Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42
Tabular Output Report in Format: HTML
Building: MF+CZ4CWH+USA_OR_Salem-McNary.Field.726940+oilfurnace+heatedbsmt+IECC_2009
Environment: ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2019-02-14 08:42:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1016206.10 | 26.05 | 34.56 |
Net Site Energy | 1016206.10 | 26.05 | 34.56 |
Total Source Energy | 1981852.79 | 50.81 | 67.40 |
Net Source Energy | 1981852.79 | 50.81 | 67.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 283849.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21789.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 309752.22 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 422604.60 | 593601.50 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 283849.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 39162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 21789.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 309752.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.07 | 20.19 | 0.00 | 0.00 | 0.00 | 14.27 |
Other | 10.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.37 | 20.19 | 0.00 | 0.00 | 0.00 | 14.27 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1.56 | 15.22 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 10.83 | 15.22 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 422604.598 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 422604.598 | 100.00 |
Total On-Site and Utility Electric Sources | 422604.598 | 100.00 |
Total Electricity End Uses | 422604.598 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 907.25 |
Time Setpoint Not Met During Occupied Cooling | 73.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 201.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42 |
RunPeriod | ANNUAL |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [ft] | 196.86 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.5522 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 16-JUL-18:15 | 23-DEC-07:15 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 197.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 115.67 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 121.60 | 312.72 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 197.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 40.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 115.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 307692.63 | 0.00 | 0.00 | 0.00 |
Cooling | 124028.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69006.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 335771.40 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1338388.76 | 643464.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 10.46 | 0.00 | 0.00 | 0.00 |
Cooling | 4.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.42 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 45.52 | 21.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 10.46 | 0.00 | 0.00 | 0.00 |
Cooling | 4.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.42 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 45.52 | 21.88 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 21.92 | 0.00 | 21.92 | Wetbulb [F] | 413.41 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 91.94 | 27.72 | 66.92 | Wetbulb [F] | 846.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 384876.45 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23079.15 | 18432.28 | 4646.87 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6794.98 | 5222.27 | 1572.71 | 0.77 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8751.24 | 6835.22 | 1916.02 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11410.58 | 9113.12 | 2297.46 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5003.00 | 3950.23 | 1052.76 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6982.07 | 5576.26 | 1405.80 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12013.62 | 9594.74 | 2418.88 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6313.55 | 4831.27 | 1482.27 | 0.77 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8392.60 | 6546.50 | 1846.10 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10989.82 | 8777.08 | 2212.74 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4862.04 | 3876.24 | 985.81 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6694.82 | 5346.85 | 1347.97 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13261.80 | 10591.61 | 2670.19 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6981.07 | 5574.70 | 1406.37 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9100.27 | 7124.44 | 1975.84 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12877.36 | 10284.57 | 2592.79 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6662.59 | 5321.11 | 1341.48 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7968.35 | 6277.67 | 1690.68 | 0.79 | 3.97 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 2257.03 | 1674.33 | 582.71 | 0.74 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.8 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.25 | 11.08 | 11.74 | 11.37 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.22 | 11.00 | 11.65 | 11.24 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.21 | 10.95 | 11.60 | 11.16 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.25 | 11.10 | 11.76 | 11.40 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.23 | 11.01 | 11.66 | 11.25 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.19 | 10.90 | 11.54 | 11.09 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.08 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.22 | 10.99 | 11.64 | 11.23 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.21 | 10.96 | 11.61 | 11.18 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.2 | 3.30 | 11.25 | 11.93 | 11.64 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 48960.75 | 52416.37 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 15004.74 | 15119.02 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19228.31 | 19778.62 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 25437.19 | 26615.08 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 12263.40 | 12082.03 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 16504.70 | 16774.51 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 26651.86 | 27948.99 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 13997.33 | 14003.28 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18491.30 | 18964.59 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 24586.98 | 25677.60 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 12190.15 | 11999.77 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 15924.46 | 16132.41 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29171.27 | 30718.41 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 16498.26 | 16767.39 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19989.76 | 20615.95 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 28395.82 | 29865.97 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 15860.09 | 16062.64 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 18020.70 | 18445.76 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 6270.02 | 5328.56 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 865.72 | 433.55 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 234.01 | 117.19 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 312.55 | 156.53 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 428.02 | 214.35 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 183.03 | 91.66 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 261.90 | 131.16 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 450.64 | 225.68 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 215.29 | 107.82 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 298.87 | 149.67 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 412.24 | 206.45 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 181.68 | 90.98 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 251.13 | 125.76 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 497.46 | 249.13 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 261.79 | 131.10 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 326.71 | 163.62 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 483.04 | 241.91 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 249.92 | 125.16 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 290.10 | 145.28 | 0.50 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.38 | 0.06 | 71.58 | 35.85 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 38.702290 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 20195.58 | 20195.58 | 16.82 | 865.720 | 865.720 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00814 | 86.67 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5458.94 | 5458.94 | 4.55 | 234.013 | 234.013 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 74.98 | 74.98 | 0.00828 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7291.20 | 7291.20 | 6.07 | 312.555 | 312.555 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 74.98 | 74.98 | 0.00823 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9984.94 | 9984.94 | 8.32 | 428.021 | 428.021 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00826 