143
May 328.063 9.529 145.832 0.977 11.329
June 540.926 23.849 25.038 0.112 23.974
July 723.638 34.366 0.000 0.000 34.366
August 670.493 28.034 0.000 0.000 28.034
September 461.687 13.798 18.208 0.024 13.822
October 159.711 3.415 326.232 3.492 8.619
November 0.000 0.000 633.535 9.372 15.712
December 0.000 0.000 733.201 16.395 17.369
           
Annual Sum or Average 3056.296 116.386 4068.094 68.616 209.250
Minimum of Months 0.000 0.000 0.000 0.000 8.143
Maximum of Months 723.638 34.366 733.201 16.395 34.366



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.998 33.621 33.847
February 1.763 0.007 629.265 25.646 26.400
March 27.108 0.260 539.097 15.568 17.412
April 262.307 8.069 226.488 5.022 17.567
May 401.831 17.581 107.042 1.796 23.626
June 563.319 37.580 17.375 0.267 39.674
July 705.908 49.877 0.000 0.000 49.877
August 660.665 42.247 0.000 0.000 42.247
September 491.760 22.610 13.500 0.133 25.958
October 204.382 6.110 275.657 7.242 17.283
November 0.000 0.000 692.063 20.339 21.717
December 0.000 0.000 742.984 35.013 35.125
           
Annual Sum or Average 3319.042 184.341 3985.467 144.647 350.733
Minimum of Months 0.000 0.000 0.000 0.000 17.283
Maximum of Months 705.908 49.877 742.984 35.013 49.877



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 103.191 4.114 530.562 21.684 25.799
February 116.471 5.214 425.212 16.352 21.748
March 159.617 7.156 379.876 10.444 25.236
April 287.824 14.845 176.925 3.426 27.066
May 391.006 21.833 85.382 1.142 26.690
June 570.745 40.087 15.200 0.152 40.673
July 731.544 53.380 0.000 0.000 53.380
August 698.056 48.632 0.000 0.000 48.632
September 514.155 33.632 6.075 0.021 33.778
October 336.340 20.102 196.458 4.700 28.890
November 150.172 5.959 388.583 11.108 17.518
December 92.672 2.805 514.125 20.917 23.722
           
Annual Sum or Average 4151.792 257.761 2718.400 89.947 373.132
Minimum of Months 92.672 2.805 0.000 0.000 17.518
Maximum of Months 731.544 53.380 530.562 21.684 53.380



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 108.337 2.436 502.012 7.884 11.003
February 99.796 2.601 403.915 5.875 8.916
March 144.554 3.056 382.118 3.663 7.879
April 280.931 7.642 179.487 1.231 9.448
May 416.093 13.417 69.707 0.399 13.955
June 606.816 27.113 8.417 0.037 27.158
July 742.750 39.237 0.000 0.000 39.237
August 730.926 35.694 0.000 0.000 35.694
September 576.820 24.790 0.000 0.000 24.790
October 380.264 14.186 178.833 1.490 15.706
November 152.832 3.648 343.871 3.561 7.231
December 81.151 1.385 482.625 7.368 8.830
           
Annual Sum or Average 4321.272 175.205 2550.985 31.508 209.847
Minimum of Months 81.151 1.385 0.000 0.000 7.231
Maximum of Months 742.750 39.237 502.012 7.884 39.237



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 95.687 2.459 492.450 19.395 27.760
February 96.636 2.994 388.175 14.403 23.483
March 167.272 4.854 337.873 8.784 20.243
April 350.481 13.652 119.500 2.495 21.173
May 463.019 21.871 37.292 0.723 26.725
June 608.514 41.100 4.250 0.071 42.290
July 731.875 54.787 0.000 0.000 54.787
August 710.909 49.576 0.000 0.000 49.576
September 557.243 33.091 0.000 0.000 33.922
October 377.038 17.907 151.833 3.827 27.356
November 136.646 3.798 318.833 9.418 21.724
December 56.896 0.981 472.375 18.611 26.846
           
Annual Sum or Average 4352.216 247.067 2322.582 77.728 375.885
Minimum of Months 56.896 0.981 0.000 0.000 20.243
Maximum of Months 731.875 54.787 492.450 19.395 54.787



