Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:45
Tabular Output Report in Format: HTML
Building: Small Office
Environment: Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Simulation Timestamp: 2015-09-09 18:45:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 221.29 | 432.91 | 432.91 |
Net Site Energy | 221.29 | 432.91 | 432.91 |
Total Source Energy | 674.97 | 1320.47 | 1320.47 |
Net Source Energy | 674.97 | 1320.47 | 1320.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.16 |
Net Conditioned Building Area | 511.16 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 11.49 | 12.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.04 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 208.88 | 12.41 | 0.00 | 0.00 | 0.00 | 58.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 11.49 | 12.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 72.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 52.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 23.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18.04 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 170.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.99 | 24.28 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 103.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.64 | 24.28 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 170.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.99 | 24.28 | 0.00 | 0.00 | 0.00 | 0.11 |
Other | 103.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.64 | 24.28 | 0.00 | 0.00 | 0.00 | 0.11 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 208.88 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 208.88 | 100.00 |
Total On-Site and Utility Electric Sources | 208.88 | 100.00 |
Total Electricity End Uses | 208.88 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 58.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 58.31 | 100.00 |
Total Water End Uses | 58.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 53.83 |
Time Setpoint Not Met During Occupied Cooling | 59.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1817.67 |
Table of Contents
TopMONTHLY INDOOR TEMP
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |OUTDOOR AIR SUMMARY
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |VENTILATION LOAD COMPONENTS
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |OVERALL HVAC AIR SYSTEM LOADS
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK NET ELECTRICAL DEMAND
| Meter |SETPOINTS NOT MET WITH TEMPERATURES
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |COMFORT REPORT - SIMPLE 55
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - COOLING
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - HEATING
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |BUILDING LOADS - ELECTRIC
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |SPACE LOADS
| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY PART 1
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:45 |
RunPeriod | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Weather File | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Latitude [deg] | 41.98 |
Longitude [deg] | -87.9 |
Elevation [m] | 201.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.68 | 16.73 | 11.16 | 20.64 | 11.16 |
Window-Wall Ratio [%] | 21.20 | 19.81 | 19.81 | 24.44 | 19.81 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 281.51 | 84.45 | 56.30 | 84.45 | 56.30 |
Window Opening Area [m2] | 59.68 | 16.73 | 11.16 | 20.64 | 11.16 |
Window-Wall Ratio [%] | 21.20 | 19.81 | 19.81 | 24.44 | 19.81 |
Total | |
Gross Roof Area [m2] | 598.76 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_ZN | 149.66 | Yes | Yes | 456.46 | 1.00 | 0.00 | 0.00 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_1 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 20.64 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_2 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 11.16 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_3 | 113.45 | Yes | Yes | 346.02 | 1.00 | 84.45 | 16.73 | 10.7639 | 16.59 | 6.7800 |
PERIMETER_ZN_4 | 67.30 | Yes | Yes | 205.26 | 1.00 | 56.30 | 11.16 | 10.7639 | 16.59 | 6.7800 |
ATTIC | 567.98 | No | No | 720.19 | 1.00 | 0.00 | 0.00 | |||
Total | 511.16 | 1559.03 | 281.51 | 59.68 | 10.7639 | 16.59 | 6.7800 | |||
Conditioned Total | 511.16 | 1559.03 | 281.51 | 59.68 | 10.7639 | 16.59 | 6.7800 | |||
Unconditioned Total | 567.98 | 720.19 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 567.98 | 720.19 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -20.00 | 0.00 | -20.00 | Wetbulb [C] | 4.90 | 270.00 |
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 10.50 | 23.70 | Wetbulb [C] | 5.20 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_ZN_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 149.66 | 270.00 | 180.00 | |
PERIMETER_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 84.45 | 180.00 | 90.00 | S |
PERIMETER_ZN_1_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 113.45 | 135.00 | 180.00 | |
PERIMETER_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 56.30 | 90.00 | 90.00 | E |
PERIMETER_ZN_2_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 67.30 | 270.00 | 180.00 | |
PERIMETER_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 84.45 | 0.00 | 90.00 | N |
PERIMETER_ZN_3_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 113.45 | 180.00 | 180.00 | |
PERIMETER_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 56.30 | 270.00 | 90.00 | W |
PERIMETER_ZN_4_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 67.30 | 90.00 | 180.00 | |
ATTIC_SOFFIT_WEST | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 11.44 | 270.00 | 180.00 | |
ATTIC_SOFFIT_SOUTH | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 16.97 | 225.00 | 180.00 | |
ATTIC_SOFFIT_EAST | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 11.44 | 45.00 | 180.00 | |
ATTIC_SOFFIT_NORTH | EXT_SOFFIT_FLOOR | 0.30 | 2.663 | 7.547 | 16.97 | 315.00 | 180.00 | |
ATTIC_ROOF_NORTH | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 197.51 | 0.00 | 18.45 | |
ATTIC_ROOF_WEST | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 101.87 | 270.00 | 18.45 | |
ATTIC_ROOF_EAST | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 101.87 | 90.00 | 18.45 | |
ATTIC_ROOF_SOUTH | ATTICROOFDECK | 0.30 | 2.494 | 4.706 | 197.51 | 180.00 | 18.45 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_1_WALL_SOUTH_DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.91 | 0.00 | 0.00 | 3.91 | 3.91 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | PERIMETER_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 59.68 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 16.73 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 42.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6241.89 | 4529.56 | 1712.33 | 0.73 | 3.91 | |||
PSZ-AC:2 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6888.44 | 5226.28 | 1662.16 | 0.76 | 3.91 | |||
PSZ-AC:3 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5067.46 | 4047.16 | 1020.31 | 0.80 | 3.91 | |||
PSZ-AC:4 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6039.49 | 4501.35 | 1538.15 | 0.75 | 3.91 | |||
PSZ-AC:5 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5787.07 | 4604.75 | 1182.31 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6004.3 | 3.28 | 11.20 | 11.74 | 11.22 |
PSZ-AC:2 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6597.3 | 3.22 | 10.99 | 11.51 | 10.91 |
PSZ-AC:3 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4827.6 | 3.15 | 10.75 | 11.25 | 10.55 |
PSZ-AC:4 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5794.5 | 3.24 | 11.07 | 11.60 | 11.03 |
PSZ-AC:5 HEAT PUMP DX COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5515.3 | 3.16 | 10.77 | 11.27 | 10.58 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6483.2 | 3585.1 | 7.34 | 4 |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 7183.6 | 3985.4 | 7.30 | 4 |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 5310.3 | 2957.5 | 7.27 | 4 |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6288.0 | 3483.9 | 7.28 | 4 |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6062.2 | 3375.3 | 7.27 | 4 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6241.89 | 3.29 | |
PSZ-AC:1 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 4859.83 | 0.80 | |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6888.44 | 3.29 | |
PSZ-AC:2 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 7719.97 | 0.80 | |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 5067.46 | 3.29 | |
PSZ-AC:3 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 4701.34 | 0.80 | |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 6039.49 | 3.29 | |
PSZ-AC:4 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 7424.64 | 0.80 | |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | Coil:Heating:DX:SingleSpeed | 5787.07 | 3.29 | |
PSZ-AC:5 HEAT PUMP DX SUPP HEATING COIL | Coil:Heating:Gas | 4728.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
PSZ-AC:1 FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 350.83 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:2 FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 430.57 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:3 FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 355.36 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:4 FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 362.09 | 1160.84 | 1.00 | Fan Energy |
PSZ-AC:5 FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 402.56 | 1160.84 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0000 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 0.99 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
CORE_ZN | 3351.82 | 4022.18 | 0.252 | 0.302 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.77 | 0.01496 |
PERIMETER_ZN_1 | 4113.36 | 4936.03 | 0.309 | 0.371 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.12 | 0.01496 |
PERIMETER_ZN_2 | 3395.21 | 4074.25 | 0.255 | 0.306 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 27.82 | 0.01496 |
PERIMETER_ZN_3 | 3459.27 | 4151.12 | 0.260 | 0.312 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.09 | 0.01496 |
PERIMETER_ZN_4 | 3846.09 | 4615.31 | 0.289 | 0.347 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.83 | 0.01496 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
CORE_ZN | 1455.35 | 1746.42 | 0.064 | 0.077 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -20.00 | 0.00065 |
PERIMETER_ZN_1 | 4516.36 | 5419.63 | 0.199 | 0.239 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -20.00 | 0.00065 |
PERIMETER_ZN_2 | 2782.14 | 3338.56 | 0.123 | 0.147 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -20.00 | 0.00065 |
PERIMETER_ZN_3 | 4266.62 | 5119.94 | 0.188 | 0.226 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -20.00 | 0.00065 |
