Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44

Tabular Output Report in Format: HTML

Building: MF+CZ8WH+USA_AK_Fairbanks.Intl.AP.702610+oilfurnace+crawlspace+IECC_2012

Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2019-02-14 08:45:06


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1582923.00 40.58 73.25
Net Site Energy 1582923.00 40.58 73.25
Total Source Energy 2553685.66 65.47 118.17
Net Source Energy 2553685.66 65.47 118.17


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 801259.25 0.00 0.00 0.00 0.00
Cooling 21033.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28330.39 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 379456.78 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 402206.97 1180716.03 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 801259.25 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 21033.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 28330.39 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 379456.78 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 2.28 54.64 0.00 0.00 0.00 17.48
Other 13.88 0.00 0.00 0.00 0.00 0.00
Total 18.61 54.64 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 1.27 30.27 0.00 0.00 0.00 9.68
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 10.31 30.27 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 402206.975 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 402206.975 100.00
     
Total On-Site and Utility Electric Sources 402206.975 100.00
Total Electricity End Uses 402206.975 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1725.75
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3581.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44
RunPeriod ANNUAL
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [ft] 436.37
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:15 12-JAN-09:00 - - - 01-JAN-08:45
Heating 0.00 360.47 0.00 0.00 0.00 0.00
Cooling 27.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.57 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.80 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 116.81 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 102.58 477.27 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 360.47 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 27.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.38 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.80 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 116.81 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 868565.02 0.00 0.00 0.00
Cooling 66612.28 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 89722.34 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 411331.15 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1273789.49 1279896.17 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 40.19 0.00 0.00 0.00
Cooling 3.08 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.15 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.03 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 58.94 59.23 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 40.19 0.00 0.00 0.00
Cooling 3.08 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.15 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.03 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 58.94 59.23 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -43.4 0.00 -43.4 Wetbulb [F] 59.06 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 81.32 18.36 60.98 Wetbulb [F] 610.27 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.330 0.882              
North Total or Average           531.68 0.320 0.330 0.882              
Non-North Total or Average           1595.05 0.320 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 461129.26 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   21285.90 17000.10 4285.80 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8208.63 6555.87 1652.76 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10055.89 8031.19 2024.70 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10060.15 8034.59 2025.56 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8208.10 6555.44 1652.66 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10053.90 8029.60 2024.30 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10746.72 8582.92 2163.80 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6552.67 5233.33 1319.35 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8384.36 6696.21 1688.15 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9516.47 7600.38 1916.09 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6551.89 5232.70 1319.19 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8382.24 6694.52 1687.72 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11169.32 8920.44 2248.88 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9049.72 7227.61 1822.11 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10880.29 8689.60 2190.69 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10885.15 8693.49 2191.67 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9048.35 7226.51 1821.84 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10877.95 8687.73 2190.22 0.80 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 48101.24 49791.83 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 21950.16 20827.98 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 25644.78 24950.55 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 25653.31 24960.04 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 21949.10 20826.80 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 25640.81 24946.14 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 27024.58 26484.51 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 18637.35 17101.86 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 22300.46 21217.71 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 24564.40 23746.96 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 18635.79 17100.11 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 22296.23 21212.98 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 27871.50 27424.34 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 23632.18 22708.49 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 27293.46 26782.45 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 27303.18 26793.25 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 23629.43 22705.43 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 27288.78 26777.26 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 798.45 399.86 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 307.91 154.20 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 377.21 188.90 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 377.37 188.98 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 307.89 154.19 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 377.13 188.87 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 403.12 201.88 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 245.80 123.09 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 314.51 157.50 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 356.97 178.77 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 245.77 123.08 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 314.43 157.46 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 418.97 209.82 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.46 170.00 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 408.13 204.39 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 408.31 204.48 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.41 169.98 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 408.04 204.35 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 46.370098 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18465.73 18465.73 15.38 798.454 798.454 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00807 74.85 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4854.46 4854.46 4.04 209.901 209.901 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6470.34 6470.34 5.39 279.770 279.770 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8169.67 8169.67 6.80 353.254 353.254 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3089.70 3089.70 2.57 133.597 133.597 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00825 70.07 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5922.28 5922.28 4.93 256.074 256.074 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9322.88 9322.88 7.77 403.119 403.119 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4959.97 4959.97 4.13 214.464 214.464 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6717.24 6717.24 5.60 290.447 290.447 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8255.63 8255.63 6.88 356.972 356.972 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00816 73.65 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3395.04 3395.04 2.83 146.800 146.800 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 74.98 74.98 0.00827 69.66 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6052.46 6052.46 5.04 261.703 261.703 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00802 73.56 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5855.27 5855.27 4.88 253.176 253.176 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6671.75 6671.75 5.56 288.479 288.479 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9689.51 9689.51 8.07 418.972 418.972 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00813 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4201.88 4201.88 3.50 181.688 181.688 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00819 70.07 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5093.16 5093.16 4.24 220.222 220.222 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9041.20 9041.20 7.53 390.939 390.939 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00814 73.65 0.00698 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10465.59 10465.59 8.72 193.448 193.448 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00551 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16659.14 16659.14 13.88 307.913 307.913 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00629 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20408.42 20408.42 17.00 377.206 377.206 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00648 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20417.07 20417.07 17.01 377.366 377.366 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00648 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16658.07 16658.07 13.88 307.894 307.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00629 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20404.38 20404.38 17.00 377.131 377.131 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00648 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 17022.87 17022.87 14.18 314.661 314.661 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00660 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13297.13 13297.13 11.08 245.797 245.797 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00639 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17014.43 17014.43 14.17 314.505 314.505 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00660 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 17024.53 17024.53 14.18 314.692 314.692 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00660 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13295.55 13295.55 11.07 245.768 245.768 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00639 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 17010.14 17010.14 14.17 314.426 314.426 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00660 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 22076.71 22076.71 18.39 408.042 408.042 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 22081.45 22081.45 18.39 408.130 408.130 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 22092.08 22092.08 18.40 408.326 408.326 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 18363.23 18363.23 15.30 339.412 339.412 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 18366.01 18366.01 15.30 339.464 339.464 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 22091.33 22091.33 18.40 408.312 408.312 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 798.45 798.45 193.45 193.45
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 209.90 209.90 307.91 307.91
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 279.77 279.77 377.21 377.21
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 353.25 353.25 377.37 377.37
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.60 133.60 307.89 307.89
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 256.07 256.07 377.13 377.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.12 403.12 314.66 314.66
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 214.46 214.46 245.80 245.80
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 290.45 290.45 314.51 314.51
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 356.97 356.97 314.69 314.69
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 146.80 146.80 245.77 245.77
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 261.70 261.70 314.43 314.43
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.97 418.97 408.33 408.33
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.22 220.22 339.46 339.46
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.48 288.48 408.13 408.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 390.94 390.94 408.31 408.31
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.69 181.69 339.41 339.41
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.18 253.18 408.04 408.04


