Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42

Tabular Output Report in Format: HTML

Building: MF+CZ4CWH+USA_OR_Salem-McNary.Field.726940+oilfurnace+heatedbsmt+IECC_2009

Environment: ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940

Simulation Timestamp: 2019-02-14 08:42:12


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1016206.10 26.05 34.56
Net Site Energy 1016206.10 26.05 34.56
Total Source Energy 1981852.79 50.81 67.40
Net Source Energy 1981852.79 50.81 67.40


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 283849.29 0.00 0.00 0.00 0.00
Cooling 39162.63 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 21789.16 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 309752.22 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 422604.60 593601.50 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 283849.29 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 39162.63 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 21789.16 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 309752.22 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.05 0.00 0.00 0.00 0.00 0.00
HVAC 2.07 20.19 0.00 0.00 0.00 14.27
Other 10.25 0.00 0.00 0.00 0.00 0.00
Total 14.37 20.19 0.00 0.00 0.00 14.27


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 1.56 15.22 0.00 0.00 0.00 10.76
Other 7.73 0.00 0.00 0.00 0.00 0.00
Total 10.83 15.22 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 422604.598 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 422604.598 100.00
     
Total On-Site and Utility Electric Sources 422604.598 100.00
Total Electricity End Uses 422604.598 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 907.25
Time Setpoint Not Met During Occupied Cooling 73.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 201.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42
RunPeriod ANNUAL
Weather File Salem Mcnary Field OR USA TMY3 WMO#=726940
Latitude [deg] 44.90
Longitude [deg] -123.0
Elevation [ft] 196.86
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.4163 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.5522 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 16-JUL-18:15 23-DEC-07:15 - - - 01-JAN-08:15
Heating 0.00 197.05 0.00 0.00 0.00 0.00
Cooling 40.91 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.91 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 10.65 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 115.67 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 121.60 312.72 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 197.05 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 40.91 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.64 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.82 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 10.65 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 115.67 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 307692.63 0.00 0.00 0.00
Cooling 124028.05 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 69006.27 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 335771.40 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1338388.76 643464.03 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 10.46 0.00 0.00 0.00
Cooling 4.22 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.35 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.42 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 45.52 21.88 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 10.46 0.00 0.00 0.00
Cooling 4.22 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.35 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.42 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 45.52 21.88 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 21.92 0.00 21.92 Wetbulb [F] 413.41 0.00
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 91.94 27.72 66.92 Wetbulb [F] 846.50 0.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.330 0.882              
North Total or Average           531.68 0.350 0.330 0.882              
Non-North Total or Average           1595.05 0.350 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 384876.45 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   23079.15 18432.28 4646.87 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6794.98 5222.27 1572.71 0.77 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8751.24 6835.22 1916.02 0.78 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11410.58 9113.12 2297.46 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   5003.00 3950.23 1052.76 0.79 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6982.07 5576.26 1405.80 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12013.62 9594.74 2418.88 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6313.55 4831.27 1482.27 0.77 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8392.60 6546.50 1846.10 0.78 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10989.82 8777.08 2212.74 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   4862.04 3876.24 985.81 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6694.82 5346.85 1347.97 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13261.80 10591.61 2670.19 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   6981.07 5574.70 1406.37 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9100.27 7124.44 1975.84 0.78 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12877.36 10284.57 2592.79 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   6662.59 5321.11 1341.48 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7968.35 6277.67 1690.68 0.79 3.97    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   2257.03 1674.33 582.71 0.74 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.25 11.08 11.74 11.37
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.22 11.00 11.65 11.24
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.4 3.21 10.95 11.60 11.16
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.25 11.10 11.76 11.40
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.23 11.01 11.66 11.25
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.4 3.19 10.90 11.54 11.09
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.19 10.89 11.54 11.08
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.7 3.22 10.99 11.64 11.23
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.6 3.21 10.96 11.61 11.18
DX COOLING COIL_UNITHEATEDBSMT   0.2 3.30 11.25 11.93 11.64
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 48960.75 52416.37 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 15004.74 15119.02 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 19228.31 19778.62 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 25437.19 26615.08 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 12263.40 12082.03 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 16504.70 16774.51 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 26651.86 27948.99 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 13997.33 14003.28 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 18491.30 18964.59 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 24586.98 25677.60 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 12190.15 11999.77 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 15924.46 16132.41 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 29171.27 30718.41 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 16498.26 16767.39 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 19989.76 20615.95 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 28395.82 29865.97 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 15860.09 16062.64 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 18020.70 18445.76 -
MAIN WATER HEATING COIL_UNITHEATEDBSMT Coil:Heating:Water 6270.02 5328.56 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 865.72 433.55 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 234.01 117.19 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 312.55 156.53 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 428.02 214.35 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 183.03 91.66 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 261.90 131.16 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 450.64 225.68 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 215.29 107.82 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 298.87 149.67 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 412.24 206.45 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 181.68 90.98 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 251.13 125.76 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 497.46 249.13 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 261.79 131.10 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 326.71 163.62 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 483.04 241.91 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 249.92 125.16 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 290.10 145.28 0.50 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.38 0.06 71.58 35.85 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 38.702290 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20195.58 20195.58 16.82 865.720 865.720 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 74.98 74.98 0.00814 86.67 0.00850 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5458.94 5458.94 4.55 234.013 234.013 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 74.98 74.98 0.00828 91.94 0.00850 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7291.20 7291.20 6.07 312.555 312.555 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 74.98 74.98 0.00823 91.94 0.00850 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9984.94 9984.94 8.32 428.021 428.021 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00826 85.98 0.00850 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4269.80 4269.80 3.56 183.031 183.031 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 74.98 74.98 0.00852 83.21 0.00850 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6109.77 6109.77 5.09 261.904 261.904 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 74.98 74.98 0.00830 80.23 0.00850 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10512.64 10512.64 8.76 450.642 450.642 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00824 85.98 0.00850 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5022.20 5022.20 4.18 215.291 215.291 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 74.98 74.98 0.00829 91.94 0.00850 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6971.94 6971.94 5.81 298.868 298.868 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 74.98 74.98 0.00822 91.94 0.00850 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9616.75 9616.75 8.01 412.238 412.238 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 74.98 74.98 0.00827 85.29 0.00850 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4238.27 4238.27 3.53 181.680 181.680 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00857 81.13 0.00850 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5858.41 5858.41 4.88 251.129 251.129 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 74.98 74.98 0.00831 80.23 0.00850 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6767.39 6767.39 5.64 290.096 290.096 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 74.98 74.98 0.00826 89.17 0.00850 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7621.43 7621.43 6.35 326.714 326.714 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 74.98 74.98 0.00822 91.94 0.00850 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11604.86 11604.86 9.67 497.463 497.463 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00823 85.98 0.00850 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5830.18 5830.18 4.86 249.920 249.920 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 74.98 74.98 0.00842 83.21 0.00850 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6107.04 6107.04 5.09 261.788 261.788 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 74.98 74.98 0.00839 84.25 0.00850 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11268.44 11268.44 9.39 483.042 483.042 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 74.98 74.98 0.00825 85.29 0.00850 44.995 0.00
HEATEDBSMT 398.44 398.44 0.05 17.079 44.995 SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB 8/21 18:45:00 74.98 74.98 0.00829 82.17 0.00850 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 21.92 0.00237 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6958.05 6958.05 5.80 127.517 127.517 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00575 21.92 0.00237 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8994.84 8994.84 7.49 164.841 164.841 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00598 21.92 0.00237 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8999.88 8999.88 7.50 164.933 164.933 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00598 21.92 0.00237 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7043.19 7043.19 5.87 129.077 129.077 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00577 21.92 0.00237 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8996.94 8996.94 7.49 164.879 164.879 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00598 21.92 0.00237 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7266.94 7266.94 6.05 133.185 133.185 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00622 21.92 0.00237 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5496.81 5496.81 4.58 100.745 100.745 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00602 21.92 0.00237 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7482.39 7482.39 6.23 137.134 137.134 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00625 21.92 0.00237 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7484.11 7484.11 6.23 137.165 137.165 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00625 21.92 0.00237 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5516.74 5516.74 4.60 101.111 101.111 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00603 21.92 0.00237 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7481.31 7481.31 6.23 137.114 137.114 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00625 21.92 0.00237 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 10471.44 10471.44 8.72 191.900 191.900 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00617 21.92 0.00237 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10472.95 10472.95 8.72 191.928 191.928 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00617 21.92 0.00237 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10440.73 10440.73 8.70 191.338 191.338 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00616 21.92 0.00237 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8503.52 8503.52 7.08 155.840 155.840 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00600 21.92 0.00237 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8499.24 8499.24 7.08 155.761 155.761 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00600 21.92 0.00237 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10473.48 10473.48 8.72 191.938 191.938 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00617 21.92 0.00237 44.995 0.00
HEATEDBSMT 3904.62 3904.62 0.50 71.577 71.577 SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB 12/21 17:30:00 72.00 72.00 0.00800 21.92 0.00237 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 865.72 865.72 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 234.01 234.01 127.52 127.52
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 312.55 312.55 164.84 164.84
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 428.02 428.02 164.93 164.93
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 183.03 183.03 129.08 129.08
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.90 261.90 164.88 164.88
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 450.64 450.64 133.19 133.19
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.29 215.29 100.75 100.75
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 298.87 298.87 137.13 137.13
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 412.24 412.24 137.17 137.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 181.68 181.68 101.11 101.11
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 251.13 251.13 137.11 137.11
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 497.46 497.46 191.34 191.34
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 261.79 261.79 155.76 155.76
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 326.71 326.71 191.93 191.93
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 483.04 483.04 191.94 191.94
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.92 249.92 155.84 155.84
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 290.10 290.10 191.90 191.90
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.99 71.58 71.58


