Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:36
Tabular Output Report in Format: HTML
Building: MF+CZ4CWH+USA_OR_Salem-McNary.Field.726940+elecres+slab+IECC_2009
Environment: ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2019-02-14 08:36:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 819387.83 | 26.25 | 37.92 |
Net Site Energy | 819387.83 | 26.25 | 37.92 |
Total Source Energy | 2595001.25 | 83.14 | 120.08 |
Net Source Energy | 2595001.25 | 83.14 | 120.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 31210.78 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 224614.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27891.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19760.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185467.40 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 819387.83 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 224614.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27891.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19760.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 185467.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.18 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 37.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
Other | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 26.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 819387.827 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 819387.827 | 100.00 |
Total On-Site and Utility Electric Sources | 819387.827 | 100.00 |
Total Electricity End Uses | 819387.827 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 73.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 136.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:36 |
RunPeriod | ANNUAL |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [ft] | 196.86 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 31210.78 | 267087.66 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.5202 | 866.97 | 2.0143 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 2.9092 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 23-DEC-07:45 | - | - | - | - | 01-JAN-08:15 |
Heating | 155.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 34.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 130.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 336.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 155.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 6.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 0.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 4.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 130.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 711354.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88333.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62583.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 587375.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2595001.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 120.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 120.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 21.92 | 0.00 | 21.92 | Wetbulb [F] | 413.41 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 91.94 | 27.72 | 66.92 | Wetbulb [F] | 846.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14469.34 | 11556.01 | 2913.33 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6737.55 | 5174.93 | 1562.62 | 0.77 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8693.69 | 6787.65 | 1906.04 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11341.20 | 9057.71 | 2283.49 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4942.93 | 3900.37 | 1042.56 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6910.85 | 5519.38 | 1391.46 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12006.60 | 9589.13 | 2417.47 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6306.07 | 4825.10 | 1480.97 | 0.77 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8385.91 | 6540.97 | 1844.94 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10982.13 | 8770.93 | 2211.19 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4854.89 | 3870.26 | 984.63 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6683.55 | 5337.85 | 1345.70 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13260.82 | 10590.82 | 2670.00 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6980.16 | 5573.94 | 1406.22 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9099.30 | 7123.64 | 1975.67 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12876.18 | 10283.63 | 2592.55 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6661.40 | 5320.16 | 1341.24 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7967.46 | 6276.93 | 1690.53 | 0.79 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.25 | 11.08 | 11.74 | 11.37 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.22 | 11.00 | 11.66 | 11.25 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.21 | 10.95 | 11.60 | 11.17 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.25 | 11.10 | 11.76 | 11.40 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.23 | 11.01 | 11.66 | 11.26 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.20 | 10.90 | 11.55 | 11.09 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.08 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.22 | 10.99 | 11.64 | 11.23 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.21 | 10.96 | 11.61 | 11.18 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 9399.32 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 9397.73 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 11326.87 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 11327.55 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 9398.55 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 11324.65 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 9795.25 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 7859.60 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 9798.19 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 9798.49 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 7859.96 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 9795.73 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 12737.87 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 10798.40 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 12739.91 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 12740.09 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 10798.59 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 12738.07 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 542.76 | 271.81 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 231.71 | 116.04 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 310.23 | 155.36 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 425.42 | 213.05 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 180.59 | 90.44 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 259.23 | 129.82 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 450.38 | 225.55 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 214.99 | 107.67 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 298.60 | 149.54 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 411.95 | 206.30 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 181.38 | 90.84 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 250.71 | 125.55 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 497.43 | 249.11 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 261.75 | 131.08 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 326.68 | 163.60 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 483.00 | 241.88 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 249.88 | 125.14 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 290.06 | 145.26 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12661.52 | 12661.52 | 10.55 | 542.758 | 542.758 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00820 | 86.67 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5405.20 | 5405.20 | 4.50 | 231.709 | 231.709 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 74.98 | 74.98 | 0.00829 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7237.01 | 7237.01 | 6.03 | 310.232 | 310.232 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 74.98 | 74.98 | 0.00823 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9924.23 | 9924.23 | 8.27 | 425.419 | 425.419 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00826 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4212.73 | 4212.73 | 3.51 | 180.585 | 180.585 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00852 | 83.21 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6047.45 | 6047.45 | 5.04 | 259.232 | 259.232 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 74.98 | 74.98 | 0.00831 | 80.23 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10506.50 | 10506.50 | 8.75 | 450.379 | 450.379 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00824 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5015.18 | 5015.18 | 4.18 | 214.990 | 214.990 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 74.98 | 74.98 | 0.00829 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6965.63 | 6965.63 | 5.80 | 298.598 | 298.598 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 74.98 | 74.98 | 0.00822 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9610.02 | 9610.02 | 8.00 | 411.950 | 411.950 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00827 | 85.29 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4231.39 | 4231.39 | 3.52 | 181.385 | 181.385 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00857 | 81.13 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5848.55 | 5848.55 | 4.87 | 250.706 | 250.706 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 74.98 | 74.98 | 0.00832 | 80.23 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6766.54 | 6766.54 | 5.64 | 290.060 | 290.060 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 74.98 | 74.98 | 0.00826 | 89.17 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7620.52 | 7620.52 | 6.35 | 326.675 | 326.675 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 74.98 | 74.98 | 0.00822 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11603.99 | 11603.99 | 9.67 | 497.425 | 497.425 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00823 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5829.13 | 5829.13 | 4.86 | 249.875 | 249.875 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00842 | 83.21 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6106.17 | 6106.17 | 5.09 | 261.751 | 261.751 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00839 | 84.25 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11267.41 | 11267.41 | 9.39 | 482.997 | 482.997 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00825 | 85.29 | 0.00850 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7080.80 | 7080.80 | 5.90 | 129.767 | 129.767 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00568 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7079.19 | 7079.19 | 5.90 | 129.737 | 129.737 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00578 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9036.91 | 9036.91 | 7.53 | 165.612 | 165.612 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00599 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9037.59 | 9037.59 | 7.53 | 165.624 | 165.624 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00599 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7080.02 | 7080.02 | 5.90 | 129.752 | 129.752 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00578 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9034.65 | 9034.65 | 7.53 | 165.570 | 165.570 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00599 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7482.45 | 7482.45 | 6.23 | 137.135 | 137.135 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5518.14 | 5518.14 | 4.60 | 101.136 | 101.136 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00603 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7485.44 | 7485.44 | 6.23 | 137.190 | 137.190 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7485.74 | 7485.74 | 6.24 | 137.195 | 137.195 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5518.50 | 5518.50 | 4.60 | 101.143 | 101.143 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00603 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7482.95 | 7482.95 | 6.23 | 137.144 | 137.144 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 10468.98 | 10468.98 | 8.72 | 191.855 | 191.855 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10470.84 | 10470.84 | 8.72 | 191.889 | 191.889 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10468.77 | 10468.77 | 8.72 | 191.851 | 191.851 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8500.77 | 8500.77 | 7.08 | 155.789 | 155.789 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8500.58 | 8500.58 | 7.08 | 155.786 | 155.786 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10471.02 | 10471.02 | 8.72 | 191.893 | 191.893 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 | 542.76 | 129.77 | 129.77 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 | 231.71 | 129.74 | 129.74 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 | 310.23 | 165.61 | 165.61 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 | 425.42 | 165.62 | 165.62 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 | 180.59 | 129.75 | 129.75 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 | 259.23 | 165.57 | 165.57 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 | 450.38 | 137.13 | 137.13 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 | 214.99 | 101.14 | 101.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 | 298.60 | 137.19 | 137.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 | 411.95 | 137.20 | 137.20 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 | 181.38 | 101.14 | 101.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 | 250.71 | 137.14 | 137.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.43 | 497.43 | 191.85 | 191.85 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.75 | 261.75 | 155.79 | 155.79 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.68 | 326.68 | 191.89 | 191.89 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.00 | 483.00 | 191.89 | 191.89 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.88 | 249.88 | 155.79 | 155.79 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.06 | 290.06 | 191.86 | 191.86 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1193.50 | 5857.75 | 33.75 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 814.25 | 6365.50 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1295.00 | 6276.75 | 30.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1074.00 | 6785.25 | 51.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 529.75 | 6850.75 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1081.00 | 6615.25 | 45.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1374.25 | 6112.75 | 30.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 870.75 | 6018.50 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1356.25 | 6046.75 | 26.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1130.75 | 6559.25 | 47.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 659.50 | 6499.25 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1165.50 | 6373.75 | 40.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1346.75 | 6582.75 | 128.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1439.25 | 6374.25 | 86.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1393.75 | 6521.25 | 85.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 938.75 | 6801.00 | 51.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1090.75 | 6522.50 | 29.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1292.25 | 6767.25 | 123.75 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1906.75 | 7165.25 | 136.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 18.75 | 0.00 | 18.75 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 15.50 | 0.00 | 15.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 7.25 | 0.00 | 7.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 25.75 | 0.00 | 25.75 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 51.75 | 0.00 | 51.75 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 47.50 | 0.00 | 47.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 14.25 | 0.00 | 14.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 11.25 | 0.00 | 11.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 5.00 | 0.00 | 5.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 22.25 | 0.00 | 22.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 45.00 | 0.00 | 45.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 46.75 | 0.00 | 46.75 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 49.50 | 0.00 | 49.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 26.50 | 0.00 | 26.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 20.75 | 0.00 | 20.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 43.50 | 0.00 | 43.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 38.25 | 0.00 | 38.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 24.00 | 0.00 | 24.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 73.00 | 0.00 | 73.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.266 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.233 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.232 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.084 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.084 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.232 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.233 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Surfaces by ClassTotal | Outdoors | |
Wall | 74 | 50 |
Floor | 28 | 3 |
Roof | 21 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1812 |
Defaulted Fields | 436 |
Fields with Defaults | 4528 |
Autosized Fields | 288 |
Autosizable Fields | 396 |
Autocalculated Fields | 89 |
Autocalculatable Fields | 268 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Electricity:Plant | 54318.90 | 0.00 | 01-JAN-00:15 | 38722.15 | 11-FEB-08:45 |
WaterSystems:Electricity | 54318.90 | 0.00 | 01-JAN-00:15 | 38722.15 | 11-FEB-08:45 |
Water Heater:WaterSystems:Electricity | 54318.90 | 0.00 | 01-JAN-00:15 | 38722.15 | 11-FEB-08:45 |
Fans:Electricity | 5787.52 | 0.00 | 19-APR-00:30 | 2938.03 | 16-JUL-16:45 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
ElectricityPurchased:Plant | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
Cogeneration:ElectricityPurchased | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
ElectricityNet:Plant | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
Cogeneration:ElectricityNet | 239978.82 | 6919.48 | 01-JUN-03:15 | 98575.72 | 23-DEC-07:45 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 79740.58 | 0.00 | 19-APR-00:30 | 50742.60 | 21-DEC-04:00 |
General:Fans:Electricity | 5787.52 | 0.00 | 19-APR-00:30 | 2938.03 | 16-JUL-16:45 |
Heating:Electricity | 65784.22 | 0.00 | 25-FEB-16:00 | 48204.59 | 21-DEC-04:00 |
Cooling:Electricity | 8168.85 | 0.00 | 01-JAN-00:15 | 11887.52 | 16-JUL-16:00 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 03-JAN-02:30 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
PlantLoopHeatingDemand:Plant | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
WaterSystems:PlantLoopHeatingDemand | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 855247.44 | 1572.03 | 24-AUG-03:00 | 360403.80 | 23-DEC-08:15 |
