Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:45

Tabular Output Report in Format: HTML

Building: MF+CZ8WH+USA_AK_Fairbanks.Intl.AP.702610+oilfurnace+slab+IECC_2012

Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2019-02-14 08:45:20


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1566650.62 50.20 72.50
Net Site Energy 1566650.62 50.20 72.50
Total Source Energy 2537052.28 81.29 117.40
Net Source Energy 2537052.28 81.29 117.40


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.78
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 784654.10 0.00 0.00 0.00 0.00
Cooling 21698.70 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28147.83 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 379306.65 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 402689.88 1163960.74 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 784654.10 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 21698.70 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 28147.83 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 379306.65 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 2.31 53.86 0.00 0.00 0.00 17.48
Other 13.88 0.00 0.00 0.00 0.00 0.00
Total 18.63 53.86 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.70 0.00 0.00 0.00 0.00 0.00
HVAC 1.60 37.29 0.00 0.00 0.00 12.10
Other 9.61 0.00 0.00 0.00 0.00 0.00
Total 12.90 37.29 0.00 0.00 0.00 12.10


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 402689.876 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 402689.876 100.00
     
Total On-Site and Utility Electric Sources 402689.876 100.00
Total Electricity End Uses 402689.876 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1766.50
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3576.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:45
RunPeriod ANNUAL
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [ft] 436.37
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 31210.78     267087.66   16177.97 0.00 2126.74 2126.74 0.4611 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:30 12-JAN-09:00 - - - 01-JAN-08:15
Heating 0.00 354.16 0.00 0.00 0.00 0.00
Cooling 27.27 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.57 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.85 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 116.79 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 102.78 470.95 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 354.16 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 27.27 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.38 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.85 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 116.79 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 850565.04 0.00 0.00 0.00
Cooling 68719.80 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 89144.17 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 411168.41 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1275318.84 1261733.45 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 39.36 0.00 0.00 0.00
Cooling 3.18 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.13 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.03 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 59.02 58.39 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 39.36 0.00 0.00 0.00
Cooling 3.18 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.13 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.03 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 59.02 58.39 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -43.4 0.00 -43.4 Wetbulb [F] 59.06 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 81.32 18.36 60.98 Wetbulb [F] 610.27 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.330 0.882              
North Total or Average           531.68 0.320 0.330 0.882              
Non-North Total or Average           1595.05 0.320 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 456778.65 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   21412.73 17101.39 4311.34 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7786.62 6218.82 1567.79 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9626.46 7688.22 1938.24 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9630.71 7691.61 1939.09 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7786.08 6218.39 1567.69 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9624.46 7686.63 1937.84 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10762.62 8595.62 2167.00 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6507.74 5197.44 1310.30 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8342.64 6662.89 1679.75 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9534.16 7614.51 1919.65 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6506.96 5196.81 1310.14 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8340.52 6661.20 1679.32 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11171.60 8922.25 2249.34 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9044.30 7223.28 1821.02 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10875.78 8686.00 2189.78 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10880.65 8689.89 2190.76 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9042.93 7222.18 1820.75 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10873.44 8684.13 2189.31 0.80 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 48354.65 50074.63 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 21106.22 19882.61 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 24786.00 23994.86 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 24794.49 24004.32 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 21105.14 19881.40 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 24782.01 23990.42 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 27056.39 26519.92 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 18547.50 17000.33 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 22217.03 21124.41 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 24599.78 23786.45 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 18545.94 16998.57 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 22212.80 21119.67 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 27876.05 27429.40 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 23621.33 22696.39 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 27284.44 26772.44 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 27294.18 26783.25 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 23618.58 22693.33 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 27279.77 26767.25 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 803.21 402.24 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 292.08 146.27 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 361.10 180.84 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 361.26 180.92 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 292.06 146.26 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 361.02 180.80 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 403.72 202.18 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 244.11 122.25 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 312.94 156.72 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 357.64 179.10 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 244.08 122.24 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 312.86 156.68 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 419.06 209.86 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.26 169.90 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 407.96 204.30 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 408.14 204.40 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 339.21 169.87 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 407.87 204.26 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 45.932610 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18575.75 18575.75 15.47 803.211 803.211 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00807 74.85 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5002.46 5002.46 4.17 216.301 216.301 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6618.17 6618.17 5.51 286.162 286.162 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8281.06 8281.06 6.90 358.070 358.070 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3183.82 3183.82 2.65 137.667 137.667 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00824 70.07 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6084.55 6084.55 5.07 263.090 263.090 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9336.68 9336.68 7.78 403.716 403.716 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00815 74.16 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4979.53 4979.53 4.15 215.310 215.310 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6733.53 6733.53 5.61 291.151 291.151 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 74.98 74.98 0.00800 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8270.98 8270.98 6.89 357.635 357.635 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00816 73.65 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3409.01 3409.01 2.84 147.404 147.404 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 74.98 74.98 0.00827 69.66 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6069.87 6069.87 5.06 262.456 262.456 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00802 73.56 0.00698 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5857.41 5857.41 4.88 253.269 253.269 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00800 73.56 0.00698 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6673.66 6673.66 5.56 288.561 288.561 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9691.49 9691.49 8.07 419.057 419.057 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00813 74.16 0.00698 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4204.26 4204.26 3.50 181.790 181.790 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 74.98 74.98 0.00819 70.07 0.00698 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5095.89 5095.89 4.24 220.340 220.340 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 74.98 74.98 0.00797 81.32 0.00698 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9043.57 9043.57 7.53 391.041 391.041 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 74.98 74.98 0.00814 73.65 0.00698 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9593.49 9593.49 7.99 177.329 177.329 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00537 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15802.74 15802.74 13.16 292.083 292.083 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00622 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 19536.95 19536.95 16.27 361.097 361.097 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00643 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19545.56 19545.56 16.28 361.257 361.257 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00643 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15801.65 15801.65 13.16 292.063 292.063 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00622 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19532.90 19532.90 16.27 361.023 361.023 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00642 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 16938.18 16938.18 14.11 313.095 313.095 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13205.95 13205.95 11.00 244.111 244.111 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00638 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16929.77 16929.77 14.10 312.940 312.940 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 16939.88 16939.88 14.11 313.127 313.127 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13204.37 13204.37 11.00 244.082 244.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00638 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16925.47 16925.47 14.10 312.861 312.861 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00659 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 22067.56 22067.56 18.38 407.873 407.873 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 22072.31 22072.31 18.39 407.961 407.961 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 22082.93 22082.93 18.39 408.157 408.157 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 18352.22 18352.22 15.29 339.209 339.209 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00641 -43.4 0.00006 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 18355.00 18355.00 15.29 339.260 339.260 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00641 -43.4 0.00006 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 22082.18 22082.18 18.39 408.143 408.143 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00657 -43.4 0.00006 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 803.21 803.21 177.33 177.33
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 216.30 216.30 292.08 292.08
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 286.16 286.16 361.10 361.10
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 358.07 358.07 361.26 361.26
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 137.67 137.67 292.06 292.06
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.09 263.09 361.02 361.02
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.72 403.72 313.10 313.10
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.31 215.31 244.11 244.11
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.15 291.15 312.94 312.94
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.64 357.64 313.13 313.13
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.40 147.40 244.08 244.08
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.46 262.46 312.86 312.86
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.06 419.06 408.16 408.16
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.34 220.34 339.26 339.26
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.56 288.56 407.96 407.96
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.04 391.04 408.14 408.14
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.79 181.79 339.21 339.21
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.27 253.27 407.87 407.87