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1000.25 6064.50 22.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 952.50 6289.25 104.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1330.25 6244.00 35.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1121.00 6756.25 79.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 563.25 6798.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1105.25 6580.00 41.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1381.25 6073.50 27.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 875.75 5994.50 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1361.50 6037.50 27.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1150.50 6559.50 66.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 664.25 6487.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1169.00 6369.00 40.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1347.50 6582.75 128.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 1440.50 6374.75 86.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 1392.75 6517.25 83.25
LIVING_UNIT2_BACKROW_TOPFLOOR 940.00 6800.50 51.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 1092.00 6520.25 29.75
LIVING_UNIT1_BACKROW_TOPFLOOR 1302.00 6774.50 135.25
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 1984.75 7161.00 201.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 15.25 0.00 15.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 101.75 16.00 101.75 16.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 110.00 8.00 110.00 8.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 219.00 25.75 219.00 25.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 60.00 52.25 60.00 52.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 58.50 48.00 58.50 48.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20.50 14.25 20.50 14.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3.50 11.25 3.50 11.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 142.00 5.00 142.00 5.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 236.25 22.25 236.25 22.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 25.75 45.00 25.75 45.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 100.50 47.00 100.50 47.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.50 49.50 44.50 49.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 59.75 26.50 59.75 26.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 121.50 20.75 121.50 20.75
LIVING_UNIT2_BACKROW_TOPFLOOR 41.25 43.50 41.25 43.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 8.00 38.25 8.00 38.25
LIVING_UNIT1_BACKROW_TOPFLOOR 175.25 24.00 175.25 24.00
HEATEDBSMT 242.75 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1125.25 73.50 907.25 73.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.271 0.000 0.276
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.233 0.000 0.275
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.264 0.000 0.275
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.263 0.000 0.275
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.232 0.000 0.275
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.264 0.000 0.275
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.116 0.000 0.275
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.084 0.000 0.275
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.116 0.000 0.275
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.116 0.000 0.275
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.084 0.000 0.275
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.116 0.000 0.275
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.264 0.000 0.275
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.264 0.000 0.275
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.264 0.000 0.275
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.232 0.000 0.275
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.233 0.000 0.275
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.264 0.000 0.275
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1890
Defaulted Fields 455
Fields with Defaults 4813
Autosized Fields 342
Autosizable Fields 454
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Fans:Electricity 6381.52 139.94 04-OCT-23:15 3118.76 16-JUL-18:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
ElectricityPurchased:Plant 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
Cogeneration:ElectricityPurchased 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
ElectricityNet:Plant 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
Cogeneration:ElectricityNet 123770.64 7505.52 24-AUG-03:15 35613.91 16-JUL-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 17851.30 529.57 04-OCT-23:15 15715.64 16-JUL-16:00
General:Fans:Electricity 6381.52 139.94 04-OCT-23:15 3118.76 16-JUL-18:30
Cooling:Electricity 11469.78 0.00 01-JAN-03:30 12599.56 16-JUL-16:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 5936.02 0.00 25-FEB-16:00 312497.63 23-DEC-07:15
Gas:Plant 5936.02 0.00 25-FEB-16:00 312497.63 23-DEC-07:15
WaterSystems:Gas 3097.52 0.00 01-JAN-00:15 115981.97 19-FEB-08:15
Water Heater:WaterSystems:Gas 3097.52 0.00 01-JAN-00:15 115981.97 19-FEB-08:15
Heating:Gas 2838.49 0.00 25-FEB-15:45 204930.43 21-DEC-04:00
Boiler:Heating:Gas 2838.49 0.00 25-FEB-15:45 204930.43 21-DEC-04:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 25-JAN-03:00 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 396837.61 1566.06 11-AUG-02:45 197359.51 23-DEC-08:15
PlantLoopHeatingDemand:Plant 169593.23 1566.06 11-AUG-02:45 41980.69 11-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 169593.23 1566.06 11-AUG-02:45 41980.69 11-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1195134.35 15944.68 01-SEP-02:15 518223.56 23-DEC-07:15
EnergyTransfer:Building 391202.62 6492.81 17-JUN-00:30 170846.59 21-DEC-04:00
EnergyTransfer:Zone:HEATEDBSMT 11657.46 0.00 01-MAY-12:00 4822.41 24-APR-22:30
Heating:EnergyTransfer 237126.12 0.00 01-MAY-12:00 170846.59 21-DEC-04:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 11633.80 0.00 01-MAY-12:00 4822.41 24-APR-22:30
Cooling:EnergyTransfer 154076.50 0.00 01-JAN-03:30 145201.03 24-JUN-18:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 23.66 0.00 01-JAN-00:15 567.84 16-JUL-19:45
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63727.74 0.00 01-JAN-03:30 20132.57 24-JUN-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7.12 0.00 01-JAN-00:15 934.56 21-DEC-03:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63720.62 0.00 01-JAN-03:30 20132.57 24-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13932.23 0.00 01-JAN-14:00 14066.69 15-FEB-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9621.54 0.00 01-JAN-14:00 14066.69 15-FEB-14:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4310.69 0.00 01-JAN-00:15 5909.89 24-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20468.90 0.00 19-JAN-11:00 10768.69 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 14252.41 0.00 19-JAN-11:00 10768.69 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6216.49 0.00 01-JAN-00:15 7407.39 09-SEP-13:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 21315.71 0.00 30-JAN-16:00 10686.59 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15851.48 0.00 30-JAN-16:00 10686.59 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5464.23 0.00 01-JAN-00:15 10173.39 23-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15027.88 0.00 25-FEB-15:45 8435.85 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12166.89 0.00 25-FEB-15:45 8435.85 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2860.98 0.00 01-JAN-00:15 4558.75 24-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20601.37 0.00 25-FEB-15:30 10713.13 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15890.76 0.00 25-FEB-15:30 10713.13 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4710.60 0.00 01-JAN-00:15 6204.82 24-JUN-19:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 16878.17 0.00 01-JAN-14:00 10541.65 24-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9317.34 0.00 01-JAN-14:00 8440.81 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7560.83 0.00 01-JAN-00:15 10541.65 24-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 11286.61 0.00 01-JAN-13:00 6709.04 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6603.07 0.00 01-JAN-13:00 6709.04 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4683.54 0.00 01-JAN-00:15 5417.61 24-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16843.26 0.00 01-JAN-13:30 8604.84 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10254.24 0.00 01-JAN-13:30 8604.84 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6589.02 0.00 01-JAN-00:15 7055.51 09-SEP-13:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 17442.42 0.00 30-JAN-16:00 9822.68 24-JUN-19:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11711.36 0.00 30-JAN-16:00 8655.86 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5731.05 0.00 01-JAN-00:15 9822.68 24-JUN-19:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11310.61 0.00 25-FEB-15:15 6387.31 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8101.89 0.00 25-FEB-15:15 6387.31 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3208.72 0.00 01-JAN-00:15 4410.72 24-JUN-19:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16774.57 0.00 25-FEB-15:00 8683.64 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11723.88 0.00 25-FEB-15:00 8683.64 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5050.69 0.00 01-JAN-00:15 5992.09 24-JUN-19:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 24192.58 0.00 25-FEB-15:45 12250.65 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18707.57 0.00 25-FEB-15:45 12250.65 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5485.01 0.00 01-JAN-00:15 7220.09 24-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 23569.44 0.00 19-JAN-12:00 12160.06 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 17201.50 0.00 19-JAN-12:00 12160.06 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 6367.94 0.00 01-JAN-00:15 7934.04 24-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24431.31 0.00 19-JAN-12:45 12098.29 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 17139.97 0.00 19-JAN-12:45 12098.29 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 7291.34 0.00 01-JAN-00:15 11686.97 24-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 18707.77 0.00 25-FEB-16:15 9960.90 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14870.11 0.00 25-FEB-16:15 9960.90 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3837.66 0.00 01-JAN-00:15 6088.62 24-JUN-20:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 17893.16 0.00 19-JAN-12:15 9890.55 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 13260.39 0.00 19-JAN-12:15 9890.55 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4632.77 0.00 01-JAN-00:15 6326.58 24-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 25141.44 0.00 21-FEB-16:30 12227.52 21-DEC-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18810.79 0.00 21-FEB-16:30 12227.52 21-DEC-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 6330.65 0.00 01-JAN-00:15 11520.10 24-JUN-19:45
EnergyTransfer:Plant 396672.66 1566.06 11-AUG-02:45 197030.88 23-DEC-07:15
WaterSystems:EnergyTransfer 169593.23 1566.06 11-AUG-02:45 41980.69 11-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 169593.23 1566.06 11-AUG-02:45 41980.69 11-FEB-09:00
EnergyTransfer:HVAC 407259.08 7060.35 03-JUL-01:30 168596.94 18-JUL-19:00
HeatingCoils:EnergyTransfer 227244.39 0.00 25-FEB-15:45 165032.59 21-DEC-04:00
PlantLoopHeatingDemand:HVAC 227244.39 0.00 25-FEB-15:45 165032.59 21-DEC-04:00
HeatingCoils:PlantLoopHeatingDemand 227244.39 0.00 25-FEB-15:45 165032.59 21-DEC-04:00
CoolingCoils:EnergyTransfer 180014.69 0.00 01-JAN-03:30 168596.94 18-JUL-19:00
Boilers:EnergyTransfer 227079.43 0.00 25-FEB-15:45 163944.35 21-DEC-04:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 7.121 -5306.50 0.000 0.000 2875.343 2771.241 10464.601 7939.662 0.000 360.520 66257.466 0.000 -6557.27 0.000 -20398.12 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 9621.503 -358.98 0.000 0.000 3080.084 2771.241 10464.601 3411.319 0.000 339.591 0.347 0.000 -2481.80 0.000 -17211.13 -5684.77
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 14252.331 -517.69 0.000 0.000 3085.845 2771.241 10464.601 7370.776 0.000 361.244 0.000 0.000 -5945.92 0.000 -18374.20 -7769.47
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 15851.401 -455.04 0.000 0.000 3093.795 2771.241 10464.601 5770.641 0.000 358.772 0.000 0.000 -6240.85 0.000 -18207.39 -8398.05
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 12166.843 -238.25 0.000 0.000 3086.592 2771.241 10464.601 968.025 0.000 334.416 0.000 0.000 -2590.12 0.000 -17150.76 -7189.88
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 15890.685 -392.29 0.000 0.000 3093.356 2771.241 10464.601 5000.646 0.000 356.183 0.000 0.000 -6046.04 0.000 -18268.02 -8552.07
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 9317.277 -629.64 0.000 0.000 3062.438 2771.241 10464.601 8055.609 0.000 259.866 0.000 0.000 -6253.81 0.000 -13285.48 -6831.02
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 6603.032 -390.03 0.000 0.000 3051.120 2771.241 10464.601 3405.251 0.000 239.045 0.000 0.000 -2523.17 0.000 -12204.35 -7123.30
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 10254.173 -548.71 0.000 0.000 3070.043 2771.241 10464.601 7356.715 0.000 260.555 0.000 0.000 -6032.31 0.000 -13263.04 -8293.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 11711.298 -477.26 0.000 0.000 3077.884 2771.241 10464.601 5762.792 0.000 259.548 0.000 0.000 -6327.15 0.000 -13140.35 -8848.89
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 8101.850 -267.21 0.000 0.000 3066.911 2771.241 10464.601 967.287 0.000 236.919 0.000 0.000 -2623.37 0.000 -12083.92 -7692.82
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 11723.813 -420.61 0.000 0.000 3079.321 2771.241 10464.601 4991.313 0.000 257.159 0.000 0.000 -6124.53 0.000 -13177.73 -8934.52
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 18707.486 -456.78 0.000 0.000 3091.359 2771.241 10464.601 5020.160 0.000 350.506 0.000 0.000 -6078.23 0.000 -18313.84 -10528.31
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 17201.419 -530.30 0.000 0.000 3086.201 2771.241 10464.601 7406.090 0.000 355.485 0.000 0.000 -5971.71 0.000 -18388.43 -10557.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 17139.896 -607.20 0.000 0.000 3085.630 2771.241 10464.601 8123.410 0.000 356.342 0.000 0.000 -6137.29 0.000 -18356.44 -10156.16
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 14870.056 -319.59 0.000 0.000 3085.419 2771.241 10464.601 976.709 0.000 333.186 0.000 0.000 -2593.49 0.000 -17199.18 -8870.92
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 13260.344 -385.80 0.000 0.000 3076.862 2771.241 10464.601 3426.525 0.000 333.280 0.000 0.000 -2487.39 0.000 -17294.26 -8918.50
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 18810.715 -527.19 0.000 0.000 3091.914 2771.241 10464.601 5776.805 0.000 356.766 0.000 0.000 -6264.89 0.000 -18268.02 -10408.58
HEATEDBSMT 0.000 0.000 11633.802 -1.97 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -11610.14
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4151.043 38880.147 0.000 0.000 0.000 -43031.19 -0.06
Total Facility 0.000 0.000 237125.045 -12831.05 0.000 0.000 55240.118 49882.340 188362.826 91729.735 0.000 9860.424 105137.961 0.000 -89279.35 0.000 -337615.85 -156367.46