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4269.80 | 4269.80 | 3.56 | 183.031 | 183.031 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00852 | 83.21 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6109.77 | 6109.77 | 5.09 | 261.904 | 261.904 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 74.98 | 74.98 | 0.00830 | 80.23 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10512.64 | 10512.64 | 8.76 | 450.642 | 450.642 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00824 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5022.20 | 5022.20 | 4.18 | 215.291 | 215.291 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 74.98 | 74.98 | 0.00829 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6971.94 | 6971.94 | 5.81 | 298.868 | 298.868 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 74.98 | 74.98 | 0.00822 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9616.75 | 9616.75 | 8.01 | 412.238 | 412.238 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00827 | 85.29 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4238.27 | 4238.27 | 3.53 | 181.680 | 181.680 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00857 | 81.13 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5858.41 | 5858.41 | 4.88 | 251.129 | 251.129 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 74.98 | 74.98 | 0.00831 | 80.23 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6767.39 | 6767.39 | 5.64 | 290.096 | 290.096 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 74.98 | 74.98 | 0.00826 | 89.17 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7621.43 | 7621.43 | 6.35 | 326.714 | 326.714 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 74.98 | 74.98 | 0.00822 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11604.86 | 11604.86 | 9.67 | 497.463 | 497.463 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00823 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5830.18 | 5830.18 | 4.86 | 249.920 | 249.920 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00842 | 83.21 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6107.04 | 6107.04 | 5.09 | 261.788 | 261.788 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00839 | 84.25 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11268.44 | 11268.44 | 9.39 | 483.042 | 483.042 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00825 | 85.29 | 0.00850 | 44.995 | 0.00 |
HEATEDBSMT | 398.44 | 398.44 | 0.05 | 17.079 | 44.995 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00829 | 82.17 | 0.00850 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 21.92 | 0.00237 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6958.05 | 6958.05 | 5.80 | 127.517 | 127.517 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00575 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8994.84 | 8994.84 | 7.49 | 164.841 | 164.841 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00598 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8999.88 | 8999.88 | 7.50 | 164.933 | 164.933 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00598 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7043.19 | 7043.19 | 5.87 | 129.077 | 129.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00577 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8996.94 | 8996.94 | 7.49 | 164.879 | 164.879 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00598 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7266.94 | 7266.94 | 6.05 | 133.185 | 133.185 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00622 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5496.81 | 5496.81 | 4.58 | 100.745 | 100.745 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00602 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7482.39 | 7482.39 | 6.23 | 137.134 | 137.134 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7484.11 | 7484.11 | 6.23 | 137.165 | 137.165 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5516.74 | 5516.74 | 4.60 | 101.111 | 101.111 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00603 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7481.31 | 7481.31 | 6.23 | 137.114 | 137.114 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00625 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 10471.44 | 10471.44 | 8.72 | 191.900 | 191.900 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10472.95 | 10472.95 | 8.72 | 191.928 | 191.928 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10440.73 | 10440.73 | 8.70 | 191.338 | 191.338 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00616 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8503.52 | 8503.52 | 7.08 | 155.840 | 155.840 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8499.24 | 8499.24 | 7.08 | 155.761 | 155.761 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10473.48 | 10473.48 | 8.72 | 191.938 | 191.938 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 21.92 | 0.00237 | 44.995 | 0.00 |
HEATEDBSMT | 3904.62 | 3904.62 | 0.50 | 71.577 | 71.577 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | 72.00 | 72.00 | 0.00800 | 21.92 | 0.00237 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 | 865.72 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 | 234.01 | 127.52 | 127.52 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 | 312.55 | 164.84 | 164.84 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 | 428.02 | 164.93 | 164.93 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 | 183.03 | 129.08 | 129.08 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 | 261.90 | 164.88 | 164.88 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 | 450.64 | 133.19 | 133.19 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 | 215.29 | 100.75 | 100.75 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 | 298.87 | 137.13 | 137.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 | 412.24 | 137.17 | 137.17 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 | 181.68 | 101.11 | 101.11 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 | 251.13 | 137.11 | 137.11 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.46 | 497.46 | 191.34 | 191.34 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.79 | 261.79 | 155.76 | 155.76 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.71 | 326.71 | 191.93 | 191.93 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.04 | 483.04 | 191.94 | 191.94 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.92 | 249.92 | 155.84 | 155.84 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.10 | 290.10 | 191.90 | 191.90 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 71.58 | 71.58 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1000.25 | 6064.50 | 22.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 952.50 | 6289.25 | 104.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1330.25 | 6244.00 | 35.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1121.00 | 6756.25 | 79.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 563.25 | 6798.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1105.25 | 6580.00 | 41.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1381.25 | 6073.50 | 27.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 875.75 | 5994.50 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1361.50 | 6037.50 | 27.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1150.50 | 6559.50 | 66.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 664.25 | 6487.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1169.00 | 6369.00 | 40.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1347.50 | 6582.75 | 128.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1440.50 | 6374.75 | 86.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1392.75 | 6517.25 | 83.25 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 940.00 | 6800.50 | 51.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1092.00 | 6520.25 | 29.75 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1302.00 | 6774.50 | 135.25 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1984.75 | 7161.00 | 201.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 15.25 | 0.00 | 15.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 101.75 | 16.00 | 101.75 | 16.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 110.00 | 8.00 | 110.00 | 8.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 219.00 | 25.75 | 219.00 | 25.75 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 60.00 | 52.25 | 60.00 | 52.25 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 58.50 | 48.00 | 58.50 | 48.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 20.50 | 14.25 | 20.50 | 14.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3.50 | 11.25 | 3.50 | 11.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 142.00 | 5.00 | 142.00 | 5.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 236.25 | 22.25 | 236.25 | 22.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 25.75 | 45.00 | 25.75 | 45.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 100.50 | 47.00 | 100.50 | 47.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.50 | 49.50 | 44.50 | 49.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 59.75 | 26.50 | 59.75 | 26.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 121.50 | 20.75 | 121.50 | 20.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 41.25 | 43.50 | 41.25 | 43.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8.00 | 38.25 | 8.00 | 38.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 175.25 | 24.00 | 175.25 | 24.00 |