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2514.75 7279.25 2170.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3098.50 7379.50 2854.25
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3382.50 7075.50 2805.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3476.00 7626.75 3181.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1873.50 7682.00 1781.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3335.25 7339.25 2987.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2940.00 7064.00 2349.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1437.50 7086.25 1073.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3095.75 6827.75 2385.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3201.75 7383.25 2822.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1184.75 7336.25 1034.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3105.50 7110.75 2651.75
LIVING_UNIT3_BACKROW_TOPFLOOR 3846.25 7197.75 3354.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 3778.00 7026.50 3088.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 3729.25 7276.50 3170.25
LIVING_UNIT2_BACKROW_TOPFLOOR 2790.75 7442.50 2563.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 2686.75 7288.00 2293.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3897.50 7474.25 3475.25
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4518.00 7916.25 3581.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1236.25 0.00 1236.25 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 19.00 0.00 19.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 231.00 0.00 231.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 27.00 0.00 27.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.75 0.00 0.75 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.25 0.00 44.25 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12.00 0.00 12.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 52.75 0.00 52.75 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 242.00 0.00 242.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18.50 0.00 18.50 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11.75 0.00 11.75 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 2.00 0.00 2.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10.75 0.00 10.75 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 122.00 0.00 122.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 17.75 0.00 17.75 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5.00 0.00 5.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 200.00 0.00 200.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1725.75 0.00 1725.75 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.290
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.119 0.000 0.288
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.121 0.000 0.289
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.138 0.000 0.289
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1867
Defaulted Fields 446
Fields with Defaults 4736
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Fans:Electricity 8297.28 138.59 12-JUN-04:00 2651.15 12-JAN-10:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
ElectricityPurchased:Plant 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
Cogeneration:ElectricityPurchased 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
ElectricityNet:Plant 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
Cogeneration:ElectricityNet 117796.67 7319.70 12-JUN-04:00 30042.73 29-JUL-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 14457.41 527.50 12-JUN-04:00 10446.71 29-JUL-17:15
General:Fans:Electricity 8297.28 138.59 12-JUN-04:00 2651.15 12-JAN-10:00
Cooling:Electricity 6160.13 0.00 01-JAN-00:15 8155.87 29-JUL-17:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 11807.16 0.00 17-APR-16:30 476934.41 12-JAN-10:00
Gas:Plant 11807.16 0.00 17-APR-16:30 476934.41 12-JAN-10:00
WaterSystems:Gas 3794.57 0.00 01-JAN-00:15 118005.15 15-JAN-08:30
Water Heater:WaterSystems:Gas 3794.57 0.00 01-JAN-00:15 118005.15 15-JAN-08:30
Heating:Gas 8012.59 0.00 17-APR-16:30 360210.82 12-JAN-10:00
Boiler:Heating:Gas 8012.59 0.00 17-APR-16:30 360210.82 12-JAN-10:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
Water:Plant 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
WaterSystems:Water 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
MainsWater:Plant 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
WaterSystems:MainsWater 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 25-OCT-02:30 0.18 01-JAN-08:45