EnergyTransfer:Building | 338363.08 | 0.00 | 19-APR-00:30 | 173133.74 | 21-DEC-04:00 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 236189.40 | 0.00 | 25-FEB-16:00 | 173133.74 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 102173.69 | 0.00 | 01-JAN-00:15 | 137342.84 | 24-JUN-18:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 19205.50 | 0.00 | 01-JAN-12:30 | 12724.44 | 23-JUN-17:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6607.25 | 0.00 | 01-JAN-12:30 | 8656.90 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12598.25 | 0.00 | 01-JAN-00:15 | 12724.44 | 23-JUN-17:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14789.81 | 0.00 | 01-JAN-13:45 | 8301.94 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10620.08 | 0.00 | 01-JAN-13:45 | 8301.94 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4169.73 | 0.00 | 01-JAN-00:15 | 5846.93 | 24-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20614.67 | 0.00 | 19-JAN-11:00 | 10627.85 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14525.58 | 0.00 | 19-JAN-11:00 | 10627.85 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6089.09 | 0.00 | 01-JAN-00:15 | 7360.18 | 09-SEP-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21606.65 | 0.00 | 30-JAN-15:30 | 10731.29 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 16237.99 | 0.00 | 30-JAN-15:30 | 10731.29 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5368.65 | 0.00 | 01-JAN-00:15 | 10110.39 | 23-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15186.02 | 0.00 | 25-FEB-16:00 | 8478.75 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12422.58 | 0.00 | 25-FEB-16:00 | 8478.75 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2763.44 | 0.00 | 01-JAN-00:15 | 4503.55 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20771.48 | 0.00 | 25-FEB-15:30 | 10758.39 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16167.18 | 0.00 | 25-FEB-15:30 | 10758.39 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4604.30 | 0.00 | 01-JAN-00:15 | 6140.68 | 24-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17775.73 | 0.00 | 01-JAN-14:30 | 10536.02 | 24-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10306.73 | 0.00 | 01-JAN-14:30 | 8522.19 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7469.01 | 0.00 | 01-JAN-00:15 | 10536.02 | 24-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11317.96 | 0.00 | 01-JAN-12:45 | 6212.89 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6673.09 | 0.00 | 01-JAN-12:45 | 6212.89 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4644.87 | 0.00 | 01-JAN-00:15 | 5410.70 | 24-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16925.56 | 0.00 | 01-JAN-13:30 | 8559.48 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10356.39 | 0.00 | 01-JAN-13:30 | 8559.48 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6569.17 | 0.00 | 01-JAN-00:15 | 7049.61 | 09-SEP-13:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17605.09 | 0.00 | 19-JAN-16:00 | 9815.05 | 24-JUN-19:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11879.11 | 0.00 | 19-JAN-16:00 | 8661.30 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5725.98 | 0.00 | 01-JAN-00:15 | 9815.05 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11317.12 | 0.00 | 25-FEB-15:15 | 6392.90 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8130.81 | 0.00 | 25-FEB-15:15 | 6392.90 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3186.31 | 0.00 | 01-JAN-00:15 | 4403.32 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16839.09 | 0.00 | 25-FEB-15:00 | 8688.54 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11804.12 | 0.00 | 25-FEB-15:00 | 8688.54 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5034.97 | 0.00 | 01-JAN-00:15 | 5981.95 | 24-JUN-19:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 24218.98 | 0.00 | 25-FEB-16:00 | 12250.76 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 18733.09 | 0.00 | 25-FEB-16:00 | 12250.76 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5485.90 | 0.00 | 01-JAN-00:15 | 7219.19 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23602.04 | 0.00 | 19-JAN-12:00 | 12153.87 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 17233.64 | 0.00 | 19-JAN-12:00 | 12153.87 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 6368.39 | 0.00 | 01-JAN-00:15 | 7932.89 | 24-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24703.99 | 0.00 | 19-JAN-12:45 | 12124.26 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 17416.79 | 0.00 | 19-JAN-12:45 | 12124.26 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 7287.20 | 0.00 | 01-JAN-00:15 | 11686.09 | 24-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 18715.48 | 0.00 | 25-FEB-16:00 | 9959.66 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 14880.59 | 0.00 | 25-FEB-16:00 | 9959.66 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3834.89 | 0.00 | 01-JAN-00:15 | 6087.43 | 24-JUN-20:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 17920.57 | 0.00 | 19-JAN-12:15 | 9824.05 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 13292.45 | 0.00 | 19-JAN-12:15 | 9824.05 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4628.12 | 0.00 | 01-JAN-00:15 | 6325.74 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25247.33 | 0.00 | 30-JAN-16:15 | 12228.70 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 18901.92 | 0.00 | 30-JAN-16:15 | 12228.70 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 6345.42 | 0.00 | 01-JAN-00:15 | 11519.03 | 24-JUN-19:45 |
EnergyTransfer:Plant | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
WaterSystems:EnergyTransfer | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 169594.90 | 1566.04 | 11-AUG-02:15 | 41981.67 | 11-FEB-08:30 |
EnergyTransfer:HVAC | 347289.46 | 0.00 | 19-APR-00:30 | 164474.06 | 21-DEC-04:00 |
HeatingCoils:EnergyTransfer | 224614.77 | 0.00 | 25-FEB-16:00 | 164474.06 | 21-DEC-04:00 |
CoolingCoils:EnergyTransfer | 122674.69 | 0.00 | 01-JAN-00:15 | 159576.40 | 18-JUL-19:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 6607.218 | -1049.15 | 0.000 | 0.000 | 3021.986 | 2771.241 | 10464.601 | 8033.454 | 0.000 | 360.030 | 6439.235 | 0.000 | -6202.66 | 0.000 | -18896.94 | -0.09 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 10620.030 | -347.24 | 0.000 | 0.000 | 3075.109 | 2771.241 | 10464.601 | 3414.482 | 0.000 | 339.619 | 0.000 | 0.000 | -2478.50 | 0.000 | -17293.43 | -6743.48 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 14525.495 | -507.08 | 0.000 | 0.000 | 3086.097 | 2771.241 | 10464.601 | 7377.645 | 0.000 | 361.273 | 0.000 | 0.000 | -5935.74 | 0.000 | -18370.39 | -8191.17 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 16237.914 | -447.08 | 0.000 | 0.000 | 3093.159 | 2771.241 | 10464.601 | 5766.407 | 0.000 | 358.813 | 0.000 | 0.000 | -6231.62 | 0.000 | -18239.46 | -8852.48 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 12422.523 | -230.13 | 0.000 | 0.000 | 3088.097 | 2771.241 | 10464.601 | 970.766 | 0.000 | 334.530 | 0.000 | 0.000 | -2584.88 | 0.000 | -17142.09 | -7561.37 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 16167.096 | -383.43 | 0.000 | 0.000 | 3094.013 | 2771.241 | 10464.601 | 5006.949 | 0.000 | 356.235 | 0.000 | 0.000 | -6034.27 | 0.000 | -18261.67 | -8959.92 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 10306.664 | -621.99 | 0.000 | 0.000 | 3063.810 | 2771.241 | 10464.601 | 8073.164 | 0.000 | 259.864 | 0.000 | 0.000 | -6215.65 | 0.000 | -13271.91 | -7982.88 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6673.055 | -386.81 | 0.000 | 0.000 | 3052.050 | 2771.241 | 10464.601 | 3406.573 | 0.000 | 239.048 | 0.000 | 0.000 | -2520.90 | 0.000 | -12198.49 | -7242.37 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 10356.326 | -547.06 | 0.000 | 0.000 | 3068.523 | 2771.241 | 10464.601 | 7357.460 | 0.000 | 260.558 | 0.000 | 0.000 | -6033.55 | 0.000 | -13270.86 | -8405.19 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11879.044 | -476.84 | 0.000 | 0.000 | 3075.920 | 2771.241 | 10464.601 | 5753.872 | 0.000 | 259.530 | 0.000 | 0.000 | -6329.92 | 0.000 | -13169.75 | -8978.64 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8130.764 | -265.35 | 0.000 | 0.000 | 3067.134 | 2771.241 | 10464.601 | 967.775 | 0.000 | 236.932 | 0.000 | 0.000 | -2622.88 | 0.000 | -12083.50 | -7745.78 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11804.049 | -419.30 | 0.000 | 0.000 | 3078.285 | 2771.241 | 10464.601 | 4991.724 | 0.000 | 257.153 | 0.000 | 0.000 | -6124.48 | 0.000 | -13182.79 | -9024.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 18732.996 | -456.85 | 0.000 | 0.000 | 3090.738 | 2771.241 | 10464.601 | 5019.765 | 0.000 | 350.506 | 0.000 | 0.000 | -6079.20 | 0.000 | -18318.29 | -10546.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17233.556 | -530.34 | 0.000 | 0.000 | 3085.428 | 2771.241 | 10464.601 | 7405.797 | 0.000 | 355.486 | 0.000 | 0.000 | -5973.09 | 0.000 | -18394.08 | -10580.59 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17416.712 | -606.85 | 0.000 | 0.000 | 3084.625 | 2771.241 | 10464.601 | 8121.098 | 0.000 | 356.340 | 0.000 | 0.000 | -6131.21 | 0.000 | -18371.85 | -10424.46 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 14880.534 | -319.36 | 0.000 | 0.000 | 3085.127 | 2771.241 | 10464.601 | 976.663 | 0.000 | 333.184 | 0.000 | 0.000 | -2594.00 | 0.000 | -17202.95 | -8879.54 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13292.394 | -385.41 | 0.000 | 0.000 | 3076.923 | 2771.241 | 10464.601 | 3426.684 | 0.000 | 333.284 | 0.000 | 0.000 | -2486.90 | 0.000 | -17294.04 | -8956.12 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 18901.836 | -528.42 | 0.000 | 0.000 | 3090.431 | 2771.241 | 10464.601 | 5768.481 | 0.000 | 356.703 | 0.000 | 0.000 | -6267.29 | 0.000 | -18297.16 | -10443.52 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4154.689 | 38875.958 | 0.000 | 0.000 | 0.000 | -43030.65 | -0.49 |
