Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:45
Tabular Output Report in Format: HTML
Building: Small Office
Environment: Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Simulation Timestamp: 2015-09-09 18:45:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 195.78 | 383.02 | 383.02 |
Net Site Energy | 195.78 | 383.02 | 383.02 |
Total Source Energy | 618.29 | 1209.59 | 1209.59 |
Net Source Energy | 618.29 | 1209.59 | 1209.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.16 |
Net Conditioned Building Area | 511.16 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 7.10 | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.04 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 194.94 | 0.84 | 0.00 | 0.00 | 0.00 | 58.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 7.10 | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 52.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18.04 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.78 | 1.64 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 103.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 381.37 | 1.64 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.78 | 1.64 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 103.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 381.37 | 1.64 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 194.94 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 194.94 | 100.00 |
Total On-Site and Utility Electric Sources | 194.94 | 100.00 |
Total Electricity End Uses | 194.94 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 58.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 58.31 | 100.00 |
Total Water End Uses | 58.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 26.33 |
Time Setpoint Not Met During Occupied Cooling | 11.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1238.67 |
Table of Contents
TopMONTHLY INDOOR TEMP
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |OUTDOOR AIR SUMMARY
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |VENTILATION LOAD COMPONENTS
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |OVERALL HVAC AIR SYSTEM LOADS
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK NET ELECTRICAL DEMAND
| Meter |SETPOINTS NOT MET WITH TEMPERATURES
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |COMFORT REPORT - SIMPLE 55
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - COOLING
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - HEATING
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - ELECTRIC
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |SPACE LOADS
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY PART 1
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:45 |
RunPeriod | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Latitude [deg] | 49.18 |
Longitude [deg] | -123.2 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.68 | 16.73 | 11.16 | 20.64 | 11.16 |
Window-Wall Ratio [%] | 21.20 | 19.81 | 19.81 | 24.44 | 19.81 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.68 | 16.73 | 11.16 | 20.64 | 11.16 |
Window-Wall Ratio [%] | 21.20 | 19.81 | 19.81 | 24.44 | 19.81 |
Total | |
Gross Roof Area [m2] | 598.76 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_ZN | 149.66 | Yes | Yes | 456.46 | 1.00 | 0.00 | 0.00 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_1 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 20.64 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_2 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 11.16 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_3 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 16.73 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_4 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 11.16 | 10.7639 | 16.59 | 6.7800 |
ATTIC | 567.98 | No | No | 720.19 | 1.00 | 0.00 | 0.00 | |||
Total | 511.16 | 1559.03 | 281.51 | 59.68 | 10.7639 | 16.59 | 6.7800 | |||
Conditioned Total | 511.16 | 1559.03 | 281.51 | 59.68 | 10.7639 | 16.59 | 6.7800 | |||
Unconditioned Total | 567.98 | 720.19 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 567.98 | 720.19 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00 | -7.00 | Wetbulb [C] | 2.90 | 100.00 |
VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 7.60 | 18.20 | Wetbulb [C] | 3.60 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_ZN_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 149.66 | 270.00 | 180.00 | |
PERIMETER_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 84.45 | 180.00 | 90.00 | S |
PERIMETER_ZN_1_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 113.45 | 135.00 | 180.00 | |
PERIMETER_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 56.30 | 90.00 | 90.00 | E |
PERIMETER_ZN_2_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 67.30 | 270.00 | 180.00 | |
PERIMETER_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 84.45 | 0.00 | 90.00 | N |
PERIMETER_ZN_3_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 113.45 | 180.00 | 180.00 | |
PERIMETER_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 56.30 | 270.00 | 90.00 | W |
PERIMETER_ZN_4_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 67.30 | 90.00 | 180.00 | |
ATTIC_SOFFIT_WEST | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 11.44 | 270.00 | 180.00 | |
ATTIC_SOFFIT_SOUTH | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 16.97 | 225.00 | 180.00 | |
ATTIC_SOFFIT_EAST | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 11.44 | 45.00 | 180.00 | |
ATTIC_SOFFIT_NORTH | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 16.97 | 315.00 | 180.00 | |
ATTIC_ROOF_NORTH | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 197.51 | 0.00 | 18.45 | |
ATTIC_ROOF_WEST | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 101.87 | 270.00 | 18.45 | |
ATTIC_ROOF_EAST | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 101.87 | 90.00 | 18.45 | |
ATTIC_ROOF_SOUTH | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 197.51 | 180.00 | 18.45 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.91 | 0.00 | 0.00 | 3.91 | 3.91 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 59.68 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 16.73 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 42.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4594.49 | 3669.41 | 925.08 | 0.80 | 3.91 | |||
PSZ-AC:2 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7769.88 | 6205.46 | 1564.43 | 0.80 | 3.91 | |||
PSZ-AC:3 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4586.17 | 3662.77 | 923.40 | 0.80 | 3.91 | |||
PSZ-AC:4 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3972.09 | 3172.33 | 799.76 | 0.80 | 3.91 | |||
PSZ-AC:5 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5092.74 | 4067.34 | 1025.40 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4377.0 | 3.15 | 10.75 | 11.25 | 10.55 |
PSZ-AC:2 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7402.0 | 3.15 | 10.75 | 11.25 | 10.55 |
PSZ-AC:3 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4369.0 | 3.15 | 10.75 | 11.25 | 10.55 |
PSZ-AC:4 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3784.0 | 3.15 | 10.75 | 11.25 | 10.55 |
PSZ-AC:5 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4851.6 | 3.15 | 10.75 | 11.25 | 10.55 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 4814.7 | 2681.5 | 7.23 | 4 |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 8142.3 | 4534.8 | 7.22 | 4 |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 4806.0 | 2676.6 | 7.22 | 4 |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 4162.5 | 2318.2 | 7.22 | 4 |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 5336.8 | 2972.3 | 7.22 | 4 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 4594.49 | 3.29 | |
PSZ-AC:1 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 3674.44 | 0.80 | |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 7769.88 | 3.29 | |
PSZ-AC:2 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 4929.90 | 0.80 | |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 4586.17 | 3.29 | |
PSZ-AC:3 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 2994.97 | 0.80 | |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 3972.09 | 3.29 | |
PSZ-AC:4 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 4726.83 | 0.80 | |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 5092.74 | 3.29 | |
PSZ-AC:5 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 2982.53 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
PSZ-AC:1 FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.19 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:2 FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 544.87 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:3 FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 321.61 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:4 FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 278.55 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:5 FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 357.13 | 1160.84 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0000 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 0.99 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
CORE_ZN | 3151.89 | 3782.27 | 0.231 | 0.278 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.70 | 0.01029 |
PERIMETER_ZN_1 | 5330.08 | 6396.10 | 0.391 | 0.469 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.87 | 0.01029 |
PERIMETER_ZN_2 | 3146.29 | 3775.55 | 0.231 | 0.277 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 21.68 | 0.01029 |
PERIMETER_ZN_3 | 2724.92 | 3269.91 | 0.200 | 0.240 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 24.62 | 0.01029 |
PERIMETER_ZN_4 | 3493.80 | 4192.55 | 0.256 | 0.308 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 23.56 | 0.01029 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
CORE_ZN | 1044.58 | 1253.50 | 0.045 | 0.065 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -7.00 | 0.00208 |
PERIMETER_ZN_1 | 2760.24 | 3312.28 | 0.119 | 0.143 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.00 | 0.00208 |
PERIMETER_ZN_2 | 1697.02 | 2036.43 | 0.073 | 0.088 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.00 | 0.00208 |
PERIMETER_ZN_3 | 2588.52 | 3106.22 | 0.112 | 0.134 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.00 | 0.00208 |
PERIMETER_ZN_4 | 1686.50 | 2023.80 | 0.073 | 0.087 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.00 | 0.00208 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
PSZ-AC:1 | 0.28 | 0.28 | 0.06 | 0.06 |