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2301.00 7166.25 1923.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2739.25 7228.00 2432.25
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3183.50 6947.75 2538.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3238.25 7509.00 2895.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1233.50 7519.25 1110.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3115.25 7237.25 2708.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2877.25 7043.50 2279.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1503.75 7050.50 1122.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3070.50 6800.25 2348.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3165.00 7351.75 2776.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1118.00 7300.75 961.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3074.00 7086.50 2611.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3841.50 7191.50 3347.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 3772.75 7022.25 3082.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 3723.50 7273.75 3161.75
LIVING_UNIT2_BACKROW_TOPFLOOR 2779.00 7434.25 2550.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 2679.00 7283.00 2282.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3894.00 7469.25 3469.75
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4528.75 7831.00 3576.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1267.75 0.00 1267.75 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 32.50 0.00 32.50 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 237.00 0.00 237.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23.75 0.00 23.75 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2.50 0.00 2.50 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 51.50 0.00 51.50 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 11.00 0.00 11.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 56.00 0.00 56.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 237.25 0.00 237.25 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 17.75 0.00 17.75 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11.25 0.00 11.25 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 2.00 0.00 2.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11.75 0.00 11.75 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 125.75 0.00 125.75 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 18.25 0.00 18.25 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4.50 0.00 4.50 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 199.50 0.00 199.50 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1766.50 0.00 1766.50 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.290
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.119 0.000 0.288
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.121 0.000 0.289
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.137 0.000 0.289
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.289
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.060 0.000 0.289
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.138 0.000 0.289
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.121 0.000 0.289
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.137 0.000 0.289
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1855
Defaulted Fields 436
Fields with Defaults 4694
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 90
Autocalculatable Fields 269