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 865587.99 2173.13 28-AUG-03:00 334133.72 12-JAN-08:15
PlantLoopHeatingDemand:Plant 223779.61 2170.94 04-SEP-02:15 51553.29 04-MAR-08:15
WaterSystems:PlantLoopHeatingDemand 223779.61 2170.94 04-SEP-02:15 51553.29 04-MAR-08:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2360746.82 16860.54 12-JUN-04:00 920264.71 12-JAN-10:00
EnergyTransfer:Building 753262.77 6722.31 12-JUN-04:00 297976.61 12-JAN-10:00
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 663373.76 0.00 17-APR-17:15 297976.61 12-JAN-10:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 89889.01 0.00 01-JAN-00:15 107852.30 11-JUL-18:15
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44426.82 0.00 01-JAN-00:15 17462.52 06-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4428.03 0.00 01-JAN-00:15 9221.41 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 39998.79 0.00 01-JAN-00:15 17462.52 06-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29895.74 0.00 20-MAR-13:15 19400.79 12-NOV-23:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 27633.12 0.00 20-MAR-13:15 19400.79 12-NOV-23:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2262.62 0.00 01-JAN-00:15 4590.55 29-JUL-15:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 45882.12 0.00 20-MAR-13:15 18765.36 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 41944.01 0.00 20-MAR-13:15 18765.36 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3938.11 0.00 01-JAN-00:15 6605.70 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 47078.60 0.00 12-APR-18:15 18776.07 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44860.33 0.00 12-APR-18:15 18776.07 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2218.27 0.00 01-JAN-00:15 7561.63 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 36774.36 0.00 17-APR-17:15 15269.02 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 35599.53 0.00 17-APR-17:15 15269.02 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1174.83 0.00 01-JAN-00:15 3297.67 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 46689.83 0.00 17-APR-16:30 18770.28 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44030.74 0.00 17-APR-16:30 18770.28 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2659.09 0.00 01-JAN-00:15 6794.34 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 38404.16 0.00 20-MAR-13:30 15690.09 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 34250.90 0.00 20-MAR-13:30 15690.09 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4153.26 0.00 01-JAN-00:15 8447.25 06-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29643.79 0.00 20-MAR-13:15 12218.56 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26801.53 0.00 20-MAR-13:15 12218.56 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2842.26 0.00 01-JAN-00:15 4701.79 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 39093.56 0.00 20-MAR-12:30 15691.73 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 34428.70 0.00 20-MAR-12:30 15691.73 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4664.86 0.00 01-JAN-00:15 6790.98 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 40138.42 0.00 11-APR-18:15 15699.17 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 37463.46 0.00 11-APR-18:15 15699.17 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2674.96 0.00 01-JAN-00:15 7632.73 11-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29966.32 0.00 17-APR-17:00 12226.43 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 28305.65 0.00 17-APR-17:00 12226.43 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1660.68 0.00 01-JAN-00:15 3485.83 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 40048.76 0.00 17-APR-13:30 15696.04 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 36752.36 0.00 17-APR-13:30 15696.04 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3296.40 0.00 01-JAN-00:15 6851.98 07-JUL-08:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 51464.18 0.00 17-APR-16:15 20273.37 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 48245.86 0.00 17-APR-16:15 20273.37 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 3218.32 0.00 01-JAN-00:15 6540.64 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 50048.04 0.00 22-MAR-14:15 20269.18 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 45883.30 0.00 22-MAR-14:15 20269.18 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4164.74 0.00 01-JAN-00:15 6567.94 22-JUL-12:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 50316.44 0.00 06-APR-13:00 20267.91 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 46566.52 0.00 06-APR-13:00 20267.91 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3749.92 0.00 01-JAN-00:15 8749.16 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 41551.58 0.00 17-APR-17:15 16805.12 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 39741.16 0.00 17-APR-17:15 16805.12 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1810.42 0.00 01-JAN-00:15 4241.26 29-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 39938.18 0.00 06-APR-12:45 16798.25 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 37329.77 0.00 06-APR-12:45 16798.25 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2608.41 0.00 01-JAN-00:15 4825.95 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 51901.87 0.00 12-APR-18:00 20278.07 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 49108.79 0.00 12-APR-18:00 20278.07 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2793.08 0.00 01-JAN-00:15 8331.84 11-JUL-18:30
EnergyTransfer:Plant 864787.01 2173.13 28-AUG-03:00 333357.38 12-JAN-10:00
WaterSystems:EnergyTransfer 223779.61 2170.94 04-SEP-02:15 51553.29 04-MAR-08:15
Domestic Hot Water:WaterSystems:EnergyTransfer 223779.61 2170.94 04-SEP-02:15 51553.29 04-MAR-08:15
EnergyTransfer:HVAC 742697.04 7059.50 07-JUN-03:15 288930.72 12-JAN-10:00
HeatingCoils:EnergyTransfer 641808.38 0.00 17-APR-16:30 288930.72 12-JAN-10:00
PlantLoopHeatingDemand:HVAC 641808.38 0.00 17-APR-16:30 288930.72 12-JAN-10:00
HeatingCoils:PlantLoopHeatingDemand 641808.38 0.00 17-APR-16:30 288930.72 12-JAN-10:00
CoolingCoils:EnergyTransfer 100888.66 0.00 01-JAN-00:15 119605.99 11-JUL-18:15
Boilers:EnergyTransfer 641007.40 0.00 17-APR-16:30 288168.66 12-JAN-10:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 4428.003 -3331.00 0.000 0.000 2960.751 2456.001 10405.511 5506.264 0.000 18.542 58668.872 0.000 -12383.86 0.000 -32061.31 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 27633.048 -188.42 0.000 0.000 3215.117 2456.001 10405.511 3409.588 0.000 18.000 0.139 0.000 -4670.74 0.000 -28674.80 -11529.12
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 41943.855 -327.95 0.000 0.000 3103.656 2456.001 10405.511 6858.459 0.000 18.542 0.000 0.000 -11746.53 0.000 -31067.66 -18033.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 44860.170 -184.73 0.000 0.000 3118.636 2456.001 10405.511 3131.843 0.000 18.542 0.000 0.000 -12803.35 0.000 -30893.38 -18075.70
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 35599.412 -97.84 0.000 0.000 3115.162 2456.001 10405.511 588.590 0.000 17.999 0.000 0.000 -5302.91 0.000 -29651.40 -16053.54
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 44030.584 -221.44 0.000 0.000 3112.003 2456.001 10405.511 4311.840 0.000 18.542 0.000 0.000 -12429.08 0.000 -30992.94 -18253.38
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 34250.765 -345.87 0.000 0.000 3094.446 2456.001 10405.511 5554.973 0.000 15.798 0.000 0.000 -12273.32 0.000 -25059.79 -14291.14
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 26801.432 -236.70 0.000 0.000 3088.353 2456.001 10405.511 3371.344 0.000 15.263 0.000 0.000 -4855.65 0.000 -23797.17 -14642.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 34428.568 -388.48 0.000 0.000 3092.661 2456.001 10405.511 6804.217 0.000 15.798 0.000 0.000 -11905.51 0.000 -25093.62 -15538.79
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 37463.327 -222.76 0.000 0.000 3107.499 2456.001 10405.511 3095.328 0.000 15.798 0.000 0.000 -12967.49 0.000 -24953.47 -15947.54
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 28305.547 -138.30 0.000 0.000 3102.460 2456.001 10405.511 574.764 0.000 15.262 0.000 0.000 -5372.15 0.000 -23710.91 -14115.80
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 36752.233 -274.52 0.000 0.000 3102.004 2456.001 10405.511 4267.645 0.000 15.798 0.000 0.000 -12587.15 0.000 -25030.59 -16085.06
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 48245.701 -268.01 0.000 0.000 3107.520 2456.001 10405.511 4282.974 0.000 18.122 0.000 0.000 -12518.80 0.000 -31059.45 -21719.27
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 45883.138 -346.83 0.000 0.000 3100.709 2456.001 10405.511 6834.791 0.000 18.122 0.000 0.000 -11828.31 0.000 -31118.92 -21586.32
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 46566.359 -312.28 0.000 0.000 3106.470 2456.001 10405.511 5598.563 0.000 18.123 0.000 0.000 -12160.94 0.000 -31045.08 -21195.11
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 39741.037 -150.77 0.000 0.000 3108.927 2456.001 10405.511 578.701 0.000 17.592 0.000 0.000 -5337.39 0.000 -29729.56 -19430.40
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 37329.642 -217.22 0.000 0.000 3099.691 2456.001 10405.511 3382.672 0.000 17.593 0.000 0.000 -4824.75 0.000 -29801.93 -19456.03
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 49108.627 -232.60 0.000 0.000 3112.906 2456.001 10405.511 3101.889 0.000 18.123 0.000 0.000 -12895.08 0.000 -30976.07 -21538.83
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1089.859 183268.021 0.000 0.000 0.000 -184357.88 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 6561.139 22204.706 0.000 0.000 0.000 -28765.84 -3.82
Total Facility 0.000 0.000 663371.446 -7485.73 0.000 0.000 55848.972 44208.020 187299.191 71254.445 0.000 7962.557 264141.738 0.000 -178863.00 0.000 -727841.77 -297496.41