HEATEDBSMT | 242.75 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1125.25 | 73.50 | 907.25 | 73.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.271 | 0.000 | 0.276 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.233 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.263 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.232 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.084 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.084 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.232 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.233 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.264 | 0.000 | 0.275 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 6381.52 | 139.94 | 04-OCT-23:15 | 3118.76 | 16-JUL-18:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
ElectricityPurchased:Plant | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
Cogeneration:ElectricityPurchased | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
ElectricityNet:Plant | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
Cogeneration:ElectricityNet | 123770.64 | 7505.52 | 24-AUG-03:15 | 35613.91 | 16-JUL-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 17851.30 | 529.57 | 04-OCT-23:15 | 15715.64 | 16-JUL-16:00 |
General:Fans:Electricity | 6381.52 | 139.94 | 04-OCT-23:15 | 3118.76 | 16-JUL-18:30 |
Cooling:Electricity | 11469.78 | 0.00 | 01-JAN-03:30 | 12599.56 | 16-JUL-16:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 5936.02 | 0.00 | 25-FEB-16:00 | 312497.63 | 23-DEC-07:15 |
Gas:Plant | 5936.02 | 0.00 | 25-FEB-16:00 | 312497.63 | 23-DEC-07:15 |
WaterSystems:Gas | 3097.52 | 0.00 | 01-JAN-00:15 | 115981.97 | 19-FEB-08:15 |
Water Heater:WaterSystems:Gas | 3097.52 | 0.00 | 01-JAN-00:15 | 115981.97 | 19-FEB-08:15 |
Heating:Gas | 2838.49 | 0.00 | 25-FEB-15:45 | 204930.43 | 21-DEC-04:00 |
Boiler:Heating:Gas | 2838.49 | 0.00 | 25-FEB-15:45 | 204930.43 | 21-DEC-04:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 25-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 396837.61 | 1566.06 | 11-AUG-02:45 | 197359.51 | 23-DEC-08:15 |
PlantLoopHeatingDemand:Plant | 169593.23 | 1566.06 | 11-AUG-02:45 | 41980.69 | 11-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 169593.23 | 1566.06 | 11-AUG-02:45 | 41980.69 | 11-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1195134.35 | 15944.68 | 01-SEP-02:15 | 518223.56 | 23-DEC-07:15 |
EnergyTransfer:Building | 391202.62 | 6492.81 | 17-JUN-00:30 | 170846.59 | 21-DEC-04:00 |
EnergyTransfer:Zone:HEATEDBSMT | 11657.46 | 0.00 | 01-MAY-12:00 | 4822.41 | 24-APR-22:30 |
Heating:EnergyTransfer | 237126.12 | 0.00 | 01-MAY-12:00 | 170846.59 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 11633.80 | 0.00 | 01-MAY-12:00 | 4822.41 | 24-APR-22:30 |
Cooling:EnergyTransfer | 154076.50 | 0.00 | 01-JAN-03:30 | 145201.03 | 24-JUN-18:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 23.66 | 0.00 | 01-JAN-00:15 | 567.84 | 16-JUL-19:45 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 63727.74 | 0.00 | 01-JAN-03:30 | 20132.57 | 24-JUN-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7.12 | 0.00 | 01-JAN-00:15 | 934.56 | 21-DEC-03:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 63720.62 | 0.00 | 01-JAN-03:30 | 20132.57 | 24-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13932.23 | 0.00 | 01-JAN-14:00 | 14066.69 | 15-FEB-14:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9621.54 | 0.00 | 01-JAN-14:00 | 14066.69 | 15-FEB-14:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4310.69 | 0.00 | 01-JAN-00:15 | 5909.89 | 24-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20468.90 | 0.00 | 19-JAN-11:00 | 10768.69 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14252.41 | 0.00 | 19-JAN-11:00 | 10768.69 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6216.49 | 0.00 | 01-JAN-00:15 | 7407.39 | 09-SEP-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21315.71 | 0.00 | 30-JAN-16:00 | 10686.59 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15851.48 | 0.00 | 30-JAN-16:00 | 10686.59 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5464.23 | 0.00 | 01-JAN-00:15 | 10173.39 | 23-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15027.88 | 0.00 | 25-FEB-15:45 | 8435.85 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12166.89 | 0.00 | 25-FEB-15:45 | 8435.85 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2860.98 | 0.00 | 01-JAN-00:15 | 4558.75 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20601.37 | 0.00 | 25-FEB-15:30 | 10713.13 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15890.76 | 0.00 | 25-FEB-15:30 | 10713.13 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4710.60 | 0.00 | 01-JAN-00:15 | 6204.82 | 24-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16878.17 | 0.00 | 01-JAN-14:00 | 10541.65 | 24-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9317.34 | 0.00 | 01-JAN-14:00 | 8440.81 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7560.83 | 0.00 | 01-JAN-00:15 | 10541.65 | 24-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11286.61 | 0.00 | 01-JAN-13:00 | 6709.04 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6603.07 | 0.00 | 01-JAN-13:00 | 6709.04 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4683.54 | 0.00 | 01-JAN-00:15 | 5417.61 | 24-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16843.26 | 0.00 | 01-JAN-13:30 | 8604.84 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10254.24 | 0.00 | 01-JAN-13:30 | 8604.84 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6589.02 | 0.00 | 01-JAN-00:15 | 7055.51 | 09-SEP-13:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17442.42 | 0.00 | 30-JAN-16:00 | 9822.68 | 24-JUN-19:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11711.36 | 0.00 | 30-JAN-16:00 | 8655.86 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5731.05 | 0.00 | 01-JAN-00:15 | 9822.68 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11310.61 | 0.00 | 25-FEB-15:15 | 6387.31 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8101.89 | 0.00 | 25-FEB-15:15 | 6387.31 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3208.72 | 0.00 | 01-JAN-00:15 | 4410.72 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16774.57 | 0.00 | 25-FEB-15:00 | 8683.64 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11723.88 | 0.00 | 25-FEB-15:00 | 8683.64 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5050.69 | 0.00 | 01-JAN-00:15 | 5992.09 | 24-JUN-19:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 24192.58 | 0.00 | 25-FEB-15:45 | 12250.65 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 18707.57 | 0.00 | 25-FEB-15:45 | 12250.65 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5485.01 | 0.00 | 01-JAN-00:15 | 7220.09 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23569.44 | 0.00 | 19-JAN-12:00 | 12160.06 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 17201.50 | 0.00 | 19-JAN-12:00 | 12160.06 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 6367.94 | 0.00 | 01-JAN-00:15 | 7934.04 | 24-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24431.31 | 0.00 | 19-JAN-12:45 | 12098.29 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 17139.97 | 0.00 | 19-JAN-12:45 | 12098.29 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 7291.34 | 0.00 | 01-JAN-00:15 | 11686.97 | 24-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 18707.77 | 0.00 | 25-FEB-16:15 | 9960.90 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 14870.11 | 0.00 | 25-FEB-16:15 | 9960.90 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3837.66 | 0.00 | 01-JAN-00:15 | 6088.62 | 24-JUN-20:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 17893.16 | 0.00 | 19-JAN-12:15 | 9890.55 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 13260.39 | 0.00 | 19-JAN-12:15 | 9890.55 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4632.77 | 0.00 | 01-JAN-00:15 | 6326.58 | 24-JUN-20:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25141.44 | 0.00 | 21-FEB-16:30 | 12227.52 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 18810.79 | 0.00 | 21-FEB-16:30 | 12227.52 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 6330.65 | 0.00 | 01-JAN-00:15 | 11520.10 | 24-JUN-19:45 |
EnergyTransfer:Plant | 396672.66 | 1566.06 | 11-AUG-02:45 | 197030.88 | 23-DEC-07:15 |
WaterSystems:EnergyTransfer | 169593.23 | 1566.06 | 11-AUG-02:45 | 41980.69 | 11-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 169593.23 | 1566.06 | 11-AUG-02:45 | 41980.69 | 11-FEB-09:00 |
EnergyTransfer:HVAC | 407259.08 | 7060.35 | 03-JUL-01:30 | 168596.94 | 18-JUL-19:00 |
HeatingCoils:EnergyTransfer | 227244.39 | 0.00 | 25-FEB-15:45 | 165032.59 | 21-DEC-04:00 |
PlantLoopHeatingDemand:HVAC | 227244.39 | 0.00 | 25-FEB-15:45 | 165032.59 | 21-DEC-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 227244.39 | 0.00 | 25-FEB-15:45 | 165032.59 | 21-DEC-04:00 |
CoolingCoils:EnergyTransfer | 180014.69 | 0.00 | 01-JAN-03:30 | 168596.94 | 18-JUL-19:00 |
