Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:50

Tabular Output Report in Format: HTML

Building: MF+CZ8WH+USA_AK_Fairbanks.Intl.AP.702610+elecres+heatedbsmt+IECC_2012

Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2019-02-14 08:50:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1310509.99 33.60 44.57
Net Site Energy 1310509.99 33.60 44.57
Total Source Energy 4150385.12 106.41 141.15
Net Source Energy 4150385.12 106.41 141.15


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 680623.16 0.00 0.00 0.00 0.00 0.00
Cooling 15150.99 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 22052.24 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 239840.26 0.00 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1310509.99 0.00 0.00 0.00 0.00 377715.79
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 680623.16 0.00 0.00 0.00 0.00 0.00
Cooling General 15150.99 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 22052.24 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 239840.26 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.80 0.00 0.00 0.00 0.00 0.00
HVAC 32.57 0.00 0.00 0.00 0.00 12.85
Other 10.20 0.00 0.00 0.00 0.00 0.00
Total 44.57 0.00 0.00 0.00 0.00 12.85


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 24.55 0.00 0.00 0.00 0.00 9.68
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 33.60 0.00 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1310509.985 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1310509.985 100.00
     
Total On-Site and Utility Electric Sources 1310509.985 100.00
Total Electricity End Uses 1310509.985 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3457.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:50
RunPeriod ANNUAL
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [ft] 436.37
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.4894 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 12-JAN-09:30 - - - - 01-JAN-08:15
Heating 296.53 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1.86 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.07 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.85 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.58 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 134.05 0.00 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 473.93 0.00 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 296.53 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 1.86 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.07 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 1.65 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.64 0.00 0.00 0.00 0.00 0.00
  clotheswasher 1.07 0.00 0.00 0.00 0.00 0.00
  electric_dryer 7.49 0.00 0.00 0.00 0.00 0.00
  electric_range 4.08 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 14.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 0.93 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.58 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 134.05 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 2155533.54 0.00 0.00 0.00 0.00
Cooling 47983.17 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 69839.45 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 759574.09 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4150385.12 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 73.31 0.00 0.00 0.00 0.00
Cooling 1.63 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.38 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 25.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 141.15 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 73.31 0.00 0.00 0.00 0.00
Cooling 1.63 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.38 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 25.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 141.15 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -43.4 0.00 -43.4 Wetbulb [F] 59.06 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 81.32 18.36 60.98 Wetbulb [F] 610.27 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.330 0.882              
North Total or Average           531.68 0.320 0.330 0.882              
Non-North Total or Average           1595.05 0.320 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12875.43 10283.03 2592.40 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7724.08 6168.88 1555.20 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9562.98 7637.53 1925.46 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9625.29 7687.29 1938.00 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7723.44 6168.36 1555.07 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9560.98 7635.93 1925.05 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10770.76 8602.12 2168.64 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6500.78 5191.88 1308.90 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8336.27 6657.81 1678.46 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9543.17 7621.70 1921.47 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6499.98 5191.24 1308.74 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8334.15 6656.11 1678.04 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11172.67 8923.11 2249.56 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9043.44 7222.59 1820.85 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10875.08 8685.44 2189.64 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10879.95 8689.33 2190.62 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9042.07 7221.49 1820.57 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10872.74 8683.57 2189.17 0.80 3.97    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   3231.60 2483.12 748.48 0.77 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNITHEATEDBSMT   0.3 3.25 11.08 11.74 11.37
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   22742.54 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   20981.16 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   24659.05 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   24667.53 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   20979.88 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   24655.05 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   22213.06 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   18533.58 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   22204.30 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   22214.26 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   18531.99 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   22200.06 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   27293.56 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   23619.61 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   27283.04 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   27292.77 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   23616.86 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   27278.36 1.00
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT Coil:Heating:Electric   11463.01 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 482.97 241.87 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 289.74 145.10 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 358.72 179.64 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 361.05 180.81 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 289.71 145.09 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 358.64 179.61 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 404.02 202.33 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 243.85 122.12 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 312.70 156.60 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 357.97 179.27 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 243.82 122.10 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 312.62 156.56 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 419.10 209.88 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.23 169.88 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 407.93 204.29 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 408.12 204.38 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.18 169.86 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 407.85 204.25 0.50 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.38 0.06 111.24 55.71 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11169.58 11169.58 9.30 482.969 482.969 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00811 74.85 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5069.85 5069.85 4.22 219.215 219.215 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6684.40 6684.40 5.57 289.026 289.026 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8350.05 8350.05 6.96 361.053 361.053 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3249.33 3249.33 2.71 140.500 140.500 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00824 70.07 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6156.77 6156.77 5.13 266.213 266.213 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9343.73 9343.73 7.78 404.021 404.021 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4988.20 4988.20 4.15 215.685 215.685 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6740.81 6740.81 5.61 291.466 291.466 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8278.79 8278.79 6.90 357.973 357.973 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00816 73.65 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3417.04 3417.04 2.85 147.752 147.752 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 74.98 74.98 0.00827 69.66 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6078.76 6078.76 5.06 262.840 262.840 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00802 73.56 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5858.66 5858.66 4.88 253.323 253.323 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6674.60 6674.60 5.56 288.602 288.602 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9692.42 9692.42 8.07 419.097 419.097 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00813 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4205.41 4205.41 3.50 181.840 181.840 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00819 70.07 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.20 5097.20 4.25 220.397 220.397 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9044.68 9044.68 7.53 391.089 391.089 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00814 73.65 0.00698 44.995 0.00
HEATEDBSMT 0.00 0.00 0.00 0.000 44.995 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   73.79 32.00 0.00000 81.32 0.00698 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17463.26 17463.26 14.55 322.773 322.773 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00628 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15675.83 15675.83 13.06 289.737 289.737 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00621 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 19408.13 19408.13 16.17 358.716 358.716 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19416.73 19416.73 16.17 358.875 358.875 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15674.53 15674.53 13.06 289.713 289.713 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00621 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19404.07 19404.07 16.16 358.641 358.641 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 16925.75 16925.75 14.10 312.866 312.866 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13191.83 13191.83 10.99 243.850 243.850 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00638 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16916.85 16916.85 14.09 312.701 312.701 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 16926.96 16926.96 14.10 312.888 312.888 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13190.21 13190.21 10.99 243.820 243.820 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00638 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16912.55 16912.55 14.09 312.622 312.622 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 22066.13 22066.13 18.38 407.847 407.847 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 22070.88 22070.88 18.38 407.934 407.934 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 22081.56 22081.56 18.39 408.132 408.132 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 18350.47 18350.47 15.29 339.176 339.176 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00641 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 18353.26 18353.26 15.29 339.228 339.228 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00641 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 22080.76 22080.76 18.39 408.117 408.117 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
HEATEDBSMT 6015.95 6015.95 0.77 111.241 111.241 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:45:00 72.00 72.00 0.00800 -43.4 0.00006 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 482.97 482.97 322.77 322.77
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 219.21 219.21 289.74 289.74
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 289.03 289.03 358.72 358.72
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.05 361.05 358.88 358.88
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 140.50 140.50 289.71 289.71
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 266.21 266.21 358.64 358.64
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 404.02 404.02 312.87 312.87
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.68 215.68 243.85 243.85
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.47 291.47 312.70 312.70
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.97 357.97 312.89 312.89
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.75 147.75 243.82 243.82
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.84 262.84 312.62 312.62
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.10 419.10 408.13 408.13
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.40 220.40 339.23 339.23
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.60 288.60 407.93 407.93
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.09 391.09 408.12 408.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.84 181.84 339.18 339.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.32 253.32 407.85 407.85
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.99 111.24 111.24