PSZ-AC:2 | 0.47 | 0.47 | 0.14 | 0.14 |
PSZ-AC:3 | 0.28 | 0.28 | 0.09 | 0.09 |
PSZ-AC:4 | 0.24 | 0.24 | 0.13 | 0.13 |
PSZ-AC:5 | 0.31 | 0.31 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_ZN | 801.67 | 2885.83 | 71.17 |
PERIMETER_ZN_1 | 1703.50 | 2999.00 | 974.67 |
PERIMETER_ZN_2 | 1664.83 | 3033.33 | 977.83 |
PERIMETER_ZN_3 | 1433.50 | 3236.33 | 1034.50 |
PERIMETER_ZN_4 | 1665.00 | 3141.17 | 1094.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 2215.67 | 3407.17 | 1238.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_ZN | 0.00 | 10.17 | 0.00 | 10.17 |
PERIMETER_ZN_1 | 13.17 | 1.67 | 13.17 | 0.00 |
PERIMETER_ZN_2 | 17.33 | 0.00 | 14.33 | 0.00 |
PERIMETER_ZN_3 | 25.00 | 0.00 | 25.00 | 0.00 |
PERIMETER_ZN_4 | 14.83 | 15.50 | 12.00 | 0.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 29.33 | 27.33 | 26.33 | 11.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:45
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
CORE_ZN DIRECT AIR | 0.277553 |
PERIMETER_ZN_1 DIRECT AIR | 0.469379 |
PERIMETER_ZN_2 DIRECT AIR | 0.277050 |
PERIMETER_ZN_3 DIRECT AIR | 0.239954 |
PERIMETER_ZN_4 DIRECT AIR | 0.307652 |
Maximum Flow Rate [m3/s] | |
PSZ-AC:1 AIR LOOP MAIN BRANCH | 0.277553 |
PSZ-AC:2 AIR LOOP MAIN BRANCH | 0.469379 |
PSZ-AC:3 AIR LOOP MAIN BRANCH | 0.277050 |
PSZ-AC:4 AIR LOOP MAIN BRANCH | 0.239954 |
PSZ-AC:5 AIR LOOP MAIN BRANCH | 0.307652 |
Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 0.277553 |
PSZ-AC:2 | 0.469379 |
PSZ-AC:3 | 0.277050 |
PSZ-AC:4 | 0.239954 |
PSZ-AC:5 | 0.307652 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 0.277553 | 0.064618 |
PSZ-AC:2_OA_CONTROLLER | 0.469379 | 0.048985 |
PSZ-AC:3_OA_CONTROLLER | 0.277050 | 0.029058 |
PSZ-AC:4_OA_CONTROLLER | 0.239954 | 0.048985 |
PSZ-AC:5_OA_CONTROLLER | 0.307652 | 0.029058 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | 0.277553 | 4594.49 | 0.798655 |
PSZ-AC:2 HEAT PUMP DX COOLING COIL | 0.469379 | 7769.88 | 0.798655 |
PSZ-AC:3 HEAT PUMP DX COOLING COIL | 0.277050 | 4586.17 | 0.798655 |
PSZ-AC:4 HEAT PUMP DX COOLING COIL | 0.239954 | 3972.09 | 0.798655 |
PSZ-AC:5 HEAT PUMP DX COOLING COIL | 0.307652 | 5092.74 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Maximum Supply Air Temperature from Supplemental Heater [C] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_HEATPUMP | 0.277553 | 0.277553 | 0.277553 | 0.277553 | 4594.49 | 4594.49 | 40.00 | 3674.44 | 1.00 |
PSZ-AC:2_HEATPUMP | 0.469379 | 0.469379 | 0.469379 | 0.469379 | 7769.88 | 7769.88 | 40.00 | 4929.90 | 1.00 |
PSZ-AC:3_HEATPUMP | 0.277050 | 0.277050 | 0.277050 | 0.277050 | 4586.17 | 4586.17 | 40.00 | 2994.97 | 1.00 |
PSZ-AC:4_HEATPUMP | 0.239954 | 0.239954 | 0.239954 | 0.239954 | 3972.09 | 3972.09 | 40.00 | 4726.83 | 1.00 |
PSZ-AC:5_HEATPUMP | 0.307652 | 0.307652 | 0.307652 | 0.307652 | 5092.74 | 5092.74 | 40.00 | 2982.53 | 1.00 |
Maximum Flow Rate [m3/s] | |
PSZ-AC:1 FAN | 0.277553 |
PSZ-AC:2 FAN | 0.469379 |
PSZ-AC:3 FAN | 0.277050 |
PSZ-AC:4 FAN | 0.239954 |
PSZ-AC:5 FAN | 0.307652 |
Rated Air Flow Rate [m3/s] | Rated Total Heating Capacity [W] | Resistive Defrost Heater Capacity | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | 0.277553 | 4594.49 | 0.000000 |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | 0.469379 | 7769.88 | 0.000000 |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | 0.277050 | 4586.17 | 0.000000 |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | 0.239954 | 3972.09 | 0.000000 |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | 0.307652 | 5092.74 | 0.000000 |
Nominal Capacity [W] | |
PSZ-AC:1 HEAT PUMP DX SUPP HEATING COIL | 3674.44 |
PSZ-AC:2 HEAT PUMP DX SUPP HEATING COIL | 4929.90 |
PSZ-AC:3 HEAT PUMP DX SUPP HEATING COIL | 2994.97 |
PSZ-AC:4 HEAT PUMP DX SUPP HEATING COIL | 4726.83 |
PSZ-AC:5 HEAT PUMP DX SUPP HEATING COIL | 2982.53 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000004 | 0.003036 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000004 | 0.000000 |
Report: MONTHLY INDOOR TEMP
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | 3.20 |
February | 21.61 | 5.10 |
March | 21.94 | 6.09 |
April | 22.63 | 8.68 |
May | 23.33 | 11.83 |
June | 24.60 | 15.06 |
July | 25.15 | 16.98 |
August | 24.99 | 17.08 |
September | 24.67 | 13.78 |
October | 22.95 | 9.83 |
November | 21.75 | 5.28 |
December | 21.13 | 3.63 |
Annual Sum or Average | 22.99 | 9.74 |
Minimum of Months | 21.07 | 3.20 |
Maximum of Months | 25.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | 3.20 |
February | 20.47 | 5.10 |
March | 20.72 | 6.09 |
April | 21.61 | 8.68 |
May | 22.37 | 11.83 |
June | 23.80 | 15.06 |
July | 24.54 | 16.98 |
August | 24.48 | 17.08 |
September | 23.91 | 13.78 |
October | 21.63 | 9.83 |
November | 20.12 | 5.28 |
December | 19.40 | 3.63 |
Annual Sum or Average | 21.89 | 9.74 |
Minimum of Months | 19.40 | 3.20 |
Maximum of Months | 24.54 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.22 | 3.20 |
February | 20.02 | 5.10 |
March | 20.52 | 6.09 |
April | 21.53 | 8.68 |
May | 22.57 | 11.83 |
June | 23.91 | 15.06 |
July | 24.67 | 16.98 |
August | 24.44 | 17.08 |
September | 23.60 | 13.78 |
October | 21.44 | 9.83 |
November | 19.94 | 5.28 |
December | 19.06 | 3.63 |
Annual Sum or Average | 21.75 | 9.74 |
Minimum of Months | 19.06 | 3.20 |
Maximum of Months | 24.67 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.25 | 3.20 |
February | 19.82 | 5.10 |
March | 20.29 | 6.09 |
April | 21.15 | 8.68 |
May | 22.25 | 11.83 |
June | 23.86 | 15.06 |
July | 24.45 | 16.98 |
August | 24.21 | 17.08 |
September | 23.42 | 13.78 |
October | 21.25 | 9.83 |
November | 19.91 | 5.28 |
December | 19.10 | 3.63 |
Annual Sum or Average | 21.59 | 9.74 |
Minimum of Months | 19.10 | 3.20 |
Maximum of Months | 24.45 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.27 | 3.20 |
February | 20.09 | 5.10 |
March | 20.64 | 6.09 |
April | 21.73 | 8.68 |
May | 22.84 | 11.83 |
June | 24.39 | 15.06 |
July | 25.19 | 16.98 |
August | 24.70 | 17.08 |
September | 23.85 | 13.78 |
October | 21.41 | 9.83 |
November | 19.98 | 5.28 |
December | 19.09 | 3.63 |
Annual Sum or Average | 21.94 | 9.74 |
Minimum of Months | 19.09 | 3.20 |
Maximum of Months | 25.19 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.74 | 3.20 |
February | 5.69 | 5.10 |
March | 8.11 | 6.09 |
April | 12.94 | 8.68 |
May | 17.52 | 11.83 |
June | 21.43 | 15.06 |
July | 23.74 | 16.98 |
August | 22.16 | 17.08 |
September | 17.06 | 13.78 |
October | 10.80 | 9.83 |
November | 4.90 | 5.28 |
December | 3.34 | 3.63 |
Annual Sum or Average | 12.58 | 9.74 |
Minimum of Months | 2.74 | 3.20 |
Maximum of Months | 23.74 | 17.08 |
Report: OUTDOOR AIR SUMMARY
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE [Invalid/Undefined] | |
January | 357.000 | 5.127 | 0.397 | 0.000 |
February | 323.000 | 5.127 | 0.395 | 0.000 |
March | 391.000 | 5.127 | 0.397 | 0.000 |
April | 340.000 | 5.127 | 0.397 | 0.000 |
May | 374.000 | 5.127 | 0.399 | 0.000 |
June | 374.000 | 5.127 | 0.399 | 0.000 |
July | 340.000 | 5.127 | 0.399 | 0.000 |
August | 391.000 | 5.127 | 0.400 | 0.000 |
September | 340.000 | 5.127 | 0.400 | 0.000 |
October | 357.000 | 5.127 | 0.399 | 0.000 |
November | 357.000 | 5.127 | 0.397 | 0.000 |
December | 340.000 | 5.127 | 0.395 | 0.000 |
Annual Sum or Average | 4284.000 | 5.127 | 0.398 | 0.000 |
Minimum of Months | 323.000 | 5.127 | 0.395 | 0.000 |
Maximum of Months | 391.000 | 5.127 | 0.400 | 0.000 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 3.886 | 0.395 | 0.458 |
February | 323.000 | 3.886 | 0.393 | 0.441 |
March | 391.000 | 3.886 | 0.395 | 0.445 |
April | 340.000 | 3.886 | 0.395 | 0.449 |
May | 374.000 | 3.886 | 0.397 | 0.446 |
June | 374.000 | 3.886 | 0.397 | 0.421 |
July | 340.000 | 3.886 | 0.398 | 0.420 |
August | 391.000 | 3.886 | 0.400 | 0.430 |
September | 340.000 | 3.886 | 0.399 | 0.455 |
October | 357.000 | 3.886 | 0.396 | 0.449 |
November | 357.000 | 3.886 | 0.395 | 0.452 |
December | 340.000 | 3.886 | 0.393 | 0.476 |
Annual Sum or Average | 4284.000 | 3.886 | 0.396 | 0.445 |
Minimum of Months | 323.000 | 3.886 | 0.393 | 0.420 |
Maximum of Months | 391.000 | 3.886 | 0.400 | 0.476 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 2.305 | 0.395 | 0.094 |
February | 323.000 | 2.305 | 0.394 | 0.077 |
March | 391.000 | 2.305 | 0.395 | 0.083 |
April | 340.000 | 2.305 | 0.396 | 0.091 |
May | 374.000 | 2.305 | 0.397 | 0.092 |
June | 374.000 | 2.305 | 0.398 | 0.067 |
July | 340.000 | 2.305 | 0.398 | 0.068 |
August | 391.000 | 2.305 | 0.400 | 0.080 |
September | 340.000 | 2.305 | 0.399 | 0.103 |
October | 357.000 | 2.305 | 0.397 | 0.092 |
November | 357.000 | 2.305 | 0.395 | 0.089 |
December | 340.000 | 2.305 | 0.393 | 0.114 |
Annual Sum or Average | 4284.000 | 2.305 | 0.397 | 0.087 |
Minimum of Months | 323.000 | 2.305 | 0.393 | 0.067 |
Maximum of Months | 391.000 | 2.305 | 0.400 | 0.114 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 3.886 | 0.395 | 0.083 |
February | 323.000 | 3.886 | 0.393 | 0.068 |
March | 391.000 | 3.886 | 0.395 | 0.074 |
April | 340.000 | 3.886 | 0.395 | 0.081 |
May | 374.000 | 3.886 | 0.397 | 0.081 |
June | 374.000 | 3.886 | 0.398 | 0.059 |
July | 340.000 | 3.886 | 0.398 | 0.060 |
August | 391.000 | 3.886 | 0.400 | 0.071 |
September | 340.000 | 3.886 | 0.399 | 0.091 |
October | 357.000 | 3.886 | 0.397 | 0.082 |
November | 357.000 | 3.886 | 0.395 | 0.079 |
December | 340.000 | 3.886 | 0.393 | 0.102 |
Annual Sum or Average | 4284.000 | 3.886 | 0.396 | 0.078 |
Minimum of Months | 323.000 | 3.886 | 0.393 | 0.059 |
Maximum of Months | 391.000 | 3.886 | 0.400 | 0.102 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 2.305 | 0.395 | 0.094 |
February | 323.000 | 2.305 | 0.394 | 0.077 |
March | 391.000 | 2.305 | 0.395 | 0.083 |
April | 340.000 | 2.305 | 0.396 | 0.091 |
May | 374.000 | 2.305 | 0.398 | 0.092 |
June | 374.000 | 2.305 | 0.398 | 0.067 |
July | 340.000 | 2.305 | 0.399 | 0.068 |
August | 391.000 | 2.305 | 0.400 | 0.080 |
September | 340.000 | 2.305 | 0.399 | 0.103 |
October | 357.000 | 2.305 | 0.397 | 0.092 |
November | 357.000 | 2.305 | 0.395 | 0.089 |
December | 340.000 | 2.305 | 0.393 | 0.114 |
Annual Sum or Average | 4284.000 | 2.305 | 0.397 | 0.087 |
Minimum of Months | 323.000 | 2.305 | 0.393 | 0.067 |
Maximum of Months | 391.000 | 2.305 | 0.400 | 0.114 |
Report: OUTDOOR AIR SUMMARY
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE OCCUPANT COUNT [Invalid/Undefined] | ZONE PEOPLE OCCUPANT COUNT [Invalid/Undefined] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [Invalid/Undefined] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | 0.000 | 0.000 | |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 | 0.000 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.182316E+10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.128975E+09 | 0.000 | 0.000 |