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 24-JUN-18:45 0.00 0.00 0.00 -1.7 0.00 0.00 421.00 813.96 1748.06 5420.56 0.00 1548.02 10241.70 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24-JUN-18:15 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 813.96 1748.06 433.36 0.00 1703.21 785.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 09-SEP-13:30 0.00 0.00 0.00 -0.6 0.00 0.00 114.40 116.28 1109.73 4440.56 0.00 1772.02 0.00 0.00 0.00 0.00 0.00 -145.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 24-JUN-19:33 0.00 0.00 0.00 -0.9 0.00 0.00 420.46 902.05 1689.30 2451.23 0.00 927.57 3833.98 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 24-JUN-20:03 0.00 0.00 0.00 -0.4 0.00 0.00 408.19 902.05 1651.67 23.34 0.00 556.96 1027.85 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 24-JUN-19:33 0.00 0.00 0.00 -0.5 0.00 0.00 424.22 902.05 1689.30 812.15 0.00 953.88 1481.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24-JUN-19:04 0.00 0.00 0.00 -0.9 0.00 0.00 422.84 902.05 1689.30 3760.26 0.00 897.34 2945.68 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24-JUN-18:33 0.00 0.00 0.00 -0.5 0.00 0.00 426.68 813.96 1748.06 350.57 0.00 987.26 1096.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 09-SEP-13:45 0.00 0.00 0.00 -0.6 0.00 0.00 115.07 116.28 1109.73 4247.78 0.00 1227.06 239.63 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 24-JUN-19:33 0.00 0.00 0.00 -0.8 0.00 0.00 418.61 902.05 1689.30 2451.72 0.00 661.23 3776.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 24-JUN-19:33 0.00 0.00 0.00 -0.4 0.00 0.00 406.77 902.05 1689.30 626.41 0.00 564.29 229.89 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24-JUN-19:33 0.00 0.00 0.00 -0.5 0.00 0.00 422.77 902.05 1689.30 817.90 0.00 681.01 1500.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 24-JUN-19:57 0.00 0.00 0.00 -0.6 0.00 0.00 414.25 902.05 1689.30 81.66 0.00 766.82 3377.33 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 24-JUN-18:42 0.00 0.00 0.00 -0.7 0.00 0.00 425.30 813.96 1748.06 848.98 0.00 1568.23 2538.41 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 24-JUN-19:23 0.00 0.00 0.00 -1.0 0.00 0.00 421.31 902.05 1689.30 2810.22 0.00 1116.33 4797.72 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 24-JUN-20:06 0.00 0.00 0.00 -0.5 0.00 0.00 411.08 902.05 1651.67 18.29 0.00 571.25 2551.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 24-JUN-20:00 0.00 0.00 0.00 -0.5 0.00 0.00 418.88 902.05 1689.30 43.49 0.00 741.32 2541.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 24-JUN-19:33 0.00 0.00 0.00 -1.0 0.00 0.00 419.19 902.05 1689.30 2424.95 0.00 915.47 5198.87 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 16-JUL-19:32 0.00 0.00 0.00 -0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 567.84 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-JUN-18:08 0.00 0.00 0.00 -12.1 0.00 0.00 7478.39 14651.21 31465.06 51280.35 0.00 27075.10 27664.43 0.00 0.00 0.00 -14360.8 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 21-DEC-03:30 0.00 0.00 934.58 0.00 0.00 0.00 526.31 62.02 847.43 0.00 0.00 0.00 7079.53 0.00 -2484.1 0.00 -6965.7 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23-DEC-04:51 0.00 0.00 14756.08 0.00 0.00 0.00 687.65 186.05 833.94 0.00 0.00 0.00 0.00 0.00 -844.8 0.00 -4698.3 -10920.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21-DEC-04:00 0.00 0.00 10769.07 0.00 0.00 0.00 526.28 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2498.5 0.00 -7142.2 -2564.1
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20-MAR-09:20 0.00 0.00 19585.61 0.00 0.00 0.00 134.76 116.28 1096.02 317.56 0.00 0.00 0.00 0.00 0.00 0.00 -1423.5 -19826.7
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 06-MAR-17:23 0.00 0.00 10783.44 0.00 0.00 0.00 303.63 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -473.9 0.00 -2018.3 -10863.6
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21-DEC-04:00 0.00 0.00 10713.51 0.00 0.00 0.00 526.33 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2508.0 0.00 -7141.8 -2499.4
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13-MAY-08:43 0.00 0.00 10217.30 0.00 0.00 0.00 221.31 170.54 1179.68 721.19 0.00 0.00 0.00 0.00 0.00 0.00 -1165.0 -11345.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-DEC-04:00 0.00 0.00 6709.20 0.00 0.00 0.00 526.28 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -1020.1 0.00 -4508.8 -2616.0
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 30-JAN-22:40 0.00 0.00 8874.59 0.00 0.00 0.00 551.70 379.85 1340.18 0.00 0.00 0.00 0.00 0.00 -1816.8 0.00 -2874.8 -6454.8
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 01-JAN-14:49 0.00 0.00 18842.87 0.00 0.00 0.00 141.72 116.28 1113.97 1692.40 0.00 0.00 0.00 0.00 0.00 0.00 -2336.0 -19571.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 01-JAN-14:58 0.00 0.00 10747.68 0.00 0.00 0.00 127.31 116.28 1113.97 0.00 0.00 0.00 0.00 0.00 -448.6 0.00 -2306.8 -9349.8
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21-DEC-04:00 0.00 0.00 8683.86 0.00 0.00 0.00 526.29 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2527.6 0.00 -4971.2 -2620.9
LIVING_UNIT3_BACKROW_TOPFLOOR 21-DEC-04:00 0.00 0.00 12251.08 0.00 0.00 0.00 526.30 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2511.1 0.00 -7152.2 -4023.5
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-DEC-04:00 0.00 0.00 12160.49 0.00 0.00 0.00 526.31 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -2507.6 0.00 -7152.2 -3936.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-SEP-08:24 0.00 0.00 17461.02 0.00 0.00 0.00 223.61 170.54 1155.86 759.84 0.00 0.00 0.00 0.00 0.00 0.00 -1074.2 -18696.7
LIVING_UNIT2_BACKROW_TOPFLOOR 18-FEB-15:15 0.00 0.00 10933.11 0.00 0.00 0.00 127.31 201.55 1168.29 0.00 0.00 0.00 0.00 0.00 -216.9 0.00 -2675.3 -9538.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-DEC-04:00 0.00 0.00 9890.90 0.00 0.00 0.00 526.26 62.02 847.43 0.00 0.00 0.00 0.00 0.00 -1017.3 0.00 -6689.8 -3619.4
LIVING_UNIT1_BACKROW_TOPFLOOR 18-FEB-15:06 0.00 0.00 18256.36 0.00 0.00 0.00 136.68 201.55 1168.29 4073.74 0.00 0.00 0.00 0.00 0.00 0.00 -2811.9 -21024.7
HEATEDBSMT 24-APR-22:23 0.00 0.00 4833.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -4833.8
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-DEC-04:00 0.00 0.00 170852.17 0.00 0.00 0.00 9473.26 1116.28 15253.70 0.00 0.00 649.10 0.00 0.00 -36296.0 0.00 -112819.3 -48229.3