Boilers:EnergyTransfer | 227079.43 | 0.00 | 25-FEB-15:45 | 163944.35 | 21-DEC-04:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 7.121 | -5306.50 | 0.000 | 0.000 | 2875.343 | 2771.241 | 10464.601 | 7939.662 | 0.000 | 360.520 | 66257.466 | 0.000 | -6557.27 | 0.000 | -20398.12 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 9621.503 | -358.98 | 0.000 | 0.000 | 3080.084 | 2771.241 | 10464.601 | 3411.319 | 0.000 | 339.591 | 0.347 | 0.000 | -2481.80 | 0.000 | -17211.13 | -5684.77 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 14252.331 | -517.69 | 0.000 | 0.000 | 3085.845 | 2771.241 | 10464.601 | 7370.776 | 0.000 | 361.244 | 0.000 | 0.000 | -5945.92 | 0.000 | -18374.20 | -7769.47 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 15851.401 | -455.04 | 0.000 | 0.000 | 3093.795 | 2771.241 | 10464.601 | 5770.641 | 0.000 | 358.772 | 0.000 | 0.000 | -6240.85 | 0.000 | -18207.39 | -8398.05 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 12166.843 | -238.25 | 0.000 | 0.000 | 3086.592 | 2771.241 | 10464.601 | 968.025 | 0.000 | 334.416 | 0.000 | 0.000 | -2590.12 | 0.000 | -17150.76 | -7189.88 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 15890.685 | -392.29 | 0.000 | 0.000 | 3093.356 | 2771.241 | 10464.601 | 5000.646 | 0.000 | 356.183 | 0.000 | 0.000 | -6046.04 | 0.000 | -18268.02 | -8552.07 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 9317.277 | -629.64 | 0.000 | 0.000 | 3062.438 | 2771.241 | 10464.601 | 8055.609 | 0.000 | 259.866 | 0.000 | 0.000 | -6253.81 | 0.000 | -13285.48 | -6831.02 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6603.032 | -390.03 | 0.000 | 0.000 | 3051.120 | 2771.241 | 10464.601 | 3405.251 | 0.000 | 239.045 | 0.000 | 0.000 | -2523.17 | 0.000 | -12204.35 | -7123.30 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 10254.173 | -548.71 | 0.000 | 0.000 | 3070.043 | 2771.241 | 10464.601 | 7356.715 | 0.000 | 260.555 | 0.000 | 0.000 | -6032.31 | 0.000 | -13263.04 | -8293.01 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11711.298 | -477.26 | 0.000 | 0.000 | 3077.884 | 2771.241 | 10464.601 | 5762.792 | 0.000 | 259.548 | 0.000 | 0.000 | -6327.15 | 0.000 | -13140.35 | -8848.89 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8101.850 | -267.21 | 0.000 | 0.000 | 3066.911 | 2771.241 | 10464.601 | 967.287 | 0.000 | 236.919 | 0.000 | 0.000 | -2623.37 | 0.000 | -12083.92 | -7692.82 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11723.813 | -420.61 | 0.000 | 0.000 | 3079.321 | 2771.241 | 10464.601 | 4991.313 | 0.000 | 257.159 | 0.000 | 0.000 | -6124.53 | 0.000 | -13177.73 | -8934.52 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 18707.486 | -456.78 | 0.000 | 0.000 | 3091.359 | 2771.241 | 10464.601 | 5020.160 | 0.000 | 350.506 | 0.000 | 0.000 | -6078.23 | 0.000 | -18313.84 | -10528.31 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17201.419 | -530.30 | 0.000 | 0.000 | 3086.201 | 2771.241 | 10464.601 | 7406.090 | 0.000 | 355.485 | 0.000 | 0.000 | -5971.71 | 0.000 | -18388.43 | -10557.01 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17139.896 | -607.20 | 0.000 | 0.000 | 3085.630 | 2771.241 | 10464.601 | 8123.410 | 0.000 | 356.342 | 0.000 | 0.000 | -6137.29 | 0.000 | -18356.44 | -10156.16 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 14870.056 | -319.59 | 0.000 | 0.000 | 3085.419 | 2771.241 | 10464.601 | 976.709 | 0.000 | 333.186 | 0.000 | 0.000 | -2593.49 | 0.000 | -17199.18 | -8870.92 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13260.344 | -385.80 | 0.000 | 0.000 | 3076.862 | 2771.241 | 10464.601 | 3426.525 | 0.000 | 333.280 | 0.000 | 0.000 | -2487.39 | 0.000 | -17294.26 | -8918.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 18810.715 | -527.19 | 0.000 | 0.000 | 3091.914 | 2771.241 | 10464.601 | 5776.805 | 0.000 | 356.766 | 0.000 | 0.000 | -6264.89 | 0.000 | -18268.02 | -10408.58 |
HEATEDBSMT | 0.000 | 0.000 | 11633.802 | -1.97 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -11610.14 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4151.043 | 38880.147 | 0.000 | 0.000 | 0.000 | -43031.19 | -0.06 |
Total Facility | 0.000 | 0.000 | 237125.045 | -12831.05 | 0.000 | 0.000 | 55240.118 | 49882.340 | 188362.826 | 91729.735 | 0.000 | 9860.424 | 105137.961 | 0.000 | -89279.35 | 0.000 | -337615.85 | -156367.46 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 24-JUN-18:45 | 0.00 | 0.00 | 0.00 | -1.7 | 0.00 | 0.00 | 421.00 | 813.96 | 1748.06 | 5420.56 | 0.00 | 1548.02 | 10241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 813.96 | 1748.06 | 433.36 | 0.00 | 1703.21 | 785.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 09-SEP-13:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.40 | 116.28 | 1109.73 | 4440.56 | 0.00 | 1772.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -145.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 420.46 | 902.05 | 1689.30 | 2451.23 | 0.00 | 927.57 | 3833.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 24-JUN-20:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 408.19 | 902.05 | 1651.67 | 23.34 | 0.00 | 556.96 | 1027.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.22 | 902.05 | 1689.30 | 812.15 | 0.00 | 953.88 | 1481.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24-JUN-19:04 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 422.84 | 902.05 | 1689.30 | 3760.26 | 0.00 | 897.34 | 2945.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24-JUN-18:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.68 | 813.96 | 1748.06 | 350.57 | 0.00 | 987.26 | 1096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 09-SEP-13:45 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.07 | 116.28 | 1109.73 | 4247.78 | 0.00 | 1227.06 | 239.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 418.61 | 902.05 | 1689.30 | 2451.72 | 0.00 | 661.23 | 3776.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 406.77 | 902.05 | 1689.30 | 626.41 | 0.00 | 564.29 | 229.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 422.77 | 902.05 | 1689.30 | 817.90 | 0.00 | 681.01 | 1500.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 24-JUN-19:57 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 414.25 | 902.05 | 1689.30 | 81.66 | 0.00 | 766.82 | 3377.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 24-JUN-18:42 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 425.30 | 813.96 | 1748.06 | 848.98 | 0.00 | 1568.23 | 2538.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 24-JUN-19:23 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 421.31 | 902.05 | 1689.30 | 2810.22 | 0.00 | 1116.33 | 4797.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 24-JUN-20:06 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 411.08 | 902.05 | 1651.67 | 18.29 | 0.00 | 571.25 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 24-JUN-20:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 418.88 | 902.05 | 1689.30 | 43.49 | 0.00 | 741.32 | 2541.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 419.19 | 902.05 | 1689.30 | 2424.95 | 0.00 | 915.47 | 5198.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-19:32 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUN-18:08 | 0.00 | 0.00 | 0.00 | -12.1 | 0.00 | 0.00 | 7478.39 | 14651.21 | 31465.06 | 51280.35 | 0.00 | 27075.10 | 27664.43 | 0.00 | 0.00 | 0.00 | -14360.8 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21-DEC-03:30 | 0.00 | 0.00 | 934.58 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 7079.53 | 0.00 | -2484.1 | 0.00 | -6965.7 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23-DEC-04:51 | 0.00 | 0.00 | 14756.08 | 0.00 | 0.00 | 0.00 | 687.65 | 186.05 | 833.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -844.8 | 0.00 | -4698.3 | -10920.7 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 10769.07 | 0.00 | 0.00 | 0.00 | 526.28 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2498.5 | 0.00 | -7142.2 | -2564.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 20-MAR-09:20 | 0.00 | 0.00 | 19585.61 | 0.00 | 0.00 | 0.00 | 134.76 | 116.28 | 1096.02 | 317.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1423.5 | -19826.7 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 06-MAR-17:23 | 0.00 | 0.00 | 10783.44 | 0.00 | 0.00 | 0.00 | 303.63 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -473.9 | 0.00 | -2018.3 | -10863.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 10713.51 | 0.00 | 0.00 | 0.00 | 526.33 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2508.0 | 0.00 | -7141.8 | -2499.4 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13-MAY-08:43 | 0.00 | 0.00 | 10217.30 | 0.00 | 0.00 | 0.00 | 221.31 | 170.54 | 1179.68 | 721.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1165.0 | -11345.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6709.20 | 0.00 | 0.00 | 0.00 | 526.28 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1020.1 | 0.00 | -4508.8 | -2616.0 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 30-JAN-22:40 | 0.00 | 0.00 | 8874.59 | 0.00 | 0.00 | 0.00 | 551.70 | 379.85 | 1340.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1816.8 | 0.00 | -2874.8 | -6454.8 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 01-JAN-14:49 | 0.00 | 0.00 | 18842.87 | 0.00 | 0.00 | 0.00 | 141.72 | 116.28 | 1113.97 | 1692.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2336.0 | -19571.2 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 01-JAN-14:58 | 0.00 | 0.00 | 10747.68 | 0.00 | 0.00 | 0.00 | 127.31 | 116.28 | 1113.