February | 0.162550E+10 | 0.000 | 0.000 | 38185.276 | 0.000 | 0.313170E+08 | 0.229977E+08 | 0.000 |
March | 0.166776E+10 | 0.000 | 0.000 | 337195.691 | 0.000 | 0.302025E+08 | 0.251673E+09 | 0.000 |
April | 0.106563E+10 | 0.000 | 0.000 | 1144482.576 | 0.000 | 0.000 | 0.491862E+09 | 0.000 |
May | 0.543471E+09 | 0.000 | 0.000 | 2971398.377 | 0.000 | 0.000 | 0.857801E+09 | 0.000 |
June | 0.877340E+08 | 5924.806 | 0.000 | 7386329.758 | 0.000 | 0.000 | 0.857252E+09 | 0.000 |
July | 0.400189E+08 | 2656789.835 | 0.000 | 8208804.324 | 177123.349 | 0.000 | 0.520964E+09 | 0.000 |
August | 0.438234E+08 | 482307.806 | 0.000 | 0.102025E+08 | 0.000 | 0.000 | 0.512269E+09 | 0.000 |
September | 0.117890E+09 | 2072749.992 | 0.000 | 7028348.460 | 222505.392 | 0.000 | 0.859555E+09 | 0.000 |
October | 0.817365E+09 | 0.000 | 0.000 | 1662972.825 | 0.000 | 0.000 | 0.733315E+09 | 0.000 |
November | 0.162489E+10 | 0.000 | 0.000 | 296733.769 | 0.000 | 0.396635E+08 | 0.220665E+09 | 0.000 |
December | 0.177974E+10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.927079E+08 | 0.000 | 0.000 |
Annual Sum or Average | 0.112370E+11 | 5217772.440 | 0.000 | 0.392770E+08 | 399628.741 | 0.322866E+09 | 0.532835E+10 | 0.000 |
Minimum of Months | 0.400189E+08 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.182316E+10 | 2656789.835 | 0.000 | 0.102025E+08 | 222505.392 | 0.128975E+09 | 0.859555E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.326334E+09 | 0.000 | 0.000 | 90344.613 | 0.000 | 0.741996E+09 | 0.403304E+08 | 0.000 |
February | 0.402102E+09 | 0.000 | 0.000 | 549878.254 | 0.000 | 0.379553E+09 | 0.142724E+09 | 0.000 |
March | 0.484579E+09 | 0.000 | 0.000 | 922307.655 | 0.000 | 0.366331E+09 | 0.220350E+09 | 0.000 |
April | 0.414658E+09 | 0.000 | 0.000 | 1518544.557 | 0.000 | 0.178231E+09 | 0.230867E+09 | 0.000 |
May | 0.340725E+09 | 0.000 | 0.000 | 1708747.130 | 0.000 | 0.102441E+09 | 0.277993E+09 | 0.000 |
June | 0.183730E+09 | 1334608.488 | 0.000 | 3943492.074 | 3552.335 | 9645253.932 | 0.316394E+09 | 0.000 |
July | 0.116486E+09 | 9483534.315 | 0.000 | 4692843.529 | 308164.117 | 0.000 | 0.203924E+09 | 0.000 |
August | 0.125870E+09 | 0.119594E+08 | 0.000 | 6566716.300 | 0.000 | 0.000 | 0.179272E+09 | 0.000 |
September | 0.200830E+09 | 3583657.832 | 0.000 | 6013590.343 | 106872.834 | 0.261713E+08 | 0.310522E+09 | 0.000 |
October | 0.414194E+09 | 0.000 | 0.000 | 1623916.740 | 0.000 | 0.172181E+09 | 0.210442E+09 | 0.000 |
November | 0.482238E+09 | 0.000 | 0.000 | 428095.641 | 0.000 | 0.470789E+09 | 0.880641E+08 | 0.000 |
December | 0.295023E+09 | 0.000 | 0.000 | 71840.177 | 0.000 | 0.729672E+09 | 0.333411E+08 | 0.000 |
Annual Sum or Average | 0.378677E+10 | 0.263612E+08 | 0.000 | 0.281303E+08 | 418589.287 | 0.317701E+10 | 0.225422E+10 | 0.000 |
Minimum of Months | 0.116486E+09 | 0.000 | 0.000 | 71840.177 | 0.000 | 0.000 | 0.333411E+08 | 0.000 |
Maximum of Months | 0.484579E+09 | 0.119594E+08 | 0.000 | 6566716.300 | 308164.117 | 0.741996E+09 | 0.316394E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.361823E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.320881E+09 | 0.000 | 0.000 |
February | 0.417317E+09 | 0.000 | 0.000 | 19281.181 | 0.000 | 0.145556E+09 | 0.142975E+08 | 0.000 |
March | 0.424468E+09 | 0.000 | 0.000 | 297711.000 | 0.000 | 0.143667E+09 | 0.111848E+09 | 0.000 |
April | 0.251742E+09 | 0.000 | 0.000 | 1244564.217 | 0.000 | 0.654866E+08 | 0.217035E+09 | 0.000 |
May | 0.158532E+09 | 0.000 | 0.000 | 2135817.221 | 0.000 | 0.178710E+08 | 0.287927E+09 | 0.000 |
June | 0.637201E+08 | 1334398.751 | 0.000 | 4709366.635 | 46910.603 | 0.000 | 0.244102E+09 | 0.000 |
July | 0.305096E+08 | 7314321.358 | 0.000 | 4681969.197 | 448809.728 | 0.000 | 0.141114E+09 | 0.000 |
August | 0.296101E+08 | 8621292.343 | 0.000 | 4857780.458 | 57634.476 | 0.000 | 0.133886E+09 | 0.000 |
September | 0.105818E+09 | 1932093.074 | 0.000 | 3992257.160 | 219216.167 | 0.000 | 0.230269E+09 | 0.000 |
October | 0.291493E+09 | 0.000 | 0.000 | 671174.281 | 0.000 | 0.515561E+08 | 0.173084E+09 | 0.000 |
November | 0.423565E+09 | 0.000 | 0.000 | 40915.808 | 0.000 | 0.199751E+09 | 0.333299E+08 | 0.000 |
December | 0.332227E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.316125E+09 | 0.000 | 0.000 |
Annual Sum or Average | 0.289082E+10 | 0.192021E+08 | 0.000 | 0.226508E+08 | 772570.973 | 0.126089E+10 | 0.158689E+10 | 0.000 |
Minimum of Months | 0.296101E+08 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.424468E+09 | 8621292.343 | 0.000 | 4857780.458 | 448809.728 | 0.320881E+09 | 0.287927E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.668089E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.484831E+09 | 0.000 | 0.000 |
February | 0.701159E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.256043E+09 | 0.000 | 0.000 |
March | 0.834698E+09 | 0.000 | 0.000 | 68002.298 | 0.000 | 0.237540E+09 | 0.481857E+08 | 0.000 |
April | 0.575182E+09 | 0.000 | 0.000 | 436833.715 | 0.000 | 0.132309E+09 | 0.173163E+09 | 0.000 |
May | 0.405761E+09 | 0.000 | 0.000 | 1468055.538 | 0.000 | 0.312049E+08 | 0.352416E+09 | 0.000 |
June | 0.145929E+09 | 1156126.783 | 0.000 | 4563413.627 | 60076.005 | 0.000 | 0.394264E+09 | 0.000 |
July | 0.668715E+08 | 8600100.235 | 0.000 | 4901328.744 | 716457.979 | 0.000 | 0.254442E+09 | 0.000 |
August | 0.868458E+08 | 7571035.134 | 0.000 | 5826225.709 | 69173.564 | 0.000 | 0.225653E+09 | 0.000 |
September | 0.220115E+09 | 2672095.157 | 0.000 | 3453142.022 | 334890.275 | 0.000 | 0.371153E+09 | 0.000 |
October | 0.640893E+09 | 0.000 | 0.000 | 368705.610 | 0.000 | 0.817808E+08 | 0.145083E+09 | 0.000 |
November | 0.748976E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.344329E+09 | 0.000 | 0.000 |
December | 0.611812E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.483105E+09 | 0.000 | 0.000 |
Annual Sum or Average | 0.570633E+10 | 0.199994E+08 | 0.000 | 0.210857E+08 | 1180597.822 | 0.205114E+10 | 0.196436E+10 | 0.000 |
Minimum of Months | 0.668715E+08 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.834698E+09 | 8600100.235 | 0.000 | 5826225.709 | 716457.979 | 0.484831E+09 | 0.394264E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.359470E+09 | 0.000 | 0.000 | 277.331 | 0.000 | 0.322990E+09 | 1380008.556 | 0.000 |
February | 0.383948E+09 | 0.000 | 0.000 | 140206.432 | 0.000 | 0.144636E+09 | 0.502240E+08 | 0.000 |
March | 0.418404E+09 | 0.000 | 0.000 | 420034.361 | 0.000 | 0.143188E+09 | 0.115532E+09 | 0.000 |
April | 0.293185E+09 | 0.000 | 0.000 | 861994.930 | 0.000 | 0.754455E+08 | 0.162807E+09 | 0.000 |
May | 0.204093E+09 | 0.000 | 0.000 | 1640329.185 | 0.000 | 0.176167E+08 | 0.244121E+09 | 0.000 |
June | 0.729639E+08 | 1512077.917 | 0.000 | 3309285.082 | 69601.307 | 0.000 | 0.244663E+09 | 0.000 |
July | 0.240062E+08 | 7060870.669 | 0.000 | 3545534.358 | 394643.240 | 0.000 | 0.161123E+09 | 0.000 |
August | 0.328782E+08 | 7318315.738 | 0.000 | 3917990.482 | 179014.287 | 0.000 | 0.142837E+09 | 0.000 |
September | 0.119859E+09 | 2230974.163 | 0.000 | 2835587.858 | 262415.401 | 0.000 | 0.226369E+09 | 0.000 |
October | 0.331970E+09 | 0.000 | 0.000 | 487862.256 | 0.000 | 0.507862E+08 | 0.131889E+09 | 0.000 |
November | 0.414301E+09 | 0.000 | 0.000 | 82618.371 | 0.000 | 0.211689E+09 | 0.295088E+08 | 0.000 |
December | 0.325004E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.323666E+09 | 0.000 | 0.000 |
Annual Sum or Average | 0.298008E+10 | 0.181222E+08 | 0.000 | 0.172417E+08 | 905674.236 | 0.129002E+10 | 0.151045E+10 | 0.000 |
Minimum of Months | 0.240062E+08 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.418404E+09 | 7318315.738 | 0.000 | 3917990.482 | 394643.240 | 0.323666E+09 | 0.244663E+09 | 0.000 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:1
Timestamp: 2015-09-09 18:45:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.548381E+09 | 0.000 |
February | 0.390896E+09 | 748960.242 |
March | 0.440119E+09 | 0.583724E+08 |
April | 0.312844E+09 | 0.204273E+09 |
May | 0.331731E+09 | 0.628547E+09 |
June | 0.331731E+09 | 0.182094E+10 |
July | 0.301574E+09 | 0.229384E+10 |
August | 0.346810E+09 | 0.271066E+10 |
September | 0.301574E+09 | 0.164955E+10 |
October | 0.316714E+09 | 0.318384E+09 |
November | 0.442700E+09 | 0.253559E+08 |
December | 0.513527E+09 | 0.000 |
Annual Sum or Average | 0.457860E+10 | 0.971068E+10 |
Minimum of Months | 0.301574E+09 | 0.000 |
Maximum of Months | 0.548381E+09 | 0.271066E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:2
Timestamp: 2015-09-09 18:45:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.207248E+10 | 0.165980E+08 |
February | 0.133727E+10 | 0.107524E+09 |
March | 0.141342E+10 | 0.239521E+09 |
April | 0.925798E+09 | 0.440136E+09 |
May | 0.740953E+09 | 0.579448E+09 |
June | 0.568317E+09 | 0.135181E+10 |
July | 0.510001E+09 | 0.191851E+10 |
August | 0.586502E+09 | 0.259402E+10 |
September | 0.548265E+09 | 0.180775E+10 |
October | 0.868743E+09 | 0.454580E+09 |
November | 0.156968E+10 | 0.117404E+09 |
December | 0.203511E+10 | 0.109407E+08 |
Annual Sum or Average | 0.131765E+11 | 0.963823E+10 |
Minimum of Months | 0.510001E+09 | 0.109407E+08 |
Maximum of Months | 0.207248E+10 | 0.259402E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:3
Timestamp: 2015-09-09 18:45:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.806724E+09 | 0.000 |
February | 0.535536E+09 | 876686.447 |
March | 0.587138E+09 | 0.526889E+08 |
April | 0.390175E+09 | 0.229287E+09 |
May | 0.348938E+09 | 0.514437E+09 |
June | 0.331131E+09 | 0.122471E+10 |
July | 0.301028E+09 | 0.145787E+10 |
August | 0.346182E+09 | 0.160513E+10 |
September | 0.301576E+09 | 0.962942E+09 |
October | 0.374767E+09 | 0.152572E+09 |
November | 0.635100E+09 | 4905394.298 |
December | 0.799162E+09 | 0.000 |
Annual Sum or Average | 0.575746E+10 | 0.620542E+10 |
Minimum of Months | 0.301028E+09 | 0.000 |
Maximum of Months | 0.806724E+09 | 0.160513E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:4
Timestamp: 2015-09-09 18:45:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.119828E+10 | 0.000 |
February | 0.746185E+09 | 0.000 |
March | 0.781532E+09 | 0.133815E+08 |
April | 0.458429E+09 | 0.682268E+08 |
May | 0.335341E+09 | 0.336146E+09 |
June | 0.286793E+09 | 0.122671E+10 |
July | 0.260721E+09 | 0.158030E+10 |
August | 0.299829E+09 | 0.180339E+10 |
September | 0.262604E+09 | 0.860093E+09 |
October | 0.396625E+09 | 0.697441E+08 |
November | 0.897454E+09 | 0.000 |