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2846.00 6949.25 2376.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1018.75 7181.50 690.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2975.25 6903.75 2309.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3077.50 7466.25 2722.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1085.50 7468.00 950.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3029.75 7197.00 2609.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2976.75 7045.75 2376.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1070.25 7040.00 683.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3033.25 6790.50 2308.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3093.00 7341.75 2701.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1100.00 7286.00 941.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3064.00 7079.25 2599.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3839.50 7191.25 3345.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 3767.25 7020.00 3076.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 3730.25 7268.75 3168.50
LIVING_UNIT2_BACKROW_TOPFLOOR 2778.50 7431.25 2548.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 2603.50 7281.00 2206.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3840.25 7462.75 3414.75
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4417.25 7747.50 3457.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.138 0.000 0.289
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.121 0.000 0.289
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.121 0.000 0.289
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.138 0.000 0.289
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.007
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.007
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1846
Defaulted Fields 455
Fields with Defaults 4639
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Electricity:Plant 70243.39 0.00 01-JAN-00:15 40385.17 14-JAN-08:45
WaterSystems:Electricity 70243.39 0.00 01-JAN-00:15 40385.17 14-JAN-08:45
Water Heater:WaterSystems:Electricity 70243.39 0.00 01-JAN-00:15 40385.17 14-JAN-08:45
Fans:Electricity 6458.57 0.00 01-JUN-03:30 2238.01 11-JUL-18:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
ElectricityPurchased:Plant 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
Cogeneration:ElectricityPurchased 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
ElectricityNet:Plant 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
Cogeneration:ElectricityNet 383816.59 6792.20 01-JUN-03:30 138803.32 12-JAN-09:30
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 210233.94 0.00 01-JUN-03:30 89531.47 12-JAN-10:00
General:Fans:Electricity 6458.57 0.00 01-JUN-03:30 2238.01 11-JUL-18:15
Heating:Electricity 199338.01 0.00 10-MAY-19:00 87300.59 12-JAN-10:00
Cooling:Electricity 4437.36 0.00 01-JAN-00:15 7694.43 29-JUL-17:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
Water:Plant 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
WaterSystems:Water 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
MainsWater:Plant 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
WaterSystems:MainsWater 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 07-NOV-02:15 0.18 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
PlantLoopHeatingDemand:Plant 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
WaterSystems:PlantLoopHeatingDemand 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1732317.85 2265.55 17-JUL-03:00 648540.59 12-JAN-10:00
EnergyTransfer:Building 758544.62 0.00 01-JUN-03:30 305481.36 12-JAN-10:00
EnergyTransfer:Zone:HEATEDBSMT 21330.35 0.00 10-MAY-19:00 5873.05 12-JAN-11:30
Heating:EnergyTransfer 697882.05 0.00 10-MAY-19:00 305481.36 12-JAN-10:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 21330.35 0.00 10-MAY-19:00 5873.05 12-JAN-11:30
Cooling:EnergyTransfer 60662.56 0.00 01-JAN-00:15 101709.16 11-JUL-18:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 37451.46 0.00 11-MAR-14:30 15957.61 12-JAN-09:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29199.66 0.00 11-MAR-14:30 15957.61 12-JAN-09:45
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8251.80 0.00 01-JAN-00:15 10363.48 06-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 32804.90 0.00 20-MAR-13:00 14373.34 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 30142.47 0.00 20-MAR-13:00 14373.34 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2662.43 0.00 01-JAN-00:15 4809.77 29-JUL-15:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 43161.82 0.00 20-MAR-12:30 17864.07 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 38735.62 0.00 20-MAR-12:30 17864.07 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4426.20 0.00 01-JAN-00:15 6844.56 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44715.21 0.00 10-APR-17:30 17872.46 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 42169.34 0.00 10-APR-17:30 17872.46 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2545.87 0.00 01-JAN-00:15 7752.65 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 34313.45 0.00 17-APR-16:45 14382.22 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 32845.31 0.00 17-APR-16:45 14382.22 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1468.15 0.00 01-JAN-00:15 3450.40 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44313.79 0.00 17-APR-13:30 17869.20 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 41259.44 0.00 17-APR-13:30 17869.20 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3054.35 0.00 01-JAN-00:15 7028.03 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 38859.63 0.00 20-MAR-13:45 15601.38 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 34657.04 0.00 20-MAR-13:45 15601.38 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4202.59 0.00 01-JAN-00:15 8475.75 06-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 28318.35 0.00 20-MAR-13:15 12122.11 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 25385.08 0.00 20-MAR-13:15 12122.11 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2933.27 0.00 01-JAN-00:15 4737.70 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 38762.35 0.00 20-MAR-12:30 15604.06 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 34000.60 0.00 20-MAR-12:30 15604.06 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4761.75 0.00 01-JAN-00:15 6818.25 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 40010.10 0.00 10-APR-17:15 15611.64 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 37243.67 0.00 10-APR-17:15 15611.64 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2766.44 0.00 01-JAN-00:15 7657.94 11-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29641.32 0.00 17-APR-16:45 12130.18 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 27901.08 0.00 17-APR-16:45 12130.18 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1740.24 0.00 01-JAN-00:15 3511.18 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 39780.42 0.00 17-APR-13:15 15608.49 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 36401.96 0.00 17-APR-13:15 15608.49 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3378.46 0.00 01-JAN-00:15 6880.41 07-JUL-08:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 51417.01 0.00 17-APR-16:15 20264.70 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 48182.31 0.00 17-APR-16:15 20264.70 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 3234.70 0.00 01-JAN-00:15 6544.62 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 49990.79 0.00 22-MAR-14:15 20260.48 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 45807.42 0.00 22-MAR-14:15 20260.48 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4183.37 0.00 01-JAN-00:15 6571.17 22-JUL-12:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 50489.47 0.00 06-APR-13:15 20258.60 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 46714.81 0.00 06-APR-13:15 20258.60 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3774.66 0.00 01-JAN-00:15 8753.12 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 41478.71 0.00 17-APR-17:00 16791.65 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 39649.99 0.00 17-APR-17:00 16791.65 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1828.72 0.00 01-JAN-00:15 4245.24 29-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 39742.32 0.00 06-APR-12:45 16784.63 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 37114.46 0.00 06-APR-12:45 16784.63 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2627.86 0.00 01-JAN-00:15 4832.30 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 51963.16 0.00 11-APR-16:30 20267.08 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 49141.44 0.00 11-APR-16:30 20267.08 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2821.71 0.00 01-JAN-00:15 8335.91 11-JUL-18:30
EnergyTransfer:Plant 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
WaterSystems:EnergyTransfer 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 223781.39 2170.96 04-SEP-03:00 51554.94 01-JAN-08:45
EnergyTransfer:HVAC 749991.84 0.00 01-JUN-03:30 297869.63 12-JAN-10:00
HeatingCoils:EnergyTransfer 680623.16 0.00 10-MAY-19:00 297869.63 12-JAN-10:00
CoolingCoils:EnergyTransfer 69368.69 0.00 01-JAN-00:15 113032.22 11-JUL-18:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 29199.551 -687.19 0.000 0.000 3062.814 2456.001 10405.511 5534.254 0.000 18.542 1104.016 0.000 -12225.37 0.000 -31303.51 -0.06
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 30142.348 -221.72 0.000 0.000 3095.006 2456.001 10405.511 3376.847 0.000 18.000 0.000 0.000 -4840.30 0.000 -29803.45 -12187.54
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 38735.467 -368.60 0.000 0.000 3097.909 2456.001 10405.511 6825.443 0.000 18.542 0.000 0.000 -11836.47 0.000 -31104.30 -14171.92
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 42169.182 -212.01 0.000 0.000 3109.863 2456.001 10405.511 3091.239 0.000 18.542 0.000 0.000 -12895.07 0.000 -30972.61 -14836.80
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 32845.188 -122.26 0.000 0.000 3107.849 2456.001 10405.511 577.291 0.000 18.000 0.000 0.000 -5343.21 0.000 -29697.30 -12901.17
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 41259.286 -254.36 0.000 0.000 3106.627 2456.001 10405.511 4284.422 0.000 18.542 0.000 0.000 -12512.92 0.000 -31027.42 -14935.71
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 34656.901 -349.98 0.000 0.000 3093.663 2456.001 10405.511 5556.441 0.000 15.798 0.000 0.000 -12262.83 0.000 -25063.83 -14655.07
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 25384.981 -244.27 0.000 0.000 3086.726 2456.001 10405.511 3367.014 0.000 15.262 0.000 0.000 -4872.85 0.000 -23805.73 -13103.66
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 34000.461 -396.55 0.000 0.000 3090.756 2456.001 10405.511 6797.934 0.000 15.798 0.000 0.000 -11921.01 0.000 -25102.87 -14980.85
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 37243.532 -230.38 0.000 0.000 3102.781 2456.001 10405.511 3077.482 0.000 15.798 0.000 0.000 -12988.40 0.000 -24995.55 -15550.71
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 27900.979 -144.92 0.000 0.000 3100.281 2456.001 10405.511 571.990 0.000 15.262 0.000 0.000 -5379.55 0.000 -23721.94 -13608.28
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 36401.830 -281.35 0.000 0.000 3100.376 2456.001 10405.511 4262.054 0.000 15.798 0.000 0.000 -12600.61 0.000 -25038.83 -15623.67
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 48182.150 -269.38 0.000 0.000 3107.122 2456.001 10405.511 4281.617 0.000 18.122 0.000 0.000 -12521.41 0.000 -31062.02 -21632.40
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 45807.248 -348.38 0.000 0.000 3100.224 2456.001 10405.511 6833.288 0.000 18.122 0.000 0.000 -11831.32 0.000 -31121.98 -21483.74
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 46714.641 -314.34 0.000 0.000 3104.774 2456.001 10405.511 5593.152 0.000 18.123 0.000 0.000 -12161.06 0.000 -31062.58 -21293.92
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 39649.861 -152.29 0.000 0.000 3108.196 2456.001 10405.511 577.865 0.000 17.592 0.000 0.000 -5339.25 0.000 -29734.25 -19312.81
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 37114.331 -218.84 0.000 0.000 3099.266 2456.001 10405.511 3381.736 0.000 17.593 0.000 0.000 -4827.33 0.000 -29805.02 -19214.24
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 49141.279 -234.99 0.000 0.000 3110.093 2456.001 10405.511 3089.582 0.000 18.123 0.000 0.000 -12902.29 0.000 -31010.10 -21486.48
HEATEDBSMT 0.000 0.000 21330.352 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -21330.35
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 6563.078 22215.144 0.000 0.000 0.000 -28778.22 -1.18
Total Facility 0.000 0.000 697879.567 -5051.83 0.000 0.000 55784.326 44208.020 187299.191 71079.651 0.000 6874.639 23319.161 0.000 -179261.26 0.000 -544211.51 -302310.59