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -448.6 | 0.00 | -2306.8 | -9349.8 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8683.86 | 0.00 | 0.00 | 0.00 | 526.29 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2527.6 | 0.00 | -4971.2 | -2620.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12251.08 | 0.00 | 0.00 | 0.00 | 526.30 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2511.1 | 0.00 | -7152.2 | -4023.5 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 12160.49 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2507.6 | 0.00 | -7152.2 | -3936.4 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 04-SEP-08:24 | 0.00 | 0.00 | 17461.02 | 0.00 | 0.00 | 0.00 | 223.61 | 170.54 | 1155.86 | 759.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1074.2 | -18696.7 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 18-FEB-15:15 | 0.00 | 0.00 | 10933.11 | 0.00 | 0.00 | 0.00 | 127.31 | 201.55 | 1168.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -216.9 | 0.00 | -2675.3 | -9538.0 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9890.90 | 0.00 | 0.00 | 0.00 | 526.26 | 62.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.3 | 0.00 | -6689.8 | -3619.4 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 18-FEB-15:06 | 0.00 | 0.00 | 18256.36 | 0.00 | 0.00 | 0.00 | 136.68 | 201.55 | 1168.29 | 4073.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2811.9 | -21024.7 |
HEATEDBSMT | 24-APR-22:23 | 0.00 | 0.00 | 4833.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4833.8 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-04:00 | 0.00 | 0.00 | 170852.17 | 0.00 | 0.00 | 0.00 | 9473.26 | 1116.28 | 15253.70 | 0.00 | 0.00 | 649.10 | 0.00 | 0.00 | -36296.0 | 0.00 | -112819.3 | -48229.3 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 865.720 | 2.00 | 2.00 | 1.00 | 44.9950 | 865.720 | 0.052 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 234.013 | 2.00 | 2.00 | 1.00 | 44.9950 | 234.013 | 0.192 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 312.555 | 2.00 | 2.00 | 1.00 | 44.9950 | 312.555 | 0.144 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 428.021 | 2.00 | 2.00 | 1.00 | 44.9950 | 428.021 | 0.105 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 183.031 | 2.00 | 2.00 | 1.00 | 44.9950 | 183.031 | 0.246 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 261.904 | 2.00 | 2.00 | 1.00 | 44.9950 | 261.904 | 0.172 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.642 | 2.00 | 2.00 | 1.00 | 44.9950 | 450.642 | 0.100 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 215.291 | 2.00 | 2.00 | 1.00 | 44.9950 | 215.291 | 0.209 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.868 | 2.00 | 2.00 | 1.00 | 44.9950 | 298.868 | 0.151 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 412.238 | 2.00 | 2.00 | 1.00 | 44.9950 | 412.238 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.680 | 2.00 | 2.00 | 1.00 | 44.9950 | 181.680 | 0.248 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 251.129 | 2.00 | 2.00 | 1.00 | 44.9950 | 251.129 | 0.179 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.463 | 2.00 | 2.00 | 1.00 | 44.9950 | 497.463 | 0.090 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.788 | 2.00 | 2.00 | 1.00 | 44.9950 | 261.788 | 0.172 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.714 | 2.00 | 2.00 | 1.00 | 44.9950 | 326.714 | 0.138 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.042 | 2.00 | 2.00 | 1.00 | 44.9950 | 483.042 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.920 | 2.00 | 2.00 | 1.00 | 44.9950 | 249.920 | 0.180 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.096 | 2.00 | 2.00 | 1.00 | 44.9950 | 290.096 | 0.155 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 0.00 | 0.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 127.517 | 2.00 | 2.00 | 1.00 | 44.9950 | 127.517 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 164.841 | 2.00 | 2.00 | 1.00 | 44.9950 | 164.841 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 164.933 | 2.00 | 2.00 | 1.00 | 44.9950 | 164.933 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.077 | 2.00 | 2.00 | 1.00 | 44.9950 | 129.077 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 164.879 | 2.00 | 2.00 | 1.00 | 44.9950 | 164.879 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 133.185 | 2.00 | 2.00 | 1.00 | 44.9950 | 133.185 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 100.745 | 2.00 | 2.00 | 1.00 | 44.9950 | 100.745 | 1.000 | 1.000 | 44.9950 | 0.45 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.134 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.134 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.165 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.165 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.111 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.111 | 1.000 | 1.000 | 44.9950 | 0.45 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.114 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.114 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.338 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.338 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.761 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.761 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.928 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.928 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.938 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.938 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.840 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.840 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.900 | 2.00 | 2.00 | 1.00 | 44.9950 | 191.900 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.577 | 0.00 | 0.00 | 1.00 | 44.9950 | 71.577 | 1.000 | 1.000 | 44.9950 | 0.63 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 865.720 | 865.7202 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 234.013 | 234.0131 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 312.555 | 312.5548 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 428.021 | 428.0215 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 183.031 | 183.0314 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 261.904 | 261.9038 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.642 | 450.6420 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 215.291 | 215.2914 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.868 | 298.8681 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 412.238 | 412.2382 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.680 | 181.6798 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 251.129 | 251.1288 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.096 | 290.0959 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.714 | 326.7144 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.463 | 497.4625 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.920 | 249.9199 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.788 | 261.7882 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.042 | 483.0416 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 44.9950 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 | 865.720 | 865.72 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 | 234.013 | 234.01 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 | 312.555 | 312.55 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 | 428.021 | 428.02 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 | 183.031 | 183.03 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 | 261.904 | 261.90 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 | 450.642 | 450.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 | 215.291 | 215.29 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 | 298.868 | 298.87 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 | 412.238 | 412.24 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 | 181.680 | 181.68 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 | 251.129 | 251.13 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.46 | 497.463 | 497.46 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.79 | 261.788 | 261.79 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.71 | 326.714 | 326.71 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.04 | 483.042 | 483.04 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.92 | 249.920 | 249.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.10 | 290.096 | 290.