Total Facility | 0.000 | 0.000 | 236188.205 | -8508.70 | 0.000 | 0.000 | 55377.456 | 49882.340 | 188362.826 | 91838.758 | 0.000 | 9863.778 | 45315.193 | 0.000 | -88846.74 | 0.000 | -336290.30 | -149519.43 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 262.98 | 604.65 | 1664.02 | 7398.34 | 0.00 | 1713.70 | 1092.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 813.96 | 1748.06 | 434.10 | 0.00 | 1703.71 | 721.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 09-SEP-13:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.33 | 116.28 | 1109.73 | 4440.78 | 0.00 | 1769.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -190.6 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 420.86 | 902.05 | 1689.30 | 2453.78 | 0.00 | 929.96 | 3765.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 24-JUN-20:00 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 404.59 | 902.05 | 1689.30 | 44.95 | 0.00 | 671.42 | 797.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.60 | 902.05 | 1689.30 | 814.95 | 0.00 | 956.20 | 1411.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24-JUN-19:04 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 422.74 | 902.05 | 1689.30 | 3760.05 | 0.00 | 896.92 | 2940.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24-JUN-18:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.71 | 813.96 | 1748.06 | 350.68 | 0.00 | 987.35 | 1089.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 09-SEP-13:45 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.07 | 116.28 | 1109.73 | 4247.89 | 0.00 | 1227.01 | 233.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 418.66 | 902.05 | 1689.30 | 2452.01 | 0.00 | 661.42 | 3768.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 406.88 | 902.05 | 1689.30 | 626.61 | 0.00 | 564.67 | 221.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 422.78 | 902.05 | 1689.30 | 818.17 | 0.00 | 681.03 | 1489.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 24-JUN-19:57 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 414.26 | 902.05 | 1689.30 | 81.72 | 0.00 | 766.89 | 3376.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 24-JUN-18:42 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 425.30 | 813.96 | 1748.06 | 849.02 | 0.00 | 1568.25 | 2537.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 24-JUN-19:23 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 421.31 | 902.05 | 1689.30 | 2810.25 | 0.00 | 1116.36 | 4796.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 24-JUN-20:06 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 411.10 | 902.05 | 1651.67 | 18.32 | 0.00 | 571.34 | 2550.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 24-JUN-20:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 418.89 | 902.05 | 1689.30 | 43.51 | 0.00 | 741.39 | 2540.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 419.19 | 902.05 | 1689.30 | 2424.99 | 0.00 | 915.52 | 5197.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUN-18:08 | 0.00 | 0.00 | 0.00 | -11.4 | 0.00 | 0.00 | 7473.45 | 14651.21 | 31465.06 | 51280.62 | 0.00 | 27052.31 | 19820.57 | 0.00 | 0.00 | 0.00 | -14360.7 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8657.17 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2504.9 | 0.00 | -7142.0 | -446.0 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8302.23 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.6 | 0.00 | -6680.0 | -2040.4 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 10628.22 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2501.6 | 0.00 | -7142.0 | -2420.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 10731.64 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2510.0 | 0.00 | -7142.0 | -2515.4 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8479.05 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1024.1 | 0.00 | -6680.0 | -2210.7 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 10758.77 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2506.9 | 0.00 | -7142.0 | -2545.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8522.38 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2526.5 | 0.00 | -4971.1 | -2460.5 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6213.03 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.4 | 0.00 | -4508.7 | -2113.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8559.69 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2523.8 | 0.00 | -4971.1 | -2500.6 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8661.50 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2529.8 | 0.00 | -4971.1 | -2596.4 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6393.05 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1031.1 | 0.00 | -4508.7 | -2289.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8688.76 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2527.4 | 0.00 | -4971.1 | -2626.0 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12251.18 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2511.0 | 0.00 | -7152.2 | -4023.7 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12154.28 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2507.8 | 0.00 | -7152.2 | -3930.1 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12124.64 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2509.8 | 0.00 | -7152.2 | -3898.4 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9960.00 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1022.1 | 0.00 | -6689.4 | -3684.3 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9824.37 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1018.0 | 0.00 | -6689.4 | -3552.7 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12229.08 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2512.8 | 0.00 | -7152.2 | -3999.8 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-04:00 | 0.00 | 0.00 | 173139.02 | 0.00 | 0.00 | 0.00 | 9473.52 | 1116.28 | 15253.70 | 0.00 | 0.00 | 648.67 | 0.00 | 0.00 | -36311.6 | 0.00 | -112817.3 | -50502.3 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 542.758 | 2.00 | 2.00 | 1.00 | 44.9950 | 542.758 | 0.083 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 231.709 | 2.00 | 2.00 | 1.00 | 44.9950 | 231.709 | 0.194 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 310.232 | 2.00 | 2.00 | 1.00 | 44.9950 | 310.232 | 0.145 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.419 | 2.00 | 2.00 | 1.00 | 44.9950 | 425.419 | 0.106 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 180.585 | 2.00 | 2.00 | 1.00 | 44.9950 | 180.585 | 0.249 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 259.232 | 2.00 | 2.00 | 1.00 | 44.9950 | 259.232 | 0.174 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.379 | 2.00 | 2.00 | 1.00 | 44.9950 | 450.379 | 0.100 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 214.990 | 2.00 | 2.00 | 1.00 | 44.9950 | 214.990 | 0.209 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.598 | 2.00 | 2.00 | 1.00 | 44.9950 | 298.598 | 0.151 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 411.950 | 2.00 | 2.00 | 1.00 | 44.9950 | 411.950 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.385 | 2.00 | 2.00 | 1.00 | 44.9950 | 181.385 | 0.248 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 250.706 | 2.00 | 2.00 | 1.00 | 44.9950 | 250.706 | 0.179 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.425 | 2.00 | 2.00 | 1.00 | 44.9950 | 497.425 | 0.090 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.751 | 2.00 | 2.00 | 1.00 | 44.9950 | 261.751 | 0.172 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.675 | 2.00 | 2.00 | 1.00 | 44.9950 | 326.675 | 0.138 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 482.997 | 2.00 | 2.00 | 1.00 | 44.9950 | 482.997 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.875 | 2.00 | 2.00 | 1.00 | 44.9950 | 249.875 | 0.180 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.060 | 2.00 | 2.00 | 1.00 | 44.9950 | 290.060 | 0.155 | 1.000 | 44.9950 | 0.16 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 129.767 | 2.00 | 2.00 | 1.00 | 44.9950 | 129.767 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 129.737 | 2.00 | 2.00 | 1.00 | 44.9950 | 129.737 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 165.612 | 2.00 | 2.00 | 1.00 | 44.9950 | 165.612 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 165.624 | 2.00 | 2.00 | 1.00 | 44.9950 | 165.624 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.752 | 2.00 | 2.00 | 1.00 | 44.9950 | 129.752 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 165.570 | 2.00 | 2.00 | 1.00 | 44.9950 | 165.570 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.135 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.135 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 101.136 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.136 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.190 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.190 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.195 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.195 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.143 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.143 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.144 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.144 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.851 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.851 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.786 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.786 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.889 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.889 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.893 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.893 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.789 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.789 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.855 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.855 | 1.000 | 1.000 | 44.9950 | 0.23 