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 06-JUL-18:30 0.00 0.00 0.00 -1.5 0.00 0.00 426.99 721.37 1713.78 6553.14 0.00 55.68 8080.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-15:00 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 103.05 1106.23 2811.91 0.00 602.62 0.00 0.00 0.00 0.00 0.00 -148.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6536.28 0.00 0.00 0.00 0.00 0.00 0.00 -59.3 -1198.4
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11-JUL-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 427.03 721.37 1713.78 6069.91 0.00 263.96 0.00 0.00 0.00 0.00 0.00 -1630.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 252.91 0.00 366.74 0.00 0.00 0.00 0.00 0.00 -222.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.6 0.00 0.00 420.44 343.51 1204.86 7716.34 0.00 0.00 0.00 0.00 0.00 0.00 -455.0 -2435.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JUL-18:45 0.00 0.00 0.00 -0.7 0.00 0.00 427.01 721.37 1713.78 6222.02 0.00 47.75 0.00 0.00 0.00 0.00 0.00 -684.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2543.42 0.00 529.42 174.18 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6526.00 0.00 0.00 0.00 0.00 0.00 0.00 -55.1 -1007.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 721.37 1713.78 5763.71 0.00 203.20 0.00 0.00 0.00 0.00 0.00 -1196.3
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 251.80 0.00 283.34 49.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 07-JUL-07:48 0.00 0.00 0.00 -0.6 0.00 0.00 420.43 343.51 1204.86 7714.73 0.00 0.00 0.00 0.00 0.00 0.00 -417.3 -2413.5
LIVING_UNIT3_BACKROW_TOPFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.5 0.00 0.00 420.44 343.51 1204.86 7719.77 0.00 0.00 0.00 0.00 0.00 0.00 -458.8 -2689.1
LIVING_UNIT3_FRONTROW_TOPFLOOR 22-JUL-11:53 0.00 0.00 0.00 -0.5 0.00 0.00 115.16 103.05 1112.02 4695.38 0.00 290.62 251.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-JUL-18:05 0.00 0.00 0.00 -0.7 0.00 0.00 426.99 721.37 1713.78 6015.53 0.00 259.70 0.00 0.00 0.00 0.00 0.00 -386.5
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUN-19:53 0.00 0.00 0.00 -0.4 0.00 0.00 427.03 799.44 1651.33 438.43 0.00 115.27 810.53 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2542.60 0.00 625.93 202.64 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.7 0.00 0.00 427.00 721.37 1713.78 5743.16 0.00 250.00 0.00 0.00 0.00 0.00 0.00 -523.4
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-18:10 0.00 0.00 0.00 -9.0 0.00 0.00 7686.29 12984.58 30848.11 43170.67 0.00 10850.30 16874.83 0.00 0.00 0.00 -14470.0 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 9221.09 0.00 0.00 0.00 127.30 103.05 1084.61 0.00 0.00 0.00 4548.32 0.00 -4135.5 0.00 -10948.9 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 05-NOV-06:33 0.00 0.00 20798.24 0.00 0.00 0.00 719.88 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -853.6 0.00 -4071.5 -18059.6
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-11:58 0.00 0.00 19518.75 0.00 0.00 0.00 127.31 103.05 1112.02 0.00 0.00 0.00 0.00 0.00 -187.4 0.00 -6229.1 -14444.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31-AUG-10:21 0.00 0.00 22874.88 0.00 0.00 0.00 147.20 103.05 1079.31 0.00 0.00 0.00 0.00 0.00 -122.4 0.00 -1921.5 -22160.6
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 15268.46 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1672.4 0.00 -10424.7 -4486.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 18769.66 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4135.3 0.00 -10948.5 -5000.8
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15689.48 0.00 0.00 0.00 127.30 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4149.7 0.00 -8484.0 -4370.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-APR-18:54 0.00 0.00 15179.35 0.00 0.00 0.00 506.38 721.37 1735.60 0.00 0.00 0.00 0.00 0.00 -869.2 0.00 -3525.5 -13748.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15691.13 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4149.6 0.00 -8483.7 -4372.8
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 14-OCT-14:53 0.00 0.00 19869.27 0.00 0.00 0.00 144.04 103.05 1106.23 494.58 0.00 0.00 0.00 0.00 0.00 0.00 -1827.5 -19889.7
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 12225.91 0.00 0.00 0.00 127.30 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1678.4 0.00 -7959.4 -3903.0
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15695.44 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4149.5 0.00 -8483.7 -4377.2
LIVING_UNIT3_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20272.71 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.7 0.00 -10957.4 -6514.5
LIVING_UNIT3_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20268.52 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.8 0.00 -10957.4 -6510.3
LIVING_UNIT1_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20267.26 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.9 0.00 -10957.7 -6508.7
LIVING_UNIT2_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16804.51 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.3 0.00 -10433.1 -6023.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16797.64 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.4 0.00 -10433.1 -6016.1
LIVING_UNIT1_BACKROW_TOPFLOOR 31-AUG-12:23 0.00 0.00 24263.48 0.00 0.00 0.00 144.64 103.05 1082.63 226.98 0.00 0.00 0.00 0.00 0.00 0.00 -1445.1 -24375.7
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-JAN-10:00 0.00 0.00 297965.95 0.00 0.00 0.00 2291.46 1854.94 19523.00 0.00 0.00 4113.86 0.00 0.00 -59631.9 0.00 -255049.3 -11068.0



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 798.454 2.00 2.00 1.00 44.9950 798.454 0.056 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 209.901 2.00 2.00 1.00 44.9950 209.901 0.214 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 279.770 2.00 2.00 1.00 44.9950 279.770 0.161 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 353.254 2.00 2.00 1.00 44.9950 353.254 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.597 2.00 2.00 1.00 44.9950 133.597 0.337 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 256.074 2.00 2.00 1.00 44.9950 256.074 0.176 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.119 2.00 2.00 1.00 44.9950 403.119 0.112 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 214.464 2.00 2.00 1.00 44.9950 214.464 0.210 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 290.447 2.00 2.00 1.00 44.9950 290.447 0.155 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 356.972 2.00 2.00 1.00 44.9950 356.972 0.126 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 146.800 2.00 2.00 1.00 44.9950 146.800 0.307 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 261.703 2.00 2.00 1.00 44.9950 261.703 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.972 2.00 2.00 1.00 44.9950 418.972 0.107 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.222 2.00 2.00 1.00 44.9950 220.222 0.204 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.479 2.00 2.00 1.00 44.9950 288.479 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 390.939 2.00 2.00 1.00 44.9950 390.939 0.115 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.688 2.00 2.00 1.00 44.9950 181.688 0.248 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.176 2.00 2.00 1.00 44.9950 253.176 0.178 1.000 44.9950 0.18