PERIMETER_ZN_4 | 2805.26 | 3366.31 | 0.124 | 0.149 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -20.00 | 0.00065 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
PSZ-AC:1 | 0.30 | 0.30 | 0.08 | 0.08 |
PSZ-AC:2 | 0.37 | 0.37 | 0.24 | 0.24 |
PSZ-AC:3 | 0.31 | 0.31 | 0.15 | 0.15 |
PSZ-AC:4 | 0.31 | 0.31 | 0.23 | 0.23 |
PSZ-AC:5 | 0.35 | 0.35 | 0.15 | 0.15 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_ZN | 1659.33 | 2815.50 | 667.33 |
PERIMETER_ZN_1 | 2455.83 | 2880.50 | 1436.67 |
PERIMETER_ZN_2 | 2618.00 | 2775.33 | 1438.50 |
PERIMETER_ZN_3 | 2498.67 | 2934.00 | 1559.67 |
PERIMETER_ZN_4 | 2554.00 | 2862.83 | 1502.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 2981.17 | 3165.17 | 1817.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_ZN | 7.67 | 19.50 | 7.67 | 19.50 |
PERIMETER_ZN_1 | 171.17 | 47.50 | 48.67 | 44.83 |
PERIMETER_ZN_2 | 192.00 | 9.67 | 29.83 | 2.33 |
PERIMETER_ZN_3 | 209.00 | 5.67 | 29.00 | 5.67 |
PERIMETER_ZN_4 | 201.33 | 13.67 | 26.67 | 2.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 396.00 | 79.17 | 53.83 | 59.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:45:33
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
CORE_ZN DIRECT AIR | 0.302219 |
PERIMETER_ZN_1 DIRECT AIR | 0.370911 |
PERIMETER_ZN_2 DIRECT AIR | 0.306125 |
PERIMETER_ZN_3 DIRECT AIR | 0.311917 |
PERIMETER_ZN_4 DIRECT AIR | 0.346784 |
Maximum Flow Rate [m3/s] | |
PSZ-AC:1 AIR LOOP MAIN BRANCH | 0.302219 |
PSZ-AC:2 AIR LOOP MAIN BRANCH | 0.370911 |
PSZ-AC:3 AIR LOOP MAIN BRANCH | 0.306125 |
PSZ-AC:4 AIR LOOP MAIN BRANCH | 0.311917 |
PSZ-AC:5 AIR LOOP MAIN BRANCH | 0.346784 |
Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 0.302219 |
PSZ-AC:2 | 0.370911 |
PSZ-AC:3 | 0.306125 |
PSZ-AC:4 | 0.311917 |
PSZ-AC:5 | 0.346784 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 0.302219 | 0.064618 |
PSZ-AC:2_OA_CONTROLLER | 0.370911 | 0.048985 |
PSZ-AC:3_OA_CONTROLLER | 0.306125 | 0.029058 |
PSZ-AC:4_OA_CONTROLLER | 0.311917 | 0.048985 |
PSZ-AC:5_OA_CONTROLLER | 0.346784 | 0.029058 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
PSZ-AC:1 HEAT PUMP DX COOLING COIL | 0.302219 | 6241.89 | 0.725671 |
PSZ-AC:2 HEAT PUMP DX COOLING COIL | 0.370911 | 6888.44 | 0.758704 |
PSZ-AC:3 HEAT PUMP DX COOLING COIL | 0.306125 | 5067.46 | 0.798655 |
PSZ-AC:4 HEAT PUMP DX COOLING COIL | 0.311917 | 6039.49 | 0.745319 |
PSZ-AC:5 HEAT PUMP DX COOLING COIL | 0.346784 | 5787.07 | 0.795698 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Maximum Supply Air Temperature from Supplemental Heater [C] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_HEATPUMP | 0.302219 | 0.302219 | 0.302219 | 0.302219 | 6241.89 | 6241.89 | 40.00 | 4859.83 | 1.00 |
PSZ-AC:2_HEATPUMP | 0.370911 | 0.370911 | 0.370911 | 0.370911 | 6888.44 | 6888.44 | 40.00 | 7719.97 | 1.00 |
PSZ-AC:3_HEATPUMP | 0.306125 | 0.306125 | 0.306125 | 0.306125 | 5067.46 | 5067.46 | 40.00 | 4701.34 | 1.00 |
PSZ-AC:4_HEATPUMP | 0.311917 | 0.311917 | 0.311917 | 0.311917 | 6039.49 | 6039.49 | 40.00 | 7424.64 | 1.00 |
PSZ-AC:5_HEATPUMP | 0.346784 | 0.346784 | 0.346784 | 0.346784 | 5787.07 | 5787.07 | 40.00 | 4728.69 | 1.00 |
Maximum Flow Rate [m3/s] | |
PSZ-AC:1 FAN | 0.302219 |
PSZ-AC:2 FAN | 0.370911 |
PSZ-AC:3 FAN | 0.306125 |
PSZ-AC:4 FAN | 0.311917 |
PSZ-AC:5 FAN | 0.346784 |
Rated Air Flow Rate [m3/s] | Rated Total Heating Capacity [W] | Resistive Defrost Heater Capacity | |
PSZ-AC:1 HEAT PUMP DX HEATING COIL | 0.302219 | 6241.89 | 0.000000 |
PSZ-AC:2 HEAT PUMP DX HEATING COIL | 0.370911 | 6888.44 | 0.000000 |
PSZ-AC:3 HEAT PUMP DX HEATING COIL | 0.306125 | 5067.46 | 0.000000 |
PSZ-AC:4 HEAT PUMP DX HEATING COIL | 0.311917 | 6039.49 | 0.000000 |
PSZ-AC:5 HEAT PUMP DX HEATING COIL | 0.346784 | 5787.07 | 0.000000 |
Nominal Capacity [W] | |
PSZ-AC:1 HEAT PUMP DX SUPP HEATING COIL | 4859.83 |
PSZ-AC:2 HEAT PUMP DX SUPP HEATING COIL | 7719.97 |
PSZ-AC:3 HEAT PUMP DX SUPP HEATING COIL | 4701.34 |
PSZ-AC:4 HEAT PUMP DX SUPP HEATING COIL | 7424.64 |
PSZ-AC:5 HEAT PUMP DX SUPP HEATING COIL | 4728.69 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000004 | 0.003036 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000004 | 0.000000 |
Report: MONTHLY INDOOR TEMP
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.31 | -4.6 |
February | 20.62 | -2.5 |
March | 21.54 | 3.82 |
April | 22.43 | 9.95 |
May | 23.56 | 15.30 |
June | 24.95 | 21.11 |
July | 25.60 | 24.13 |
August | 25.33 | 21.78 |
September | 25.13 | 18.14 |
October | 23.38 | 10.98 |
November | 21.98 | 4.73 |
December | 20.52 | -3.7 |
Annual Sum or Average | 22.96 | 9.99 |
Minimum of Months | 20.31 | -4.6 |
Maximum of Months | 25.60 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.67 | -4.6 |
February | 18.94 | -2.5 |
March | 20.16 | 3.82 |
April | 21.26 | 9.95 |
May | 22.74 | 15.30 |
June | 24.43 | 21.11 |
July | 25.38 | 24.13 |
August | 25.00 | 21.78 |
September | 24.64 | 18.14 |
October | 22.39 | 10.98 |
November | 20.46 | 4.73 |
December | 18.68 | -3.7 |
Annual Sum or Average | 21.91 | 9.99 |
Minimum of Months | 18.67 | -4.6 |
Maximum of Months | 25.38 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.25 | -4.6 |
February | 18.63 | -2.5 |
March | 20.01 | 3.82 |
April | 21.36 | 9.95 |
May | 23.03 | 15.30 |
June | 24.64 | 21.11 |
July | 25.48 | 24.13 |
August | 25.02 | 21.78 |
September | 24.48 | 18.14 |
October | 22.10 | 10.98 |
November | 20.13 | 4.73 |
December | 18.31 | -3.7 |
Annual Sum or Average | 21.80 | 9.99 |
Minimum of Months | 18.25 | -4.6 |
Maximum of Months | 25.48 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.25 | -4.6 |
February | 18.62 | -2.5 |
March | 19.72 | 3.82 |
April | 21.11 | 9.95 |
May | 22.73 | 15.30 |
June | 24.46 | 21.11 |
July | 25.28 | 24.13 |
August | 24.85 | 21.78 |
September | 24.25 | 18.14 |
October | 21.85 | 10.98 |
November | 20.07 | 4.73 |
December | 18.30 | -3.7 |
Annual Sum or Average | 21.64 | 9.99 |
Minimum of Months | 18.25 | -4.6 |
Maximum of Months | 25.28 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.30 | -4.6 |
February | 18.70 | -2.5 |
March | 20.00 | 3.82 |
April | 21.46 | 9.95 |
May | 23.13 | 15.30 |
June | 24.82 | 21.11 |
July | 25.67 | 24.13 |
August | 25.17 | 21.78 |
September | 24.57 | 18.14 |
October | 22.09 | 10.98 |
November | 20.17 | 4.73 |
December | 18.31 | -3.7 |
Annual Sum or Average | 21.88 | 9.99 |
Minimum of Months | 18.30 | -4.6 |
Maximum of Months | 25.67 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.9 | -4.6 |
February | -0.8 | -2.5 |
March | 6.77 | 3.82 |
April | 13.99 | 9.95 |
May | 21.23 | 15.30 |
June | 27.25 | 21.11 |
July | 30.16 | 24.13 |
August | 26.64 | 21.78 |
September | 21.69 | 18.14 |
October | 12.82 | 10.98 |
November | 5.69 | 4.73 |
December | -3.4 | -3.7 |
Annual Sum or Average | 13.25 | 9.99 |
Minimum of Months | -3.9 | -4.6 |
Maximum of Months | 30.16 | 24.13 |
Report: OUTDOOR AIR SUMMARY
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE [Invalid/Undefined] | |
January | 357.000 | 5.127 | 0.393 | 0.000 |
February | 323.000 | 5.127 | 0.395 | 0.000 |
March | 391.000 | 5.127 | 0.396 | 0.000 |
April | 340.000 | 5.127 | 0.396 | 0.000 |
May | 374.000 | 5.127 | 0.400 | 0.000 |
June | 374.000 | 5.127 | 0.401 | 0.000 |
July | 340.000 | 5.127 | 0.401 | 0.000 |
August | 391.000 | 5.127 | 0.400 | 0.000 |
September | 340.000 | 5.127 | 0.400 | 0.000 |
October | 357.000 | 5.127 | 0.399 | 0.000 |
November | 357.000 | 5.127 | 0.398 | 0.000 |
December | 340.000 | 5.127 | 0.394 | 0.000 |
Annual Sum or Average | 4284.000 | 5.127 | 0.398 | 0.000 |
Minimum of Months | 323.000 | 5.127 | 0.393 | 0.000 |
Maximum of Months | 391.000 | 5.127 | 0.401 | 0.000 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 3.886 | 0.394 | 0.511 |
February | 323.000 | 3.886 | 0.393 | 0.511 |
March | 391.000 | 3.886 | 0.394 | 0.504 |
April | 340.000 | 3.886 | 0.395 | 0.489 |
May | 374.000 | 3.886 | 0.399 | 0.450 |
June | 374.000 | 3.886 | 0.400 | 0.465 |
July | 340.000 | 3.886 | 0.401 | 0.455 |
August | 391.000 | 3.886 | 0.400 | 0.444 |
September | 340.000 | 3.886 | 0.400 | 0.433 |
October | 357.000 | 3.886 | 0.397 | 0.476 |
November | 357.000 | 3.886 | 0.396 | 0.496 |
December | 340.000 | 3.886 | 0.392 | 0.484 |
Annual Sum or Average | 4284.000 | 3.886 | 0.397 | 0.476 |
Minimum of Months | 323.000 | 3.886 | 0.392 | 0.433 |
Maximum of Months | 391.000 | 3.886 | 0.401 | 0.511 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 2.305 | 0.394 | 0.142 |
February | 323.000 | 2.305 | 0.393 | 0.143 |
March | 391.000 | 2.305 | 0.394 | 0.146 |
April | 340.000 | 2.305 | 0.395 | 0.137 |
May | 374.000 | 2.305 | 0.399 | 0.101 |
June | 374.000 | 2.305 | 0.400 | 0.126 |
July | 340.000 | 2.305 | 0.401 | 0.117 |
August | 391.000 | 2.305 | 0.400 | 0.102 |
September | 340.000 | 2.305 | 0.400 | 0.085 |
October | 357.000 | 2.305 | 0.397 | 0.124 |
November | 357.000 | 2.305 | 0.397 | 0.140 |
December | 340.000 | 2.305 | 0.393 | 0.113 |
Annual Sum or Average | 4284.000 | 2.305 | 0.397 | 0.123 |
Minimum of Months | 323.000 | 2.305 | 0.393 | 0.085 |
Maximum of Months | 391.000 | 2.305 | 0.401 | 0.146 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 3.886 | 0.394 | 0.126 |
February | 323.000 | 3.886 | 0.393 | 0.127 |
March | 391.000 | 3.886 | 0.394 | 0.130 |
April | 340.000 | 3.886 | 0.395 | 0.122 |
May | 374.000 | 3.886 | 0.399 | 0.090 |
June | 374.000 | 3.886 | 0.400 | 0.112 |
July | 340.000 | 3.886 | 0.401 | 0.104 |
August | 391.000 | 3.886 | 0.400 | 0.091 |
September | 340.000 | 3.886 | 0.400 | 0.076 |
October | 357.000 | 3.886 | 0.397 | 0.111 |
November | 357.000 | 3.886 | 0.396 | 0.124 |
December | 340.000 | 3.886 | 0.392 | 0.100 |
Annual Sum or Average | 4284.000 | 3.886 | 0.397 | 0.109 |
Minimum of Months | 323.000 | 3.886 | 0.392 | 0.076 |
Maximum of Months | 391.000 | 3.886 | 0.401 | 0.130 |
Report: OUTDOOR AIR SUMMARY
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR {FOR HOURS SHOWN} [ach] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 357.000 | 2.305 | 0.395 | 0.142 |
February | 323.000 | 2.305 | 0.393 | 0.143 |
March | 391.000 | 2.305 | 0.394 | 0.146 |
April | 340.000 | 2.305 | 0.395 | 0.137 |
May | 374.000 | 2.305 | 0.399 | 0.102 |
June | 374.000 | 2.305 | 0.400 | 0.126 |
July | 340.000 | 2.305 | 0.401 | 0.117 |
August | 391.000 | 2.305 | 0.400 | 0.102 |
September | 340.000 | 2.305 | 0.400 | 0.085 |
October | 357.000 | 2.305 | 0.397 | 0.124 |
November | 357.000 | 2.305 | 0.397 | 0.140 |
December | 340.000 | 2.305 | 0.393 | 0.113 |
Annual Sum or Average | 4284.000 | 2.305 | 0.397 | 0.123 |
Minimum of Months | 323.000 | 2.305 | 0.393 | 0.085 |
Maximum of Months | 391.000 | 2.305 | 0.401 | 0.146 |
Report: OUTDOOR AIR SUMMARY
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE OCCUPANT COUNT [Invalid/Undefined] | ZONE PEOPLE OCCUPANT COUNT [Invalid/Undefined] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [Invalid/Undefined] | ZONE INFILTRATION AIR CHANGE RATE {FOR HOURS SHOWN} [ach] | |
January | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | 0.000 | 0.000 | |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 | 0.000 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.198077E+10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.433151E+09 | 0.000 | 0.000 |
February | 0.173456E+10 | 0.000 | 0.000 | 15883.387 | 0.000 | 0.380534E+09 | 0.169000E+08 | 0.000 |
March | 0.180139E+10 | 0.000 | 0.000 | 328264.302 | 0.000 | 0.117958E+09 | 0.149383E+09 | 0.000 |
April | 0.101933E+10 | 0.315572E+08 | 0.000 | 1308538.417 | 1494552.589 | 0.268242E+08 | 0.296517E+09 | 0.000 |
May | 0.344749E+09 | 0.279902E+08 | 0.000 | 4002547.285 | 2741295.435 | 0.000 | 0.518018E+09 | 0.000 |
June | 0.174626E+08 | 0.450303E+09 | 0.000 | 3732798.012 | 0.265065E+08 | 0.000 | 0.166912E+09 | 0.000 |
July | 762789.855 | 0.861777E+09 | 0.000 | 1739054.006 | 0.587766E+08 | 0.000 | 0.223973E+08 | 0.000 |
August | 7134117.544 | 0.547462E+09 | 0.000 | 3523253.421 | 0.364972E+08 | 0.000 | 0.945154E+08 | 0.000 |
September | 0.265347E+08 | 0.145819E+09 | 0.000 | 5704048.026 | 9429318.850 | 0.000 | 0.322079E+09 | 0.000 |
October | 0.527645E+09 | 0.000 | 0.000 | 3254491.429 | 0.000 | 0.000 | 0.774084E+09 | 0.000 |
November | 0.123811E+10 | 0.000 | 0.000 | 1028757.072 | 0.000 | 0.113428E+09 | 0.319811E+09 | 0.000 |
December | 0.194433E+10 | 0.000 | 0.000 | 30.957 | 0.000 | 0.314650E+09 | 990098.294 | 0.000 |
Annual Sum or Average | 0.106428E+11 | 0.206491E+10 | 0.000 | 0.246377E+08 | 0.135445E+09 | 0.138654E+10 | 0.268161E+10 | 0.000 |
Minimum of Months | 762789.855 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.198077E+10 | 0.861777E+09 | 0.000 | 5704048.026 | 0.587766E+08 | 0.433151E+09 | 0.774084E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.398536E+09 | 0.000 | 0.000 | 109578.732 | 0.000 | 0.132899E+10 | 0.437927E+08 | 0.000 |
February | 0.500066E+09 | 0.000 | 0.000 | 107380.965 | 0.000 | 0.855283E+09 | 0.435586E+08 | 0.000 |
March | 0.553811E+09 | 0.000 | 0.000 | 816957.687 | 0.000 | 0.469789E+09 | 0.148952E+09 | 0.000 |
April | 0.326952E+09 | 0.329645E+08 | 0.000 | 1358221.615 | 1744492.400 | 0.257357E+09 | 0.133731E+09 | 0.000 |
May | 0.187130E+09 | 0.346406E+08 | 0.000 | 2267781.222 | 1460059.036 | 0.621893E+08 | 0.164087E+09 | 0.000 |
June | 0.464195E+08 | 0.345978E+09 | 0.000 | 1746645.147 | 0.164148E+08 | 2111542.655 | 0.501272E+08 | 0.000 |
July | 6856118.867 | 0.596846E+09 | 0.000 | 858391.857 | 0.317924E+08 | 0.000 | 0.122906E+08 | 0.000 |
August | 0.364488E+08 | 0.394128E+09 | 0.000 | 1520704.133 | 0.192268E+08 | 0.000 | 0.343555E+08 | 0.000 |
September | 0.926757E+08 | 0.130267E+09 | 0.000 | 3504271.028 | 5107799.474 | 5514601.065 | 0.121041E+09 | 0.000 |
October | 0.261647E+09 | 64876.285 | 0.000 | 3264614.816 | 0.000 | 0.107228E+09 | 0.317212E+09 | 0.000 |
November | 0.421306E+09 | 1527531.891 | 0.000 | 726007.385 | 93459.625 | 0.427388E+09 | 0.132517E+09 | 0.000 |
December | 0.526223E+09 | 0.000 | 0.000 | 81225.510 | 0.000 | 0.895703E+09 | 0.225114E+08 | 0.000 |
Annual Sum or Average | 0.335807E+10 | 0.153642E+10 | 0.000 | 0.163618E+08 | 0.758398E+08 | 0.441156E+10 | 0.122418E+10 | 0.000 |
Minimum of Months | 6856118.867 | 0.000 | 0.000 | 81225.510 | 0.000 | 0.000 | 0.122906E+08 | 0.000 |
Maximum of Months | 0.553811E+09 | 0.596846E+09 | 0.000 | 3504271.028 | 0.317924E+08 | 0.132899E+10 | 0.317212E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.313206E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.820321E+09 | 0.000 | 0.000 |
February | 0.367167E+09 | 0.000 | 0.000 | 708.635 | 0.000 | 0.506491E+09 | 3943316.864 | 0.000 |
March | 0.465699E+09 | 0.000 | 0.000 | 238890.148 | 0.000 | 0.181812E+09 | 0.929315E+08 | 0.000 |
April | 0.232973E+09 | 0.203505E+08 | 0.000 | 1297134.334 | 894165.814 | 0.807691E+08 | 0.149206E+09 | 0.000 |
May | 0.830362E+08 | 0.186833E+08 | 0.000 | 3071157.004 | 894088.323 | 0.100080E+08 | 0.177337E+09 | 0.000 |
June | 0.136357E+08 | 0.234707E+09 | 0.000 | 1826323.188 | 0.127451E+08 | 0.000 | 0.445899E+08 | 0.000 |
July | 458051.850 | 0.405558E+09 | 0.000 | 708068.881 | 0.264904E+08 | 0.000 | 8561538.697 | 0.000 |
August | 4944604.548 | 0.257235E+09 | 0.000 | 1522891.754 | 0.166814E+08 | 0.000 | 0.322367E+08 | 0.000 |
September | 0.364258E+08 | 0.759508E+08 | 0.000 | 2871367.727 | 4658939.773 | 0.000 | 0.975726E+08 | 0.000 |
October | 0.143588E+09 | 0.000 | 0.000 | 1589346.379 | 0.000 | 0.405866E+08 | 0.263036E+09 | 0.000 |
November | 0.319149E+09 | 161207.471 | 0.000 | 302764.046 | 28859.733 | 0.212995E+09 | 0.841945E+08 | 0.000 |
December | 0.364451E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.546327E+09 | 0.000 | 0.000 |
Annual Sum or Average | 0.234473E+10 | 0.101265E+10 | 0.000 | 0.134287E+08 | 0.623930E+08 | 0.239931E+10 | 0.953610E+09 | 0.000 |
Minimum of Months | 458051.850 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.465699E+09 | 0.405558E+09 | 0.000 | 3071157.004 | 0.264904E+08 | 0.820321E+09 | 0.263036E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.446121E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.149204E+10 | 0.000 | 0.000 |
February | 0.453555E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.103164E+10 | 0.000 | 0.000 |
March | 0.824178E+09 | 0.000 | 0.000 | 79240.296 | 0.000 | 0.363389E+09 | 0.263629E+08 | 0.000 |
April | 0.487537E+09 | 0.312629E+08 | 0.000 | 792570.548 | 2026823.094 | 0.155978E+09 | 0.119992E+09 | 0.000 |
May | 0.191382E+09 | 0.329044E+08 | 0.000 | 2368578.621 | 1886132.741 | 0.229200E+08 | 0.230835E+09 | 0.000 |
June | 0.334665E+08 | 0.403211E+09 | 0.000 | 1731396.098 | 0.246262E+08 | 0.000 | 0.623088E+08 | 0.000 |
July | 1365600.327 | 0.690044E+09 | 0.000 | 891789.317 | 0.489608E+08 | 0.000 | 0.144892E+08 | 0.000 |
August | 0.144038E+08 | 0.451549E+09 | 0.000 | 1495629.818 | 0.319666E+08 | 0.000 | 0.495716E+08 | 0.000 |
September | 0.715646E+08 | 0.135525E+09 | 0.000 | 2757341.136 | 9799088.745 | 0.000 | 0.150634E+09 | 0.000 |
October | 0.369747E+09 | 0.000 | 0.000 | 1196774.530 | 0.000 | 0.699742E+08 | 0.300327E+09 | 0.000 |
November | 0.535428E+09 | 130506.113 | 0.000 | 356616.625 | 77812.239 | 0.415417E+09 | 0.938104E+08 | 0.000 |
December | 0.507121E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.102241E+10 | 0.000 | 0.000 |
Annual Sum or Average | 0.393587E+10 | 0.174463E+10 | 0.000 | 0.116699E+08 | 0.119343E+09 | 0.457378E+10 | 0.104833E+10 | 0.000 |
Minimum of Months | 1365600.327 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.824178E+09 | 0.690044E+09 | 0.000 | 2757341.136 | 0.489608E+08 | 0.149204E+10 | 0.300327E+09 | 0.000 |
Report: VENTILATION LOAD COMPONENTS
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | |
January | 0.288555E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.860519E+09 | 0.000 | 0.000 |
February | 0.309839E+09 | 0.000 | 0.000 | 33900.814 | 0.000 | 0.558542E+09 | 0.146354E+08 | 0.000 |
March | 0.442876E+09 | 0.000 | 0.000 | 351599.478 | 0.000 | 0.212022E+09 | 0.734788E+08 | 0.000 |
April | 0.268142E+09 | 0.187020E+08 | 0.000 | 949873.059 | 917362.077 | 0.902870E+08 | 0.999427E+08 | 0.000 |
May | 0.104049E+09 | 0.186729E+08 | 0.000 | 2145661.282 | 1022446.816 | 0.167548E+08 | 0.149283E+09 | 0.000 |
June | 0.176539E+08 | 0.224426E+09 | 0.000 | 1334773.272 | 0.128238E+08 | 0.000 | 0.442978E+08 | 0.000 |
July | 505424.323 | 0.392023E+09 | 0.000 | 535398.820 | 0.272609E+08 | 0.000 | 9590048.760 | 0.000 |
August | 6679289.689 | 0.250131E+09 | 0.000 | 1054730.191 | 0.174038E+08 | 0.000 | 0.337303E+08 | 0.000 |
September | 0.422384E+08 | 0.722723E+08 | 0.000 | 1980289.066 | 4846120.670 | 0.000 | 0.974224E+08 | 0.000 |
October | 0.178934E+09 | 0.000 | 0.000 | 1245742.124 | 0.000 | 0.459249E+08 | 0.217753E+09 | 0.000 |
November | 0.298128E+09 | 119649.293 | 0.000 | 297326.160 | 24565.824 | 0.243167E+09 | 0.763479E+08 | 0.000 |
December | 0.352681E+09 | 0.000 | 0.000 | 0.000 | 0.000 | 0.556750E+09 | 0.000 | 0.000 |
Annual Sum or Average | 0.231028E+10 | 0.976347E+09 | 0.000 | 9929294.267 | 0.642989E+08 | 0.258397E+10 | 0.816481E+09 | 0.000 |
Minimum of Months | 505424.323 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.442876E+09 | 0.392023E+09 | 0.000 | 2145661.282 | 0.272609E+08 | 0.860519E+09 | 0.217753E+09 | 0.000 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:1
Timestamp: 2015-09-09 18:45:33
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.112485E+10 | 0.000 |
February | 0.976760E+09 | 3527857.063 |
March | 0.581982E+09 | 0.529335E+08 |
April | 0.392587E+09 | 0.563056E+09 |
May | 0.361212E+09 | 0.130080E+10 |
June | 0.361212E+09 | 0.344304E+10 |
July | 0.328374E+09 | 0.420882E+10 |
August | 0.377631E+09 | 0.411752E+10 |
September | 0.328374E+09 | 0.276270E+10 |
October | 0.345280E+09 | 0.782994E+09 |
November | 0.532754E+09 | 0.372257E+09 |
December | 0.907283E+09 | 0.000 |
Annual Sum or Average | 0.661830E+10 | 0.176077E+11 |
Minimum of Months | 0.328374E+09 | 0.000 |
Maximum of Months | 0.112485E+10 | 0.420882E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:2
Timestamp: 2015-09-09 18:45:33
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.356858E+10 | 0.122915E+08 |
February | 0.255953E+10 | 0.114071E+08 |
March | 0.172504E+10 | 0.174898E+09 |
April | 0.104056E+10 | 0.691763E+09 |
May | 0.574567E+09 | 0.116803E+10 |
June | 0.444804E+09 | 0.316808E+10 |
July | 0.403012E+09 | 0.416471E+10 |
August | 0.463464E+09 | 0.396364E+10 |
September | 0.408534E+09 | 0.270490E+10 |
October | 0.678162E+09 | 0.875603E+09 |
November | 0.151535E+10 | 0.292687E+09 |
December | 0.270471E+10 | 9687677.916 |
Annual Sum or Average | 0.160863E+11 | 0.172377E+11 |
Minimum of Months | 0.403012E+09 | 9687677.916 |
Maximum of Months | 0.356858E+10 | 0.416471E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:3
Timestamp: 2015-09-09 18:45:33
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.182844E+10 | 0.000 |
February | 0.125318E+10 | 308470.488 |
March | 0.748296E+09 | 0.431333E+08 |
April | 0.460248E+09 | 0.454762E+09 |
May | 0.376764E+09 | 0.978674E+09 |
June | 0.365881E+09 | 0.227095E+10 |
July | 0.333084E+09 | 0.270395E+10 |
August | 0.382512E+09 | 0.248908E+10 |
September | 0.332619E+09 | 0.159588E+10 |
October | 0.401421E+09 | 0.416043E+09 |
November | 0.746156E+09 | 0.152741E+09 |
December | 0.133432E+10 | 0.000 |
Annual Sum or Average | 0.856292E+10 | 0.111055E+11 |
Minimum of Months | 0.332619E+09 | 0.000 |
Maximum of Months | 0.182844E+10 | 0.270395E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:4
Timestamp: 2015-09-09 18:45:33
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.302893E+10 | 0.000 |
February | 0.217293E+10 | 0.000 |
March | 0.115513E+10 | 0.230340E+08 |
April | 0.621771E+09 | 0.420169E+09 |
May | 0.407926E+09 | 0.102244E+10 |
June | 0.372803E+09 | 0.286790E+10 |
July | 0.338912E+09 | 0.360945E+10 |
August | 0.389748E+09 | 0.325333E+10 |
September | 0.338912E+09 | 0.194907E+10 |
October | 0.460326E+09 | 0.342256E+09 |
November | 0.112659E+10 | 0.173589E+09 |
December | 0.216570E+10 | 0.000 |
Annual Sum or Average | 0.125797E+11 | 0.136612E+11 |