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 542.758 | 542.7582 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 231.709 | 231.7091 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 310.232 | 310.2319 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.419 | 425.4191 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 180.585 | 180.5850 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 259.232 | 259.2323 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.379 | 450.3785 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 214.990 | 214.9903 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.598 | 298.5975 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 411.950 | 411.9498 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.385 | 181.3849 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 250.706 | 250.7061 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.060 | 290.0596 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.675 | 326.6751 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.425 | 497.4255 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.875 | 249.8752 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.751 | 261.7506 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 482.997 | 482.9974 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 | 542.758 | 542.76 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 | 231.709 | 231.71 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 | 310.232 | 310.23 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 | 425.419 | 425.42 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 | 180.585 | 180.59 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 | 259.232 | 259.23 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 | 450.379 | 450.38 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 | 214.990 | 214.99 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 | 298.598 | 298.60 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 | 411.950 | 411.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 | 181.385 | 181.38 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 | 250.706 | 250.71 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.43 | 497.425 | 497.43 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.75 | 261.751 | 261.75 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.68 | 326.675 | 326.68 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.00 | 482.997 | 483.00 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.88 | 249.875 | 249.88 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.06 | 290.060 | 290.06 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 129.767 | 129.767 | 129.767 | 44.9950 | 0.347 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 129.737 | 129.737 | 129.737 | 44.9950 | 0.347 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 165.612 | 165.612 | 165.612 | 44.9950 | 0.272 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 165.624 | 165.624 | 165.624 | 44.9950 | 0.272 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.752 | 129.752 | 129.752 | 44.9950 | 0.347 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 165.570 | 165.570 | 165.570 | 44.9950 | 0.272 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.135 | 137.135 | 137.135 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 101.136 | 101.136 | 101.136 | 44.9950 | 0.445 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.190 | 137.190 | 137.190 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.195 | 137.195 | 137.195 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.143 | 101.143 | 101.143 | 44.9950 | 0.445 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.144 | 137.144 | 137.144 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.855 | 191.855 | 191.855 | 44.9950 | 0.235 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.889 | 191.889 | 191.889 | 44.9950 | 0.234 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.851 | 191.851 | 191.851 | 44.9950 | 0.235 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.789 | 155.789 | 155.789 | 44.9950 | 0.289 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.786 | 155.786 | 155.786 | 44.9950 | 0.289 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.893 | 191.893 | 191.893 | 44.9950 | 0.234 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 129.77 | 129.767 | 129.77 | 129.77 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 129.74 | 129.737 | 129.74 | 129.74 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 165.61 | 165.612 | 165.61 | 165.61 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 165.62 | 165.624 | 165.62 | 165.62 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.75 | 129.752 | 129.75 | 129.75 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 165.57 | 165.570 | 165.57 | 165.57 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.13 | 137.135 | 137.13 | 137.13 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 101.14 | 101.136 | 101.14 | 101.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.19 | 137.190 | 137.19 | 137.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.20 | 137.195 | 137.20 | 137.20 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.14 | 101.143 | 101.14 | 101.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.14 | 137.144 | 137.14 | 137.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.85 | 191.851 | 191.85 | 191.85 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.79 | 155.786 | 155.79 | 155.79 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.89 | 191.889 | 191.89 | 191.89 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.89 | 191.893 | 191.89 | 191.89 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.79 | 155.789 | 155.79 | 155.79 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.86 | 191.855 | 191.86 | 191.86 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Total gross floor area [ft2] | 31210.78 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 31210.78 | 21609.96 | 9600.82 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 73.00 |
Number of hours not met | 73.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 2044.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 78.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 65784.22 | 45553.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Cooling | 8168.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 5787.52 | 2399.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 54318.90 | 38296.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 10202.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 239978.82 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 819387.83 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 819387.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.47 |
Space Heating | 2.11 |
Space Cooling | 0.26 |
Fans-Interior | 0.19 |
Service Water Heating | 1.74 |
Receptacle Equipment | 2.83 |
Miscellaneous | 0.10 |
Subtotal | 7.69 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.09 |
Space Heating | 27.41 |
Space Cooling | 3.40 |
Fans-Interior | 2.41 |
Service Water Heating | 22.63 |
Receptacle Equipment | 36.80 |
Miscellaneous | 1.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 290.06 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 326.68 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 497.43 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 249.88 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 261.75 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 483.00 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.43 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.75 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.68 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.88 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.06 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 | 1.21 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 | 0.561462 | 0.768073 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 | 0.724474 | 0.780756 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 | 0.945100 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 | 0.411910 | 0.789081 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 | 0.575904 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 | 1.00 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 | 0.525506 | 0.765151 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 | 0.698826 | 0.779995 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 | 0.915177 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 | 0.404574 | 0.797188 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 | 0.556962 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 497.43 | 1.11 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 261.75 | 0.581680 | 0.798541 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 326.68 | 0.758275 | 0.782877 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 483.00 | 1.07 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 249.88 | 0.555116 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 290.06 | 0.663955 | 0.787821 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 | 542.76 | 542.76 | 9399.32 | 1.21 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 | 231.71 | 231.71 | 9397.73 | 0.561462 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 | 310.23 | 310.23 | 11326.87 | 0.724474 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 | 425.42 | 425.42 | 11327.55 | 0.945100 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 | 180.59 | 180.59 | 9398.55 | 0.411910 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 | 259.23 | 259.23 | 11324.65 | 0.575904 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 | 450.38 | 450.38 | 9795.25 | 1.00 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 | 214.99 | 214.99 | 7859.60 | 0.525506 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 | 298.60 | 298.60 | 9798.19 | 0.698826 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 | 411.95 | 411.95 | 9798.49 | 0.915177 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 | 181.38 | 181.38 | 7859.96 | 0.404574 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 | 250.71 | 250.71 | 9795.73 | 0.556962 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 497.43 | 497.43 | 497.43 | 12737.87 | 1.11 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 261.75 | 261.75 | 261.75 | 10798.40 | 0.581680 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 326.68 | 326.68 | 326.68 | 12739.91 | 0.758275 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 483.00 | 483.00 | 483.00 | 12740.09 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 249.88 | 249.88 | 249.88 | 10798.59 | 0.555116 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 290.06 | 290.06 | 290.06 | 12738.07 | 0.663955 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 542.76 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 231.71 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 310.23 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 425.42 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 180.59 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 259.23 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 450.38 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 214.99 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 298.60 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 411.95 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 181.38 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 250.71 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 497.43 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 261.75 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 326.68 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 483.00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 249.88 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 290.06 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 9399.32 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 9397.73 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 11326.87 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 11327.55 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 9398.55 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 11324.65 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 9795.25 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 7859.60 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 9798.19 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 9798.49 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 7859.96 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 9795.73 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 12737.87 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 10798.40 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 12739.91 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 12740.09 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 10798.59 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 12738.07 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:36:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 27.083 | 1.026 | 632.125 | 38.087 | 39.113 |
February | 55.220 | 3.417 | 531.540 | 38.310 | 41.727 |
March | 165.802 | 8.280 | 350.386 | 14.769 | 23.049 |
April | 242.060 | 13.995 | 254.075 | 9.020 | 23.015 |
May | 393.835 | 26.223 | 95.186 | 2.012 | 28.234 |
June | 596.834 | 46.556 | 0.375 | 0.003 | 46.559 |
July | 691.410 | 68.282 | 0.000 | 0.000 | 68.282 |
August | 702.256 | 63.554 | 0.000 | 0.000 | 63.554 |
September | 555.054 | 46.442 | 7.208 | 0.068 | 46.510 |
October | 269.511 | 15.727 | 210.522 | 6.826 | 22.553 |
November | 44.515 | 1.474 | 454.442 | 17.299 | 18.773 |
December | 24.042 | 0.622 | 645.079 | 47.393 | 48.016 |
Annual Sum or Average | 3767.622 | 295.599 | 3180.938 | 173.786 | 469.385 |
Minimum of Months | 24.042 | 0.622 | 0.000 | 0.000 | 18.773 |
Maximum of Months | 702.256 | 68.282 | 645.079 | 47.393 | 68.282 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 7.271 | 0.093 | 699.777 | 24.227 | 24.320 |
February | 29.562 | 0.845 | 607.075 | 23.304 | 24.149 |
March | 56.819 | 1.522 | 545.396 | 13.088 | 14.610 |
April | 74.026 | 2.461 | 460.262 | 9.498 | 11.959 |
May | 154.020 | 5.507 | 309.792 | 4.337 | 9.844 |
June | 326.514 | 13.520 | 61.887 | 0.402 | 13.922 |
July | 491.474 | 25.167 | 18.125 | 0.090 | 25.257 |
August | 476.196 | 23.648 | 4.250 | 0.011 | 23.659 |
September | 344.693 | 17.137 | 91.129 | 0.658 | 17.795 |
October | 138.153 | 4.173 | 398.750 | 7.331 | 11.504 |
November | 6.775 | 0.073 | 639.521 | 15.075 | 15.148 |
December | 6.250 | 0.053 | 704.604 | 27.720 | 27.773 |
Annual Sum or Average | 2111.754 | 94.200 | 4540.568 | 125.742 | 219.942 |
Minimum of Months | 6.250 | 0.053 | 4.250 | 0.011 | 9.844 |
Maximum of Months | 491.474 | 25.167 | 704.604 | 27.720 | 27.773 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 5.208 | 0.061 | 710.725 | 35.919 | 35.980 |
February | 27.592 | 1.014 | 611.563 | 33.723 | 34.737 |
March | 67.942 | 2.344 | 567.179 | 19.358 | 21.701 |
April | 100.547 | 3.966 | 461.354 | 13.837 | 17.803 |
May | 195.798 | 9.024 | 301.552 | 6.734 | 15.758 |
June | 362.443 | 21.841 | 109.367 | 1.256 | 23.097 |
July | 517.238 | 38.529 | 41.583 | 0.437 | 38.965 |
August | 496.045 | 34.126 | 34.250 | 0.242 | 34.369 |
September | 352.754 | 23.030 | 137.000 | 1.875 | 24.905 |
October | 129.286 | 5.281 | 445.525 | 12.522 | 17.803 |
November | 3.000 | 0.056 | 677.358 | 23.500 | 23.557 |
December | 2.875 | 0.038 | 721.125 | 40.791 | 40.829 |
Annual Sum or Average | 2260.727 | 139.308 | 4818.581 | 190.195 | 329.503 |
Minimum of Months | 2.875 | 0.038 | 34.250 | 0.242 | 15.758 |
Maximum of Months | 517.238 | 38.529 | 721.125 | 40.791 | 40.829 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 742.125 | 53.956 | 53.956 |
February | 6.542 | 0.112 | 635.125 | 49.107 | 49.219 |
March | 21.333 | 0.559 | 623.387 | 30.360 | 30.919 |
April | 74.821 | 3.860 | 502.362 | 20.976 | 24.836 |
May | 168.697 | 10.592 | 352.616 | 10.124 | 20.715 |
June | 319.921 | 23.615 | 128.492 | 1.798 | 25.413 |
July | 461.415 | 39.255 | 48.250 | 0.592 | 39.848 |
August | 421.267 | 31.576 | 43.562 | 0.400 | 31.976 |
September | 265.907 | 17.371 | 191.375 | 3.438 | 20.809 |
October | 55.542 | 1.961 | 544.687 | 20.294 | 22.255 |
November | 0.000 | 0.000 | 705.758 | 35.584 | 35.584 |
December | 0.000 | 0.000 | 742.438 | 60.154 | 60.154 |
Annual Sum or Average | 1795.446 | 128.901 | 5260.178 | 286.783 | 415.684 |
Minimum of Months | 0.000 | 0.000 | 43.562 | 0.400 | 20.715 |
Maximum of Months | 461.415 | 39.255 | 742.438 | 60.154 | 60.154 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 22.060 | 22.060 |
February | 0.000 | 0.000 | 654.042 | 20.506 | 20.506 |
March | 0.000 | 0.000 | 662.944 | 12.703 | 12.703 |
April | 43.887 | 1.177 | 530.350 | 8.923 | 10.100 |
May | 118.896 | 3.689 | 349.144 | 3.821 | 7.510 |
June | 309.343 | 11.937 | 68.408 | 0.346 | 12.283 |
July | 486.740 | 22.325 | 20.000 | 0.080 | 22.406 |
August | 453.605 | 18.046 | 6.375 | 0.017 | 18.063 |
September | 269.065 | 8.310 | 127.793 | 0.739 | 9.049 |
October | 33.296 | 0.494 | 553.038 | 7.756 | 8.250 |
November | 0.000 | 0.000 | 702.125 | 14.124 | 14.124 |
December | 0.000 | 0.000 | 739.000 | 24.577 | 24.577 |
Annual Sum or Average | 1714.833 | 65.978 | 5157.218 | 115.653 | 181.631 |
Minimum of Months | 0.000 | 0.000 | 6.375 | 0.017 | 7.510 |
Maximum of Months | 486.740 | 22.325 | 744.000 | 24.577 | 24.577 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 33.729 | 33.729 |
February | 0.000 | 0.000 | 649.692 | 30.862 | 30.862 |
March | 9.438 | 0.080 | 658.646 | 18.657 | 18.737 |
April | 60.834 | 2.216 | 506.096 | 13.003 | 15.219 |
May | 174.335 | 6.981 | 324.879 | 5.936 | 12.917 |
June | 353.415 | 20.446 | 108.971 | 1.046 | 21.492 |
July | 518.205 | 36.024 | 41.167 | 0.360 | 36.385 |
August | 490.689 | 29.010 | 36.958 | 0.224 | 29.234 |
September | 318.668 | 14.150 | 149.042 | 1.773 | 15.923 |
October | 56.064 | 1.180 | 560.587 | 12.731 | 13.911 |
November | 0.000 | 0.000 | 711.958 | 22.328 | 22.328 |
December | 0.000 | 0.000 | 744.000 | 37.585 | 37.585 |
Annual Sum or Average | 1981.649 | 110.087 | 5235.996 | 178.233 | 288.320 |
Minimum of Months | 0.000 | 0.000 | 36.958 | 0.224 | 12.917 |
Maximum of Months | 518.205 | 36.024 | 744.000 | 37.585 | 37.585 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 12.375 | 0.310 | 691.929 | 44.108 | 44.418 |
February | 37.708 | 1.850 | 588.971 | 39.896 | 41.746 |
March | 88.750 | 3.984 | 510.917 | 22.551 | 26.535 |
April | 135.122 | 7.271 | 379.979 | 14.780 | 22.052 |
May | 232.494 | 14.936 | 251.508 | 6.161 | 21.097 |
June | 384.842 | 27.939 | 50.492 | 0.554 | 28.493 |
July | 514.929 | 44.427 | 15.250 | 0.118 | 44.545 |
August | 484.453 | 39.903 | 4.625 | 0.024 | 39.926 |
September | 357.478 | 28.231 | 105.183 | 1.452 | 29.682 |
October | 159.733 | 7.835 | 387.176 | 13.558 | 21.393 |
November | 15.517 | 0.312 | 628.565 | 27.094 | 27.406 |
December | 7.000 | 0.146 | 701.033 | 49.586 | 49.732 |
Annual Sum or Average | 2430.401 | 177.144 | 4315.629 | 219.881 | 397.025 |
Minimum of Months | 7.000 | 0.146 | 4.625 | 0.024 | 21.097 |
Maximum of Months | 514.929 | 44.427 | 701.033 | 49.586 | 49.732 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 12.917 | 0.154 | 670.500 | 17.999 | 18.154 |
February | 37.396 | 1.090 | 587.188 | 16.671 | 17.761 |
March | 80.158 | 2.081 | 482.083 | 8.966 | 11.047 |
April | 107.683 | 3.116 | 362.437 | 5.971 | 9.086 |
May | 193.554 | 6.632 | 208.478 | 2.050 | 8.682 |
June | 393.989 | 15.150 | 15.104 | 0.043 | 15.193 |
July | 564.096 | 26.673 | 0.250 | 0.000 | 26.674 |
August | 539.694 | 25.223 | 0.000 | 0.000 | 25.223 |
September | 391.816 | 18.189 | 39.079 | 0.199 | 18.388 |