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 06-JUL-18:25 0.00 0.00 0.00 -0.9 0.00 0.00 427.00 721.37 1713.78 6549.57 0.00 55.72 906.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-15:00 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 103.05 1106.23 2810.00 0.00 602.62 72.70 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6531.74 0.00 0.00 0.00 0.00 0.00 0.00 -59.3 -955.0
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11-JUL-18:05 0.00 0.00 0.00 -0.6 0.00 0.00 427.00 721.37 1713.78 6066.13 0.00 263.99 0.00 0.00 0.00 0.00 0.00 -1438.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 251.20 0.00 366.74 0.00 0.00 0.00 0.00 0.00 -68.4
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.6 0.00 0.00 420.44 343.51 1204.86 7712.11 0.00 0.00 0.00 0.00 0.00 0.00 -455.0 -2197.8
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JUL-18:45 0.00 0.00 0.00 -0.7 0.00 0.00 427.01 721.37 1713.78 6221.47 0.00 47.75 0.00 0.00 0.00 0.00 0.00 -655.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2543.10 0.00 529.41 210.42 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6525.48 0.00 0.00 0.00 0.00 0.00 0.00 -55.1 -979.3
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 721.37 1713.78 5763.20 0.00 203.20 0.00 0.00 0.00 0.00 0.00 -1170.6
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 251.52 0.00 283.34 75.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 07-JUL-07:48 0.00 0.00 0.00 -0.6 0.00 0.00 420.43 343.51 1204.86 7714.21 0.00 0.00 0.00 0.00 0.00 0.00 -417.3 -2384.6
LIVING_UNIT3_BACKROW_TOPFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.5 0.00 0.00 420.44 343.51 1204.86 7719.70 0.00 0.00 0.00 0.00 0.00 0.00 -458.8 -2685.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 22-JUL-11:53 0.00 0.00 0.00 -0.5 0.00 0.00 115.16 103.05 1112.02 4695.31 0.00 290.62 255.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-JUL-18:05 0.00 0.00 0.00 -0.7 0.00 0.00 426.99 721.37 1713.78 6015.45 0.00 259.70 0.00 0.00 0.00 0.00 0.00 -382.4
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUN-19:53 0.00 0.00 0.00 -0.4 0.00 0.00 427.03 799.44 1651.33 438.39 0.00 115.27 814.56 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2542.54 0.00 625.93 209.05 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.7 0.00 0.00 427.00 721.37 1713.78 5743.07 0.00 250.00 0.00 0.00 0.00 0.00 0.00 -519.3
HEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-18:05 0.00 0.00 0.00 -8.5 0.00 0.00 7686.29 12984.58 30848.11 43147.93 0.00 4360.89 17709.81 0.00 0.00 0.00 -15003.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12-JAN-09:45 0.00 0.00 15957.02 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4144.2 0.00 -10918.5 -2209.3
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 14372.81 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1680.7 0.00 -10424.3 -3582.8
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 17863.44 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4154.2 0.00 -10948.8 -4075.4
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 17871.83 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4154.1 0.00 -10948.8 -4084.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 14381.69 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1680.7 0.00 -10424.3 -3591.7
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 17868.57 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4154.1 0.00 -10948.8 -4080.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15600.77 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.6 0.00 -8483.9 -4280.3
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 12121.59 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1679.4 0.00 -7959.2 -3798.0
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15603.42 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.5 0.00 -8483.9 -4283.0
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15611.02 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.4 0.00 -8483.9 -4290.7
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 12129.65 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1679.3 0.00 -7959.2 -3806.2
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15607.85 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.4 0.00 -8483.9 -4287.5
LIVING_UNIT3_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20264.00 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4116.0 0.00 -10957.6 -6505.4
LIVING_UNIT3_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20259.78 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4116.0 0.00 -10957.6 -6501.1
LIVING_UNIT1_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20257.91 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4116.0 0.00 -10957.6 -6499.2
LIVING_UNIT2_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16791.04 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.4 0.00 -10432.7 -6010.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16784.02 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.4 0.00 -10432.7 -6002.9
LIVING_UNIT1_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20266.38 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.9 0.00 -10957.6 -6507.8
HEATEDBSMT 12-JAN-11:30 0.00 0.00 5873.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -5873.0
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-JAN-10:00 0.00 0.00 305470.31 0.00 0.00 0.00 2291.55 1854.94 19523.00 0.00 0.00 4113.77 0.00 0.00 -59733.4 0.00 -179193.3 -94326.9