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 865.720 2.00 2.00 1.00 44.9950 865.720 0.052 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 234.013 2.00 2.00 1.00 44.9950 234.013 0.192 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 312.555 2.00 2.00 1.00 44.9950 312.555 0.144 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 428.021 2.00 2.00 1.00 44.9950 428.021 0.105 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 183.031 2.00 2.00 1.00 44.9950 183.031 0.246 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.904 2.00 2.00 1.00 44.9950 261.904 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 450.642 2.00 2.00 1.00 44.9950 450.642 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.291 2.00 2.00 1.00 44.9950 215.291 0.209 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 298.868 2.00 2.00 1.00 44.9950 298.868 0.151 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 412.238 2.00 2.00 1.00 44.9950 412.238 0.109 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 181.680 2.00 2.00 1.00 44.9950 181.680 0.248 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 251.129 2.00 2.00 1.00 44.9950 251.129 0.179 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 497.463 2.00 2.00 1.00 44.9950 497.463 0.090 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 261.788 2.00 2.00 1.00 44.9950 261.788 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 326.714 2.00 2.00 1.00 44.9950 326.714 0.138 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 483.042 2.00 2.00 1.00 44.9950 483.042 0.093 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.920 2.00 2.00 1.00 44.9950 249.920 0.180 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 290.096 2.00 2.00 1.00 44.9950 290.096 0.155 1.000 44.9950 0.16
CENTRAL SYSTEM_UNITHEATEDBSMT 44.995 0.00 0.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 127.517 2.00 2.00 1.00 44.9950 127.517 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 164.841 2.00 2.00 1.00 44.9950 164.841 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 164.933 2.00 2.00 1.00 44.9950 164.933 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 129.077 2.00 2.00 1.00 44.9950 129.077 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 164.879 2.00 2.00 1.00 44.9950 164.879 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 133.185 2.00 2.00 1.00 44.9950 133.185 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 100.745 2.00 2.00 1.00 44.9950 100.745 1.000 1.000 44.9950 0.45
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 137.134 2.00 2.00 1.00 44.9950 137.134 1.000 1.000 44.9950 0.33
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 137.165 2.00 2.00 1.00 44.9950 137.165 1.000 1.000 44.9950 0.33
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 101.111 2.00 2.00 1.00 44.9950 101.111 1.000 1.000 44.9950 0.45
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 137.114 2.00 2.00 1.00 44.9950 137.114 1.000 1.000 44.9950 0.33
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 191.338 2.00 2.00 1.00 44.9950 191.338 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 155.761 2.00 2.00 1.00 44.9950 155.761 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 191.928 2.00 2.00 1.00 44.9950 191.928 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 191.938 2.00 2.00 1.00 44.9950 191.938 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 155.840 2.00 2.00 1.00 44.9950 155.840 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 191.900 2.00 2.00 1.00 44.9950 191.900 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNITHEATEDBSMT 71.577 0.00 0.00 1.00 44.9950 71.577 1.000 1.000 44.9950 0.63