Minimum of Months | 0.338912E+09 | 0.000 |
Maximum of Months | 0.302893E+10 | 0.360945E+10 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: PSZ-AC:5
Timestamp: 2015-09-09 18:45:33
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.189746E+10 | 0.000 |
February | 0.133704E+10 | 4603681.827 |
March | 0.819942E+09 | 0.731595E+08 |
April | 0.513006E+09 | 0.432148E+09 |
May | 0.428546E+09 | 0.949172E+09 |
June | 0.414477E+09 | 0.211533E+10 |
July | 0.379100E+09 | 0.260812E+10 |
August | 0.433837E+09 | 0.240763E+10 |
September | 0.376971E+09 | 0.149628E+10 |
October | 0.445681E+09 | 0.408683E+09 |
November | 0.817470E+09 | 0.169540E+09 |
December | 0.137699E+10 | 0.000 |
Annual Sum or Average | 0.924052E+10 | 0.106647E+11 |
Minimum of Months | 0.376971E+09 | 0.000 |
Maximum of Months | 0.189746E+10 | 0.260812E+10 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2015-09-09 18:45:33
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.515295E+10 | 0.509088E+10 |
February | 0.395644E+10 | 0.343911E+10 |
March | 0.364612E+10 | 0.315463E+09 |
April | 0.301541E+10 | 0.105932E+09 |
May | 0.332279E+10 | 376767.978 |
June | 0.522862E+10 | 0.000 |
July | 0.583780E+10 | 0.000 |
August | 0.577736E+10 | 0.000 |
September | 0.420783E+10 | 0.000 |
October | 0.275202E+10 | 8030393.467 |
November | 0.342819E+10 | 0.968043E+09 |
December | 0.463806E+10 | 0.248074E+10 |
Annual Sum or Average | 0.509636E+11 | 0.124086E+11 |
Minimum of Months | 0.275202E+10 | 0.000 |
Maximum of Months | 0.583780E+10 | 0.509088E+10 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:33
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.187347E+11 | 16715.712 | 09-JAN-08:09 | 5078.615 | 3465.647 | 1901.404 | 5698.046 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.161304E+11 | 16796.238 | 21-FEB-08:09 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.175448E+11 | 15264.027 | 06-MAR-08:09 | 5078.615 | 3465.647 | 1901.404 | 4246.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.156769E+11 | 16069.956 | 18-APR-13:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5052.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.166618E+11 | 15425.685 | 30-MAY-15:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 4408.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.182822E+11 | 17663.449 | 08-JUN-12:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6645.783 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.185666E+11 | 18315.075 | 19-JUL-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.194720E+11 | 17874.604 | 04-AUG-15:39 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6856.938 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.169508E+11 | 16810.059 | 05-SEP-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5792.393 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.161624E+11 | 14179.055 | 02-OCT-13:30 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 3161.390 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.167274E+11 | 16759.242 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1901.404 | 5741.576 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.179681E+11 | 16397.330 | 15-DEC-08:09 | 5078.615 | 3465.647 | 1901.404 | 5379.664 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.208878E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.156769E+11 | 14179.055 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.194720E+11 | 18315.075 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK NET ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:33
ELECTRICITYNET:FACILITY [J] | ELECTRICITYNET:FACILITY {Maximum}[W] | ELECTRICITYNET:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.187347E+11 | 16715.712 | 09-JAN-08:09 | 5078.615 | 3465.647 | 1901.404 | 5698.046 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.161304E+11 | 16796.238 | 21-FEB-08:09 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.175448E+11 | 15264.027 | 06-MAR-08:09 | 5078.615 | 3465.647 | 1901.404 | 4246.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.156769E+11 | 16069.956 | 18-APR-13:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5052.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.166618E+11 | 15425.685 | 30-MAY-15:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 4408.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.182822E+11 | 17663.449 | 08-JUN-12:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6645.783 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.185666E+11 | 18315.075 | 19-JUL-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.194720E+11 | 17874.604 | 04-AUG-15:39 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6856.938 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.169508E+11 | 16810.059 | 05-SEP-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5792.393 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.161624E+11 | 14179.055 | 02-OCT-13:30 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 3161.390 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.167274E+11 | 16759.242 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1901.404 | 5741.576 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.179681E+11 | 16397.330 | 15-DEC-08:09 | 5078.615 | 3465.647 | 1901.404 | 5379.664 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.208878E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.156769E+11 | 14179.055 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.194720E+11 | 18315.075 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.45 | 2.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.50 | 20.44 | 3.50 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.83 | 0.17 | 20.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.40 | 2.83 | 24.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.57 | 8.83 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.58 | 5.33 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.45 | 2.50 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.88 | 0.17 | 20.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.60 | 1.50 | 20.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.67 | 20.49 | 7.67 | 20.49 | 19.50 | 24.53 | 19.50 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.88 | 3.50 | 20.88 | 8.83 | 24.58 | 8.83 | 24.58 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.17 | 16.25 | 17.17 | 18.90 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37.00 | 16.47 | 12.67 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9.67 | 16.72 | 2.67 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.00 | 20.73 | 1.00 | 20.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.18 | 1.00 | 24.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 24.41 | 24.83 | 24.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.36 | 12.00 | 24.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.85 | 7.00 | 24.36 |
October | 0.17 | 20.63 | 0.17 | 20.63 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.00 | 16.79 | 3.33 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55.17 | 16.03 | 11.67 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.17 | 16.31 | 48.67 | 19.21 | 47.50 | 24.69 | 44.83 | 24.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.17 | 20.73 | 17.17 | 20.73 | 24.83 | 25.85 | 24.83 | 24.41 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.83 | 15.66 | 8.67 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39.00 | 15.99 | 7.00 | 19.88 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14.50 | 16.20 | 2.67 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.70 | 0.67 | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.83 | 1.67 | 24.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.25 | 0.67 | 24.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.72 | 0.17 | 20.72 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.83 | 15.91 | 2.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60.00 | 15.68 | 8.33 | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.00 | 15.82 | 29.83 | 19.57 | 9.67 | 28.51 | 2.33 | 24.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.83 | 20.72 | 8.67 | 20.72 | 9.00 | 28.83 | 1.67 | 24.43 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.00 | 15.64 | 8.83 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35.17 | 16.14 | 7.33 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15.50 | 16.24 | 3.00 | 20.66 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.00 | 20.75 | 1.00 | 20.75 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.16 | 0.50 | 24.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.36 | 3.83 | 24.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.28 | 1.33 | 24.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.60 | 0.17 | 20.60 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20.17 | 15.72 | 2.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 15.68 | 6.50 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 209.00 | 15.82 | 29.00 | 19.88 | 5.67 | 24.32 | 5.67 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.00 | 20.75 | 8.83 | 20.75 | 3.83 | 24.36 | 3.83 | 24.36 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.83 | 15.62 | 8.50 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35.17 | 16.02 | 6.67 | 19.89 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15.50 | 16.02 | 2.33 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.68 | 0.50 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 29.78 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.77 | 1.83 | 24.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 0.83 | 24.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 29.75 | 0.00 | 0.00 |
October | 0.17 | 20.74 | 0.17 | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19.17 | 15.69 | 2.00 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67.00 | 15.58 | 6.50 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.33 | 15.73 | 26.67 | 19.67 | 13.67 | 28.75 | 2.67 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.00 | 20.74 | 8.50 | 20.74 | 9.50 | 29.78 | 1.83 | 24.34 |
Report: SETPOINTS NOT MET WITH TEMPERATURES
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: COMFORT REPORT - SIMPLE 55
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 21.23 | 167.33 | 20.93 | 167.33 | 20.93 |
February | 323.00 | 21.36 | 141.00 | 20.95 | 141.00 | 20.95 |
March | 391.00 | 22.13 | 30.33 | 21.16 | 30.33 | 21.16 |
April | 303.17 | 22.76 | 19.33 | 22.90 | 9.33 | 21.11 |
May | 277.17 | 23.63 | 23.00 | 24.28 | 11.67 | 24.22 |
June | 41.83 | 24.82 | 260.33 | 24.58 | 26.67 | 25.35 |
July | 66.17 | 25.98 | 326.50 | 24.56 | 66.17 | 25.98 |
August | 37.83 | 25.79 | 332.33 | 24.55 | 37.83 | 25.79 |
September | 24.50 | 24.71 | 194.50 | 24.67 | 12.33 | 25.53 |
October | 326.67 | 23.54 | 1.50 | 23.39 | 1.50 | 23.39 |
November | 327.17 | 22.45 | 52.67 | 22.18 | 52.67 | 22.18 |
December | 340.00 | 21.36 | 110.50 | 20.97 | 110.50 | 20.97 |