December | 0.118029E+10 | 0.000 |
Annual Sum or Average | 0.710408E+10 | 0.595799E+10 |
Minimum of Months | 0.260721E+09 | 0.000 |
Maximum of Months | 0.119828E+10 | 0.180339E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:5
Timestamp: 2015-09-09 18:45:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.821206E+09 | 0.000 |
February | 0.553728E+09 | 0.163712E+08 |
March | 0.617408E+09 | 0.926338E+08 |
April | 0.413530E+09 | 0.223082E+09 |
May | 0.381926E+09 | 0.499148E+09 |
June | 0.367706E+09 | 0.109585E+10 |
July | 0.335447E+09 | 0.138573E+10 |
August | 0.384504E+09 | 0.151228E+10 |
September | 0.334689E+09 | 0.863800E+09 |
October | 0.404009E+09 | 0.142164E+09 |
November | 0.665732E+09 | 0.188096E+08 |
December | 0.811976E+09 | 0.000 |
Annual Sum or Average | 0.609186E+10 | 0.584988E+10 |
Minimum of Months | 0.334689E+09 | 0.000 |
Maximum of Months | 0.821206E+09 | 0.151228E+10 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2015-09-09 18:45:45
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.357631E+10 | 0.231149E+09 |
February | 0.257128E+10 | 0.944110E+08 |
March | 0.296588E+10 | 0.876051E+08 |
April | 0.231258E+10 | 6597625.146 |
May | 0.256494E+10 | 0.000 |
June | 0.340538E+10 | 0.000 |
July | 0.364225E+10 | 0.000 |
August | 0.424101E+10 | 0.000 |
September | 0.310766E+10 | 0.000 |
October | 0.226815E+10 | 0.000 |
November | 0.296220E+10 | 0.197940E+09 |
December | 0.343381E+10 | 0.221653E+09 |
Annual Sum or Average | 0.370515E+11 | 0.839355E+09 |
Minimum of Months | 0.226815E+10 | 0.000 |
Maximum of Months | 0.424101E+10 | 0.231149E+09 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:45
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.172435E+11 | 15195.937 | 05-JAN-08:09 | 5078.615 | 3465.647 | 1824.361 | 3318.704 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.147891E+11 | 13251.501 | 21-FEB-07:10 | 2370.020 | 1732.824 | 1824.361 | 5815.686 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.168713E+11 | 13471.154 | 20-MAR-07:10 | 5078.615 | 3465.647 | 1824.361 | 2530.531 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.149414E+11 | 13006.222 | 28-APR-15:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2065.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.158303E+11 | 13505.704 | 11-MAY-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2565.081 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.163590E+11 | 14592.320 | 23-JUN-15:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 3651.697 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.162833E+11 | 15186.364 | 12-JUL-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4245.741 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.178834E+11 | 14962.059 | 09-AUG-15:20 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4021.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.158394E+11 | 15145.853 | 13-SEP-15:09 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4205.230 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.157089E+11 | 13088.043 | 06-OCT-14:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2147.420 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.163306E+11 | 14920.469 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1824.361 | 3979.846 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.168622E+11 | 15439.275 | 26-DEC-08:09 | 5078.615 | 3465.647 | 1824.361 | 3562.042 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.194942E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.147891E+11 | 13006.222 | 2370.020 | 1732.824 | 1824.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.178834E+11 | 15439.275 | 5078.615 | 3465.647 | 1824.361 | 5815.686 | 4245.741 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK NET ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:45
ELECTRICITYNET:FACILITY [J] | ELECTRICITYNET:FACILITY {Maximum}[W] | ELECTRICITYNET:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.172435E+11 | 15195.937 | 05-JAN-08:09 | 5078.615 | 3465.647 | 1824.361 | 3318.704 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.147891E+11 | 13251.501 | 21-FEB-07:10 | 2370.020 | 1732.824 | 1824.361 | 5815.686 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.168713E+11 | 13471.154 | 20-MAR-07:10 | 5078.615 | 3465.647 | 1824.361 | 2530.531 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.149414E+11 | 13006.222 | 28-APR-15:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2065.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.158303E+11 | 13505.704 | 11-MAY-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2565.081 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.163590E+11 | 14592.320 | 23-JUN-15:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 3651.697 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.162833E+11 | 15186.364 | 12-JUL-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4245.741 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.178834E+11 | 14962.059 | 09-AUG-15:20 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4021.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.158394E+11 | 15145.853 | 13-SEP-15:09 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4205.230 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.157089E+11 | 13088.043 | 06-OCT-14:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2147.420 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.163306E+11 | 14920.469 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1824.361 | 3979.846 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.168622E+11 | 15439.275 | 26-DEC-08:09 | 5078.615 | 3465.647 | 1824.361 | 3562.042 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.194942E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.147891E+11 | 13006.222 | 2370.020 | 1732.824 | 1824.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.178834E+11 | 15439.275 | 5078.615 | 3465.647 | 1824.361 | 5815.686 | 4245.741 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.17 | 1.00 | 24.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.37 | 3.50 | 24.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.37 | 3.83 | 24.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.24 | 1.83 | 24.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 24.33 | 10.17 | 24.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.37 | 3.83 | 24.37 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.59 | 3.67 | 20.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.67 | 20.68 | 1.67 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.17 | 20.69 | 2.17 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.89 | 0.50 | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 29.76 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 20.51 | 1.67 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 20.56 | 3.50 | 20.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.17 | 20.61 | 13.17 | 20.61 | 1.67 | 29.76 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.89 | 3.67 | 20.89 | 1.67 | 29.76 | 0.00 | 0.00 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 20.57 | 3.83 | 20.57 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.83 | 20.66 | 1.83 | 20.66 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 20.65 | 2.33 | 20.65 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.86 | 0.50 | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.90 | 0.33 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 20.49 | 1.83 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 18.18 | 3.67 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.33 | 19.68 | 14.33 | 20.59 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 20.90 | 3.83 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.34 | 6.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.33 | 20.57 | 3.33 | 20.57 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.00 | 20.48 | 4.00 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.63 | 0.67 | 20.63 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.86 | 0.17 | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 20.76 | 0.83 | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 20.38 | 3.17 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.33 | 20.31 | 6.33 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.00 | 20.41 | 25.00 | 20.41 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.86 | 6.50 | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.60 | 3.50 | 20.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.68 | 1.50 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 20.69 | 1.83 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.90 | 0.17 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 29.66 | 0.50 | 29.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 29.80 | 0.33 | 29.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 29.78 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 20.58 | 2.00 | 20.58 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.83 | 17.99 | 3.00 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.83 | 19.59 | 12.00 | 20.60 | 15.50 | 29.79 | 0.83 | 29.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 20.90 | 3.50 | 20.90 | 10.83 | 29.80 | 0.50 | 29.66 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: COMFORT REPORT - SIMPLE 55
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 21.66 | 25.00 | 21.07 | 25.00 | 21.07 |
February | 323.00 | 22.09 | 2.00 | 21.10 | 2.00 | 21.10 |
March | 391.00 | 22.45 | 6.00 | 21.11 | 6.00 | 21.11 |
April | 340.00 | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 314.33 | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 56.67 | 23.85 | 126.50 | 24.84 | 0.00 | 0.00 |
July | 1.17 | 23.89 | 214.67 | 24.64 | 0.00 | 0.00 |
August | 0.67 | 24.83 | 274.00 | 24.50 | 0.67 | 24.83 |
September | 54.67 | 23.86 | 118.67 | 24.68 | 2.67 | 25.50 |
October | 350.33 | 23.26 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 357.00 | 22.27 | 17.50 | 21.10 | 17.50 | 21.10 |
December | 340.00 | 21.70 | 17.33 | 21.02 | 17.33 | 21.02 |
Annual Sum or Average | 2885.83 | 22.54 | 801.67 | 24.33 | 71.17 | 21.27 |
Minimum of Months | 0.67 | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 391.00 | 24.83 | 274.00 | 24.84 | 25.00 | 25.50 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.92 | 252.17 | 20.56 | 252.17 | 20.56 |
February | 309.50 | 21.32 | 130.00 | 20.61 | 130.00 | 20.61 |
March | 367.67 | 21.72 | 120.83 | 20.76 | 119.00 | 20.71 |
April | 288.33 | 22.10 | 54.67 | 21.07 | 50.67 | 20.85 |
May | 293.17 | 22.70 | 14.00 | 22.54 | 6.83 | 20.98 |