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 193.448 2.00 2.00 1.00 44.9950 193.448 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 307.913 2.00 2.00 1.00 44.9950 307.913 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 377.206 2.00 2.00 1.00 44.9950 377.206 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 377.366 2.00 2.00 1.00 44.9950 377.366 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 307.894 2.00 2.00 1.00 44.9950 307.894 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 377.131 2.00 2.00 1.00 44.9950 377.131 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 314.661 2.00 2.00 1.00 44.9950 314.661 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 245.797 2.00 2.00 1.00 44.9950 245.797 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 314.505 2.00 2.00 1.00 44.9950 314.505 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 314.692 2.00 2.00 1.00 44.9950 314.692 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.768 2.00 2.00 1.00 44.9950 245.768 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 314.426 2.00 2.00 1.00 44.9950 314.426 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.326 2.00 2.00 1.00 44.9950 408.326 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.464 2.00 2.00 1.00 44.9950 339.464 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 408.130 2.00 2.00 1.00 44.9950 408.130 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.312 2.00 2.00 1.00 44.9950 408.312 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.412 2.00 2.00 1.00 44.9950 339.412 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 408.042 2.00 2.00 1.00 44.9950 408.042 1.000 1.000 44.9950 0.11


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   798.454 798.4537 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   209.901 209.9011 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   279.770 279.7700 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   353.254 353.2540 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   133.597 133.5972 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   256.074 256.0737 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   403.119 403.1193 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   214.464 214.4642 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   290.447 290.4466 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   356.972 356.9717 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   146.800 146.8003 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   261.703 261.7031 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   253.176 253.1763 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   288.479 288.4788 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   418.972 418.9716 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   181.688 181.6875 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   220.222 220.2223 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   390.939 390.9386 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 798.45 798.454 798.45 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 209.90 209.901 209.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 279.77 279.770 279.77 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 353.25 353.254 353.25 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.60 133.597 133.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 256.07 256.074 256.07 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.12 403.119 403.12 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 214.46 214.464 214.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 290.45 290.447 290.45 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 356.97 356.972 356.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 146.80 146.800 146.80 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 261.70 261.703 261.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.97 418.972 418.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.22 220.222 220.22 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.48 288.479 288.48 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 390.94 390.939 390.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.69 181.688 181.69 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.18 253.176 253.18 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   193.448 193.448 193.448 44.9950 0.233 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   307.913 307.913 307.913 44.9950 0.146 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   377.206 377.206 377.206 44.9950 0.119 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   377.366 377.366 377.366 44.9950 0.119 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   307.894 307.894 307.894 44.9950 0.146 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   377.131 377.131 377.131 44.9950 0.119 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   314.661 314.661 314.661 44.9950 0.143 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   245.797 245.797 245.797 44.9950 0.183 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   314.505 314.505 314.505 44.9950 0.143 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   314.692 314.692 314.692 44.9950 0.143 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   245.768 245.768 245.768 44.9950 0.183 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   314.426 314.426 314.426 44.9950 0.143 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   408.042 408.042 408.042 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   408.130 408.130 408.130 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   408.326 408.326 408.326 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   339.412 339.412 339.412 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   339.464 339.464 339.464 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   408.312 408.312 408.312 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 193.45 193.448 193.45 193.45 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 307.91 307.913 307.91 307.91 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 377.21 377.206 377.21 377.21 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 377.37 377.366 377.37 377.37 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 307.89 307.894 307.89 307.89 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 377.13 377.131 377.13 377.13 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 314.66 314.661 314.66 314.66 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 245.80 245.797 245.80 245.80 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 314.51 314.505 314.51 314.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 314.69 314.692 314.69 314.69 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.77 245.768 245.77 245.77 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 314.43 314.426 314.43 314.43 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.33 408.326 408.33 408.33 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.46 339.464 339.46 339.46 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 408.13 408.130 408.13 408.13 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.31 408.312 408.31 408.31 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.41 339.412 339.41 339.41 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 408.04 408.042 408.04 408.04 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Sec1.1A-General Information

Data
Weather File ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1725.75
Number of hours cooling loads not met 0.00
Number of hours not met 1725.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 8012.59 360210.82 0.00 0.00
Space Cooling 6160.13 7941.44 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8297.28 2285.12 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3794.57 116723.59 0.00 0.00
Receptacle Equipment 87836.46 15395.85 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 117796.67   11807.16   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 402206.97
Natural Gas 0.00 1180716.03
Additional 0.00 0.00
Total 299910.33 1582923.00


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 0.16
Fans-Interior 0.21
Service Water Heating 0.00
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 3.02


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 6.02
Service Water Heating 2.85
Miscellaneous -0.0
Subtotal 8.87


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 2.79
Space Heating 50.62
Space Cooling 1.33
Fans-Interior 1.79
Service Water Heating 23.97
Receptacle Equipment 18.95
Miscellaneous 0.55