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 482.969 2.00 2.00 1.00 44.9950 482.969 0.093 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 219.215 2.00 2.00 1.00 44.9950 219.215 0.205 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 289.026 2.00 2.00 1.00 44.9950 289.026 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.053 2.00 2.00 1.00 44.9950 361.053 0.125 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 140.500 2.00 2.00 1.00 44.9950 140.500 0.320 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 266.213 2.00 2.00 1.00 44.9950 266.213 0.169 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 404.021 2.00 2.00 1.00 44.9950 404.021 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.685 2.00 2.00 1.00 44.9950 215.685 0.209 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.466 2.00 2.00 1.00 44.9950 291.466 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.973 2.00 2.00 1.00 44.9950 357.973 0.126 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.752 2.00 2.00 1.00 44.9950 147.752 0.305 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.840 2.00 2.00 1.00 44.9950 262.840 0.171 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.097 2.00 2.00 1.00 44.9950 419.097 0.107 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.397 2.00 2.00 1.00 44.9950 220.397 0.204 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.602 2.00 2.00 1.00 44.9950 288.602 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.089 2.00 2.00 1.00 44.9950 391.089 0.115 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.840 2.00 2.00 1.00 44.9950 181.840 0.247 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.323 2.00 2.00 1.00 44.9950 253.323 0.178 1.000 44.9950 0.18
CENTRAL SYSTEM_UNITHEATEDBSMT 44.995 0.00 0.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 322.773 2.00 2.00 1.00 44.9950 322.773 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 289.737 2.00 2.00 1.00 44.9950 289.737 1.000 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 358.716 2.00 2.00 1.00 44.9950 358.716 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 358.875 2.00 2.00 1.00 44.9950 358.875 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 289.713 2.00 2.00 1.00 44.9950 289.713 1.000 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.641 2.00 2.00 1.00 44.9950 358.641 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 312.866 2.00 2.00 1.00 44.9950 312.866 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.850 2.00 2.00 1.00 44.9950 243.850 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.701 2.00 2.00 1.00 44.9950 312.701 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 312.888 2.00 2.00 1.00 44.9950 312.888 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 243.820 2.00 2.00 1.00 44.9950 243.820 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.622 2.00 2.00 1.00 44.9950 312.622 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.132 2.00 2.00 1.00 44.9950 408.132 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.228 2.00 2.00 1.00 44.9950 339.228 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.934 2.00 2.00 1.00 44.9950 407.934 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.117 2.00 2.00 1.00 44.9950 408.117 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.176 2.00 2.00 1.00 44.9950 339.176 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.847 2.00 2.00 1.00 44.9950 407.847 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNITHEATEDBSMT 111.241 0.00 0.00 1.00 44.9950 111.241 1.000 1.000 44.9950 0.40


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   482.969 482.9691 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   219.215 219.2145 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   289.026 289.0260 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   361.053 361.0534 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   140.500 140.4996 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   266.213 266.2130 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   404.021 404.0210 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   215.685 215.6848 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   291.466 291.4658 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   357.973 357.9731 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   147.752 147.7518 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   262.840 262.8405 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   253.323 253.3230 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   288.602 288.6020 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   419.097 419.0971 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   181.840 181.8401 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   220.397 220.3967 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   391.089 391.0890 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   44.995 44.9950 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 482.97 482.969 482.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 219.21 219.215 219.21 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 289.03 289.026 289.03 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.05 361.053 361.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 140.50 140.500 140.50 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 266.21 266.213 266.21 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 404.02 404.021 404.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.68 215.685 215.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.47 291.466 291.47 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.97 357.973 357.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.75 147.752 147.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.84 262.840 262.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.10 419.097 419.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.40 220.397 220.40 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.60 288.602 288.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.09 391.089 391.09 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.84 181.840 181.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.32 253.323 253.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.995 44.99 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   322.773 322.773 322.773 44.9950 0.139 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   289.737 289.737 289.737 44.9950 0.155 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   358.716 358.716 358.716 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   358.875 358.875 358.875 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   289.713 289.713 289.713 44.9950 0.155 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   358.641 358.641 358.641 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   312.866 312.866 312.866 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   243.850 243.850 243.850 44.9950 0.185 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   312.701 312.701 312.701 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   312.888 312.888 312.888 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   243.820 243.820 243.820 44.9950 0.185 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   312.622 312.622 312.622 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   407.847 407.847 407.847 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   407.934 407.934 407.934 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   408.132 408.132 408.132 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   339.176 339.176 339.176 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   339.228 339.228 339.228 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   408.117 408.117 408.117 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   111.241 111.241 111.241 44.9950 0.404 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 322.77 322.773 322.77 322.77 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 289.74 289.737 289.74 289.74 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 358.72 358.716 358.72 358.72 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 358.88 358.875 358.88 358.88 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 289.71 289.713 289.71 289.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.64 358.641 358.64 358.64 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 312.87 312.866 312.87 312.87 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.85 243.850 243.85 243.85 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.70 312.701 312.70 312.70 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 312.89 312.888 312.89 312.89 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 243.82 243.820 243.82 243.82 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.62 312.622 312.62 312.62 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.13 408.132 408.13 408.13 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.23 339.228 339.23 339.23 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.93 407.934 407.93 407.93 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.12 408.117 408.12 408.12 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.18 339.176 339.18 339.18 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.85 407.847 407.85 407.85 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 111.24 111.241 111.24 111.24 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Sec1.1A-General Information

Data
Weather File ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 543.65 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 20.06 0.00 0.00 0.00 0.00
Space Heating 199338.01 86847.12 0.00 0.00 0.00 0.00
Space Cooling 4437.36 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6458.57 2219.36 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 70243.39 39258.94 0.00 0.00 0.00 0.00
Receptacle Equipment 87836.46 9914.19 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 383816.59   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 1310509.99
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299910.33 1310509.99


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 5.11
Space Cooling 0.11
Fans-Interior 0.17
Service Water Heating 1.80
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 9.84


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 3.37
Space Heating 51.94
Space Cooling 1.16
Fans-Interior 1.68
Service Water Heating 18.30
Receptacle Equipment 22.89
Miscellaneous 0.67