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.995 | 44.99 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 127.517 | 127.517 | 127.517 | 44.9950 | 0.353 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 164.841 | 164.841 | 164.841 | 44.9950 | 0.273 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 164.933 | 164.933 | 164.933 | 44.9950 | 0.273 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.077 | 129.077 | 129.077 | 44.9950 | 0.349 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 164.879 | 164.879 | 164.879 | 44.9950 | 0.273 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 133.185 | 133.185 | 133.185 | 44.9950 | 0.338 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 100.745 | 100.745 | 100.745 | 44.9950 | 0.447 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.134 | 137.134 | 137.134 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.165 | 137.165 | 137.165 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.111 | 101.111 | 101.111 | 44.9950 | 0.445 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.114 | 137.114 | 137.114 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.900 | 191.900 | 191.900 | 44.9950 | 0.234 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.928 | 191.928 | 191.928 | 44.9950 | 0.234 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.338 | 191.338 | 191.338 | 44.9950 | 0.235 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.840 | 155.840 | 155.840 | 44.9950 | 0.289 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.761 | 155.761 | 155.761 | 44.9950 | 0.289 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.938 | 191.938 | 191.938 | 44.9950 | 0.234 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 71.577 | 71.577 | 71.577 | 44.9950 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 127.52 | 127.517 | 127.52 | 127.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 164.84 | 164.841 | 164.84 | 164.84 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 164.93 | 164.933 | 164.93 | 164.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 129.08 | 129.077 | 129.08 | 129.08 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 164.88 | 164.879 | 164.88 | 164.88 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 133.19 | 133.185 | 133.19 | 133.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 100.75 | 100.745 | 100.75 | 100.75 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 137.13 | 137.134 | 137.13 | 137.13 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 137.17 | 137.165 | 137.17 | 137.17 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 101.11 | 101.111 | 101.11 | 101.11 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 137.11 | 137.114 | 137.11 | 137.11 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 191.34 | 191.338 | 191.34 | 191.34 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.76 | 155.761 | 155.76 | 155.76 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 191.93 | 191.928 | 191.93 | 191.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 191.94 | 191.938 | 191.94 | 191.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.84 | 155.840 | 155.84 | 155.84 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 191.90 | 191.900 | 191.90 | 191.90 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.58 | 71.577 | 71.58 | 71.58 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 907.25 |
Number of hours cooling loads not met | 73.50 |
Number of hours not met | 980.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 2838.49 | 196913.17 | 0.00 | 0.00 |
Space Cooling | 11469.78 | 11980.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 6381.52 | 3118.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 3097.52 | 115584.46 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15497.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 123770.64 | 5936.02 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 422604.60 |
Natural Gas | 0.00 | 593601.50 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 1016206.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 0.29 |
Fans-Interior | 0.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 3.17 |
Natural Gas [kWh/ft2] | |
Space Heating | 2.13 |
Service Water Heating | 2.33 |
Miscellaneous | 0.00 |
Subtotal | 4.46 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.91 |
Space Heating | 27.93 |
Space Cooling | 3.85 |
Fans-Interior | 2.14 |
Service Water Heating | 30.48 |
Receptacle Equipment | 29.67 |
Miscellaneous | 1.01 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 71.58 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 290.10 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 326.71 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 497.46 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 249.92 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 261.79 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 483.04 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 497.46 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 261.79 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.71 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 483.04 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 249.92 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.10 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.58 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 | 1.92 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 | 0.566248 | 0.768548 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 | 0.729270 | 0.781058 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 | 0.950882 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 | 0.416916 | 0.789574 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 | 0.581839 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 | 1.00 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 | 0.526129 | 0.765223 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 | 0.699383 | 0.780033 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 | 0.915818 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 | 0.405170 | 0.797244 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 | 0.557902 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 497.46 | 1.11 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 261.79 | 0.581756 | 0.798546 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 326.71 | 0.758356 | 0.782882 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 483.04 | 1.07 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 249.92 | 0.555216 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 290.10 | 0.664029 | 0.787826 |
DX COOLING COIL_UNITHEATEDBSMT | 71.58 | 0.188086 | 0.741826 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 | 865.72 | 865.72 | 1.92 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 | 234.01 | 234.01 | 0.566248 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 | 312.55 | 312.55 | 0.729270 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 | 428.02 | 428.02 | 0.950882 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 | 183.03 | 183.03 | 0.416916 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 | 261.90 | 261.90 | 0.581839 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 | 450.64 | 450.64 | 1.00 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 | 215.29 | 215.29 | 0.526129 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 | 298.87 | 298.87 | 0.699383 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 | 412.24 | 412.24 | 0.915818 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 | 181.68 | 181.68 | 0.405170 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 | 251.13 | 251.13 | 0.557902 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 497.46 | 497.46 | 497.46 | 1.11 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 261.79 | 261.79 | 261.79 | 0.581756 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 326.71 | 326.71 | 326.71 | 0.758356 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 483.04 | 483.04 | 483.04 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 249.92 | 249.92 | 249.92 | 0.555216 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 290.10 | 290.10 | 290.10 | 0.664029 | 1.00 |
ACANDF_UNITHEATEDBSMT | 71.58 | 71.58 | 71.58 | 0.188086 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 48960.75 | 4.94 | 696.03 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 15004.74 | 1.51 | 204.65 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19228.31 | 1.94 | 266.02 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 25437.19 | 2.57 | 356.15 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 12263.40 | 1.24 | 164.68 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 16504.70 | 1.67 | 226.44 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 26651.86 | 2.69 | 373.71 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 13997.33 | 1.41 | 189.95 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 18491.30 | 1.87 | 255.27 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 24586.98 | 2.48 | 343.76 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 12190.15 | 1.23 | 163.59 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 15924.46 | 1.61 | 217.97 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29171.27 | 2.94 | 410.23 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16498.26 | 1.67 | 226.35 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19989.76 | 2.02 | 277.04 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 28395.82 | 2.87 | 398.99 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 15860.09 | 1.60 | 217.07 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 18020.70 | 1.82 | 248.45 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 6270.02 | 0.632849 | 76.06 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 865.72 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 234.01 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 312.55 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 428.02 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 183.03 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 261.90 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 450.64 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 215.29 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 298.87 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 412.24 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 181.68 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 251.13 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 497.46 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 261.79 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 326.71 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 483.04 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 249.92 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 290.10 |