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Fans:Electricity 8243.82 139.23 12-JUN-04:00 2605.86 12-JAN-10:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
ElectricityPurchased:Plant 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
Cogeneration:ElectricityPurchased 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
ElectricityNet:Plant 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
Cogeneration:ElectricityNet 117938.10 7322.10 12-JUN-04:00 30101.48 29-JUL-18:30
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 14598.84 527.62 02-JUN-00:45 10522.44 29-JUL-17:15
General:Fans:Electricity 8243.82 139.23 12-JUN-04:00 2605.86 12-JAN-10:00
Cooling:Electricity 6355.02 0.00 01-JAN-00:15 8214.90 29-JUL-17:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 11639.61 0.00 17-APR-16:30 470620.90 12-JAN-10:00
Gas:Plant 11639.61 0.00 17-APR-16:30 470620.90 12-JAN-10:00
WaterSystems:Gas 3793.07 0.00 01-JAN-00:15 118000.67 04-MAR-08:30
Water Heater:WaterSystems:Gas 3793.07 0.00 01-JAN-00:15 118000.67 04-MAR-08:30
Heating:Gas 7846.54 0.00 17-APR-16:30 353913.75 12-JAN-10:00
Boiler:Heating:Gas 7846.54 0.00 17-APR-16:30 353913.75 12-JAN-10:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
Water:Plant 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
WaterSystems:Water 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
MainsWater:Plant 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
WaterSystems:MainsWater 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 11-MAY-03:00 0.18 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 852320.90 2172.58 29-AUG-02:15 329320.97 12-JAN-08:15
PlantLoopHeatingDemand:Plant 223779.54 2170.95 04-SEP-03:00 51553.19 07-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 223779.54 2170.95 04-SEP-03:00 51553.19 07-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2327099.79 16540.77 07-JUN-03:30 904857.39 12-JAN-10:00
EnergyTransfer:Building 742700.12 6727.00 07-JUN-03:30 292714.56 12-JAN-10:00
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 649699.43 0.00 17-APR-17:15 292714.56 12-JAN-10:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 93000.70 0.00 01-JAN-00:15 108670.90 11-JUL-18:30
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44818.23 0.00 01-JAN-00:15 17661.73 06-JUL-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3518.85 0.00 01-JAN-00:15 8539.13 12-JAN-09:45
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 41299.38 0.00 01-JAN-00:15 17661.73 06-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 28066.63 0.00 20-MAR-13:00 18718.64 24-NOV-20:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 25505.28 0.00 20-MAR-13:00 18718.64 24-NOV-20:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2561.35 0.00 01-JAN-00:15 4759.27 29-JUL-15:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44142.76 0.00 20-MAR-12:45 17993.00 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 39852.37 0.00 20-MAR-12:45 17993.00 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4290.38 0.00 01-JAN-00:15 6781.57 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 45082.90 0.00 12-APR-18:15 18003.82 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 42638.22 0.00 12-APR-18:15 18003.82 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2444.68 0.00 01-JAN-00:15 7694.33 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 34846.11 0.00 17-APR-17:15 14511.48 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 33459.13 0.00 17-APR-17:15 14511.48 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1386.98 0.00 01-JAN-00:15 3399.94 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44798.26 0.00 17-APR-14:00 17998.01 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 41857.26 0.00 17-APR-14:00 17998.01 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2940.99 0.00 01-JAN-00:15 6981.07 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 38134.09 0.00 20-MAR-13:30 15613.56 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 33929.68 0.00 20-MAR-13:30 15613.56 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4204.41 0.00 01-JAN-00:15 8475.39 06-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29444.62 0.00 20-MAR-13:15 12137.57 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26531.97 0.00 20-MAR-13:15 12137.57 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2912.66 0.00 01-JAN-00:15 4730.17 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 38895.00 0.00 20-MAR-12:30 15616.45 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 34160.77 0.00 20-MAR-12:30 15616.45 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4734.24 0.00 01-JAN-00:15 6810.35 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 39928.11 0.00 11-APR-18:30 15623.92 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 37194.87 0.00 11-APR-18:30 15623.92 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2733.24 0.00 01-JAN-00:15 7651.24 11-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29729.93 0.00 17-APR-16:45 12145.51 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 28009.75 0.00 17-APR-16:45 12145.51 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1720.18 0.00 01-JAN-00:15 3504.66 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 39831.68 0.00 17-APR-13:30 15620.86 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 36476.71 0.00 17-APR-13:30 15620.86 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3354.97 0.00 01-JAN-00:15 6874.79 07-JUL-08:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 51427.21 0.00 17-APR-16:15 20265.11 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 48197.52 0.00 17-APR-16:15 20265.11 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 3229.68 0.00 01-JAN-00:15 6543.89 07-JUL-08:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 50013.19 0.00 22-MAR-14:15 20260.88 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 45836.40 0.00 22-MAR-14:15 20260.88 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4176.79 0.00 01-JAN-00:15 6570.18 22-JUL-12:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 50270.08 0.00 06-APR-13:00 20259.90 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 46511.08 0.00 06-APR-13:00 20259.90 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3759.00 0.00 01-JAN-00:15 8752.15 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 41507.47 0.00 17-APR-17:15 16795.14 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 39683.54 0.00 17-APR-17:15 16795.14 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1823.93 0.00 01-JAN-00:15 4243.97 29-JUN-20:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 39896.91 0.00 06-APR-12:45 16788.22 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 37275.38 0.00 06-APR-12:45 16788.22 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2621.52 0.00 01-JAN-00:15 4830.87 29-JUL-15:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 51866.95 0.00 12-APR-18:00 20269.83 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 49060.65 0.00 12-APR-18:00 20269.83 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2806.30 0.00 01-JAN-00:15 8334.92 11-JUL-18:30
EnergyTransfer:Plant 851502.82 2172.58 29-AUG-02:15 328386.40 12-JAN-08:30
WaterSystems:EnergyTransfer 223779.54 2170.95 04-SEP-03:00 51553.19 07-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 223779.54 2170.95 04-SEP-03:00 51553.19 07-JAN-09:00
EnergyTransfer:HVAC 732896.85 6921.86 13-MAY-04:45 283823.22 12-JAN-10:00
HeatingCoils:EnergyTransfer 628541.36 0.00 17-APR-16:30 283823.22 12-JAN-10:00
PlantLoopHeatingDemand:HVAC 628541.36 0.00 17-APR-16:30 283823.22 12-JAN-10:00
HeatingCoils:PlantLoopHeatingDemand 628541.36 0.00 17-APR-16:30 283823.22 12-JAN-10:00
CoolingCoils:EnergyTransfer 104355.50 0.00 01-JAN-00:15 120524.08 11-JUL-18:30
Boilers:EnergyTransfer 627723.28 0.00 17-APR-16:30 283131.00 12-JAN-10:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 3518.826 -3439.31 0.000 0.000 2953.917 2456.001 10405.511 5488.348 0.000 18.541 61034.577 0.000 -12459.42 0.000 -32116.94 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 25505.223 -213.30 0.000 0.000 3212.502 2456.001 10405.511 3397.335 0.000 18.000 0.849 0.000 -4694.72 0.000 -28687.23 -9051.29
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 39852.224 -357.29 0.000 0.000 3099.787 2456.001 10405.511 6834.563 0.000 18.542 0.000 0.000 -11806.67 0.000 -31092.96 -15476.62
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 42638.073 -203.59 0.000 0.000 3114.501 2456.001 10405.511 3110.841 0.000 18.542 0.000 0.000 -12868.12 0.000 -30919.49 -15511.19
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 33459.014 -115.50 0.000 0.000 3109.950 2456.001 10405.511 580.317 0.000 18.000 0.000 0.000 -5333.39 0.000 -29683.86 -13624.56
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 41857.118 -244.92 0.000 0.000 3108.122 2456.001 10405.511 4291.423 0.000 18.542 0.000 0.000 -12493.60 0.000 -31018.04 -15684.09
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 33929.551 -350.13 0.000 0.000 3093.827 2456.001 10405.511 5551.474 0.000 15.798 0.000 0.000 -12283.22 0.000 -25063.12 -13901.43
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 26531.868 -242.56 0.000 0.000 3087.101 2456.001 10405.511 3369.216 0.000 15.262 0.000 0.000 -4860.18 0.000 -23803.74 -14288.39
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 34160.640 -394.25 0.000 0.000 3091.778 2456.001 10405.511 6799.991 0.000 15.798 0.000 0.000 -11914.66 0.000 -25098.21 -15182.63
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 37194.744 -227.62 0.000 0.000 3106.359 2456.001 10405.511 3090.503 0.000 15.798 0.000 0.000 -12977.27 0.000 -24959.75 -15598.65
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 28009.655 -143.25 0.000 0.000 3101.083 2456.001 10405.511 572.840 0.000 15.262 0.000 0.000 -5377.28 0.000 -23717.91 -13744.97
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 36476.586 -279.39 0.000 0.000 3100.988 2456.001 10405.511 4263.677 0.000 15.798 0.000 0.000 -12597.15 0.000 -25035.90 -15730.54
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 48197.370 -268.96 0.000 0.000 3107.307 2456.001 10405.511 4282.073 0.000 18.122 0.000 0.000 -12520.55 0.000 -31060.83 -21655.33
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 45836.242 -347.83 0.000 0.000 3100.535 2456.001 10405.511 6833.902 0.000 18.122 0.000 0.000 -11829.88 0.000 -31120.09 -21523.57
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 46510.921 -313.04 0.000 0.000 3106.416 2456.001 10405.511 5597.998 0.000 18.123 0.000 0.000 -12162.40 0.000 -31045.37 -21128.22
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 39683.417 -151.89 0.000 0.000 3108.624 2456.001 10405.511 578.206 0.000 17.592 0.000 0.000 -5338.33 0.000 -29731.52 -19355.56
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 37275.255 -218.31 0.000 0.000 3099.442 2456.001 10405.511 3382.225 0.000 17.593 0.000 0.000 -4825.61 0.000 -29803.57 -19385.34
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 49060.493 -233.70 0.000 0.000 3112.689 2456.001 10405.511 3100.772 0.000 18.123 0.000 0.000 -12896.76 0.000 -30977.51 -21473.02
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 6558.189 22214.211 0.000 0.000 0.000 -28772.40 -0.26
Total Facility 0.000 0.000 649697.218 -7744.87 0.000 0.000 55814.928 44208.020 187299.191 71125.704 0.000 6869.748 83249.637 0.000 -179239.21 0.000 -543708.43 -282315.67