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   865.720 865.7202 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   234.013 234.0131 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   312.555 312.5548 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   428.021 428.0215 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   183.031 183.0314 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   261.904 261.9038 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   450.642 450.6420 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   215.291 215.2914 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   298.868 298.8681 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   412.238 412.2382 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   181.680 181.6798 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   251.129 251.1288 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   290.096 290.0959 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   326.714 326.7144 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   497.463 497.4625 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   249.920 249.9199 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   261.788 261.7882 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   483.042 483.0416 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   44.995 44.9950 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 865.72 865.720 865.72 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 234.01 234.013 234.01 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 312.55 312.555 312.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 428.02 428.021 428.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 183.03 183.031 183.03 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.90 261.904 261.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 450.64 450.642 450.64 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.29 215.291 215.29 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 298.87 298.868 298.87 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 412.24 412.238 412.24 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 181.68 181.680 181.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 251.13 251.129 251.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 497.46 497.463 497.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 261.79 261.788 261.79 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 326.71 326.714 326.71 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 483.04 483.042 483.04 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.92 249.920 249.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 290.10 290.096 290.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.995 44.99 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   127.517 127.517 127.517 44.9950 0.353 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   164.841 164.841 164.841 44.9950 0.273 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   164.933 164.933 164.933 44.9950 0.273 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   129.077 129.077 129.077 44.9950 0.349 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   164.879 164.879 164.879 44.9950 0.273 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   133.185 133.185 133.185 44.9950 0.338 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   100.745 100.745 100.745 44.9950 0.447 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   137.134 137.134 137.134 44.9950 0.328 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   137.165 137.165 137.165 44.9950 0.328 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   101.111 101.111 101.111 44.9950 0.445 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   137.114 137.114 137.114 44.9950 0.328 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   191.900 191.900 191.900 44.9950 0.234 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   191.928 191.928 191.928 44.9950 0.234 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   191.338 191.338 191.338 44.9950 0.235 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   155.840 155.840 155.840 44.9950 0.289 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   155.761 155.761 155.761 44.9950 0.289 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   191.938 191.938 191.938 44.9950 0.234 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   71.577 71.577 71.577 44.9950 0.629 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 127.52 127.517 127.52 127.52 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 164.84 164.841 164.84 164.84 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 164.93 164.933 164.93 164.93 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 129.08 129.077 129.08 129.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 164.88 164.879 164.88 164.88 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 133.19 133.185 133.19 133.19 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 100.75 100.745 100.75 100.75 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 137.13 137.134 137.13 137.13 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 137.17 137.165 137.17 137.17 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 101.11 101.111 101.11 101.11 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 137.11 137.114 137.11 137.11 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 191.34 191.338 191.34 191.34 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 155.76 155.761 155.76 155.76 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 191.93 191.928 191.93 191.93 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 191.94 191.938 191.94 191.94 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 155.84 155.840 155.84 155.84 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 191.90 191.900 191.90 191.90 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 71.58 71.577 71.58 71.58 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Sec1.1A-General Information

Data
Weather File ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 907.25
Number of hours cooling loads not met 73.50
Number of hours not met 980.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 2838.49 196913.17 0.00 0.00
Space Cooling 11469.78 11980.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6381.52 3118.59 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3097.52 115584.46 0.00 0.00
Receptacle Equipment 88303.07 15497.32 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 123770.64   5936.02   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 422604.60
Natural Gas 0.00 593601.50
Additional 0.00 0.00
Total 301503.54 1016206.10


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 0.29
Fans-Interior 0.16
Service Water Heating 0.00
Receptacle Equipment 2.26
Miscellaneous 0.08
Subtotal 3.17


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 2.13
Service Water Heating 2.33
Miscellaneous 0.00
Subtotal 4.46


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.91
Space Heating 27.93
Space Cooling 3.85
Fans-Interior 2.14
Service Water Heating 30.48
Receptacle Equipment 29.67
Miscellaneous 1.01