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 590.042 27.473 47.874
February 23.629 0.526 466.266 20.078 40.493
March 83.204 2.407 425.486 12.248 32.744
April 243.321 10.871 188.682 3.702 30.311
May 378.109 19.975 82.144 1.088 28.835
June 569.264 39.697 16.846 0.182 40.428
July 730.898 52.409 0.000 0.000 52.409
August 695.219 45.536 0.000 0.000 45.536
September 488.052 26.296 10.248 0.036 26.823
October 239.196 9.935 253.740 6.044 25.773
November 9.425 0.131 448.817 15.161 42.396
December 0.000 0.000 572.795 27.759 59.228
           
Annual Sum or Average 3460.317 207.783 3055.064 113.770 472.850
Minimum of Months 0.000 0.000 0.000 0.000 25.773
Maximum of Months 730.898 52.409 590.042 27.759 59.228



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 693.015 11.148 16.138
February 0.000 0.000 568.333 8.366 13.073
March 21.963 0.160 506.972 4.784 8.476
April 212.281 4.860 217.416 1.525 7.650
May 409.063 12.216 77.061 0.432 12.931
June 610.293 27.111 8.242 0.036 27.160
July 742.375 38.392 0.000 0.000 38.392
August 729.967 32.804 0.000 0.000 32.804
September 553.823 17.791 0.000 0.000 17.791
October 229.689 4.994 268.127 2.186 9.032
November 0.000 0.000 585.722 6.387 12.980
December 0.000 0.000 727.671 11.884 13.405
           
Annual Sum or Average 3509.454 138.328 3652.559 46.748 209.833
Minimum of Months 0.000 0.000 0.000 0.000 7.650
Maximum of Months 742.375 38.392 727.671 11.884 38.392



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.957 25.522 25.745
February 4.733 0.027 601.656 18.828 20.602
March 49.537 0.567 446.825 10.116 14.690
April 299.761 10.215 133.333 2.725 17.653
May 458.592 20.640 40.771 0.737 25.223
June 610.535 40.840 4.375 0.071 41.974
July 731.875 53.653 0.000 0.000 53.653
August 710.249 46.642 0.000 0.000 46.642
September 552.025 26.472 0.000 0.000 27.399
October 255.824 7.814 220.112 4.693 16.899
November 0.000 0.000 638.566 14.414 17.753
December 0.000 0.000 742.474 26.923 27.099
           
Annual Sum or Average 3673.132 206.870 3570.069 104.030 335.334
Minimum of Months 0.000 0.000 0.000 0.000 14.690
Maximum of Months 731.875 53.653 742.474 26.923 53.653



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 61.779 2.054 592.442 38.527 40.581
February 75.783 3.447 494.829 29.535 33.484
March 118.633 5.433 435.098 19.748 40.357
April 245.129 14.151 201.124 6.472 45.597
May 349.789 22.890 100.806 2.344 40.205
June 532.937 44.773 22.563 0.428 47.842
July 717.873 60.200 0.000 0.000 60.200
August 663.155 53.496 0.000 0.000 53.496
September 467.275 34.688 15.803 0.149 39.307
October 288.442 18.602 230.657 9.089 38.008
November 95.375 3.548 470.100 21.554 27.758
December 36.904 0.864 601.492 37.836 38.700
           
Annual Sum or Average 3653.075 264.145 3164.913 165.681 505.534
Minimum of Months 36.904 0.864 0.000 0.000 27.758
Maximum of Months 717.873 60.200 601.492 38.527 60.200



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 45.892 0.780 572.087 14.386 15.973
February 66.579 1.549 480.950 11.069 15.158
March 95.304 2.161 482.472 7.748 11.825
April 236.250 7.760 260.737 2.956 11.309
May 361.950 15.014 133.461 1.135 16.641
June 565.843 32.085 21.454 0.133 32.237
July 734.974 46.387 0.000 0.000 46.387
August 697.805 40.827 0.000 0.000 40.827
September 510.244 26.117 14.098 0.019 26.136
October 313.613 13.060 234.262 3.271 17.068
November 86.146 1.716 447.377 7.611 10.001
December 18.586 0.227 579.117 13.948 14.897
           