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 06-JUL-18:40 0.00 0.00 0.00 -1.5 0.00 0.00 426.99 721.37 1713.78 6239.80 0.00 56.10 8590.88 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-15:00 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 103.05 1106.23 2810.43 0.00 602.62 21.76 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6532.94 0.00 0.00 0.00 0.00 0.00 0.00 -59.3 -1019.2
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11-JUL-18:05 0.00 0.00 0.00 -0.6 0.00 0.00 427.00 721.37 1713.78 6067.27 0.00 263.99 0.00 0.00 0.00 0.00 0.00 -1497.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 251.75 0.00 366.74 0.00 0.00 0.00 0.00 0.00 -119.4
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.6 0.00 0.00 420.44 343.51 1204.86 7712.96 0.00 0.00 0.00 0.00 0.00 0.00 -455.0 -2245.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JUL-18:45 0.00 0.00 0.00 -0.7 0.00 0.00 427.01 721.37 1713.78 6221.48 0.00 47.75 0.00 0.00 0.00 0.00 0.00 -655.9
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2543.17 0.00 529.41 202.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-10:25 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1109.09 6525.63 0.00 0.00 0.00 0.00 0.00 0.00 -55.1 -987.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 721.37 1713.78 5763.33 0.00 203.20 0.00 0.00 0.00 0.00 0.00 -1177.4
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-19:55 0.00 0.00 0.00 -0.3 0.00 0.00 427.03 799.44 1674.43 251.59 0.00 283.34 68.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 07-JUL-07:48 0.00 0.00 0.00 -0.6 0.00 0.00 420.43 343.51 1204.86 7714.31 0.00 0.00 0.00 0.00 0.00 0.00 -417.3 -2390.3
LIVING_UNIT3_BACKROW_TOPFLOOR 07-JUL-07:53 0.00 0.00 0.00 -0.5 0.00 0.00 420.44 343.51 1204.86 7719.71 0.00 0.00 0.00 0.00 0.00 0.00 -458.8 -2685.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 22-JUL-11:53 0.00 0.00 0.00 -0.5 0.00 0.00 115.16 103.05 1112.02 4695.33 0.00 290.62 254.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-JUL-18:05 0.00 0.00 0.00 -0.7 0.00 0.00 426.99 721.37 1713.78 6015.47 0.00 259.70 0.00 0.00 0.00 0.00 0.00 -383.4
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUN-19:53 0.00 0.00 0.00 -0.4 0.00 0.00 427.03 799.44 1651.33 438.41 0.00 115.27 813.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-15:15 0.00 0.00 0.00 -0.4 0.00 0.00 115.16 178.62 1161.01 2542.56 0.00 625.93 207.61 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11-JUL-18:20 0.00 0.00 0.00 -0.7 0.00 0.00 427.00 721.37 1713.78 5743.09 0.00 250.00 0.00 0.00 0.00 0.00 0.00 -520.3
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-18:25 0.00 0.00 0.00 -9.1 0.00 0.00 7686.27 12984.58 30848.11 40919.19 0.00 4183.83 26024.29 0.00 0.00 0.00 -13892.9 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12-JAN-09:45 0.00 0.00 8538.79 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 5206.33 0.00 -4141.5 0.00 -10918.6 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 05-JAN-08:41 0.00 0.00 19854.98 0.00 0.00 0.00 293.70 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -917.7 0.00 -4189.1 -16339.0
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 17992.40 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.4 0.00 -10948.5 -4207.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31-AUG-09:52 0.00 0.00 21891.30 0.00 0.00 0.00 145.81 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -267.2 0.00 -2125.1 -20832.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 14510.95 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1679.5 0.00 -10424.7 -3721.7
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12-JAN-10:00 0.00 0.00 17997.41 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.3 0.00 -10948.5 -4212.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15612.96 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.2 0.00 -8483.8 -4292.9
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-APR-19:00 0.00 0.00 12174.34 0.00 0.00 0.00 504.00 721.37 1735.60 0.00 0.00 0.00 0.00 0.00 -872.6 0.00 -3561.2 -10701.5
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15615.85 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.2 0.00 -8483.7 -4295.9
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-APR-14:13 0.00 0.00 19975.83 0.00 0.00 0.00 146.02 103.05 1085.09 758.96 0.00 0.00 0.00 0.00 0.00 0.00 -1628.3 -20440.7
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 12144.99 0.00 0.00 0.00 127.30 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1679.2 0.00 -7959.4 -3821.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12-JAN-10:00 0.00 0.00 15620.26 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4151.1 0.00 -8483.7 -4300.4
LIVING_UNIT3_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20264.45 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.9 0.00 -10957.4 -6506.1
LIVING_UNIT3_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20260.22 0.00 0.00 0.00 127.32 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4115.9 0.00 -10957.4 -6501.8
LIVING_UNIT1_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 20259.25 0.00 0.00 0.00 127.31 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -4116.0 0.00 -10957.7 -6500.5
LIVING_UNIT2_BACKROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16794.53 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.4 0.00 -10433.1 -6012.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 12-JAN-10:00 0.00 0.00 16787.62 0.00 0.00 0.00 127.29 103.05 1084.61 0.00 0.00 0.00 0.00 0.00 -1663.5 0.00 -10433.1 -6006.0
LIVING_UNIT1_BACKROW_TOPFLOOR 31-AUG-12:22 0.00 0.00 24254.86 0.00 0.00 0.00 144.61 103.05 1082.63 226.67 0.00 0.00 0.00 0.00 0.00 0.00 -1444.9 -24366.9
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-JAN-10:00 0.00 0.00 292704.06 0.00 0.00 0.00 2291.47 1854.94 19523.00 0.00 0.00 4113.69 0.00 0.00 -59718.6 0.00 -179195.4 -81573.1