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 71.58
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 865.72
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 234.01
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 312.55
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 428.02
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 183.03
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 261.90
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 450.64
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 215.29
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 298.87
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 412.24
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 181.68
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 251.13
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 290.10
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 326.71
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 497.46
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 249.92
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 261.79
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 483.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 865.72
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 234.01
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 312.55
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 428.02
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 183.03
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.90
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 450.64
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.29
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 298.87
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 412.24
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 181.68
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 251.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 497.46
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 261.79
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 326.71
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 483.04
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.92
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 290.10
CENTRAL SYSTEM_UNITHEATEDBSMT 71.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 865.72 1.92 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 234.01 0.566248 0.768548
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 312.55 0.729270 0.781058
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 428.02 0.950882 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 183.03 0.416916 0.789574
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 261.90 0.581839 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 450.64 1.00 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 215.29 0.526129 0.765223
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 298.87 0.699383 0.780033
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 412.24 0.915818 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 181.68 0.405170 0.797244
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 251.13 0.557902 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 497.46 1.11 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 261.79 0.581756 0.798546
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 326.71 0.758356 0.782882
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 483.04 1.07 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 249.92 0.555216 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 290.10 0.664029 0.787826
DX COOLING COIL_UNITHEATEDBSMT 71.58 0.188086 0.741826
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 865.72 865.72 865.72 1.92 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 234.01 234.01 234.01 0.566248 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 312.55 312.55 312.55 0.729270 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 428.02 428.02 428.02 0.950882 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 183.03 183.03 183.03 0.416916 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 261.90 261.90 261.90 0.581839 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 450.64 450.64 450.64 1.00 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 215.29 215.29 215.29 0.526129 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 298.87 298.87 298.87 0.699383 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 412.24 412.24 412.24 0.915818 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 181.68 181.68 181.68 0.405170 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 251.13 251.13 251.13 0.557902 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 497.46 497.46 497.46 1.11 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 261.79 261.79 261.79 0.581756 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 326.71 326.71 326.71 0.758356 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 483.04 483.04 483.04 1.07 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 249.92 249.92 249.92 0.555216 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 290.10 290.10 290.10 0.664029 1.00
ACANDF_UNITHEATEDBSMT 71.58 71.58 71.58 0.188086 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 48960.75 4.94 696.03
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 15004.74 1.51 204.65
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 19228.31 1.94 266.02
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 25437.19 2.57 356.15
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 12263.40 1.24 164.68
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 16504.70 1.67 226.44
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 26651.86 2.69 373.71
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 13997.33 1.41 189.95
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 18491.30 1.87 255.27
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 24586.98 2.48 343.76
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 12190.15 1.23 163.59
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 15924.46 1.61 217.97
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 29171.27 2.94 410.23
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 16498.26 1.67 226.35
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 19989.76 2.02 277.04
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 28395.82 2.87 398.99
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 15860.09 1.60 217.07
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 18020.70 1.82 248.45
MAIN WATER HEATING COIL_UNITHEATEDBSMT 6270.02 0.632849 76.06
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 865.72
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 234.01
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 312.55
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 428.02
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 183.03
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 261.90
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 450.64
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 215.29
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 298.87
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 412.24
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 181.68
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 251.13
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 497.46
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 261.79
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 326.71
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 483.04
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 249.92
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 290.10
SUPPLY FAN_UNITHEATEDBSMT 71.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.17 97.01
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.17
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 384876.45 38.70
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:42:12

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 739.353 63.198 0.000 0.000 63.198
February 639.234 57.234 0.000 0.000 57.234
March 744.000 95.882 0.000 0.000 95.882
April 720.000 105.791 0.000 0.000 105.791
May 744.000 132.206 0.000 0.000 132.206
June 720.000 156.339 0.000 0.000 156.339
July 744.000 182.676 0.000 0.000 182.676
August 744.000 177.986 0.000 0.000 177.986
September 720.000 154.761 0.000 0.000 154.761
October 744.000 114.255 0.000 0.000 114.255
November 720.000 81.364 0.000 0.000 81.364
December 674.799 57.124 16.468 0.387 57.510
           
Annual Sum or Average 8653.386 1378.816 16.468 0.387 1379.202
Minimum of Months 639.234 57.124 0.000 0.000 57.234
Maximum of Months 744.000 182.676 16.468 0.387 182.676



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 8.667 0.124 690.020 10.774 11.442
February 30.600 0.924 569.226 9.796 14.560
March 61.654 1.661 531.876 5.538 7.199
April 81.217 2.628 437.458 3.942 6.570
May 163.080 5.947 289.658 1.641 7.588
June 337.628 14.003 53.241 0.138 14.142
July 502.410 25.844 14.557 0.030 25.874
August 484.320 24.196 3.000 0.003 24.199
September 348.015 17.393 84.313 0.244 17.637
October 144.770 4.477 384.600 3.008 7.485
November 7.675 0.096 630.917 6.363 6.459
December 7.125 0.072 647.946 11.804 18.056
           
Annual Sum or Average 2177.162 97.364 4336.811 53.281 161.210
Minimum of Months 7.125 0.072 3.000 0.003 6.459
Maximum of Months 502.410 25.844 690.020 11.804 25.874



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 5.221 0.070 693.958 28.221 30.375
February 28.350 1.062 598.108 26.656 29.349
March 69.880 2.458 512.081 14.860 23.081
April 104.804 4.139 405.742 10.518 20.847
May 202.741 9.501 248.752 4.830 20.299
June 367.771 22.316 43.667 0.620 30.140
July 521.183 39.208 12.125 0.166 42.813
August 498.555 34.671 2.375 0.034 37.892
September 354.088 23.209 68.125 1.055 33.179
October 132.791 5.474 373.933 9.374 23.708
November 3.300 0.061 630.238 18.272 24.030
December 3.250 0.044 699.971 32.394 34.389
           
Annual Sum or Average 2291.932 142.213 4289.075 147.002 350.102
Minimum of Months 3.250 0.044 2.375 0.034 20.299
Maximum of Months 521.183 39.208 699.971 32.394 42.813



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 712.938 32.224 38.396
February 6.125 0.098 614.325 29.391 33.497
March 19.268 0.537 562.994 17.420 29.712
April 76.050 3.930 444.465 11.928 26.259
May 173.138 10.993 289.452 5.473 24.587
June 326.544 24.085 95.534 0.916 27.614
July 466.942 39.926 34.042 0.295 41.271
August 427.154 32.082 27.156 0.172 33.390
September 267.038 17.495 147.912 1.752 25.755
October 57.707 2.035 457.495 11.415 28.470
November 0.000 0.000 676.921 21.225 26.919
December 0.000 0.000 720.171 36.283 40.041
           
Annual Sum or Average 1819.965 131.183 4783.405 168.495 375.910
Minimum of Months 0.000 0.000 27.156 0.172 24.587
Maximum of Months 466.942 39.926 720.171 36.283 41.271



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.842 13.658 13.839
February 0.000 0.000 634.558 12.925 14.271
March 0.250 0.000 610.375 7.384 11.275
April 45.426 1.258 476.007 5.074 9.623
May 126.525 4.022 315.514 2.045 7.402
June 317.715 12.394 61.884 0.180 12.574
July 496.522 23.013 16.625 0.041 23.054
August 463.404 18.588 4.875 0.007 18.595
September 272.461 8.473 120.551 0.412 8.945
October 36.417 0.568 507.892 4.401 7.747
November 0.000 0.000 694.204 8.342 8.800
December 0.000 0.000 736.267 15.950 16.091
           
Annual Sum or Average 1758.721 68.317 4920.594 70.419 152.215
Minimum of Months 0.000 0.000 4.875 0.007 7.402
Maximum of Months 496.522 23.013 741.842 15.950 23.054



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.750 32.766 32.790
February 0.000 0.000 642.542 29.938 30.552
March 11.671 0.102 626.967 17.832 20.921
April 63.711 2.322 466.296 12.325 18.560
May 180.589 7.407 274.146 5.336 16.992
June 358.541 20.906 47.625 0.676 27.339
July 521.560 36.698 13.625 0.184 39.712
August 494.772 29.543 4.375 0.056 32.600
September 320.450 14.294 89.800 1.382 22.262
October 60.127 1.289 512.751 12.067 17.943
November 0.000 0.000 698.600 21.626 23.201
December 0.000 0.000 737.804 36.591 37.337
           