June | 140.67 | 23.20 | 112.00 | 24.61 | 0.00 | 0.00 |
July | 64.83 | 23.28 | 194.00 | 24.61 | 0.00 | 0.00 |
August | 65.67 | 23.29 | 250.17 | 24.44 | 0.00 | 0.00 |
September | 128.83 | 22.90 | 142.33 | 24.33 | 0.00 | 0.00 |
October | 301.67 | 21.97 | 39.00 | 21.90 | 23.50 | 20.59 |
November | 342.50 | 21.33 | 157.33 | 20.63 | 155.50 | 20.60 |
December | 339.17 | 20.90 | 237.00 | 20.50 | 237.00 | 20.50 |
Annual Sum or Average | 2999.00 | 21.79 | 1703.50 | 22.25 | 974.67 | 20.60 |
Minimum of Months | 64.83 | 20.90 | 14.00 | 20.50 | 0.00 | 0.00 |
Maximum of Months | 367.67 | 23.29 | 252.17 | 24.61 | 252.17 | 20.98 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.81 | 251.67 | 20.50 | 251.67 | 20.50 |
February | 323.00 | 21.34 | 137.33 | 20.49 | 137.33 | 20.49 |
March | 391.00 | 21.88 | 123.17 | 20.61 | 123.17 | 20.61 |
April | 325.67 | 22.52 | 41.50 | 20.78 | 41.50 | 20.78 |
May | 285.83 | 23.04 | 7.67 | 22.05 | 5.17 | 21.08 |
June | 98.33 | 23.57 | 136.17 | 24.47 | 0.00 | 0.00 |
July | 37.17 | 23.74 | 217.33 | 24.46 | 0.00 | 0.00 |
August | 38.50 | 23.76 | 244.50 | 24.34 | 0.00 | 0.00 |
September | 129.67 | 23.31 | 86.50 | 24.24 | 0.00 | 0.00 |
October | 350.17 | 22.42 | 22.17 | 20.63 | 22.17 | 20.63 |
November | 357.00 | 21.43 | 159.17 | 20.57 | 159.17 | 20.57 |
December | 340.00 | 20.79 | 237.67 | 20.45 | 237.67 | 20.45 |
Annual Sum or Average | 3033.33 | 21.92 | 1664.83 | 22.12 | 977.83 | 20.53 |
Minimum of Months | 37.17 | 20.79 | 7.67 | 20.45 | 0.00 | 0.00 |
Maximum of Months | 391.00 | 23.76 | 251.67 | 24.47 | 251.67 | 21.08 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.76 | 261.00 | 20.55 | 261.00 | 20.55 |
February | 323.00 | 21.07 | 151.67 | 20.54 | 151.67 | 20.54 |
March | 391.00 | 21.54 | 136.83 | 20.66 | 136.83 | 20.66 |
April | 340.00 | 22.24 | 48.33 | 20.86 | 48.33 | 20.86 |
May | 352.33 | 23.00 | 4.17 | 21.10 | 4.17 | 21.10 |
June | 134.50 | 23.55 | 76.67 | 25.17 | 0.00 | 0.00 |
July | 47.00 | 23.68 | 136.17 | 24.93 | 0.00 | 0.00 |
August | 59.17 | 23.67 | 165.17 | 24.51 | 0.00 | 0.00 |
September | 178.33 | 23.33 | 21.00 | 24.74 | 0.00 | 0.00 |
October | 357.00 | 22.22 | 21.00 | 20.69 | 21.00 | 20.69 |
November | 357.00 | 21.23 | 169.67 | 20.63 | 169.67 | 20.63 |
December | 340.00 | 20.73 | 241.83 | 20.49 | 241.83 | 20.49 |
Annual Sum or Average | 3236.33 | 21.85 | 1433.50 | 21.75 | 1034.50 | 20.58 |
Minimum of Months | 47.00 | 20.73 | 4.17 | 20.49 | 0.00 | 0.00 |
Maximum of Months | 391.00 | 23.68 | 261.00 | 25.17 | 261.00 | 21.10 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.87 | 255.50 | 20.54 | 255.50 | 20.54 |
February | 323.00 | 21.45 | 135.00 | 20.60 | 135.00 | 20.60 |
March | 374.17 | 21.91 | 118.83 | 20.83 | 116.50 | 20.74 |
April | 289.17 | 22.52 | 57.67 | 22.50 | 37.00 | 20.88 |
May | 261.17 | 23.08 | 74.67 | 25.19 | 6.83 | 23.81 |
June | 167.00 | 24.68 | 136.17 | 25.92 | 37.33 | 28.24 |
July | 96.17 | 26.37 | 171.67 | 25.79 | 52.83 | 28.45 |
August | 77.83 | 25.07 | 200.17 | 25.02 | 23.17 | 28.06 |
September | 156.33 | 23.58 | 90.83 | 25.10 | 5.67 | 27.65 |
October | 342.33 | 22.39 | 21.33 | 20.65 | 21.33 | 20.65 |
November | 357.00 | 21.46 | 162.17 | 20.60 | 162.17 | 20.60 |
December | 340.00 | 20.82 | 241.00 | 20.47 | 241.00 | 20.47 |
Annual Sum or Average | 3141.17 | 22.23 | 1665.00 | 22.61 | 1094.33 | 21.43 |
Minimum of Months | 77.83 | 20.82 | 21.33 | 20.47 | 5.67 | 20.47 |
Maximum of Months | 374.17 | 26.37 | 255.50 | 25.92 | 255.50 | 28.45 |
Report: COMFORT REPORT - SIMPLE 55
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BUILDING LOADS - COOLING
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854265E+09 | 1496.11 | 05-JAN-06:02 | -1.8 | -2.4 | 0.270648E+09 | 431.34 | 20-JAN-16:10 | 8.95 | 7.69 |
February | 0.757161E+09 | 1378.04 | 14-FEB-06:01 | -0.6 | -0.8 | 0.257418E+09 | 450.64 | 10-FEB-16:30 | 7.75 | 5.94 |
March | 0.920729E+09 | 1464.17 | 03-MAR-06:01 | -1.7 | -2.1 | 0.321526E+09 | 450.65 | 27-MAR-15:00 | 10.60 | 8.76 |
April | 0.861183E+09 | 1795.67 | 28-APR-15:47 | 17.62 | 10.51 | 0.294254E+09 | 450.65 | 28-APR-08:20 | 16.30 | 10.08 |
May | 0.104427E+10 | 1924.94 | 11-MAY-15:53 | 19.40 | 14.48 | 0.338706E+09 | 450.65 | 11-MAY-07:40 | 15.03 | 10.69 |
June | 0.177679E+10 | 4523.70 | 08-JUN-05:03 | 9.78 | 8.00 | 0.346623E+09 | 450.65 | 08-JUN-07:10 | 13.40 | 10.97 |
July | 0.194958E+10 | 4432.03 | 11-JUL-05:02 | 12.07 | 11.35 | 0.315927E+09 | 450.65 | 11-JUL-07:10 | 16.47 | 14.27 |
August | 0.222454E+10 | 4278.93 | 14-AUG-05:02 | 15.00 | 12.89 | 0.363037E+09 | 450.65 | 25-AUG-07:10 | 15.72 | 14.89 |
September | 0.171759E+10 | 4669.08 | 21-SEP-05:03 | 5.78 | 5.46 | 0.314722E+09 | 450.65 | 13-SEP-07:10 | 12.35 | 11.67 |
October | 0.927591E+09 | 1832.09 | 06-OCT-15:57 | 15.90 | 11.34 | 0.317541E+09 | 450.65 | 11-OCT-10:09 | 12.60 | 10.50 |
November | 0.868336E+09 | 1653.32 | 22-NOV-06:02 | -3.9 | -6.3 | 0.289462E+09 | 450.66 | 07-NOV-16:40 | 10.77 | 9.46 |
December | 0.830373E+09 | 1561.68 | 11-DEC-06:04 | -2.8 | -4.2 | 0.258981E+09 | 435.47 | 29-DEC-16:00 | 9.40 | 7.72 |
Annual Sum or Average | 0.147324E+11 | 0.368885E+10 | ||||||||
Minimum of Months | 0.757161E+09 | 1378.04 | -3.9 | -6.3 | 0.257418E+09 | 431.34 | 7.75 | 5.94 | ||
Maximum of Months | 0.222454E+10 | 4669.08 | 19.40 | 14.48 | 0.363037E+09 | 450.66 | 16.47 | 14.89 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132999E+09 | 1493.00 | 03-JAN-13:30 | 4.40 | 2.74 | 0.194718E+09 | 341.62 | 03-JAN-16:10 | 3.12 | 1.98 |
February | 0.292406E+09 | 2812.78 | 07-FEB-13:20 | 5.20 | 4.43 | 0.186582E+09 | 341.62 | 22-FEB-16:00 | 6.70 | 5.11 |
March | 0.451218E+09 | 3371.26 | 24-MAR-14:00 | 10.00 | 7.22 | 0.234254E+09 | 341.62 | 27-MAR-15:00 | 10.60 | 8.76 |
April | 0.586677E+09 | 3642.63 | 28-APR-13:00 | 18.90 | 11.22 | 0.212333E+09 | 341.63 | 28-APR-13:09 | 18.62 | 11.14 |
May | 0.599465E+09 | 2870.96 | 11-MAY-13:40 | 20.73 | 14.13 | 0.246436E+09 | 341.63 | 11-MAY-08:39 | 16.33 | 11.85 |
June | 0.113625E+10 | 3328.18 | 23-JUN-13:50 | 22.62 | 16.62 | 0.259139E+09 | 341.62 | 19-JUN-09:20 | 12.07 | 9.59 |
July | 0.150478E+10 | 4559.40 | 31-JUL-13:30 | 20.85 | 17.27 | 0.238004E+09 | 341.62 | 14-JUL-07:30 | 14.70 | 13.07 |
August | 0.201125E+10 | 5003.61 | 31-AUG-13:30 | 20.10 | 14.40 | 0.273563E+09 | 341.62 | 11-AUG-07:49 | 14.23 | 12.67 |
September | 0.165278E+10 | 5781.74 | 13-SEP-13:20 | 22.40 | 16.28 | 0.233812E+09 | 341.63 | 21-SEP-08:50 | 10.63 | 8.85 |
October | 0.566312E+09 | 4168.97 | 06-OCT-13:30 | 14.90 | 12.03 | 0.222225E+09 | 341.63 | 04-OCT-08:00 | 11.50 | 9.89 |
November | 0.286701E+09 | 2996.79 | 02-NOV-13:40 | 9.63 | 8.66 | 0.206565E+09 | 341.63 | 02-NOV-10:50 | 10.13 | 9.04 |
December | 0.116407E+09 | 2092.75 | 08-DEC-13:20 | 4.40 | 3.54 | 0.186084E+09 | 341.62 | 08-DEC-15:30 | 3.60 | 2.54 |
Annual Sum or Average | 0.933724E+10 | 0.269371E+10 | ||||||||
Minimum of Months | 0.116407E+09 | 1493.00 | 4.40 | 2.74 | 0.186084E+09 | 341.62 | 3.12 | 1.98 | ||
Maximum of Months | 0.201125E+10 | 5781.74 | 22.62 | 17.27 | 0.273563E+09 | 341.63 | 18.62 | 13.07 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107111E+09 | 497.17 | 06-JAN-06:04 | 2.12 | 0.13 | 0.113839E+09 | 181.66 | 20-JAN-15:00 | 9.40 | 7.98 |
February | 0.137565E+09 | 584.91 | 14-FEB-06:04 | -0.6 | -0.8 | 0.109548E+09 | 202.66 | 10-FEB-11:00 | 8.90 | 7.01 |
March | 0.212240E+09 | 878.73 | 24-MAR-09:43 | 7.70 | 5.60 | 0.140171E+09 | 202.66 | 24-MAR-08:50 | 6.93 | 5.14 |
April | 0.342953E+09 | 2015.47 | 28-APR-09:25 | 18.90 | 9.61 | 0.130037E+09 | 202.66 | 28-APR-07:10 | 11.75 | 8.38 |
May | 0.533131E+09 | 1901.13 | 11-MAY-09:02 | 16.78 | 12.36 | 0.150550E+09 | 202.66 | 22-MAY-07:30 | 12.50 | 10.11 |
June | 0.108015E+10 | 2916.12 | 09-JUN-08:32 | 15.77 | 12.65 | 0.155301E+09 | 202.66 | 08-JUN-07:10 | 13.40 | 10.97 |
July | 0.119605E+10 | 3577.68 | 24-JUL-05:02 | 12.07 | 10.98 | 0.141824E+09 | 202.66 | 05-JUL-07:10 | 15.68 | 13.85 |
August | 0.126417E+10 | 2845.45 | 09-AUG-08:54 | 19.00 | 14.67 | 0.162884E+09 | 202.66 | 29-AUG-07:10 | 15.07 | 14.39 |
September | 0.881930E+09 | 2700.57 | 13-SEP-09:24 | 18.05 | 13.82 | 0.140196E+09 | 202.66 | 18-SEP-07:10 | 15.00 | 13.09 |
October | 0.238333E+09 | 1005.17 | 04-OCT-09:52 | 12.50 | 10.16 | 0.135023E+09 | 202.70 | 18-OCT-15:00 | 11.40 | 10.87 |
November | 0.133278E+09 | 549.68 | 02-NOV-05:04 | 0.50 | 0.26 | 0.122304E+09 | 202.66 | 02-NOV-10:00 | 10.60 | 9.39 |
December | 93612257.65 | 495.01 | 27-DEC-06:05 | -0.9 | -1.4 | 0.108480E+09 | 180.09 | 29-DEC-16:19 | 9.80 | 8.10 |
Annual Sum or Average | 0.622053E+10 | 0.161016E+10 | ||||||||
Minimum of Months | 93612257.65 | 495.01 | -0.9 | -1.4 | 0.108480E+09 | 180.09 | 6.93 | 5.14 | ||
Maximum of Months | 0.126417E+10 | 3577.68 | 19.00 | 14.67 | 0.162884E+09 | 202.70 | 15.68 | 14.39 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244003E+09 | 962.84 | 18-JAN-06:06 | 0.60 | 0.37 | 0.189459E+09 | 296.89 | 20-JAN-15:00 | 9.40 | 7.98 |
February | 0.332597E+09 | 1026.55 | 16-FEB-06:05 | 0.68 | 0.45 | 0.177094E+09 | 310.42 | 10-FEB-16:19 | 7.93 | 6.03 |
March | 0.429038E+09 | 1035.66 | 01-MAR-06:05 | 0.27 | 0.04 | 0.224937E+09 | 341.62 | 27-MAR-15:30 | 11.15 | 8.91 |
April | 0.430107E+09 | 1391.38 | 28-APR-15:53 | 17.80 | 10.38 | 0.209445E+09 | 341.62 | 28-APR-09:09 | 18.90 | 9.71 |
May | 0.615728E+09 | 1589.83 | 11-MAY-15:37 | 19.97 | 14.61 | 0.248026E+09 | 341.62 | 22-MAY-09:50 | 14.90 | 12.45 |
June | 0.126098E+10 | 2514.26 | 23-JUN-15:32 | 23.30 | 16.94 | 0.261490E+09 | 341.63 | 23-JUN-07:10 | 15.10 | 13.13 |
July | 0.140950E+10 | 3618.38 | 24-JUL-05:02 | 12.07 | 10.98 | 0.239139E+09 | 341.63 | 11-JUL-07:10 | 16.47 | 14.27 |
August | 0.154571E+10 | 3299.28 | 01-AUG-05:02 | 16.02 | 15.01 | 0.274297E+09 | 341.63 | 23-AUG-07:10 | 15.83 | 15.35 |
September | 0.986018E+09 | 2252.43 | 13-SEP-15:43 | 22.88 | 18.38 | 0.234792E+09 | 341.62 | 26-SEP-08:00 | 12.20 | 9.50 |
October | 0.423922E+09 | 1098.04 | 06-OCT-15:40 | 15.67 | 11.49 | 0.221006E+09 | 341.62 | 06-OCT-10:39 | 13.63 | 11.90 |
November | 0.318045E+09 | 1012.79 | 03-NOV-05:05 | 0.92 | 0.48 | 0.199891E+09 | 330.03 | 09-NOV-16:10 | 10.92 | 8.02 |
December | 0.218515E+09 | 942.52 | 12-DEC-06:06 | -1.1 | -2.1 | 0.180373E+09 | 296.63 | 29-DEC-16:19 | 9.80 | 8.10 |
Annual Sum or Average | 0.821417E+10 | 0.265995E+10 | ||||||||
Minimum of Months | 0.218515E+09 | 942.52 | -1.1 | -2.1 | 0.177094E+09 | 296.63 | 7.93 | 6.03 | ||
Maximum of Months | 0.154571E+10 | 3618.38 | 23.30 | 18.38 | 0.274297E+09 | 341.63 | 18.90 | 15.35 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93006017.73 | 497.47 | 06-JAN-06:04 | 2.12 | 0.13 | 0.114638E+09 | 200.64 | 27-JAN-16:19 | 5.93 | 4.16 |