SUPPLY FAN_UNITHEATEDBSMT | 71.58 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.17 | 97.01 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.17 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 384876.45 | 38.70 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 739.353 | 63.198 | 0.000 | 0.000 | 63.198 |
February | 639.234 | 57.234 | 0.000 | 0.000 | 57.234 |
March | 744.000 | 95.882 | 0.000 | 0.000 | 95.882 |
April | 720.000 | 105.791 | 0.000 | 0.000 | 105.791 |
May | 744.000 | 132.206 | 0.000 | 0.000 | 132.206 |
June | 720.000 | 156.339 | 0.000 | 0.000 | 156.339 |
July | 744.000 | 182.676 | 0.000 | 0.000 | 182.676 |
August | 744.000 | 177.986 | 0.000 | 0.000 | 177.986 |
September | 720.000 | 154.761 | 0.000 | 0.000 | 154.761 |
October | 744.000 | 114.255 | 0.000 | 0.000 | 114.255 |
November | 720.000 | 81.364 | 0.000 | 0.000 | 81.364 |
December | 674.799 | 57.124 | 16.468 | 0.387 | 57.510 |
Annual Sum or Average | 8653.386 | 1378.816 | 16.468 | 0.387 | 1379.202 |
Minimum of Months | 639.234 | 57.124 | 0.000 | 0.000 | 57.234 |
Maximum of Months | 744.000 | 182.676 | 16.468 | 0.387 | 182.676 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 8.667 | 0.124 | 690.020 | 10.774 | 11.442 |
February | 30.600 | 0.924 | 569.226 | 9.796 | 14.560 |
March | 61.654 | 1.661 | 531.876 | 5.538 | 7.199 |
April | 81.217 | 2.628 | 437.458 | 3.942 | 6.570 |
May | 163.080 | 5.947 | 289.658 | 1.641 | 7.588 |
June | 337.628 | 14.003 | 53.241 | 0.138 | 14.142 |
July | 502.410 | 25.844 | 14.557 | 0.030 | 25.874 |
August | 484.320 | 24.196 | 3.000 | 0.003 | 24.199 |
September | 348.015 | 17.393 | 84.313 | 0.244 | 17.637 |
October | 144.770 | 4.477 | 384.600 | 3.008 | 7.485 |
November | 7.675 | 0.096 | 630.917 | 6.363 | 6.459 |
December | 7.125 | 0.072 | 647.946 | 11.804 | 18.056 |
Annual Sum or Average | 2177.162 | 97.364 | 4336.811 | 53.281 | 161.210 |
Minimum of Months | 7.125 | 0.072 | 3.000 | 0.003 | 6.459 |
Maximum of Months | 502.410 | 25.844 | 690.020 | 11.804 | 25.874 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 5.221 | 0.070 | 693.958 | 28.221 | 30.375 |
February | 28.350 | 1.062 | 598.108 | 26.656 | 29.349 |
March | 69.880 | 2.458 | 512.081 | 14.860 | 23.081 |
April | 104.804 | 4.139 | 405.742 | 10.518 | 20.847 |
May | 202.741 | 9.501 | 248.752 | 4.830 | 20.299 |
June | 367.771 | 22.316 | 43.667 | 0.620 | 30.140 |
July | 521.183 | 39.208 | 12.125 | 0.166 | 42.813 |
August | 498.555 | 34.671 | 2.375 | 0.034 | 37.892 |
September | 354.088 | 23.209 | 68.125 | 1.055 | 33.179 |
October | 132.791 | 5.474 | 373.933 | 9.374 | 23.708 |
November | 3.300 | 0.061 | 630.238 | 18.272 | 24.030 |
December | 3.250 | 0.044 | 699.971 | 32.394 | 34.389 |
Annual Sum or Average | 2291.932 | 142.213 | 4289.075 | 147.002 | 350.102 |
Minimum of Months | 3.250 | 0.044 | 2.375 | 0.034 | 20.299 |
Maximum of Months | 521.183 | 39.208 | 699.971 | 32.394 | 42.813 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 712.938 | 32.224 | 38.396 |
February | 6.125 | 0.098 | 614.325 | 29.391 | 33.497 |
March | 19.268 | 0.537 | 562.994 | 17.420 | 29.712 |
April | 76.050 | 3.930 | 444.465 | 11.928 | 26.259 |
May | 173.138 | 10.993 | 289.452 | 5.473 | 24.587 |
June | 326.544 | 24.085 | 95.534 | 0.916 | 27.614 |
July | 466.942 | 39.926 | 34.042 | 0.295 | 41.271 |
August | 427.154 | 32.082 | 27.156 | 0.172 | 33.390 |
September | 267.038 | 17.495 | 147.912 | 1.752 | 25.755 |
October | 57.707 | 2.035 | 457.495 | 11.415 | 28.470 |
November | 0.000 | 0.000 | 676.921 | 21.225 | 26.919 |
December | 0.000 | 0.000 | 720.171 | 36.283 | 40.041 |
Annual Sum or Average | 1819.965 | 131.183 | 4783.405 | 168.495 | 375.910 |
Minimum of Months | 0.000 | 0.000 | 27.156 | 0.172 | 24.587 |
Maximum of Months | 466.942 | 39.926 | 720.171 | 36.283 | 41.271 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.842 | 13.658 | 13.839 |
February | 0.000 | 0.000 | 634.558 | 12.925 | 14.271 |
March | 0.250 | 0.000 | 610.375 | 7.384 | 11.275 |
April | 45.426 | 1.258 | 476.007 | 5.074 | 9.623 |
May | 126.525 | 4.022 | 315.514 | 2.045 | 7.402 |
June | 317.715 | 12.394 | 61.884 | 0.180 | 12.574 |
July | 496.522 | 23.013 | 16.625 | 0.041 | 23.054 |
August | 463.404 | 18.588 | 4.875 | 0.007 | 18.595 |
September | 272.461 | 8.473 | 120.551 | 0.412 | 8.945 |
October | 36.417 | 0.568 | 507.892 | 4.401 | 7.747 |
November | 0.000 | 0.000 | 694.204 | 8.342 | 8.800 |
December | 0.000 | 0.000 | 736.267 | 15.950 | 16.091 |
Annual Sum or Average | 1758.721 | 68.317 | 4920.594 | 70.419 | 152.215 |
Minimum of Months | 0.000 | 0.000 | 4.875 | 0.007 | 7.402 |
Maximum of Months | 496.522 | 23.013 | 741.842 | 15.950 | 23.054 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.750 | 32.766 | 32.790 |
February | 0.000 | 0.000 | 642.542 | 29.938 | 30.552 |
March | 11.671 | 0.102 | 626.967 | 17.832 | 20.921 |
April | 63.711 | 2.322 | 466.296 | 12.325 | 18.560 |
May | 180.589 | 7.407 | 274.146 | 5.336 | 16.992 |
June | 358.541 | 20.906 | 47.625 | 0.676 | 27.339 |
July | 521.560 | 36.698 | 13.625 | 0.184 | 39.712 |
August | 494.772 | 29.543 | 4.375 | 0.056 | 32.600 |
September | 320.450 | 14.294 | 89.800 | 1.382 | 22.262 |
October | 60.127 | 1.289 | 512.751 | 12.067 | 17.943 |
November | 0.000 | 0.000 | 698.600 | 21.626 | 23.201 |
December | 0.000 | 0.000 | 737.804 | 36.591 | 37.337 |
Annual Sum or Average | 2011.422 | 112.561 | 4858.280 | 170.779 | 320.208 |
Minimum of Months | 0.000 | 0.000 | 4.375 | 0.056 | 16.992 |
Maximum of Months | 521.560 | 36.698 | 743.750 | 36.591 | 39.712 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 14.000 | 0.384 | 681.254 | 23.613 | 23.998 |
February | 39.138 | 1.997 | 584.104 | 21.574 | 23.570 |
March | 95.050 | 4.237 | 489.462 | 11.793 | 17.742 |
April | 139.720 | 7.498 | 339.937 | 7.519 | 19.232 |
May | 239.218 | 15.261 | 211.735 | 2.961 | 22.610 |
June | 388.073 | 28.103 | 38.060 | 0.256 | 29.003 |
July | 516.357 | 44.549 | 12.312 | 0.055 | 44.700 |
August | 486.142 | 40.006 | 2.875 | 0.010 | 40.045 |
September | 359.748 | 28.385 | 78.357 | 0.638 | 31.800 |
October | 167.221 | 8.231 | 366.167 | 7.117 | 16.803 |
November | 17.667 | 0.384 | 610.854 | 14.095 | 14.479 |
December | 7.250 | 0.171 | 693.525 | 27.026 | 27.197 |
Annual Sum or Average | 2469.584 | 179.207 | 4108.642 | 116.658 | 311.180 |
Minimum of Months | 7.250 | 0.171 | 2.875 | 0.010 | 14.479 |
Maximum of Months | 516.357 | 44.549 | 693.525 | 27.026 | 44.700 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 14.413 | 0.170 | 665.392 | 7.849 | 8.069 |
February | 37.854 | 1.117 | 575.083 | 7.449 | 9.564 |
March | 82.483 | 2.132 | 467.329 | 3.858 | 6.719 |
April | 110.207 | 3.178 | 336.196 | 2.563 | 6.584 |
May | 197.355 | 6.758 | 191.091 | 0.860 | 8.016 |
June | 396.601 | 15.275 | 13.646 | 0.018 | 15.293 |
July | 565.846 | 26.809 | 0.125 | 0.000 | 26.809 |
August | 542.641 | 25.339 | 0.000 | 0.000 | 25.339 |
September | 392.764 | 18.252 | 36.854 | 0.085 | 18.347 |
October | 173.158 | 5.029 | 305.833 | 2.028 | 7.079 |
November | 14.963 | 0.158 | 568.812 | 4.451 | 4.630 |
December | 9.000 | 0.146 | 678.617 | 9.288 | 9.610 |
Annual Sum or Average | 2537.284 | 104.362 | 3838.978 | 38.449 | 146.059 |
Minimum of Months | 9.000 | 0.146 | 0.000 | 0.000 | 4.630 |
Maximum of Months | 565.846 | 26.809 | 678.617 | 9.288 | 26.809 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 6.950 | 0.097 | 665.962 | 21.900 | 25.829 |
February | 33.175 | 1.235 | 580.979 | 20.004 | 23.792 |
March | 85.316 | 2.994 | 451.414 | 10.709 | 21.608 |
April | 126.784 | 4.830 | 318.583 | 7.016 | 19.467 |
May | 233.316 | 10.560 | 161.521 | 2.542 | 22.319 |
June | 413.095 | 23.716 | 11.021 | 0.119 | 27.951 |
July | 558.152 | 40.333 | 0.125 | 0.004 | 42.224 |
August | 534.886 | 35.954 | 0.000 | 0.000 | 36.445 |
September | 388.207 | 24.130 | 27.375 | 0.347 | 31.862 |
October | 146.596 | 5.932 | 296.208 | 6.393 | 24.533 |
November | 4.625 | 0.070 | 568.562 | 13.366 | 21.991 |
December | 6.750 | 0.080 | 679.792 | 24.828 | 28.053 |
Annual Sum or Average | 2537.852 | 149.931 | 3761.543 | 107.229 | 326.074 |
Minimum of Months | 4.625 | 0.070 | 0.000 | 0.000 | 19.467 |
Maximum of Months | 558.152 | 40.333 | 679.792 | 24.828 | 42.224 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 700.885 | 25.004 | 33.374 |
February | 6.479 | 0.079 | 604.125 | 22.130 | 26.273 |
March | 29.305 | 0.653 | 518.479 | 12.716 | 26.137 |
April | 91.558 | 4.436 | 378.199 | 7.989 | 24.212 |
May | 203.311 | 12.040 | 223.569 | 3.097 | 23.721 |
June | 370.323 | 25.466 | 39.812 | 0.280 | 27.336 |
July | 506.988 | 40.999 | 13.375 | 0.068 | 41.387 |