October | 171.296 | 4.933 | 315.125 | 4.690 | 9.623 |
November | 14.663 | 0.144 | 574.475 | 10.301 | 10.444 |
December | 8.750 | 0.138 | 684.550 | 20.379 | 20.517 |
Annual Sum or Average | 2516.011 | 103.523 | 3939.269 | 87.269 | 190.792 |
Minimum of Months | 8.750 | 0.138 | 0.000 | 0.000 | 8.682 |
Maximum of Months | 564.096 | 26.673 | 684.550 | 20.379 | 26.674 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 6.792 | 0.095 | 696.833 | 30.006 | 30.101 |
February | 33.050 | 1.226 | 602.017 | 27.296 | 28.522 |
March | 85.108 | 2.972 | 512.440 | 15.116 | 18.087 |
April | 125.569 | 4.791 | 384.708 | 10.062 | 14.853 |
May | 230.929 | 10.473 | 232.979 | 4.119 | 14.592 |
June | 411.682 | 23.638 | 49.754 | 0.420 | 24.059 |
July | 557.926 | 40.231 | 17.312 | 0.121 | 40.351 |
August | 533.767 | 35.861 | 5.500 | 0.027 | 35.889 |
September | 388.368 | 24.135 | 89.125 | 0.941 | 25.076 |
October | 146.276 | 5.908 | 393.417 | 9.516 | 15.424 |
November | 4.375 | 0.068 | 648.150 | 18.678 | 18.745 |
December | 6.500 | 0.077 | 705.288 | 33.825 | 33.903 |
Annual Sum or Average | 2530.341 | 149.476 | 4337.523 | 150.126 | 299.602 |
Minimum of Months | 4.375 | 0.068 | 5.500 | 0.027 | 14.592 |
Maximum of Months | 557.926 | 40.231 | 705.288 | 33.825 | 40.351 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.188 | 46.426 | 46.426 |
February | 8.508 | 0.113 | 624.563 | 40.678 | 40.791 |
March | 33.067 | 0.737 | 584.000 | 24.541 | 25.278 |
April | 92.921 | 4.504 | 444.925 | 15.724 | 20.228 |
May | 202.903 | 12.012 | 280.062 | 6.410 | 18.422 |
June | 368.779 | 25.364 | 59.494 | 0.627 | 25.991 |
July | 505.888 | 40.870 | 19.375 | 0.151 | 41.021 |
August | 462.001 | 33.221 | 8.250 | 0.049 | 33.270 |
September | 298.677 | 18.261 | 141.933 | 1.957 | 20.218 |
October | 68.896 | 2.220 | 493.583 | 16.022 | 18.242 |
November | 0.000 | 0.000 | 692.533 | 29.354 | 29.354 |
December | 0.000 | 0.000 | 733.000 | 51.241 | 51.241 |
Annual Sum or Average | 2041.639 | 137.303 | 4822.906 | 233.181 | 370.484 |
Minimum of Months | 0.000 | 0.000 | 8.250 | 0.049 | 18.242 |
Maximum of Months | 505.888 | 40.870 | 741.188 | 51.241 | 51.241 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 18.550 | 18.550 |
February | 0.000 | 0.000 | 638.708 | 16.467 | 16.467 |
March | 7.400 | 0.042 | 605.725 | 9.740 | 9.782 |
April | 60.509 | 1.640 | 456.521 | 6.238 | 7.878 |
May | 160.153 | 4.903 | 235.042 | 1.934 | 6.837 |
June | 378.464 | 14.228 | 13.483 | 0.033 | 14.262 |
July | 560.360 | 25.102 | 0.000 | 0.000 | 25.102 |
August | 524.924 | 20.674 | 0.000 | 0.000 | 20.674 |
September | 318.908 | 9.761 | 51.546 | 0.251 | 10.012 |
October | 52.404 | 0.828 | 474.412 | 5.642 | 6.470 |
November | 0.000 | 0.000 | 669.875 | 11.070 | 11.070 |
December | 0.000 | 0.000 | 728.250 | 20.413 | 20.413 |
Annual Sum or Average | 2063.123 | 77.177 | 4617.563 | 90.338 | 167.515 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.470 |
Maximum of Months | 560.360 | 25.102 | 744.000 | 20.413 | 25.102 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 29.080 | 29.080 |
February | 0.000 | 0.000 | 637.750 | 25.615 | 25.615 |
March | 21.292 | 0.228 | 611.801 | 14.838 | 15.066 |
April | 79.068 | 2.741 | 451.500 | 9.654 | 12.395 |
May | 210.516 | 8.423 | 246.613 | 3.657 | 12.080 |
June | 404.702 | 22.445 | 46.958 | 0.348 | 22.793 |
July | 558.774 | 38.143 | 16.812 | 0.097 | 38.241 |
August | 529.533 | 31.138 | 6.000 | 0.028 | 31.165 |
September | 353.288 | 15.320 | 99.125 | 0.928 | 16.248 |
October | 72.631 | 1.525 | 515.030 | 10.062 | 11.587 |
November | 0.000 | 0.000 | 703.000 | 18.475 | 18.475 |
December | 0.000 | 0.000 | 742.250 | 32.071 | 32.071 |
Annual Sum or Average | 2229.804 | 119.963 | 4820.840 | 144.852 | 264.816 |
Minimum of Months | 0.000 | 0.000 | 6.000 | 0.028 | 11.587 |
Maximum of Months | 558.774 | 38.143 | 744.000 | 32.071 | 38.241 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.625 | 0.030 | 719.921 | 59.869 | 59.899 |
February | 24.333 | 1.122 | 611.663 | 54.784 | 55.905 |
March | 59.142 | 2.826 | 571.114 | 32.986 | 35.811 |
April | 99.954 | 6.252 | 471.308 | 23.257 | 29.510 |
May | 189.813 | 14.325 | 343.788 | 11.562 | 25.887 |
June | 331.405 | 28.127 | 143.250 | 2.348 | 30.475 |
July | 460.762 | 46.564 | 59.208 | 0.796 | 47.360 |
August | 429.996 | 40.446 | 54.281 | 0.520 | 40.967 |
September | 308.748 | 26.998 | 188.446 | 4.203 | 31.200 |
October | 121.433 | 5.914 | 481.810 | 21.881 | 27.796 |
November | 3.417 | 0.057 | 681.063 | 39.699 | 39.757 |
December | 1.500 | 0.015 | 728.000 | 67.175 | 67.190 |
Annual Sum or Average | 2033.129 | 172.678 | 5053.851 | 319.079 | 491.757 |
Minimum of Months | 1.500 | 0.015 | 54.281 | 0.520 | 25.887 |
Maximum of Months | 460.762 | 46.564 | 728.000 | 67.175 | 67.190 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 717.408 | 29.586 | 29.586 |
February | 24.375 | 0.531 | 615.875 | 27.601 | 28.132 |
March | 50.200 | 1.527 | 579.792 | 16.188 | 17.715 |
April | 74.925 | 3.020 | 489.667 | 11.687 | 14.707 |
May | 158.375 | 7.329 | 328.792 | 5.335 | 12.664 |
June | 324.845 | 17.016 | 97.208 | 0.692 | 17.708 |
July | 484.088 | 30.691 | 29.790 | 0.179 | 30.869 |
August | 454.544 | 27.814 | 9.281 | 0.035 | 27.849 |
September | 324.276 | 18.508 | 143.606 | 1.308 | 19.816 |
October | 113.358 | 3.659 | 449.060 | 9.792 | 13.451 |
November | 0.375 | 0.001 | 678.750 | 19.048 | 19.049 |
December | 0.000 | 0.000 | 722.875 | 33.382 | 33.382 |
Annual Sum or Average | 2009.362 | 110.095 | 4862.104 | 154.832 | 264.927 |
Minimum of Months | 0.000 | 0.000 | 9.281 | 0.035 | 12.664 |
Maximum of Months | 484.088 | 30.691 | 722.875 | 33.382 | 33.382 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 723.875 | 40.162 | 40.162 |
February | 22.125 | 0.602 | 622.000 | 36.872 | 37.474 |
March | 56.908 | 1.992 | 595.262 | 21.669 | 23.662 |
April | 92.132 | 4.136 | 484.842 | 15.318 | 19.454 |
May | 194.127 | 10.028 | 313.125 | 7.151 | 17.179 |
June | 363.374 | 23.908 | 122.583 | 1.354 | 25.262 |
July | 518.911 | 41.868 | 41.375 | 0.442 | 42.310 |
August | 493.919 | 36.249 | 38.542 | 0.271 | 36.520 |
September | 340.274 | 22.817 | 153.750 | 2.265 | 25.082 |
October | 110.642 | 4.394 | 477.458 | 14.497 | 18.891 |
November | 0.250 | 0.000 | 692.692 | 26.731 | 26.731 |
December | 0.000 | 0.000 | 730.750 | 45.132 | 45.132 |
Annual Sum or Average | 2192.660 | 145.995 | 4996.254 | 211.863 | 357.858 |
Minimum of Months | 0.000 | 0.000 | 38.542 | 0.271 | 17.179 |
Maximum of Months | 518.911 | 41.868 | 730.750 | 45.132 | 45.132 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.333 | 63.448 | 63.448 |
February | 4.542 | 0.040 | 636.938 | 56.835 | 56.875 |
March | 27.575 | 0.864 | 619.358 | 35.334 | 36.198 |
April | 83.617 | 4.930 | 499.025 | 24.241 | 29.171 |
May | 179.198 | 13.134 | 354.583 | 11.606 | 24.740 |
June | 324.340 | 27.363 | 143.502 | 2.282 | 29.646 |
July | 458.671 | 45.297 | 58.042 | 0.757 | 46.053 |
August | 417.857 | 36.968 | 55.521 | 0.531 | 37.499 |
September | 268.008 | 20.226 | 210.378 | 4.570 | 24.797 |
October | 55.812 | 2.293 | 550.075 | 24.605 | 26.898 |
November | 0.000 | 0.000 | 710.533 | 42.401 | 42.401 |
December | 0.000 | 0.000 | 744.000 | 70.189 | 70.189 |
Annual Sum or Average | 1819.620 | 151.115 | 5325.288 | 336.799 | 487.914 |
Minimum of Months | 0.000 | 0.000 | 55.521 | 0.531 | 24.740 |
Maximum of Months | 458.671 | 45.297 | 744.000 | 70.189 | 70.189 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 31.697 | 31.697 |
February | 0.000 | 0.000 | 651.250 | 28.801 | 28.801 |
March | 11.066 | 0.154 | 650.375 | 17.838 | 17.992 |
April | 57.904 | 2.152 | 519.738 | 12.354 | 14.507 |
May | 144.789 | 6.361 | 342.979 | 5.320 | 11.681 |
June | 320.656 | 16.484 | 97.165 | 0.646 | 17.130 |
July | 483.454 | 29.627 | 27.658 | 0.162 | 29.789 |
August | 444.157 | 24.502 | 10.125 | 0.036 | 24.538 |
September | 274.443 | 11.866 | 167.156 | 1.485 | 13.351 |
October | 45.112 | 0.925 | 563.575 | 11.702 | 12.627 |
November | 0.000 | 0.000 | 713.000 | 20.692 | 20.692 |
December | 0.000 | 0.000 | 743.500 | 35.029 | 35.029 |
Annual Sum or Average | 1781.582 | 92.070 | 5230.522 | 165.763 | 257.833 |
Minimum of Months | 0.000 | 0.000 | 10.125 | 0.036 | 11.681 |
Maximum of Months | 483.454 | 29.627 | 744.000 | 35.029 | 35.029 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 39.095 | 39.095 |
February | 0.000 | 0.000 | 651.354 | 35.177 | 35.177 |
March | 19.242 | 0.353 | 656.750 | 21.387 | 21.739 |
April | 68.004 | 3.074 | 508.370 | 14.675 | 17.749 |
May | 183.791 | 9.012 | 322.958 | 6.542 | 15.554 |
June | 359.820 | 23.326 | 123.208 | 1.190 | 24.516 |
July | 521.840 | 40.462 | 40.750 | 0.384 | 40.847 |
August | 491.939 | 33.155 | 38.542 | 0.250 | 33.405 |
September | 308.043 | 16.202 | 163.208 | 2.172 | 18.373 |
October | 54.892 | 1.465 | 571.470 | 15.132 | 16.597 |
November | 0.000 | 0.000 | 713.708 | 26.206 | 26.206 |
December | 0.000 | 0.000 | 744.000 | 43.269 | 43.269 |
Annual Sum or Average | 2007.571 | 127.049 | 5278.319 | 205.479 | 332.528 |
Minimum of Months | 0.000 | 0.000 | 38.542 | 0.250 | 15.554 |
Maximum of Months | 521.840 | 40.462 | 744.000 | 43.269 | 43.269 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1770.23 | 0.00 |
February | 0.00 | 1971.38 | 0.00 |
March | 0.00 | 686.45 | 0.00 |
April | 0.00 | 433.21 | 0.00 |
May | 0.00 | 93.50 | 0.00 |
June | 0.00 | 0.14 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 3.28 | 0.00 |
October | 0.00 | 317.25 | 0.00 |
November | 0.00 | 830.84 | 0.00 |
December | 0.00 | 2202.78 | 0.00 |
Annual Sum or Average | 0.00 | 686.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 2202.78 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2637.18 | 0.00 |
February | 0.00 | 2808.53 | 0.00 |
March | 0.00 | 1424.67 | 0.00 |
April | 0.00 | 1068.37 | 0.00 |
May | 0.00 | 472.09 | 0.00 |
June | 0.00 | 45.24 | 0.00 |
July | 0.00 | 9.80 | 0.00 |
August | 0.00 | 1.25 | 0.00 |