February | 0.135599E+09 | 827.62 | 10-FEB-16:03 | 8.12 | 6.12 | 0.110186E+09 | 202.66 | 22-FEB-16:00 | 6.70 | 5.11 |
March | 0.222451E+09 | 1497.49 | 30-MAR-16:00 | 14.40 | 11.06 | 0.139149E+09 | 202.66 | 27-MAR-15:00 | 10.60 | 8.76 |
April | 0.308735E+09 | 2189.96 | 27-APR-15:57 | 15.60 | 10.28 | 0.128626E+09 | 202.66 | 28-APR-08:50 | 18.25 | 9.90 |
May | 0.486204E+09 | 2354.55 | 23-MAY-15:57 | 18.30 | 13.16 | 0.150378E+09 | 202.66 | 25-MAY-10:30 | 12.80 | 11.78 |
June | 0.920369E+09 | 3025.62 | 28-JUN-16:00 | 22.80 | 16.53 | 0.156768E+09 | 202.66 | 08-JUN-07:10 | 13.40 | 10.97 |
July | 0.109505E+10 | 3997.90 | 24-JUL-05:02 | 12.07 | 10.98 | 0.143420E+09 | 202.66 | 11-JUL-07:10 | 16.47 | 14.27 |
August | 0.114062E+10 | 3923.92 | 01-AUG-05:02 | 16.02 | 15.01 | 0.163767E+09 | 202.66 | 24-AUG-07:10 | 15.40 | 14.38 |
September | 0.756680E+09 | 3127.39 | 12-SEP-15:57 | 21.70 | 14.42 | 0.140628E+09 | 202.66 | 26-SEP-08:30 | 11.10 | 8.92 |
October | 0.199095E+09 | 1613.20 | 03-OCT-16:00 | 14.40 | 10.43 | 0.134095E+09 | 202.66 | 05-OCT-10:39 | 14.17 | 11.34 |
November | 0.117739E+09 | 872.31 | 02-NOV-15:25 | 10.25 | 8.66 | 0.122222E+09 | 202.66 | 09-NOV-16:00 | 10.00 | 8.02 |
December | 79360453.29 | 488.38 | 13-DEC-06:04 | 0.00 | -0.3 | 0.109015E+09 | 189.24 | 04-DEC-15:00 | 7.80 | 6.14 |
Annual Sum or Average | 0.555491E+10 | 0.161289E+10 | ||||||||
Minimum of Months | 79360453.29 | 488.38 | 0.00 | -0.3 | 0.109015E+09 | 189.24 | 5.93 | 4.16 | ||
Maximum of Months | 0.114062E+10 | 3997.90 | 22.80 | 16.53 | 0.163767E+09 | 202.66 | 18.25 | 14.38 |
Report: BUILDING LOADS - COOLING
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.10 | 0.91 | 0.00 | 0.00 | 01-JAN-00:10 | 1.10 | 0.91 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4.27 | 3.07 | 0.00 | 0.00 | 01-FEB-00:10 | 4.27 | 3.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.75 | 2.32 | 0.00 | 0.00 | 01-MAR-00:10 | 2.75 | 2.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.08 | 2.82 | 0.00 | 0.00 | 01-APR-00:10 | 4.08 | 2.82 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12.65 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 12.65 | 9.49 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.58 | 10.94 | 0.00 | 0.00 | 01-JUN-00:10 | 12.58 | 10.94 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.07 | 12.46 | 0.00 | 0.00 | 01-JUL-00:10 | 14.07 | 12.46 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15.52 | 14.51 | 0.00 | 0.00 | 01-AUG-00:10 | 15.52 | 14.51 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15.38 | 13.72 | 0.00 | 0.00 | 01-SEP-00:10 | 15.38 | 13.72 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9.12 | 8.37 | 0.00 | 0.00 | 01-OCT-00:10 | 9.12 | 8.37 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 5.18 | 4.67 | 0.00 | 0.00 | 01-NOV-00:10 | 5.18 | 4.67 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.57 | 4.43 | 0.00 | 0.00 | 01-DEC-00:10 | 5.57 | 4.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.10 | 0.91 | 0.00 | 0.00 | 1.10 | 0.91 | ||
Maximum of Months | 0.00 | 0.00 | 15.52 | 14.51 | 0.00 | 0.00 | 15.52 | 14.51 |
Report: BUILDING LOADS - HEATING
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23461195.51 | 5194.19 | 02-JAN-06:01 | 1.20 |
February | 8308280.05 | 6371.43 | 13-FEB-06:01 | 2.88 |
March | 7638639.01 | 6385.14 | 20-MAR-05:01 | 2.88 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.08 |
May | 5778.17 | 23.14 | 11-MAY-17:03 | 20.40 |
June | 268351.62 | 146.00 | 28-JUN-17:02 | 22.20 |
July | 2779214.13 | 411.94 | 11-JUL-17:02 | 25.73 |
August | 201650.65 | 132.58 | 09-AUG-17:02 | 22.10 |
September | 92352.44 | 106.23 | 12-SEP-17:02 | 21.83 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9.12 |
November | 7128583.41 | 5253.10 | 27-NOV-06:01 | 1.10 |
December | 24218726.04 | 6378.48 | 26-DEC-06:01 | 2.80 |
Annual Sum or Average | 74102771.03 | |||
Minimum of Months | 0.00 | 0.00 | 1.10 | |
Maximum of Months | 24218726.04 | 6385.14 | 25.73 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116319E+10 | 10811.06 | 19-JAN-06:01 | 3.30 |
February | 0.677723E+09 | 10927.15 | 01-FEB-06:01 | 3.97 |
March | 0.658840E+09 | 10758.28 | 20-MAR-05:01 | 2.88 |
April | 0.343122E+09 | 10475.13 | 18-APR-05:02 | 3.30 |
May | 0.166070E+09 | 6920.35 | 08-MAY-05:03 | 8.30 |
June | 21838447.83 | 1061.20 | 19-JUN-06:10 | 10.10 |
July | 22161805.57 | 544.04 | 11-JUL-17:11 | 25.37 |
August | 23198021.53 | 322.67 | 11-AUG-17:12 | 21.47 |
September | 37776509.08 | 2710.68 | 29-SEP-06:10 | 2.98 |
October | 0.289865E+09 | 7129.25 | 10-OCT-05:02 | 8.40 |
November | 0.796952E+09 | 10125.20 | 01-NOV-05:02 | 2.43 |
December | 0.115978E+10 | 10763.86 | 26-DEC-06:01 | 2.80 |
Annual Sum or Average | 0.536052E+10 | |||
Minimum of Months | 21838447.83 | 322.67 | 2.43 | |
Maximum of Months | 0.116319E+10 | 10927.15 | 25.37 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308518E+09 | 6457.20 | 19-JAN-06:01 | 3.30 |
February | 0.172140E+09 | 6528.11 | 01-FEB-06:01 | 3.97 |
March | 0.168375E+09 | 6431.31 | 20-MAR-05:01 | 2.88 |
April | 60590569.10 | 6253.31 | 18-APR-05:02 | 3.30 |
May | 12438214.52 | 3853.27 | 08-MAY-05:03 | 8.30 |
June | 3903181.42 | 208.10 | 28-JUN-17:23 | 22.20 |
July | 7684702.73 | 324.74 | 11-JUL-17:11 | 25.37 |
August | 6661293.08 | 195.78 | 11-AUG-17:12 | 21.47 |
September | 2076196.02 | 198.90 | 12-SEP-17:12 | 21.47 |
October | 40817297.69 | 4347.69 | 16-OCT-05:03 | 9.77 |
November | 0.202171E+09 | 6036.74 | 01-NOV-05:02 | 2.43 |
December | 0.314474E+09 | 6435.92 | 26-DEC-06:01 | 2.80 |
Annual Sum or Average | 0.129985E+10 | |||
Minimum of Months | 2076196.02 | 195.78 | 2.43 | |
Maximum of Months | 0.314474E+09 | 6528.11 | 25.37 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430110E+09 | 7369.38 | 19-JAN-06:01 | 3.30 |
February | 0.255405E+09 | 7451.10 | 01-FEB-06:01 | 3.97 |
March | 0.250836E+09 | 7364.18 | 20-MAR-05:01 | 2.88 |
April | 97113599.48 | 7193.75 | 18-APR-05:02 | 3.30 |
May | 16508556.09 | 3401.97 | 08-MAY-05:03 | 8.30 |
June | 292120.04 | 130.33 | 28-JUN-17:02 | 22.20 |
July | 2573225.63 | 325.45 | 11-JUL-17:02 | 25.73 |
August | 327646.61 | 122.80 | 09-AUG-17:02 | 22.10 |
September | 177066.71 | 109.01 | 12-SEP-17:02 | 21.83 |
October | 53075317.31 | 3658.13 | 11-OCT-05:03 | 11.05 |
November | 0.286290E+09 | 7231.64 | 14-NOV-06:03 | 4.40 |
December | 0.432051E+09 | 7376.95 | 26-DEC-06:01 | 2.80 |
Annual Sum or Average | 0.182476E+10 | |||
Minimum of Months | 177066.71 | 109.01 | 2.80 | |
Maximum of Months | 0.432051E+09 | 7451.10 | 25.73 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306484E+09 | 6863.61 | 19-JAN-06:01 | 3.30 |
February | 0.169481E+09 | 6937.50 | 01-FEB-06:01 | 3.97 |
March | 0.166603E+09 | 6832.74 | 20-MAR-05:01 | 2.88 |
April | 53210572.05 | 6619.85 | 18-APR-05:02 | 3.30 |
May | 10331961.56 | 3358.79 | 08-MAY-05:03 | 8.30 |
June | 1787375.88 | 169.68 | 28-JUN-17:23 | 22.20 |
July | 3830137.33 | 302.84 | 11-JUL-17:11 | 25.37 |
August | 5106016.14 | 229.54 | 01-AUG-05:04 | 16.02 |
September | 1528233.43 | 181.06 | 12-SEP-17:12 | 21.47 |
October | 40576976.03 | 4668.79 | 30-OCT-05:02 | 7.97 |
November | 0.202838E+09 | 6393.70 | 01-NOV-05:02 | 2.43 |
December | 0.311405E+09 | 6836.35 | 26-DEC-06:01 | 2.80 |
Annual Sum or Average | 0.127318E+10 | |||
Minimum of Months | 1528233.43 | 169.68 | 2.43 | |
Maximum of Months | 0.311405E+09 | 6937.50 | 25.37 |
Report: BUILDING LOADS - HEATING
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4.27 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.75 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15.52 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9.12 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 5.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.57 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.10 | |
Maximum of Months | 0.00 | 0.00 | 15.52 |
Report: BUILDING LOADS - ELECTRIC
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.178023E+10 | 1486.92 | 02-JAN-08:09 | 0.129836E+10 | 1014.68 | 02-JAN-08:09 |
February | 0.160950E+10 | 1486.92 | 01-FEB-08:09 | 0.117388E+10 | 1014.68 | 01-FEB-08:09 |
March | 0.187582E+10 | 1486.92 | 01-MAR-08:09 | 0.137025E+10 | 1014.68 | 01-MAR-08:09 |
April | 0.170739E+10 | 1486.92 | 03-APR-07:10 | 0.124489E+10 | 1014.68 | 03-APR-07:10 |
May | 0.182803E+10 | 1486.92 | 01-MAY-07:10 | 0.133431E+10 | 1014.68 | 01-MAY-07:10 |
June | 0.180297E+10 | 1486.92 | 01-JUN-07:10 | 0.131677E+10 | 1014.68 | 01-JUN-07:10 |
July | 0.173244E+10 | 1486.92 | 03-JUL-07:10 | 0.126242E+10 | 1014.68 | 03-JUL-07:10 |
August | 0.187582E+10 | 1486.92 | 01-AUG-07:10 | 0.137025E+10 | 1014.68 | 01-AUG-07:10 |
September | 0.170739E+10 | 1486.92 | 01-SEP-07:10 | 0.124489E+10 | 1014.68 | 01-SEP-07:10 |
October | 0.178023E+10 | 1486.92 | 02-OCT-07:10 | 0.129836E+10 | 1014.68 | 02-OCT-07:10 |
November | 0.175518E+10 | 1486.92 | 01-NOV-07:10 | 0.128083E+10 | 1014.68 | 01-NOV-07:10 |
December | 0.173244E+10 | 1486.92 | 01-DEC-08:09 | 0.126242E+10 | 1014.68 | 01-DEC-08:09 |
Annual Sum or Average | 0.211874E+11 | 0.154576E+11 | ||||
Minimum of Months | 0.160950E+10 | 1486.92 | 0.117388E+10 | 1014.68 | ||
Maximum of Months | 0.187582E+10 | 1486.92 | 0.137025E+10 | 1014.68 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134953E+10 | 1127.18 | 02-JAN-08:09 | 0.984244E+09 | 769.19 | 02-JAN-08:09 |
February | 0.122010E+10 | 1127.18 | 01-FEB-08:09 | 0.889874E+09 | 769.19 | 01-FEB-08:09 |
March | 0.142199E+10 | 1127.18 | 01-MAR-08:09 | 0.103874E+10 | 769.19 | 01-MAR-08:09 |
April | 0.129431E+10 | 1127.18 | 03-APR-07:10 | 0.943705E+09 | 769.19 | 03-APR-07:10 |
May | 0.138576E+10 | 1127.18 | 01-MAY-07:10 | 0.101149E+10 | 769.19 | 01-MAY-07:10 |
June | 0.136677E+10 | 1127.18 | 01-JUN-07:10 | 0.998201E+09 | 769.19 | 01-JUN-07:10 |
July | 0.131330E+10 | 1127.18 | 03-JUL-07:10 | 0.956997E+09 | 769.19 | 03-JUL-07:10 |
August | 0.142199E+10 | 1127.18 | 01-AUG-07:10 | 0.103874E+10 | 769.19 | 01-AUG-07:10 |
September | 0.129431E+10 | 1127.18 | 01-SEP-07:10 | 0.943705E+09 | 769.19 | 01-SEP-07:10 |
October | 0.134953E+10 | 1127.18 | 02-OCT-07:10 | 0.984244E+09 | 769.19 | 02-OCT-07:10 |
November | 0.133054E+10 | 1127.18 | 01-NOV-07:10 | 0.970953E+09 | 769.19 | 01-NOV-07:10 |
December | 0.131330E+10 | 1127.18 | 01-DEC-08:09 | 0.956997E+09 | 769.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.160615E+11 | 0.117179E+11 | ||||
Minimum of Months | 0.122010E+10 | 1127.18 | 0.889874E+09 | 769.19 | ||
Maximum of Months | 0.142199E+10 | 1127.18 | 0.103874E+10 | 769.19 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.800560E+09 | 668.66 | 02-JAN-08:09 | 0.583867E+09 | 456.29 | 02-JAN-08:09 |