Annual Sum or Average 3733.185 187.682 3226.016 62.276 258.459
Minimum of Months 18.586 0.227 0.000 0.000 10.001
Maximum of Months 734.974 46.387 579.117 14.386 46.387



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 43.433 0.770 571.354 28.359 33.102
February 63.503 1.814 488.804 21.620 26.939
March 120.592 3.254 453.833 14.139 21.296
April 298.723 12.610 190.167 4.572 22.711
May 418.956 22.528 95.885 1.646 28.637
June 580.498 45.426 13.208 0.222 47.195
July 722.817 61.528 0.000 0.000 61.528
August 687.537 54.413 0.000 0.000 54.413
September 521.364 34.070 8.625 0.071 37.151
October 324.876 16.218 209.575 6.297 27.305
November 79.134 1.766 427.696 15.180 23.132
December 10.938 0.156 583.526 27.928 34.772
           
Annual Sum or Average 3872.370 254.553 3042.674 120.032 418.180
Minimum of Months 10.938 0.156 0.000 0.000 21.296
Maximum of Months 722.817 61.528 583.526 28.359 61.528



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 617.661 39.359 59.442
February 24.783 0.708 527.480 29.996 43.701
March 80.979 2.979 482.705 19.391 38.479
April 230.675 12.692 246.676 6.940 37.640
May 348.049 22.565 133.390 2.663 33.629
June 535.524 45.075 26.646 0.372 47.518
July 718.401 60.237 0.000 0.000 60.237
August 662.376 52.608 0.000 0.000 52.608
September 453.852 30.813 35.605 0.236 33.296
October 226.914 11.734 277.005 9.223 34.848
November 12.204 0.176 502.670 23.265 49.438
December 0.000 0.000 637.446 40.887 63.615
           
Annual Sum or Average 3293.758 239.585 3487.283 172.331 554.450
Minimum of Months 0.000 0.000 0.000 0.000 33.296
Maximum of Months 718.401 60.237 637.446 40.887 63.615



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 705.186 18.503 23.317
February 6.342 0.034 584.392 14.054 18.106
March 38.137 0.485 543.370 8.866 13.142
April 207.906 6.621 278.254 3.183 10.769
May 361.575 14.825 132.429 1.137 16.543
June 568.942 32.500 21.500 0.130 32.641
July 734.961 46.448 0.000 0.000 46.448
August 697.218 39.968 0.000 0.000 39.968
September 495.334 22.294 15.987 0.022 22.316
October 214.870 6.628 304.408 4.142 12.459
November 0.000 0.000 618.846 11.183 17.211
December 0.000 0.000 735.132 19.391 20.478
           
Annual Sum or Average 3325.285 169.803 3939.502 80.612 273.398
Minimum of Months 0.000 0.000 0.000 0.000 10.769
Maximum of Months 734.961 46.448 735.132 19.391 46.448



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 742.243 34.397 34.647
February 8.875 0.108 607.786 25.788 27.390
March 56.742 1.054 527.113 15.404 19.196
April 276.989 11.271 207.192 4.778 21.588
May 418.657 22.345 96.875 1.659 28.386
June 582.437 45.697 13.333 0.218 47.410
July 723.242 61.423 0.000 0.000 61.423
August 686.724 53.503 0.000 0.000 53.503
September 517.996 30.416 10.000 0.075 33.476
October 240.330 9.334 265.284 7.221 20.648
November 0.000 0.000 659.510 20.496 22.959
December 0.000 0.000 743.199 35.948 36.055
           
Annual Sum or Average 3511.991 235.152 3872.535 145.984 406.681
Minimum of Months 0.000 0.000 0.000 0.000 19.196
Maximum of Months 723.242 61.423 743.199 35.948 61.423



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.38
February 0.00 0.00 0.44
March 0.00 0.00 0.55
April 0.00 0.00 0.73
May 0.00 0.00 0.85
June 0.00 0.00 1.04
July 0.00 0.00 1.17
August 0.00 0.00 1.13
September 0.00 0.00 1.01
October 0.00 0.00 0.78
November 0.00 0.00 0.54
December 0.00 0.00 0.38
       