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 798.45
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 307.91
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 377.21
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 377.37
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 307.89
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 377.13
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 403.12
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 245.80
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 314.51
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 356.97
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 245.77
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 314.43
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 408.04
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 408.13
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 418.97
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 339.41
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 339.46
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 408.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 798.45
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 307.91
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 377.21
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 377.37
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 307.89
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 377.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.12
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 245.80
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 314.51
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 356.97
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.77
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 314.43
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.97
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.46
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 408.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.31
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.41
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 408.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 798.45 1.77 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 307.91 0.684053 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 377.21 0.837990 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 377.37 0.838346 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 307.89 0.684008 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 377.13 0.837825 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 403.12 0.895560 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 245.80 0.546056 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 314.51 0.698696 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 356.97 0.793039 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 245.77 0.545991 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 314.43 0.698520 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 418.97 0.930777 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 339.46 0.754144 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 408.13 0.906691 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 408.31 0.907096 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 339.41 0.754029 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 408.04 0.906496 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 798.45 798.45 798.45 1.77 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 307.91 307.91 307.91 0.684053 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 377.21 377.21 377.21 0.837990 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 377.37 377.37 377.37 0.838346 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 307.89 307.89 307.89 0.684008 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 377.13 377.13 377.13 0.837825 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 403.12 403.12 403.12 0.895560 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 245.80 245.80 245.80 0.546056 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 314.51 314.51 314.51 0.698696 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 356.97 356.97 356.97 0.793039 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 245.77 245.77 245.77 0.545991 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 314.43 314.43 314.43 0.698520 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 418.97 418.97 418.97 0.930777 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 339.46 339.46 339.46 0.754144 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 408.13 408.13 408.13 0.906691 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 408.31 408.31 408.31 0.907096 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 339.41 339.41 339.41 0.754029 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 408.04 408.04 408.04 0.906496 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 48101.24 4.85 668.53
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 21950.16 2.22 287.09
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 25644.78 2.59 341.24
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 25653.31 2.59 341.37
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 21949.10 2.22 287.08
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 25640.81 2.59 341.18
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 27024.58 2.73 361.39
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 18637.35 1.88 238.21
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 22300.46 2.25 292.17
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 24564.40 2.48 325.41
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 18635.79 1.88 238.18
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 22296.23 2.25 292.11
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 27871.50 2.81 373.76
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 23632.18 2.39 311.79
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 27293.46 2.75 365.32
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 27303.18 2.76 365.46
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 23629.43 2.38 311.75
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 27288.78 2.75 365.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 798.45
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 307.91
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 377.21
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 377.37
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 307.89
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 377.13
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 403.12
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 245.80
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 314.51
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 356.97
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 245.77
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 314.43
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 418.97
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 339.46
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 408.13
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 408.31
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 339.41
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 408.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 6.20 116.23
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 6.20
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 461129.26 46.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:06

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 102.849 2.041 449.222 15.789 17.830
February 206.441 8.512 289.295 9.812 18.324
March 467.254 25.193 109.063 3.431 28.625
April 667.631 78.090 6.151 0.103 78.193
May 744.000 126.492 0.000 0.000 126.492
June 720.000 151.176 0.000 0.000 151.176
July 744.000 161.530 0.000 0.000 161.530
August 744.000 144.774 0.000 0.000 144.774
September 720.000 94.970 0.000 0.000 94.970
October 571.785 43.495 28.411 0.418 43.913
November 25.837 0.309 396.822 11.288 11.597
December 50.828 1.964 570.108 20.071 22.035
           
Annual Sum or Average 5764.625 838.545 1849.071 60.912 899.458
Minimum of Months 25.837 0.309 0.000 0.000 11.597
Maximum of Months 744.000 161.530 570.108 20.071 161.530



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 551.893 32.983 62.579
February 0.000 0.000 495.424 25.190 52.340
March 0.000 0.000 570.637 18.914 44.763
April 48.571 0.963 477.990 7.690 15.780
May 191.496 5.409 273.988 1.652 7.061
June 407.701 14.969 28.625 0.100 15.068
July 443.035 19.014 33.583 0.091 19.105
August 331.181 12.217 92.208 0.514 12.731
September 67.321 1.057 487.375 4.110 5.167
October 1.000 0.006 578.970 11.621 33.794
November 0.000 0.000 422.618 27.651 73.502
December 0.000 0.000 620.863 37.565 56.542
           
Annual Sum or Average 1490.304 53.634 4634.175 168.081 398.431
Minimum of Months 0.000 0.000 28.625 0.091 5.167
Maximum of Months 443.035 19.014 620.863 37.565 73.502



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.823 74.650 74.683
February 0.000 0.000 671.488 58.381 58.477
March 0.000 0.000 736.354 46.362 46.460
April 66.493 1.766 493.067 19.207 25.662
May 299.065 13.095 187.833 3.454 23.163
June 483.749 25.380 21.750 0.257 27.438
July 486.772 30.878 29.958 0.255 33.704
August 361.498 17.927 74.858 1.104 23.938
September 79.754 1.583 455.521 10.334 18.059
October 1.819 0.018 721.162 35.521 36.802
November 0.000 0.000 719.958 70.723 70.731
December 0.000 0.000 743.927 79.261 79.275
           
Annual Sum or Average 1779.151 90.647 5599.700 399.508 518.391
Minimum of Months 0.000 0.000 21.750 0.255 18.059
Maximum of Months 486.772 30.878 743.927 79.261 79.275



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 66.243 66.243
February 0.000 0.000 672.000 54.772 54.772
March 0.000 0.000 736.878 47.526 48.806
April 21.029 0.731 549.429 20.659 38.212
May 121.521 4.773 318.477 4.537 25.014
June 375.848 18.007 39.344 0.301 19.410
July 403.203 19.614 55.321 0.329 20.703
August 218.146 8.768 144.098 1.812 22.433
September 5.167 0.109 528.658 11.970 29.115
October 0.000 0.000 732.206 34.588 36.717
November 0.000 0.000 720.000 62.882 62.882
December 0.000 0.000 744.000 69.685 69.685
           
Annual Sum or Average 1144.914 52.002 5984.409 375.306 493.992
Minimum of Months 0.000 0.000 39.344 0.301 19.410
Maximum of Months 403.203 19.614 744.000 69.685 69.685



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 45.232 45.232
February 0.000 0.000 672.000 37.596 37.596
March 0.000 0.000 743.610 33.222 33.275
April 0.000 0.000 646.062 16.055 23.076
May 62.292 1.034 374.873 3.170 6.352
June 381.274 10.097 25.000 0.146 10.243
July 437.586 12.952 34.708 0.158 13.125
August 216.200 4.965 154.535 1.230 7.603
September 0.000 0.000 610.231 8.396 11.297
October 0.000 0.000 743.469 23.216 23.298
November 0.000 0.000 720.000 43.109 43.109
December 0.000 0.000 744.000 47.663 47.663
           
Annual Sum or Average 1097.352 29.048 6212.489 259.193 301.869
Minimum of Months 0.000 0.000 25.000 0.146 6.352
Maximum of Months 437.586 12.952 744.000 47.663 47.663