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 803.211 2.00 2.00 1.00 44.9950 803.211 0.056 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 216.301 2.00 2.00 1.00 44.9950 216.301 0.208 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 286.162 2.00 2.00 1.00 44.9950 286.162 0.157 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 358.070 2.00 2.00 1.00 44.9950 358.070 0.126 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 137.667 2.00 2.00 1.00 44.9950 137.667 0.327 1.000 44.9950 0.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.090 2.00 2.00 1.00 44.9950 263.090 0.171 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.716 2.00 2.00 1.00 44.9950 403.716 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.310 2.00 2.00 1.00 44.9950 215.310 0.209 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.151 2.00 2.00 1.00 44.9950 291.151 0.155 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.635 2.00 2.00 1.00 44.9950 357.635 0.126 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.404 2.00 2.00 1.00 44.9950 147.404 0.305 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.456 2.00 2.00 1.00 44.9950 262.456 0.171 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.057 2.00 2.00 1.00 44.9950 419.057 0.107 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.340 2.00 2.00 1.00 44.9950 220.340 0.204 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.561 2.00 2.00 1.00 44.9950 288.561 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.041 2.00 2.00 1.00 44.9950 391.041 0.115 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.790 2.00 2.00 1.00 44.9950 181.790 0.248 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.269 2.00 2.00 1.00 44.9950 253.269 0.178 1.000 44.9950 0.18


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 177.329 2.00 2.00 1.00 44.9950 177.329 1.000 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.083 2.00 2.00 1.00 44.9950 292.083 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 361.097 2.00 2.00 1.00 44.9950 361.097 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.257 2.00 2.00 1.00 44.9950 361.257 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 292.063 2.00 2.00 1.00 44.9950 292.063 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 361.023 2.00 2.00 1.00 44.9950 361.023 1.000 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 313.095 2.00 2.00 1.00 44.9950 313.095 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.111 2.00 2.00 1.00 44.9950 244.111 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.940 2.00 2.00 1.00 44.9950 312.940 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 313.127 2.00 2.00 1.00 44.9950 313.127 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 244.082 2.00 2.00 1.00 44.9950 244.082 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.861 2.00 2.00 1.00 44.9950 312.861 1.000 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.157 2.00 2.00 1.00 44.9950 408.157 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.260 2.00 2.00 1.00 44.9950 339.260 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.961 2.00 2.00 1.00 44.9950 407.961 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.143 2.00 2.00 1.00 44.9950 408.143 1.000 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.209 2.00 2.00 1.00 44.9950 339.209 1.000 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.873 2.00 2.00 1.00 44.9950 407.873 1.000 1.000 44.9950 0.11


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   803.211 803.2112 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   216.301 216.3006 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   286.162 286.1620 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   358.070 358.0703 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   137.667 137.6667 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   263.090 263.0903 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   403.716 403.7159 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   215.310 215.3102 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   291.151 291.1513 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   357.635 357.6351 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   147.404 147.4043 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   262.456 262.4557 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   253.269 253.2688 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   288.561 288.5613 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   419.057 419.0569 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   181.790 181.7902 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   220.340 220.3402 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   391.041 391.0412 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 803.21 803.211 803.21 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 216.30 216.301 216.30 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 286.16 286.162 286.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 358.07 358.070 358.07 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 137.67 137.667 137.67 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.09 263.090 263.09 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.72 403.716 403.72 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.31 215.310 215.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 291.15 291.151 291.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.64 357.635 357.64 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 147.40 147.404 147.40 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 262.46 262.456 262.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.06 419.057 419.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 220.34 220.340 220.34 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 288.56 288.561 288.56 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 391.04 391.041 391.04 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 181.79 181.790 181.79 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 253.27 253.269 253.27 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   177.329 177.329 177.329 44.9950 0.254 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   292.083 292.083 292.083 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   361.097 361.097 361.097 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   361.257 361.257 361.257 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   292.063 292.063 292.063 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   361.023 361.023 361.023 44.9950 0.125 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   313.095 313.095 313.095 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   244.111 244.111 244.111 44.9950 0.184 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   312.940 312.940 312.940 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   313.127 313.127 313.127 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   244.082 244.082 244.082 44.9950 0.184 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   312.861 312.861 312.861 44.9950 0.144 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   407.873 407.873 407.873 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   407.961 407.961 407.961 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   408.157 408.157 408.157 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   339.209 339.209 339.209 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   339.260 339.260 339.260 44.9950 0.133 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   408.143 408.143 408.143 44.9950 0.110 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 177.33 177.329 177.33 177.33 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.08 292.083 292.08 292.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 361.10 361.097 361.10 361.10 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.26 361.257 361.26 361.26 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 292.06 292.063 292.06 292.06 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 361.02 361.023 361.02 361.02 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 313.10 313.095 313.10 313.10 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.11 244.111 244.11 244.11 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.94 312.940 312.94 312.94 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 313.13 313.127 313.13 313.13 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 244.08 244.082 244.08 244.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.86 312.861 312.86 312.86 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.16 408.157 408.16 408.16 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.26 339.260 339.26 339.26 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.96 407.961 407.96 407.96 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.14 408.143 408.14 408.14 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.21 339.209 339.21 339.21 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.87 407.873 407.87 407.87 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Sec1.1A-General Information

Data
Weather File ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [ft2] 31210.78
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 31210.78 21609.96 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1766.50
Number of hours cooling loads not met 0.00
Number of hours not met 1766.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 7846.54 353913.75 0.00 0.00
Space Cooling 6355.02 7985.32 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8243.82 2299.99 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3793.07 116707.15 0.00 0.00
Receptacle Equipment 87836.46 15395.85 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 117938.10   11639.61   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 402689.88
Natural Gas 0.00 1163960.74
Additional 0.00 0.00
Total 299910.33 1566650.62


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.41
Space Heating 0.00
Space Cooling 0.20
Fans-Interior 0.26
Service Water Heating 0.00
Receptacle Equipment 2.81
Miscellaneous 0.08
Subtotal 3.78


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 7.36
Service Water Heating 3.56
Miscellaneous 0.00
Subtotal 10.92


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 2.82
Space Heating 50.08
Space Cooling 1.39
Fans-Interior 1.80
Service Water Heating 24.21
Receptacle Equipment 19.14
Miscellaneous 0.56