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 111.24
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 482.97
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 289.74
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 358.72
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 361.05
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 289.71
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 358.64
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 404.02
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 243.85
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 312.70
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 357.97
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 243.82
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 312.62
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 407.85
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 407.93
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 419.10
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 339.18
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 339.23
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 408.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 482.97
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 289.74
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 358.72
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.05
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 289.71
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.64
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 404.02
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.85
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.70
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.97
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 243.82
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.62
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.23
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.93
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.85
CENTRAL SYSTEM_UNITHEATEDBSMT 111.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 482.97 1.07 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 289.74 0.643673 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 358.72 0.796915 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 361.05 0.802107 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 289.71 0.643620 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 358.64 0.796748 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 404.02 0.897563 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 243.85 0.541731 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 312.70 0.694689 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 357.97 0.795264 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 243.82 0.541665 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 312.62 0.694512 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 419.10 0.931056 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 339.23 0.753620 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 407.93 0.906257 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 408.12 0.906662 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 339.18 0.753505 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 407.85 0.906062 0.798655
DX COOLING COIL_UNITHEATEDBSMT 111.24 0.269300 0.768388
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 482.97 482.97 482.97 22742.54 1.07 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 289.74 289.74 289.74 20981.16 0.643673 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 358.72 358.72 358.72 24659.05 0.796915 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 361.05 361.05 361.05 24667.53 0.802107 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 289.71 289.71 289.71 20979.88 0.643620 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 358.64 358.64 358.64 24655.05 0.796748 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 404.02 404.02 404.02 22213.06 0.897563 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 243.85 243.85 243.85 18533.58 0.541731 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 312.70 312.70 312.70 22204.30 0.694689 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 357.97 357.97 357.97 22214.26 0.795264 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 243.82 243.82 243.82 18531.99 0.541665 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 312.62 312.62 312.62 22200.06 0.694512 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 419.10 419.10 419.10 27293.56 0.931056 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 339.23 339.23 339.23 23619.61 0.753620 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 407.93 407.93 407.93 27283.04 0.906257 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 408.12 408.12 408.12 27292.77 0.906662 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 339.18 339.18 339.18 23616.86 0.753505 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 407.85 407.85 407.85 27278.36 0.906062 1.00
ACANDF_UNITHEATEDBSMT 111.24 111.24 111.24 11463.01 0.269300 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 482.97
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 289.74
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 358.72
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 361.05
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 289.71
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 358.64
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 404.02
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 243.85
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 312.70
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 357.97
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 243.82
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 312.62
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 419.10
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 339.23
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 407.93
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 408.12
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 339.18
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 407.85
SUPPLY FAN_UNITHEATEDBSMT 111.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 22742.54
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 20981.16
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 24659.05
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 24667.53
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 20979.88
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 24655.05
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 22213.06
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 18533.58
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 22204.30
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 22214.26
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 18531.99
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 22200.06
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 27293.56
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 23619.61
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 27283.04
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 27292.77
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 23616.86
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 27278.36
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT 11463.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:50:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 60.651 60.651
February 0.000 0.000 672.000 46.166 46.166
March 4.442 0.041 698.715 34.075 34.115
April 183.202 10.145 372.801 10.405 20.550
May 437.937 26.182 62.333 0.531 26.713
June 680.475 48.291 0.000 0.000 48.291
July 717.150 53.730 0.000 0.000 53.730
August 646.137 39.253 18.375 0.264 39.517
September 217.654 8.420 245.313 3.021 11.441
October 15.375 0.298 628.938 22.344 22.642
November 0.000 0.000 720.000 56.363 56.363
December 0.000 0.000 744.000 65.636 65.636
           
Annual Sum or Average 2902.371 186.360 4906.474 299.455 485.815
Minimum of Months 0.000 0.000 0.000 0.000 11.441
Maximum of Months 717.150 53.730 744.000 65.636 65.636



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 38.156 38.156
February 0.000 0.000 672.000 29.885 29.885
March 0.000 0.000 735.958 24.272 24.272
April 57.775 1.292 501.613 9.885 11.177
May 224.163 6.578 235.675 1.778 8.356
June 442.295 17.192 22.500 0.084 17.276
July 493.900 21.495 19.750 0.064 21.560
August 372.593 14.271 68.354 0.529 14.800
September 85.125 1.552 447.271 4.769 6.322
October 2.250 0.024 717.750 17.380 17.404
November 0.000 0.000 720.000 35.775 35.775
December 0.000 0.000 744.000 40.930 40.930
           
Annual Sum or Average 1678.100 62.405 5628.871 203.506 265.911
Minimum of Months 0.000 0.000 19.750 0.064 6.322
Maximum of Months 493.900 21.495 744.000 40.930 40.930



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 51.790 51.790
February 0.000 0.000 672.000 40.364 40.364
March 0.000 0.000 733.325 31.639 31.639
April 80.107 2.349 495.087 12.969 15.318
May 331.407 14.929 206.333 2.318 17.247
June 506.077 27.851 27.875 0.161 28.012
July 517.317 33.380 35.250 0.156 33.536
August 390.360 20.089 88.479 0.731 20.820
September 93.071 2.219 469.213 6.945 9.164
October 3.125 0.048 725.500 24.088 24.136
November 0.000 0.000 720.000 48.635 48.635
December 0.000 0.000 744.000 55.359 55.359
           
Annual Sum or Average 1921.464 100.865 5661.063 275.154 376.019
Minimum of Months 0.000 0.000 27.875 0.156 9.164
Maximum of Months 517.317 33.380 744.000 55.359 55.359



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 53.228 53.228
February 0.000 0.000 672.000 43.958 43.958
March 0.000 0.000 744.000 37.994 37.994
April 28.054 1.009 615.425 16.867 17.876
May 139.637 5.656 368.017 3.640 9.296
June 411.779 20.131 32.125 0.190 20.321
July 447.727 21.966 43.708 0.180 22.146
August 255.023 10.294 186.775 1.490 11.784
September 12.317 0.207 597.375 9.745 9.952
October 0.000 0.000 744.000 27.515 27.515
November 0.000 0.000 720.000 50.518 50.518
December 0.000 0.000 744.000 56.021 56.021
           
Annual Sum or Average 1294.538 59.264 6211.425 301.347 360.611
Minimum of Months 0.000 0.000 32.125 0.180 9.296
Maximum of Months 447.727 21.966 744.000 56.021 56.021



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 39.069 39.069
February 0.000 0.000 672.000 32.451 32.451
March 0.000 0.000 744.000 28.509 28.509
April 0.000 0.000 680.958 13.531 13.531
May 85.333 1.502 317.238 2.256 3.758
June 436.804 12.322 20.500 0.083 12.405
July 494.466 15.566 26.000 0.081 15.647
August 269.504 6.543 118.021 0.877 7.420
September 0.000 0.000 598.375 6.722 6.722
October 0.000 0.000 744.000 19.706 19.706
November 0.000 0.000 720.000 37.250 37.250
December 0.000 0.000 744.000 41.215 41.215
           
Annual Sum or Average 1286.107 35.933 6129.092 221.750 257.683
Minimum of Months 0.000 0.000 20.500 0.081 3.758
Maximum of Months 494.466 15.566 744.000 41.215 41.215



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 52.750 52.750
February 0.000 0.000 672.000 43.087 43.087
March 0.000 0.000 744.000 36.017 36.017
April 4.509 0.030 636.988 16.358 16.389
May 258.357 7.986 230.996 2.609 10.595
June 515.205 23.340 25.125 0.155 23.495
July 520.029 27.778 38.000 0.163 27.941
August 326.789 12.231 122.021 0.963 13.193
September 3.442 0.019 579.842 8.635 8.654
October 0.000 0.000 744.000 26.479 26.479
November 0.000 0.000 720.000 50.204 50.204
December 0.000 0.000 744.000 55.648 55.648
           
Annual Sum or Average 1628.331 71.384 6000.972 293.068 364.451
Minimum of Months 0.000 0.000 25.125 0.155 8.654
Maximum of Months 520.029 27.778 744.000 55.648 55.648



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 57.254 57.254
February 0.000 0.000 672.000 44.908 44.908
March 0.000 0.000 732.146 36.079 36.079
April 99.875 4.534 476.188 13.844 18.378
May 259.729 12.646 243.333 2.616 15.262
June 451.552 27.071 23.350 0.119 27.190
July 490.862 29.931 18.375 0.097 30.027
August 373.732 19.538 78.042 0.869 20.408
September 79.000 2.459 476.725 7.928 10.387
October 1.000 0.003 726.625 27.297 27.300
November 0.000 0.000 720.000 53.697 53.697
December 0.000 0.000 744.000 61.240 61.240
           
Annual Sum or Average 1755.750 96.182 5654.783 305.948 402.130
Minimum of Months 0.000 0.000 18.375 0.097 10.387
Maximum of Months 490.862 29.931 744.000 61.240 61.240