Annual Sum or Average 0.00 0.00 0.75
Minimum of Months 0.00 0.00 0.38
Maximum of Months 0.00 0.00 1.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.04
May 0.00 0.00 0.07
June 0.00 0.00 0.17
July 0.00 0.00 0.25
August 0.00 0.00 0.22
September 0.00 0.00 0.16
October 0.00 0.00 0.08
November 0.00 0.00 0.02
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.08
May 0.00 0.00 0.13
June 0.00 0.00 0.27
July 0.00 0.00 0.37
August 0.00 0.00 0.33
September 0.00 0.00 0.22
October 0.00 0.00 0.11
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.12
June 0.00 0.00 0.26
July 0.00 0.00 0.33
August 0.00 0.00 0.28
September 0.00 0.00 0.16
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.17
July 0.00 0.00 0.24
August 0.00 0.00 0.20
September 0.00 0.00 0.10
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.06
May 0.00 0.00 0.12
June 0.00 0.00 0.27
July 0.00 0.00 0.36
August 0.00 0.00 0.30
September 0.00 0.00 0.16
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.15
June 0.00 0.00 0.28
July 0.00 0.00 0.37
August 0.00 0.00 0.34
September 0.00 0.00 0.24
October 0.00 0.00 0.14
November 0.00 0.00 0.04
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.19
July 0.00 0.00 0.28
August 0.00 0.00 0.26
September 0.00 0.00 0.18
October 0.00 0.00 0.10
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.15
June 0.00 0.00 0.30
July 0.00 0.00 0.39
August 0.00 0.00 0.36
September 0.00 0.00 0.25
October 0.00 0.00 0.13
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.14
June 0.00 0.00 0.28
July 0.00 0.00 0.36
August 0.00 0.00 0.31
September 0.00 0.00 0.19
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.08
June 0.00 0.00 0.19
July 0.00 0.00 0.27
August 0.00 0.00 0.23
September 0.00 0.00 0.13
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.07
May 0.00 0.00 0.14
June 0.00 0.00 0.30
July 0.00 0.00 0.39
August 0.00 0.00 0.34
September 0.00 0.00 0.19
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.10
May 0.00 0.00 0.16
June 0.00 0.00 0.31
July 0.00 0.00 0.41
August 0.00 0.00 0.37
September 0.00 0.00 0.25
October 0.00 0.00 0.13
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.33
August 0.00 0.00 0.29
September 0.00 0.00 0.19
October 0.00 0.00 0.09
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.09
May 0.00 0.00 0.16
June 0.00 0.00 0.33
July 0.00 0.00 0.44
August 0.00 0.00 0.39
September 0.00 0.00 0.25
October 0.00 0.00 0.11
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.09
May 0.00 0.00 0.15
June 0.00 0.00 0.32
July 0.00 0.00 0.41
August 0.00 0.00 0.36
September 0.00 0.00 0.22
October 0.00 0.00 0.08
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.33
August 0.00 0.00 0.28
September 0.00 0.00 0.16
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.08
May 0.00 0.00 0.15
June 0.00 0.00 0.33
July 0.00 0.00 0.44
August 0.00 0.00 0.38
September 0.00 0.00 0.22
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1718.68 1279.60
February 0.00 0.00 1735.31 1166.96
March 0.00 0.00 1688.37 1257.04
April 0.00 0.00 1595.34 1149.46
May 0.00 0.00 1465.06 1090.78
June 0.00 0.00 1349.20 972.11
July 0.00 0.00 1270.62 946.01
August 0.00 0.00 1249.69 930.43
September 0.00 0.00 1298.82 935.81
October 0.00 0.00 1396.40 1039.66
November 0.00 0.00 1522.31 1096.84
December 0.00 0.00 1641.51 1222.15
         
Annual Sum or Average 0.00 0.00 1492.87 13086.85
Minimum of Months 0.00 0.00 1249.69 930.43
Maximum of Months 0.00 0.00 1735.31 1279.60