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 74.975 74.975
February 0.000 0.000 672.000 61.346 61.346
March 0.000 0.000 743.958 51.636 51.644
April 1.357 0.007 655.871 24.059 24.889
May 223.396 6.498 242.167 4.071 14.577
June 488.192 20.728 21.667 0.254 22.356
July 482.239 25.157 33.375 0.277 27.724
August 300.401 10.335 122.075 1.555 16.864
September 0.875 0.002 590.715 12.999 15.836
October 0.000 0.000 744.000 38.202 38.202
November 0.000 0.000 720.000 71.363 71.363
December 0.000 0.000 744.000 79.048 79.048
           
Annual Sum or Average 1496.460 62.726 6033.827 419.787 498.825
Minimum of Months 0.000 0.000 21.667 0.254 14.577
Maximum of Months 488.192 25.157 744.000 79.048 79.048



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 57.225 57.225
February 0.000 0.000 672.000 44.531 44.531
March 0.000 0.000 730.250 35.086 35.086
April 103.704 4.627 454.050 13.027 20.059
May 258.683 12.523 198.146 2.164 22.287
June 447.249 26.721 20.890 0.106 27.208
July 485.296 29.536 16.250 0.088 30.001
August 367.894 19.159 65.971 0.677 22.784
September 78.500 2.486 454.219 7.214 12.600
October 1.750 0.010 721.583 26.028 26.038
November 0.000 0.000 720.000 53.812 53.812
December 0.000 0.000 744.000 61.411 61.411
           
Annual Sum or Average 1743.076 95.063 5541.358 301.368 413.041
Minimum of Months 0.000 0.000 16.250 0.088 12.600
Maximum of Months 485.296 29.536 744.000 61.411 61.411



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 31.569 31.569
February 0.000 0.000 672.000 24.288 24.288
March 0.000 0.000 728.687 19.265 19.507
April 64.433 1.383 451.760 7.182 11.725
May 241.154 6.988 189.808 1.033 8.744
June 483.423 18.344 16.062 0.040 18.404
July 535.018 22.635 15.000 0.043 22.778
August 395.743 14.883 57.208 0.348 15.235
September 87.792 1.550 416.885 3.469 5.432
October 1.750 0.011 710.250 14.044 14.145
November 0.000 0.000 720.000 30.108 30.108
December 0.000 0.000 744.000 33.525 33.525
           
Annual Sum or Average 1809.313 65.794 5465.661 164.915 235.459
Minimum of Months 0.000 0.000 15.000 0.040 5.432
Maximum of Months 535.018 22.635 744.000 33.525 33.525



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.070 63.070
February 0.000 0.000 672.000 48.913 48.913
March 0.000 0.000 727.521 37.789 38.334
April 85.165 2.447 444.287 14.678 22.079
May 349.985 15.672 128.583 1.955 23.563
June 528.506 29.372 14.375 0.104 30.336
July 543.635 34.516 14.000 0.116 35.406
August 416.950 20.900 41.425 0.617 24.444
September 96.750 2.223 392.433 7.824 18.488
October 2.964 0.038 710.125 29.279 30.860
November 0.000 0.000 720.000 59.449 59.449
December 0.000 0.000 744.000 67.520 67.520
           
Annual Sum or Average 2023.955 105.168 5352.750 331.314 462.463
Minimum of Months 0.000 0.000 14.000 0.104 18.488
Maximum of Months 543.635 34.516 744.000 67.520 67.520



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 60.320 60.320
February 0.000 0.000 672.000 49.801 49.801
March 0.000 0.000 731.762 42.710 44.859
April 25.979 0.864 514.291 17.342 35.884
May 149.079 5.786 245.124 2.992 21.671
June 443.619 21.508 22.375 0.145 21.932
July 480.129 23.350 21.500 0.143 23.788
August 272.068 10.744 85.996 1.185 18.241
September 6.942 0.131 487.379 10.063 28.476
October 0.000 0.000 726.375 31.252 34.280
November 0.000 0.000 720.000 57.397 57.397
December 0.000 0.000 744.000 63.590 63.590
           
Annual Sum or Average 1377.816 62.383 5714.804 336.939 460.237
Minimum of Months 0.000 0.000 21.500 0.143 18.241
Maximum of Months 480.129 23.350 744.000 63.590 63.590



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 32.521 32.521
February 0.000 0.000 672.000 26.835 26.835
March 0.000 0.000 743.783 23.422 23.448
April 0.000 0.000 618.262 10.654 15.812
May 97.396 1.770 251.300 1.450 4.100
June 491.354 13.972 13.000 0.039 14.012
July 542.915 17.218 15.875 0.048 17.322
August 289.104 7.209 90.531 0.611 8.750
September 0.000 0.000 568.987 5.482 6.574
October 0.000 0.000 743.594 16.328 16.373
November 0.000 0.000 720.000 30.926 30.926
December 0.000 0.000 744.000 34.210 34.210
           
Annual Sum or Average 1420.769 40.168 5925.334 182.527 230.884
Minimum of Months 0.000 0.000 13.000 0.039 4.100
Maximum of Months 542.915 17.218 744.000 34.210 34.210



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 64.143 64.143
February 0.000 0.000 672.000 52.327 52.327
March 0.000 0.000 744.000 43.430 43.430
April 4.643 0.021 607.300 19.079 20.629
May 286.200 8.717 155.500 2.397 15.724
June 541.200 25.251 13.000 0.100 26.200
July 546.127 29.256 16.750 0.120 30.189
August 347.856 13.111 68.417 0.861 17.122
September 3.417 0.006 520.196 10.205 15.220
October 0.000 0.000 743.964 32.367 32.372
November 0.000 0.000 720.000 61.220 61.220
December 0.000 0.000 744.000 67.788 67.788
           
Annual Sum or Average 1729.442 76.362 5749.127 354.038 446.365
Minimum of Months 0.000 0.000 13.000 0.100 15.220
Maximum of Months 546.127 29.256 744.000 67.788 67.788



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 86.741 86.741
February 0.000 0.000 672.000 68.867 68.867
March 0.000 0.000 744.000 56.695 56.695
April 62.050 2.731 518.973 23.072 30.217
May 200.417 10.153 236.999 4.625 31.514
June 413.546 25.764 34.984 0.336 28.841
July 439.333 28.937 32.812 0.297 31.327
August 312.547 17.152 92.117 1.492 29.825
September 48.125 1.302 508.030 13.542 21.551
October 0.000 0.000 737.161 42.657 42.657
November 0.000 0.000 720.000 81.753 81.753
December 0.000 0.000 744.000 92.370 92.370
           