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 31.060 31.060
February 0.000 0.000 672.000 24.102 24.102
March 0.000 0.000 730.417 19.205 19.205
April 68.675 1.465 477.875 7.375 8.840
May 251.346 7.270 186.638 1.053 8.323
June 491.896 18.831 15.917 0.035 18.866
July 544.379 23.162 16.250 0.040 23.202
August 403.648 15.367 54.375 0.347 15.714
September 91.208 1.655 415.542 3.625 5.280
October 2.500 0.015 708.625 13.952 13.966
November 0.000 0.000 720.000 29.186 29.186
December 0.000 0.000 744.000 33.491 33.491
           
Annual Sum or Average 1853.652 67.765 5485.638 163.471 231.235
Minimum of Months 0.000 0.000 15.917 0.035 5.280
Maximum of Months 544.379 23.162 744.000 33.491 33.491



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 44.516 44.516
February 0.000 0.000 672.000 34.474 34.474
March 0.000 0.000 731.146 26.551 26.551
April 90.817 2.584 475.396 10.399 12.983
May 357.313 16.063 168.458 1.521 17.584
June 532.871 29.812 19.250 0.087 29.899
July 550.368 34.971 20.250 0.091 35.063
August 423.215 21.355 61.563 0.487 21.842
September 99.208 2.364 450.417 5.677 8.042
October 3.500 0.045 722.542 20.590 20.635
November 0.000 0.000 720.000 41.869 41.869
December 0.000 0.000 744.000 47.731 47.731
           
Annual Sum or Average 2057.293 107.194 5529.021 233.994 341.188
Minimum of Months 0.000 0.000 19.250 0.087 8.042
Maximum of Months 550.368 34.971 744.000 47.731 47.731



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 51.961 51.961
February 0.000 0.000 672.000 42.884 42.884
March 0.000 0.000 744.000 36.868 36.868
April 30.933 1.042 598.600 15.756 16.799
May 157.646 6.101 320.225 2.870 8.971
June 452.945 22.037 22.750 0.120 22.156
July 488.862 23.908 24.750 0.118 24.025
August 285.124 11.207 129.042 1.185 12.393
September 10.900 0.177 582.375 9.331 9.509
October 0.000 0.000 744.000 26.986 26.986
November 0.000 0.000 720.000 49.438 49.438
December 0.000 0.000 744.000 54.781 54.781
           
Annual Sum or Average 1426.410 64.472 6045.742 292.299 356.771
Minimum of Months 0.000 0.000 22.750 0.118 8.971
Maximum of Months 488.862 23.908 744.000 54.781 54.781



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 31.906 31.906
February 0.000 0.000 672.000 26.488 26.488
March 0.000 0.000 744.000 23.121 23.121
April 0.000 0.000 660.333 10.484 10.484
May 105.187 1.952 248.530 1.353 3.305
June 509.837 14.557 12.250 0.033 14.590
July 554.743 17.820 16.000 0.041 17.861
August 305.249 7.680 91.933 0.586 8.266
September 0.000 0.000 570.750 5.268 5.268
October 0.000 0.000 744.000 16.075 16.075
November 0.000 0.000 720.000 30.558 30.558
December 0.000 0.000 744.000 33.753 33.753
           
Annual Sum or Average 1475.017 42.009 5967.796 179.666 221.675
Minimum of Months 0.000 0.000 12.250 0.033 3.305
Maximum of Months 554.743 17.820 744.000 33.753 33.753



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 45.416 45.416
February 0.000 0.000 672.000 37.032 37.032
March 0.000 0.000 744.000 30.669 30.669
April 6.923 0.034 610.662 13.409 13.443
May 294.139 9.072 183.292 1.755 10.827
June 547.815 25.731 18.250 0.085 25.816
July 556.592 29.757 23.125 0.094 29.851
August 358.046 13.542 89.167 0.650 14.192
September 6.083 0.018 555.767 7.215 7.232
October 0.000 0.000 744.000 22.837 22.837
November 0.000 0.000 720.000 43.343 43.343
December 0.000 0.000 744.000 48.001 48.001
           
Annual Sum or Average 1769.598 78.153 5848.263 250.505 328.658
Minimum of Months 0.000 0.000 18.250 0.085 7.232
Maximum of Months 556.592 29.757 744.000 48.001 48.001



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.786 63.786
February 0.000 0.000 672.000 50.690 50.690
March 0.000 0.000 744.000 41.829 41.829
April 62.850 2.804 540.208 17.330 20.135
May 202.871 10.250 324.233 4.078 14.328
June 414.912 25.844 56.642 0.328 26.173
July 440.581 29.015 52.300 0.274 29.290
August 314.214 17.333 171.792 1.550 18.883
September 48.229 1.339 541.500 10.368 11.707
October 0.000 0.000 738.000 31.570 31.570
November 0.000 0.000 720.000 60.092 60.092
December 0.000 0.000 744.000 67.899 67.899
           
Annual Sum or Average 1483.657 86.586 6048.675 349.796 436.382
Minimum of Months 0.000 0.000 52.300 0.274 11.707
Maximum of Months 440.581 29.015 744.000 67.899 67.899



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 48.027 48.027
February 0.000 0.000 672.000 37.911 37.911
March 0.000 0.000 744.000 31.226 31.226
April 35.875 0.665 557.137 13.068 13.734
May 184.208 5.697 275.625 2.525 8.221
June 435.961 18.384 26.883 0.148 18.532
July 487.374 22.989 31.302 0.139 23.128
August 343.879 13.799 101.875 0.833 14.632
September 47.083 0.609 515.083 6.938 7.547
October 0.000 0.000 733.750 22.831 22.831
November 0.000 0.000 720.000 45.337 45.337
December 0.000 0.000 744.000 51.384 51.384
           
Annual Sum or Average 1534.381 62.144 5865.656 260.367 322.511
Minimum of Months 0.000 0.000 26.883 0.139 7.547
Maximum of Months 487.374 22.989 744.000 51.384 51.384



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 62.030 62.030
February 0.000 0.000 672.000 48.830 48.830
March 0.000 0.000 742.875 39.035 39.035
April 51.846 1.180 549.871 16.281 17.460
May 297.138 12.497 220.792 2.804 15.301
June 506.093 28.594 30.625 0.219 28.813
July 521.687 34.491 40.375 0.219 34.711
August 370.875 19.138 105.479 0.993 20.131
September 59.625 0.977 520.321 9.160 10.137
October 0.000 0.000 735.500 29.940 29.940
November 0.000 0.000 720.000 58.560 58.560
December 0.000 0.000 744.000 66.148 66.148
           
Annual Sum or Average 1807.264 96.877 5825.838 334.218 431.095
Minimum of Months 0.000 0.000 30.625 0.219 10.137
Maximum of Months 521.687 34.491 744.000 66.148 66.148



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.094 63.094
February 0.000 0.000 672.000 51.988 51.988
March 0.000 0.000 744.000 44.803 44.803
April 24.167 0.849 622.571 20.034 20.883
May 138.650 5.988 389.817 4.442 10.431
June 412.431 22.601 42.229 0.260 22.861
July 447.336 24.782 52.275 0.254 25.036
August 249.384 11.380 212.296 1.933 13.313
September 6.083 0.118 619.417 12.117 12.235
October 0.000 0.000 744.000 33.129 33.129
November 0.000 0.000 720.000 60.060 60.060
December 0.000 0.000 744.000 66.462 66.462
           