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 803.21
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 292.08
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 361.10
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 361.26
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 292.06
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 361.02
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 403.72
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 244.11
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 312.94
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 357.64
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 244.08
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 312.86
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 407.87
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 407.96
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 419.06
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 339.21
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 339.26
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 408.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 803.21
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.08
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 361.10
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.26
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 292.06
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 361.02
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 403.72
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.11
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.94
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 357.64
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 244.08
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 312.86
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 419.06
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 339.26
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 407.96
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 408.14
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 339.21
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 407.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 803.21 1.78 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 292.08 0.648885 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 361.10 0.802205 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 361.26 0.802559 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 292.06 0.648840 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 361.02 0.802039 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 403.72 0.896885 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 244.11 0.542311 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 312.94 0.695220 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 357.64 0.794513 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 244.08 0.542246 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 312.86 0.695043 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 419.06 0.930966 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 339.26 0.753692 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 407.96 0.906315 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 408.14 0.906721 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 339.21 0.753577 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 407.87 0.906120 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 803.21 803.21 803.21 1.78 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 292.08 292.08 292.08 0.648885 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 361.10 361.10 361.10 0.802205 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 361.26 361.26 361.26 0.802559 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 292.06 292.06 292.06 0.648840 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 361.02 361.02 361.02 0.802039 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 403.72 403.72 403.72 0.896885 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 244.11 244.11 244.11 0.542311 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 312.94 312.94 312.94 0.695220 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 357.64 357.64 357.64 0.794513 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 244.08 244.08 244.08 0.542246 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 312.86 312.86 312.86 0.695043 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 419.06 419.06 419.06 0.930966 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 339.26 339.26 339.26 0.753692 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 407.96 407.96 407.96 0.906315 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 408.14 408.14 408.14 0.906721 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 339.21 339.21 339.21 0.753577 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 407.87 407.87 407.87 0.906120 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 48354.65 4.88 672.29
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 21106.22 2.13 274.69
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 24786.00 2.50 328.69
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 24794.49 2.50 328.81
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 21105.14 2.13 274.67
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 24782.01 2.50 328.63
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 27056.39 2.73 361.86
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 18547.50 1.87 236.88
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 22217.03 2.24 290.95
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 24599.78 2.48 325.93
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 18545.94 1.87 236.85
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 22212.80 2.24 290.89
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 27876.05 2.81 373.82
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 23621.33 2.38 311.63
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 27284.44 2.75 365.18
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 27294.18 2.75 365.33
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 23618.58 2.38 311.59
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 27279.77 2.75 365.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 803.21
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 292.08
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 361.10
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 361.26
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 292.06
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 361.02
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 403.72
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 244.11
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 312.94
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 357.64
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 244.08
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 312.86
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 419.06
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 339.26
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 407.96
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 408.14
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 339.21
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 407.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 6.14 115.14
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 6.14
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 456778.65 45.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:45:20

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 126.436 2.901 402.891 12.846 15.747
February 230.925 9.967 257.346 7.918 17.885
March 488.530 28.144 94.667 2.713 30.857
April 675.836 80.862 5.298 0.061 80.923
May 744.000 128.285 0.000 0.000 128.285
June 720.000 153.211 0.000 0.000 153.211
July 744.000 163.891 0.000 0.000 163.891
August 744.000 147.582 0.000 0.000 147.582
September 720.000 98.543 0.000 0.000 98.543
October 612.178 47.177 20.880 0.218 47.395
November 69.064 1.056 337.344 8.663 9.719
December 58.869 2.374 535.709 16.215 18.589
           
Annual Sum or Average 5933.838 863.993 1654.134 48.633 912.627
Minimum of Months 58.869 1.056 0.000 0.000 9.719
Maximum of Months 744.000 163.891 535.709 16.215 163.891



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 529.277 30.168 61.569
February 0.000 0.000 488.133 23.156 50.024
March 0.000 0.000 574.977 17.654 41.164
April 52.942 1.153 470.902 7.289 14.120
May 208.771 5.961 253.288 1.410 7.371
June 431.412 16.490 23.625 0.064 16.554
July 480.558 20.903 21.167 0.047 20.951
August 368.669 14.043 67.917 0.383 14.426
September 86.083 1.611 439.154 3.399 5.010
October 2.250 0.023 606.507 11.561 27.812
November 0.000 0.000 406.330 24.876 70.739
December 0.000 0.000 594.578 34.437 56.287
           
Annual Sum or Average 1630.686 60.184 4475.854 154.445 386.027
Minimum of Months 0.000 0.000 21.167 0.047 5.010
Maximum of Months 480.558 20.903 606.507 34.437 70.739



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.950 71.745 71.754
February 0.000 0.000 671.811 55.996 56.030
March 0.000 0.000 732.953 44.124 44.330
April 74.466 2.077 474.882 18.011 24.676
May 314.624 13.975 173.063 3.123 23.864
June 498.268 27.075 19.000 0.201 28.282
July 510.573 32.785 18.250 0.153 34.994
August 387.015 19.830 51.167 0.831 25.124
September 93.005 2.217 412.833 9.001 19.451
October 2.906 0.042 715.887 33.191 34.602
November 0.000 0.000 719.873 67.687 67.710
December 0.000 0.000 743.950 76.131 76.140
           
Annual Sum or Average 1880.857 98.000 5477.618 380.193 506.957
Minimum of Months 0.000 0.000 18.250 0.153 19.451
Maximum of Months 510.573 32.785 743.950 76.131 76.140



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.187 63.187
February 0.000 0.000 672.000 52.264 52.264
March 0.000 0.000 734.257 45.213 46.940
April 22.183 0.821 538.741 19.352 37.161
May 127.833 5.130 301.685 4.102 23.356
June 401.042 19.438 29.687 0.227 20.183
July 435.333 21.390 37.125 0.210 22.188
August 248.211 10.051 115.730 1.435 20.235
September 9.958 0.173 501.794 10.565 27.931
October 0.000 0.000 728.712 32.476 35.056
November 0.000 0.000 720.000 59.761 59.761
December 0.000 0.000 744.000 66.399 66.399
           
Annual Sum or Average 1244.561 57.002 5867.733 355.192 474.662
Minimum of Months 0.000 0.000 29.687 0.210 20.183
Maximum of Months 435.333 21.390 744.000 66.399 66.399



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 42.393 42.393
February 0.000 0.000 672.000 35.257 35.257
March 0.000 0.000 743.752 31.113 31.142
April 0.000 0.000 638.823 14.881 21.349
May 71.129 1.201 337.760 2.702 5.559
June 419.053 11.598 21.812 0.099 11.698
July 480.488 14.941 25.250 0.091 15.094
August 263.583 6.308 110.132 0.921 8.357
September 0.000 0.000 582.067 7.182 8.524
October 0.000 0.000 743.347 21.344 21.439
November 0.000 0.000 720.000 40.224 40.224
December 0.000 0.000 744.000 44.611 44.611
           
Annual Sum or Average 1234.254 34.049 6082.944 240.818 285.646
Minimum of Months 0.000 0.000 21.812 0.091 5.559
Maximum of Months 480.488 14.941 744.000 44.611 44.611