February | 0.723780E+09 | 668.66 | 01-FEB-08:09 | 0.527885E+09 | 456.29 | 01-FEB-08:09 |
March | 0.843543E+09 | 668.66 | 01-MAR-08:09 | 0.616194E+09 | 456.29 | 01-MAR-08:09 |
April | 0.767803E+09 | 668.66 | 03-APR-07:10 | 0.559818E+09 | 456.29 | 03-APR-07:10 |
May | 0.822052E+09 | 668.66 | 01-MAY-07:10 | 0.600030E+09 | 456.29 | 01-MAY-07:10 |
June | 0.810786E+09 | 668.66 | 01-JUN-07:10 | 0.592146E+09 | 456.29 | 01-JUN-07:10 |
July | 0.779069E+09 | 668.66 | 03-JUL-07:10 | 0.567703E+09 | 456.29 | 03-JUL-07:10 |
August | 0.843543E+09 | 668.66 | 01-AUG-07:10 | 0.616194E+09 | 456.29 | 01-AUG-07:10 |
September | 0.767803E+09 | 668.66 | 01-SEP-07:10 | 0.559818E+09 | 456.29 | 01-SEP-07:10 |
October | 0.800560E+09 | 668.66 | 02-OCT-07:10 | 0.583867E+09 | 456.29 | 02-OCT-07:10 |
November | 0.789294E+09 | 668.66 | 01-NOV-07:10 | 0.575982E+09 | 456.29 | 01-NOV-07:10 |
December | 0.779069E+09 | 668.66 | 01-DEC-08:09 | 0.567703E+09 | 456.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.952786E+10 | 0.695120E+10 | ||||
Minimum of Months | 0.723780E+09 | 668.66 | 0.527885E+09 | 456.29 | ||
Maximum of Months | 0.843543E+09 | 668.66 | 0.616194E+09 | 456.29 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134953E+10 | 1127.18 | 02-JAN-08:09 | 0.984244E+09 | 769.19 | 02-JAN-08:09 |
February | 0.122010E+10 | 1127.18 | 01-FEB-08:09 | 0.889874E+09 | 769.19 | 01-FEB-08:09 |
March | 0.142199E+10 | 1127.18 | 01-MAR-08:09 | 0.103874E+10 | 769.19 | 01-MAR-08:09 |
April | 0.129431E+10 | 1127.18 | 03-APR-07:10 | 0.943705E+09 | 769.19 | 03-APR-07:10 |
May | 0.138576E+10 | 1127.18 | 01-MAY-07:10 | 0.101149E+10 | 769.19 | 01-MAY-07:10 |
June | 0.136677E+10 | 1127.18 | 01-JUN-07:10 | 0.998201E+09 | 769.19 | 01-JUN-07:10 |
July | 0.131330E+10 | 1127.18 | 03-JUL-07:10 | 0.956997E+09 | 769.19 | 03-JUL-07:10 |
August | 0.142199E+10 | 1127.18 | 01-AUG-07:10 | 0.103874E+10 | 769.19 | 01-AUG-07:10 |
September | 0.129431E+10 | 1127.18 | 01-SEP-07:10 | 0.943705E+09 | 769.19 | 01-SEP-07:10 |
October | 0.134953E+10 | 1127.18 | 02-OCT-07:10 | 0.984244E+09 | 769.19 | 02-OCT-07:10 |
November | 0.133054E+10 | 1127.18 | 01-NOV-07:10 | 0.970953E+09 | 769.19 | 01-NOV-07:10 |
December | 0.131330E+10 | 1127.18 | 01-DEC-08:09 | 0.956997E+09 | 769.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.160615E+11 | 0.117179E+11 | ||||
Minimum of Months | 0.122010E+10 | 1127.18 | 0.889874E+09 | 769.19 | ||
Maximum of Months | 0.142199E+10 | 1127.18 | 0.103874E+10 | 769.19 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.800560E+09 | 668.66 | 02-JAN-08:09 | 0.583867E+09 | 456.29 | 02-JAN-08:09 |
February | 0.723780E+09 | 668.66 | 01-FEB-08:09 | 0.527885E+09 | 456.29 | 01-FEB-08:09 |
March | 0.843543E+09 | 668.66 | 01-MAR-08:09 | 0.616194E+09 | 456.29 | 01-MAR-08:09 |
April | 0.767803E+09 | 668.66 | 03-APR-07:10 | 0.559818E+09 | 456.29 | 03-APR-07:10 |
May | 0.822052E+09 | 668.66 | 01-MAY-07:10 | 0.600030E+09 | 456.29 | 01-MAY-07:10 |
June | 0.810786E+09 | 668.66 | 01-JUN-07:10 | 0.592146E+09 | 456.29 | 01-JUN-07:10 |
July | 0.779069E+09 | 668.66 | 03-JUL-07:10 | 0.567703E+09 | 456.29 | 03-JUL-07:10 |
August | 0.843543E+09 | 668.66 | 01-AUG-07:10 | 0.616194E+09 | 456.29 | 01-AUG-07:10 |
September | 0.767803E+09 | 668.66 | 01-SEP-07:10 | 0.559818E+09 | 456.29 | 01-SEP-07:10 |
October | 0.800560E+09 | 668.66 | 02-OCT-07:10 | 0.583867E+09 | 456.29 | 02-OCT-07:10 |
November | 0.789294E+09 | 668.66 | 01-NOV-07:10 | 0.575982E+09 | 456.29 | 01-NOV-07:10 |
December | 0.779069E+09 | 668.66 | 01-DEC-08:09 | 0.567703E+09 | 456.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.952786E+10 | 0.695120E+10 | ||||
Minimum of Months | 0.723780E+09 | 668.66 | 0.527885E+09 | 456.29 | ||
Maximum of Months | 0.843543E+09 | 668.66 | 0.616194E+09 | 456.29 |
Report: SPACE LOADS
For: CORE_ZN
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [Invalid/Undefined] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [Invalid/Undefined] | |
January | 0.790646E+09 | 0.178023E+10 | 0.129836E+10 | 0.00 | 0.00 |
February | 0.715347E+09 | 0.160950E+10 | 0.117388E+10 | 0.00 | 0.00 |
March | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
April | 0.752997E+09 | 0.170739E+10 | 0.124489E+10 | 0.00 | 0.00 |
May | 0.828296E+09 | 0.182803E+10 | 0.133431E+10 | 0.00 | 0.00 |
June | 0.828296E+09 | 0.180297E+10 | 0.131677E+10 | 0.00 | 0.00 |
July | 0.752997E+09 | 0.173244E+10 | 0.126242E+10 | 0.00 | 0.00 |
August | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
September | 0.752997E+09 | 0.170739E+10 | 0.124489E+10 | 0.00 | 0.00 |
October | 0.790646E+09 | 0.178023E+10 | 0.129836E+10 | 0.00 | 0.00 |
November | 0.790646E+09 | 0.175518E+10 | 0.128083E+10 | 0.00 | 0.00 |
December | 0.752997E+09 | 0.173244E+10 | 0.126242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.948776E+10 | 0.211874E+11 | 0.154576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715347E+09 | 0.160950E+10 | 0.117388E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
Report: SPACE LOADS
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.146007E+10 |
February | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.116301E+10 |
March | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.137939E+10 |
April | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 0.00 | 0.107039E+10 |
May | 0.627902E+09 | 0.138576E+10 | 0.101149E+10 | 0.00 | 0.901805E+09 |
June | 0.627902E+09 | 0.136677E+10 | 0.998201E+09 | 0.00 | 0.671398E+09 |
July | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 1355917.45 | 0.530933E+09 |
August | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.584589E+09 |
September | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 0.00 | 0.801359E+09 |
October | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.105649E+10 |
November | 0.599361E+09 | 0.133054E+10 | 0.970953E+09 | 0.00 | 0.138334E+10 |
December | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 0.00 | 0.163908E+10 |
Annual Sum or Average | 0.719233E+10 | 0.160615E+11 | 0.117179E+11 | 1355917.45 | 0.126418E+11 |
Minimum of Months | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.530933E+09 |
Maximum of Months | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 1355917.45 | 0.163908E+10 |
Report: SPACE LOADS
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.318982E+09 |
February | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.238044E+09 |
March | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.313598E+09 |
April | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 0.00 | 0.259163E+09 |
May | 0.372480E+09 | 0.822052E+09 | 0.600030E+09 | 0.00 | 0.225265E+09 |
June | 0.372480E+09 | 0.810786E+09 | 0.592146E+09 | 0.00 | 0.173278E+09 |
July | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 28668.46 | 0.160727E+09 |
August | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.167156E+09 |
September | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 0.00 | 0.223291E+09 |
October | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.268851E+09 |
November | 0.355549E+09 | 0.789294E+09 | 0.575982E+09 | 0.00 | 0.322903E+09 |
December | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 0.00 | 0.460246E+09 |
Annual Sum or Average | 0.426659E+10 | 0.952786E+10 | 0.695120E+10 | 28668.46 | 0.313150E+10 |
Minimum of Months | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.160727E+09 |
Maximum of Months | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 28668.46 | 0.460246E+09 |
Report: SPACE LOADS
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.481704E+09 |
February | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.355885E+09 |
March | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.469461E+09 |
April | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 0.00 | 0.381706E+09 |
May | 0.627902E+09 | 0.138576E+10 | 0.101149E+10 | 0.00 | 0.330542E+09 |
June | 0.627902E+09 | 0.136677E+10 | 0.998201E+09 | 0.00 | 0.259853E+09 |
July | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 43236.13 | 0.232538E+09 |
August | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.241760E+09 |
September | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 0.00 | 0.330081E+09 |
October | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.400682E+09 |
November | 0.599361E+09 | 0.133054E+10 | 0.970953E+09 | 0.00 | 0.488323E+09 |
December | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 0.00 | 0.696234E+09 |
Annual Sum or Average | 0.719233E+10 | 0.160615E+11 | 0.117179E+11 | 43236.13 | 0.466877E+10 |
Minimum of Months | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.232538E+09 |
Maximum of Months | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 43236.13 | 0.696234E+09 |
Report: SPACE LOADS
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.320460E+09 |
February | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.238928E+09 |
March | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.316649E+09 |
April | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 0.00 | 0.266857E+09 |
May | 0.372480E+09 | 0.822052E+09 | 0.600030E+09 | 0.00 | 0.234780E+09 |
June | 0.372480E+09 | 0.810786E+09 | 0.592146E+09 | 0.00 | 0.185506E+09 |
July | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 28373.99 | 0.172894E+09 |
August | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.176234E+09 |
September | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 0.00 | 0.230643E+09 |
October | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.268614E+09 |
November | 0.355549E+09 | 0.789294E+09 | 0.575982E+09 | 0.00 | 0.324247E+09 |
December | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 0.00 | 0.460858E+09 |
Annual Sum or Average | 0.426659E+10 | 0.952786E+10 | 0.695120E+10 | 28373.99 | 0.319667E+10 |
Minimum of Months | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.172894E+09 |
Maximum of Months | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 28373.99 | 0.460858E+09 |
Report: SPACE LOADS
For: ATTIC
Timestamp: 2015-09-09 18:45:45
ZONE PEOPLE TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE LIGHTS TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.862206E+09 | 0.548753E+09 |
February | 0.00 | 0.00 | 0.00 | 0.771978E+09 | 0.113370E+10 |
March | 0.00 | 0.00 | 0.00 | 0.726513E+09 | 0.209614E+10 |
April | 0.00 | 0.00 | 0.00 | 0.699565E+09 | 0.346714E+10 |
May | 0.00 | 0.00 | 0.00 | 0.656860E+09 | 0.444754E+10 |
June | 0.00 | 0.00 | 0.00 | 0.466372E+09 | 0.453634E+10 |
July | 0.00 | 0.00 | 0.00 | 0.652407E+09 | 0.506232E+10 |