Annual Sum or Average 1278.051 65.719 6306.604 358.576 424.294
Minimum of Months 0.000 0.000 42.229 0.254 10.431
Maximum of Months 447.336 24.782 744.000 66.462 66.462



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 48.926 48.926
February 0.000 0.000 672.000 40.447 40.447
March 0.000 0.000 744.000 35.196 35.196
April 0.000 0.000 679.042 16.576 16.576
May 96.583 2.175 357.083 2.981 5.156
June 440.086 15.295 24.250 0.132 15.426
July 500.641 18.838 31.000 0.136 18.974
August 267.194 7.981 151.063 1.224 9.205
September 0.000 0.000 630.625 8.942 8.942
October 0.000 0.000 744.000 25.122 25.122
November 0.000 0.000 720.000 46.802 46.802
December 0.000 0.000 744.000 51.660 51.660
           
Annual Sum or Average 1304.505 44.289 6241.063 278.145 322.434
Minimum of Months 0.000 0.000 24.250 0.132 5.156
Maximum of Months 500.641 18.838 744.000 51.660 51.660



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 62.941 62.941
February 0.000 0.000 672.000 51.399 51.399
March 0.000 0.000 744.000 43.062 43.062
April 0.000 0.000 657.863 19.591 19.591
May 244.575 7.220 251.750 3.060 10.280
June 519.935 25.574 28.875 0.209 25.782
July 527.812 30.425 40.875 0.219 30.644
August 324.004 13.053 150.162 1.292 14.345
September 0.000 0.000 634.004 11.034 11.034
October 0.000 0.000 744.000 32.253 32.253
November 0.000 0.000 720.000 60.051 60.051
December 0.000 0.000 744.000 66.422 66.422
           
Annual Sum or Average 1616.327 76.272 6131.530 351.531 427.803
Minimum of Months 0.000 0.000 28.875 0.209 10.280
Maximum of Months 527.812 30.425 744.000 66.422 66.422



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 18.586 18.586
February 0.000 0.000 672.000 15.342 15.342
March 0.000 0.000 744.000 14.633 14.633
April 0.000 0.000 720.000 9.953 9.953
May 0.000 0.000 706.467 1.571 1.571
June 0.000 0.000 26.675 0.018 0.018
July 0.000 0.000 13.427 0.003 0.003
August 0.000 0.000 55.125 0.047 0.047
September 0.000 0.000 716.000 2.044 2.044
October 0.000 0.000 744.000 5.889 5.889
November 0.000 0.000 720.000 15.096 15.096
December 0.000 0.000 744.000 18.718 18.718
           
Annual Sum or Average 0.000 0.000 6605.694 101.900 101.900
Minimum of Months 0.000 0.000 13.427 0.003 0.003
Maximum of Months 0.000 0.000 744.000 18.718 18.718



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7665.19 0.00
February 0.00 6459.73 0.00
March 0.00 4306.41 0.00
April 0.00 1358.80 0.00
May 0.00 67.07 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 33.40 0.00
September 0.00 394.46 0.00
October 0.00 2823.87 0.00
November 0.00 7360.77 0.00
December 0.00 8295.19 0.00
       
Annual Sum or Average 0.00 3214.30 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 8295.19 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7415.76 0.00
February 0.00 6430.54 0.00
March 0.00 4717.33 0.00
April 0.00 1985.16 0.00
May 0.00 345.50 0.00
June 0.00 16.86 0.00
July 0.00 12.53 0.00
August 0.00 102.73 0.00
September 0.00 957.80 0.00
October 0.00 3377.87 0.00
November 0.00 7184.75 0.00
December 0.00 7954.80 0.00
       
Annual Sum or Average 0.00 3359.22 0.00
Minimum of Months 0.00 12.53 0.00
Maximum of Months 0.00 7954.80 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9555.14 0.00
February 0.00 8244.88 0.00
March 0.00 5837.33 0.00
April 0.00 2472.48 0.00
May 0.00 427.62 0.00
June 0.00 30.65 0.00
July 0.00 28.74 0.00
August 0.00 134.86 0.00
September 0.00 1324.12 0.00
October 0.00 4444.12 0.00
November 0.00 9272.15 0.00
December 0.00 10213.61 0.00
       
Annual Sum or Average 0.00 4311.57 0.00
Minimum of Months 0.00 28.74 0.00
Maximum of Months 0.00 10213.61 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9760.28 0.00
February 0.00 8924.06 0.00
March 0.00 6966.92 0.00
April 0.00 3196.00 0.00
May 0.00 667.42 0.00
June 0.00 36.03 0.00
July 0.00 33.08 0.00
August 0.00 273.14 0.00
September 0.00 1846.50 0.00
October 0.00 5045.37 0.00
November 0.00 9572.13 0.00
December 0.00 10272.36 0.00
       
Annual Sum or Average 0.00 4693.07 0.00
Minimum of Months 0.00 33.08 0.00
Maximum of Months 0.00 10272.36 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7593.29 0.00
February 0.00 6982.88 0.00
March 0.00 5540.99 0.00
April 0.00 2717.57 0.00
May 0.00 438.56 0.00
June 0.00 16.73 0.00
July 0.00 15.75 0.00
August 0.00 170.36 0.00
September 0.00 1349.99 0.00
October 0.00 3829.97 0.00
November 0.00 7481.07 0.00
December 0.00 8010.35 0.00
       
Annual Sum or Average 0.00 3660.44 0.00
Minimum of Months 0.00 15.75 0.00
Maximum of Months 0.00 8010.35 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9732.65 0.00
February 0.00 8801.67 0.00
March 0.00 6645.38 0.00
April 0.00 3118.79 0.00
May 0.00 481.41 0.00
June 0.00 29.52 0.00
July 0.00 30.07 0.00
August 0.00 177.63 0.00
September 0.00 1646.35 0.00
October 0.00 4885.61 0.00
November 0.00 9571.68 0.00
December 0.00 10267.36 0.00
       
Annual Sum or Average 0.00 4592.49 0.00
Minimum of Months 0.00 29.52 0.00
Maximum of Months 0.00 10267.36 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 8448.48 0.00
February 0.00 7336.60 0.00
March 0.00 5323.90 0.00
April 0.00 2110.99 0.00
May 0.00 386.03 0.00
June 0.00 18.12 0.00
July 0.00 14.26 0.00
August 0.00 128.28 0.00
September 0.00 1208.84 0.00
October 0.00 4027.91 0.00
November 0.00 8187.76 0.00
December 0.00 9036.56 0.00
       
Annual Sum or Average 0.00 3834.31 0.00
Minimum of Months 0.00 14.26 0.00
Maximum of Months 0.00 9036.56 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6335.84 0.00
February 0.00 5443.33 0.00
March 0.00 3917.55 0.00
April 0.00 1554.58 0.00
May 0.00 214.72 0.00
June 0.00 7.43 0.00
July 0.00 8.13 0.00
August 0.00 70.81 0.00
September 0.00 764.10 0.00
October 0.00 2845.95 0.00
November 0.00 6152.04 0.00
December 0.00 6831.65 0.00
       
Annual Sum or Average 0.00 2832.12 0.00
Minimum of Months 0.00 7.43 0.00
Maximum of Months 0.00 6831.65 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 8483.81 0.00
February 0.00 7273.96 0.00
March 0.00 5059.97 0.00
April 0.00 2047.88 0.00
May 0.00 289.92 0.00
June 0.00 17.18 0.00
July 0.00 17.43 0.00
August 0.00 92.90 0.00
September 0.00 1118.06 0.00
October 0.00 3923.98 0.00
November 0.00 8245.21 0.00
December 0.00 9096.53 0.00
       