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 71.953 71.953
February 0.000 0.000 672.000 58.872 58.872
March 0.000 0.000 743.950 49.411 49.420
April 1.917 0.017 642.092 22.741 23.704
May 243.575 7.200 215.200 3.660 15.568
June 508.426 22.529 19.250 0.201 23.432
July 511.929 27.165 25.000 0.181 28.871
August 323.449 11.973 86.112 1.173 17.301
September 3.400 0.018 542.946 11.465 15.709
October 0.000 0.000 744.000 36.062 36.062
November 0.000 0.000 720.000 68.242 68.242
December 0.000 0.000 744.000 75.787 75.787
           
Annual Sum or Average 1592.696 68.902 5898.551 399.747 484.921
Minimum of Months 0.000 0.000 19.250 0.181 15.568
Maximum of Months 511.929 27.165 744.000 75.787 75.787



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 58.451 58.451
February 0.000 0.000 672.000 45.453 45.453
March 0.000 0.000 729.646 35.734 35.734
April 105.329 4.696 449.314 13.206 20.843
May 260.542 12.656 195.004 2.173 22.574
June 449.507 26.970 19.693 0.091 27.669
July 489.575 29.845 15.333 0.081 30.303
August 372.690 19.467 59.717 0.641 23.489
September 80.650 2.564 442.888 7.200 13.385
October 1.750 0.013 719.750 26.390 26.403
November 0.000 0.000 720.000 54.844 54.844
December 0.000 0.000 744.000 62.773 62.773
           
Annual Sum or Average 1760.043 96.212 5511.345 307.037 421.921
Minimum of Months 0.000 0.000 15.333 0.081 13.385
Maximum of Months 489.575 29.845 744.000 62.773 62.773



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 31.431 31.431
February 0.000 0.000 672.000 24.104 24.104
March 0.000 0.000 727.896 18.925 19.211
April 67.200 1.438 448.587 6.964 11.455
May 247.729 7.142 184.933 0.985 8.814
June 489.262 18.687 15.781 0.034 18.733
July 542.838 23.048 14.000 0.036 23.164
August 402.562 15.306 54.500 0.323 15.636
September 91.508 1.678 408.729 3.307 5.396
October 2.708 0.017 707.000 13.494 13.571
November 0.000 0.000 720.000 29.923 29.923
December 0.000 0.000 744.000 33.404 33.404
           
Annual Sum or Average 1843.809 67.318 5441.427 162.931 234.842
Minimum of Months 0.000 0.000 14.000 0.034 5.396
Maximum of Months 542.838 23.048 744.000 33.404 33.404



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 62.782 62.782
February 0.000 0.000 672.000 48.645 48.645
March 0.000 0.000 726.979 37.489 38.049
April 88.391 2.520 440.742 14.481 22.042
May 354.443 15.856 126.458 1.909 23.765
June 531.735 29.677 13.833 0.095 30.552
July 548.998 34.868 13.000 0.103 35.707
August 422.791 21.296 39.083 0.579 24.586
September 99.158 2.357 384.475 7.584 18.630
October 3.375 0.044 706.375 28.937 30.820
November 0.000 0.000 720.000 59.135 59.135
December 0.000 0.000 744.000 67.216 67.216
           
Annual Sum or Average 2048.892 106.618 5330.946 328.956 461.930
Minimum of Months 0.000 0.000 13.000 0.095 18.630
Maximum of Months 548.998 34.868 744.000 67.216 67.216



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 60.261 60.261
February 0.000 0.000 672.000 49.745 49.745
March 0.000 0.000 731.529 42.623 44.839
April 26.562 0.896 513.168 17.273 35.787
May 152.479 5.902 242.825 2.935 21.211
June 449.485 21.883 20.258 0.133 22.313
July 487.062 23.787 19.688 0.129 24.191
August 282.963 11.115 78.573 1.121 18.284
September 8.467 0.146 482.730 9.875 27.972
October 0.000 0.000 725.504 31.116 34.259
November 0.000 0.000 720.000 57.312 57.312
December 0.000 0.000 744.000 63.524 63.524
           
Annual Sum or Average 1407.019 63.729 5694.275 336.047 459.697
Minimum of Months 0.000 0.000 19.688 0.129 18.284
Maximum of Months 487.062 23.787 744.000 63.524 63.524



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 32.112 32.112
February 0.000 0.000 672.000 26.489 26.489
March 0.000 0.000 743.900 23.084 23.096
April 0.000 0.000 616.008 10.444 15.453
May 100.625 1.851 245.108 1.381 4.067
June 505.610 14.391 12.500 0.034 14.425
July 552.262 17.692 14.500 0.040 17.800
August 303.958 7.615 83.461 0.570 9.051
September 0.000 0.000 558.048 5.249 6.191
October 0.000 0.000 743.637 16.017 16.061
November 0.000 0.000 720.000 30.508 30.508
December 0.000 0.000 744.000 33.777 33.777
           
Annual Sum or Average 1462.456 41.548 5897.162 179.703 229.031
Minimum of Months 0.000 0.000 12.500 0.034 4.067
Maximum of Months 552.262 17.692 744.000 33.777 33.777



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.837 63.837
February 0.000 0.000 672.000 52.066 52.066
March 0.000 0.000 744.000 43.158 43.158
April 5.824 0.027 602.325 18.886 20.447
May 290.362 8.883 151.625 2.332 15.808
June 545.368 25.586 12.500 0.090 26.523
July 553.446 29.645 14.500 0.106 30.519
August 357.448 13.485 62.583 0.808 17.138
September 6.042 0.017 506.142 9.906 15.499
October 0.000 0.000 744.000 32.083 32.083
November 0.000 0.000 720.000 60.897 60.897
December 0.000 0.000 744.000 67.460 67.460
           
Annual Sum or Average 1758.490 77.643 5717.675 351.628 445.435
Minimum of Months 0.000 0.000 12.500 0.090 15.499
Maximum of Months 553.446 29.645 744.000 67.460 67.460



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 86.981 86.981
February 0.000 0.000 672.000 69.048 69.048
March 0.000 0.000 744.000 56.826 56.826
April 62.038 2.733 517.895 23.098 30.421
May 201.104 10.176 234.376 4.600 31.922
June 414.237 25.818 33.890 0.328 28.974
July 440.079 28.997 30.438 0.287 31.471
August 312.714 17.211 87.031 1.442 30.531
September 48.125 1.308 503.892 13.498 22.233
October 0.000 0.000 737.125 42.729 42.729
November 0.000 0.000 720.000 81.960 81.960
December 0.000 0.000 744.000 92.635 92.635
           