Annual Sum or Average | 2815.50 | 22.45 | 1659.33 | 23.50 | 667.33 | 22.15 |
Minimum of Months | 24.50 | 21.23 | 1.50 | 20.93 | 1.50 | 20.93 |
Maximum of Months | 391.00 | 25.98 | 332.33 | 24.67 | 167.33 | 25.98 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.55 | 286.50 | 20.19 | 286.50 | 20.19 |
February | 323.00 | 20.77 | 221.17 | 20.21 | 221.17 | 20.21 |
March | 375.67 | 21.34 | 171.50 | 20.42 | 171.50 | 20.42 |
April | 275.00 | 21.78 | 127.17 | 21.59 | 96.67 | 20.71 |
May | 260.17 | 22.99 | 47.33 | 23.77 | 15.67 | 22.54 |
June | 78.33 | 24.09 | 269.83 | 24.56 | 38.33 | 24.90 |
July | 122.00 | 25.37 | 330.50 | 24.66 | 119.50 | 25.41 |
August | 82.33 | 24.87 | 350.33 | 24.53 | 68.50 | 25.19 |
September | 75.50 | 23.63 | 225.17 | 24.45 | 21.83 | 25.13 |
October | 268.83 | 22.60 | 37.17 | 22.68 | 16.17 | 21.10 |
November | 322.67 | 21.59 | 133.33 | 20.63 | 125.00 | 20.41 |
December | 340.00 | 20.65 | 255.83 | 20.28 | 255.83 | 20.28 |
Annual Sum or Average | 2880.50 | 21.84 | 2455.83 | 22.51 | 1436.67 | 21.20 |
Minimum of Months | 75.50 | 20.55 | 37.17 | 20.19 | 15.67 | 20.19 |
Maximum of Months | 375.67 | 25.37 | 350.33 | 24.66 | 286.50 | 25.41 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.44 | 324.00 | 20.29 | 324.00 | 20.29 |
February | 323.00 | 20.63 | 268.00 | 20.32 | 268.00 | 20.32 |
March | 391.00 | 21.61 | 168.00 | 20.31 | 168.00 | 20.31 |
April | 273.50 | 22.17 | 102.83 | 21.61 | 75.17 | 20.60 |
May | 223.17 | 23.25 | 59.00 | 24.05 | 8.50 | 22.48 |
June | 38.83 | 24.39 | 312.67 | 24.48 | 17.00 | 25.31 |
July | 72.33 | 25.86 | 335.83 | 24.60 | 72.00 | 25.86 |
August | 45.17 | 25.33 | 370.83 | 24.45 | 41.17 | 25.48 |
September | 43.33 | 23.63 | 217.83 | 24.39 | 5.67 | 24.69 |
October | 326.83 | 23.00 | 15.67 | 21.08 | 15.67 | 21.08 |
November | 341.17 | 21.76 | 142.17 | 20.41 | 142.17 | 20.41 |
December | 340.00 | 20.53 | 301.17 | 20.37 | 301.17 | 20.37 |
Annual Sum or Average | 2775.33 | 21.82 | 2618.00 | 22.44 | 1438.50 | 20.87 |
Minimum of Months | 38.83 | 20.44 | 15.67 | 20.29 | 5.67 | 20.29 |
Maximum of Months | 391.00 | 25.86 | 370.83 | 24.60 | 324.00 | 25.86 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.41 | 340.67 | 20.36 | 340.67 | 20.36 |
February | 323.00 | 20.57 | 280.00 | 20.38 | 280.00 | 20.38 |
March | 391.00 | 21.18 | 207.33 | 20.44 | 207.33 | 20.44 |
April | 306.83 | 22.04 | 107.67 | 21.22 | 94.00 | 20.73 |
May | 283.33 | 23.21 | 32.00 | 23.74 | 12.17 | 22.18 |
June | 53.67 | 24.18 | 248.17 | 24.64 | 17.17 | 25.20 |
July | 71.17 | 25.75 | 325.50 | 24.62 | 69.17 | 25.80 |
August | 47.83 | 25.08 | 316.50 | 24.52 | 37.17 | 25.45 |
September | 60.00 | 23.54 | 142.67 | 24.55 | 3.83 | 24.40 |
October | 350.33 | 22.83 | 18.33 | 21.09 | 18.33 | 21.09 |
November | 349.83 | 21.67 | 164.33 | 20.53 | 164.33 | 20.53 |
December | 340.00 | 20.52 | 315.50 | 20.44 | 315.50 | 20.44 |
Annual Sum or Average | 2934.00 | 21.76 | 2498.67 | 22.22 | 1559.67 | 20.88 |
Minimum of Months | 47.83 | 20.41 | 18.33 | 20.36 | 3.83 | 20.36 |
Maximum of Months | 391.00 | 25.75 | 340.67 | 24.64 | 340.67 | 25.80 |
Report: COMFORT REPORT - SIMPLE 55
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.00 | 20.50 | 317.17 | 20.29 | 317.17 | 20.29 |
February | 323.00 | 20.77 | 252.00 | 20.34 | 252.00 | 20.34 |
March | 388.33 | 21.54 | 178.67 | 20.47 | 178.67 | 20.47 |
April | 272.50 | 22.14 | 117.00 | 21.98 | 82.50 | 20.82 |
May | 223.33 | 23.30 | 95.67 | 24.70 | 13.00 | 23.27 |
June | 81.00 | 25.89 | 282.17 | 24.93 | 50.33 | 27.18 |
July | 92.67 | 26.74 | 329.00 | 24.90 | 90.67 | 26.80 |
August | 69.17 | 26.23 | 337.17 | 24.80 | 58.50 | 26.67 |
September | 58.17 | 23.84 | 189.67 | 24.69 | 6.83 | 25.88 |
October | 316.67 | 22.95 | 20.67 | 21.43 | 18.33 | 21.12 |
November | 341.00 | 21.79 | 143.50 | 20.44 | 143.50 | 20.44 |
December | 340.00 | 20.60 | 291.33 | 20.38 | 291.33 | 20.38 |
Annual Sum or Average | 2862.83 | 22.04 | 2554.00 | 22.61 | 1502.83 | 21.31 |
Minimum of Months | 58.17 | 20.50 | 20.67 | 20.29 | 6.83 | 20.29 |
Maximum of Months | 388.33 | 26.74 | 337.17 | 24.93 | 317.17 | 27.18 |
Report: COMFORT REPORT - SIMPLE 55
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BUILDING LOADS - COOLING
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.868461E+09 | 1692.60 | 13-JAN-15:07 | -6.3 | -8.0 | 0.257406E+09 | 432.45 | 17-JAN-16:19 | 9.43 | 6.12 |
February | 0.779555E+09 | 2112.22 | 15-FEB-06:04 | -11.0 | -12.1 | 0.236402E+09 | 450.64 | 23-FEB-16:30 | 13.30 | 11.50 |
March | 0.917050E+09 | 1523.15 | 14-MAR-05:02 | -2.7 | -3.1 | 0.312318E+09 | 450.65 | 27-MAR-12:09 | 18.07 | 14.64 |
April | 0.911343E+09 | 2556.15 | 17-APR-05:05 | 18.98 | 17.69 | 0.290909E+09 | 450.66 | 18-APR-07:10 | 22.48 | 18.97 |
May | 0.112618E+10 | 2167.78 | 05-MAY-15:04 | 27.70 | 14.45 | 0.341458E+09 | 450.65 | 30-MAY-07:10 | 21.10 | 19.62 |
June | 0.215559E+10 | 5683.52 | 26-JUN-05:02 | 12.15 | 8.18 | 0.347686E+09 | 450.66 | 07-JUN-07:10 | 25.10 | 21.16 |
July | 0.239540E+10 | 4966.57 | 03-JUL-05:02 | 12.48 | 11.10 | 0.317065E+09 | 460.61 | 17-JUL-15:09 | 33.80 | 25.43 |
August | 0.257545E+10 | 5320.11 | 08-AUG-05:02 | 11.88 | 10.32 | 0.363946E+09 | 455.38 | 04-AUG-15:00 | 31.10 | 26.46 |
September | 0.202589E+10 | 5691.74 | 26-SEP-05:03 | 8.30 | 6.63 | 0.315826E+09 | 450.65 | 14-SEP-07:10 | 14.05 | 13.37 |
October | 0.110511E+10 | 2064.13 | 02-OCT-14:35 | 21.87 | 14.94 | 0.323058E+09 | 450.65 | 20-OCT-08:00 | 15.00 | 11.00 |
November | 0.922813E+09 | 2127.02 | 28-NOV-06:03 | -11.4 | -11.8 | 0.296836E+09 | 450.65 | 15-NOV-10:50 | 15.22 | 11.35 |
December | 0.895090E+09 | 1917.48 | 29-DEC-15:23 | -8.6 | -9.8 | 0.248548E+09 | 442.51 | 07-DEC-15:00 | 9.40 | 6.72 |
Annual Sum or Average | 0.166779E+11 | 0.365146E+10 | ||||||||
Minimum of Months | 0.779555E+09 | 1523.15 | -11.4 | -12.1 | 0.236402E+09 | 432.45 | 9.40 | 6.12 | ||
Maximum of Months | 0.257545E+10 | 5691.74 | 27.70 | 17.69 | 0.363946E+09 | 460.61 | 33.80 | 26.46 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191496E+09 | 2204.79 | 17-JAN-13:10 | 11.60 | 7.11 | 0.192554E+09 | 341.62 | 17-JAN-15:39 | 10.20 | 6.38 |
February | 0.265505E+09 | 1577.79 | 10-FEB-14:20 | 7.40 | 4.84 | 0.177929E+09 | 341.63 | 28-FEB-14:50 | 2.30 | -1.0 |
March | 0.456011E+09 | 2678.12 | 08-MAR-13:10 | 10.10 | 4.85 | 0.228289E+09 | 341.62 | 27-MAR-12:09 | 18.07 | 14.64 |
April | 0.681321E+09 | 4227.13 | 18-APR-13:30 | 30.85 | 21.14 | 0.209817E+09 | 341.63 | 18-APR-07:10 | 22.48 | 18.97 |
May | 0.914215E+09 | 3140.64 | 05-MAY-12:00 | 28.90 | 16.61 | 0.253060E+09 | 342.39 | 22-MAY-07:49 | 21.13 | 14.78 |
June | 0.202806E+10 | 6058.14 | 27-JUN-05:02 | 19.40 | 13.46 | 0.262936E+09 | 355.44 | 08-JUN-12:09 | 31.47 | 25.37 |
July | 0.245677E+10 | 4923.76 | 31-JUL-11:05 | 29.60 | 20.85 | 0.241677E+09 | 385.86 | 17-JUL-12:09 | 33.30 | 25.42 |
August | 0.256935E+10 | 5304.54 | 30-AUG-13:30 | 26.95 | 17.72 | 0.276183E+09 | 372.62 | 03-AUG-12:09 | 30.60 | 24.46 |
September | 0.206597E+10 | 5397.91 | 05-SEP-05:01 | 14.90 | 13.95 | 0.237941E+09 | 365.39 | 06-SEP-12:09 | 29.22 | 21.14 |
October | 0.956689E+09 | 4641.85 | 02-OCT-13:10 | 22.70 | 15.62 | 0.237141E+09 | 341.63 | 20-OCT-08:00 | 15.00 | 11.00 |
November | 0.420407E+09 | 3666.48 | 02-NOV-12:30 | 21.15 | 17.04 | 0.216356E+09 | 341.62 | 06-NOV-15:00 | 13.30 | 12.35 |
December | 0.242303E+09 | 2093.36 | 05-DEC-13:20 | 2.57 | -0.2 | 0.183393E+09 | 341.62 | 05-DEC-15:00 | 0.60 | -1.0 |
Annual Sum or Average | 0.132481E+11 | 0.271728E+10 | ||||||||
Minimum of Months | 0.191496E+09 | 1577.79 | 2.57 | -0.2 | 0.177929E+09 | 341.62 | 0.60 | -1.0 | ||
Maximum of Months | 0.256935E+10 | 6058.14 | 30.85 | 21.14 | 0.276183E+09 | 385.86 | 33.30 | 25.42 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70194227.18 | 723.09 | 05-JAN-09:32 | -12.4 | -13.0 | 0.112185E+09 | 191.14 | 17-JAN-15:09 | 10.50 | 6.45 |
February | 92113287.86 | 635.06 | 08-FEB-09:43 | -9.6 | -10.5 | 0.103436E+09 | 202.66 | 23-FEB-16:30 | 13.30 | 11.50 |
March | 0.204891E+09 | 621.32 | 15-MAR-09:42 | 5.73 | 1.63 | 0.139536E+09 | 202.67 | 20-MAR-10:50 | 5.60 | 2.39 |
April | 0.430493E+09 | 1759.86 | 17-APR-08:25 | 21.95 | 18.77 | 0.129750E+09 | 202.69 | 06-APR-10:00 | 5.00 | 0.70 |
May | 0.758639E+09 | 2339.96 | 05-MAY-08:42 | 23.43 | 14.35 | 0.153356E+09 | 202.66 | 22-MAY-07:10 | 18.87 | 14.40 |
June | 0.157161E+10 | 4420.56 | 27-JUN-05:02 | 19.40 | 13.46 | 0.156380E+09 | 202.66 | 26-JUN-07:19 | 20.33 | 15.36 |
July | 0.173118E+10 | 3683.20 | 05-JUL-08:35 | 27.77 | 23.02 | 0.142688E+09 | 202.66 | 10-JUL-07:10 | 19.60 | 17.76 |
August | 0.167473E+10 | 3592.50 | 02-AUG-05:02 | 18.30 | 16.58 | 0.163599E+09 | 202.66 | 15-AUG-07:10 | 19.60 | 18.70 |
September | 0.118294E+10 | 3966.40 | 05-SEP-05:01 | 14.90 | 13.95 | 0.141634E+09 | 202.66 | 13-SEP-07:10 | 14.45 | 12.79 |
October | 0.402085E+09 | 1220.96 | 05-OCT-09:23 | 15.60 | 11.15 | 0.143195E+09 | 202.66 | 20-OCT-09:50 | 16.42 | 12.53 |
November | 0.186809E+09 | 891.73 | 02-NOV-13:25 | 21.70 | 17.40 | 0.128629E+09 | 202.69 | 16-NOV-16:00 | 8.90 | 4.72 |
December | 86750906.98 | 597.68 | 15-DEC-09:53 | -8.9 | -9.9 | 0.106969E+09 | 186.95 | 07-DEC-15:39 | 9.97 | 6.92 |
Annual Sum or Average | 0.839244E+10 | 0.162136E+10 | ||||||||
Minimum of Months | 70194227.18 | 597.68 | -12.4 | -13.0 | 0.103436E+09 | 186.95 | 5.00 | 0.70 | ||
Maximum of Months | 0.173118E+10 | 4420.56 | 27.77 | 23.02 | 0.163599E+09 | 202.69 | 20.33 | 18.70 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123031E+09 | 1160.30 | 31-JAN-06:06 | -6.0 | -6.5 | 0.187187E+09 | 295.24 | 17-JAN-16:10 | 9.72 | 6.23 |
February | 0.132910E+09 | 913.52 | 03-FEB-11:03 | -2.1 | -3.7 | 0.171839E+09 | 333.83 | 23-FEB-15:39 | 13.50 | 11.84 |
March | 0.366076E+09 | 1140.92 | 22-MAR-05:04 | -3.2 | -4.4 | 0.220081E+09 | 341.62 | 27-MAR-12:30 | 18.60 | 14.37 |
April | 0.520477E+09 | 2378.82 | 18-APR-14:40 | 30.77 | 20.55 | 0.210363E+09 | 341.63 | 24-APR-15:00 | 16.10 | 15.79 |
May | 0.840025E+09 | 2252.18 | 05-MAY-14:34 | 28.73 | 14.77 | 0.255255E+09 | 341.63 | 22-MAY-07:40 | 20.57 | 14.71 |
June | 0.189559E+10 | 5308.83 | 27-JUN-05:02 | 19.40 | 13.46 | 0.263544E+09 | 341.63 | 26-JUN-07:19 | 20.33 | 15.36 |
July | 0.218152E+10 | 4632.67 | 10-JUL-05:02 | 15.87 | 14.53 | 0.240588E+09 | 349.67 | 17-JUL-15:09 | 33.80 | 25.43 |
August | 0.209961E+10 | 4440.49 | 10-AUG-05:02 | 16.78 | 14.75 | 0.275653E+09 | 341.63 | 02-AUG-07:10 | 22.07 | 19.26 |
September | 0.144293E+10 | 4618.95 | 05-SEP-05:01 | 14.90 | 13.95 | 0.238298E+09 | 341.63 | 26-SEP-07:49 | 14.85 | 10.91 |
October | 0.496285E+09 | 1477.40 | 02-OCT-14:35 | 21.87 | 14.94 | 0.235146E+09 | 341.63 | 20-OCT-10:20 | 17.23 | 12.70 |
November | 0.327450E+09 | 1238.77 | 03-NOV-14:10 | 20.50 | 17.67 | 0.212204E+09 | 341.62 | 02-NOV-09:20 | 17.23 | 14.64 |
December | 0.158236E+09 | 1313.35 | 29-DEC-16:03 | -9.6 | -10.7 | 0.178932E+09 | 304.16 | 07-DEC-15:30 | 10.25 | 7.01 |
Annual Sum or Average | 0.105841E+11 | 0.268909E+10 | ||||||||
Minimum of Months | 0.123031E+09 | 913.52 | -9.6 | -10.7 | 0.171839E+09 | 295.24 | 9.72 | 6.23 | ||