Annual Sum or Average 1476.017 86.039 5785.076 472.447 602.359
Minimum of Months 0.000 0.000 32.812 0.297 21.551
Maximum of Months 439.333 28.937 744.000 92.370 92.370



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 50.565 50.565
February 0.000 0.000 672.000 39.914 39.914
March 0.000 0.000 744.000 32.893 32.893
April 35.708 0.645 528.690 13.673 17.781
May 181.650 5.635 273.693 2.656 8.883
June 434.570 18.276 28.824 0.160 18.458
July 484.484 22.881 30.146 0.148 23.139
August 341.787 13.681 104.250 0.892 14.623
September 45.708 0.584 511.565 7.280 8.132
October 0.000 0.000 733.250 24.058 24.107
November 0.000 0.000 720.000 47.850 47.850
December 0.000 0.000 744.000 53.979 53.979
           
Annual Sum or Average 1523.908 61.703 5834.419 274.068 340.323
Minimum of Months 0.000 0.000 28.824 0.148 8.132
Maximum of Months 484.484 22.881 744.000 53.979 53.979



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 80.882 80.882
February 0.000 0.000 672.000 63.686 63.686
March 0.000 0.000 742.950 50.937 50.937
April 51.215 1.158 529.337 21.152 25.857
May 295.224 12.408 184.996 3.455 21.896
June 505.355 28.505 22.625 0.259 29.733
July 521.282 34.403 26.875 0.242 36.189
August 369.387 19.042 80.208 1.194 23.637
September 57.508 0.949 485.562 11.780 18.095
October 0.000 0.000 732.750 39.039 39.450
November 0.000 0.000 720.000 76.385 76.385
December 0.000 0.000 744.000 86.240 86.240
           
Annual Sum or Average 1799.971 96.466 5685.304 435.250 552.988
Minimum of Months 0.000 0.000 22.625 0.242 18.095
Maximum of Months 521.282 34.403 744.000 86.240 86.240



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 73.349 73.349
February 0.000 0.000 672.000 60.438 60.438
March 0.000 0.000 742.850 52.110 52.324
April 21.792 0.728 559.264 22.588 37.963
May 137.225 5.862 298.707 4.505 27.782
June 410.639 22.484 31.552 0.284 23.617
July 446.026 24.667 43.262 0.280 25.700
August 247.432 11.241 127.947 1.798 24.967
September 4.333 0.099 538.805 13.436 29.600
October 0.000 0.000 735.542 38.419 40.132
November 0.000 0.000 720.000 69.826 69.826
December 0.000 0.000 744.000 77.270 77.270
           
Annual Sum or Average 1267.446 65.080 5957.930 414.302 542.968
Minimum of Months 0.000 0.000 31.552 0.280 23.617
Maximum of Months 446.026 24.667 744.000 77.270 77.270



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 52.049 52.049
February 0.000 0.000 672.000 43.027 43.027
March 0.000 0.000 743.900 37.459 37.476
April 0.000 0.000 634.714 17.536 24.092
May 94.417 2.119 349.896 3.209 6.342
June 437.673 15.173 24.469 0.145 15.321
July 497.066 18.710 29.250 0.148 18.935
August 264.158 7.858 144.506 1.299 10.500
September 0.000 0.000 608.378 9.542 11.704
October 0.000 0.000 743.917 26.747 26.761
November 0.000 0.000 720.000 49.786 49.786
December 0.000 0.000 744.000 54.953 54.953
           
Annual Sum or Average 1293.314 43.860 6159.029 295.900 350.946
Minimum of Months 0.000 0.000 24.469 0.145 6.342
Maximum of Months 497.066 18.710 744.000 54.953 54.953



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 82.032 82.032
February 0.000 0.000 672.000 66.995 66.995
March 0.000 0.000 744.000 56.146 56.146
April 0.000 0.000 652.446 25.551 26.722
May 242.881 7.142 222.017 3.863 15.660
June 517.733 25.476 21.000 0.245 26.714
July 525.008 30.326 29.125 0.249 31.860
August 321.533 12.955 123.792 1.598 17.966
September 0.000 0.000 609.364 14.331 17.304
October 0.000 0.000 744.000 42.036 42.036
November 0.000 0.000 720.000 78.270 78.270
December 0.000 0.000 744.000 86.577 86.577
           
Annual Sum or Average 1607.156 75.899 6025.743 457.894 548.284
Minimum of Months 0.000 0.000 21.000 0.245 15.660
Maximum of Months 525.008 30.326 744.000 86.577 86.577



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.15
April 0.00 0.00 0.48
May 0.00 0.00 0.73
June 0.00 0.00 0.91
July 0.00 0.00 0.94
August 0.00 0.00 0.85
September 0.00 0.00 0.58
October 0.00 0.00 0.25
November 0.00 0.00 0.00
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.94



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.07
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.14
July 0.00 0.00 0.17
August 0.00 0.00 0.10
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.10
July 0.00 0.00 0.11
August 0.00 0.00 0.05
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.11



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.06
July 0.00 0.00 0.07
August 0.00 0.00 0.03
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.01
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.07



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.12
July 0.00 0.00 0.14
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.15
July 0.00 0.00 0.16
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.11
July 0.00 0.00 0.13
August 0.00 0.00 0.08
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.17
July 0.00 0.00 0.20
August 0.00 0.00 0.12
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.12
July 0.00 0.00 0.13
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.16
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.16
August 0.00 0.00 0.09
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.10
July 0.00 0.00 0.13
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.19
August 0.00 0.00 0.10
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.14
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.14
July 0.00 0.00 0.17
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2030.07 1511.45
February 0.00 0.00 2022.34 1359.98
March 0.00 0.00 2010.12 1496.59
April 0.00 0.00 2006.69 1445.84
May 0.00 0.00 1986.78 1479.22
June 0.00 0.00 1911.47 1377.23
July 0.00 0.00 1837.89 1368.36
August 0.00 0.00 1783.64 1327.97
September 0.00 0.00 1778.12 1281.15
October 0.00 0.00 1816.43 1352.38
November 0.00 0.00 1909.13 1375.55
December 0.00 0.00 1999.96 1489.03
         
Annual Sum or Average 0.00 0.00 1923.83 16864.75
Minimum of Months 0.00 0.00 1778.12 1281.15
Maximum of Months 0.00 0.00 2030.07 1511.45