Annual Sum or Average 1478.297 86.243 5768.646 473.432 605.730
Minimum of Months 0.000 0.000 30.438 0.287 22.233
Maximum of Months 440.079 28.997 744.000 92.635 92.635



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 50.519 50.519
February 0.000 0.000 672.000 39.862 39.862
March 0.000 0.000 744.000 32.821 32.821
April 36.000 0.651 528.033 13.619 17.618
May 182.908 5.660 272.456 2.636 8.896
June 435.784 18.353 27.087 0.156 18.531
July 486.541 22.966 29.484 0.143 23.215
August 343.629 13.770 101.354 0.875 14.697
September 46.979 0.600 511.417 7.227 8.051
October 0.000 0.000 733.000 23.948 23.996
November 0.000 0.000 720.000 47.793 47.793
December 0.000 0.000 744.000 53.934 53.934
           
Annual Sum or Average 1531.842 62.000 5826.829 273.532 339.932
Minimum of Months 0.000 0.000 27.087 0.143 8.051
Maximum of Months 486.541 22.966 744.000 53.934 53.934



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 80.846 80.846
February 0.000 0.000 672.000 63.648 63.648
March 0.000 0.000 742.900 50.888 50.888
April 51.340 1.166 527.879 21.104 25.955
May 295.766 12.440 184.000 3.435 21.932
June 506.010 28.567 21.125 0.252 29.857
July 521.615 34.472 26.750 0.239 36.173
August 370.762 19.120 78.750 1.175 23.749
September 58.867 0.968 484.488 11.721 17.955
October 0.000 0.000 732.500 38.979 39.423
November 0.000 0.000 720.000 76.345 76.345
December 0.000 0.000 744.000 86.204 86.204
           
Annual Sum or Average 1804.361 96.733 5678.392 434.835 552.975
Minimum of Months 0.000 0.000 21.125 0.239 17.955
Maximum of Months 521.615 34.472 744.000 86.204 86.204



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 73.306 73.306
February 0.000 0.000 672.000 60.401 60.401
March 0.000 0.000 742.800 52.071 52.296
April 22.187 0.734 558.727 22.556 37.985
May 137.483 5.889 297.657 4.479 27.832
June 411.868 22.567 31.177 0.279 23.641
July 447.086 24.758 42.762 0.274 25.750
August 248.863 11.330 127.146 1.781 24.653
September 4.417 0.101 536.638 13.363 29.608
October 0.000 0.000 735.350 38.369 40.116
November 0.000 0.000 720.000 69.782 69.782
December 0.000 0.000 744.000 77.226 77.226
           
Annual Sum or Average 1271.905 65.379 5952.258 413.886 542.596
Minimum of Months 0.000 0.000 31.177 0.274 23.641
Maximum of Months 447.086 24.758 744.000 77.226 77.226



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 51.998 51.998
February 0.000 0.000 672.000 42.982 42.982
March 0.000 0.000 743.900 37.410 37.427
April 0.000 0.000 634.518 17.493 23.980
May 95.375 2.143 348.275 3.181 6.326
June 439.542 15.261 24.219 0.141 15.405
July 499.620 18.812 29.125 0.143 19.028
August 266.840 7.961 140.821 1.273 10.611
September 0.000 0.000 607.131 9.476 11.554
October 0.000 0.000 743.900 26.695 26.712
November 0.000 0.000 720.000 49.732 49.732
December 0.000 0.000 744.000 54.899 54.899
           
Annual Sum or Average 1301.377 44.178 6151.888 295.423 350.656
Minimum of Months 0.000 0.000 24.219 0.141 6.326
Maximum of Months 499.620 18.812 744.000 54.899 54.899



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 81.995 81.995
February 0.000 0.000 672.000 66.961 66.961
March 0.000 0.000 744.000 56.104 56.104
April 0.000 0.000 650.629 25.509 26.716
May 243.675 7.172 220.592 3.836 15.783
June 519.219 25.544 20.750 0.239 26.767
July 527.417 30.404 29.000 0.246 31.870
August 323.350 13.039 122.250 1.572 17.895
September 0.000 0.000 606.275 14.250 17.386
October 0.000 0.000 744.000 41.990 41.990
November 0.000 0.000 720.000 78.230 78.230
December 0.000 0.000 744.000 86.538 86.538
           
Annual Sum or Average 1613.660 76.160 6017.496 457.468 548.233
Minimum of Months 0.000 0.000 20.750 0.239 15.783
Maximum of Months 527.417 30.404 744.000 86.538 86.538



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.17
April 0.00 0.00 0.49
May 0.00 0.00 0.74
June 0.00 0.00 0.92
July 0.00 0.00 0.96
August 0.00 0.00 0.86
September 0.00 0.00 0.60
October 0.00 0.00 0.28
November 0.00 0.00 0.01
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.43
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.96



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.09
July 0.00 0.00 0.12
August 0.00 0.00 0.08
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.12



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.15
July 0.00 0.00 0.18
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.18



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.11
July 0.00 0.00 0.12
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.12



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.06
July 0.00 0.00 0.08
August 0.00 0.00 0.03
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.13
July 0.00 0.00 0.15
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.15
July 0.00 0.00 0.17
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.11
July 0.00 0.00 0.13
August 0.00 0.00 0.09
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.17
July 0.00 0.00 0.20
August 0.00 0.00 0.12
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.13
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.05
June 0.00 0.00 0.15
July 0.00 0.00 0.17
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.16
August 0.00 0.00 0.10
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.10
July 0.00 0.00 0.13
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.13



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.19
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.14
August 0.00 0.00 0.06
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.10
August 0.00 0.00 0.04
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.14
July 0.00 0.00 0.17
August 0.00 0.00 0.07
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:45:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2028.23 1510.07
February 0.00 0.00 2022.03 1359.77
March 0.00 0.00 2008.27 1495.22
April 0.00 0.00 2006.77 1445.90
May 0.00 0.00 1986.55 1479.04
June 0.00 0.00 1911.90 1377.55
July 0.00 0.00 1836.65 1367.44
August 0.00 0.00 1783.80 1328.09
September 0.00 0.00 1777.99 1281.06
October 0.00 0.00 1816.13 1352.16
November 0.00 0.00 1907.22 1374.17
December 0.00 0.00 1998.06 1487.61
         
Annual Sum or Average 0.00 0.00 1923.07 16858.07
Minimum of Months 0.00 0.00 1777.99 1281.06
Maximum of Months 0.00 0.00 2028.23 1510.07