Maximum of Months | 0.218152E+10 | 5308.83 | 30.77 | 20.55 | 0.275653E+09 | 349.67 | 33.80 | 25.43 |
Report: BUILDING LOADS - COOLING
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72832499.89 | 506.91 | 13-JAN-16:20 | -7.6 | -9.0 | 0.112936E+09 | 190.94 | 11-JAN-16:10 | 3.12 | 1.38 |
February | 0.101201E+09 | 691.56 | 07-FEB-16:45 | -10.8 | -12.2 | 0.104897E+09 | 202.66 | 23-FEB-16:30 | 13.30 | 11.50 |
March | 0.186600E+09 | 1298.87 | 15-MAR-15:53 | 8.90 | 3.73 | 0.135777E+09 | 202.68 | 10-MAR-13:09 | 16.52 | 9.32 |
April | 0.372203E+09 | 2814.38 | 17-APR-15:55 | 28.90 | 18.33 | 0.127505E+09 | 202.72 | 11-APR-09:09 | 16.57 | 10.74 |
May | 0.686608E+09 | 2909.24 | 22-MAY-15:57 | 26.70 | 15.72 | 0.153007E+09 | 203.40 | 01-MAY-10:09 | 15.10 | 11.88 |
June | 0.137496E+10 | 5126.20 | 27-JUN-05:02 | 19.40 | 13.46 | 0.157212E+09 | 202.66 | 26-JUN-07:19 | 20.33 | 15.36 |
July | 0.158686E+10 | 4211.68 | 16-JUL-17:53 | 31.70 | 25.06 | 0.143444E+09 | 202.66 | 10-JUL-07:10 | 19.60 | 17.76 |
August | 0.153887E+10 | 4166.89 | 02-AUG-05:02 | 18.30 | 16.58 | 0.164373E+09 | 202.66 | 15-AUG-07:10 | 19.60 | 18.70 |
September | 0.104579E+10 | 4527.01 | 05-SEP-05:01 | 14.90 | 13.95 | 0.141906E+09 | 202.66 | 27-SEP-07:10 | 19.27 | 16.32 |
October | 0.352730E+09 | 1931.31 | 20-OCT-15:25 | 22.25 | 13.68 | 0.141242E+09 | 202.66 | 20-OCT-10:09 | 16.97 | 12.77 |
November | 0.168150E+09 | 1061.93 | 09-NOV-15:00 | 18.30 | 12.82 | 0.128699E+09 | 203.79 | 01-NOV-09:39 | 15.40 | 14.49 |
December | 98464524.26 | 650.46 | 12-DEC-06:05 | -8.2 | -8.6 | 0.107923E+09 | 198.64 | 07-DEC-15:30 | 10.25 | 7.01 |
Annual Sum or Average | 0.758527E+10 | 0.161892E+10 | ||||||||
Minimum of Months | 72832499.89 | 506.91 | -10.8 | -12.2 | 0.104897E+09 | 190.94 | 3.12 | 1.38 | ||
Maximum of Months | 0.158686E+10 | 5126.20 | 31.70 | 25.06 | 0.164373E+09 | 203.79 | 20.33 | 18.70 |
Report: BUILDING LOADS - COOLING
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -3.5 | -4.7 | 0.00 | 0.00 | 01-JAN-00:10 | -3.5 | -4.7 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -6.0 | -6.7 | 0.00 | 0.00 | 01-FEB-00:10 | -6.0 | -6.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.32 | -1.2 | 0.00 | 0.00 | 01-MAR-00:10 | 0.32 | -1.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | -0.7 | -2.1 | 0.00 | 0.00 | 01-APR-00:10 | -0.7 | -2.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.07 | 6.46 | 0.00 | 0.00 | 01-MAY-00:10 | 8.07 | 6.46 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.02 | 15.38 | 0.00 | 0.00 | 01-JUN-00:10 | 18.02 | 15.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17.33 | 15.09 | 0.00 | 0.00 | 01-JUL-00:10 | 17.33 | 15.09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21.15 | 17.38 | 0.00 | 0.00 | 01-AUG-00:10 | 21.15 | 17.38 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.96 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.96 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.53 | 8.77 | 0.00 | 0.00 | 01-OCT-00:10 | 10.53 | 8.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 8.88 | 8.09 | 0.00 | 0.00 | 01-NOV-00:10 | 8.88 | 8.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3.17 | 2.90 | 0.00 | 0.00 | 01-DEC-00:10 | 3.17 | 2.90 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -6.0 | -6.7 | 0.00 | 0.00 | -6.0 | -6.7 | ||
Maximum of Months | 0.00 | 0.00 | 21.15 | 17.38 | 0.00 | 0.00 | 21.15 | 17.38 |
Report: BUILDING LOADS - HEATING
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142372E+09 | 8931.54 | 17-JAN-06:01 | 2.80 |
February | 0.139952E+09 | 7835.10 | 13-FEB-06:01 | 1.20 |
March | 22701355.59 | 7014.01 | 07-MAR-06:01 | 0.60 |
April | 12471452.07 | 7077.73 | 03-APR-05:01 | -1.0 |
May | 8623532.07 | 687.90 | 04-MAY-17:02 | 28.95 |
June | 27296960.84 | 849.07 | 20-JUN-17:02 | 31.42 |
July | 30402907.38 | 947.71 | 19-JUL-17:02 | 32.62 |
August | 18772345.05 | 818.55 | 04-AUG-17:02 | 30.92 |
September | 8565982.77 | 606.27 | 27-SEP-17:02 | 28.25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.53 |
November | 25671095.40 | 7395.46 | 24-NOV-06:01 | 0.00 |
December | 97742825.32 | 7553.86 | 04-DEC-06:01 | 1.10 |
Annual Sum or Average | 0.534573E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.142372E+09 | 8931.54 | 32.62 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205651E+10 | 12685.15 | 17-JAN-06:01 | 2.80 |
February | 0.148544E+10 | 11566.16 | 13-FEB-06:01 | 1.20 |
March | 0.933702E+09 | 12770.96 | 01-MAR-06:01 | 3.30 |
April | 0.491389E+09 | 12797.75 | 21-APR-05:01 | 3.90 |
May | 0.125938E+09 | 6387.25 | 09-MAY-05:03 | 2.07 |
June | 33861744.29 | 736.75 | 15-JUN-17:11 | 30.93 |
July | 30721329.68 | 779.48 | 17-JUL-17:11 | 32.23 |
August | 26517730.91 | 708.51 | 03-AUG-17:11 | 30.60 |
September | 16969424.71 | 1291.44 | 25-SEP-06:10 | 6.97 |
October | 0.203685E+09 | 10775.23 | 17-OCT-05:02 | 1.20 |
November | 0.783272E+09 | 12404.46 | 14-NOV-06:01 | 2.02 |
December | 0.157203E+10 | 12435.63 | 08-DEC-06:01 | 2.12 |
Annual Sum or Average | 0.776003E+10 | |||
Minimum of Months | 16969424.71 | 708.51 | 1.20 | |
Maximum of Months | 0.205651E+10 | 12797.75 | 32.23 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832834E+09 | 8439.40 | 17-JAN-06:01 | 2.80 |
February | 0.527744E+09 | 7626.16 | 13-FEB-06:01 | 1.20 |
March | 0.258354E+09 | 8502.43 | 01-MAR-06:01 | 3.30 |
April | 94626809.29 | 8493.15 | 21-APR-05:01 | 3.90 |
May | 21841505.37 | 4385.21 | 01-MAY-05:02 | 6.88 |
June | 23748226.99 | 529.00 | 15-JUN-17:11 | 30.93 |
July | 23690838.29 | 566.74 | 17-JUL-17:11 | 32.23 |
August | 20890256.63 | 524.26 | 04-AUG-17:11 | 30.73 |
September | 11986385.01 | 390.47 | 27-SEP-17:02 | 28.25 |
October | 39708503.47 | 7014.47 | 17-OCT-05:02 | 1.20 |
November | 0.250733E+09 | 8232.95 | 14-NOV-06:01 | 2.02 |
December | 0.579781E+09 | 8254.85 | 08-DEC-06:01 | 2.12 |
Annual Sum or Average | 0.268594E+10 | |||
Minimum of Months | 11986385.01 | 390.47 | 1.20 | |
Maximum of Months | 0.832834E+09 | 8502.43 | 32.23 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134277E+10 | 11704.30 | 17-JAN-06:01 | 2.80 |
February | 0.931958E+09 | 10699.32 | 13-FEB-06:01 | 1.20 |
March | 0.433251E+09 | 11778.89 | 01-MAR-06:01 | 3.30 |
April | 0.162185E+09 | 11790.85 | 21-APR-05:01 | 3.90 |
May | 26606118.33 | 5126.76 | 01-MAY-05:02 | 6.88 |
June | 24221289.01 | 681.34 | 15-JUN-17:11 | 30.93 |
July | 26729470.01 | 749.76 | 19-JUL-17:02 | 32.62 |
August | 19435315.07 | 674.00 | 04-AUG-17:11 | 30.73 |
September | 9793459.67 | 515.87 | 27-SEP-17:02 | 28.25 |
October | 52337287.82 | 9994.75 | 17-OCT-05:02 | 1.20 |
November | 0.390467E+09 | 11429.56 | 14-NOV-06:01 | 2.02 |
December | 0.922885E+09 | 11462.84 | 08-DEC-06:01 | 2.12 |
Annual Sum or Average | 0.434264E+10 | |||
Minimum of Months | 9793459.67 | 515.87 | 1.20 | |
Maximum of Months | 0.134277E+10 | 11790.85 | 32.62 |
Report: BUILDING LOADS - HEATING
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.885288E+09 | 9034.47 | 17-JAN-06:01 | 2.80 |
February | 0.608316E+09 | 8114.97 | 13-FEB-06:01 | 1.20 |
March | 0.285430E+09 | 9104.30 | 01-MAR-06:01 | 3.30 |
April | 0.110437E+09 | 9091.60 | 21-APR-05:01 | 3.90 |
May | 31836619.70 | 5000.05 | 01-MAY-05:02 | 6.88 |
June | 22628545.72 | 545.72 | 20-JUN-17:23 | 30.85 |
July | 21035891.09 | 582.51 | 17-JUL-17:11 | 32.23 |
August | 19400158.29 | 537.24 | 04-AUG-17:11 | 30.73 |
September | 12876646.51 | 391.67 | 26-SEP-17:12 | 25.93 |
October | 44104116.66 | 6276.90 | 24-OCT-05:02 | 1.10 |
November | 0.283520E+09 | 8806.43 | 14-NOV-06:01 | 2.02 |
December | 0.633211E+09 | 8830.18 | 08-DEC-06:01 | 2.12 |
Annual Sum or Average | 0.295808E+10 | |||
Minimum of Months | 12876646.51 | 391.67 | 1.10 | |
Maximum of Months | 0.885288E+09 | 9104.30 | 32.23 |
Report: BUILDING LOADS - HEATING
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -3.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | -0.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.53 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 8.88 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3.17 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.00 | 0.00 | 21.15 |
Report: BUILDING LOADS - ELECTRIC
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.178023E+10 | 1486.92 | 02-JAN-08:09 | 0.129836E+10 | 1014.68 | 02-JAN-08:09 |
February | 0.160950E+10 | 1486.92 | 01-FEB-08:09 | 0.117388E+10 | 1014.68 | 01-FEB-08:09 |
March | 0.187582E+10 | 1486.92 | 01-MAR-08:09 | 0.137025E+10 | 1014.68 | 01-MAR-08:09 |
April | 0.170739E+10 | 1486.92 | 03-APR-07:10 | 0.124489E+10 | 1014.68 | 03-APR-07:10 |
May | 0.182803E+10 | 1486.92 | 01-MAY-07:10 | 0.133431E+10 | 1014.68 | 01-MAY-07:10 |
June | 0.180297E+10 | 1486.92 | 01-JUN-07:10 | 0.131677E+10 | 1014.68 | 01-JUN-07:10 |
July | 0.173244E+10 | 1486.92 | 03-JUL-07:10 | 0.126242E+10 | 1014.68 | 03-JUL-07:10 |
August | 0.187582E+10 | 1486.92 | 01-AUG-07:10 | 0.137025E+10 | 1014.68 | 01-AUG-07:10 |
September | 0.170739E+10 | 1486.92 | 01-SEP-07:10 | 0.124489E+10 | 1014.68 | 01-SEP-07:10 |
October | 0.178023E+10 | 1486.92 | 02-OCT-07:10 | 0.129836E+10 | 1014.68 | 02-OCT-07:10 |
November | 0.175518E+10 | 1486.92 | 01-NOV-07:10 | 0.128083E+10 | 1014.68 | 01-NOV-07:10 |
December | 0.173244E+10 | 1486.92 | 01-DEC-08:09 | 0.126242E+10 | 1014.68 | 01-DEC-08:09 |
Annual Sum or Average | 0.211874E+11 | 0.154576E+11 | ||||
Minimum of Months | 0.160950E+10 | 1486.92 | 0.117388E+10 | 1014.68 | ||
Maximum of Months | 0.187582E+10 | 1486.92 | 0.137025E+10 | 1014.68 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134953E+10 | 1127.18 | 02-JAN-08:09 | 0.984244E+09 | 769.19 | 02-JAN-08:09 |
February | 0.122010E+10 | 1127.18 | 01-FEB-08:09 | 0.889874E+09 | 769.19 | 01-FEB-08:09 |
March | 0.142199E+10 | 1127.18 | 01-MAR-08:09 | 0.103874E+10 | 769.19 | 01-MAR-08:09 |
April | 0.129431E+10 | 1127.18 | 03-APR-07:10 | 0.943705E+09 | 769.19 | 03-APR-07:10 |
May | 0.138576E+10 | 1127.18 | 01-MAY-07:10 | 0.101149E+10 | 769.19 | 01-MAY-07:10 |
June | 0.136677E+10 | 1127.18 | 01-JUN-07:10 | 0.998201E+09 | 769.19 | 01-JUN-07:10 |
July | 0.131330E+10 | 1127.18 | 03-JUL-07:10 | 0.956997E+09 | 769.19 | 03-JUL-07:10 |
August | 0.142199E+10 | 1127.18 | 01-AUG-07:10 | 0.103874E+10 | 769.19 | 01-AUG-07:10 |
September | 0.129431E+10 | 1127.18 | 01-SEP-07:10 | 0.943705E+09 | 769.19 | 01-SEP-07:10 |
October | 0.134953E+10 | 1127.18 | 02-OCT-07:10 | 0.984244E+09 | 769.19 | 02-OCT-07:10 |
November | 0.133054E+10 | 1127.18 | 01-NOV-07:10 | 0.970953E+09 | 769.19 | 01-NOV-07:10 |
December | 0.131330E+10 | 1127.18 | 01-DEC-08:09 | 0.956997E+09 | 769.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.160615E+11 | 0.117179E+11 | ||||
Minimum of Months | 0.122010E+10 | 1127.18 | 0.889874E+09 | 769.19 | ||
Maximum of Months | 0.142199E+10 | 1127.18 | 0.103874E+10 | 769.19 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.800560E+09 | 668.66 | 02-JAN-08:09 | 0.583867E+09 | 456.29 | 02-JAN-08:09 |