August | 0.00 | 0.00 | 0.00 | 0.739861E+09 | 0.404968E+10 |
September | 0.00 | 0.00 | 0.00 | 0.796769E+09 | 0.288179E+10 |
October | 0.00 | 0.00 | 0.00 | 0.620004E+09 | 0.126547E+10 |
November | 0.00 | 0.00 | 0.00 | 0.851193E+09 | 0.600020E+09 |
December | 0.00 | 0.00 | 0.00 | 0.638799E+09 | 0.442674E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.848253E+10 | 0.305316E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.466372E+09 | 0.442674E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.862206E+09 | 0.506232E+10 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2015-09-09 18:45:45
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [Invalid/Undefined] | GAS:BUILDING [Invalid/Undefined] | |
January | 0.105150E+11 | 8544.26 | 02-JAN-08:09 | 0.00 | 0.00 |
February | 0.950665E+10 | 8544.26 | 01-FEB-08:09 | 0.00 | 0.00 |
March | 0.110870E+11 | 8544.26 | 01-MAR-08:09 | 0.00 | 0.00 |
April | 0.100836E+11 | 8544.26 | 03-APR-07:10 | 0.00 | 0.00 |
May | 0.108010E+11 | 8544.26 | 01-MAY-07:10 | 0.00 | 0.00 |
June | 0.106556E+11 | 8544.26 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 0.102290E+11 | 8544.26 | 03-JUL-07:10 | 0.00 | 0.00 |
August | 0.110870E+11 | 8544.26 | 01-AUG-07:10 | 0.00 | 0.00 |
September | 0.100836E+11 | 8544.26 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.105150E+11 | 8544.26 | 02-OCT-07:10 | 0.00 | 0.00 |
November | 0.103696E+11 | 8544.26 | 01-NOV-07:10 | 0.00 | 0.00 |
December | 0.102290E+11 | 8544.26 | 01-DEC-08:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125162E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.950665E+10 | 8544.26 | 0.00 | 0.00 | |
Maximum of Months | 0.110870E+11 | 8544.26 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2015-09-09 18:45:45
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.608042E+10 | 0.00 | 0.162015E+10 | 0.443459E+10 | 0.00 | 0.179298E+10 | 0.02 | 0.177937E+10 | 3960362.21 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
February | 0.549726E+10 | 0.00 | 0.132736E+10 | 0.400939E+10 | 0.00 | 0.162222E+10 | 0.02 | 0.919419E+09 | 29643909.54 | 0.00 | 0.00 | 0.00 | 0.138378E+10 | 0.00 |
March | 0.640688E+10 | 0.00 | 0.128634E+10 | 0.468012E+10 | 0.00 | 0.196374E+10 | 0.02 | 0.894833E+09 | 0.107307E+09 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
April | 0.583162E+10 | 0.00 | 0.106268E+10 | 0.425193E+10 | 0.00 | 0.170760E+10 | 0.02 | 0.332859E+09 | 0.272123E+09 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
May | 0.624365E+10 | 0.00 | 0.932302E+09 | 0.455735E+10 | 0.00 | 0.187836E+10 | 0.02 | 91200237.85 | 0.595381E+09 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
June | 0.615808E+10 | 0.00 | 0.815413E+09 | 0.449747E+10 | 0.00 | 0.187836E+10 | 0.02 | 2470104.12 | 0.152454E+10 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
July | 0.591719E+10 | 0.00 | 0.880039E+09 | 0.431182E+10 | 0.00 | 0.170877E+10 | 0.02 | 0.00 | 0.193348E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
August | 0.640688E+10 | 0.00 | 0.102334E+10 | 0.468012E+10 | 0.00 | 0.196383E+10 | 0.02 | 0.00 | 0.227719E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
September | 0.583162E+10 | 0.00 | 0.116552E+10 | 0.425193E+10 | 0.00 | 0.170760E+10 | 0.02 | 16472577.64 | 0.138358E+10 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
October | 0.608042E+10 | 0.00 | 0.139368E+10 | 0.443459E+10 | 0.00 | 0.179298E+10 | 0.02 | 0.209780E+09 | 0.265388E+09 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
November | 0.599485E+10 | 0.00 | 0.151618E+10 | 0.437470E+10 | 0.00 | 0.179298E+10 | 0.02 | 0.113018E+10 | 39030599.17 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
December | 0.591719E+10 | 0.00 | 0.166735E+10 | 0.431182E+10 | 0.00 | 0.170760E+10 | 0.02 | 0.172361E+10 | 2603428.44 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
Annual Sum or Average | 0.723661E+11 | 0.00 | 0.146904E+11 | 0.527958E+11 | 0.00 | 0.215170E+11 | 0.24 | 0.710020E+10 | 0.843423E+10 | 0.00 | 0.00 | 0.00 | 0.180386E+11 | 0.00 |
Minimum of Months | 0.549726E+10 | 0.00 | 0.815413E+09 | 0.400939E+10 | 0.00 | 0.162222E+10 | 0.02 | 0.00 | 2603428.44 | 0.00 | 0.00 | 0.00 | 0.138378E+10 | 0.00 |
Maximum of Months | 0.640688E+10 | 0.00 | 0.166735E+10 | 0.468012E+10 | 0.00 | 0.196383E+10 | 0.02 | 0.177937E+10 | 0.227719E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2015-09-09 18:45:45
INTERIOREQUIPMENT:GAS [Invalid/Undefined] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.231149E+09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 94411017.59 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 87605079.85 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6597625.15 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.197940E+09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.221653E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.839355E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.231149E+09 | 0.00 | 0.00 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY PART 1
For: Meter
Timestamp: 2015-09-09 18:45:45
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 5078.61 | 02-JAN-08:09 | 0.00 | 936.61 | 01-JAN-00:10 | 3465.65 | 02-JAN-08:09 | 0.00 | 1824.36 | 02-JAN-06:10 | 0.00 | 02-JAN-07:10 | 6625.23 | 30-JAN-06:30 |
February | 5078.61 | 01-FEB-08:09 | 0.00 | 936.61 | 01-FEB-00:10 | 3465.65 | 01-FEB-08:09 | 0.00 | 1824.36 | 06-FEB-17:10 | 0.00 | 01-FEB-07:10 | 6677.32 | 21-FEB-06:30 |
March | 5078.61 | 01-MAR-08:09 | 0.00 | 936.61 | 01-MAR-00:10 | 3465.65 | 01-MAR-08:09 | 0.00 | 1824.36 | 02-MAR-10:20 | 0.00 | 27-MAR-15:50 | 6235.69 | 20-MAR-05:30 |
April | 5078.61 | 03-APR-07:10 | 0.00 | 936.61 | 01-APR-00:10 | 3465.65 | 03-APR-07:10 | 0.00 | 1824.36 | 03-APR-05:10 | 0.00 | 11-APR-16:10 | 3376.36 | 17-APR-05:10 |
May | 5078.61 | 01-MAY-07:10 | 0.00 | 936.61 | 01-MAY-00:10 | 3465.65 | 01-MAY-07:10 | 0.00 | 1824.36 | 03-MAY-07:10 | 0.00 | 24-MAY-13:09 | 2181.69 | 08-MAY-05:10 |
June | 5078.61 | 01-JUN-07:10 | 0.00 | 936.61 | 01-JUN-00:10 | 3465.65 | 01-JUN-07:10 | 0.00 | 1824.36 | 05-JUN-08:00 | 0.00 | 13-JUN-14:20 | 346.29 | 19-JUN-06:19 |
July | 5078.61 | 03-JUL-07:10 | 0.00 | 936.61 | 01-JUL-00:10 | 3465.65 | 03-JUL-07:10 | 0.00 | 1824.36 | 03-JUL-05:10 | 0.00 | 03-JUL-06:40 | 0.00 | 01-JUL-00:10 |
August | 5078.61 | 01-AUG-07:10 | 0.00 | 936.61 | 01-AUG-00:10 | 3465.65 | 01-AUG-07:10 | 0.00 | 1824.36 | 01-AUG-05:10 | 0.00 | 18-AUG-13:09 | 0.00 | 01-AUG-00:10 |
September | 5078.61 | 01-SEP-07:10 | 0.00 | 936.61 | 01-SEP-00:10 | 3465.65 | 01-SEP-07:10 | 0.00 | 1824.36 | 01-SEP-05:10 | 0.00 | 01-SEP-06:10 | 1576.19 | 29-SEP-06:10 |
October | 5078.61 | 02-OCT-07:10 | 0.00 | 936.61 | 01-OCT-00:10 | 3465.65 | 02-OCT-07:10 | 0.00 | 1824.36 | 03-OCT-08:39 | 0.00 | 02-OCT-06:10 | 3248.39 | 26-OCT-05:10 |
November | 5078.61 | 01-NOV-07:10 | 0.00 | 936.61 | 01-NOV-00:10 | 3465.65 | 01-NOV-07:10 | 0.00 | 1824.36 | 01-NOV-05:10 | 0.00 | 01-NOV-06:10 | 6805.06 | 27-NOV-06:30 |
December | 5078.61 | 01-DEC-08:09 | 0.00 | 936.61 | 01-DEC-00:10 | 3465.65 | 01-DEC-08:09 | 0.00 | 1824.36 | 04-DEC-06:10 | 0.00 | 01-DEC-07:10 | 6882.01 | 18-DEC-06:19 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 5078.61 | 0.00 | 936.61 | 3465.65 | 0.00 | 1824.36 | 0.00 | 0.00 | ||||||
Maximum of Months | 5078.61 | 0.00 | 936.61 | 3465.65 | 0.00 | 1824.36 | 0.00 | 6882.01 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:45
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.172435E+11 | 15195.937 | 05-JAN-08:09 | 5078.615 | 3465.647 | 1824.361 | 3318.704 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.147891E+11 | 13251.501 | 21-FEB-07:10 | 2370.020 | 1732.824 | 1824.361 | 5815.686 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.168713E+11 | 13471.154 | 20-MAR-07:10 | 5078.615 | 3465.647 | 1824.361 | 2530.531 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.149414E+11 | 13006.222 | 28-APR-15:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2065.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.158303E+11 | 13505.704 | 11-MAY-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2565.081 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.163590E+11 | 14592.320 | 23-JUN-15:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 3651.697 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.162833E+11 | 15186.364 | 12-JUL-14:00 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4245.741 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.178834E+11 | 14962.059 | 09-AUG-15:20 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4021.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.158394E+11 | 15145.853 | 13-SEP-15:09 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 4205.230 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.157089E+11 | 13088.043 | 06-OCT-14:30 | 5078.615 | 3465.647 | 1824.361 | 0.000 | 2147.420 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.163306E+11 | 14920.469 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1824.361 | 3979.846 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.168622E+11 | 15439.275 | 26-DEC-08:09 | 5078.615 | 3465.647 | 1824.361 | 3562.042 | 0.000 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.194942E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.147891E+11 | 13006.222 | 2370.020 | 1732.824 | 1824.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.178834E+11 | 15439.275 | 5078.615 | 3465.647 | 1824.361 | 5815.686 | 4245.741 | 936.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:45
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.231149E+09 | 10426.419 | 17-JAN-06:10 | 10426.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10426.419 |
February | 0.944110E+08 | 10018.945 | 21-FEB-06:10 | 10018.945 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10018.945 |
March | 0.876051E+08 | 10013.595 | 20-MAR-05:10 | 10013.595 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10013.595 |
April | 6597625.146 | 3657.828 | 18-APR-05:10 | 3657.828 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3657.828 |
May | 0.000 | 0.000 | 01-MAY-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 01-OCT-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.197940E+09 | 13124.814 | 27-NOV-06:10 | 13124.814 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13124.814 |
December | 0.221653E+09 | 14959.115 | 11-DEC-06:10 | 14959.115 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14959.115 |
Annual Sum or Average | 0.839355E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.231149E+09 | 14959.115 | 14959.115 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14959.115 |