Annual Sum or Average 2011.422 112.561 4858.280 170.779 320.208
Minimum of Months 0.000 0.000 4.375 0.056 16.992
Maximum of Months 521.560 36.698 743.750 36.591 39.712



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 14.000 0.384 681.254 23.613 23.998
February 39.138 1.997 584.104 21.574 23.570
March 95.050 4.237 489.462 11.793 17.742
April 139.720 7.498 339.937 7.519 19.232
May 239.218 15.261 211.735 2.961 22.610
June 388.073 28.103 38.060 0.256 29.003
July 516.357 44.549 12.312 0.055 44.700
August 486.142 40.006 2.875 0.010 40.045
September 359.748 28.385 78.357 0.638 31.800
October 167.221 8.231 366.167 7.117 16.803
November 17.667 0.384 610.854 14.095 14.479
December 7.250 0.171 693.525 27.026 27.197
           
Annual Sum or Average 2469.584 179.207 4108.642 116.658 311.180
Minimum of Months 7.250 0.171 2.875 0.010 14.479
Maximum of Months 516.357 44.549 693.525 27.026 44.700



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 14.413 0.170 665.392 7.849 8.069
February 37.854 1.117 575.083 7.449 9.564
March 82.483 2.132 467.329 3.858 6.719
April 110.207 3.178 336.196 2.563 6.584
May 197.355 6.758 191.091 0.860 8.016
June 396.601 15.275 13.646 0.018 15.293
July 565.846 26.809 0.125 0.000 26.809
August 542.641 25.339 0.000 0.000 25.339
September 392.764 18.252 36.854 0.085 18.347
October 173.158 5.029 305.833 2.028 7.079
November 14.963 0.158 568.812 4.451 4.630
December 9.000 0.146 678.617 9.288 9.610
           
Annual Sum or Average 2537.284 104.362 3838.978 38.449 146.059
Minimum of Months 9.000 0.146 0.000 0.000 4.630
Maximum of Months 565.846 26.809 678.617 9.288 26.809



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 6.950 0.097 665.962 21.900 25.829
February 33.175 1.235 580.979 20.004 23.792
March 85.316 2.994 451.414 10.709 21.608
April 126.784 4.830 318.583 7.016 19.467
May 233.316 10.560 161.521 2.542 22.319
June 413.095 23.716 11.021 0.119 27.951
July 558.152 40.333 0.125 0.004 42.224
August 534.886 35.954 0.000 0.000 36.445
September 388.207 24.130 27.375 0.347 31.862
October 146.596 5.932 296.208 6.393 24.533
November 4.625 0.070 568.562 13.366 21.991
December 6.750 0.080 679.792 24.828 28.053
           
Annual Sum or Average 2537.852 149.931 3761.543 107.229 326.074
Minimum of Months 4.625 0.070 0.000 0.000 19.467
Maximum of Months 558.152 40.333 679.792 24.828 42.224



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 700.885 25.004 33.374
February 6.479 0.079 604.125 22.130 26.273
March 29.305 0.653 518.479 12.716 26.137
April 91.558 4.436 378.199 7.989 24.212
May 203.311 12.040 223.569 3.097 23.721
June 370.323 25.466 39.812 0.280 27.336
July 506.988 40.999 13.375 0.068 41.387
August 463.204 33.329 3.750 0.015 33.605
September 298.517 18.245 96.806 0.829 24.736
October 68.112 2.198 407.540 8.131 24.894
November 0.000 0.000 647.200 15.757 23.375
December 0.000 0.000 706.142 27.958 32.639
           
Annual Sum or Average 2037.798 137.446 4339.881 123.973 341.688
Minimum of Months 0.000 0.000 3.750 0.015 23.375
Maximum of Months 506.988 40.999 706.142 27.958 41.387



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.293 9.393 9.612
February 0.000 0.000 623.183 8.367 9.396
March 7.400 0.044 566.526 4.779 7.682
April 60.970 1.660 416.628 3.018 7.636
May 162.694 4.992 222.825 0.929 6.197
June 381.190 14.343 13.192 0.016 14.359
July 563.101 25.241 0.000 0.000 25.241
August 527.999 20.799 0.000 0.000 20.799
September 319.212 9.789 50.400 0.124 9.932
October 52.975 0.847 438.650 2.734 5.809
November 0.000 0.000 659.833 5.461 6.237
December 0.000 0.000 724.550 10.658 10.927
           
Annual Sum or Average 2075.541 77.715 4457.080 45.480 133.827
Minimum of Months 0.000 0.000 0.000 0.000 5.809
Maximum of Months 563.101 25.241 741.293 10.658 25.241



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.693 24.981 25.020
February 0.000 0.000 627.771 21.955 23.018
March 21.438 0.238 567.290 12.526 16.995
April 79.593 2.766 407.292 8.069 15.105
May 213.000 8.501 177.104 2.696 18.934
June 405.704 22.519 10.875 0.118 26.145
July 559.796 38.244 0.000 0.000 39.944
August 530.318 31.230 0.000 0.000 31.774
September 352.723 15.298 34.408 0.445 22.910
October 73.148 1.544 442.500 8.261 17.469
November 0.000 0.000 668.204 15.722 19.114
December 0.000 0.000 727.763 27.526 28.713
           
Annual Sum or Average 2235.718 120.340 4406.901 122.298 285.141
Minimum of Months 0.000 0.000 0.000 0.000 15.105
Maximum of Months 559.796 38.244 743.693 27.526 39.944



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 2.750 0.036 719.113 44.992 45.028
February 24.875 1.149 610.375 41.246 42.477
March 59.654 2.810 546.823 24.355 31.853
April 100.279 6.215 410.075 16.529 34.271
May 189.688 14.338 254.442 7.570 38.374
June 331.655 28.159 53.933 1.047 42.947
July 460.762 46.590 23.812 0.348 51.945
August 429.996 40.467 9.323 0.109 46.368
September 308.415 26.963 108.236 2.287 43.780
October 123.346 5.962 443.506 16.007 28.558
November 3.542 0.065 673.025 29.673 30.928
December 1.500 0.019 726.729 50.594 50.651
           
Annual Sum or Average 2036.462 172.775 4579.392 234.757 487.181
Minimum of Months 1.500 0.019 9.323 0.109 28.558
Maximum of Months 460.762 46.590 726.729 50.594 51.945



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 715.125 15.654 15.882
February 24.250 0.536 606.625 14.687 16.249
March 50.221 1.526 552.024 8.474 12.485
April 75.033 3.022 451.562 6.077 12.913
May 158.719 7.348 315.982 2.794 10.930
June 325.219 17.041 95.126 0.365 17.446
July 484.632 30.716 29.190 0.094 30.810
August 454.600 27.836 8.906 0.018 27.854
September 324.185 18.508 138.948 0.687 19.354
October 113.421 3.668 446.554 5.161 8.911
November 0.750 0.001 673.483 10.032 10.493
December 0.000 0.000 721.104 18.010 18.134
           
Annual Sum or Average 2011.031 110.204 4754.631 82.052 201.462
Minimum of Months 0.000 0.000 8.906 0.018 8.911
Maximum of Months 484.632 30.716 721.104 18.010 30.810