February | 0.723780E+09 | 668.66 | 01-FEB-08:09 | 0.527885E+09 | 456.29 | 01-FEB-08:09 |
March | 0.843543E+09 | 668.66 | 01-MAR-08:09 | 0.616194E+09 | 456.29 | 01-MAR-08:09 |
April | 0.767803E+09 | 668.66 | 03-APR-07:10 | 0.559818E+09 | 456.29 | 03-APR-07:10 |
May | 0.822052E+09 | 668.66 | 01-MAY-07:10 | 0.600030E+09 | 456.29 | 01-MAY-07:10 |
June | 0.810786E+09 | 668.66 | 01-JUN-07:10 | 0.592146E+09 | 456.29 | 01-JUN-07:10 |
July | 0.779069E+09 | 668.66 | 03-JUL-07:10 | 0.567703E+09 | 456.29 | 03-JUL-07:10 |
August | 0.843543E+09 | 668.66 | 01-AUG-07:10 | 0.616194E+09 | 456.29 | 01-AUG-07:10 |
September | 0.767803E+09 | 668.66 | 01-SEP-07:10 | 0.559818E+09 | 456.29 | 01-SEP-07:10 |
October | 0.800560E+09 | 668.66 | 02-OCT-07:10 | 0.583867E+09 | 456.29 | 02-OCT-07:10 |
November | 0.789294E+09 | 668.66 | 01-NOV-07:10 | 0.575982E+09 | 456.29 | 01-NOV-07:10 |
December | 0.779069E+09 | 668.66 | 01-DEC-08:09 | 0.567703E+09 | 456.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.952786E+10 | 0.695120E+10 | ||||
Minimum of Months | 0.723780E+09 | 668.66 | 0.527885E+09 | 456.29 | ||
Maximum of Months | 0.843543E+09 | 668.66 | 0.616194E+09 | 456.29 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134953E+10 | 1127.18 | 02-JAN-08:09 | 0.984244E+09 | 769.19 | 02-JAN-08:09 |
February | 0.122010E+10 | 1127.18 | 01-FEB-08:09 | 0.889874E+09 | 769.19 | 01-FEB-08:09 |
March | 0.142199E+10 | 1127.18 | 01-MAR-08:09 | 0.103874E+10 | 769.19 | 01-MAR-08:09 |
April | 0.129431E+10 | 1127.18 | 03-APR-07:10 | 0.943705E+09 | 769.19 | 03-APR-07:10 |
May | 0.138576E+10 | 1127.18 | 01-MAY-07:10 | 0.101149E+10 | 769.19 | 01-MAY-07:10 |
June | 0.136677E+10 | 1127.18 | 01-JUN-07:10 | 0.998201E+09 | 769.19 | 01-JUN-07:10 |
July | 0.131330E+10 | 1127.18 | 03-JUL-07:10 | 0.956997E+09 | 769.19 | 03-JUL-07:10 |
August | 0.142199E+10 | 1127.18 | 01-AUG-07:10 | 0.103874E+10 | 769.19 | 01-AUG-07:10 |
September | 0.129431E+10 | 1127.18 | 01-SEP-07:10 | 0.943705E+09 | 769.19 | 01-SEP-07:10 |
October | 0.134953E+10 | 1127.18 | 02-OCT-07:10 | 0.984244E+09 | 769.19 | 02-OCT-07:10 |
November | 0.133054E+10 | 1127.18 | 01-NOV-07:10 | 0.970953E+09 | 769.19 | 01-NOV-07:10 |
December | 0.131330E+10 | 1127.18 | 01-DEC-08:09 | 0.956997E+09 | 769.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.160615E+11 | 0.117179E+11 | ||||
Minimum of Months | 0.122010E+10 | 1127.18 | 0.889874E+09 | 769.19 | ||
Maximum of Months | 0.142199E+10 | 1127.18 | 0.103874E+10 | 769.19 |
Report: BUILDING LOADS - ELECTRIC
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.800560E+09 | 668.66 | 02-JAN-08:09 | 0.583867E+09 | 456.29 | 02-JAN-08:09 |
February | 0.723780E+09 | 668.66 | 01-FEB-08:09 | 0.527885E+09 | 456.29 | 01-FEB-08:09 |
March | 0.843543E+09 | 668.66 | 01-MAR-08:09 | 0.616194E+09 | 456.29 | 01-MAR-08:09 |
April | 0.767803E+09 | 668.66 | 03-APR-07:10 | 0.559818E+09 | 456.29 | 03-APR-07:10 |
May | 0.822052E+09 | 668.66 | 01-MAY-07:10 | 0.600030E+09 | 456.29 | 01-MAY-07:10 |
June | 0.810786E+09 | 668.66 | 01-JUN-07:10 | 0.592146E+09 | 456.29 | 01-JUN-07:10 |
July | 0.779069E+09 | 668.66 | 03-JUL-07:10 | 0.567703E+09 | 456.29 | 03-JUL-07:10 |
August | 0.843543E+09 | 668.66 | 01-AUG-07:10 | 0.616194E+09 | 456.29 | 01-AUG-07:10 |
September | 0.767803E+09 | 668.66 | 01-SEP-07:10 | 0.559818E+09 | 456.29 | 01-SEP-07:10 |
October | 0.800560E+09 | 668.66 | 02-OCT-07:10 | 0.583867E+09 | 456.29 | 02-OCT-07:10 |
November | 0.789294E+09 | 668.66 | 01-NOV-07:10 | 0.575982E+09 | 456.29 | 01-NOV-07:10 |
December | 0.779069E+09 | 668.66 | 01-DEC-08:09 | 0.567703E+09 | 456.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.952786E+10 | 0.695120E+10 | ||||
Minimum of Months | 0.723780E+09 | 668.66 | 0.527885E+09 | 456.29 | ||
Maximum of Months | 0.843543E+09 | 668.66 | 0.616194E+09 | 456.29 |
Report: SPACE LOADS
For: CORE_ZN
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [Invalid/Undefined] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [Invalid/Undefined] | |
January | 0.790646E+09 | 0.178023E+10 | 0.129836E+10 | 0.00 | 0.00 |
February | 0.715347E+09 | 0.160950E+10 | 0.117388E+10 | 0.00 | 0.00 |
March | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
April | 0.752997E+09 | 0.170739E+10 | 0.124489E+10 | 0.00 | 0.00 |
May | 0.828296E+09 | 0.182803E+10 | 0.133431E+10 | 0.00 | 0.00 |
June | 0.828296E+09 | 0.180297E+10 | 0.131677E+10 | 0.00 | 0.00 |
July | 0.752997E+09 | 0.173244E+10 | 0.126242E+10 | 0.00 | 0.00 |
August | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
September | 0.752997E+09 | 0.170739E+10 | 0.124489E+10 | 0.00 | 0.00 |
October | 0.790646E+09 | 0.178023E+10 | 0.129836E+10 | 0.00 | 0.00 |
November | 0.790646E+09 | 0.175518E+10 | 0.128083E+10 | 0.00 | 0.00 |
December | 0.752997E+09 | 0.173244E+10 | 0.126242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.948776E+10 | 0.211874E+11 | 0.154576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715347E+09 | 0.160950E+10 | 0.117388E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865946E+09 | 0.187582E+10 | 0.137025E+10 | 0.00 | 0.00 |
Report: SPACE LOADS
For: PERIMETER_ZN_1
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.258400E+10 |
February | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.215316E+10 |
March | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.191901E+10 |
April | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 21055720.78 | 0.109376E+10 |
May | 0.627902E+09 | 0.138576E+10 | 0.101149E+10 | 31173457.46 | 0.608119E+09 |
June | 0.627902E+09 | 0.136677E+10 | 0.998201E+09 | 0.125391E+09 | 0.322648E+09 |
July | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 0.178387E+09 | 0.139679E+09 |
August | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 77866101.59 | 0.252170E+09 |
September | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 35194461.83 | 0.452242E+09 |
October | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.109818E+10 |
November | 0.599361E+09 | 0.133054E+10 | 0.970953E+09 | 0.00 | 0.167457E+10 |
December | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 0.00 | 0.229631E+10 |
Annual Sum or Average | 0.719233E+10 | 0.160615E+11 | 0.117179E+11 | 0.469069E+09 | 0.145939E+11 |
Minimum of Months | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.139679E+09 |
Maximum of Months | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.178387E+09 | 0.258400E+10 |
Report: SPACE LOADS
For: PERIMETER_ZN_2
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.786046E+09 |
February | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.624666E+09 |
March | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.588418E+09 |
April | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 6453910.51 | 0.320072E+09 |
May | 0.372480E+09 | 0.822052E+09 | 0.600030E+09 | 3605199.89 | 0.193460E+09 |
June | 0.372480E+09 | 0.810786E+09 | 0.592146E+09 | 15086054.41 | 0.143944E+09 |
July | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 23516219.41 | 68374900.88 |
August | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 6841973.70 | 99027070.13 |
September | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 2467410.38 | 0.150122E+09 |
October | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 44697.76 | 0.346135E+09 |
November | 0.355549E+09 | 0.789294E+09 | 0.575982E+09 | 0.00 | 0.546186E+09 |
December | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 0.00 | 0.675674E+09 |
Annual Sum or Average | 0.426659E+10 | 0.952786E+10 | 0.695120E+10 | 58015466.06 | 0.454213E+10 |
Minimum of Months | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 68374900.88 |
Maximum of Months | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 23516219.41 | 0.786046E+09 |
Report: SPACE LOADS
For: PERIMETER_ZN_3
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 0.00 | 0.118186E+10 |
February | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 0.940131E+09 |
March | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 0.00 | 0.872334E+09 |
April | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 13543235.23 | 0.473743E+09 |
May | 0.627902E+09 | 0.138576E+10 | 0.101149E+10 | 7452669.90 | 0.281279E+09 |
June | 0.627902E+09 | 0.136677E+10 | 0.998201E+09 | 25008650.89 | 0.210101E+09 |
July | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 40837341.19 | 98400744.93 |
August | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 11431456.71 | 0.142010E+09 |
September | 0.570820E+09 | 0.129431E+10 | 0.943705E+09 | 4126282.34 | 0.216602E+09 |
October | 0.599361E+09 | 0.134953E+10 | 0.984244E+09 | 290248.37 | 0.510348E+09 |
November | 0.599361E+09 | 0.133054E+10 | 0.970953E+09 | 0.00 | 0.818785E+09 |
December | 0.570820E+09 | 0.131330E+10 | 0.956997E+09 | 0.00 | 0.101492E+10 |
Annual Sum or Average | 0.719233E+10 | 0.160615E+11 | 0.117179E+11 | 0.102690E+09 | 0.676052E+10 |
Minimum of Months | 0.542279E+09 | 0.122010E+10 | 0.889874E+09 | 0.00 | 98400744.93 |
Maximum of Months | 0.656443E+09 | 0.142199E+10 | 0.103874E+10 | 40837341.19 | 0.118186E+10 |
Report: SPACE LOADS
For: PERIMETER_ZN_4
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 0.00 | 0.787418E+09 |
February | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 0.626489E+09 |
March | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 0.00 | 0.589908E+09 |
April | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 6144261.20 | 0.325065E+09 |
May | 0.372480E+09 | 0.822052E+09 | 0.600030E+09 | 4120862.01 | 0.198235E+09 |
June | 0.372480E+09 | 0.810786E+09 | 0.592146E+09 | 14437255.38 | 0.151722E+09 |
July | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 22474235.60 | 75532937.44 |
August | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 6598430.52 | 0.103339E+09 |
September | 0.338618E+09 | 0.767803E+09 | 0.559818E+09 | 2452143.50 | 0.153163E+09 |
October | 0.355549E+09 | 0.800560E+09 | 0.583867E+09 | 96377.23 | 0.347309E+09 |
November | 0.355549E+09 | 0.789294E+09 | 0.575982E+09 | 0.00 | 0.547050E+09 |
December | 0.338618E+09 | 0.779069E+09 | 0.567703E+09 | 0.00 | 0.675633E+09 |
Annual Sum or Average | 0.426659E+10 | 0.952786E+10 | 0.695120E+10 | 56323565.43 | 0.458086E+10 |
Minimum of Months | 0.321687E+09 | 0.723780E+09 | 0.527885E+09 | 0.00 | 75532937.44 |
Maximum of Months | 0.389411E+09 | 0.843543E+09 | 0.616194E+09 | 22474235.60 | 0.787418E+09 |
Report: SPACE LOADS
For: ATTIC
Timestamp: 2015-09-09 18:45:33
ZONE PEOPLE TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE LIGHTS TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [Invalid/Undefined] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.896460E+09 | 0.138613E+10 |
February | 0.00 | 0.00 | 0.00 | 0.813396E+09 | 0.186018E+10 |
March | 0.00 | 0.00 | 0.00 | 0.782135E+09 | 0.274247E+10 |
April | 0.00 | 0.00 | 0.00 | 0.631686E+09 | 0.317948E+10 |
May | 0.00 | 0.00 | 0.00 | 0.688128E+09 | 0.443585E+10 |
June | 0.00 | 0.00 | 0.00 | 0.602792E+09 | 0.432497E+10 |
July | 0.00 | 0.00 | 0.00 | 0.653776E+09 | 0.439533E+10 |
August | 0.00 | 0.00 | 0.00 | 0.703090E+09 | 0.374325E+10 |