September | 0.00 | 74.02 | 0.00 |
October | 0.00 | 798.03 | 0.00 |
November | 0.00 | 1695.69 | 0.00 |
December | 0.00 | 3017.46 | 0.00 |
Annual Sum or Average | 0.00 | 1162.50 | 0.00 |
Minimum of Months | 0.00 | 1.25 | 0.00 |
Maximum of Months | 0.00 | 3017.46 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3519.80 | 0.00 |
February | 0.00 | 3658.61 | 0.00 |
March | 0.00 | 1896.90 | 0.00 |
April | 0.00 | 1401.13 | 0.00 |
May | 0.00 | 659.89 | 0.00 |
June | 0.00 | 127.19 | 0.00 |
July | 0.00 | 42.79 | 0.00 |
August | 0.00 | 23.76 | 0.00 |
September | 0.00 | 189.85 | 0.00 |
October | 0.00 | 1227.07 | 0.00 |
November | 0.00 | 2379.62 | 0.00 |
December | 0.00 | 3997.18 | 0.00 |
Annual Sum or Average | 0.00 | 1582.91 | 0.00 |
Minimum of Months | 0.00 | 23.76 | 0.00 |
Maximum of Months | 0.00 | 3997.18 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3855.90 | 0.00 |
February | 0.00 | 3885.34 | 0.00 |
March | 0.00 | 2169.61 | 0.00 |
April | 0.00 | 1548.96 | 0.00 |
May | 0.00 | 723.48 | 0.00 |
June | 0.00 | 132.81 | 0.00 |
July | 0.00 | 42.34 | 0.00 |
August | 0.00 | 28.62 | 0.00 |
September | 0.00 | 253.89 | 0.00 |
October | 0.00 | 1450.28 | 0.00 |
November | 0.00 | 2627.76 | 0.00 |
December | 0.00 | 4298.81 | 0.00 |
Annual Sum or Average | 0.00 | 1740.64 | 0.00 |
Minimum of Months | 0.00 | 28.62 | 0.00 |
Maximum of Months | 0.00 | 4298.81 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3081.44 | 0.00 |
February | 0.00 | 3171.19 | 0.00 |
March | 0.00 | 1774.47 | 0.00 |
April | 0.00 | 1287.99 | 0.00 |
May | 0.00 | 533.76 | 0.00 |
June | 0.00 | 49.90 | 0.00 |
July | 0.00 | 11.22 | 0.00 |
August | 0.00 | 2.32 | 0.00 |
September | 0.00 | 106.69 | 0.00 |
October | 0.00 | 1083.38 | 0.00 |
November | 0.00 | 2038.65 | 0.00 |
December | 0.00 | 3433.04 | 0.00 |
Annual Sum or Average | 0.00 | 1372.05 | 0.00 |
Minimum of Months | 0.00 | 2.32 | 0.00 |
Maximum of Months | 0.00 | 3433.04 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3954.62 | 0.00 |
February | 0.00 | 4006.11 | 0.00 |
March | 0.00 | 2187.44 | 0.00 |
April | 0.00 | 1575.42 | 0.00 |
May | 0.00 | 695.92 | 0.00 |
June | 0.00 | 126.73 | 0.00 |
July | 0.00 | 42.23 | 0.00 |
August | 0.00 | 26.29 | 0.00 |
September | 0.00 | 214.83 | 0.00 |
October | 0.00 | 1492.63 | 0.00 |
November | 0.00 | 2705.12 | 0.00 |
December | 0.00 | 4406.74 | 0.00 |
Annual Sum or Average | 0.00 | 1774.84 | 0.00 |
Minimum of Months | 0.00 | 26.29 | 0.00 |
Maximum of Months | 0.00 | 4406.74 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2574.68 | 0.00 |
February | 0.00 | 2578.30 | 0.00 |
March | 0.00 | 1316.32 | 0.00 |
April | 0.00 | 891.52 | 0.00 |
May | 0.00 | 359.65 | 0.00 |
June | 0.00 | 33.42 | 0.00 |
July | 0.00 | 6.87 | 0.00 |
August | 0.00 | 1.38 | 0.00 |
September | 0.00 | 87.56 | 0.00 |
October | 0.00 | 791.43 | 0.00 |
November | 0.00 | 1634.22 | 0.00 |
December | 0.00 | 2894.43 | 0.00 |
Annual Sum or Average | 0.00 | 1090.09 | 0.00 |
Minimum of Months | 0.00 | 1.38 | 0.00 |
Maximum of Months | 0.00 | 2894.43 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1766.07 | 0.00 |
February | 0.00 | 1810.98 | 0.00 |
March | 0.00 | 879.71 | 0.00 |
April | 0.00 | 605.35 | 0.00 |
May | 0.00 | 201.16 | 0.00 |
June | 0.00 | 4.35 | 0.00 |
July | 0.00 | 0.03 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 20.14 | 0.00 |
October | 0.00 | 460.15 | 0.00 |
November | 0.00 | 1044.38 | 0.00 |
December | 0.00 | 1999.58 | 0.00 |
Annual Sum or Average | 0.00 | 727.24 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1999.58 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2642.59 | 0.00 |
February | 0.00 | 2661.46 | 0.00 |
March | 0.00 | 1331.24 | 0.00 |
April | 0.00 | 915.66 | 0.00 |
May | 0.00 | 362.78 | 0.00 |
June | 0.00 | 38.26 | 0.00 |
July | 0.00 | 10.62 | 0.00 |
August | 0.00 | 2.40 | 0.00 |
September | 0.00 | 85.61 | 0.00 |
October | 0.00 | 838.08 | 0.00 |
November | 0.00 | 1699.76 | 0.00 |
December | 0.00 | 2978.98 | 0.00 |
Annual Sum or Average | 0.00 | 1122.92 | 0.00 |
Minimum of Months | 0.00 | 2.40 | 0.00 |
Maximum of Months | 0.00 | 2978.98 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2963.78 | 0.00 |
February | 0.00 | 2875.06 | 0.00 |
March | 0.00 | 1566.66 | 0.00 |
April | 0.00 | 1037.24 | 0.00 |
May | 0.00 | 409.20 | 0.00 |
June | 0.00 | 41.35 | 0.00 |
July | 0.00 | 9.62 | 0.00 |
August | 0.00 | 3.12 | 0.00 |
September | 0.00 | 129.07 | 0.00 |
October | 0.00 | 1022.84 | 0.00 |
November | 0.00 | 1936.39 | 0.00 |
December | 0.00 | 3271.16 | 0.00 |
Annual Sum or Average | 0.00 | 1264.28 | 0.00 |
Minimum of Months | 0.00 | 3.12 | 0.00 |
Maximum of Months | 0.00 | 3271.16 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2157.42 | 0.00 |
February | 0.00 | 2120.28 | 0.00 |
March | 0.00 | 1132.79 | 0.00 |
April | 0.00 | 749.68 | 0.00 |
May | 0.00 | 224.90 | 0.00 |
June | 0.00 | 4.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 30.19 | 0.00 |
October | 0.00 | 656.18 | 0.00 |
November | 0.00 | 1330.33 | 0.00 |
December | 0.00 | 2374.07 | 0.00 |
Annual Sum or Average | 0.00 | 892.33 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 2374.07 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3049.55 | 0.00 |
February | 0.00 | 2973.95 | 0.00 |
March | 0.00 | 1556.01 | 0.00 |
April | 0.00 | 1046.15 | 0.00 |
May | 0.00 | 383.46 | 0.00 |
June | 0.00 | 37.72 | 0.00 |
July | 0.00 | 10.22 | 0.00 |
August | 0.00 | 2.89 | 0.00 |
September | 0.00 | 100.57 | 0.00 |
October | 0.00 | 1055.17 | 0.00 |
November | 0.00 | 2001.96 | 0.00 |
December | 0.00 | 3363.16 | 0.00 |
Annual Sum or Average | 0.00 | 1290.13 | 0.00 |
Minimum of Months | 0.00 | 2.89 | 0.00 |
Maximum of Months | 0.00 | 3363.16 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4114.67 | 0.00 |
February | 0.00 | 4168.58 | 0.00 |
March | 0.00 | 2267.05 | 0.00 |
April | 0.00 | 1651.71 | 0.00 |
May | 0.00 | 794.62 | 0.00 |
June | 0.00 | 166.75 | 0.00 |
July | 0.00 | 54.69 | 0.00 |
August | 0.00 | 35.75 | 0.00 |
September | 0.00 | 298.47 | 0.00 |
October | 0.00 | 1503.85 | 0.00 |
November | 0.00 | 2819.41 | 0.00 |
December | 0.00 | 4616.81 | 0.00 |
Annual Sum or Average | 0.00 | 1862.52 | 0.00 |
Minimum of Months | 0.00 | 35.75 | 0.00 |
Maximum of Months | 0.00 | 4616.81 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3275.86 | 0.00 |
February | 0.00 | 3383.45 | 0.00 |
March | 0.00 | 1792.43 | 0.00 |
April | 0.00 | 1337.16 | 0.00 |
May | 0.00 | 590.66 | 0.00 |
June | 0.00 | 79.18 | 0.00 |
July | 0.00 | 19.78 | 0.00 |
August | 0.00 | 3.88 | 0.00 |
September | 0.00 | 149.64 | 0.00 |
October | 0.00 | 1084.20 | 0.00 |
November | 0.00 | 2179.35 | 0.00 |
December | 0.00 | 3696.11 | 0.00 |
Annual Sum or Average | 0.00 | 1456.02 | 0.00 |
Minimum of Months | 0.00 | 3.88 | 0.00 |
Maximum of Months | 0.00 | 3696.11 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4203.70 | 0.00 |
February | 0.00 | 4272.80 | 0.00 |
March | 0.00 | 2268.09 | 0.00 |
April | 0.00 | 1656.72 | 0.00 |
May | 0.00 | 748.48 | 0.00 |
June | 0.00 | 146.44 | 0.00 |
July | 0.00 | 46.28 | 0.00 |
August | 0.00 | 28.38 | 0.00 |
September | 0.00 | 244.98 | 0.00 |
October | 0.00 | 1517.38 | 0.00 |
November | 0.00 | 2891.13 | 0.00 |
December | 0.00 | 4723.92 | 0.00 |
Annual Sum or Average | 0.00 | 1883.39 | 0.00 |
Minimum of Months | 0.00 | 28.38 | 0.00 |
Maximum of Months | 0.00 | 4723.92 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4491.68 | 0.00 |
February | 0.00 | 4454.67 | 0.00 |
March | 0.00 | 2501.41 | 0.00 |
April | 0.00 | 1773.33 | 0.00 |
May | 0.00 | 821.64 | 0.00 |
June | 0.00 | 166.96 | 0.00 |
July | 0.00 | 53.56 | 0.00 |
August | 0.00 | 37.61 | 0.00 |
September | 0.00 | 334.34 | 0.00 |
October | 0.00 | 1741.86 | 0.00 |
November | 0.00 | 3101.75 | 0.00 |
December | 0.00 | 4968.91 | 0.00 |
Annual Sum or Average | 0.00 | 2025.04 | 0.00 |
Minimum of Months | 0.00 | 37.61 | 0.00 |
Maximum of Months | 0.00 | 4968.91 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3676.48 | 0.00 |
February | 0.00 | 3698.50 | 0.00 |
March | 0.00 | 2068.96 | 0.00 |
April | 0.00 | 1480.70 | 0.00 |
May | 0.00 | 617.02 | 0.00 |
June | 0.00 | 77.39 | 0.00 |
July | 0.00 | 18.82 | 0.00 |
August | 0.00 | 4.22 | 0.00 |
September | 0.00 | 178.04 | 0.00 |
October | 0.00 | 1357.28 | 0.00 |
November | 0.00 | 2480.06 | 0.00 |
December | 0.00 | 4062.87 | 0.00 |
Annual Sum or Average | 0.00 | 1632.93 | 0.00 |
Minimum of Months | 0.00 | 4.22 | 0.00 |
Maximum of Months | 0.00 | 4062.87 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4607.94 | 0.00 |
February | 0.00 | 4590.39 | 0.00 |
March | 0.00 | 2520.71 | 0.00 |
April | 0.00 | 1787.30 | 0.00 |
May | 0.00 | 771.06 | 0.00 |
June | 0.00 | 144.92 | 0.00 |
July | 0.00 | 45.30 | 0.00 |
August | 0.00 | 29.43 | 0.00 |
September | 0.00 | 264.51 | 0.00 |
October | 0.00 | 1783.51 | 0.00 |
November | 0.00 | 3191.74 | 0.00 |
December | 0.00 | 5099.93 | 0.00 |
Annual Sum or Average | 0.00 | 2056.93 | 0.00 |
Minimum of Months | 0.00 | 29.43 | 0.00 |
Maximum of Months | 0.00 | 5099.93 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.00 | 0.27 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.08 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.08 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:36:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1314.32 | 978.55 |
February | 0.00 | 0.00 | 1328.99 | 893.72 |
March | 0.00 | 0.00 | 1301.28 | 968.84 |
April | 0.00 | 0.00 | 1249.37 | 900.19 |
May | 0.00 | 0.00 | 1165.82 | 867.99 |
June | 0.00 | 0.00 | 1090.40 | 785.65 |
July | 0.00 | 0.00 | 1039.38 | 773.85 |
August | 0.00 | 0.00 | 1019.32 | 758.91 |
September | 0.00 | 0.00 | 1048.43 | 755.40 |
October | 0.00 | 0.00 | 1107.29 | 824.41 |
November | 0.00 | 0.00 | 1186.77 | 855.08 |
December | 0.00 | 0.00 | 1264.13 | 941.18 |
Annual Sum or Average | 0.00 | 0.00 | 1175.39 | 10303.74 |
Minimum of Months | 0.00 | 0.00 | 1019.32 | 755.40 |
Maximum of Months | 0.00 | 0.00 | 1328.99 | 978.55 |