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 716.588 32.803 33.761
February 22.150 0.602 612.375 30.117 31.787
March 56.680 1.990 561.091 17.534 23.934
April 92.319 4.139 456.071 12.355 20.331
May 194.079 10.032 275.125 5.615 20.793
June 363.332 23.912 73.975 0.867 30.604
July 518.946 41.877 20.458 0.254 44.648
August 493.868 36.258 7.125 0.076 39.920
September 339.798 22.795 107.444 1.567 30.884
October 110.650 4.390 430.667 11.581 22.196
November 0.250 0.000 678.000 21.761 23.725
December 0.000 0.000 721.125 36.884 38.033
           
Annual Sum or Average 2192.073 145.995 4660.044 171.415 360.614
Minimum of Months 0.000 0.000 7.125 0.076 20.331
Maximum of Months 518.946 41.877 721.125 36.884 44.648



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 723.250 40.375 45.219
February 3.062 0.014 622.463 36.204 39.666
March 24.299 0.772 582.365 22.074 31.587
April 82.062 4.832 460.467 15.030 28.168
May 178.489 13.068 306.008 6.926 28.949
June 324.695 27.381 117.365 1.299 32.391
July 458.790 45.322 39.317 0.401 47.754
August 418.093 36.992 35.768 0.268 39.056
September 267.425 20.163 162.055 2.438 31.928
October 54.646 2.243 483.986 15.030 30.976
November 0.000 0.000 692.567 27.003 30.572
December 0.000 0.000 730.750 44.881 47.443
           
Annual Sum or Average 1811.562 150.788 4956.360 211.929 433.709
Minimum of Months 0.000 0.000 35.768 0.268 28.168
Maximum of Months 458.790 45.322 730.750 44.881 47.754



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.604 17.457 17.502
February 0.000 0.000 638.029 15.936 17.241
March 10.491 0.150 612.521 9.659 13.781
April 57.883 2.149 486.415 6.659 12.172
May 144.798 6.369 328.595 2.883 10.198
June 320.911 16.506 95.370 0.352 16.881
July 483.454 29.652 27.333 0.088 29.740
August 444.376 24.527 10.000 0.019 24.546
September 274.093 11.860 162.638 0.808 12.849
October 45.000 0.923 530.606 6.324 10.548
November 0.000 0.000 710.008 11.309 11.577
December 0.000 0.000 744.000 19.802 19.802
           
Annual Sum or Average 1781.007 92.136 5089.121 91.296 196.837
Minimum of Months 0.000 0.000 10.000 0.019 10.198
Maximum of Months 483.454 29.652 744.000 19.802 29.740



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.958 34.004 34.010
February 0.000 0.000 645.333 30.578 31.233
March 19.242 0.353 632.210 18.500 21.671
April 68.004 3.076 483.316 12.639 18.893
May 183.669 9.014 287.167 5.491 18.948
June 359.492 23.327 74.540 0.820 29.500
July 521.696 40.467 19.875 0.234 43.075
August 491.877 33.161 7.625 0.083 36.594
September 307.713 16.174 118.667 1.644 23.528
October 54.892 1.463 535.167 12.991 18.683
November 0.000 0.000 711.525 22.771 23.039
December 0.000 0.000 744.000 37.646 37.646
           
Annual Sum or Average 2006.584 127.036 5003.383 177.402 336.822
Minimum of Months 0.000 0.000 7.625 0.083 18.683
Maximum of Months 521.696 40.467 744.000 37.646 43.075



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 14.971 14.971
February 0.000 0.000 651.229 13.103 13.847
March 0.000 0.000 675.931 10.645 13.081
April 0.000 0.000 576.387 8.138 13.285
May 0.000 0.000 140.497 0.182 0.924
June 0.000 0.000 0.000 0.000 0.000
July 89.167 0.477 0.000 0.000 0.477
August 19.380 0.033 0.000 0.000 0.033
September 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 285.988 0.332 0.350
November 0.000 0.000 713.583 9.867 10.097
December 0.000 0.000 744.000 15.011 15.011
           
Annual Sum or Average 108.547 0.509 4531.616 72.248 82.076
Minimum of Months 0.000 0.000 0.000 0.000 0.000
Maximum of Months 89.167 0.477 744.000 15.011 15.011



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.37
February 0.00 0.00 0.37
March 0.00 0.00 0.56
April 0.00 0.00 0.63
May 0.00 0.00 0.77
June 0.00 0.00 0.93
July 0.00 0.00 1.05
August 0.00 0.00 1.02
September 0.00 0.00 0.93
October 0.00 0.00 0.66
November 0.00 0.00 0.49
December 0.00 0.00 0.33
       
Annual Sum or Average 0.00 0.00 0.68
Minimum of Months 0.00 0.00 0.33
Maximum of Months 0.00 0.00 1.05



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.09
July 0.00 0.00 0.16
August 0.00 0.00 0.15
September 0.00 0.00 0.11
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.06
June 0.00 0.00 0.13
July 0.00 0.00 0.23
August 0.00 0.00 0.20
September 0.00 0.00 0.14
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.14
July 0.00 0.00 0.22
August 0.00 0.00 0.18
September 0.00 0.00 0.10
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.02
June 0.00 0.00 0.07
July 0.00 0.00 0.14
August 0.00 0.00 0.11
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.12
July 0.00 0.00 0.21
August 0.00 0.00 0.17
September 0.00 0.00 0.08
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.04
May 0.00 0.00 0.09
June 0.00 0.00 0.16
July 0.00 0.00 0.25
August 0.00 0.00 0.22
September 0.00 0.00 0.16
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.10
July 0.00 0.00 0.17
August 0.00 0.00 0.16
September 0.00 0.00 0.12
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.03
May 0.00 0.00 0.06
June 0.00 0.00 0.14
July 0.00 0.00 0.24
August 0.00 0.00 0.21
September 0.00 0.00 0.15
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.15
July 0.00 0.00 0.23
August 0.00 0.00 0.19
September 0.00 0.00 0.10
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.09
July 0.00 0.00 0.15
August 0.00 0.00 0.12
September 0.00 0.00 0.06
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.05
June 0.00 0.00 0.13
July 0.00 0.00 0.22
August 0.00 0.00 0.18
September 0.00 0.00 0.09
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.04
May 0.00 0.00 0.08
June 0.00 0.00 0.16
July 0.00 0.00 0.26
August 0.00 0.00 0.23
September 0.00 0.00 0.15
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.10
July 0.00 0.00 0.18
August 0.00 0.00 0.16
September 0.00 0.00 0.11
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.18



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.06
June 0.00 0.00 0.14
July 0.00 0.00 0.25
August 0.00 0.00 0.21
September 0.00 0.00 0.14
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.25
August 0.00 0.00 0.21
September 0.00 0.00 0.11
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.10
July 0.00 0.00 0.17
August 0.00 0.00 0.14
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.24
August 0.00 0.00 0.19
September 0.00 0.00 0.10
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:42:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1706.17 1270.29
February 0.00 0.00 1721.47 1157.65
March 0.00 0.00 1695.23 1262.15
April 0.00 0.00 1642.19 1183.21
May 0.00 0.00 1562.60 1163.40
June 0.00 0.00 1487.59 1071.83
July 0.00 0.00 1438.55 1071.04
August 0.00 0.00 1417.56 1055.41
September 0.00 0.00 1445.42 1041.44
October 0.00 0.00 1502.20 1118.43
November 0.00 0.00 1579.42 1137.99
December 0.00 0.00 1657.34 1233.93
         
Annual Sum or Average 0.00 0.00 1570.43 13766.77
Minimum of Months 0.00 0.00 1417.56 1041.44
Maximum of Months 0.00 0.00 1721.47 1270.29