Annual Sum or Average 0.00 3787.46 0.00
Minimum of Months 0.00 17.18 0.00
Maximum of Months 0.00 9096.53 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 8654.23 0.00
February 0.00 7907.55 0.00
March 0.00 6140.48 0.00
April 0.00 2711.74 0.00
May 0.00 477.96 0.00
June 0.00 20.62 0.00
July 0.00 19.57 0.00
August 0.00 197.41 0.00
September 0.00 1605.95 0.00
October 0.00 4494.60 0.00
November 0.00 8508.42 0.00
December 0.00 9123.84 0.00
       
Annual Sum or Average 0.00 4134.70 0.00
Minimum of Months 0.00 19.57 0.00
Maximum of Months 0.00 9123.84 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6508.66 0.00
February 0.00 5982.33 0.00
March 0.00 4716.56 0.00
April 0.00 2209.90 0.00
May 0.00 275.97 0.00
June 0.00 6.86 0.00
July 0.00 8.37 0.00
August 0.00 119.60 0.00
September 0.00 1110.46 0.00
October 0.00 3279.25 0.00
November 0.00 6441.55 0.00
December 0.00 6885.47 0.00
       
Annual Sum or Average 0.00 3112.82 0.00
Minimum of Months 0.00 6.86 0.00
Maximum of Months 0.00 6885.47 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 8655.83 0.00
February 0.00 7814.10 0.00
March 0.00 5845.23 0.00
April 0.00 2640.77 0.00
May 0.00 334.50 0.00
June 0.00 16.78 0.00
July 0.00 17.96 0.00
August 0.00 123.89 0.00
September 0.00 1420.92 0.00
October 0.00 4352.54 0.00
November 0.00 8536.03 0.00
December 0.00 9148.45 0.00
       
Annual Sum or Average 0.00 4054.96 0.00
Minimum of Months 0.00 16.78 0.00
Maximum of Months 0.00 9148.45 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 11149.11 0.00
February 0.00 9809.20 0.00
March 0.00 7311.13 0.00
April 0.00 3130.13 0.00
May 0.00 712.73 0.00
June 0.00 59.33 0.00
July 0.00 47.95 0.00
August 0.00 270.99 0.00
September 0.00 1872.55 0.00
October 0.00 5518.11 0.00
November 0.00 10853.49 0.00
December 0.00 11868.01 0.00
       
Annual Sum or Average 0.00 5192.72 0.00
Minimum of Months 0.00 47.95 0.00
Maximum of Months 0.00 11868.01 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 8974.97 0.00
February 0.00 7843.61 0.00
March 0.00 5835.36 0.00
April 0.00 2523.54 0.00
May 0.00 471.77 0.00
June 0.00 28.57 0.00
July 0.00 25.88 0.00
August 0.00 155.73 0.00
September 0.00 1339.72 0.00
October 0.00 4266.54 0.00
November 0.00 8754.65 0.00
December 0.00 9602.29 0.00
       
Annual Sum or Average 0.00 4132.40 0.00
Minimum of Months 0.00 25.88 0.00
Maximum of Months 0.00 9602.29 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 11134.49 0.00
February 0.00 9704.12 0.00
March 0.00 7006.86 0.00
April 0.00 3019.79 0.00
May 0.00 503.26 0.00
June 0.00 40.66 0.00
July 0.00 39.40 0.00
August 0.00 178.20 0.00
September 0.00 1699.09 0.00
October 0.00 5374.27 0.00
November 0.00 10861.99 0.00
December 0.00 11873.63 0.00
       
Annual Sum or Average 0.00 5095.27 0.00
Minimum of Months 0.00 39.40 0.00
Maximum of Months 0.00 11873.63 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 11324.38 0.00
February 0.00 10330.81 0.00
March 0.00 8041.51 0.00
April 0.00 3715.59 0.00
May 0.00 797.35 0.00
June 0.00 48.31 0.00
July 0.00 45.51 0.00
August 0.00 346.99 0.00
September 0.00 2247.36 0.00
October 0.00 5946.09 0.00
November 0.00 11139.27 0.00
December 0.00 11928.90 0.00
       
Annual Sum or Average 0.00 5466.11 0.00
Minimum of Months 0.00 45.51 0.00
Maximum of Months 0.00 11928.90 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9143.34 0.00
February 0.00 8368.61 0.00
March 0.00 6577.44 0.00
April 0.00 3201.03 0.00
May 0.00 557.00 0.00
June 0.00 25.40 0.00
July 0.00 25.42 0.00
August 0.00 228.77 0.00
September 0.00 1726.81 0.00
October 0.00 4694.87 0.00
November 0.00 9037.84 0.00
December 0.00 9654.29 0.00
       
Annual Sum or Average 0.00 4414.71 0.00
Minimum of Months 0.00 25.40 0.00
Maximum of Months 0.00 9654.29 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 11298.42 0.00
February 0.00 10215.25 0.00
March 0.00 7729.96 0.00
April 0.00 3634.06 0.00
May 0.00 549.22 0.00
June 0.00 38.70 0.00
July 0.00 39.35 0.00
August 0.00 231.85 0.00
September 0.00 2046.66 0.00
October 0.00 5789.72 0.00
November 0.00 11139.01 0.00
December 0.00 11923.32 0.00
       
Annual Sum or Average 0.00 5359.44 0.00
Minimum of Months 0.00 38.70 0.00
Maximum of Months 0.00 11923.32 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5140.26 0.00
February 0.00 4697.85 0.00
March 0.00 4047.08 0.00
April 0.00 2844.28 0.00
May 0.00 434.52 0.00
June 0.00 5.05 0.00
July 0.00 0.84 0.00
August 0.00 13.08 0.00
September 0.00 584.06 0.00
October 0.00 1628.65 0.00
November 0.00 4314.26 0.00
December 0.00 5176.81 0.00
       
Annual Sum or Average 0.00 2393.56 0.00
Minimum of Months 0.00 0.84 0.00
Maximum of Months 0.00 5176.81 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.06
May 0.00 0.00 0.14
June 0.00 0.00 0.28
July 0.00 0.00 0.30
August 0.00 0.00 0.22
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.10
July 0.00 0.00 0.12
August 0.00 0.00 0.08
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.12



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.16
July 0.00 0.00 0.19
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.11
July 0.00 0.00 0.12
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.12



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.07
July 0.00 0.00 0.08
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.13
July 0.00 0.00 0.15
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.15
July 0.00 0.00 0.17
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.11
July 0.00 0.00 0.13
August 0.00 0.00 0.09
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.17
July 0.00 0.00 0.20
August 0.00 0.00 0.12
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.13
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.05
June 0.00 0.00 0.15
July 0.00 0.00 0.17
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.16
August 0.00 0.00 0.10
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.10
July 0.00 0.00 0.13
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.19
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.14
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.09
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.14
July 0.00 0.00 0.17
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46
Minimum of Months 0.00 0.00 1383.75 997.00
Maximum of Months 0.00 0.00 1613.07 1198.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:50:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1610.28 1198.90
February 0.00 0.00 1613.07 1084.75
March 0.00 0.00 1609.56 1198.36
April 0.00 0.00 1611.68 1161.24
May 0.00 0.00 1590.41 1184.11
June 0.00 0.00 1512.16 1089.53
July 0.00 0.00 1440.11 1072.20
August 0.00 0.00 1386.31 1032.14
September 0.00 0.00 1383.75 997.00
October 0.00 0.00 1421.22 1058.14
November 0.00 0.00 1491.76 1074.83
December 0.00 0.00 1575.83 1173.25
         
Annual Sum or Average 0.00 0.00 1519.98 13324.46