September | 0.00 | 0.00 | 0.00 | 0.758864E+09 | 0.291892E+10 |
October | 0.00 | 0.00 | 0.00 | 0.898093E+09 | 0.207654E+10 |
November | 0.00 | 0.00 | 0.00 | 0.715189E+09 | 0.132638E+10 |
December | 0.00 | 0.00 | 0.00 | 0.939789E+09 | 0.115310E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.908340E+10 | 0.335426E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.602792E+09 | 0.115310E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.939789E+09 | 0.443585E+10 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2015-09-09 18:45:33
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [Invalid/Undefined] | GAS:BUILDING [Invalid/Undefined] | |
January | 0.105150E+11 | 8544.26 | 02-JAN-08:09 | 0.00 | 0.00 |
February | 0.950665E+10 | 8544.26 | 01-FEB-08:09 | 0.00 | 0.00 |
March | 0.110870E+11 | 8544.26 | 01-MAR-08:09 | 0.00 | 0.00 |
April | 0.100836E+11 | 8544.26 | 03-APR-07:10 | 0.00 | 0.00 |
May | 0.108010E+11 | 8544.26 | 01-MAY-07:10 | 0.00 | 0.00 |
June | 0.106556E+11 | 8544.26 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 0.102290E+11 | 8544.26 | 03-JUL-07:10 | 0.00 | 0.00 |
August | 0.110870E+11 | 8544.26 | 01-AUG-07:10 | 0.00 | 0.00 |
September | 0.100836E+11 | 8544.26 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.105150E+11 | 8544.26 | 02-OCT-07:10 | 0.00 | 0.00 |
November | 0.103696E+11 | 8544.26 | 01-NOV-07:10 | 0.00 | 0.00 |
December | 0.102290E+11 | 8544.26 | 01-DEC-08:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125162E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.950665E+10 | 8544.26 | 0.00 | 0.00 | |
Maximum of Months | 0.110870E+11 | 8544.26 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2015-09-09 18:45:33
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.608042E+10 | 0.00 | 0.153473E+10 | 0.443459E+10 | 0.00 | 0.219365E+10 | 0.02 | 0.295639E+10 | 2910240.43 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
February | 0.549726E+10 | 0.00 | 0.128353E+10 | 0.400939E+10 | 0.00 | 0.181151E+10 | 0.02 | 0.214020E+10 | 4736714.39 | 0.00 | 0.00 | 0.00 | 0.138378E+10 | 0.00 |
March | 0.640688E+10 | 0.00 | 0.127960E+10 | 0.468012E+10 | 0.00 | 0.206303E+10 | 0.02 | 0.149693E+10 | 86150540.72 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
April | 0.583162E+10 | 0.00 | 0.109527E+10 | 0.425193E+10 | 0.00 | 0.177971E+10 | 0.02 | 0.626835E+09 | 0.608857E+09 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
May | 0.624365E+10 | 0.00 | 0.100592E+10 | 0.455735E+10 | 0.00 | 0.195769E+10 | 0.02 | 73325568.45 | 0.129178E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
June | 0.615808E+10 | 0.00 | 0.915443E+09 | 0.449747E+10 | 0.00 | 0.195769E+10 | 0.02 | 509045.38 | 0.327042E+10 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
July | 0.591719E+10 | 0.00 | 0.967705E+09 | 0.431182E+10 | 0.00 | 0.178248E+10 | 0.02 | 0.00 | 0.405532E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
August | 0.640688E+10 | 0.00 | 0.107560E+10 | 0.468012E+10 | 0.00 | 0.204719E+10 | 0.02 | 0.00 | 0.373017E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
September | 0.583162E+10 | 0.00 | 0.117676E+10 | 0.425193E+10 | 0.00 | 0.178012E+10 | 0.02 | 1840566.61 | 0.242588E+10 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
October | 0.608042E+10 | 0.00 | 0.136333E+10 | 0.443459E+10 | 0.00 | 0.186870E+10 | 0.02 | 0.225870E+09 | 0.657445E+09 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
November | 0.599485E+10 | 0.00 | 0.144706E+10 | 0.437470E+10 | 0.00 | 0.192227E+10 | 0.02 | 0.123615E+10 | 0.269781E+09 | 0.00 | 0.00 | 0.00 | 0.148262E+10 | 0.00 |
December | 0.591719E+10 | 0.00 | 0.156901E+10 | 0.431182E+10 | 0.00 | 0.190567E+10 | 0.02 | 0.273011E+10 | 2287228.37 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
Annual Sum or Average | 0.723661E+11 | 0.00 | 0.147140E+11 | 0.527958E+11 | 0.00 | 0.230697E+11 | 0.24 | 0.114882E+11 | 0.164057E+11 | 0.00 | 0.00 | 0.00 | 0.180386E+11 | 0.00 |
Minimum of Months | 0.549726E+10 | 0.00 | 0.915443E+09 | 0.400939E+10 | 0.00 | 0.177971E+10 | 0.02 | 0.00 | 2287228.37 | 0.00 | 0.00 | 0.00 | 0.138378E+10 | 0.00 |
Maximum of Months | 0.640688E+10 | 0.00 | 0.156901E+10 | 0.468012E+10 | 0.00 | 0.219365E+10 | 0.02 | 0.295639E+10 | 0.405532E+10 | 0.00 | 0.00 | 0.00 | 0.153204E+10 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2015-09-09 18:45:33
INTERIOREQUIPMENT:GAS [Invalid/Undefined] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.509088E+10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.343911E+10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.315463E+09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105932E+09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 376767.98 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 8030393.47 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.968043E+09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248074E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124086E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.509088E+10 | 0.00 | 0.00 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY PART 1
For: Meter
Timestamp: 2015-09-09 18:45:33
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 5078.61 | 02-JAN-08:09 | 0.00 | 936.61 | 01-JAN-00:10 | 3465.65 | 02-JAN-08:09 | 0.00 | 1901.40 | 02-JAN-06:10 | 0.00 | 05-JAN-08:09 | 7311.73 | 02-JAN-06:30 |
February | 5078.61 | 01-FEB-08:09 | 0.00 | 936.61 | 01-FEB-00:10 | 3465.65 | 01-FEB-08:09 | 0.00 | 1901.40 | 02-FEB-06:10 | 0.00 | 01-FEB-08:09 | 7398.26 | 27-FEB-06:30 |
March | 5078.61 | 01-MAR-08:09 | 0.00 | 936.61 | 01-MAR-00:10 | 3465.65 | 01-MAR-08:09 | 0.00 | 1901.40 | 01-MAR-06:10 | 0.00 | 01-MAR-07:10 | 7014.39 | 14-MAR-05:30 |
April | 5078.61 | 03-APR-07:10 | 0.00 | 936.61 | 01-APR-00:10 | 3465.65 | 03-APR-07:10 | 0.00 | 1901.40 | 03-APR-05:10 | 0.00 | 03-APR-06:10 | 7388.86 | 03-APR-05:30 |
May | 5078.61 | 01-MAY-07:10 | 0.00 | 936.61 | 01-MAY-00:10 | 3465.65 | 01-MAY-07:10 | 0.00 | 1901.40 | 02-MAY-08:30 | 0.00 | 02-MAY-08:00 | 3040.19 | 08-MAY-05:10 |
June | 5078.61 | 01-JUN-07:10 | 0.00 | 936.61 | 01-JUN-00:10 | 3465.65 | 01-JUN-07:10 | 0.00 | 1901.40 | 08-JUN-14:30 | 0.00 | 08-JUN-14:20 | 163.56 | 23-JUN-06:19 |
July | 5078.61 | 03-JUL-07:10 | 0.00 | 936.61 | 01-JUL-00:10 | 3465.65 | 03-JUL-07:10 | 0.00 | 1901.40 | 03-JUL-05:10 | 0.00 | 05-JUL-17:19 | 0.00 | 01-JUL-00:10 |
August | 5078.61 | 01-AUG-07:10 | 0.00 | 936.61 | 01-AUG-00:10 | 3465.65 | 01-AUG-07:10 | 0.00 | 1901.40 | 01-AUG-05:10 | 0.00 | 01-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 5078.61 | 01-SEP-07:10 | 0.00 | 936.61 | 01-SEP-00:10 | 3465.65 | 01-SEP-07:10 | 0.00 | 1901.40 | 01-SEP-05:10 | 0.00 | 14-SEP-07:49 | 317.06 | 25-SEP-06:40 |
October | 5078.61 | 02-OCT-07:10 | 0.00 | 936.61 | 01-OCT-00:10 | 3465.65 | 02-OCT-07:10 | 0.00 | 1901.40 | 02-OCT-05:10 | 0.00 | 20-OCT-08:20 | 4135.69 | 16-OCT-05:10 |
November | 5078.61 | 01-NOV-07:10 | 0.00 | 936.61 | 01-NOV-00:10 | 3465.65 | 01-NOV-07:10 | 0.00 | 1901.40 | 13-NOV-06:10 | 0.00 | 01-NOV-06:10 | 7082.22 | 27-NOV-06:49 |
December | 5078.61 | 01-DEC-08:09 | 0.00 | 936.61 | 01-DEC-00:10 | 3465.65 | 01-DEC-08:09 | 0.00 | 1901.40 | 04-DEC-06:10 | 0.00 | 18-DEC-08:09 | 7474.30 | 04-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 5078.61 | 0.00 | 936.61 | 3465.65 | 0.00 | 1901.40 | 0.00 | 0.00 | ||||||
Maximum of Months | 5078.61 | 0.00 | 936.61 | 3465.65 | 0.00 | 1901.40 | 0.00 | 7474.30 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:33
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.187347E+11 | 16715.712 | 09-JAN-08:09 | 5078.615 | 3465.647 | 1901.404 | 5698.046 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
February | 0.161304E+11 | 16796.238 | 21-FEB-08:09 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
March | 0.175448E+11 | 15264.027 | 06-MAR-08:09 | 5078.615 | 3465.647 | 1901.404 | 4246.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
April | 0.156769E+11 | 16069.956 | 18-APR-13:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5052.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
May | 0.166618E+11 | 15425.685 | 30-MAY-15:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 4408.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
June | 0.182822E+11 | 17663.449 | 08-JUN-12:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6645.783 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
July | 0.185666E+11 | 18315.075 | 19-JUL-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
August | 0.194720E+11 | 17874.604 | 04-AUG-15:39 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 6856.938 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
September | 0.169508E+11 | 16810.059 | 05-SEP-14:00 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 5792.393 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
October | 0.161624E+11 | 14179.055 | 02-OCT-13:30 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 3161.390 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
November | 0.167274E+11 | 16759.242 | 27-NOV-08:09 | 5078.615 | 3465.647 | 1901.404 | 5741.576 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
December | 0.179681E+11 | 16397.330 | 15-DEC-08:09 | 5078.615 | 3465.647 | 1901.404 | 5379.664 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.208878E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||||||||
Minimum of Months | 0.156769E+11 | 14179.055 | 5078.615 | 3465.647 | 1901.404 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.194720E+11 | 18315.075 | 5078.615 | 3465.647 | 1901.404 | 5778.572 | 7297.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 572.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:45:33
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.509088E+10 | 36793.101 | 27-JAN-06:10 | 36793.101 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36793.101 |
February | 0.343911E+10 | 36793.101 | 06-FEB-06:10 | 36793.101 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36793.101 |
March | 0.315463E+09 | 19635.974 | 06-MAR-06:19 | 19635.974 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19635.974 |
April | 0.105932E+09 | 12613.953 | 03-APR-05:19 | 12613.953 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12613.953 |
May | 376767.978 | 627.947 | 09-MAY-05:10 | 627.947 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 627.947 |
June | 0.000 | 0.000 | 01-JUN-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 8030393.467 | 5830.042 | 17-OCT-05:10 | 5830.042 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5830.042 |
November | 0.968043E+09 | 32450.996 | 28-NOV-06:40 | 32450.996 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32450.996 |
December | 0.248074E+10 | 36793.101 | 18-DEC-06:10 | 36793.101 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36793.101 |
Annual Sum or Average | 0.124086E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.509088E+10 | 36793.101 | 36793.101 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36793.101 |