August | 463.204 | 33.329 | 3.750 | 0.015 | 33.605 |
September | 298.517 | 18.245 | 96.806 | 0.829 | 24.736 |
October | 68.112 | 2.198 | 407.540 | 8.131 | 24.894 |
November | 0.000 | 0.000 | 647.200 | 15.757 | 23.375 |
December | 0.000 | 0.000 | 706.142 | 27.958 | 32.639 |
Annual Sum or Average | 2037.798 | 137.446 | 4339.881 | 123.973 | 341.688 |
Minimum of Months | 0.000 | 0.000 | 3.750 | 0.015 | 23.375 |
Maximum of Months | 506.988 | 40.999 | 706.142 | 27.958 | 41.387 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.293 | 9.393 | 9.612 |
February | 0.000 | 0.000 | 623.183 | 8.367 | 9.396 |
March | 7.400 | 0.044 | 566.526 | 4.779 | 7.682 |
April | 60.970 | 1.660 | 416.628 | 3.018 | 7.636 |
May | 162.694 | 4.992 | 222.825 | 0.929 | 6.197 |
June | 381.190 | 14.343 | 13.192 | 0.016 | 14.359 |
July | 563.101 | 25.241 | 0.000 | 0.000 | 25.241 |
August | 527.999 | 20.799 | 0.000 | 0.000 | 20.799 |
September | 319.212 | 9.789 | 50.400 | 0.124 | 9.932 |
October | 52.975 | 0.847 | 438.650 | 2.734 | 5.809 |
November | 0.000 | 0.000 | 659.833 | 5.461 | 6.237 |
December | 0.000 | 0.000 | 724.550 | 10.658 | 10.927 |
Annual Sum or Average | 2075.541 | 77.715 | 4457.080 | 45.480 | 133.827 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.809 |
Maximum of Months | 563.101 | 25.241 | 741.293 | 10.658 | 25.241 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.693 | 24.981 | 25.020 |
February | 0.000 | 0.000 | 627.771 | 21.955 | 23.018 |
March | 21.438 | 0.238 | 567.290 | 12.526 | 16.995 |
April | 79.593 | 2.766 | 407.292 | 8.069 | 15.105 |
May | 213.000 | 8.501 | 177.104 | 2.696 | 18.934 |
June | 405.704 | 22.519 | 10.875 | 0.118 | 26.145 |
July | 559.796 | 38.244 | 0.000 | 0.000 | 39.944 |
August | 530.318 | 31.230 | 0.000 | 0.000 | 31.774 |
September | 352.723 | 15.298 | 34.408 | 0.445 | 22.910 |
October | 73.148 | 1.544 | 442.500 | 8.261 | 17.469 |
November | 0.000 | 0.000 | 668.204 | 15.722 | 19.114 |
December | 0.000 | 0.000 | 727.763 | 27.526 | 28.713 |
Annual Sum or Average | 2235.718 | 120.340 | 4406.901 | 122.298 | 285.141 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 15.105 |
Maximum of Months | 559.796 | 38.244 | 743.693 | 27.526 | 39.944 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.750 | 0.036 | 719.113 | 44.992 | 45.028 |
February | 24.875 | 1.149 | 610.375 | 41.246 | 42.477 |
March | 59.654 | 2.810 | 546.823 | 24.355 | 31.853 |
April | 100.279 | 6.215 | 410.075 | 16.529 | 34.271 |
May | 189.688 | 14.338 | 254.442 | 7.570 | 38.374 |
June | 331.655 | 28.159 | 53.933 | 1.047 | 42.947 |
July | 460.762 | 46.590 | 23.812 | 0.348 | 51.945 |
August | 429.996 | 40.467 | 9.323 | 0.109 | 46.368 |
September | 308.415 | 26.963 | 108.236 | 2.287 | 43.780 |
October | 123.346 | 5.962 | 443.506 | 16.007 | 28.558 |
November | 3.542 | 0.065 | 673.025 | 29.673 | 30.928 |
December | 1.500 | 0.019 | 726.729 | 50.594 | 50.651 |
Annual Sum or Average | 2036.462 | 172.775 | 4579.392 | 234.757 | 487.181 |
Minimum of Months | 1.500 | 0.019 | 9.323 | 0.109 | 28.558 |
Maximum of Months | 460.762 | 46.590 | 726.729 | 50.594 | 51.945 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 715.125 | 15.654 | 15.882 |
February | 24.250 | 0.536 | 606.625 | 14.687 | 16.249 |
March | 50.221 | 1.526 | 552.024 | 8.474 | 12.485 |
April | 75.033 | 3.022 | 451.562 | 6.077 | 12.913 |
May | 158.719 | 7.348 | 315.982 | 2.794 | 10.930 |
June | 325.219 | 17.041 | 95.126 | 0.365 | 17.446 |
July | 484.632 | 30.716 | 29.190 | 0.094 | 30.810 |
August | 454.600 | 27.836 | 8.906 | 0.018 | 27.854 |
September | 324.185 | 18.508 | 138.948 | 0.687 | 19.354 |
October | 113.421 | 3.668 | 446.554 | 5.161 | 8.911 |
November | 0.750 | 0.001 | 673.483 | 10.032 | 10.493 |
December | 0.000 | 0.000 | 721.104 | 18.010 | 18.134 |
Annual Sum or Average | 2011.031 | 110.204 | 4754.631 | 82.052 | 201.462 |
Minimum of Months | 0.000 | 0.000 | 8.906 | 0.018 | 8.911 |
Maximum of Months | 484.632 | 30.716 | 721.104 | 18.010 | 30.810 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 716.588 | 32.803 | 33.761 |
February | 22.150 | 0.602 | 612.375 | 30.117 | 31.787 |
March | 56.680 | 1.990 | 561.091 | 17.534 | 23.934 |
April | 92.319 | 4.139 | 456.071 | 12.355 | 20.331 |
May | 194.079 | 10.032 | 275.125 | 5.615 | 20.793 |
June | 363.332 | 23.912 | 73.975 | 0.867 | 30.604 |
July | 518.946 | 41.877 | 20.458 | 0.254 | 44.648 |
August | 493.868 | 36.258 | 7.125 | 0.076 | 39.920 |
September | 339.798 | 22.795 | 107.444 | 1.567 | 30.884 |
October | 110.650 | 4.390 | 430.667 | 11.581 | 22.196 |
November | 0.250 | 0.000 | 678.000 | 21.761 | 23.725 |
December | 0.000 | 0.000 | 721.125 | 36.884 | 38.033 |
Annual Sum or Average | 2192.073 | 145.995 | 4660.044 | 171.415 | 360.614 |
Minimum of Months | 0.000 | 0.000 | 7.125 | 0.076 | 20.331 |
Maximum of Months | 518.946 | 41.877 | 721.125 | 36.884 | 44.648 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 723.250 | 40.375 | 45.219 |
February | 3.062 | 0.014 | 622.463 | 36.204 | 39.666 |
March | 24.299 | 0.772 | 582.365 | 22.074 | 31.587 |
April | 82.062 | 4.832 | 460.467 | 15.030 | 28.168 |
May | 178.489 | 13.068 | 306.008 | 6.926 | 28.949 |
June | 324.695 | 27.381 | 117.365 | 1.299 | 32.391 |
July | 458.790 | 45.322 | 39.317 | 0.401 | 47.754 |
August | 418.093 | 36.992 | 35.768 | 0.268 | 39.056 |
September | 267.425 | 20.163 | 162.055 | 2.438 | 31.928 |
October | 54.646 | 2.243 | 483.986 | 15.030 | 30.976 |
November | 0.000 | 0.000 | 692.567 | 27.003 | 30.572 |
December | 0.000 | 0.000 | 730.750 | 44.881 | 47.443 |
Annual Sum or Average | 1811.562 | 150.788 | 4956.360 | 211.929 | 433.709 |
Minimum of Months | 0.000 | 0.000 | 35.768 | 0.268 | 28.168 |
Maximum of Months | 458.790 | 45.322 | 730.750 | 44.881 | 47.754 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.604 | 17.457 | 17.502 |
February | 0.000 | 0.000 | 638.029 | 15.936 | 17.241 |
March | 10.491 | 0.150 | 612.521 | 9.659 | 13.781 |
April | 57.883 | 2.149 | 486.415 | 6.659 | 12.172 |
May | 144.798 | 6.369 | 328.595 | 2.883 | 10.198 |
June | 320.911 | 16.506 | 95.370 | 0.352 | 16.881 |
July | 483.454 | 29.652 | 27.333 | 0.088 | 29.740 |
August | 444.376 | 24.527 | 10.000 | 0.019 | 24.546 |
September | 274.093 | 11.860 | 162.638 | 0.808 | 12.849 |
October | 45.000 | 0.923 | 530.606 | 6.324 | 10.548 |
November | 0.000 | 0.000 | 710.008 | 11.309 | 11.577 |
December | 0.000 | 0.000 | 744.000 | 19.802 | 19.802 |
Annual Sum or Average | 1781.007 | 92.136 | 5089.121 | 91.296 | 196.837 |
Minimum of Months | 0.000 | 0.000 | 10.000 | 0.019 | 10.198 |
Maximum of Months | 483.454 | 29.652 | 744.000 | 19.802 | 29.740 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.958 | 34.004 | 34.010 |
February | 0.000 | 0.000 | 645.333 | 30.578 | 31.233 |
March | 19.242 | 0.353 | 632.210 | 18.500 | 21.671 |
April | 68.004 | 3.076 | 483.316 | 12.639 | 18.893 |
May | 183.669 | 9.014 | 287.167 | 5.491 | 18.948 |
June | 359.492 | 23.327 | 74.540 | 0.820 | 29.500 |
July | 521.696 | 40.467 | 19.875 | 0.234 | 43.075 |
August | 491.877 | 33.161 | 7.625 | 0.083 | 36.594 |
September | 307.713 | 16.174 | 118.667 | 1.644 | 23.528 |
October | 54.892 | 1.463 | 535.167 | 12.991 | 18.683 |
November | 0.000 | 0.000 | 711.525 | 22.771 | 23.039 |
December | 0.000 | 0.000 | 744.000 | 37.646 | 37.646 |
Annual Sum or Average | 2006.584 | 127.036 | 5003.383 | 177.402 | 336.822 |
Minimum of Months | 0.000 | 0.000 | 7.625 | 0.083 | 18.683 |
Maximum of Months | 521.696 | 40.467 | 744.000 | 37.646 | 43.075 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 14.971 | 14.971 |
February | 0.000 | 0.000 | 651.229 | 13.103 | 13.847 |
March | 0.000 | 0.000 | 675.931 | 10.645 | 13.081 |
April | 0.000 | 0.000 | 576.387 | 8.138 | 13.285 |
May | 0.000 | 0.000 | 140.497 | 0.182 | 0.924 |
June | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 89.167 | 0.477 | 0.000 | 0.000 | 0.477 |
August | 19.380 | 0.033 | 0.000 | 0.000 | 0.033 |
September | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 285.988 | 0.332 | 0.350 |
November | 0.000 | 0.000 | 713.583 | 9.867 | 10.097 |
December | 0.000 | 0.000 | 744.000 | 15.011 | 15.011 |
Annual Sum or Average | 108.547 | 0.509 | 4531.616 | 72.248 | 82.076 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 89.167 | 0.477 | 744.000 | 15.011 | 15.011 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.37 |
February | 0.00 | 0.00 | 0.37 |
March | 0.00 | 0.00 | 0.56 |
April | 0.00 | 0.00 | 0.63 |
May | 0.00 | 0.00 | 0.77 |
June | 0.00 | 0.00 | 0.93 |
July | 0.00 | 0.00 | 1.05 |
August | 0.00 | 0.00 | 1.02 |
September | 0.00 | 0.00 | 0.93 |
October | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.00 | 1.05 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1706.17 | 1270.29 |
February | 0.00 | 0.00 | 1721.47 | 1157.65 |
March | 0.00 | 0.00 | 1695.23 | 1262.15 |
April | 0.00 | 0.00 | 1642.19 | 1183.21 |
May | 0.00 | 0.00 | 1562.60 | 1163.40 |
June | 0.00 | 0.00 | 1487.59 | 1071.83 |
July | 0.00 | 0.00 | 1438.55 | 1071.04 |
August | 0.00 | 0.00 | 1417.56 | 1055.41 |
September | 0.00 | 0.00 | 1445.42 | 1041.44 |
October | 0.00 | 0.00 | 1502.20 | 1118.43 |
November | 0.00 | 0.00 | 1579.42 | 1137.99 |
December | 0.00 | 0.00 | 1657.34 | 1233.93 |
Annual Sum or Average | 0.00 | 0.00 | 1570.43 | 13766.77 |
Minimum of Months | 0.00 | 0.00 | 1417.56 | 1041.44 |
Maximum of Months | 0.00 | 0.00 | 1721.47 | 1270.29 |